test report based on din en iso/iec 17025:2005 · 2018-02-04 · document-no: p4945b-18-e test...

37
Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link, Copper, Class E according ISO/IEC 11801-1 Ed.1.0 2017-11 Project-no: OPTDA0117 This Test Report with the measurements consists of 37 pages. GHMT AG and the customer shall grant each other an unlimited right to copy and disclose this report insofar as the measuring results and specifications published are neither altered by way of including or removing information nor changed in a way that does not correspond to the original meaning of the report.

Upload: others

Post on 02-Feb-2020

6 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

Document-no: P4945b-18-E

Test Report based on DIN EN ISO/IEC 17025:2005

GHMT Type Approval

2 Connector Permanent Link, Copper, Class E

according ISO/IEC 11801-1 Ed.1.0 2017-11

Project-no: OPTDA0117

This Test Report with the measurements consists of 37 pages.

GHMT AG and the customer shall grant each other an unlimited right to copy and disclose this report insofar as the measuring results and specifications published are neither altered by way of including or removing information nor changed in a way that does not correspond to the original meaning of the report.

Page 2: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 2 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

Table of Contents Table of Contents ................................................................................................. 2

Revision history ................................................................................................... 4

1 General statements ................................................................................ 5

1.1 Test Laboratory ........................................................................................... 5

1.2 Test Date ................................................................................................... 5

1.3 Environmental conditions during testing .......................................................... 5

1.4 Test Conducted by ........................................................................................ 5

1.5 Persons Present at Test ................................................................................. 5

2 Customer............................................................................................. 6

2.1 Address ..................................................................................................... 6

2.2 Responsible contact person ........................................................................... 6

3 Device under test (DUT) ........................................................................... 7

3.1 Description of the Components ....................................................................... 7

3.2 Provision ................................................................................................... 9

3.3 Definition of the Device Under Test (DUT) .......................................................... 10

4 Test Type ............................................................................................ 11

4.1 Reference of testing .................................................................................... 11

4.2 Definition of the testing parameters ............................................................... 12

4.2.1 Insertion loss ............................................................................................. 12

4.2.2 NEXT ........................................................................................................ 13

4.2.3 Power sum NEXT (PS NEXT) ............................................................................. 14

4.2.4 Attenuation to crosstalk ratio at the near-end (ACR-N) ....................................... 15

4.2.5 Power sum ACR-N (PS ACR-N) ......................................................................... 15

4.2.6 Attenuation to crosstalk ratio at the far-end (ACR-F) .......................................... 16

4.2.7 Power sum ACR-F (PS ACR-F) .......................................................................... 17

4.2.8 Return loss ................................................................................................ 18

4.2.9 Propagation delay ...................................................................................... 19

4.2.10 Delay skew ................................................................................................ 20

4.2.11 Coupling attenuation .................................................................................. 21

5 Applied Standards ................................................................................ 22

5.1 Applied Rules and Regulations ...................................................................... 22

5.2 Applied Limits ............................................................................................ 22

5.3 Deviations ................................................................................................ 22

5.4 None Standardised Test Procedures ................................................................. 22

6 Testing equipment ............................................................................... 23

7 Summary............................................................................................ 24

Page 3: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 3 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

8 ANNEX: Documentation of measurements .................................................... 25

8.1 SETUP ....................................................................................................... 26

8.2 Measurement results of the NF-parameters ...................................................... 27

8.3 Measurement results of the HF-parameters ...................................................... 28

8.4 Measurement results of the EMC-parameters .................................................... 37

Page 4: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 4 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

Revision history

Document number Date Content/ Changes

P4945a-18-E 23.01.2018 initial version

P4945b-18-E 01.02.2018 Change customer data chapter 2

Page 5: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 5 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

1 General statements

1.1 Test Laboratory

GHMT AG

In der Kolling 13

66450 Bexbach, Germany

Phone: +49 / 68 26 / 92 28 – 0

Fax: +49 / 68 26 / 92 28 – 290

E–Mail: [email protected]

Internet: www.ghmt.de

1.2 Test Date

Receipt of goods: 02. January 2018

Test number: 18-CS025

Testing from: 18. January 2018

until: 19. January 2018

during: (23 ± 3)°C

1.3 Environmental conditions during testing

Ambient temperature (23 ± 3)°C

Relative humidity (50 ± 25)%

1.4 Test Conducted by

Mr. Roman Schwoll, GHMT AG

1.5 Persons Present at Test

Mr. Stefan Grüner, GHMT AG (present temporarily)

Page 6: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 6 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

2 Customer

2.1 Address

OPTRONICS PLUS LIMITED

Grand Millennium Plaza, 1501 181 Queens Road Central

HONG KONG

Phone: +852 5808 2426

Internet: www.optronicsplus.net

2.2 Responsible contact person

OPTRONICS PLUS LIMITED

Ms. Khushbu Solanki

Application Engineer

42-44 Griva Digeni Avenue, Office 402 Nicosia 1091

25665 Nicosia 1311, Cyprus

Phone: +357 22 050 910

Fax: +357 22 050 901

E-Mail: [email protected]

Internet: www.optronicsplus.net

Page 7: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 7 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

3 Device under test (DUT)

3.1 Description of the Components

The following sample(s) was/were part of the test:

Data cable: CAT6 U/UTP 23 AWG Cable

Part-no: OCC-6-1X-XXX (first "X" = 1-LSZH, 2-PVC, 3-PE)

Charge-no: -

The cable was marked with an imprinted meter counter.

Cable end A: 206m Cable end B: 296m

Cable length: 90m (determined on imprinted length counter)

Picture:

Connector: CAT6 UTP Keystone Jack

Part-no: OKJ-6-1-X

Charge-no: -

Picture:

Page 8: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 8 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

Patch panel: CAT6 UTP 1U 24 Port Patch Panel

Part-no: OPPC-6-1-24

Charge-no: -

Picture:

Condition of

the sample(s):

The sample(s) had no visible damages

Page 9: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 9 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

3.2 Provision

The DUT was / the specimens were...

… with drawn on site. The selection of the sample was neutral and unaffected by the client.

... obtained by GHMT through resellers. The selection of the sample was neutral and unaffected by the client.

... obtained by GHMT through the client.

Page 10: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 10 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

3.3 Definition of the Device Under Test (DUT)

According to the specifications laid down in the document ISO/IEC 11801-1 Ed. 1.0, a Permanent Link was assembled in order to conduct the test:

End A

Patch panel: CAT6 UTP 1U 24 Port Patch Panel

Data Cable: 90m

CAT6 U/UTP 23 AWG Cable

Connector:

RJ45

CAT6 UTP Keystone Jack

End B

Figure 1: 2-Connector Permanent Link

Page 11: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 11 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

4 Test Type

4.1 Reference of testing

Testing of transmission parameters of a 2 Connector Permanent Link according to the specifications Class E in accordance with ISO/IEC 11801-1 Ed. 1.0. 2017-11

The following parameters are part of this test:

NF-parameters:

Direct current (d.c.) loop resistance

Direct current (d.c.) loop resistance unbalance

HF-parameters:

Insertion loss

NEXT

Power sum NEXT (PS NEXT)

Attenuation to crosstalk ratio at the near-end (ACR-N)

Power sum ACR-N (PS ACR-N)

Attenuation to crosstalk ratio at the far-end (ACR-F)

Power sum ACR-F (PS ACR-F)

Return loss

Propagation delay

Delay skew

EMC-parameters:

Coupling attenuation

Page 12: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 12 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

4.2 Definition of the testing parameters

4.2.1 Insertion loss

SMZ

SMZ

Baluns

Transmitter

Receiver

A B

Core pair

Definition The attenuation is determined by the ratio of the power supplied to the port A and the measured power at the port B as specified below:

B

AV

P

P log 10 = [dB] a

Both the input and the output of the two-port network must be terminated with the nominal impedance.

Influencing variables In case of cables, the attenuation is primarily determined by the cross-sectional area and the conductivity of the copper wires. Especially in high frequency ranges, the attenuation is increased by the dielectric losses of the core insulating material.

The attenuation is dependent on the length, the frequency, and the temperature.

Significance A low attenuation improves the transmission reliability of the cabling system. The attenuations of cables and connecting devices are accumulative although they are largely dominated by those of the cables.

Page 13: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 13 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

4.2.2 NEXT

SMZ

SMZ

Baluns

Transmitter

Receiver

Core pair 1

Core pair 2

A

B

Zo

Zo

Definition The near-end crosstalk attenuation is determined by the ratio of the power supplied to the port A and the measured power at the port B as specified below:

B

ANEXT

P

P log 10 = [dB] a

Both sides of the specimen must be terminated with the nominal impedance. In the event that the sender and the receiver are located at the same end of the specimen, we are speaking of near-end crosstalk (NEXT) attenuation.

Influencing variables In case of cables, the near-end crosstalk attenuation is primarily determined by the twisting of the cores and (if existing) the paired foil screens.

The near-end crosstalk attenuation is largely dependent on the frequency and – to a minor degree – also on the lengths.

Significance A high near-end crosstalk attenuation improves the reliability of transmissions. Within the cabling system, the reliability of transmissions is primarily determined by the component having the lowest near-end crosstalk attenuation.

Page 14: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 14 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

4.2.3 Power sum NEXT (PS NEXT)

Transmitter

Power Splitter

SUA-71 50 / 100 Ohm

SUA-71 50 / 100 Ohm

SUA-71 50 / 100 Ohm

100

100

100

100 SUA-71 50 / 100 Ohm

Receiver

Definition The power sum of the near-end cross-talk is defined on the basis of the ratio of the power input at the three pairs A, B and C to the power output at pair D. The power-sum NEXT value of cables can be measured by means of a phase-correlated 4-port power splitter. On the basis of the pair-to-pair NEXT measurements, the power sum can also be calculated according to the following formula:

3

1i

0,1-

10 log 10 = [dB] aiNEXTa

PSNEXT

Influencing factors The power-sum NEXT value of cables is decisively influenced by the stranding and the foil pair shield (if applicable). Power-sum NEXT strongly depends on the frequency used and – only to a minor extent – on the cabling length.

Meaning With regard to network protocols that distribute the bi-directional data load over all four pairs, power-sum NEXT is of great importance for transmission reliability since power-sum cross-talk is expected to impair transmission via the data channel.

Page 15: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 15 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

4.2.4 Attenuation to crosstalk ratio at the near-end (ACR-N)

Definition The ratio of the level of the incoming useful signal to the noise level at the opposite end of the measured link is referred to as Attenuation-to-Cross-Talk Ratio (abbr. ACR).

ACR may be interpreted as the signal-to-noise ratio with the near-end cross-talk being regarded as the interfering signal or noise.

[dB] a - [dB] a = [dB] ACR VN

Calculation As agreed, the ACR value is calculated for every frequency response of the near-end cross-talk with the two relevant frequency responses of the attenuation.

Alternatively, the minimum value of the ACR calculation may be allocated for every measuring point of the two attenuation values involved. The determination of the double-ended system dynamics thus results in 12 ACR frequency responses for a four-pair specimen.

Meaning The ACR value is of decisive importance to system designers, system manufacturers and operators of data communications equipment since it provides immediate insight into system dynamics and system reserve. The larger the distance between the useful signal and the noise signal over the entire frequency range, the larger the infrastructural reserve.

4.2.5 Power sum ACR-N (PS ACR-N)

Definition The power sum of the ACR reserve is calculated as follows:

PS ACR [dB] = aPSNEXT [dB] – aV [dB]

Meaning With regard to network protocols that distribute the bi-directional data load over all four pairs, power-sum ACR is of great importance for transmission reliability since cross-talk is expected to impair transmission via the data channel.

Page 16: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 16 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

4.2.6 Attenuation to crosstalk ratio at the far-end (ACR-F)

Definition The equal-level far-end cross-talk (abbr. EL FEXT) is determined by the ratio of the power measured at the remote port B to the power measured at the remote port C. The measuring signal is supplied to the near end of the cable.

C

BELFEXT

P

P log 10 = [dB] a

All pairs of the EUT are terminated with their characteristic impedance.

Influencing factors The EL FEXT value of cables is decisively influenced by the stranding and the foil pair shield (if applicable).

EL FEXT strongly depends on the frequency used.

Page 17: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 17 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

4.2.7 Power sum ACR-F (PS ACR-F)

Definition The power-sum EL FEXT value can be calculated on the basis of the pair-to-pair EL FEXT measurements according to the following formula:

3

1i

0,1-

10 log 10 = [dB] aiELFEXTa

PSELFEXT

Meaning With regard to network protocols that distribute the bi-directional data load over all four pairs, power-sum EL FEXT is of great importance for transmission reliability since cross-talk is expected to impair transmission via the data channel.

Page 18: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 18 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

4.2.8 Return loss

SMZ

Balun

Receiver

Transmitter

Pair of Cores Return loss measuring bridge

R = Z

Differential-mode termination

Definition The return loss represents the ratio of the power supplied to the EUT to the power reflected by the EUT.

output

input

RP

P log 10 = [dB] a

The EUT end is terminated with the characteristic impedance in order to absorb any non-reflected power. The EUT and the test-value transmitter must have the same rated impedance in the broadband range.

Influencing factors The return loss value of cables is decisively influenced by the homogeneity of the conductors and the core of the cable. Mechanical load during the manufacturing or installation of the cables may impair the return loss.

The parameters return loss and characteristic impedance correlate.

Meaning A high degree of return loss improves the transmission reliability. A low degree of return loss may lead to an unwanted overlap of returning signal components.

Page 19: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 19 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

4.2.9 Propagation delay

SMZ

SMZ

Baluns

Transmitter

Receiver

A B

Pair of Cores

Definition The velocity of propagation v of cables is stated in relation to the maximum velocity of propagation of electromagnetic waves in the vacuum co. The parameter "Nominal Velocity of Propagation" (abbr. NVP) is defined as follows:

NVPv

oc

The delay is the period of time the signal requires in order to travel through a cabling link with a length of l. The delay is calculated on the basis of the NVP value (Nominal Velocity of Propagation) of the cable and the velocity of light c0 according to the following formula:

cNVP

l

0

Influencing factors The delay of cables is decisively influenced by the dielectric loss of the core insulation material. This material-induced loss may be minimised by selecting various compounds and by varying the degree of foaming.

The impact of colour addition on the NVP value is not to be neglected since the colours vary strongly in their dielectric constants, which are considerably higher than in the basic compound.

Page 20: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 20 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

Influencing factors

(continued) The velocity of propagation does not depend on the cable length and may be calculated on the basis of the measurement of the length-dependent group delay. The reference length used for calculation is the cable length and not the lay length of the twisted pairs. Different lay length values in the four pairs lead to different NVP values.

Meaning In order to ensure distortion-free signal transmission, the velocity of propagation must not fall below a lower limiting value, which is determined by the system requirements. The velocity of propagation has to be virtually independent of the frequency within the signal bandwidth in order to avoid a divergence of the spectral signal components.

High-bit rate network protocols that use parallel data transmission via the four pairs, moreover, require a highly consistent velocity of propagation in order to avoid synchronisation errors. Future normative standards will define this so-called "delay skew".

4.2.10 Delay skew

Definition The delay skew of cables with a length of l marks the time difference between signals travelling along the individual transmission links at the propagation velocity vi,j.

= li j

i j

v v

v v

Influencing factors The delay skew of cables is decisively influenced by the dielectric loss of the core insulation material and the various lay length values.

Meaning The delay skew will be an important parameter for a distortion-free data transmission in balanced cables in view of future network protocols.

Page 21: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 21 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

4.2.11 Coupling attenuation

Definition Coupling Attenuation is the relation between the transmitted power through the conductor and the maximum radiated peak power, conducted and generated by the excited common mode currents. The measurement is independent of the bandwith and shall be measured form 30MHz up to 1GHz.

Influencing factors The Coupling Attenuation is primarily determined by the mechanical structure of the component. The Coupling Attenuation is very much dependent on the frequency.

Meaning The better the effectiveness of the Coupling Attenuation is, the smaller is the value of the noiseresistance.

Page 22: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 22 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

5 Applied Standards

5.1 Applied Rules and Regulations

ISO/IEC 11801-1 Ed. 1.0: 2017-11

Information technology – Generic cabling for customer premises

5.2 Applied Limits

ISO/IEC 11801-1 Ed. 1.0: 2017-11

Information technology – Generic cabling for customer premises

Note: In Chapter 8 "ANNEX: Documentation of measurements", the applied limits are diagrammed within the measurement results.

5.3 Deviations

None.

5.4 None Standardised Test Procedures

None.

Page 23: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 23 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

6 Testing equipment

The following testing equipment was used for the measurements:

Equipment Manufacturer Stock ID

Network Analyzer I Rohde & Schwarz GHMTA0002

Network Analyzer II Agilent GHMTA0018

LCR-Meter Agilent GHMTA0034

Time-Domain-Reflectometer Tektronix GHMTA0004

Reference clamp GHMT GHMTA0047

Absorbing Clamp Lüthi GHMTA0070

Decoupling Clamp Lüthi GHMTA0071

Switch unit Novotronic GHMTA0028

Coaxial probe GHMT -

Schedule 1: Measurement equipment

Page 24: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 24 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

7 Summary

Customer: OPTRONICS PLUS LIMITED

181 Queens Road Central

HONG KONG

Description: Data Cable:

CAT6 U/UTP 23 AWG Cable

Part-no: OCC-6-1X-XXX (first "X" = 1-LSZH, 2-PVC, 3-PE)

Connector:

CAT6 UTP Keystone Jack

Part-no: OKJ-6-1-X

Patch panel:

CAT6 UTP 1U 24 Port Patch Panel

Part-no: OPPC-6-1-24

Applied standards: ISO/IEC 11801-1 Ed. 1.0: 2017-11

Information technology – Generic cabling for customer premises

Result: The sample meets the limits of the applied standards and regulations with respect to the parameters indicated above.

The test results which were determined in the course of the measurement refer to the submitted specimen.

Bexbach, 01. February 2018

GHMT AG

In der Kolling 13

D-66450 Bexbach

[email protected]

www.ghmt.de

i.O. Stefan Grüner, engineer

(Head of Accrediteded Test Laboratory)

Page 25: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 25 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

8 ANNEX: Documentation of measurements

As follows the measurement results of the tested parameters defined in chapter 4.1.

18-CS025

Insertion Loss 0,32 PASS

NEXT A 4,37 PASS

NEXT B 5,04 PASS

PS NEXT A 4,57 PASS

PS-NEXT B 5,22 PASS

ACR-N A 8,55 PASS

ACR-N B 8,6 PASS

PS ACR-N A 9,45 PASS

PS ACR-N B 9,89 PASS

RL A 6,92 PASS

RL B 6,83 PASS

ACR-F A 10,28 PASS

ACR-F B 12,61 PASS

PS ACR-F A 11,79 PASS

PS ACR-F B 12,61 PASS

Delay 30,88 PASS

Delay Skew 17,61 PASS

Reserve

Page 26: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 26 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

8.1 SETUP

HF parameters EMC parameters

S11 S21

Coupling attenuation

Output Power 0 dBm 0 dBm 7 dBm

Frequency Range 1-300 MHz 1-300 MHz 30-1000 MHz

IF Filter 100 Hz 100 Hz 30 Hz

NOP 1601 1601 971

AVG - - -

Smoothing 0,3% 0,3% 0,3%

Page 27: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 27 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

8.2 Measurement results of the NF-parameters

18-CS025

Limit: 17,90 Ω

Pair 12 14,00 Ω

Pair 36 14,32 Ω

Pair 45 14,01 Ω

Pair 78 13,99 Ω

Limit: 0,54 Ω

Pair 12-36 0,32 Ω

Pair 12-45 0,01 Ω

Pair 12-78 0,00 Ω

Pair 36-45 0,31 Ω

Pair 36-78 0,32 Ω

Pair 45-78 0,01 Ω

DC Δ loop resistance

DC loop resistance

Page 28: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 28 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

8.3 Measurement results of the HF-parameters

Insertion loss

-60

-50

-40

-30

-20

-10

0

1 10 100 1000

Att

en

uati

on

[dB]

Frequency [MHz]

Pair 12

Pair 36

Pair 45

Pair 78

Limit ISO/IEC 11801-1 Ed. 1.0 Class E

Page 29: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 29 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

NEXT (End A)

NEXT (End B)

-120

-100

-80

-60

-40

-20

0

1 10 100 1000

NEX

T En

d A

[dB]

Frequency [MHz]

Pairs 12-36

Pairs 12-45

Pairs 12-78

Pairs 36-45

Pairs 36-78

Pairs 45-78

Limit ISO/IEC 11801-1 Ed. 1.0 Class E

-120

-100

-80

-60

-40

-20

0

1 10 100 1000

NEXT

En

d B

[dB]

Frequency [MHz]

Pairs 12-36

Pairs 12-45

Pairs 12-78

Pairs 36-45

Pairs 36-78

Pairs 45-78

Limit ISO/IEC 11801-1 Ed. 1.0 Class E

Page 30: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 30 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

PS NEXT (End A)

PS NEXT (End B)

-120

-100

-80

-60

-40

-20

0

1 10 100 1000

PS

NEX

T En

d A

[dB]

Frequency [MHz]

Pair 12

Pair 36

Pair 45

Pair 78

Limit ISO/IEC 11801-1 Ed. 1.0 Class E

-120

-100

-80

-60

-40

-20

0

1 10 100 1000

PS

NEX

T En

d B

[dB]

Frequency [MHz]

Pair 12

Pair 36

Pair 45

Pair 78

Limit ISO/IEC 11801-1 Ed. 1.0 Class E

Page 31: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 31 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

ACR-N (End A)

ACR-N (End B)

-120

-100

-80

-60

-40

-20

0

20

40

1 10 100 1000

ACR

En

d A

[dB]

Frequency [MHz]

Pairs 12-36

Pairs 12-45

Pairs 12-78

Pairs 36-45

Pairs 36-78

Pairs 45-78

Limit ISO/IEC 11801-1 Ed. 1.0 Class E

-120

-100

-80

-60

-40

-20

0

20

40

1 10 100 1000

ACR

En

d B

[dB]

Frequency [MHz]

Pairs 12-36

Pairs 12-45

Pairs 12-78

Pairs 36-45

Pairs 36-78

Pairs 45-78

Limit ISO/IEC 11801-1 Ed. 1.0 Class E

Page 32: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 32 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

PS ACR-N (End A)

PS ACR-N (End B)

-120

-100

-80

-60

-40

-20

0

20

40

1 10 100 1000

PS

ACR

-N

En

d A

[dB]

Frequency [MHz]

Pair 12

Pair 36

Pair 45

Pair 78

Limit ISO/IEC 11801-1 Ed. 1.0 Class E

-120

-100

-80

-60

-40

-20

0

20

40

1 10 100 1000

PS

ACR

-N

En

d B

[dB]

Frequency [MHz]

Pair 12

Pair 36

Pair 45

Pair 78

Limit ISO/IEC 11801-1 Ed. 1.0 Class E

Page 33: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 33 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

ACR-F (End A)

ACR-F (End B)

-120

-100

-80

-60

-40

-20

0

1 10 100 1000

ACR

-F

End A

[dB]

Frequency [MHz]

Pairs 12-36

Pairs 12-45

Pairs 12-78

Pairs 36-45

Pairs 36-78

Pairs 45-78

Limit ISO/IEC 11801-1 Ed. 1.0 Class E

-120

-100

-80

-60

-40

-20

0

1 10 100 1000

ACR

-F

End B

[dB]

Frequency [MHz]

Pairs 12-36

Pairs 12-45

Pairs 12-78

Pairs 36-45

Pairs 36-78

Pairs 45-78

Limit ISO/IEC 11801-1 Ed. 1.0 Class E

Page 34: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 34 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

PS ACR-F (End A)

PS ACR-F (End B)

-120

-100

-80

-60

-40

-20

0

1 10 100 1000

PS

ACR

-F

End A

[dB]

Frequency [MHz]

Pair 12

Pair 36

Pair 45

Pair 78

Limit ISO/IEC 11801-1 Ed. 1.0 Class E

-120

-100

-80

-60

-40

-20

0

1 10 100 1000

PS

ACR

-F

End B

[dB]

Frequency [MHz]

Pair 12

Pair 36

Pair 45

Pair 78

Limit ISO/IEC 11801-1 Ed. 1.0 Class E

Page 35: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 35 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

Return loss (End A)

Return loss (End B)

-60

-50

-40

-30

-20

-10

0

1 10 100 1000

Retu

rn L

oss

En

d A

[dB]

Frequency [MHz]

Pair 12

Pair 36

Pair 45

Pair 78

Limit ISO/IEC 11801-1 Ed. 1.0 Class ELimit (information only)

-60

-50

-40

-30

-20

-10

0

1 10 100 1000

Retu

rn L

oss

En

d B

[dB]

Frequency [MHz]

Pair 12

Pair 36

Pair 45

Pair 78

Limit ISO/IEC 11801-1 Ed. 1.0 Class ELimit (information only)

Page 36: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 36 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

Propagation delay

Delay skew

0

100

200

300

400

500

600

700

800

0 50 100 150 200 250 300

Dela

y [n

s]

Frequency [MHz]

Pair 12

Pair 36

Pair 45

Pair 78

Limit ISO/IEC 11801-1 Ed. 1.0 Class E

0

0

1

10

100

1000

0 100 200 300

Dela

y S

kew

[n

s]

Frequency [MHz]

Pairs 12-36

Pairs 12-45

Pairs 12-78

Pairs 36-45

Pairs 36-78

Pairs 45-78

Limit ISO/IEC 11801-1 Ed. 1.0 Class E

Page 37: Test Report based on DIN EN ISO/IEC 17025:2005 · 2018-02-04 · Document-no: P4945b-18-E Test Report based on DIN EN ISO/IEC 17025:2005 GHMT Type Approval 2 Connector Permanent Link,

GHMT Type Approval Project-no: OPTDA0117

2 Connector Permanent Link, Copper, Class E ISO/IEC 11801-1 Ed.1.0 Document-no: P4945b-18-E

GHMT AG Bexbach/Germany page 37 of 37 Test laboratory accredited by DAkkS in accordance with DIN EN ISO/IEC 17025:2005. The accreditation is valid for the test methods listed in certificate (D-PL-17559-01-00). Certificate of qualification to perform system- and product-related quality assurance according to the KTA 1401 safety standard of the Nuclear Safety Standards Commission (KTA).

© GHMT AG. Please observe note on industrial property rights pursuant to DIN ISO 16016

8.4 Measurement results of the EMC-parameters

Coupling attenuation

0

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

0 100 200 300 400 500 600 700 800 900 1000

Cou

pli

ng

Att

en

uati

on

[d

B]

Frequency [MHz]

Coupling attenuation(All In One)

Pair 12 Near End

Pair 12 Far End

Pair 36 Near End

Pair 36 Far End

Pair 45 Near End

Pair 45 Far End

Pair 78 Near End

Pair 78 Far End

Evaluation Envelope (CA= 42,07 dB)

Limit ISO/IEC 11801-1 Ed. 1.0

18-CS025