vocational training wbsetcl

Upload: abhishek-jain

Post on 04-Apr-2018

254 views

Category:

Documents


6 download

TRANSCRIPT

  • 7/30/2019 vocational training wbsetcl

    1/55

    WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY

    LIMITED (WBSETCL)

    2012

    VOCATIONAL

    TRAINING REPORT

    K A L Y A N I T R A N S M I S S I O N ( O & M ) S U B - D I V I S I O N , 1 3 2 K V S U B - S T A T I O N

  • 7/30/2019 vocational training wbsetcl

    2/55

    2

    WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED

    KALYANI 132/33/11 KV SUB-STATION

    KALYANI TR. (O & M) SUB-DIVISION

    KALYANI, NADIA

    A

    REPORT ON KALYANI 132KV SUB-STATION & ITS INSTRUMENTS

    FOR

    MR. SIBASISH GHOSH

    ASSISTANT ENGINEER

    KALYANI TRANSMISSION (O & M) SUB-DIVISION

    WBSETCL

    BY

    STUDENT OF

    ELECTRICAL ENGINEERING

    JIS COLLEGE OF ENGINEERING

  • 7/30/2019 vocational training wbsetcl

    3/55

    3

    SL. NO. TOPICS PAGE NO.

    1 PREFACE 42 ACKNOWLEDGEMENT 5

    3 INTRODUCTION 6

    4 ELECTRIC SUBSTATION 7-8

    5 TRANSMISSION TOWER 9-11

    6 ELECTRICAL BUS SYSTEM 12-14

    7 CONDUCTORS 15

    8 INSULATORS 16-22

    9 CAPACITOR BANK 23

    10 BUS COUPLER 24

    11 CIRCUIT BREAKERS 25-31

    12 ARC IN CIRCUIT BREAKER 32-3313 LIGHTNING ARRESTORS 34

    14 TRANSFORMER 35-40

    15 INTRODUCTION OF INSULATING OIL 41-44

    16 BUCHHOLZ RELAY 45-46

    17 EARTHING TRANSFORMER 47-48

    18 CONTROL ROOM 49

    19 PLCC 50

    20 ELECTRICAL SWITCHGEAR 51

    21 ELECTRICAL PROTECTION RELAY 52

    22 BATTERY 53

    23 CONCLUSION 54

    24 BIBLIOGRAPHY 55

  • 7/30/2019 vocational training wbsetcl

    4/55

    4

    PREFACEI have experienced vocational training in W.B.S.E.T.C.L. Kalyani

    sub-station from 25th

    June to 7th

    July, 2012.

    I am very grateful to all of the officers who gave warm

    reception & the valuable time for me. I have learnt many more

    things while doing training in sub-station which has helped me

    to enlarge my practical knowledge. By undergoing this training

    program I am able to relate my bookish knowledge with its

    practical application.

  • 7/30/2019 vocational training wbsetcl

    5/55

    5

    ACKNOWLEDGEMENT

    Before going into the report, I would like to thank to the H.R.D. department of the

    W.B.S.E.T.C.L., Bidhyut Bhawan, Saltlake & Kalyani sub-station for providing me the

    opportunity to do the vocational training at their sub-station. I am highly thankful to

    Sri. Sibasish Ghosh (A.E.), Sri. Sadhan Ghosh (LNSS), Sri. Ashit Ghosh (A.E.) for their

    kind attention. I am also thankful to the other officers for sharing their valuable

    experiences & time with me during this training. In this training, I also got the

    opportunity to understand the status of export-import of in W.B.S.E.T.CL. & the overall

    view of the grid system.

    For this constant inspiration & active supervision from the very beginning of the

    training, I gratefully acknowledge their significant contribution to the successful

    completion of my training.

  • 7/30/2019 vocational training wbsetcl

    6/55

    6

    INTRODUCTION

    Substation is a part of an electrical generation, transmission, &

    distribution system. Substations transform voltage from high to low, or the

    reverse, or perform any of several other important functions. Electric power may flow

    through several substations between generating plant and consumer, and its voltage

    may change in several steps.

    Substations may be owned and operated by a transmission or generation electricalutility, or may be owned by a large industrial or commercial customer. Generally

    substations are un-attended, relying on SCADA for remote supervision and control.

    A substation may include transformers to change voltage levels between high

    transmission voltages and lower distribution voltages, or at the interconnection of two

    different transmission voltages. The word substation comes from the days before the

    distribution system became a grid. As central generation stations became larger,

    smaller generating plants were converted to distribution stations, receiving their

    energy supply from a larger plant instead of using their own generators. The first

    substations were connected to only one power station, where the generators were

    housed, and were subsidiaries of that power station.

  • 7/30/2019 vocational training wbsetcl

    7/55

    7

    ELECTRIC SUB-STATION

    An Electric sub-station is an assembly of equipment in an electric power system through

    which electrical energy is passed for transmission, distribution, interconnection,

    transformation, conversion or switching.

    TYPES OF SUB-STATION:

    A.Transmission sub-station,

    B.Distribution sub-station,

    C.Collector sub-station,

    A.Transmission sub-station: A transmission substation connects two or moretransmission lines. The simplest case is where all transmission lines have the same

    voltage. In such cases, the substation

    contains high-voltage switches that allow

    lines to be connected or isolated for faultclearance or maintenance. A transmission

    station may have transformers to convert

    between two transmission voltages,

    voltage control/power factor

    correction devices such as capacitors,

    reactors or static VAr compensators and

    equipment such as phase shifting transformers to control power flow between two

    adjacent power systems.B.Distribution sub-station: A distribution substation transfers power from the

    transmission system to the distribution

    system of an area. It is uneconomical to

    directly connect electricity consumers to

    the main transmission network, unless

    they use large amounts of power, so the

    distribution station reduces voltage to avalue suitable for local distribution. The

    input for a distribution substation is

    typically at least two transmission or sub

    http://en.wikipedia.org/wiki/Transformerhttp://en.wikipedia.org/wiki/Voltage_compensationhttp://en.wikipedia.org/wiki/Power_factor_correctionhttp://en.wikipedia.org/wiki/Power_factor_correctionhttp://en.wikipedia.org/wiki/Static_VAr_compensatorhttp://en.wikipedia.org/wiki/Static_VAr_compensatorhttp://en.wikipedia.org/wiki/Static_VAr_compensatorhttp://en.wikipedia.org/wiki/Quadrature_boosterhttp://en.wikipedia.org/wiki/Quadrature_boosterhttp://en.wikipedia.org/wiki/Static_VAr_compensatorhttp://en.wikipedia.org/wiki/Power_factor_correctionhttp://en.wikipedia.org/wiki/Power_factor_correctionhttp://en.wikipedia.org/wiki/Voltage_compensationhttp://en.wikipedia.org/wiki/Transformer
  • 7/30/2019 vocational training wbsetcl

    8/55

    8

    transmission lines. Input voltage may be, for example, 115 kV, or whatever is

    common in the area. The output is a number of feeders. Distribution voltages are

    typically medium voltage, between 2.4 kV and 33 kV depending on the size of the

    area served and the practices of the local utility.

    C.Collector sub-station: In distributed generation projects such as a wind farm,a collector substation may be required. It resembles a distribution substation

    although power flow is in the opposite

    direction, from many wind turbines up

    into the transmission grid. Usually for

    economy of construction the collector

    system operates around 35 kV, and the

    collector substation steps up voltage to atransmission voltage for the grid. The

    collector substation can also

    provide power factor correction if it is

    needed, metering and control of the wind farm. In some special cases a collector

    substation can also contain an HVDC static inverter plant.Collector substations also

    exist where multiple thermal or hydroelectric power plants of comparable output

    power are in proximity. Examples for such substations are Brauweiler in Germany

    and Hradec in the Czech Republic, where power is collected from nearby lignite-

    fired power plants. If no transformers are required for increase of voltage to

    transmission level, the substation is a switching station.

    http://en.wikipedia.org/wiki/Distributed_generationhttp://en.wikipedia.org/wiki/Wind_farmhttp://en.wikipedia.org/wiki/Wind_turbinehttp://en.wikipedia.org/wiki/Power_factor_correctionhttp://en.wikipedia.org/wiki/Power_factor_correctionhttp://en.wikipedia.org/wiki/Wind_turbinehttp://en.wikipedia.org/wiki/Wind_farmhttp://en.wikipedia.org/wiki/Distributed_generation
  • 7/30/2019 vocational training wbsetcl

    9/55

    9

    TRANSMISSION TOWER

    The main supporting unit of overhead transmission line is transmission tower. Transmission

    towers have to carry the heavy transmission conductor

    at a sufficient safe height from ground. In addition to

    that all towers have to sustain all kinds of natural

    calamities. So transmission tower designing is an

    important engineering job where all three basic

    engineering concepts, civil, mechanical and electrical

    engineering concepts are equally applicable. Main parts

    of a transmission tower.

    A power transmission tower consists of the following

    parts,

    1) Peak of transmission tower

    2) Cross Arm of transmission tower

    3) Boom of transmission tower

    4) Cage of transmission tower

    5) Transmission Tower Body

    6) Leg of transmission tower

    7) Stub/Anchor Bolt and Base plate assembly of transmission tower.

    THE MAIN PARTS AMONG THESE ARE SHOWN IN THE PICTURES:

  • 7/30/2019 vocational training wbsetcl

    10/55

    10

    Peak of transmission tower:

    The portion above the top cross arm is called peak of transmission tower. Generally earth

    shield wire connected to the tip of this peak.

    Cross Arm of transmission tower:

    Cross arms of transmission tower hold the transmission conductor. The dimension of cross

    arm depends on the level of transmission voltage, configuration and minimum forming

    angle for stress distribution.

    Cage of transmission tower:

    The portion between tower body and peak is known as cage of transmission tower. This

    portion of the tower holds the cross arms.

    Transmission Tower Body:

    The portion from bottom cross arms up to the ground level is called transmission tower

    body. This portion of the tower plays a vital role for maintaining required ground

    clearance of the bottom conductor of the transmission line.

    DESIGN OF TRANSMISSION TOWER:

    To determine the actual transmission tower height by considering the above points, we have

    divided the total height of tower in four parts -

    i. Minimum permissible ground clearance(H1),

    ii. Maximum sag of the conductors (H2),

    iii. Vertical spacing between top & bottom

    conductors (H3),

    iv. Vertical clearance between ground wire and top

    conductors (H4),

  • 7/30/2019 vocational training wbsetcl

    11/55

    11

    TYPES OF TRANSMISSION TOWER:

    According to different considerations, there are different types of transmission towers.

    The transmission line goes as per available corridors. Due to unavailability of shortest

    distance straight corridor transmission line has to deviate from its straight way whenobstruction comes. In total length of a long transmission line there may be several

    deviation points. According to the angle of deviation there are four types of

    transmission tower

    A type tower angle of deviation 0o to 2o.

    B type tower angle of deviation 2o to 15o.

    C type tower angle of deviation 15o to 30o.

    D type tower angle of deviation 30

    o

    to 60

    o

    .

    As per the force applied by the conductor on the cross arms, the transmission towers

    can be categorized in another way.

    Tangent Suspension tower and it is generally A - type tower.

    Angle tower or tension tower or sometime it is called section tower. All B, C and

    D types of transmission towers come under this category.

    Apart from the above customized type of tower, the tower is designed to meet special

    usages listed below,

    These are called special type tower

    River Crossing Tower

    Railway/ Highway Crossing tower

    Transposition tower

    Based on numbers of circuits carried by a transmission tower, transportation can be

    classified as

    Single Circuit tower

    Double Circuit tower

    Multi Circuit tower.

  • 7/30/2019 vocational training wbsetcl

    12/55

    12

    ELECTRICAL BUS SYSTEM & SUBSTATION LAYOUT

    There are many different electrical bus system schemes available but selection of a

    particular scheme depends upon the system voltage, position of substation in electrical

    power system, flexibility needed in system and cost to be expensed.

    The main criterias to be considered during selection of one particular Bus Bar

    Arrangement Scheme among others

    Simplicity of system.

    Easy maintenance of different equipments.

    Minimizing the outage during maintenance.

    Future provision of extension with growth of demand.

    Optimizing the selection of bus bar arrangement scheme so that it gives maximum

    return from the system.

    Some very commonly used bus bar arrangement are discussed below

    SINGLE BUS SYSTEM:

    Single Bus System is simplest and cheapest one. In this scheme all the feeders and

    transformer bay are connected to only one single bus as shown.

    Advantages of single bus system:

    This is very simple in design

    This is very cost effective scheme

    This is very convenient to operate

    Disadvantages of single bus system:

    One but major difficulty of these type of

    arrangement is that, maintenance of

    equipment of any bay cannot be

    possible without interrupting the feeder or transformer connected to that bay. The

    indoor 11KV switchboards have quite often single bus bar arrangement.

  • 7/30/2019 vocational training wbsetcl

    13/55

    13

    Single Bus System with Bus Sectionalizer:

    Some advantages are realized if a single

    bus bar is sectionalized with circuit

    breaker. If there are more than one

    incoming and the incoming sources and

    outgoing feeders are evenly distributed

    on the sections as shown in the figure,

    interruption of system can be reduced to

    a good extent.

    DOUBLE BUS SYSTEM:

    In double bus bar system two identical bus bars are used in such a way that any

    outgoing or incoming feeder can be taken from any of the bus. Actually every feeder is

    connected to both of the buses in parallel through individual isolator as shown in the

    figure. By closing any of the isolators one

    can put the feeder to associated bus.

    Both of the buses are energized and

    total feeders are divided into two

    groups, one group is fed from one bus

    and other from other bus. But any

    feeder at any time can be transferred

    from one bus to other. There is one bus

    coupler breaker which should be kept

    close during bus transfer operation. For transfer operation, one should first close the

    bus coupler circuit breaker then close the isolator associated with the bus to where

    the feeder would be transferred and then open the isolator associated with the bus

    from where feeder is transferred. Lastly after this transfer operation he or she should

    open the bus coupler breaker.

    Advantages of Double Bus System:

    Double Bus Bar Arrangement increases the flexibility of system.

    Disadvantages of Double Bus System:

    The arrangement does not permit breaker maintenance without interruption.

  • 7/30/2019 vocational training wbsetcl

    14/55

    14

    ONE AND A HALF BREAKER BUS SYSTEM:

    This is an improvement on the double breaker scheme to effect saving in the number

    of circuit breakers. For every two circuits only one spare breaker is provided. The

    protection is however complicated

    since it must associate the central

    breaker with the feeder whose own

    breaker is taken out for

    maintenance. For the reasons given

    under double breaker scheme and

    because of the prohibitory costs of

    equipment even this scheme is not

    much popular. As shown in the figure

    that it is a simple design, two feeders

    are fed from two different buses through their associated breakers and these two

    feeders are coupled by a third breaker which is called tie breaker. Normally all the

    three breakers are closed and power is fed to both the circuits from two buses which

    are operated in parallel. The tie breaker acts as coupler for the two feeder circuits.

    MAIN AND TRANSFER BUS SYSTEM:This is an alternative of double bus system. The main conception of Main and Transfer

    Bus System is, here every feeder line is directly connected through an isolator to a

    second bus called transfer bus. The

    said isolator in between transfer bus

    and feeder line is generally called

    bypass isolator. The main bus is as

    usual connected to each feeder

    through a bay consists of circuit

    breaker and associated isolators at

    both side of the breaker. There is

    one bus coupler bay which couples

    transfer bus and main bus through a

    circuit breaker and associated isolators at both sides of the breaker. If necessary the

    transfer bus can be energized by main bus power by closing the transfer bus coupler

    isolators and then breaker. Then the power in transfer bus can directly be fed to thefeeder line by closing the bypass isolator.

  • 7/30/2019 vocational training wbsetcl

    15/55

    15

    CONDUCTORS

    TYPES OF CONDUCTORS:

    For 400 kV transmission line MOOSE wire is used.

    For 132 kV transmission line PANTHER wire is used. The diameter is 3mm.

    For 220 kV transmission line DEER wire is used. The diameter is 3.45mm.

    For 220kV transmission line ZEBRA wire is used. The diameter is 3.15mm.

    For 66 kV transmission line DOG wire is used.

    TABLE OF CONDUCTORS:

    NAMEVOLTAGE

    LEVEL

    WIRE IN

    CONDUCTORWEIGHT

    DIAMETER

    OF SINGLE

    WIRE

    Moose 400kV 7/54 2.00kg/m N/A

    Deer 220kV 7/30 1.977kg/m 3.54mm

    Zebra 220kV 7/54 1.6kg/m 3.15mm

    Panther 132kV 7/30 0.976kg/m N/A

    Dog 66kV N/A N/A N/A

  • 7/30/2019 vocational training wbsetcl

    16/55

    16

    ELECTRICAL INSULATOR

    Electrical Insulator must be used in electrical system to prevent unwanted flow of

    electric current to the earth from its supporting points. Example: Porcelain insulator,

    glass insulator, polymer insulator.

    Properties of insulating material:

    a. It must be mechanically strong enough to carry tension and weight of conductors.

    b. It must have very high dielectric strength to withstand the voltage stresses in

    High Voltage system.

    c. It must possess high Insulation Resistance to prevent leakage current to the

    earth.

    d. The insulating material must be free from unwanted impurities.

    PORCELAIN INSULATOR:

    Porcelain in most commonly used material for over head insulator in present days.

    The porcelain is aluminium silicate. The aluminium silicate is mixed with plastic

    kaolin, feldspar and quartz to obtain final hard and glazed porcelain

    insulator material. The surface of the

    insulator should be glazed enough so that

    water should not be traced on it. Porcelain

    also should be free from porosity since

    porosity is the main cause of deterioration

    of its dielectric property. It must also be

    free from any impurity and air bubble

    inside the material which may affect the

    insulator properties.

    PROPERTY VALUE

    Dielectric strength 60kV/cm

    Compressive strength 70,000kg/cm2

    Tensile strength 500kg/cm2

  • 7/30/2019 vocational training wbsetcl

    17/55

    17

    GLASS INSULATOR:

    Nowadays glass insulator has become popular in transmission and distribution

    system. Annealed tough glass is used for insulating purpose. Glass insulator has

    numbers of advantages over conventional porcelain insulator.

    Advantages of glass insulator:

    It has very high dielectric strength compared to porcelain.

    Its resistivity is also very high.

    It has low coefficient of thermal expansion.

    It has higher tensile strength compared to porcelain insulator.

    As it is transparent in nature it is not heated up in sunlight as porcelain.

    The impurities and air bubble can be easily detected inside the glass insulator body

    because of its transparency.

    PROPERTY VALUE

    Dielectric strength 140kV/cm

    Compressive strength 10,000kg/cm2

    Tensile strength 35,000kg/cm

    2

  • 7/30/2019 vocational training wbsetcl

    18/55

    18

    POLYMER INSULATOR:

    In a polymer insulator has two parts, one is glass fiber reinforced epoxy resin rod

    shaped core and other is silicone rubber or EPDM (Ethylene Propylene Diene

    Monomer) made weather sheds. Rod shaped core is covered by weather sheds.Weather sheds protect the insulator core from outside environment. As it is made of

    two parts, core and weather sheds, polymer insulator is also calledcomposite

    insulator. The rod shaped core is fixed with Hop dip galvanized cast steel made end

    fittings in both sides.

    Advantages of polymer insulator:

    It is very light weight compared to porcelain

    and glass insulator.

    As the composite insulator is flexible the

    chance of breakage becomes minimum.

    Because of lighter in weight and smaller in

    size, this insulator has lower installation cost.

    It has higher tensile strength compared to

    porcelain insulator.

    Disadvantages of polymer insulator:

    Moisture may enter in the core if there is any

    unwanted gap between core and weather sheds.

    This may cause electrical failure of the insulator.

    Over crimping in end fittings may result to

    cracks in the core which leads to mechanical failure

    of polymer insulator.

    Types of Insulator:

    There are mainly three types of insulator used as overhead insulator likewise

    Pin Insulator

    Suspension Insulator Stray Insulator

  • 7/30/2019 vocational training wbsetcl

    19/55

    19

    PIN INSULATOR:

    Pin Insulator is earliest developed overhead insulator, but still popularly used in

    power network up to 33KV system.Pin type insulator can be one part,

    two parts or three parts type,

    depending upon application voltage.

    In 11KV system we generally use

    one part type insulator where whole

    pin insulator is one piece of properly

    shaped porcelain or glass. As the

    leakage path of insulator is through

    its surface, it is desirable to increase

    the vertical length of the insulator

    surface area for lengthening leakage

    path. In order to obtain lengthy

    leakage path, one, two or more rain

    sheds or petticoats are provided on

    the insulator body. In addition to that rain shed or petticoats on an insulator serve

    another purpose. These rain sheds or petticoats are so designed, that during raining

    the outer surface of the rain shed becomes wet but the inner surface remains dry

    and non-conductive. So there will be discontinuations of conducting path through

    the wet pin insulator surface.

    Designing consideration of Electrical Insulator:

    The live conductor attached to the top of the pin insulator is at a potential and

    bottom of the insulator fixed to supporting structure of earth potential. Theinsulator has to withstand the potential stresses between conductor and earth.

    The shortest distance between conductor and earth, surrounding the insulator

    body, along which electrical discharge may take place through air, is known as

    flash over distance.

    1. When insulator is wet, its outer surface becomes almost conducting. Hence

    the flash over distance of insulator is decreased. The design of an electrical

    insulator should be such that the decrease of flash over distance is minimum

    when the insulator is wet. That is why the upper most petticoat of a pininsulator has umbrella type designed so that it can protect, the rest lower part

    of the insulator from rain. The upper surface of top most petticoat is inclined as

    less as possible to maintain maximum flash over voltage during raining.

  • 7/30/2019 vocational training wbsetcl

    20/55

    20

    2. To keep the inner side of the insulator dry, the rain sheds are made in order

    that these rain sheds should not disturb the voltage distribution they are so

    designed that their subsurface at right angle to the electromagnetic lines of

    force.

    POST INSULATOR:

    Post insulator is more or less similar to Pin insulator but former is suitable for higher

    voltage application. Post insulator has higher numbers of petticoats and has greater

    height. This type of insulator can be mounted on supporting structure horizontally as

    well as vertically. The insulator is made of one piece of porcelain but has fixing clamp

    arrangement are in both top and bottom end.

    The main differences between pin insulator and post insulator are:

    SUSPENSION INSULATOR:

    In higher voltage, beyond 33KV, it becomes uneconomical to use pin insulator

    because size, weight of the insulator become more. Handling and replacing bigger

    size single unit insulator are quite difficult task. For overcoming these

    difficulties, suspension insulator was developed.

    In suspension insulator numbers of insulators are connected in series to form a

    string and the line conductor is carried by the bottom most insulator. Each

    insulator of a suspension string is called disc insulator because of their disc like

    shape

    SL. NO. PIN INSULATOR POST INSULATOR

    1It is generally used up to 33KV

    system.

    It is suitable for lower voltage and also

    for higher voltage.

    2It is single stag. It can be single stag as well as multiple

    stags.

    3

    Two insulators cannot be fixed

    together for higher voltage

    application.

    Two or more insulators can be fixed

    together one above other for higher

    voltage application.

    4

    Metallic fixing arrangement

    provided only on bottom end of

    the insulator.

    Metallic fixing arrangement provided

    on both top and bottom ends of the

    insulator.

  • 7/30/2019 vocational training wbsetcl

    21/55

    21

    Advantages of Suspension Insulator:

    1. Each suspension disc is designed for normal voltage rating 11KV(Higher voltage

    rating 15KV), so by using different numbers of discs, a suspension string can be

    made suitable for any voltage level.

    2. If any one of the disc insulators in a suspension string is damaged, it can be

    replaced much easily.

    3. Mechanical stresses on the suspension insulator is less since the line hanged on

    a flexible suspension string.

    4. As the current carrying conductors are suspended from supporting structure by

    suspension string, the height of the conductor position is always less than the total

    height of the supporting structure. Therefore, the conductors may be safe from

    lightening.

    Disadvantages of Suspension Insulator:

    Suspension insulator string costlier than pin and post type insulator.

    Suspension string requires more height of supporting structure than that for pin

    or post insulator to maintain same ground clearance of current conductor.

    The amplitude of free swing of conductors is larger in suspension insulator

    system, hence, more spacing between conductors should be provided.

  • 7/30/2019 vocational training wbsetcl

    22/55

    22

    STRAIN INSULATOR:

    When suspension string is used to sustain

    extraordinary tensile load of conductor it is

    referred as string insulator. When there is a deadend or there is a sharp corner in transmission line,

    the line has to sustain a great tensile load of

    conductor or strain. A strain insulator must have

    considerable mechanical strength as well as the

    necessary electrical insulating properties.

    There are other two types of insulator for low voltage application. Those are i.Stay

    Insulator ii.Shackle Insulator.

    STAY INSULATOR:

    For low voltage lines, the stays

    are to be insulated from ground

    at a height. The insulator used

    in the stay wire is called as

    the stay insulator and is usually

    of porcelain and is so designed

    that in case of breakage of the

    insulator the guy-wire will not fall to the ground.

    SHACKLE INSULATOR:

    Theshackle insulatororspool insulatoris usually used

    inlow voltage distribution network. It can be used

    both in horizontal and vertical position.

    Rated

    SystemVoltage

    Number of disc insulator used in strain

    type tension insulator string

    Number of disc insulator

    used in suspensioninsulator string

    33KV 3 3

    66KV 5 4

    132KV 9 8

    220KV 15 14

  • 7/30/2019 vocational training wbsetcl

    23/55

    23

    CAPACITOR BANK

    Acapacitorbank is a grouping of several identical capacitors interconnected in parallel or in

    series with one another. These groups of capacitors are typically used to correct or

    counteract undesirable characteristics, such aspower factorlag or phase shifts inherent in

    alternating current (AC) electricalpower supplies. Capacitor banks may also be used in

    direct current (DC) power supplies to increase stored energy and improve the ripple current

    capacity of thepower supply.

    Single capacitors are electrical or electronic components which storeelectrical energy.

    Capacitors consist of two conductors that are separated by an insulating material or

    dielectric. When an electrical current is passed

    through the conductor pair, a staticelectric

    fielddevelops in the dielectric which represents

    the stored energy. Unlike batteries, this stored

    energy is not maintained indefinitely, as the

    dielectric allows for a certain amount of current

    leakage which results in the gradual dissipation

    of the stored energy.

    The energy storing characteristic of capacitors is

    known ascapacitanceand is expressed or

    measured by the unit farads. These

    characteristics also allow capacitors to be used

    in a group or capacitor bank to absorb and correct AC power supply faults.

    The use of a capacitor bank to correct AC power supply anomalies is typically found in heavy

    industrial environments that feature working loads made up of electric motors and

    transformers. This type of working load is problematic from a power supply perspective aselectric motors and transformers represent inductive loads, which cause a phenomenon

    known as phase shift or power factor lag in the power supply.

    The use of a capacitor bank in the power supply system effectively cancels out or

    counteracts these phase shift issues, making the power supply far more efficient and cost

    effective. The installation of a capacitor bank is also one of the cheapest methods of

    correcting power lag problems and maintaining a power factor capacitor bank is simple and

    cost effective. One thing that should always be kept in mind when working withany capacitor or capacitor bank is the fact that the stored energy, if incorrectly discharged,

    can cause serious burns or electric shocks.

    http://www.wisegeek.com/what-is-a-capacitor.htmhttp://www.wisegeek.com/what-is-a-capacitor.htmhttp://www.wisegeek.com/what-is-a-capacitor.htmhttp://www.wisegeek.com/what-is-power-factor.htmhttp://www.wisegeek.com/what-is-power-factor.htmhttp://www.wisegeek.com/what-is-power-factor.htmhttp://www.wisegeek.com/what-are-the-most-common-applications-for-ac-current.htmhttp://www.wisegeek.com/what-are-the-most-common-applications-for-ac-current.htmhttp://www.wisegeek.com/what-are-the-most-common-applications-for-ac-current.htmhttp://www.wisegeek.com/what-are-power-supplies.htmhttp://www.wisegeek.com/what-are-power-supplies.htmhttp://www.wisegeek.com/what-are-power-supplies.htmhttp://www.wisegeek.com/what-is-a-power-supply.htmhttp://www.wisegeek.com/what-is-a-power-supply.htmhttp://www.wisegeek.com/what-is-a-power-supply.htmhttp://www.wisegeek.com/what-is-electrical-energy.htmhttp://www.wisegeek.com/what-is-electrical-energy.htmhttp://www.wisegeek.com/what-is-electrical-energy.htmhttp://www.wisegeek.com/what-is-an-electric-field.htmhttp://www.wisegeek.com/what-is-an-electric-field.htmhttp://www.wisegeek.com/what-is-an-electric-field.htmhttp://www.wisegeek.com/what-is-an-electric-field.htmhttp://www.wisegeek.com/what-is-capacitance.htmhttp://www.wisegeek.com/what-is-capacitance.htmhttp://www.wisegeek.com/what-is-capacitance.htmhttp://www.wisegeek.com/what-is-capacitance.htmhttp://www.wisegeek.com/what-is-an-electric-field.htmhttp://www.wisegeek.com/what-is-an-electric-field.htmhttp://www.wisegeek.com/what-is-electrical-energy.htmhttp://www.wisegeek.com/what-is-a-power-supply.htmhttp://www.wisegeek.com/what-are-power-supplies.htmhttp://www.wisegeek.com/what-are-the-most-common-applications-for-ac-current.htmhttp://www.wisegeek.com/what-is-power-factor.htmhttp://www.wisegeek.com/what-is-a-capacitor.htm
  • 7/30/2019 vocational training wbsetcl

    24/55

    24

    BUS COUPLER

    Bus coupler is a device which is used to switch from one bus to the other without anyinterruption in power supply and without creating hazardous arcs. It is achieved with the

    help of circuit breaker and isolators.

    Bus coupler configurations are available as non-terminated or internally terminated. If two

    or more non-terminated couplers are used on a bus, then the couplers at each end of the

    bus must be terminated externally with 78 ohm terminators on the unused bus connections

    of the end couplers. Alternately, internally single terminated couplers (with or without the

    non-functional bus connectors) can be supplied.

    Even if only one non-terminated coupler acts as the bus because all devices (bus controller,

    remote terminals, etc.) are connected to the couplers stubs, the external bus connections

    of the coupler must be terminated. A dual-terminated coupler (with or without non-

    functional bus connectors) can be employed where the coupler acts as the bus without

    other couplers.

    COMPONENTS OF BUS COUPLER:

    Main bus isolator

    Current transformer

    Circuit breaker

    Line isolator

    Supporting insulator

    Potential transformer

  • 7/30/2019 vocational training wbsetcl

    25/55

    25

    CIRCUIT BREAKERS

    Electrical Circuit Breaker is a switching device which can be operated manually as well as

    automatically for controlling and protection of electrical power system respectively.

    TYPES OF CIRCUIT BREAKER:

    According different criteria there are different types of circuit breaker.According to

    their arc quenching media the circuit breaker can be divided as

    SF6 CIRCUIT BREAKER

    VACCUM CIRCUIT BREAKER

    OIL CIRCUIT BREAKER

    GAS CIRCUIT BREAKER

    SF6 CIRCUIT BREAKER:

    A circuit breaker in which the current carrying contacts operate in Sulphur Hexafluoride or

    SF6 gas is known as an SF6 Circuit Breaker.

    SF6 has excellent insulating property. SF6 has high electro-negativity. That means it has

    high affinity of absorbing free electron. Whenever a free electron collides with the SF6

    gas molecule, it is absorbed by that gas molecule and forms a negative ion.

    The attachment of electron with SF6 gas molecules may occur in tow different ways,

    1) SF6 +e=SF6

    2) SF6 + e = SF5-+ F

    These negative ions obviously much heavier than a free electron and therefore over all

    mobility of the charged particle in the SF6 gas is much less as compared other common

    gases. We know that mobility of charged particle is majorly responsible for conducting

    current through a gas.

    WORKING OF SF6 CIRCUIT BREAKER:

    The working of SF6 circuit Breaker of first generation was quite simple it is some extent

    similar to air blast circuit breaker. Here SF6 gas was compressed and stored in a highpressure reservoir. During operation of SF6 circuit breaker this highly compressed gas is

    released through the arc and collected to relatively low pressure reservoir and then it

    pumped back to the high pressure reservoir for reutilize.

  • 7/30/2019 vocational training wbsetcl

    26/55

    26

    The working of SF6 circuit breaker is little bit different in modern time. Innovation of

    puffer type design makes operation of SF6 circuit breaker much easier. In buffer type

    design, the arc energy is utilized to develop pressure in the arcing chamber for arc

    quenching.

    Here the breaker is filled with SF6 gas at rated pressure. There are two fixed contact

    fitted with a specific contact gap. A sliding cylinder bridges these to fixed contacts. The

    cylinder can axially slide upward and downward along the contacts. There is one

    stationary piston inside the cylinder which is fixed with other stationary parts of the

    breaker, in such a way that it can not change its position during the movement of the

    cylinder. As the piston is fixed and cylinder is movable or sliding, the internal volume of

    the cylinder changes when the cylinder slides.

    During opening of the breaker the cylinder moves downwards against position of the

    fixed piston hence the volume inside the cylinder is reduced which produces

    compressed SF6 gas inside the cylinder. The cylinder has numbers of side vents which

    were blocked by upper fixed contact body during closed position. As the cylinder move

    further downwards, these vent openings cross the upper fixed contact, and become

    unblocked and then compressed SF6 gas inside the cylinder will come out through this

    vents in high speed towards the arc and passes through the axial hole of the both fixed

    contacts. The arc is quenched during this flow of SF6 gas.

    During closing of the breaker, the sliding cylinder moves upwards and as the position of

    piston remains at fixed height, the volume of the cylinder increases which introduces

    low pressure inside the cylinder compared to the surrounding. Due to this pressure

    difference SF6 gas from surrounding will try to enter in the cylinder. The higher pressure

    gas will come through the axial hole of both fixed contact and enters into cylinder via

    vent and during this flow; the gas will quench the arc.

  • 7/30/2019 vocational training wbsetcl

    27/55

    27

    VACUUM CIRCUIT BREAKER:

    A vacuum circuit breaker is such kind of circuit breaker where the arc quenching takes place in

    vacuum. The technology is suitable for mainly medium voltage application. For higher voltage

    Vacuum technology has been developed but not commercially viable. The operation of

    opening and closing of current carrying contacts and associated arc interruption take place in

    a vacuum chamber in the breaker which is called vacuum interrupter. The vacuum interrupter

    consists of a steel arc chamber in the centre symmetrically arranged ceramic insulators. The

    vacuum pressure inside a vacuum interrupter is normally maintained at 10- 6

    bar.

    The material used for current carrying contacts plays an important role in the performance of

    the vacuum circuit breaker. CuCr is the most ideal material to make VCB contacts. Vacuum

    interrupter technology was first introduced in the year of 1960. But still it is a developing

    technology. As time goes on, the size of the vacuum interrupter is being reducing from its

    early 1960s size due to different technical developments in this field of engineering. The

    contact geometry is also improving with time, from butt contact of early days it gradually

    changes to spiral shape, cup shape and axial magnetic field contact. The vacuum circuit

    breaker is today recognized as most reliable current interruption technology for medium

    voltage system. It requires minimum maintenance compared to other circuit breaker

    technologies.

    Advantages of vacuum circuit breaker:

    Service life of Vacuum Circuit Breaker is much longer than other types of circuit breakers.There is no chance of fire hazard as oil circuit breaker. It is much environment friendly

    than SF6 Circuit breaker. Beside of that contraction of VCB is much user friendly. Replacement

    of Vacuum Interrupter (VI) is much convenient.

    Operation of Vacuum Circuit Breaker:

    The main aim of any circuit breaker is to quench arc during current zero crossing, by

    establishing high dielectric strength in between the contacts so that reestablishment of arc

    after current zero becomes impossible. The dielectric strength of vacuum is eight times

    greater than that of air and four times greater than that of SF6 gas. This high dielectric

    strength makes it possible to quench a vacuum arc within very small contact gap. For short

    contact gap, low contact mass and no compression of medium the drive energy required in

    vacuum circuit breaker is minimum. When two face to face contact areas are just being

    separated to each other, they do not be separated instantly, contact area on the contact face

    is being reduced and ultimately comes to a point and then they are finally de-touched.

    Although this happens in a fraction of micro second but it is the fact.

    At thid instant of de-touching of contacts in a vacuum, the current through the contacts

    concentrated on that last contact point on the contact surface and makes a hot spot. As it isvacuum, the metal on the contact surface is easily vaporized due to that hot spot and create

    a conducting media for arc path. Then the arc will be initiated and continued until the next

    current zero. At current zero this vacuum arc is extinguished and the conducting metal

    vapour is re-condensed on the contact surface. At this point, the contacts are already

  • 7/30/2019 vocational training wbsetcl

    28/55

    28

    separated hence there is no question of re-vaporization of contact surface, for next cycle of

    current. That means, the arc cannot be reestablished again. In this way vacuum circuit

    breaker prevents the reestablishment of arc by producing high dielectric strength in the

    contact gap after current zero.

    There are two types of arc shapes. For interrupting current up to 10kA, the arc remains

    diffused and the form of vapour discharge and cover the entire contact surface. Above 10kA

    the diffused arc is constricted considerably by its own magnetic field and it contracts. The

    phenomenon gives rise over heating of contact at its center. In order to prevent this, the

    design of the contacts should be such that the arc does not remain stationary but keeps

    travelling by its own magnetic field. Specially designed contact shape of vacuum circuit

    breaker make the constricted stationary arc travel along the surface of the contacts, thereby

    causing minimum and uniform contact erosion.

    OIL CIRCUIT BREAKER:

    Mineral oil has better insulating property than air. In oil circuit breaker the fixed contact and

    moving contact are immerged inside the insulating oil. Whenever there is a separation of

    current carrying contacts in the oil, the arc is initialized at the moment of separation of

    contacts, and due to this arc the oil is vaporized and decomposed in mostly hydrogen gas

    and ultimately creates a hydrogen bubble around the arc. This highly compressed gas

    bubble around the arc prevents re-striking of the arc after current reaches zero crossing of

    the cycle. The Oil Circuit Breaker is the one of the oldest type of circuit breakers.

    Operation of Oil Circuit Breaker:

    The operation of oil circuit breaker is quite simple lets have a discussion. When the current

    carrying contacts in the oil are separated an arc is established in between the separated

    contacts. Actually, when separation of contacts has just started, distance between the

    current contacts is small as a result the voltage gradient between contacts becomes high.

    This high voltage gradient between the contacts ionized the oil and consequently initiates

    arcing between the contacts. This arc will produce a large amount of heat in surrounding oil

    and vaporizes the oil and decomposes the oil in mostly hydrogen and a small amount of

    methane, ethylene and acetylene. The hydrogen gas can not remain in molecular form and

    its is broken into its atomic form releasing lot of heat. The arc temperature may reach up to

    50000K. Due to this high temperature the gas is liberated surround the arc very rapidly and

  • 7/30/2019 vocational training wbsetcl

    29/55

    29

    forms an excessively fast growing gas bubble around the arc. It is found that the mixture of

    gases occupies a volume about one thousand times that of the oil decomposed. From this

    figure we can assume how fast the gas bubble around the arc will grow in size. If this

    growing gas bubble around the arc is compressed by any means then rate of de ionization

    process of ionized gaseous media in between the contacts will accelerate which rapidly

    increase the dielectric strength between the contacts and consequently the arc will bequenched at zero crossing of the current cycle. This is the basic operation of oil circuit

    breaker. In addition to that cooling effect of hydrogen gas surround the arc path also helps,

    the quick arc quenching in oil circuit breaker.

    Types of oil circuit breakers:

    There are mainly two types of oil circuit breaker.

    Bulk Oil Circuit Breaker:

    Bulk Oil Circuit Breaker is such types of circuitbreakers where oil is used as arc quenching

    media as well as insulating media between

    current carrying contacts and earthed parts of

    the breaker. The oil used here is same as

    transformer insulating oil.

    Minimum Oil Circuit Breaker:

    These types of circuit breakers utilize oil as theinterrupting media. However, unlike bulk oil

    circuit breaker, a minimum oil circuit

    breaker places the interrupting unit in insulating

    chamber at live potential. The insulating oil is

    available only in interrupting chamber. The

    features of designing MOCBare to reduce

    requirement of oil, and hence these breaker are

    called minimum oil circuit breaker.

    AIR CIRCUIT BREAKER:

    An air circuit breaker is that kind of circuit breaker which operates in air at atmospheric

    pressure. After development of oil breaker, the medium voltage air circuit breaker is

    replaced completely by oil circuit breaker in different countries. But in countries like France

    and Italy, air circuit breakers are still preferable choice up to voltage 15 KV. It is also good

    choice to avoid the risk of oil fire, in case of oil circuit breaker. In America air circuit

    breakers were exclusively used for the system up to 15 KV until the development of new

    vacuum and SF6 circuit breakers.

    Working principle of Air Circuit Breaker:

    The working principle of air circuit breaker is rather different from those in any other types

    of circuit breakers. The main aim of all kind of circuit breaker is to prevent the

  • 7/30/2019 vocational training wbsetcl

    30/55

    30

    reestablishment of arcing after current zero by creating a situation where in the contact gap

    will withstand the system recovery voltage. The air circuit breaker does the same but in

    different manner. For interrupting arc it creates an arc voltage in excess of the supply

    voltage. Arc voltage is defined as the minimum voltage required maintaining the arc. This

    circuit breaker increases the arc voltage by mainly three different ways.

    It may increase the arc voltage by cooling the arc plasma. As the temperature of arc plasma

    is decreased, the mobility of the particle in arc plasma is reduced; hence more voltage

    gradient is required to maintain the arc.

    It may increase the arc voltage by lengthening the arc path. As the length of arc path is

    increased, the resistance of the path is increased, and hence to maintain the same arc

    current more voltage is required to be applied across the arc path. That means arc voltage

    is increased. Splitting up the arc into a number of series arcs also increases the arc voltage.

    Types of air circuit breaker:

    There are mainly two types of air circuit breaker are available.

    1) Plain air circuit breaker

    2) Air blast Circuit Breaker

    Operation of Air Circuit Breaker:

    The first objective is usually achieved by forcing the arc into contact with as large an area as

    possible of insulating material. All the air circuit breakers are fitted with a chamber

    surrounding the contact. This chamber is called 'arc chute'. The arc is driven into it. If inside

    of the arc chute is suitably shaped, and if the arc can be made conform to the shape, the

    arc chute wall will help to achieve cooling. This type of arc chute should be made from

    some kind of refractory material. High temperature plastics reinforced with glass fiber and

    ceramics are preferable materials for making arc chute.

    The second objective that is lengthening the arc path, is achieved concurrently with fist

    objective. If the inner walls of the arc chute is shaped in such a way that the arc is not onlyforced into close proximity with it but also driven into a serpentine channel projected on

    the arc chute wall. The lengthening of the arc path increases the arc resistance.

    The third technique is achieved by using metal arc slitter inside the arc chute. The main arc

    chute is divided into numbers of small compartments by using metallic separation plates.

    These metallic separation plates are actually the arc splitters and each of the small

    compartments behaves as individual mini arc chute. In this system the initial arc is split into

    a number of series arcs, each of which will have its won mini arc chute. So each of the split

    arcs has its won cooling and lengthening effect due to its won mini arc chute and hence

    individual split arc voltage becomes high. These collectively, make the over all arc voltage,

    much higher than the system voltage.

  • 7/30/2019 vocational training wbsetcl

    31/55

    31

    This was working principleof air circuit breaker now we will discuss in details the operation

    of air circuit breaker in practice.

    The air circuit breaker, operated within the voltage level 1KV, does not require any arc

    control device. Mainly for heavy fault current on low voltages (low voltage level above 1 KV)

    air circuit breakers with appropriate arc control device, are good choice. These breakers

    normally have two pairs of contacts. The main pair of contacts carries the current at normal

    load and these contacts are made of copper. The additional pair is the arcing contact and is

    made of carbon. When circuit breaker is being opened, the main contacts open first and

    during opening of main contacts the arcing contacts are still in touch with each other. As

    the current gets, a parallel low resistive path

    through the arcing contact during opening of

    main contacts, there will not be any arcing in

    the main contact. The arcing is only initiated

    when finally the arcing contacts are separated.

    The each of the arc contacts is fitted with an

    arc runner which helps, the arc discharge to

    move upward due to both thermal and

    electromagnetic effects as shown in the figure.

    As the arc is driven upward it enters in the arc

    chute, consisting of splitters. The arc in chute

    will become colder, lengthen and split hence arc voltage becomes much larger than systemvoltage at the time of operation of air circuit breaker, and therefore the arc is quenched

    finally during the current zero.

  • 7/30/2019 vocational training wbsetcl

    32/55

    32

    ARC IN CIRCUIT BREAKER

    Before going through details arc quenchingorarc extinction technologies employed in

    circuit breaker we should know first what is arc actually.

    Definition of arc:

    During opening of current carrying contacts in a circuit breaker the medium in between

    opening contacts become highly ionized through which the interrupting current gets low

    resistive path and continues to flow through this path even the contacts are physically

    separated. During the flowing of current from one contact to other the path becomes so

    heated that it glows. This is called arc.

    Arc in Circuit Breaker:

    Whenever, on load current contacts of circuit breaker open there is an arc in circuit

    breaker, established between the separating contacts. As long as this arc is sustained in

    between the contacts the current through the circuit breaker will not be interrupted finally

    as because arc is itself a conductive path of electricity. For total interruption of current the

    circuit breaker it is essential to quench the arc as quick as possible. The main designing

    criteria of a circuit breaker is to provide appropriate technology of arc quenching in circuit

    breaker to fulfill quick and safe current interruption. So before going through different arc

    quenching techniques employed in circuit breaker, we should try to understand "what is

    arc" and basic theory of arc in circuit breaker, lets discuss.

    Thermal Ionization of gas:

    There are numbers of free electrons and ions present in a gas at room temperature due to

    ultraviolet rays, cosmic rays and radioactivity of the earth. These free electrons and ions are

    so few in number that they are insufficient to sustain conduction of electricity. The gas

    molecules move randomly at room temperature. It is found an air molecule at a

    temperature of 300oK (Room temperature) moves randomly with an approximate average

    velocity of 500 meters/second and collides other molecules at a rate of 1010times/second.

    These randomly moving molecules collide each other in very frequent manner but the

    kinetic energy of the molecules is not sufficient to extract an electron from atoms of the

    molecules. If the temperature is increased the air will be heated up and consequently the

    velocity on the molecules increased. Higher velocity means higher impact during

    intermolecular collision. During this situation some of the molecules are disassociated in to

    atoms. If temperature of the air is further increased many atoms are deprived of valence

    electrons and make the gas ionized. Then this ionized gas can conduct electricity because of

    sufficient free electrons. This condition of any gas or air is called plasma. This phenomenon

    is called thermal ionization of gas.

  • 7/30/2019 vocational training wbsetcl

    33/55

    33

    Ionization due to electron collision:

    As we discussed that there are always some free electrons and ions presents in the air or

    gas but they are insufficient to conduct electricity. Whenever these free electrons come

    across a strong electric field, these are directed towards higher potential points in the

    field and acquire sufficiently high velocity. In other words, the electrons are accelerated

    along the direction of the electric field due to high potential gradient. During their travel

    these electrons collide with other atoms and molecules of the air or gas and extract

    valance electrons from their orbits. After extracted from parent atoms, the electrons will

    also run along the direction of the same electric field due to potential gradient. These

    electrons will similarly collide with other atoms and create more free electrons which will

    also be directed along the electric field. Due to this conjugative action the numbers of

    free electrons in the gas will become so high that the gas stars conducting electricity. This

    phenomenon is known as ionization of gas due to electron collision.

    Deionization of gas:

    If all the cause of ionization of gas are removed from an ionized gas it rapidly come back

    to its neutral state by recombination of the positive and negative charges. The process of

    recombination of positive and negative charges is known as deionization process. In

    deionization by diffusion, the negative ions or electrons and positive ions move to the

    walls under the influence of concentration gradients and thus completing the process of

    recombination.

    Role of arc in Circuit Breaker:

    When two current contacts just open, an arc bridges the contact gap through which the

    current gets a low resistive path to flow so there will not be any sudden interruption of

    current. As there is no sudden and abrupt change in current during opening of the

    contacts, there will not be any abnormal switching over voltage in the system. If i is the

    current flows through the contacts just before they open, L is the system inductance,

    switching over voltage during opening of contacts, may be expressed as V = L.(di/dt)

    where (di/dt) rate of change of current with respect to time during opening of the

    contacts. In the case of alternating current arc is monetarily extinguished at every currentzero. After crossing every current zero the media between separated contacts gets

    ionized again during next cycle of current and the arc in circuit breaker is reestablished.

    To make the interruption complete and successful, this re-ionization in between

    separated contacts to be prevented after a current zero.

    If arc in circuit breaker is absence during opening of current carrying contacts, there

    would be sudden and abrupt interruption of current which will cause a huge switching

    over voltage sufficient to severely stress the insulation of the system. On the other hand,

    the arc provides a gradual but quick, transition from the current carrying to the current

    breaking states of the contacts.

  • 7/30/2019 vocational training wbsetcl

    34/55

    34

    LIGHTNING ARRESTORS (L.A)

    A lightning arrester is a device used on electrical power systems

    & telecommunications systems to protect the insulation and conductors of thesystem from the damaging effects of lightning. The typical lightning arrester has a

    high-voltage terminal and a ground terminal. When a lightning surge (or switching

    surge, which is very similar) travels along the power line to the arrester, the current

    from the surge is diverted through the arrestor, in most cases to earth.

    In telegraphy and telephony, a lightning

    arrestor is placed where wires enter a

    structure, preventing damage to

    electronic instruments within andensuring the safety of individuals near

    them. Smaller versions of lightning

    arresters, also called surge protectors,

    are devices that are connected between

    each electrical conductor in power and

    communications systems and the Earth.

    These prevent the flow of the normal

    power or signal currents to ground, but provide a path over which high-voltage

    lightning current flows, bypassing the connected equipment. Their purpose is to limitthe rise in voltage when a communications or power line is struck by lightning or is

    near to a lightning strike.

    If protection fails or is absent, lightening that strikes the electrical system introduces

    thousands of kilovolts that may damage the transmission lines, and can also cause

    severe damage to transformers and other electrical or electronic devices. Lightning-

    produced extreme voltage spikes in incoming power lines can damage electrical

    home appliances.

  • 7/30/2019 vocational training wbsetcl

    35/55

    35

    TRANSFORMER

    Electrical Power Transformer is a static device which transforms electrical energy from onecircuit to another without any direct electrical connection and with the help of mutual

    induction between to windings. It transforms power from one circuit to another without

    changing its frequency but may be in different voltage level.

    Working Principle of transformer:

    The working principle of transformer is very simple. It depends upon Faraday's laws of

    Electromagnetic Induction. Actually mutual induction between two or more winding is

    responsible for transformation action in an electrical transformer.

    Faraday's laws of Electromagnetic Induction:

    According to these Faraday's laws, "Rate of change of flux linkage with respect to time is

    directly proportional to the induced EMF in a conductor or coil".

    Basic Theory of Transformer:

    Say you have one winding which is supplied by an alternating electrical source. The

    alternating current through the winding produces a continually changing flux or alternating

    flux surrounds the winding. If any other winding is brought nearer to the previous one,

    obviously some portion of this flux will link with

    the second. As this flux is continually changing in

    its amplitude and direction, there must be a

    change in flux linkage in the second winding or

    coil. According to Faraday's laws of

    Electromagnetic Induction, there must be an EMF

    induced in the second. If the circuit of the latter

    winding is closed, there must be current flows

    through it. This is the simplest form of electricalpower transformer and this is most basic

    ofworking principle of transformer.

    The winding which takes electrical power from the source, is generally known as Primary

    Winding of transformer. Here it is first winding. The winding which gives the desired output

    voltage due to mutual induction in the transformer, is commonly known as Secondary

    Winding of Transformer. Here it is second winding.

  • 7/30/2019 vocational training wbsetcl

    36/55

    36

    The above mentioned form of transformer is theoretically possible but not practically,

    because in open air very tiny portion of the flux

    of the first winding will link with second so the

    current flows through the closed circuit of latter,

    will be so small that it may be difficult to

    measure.

    The rate of change of flux linkage depends upon

    the amount of linked flux, with the second

    winding. So it desired to be linked almost all flux

    of primary winding, to the secondary winding.

    This is effectively and efficiently done by placing

    one low reluctance path common to both the

    winding. This low reluctance path is core of

    transformer, through which maximum number of flux produced by the primary is passedthrough and linked with the secondary winding. This is most basic theory of transformer.

    Main constructional parts of transformer:

    So three main parts of a transformer are,

    1. Primary Winding of transformer - which produces magnetic flux when it is connected to

    electrical source.

    2. Magnetic Core of transformer - the magnetic flux produced by the primary winding, will

    pass through this low reluctance path linked with secondary winding and creates a closedmagnetic circuit.

    3. Secondary Winding of transformer - the flux, produced by primary winding, passes

    through the core, will link with the secondary winding. This winding is also wound on the

    same core and gives the desired output of the transformer.

    Definition of Instrument Transformer:

    Instrument transformers means current transformer & voltage transformer are used

    in electrical power system for stepping down currents and voltages of the system for

    metering and protection purpose. Actually relays and meters used for protection and

    metering, are not designed for high currents and voltages.

    High currents or voltages of electrical power system cannot be directly fed to relays and

    meters. Current transformer steps down rated system current to 1 Amp or 5 Amp

    similarly voltage transformer steps down system voltages to 110V. The relays and meters

    are generally designed for 1 Amp, 5 Amp and 110V.

    Definition of current transformer (CT):

    A current transformer (CT) is an instrument transformer in which the secondary current issubstantially proportional to primary current and differs in phase from it by ideally zero

    degree.

  • 7/30/2019 vocational training wbsetcl

    37/55

    37

    Theory of Current Transformer or CT:

    A current transformer functions with the same basic working principle of electrical power

    transformer, as we discussed earlier, but here is some difference. If a electrical power

    transformer or other general purpose transformer, primary current varies with load or

    secondary current. In case of current transformer, primary currentis the system current and this primary current or system current

    transforms to the CT secondary, hence secondary current or

    burden current depends upon primary current of the current

    transformer.

    In a power transformer, if load is disconnected, there will be only

    magnetizing current flows in the primary. The primary of the power

    transformer takes current from the source proportional to the load

    connected with secondary. But in case of Current transformer, theprimary is connected in series with power line. So current through

    its primary is nothing but the current flows through that power

    line. The primary current of the CT, hence does not depend upon whether the load or

    burden is connected to the secondary or not or what is the impedance value of burden.

    Generally current transformer has very few turns in primary where as secondary turn is large

    in number. Say Np is number of turns in CT primary and Ip is the current through primary.

    Hence the primary AT is equal to NpIp AT.

    If number of turns in secondary and secondary current in that CT are Ns and Is respectively

    then Secondary AT is equal to NsIs AT.

    In an ideal CT the primary AT is exactly is equal in magnitude to secondary AT.

    So from the above statement it is clear that if a CT has one turn in primary and 400 turns in

    secondary winding, if it has 400 A current in primary then it will have 1A in secondary

    burden. Thus the turn ratio of the CT is 400/1A.

    Error in Current Transformer:

    But in an actual current transformer, errors with which we are connected can best be

    considered through a study of phasor diagram for a CT,

    Is - Secondary Current

    Es - Secondary induced emf

    Ip - primary Current

    Ep - primary induced emf

    KT - turns ratio = numbers of secondary turns/number of primary turns

    Io - Excitation Current

    Im - magnetizing component of IoIw - core loss component of Io

    m - main flux.

  • 7/30/2019 vocational training wbsetcl

    38/55

    38

    Let us take flux as reference. EMF Es and Ep lags behind the flux by 90o. The magnitude of

    the passers Es and Ep are proportional to secondary and primary turns. The excitation

    current Io which is made up of two components Im and Iw. The secondary current Io lags

    behind the secondary induced emf Esby an angle s. The secondary current is now

    transferred to the primary side by reversing Is and multiplied by the turns ratio KT. The total

    current flows through the primary Ip is then vector sum of KT Is and Io.

    The Ratio Error in CurrentTransformer:

    From above passer diagram it is clear that primary current Ip is not exactly equal to the

    secondary current multiplied by turns ratio, i.e. KTIs. This difference is due to the primary

    current is contributed by the core excitation current. The error in current

    transformer introduced due to this difference is called current error of CT or Current error

    of current transformer or some times Ratio Error in Current Transformer.

    Hence, the percentage current error = {(|Ip| |KT.Is|)/Ip} X 100 %

    Phase Angle Error in CurrentTransformer:

    For a ideal current transformer the angle between the primary and reversed secondary

    current vector is zero. But for an actual current transformer there is always a difference in

    phase between two due to the fact that primary current has to supply the component of

    the exiting current. The angle between the above two phases in termed as Phase Angle

    Error in Current Transformer or CT. Here in the pharos diagram it is the phase angle error

    is usually expressed in minutes.

    Cause of error in current transformer:

    The total primary current is not actually transformed in CT. One part of the primary current

    is consumed for core excitation and remaining is actually transformers with turns ratio of

    CT so there is error in current transformer means there are both Ratio Error in Current

    Transformer as well as a Phase Angle Error in Current Transformer .

    How to reduce error in current transformer:

    It is desirable to reduce these errors, for better performance. For achieving minimum error

    in current transformer, one can follow the following,

    1) Using a core of high permeability and low hysteresis loss magnetic materials.

    2) Keeping the rated burden to the nearer value of the actual burden.

    3) Ensuring minimum length of flux path and increasing cross sectional area of the core,

    minimizing joint of the core.

    4) Lowering the secondary internal impedance.

    Potential Transformer or Voltage Transformer are used in electrical power system for

    stepping down the system voltage to a safe value which can be fed to low ratings meters

    and relays. Commercially available relays and meters used for protection and metering, are

    designed for low voltage. This is a simplest form of Potential Transformer Definition.

  • 7/30/2019 vocational training wbsetcl

    39/55

    39

    Voltage Transformer or Potential Transformer Theory:

    A Voltage Transformer theory or Potential Transformer theory is just like theory of general

    purpose step down transformer. Primary of this transformer is connected across the phases

    or and ground depending upon the requirement. Just like the transformer, used for

    stepping down purpose, potential transformer i.e. PT has lowers turns winding at itssecondary. The system voltage is applied across the terminals of primary winding of that

    transformer, and then proportionate secondary voltage appears across the secondary

    terminals of the PT. The secondary voltage of the PT is generally 110V. In an ideal Potential

    Transformer or Voltage Transformer when rated burden connected across the secondary

    the ratio of primary and secondary voltages of transformer is equal to the turns ratio and

    furthermore the two terminal voltages are in precise phase opposite to each other. But in

    actual transformer there must be an error in the voltage ratio as well as in the phase angle

    between primary and secondary voltages.

    The errors in Potential Transformer or Voltage Transformer can best be explained by phesor

    diagram, and this is the main part of Potential Transformer theory

    Error in Potential Transformer:

    Is - Secondary Current

    Es - Secondary induced emf

    Vs - Secondary terminal voltage

    Rs - Secondary winding resistance

    Xs - Secondary winding reactanceIp - Primary current

    Ep - primary induced emf

    Vp - Primary terminal voltage

    Rp - Primary winding resistance

    Xp - Primary winding reactance

    KT - turns ratio = numbers of primary turns/number of

    seconadary turns

    Io - Excitation Current

    Im - magnetizing component of IoIw - core loss component of Io

    m - main flux

    - phase angle error

    As in the case of Current Transformer and other purpose

    Electrical Power Transformer, total primary current Ip is the vector sum of excitation current

    and the current equal to reversal of secondary current multiplied by the ratio 1/KT

    Hence, Ip = Io + Is/KT

    If Vp is the system voltage applied to the primary of the PT then voltage drops due to

    resistance and reactance of primary winding due to primary current Ip will comes into

    picture. After subtracting this voltage drop from Vp, Ep will appear across the primary

  • 7/30/2019 vocational training wbsetcl

    40/55

    40

    terminals. this Ep is equal to primary induced emf. This primary emf will transform to the

    secondary winding by mutual induction and transformed emf is E s. Again this Es will be

    dropped by secondary winding resistance and reactance, and resultant will actually appear

    across the burden terminals and it is denoted as Vs

    So if system voltage is Vp, ideally Vp/KT should be the secondary voltage of PT, but in realityactual secondary voltage of PT is Vs.

    Voltage error in Potential Transformer(PT):

    The difference between the ideal value Vp/KT and actual value Vs is the voltage error or ratio

    error in a potential transformer, it can be expressed as ,

    Percentage voltage error = {(Vp KT.Vs)/Vp} X 100 %

    Phase angle error in potential transformer:

    The angle between the primary system voltage Vp and the reversed secondary voltage

    vectors KT.Vs is the phase error

    Cause of error in Potential Transformer:

    The voltage applied to the primary of the potential transformer first drops due to internal

    impedance of primary. Then it appears across the primary winding and then transformed

    proportionally to its turns ratio, to secondary winding. This transformed voltage acrosssecondary winding will again drops due to internal impedance of secondary, before

    appearing across burden terminals. This is the reason of errors in potential transformer.

  • 7/30/2019 vocational training wbsetcl

    41/55

    41

    INTRODUCTION OF INSULATING OIL

    Insulating oil in an electrical power transformer is commonly known as Transformer Oil. It is

    normally obtained by fractional distillation and subsequent treatment of crude petroleum.

    That is why this oil is also known as Mineral Insulating Oil. Transformer Oil serves mainly

    tow purposes one it is liquid insulation in electrical power transformer and two it dissipates

    heat of the transformer e.i. acts as coolant. In addition to these, this oil serves other two

    purposes, it helps to preserve the core and winding as these are fully immersed inside oil

    and another important purpose of this oil is, it prevents direct contact of atmospheric

    oxygen with cellulose made paper insulation of windings, which is susceptible to oxidation.

    Types of Transformer Oil:

    Generally there are two types of Transformer Oil used in transformer,

    1. Paraffin based Transformer Oil

    2. Naphtha based Transformer Oil

    Naphtha oil is more easily oxidized than Paraffin oil. But oxidation product i.e. sludge in the

    naphtha oil is more soluble than Paraffin oil. Thus sludge of naphtha based oil is not

    precipitated in bottom of the transformer. Hence it does not obstruct convection

    circulation of the oil, means it does not disturb the transformer cooling system. But in the

    case of Paraffin oil although oxidation rate is lower than that of Naphtha oil but the

    oxidation product or sludge is insoluble and precipitated at bottom of the tank and obstruct

    the transformer cooling system. Although Paraffin based oil has above mentioned

    disadvantage but still in our country it is generally used because of its easy availability.

    Another problem with paraffin based oil is its high pour point due to the wax content, but

    this does not effect its use due to warm climate condition of India .

    Properties of Transformer Insulating Oil:

    Some specific parameters of insulating oil should be considered to determine the

    serviceability of that oil.

    Parameters of Transformer Oil:

    The parameters of Transformer Oil are categorized as,

    1. Electrical Parameters Dielectric Strength, Specific Resistance, Dielectric Dissipation

    Factor.

    2. Chemical Parameter - Water Content, Acidity, Sludge Content.

    3. Physical Parameters - Inter Facial Tension, Viscosity, Flash Point, Pour Point.

  • 7/30/2019 vocational training wbsetcl

    42/55

    42

    Dielectric Strength of Transformer Oil:

    Dielectric Strength of Transformer Oil is also knlown as Breakdown Voltage of transformer

    oil orBDV of transformer oil. Break down voltage is measured by observing at what voltage,

    sparking strants between two electrods immerged in the oil, separated by specific gap. low

    value of BDV indicates presence of moisture content and conducting substances in the oil.For measuring BDV of transformer oil, portable BDV

    measuring kit is generally available at site. In this kit, oil is

    kept in a pot in which one pair of electrodes are fixed

    with a gap of 2.5 mm (in some kit it 4mm) between them.

    Now slowly rising voltage is applied between the

    electrodes. Rate of rise of voltage is generally controlled

    at 2KV/s and observe the voltage at which sparking starts

    between the electrodes. That means at which voltage

    Dielectric Strength of transformer oil between theelectrodes has been broken down. Generally this

    measurement is taken 3 to 6 times in same sample of oil and the average value of these

    reading is taken. BDV is important and popular test of transformer oil, as it is primary

    indication of health of oil and it can be easily carried out at site.

    Dry and clean oil gives BDV results, better than the oil with moisture content and other

    conducting impurities. Minimum Breakdown Voltage of transformer oil or Dielectric

    Strength of transformer oil at which this oil can safely be used in transformer, is considered

    as 30 KV.

    Specific Resistance of Transformer Oil:

    This is another important property of transformer oil. This is measure of DC resistance

    between two opposite sides of one cm3

    block of oil. Its unit is taken as ohm-cm at specific

    temperature. With increase in temperature the resistivity of oil decreases rapidly. Just after

    charging a transformer after long shut down, the temperature of the oil will be at ambient

    temperature and during full load the temperature will be very high and may go upto 90oC at

    over load condition. So resistivity of the insulating oil must be high at room temperature

    and also it should have good value at high temperature as well. That is why specific

    resistance or resistivity of transformer oil should be measured at 27o

    C as well as 90o

    C.

    Minimum standard Specific Resistance of Transformer oil at 90oC is 35X 10

    12ohm cm and

    at 27oC it is 1500X10

    12ohm cm.

    Dielectric Dissipation Factor of Transformer oil:

    Dielectric Dissipation Factor is also known as loss factor or tan delta of transformer oil.

    When a insulating materials is placed between live part and grounded part of an electrical

    equipment, leakage current will flow. As insulating material is dielectric in nature the

    current through the insulation ideally leads the voltage by 90 o. Here voltage means the

    instantaneous voltage between live part and ground of the equipment. But in reality no

    insulating materials are perfect dielectric in nature. Hence current through the insulator will

    lead the voltage with an angle little bit shorter than 90o. Tangent of the angle by which it is

    short of 90o

    is called Dielectric Dissipation Factor or simply tan delta of transformer oil.

  • 7/30/2019 vocational training wbsetcl

    43/55

    43

    More clearly, the leakage current through an insulation does have two component one is

    capacitive or reactive and other one is resistive or active. Again it is clear from above

    diagram, value of which is also known as loss angle, is smaller, means resistive

    component of the current IR is smaller which indicates high resistive property of the

    insulating material. High resistive insulation is good insulator. Hence it is desirable to have

    loss angle as small as possible. So we should try to keep the value of tan as small aspossible. High value of this tan is an indication of presence of contaminants in transformer

    oil. Hence there is a clear relationship between tan and resistivity of insulating oil. If

    resistivity of the insulating oil is decreased, the value of tandelta increases and vice versa.

    So both resistivity test and tan delta test of transformer oil are not normally required for

    same piece of insulator or insulating oil.

    In one sentence it can be said that, tan is measure of imperfection of dielectric nature of

    insulation materials like oil.

    Water Content in Transformer Oil:

    Moisture or Water Content in Transformer Oil is highly undesirable as it affects adversely

    the dielectric properties of oil. The water content in oil also affects the paper insulation of

    the core and winding of transformer. Paper is highly hygroscopic in nature. Paper absorbs

    maximum amount of water from oil which affects paper insulation property as well as

    reduced its life. But in loaded transformer, oil becomes hotter, hence the solubility of water

    in oil increases as a result the paper releases water and increase the water content in

    transformer oil. Thus the temperature of the oil at the time of taking sample for test is very

    important. During oxidation acid are formed in the oil the acids give rise the solubility of

    water in the oil. Acid coupled with water further decompose the oil forming more acid and

    water. This rate of degradation of oil increases. The water content in oil is measured as

    pm(parts per million unit).

    Water content in oil is allowed up to 50 ppm as recommended by IS 335(1993). The

    accurate measurement of water content at such low levels requires very sophisticated

    instrument like Coulometric Karl Fisher Titrator.

    Acidity of Transformer Oil:

    Acidity of transformer oil, is harmful property. If oil becomes acidic, water content in the oilbecomes more soluble to the the oil. Acidity of oil detoriates the insulation property of

    paper insulation of winding. Acidity accelerates thee oxidation process in the oil. Acid also

    includes rusting of iron in presence of moisture. The acidity of transformer oil is measure of

    its acidic constituents of contaminants. Acidity of oil is express in mg of KOH required to

    neutralize the acid present in a gram of oil. This is also known as neutralization number.

    Inter Facial Tension of Transformer Oil:

    Inter Facial Tension between the water and oil interface is the way to measure molecular

    attractive force between water and oil. It is measured in Dynes/cm or miliNeuton/meter.

    Inter facial Tension is exactly useful for determining the presence of polar contaminants

    and oil decay products. Good new oil generally exhibits high inter facial tension. Oil

    oxidation contaminants lower the IFT.

  • 7/30/2019 vocational training wbsetcl

    44/55

    44

    Flash Point of Transformer Oil:

    Flash point of transformer oil is the temperature at which oil gives enough vapors to

    produce a flammable mixture with air. This mixture gives momentary flash on application of

    flame under standard condition. Flash point is important because it specifies the chances of

    fire hazard in the transformer. So it is desirable to have very high flash point of transformeroil. In general it is more than 140

    o(>10

    o).

    Pour Point of Transformer Oil:

    It is the minimum temperature at which oil just start to flow under standard test condition.

    Pour Point of Transformer Oil is an important property mainly at the places where climate is

    extremely cold. If the oil temperature falls bellow the pour point, transformer oil stops

    convection flowing and obstruct cooling in transformer. Paraffin based oil has higher value

    of pour point, compared to Naphtha based oil, but in India like country, it does not effectthe use of Paraffin oil due tits warm climate condition. Pour Point of transformer oil mainly

    depends upon wax content in the oil. As Paraffin based oil has more wax content, it has

    higher pour point.

    Viscosity of Transformer Oil:

    In few wards, Viscosity of Transformer Oil can be said that Viscosity is the resistance of

    flow, at normal condition. Obviously resistance to flow of transformer oil means

    obstruction of convection circulation of oil inside the transformer. A good oil should have

    low viscosity so that it offers less resistance to the convectional flow of oil thereby notaffecting the cooling of transformer. Low viscosity of transformer oil is essential, but it is

    equally important that, the viscosity of oil should increase as less as possible with decrease

    in temperature. Every liquid becomes more viscous if temperature decreases.

  • 7/30/2019 vocational training wbsetcl

    45/55

    45

    BUCHHOLZ RELAY

    Construction of Buchholz Relay:

    Buchholz Relay in transformer is an oil container housed the connecting pipe from main

    tank to conservator tank. It has mainly two elements. The upper element consists of a float.

    The float is attached to a hinge in such a way that it can move up and down depending

    upon the oil level in the Buchholz Relay Container. One mercury switch is fixed on the float.

    The alignment of mercury switch hence depends upon the position of the float.

    The lower element consists of a baffle plate and mercury switch. This plate is fitted on a

    hinge just in front of the inlet (main tank side) of Buchholz Relay in transformer in such a

    way that when oil enters in the relay from that inlet in high pressure the alignment of the

    baffle plate along with the mercury switch attached to it, will change. In addition to these

    main elements a Buchholz Relay has gas release pockets on top. The electrical leads from

    both mercury switches are taken out through a molded terminal block.

    Buchholz Relay principle:

    The Buchholz Relay working principle of is very simple. Buchholz Relay function is based on

    very simple mechanical phenomenon. It is mechanically actuated. Whenever there will be a

    minor internal fault in the transformer such as an insulation faults between turns, break

    down of core of transformer, core heating, the transformer insulating oil will bedecomposed in different hydrocarbon gases, CO2 and CO. The gases produced due to

    decomposition of transformer insulating oil will accumulate in the upper part the Buchholz

    Container which causes fall of oil level in it. Fall of oil level means lowering the position of

    float and thereby