  • 8/22/2019 Whats Up Gold Faq

    1/26

    In this tutorial we will walk through configuring WhatsUp Gold to monitor a probe on the Senturion

    Environmental Monitor.

    Applies to:

    Senturion Environmental Monitor

    Senturion Lite Environmental Monitor

    Prerequisites:

    Working copy of WhatsUp Gold 12.3 (other versions work as well)

    Sensatronics Senturion SNMP MIBS (Get them here)

    SensatronicsSenturionorSenturion Liteconnected to network

    Sections:

    Section 1 - Install Senturion MIBS How to install the SensatronicsSenturion MIBS into WUG

    Section 2 - Add the device How to add the device

    Section 3 - Configure thePerformance Monitor

    How to add a performance monitor fora probe.

    Section 4 - Configure the Active

    Monitor

    How to setup Active Monitor

    Thresholds and Alerts

    Section 5 - Viewing the data How to view Performance Monitor andActive Monitor data

    Section 1: Install Senturion MIBS

    Download, extract and copy the sensatronics-senturion-my and sensatronics-smi mibs to the

    C:/Program Files/ipswitch/whatsup/data/mibs/ directory

    http://sensatronics.com/images/sensaproducts/it/monitors/senturion/downloads/senturion_mibs.ziphttp://sensatronics.com/index.php/products/it-products/144.htmlhttp://sensatronics.com/index.php/products/it-products/144.htmlhttp://sensatronics.com/index.php/products/it-products/144.htmlhttp://sensatronics.com/index.php/products/industrial-products/42.htmlhttp://sensatronics.com/index.php/products/industrial-products/42.htmlhttp://sensatronics.com/index.php/products/industrial-products/42.htmlhttp://sensatronics.com/index.php/whatsup-gold/198.html#Section1%23Section1http://sensatronics.com/index.php/whatsup-gold/198.html#Section1%23Section1http://sensatronics.com/index.php/whatsup-gold/198.html#Section2%23Section2http://sensatronics.com/index.php/whatsup-gold/198.html#Section2%23Section2http://sensatronics.com/index.php/whatsup-gold/198.html#Section3%23Section3http://sensatronics.com/index.php/whatsup-gold/198.html#Section3%23Section3http://sensatronics.com/index.php/whatsup-gold/198.html#Section3%23Section3http://sensatronics.com/index.php/whatsup-gold/198.html#Section4%23Section4http://sensatronics.com/index.php/whatsup-gold/198.html#Section4%23Section4http://sensatronics.com/index.php/whatsup-gold/198.html#Section4%23Section4http://sensatronics.com/index.php/whatsup-gold/198.html#Section5%23Section5http://sensatronics.com/index.php/whatsup-gold/198.html#Section5%23Section5http://sensatronics.com/images/sensaproducts/it/monitors/senturion/downloads/senturion_mibs.ziphttp://sensatronics.com/index.php/products/it-products/144.htmlhttp://sensatronics.com/index.php/products/industrial-products/42.htmlhttp://sensatronics.com/index.php/whatsup-gold/198.html#Section1%23Section1http://sensatronics.com/index.php/whatsup-gold/198.html#Section2%23Section2http://sensatronics.com/index.php/whatsup-gold/198.html#Section3%23Section3http://sensatronics.com/index.php/whatsup-gold/198.html#Section3%23Section3http://sensatronics.com/index.php/whatsup-gold/198.html#Section4%23Section4http://sensatronics.com/index.php/whatsup-gold/198.html#Section4%23Section4http://sensatronics.com/index.php/whatsup-gold/198.html#Section5%23Section5
  • 8/22/2019 Whats Up Gold Faq

    2/26

    Restart the "Ipswitch WhatsUp Engine in Windows/Services so the new mibs

    will be recognized by the system

    Section 2: Add the Device

    Open the WhatsUp Gold admin console and add a new device (File/New/New Device....)

  • 8/22/2019 Whats Up Gold Faq

    3/26

    Enter the IP address of your Senturion / Senturion Lite

    Click on "Credentials" in the properties section and select your

    "SNMP v1/v2/v3 credentials" from the drop-down. The default for the Senturion is "Public"

  • 8/22/2019 Whats Up Gold Faq

    4/26

    Section 3: Configure Performance Monitors

    Click "Performance Monitors" in the properties section and

    Click the "New" button to add a new individual performance monitor

  • 8/22/2019 Whats Up Gold Faq

    5/26

    Select a performance monitor type of "SNMP Performance Monitor and click the "OK" button

  • 8/22/2019 Whats Up Gold Faq

    6/26

    Enter a name for your probe, here we are using "Senturion Local Temperature"

    Clip the Ellipses (...) button next to the Performance Counter Instance field.

    Browse to the Probe1Value in the SNMP MIB Walker.

    private/enterprises/sensatronics/consumerproducts/envmonitors/productsenturion/probeinfo/probevalues

    Select "probe1Value" and click the OK button

  • 8/22/2019 Whats Up Gold Faq

    7/26

    You should now see the oid for that probe in the performance counter f ield.

    Set your preferred collection interval, Timeout, and Retries. Click the "OK" button

  • 8/22/2019 Whats Up Gold Faq

    8/26

    You should now see your newly created probe performance monitor in the individual performance monitors list.

    Section 4: Configure Active Monitors

    Select "Active Monitors" from the Properties Section and click the "Add..." button to add a new Active Monitor.

  • 8/22/2019 Whats Up Gold Faq

    9/26

    Don't select a monitor from the drop-down yet. Instead, click the ellipses (...) button

    to the right of the drop-down to create a new Active Monitor type

  • 8/22/2019 Whats Up Gold Faq

    10/26

    Click the "New" button

  • 8/22/2019 Whats Up Gold Faq

    11/26

    Select "SNMP Monior" and click the "OK" button

    Name the SNMP monitor after your probe name. In this Case we are using "Senturion Local Temperature"

    Click the Ellipses (...) button to the right of the Object ID - Instance field.

    Enter the IP address of your Senturion, select your SNMP credentials and click the "OK" Button

  • 8/22/2019 Whats Up Gold Faq

    12/26

    Browse to the Probe1Value in the SNMP MIB Walker.

    private/enterprises/sensatronics/consumerproducts/envmonitors/productsenturion/probeinfo/probevalues

    Select "probe1Value" and click the OK button

  • 8/22/2019 Whats Up Gold Faq

    13/26

    You should see the probe's object ID appear in the "Object ID" field

    Change the Check Type to "Range of Values"

    Enter your minimum and maximum threshold values in the Low and High value fields.

    Note: The Senturion stores the temperature value as a whole number. So a value of 600 actually means 60.0 degrees

    and a value 850 means 85.0 degrees etc.

    Click the "OK" button

  • 8/22/2019 Whats Up Gold Faq

    14/26

    Click the "OK" button in the Active Monitor Library screen

  • 8/22/2019 Whats Up Gold Faq

    15/26

    Select your newly created Active Monitor type from the dropdown and Click the "Next" button

  • 8/22/2019 Whats Up Gold Faq

    16/26

    Click "Next" in the Set Polling Properties Section

  • 8/22/2019 Whats Up Gold Faq

    17/26

    Setup your Actions. Select either Action Policy or setup individual actions.

  • 8/22/2019 Whats Up Gold Faq

    18/26

    Select an action policy if desired:

    Select the Apply individual actions radio button and click the "Add" button to setup individual actions for this monitor.

  • 8/22/2019 Whats Up Gold Faq

    19/26

    Create a new action or select existing action

    We set an individual action to email the Admin when the Monitor is out of range for 20 minutes

  • 8/22/2019 Whats Up Gold Faq

    20/26

    Click the "Finish" Button

  • 8/22/2019 Whats Up Gold Faq

    21/26

    You should see the new probe monitor show up in the Active Monitors list

    Click the "OK" button

    You should see the newly added device in the device list

    Section 5: Viewing the Data

    Right Click on the device and select "Poll Now"

  • 8/22/2019 Whats Up Gold Faq

    22/26

    Right-click on the device again and select "Device Status Report"

    This will load the web console. Enter your username and password and login.

  • 8/22/2019 Whats Up Gold Faq

    23/26

    You will see your newly added device status.

    Click on your probe name in the "Device Performance Monitor Summary"

  • 8/22/2019 Whats Up Gold Faq

    24/26

    You will see a graph load and you should see it starting to graph data on the right

  • 8/22/2019 Whats Up Gold Faq

    25/26

    Go back to your Device Status screen and click on the name of your probe in the "Device Active Monitor States" section. Youshold see a data point on the right

    side of the Monitor State graph

  • 8/22/2019 Whats Up Gold Faq

    26/26

    You can repeat the previous steps for each probe you have connected to the Senturion.