appendix i - maintenence and inspection
TRANSCRIPT
-
8/8/2019 Appendix I - Maintenence and Inspection
1/13
Changing Lives One Bridge at a Time
Volume 3: Suspended Pedestrian Bridg
Part 4: Maintenance and Inspectio
First Editon 20
-
8/8/2019 Appendix I - Maintenence and Inspection
2/13
Bridge Committee Annual Inspection Form
In order to keep your bridge in the optmum conditon, contnual upkeep is required. An annual
inspecton is essental to maintenance. Following the end of the rainy season, one or more
representatves of the Bridge Commiee must visit the bridge site and go through the following
checklist and complete corresponding maintenance.
Remove any excess mud and debris from the bridge deck.
Ensure weeds and plants growing beneath the bridge do not obstruct the bridge.
Ensure all bolts, screws and nails are in place and tghtened.
Replace deterioratng wood deck panels.
Replace deterioratng crossbeams.
Ensure that fencing is secure. Should any wires be loose or fencing missing, repair or replaceto original conditon.
Check for erosion. Should erosion or scour occur, causing the water to reroute toward the
anchor or approach, contact the local supportng agency and request assistance with a
drainage structure.
Measure the distance between the paint on the cable and the saddle guides (inset boom
right). If more than half meter, local supportng agency immediately and if possible, Bridges
to Prosperity (contact at www.BridgestoProsperity.org).
Additonal Inspecton Notes:
Paint LinePaint Line
SaddlesSaddles
Annual Inspection Pg 1
-
8/8/2019 Appendix I - Maintenence and Inspection
3/13
16 Volume 3: Suspended Part 4 Maintenance
Section 3:Quality Control Inspection
To ensure an adequate inspecton has been completed for each bridge, a Quality Control Inspecton
& Picture Inventory are required for all quality control inspectons completed on behalf of Bridges to
Prosperity. For those tracking bridges within their own agencies, a filed report is useful to ensure the
contnued maintenance needs are met. Bridges may be inspected without the design engineer on-site and furthermore, by someone without an engineering background. To ensure the evaluaton is
adequate, the submission of pictures provide a visual confirmaton of wrien statements. An As-Built
picture inventory should be on file with the Bridge Registry, which can be located in the final pages of
this manual.
To complete the quality control inspecton, prepare yourself by reading the As-Built Bridge Registry
and spend tme looking through pictures. Take special note of the size of the cables, for this will dictate
the size of torque wrench socket required. If a previous quality control review has been completed,
also review the inspectors comments and concerns. If not familiar with how to use and read a torque
wrench, reference Volume 3, Part 3: Constructon Manual.
3.1 Materials Required
3 meter measuring tape
Digital Camera
Torque Wrench
Socket (sized to correspond to cable diameter)
Pen & paper
Copy of Quality Control Inspecton (Form)
How to read aHow to read atorque wrenchtorque wrench
-
8/8/2019 Appendix I - Maintenence and Inspection
4/13
17 Volume 3: Suspended Part 4 Maintenance
3.2 Quality Control Overview
Following the completon of the bridge, a follow-up quality control inspecton must be completed
a minimum of two tmes during the lifetme of the bridge. The first should be completed between
three (3) to five (5) years afer completon, and the second inspecton between five (5) and ten (10).
If the pedestrian bridge contnues to be used beyond 10 years, the quality control inspecton should
be completed every five (5) years. Beyond 30 years, the bridge must be reviewed by an engineer to
ensure safety of cables, structure and decking.
The Quality Control Inspecton Report in Secton 5 includes the following items;
Overall Site Evaluaton
Foundaton Tiers & Towers
Anchors
Cable Conditon
Cable Clamps
Approach Walls & Ramp
Decking
For each sub-secton, an adjoining chapter is included in Secton 4: Maintenance; Secton 4 must be
referenced for both mandatory upkeep items as well as retrofit solutons for bridge concerns found
during the inspectons. Please keep one copy of each report and send a copy to Bridges to Prosperity
(contact at www.BridgestoProsperity.org).
-
8/8/2019 Appendix I - Maintenence and Inspection
5/13
Quality Control Review& Picture Inventory FormDate: __________
Country: __________________________
Bridge Name:
Name of Inspector: ___________________________
Date: __________
Region: ___________________________
Village: ___________________________
GPS coordinates: ___________________________
Directons to site: _______________________________________________________
_______________________________________________________
Contact informaton of person in community: __________________________
Bridge Span: ________meters
Contact informaton of inspecton partcipants: ___________________________
Observed traffic level: Number of persons: ____________ Time Lapse: ____________
Type of use (bicycle, pedestrian, livestock, etc.) ________________________________
Notes:
Quality Control Pg 1
-
8/8/2019 Appendix I - Maintenence and Inspection
6/13
Site Evaluation
Inspect the area surrounding the bridge, on both abutments.
Take special note if erosion has occurred and what the
drainage path of run-offwater appears to take. If the erosion
has caused scour, undercung the anchor, approach or
foundat
on structure, reference the maintenance sect
on.For all following sectons, reference Secton 4: Maintenance
to address any possible concerns. If the manual does
not address the specific issue, please contact Bridges to
Prosperity (contact at www.BridgestoProsperity.org).
Include the following pictures on disk or in printed form and
aach to Quality Control Inspecton report;
Profile (from both up and down stream)
Lef and Right abutment general picture
Pictures of bridge in use (people, livestock etc.)
Notes on site evaluaton, include drainage concerns:
Foundation Tiers & Towers
Inspect the foundaton ters and towers. Note the masonry
conditon of towers. Is one able to pick out aggregate with hands?
On either side, verify the base foundaton layer is level (see black
line on picture to right). Note if the foundaton structure appears to
be dipping (orange) towards the water, or slipping (green arrow). If
structure has seled in either manner creatng change of elevaton
of line greater than 30 cm, contact agency responsible for bridge.
Notes on foundaton ters & towers:
Include the following pictures with report:
Concerning masonry degradaton, if any
Pictures from both sides, either abutment
Picture of selement, if any
Quality Control Pg 2
Figure above: Profile picture
Figure above: Abutment picture
-
8/8/2019 Appendix I - Maintenence and Inspection
7/13
Anchors
Inspect the area surrounding the anchors (far back side
of approach, on both abutments. Take special note if
erosion has occurred and what the drainage path of run-
offwater appears to take. If the erosion has caused scour,
undercung the anchor, reference the maintenance
secton.
Walk behind the approach, if possible. The view should be
similar to that in the picture to the right. For soil conditons,
the anchor is a large beam, as shown in the picture to the
right. Note if the cable is kinked at the saddles, implying
the cable is not wrapped directly behind the corresponding
cable saddle (handrail on outsides, walkway on inside, as
shown to right).
For rock conditons, the anchor is a cylindrical drum. The
cables also should come straight off the saddles, as shownin the diagram to the boom right. Note is the cable is
kinked.
Include the following pictures with report:
Picture from behind abutment & ramp, on either
abutment
Lef and Right abutment general picture
Picture/s of erosion or drainage concerns, if any
Notes on anchor, sketch area if drainage concerns:
Quality Control Pg 3
-
8/8/2019 Appendix I - Maintenence and Inspection
8/13
Cable Condition
Inspect the cable at all points of inserton into concrete, the
approach or the ground. Inspect general cable conditon and
note if loose strands occur anywhere along the cable.
Note the slide of the cable. Reference the colored mark on
the cable, which originated between guides on saddles. Ifthe amount of movement exceeds 1 % of length of cable
(see Span on Quality Control Page 1), cable slip or excessive
cable stretch has occurred (assume 2% equally divided
between two sides as an upper limit of concern). Please
contact B2P immediately (contact informaton at www.
BridgestoProsperity.org).
Include the following pictures with report:
Cable inserton into approach, if any corrosion or rust
appears
Pictures of all four (4) handrail saddle pictures: look for
amount of slide for mark on cable.
Cable fraying, if any
Cable Clamps
Inspect all clamps that are visible above ground. Using torque
wrench, document existng torque on each above-ground
clamp. For torque standards, first measure the diameter of
the cable or reference As-Built Bridge Register. Reference the
corresponding minimum torque from the torque requirements
on the following page.
If the measured torque is less than 80% torque required,
re-tghten all above-ground clamps to specified torque. If
actual is less than 60% of specified required torque, notfy
implementng agency immediately to discuss need to rip out
approach or return with additonal clamps.
Include the following pictures with report: Clamp conditon (before re-torque, if required)
If re-torqued, torque technique used for each
Figure above: Handrail saddle
Figure above: Cable at concrete
Quality Control Pg 4
Figure above: cable clamps
Figure above: Re-torque clamps
-
8/8/2019 Appendix I - Maintenence and Inspection
9/13
Notes on cable and clamps (include existng torque for
every above-ground clamp):
Approach Walls & Ramp
Inspect the conditon of the approach walls and ramp.
Evaluate and document extent of cracking on concrete
approach ramp. Typical source of crack propagaton is the
inserton point of cable, or selement within the approach.
Note opinion on source of cracks. If cracks between rock
walls exist, look into the approach to evaluate if excessive selement has occurred inside. Note if any
usage issues occur. This may include water pooling, excessive
cracks or bumps in the approach or connecton to ground etc.
Include the following pictures with report:
Cable inserton into approach if cracks
If separaton between tower and approach, if more than 30cm separaton, note if selement occurred with tower or ap-
proach.
Notes on approach walls and ramp:
Quality Control Pg 5
Table above: Clamp torque requirements
Figure above: Cracking ramp side-view
Figure above: Cracking
-
8/8/2019 Appendix I - Maintenence and Inspection
10/13
Decking
Rate the conditon of the deck panels. Note if any
longitudinal deck panels are missing. Note if rot has
occurred and to what extent. Document with pictures,
quantty and extent of rot and opinion of current usability.
Rate conditon of cross beams (transverse beams, likely
will need to go below deck). Note if any cracking between
suspender drill hole and end of beam. Note any structural
damage (split beams, missing sectons of beams etc.).
Note if rot has occurred and to what extent. Document
with pictures, quantty and extent of rot and opinion of
current usability.
Include the following pictures with report:
General decking conditon
General crossbeam conditon
Decking/crossbeam pictures if rong or other
issues
Notes on approach walls and ramp:
Full-Bridge Photos
CrossbeamsCrossbeams
Quality Control Pg 6
-
8/8/2019 Appendix I - Maintenence and Inspection
11/13
24 Volume 3: Suspended Part 4 Maintenance
Section 4:Maintenance
This secton includes mandatory upkeep items to be completed during every Quality Control Inspecton,
as well as solutons to repair bridge components found to be substandard during inspectons.
The Maintenance chapter includes the following sectons:
4.1 Overall Site Conditon
4.2 Foundaton Tiers & Towers
4.3 Anchors
4.4 Cable & Clamps
4.5 Approach Walls & Ramp
4.6 Decking
4.1 Overall Site Condition
If the Quality Control Inspecton notes that erosion and scour are undermining the bridge structure,
a drainage structure may allow the water to reroute, thus saving the structure from further damage.
Slope protecton and drainage systems are required at sites when excess run-offmay influence the
slope stability. It is recommended to avoid sites where any instability is prevalent. If unavoidable, it is
necessary to drain out the runoffand seepage to ensure the stability of the slope and to avoid under-
scour of structures. Water should be collected as closely as possible to its origin and navigated away
from the bridge structures. A surface catch drain on a slope may be required, drainage around the
structure or both.
Below right if an example subsurface drainage systems, and boom right are example surface drainage
systems. For further details, reference Volume 2.
Surface Drainage
Subsurface Drainage
-
8/8/2019 Appendix I - Maintenence and Inspection
12/13
25 Volume 3: Suspended Part 4 Maintenance
4.2 Foundation Tiers & Towers
If the quality control inspecton finds that the masonry structure is degrading, use a cement mortar to
patch the areas. If severe degradaton, consider replacing when possible.
If the structure is found to be slipping (either slipping downhill, or tpping forward), hire a local
engineer to evaluate the stability of the slope. If considered unsafe, close the bridge. It is possible to
reconstruct the structure of the failing side using many of the scrapped materials, but do not relocate
at such a distance that the cables create a lateral load on the opposing side towers.
4.3 Anchors
If the Quality Control Inspecton notes that erosion and scour are undermining the anchor, a drainage
structure may allow the water to reroute, thus saving the structure from further damage. See secton
4.3.1 and reference Volume 2 for further details on drainage structures.
4.4 Cables & Clamps
If the cable is found to be corroding or fraying, estmate the percentage of the cable cross-secton
that has been damaged. If greater than 10% of cable is fraying, evaluate the extent of the damage. If
localized in one point, consider a splice. Reference cable-
manufacturing materials for details. If evaluated to have
extensive damage, close the bridge untl cable can be
replaced with new cables. If this occurs, contact Bridges
to Prosperity to describe situaton, providing pictures and
details when possible (contact at www.BridgestoProsperity.
org).
If the clamps are found to have less than 80% of required
torque, each above-ground clamp must be re-tghtened.
The picture to the top right depicts the cross-sectonal
reducton that is required when the clamps are fully
torqued (assuming drop-forged, not malleable. For more
informaton, see Volume 3, Part 3). Boom
right shows the proper length of the breaker
bar or torque wrench required to apply the
adequate amount of torque.
If the clamps are found to have less than60% of the required torque, additonal
clamps must be added. In severe cases the
approach should be removed to tghten
clamps below ground.
SaddleSaddle
DeadDeadcablecable
-
8/8/2019 Appendix I - Maintenence and Inspection
13/13
26 Volume 3: Suspended Part 4 Maintenance
4.5 Approach Walls & Ramp
If the quality control inspecton finds that the approach structure is degrading, use a cement mortar to
patch the areas. If severe degradaton, consider patching with wedge stones.
If the approach ramp is separatng from the tower structure, a method to te back the structures
together is required or the bridge must be closed. This method is beyond the scope of this basic
manual as it will require engineering consultaton.
If the ramp is cracking from selement (not just localized cracking around the inserton points of the
cable), rip out the 5 cm thick concrete ramp top, backfill the approach with additonal well-graded
large aggregate and stone and recover with a fresh layer of concrete, 5 cm thick.
4.6 Decking
If any decking panels are rong through or missing
entrely, they must be replaced. The standard
thickness of a decking board is 5 cm, but verify withthose on site before purchasing. Reference Volume 3,
Part 2 Drawings, specifically the decking drawings for
complete details. Note that the paern of laying the
deck panels requires an alternaton, as shown in the
picture to the right.
If any crossbeams are in need of replacement, either
an additonal board must be aached to the boom as
reinforcement or the beam must be replaced.
If replacement is chosen, start by removing the deck
panels directly above the crossbeam in queston.
Unwrap the fencing in the direct locaton; cung may
be required. Secondly, unwrap the suspenders from
the top of the cable, which likely will require a pipe.
Unwrap the suspender from the crossbeam, originally
with the configuraton shown to the right. Remove
the suspenders completely and aempt to straighten
for reuse. Take new pre-drilled crossbeam and fit into
place. Reference Volume 3, Part 3 Constructon for
details. Complete the process by screwing and nailingthe deck boards back into place. Replace and repair
any damaged fencing before leaving.