vocational training wbsetcl
TRANSCRIPT
-
7/30/2019 vocational training wbsetcl
1/55
WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY
LIMITED (WBSETCL)
2012
VOCATIONAL
TRAINING REPORT
K A L Y A N I T R A N S M I S S I O N ( O & M ) S U B - D I V I S I O N , 1 3 2 K V S U B - S T A T I O N
-
7/30/2019 vocational training wbsetcl
2/55
2
WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED
KALYANI 132/33/11 KV SUB-STATION
KALYANI TR. (O & M) SUB-DIVISION
KALYANI, NADIA
A
REPORT ON KALYANI 132KV SUB-STATION & ITS INSTRUMENTS
FOR
MR. SIBASISH GHOSH
ASSISTANT ENGINEER
KALYANI TRANSMISSION (O & M) SUB-DIVISION
WBSETCL
BY
STUDENT OF
ELECTRICAL ENGINEERING
JIS COLLEGE OF ENGINEERING
-
7/30/2019 vocational training wbsetcl
3/55
3
SL. NO. TOPICS PAGE NO.
1 PREFACE 42 ACKNOWLEDGEMENT 5
3 INTRODUCTION 6
4 ELECTRIC SUBSTATION 7-8
5 TRANSMISSION TOWER 9-11
6 ELECTRICAL BUS SYSTEM 12-14
7 CONDUCTORS 15
8 INSULATORS 16-22
9 CAPACITOR BANK 23
10 BUS COUPLER 24
11 CIRCUIT BREAKERS 25-31
12 ARC IN CIRCUIT BREAKER 32-3313 LIGHTNING ARRESTORS 34
14 TRANSFORMER 35-40
15 INTRODUCTION OF INSULATING OIL 41-44
16 BUCHHOLZ RELAY 45-46
17 EARTHING TRANSFORMER 47-48
18 CONTROL ROOM 49
19 PLCC 50
20 ELECTRICAL SWITCHGEAR 51
21 ELECTRICAL PROTECTION RELAY 52
22 BATTERY 53
23 CONCLUSION 54
24 BIBLIOGRAPHY 55
-
7/30/2019 vocational training wbsetcl
4/55
4
PREFACEI have experienced vocational training in W.B.S.E.T.C.L. Kalyani
sub-station from 25th
June to 7th
July, 2012.
I am very grateful to all of the officers who gave warm
reception & the valuable time for me. I have learnt many more
things while doing training in sub-station which has helped me
to enlarge my practical knowledge. By undergoing this training
program I am able to relate my bookish knowledge with its
practical application.
-
7/30/2019 vocational training wbsetcl
5/55
5
ACKNOWLEDGEMENT
Before going into the report, I would like to thank to the H.R.D. department of the
W.B.S.E.T.C.L., Bidhyut Bhawan, Saltlake & Kalyani sub-station for providing me the
opportunity to do the vocational training at their sub-station. I am highly thankful to
Sri. Sibasish Ghosh (A.E.), Sri. Sadhan Ghosh (LNSS), Sri. Ashit Ghosh (A.E.) for their
kind attention. I am also thankful to the other officers for sharing their valuable
experiences & time with me during this training. In this training, I also got the
opportunity to understand the status of export-import of in W.B.S.E.T.CL. & the overall
view of the grid system.
For this constant inspiration & active supervision from the very beginning of the
training, I gratefully acknowledge their significant contribution to the successful
completion of my training.
-
7/30/2019 vocational training wbsetcl
6/55
6
INTRODUCTION
Substation is a part of an electrical generation, transmission, &
distribution system. Substations transform voltage from high to low, or the
reverse, or perform any of several other important functions. Electric power may flow
through several substations between generating plant and consumer, and its voltage
may change in several steps.
Substations may be owned and operated by a transmission or generation electricalutility, or may be owned by a large industrial or commercial customer. Generally
substations are un-attended, relying on SCADA for remote supervision and control.
A substation may include transformers to change voltage levels between high
transmission voltages and lower distribution voltages, or at the interconnection of two
different transmission voltages. The word substation comes from the days before the
distribution system became a grid. As central generation stations became larger,
smaller generating plants were converted to distribution stations, receiving their
energy supply from a larger plant instead of using their own generators. The first
substations were connected to only one power station, where the generators were
housed, and were subsidiaries of that power station.
-
7/30/2019 vocational training wbsetcl
7/55
7
ELECTRIC SUB-STATION
An Electric sub-station is an assembly of equipment in an electric power system through
which electrical energy is passed for transmission, distribution, interconnection,
transformation, conversion or switching.
TYPES OF SUB-STATION:
A.Transmission sub-station,
B.Distribution sub-station,
C.Collector sub-station,
A.Transmission sub-station: A transmission substation connects two or moretransmission lines. The simplest case is where all transmission lines have the same
voltage. In such cases, the substation
contains high-voltage switches that allow
lines to be connected or isolated for faultclearance or maintenance. A transmission
station may have transformers to convert
between two transmission voltages,
voltage control/power factor
correction devices such as capacitors,
reactors or static VAr compensators and
equipment such as phase shifting transformers to control power flow between two
adjacent power systems.B.Distribution sub-station: A distribution substation transfers power from the
transmission system to the distribution
system of an area. It is uneconomical to
directly connect electricity consumers to
the main transmission network, unless
they use large amounts of power, so the
distribution station reduces voltage to avalue suitable for local distribution. The
input for a distribution substation is
typically at least two transmission or sub
http://en.wikipedia.org/wiki/Transformerhttp://en.wikipedia.org/wiki/Voltage_compensationhttp://en.wikipedia.org/wiki/Power_factor_correctionhttp://en.wikipedia.org/wiki/Power_factor_correctionhttp://en.wikipedia.org/wiki/Static_VAr_compensatorhttp://en.wikipedia.org/wiki/Static_VAr_compensatorhttp://en.wikipedia.org/wiki/Static_VAr_compensatorhttp://en.wikipedia.org/wiki/Quadrature_boosterhttp://en.wikipedia.org/wiki/Quadrature_boosterhttp://en.wikipedia.org/wiki/Static_VAr_compensatorhttp://en.wikipedia.org/wiki/Power_factor_correctionhttp://en.wikipedia.org/wiki/Power_factor_correctionhttp://en.wikipedia.org/wiki/Voltage_compensationhttp://en.wikipedia.org/wiki/Transformer -
7/30/2019 vocational training wbsetcl
8/55
8
transmission lines. Input voltage may be, for example, 115 kV, or whatever is
common in the area. The output is a number of feeders. Distribution voltages are
typically medium voltage, between 2.4 kV and 33 kV depending on the size of the
area served and the practices of the local utility.
C.Collector sub-station: In distributed generation projects such as a wind farm,a collector substation may be required. It resembles a distribution substation
although power flow is in the opposite
direction, from many wind turbines up
into the transmission grid. Usually for
economy of construction the collector
system operates around 35 kV, and the
collector substation steps up voltage to atransmission voltage for the grid. The
collector substation can also
provide power factor correction if it is
needed, metering and control of the wind farm. In some special cases a collector
substation can also contain an HVDC static inverter plant.Collector substations also
exist where multiple thermal or hydroelectric power plants of comparable output
power are in proximity. Examples for such substations are Brauweiler in Germany
and Hradec in the Czech Republic, where power is collected from nearby lignite-
fired power plants. If no transformers are required for increase of voltage to
transmission level, the substation is a switching station.
http://en.wikipedia.org/wiki/Distributed_generationhttp://en.wikipedia.org/wiki/Wind_farmhttp://en.wikipedia.org/wiki/Wind_turbinehttp://en.wikipedia.org/wiki/Power_factor_correctionhttp://en.wikipedia.org/wiki/Power_factor_correctionhttp://en.wikipedia.org/wiki/Wind_turbinehttp://en.wikipedia.org/wiki/Wind_farmhttp://en.wikipedia.org/wiki/Distributed_generation -
7/30/2019 vocational training wbsetcl
9/55
9
TRANSMISSION TOWER
The main supporting unit of overhead transmission line is transmission tower. Transmission
towers have to carry the heavy transmission conductor
at a sufficient safe height from ground. In addition to
that all towers have to sustain all kinds of natural
calamities. So transmission tower designing is an
important engineering job where all three basic
engineering concepts, civil, mechanical and electrical
engineering concepts are equally applicable. Main parts
of a transmission tower.
A power transmission tower consists of the following
parts,
1) Peak of transmission tower
2) Cross Arm of transmission tower
3) Boom of transmission tower
4) Cage of transmission tower
5) Transmission Tower Body
6) Leg of transmission tower
7) Stub/Anchor Bolt and Base plate assembly of transmission tower.
THE MAIN PARTS AMONG THESE ARE SHOWN IN THE PICTURES:
-
7/30/2019 vocational training wbsetcl
10/55
10
Peak of transmission tower:
The portion above the top cross arm is called peak of transmission tower. Generally earth
shield wire connected to the tip of this peak.
Cross Arm of transmission tower:
Cross arms of transmission tower hold the transmission conductor. The dimension of cross
arm depends on the level of transmission voltage, configuration and minimum forming
angle for stress distribution.
Cage of transmission tower:
The portion between tower body and peak is known as cage of transmission tower. This
portion of the tower holds the cross arms.
Transmission Tower Body:
The portion from bottom cross arms up to the ground level is called transmission tower
body. This portion of the tower plays a vital role for maintaining required ground
clearance of the bottom conductor of the transmission line.
DESIGN OF TRANSMISSION TOWER:
To determine the actual transmission tower height by considering the above points, we have
divided the total height of tower in four parts -
i. Minimum permissible ground clearance(H1),
ii. Maximum sag of the conductors (H2),
iii. Vertical spacing between top & bottom
conductors (H3),
iv. Vertical clearance between ground wire and top
conductors (H4),
-
7/30/2019 vocational training wbsetcl
11/55
11
TYPES OF TRANSMISSION TOWER:
According to different considerations, there are different types of transmission towers.
The transmission line goes as per available corridors. Due to unavailability of shortest
distance straight corridor transmission line has to deviate from its straight way whenobstruction comes. In total length of a long transmission line there may be several
deviation points. According to the angle of deviation there are four types of
transmission tower
A type tower angle of deviation 0o to 2o.
B type tower angle of deviation 2o to 15o.
C type tower angle of deviation 15o to 30o.
D type tower angle of deviation 30
o
to 60
o
.
As per the force applied by the conductor on the cross arms, the transmission towers
can be categorized in another way.
Tangent Suspension tower and it is generally A - type tower.
Angle tower or tension tower or sometime it is called section tower. All B, C and
D types of transmission towers come under this category.
Apart from the above customized type of tower, the tower is designed to meet special
usages listed below,
These are called special type tower
River Crossing Tower
Railway/ Highway Crossing tower
Transposition tower
Based on numbers of circuits carried by a transmission tower, transportation can be
classified as
Single Circuit tower
Double Circuit tower
Multi Circuit tower.
-
7/30/2019 vocational training wbsetcl
12/55
12
ELECTRICAL BUS SYSTEM & SUBSTATION LAYOUT
There are many different electrical bus system schemes available but selection of a
particular scheme depends upon the system voltage, position of substation in electrical
power system, flexibility needed in system and cost to be expensed.
The main criterias to be considered during selection of one particular Bus Bar
Arrangement Scheme among others
Simplicity of system.
Easy maintenance of different equipments.
Minimizing the outage during maintenance.
Future provision of extension with growth of demand.
Optimizing the selection of bus bar arrangement scheme so that it gives maximum
return from the system.
Some very commonly used bus bar arrangement are discussed below
SINGLE BUS SYSTEM:
Single Bus System is simplest and cheapest one. In this scheme all the feeders and
transformer bay are connected to only one single bus as shown.
Advantages of single bus system:
This is very simple in design
This is very cost effective scheme
This is very convenient to operate
Disadvantages of single bus system:
One but major difficulty of these type of
arrangement is that, maintenance of
equipment of any bay cannot be
possible without interrupting the feeder or transformer connected to that bay. The
indoor 11KV switchboards have quite often single bus bar arrangement.
-
7/30/2019 vocational training wbsetcl
13/55
13
Single Bus System with Bus Sectionalizer:
Some advantages are realized if a single
bus bar is sectionalized with circuit
breaker. If there are more than one
incoming and the incoming sources and
outgoing feeders are evenly distributed
on the sections as shown in the figure,
interruption of system can be reduced to
a good extent.
DOUBLE BUS SYSTEM:
In double bus bar system two identical bus bars are used in such a way that any
outgoing or incoming feeder can be taken from any of the bus. Actually every feeder is
connected to both of the buses in parallel through individual isolator as shown in the
figure. By closing any of the isolators one
can put the feeder to associated bus.
Both of the buses are energized and
total feeders are divided into two
groups, one group is fed from one bus
and other from other bus. But any
feeder at any time can be transferred
from one bus to other. There is one bus
coupler breaker which should be kept
close during bus transfer operation. For transfer operation, one should first close the
bus coupler circuit breaker then close the isolator associated with the bus to where
the feeder would be transferred and then open the isolator associated with the bus
from where feeder is transferred. Lastly after this transfer operation he or she should
open the bus coupler breaker.
Advantages of Double Bus System:
Double Bus Bar Arrangement increases the flexibility of system.
Disadvantages of Double Bus System:
The arrangement does not permit breaker maintenance without interruption.
-
7/30/2019 vocational training wbsetcl
14/55
14
ONE AND A HALF BREAKER BUS SYSTEM:
This is an improvement on the double breaker scheme to effect saving in the number
of circuit breakers. For every two circuits only one spare breaker is provided. The
protection is however complicated
since it must associate the central
breaker with the feeder whose own
breaker is taken out for
maintenance. For the reasons given
under double breaker scheme and
because of the prohibitory costs of
equipment even this scheme is not
much popular. As shown in the figure
that it is a simple design, two feeders
are fed from two different buses through their associated breakers and these two
feeders are coupled by a third breaker which is called tie breaker. Normally all the
three breakers are closed and power is fed to both the circuits from two buses which
are operated in parallel. The tie breaker acts as coupler for the two feeder circuits.
MAIN AND TRANSFER BUS SYSTEM:This is an alternative of double bus system. The main conception of Main and Transfer
Bus System is, here every feeder line is directly connected through an isolator to a
second bus called transfer bus. The
said isolator in between transfer bus
and feeder line is generally called
bypass isolator. The main bus is as
usual connected to each feeder
through a bay consists of circuit
breaker and associated isolators at
both side of the breaker. There is
one bus coupler bay which couples
transfer bus and main bus through a
circuit breaker and associated isolators at both sides of the breaker. If necessary the
transfer bus can be energized by main bus power by closing the transfer bus coupler
isolators and then breaker. Then the power in transfer bus can directly be fed to thefeeder line by closing the bypass isolator.
-
7/30/2019 vocational training wbsetcl
15/55
15
CONDUCTORS
TYPES OF CONDUCTORS:
For 400 kV transmission line MOOSE wire is used.
For 132 kV transmission line PANTHER wire is used. The diameter is 3mm.
For 220 kV transmission line DEER wire is used. The diameter is 3.45mm.
For 220kV transmission line ZEBRA wire is used. The diameter is 3.15mm.
For 66 kV transmission line DOG wire is used.
TABLE OF CONDUCTORS:
NAMEVOLTAGE
LEVEL
WIRE IN
CONDUCTORWEIGHT
DIAMETER
OF SINGLE
WIRE
Moose 400kV 7/54 2.00kg/m N/A
Deer 220kV 7/30 1.977kg/m 3.54mm
Zebra 220kV 7/54 1.6kg/m 3.15mm
Panther 132kV 7/30 0.976kg/m N/A
Dog 66kV N/A N/A N/A
-
7/30/2019 vocational training wbsetcl
16/55
16
ELECTRICAL INSULATOR
Electrical Insulator must be used in electrical system to prevent unwanted flow of
electric current to the earth from its supporting points. Example: Porcelain insulator,
glass insulator, polymer insulator.
Properties of insulating material:
a. It must be mechanically strong enough to carry tension and weight of conductors.
b. It must have very high dielectric strength to withstand the voltage stresses in
High Voltage system.
c. It must possess high Insulation Resistance to prevent leakage current to the
earth.
d. The insulating material must be free from unwanted impurities.
PORCELAIN INSULATOR:
Porcelain in most commonly used material for over head insulator in present days.
The porcelain is aluminium silicate. The aluminium silicate is mixed with plastic
kaolin, feldspar and quartz to obtain final hard and glazed porcelain
insulator material. The surface of the
insulator should be glazed enough so that
water should not be traced on it. Porcelain
also should be free from porosity since
porosity is the main cause of deterioration
of its dielectric property. It must also be
free from any impurity and air bubble
inside the material which may affect the
insulator properties.
PROPERTY VALUE
Dielectric strength 60kV/cm
Compressive strength 70,000kg/cm2
Tensile strength 500kg/cm2
-
7/30/2019 vocational training wbsetcl
17/55
17
GLASS INSULATOR:
Nowadays glass insulator has become popular in transmission and distribution
system. Annealed tough glass is used for insulating purpose. Glass insulator has
numbers of advantages over conventional porcelain insulator.
Advantages of glass insulator:
It has very high dielectric strength compared to porcelain.
Its resistivity is also very high.
It has low coefficient of thermal expansion.
It has higher tensile strength compared to porcelain insulator.
As it is transparent in nature it is not heated up in sunlight as porcelain.
The impurities and air bubble can be easily detected inside the glass insulator body
because of its transparency.
PROPERTY VALUE
Dielectric strength 140kV/cm
Compressive strength 10,000kg/cm2
Tensile strength 35,000kg/cm
2
-
7/30/2019 vocational training wbsetcl
18/55
18
POLYMER INSULATOR:
In a polymer insulator has two parts, one is glass fiber reinforced epoxy resin rod
shaped core and other is silicone rubber or EPDM (Ethylene Propylene Diene
Monomer) made weather sheds. Rod shaped core is covered by weather sheds.Weather sheds protect the insulator core from outside environment. As it is made of
two parts, core and weather sheds, polymer insulator is also calledcomposite
insulator. The rod shaped core is fixed with Hop dip galvanized cast steel made end
fittings in both sides.
Advantages of polymer insulator:
It is very light weight compared to porcelain
and glass insulator.
As the composite insulator is flexible the
chance of breakage becomes minimum.
Because of lighter in weight and smaller in
size, this insulator has lower installation cost.
It has higher tensile strength compared to
porcelain insulator.
Disadvantages of polymer insulator:
Moisture may enter in the core if there is any
unwanted gap between core and weather sheds.
This may cause electrical failure of the insulator.
Over crimping in end fittings may result to
cracks in the core which leads to mechanical failure
of polymer insulator.
Types of Insulator:
There are mainly three types of insulator used as overhead insulator likewise
Pin Insulator
Suspension Insulator Stray Insulator
-
7/30/2019 vocational training wbsetcl
19/55
19
PIN INSULATOR:
Pin Insulator is earliest developed overhead insulator, but still popularly used in
power network up to 33KV system.Pin type insulator can be one part,
two parts or three parts type,
depending upon application voltage.
In 11KV system we generally use
one part type insulator where whole
pin insulator is one piece of properly
shaped porcelain or glass. As the
leakage path of insulator is through
its surface, it is desirable to increase
the vertical length of the insulator
surface area for lengthening leakage
path. In order to obtain lengthy
leakage path, one, two or more rain
sheds or petticoats are provided on
the insulator body. In addition to that rain shed or petticoats on an insulator serve
another purpose. These rain sheds or petticoats are so designed, that during raining
the outer surface of the rain shed becomes wet but the inner surface remains dry
and non-conductive. So there will be discontinuations of conducting path through
the wet pin insulator surface.
Designing consideration of Electrical Insulator:
The live conductor attached to the top of the pin insulator is at a potential and
bottom of the insulator fixed to supporting structure of earth potential. Theinsulator has to withstand the potential stresses between conductor and earth.
The shortest distance between conductor and earth, surrounding the insulator
body, along which electrical discharge may take place through air, is known as
flash over distance.
1. When insulator is wet, its outer surface becomes almost conducting. Hence
the flash over distance of insulator is decreased. The design of an electrical
insulator should be such that the decrease of flash over distance is minimum
when the insulator is wet. That is why the upper most petticoat of a pininsulator has umbrella type designed so that it can protect, the rest lower part
of the insulator from rain. The upper surface of top most petticoat is inclined as
less as possible to maintain maximum flash over voltage during raining.
-
7/30/2019 vocational training wbsetcl
20/55
20
2. To keep the inner side of the insulator dry, the rain sheds are made in order
that these rain sheds should not disturb the voltage distribution they are so
designed that their subsurface at right angle to the electromagnetic lines of
force.
POST INSULATOR:
Post insulator is more or less similar to Pin insulator but former is suitable for higher
voltage application. Post insulator has higher numbers of petticoats and has greater
height. This type of insulator can be mounted on supporting structure horizontally as
well as vertically. The insulator is made of one piece of porcelain but has fixing clamp
arrangement are in both top and bottom end.
The main differences between pin insulator and post insulator are:
SUSPENSION INSULATOR:
In higher voltage, beyond 33KV, it becomes uneconomical to use pin insulator
because size, weight of the insulator become more. Handling and replacing bigger
size single unit insulator are quite difficult task. For overcoming these
difficulties, suspension insulator was developed.
In suspension insulator numbers of insulators are connected in series to form a
string and the line conductor is carried by the bottom most insulator. Each
insulator of a suspension string is called disc insulator because of their disc like
shape
SL. NO. PIN INSULATOR POST INSULATOR
1It is generally used up to 33KV
system.
It is suitable for lower voltage and also
for higher voltage.
2It is single stag. It can be single stag as well as multiple
stags.
3
Two insulators cannot be fixed
together for higher voltage
application.
Two or more insulators can be fixed
together one above other for higher
voltage application.
4
Metallic fixing arrangement
provided only on bottom end of
the insulator.
Metallic fixing arrangement provided
on both top and bottom ends of the
insulator.
-
7/30/2019 vocational training wbsetcl
21/55
21
Advantages of Suspension Insulator:
1. Each suspension disc is designed for normal voltage rating 11KV(Higher voltage
rating 15KV), so by using different numbers of discs, a suspension string can be
made suitable for any voltage level.
2. If any one of the disc insulators in a suspension string is damaged, it can be
replaced much easily.
3. Mechanical stresses on the suspension insulator is less since the line hanged on
a flexible suspension string.
4. As the current carrying conductors are suspended from supporting structure by
suspension string, the height of the conductor position is always less than the total
height of the supporting structure. Therefore, the conductors may be safe from
lightening.
Disadvantages of Suspension Insulator:
Suspension insulator string costlier than pin and post type insulator.
Suspension string requires more height of supporting structure than that for pin
or post insulator to maintain same ground clearance of current conductor.
The amplitude of free swing of conductors is larger in suspension insulator
system, hence, more spacing between conductors should be provided.
-
7/30/2019 vocational training wbsetcl
22/55
22
STRAIN INSULATOR:
When suspension string is used to sustain
extraordinary tensile load of conductor it is
referred as string insulator. When there is a deadend or there is a sharp corner in transmission line,
the line has to sustain a great tensile load of
conductor or strain. A strain insulator must have
considerable mechanical strength as well as the
necessary electrical insulating properties.
There are other two types of insulator for low voltage application. Those are i.Stay
Insulator ii.Shackle Insulator.
STAY INSULATOR:
For low voltage lines, the stays
are to be insulated from ground
at a height. The insulator used
in the stay wire is called as
the stay insulator and is usually
of porcelain and is so designed
that in case of breakage of the
insulator the guy-wire will not fall to the ground.
SHACKLE INSULATOR:
Theshackle insulatororspool insulatoris usually used
inlow voltage distribution network. It can be used
both in horizontal and vertical position.
Rated
SystemVoltage
Number of disc insulator used in strain
type tension insulator string
Number of disc insulator
used in suspensioninsulator string
33KV 3 3
66KV 5 4
132KV 9 8
220KV 15 14
-
7/30/2019 vocational training wbsetcl
23/55
23
CAPACITOR BANK
Acapacitorbank is a grouping of several identical capacitors interconnected in parallel or in
series with one another. These groups of capacitors are typically used to correct or
counteract undesirable characteristics, such aspower factorlag or phase shifts inherent in
alternating current (AC) electricalpower supplies. Capacitor banks may also be used in
direct current (DC) power supplies to increase stored energy and improve the ripple current
capacity of thepower supply.
Single capacitors are electrical or electronic components which storeelectrical energy.
Capacitors consist of two conductors that are separated by an insulating material or
dielectric. When an electrical current is passed
through the conductor pair, a staticelectric
fielddevelops in the dielectric which represents
the stored energy. Unlike batteries, this stored
energy is not maintained indefinitely, as the
dielectric allows for a certain amount of current
leakage which results in the gradual dissipation
of the stored energy.
The energy storing characteristic of capacitors is
known ascapacitanceand is expressed or
measured by the unit farads. These
characteristics also allow capacitors to be used
in a group or capacitor bank to absorb and correct AC power supply faults.
The use of a capacitor bank to correct AC power supply anomalies is typically found in heavy
industrial environments that feature working loads made up of electric motors and
transformers. This type of working load is problematic from a power supply perspective aselectric motors and transformers represent inductive loads, which cause a phenomenon
known as phase shift or power factor lag in the power supply.
The use of a capacitor bank in the power supply system effectively cancels out or
counteracts these phase shift issues, making the power supply far more efficient and cost
effective. The installation of a capacitor bank is also one of the cheapest methods of
correcting power lag problems and maintaining a power factor capacitor bank is simple and
cost effective. One thing that should always be kept in mind when working withany capacitor or capacitor bank is the fact that the stored energy, if incorrectly discharged,
can cause serious burns or electric shocks.
http://www.wisegeek.com/what-is-a-capacitor.htmhttp://www.wisegeek.com/what-is-a-capacitor.htmhttp://www.wisegeek.com/what-is-a-capacitor.htmhttp://www.wisegeek.com/what-is-power-factor.htmhttp://www.wisegeek.com/what-is-power-factor.htmhttp://www.wisegeek.com/what-is-power-factor.htmhttp://www.wisegeek.com/what-are-the-most-common-applications-for-ac-current.htmhttp://www.wisegeek.com/what-are-the-most-common-applications-for-ac-current.htmhttp://www.wisegeek.com/what-are-the-most-common-applications-for-ac-current.htmhttp://www.wisegeek.com/what-are-power-supplies.htmhttp://www.wisegeek.com/what-are-power-supplies.htmhttp://www.wisegeek.com/what-are-power-supplies.htmhttp://www.wisegeek.com/what-is-a-power-supply.htmhttp://www.wisegeek.com/what-is-a-power-supply.htmhttp://www.wisegeek.com/what-is-a-power-supply.htmhttp://www.wisegeek.com/what-is-electrical-energy.htmhttp://www.wisegeek.com/what-is-electrical-energy.htmhttp://www.wisegeek.com/what-is-electrical-energy.htmhttp://www.wisegeek.com/what-is-an-electric-field.htmhttp://www.wisegeek.com/what-is-an-electric-field.htmhttp://www.wisegeek.com/what-is-an-electric-field.htmhttp://www.wisegeek.com/what-is-an-electric-field.htmhttp://www.wisegeek.com/what-is-capacitance.htmhttp://www.wisegeek.com/what-is-capacitance.htmhttp://www.wisegeek.com/what-is-capacitance.htmhttp://www.wisegeek.com/what-is-capacitance.htmhttp://www.wisegeek.com/what-is-an-electric-field.htmhttp://www.wisegeek.com/what-is-an-electric-field.htmhttp://www.wisegeek.com/what-is-electrical-energy.htmhttp://www.wisegeek.com/what-is-a-power-supply.htmhttp://www.wisegeek.com/what-are-power-supplies.htmhttp://www.wisegeek.com/what-are-the-most-common-applications-for-ac-current.htmhttp://www.wisegeek.com/what-is-power-factor.htmhttp://www.wisegeek.com/what-is-a-capacitor.htm -
7/30/2019 vocational training wbsetcl
24/55
24
BUS COUPLER
Bus coupler is a device which is used to switch from one bus to the other without anyinterruption in power supply and without creating hazardous arcs. It is achieved with the
help of circuit breaker and isolators.
Bus coupler configurations are available as non-terminated or internally terminated. If two
or more non-terminated couplers are used on a bus, then the couplers at each end of the
bus must be terminated externally with 78 ohm terminators on the unused bus connections
of the end couplers. Alternately, internally single terminated couplers (with or without the
non-functional bus connectors) can be supplied.
Even if only one non-terminated coupler acts as the bus because all devices (bus controller,
remote terminals, etc.) are connected to the couplers stubs, the external bus connections
of the coupler must be terminated. A dual-terminated coupler (with or without non-
functional bus connectors) can be employed where the coupler acts as the bus without
other couplers.
COMPONENTS OF BUS COUPLER:
Main bus isolator
Current transformer
Circuit breaker
Line isolator
Supporting insulator
Potential transformer
-
7/30/2019 vocational training wbsetcl
25/55
25
CIRCUIT BREAKERS
Electrical Circuit Breaker is a switching device which can be operated manually as well as
automatically for controlling and protection of electrical power system respectively.
TYPES OF CIRCUIT BREAKER:
According different criteria there are different types of circuit breaker.According to
their arc quenching media the circuit breaker can be divided as
SF6 CIRCUIT BREAKER
VACCUM CIRCUIT BREAKER
OIL CIRCUIT BREAKER
GAS CIRCUIT BREAKER
SF6 CIRCUIT BREAKER:
A circuit breaker in which the current carrying contacts operate in Sulphur Hexafluoride or
SF6 gas is known as an SF6 Circuit Breaker.
SF6 has excellent insulating property. SF6 has high electro-negativity. That means it has
high affinity of absorbing free electron. Whenever a free electron collides with the SF6
gas molecule, it is absorbed by that gas molecule and forms a negative ion.
The attachment of electron with SF6 gas molecules may occur in tow different ways,
1) SF6 +e=SF6
2) SF6 + e = SF5-+ F
These negative ions obviously much heavier than a free electron and therefore over all
mobility of the charged particle in the SF6 gas is much less as compared other common
gases. We know that mobility of charged particle is majorly responsible for conducting
current through a gas.
WORKING OF SF6 CIRCUIT BREAKER:
The working of SF6 circuit Breaker of first generation was quite simple it is some extent
similar to air blast circuit breaker. Here SF6 gas was compressed and stored in a highpressure reservoir. During operation of SF6 circuit breaker this highly compressed gas is
released through the arc and collected to relatively low pressure reservoir and then it
pumped back to the high pressure reservoir for reutilize.
-
7/30/2019 vocational training wbsetcl
26/55
26
The working of SF6 circuit breaker is little bit different in modern time. Innovation of
puffer type design makes operation of SF6 circuit breaker much easier. In buffer type
design, the arc energy is utilized to develop pressure in the arcing chamber for arc
quenching.
Here the breaker is filled with SF6 gas at rated pressure. There are two fixed contact
fitted with a specific contact gap. A sliding cylinder bridges these to fixed contacts. The
cylinder can axially slide upward and downward along the contacts. There is one
stationary piston inside the cylinder which is fixed with other stationary parts of the
breaker, in such a way that it can not change its position during the movement of the
cylinder. As the piston is fixed and cylinder is movable or sliding, the internal volume of
the cylinder changes when the cylinder slides.
During opening of the breaker the cylinder moves downwards against position of the
fixed piston hence the volume inside the cylinder is reduced which produces
compressed SF6 gas inside the cylinder. The cylinder has numbers of side vents which
were blocked by upper fixed contact body during closed position. As the cylinder move
further downwards, these vent openings cross the upper fixed contact, and become
unblocked and then compressed SF6 gas inside the cylinder will come out through this
vents in high speed towards the arc and passes through the axial hole of the both fixed
contacts. The arc is quenched during this flow of SF6 gas.
During closing of the breaker, the sliding cylinder moves upwards and as the position of
piston remains at fixed height, the volume of the cylinder increases which introduces
low pressure inside the cylinder compared to the surrounding. Due to this pressure
difference SF6 gas from surrounding will try to enter in the cylinder. The higher pressure
gas will come through the axial hole of both fixed contact and enters into cylinder via
vent and during this flow; the gas will quench the arc.
-
7/30/2019 vocational training wbsetcl
27/55
27
VACUUM CIRCUIT BREAKER:
A vacuum circuit breaker is such kind of circuit breaker where the arc quenching takes place in
vacuum. The technology is suitable for mainly medium voltage application. For higher voltage
Vacuum technology has been developed but not commercially viable. The operation of
opening and closing of current carrying contacts and associated arc interruption take place in
a vacuum chamber in the breaker which is called vacuum interrupter. The vacuum interrupter
consists of a steel arc chamber in the centre symmetrically arranged ceramic insulators. The
vacuum pressure inside a vacuum interrupter is normally maintained at 10- 6
bar.
The material used for current carrying contacts plays an important role in the performance of
the vacuum circuit breaker. CuCr is the most ideal material to make VCB contacts. Vacuum
interrupter technology was first introduced in the year of 1960. But still it is a developing
technology. As time goes on, the size of the vacuum interrupter is being reducing from its
early 1960s size due to different technical developments in this field of engineering. The
contact geometry is also improving with time, from butt contact of early days it gradually
changes to spiral shape, cup shape and axial magnetic field contact. The vacuum circuit
breaker is today recognized as most reliable current interruption technology for medium
voltage system. It requires minimum maintenance compared to other circuit breaker
technologies.
Advantages of vacuum circuit breaker:
Service life of Vacuum Circuit Breaker is much longer than other types of circuit breakers.There is no chance of fire hazard as oil circuit breaker. It is much environment friendly
than SF6 Circuit breaker. Beside of that contraction of VCB is much user friendly. Replacement
of Vacuum Interrupter (VI) is much convenient.
Operation of Vacuum Circuit Breaker:
The main aim of any circuit breaker is to quench arc during current zero crossing, by
establishing high dielectric strength in between the contacts so that reestablishment of arc
after current zero becomes impossible. The dielectric strength of vacuum is eight times
greater than that of air and four times greater than that of SF6 gas. This high dielectric
strength makes it possible to quench a vacuum arc within very small contact gap. For short
contact gap, low contact mass and no compression of medium the drive energy required in
vacuum circuit breaker is minimum. When two face to face contact areas are just being
separated to each other, they do not be separated instantly, contact area on the contact face
is being reduced and ultimately comes to a point and then they are finally de-touched.
Although this happens in a fraction of micro second but it is the fact.
At thid instant of de-touching of contacts in a vacuum, the current through the contacts
concentrated on that last contact point on the contact surface and makes a hot spot. As it isvacuum, the metal on the contact surface is easily vaporized due to that hot spot and create
a conducting media for arc path. Then the arc will be initiated and continued until the next
current zero. At current zero this vacuum arc is extinguished and the conducting metal
vapour is re-condensed on the contact surface. At this point, the contacts are already
-
7/30/2019 vocational training wbsetcl
28/55
28
separated hence there is no question of re-vaporization of contact surface, for next cycle of
current. That means, the arc cannot be reestablished again. In this way vacuum circuit
breaker prevents the reestablishment of arc by producing high dielectric strength in the
contact gap after current zero.
There are two types of arc shapes. For interrupting current up to 10kA, the arc remains
diffused and the form of vapour discharge and cover the entire contact surface. Above 10kA
the diffused arc is constricted considerably by its own magnetic field and it contracts. The
phenomenon gives rise over heating of contact at its center. In order to prevent this, the
design of the contacts should be such that the arc does not remain stationary but keeps
travelling by its own magnetic field. Specially designed contact shape of vacuum circuit
breaker make the constricted stationary arc travel along the surface of the contacts, thereby
causing minimum and uniform contact erosion.
OIL CIRCUIT BREAKER:
Mineral oil has better insulating property than air. In oil circuit breaker the fixed contact and
moving contact are immerged inside the insulating oil. Whenever there is a separation of
current carrying contacts in the oil, the arc is initialized at the moment of separation of
contacts, and due to this arc the oil is vaporized and decomposed in mostly hydrogen gas
and ultimately creates a hydrogen bubble around the arc. This highly compressed gas
bubble around the arc prevents re-striking of the arc after current reaches zero crossing of
the cycle. The Oil Circuit Breaker is the one of the oldest type of circuit breakers.
Operation of Oil Circuit Breaker:
The operation of oil circuit breaker is quite simple lets have a discussion. When the current
carrying contacts in the oil are separated an arc is established in between the separated
contacts. Actually, when separation of contacts has just started, distance between the
current contacts is small as a result the voltage gradient between contacts becomes high.
This high voltage gradient between the contacts ionized the oil and consequently initiates
arcing between the contacts. This arc will produce a large amount of heat in surrounding oil
and vaporizes the oil and decomposes the oil in mostly hydrogen and a small amount of
methane, ethylene and acetylene. The hydrogen gas can not remain in molecular form and
its is broken into its atomic form releasing lot of heat. The arc temperature may reach up to
50000K. Due to this high temperature the gas is liberated surround the arc very rapidly and
-
7/30/2019 vocational training wbsetcl
29/55
29
forms an excessively fast growing gas bubble around the arc. It is found that the mixture of
gases occupies a volume about one thousand times that of the oil decomposed. From this
figure we can assume how fast the gas bubble around the arc will grow in size. If this
growing gas bubble around the arc is compressed by any means then rate of de ionization
process of ionized gaseous media in between the contacts will accelerate which rapidly
increase the dielectric strength between the contacts and consequently the arc will bequenched at zero crossing of the current cycle. This is the basic operation of oil circuit
breaker. In addition to that cooling effect of hydrogen gas surround the arc path also helps,
the quick arc quenching in oil circuit breaker.
Types of oil circuit breakers:
There are mainly two types of oil circuit breaker.
Bulk Oil Circuit Breaker:
Bulk Oil Circuit Breaker is such types of circuitbreakers where oil is used as arc quenching
media as well as insulating media between
current carrying contacts and earthed parts of
the breaker. The oil used here is same as
transformer insulating oil.
Minimum Oil Circuit Breaker:
These types of circuit breakers utilize oil as theinterrupting media. However, unlike bulk oil
circuit breaker, a minimum oil circuit
breaker places the interrupting unit in insulating
chamber at live potential. The insulating oil is
available only in interrupting chamber. The
features of designing MOCBare to reduce
requirement of oil, and hence these breaker are
called minimum oil circuit breaker.
AIR CIRCUIT BREAKER:
An air circuit breaker is that kind of circuit breaker which operates in air at atmospheric
pressure. After development of oil breaker, the medium voltage air circuit breaker is
replaced completely by oil circuit breaker in different countries. But in countries like France
and Italy, air circuit breakers are still preferable choice up to voltage 15 KV. It is also good
choice to avoid the risk of oil fire, in case of oil circuit breaker. In America air circuit
breakers were exclusively used for the system up to 15 KV until the development of new
vacuum and SF6 circuit breakers.
Working principle of Air Circuit Breaker:
The working principle of air circuit breaker is rather different from those in any other types
of circuit breakers. The main aim of all kind of circuit breaker is to prevent the
-
7/30/2019 vocational training wbsetcl
30/55
30
reestablishment of arcing after current zero by creating a situation where in the contact gap
will withstand the system recovery voltage. The air circuit breaker does the same but in
different manner. For interrupting arc it creates an arc voltage in excess of the supply
voltage. Arc voltage is defined as the minimum voltage required maintaining the arc. This
circuit breaker increases the arc voltage by mainly three different ways.
It may increase the arc voltage by cooling the arc plasma. As the temperature of arc plasma
is decreased, the mobility of the particle in arc plasma is reduced; hence more voltage
gradient is required to maintain the arc.
It may increase the arc voltage by lengthening the arc path. As the length of arc path is
increased, the resistance of the path is increased, and hence to maintain the same arc
current more voltage is required to be applied across the arc path. That means arc voltage
is increased. Splitting up the arc into a number of series arcs also increases the arc voltage.
Types of air circuit breaker:
There are mainly two types of air circuit breaker are available.
1) Plain air circuit breaker
2) Air blast Circuit Breaker
Operation of Air Circuit Breaker:
The first objective is usually achieved by forcing the arc into contact with as large an area as
possible of insulating material. All the air circuit breakers are fitted with a chamber
surrounding the contact. This chamber is called 'arc chute'. The arc is driven into it. If inside
of the arc chute is suitably shaped, and if the arc can be made conform to the shape, the
arc chute wall will help to achieve cooling. This type of arc chute should be made from
some kind of refractory material. High temperature plastics reinforced with glass fiber and
ceramics are preferable materials for making arc chute.
The second objective that is lengthening the arc path, is achieved concurrently with fist
objective. If the inner walls of the arc chute is shaped in such a way that the arc is not onlyforced into close proximity with it but also driven into a serpentine channel projected on
the arc chute wall. The lengthening of the arc path increases the arc resistance.
The third technique is achieved by using metal arc slitter inside the arc chute. The main arc
chute is divided into numbers of small compartments by using metallic separation plates.
These metallic separation plates are actually the arc splitters and each of the small
compartments behaves as individual mini arc chute. In this system the initial arc is split into
a number of series arcs, each of which will have its won mini arc chute. So each of the split
arcs has its won cooling and lengthening effect due to its won mini arc chute and hence
individual split arc voltage becomes high. These collectively, make the over all arc voltage,
much higher than the system voltage.
-
7/30/2019 vocational training wbsetcl
31/55
31
This was working principleof air circuit breaker now we will discuss in details the operation
of air circuit breaker in practice.
The air circuit breaker, operated within the voltage level 1KV, does not require any arc
control device. Mainly for heavy fault current on low voltages (low voltage level above 1 KV)
air circuit breakers with appropriate arc control device, are good choice. These breakers
normally have two pairs of contacts. The main pair of contacts carries the current at normal
load and these contacts are made of copper. The additional pair is the arcing contact and is
made of carbon. When circuit breaker is being opened, the main contacts open first and
during opening of main contacts the arcing contacts are still in touch with each other. As
the current gets, a parallel low resistive path
through the arcing contact during opening of
main contacts, there will not be any arcing in
the main contact. The arcing is only initiated
when finally the arcing contacts are separated.
The each of the arc contacts is fitted with an
arc runner which helps, the arc discharge to
move upward due to both thermal and
electromagnetic effects as shown in the figure.
As the arc is driven upward it enters in the arc
chute, consisting of splitters. The arc in chute
will become colder, lengthen and split hence arc voltage becomes much larger than systemvoltage at the time of operation of air circuit breaker, and therefore the arc is quenched
finally during the current zero.
-
7/30/2019 vocational training wbsetcl
32/55
32
ARC IN CIRCUIT BREAKER
Before going through details arc quenchingorarc extinction technologies employed in
circuit breaker we should know first what is arc actually.
Definition of arc:
During opening of current carrying contacts in a circuit breaker the medium in between
opening contacts become highly ionized through which the interrupting current gets low
resistive path and continues to flow through this path even the contacts are physically
separated. During the flowing of current from one contact to other the path becomes so
heated that it glows. This is called arc.
Arc in Circuit Breaker:
Whenever, on load current contacts of circuit breaker open there is an arc in circuit
breaker, established between the separating contacts. As long as this arc is sustained in
between the contacts the current through the circuit breaker will not be interrupted finally
as because arc is itself a conductive path of electricity. For total interruption of current the
circuit breaker it is essential to quench the arc as quick as possible. The main designing
criteria of a circuit breaker is to provide appropriate technology of arc quenching in circuit
breaker to fulfill quick and safe current interruption. So before going through different arc
quenching techniques employed in circuit breaker, we should try to understand "what is
arc" and basic theory of arc in circuit breaker, lets discuss.
Thermal Ionization of gas:
There are numbers of free electrons and ions present in a gas at room temperature due to
ultraviolet rays, cosmic rays and radioactivity of the earth. These free electrons and ions are
so few in number that they are insufficient to sustain conduction of electricity. The gas
molecules move randomly at room temperature. It is found an air molecule at a
temperature of 300oK (Room temperature) moves randomly with an approximate average
velocity of 500 meters/second and collides other molecules at a rate of 1010times/second.
These randomly moving molecules collide each other in very frequent manner but the
kinetic energy of the molecules is not sufficient to extract an electron from atoms of the
molecules. If the temperature is increased the air will be heated up and consequently the
velocity on the molecules increased. Higher velocity means higher impact during
intermolecular collision. During this situation some of the molecules are disassociated in to
atoms. If temperature of the air is further increased many atoms are deprived of valence
electrons and make the gas ionized. Then this ionized gas can conduct electricity because of
sufficient free electrons. This condition of any gas or air is called plasma. This phenomenon
is called thermal ionization of gas.
-
7/30/2019 vocational training wbsetcl
33/55
33
Ionization due to electron collision:
As we discussed that there are always some free electrons and ions presents in the air or
gas but they are insufficient to conduct electricity. Whenever these free electrons come
across a strong electric field, these are directed towards higher potential points in the
field and acquire sufficiently high velocity. In other words, the electrons are accelerated
along the direction of the electric field due to high potential gradient. During their travel
these electrons collide with other atoms and molecules of the air or gas and extract
valance electrons from their orbits. After extracted from parent atoms, the electrons will
also run along the direction of the same electric field due to potential gradient. These
electrons will similarly collide with other atoms and create more free electrons which will
also be directed along the electric field. Due to this conjugative action the numbers of
free electrons in the gas will become so high that the gas stars conducting electricity. This
phenomenon is known as ionization of gas due to electron collision.
Deionization of gas:
If all the cause of ionization of gas are removed from an ionized gas it rapidly come back
to its neutral state by recombination of the positive and negative charges. The process of
recombination of positive and negative charges is known as deionization process. In
deionization by diffusion, the negative ions or electrons and positive ions move to the
walls under the influence of concentration gradients and thus completing the process of
recombination.
Role of arc in Circuit Breaker:
When two current contacts just open, an arc bridges the contact gap through which the
current gets a low resistive path to flow so there will not be any sudden interruption of
current. As there is no sudden and abrupt change in current during opening of the
contacts, there will not be any abnormal switching over voltage in the system. If i is the
current flows through the contacts just before they open, L is the system inductance,
switching over voltage during opening of contacts, may be expressed as V = L.(di/dt)
where (di/dt) rate of change of current with respect to time during opening of the
contacts. In the case of alternating current arc is monetarily extinguished at every currentzero. After crossing every current zero the media between separated contacts gets
ionized again during next cycle of current and the arc in circuit breaker is reestablished.
To make the interruption complete and successful, this re-ionization in between
separated contacts to be prevented after a current zero.
If arc in circuit breaker is absence during opening of current carrying contacts, there
would be sudden and abrupt interruption of current which will cause a huge switching
over voltage sufficient to severely stress the insulation of the system. On the other hand,
the arc provides a gradual but quick, transition from the current carrying to the current
breaking states of the contacts.
-
7/30/2019 vocational training wbsetcl
34/55
34
LIGHTNING ARRESTORS (L.A)
A lightning arrester is a device used on electrical power systems
& telecommunications systems to protect the insulation and conductors of thesystem from the damaging effects of lightning. The typical lightning arrester has a
high-voltage terminal and a ground terminal. When a lightning surge (or switching
surge, which is very similar) travels along the power line to the arrester, the current
from the surge is diverted through the arrestor, in most cases to earth.
In telegraphy and telephony, a lightning
arrestor is placed where wires enter a
structure, preventing damage to
electronic instruments within andensuring the safety of individuals near
them. Smaller versions of lightning
arresters, also called surge protectors,
are devices that are connected between
each electrical conductor in power and
communications systems and the Earth.
These prevent the flow of the normal
power or signal currents to ground, but provide a path over which high-voltage
lightning current flows, bypassing the connected equipment. Their purpose is to limitthe rise in voltage when a communications or power line is struck by lightning or is
near to a lightning strike.
If protection fails or is absent, lightening that strikes the electrical system introduces
thousands of kilovolts that may damage the transmission lines, and can also cause
severe damage to transformers and other electrical or electronic devices. Lightning-
produced extreme voltage spikes in incoming power lines can damage electrical
home appliances.
-
7/30/2019 vocational training wbsetcl
35/55
35
TRANSFORMER
Electrical Power Transformer is a static device which transforms electrical energy from onecircuit to another without any direct electrical connection and with the help of mutual
induction between to windings. It transforms power from one circuit to another without
changing its frequency but may be in different voltage level.
Working Principle of transformer:
The working principle of transformer is very simple. It depends upon Faraday's laws of
Electromagnetic Induction. Actually mutual induction between two or more winding is
responsible for transformation action in an electrical transformer.
Faraday's laws of Electromagnetic Induction:
According to these Faraday's laws, "Rate of change of flux linkage with respect to time is
directly proportional to the induced EMF in a conductor or coil".
Basic Theory of Transformer:
Say you have one winding which is supplied by an alternating electrical source. The
alternating current through the winding produces a continually changing flux or alternating
flux surrounds the winding. If any other winding is brought nearer to the previous one,
obviously some portion of this flux will link with
the second. As this flux is continually changing in
its amplitude and direction, there must be a
change in flux linkage in the second winding or
coil. According to Faraday's laws of
Electromagnetic Induction, there must be an EMF
induced in the second. If the circuit of the latter
winding is closed, there must be current flows
through it. This is the simplest form of electricalpower transformer and this is most basic
ofworking principle of transformer.
The winding which takes electrical power from the source, is generally known as Primary
Winding of transformer. Here it is first winding. The winding which gives the desired output
voltage due to mutual induction in the transformer, is commonly known as Secondary
Winding of Transformer. Here it is second winding.
-
7/30/2019 vocational training wbsetcl
36/55
36
The above mentioned form of transformer is theoretically possible but not practically,
because in open air very tiny portion of the flux
of the first winding will link with second so the
current flows through the closed circuit of latter,
will be so small that it may be difficult to
measure.
The rate of change of flux linkage depends upon
the amount of linked flux, with the second
winding. So it desired to be linked almost all flux
of primary winding, to the secondary winding.
This is effectively and efficiently done by placing
one low reluctance path common to both the
winding. This low reluctance path is core of
transformer, through which maximum number of flux produced by the primary is passedthrough and linked with the secondary winding. This is most basic theory of transformer.
Main constructional parts of transformer:
So three main parts of a transformer are,
1. Primary Winding of transformer - which produces magnetic flux when it is connected to
electrical source.
2. Magnetic Core of transformer - the magnetic flux produced by the primary winding, will
pass through this low reluctance path linked with secondary winding and creates a closedmagnetic circuit.
3. Secondary Winding of transformer - the flux, produced by primary winding, passes
through the core, will link with the secondary winding. This winding is also wound on the
same core and gives the desired output of the transformer.
Definition of Instrument Transformer:
Instrument transformers means current transformer & voltage transformer are used
in electrical power system for stepping down currents and voltages of the system for
metering and protection purpose. Actually relays and meters used for protection and
metering, are not designed for high currents and voltages.
High currents or voltages of electrical power system cannot be directly fed to relays and
meters. Current transformer steps down rated system current to 1 Amp or 5 Amp
similarly voltage transformer steps down system voltages to 110V. The relays and meters
are generally designed for 1 Amp, 5 Amp and 110V.
Definition of current transformer (CT):
A current transformer (CT) is an instrument transformer in which the secondary current issubstantially proportional to primary current and differs in phase from it by ideally zero
degree.
-
7/30/2019 vocational training wbsetcl
37/55
37
Theory of Current Transformer or CT:
A current transformer functions with the same basic working principle of electrical power
transformer, as we discussed earlier, but here is some difference. If a electrical power
transformer or other general purpose transformer, primary current varies with load or
secondary current. In case of current transformer, primary currentis the system current and this primary current or system current
transforms to the CT secondary, hence secondary current or
burden current depends upon primary current of the current
transformer.
In a power transformer, if load is disconnected, there will be only
magnetizing current flows in the primary. The primary of the power
transformer takes current from the source proportional to the load
connected with secondary. But in case of Current transformer, theprimary is connected in series with power line. So current through
its primary is nothing but the current flows through that power
line. The primary current of the CT, hence does not depend upon whether the load or
burden is connected to the secondary or not or what is the impedance value of burden.
Generally current transformer has very few turns in primary where as secondary turn is large
in number. Say Np is number of turns in CT primary and Ip is the current through primary.
Hence the primary AT is equal to NpIp AT.
If number of turns in secondary and secondary current in that CT are Ns and Is respectively
then Secondary AT is equal to NsIs AT.
In an ideal CT the primary AT is exactly is equal in magnitude to secondary AT.
So from the above statement it is clear that if a CT has one turn in primary and 400 turns in
secondary winding, if it has 400 A current in primary then it will have 1A in secondary
burden. Thus the turn ratio of the CT is 400/1A.
Error in Current Transformer:
But in an actual current transformer, errors with which we are connected can best be
considered through a study of phasor diagram for a CT,
Is - Secondary Current
Es - Secondary induced emf
Ip - primary Current
Ep - primary induced emf
KT - turns ratio = numbers of secondary turns/number of primary turns
Io - Excitation Current
Im - magnetizing component of IoIw - core loss component of Io
m - main flux.
-
7/30/2019 vocational training wbsetcl
38/55
38
Let us take flux as reference. EMF Es and Ep lags behind the flux by 90o. The magnitude of
the passers Es and Ep are proportional to secondary and primary turns. The excitation
current Io which is made up of two components Im and Iw. The secondary current Io lags
behind the secondary induced emf Esby an angle s. The secondary current is now
transferred to the primary side by reversing Is and multiplied by the turns ratio KT. The total
current flows through the primary Ip is then vector sum of KT Is and Io.
The Ratio Error in CurrentTransformer:
From above passer diagram it is clear that primary current Ip is not exactly equal to the
secondary current multiplied by turns ratio, i.e. KTIs. This difference is due to the primary
current is contributed by the core excitation current. The error in current
transformer introduced due to this difference is called current error of CT or Current error
of current transformer or some times Ratio Error in Current Transformer.
Hence, the percentage current error = {(|Ip| |KT.Is|)/Ip} X 100 %
Phase Angle Error in CurrentTransformer:
For a ideal current transformer the angle between the primary and reversed secondary
current vector is zero. But for an actual current transformer there is always a difference in
phase between two due to the fact that primary current has to supply the component of
the exiting current. The angle between the above two phases in termed as Phase Angle
Error in Current Transformer or CT. Here in the pharos diagram it is the phase angle error
is usually expressed in minutes.
Cause of error in current transformer:
The total primary current is not actually transformed in CT. One part of the primary current
is consumed for core excitation and remaining is actually transformers with turns ratio of
CT so there is error in current transformer means there are both Ratio Error in Current
Transformer as well as a Phase Angle Error in Current Transformer .
How to reduce error in current transformer:
It is desirable to reduce these errors, for better performance. For achieving minimum error
in current transformer, one can follow the following,
1) Using a core of high permeability and low hysteresis loss magnetic materials.
2) Keeping the rated burden to the nearer value of the actual burden.
3) Ensuring minimum length of flux path and increasing cross sectional area of the core,
minimizing joint of the core.
4) Lowering the secondary internal impedance.
Potential Transformer or Voltage Transformer are used in electrical power system for
stepping down the system voltage to a safe value which can be fed to low ratings meters
and relays. Commercially available relays and meters used for protection and metering, are
designed for low voltage. This is a simplest form of Potential Transformer Definition.
-
7/30/2019 vocational training wbsetcl
39/55
39
Voltage Transformer or Potential Transformer Theory:
A Voltage Transformer theory or Potential Transformer theory is just like theory of general
purpose step down transformer. Primary of this transformer is connected across the phases
or and ground depending upon the requirement. Just like the transformer, used for
stepping down purpose, potential transformer i.e. PT has lowers turns winding at itssecondary. The system voltage is applied across the terminals of primary winding of that
transformer, and then proportionate secondary voltage appears across the secondary
terminals of the PT. The secondary voltage of the PT is generally 110V. In an ideal Potential
Transformer or Voltage Transformer when rated burden connected across the secondary
the ratio of primary and secondary voltages of transformer is equal to the turns ratio and
furthermore the two terminal voltages are in precise phase opposite to each other. But in
actual transformer there must be an error in the voltage ratio as well as in the phase angle
between primary and secondary voltages.
The errors in Potential Transformer or Voltage Transformer can best be explained by phesor
diagram, and this is the main part of Potential Transformer theory
Error in Potential Transformer:
Is - Secondary Current
Es - Secondary induced emf
Vs - Secondary terminal voltage
Rs - Secondary winding resistance
Xs - Secondary winding reactanceIp - Primary current
Ep - primary induced emf
Vp - Primary terminal voltage
Rp - Primary winding resistance
Xp - Primary winding reactance
KT - turns ratio = numbers of primary turns/number of
seconadary turns
Io - Excitation Current
Im - magnetizing component of IoIw - core loss component of Io
m - main flux
- phase angle error
As in the case of Current Transformer and other purpose
Electrical Power Transformer, total primary current Ip is the vector sum of excitation current
and the current equal to reversal of secondary current multiplied by the ratio 1/KT
Hence, Ip = Io + Is/KT
If Vp is the system voltage applied to the primary of the PT then voltage drops due to
resistance and reactance of primary winding due to primary current Ip will comes into
picture. After subtracting this voltage drop from Vp, Ep will appear across the primary
-
7/30/2019 vocational training wbsetcl
40/55
40
terminals. this Ep is equal to primary induced emf. This primary emf will transform to the
secondary winding by mutual induction and transformed emf is E s. Again this Es will be
dropped by secondary winding resistance and reactance, and resultant will actually appear
across the burden terminals and it is denoted as Vs
So if system voltage is Vp, ideally Vp/KT should be the secondary voltage of PT, but in realityactual secondary voltage of PT is Vs.
Voltage error in Potential Transformer(PT):
The difference between the ideal value Vp/KT and actual value Vs is the voltage error or ratio
error in a potential transformer, it can be expressed as ,
Percentage voltage error = {(Vp KT.Vs)/Vp} X 100 %
Phase angle error in potential transformer:
The angle between the primary system voltage Vp and the reversed secondary voltage
vectors KT.Vs is the phase error
Cause of error in Potential Transformer:
The voltage applied to the primary of the potential transformer first drops due to internal
impedance of primary. Then it appears across the primary winding and then transformed
proportionally to its turns ratio, to secondary winding. This transformed voltage acrosssecondary winding will again drops due to internal impedance of secondary, before
appearing across burden terminals. This is the reason of errors in potential transformer.
-
7/30/2019 vocational training wbsetcl
41/55
41
INTRODUCTION OF INSULATING OIL
Insulating oil in an electrical power transformer is commonly known as Transformer Oil. It is
normally obtained by fractional distillation and subsequent treatment of crude petroleum.
That is why this oil is also known as Mineral Insulating Oil. Transformer Oil serves mainly
tow purposes one it is liquid insulation in electrical power transformer and two it dissipates
heat of the transformer e.i. acts as coolant. In addition to these, this oil serves other two
purposes, it helps to preserve the core and winding as these are fully immersed inside oil
and another important purpose of this oil is, it prevents direct contact of atmospheric
oxygen with cellulose made paper insulation of windings, which is susceptible to oxidation.
Types of Transformer Oil:
Generally there are two types of Transformer Oil used in transformer,
1. Paraffin based Transformer Oil
2. Naphtha based Transformer Oil
Naphtha oil is more easily oxidized than Paraffin oil. But oxidation product i.e. sludge in the
naphtha oil is more soluble than Paraffin oil. Thus sludge of naphtha based oil is not
precipitated in bottom of the transformer. Hence it does not obstruct convection
circulation of the oil, means it does not disturb the transformer cooling system. But in the
case of Paraffin oil although oxidation rate is lower than that of Naphtha oil but the
oxidation product or sludge is insoluble and precipitated at bottom of the tank and obstruct
the transformer cooling system. Although Paraffin based oil has above mentioned
disadvantage but still in our country it is generally used because of its easy availability.
Another problem with paraffin based oil is its high pour point due to the wax content, but
this does not effect its use due to warm climate condition of India .
Properties of Transformer Insulating Oil:
Some specific parameters of insulating oil should be considered to determine the
serviceability of that oil.
Parameters of Transformer Oil:
The parameters of Transformer Oil are categorized as,
1. Electrical Parameters Dielectric Strength, Specific Resistance, Dielectric Dissipation
Factor.
2. Chemical Parameter - Water Content, Acidity, Sludge Content.
3. Physical Parameters - Inter Facial Tension, Viscosity, Flash Point, Pour Point.
-
7/30/2019 vocational training wbsetcl
42/55
42
Dielectric Strength of Transformer Oil:
Dielectric Strength of Transformer Oil is also knlown as Breakdown Voltage of transformer
oil orBDV of transformer oil. Break down voltage is measured by observing at what voltage,
sparking strants between two electrods immerged in the oil, separated by specific gap. low
value of BDV indicates presence of moisture content and conducting substances in the oil.For measuring BDV of transformer oil, portable BDV
measuring kit is generally available at site. In this kit, oil is
kept in a pot in which one pair of electrodes are fixed
with a gap of 2.5 mm (in some kit it 4mm) between them.
Now slowly rising voltage is applied between the
electrodes. Rate of rise of voltage is generally controlled
at 2KV/s and observe the voltage at which sparking starts
between the electrodes. That means at which voltage
Dielectric Strength of transformer oil between theelectrodes has been broken down. Generally this
measurement is taken 3 to 6 times in same sample of oil and the average value of these
reading is taken. BDV is important and popular test of transformer oil, as it is primary
indication of health of oil and it can be easily carried out at site.
Dry and clean oil gives BDV results, better than the oil with moisture content and other
conducting impurities. Minimum Breakdown Voltage of transformer oil or Dielectric
Strength of transformer oil at which this oil can safely be used in transformer, is considered
as 30 KV.
Specific Resistance of Transformer Oil:
This is another important property of transformer oil. This is measure of DC resistance
between two opposite sides of one cm3
block of oil. Its unit is taken as ohm-cm at specific
temperature. With increase in temperature the resistivity of oil decreases rapidly. Just after
charging a transformer after long shut down, the temperature of the oil will be at ambient
temperature and during full load the temperature will be very high and may go upto 90oC at
over load condition. So resistivity of the insulating oil must be high at room temperature
and also it should have good value at high temperature as well. That is why specific
resistance or resistivity of transformer oil should be measured at 27o
C as well as 90o
C.
Minimum standard Specific Resistance of Transformer oil at 90oC is 35X 10
12ohm cm and
at 27oC it is 1500X10
12ohm cm.
Dielectric Dissipation Factor of Transformer oil:
Dielectric Dissipation Factor is also known as loss factor or tan delta of transformer oil.
When a insulating materials is placed between live part and grounded part of an electrical
equipment, leakage current will flow. As insulating material is dielectric in nature the
current through the insulation ideally leads the voltage by 90 o. Here voltage means the
instantaneous voltage between live part and ground of the equipment. But in reality no
insulating materials are perfect dielectric in nature. Hence current through the insulator will
lead the voltage with an angle little bit shorter than 90o. Tangent of the angle by which it is
short of 90o
is called Dielectric Dissipation Factor or simply tan delta of transformer oil.
-
7/30/2019 vocational training wbsetcl
43/55
43
More clearly, the leakage current through an insulation does have two component one is
capacitive or reactive and other one is resistive or active. Again it is clear from above
diagram, value of which is also known as loss angle, is smaller, means resistive
component of the current IR is smaller which indicates high resistive property of the
insulating material. High resistive insulation is good insulator. Hence it is desirable to have
loss angle as small as possible. So we should try to keep the value of tan as small aspossible. High value of this tan is an indication of presence of contaminants in transformer
oil. Hence there is a clear relationship between tan and resistivity of insulating oil. If
resistivity of the insulating oil is decreased, the value of tandelta increases and vice versa.
So both resistivity test and tan delta test of transformer oil are not normally required for
same piece of insulator or insulating oil.
In one sentence it can be said that, tan is measure of imperfection of dielectric nature of
insulation materials like oil.
Water Content in Transformer Oil:
Moisture or Water Content in Transformer Oil is highly undesirable as it affects adversely
the dielectric properties of oil. The water content in oil also affects the paper insulation of
the core and winding of transformer. Paper is highly hygroscopic in nature. Paper absorbs
maximum amount of water from oil which affects paper insulation property as well as
reduced its life. But in loaded transformer, oil becomes hotter, hence the solubility of water
in oil increases as a result the paper releases water and increase the water content in
transformer oil. Thus the temperature of the oil at the time of taking sample for test is very
important. During oxidation acid are formed in the oil the acids give rise the solubility of
water in the oil. Acid coupled with water further decompose the oil forming more acid and
water. This rate of degradation of oil increases. The water content in oil is measured as
pm(parts per million unit).
Water content in oil is allowed up to 50 ppm as recommended by IS 335(1993). The
accurate measurement of water content at such low levels requires very sophisticated
instrument like Coulometric Karl Fisher Titrator.
Acidity of Transformer Oil:
Acidity of transformer oil, is harmful property. If oil becomes acidic, water content in the oilbecomes more soluble to the the oil. Acidity of oil detoriates the insulation property of
paper insulation of winding. Acidity accelerates thee oxidation process in the oil. Acid also
includes rusting of iron in presence of moisture. The acidity of transformer oil is measure of
its acidic constituents of contaminants. Acidity of oil is express in mg of KOH required to
neutralize the acid present in a gram of oil. This is also known as neutralization number.
Inter Facial Tension of Transformer Oil:
Inter Facial Tension between the water and oil interface is the way to measure molecular
attractive force between water and oil. It is measured in Dynes/cm or miliNeuton/meter.
Inter facial Tension is exactly useful for determining the presence of polar contaminants
and oil decay products. Good new oil generally exhibits high inter facial tension. Oil
oxidation contaminants lower the IFT.
-
7/30/2019 vocational training wbsetcl
44/55
44
Flash Point of Transformer Oil:
Flash point of transformer oil is the temperature at which oil gives enough vapors to
produce a flammable mixture with air. This mixture gives momentary flash on application of
flame under standard condition. Flash point is important because it specifies the chances of
fire hazard in the transformer. So it is desirable to have very high flash point of transformeroil. In general it is more than 140
o(>10
o).
Pour Point of Transformer Oil:
It is the minimum temperature at which oil just start to flow under standard test condition.
Pour Point of Transformer Oil is an important property mainly at the places where climate is
extremely cold. If the oil temperature falls bellow the pour point, transformer oil stops
convection flowing and obstruct cooling in transformer. Paraffin based oil has higher value
of pour point, compared to Naphtha based oil, but in India like country, it does not effectthe use of Paraffin oil due tits warm climate condition. Pour Point of transformer oil mainly
depends upon wax content in the oil. As Paraffin based oil has more wax content, it has
higher pour point.
Viscosity of Transformer Oil:
In few wards, Viscosity of Transformer Oil can be said that Viscosity is the resistance of
flow, at normal condition. Obviously resistance to flow of transformer oil means
obstruction of convection circulation of oil inside the transformer. A good oil should have
low viscosity so that it offers less resistance to the convectional flow of oil thereby notaffecting the cooling of transformer. Low viscosity of transformer oil is essential, but it is
equally important that, the viscosity of oil should increase as less as possible with decrease
in temperature. Every liquid becomes more viscous if temperature decreases.
-
7/30/2019 vocational training wbsetcl
45/55
45
BUCHHOLZ RELAY
Construction of Buchholz Relay:
Buchholz Relay in transformer is an oil container housed the connecting pipe from main
tank to conservator tank. It has mainly two elements. The upper element consists of a float.
The float is attached to a hinge in such a way that it can move up and down depending
upon the oil level in the Buchholz Relay Container. One mercury switch is fixed on the float.
The alignment of mercury switch hence depends upon the position of the float.
The lower element consists of a baffle plate and mercury switch. This plate is fitted on a
hinge just in front of the inlet (main tank side) of Buchholz Relay in transformer in such a
way that when oil enters in the relay from that inlet in high pressure the alignment of the
baffle plate along with the mercury switch attached to it, will change. In addition to these
main elements a Buchholz Relay has gas release pockets on top. The electrical leads from
both mercury switches are taken out through a molded terminal block.
Buchholz Relay principle:
The Buchholz Relay working principle of is very simple. Buchholz Relay function is based on
very simple mechanical phenomenon. It is mechanically actuated. Whenever there will be a
minor internal fault in the transformer such as an insulation faults between turns, break
down of core of transformer, core heating, the transformer insulating oil will bedecomposed in different hydrocarbon gases, CO2 and CO. The gases produced due to
decomposition of transformer insulating oil will accumulate in the upper part the Buchholz
Container which causes fall of oil level in it. Fall of oil level means lowering the position of
float and thereby