lighting calculation - dialux lv swgr

7
LIGHTING CALCULATION OWNER: OWNER ENGINEER: CONTRACTOR: DOC NO.: REV.NO.: Date: 21.10.2015 Operator: HHI

Upload: karthikdote

Post on 04-Dec-2015

124 views

Category:

Documents


4 download

DESCRIPTION

Lighting Calculation for LV Switchgear by using Dialux software.

TRANSCRIPT

LIGHTING CALCULATION

OWNER: OWNER ENGINEER: CONTRACTOR: DOC NO.: REV.NO.:

Date: 21.10.2015 Operator: HHI

LIGHTING CALCULATION

21.10.2015

HHI JEDDAH, KSA

Operator HHITelephone

Faxe-Mail

Table of contents

LIGHTING CALCULATIONProject Cover 1Table of contents 2LV SWITCHGER ROOM

Summary 33D Rendering 4Room Surfaces

WorkplaneValue Chart (E) 5Table (E) 6

Page 2

LIGHTING CALCULATION

21.10.2015

HHI JEDDAH, KSA

Operator HHITelephone

Faxe-Mail

LV SWITCHGER ROOM / Summary

Height of Room: 3.000 m, Mounting Height: 3.000 m, Light loss factor: 0.75

Values in Lux, Scale 1:30

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0

Workplane / 337 242 416 0.718

Floor 20 192 148 236 0.771

Ceiling 70 92 47 226 0.517

Walls (4) 50 201 90 1032 /

Workplane:Height: 1.000 mGrid: 16 x 8 Points Boundary Zone: 0.500 m

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.705, Ceiling / Working Plane: 0.272.

Luminaire Parts List

Specific connected load: 23.48 W/m² = 6.97 W/m²/100 lx (Ground area: 9.20 m²)

No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]

1 3SaudiLighting 7295S/236BF.CL.E3 Surface Mounted IP65 Industrial Flourescent Luminaire (1.000)

2845 6700 72.0

Total: 8535 Total: 20100 216.0

Page 3

LIGHTING CALCULATION

21.10.2015

HHI JEDDAH, KSA

Operator HHITelephone

Faxe-Mail

LV SWITCHGER ROOM / 3D Rendering

Page 4

LIGHTING CALCULATION

21.10.2015

HHI JEDDAH, KSA

Operator HHITelephone

Faxe-Mail

LV SWITCHGER ROOM / Workplane / Value Chart (E)

Values in Lux, Scale 1 : 29

Position of surface in room: Working plane with 0.500 m Boundary Zone Marked point: (1.000 m, 1.400 m, 1.000 m)

Grid: 16 x 8 Points

Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax

337 242 416 0.718 0.581

Page 5

LIGHTING CALCULATION

21.10.2015

HHI JEDDAH, KSA

Operator HHITelephone

Faxe-Mail

LV SWITCHGER ROOM / Workplane / Table (E)

Position of surface in room: Working plane with 0.500 m Boundary Zone Marked point: (1.000 m, 1.400 m, 1.000 m)

1.219 243 268 295 321 354 375 392 400 400 392

1.056 247 272 301 328 362 384 402 410 410 402

0.894 248 274 302 330 364 386 404 412 412 404

0.731 249 275 303 332 366 388 406 415 415 406

0.569 250 276 303 331 366 388 408 416 416 408

0.406 248 274 301 328 362 384 403 411 411 403

0.244 246 271 298 325 357 379 398 406 406 398

0.081 242 265 291 316 347 367 386 393 393 386

m 0.094 0.281 0.469 0.656 0.844 1.031 1.219 1.406 1.594 1.781Attention: The coordinates refer to the image above. Values in Lux.

Grid: 16 x 8 Points

Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax

337 242 416 0.718 0.581

Page 6

LIGHTING CALCULATION

21.10.2015

HHI JEDDAH, KSA

Operator HHITelephone

Faxe-Mail

LV SWITCHGER ROOM / Workplane / Table (E)

Position of surface in room: Working plane with 0.500 m Boundary Zone Marked point: (1.000 m, 1.400 m, 1.000 m)

1.219 375 354 321 295 267 243

1.056 384 362 328 300 272 247

0.894 386 363 330 302 274 248

0.731 388 365 331 303 275 249

0.569 388 366 332 304 276 250

0.406 384 362 328 301 274 248

0.244 379 358 325 299 272 247

0.081 368 348 316 291 266 242

m 1.969 2.156 2.344 2.531 2.719 2.906Attention: The coordinates refer to the image above. Values in Lux.

Grid: 16 x 8 Points

Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax

337 242 416 0.718 0.581

Page 7