RELAI DIFERENSIAL (DIFERENTIAL RELAY). 1. RELAI DIFERENSIAL BIAS [ PERSENTASE ]. RELAI DIFERENSIAL ADALAH SUATU RELAI YANG BEKERJA MEMBANDINGKAN DUA BUAH VEKTOR ARUS ATAU LEBIH . ARUS BEDA ( KETIDAK SEIMBANGAN ARUS ) YANG DIPEROLEH DARI - PowerPoint PPT Presentation

TRANSCRIPT

  • RELAI DIFERENSIAL

    ADALAH SUATU RELAI YANG BEKERJAMEMBANDINGKAN DUA BUAH VEKTORARUS ATAU LEBIH .ARUS BEDA ( KETIDAK SEIMBANGAN ARUS ) YANG DIPEROLEH DARI MEMBANDINGKAN DARI DUA BUAH VEKTOR ARUS ATAU LEBIH AKAN MENGERJAKAN KUMPARAN OPERATING RELAI .

  • RELAI DIFERENSIAL BIAS

    SEBAGAI PENGAMAN UTAMA :

    # GENERATOR# TRANSFORMATOR DAYA# BUSBAR# MOTOR LISTRIK KAPASITAS BESARFUNGSI RELAI DIFERENSIAL

  • RELAI DIFERENSIAL BIAS

    # SANGAT SELEKTIP DAN CEPAT# SEBAGAI PENGAMAN UTAMA# TIDAK DAPAT DIGUNAKAN SEBAGAI PENGAMAN CADANGAN# DAERAH PENGAMANANNYA DIBATASI OLEH CT1 DAN CT2SIFAT RELAI DIFERENSIAL

  • RELAI DIFERENSIAL BIASKONSEP DASAR RELAI DIFERENSIALDIFERENSIAL SEDERHANA ( UNBIAS )@ RELAI DIFERENSIAL MEMBANDINGKAN ARUS DALAM BELITAN TRAFO ( I1 & I2 )

    @ CT1 & CT2 RASIO NYA SEDEMIKIAN SEHINGGA ARUS SEKUNDERNYAR KAWASAN PENGAMANANCT1CT2I2I1i1i2

  • RELAI DIFERENSIAL BIASKONSEP DASAR RELAI DIFERENSIALDIFERENSIAL SEDERHANA ( UNBIAS )@ TERJADI ARUS SIRKULASI SELAMA KONDISI NORMAL ATAU GANGGUAN DI LUAR SEHINGGA TIDAK ADA ARUS YANG MENGALIR PADA RELAI R. SEHINGGA RELAI TIDAK KERJAR KAWASAN PENGAMANANCT1CT2I2I1i1i2F

  • RELAI DIFERENSIAL BIASKONSEP DASAR RELAI DIFERENSIALDIFERENSIAL SEDERHANA ( UNBIAS )@ GANGGUAN INTERNAL MENYEBABKAN ARUS MENGALIR PADA RELAI R MAKA RELAI AKAN BEKERJAR KAWASAN PENGAMANANCT1CT2I2I1i1i2FSATU SUMBERDUA SUMBER

  • RELAI DIFERENSIAL BIASKELEMAHAN RELAI DIFERENSIAL UNBIASDalam prakteknya relai diferensial unbias mempunyai 3 kelemahan utama :

    a) Karakteristik CT Pada saat gangguan eksternal ,karakteristik CT yang tidak sama akan menghasilkan tegangan pada masing masing sekunder Ct tidak sama. Juga panjang kabel kontrol sekunder CT tidak sama CT1CT2

  • RELAI DIFERENSIAL BIAS

    b) Perubahan rasio akibat ON LOAD TAP CHANGER

    Arus sisi sekunder CT dapat dibuat match hanya pada satu titik dari rentang pengubahan tap. Pada posisi lain akan timbul arus tak seimbang. c) Magnitising Inrush Current

    Arus ini muncul disisi primer dan condong mengerjakan relai R .

  • RELAI DIFERENSIAL BIAS UNTUK MEMBUAT RELAI STABIL :

    (1) KESULITAN (a) DAN (b) DIATASI DENGAN RELAI DIFERENSIAL PERSENTASE ATAU BIAS

    (2) KESULITAN (c) DIATASI DENGAN HARMONIC RESTRAINT

  • RELAI DIFERENSIAL BIASRELAI DIFERENSIAL PERSENTASE ( BIAS )ALAT YANGDIPROTEKSICT1CT2OPERATERESTRAINT

  • RELAI DIFERENSIAL BIASKARAKTERISTIK ( SLOPE )SLOPE V%TRIPBLOKSLOPE !SLOPE 20

  • RELAI DIFERENSIAL BIASKOMPOSISI ARUSSAAT TRAFO DAYA DIENERGISEATAU GANGGUANKOMPONEN ARUS ARUS INRUSH ARUS GANGGUAN

    SIKLUS SIKLUS SIKLUS CT CT KE 1 KE 2 KE 3 TIDAK JENUH JENUH

    DC 58 58 58 38 0 HARMONISA 100 100 100 100 100 KE 1 HARMONISA 62 63 65 9 4 KE 2 HARMONISA 25 28 30 4 32 KE 3 HARMONISA 4 5 7 7 9 KE 4 HARMONISA 2 3 3 4 2 KE 5

  • RELAI DIFERENSIAL BIAS

    HARMONIC RESTRAINT / BLOCKING

    KARENA ARUS SERBU ( INRUSH ) TERJADI HANYA PADA SALAH SATU SISI TRAFO , ARUS INI AKAN MENGALIR DALAM SIRKUITDIFERENSIAL DAN DAPAT MENGERJAKAN RELAI .MAKA DIGUNAKAN METODE HARMONIC RESTRAINT / BLOCKINGUNTUK MENSTABILKAN RELAI DIFERENSIAL PERSENTASE .

  • RELAI DIFERENSIAL BIAS

    .

    . HARMONIC RESTRAINT METODE INI MEMBUAT RELAI DIFERENSIAL TIDAK SENSITIP TERHADAP ARUS INRUSH , YAITU DENGAN MEMFILTER ARUS BEDA , DISEARAHKAN DAN MENAMBAH RESTRAINT PERSENTASE RELAI DISETEL SEDEMIKIAN SEHINGGA TIDAK AKAN BEKERJA BILA HARMONIS KE DUA TIDAK MELEBIHI 15% DARI ARUS FREKUENSI FUNDAMENTAL .

    (b) . HARMONIC BLOCKING

    METODE INI MEMBERIKAN RELAI BLOCKING SECARA TERPISAH YANG MANA KONTAKNYA DISAMBUNG SERI DENGAN KONTAK RELAI DIFERENSIAL PERSENTASE , DAN AKAN BEKERJA BILA HARMONIS KE DUA KURANG DARI 15% ARUS FUNDAMENTAL .

  • RELAI DIFERENSIAL BIASWIRING RELAI DIFERENSIAL # PENYESUAI FASA

    FASA ARUS YANG MASUK DAN YANG KELUAR DARI RELAI HARUS SAMA .

    # PENYESUAI ARUS

    BESARNYA ARUS YANG MASUK DAN YANG KELUAR DARI RELAI HARUS SAMA .

    PERLU DIKETAHUI :

    * SAMBUNGAN / POLARITAS TRAFO DAYA * POLARITAS CT DAN RASIO CT * POLARITAS DAN RASIO ACT

  • RELAI DIFERENSIAL BIASSYARAT SAMBUNGAN PROTEKSI DIFERENSIAL TRAFO DAYA SISI CT ACT TRAFO DAYA PRIMER SEKUNDER

    Y Y Y D

    D Y Y Y

    Y D

    D Y

  • RELAI DIFERENSIAL BIASRSTA1A2B1B2C1C2a1a2b1c1c2b2rstA2B2C2A1B1C1RSTa1b1c1rstSAMBUNGAN YY0SAMBUNGAN / POLARITASTRAFO DAYARSTA1A2B1B2C1C2a1a2b1c1c2b2rstA2B2C2A1B1C1RSa1b1c1rstSAMBUNGAN YY6

  • RELAI DIFERENSIAL BIASRSTA1A2B1B2C1C2a1a2b1c1c2b2rstA2B2C2A1B1C1RSTa1b1c1rstSAMBUNGAN YD1SAMBUNGAN / POLARITASTRAFO DAYAc2a2b2RSTA1A2B1B2C1C2a1a2b1c1c2b2rstA2B2C2A1B1C1RSTa1b1c1stSAMBUNGAN YD5c2a2b2r

  • RELAI DIFERENSIAL BIASRSTA1A2B1B2C1C2a1a2b1c1c2b2rstA2B2C2A1B1C1RSTa1b1c1rstSAMBUNGAN Yd11SAMBUNGAN / POLARITASTRAFO DAYAA2B2C2A1B1C1RSa1b1c1rstSAMBUNGAN Yd7a2c2b2RSTA1A2B1B2C1C2a1a2b1c1c2b2rsta2

  • RELAI DIFERENSIAL BIASCTP1P2S1S2TRSrstnRSTIrIsItSAMBUNGAN Y0S1TSrstnRS2RSTIrIsItSAMBUNGAN Y6SAMBUNGAN CT

  • RELAI DIFERENSIAL BIASCTP1P2S1S2TRSrstRSTIrIsItSAMBUNGAN D1S1TSrstRS2RSTIr-IsItSAMBUNGAN D11SAMBUNGAN CTIr-ItItIrIr-It-ItrIrIsIr-IsIr-IsrIr

  • RELAI DIFERENSIAL BIASS1P1S1YD1ACT1YD11ACT2IrIsItItIr-ItP2P1IrP2S2IrIsItIrIsIr-IsSAMBUNGAN ACTS2

  • RELAI DIFERENSIAL BIAS52RSTDIAGRAM PROTEKSI GENERATORGENERATORCT2CT1RELAI DIFERENSIAL

  • RELAI DIFERENSIAL BIASTRAFO DAYA YY0CT1CT2P1P1P1S1P1S1YD1ACT1YD1ACT2RELAI DIFERENSIALY0Y0

  • RELAI DIFERENSIAL BIASGENTRAFO GEN .CT1CT2ACTRELAI DIFERENSIAL BIASIR - ISIrIr - iSIr - isPROTEKSI GENERATOR & TRAFOirisRST

  • RELAI DIFERENSIAL BIAS0506070809010011012012345100: 68AUXILIARY ( INTERPOSSING ) CT

  • RELAI DIFERENSIAL BIAS0506070809010011012012345100: 73AUXILIARY ( INTERPOSSING ) CT

  • RELAI DIFERENSIAL BIAS07,552,50507,552,505/V3AUXILIARY CT

  • RELAI DIFERENSIAL BIAS TAP JUMLAH BELITANBELITAN RATING TRAFOPRIMER 1 /1 A 5 / 1 A 5 / 5 A

    1 - 2 5 1 1 2 - 3 5 1 1 3 - 4 5 1 1 4 - 5 5 1 1 5 - 6 125 25 25 X - 7 25 5 5 7 - 8 25 5 5 8 - 9 25 5 5 S1-S2 125 125 25 S3-S4 90 90 18ACT TIPE GEC ALSTOM

  • RELAI DIFERENSIAL BIASTRAFO DAYA YY0CT1CT2P1P1P1S1YD1ACT1YD1ACT2RELAI DIFERENSIALY0Y0P2S2P1P2S2P2P260MVA , 150KV +/- 10% / 20KV300 / 5A2000 / 5AIn = 5A

  • KERELAIKERELAIrst123456X789S2S4S3S1123456X789S2S4S3S1123456X789S2S4S3S1P2P1KE CTLINEKE CTLINERASIOACT 132 / 43RASIOACT 228 / 43rstnntsrstrRANGKAIAN ACT TIPE MBCH UNTUK PROTEKSI DIFERENSIALTRAFO TENAGA .ACT 1YD1ACT 2YD1

  • 2L1 22L2 1INPUTCIRCUITINPUTCIRCUITT2T1T3T5T4

    232425262827OPERATEOUTPUTCIRCUITTRIP OUTPUTTRIP OTHER PHASES+-VxALARMRESET13452691110131412I2I1Idiff2L1-22L