STC 51 16 mm TYPE X GYPSUM BOARD 60 mm ACOUSTIC BATT INSULATION STAGGERING STUDS WITH STUD ASSEMBLY 31 X 64 25 GA STEEL STUDS, 600 O.C. MAX., MIN. 25 mm AIR SPACE BETWEEN EXISTING WALL AND NEW STUD WALL REMOVE EXISTING GB EXISTING WOOD STRUCTURE TO REMAIN REINSTALLED BIRCH SIDING 16 GYPSUM BOARD 38X89 STEEL STUD, 600 O.C. MAX 16 GYPSUM BOARD REINSTALLED BIRCH SIDING CONTINUOUS TO U/S OF GB ON TRUSS EXISTING CMU WALL 25 mm AIR SPACE B/W EXISTING WALL AND NEW STUD WALL 31 X 64 25 GA STEEL STUDS, 600 O.C. MAX 16 GYPSUM BOARD BULKHEAD REINSTALLED BIRCH SIDING 16 GYPSUM BOARD 38 X 89 WOOD STUDS, 400 O.C. MAX 16 GYPSUM BOARD CONTINUOUS TO U/S OF GB ON TRUSS 16 GB 38 X 89 STEEL STUD, 600 O.C. MAX 16 GB 16 GB 38 X 89 WOOD STUDS, 400 O.C. MAX PARTITION TYPES: 200 mm CMU 16 TYPE X GYPSUM BOARD VAPOUR BARRIER 38X140 WOOD STUDS, 400 O.C. MAX 140 BATT INSULATION 12 mm PLYWOOD SHEATHING ALUMINUM CLADDING C/W FURRING CHANNEL 200 mm CONCRETE BLOCK 38X80 STUDS @ 400 O.C. MAX VAPOUR BARRIER 80 mm RIGID INSULATION BUILDING PAPER ALUMINUM CLADDING C/W FURRING CHANNEL 16 TYPE X GYPSUM BOARD VAPOUR BARRIER 38 X 140 WOOD STUDS, 400 O.C. MAX 140 BATT INSULATION 12 mm PLYWOOD SHEATHING REINSTALLED ALUMINUM CLADDING C/W FURRING CHANNEL 16 mm TYPE X GYPSUM BOARD 60 mm ACOUSTIC BATT INSULATION 31 X 64 25 GA STEEL STUDS, 600 O.C. MAX., MIN. 25 mm AIR SPACE BETWEEN EXISTING WALL AND NEW STUD WALL EXISTING ASSEMBLY TO REMAIN: 200 mm CMU 38 X 80 WOOD STUDS, 400 O.C. MAX 80 mm RIGID INSULATION 16 GB WALL TYPES: P1 C1 EW1 STC 50 16 mm TYPE X GYPSUM BOARD 60 ACOUSTIC BATT INSULATION 31 X 64 25 GA STEEL STUDS, 600 O.C. MAX. MIN. 25 mm AIR SPACE BETWEEN EXISTING STRUCTURE AND NEW STUD CEILING, USE 25 mm RUBBER ISOLATION PADS TO FASTEN TO STRUCTURE WHERE NEEDED. 16 TYPE X GB 19X89 STRAPPING @ 400 O.C. MAX VAPOUR BARRIER R.S.I. 5.283 BATT INSULATION EXISTING 38 X 140 WOOD CEILING FRAMING CEILING TYPES: P2 C2 EW2 P3 EW3 W4 W5 P4 WD-1 ALUMINUM FRAME INSULATED GLAZING UNIT - DOUBLE GLAZED ALUMINUM FRAME GLAZING UNIT - SINGLE GLAZED WINDOW TYPES: WD-2 P5 P6 GENERAL SHEET NOTES: THESE NOTES APPLY TO ALL PROJECT DRAWINGS DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE INDICATED. DO NOT SCALE DRAWINGS, USE DIMENSIONS ONLY. DIMENSIONS ON PLANS ARE TO FACE OF WALL STUDS,CONCRETE, CMU OR TO THE OF STRUCTURAL GRIDS, UNLESS OTHERWISE NOTED. DIMENSIONS FOR EXISTING ELEMENTS SHALL BE FIELD VERIFIED PRIOR TO FABRICATION OR CONSTRUCTION. ALL DIMENSIONS AND EXISTING CONDITIONS TO BE VERIFIED BY GC PRIOR TO CONSTRUCTION COMMENCEMENT. WHERE NEW DOUBLE WALLS ARE CONSTRUCTED, PATCH ALL HOLES IN EXISTING GYPSUM BOARD AND MAKE FLUSH WITH EXISTING, SEALING JOINTS WITH ACOUSTIC SEALANT. ALL INTERIOR PARTITIONS ARE DIMENSIONED TO FACE OF FINISH, GRID LINES, OR FACE OF CONCRETE, UNLESS OTHERWISE NOTED. SEAL ALL PENETRATIONS THROUGH FULL HEIGHT PARTITIONS. FIRE STOP ALL PENETRATIONS THROUGH FIRE RATED PARTITIONS. PROVIDE FIRE DAMPERS AS REQUIRED FOR ALL PENETRATIONS. PATCH AND MAKE GOOD ALL FLOORS, WALLS AND CEILINGS AFFECTED BY SELECTIVE DEMOLITION. ALL FIXTURES, EQUIPMENT, FURNITURE AND CLADDING REMOVED TO BE RETURNED TO CLIENT. ALL PARTITION WALLS TO U/S OF STRUCTURE UNLESS OTHERWISE NOTED.. CONTRACTOR MAY CHOOSE TO USE EITHER WOOD OR STEEL STUDS. INFILL ANY PENETRATIONS LEFT BY THE REMOVAL OF MECHANICAL EQUIPMENT. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. LEGEND: EXISTING NEW PARTITION EXISTING DOOR TO REMAIN EXISTING DOOR TO BE DEMOLISHED GB CEILING TO BE REMOVED EXTENTS OF FLOOR FINISH UPGRADE. REMOVE EXISTING FLOOR FINISH 1 HR FRR 2' X 4' LUMINAIRE TO BE REMOVED 1' X 4' SURFACE MOUNTED LUMINAIRE TO BE REMOVED. REFER TO ELECT. RECESSED LUMINAIRE TO BE REMOVED. REFER TO ELECT. STRIP LIGHT TO BE REMOVED. REFER TO ELECT. RECESSED LUMINAIRE SURFACE MOUNTED LUMINAIRE RECESSED POT LIGHT STRIP LIGHT A100 DRAWING LIST, GENERAL NOTES, LEGENDS & SCHEDULES A101 DEMOLITION FLOOR PLAN A102 FLOOR PLAN A103 REFLECTED CEILING PLAN A104 SECOND FLOOR REFLECTED CEILING PLAN & DETAILS A105 INTERIOR ELEVATIONS & SECTIONS E0.1 ELECTRICAL SYMBOLS AND ABBREVIATIONS E1.1 ELECTRICAL SITE PLAN ED1.1 ELECTRICAL SITE DEMOLITION PLAN ED2.1 MAIN FLOOR - DEMOLITION PLAN ED2.2 SECOND FLOOR - DEMOLITION PLAN EL2.1 MAIN FLOOR - LIGHTING PLAN EL2.2 SECOND FLOOR - LIGHTING PLAN EP2.1 MAIN FLOOR - POWER PLAN EP2.2 SECOND FLOOR - POWER PLAN E6.1 ELECTRICAL SCHEDULES M2.1 MAIN FLOOR - MECHANICAL DEMOLITION PLAN - STONEWALL M2.2 MAIN FLOOR - MECHANICAL RENOVATION PLAN - STONEWALL M2.3 SECOND FLOOR - MECHANICAL DEMOLITION & RENOVATION PLAN - STONEWALL M2.4 MECHANICAL DETAILS & SCHEDULES - STONEWALL FLOOR RSF - RESILIENT SHEET FLOORING CONC - CONCRETE BASE WB - WOOD BASE RB - RUBBER BASE WALLS GWB - GYPSUM WALL BOARD WD - WOOD SIDING CB - CONCRETE BLOCK FINISHES P - PAINTED DOORS HM - HOLLOW METAL HMI - HOLLOW METAL INSULATED CEILING ACT - ACOUSTICS TILE EX - EXISTING C C C C A E F C D B 1 2 3 5 4 6 7 8 9 10 1 2 3 5 4 6 7 8 9 10 A E F C D B SEAL: CLIENT: PROJECT: CLIENT REF. #: ISSUED FOR - REVISION: DESCRIPTION DATE RV. IS. ISSUE: DATE OF: ORIGINAL SCALE: CHECKED BY: DRAWN BY: RV. # SHEET #: OF TITLE: DISCIPLINE: 1" IF THIS BAR IS NOT 1" LONG, ADJUST YOUR PLOTTING SCALE. PROJECT NO: DATE: SHEET NUMBER: DESIGNED BY: F F F F F F F F F F F F KEYPLAN: Arch D-BLG, D:\2014 PROJECTS\149-12549-13 RCMP 5 Detachments\Stonewall\5 Project Documents\5_4 CAD Drawings\08_Architectural\03_Sheet\0_General\A100.dwg , 12/05/2017 5:34:17 PM -- 1600 BUFFALO PLACE WINNIPEG, MANITOBA R3T 6B8 TEL: 204-477-1260 | FAX: 204-477-6346 | architecture49.com CONSULTANT - SUB-CONSULTANT: COPYRIGHT: COPYRIGHT IN THIS ELECTRONIC DOCUMENT BELONGS TO ARCHITECTURE49 INC. THIS ELECTRONIC DOCUMENT MAY NOT BE FORWARDED TO OTHERS, TRANSMITTED, DOWNLOADED, OR REPRODUCED IN ANY FORMAT, WHETHER PRINT OR ELECTRONIC, WITHOUT THE EXPRESS, WRITTEN PERMISSION OF THE COPYRIGHT OWNER. DISCLAIMER: THE CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND UTILITY LOCATIONS AND REPORT ALL ERRORS AND OMISSIONS PRIOR TO COMMENCING WORK. THIS DRAWING IS NOT TO BE SCALED. -- -- SEE NOTED -- MJ AK ARCHITECTURE DRAWING LIST, GENERAL NOTES, LEGENDS & SCHEDULES A100 0 0 STONEWALL RCMP DETACHMENT STONEWALL, MB 1 24/04/2017 ISSUED FOR REVIEW 2 12/05/2017 ISSUED FOR TENDER

Upload: others

Post on 26-Aug-2020

9 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: WALL TYPES: LEGEND · wall types: p1 c1 ew1 stc 50 16 mm type x gypsum board 60 acoustic batt insulation 31 x 64 25 ga steel studs, 600 o.c. max. min. 25 mm air space between existing

STC 5116 mm TYPE X GYPSUM BOARD60 mm ACOUSTIC BATT INSULATIONSTAGGERING STUDS WITH STUD ASSEMBLY31 X 64 25 GA STEEL STUDS, 600 O.C. MAX.,MIN. 25 mm AIR SPACE BETWEEN EXISTING WALL AND NEW STUD WALLREMOVE EXISTING GBEXISTING WOOD STRUCTURE TO REMAIN

REINSTALLED BIRCH SIDING16 GYPSUM BOARD38X89 STEEL STUD, 600 O.C. MAX16 GYPSUM BOARDREINSTALLED BIRCH SIDINGCONTINUOUS TO U/S OF GB ON TRUSS

EXISTING CMU WALL25 mm AIR SPACE B/W EXISTING WALL AND NEW STUD WALL31 X 64 25 GA STEEL STUDS, 600 O.C. MAX16 GYPSUM BOARD

BULKHEADREINSTALLED BIRCH SIDING16 GYPSUM BOARD38 X 89 WOOD STUDS, 400 O.C. MAX16 GYPSUM BOARDCONTINUOUS TO U/S OF GB ON TRUSS

16 GB38 X 89 STEEL STUD, 600 O.C. MAX16 GB

16 GB38 X 89 WOOD STUDS, 400 O.C. MAX

PARTITION TYPES:

200 mm CMU

16 TYPE X GYPSUM BOARDVAPOUR BARRIER38X140 WOOD STUDS, 400 O.C. MAX140 BATT INSULATION12 mm PLYWOOD SHEATHINGALUMINUM CLADDING C/W FURRING CHANNEL

200 mm CONCRETE BLOCK38X80 STUDS @ 400 O.C. MAXVAPOUR BARRIER80 mm RIGID INSULATIONBUILDING PAPERALUMINUM CLADDING C/W FURRING CHANNEL

16 TYPE X GYPSUM BOARDVAPOUR BARRIER38 X 140 WOOD STUDS, 400 O.C. MAX140 BATT INSULATION12 mm PLYWOOD SHEATHINGREINSTALLED ALUMINUM CLADDING C/W FURRINGCHANNEL

16 mm TYPE X GYPSUM BOARD60 mm ACOUSTIC BATT INSULATION31 X 64 25 GA STEEL STUDS, 600 O.C. MAX.,

MIN. 25 mm AIR SPACE BETWEEN EXISTING WALLAND NEW STUD WALL

EXISTING ASSEMBLY TO REMAIN:200 mm CMU38 X 80 WOOD STUDS, 400 O.C. MAX80 mm RIGID INSULATION16 GB

WALL TYPES:

P1

C1

EW1

STC 5016 mm TYPE X GYPSUM BOARD60 ACOUSTIC BATT INSULATION31 X 64 25 GA STEEL STUDS, 600 O.C. MAX.MIN. 25 mm AIR SPACE BETWEEN EXISTING STRUCTURE

AND NEW STUD CEILING, USE 25 mm RUBBERISOLATION PADS TO FASTEN TO STRUCTUREWHERE NEEDED.

16 TYPE X GB19X89 STRAPPING @ 400 O.C. MAXVAPOUR BARRIERR.S.I. 5.283 BATT INSULATIONEXISTING 38 X 140 WOOD CEILING FRAMING

CEILING TYPES:

P2

C2

EW2

P3

EW3

W4

W5

P4

WD-1 ALUMINUM FRAME INSULATED GLAZING UNIT - DOUBLE GLAZED

ALUMINUM FRAME GLAZING UNIT - SINGLE GLAZED

WINDOW TYPES:

WD-2

P5

P6

GENERAL SHEET NOTES:THESE NOTES APPLY TO ALL PROJECT DRAWINGS

DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE INDICATED.

DO NOT SCALE DRAWINGS, USE DIMENSIONS ONLY.

DIMENSIONS ON PLANS ARE TO FACE OF WALL STUDS,CONCRETE,CMU OR TO THE ℄ OF STRUCTURAL GRIDS, UNLESS OTHERWISENOTED.

DIMENSIONS FOR EXISTING ELEMENTS SHALL BE FIELD VERIFIEDPRIOR TO FABRICATION OR CONSTRUCTION.

ALL DIMENSIONS AND EXISTING CONDITIONS TO BEVERIFIED BY GC PRIOR TO CONSTRUCTION COMMENCEMENT.

WHERE NEW DOUBLE WALLS ARE CONSTRUCTED, PATCH ALLHOLES IN EXISTING GYPSUM BOARD AND MAKE FLUSH WITHEXISTING, SEALING JOINTS WITH ACOUSTIC SEALANT.

ALL INTERIOR PARTITIONS ARE DIMENSIONED TO FACE OF FINISH,GRID LINES, OR FACE OF CONCRETE, UNLESS OTHERWISE NOTED.

SEAL ALL PENETRATIONS THROUGH FULL HEIGHT PARTITIONS. FIRESTOP ALL PENETRATIONS THROUGH FIRE RATED PARTITIONS.PROVIDE FIRE DAMPERS AS REQUIRED FOR ALL PENETRATIONS.

PATCH AND MAKE GOOD ALL FLOORS, WALLS AND CEILINGSAFFECTED BY SELECTIVE DEMOLITION.

ALL FIXTURES, EQUIPMENT, FURNITURE AND CLADDING REMOVED TOBE RETURNED TO CLIENT.

ALL PARTITION WALLS TO U/S OF STRUCTURE UNLESS OTHERWISENOTED..

CONTRACTOR MAY CHOOSE TO USE EITHER WOOD OR STEEL STUDS.

INFILL ANY PENETRATIONS LEFT BY THE REMOVAL OF MECHANICALEQUIPMENT.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

LEGEND:

EXISTING

NEW PARTITION

EXISTING DOOR TO REMAIN

EXISTING DOOR TO BE DEMOLISHED

GB CEILING

TO BE REMOVED

EXTENTS OF FLOOR FINISH UPGRADE.REMOVE EXISTING FLOOR FINISH

1 HR FRR

2' X 4' LUMINAIRE TO BE REMOVED

1' X 4' SURFACE MOUNTED LUMINAIRE TO BE REMOVED.REFER TO ELECT.

RECESSED LUMINAIRE TO BE REMOVED. REFER TO ELECT.

STRIP LIGHT TO BE REMOVED. REFER TO ELECT.

RECESSED LUMINAIRE

SURFACE MOUNTED LUMINAIRE

RECESSED POT LIGHT

STRIP LIGHT

A100 DRAWING LIST, GENERAL NOTES, LEGENDS & SCHEDULES

A101 DEMOLITION FLOOR PLANA102 FLOOR PLANA103 REFLECTED CEILING PLANA104 SECOND FLOOR REFLECTED CEILING PLAN & DETAILSA105 INTERIOR ELEVATIONS & SECTIONS

E0.1 ELECTRICAL SYMBOLS AND ABBREVIATIONSE1.1 ELECTRICAL SITE PLANED1.1 ELECTRICAL SITE DEMOLITION PLANED2.1 MAIN FLOOR - DEMOLITION PLANED2.2 SECOND FLOOR - DEMOLITION PLANEL2.1 MAIN FLOOR - LIGHTING PLANEL2.2 SECOND FLOOR - LIGHTING PLANEP2.1 MAIN FLOOR - POWER PLANEP2.2 SECOND FLOOR - POWER PLANE6.1 ELECTRICAL SCHEDULES

M2.1 MAIN FLOOR - MECHANICAL DEMOLITION PLAN - STONEWALLM2.2 MAIN FLOOR - MECHANICAL RENOVATION PLAN - STONEWALLM2.3 SECOND FLOOR - MECHANICAL DEMOLITION & RENOVATION PLAN - STONEWALLM2.4 MECHANICAL DETAILS & SCHEDULES - STONEWALL

FLOOR

RSF - RESILIENT SHEET FLOORINGCONC - CONCRETE

BASE

WB - WOOD BASERB - RUBBER BASE

WALLS

GWB - GYPSUM WALL BOARDWD - WOOD SIDINGCB - CONCRETE BLOCK

FINISHES

P - PAINTED

DOORS

HM - HOLLOW METALHMI - HOLLOW METAL INSULATED

CEILING

ACT - ACOUSTICS TILE

EX - EXISTING

C

C

C

C

A

E

F

C

D

B

1235 4678910

1235 4678910

A

E

F

C

D

B

SEAL:

CLIENT:

PROJECT:

CLIENT REF. #:

ISSUED FOR - REVISION:

DESCRIPTIONDATERV.IS.

ISSUE:

DATE OF:

ORIGINAL SCALE:

CHECKED BY:

DRAWN BY:

RV. #

SHEET #: OF

TITLE:

DISCIPLINE:

1"

IF THIS BAR IS NOT 1"LONG, ADJUST YOUR

PLOTTING SCALE.

PROJECT NO: DATE:

SHEET NUMBER:

DESIGNED BY:

F

F

F F

F F

F

F

F

F

F

F

KEYPLAN:

Arch D-BLG, D:\2014 PROJECTS\149-12549-13 RCMP 5 Detachments\Stonewall\5 Project Documents\5_4 CAD Drawings\08_Architectural\03_Sheet\0_General\A100.dwg , 12/05/2017 5:34:17 PM

--

1600 BUFFALO PLACEWINNIPEG, MANITOBA R3T 6B8

TEL: 204-477-1260 | FAX: 204-477-6346 | architecture49.com

CONSULTANT - SUB-CONSULTANT:

COPYRIGHT:

COPYRIGHT IN THIS ELECTRONIC DOCUMENT BELONGS TO ARCHITECTURE49 INC. THIS ELECTRONICDOCUMENT MAY NOT BE FORWARDED TO OTHERS, TRANSMITTED, DOWNLOADED, OR REPRODUCED INANY FORMAT, WHETHER PRINT OR ELECTRONIC, WITHOUT THE EXPRESS, WRITTEN PERMISSION OF THECOPYRIGHT OWNER.

DISCLAIMER:

THE CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND UTILITY LOCATIONS AND REPORTALL ERRORS AND OMISSIONS PRIOR TO COMMENCING WORK.THIS DRAWING IS NOT TO BE SCALED.

--

--

SEE NOTED

--

MJ

AK

ARCHITECTURE

DRAWING LIST, GENERAL NOTES, LEGENDS & SCHEDULES

A1000

0

STONEWALL RCMP DETACHMENT

STONEWALL, MB

1 24/04/2017 ISSUED FOR REVIEW2 12/05/2017 ISSUED FOR TENDER

Page 2: WALL TYPES: LEGEND · wall types: p1 c1 ew1 stc 50 16 mm type x gypsum board 60 acoustic batt insulation 31 x 64 25 ga steel studs, 600 o.c. max. min. 25 mm air space between existing

GYM

106

SECUREINTERVIEW ROOM

105

MONITORROOM104

EW1

P3

P1

P1

EW3

EW2P2

17A105

3A104

9A105

P3

W4

W5

EW3

101A

101B

103A

105A

106A

17A105

12A105

PUBLIC RECEPTION102

VESTIBULE101

P1

INTERVIEW ROOM103

GENERAL OFFICE107

EW1EW

1

10A105

UP

P5

P3

106B

SIM.

P5

1.

2.3.

4.

5.6.

7.8.9.10.

11.

CONSTRUCTION KEYNOTES:PROVIDE ELECTRO MECHANICAL HOLD OPEN DEVICE ON PROVOST

DOOR.PUSH BUTTON DOOR OPENER.SECURITY BARRIER, COUNTER & CABINETS. C/W REINSTALLED BIRCH

SIDING.PROVIDE SHEET FLOORING AND WALL BASE WITHIN FLOORING

UPGRADE EXTENTS.CONCRETE INFILL @ EXISTING SLAB DEPRESSION.PROVIDE 16 GB LAMINATED OVER EXISTING WALL C/W NEW DOOR

AND WINDOW TRIM. TRIM NEW GB TO EXISTING WINDOWS &DOORS W/ TEAR AWAY BEAD.

SWIPE CARD ACCESS FOR O.H. DOOR ON PEDESTAL.PHOTOCOPIER, NOT IN CONTRACT.STORAGE CUBBIES.INFILL DOORWAY BETWEEN RM. 105 & 106 WITH CMU TO

MATCH EXISTING WALL. TIE IN WALL FINISH ON RM.106 SIDE TO EXISTING FINISH.

SWIPE CARD ACCESS.

C

C

C

C

A

E

F

C

D

B

1235 4678910

1235 4678910

A

E

F

C

D

B

SEAL:

CLIENT:

PROJECT:

CLIENT REF. #:

ISSUED FOR - REVISION:

DESCRIPTIONDATERV.IS.

ISSUE:

DATE OF:

ORIGINAL SCALE:

CHECKED BY:

DRAWN BY:

RV. #

SHEET #: OF

TITLE:

DISCIPLINE:

1"

IF THIS BAR IS NOT 1"LONG, ADJUST YOUR

PLOTTING SCALE.

PROJECT NO: DATE:

SHEET NUMBER:

DESIGNED BY:

F

F

F F

F F

F

F

F

F

F

F

KEYPLAN:

Arch D-BLG, D:\2014 PROJECTS\149-12549-13 RCMP 5 Detachments\Stonewall\5 Project Documents\5_4 CAD Drawings\08_Architectural\03_Sheet\1_Plans\Stonewall_A101-106.dwg , 12/05/2017 5:22:27 PM

--

1600 BUFFALO PLACEWINNIPEG, MANITOBA R3T 6B8

TEL: 204-477-1260 | FAX: 204-477-6346 | architecture49.com

CONSULTANT - SUB-CONSULTANT:

COPYRIGHT:

COPYRIGHT IN THIS ELECTRONIC DOCUMENT BELONGS TO ARCHITECTURE49 INC. THIS ELECTRONICDOCUMENT MAY NOT BE FORWARDED TO OTHERS, TRANSMITTED, DOWNLOADED, OR REPRODUCED INANY FORMAT, WHETHER PRINT OR ELECTRONIC, WITHOUT THE EXPRESS, WRITTEN PERMISSION OF THECOPYRIGHT OWNER.

DISCLAIMER:

THE CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND UTILITY LOCATIONS AND REPORTALL ERRORS AND OMISSIONS PRIOR TO COMMENCING WORK.THIS DRAWING IS NOT TO BE SCALED.

STONEWALL RCMP DETACHMENT

STONEWALL, MB

--

24/04/2017

SEE NOTED

--

MJ

JC

ARCHITECTURE

FLOOR PLAN

A1022

0

1 24/04/2017 ISSUED FOR REVIEW2 12/05/2017 ISSUED FOR TENDER

ISSUED FOR TENDER

Page 3: WALL TYPES: LEGEND · wall types: p1 c1 ew1 stc 50 16 mm type x gypsum board 60 acoustic batt insulation 31 x 64 25 ga steel studs, 600 o.c. max. min. 25 mm air space between existing

16A105

P49A105

UP

2400

2700

2400

2400

C1

C1

C2

PROVIDE GB CEILING. TIE INTO EXISTING CEILING.PROVIDE STC 51 GB CEILING.EXTEND ACT. GRID & PANELS AS REQ'D TO SUIT REVISED

PARTITION LAYOUT.SECURITY BARRIER BULKHEAD, CONTINUOUS TO U/S OF STRUCTURE.

C/W REINSTALLED BIRCH SIDING ON ONE SIDE.APPROXIMATE AREA OF NEW INSULATED CEILING TO SUIT

RELOCATION OF EXTERIOR WALL..PATCH AND MAKE GOOD CEILING FINISH WHERE

LUMINAIRES WERE REMOVED.

CONSTRUCTION KEYNOTES:1.2.3.

4.

5.

6.

C

C

C

C

A

E

F

C

D

B

1235 4678910

1235 4678910

A

E

F

C

D

B

SEAL:

CLIENT:

PROJECT:

CLIENT REF. #:

ISSUED FOR - REVISION:

DESCRIPTIONDATERV.IS.

ISSUE:

DATE OF:

ORIGINAL SCALE:

CHECKED BY:

DRAWN BY:

RV. #

SHEET #: OF

TITLE:

DISCIPLINE:

1"

IF THIS BAR IS NOT 1"LONG, ADJUST YOUR

PLOTTING SCALE.

PROJECT NO: DATE:

SHEET NUMBER:

DESIGNED BY:

F

F

F F

F F

F

F

F

F

F

F

KEYPLAN:

Arch D-BLG, D:\2014 PROJECTS\149-12549-13 RCMP 5 Detachments\Stonewall\5 Project Documents\5_4 CAD Drawings\08_Architectural\03_Sheet\1_Plans\Stonewall_A101-106.dwg , 12/05/2017 5:22:27 PM

--

1600 BUFFALO PLACEWINNIPEG, MANITOBA R3T 6B8

TEL: 204-477-1260 | FAX: 204-477-6346 | architecture49.com

CONSULTANT - SUB-CONSULTANT:

COPYRIGHT:

COPYRIGHT IN THIS ELECTRONIC DOCUMENT BELONGS TO ARCHITECTURE49 INC. THIS ELECTRONICDOCUMENT MAY NOT BE FORWARDED TO OTHERS, TRANSMITTED, DOWNLOADED, OR REPRODUCED INANY FORMAT, WHETHER PRINT OR ELECTRONIC, WITHOUT THE EXPRESS, WRITTEN PERMISSION OF THECOPYRIGHT OWNER.

DISCLAIMER:

THE CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND UTILITY LOCATIONS AND REPORTALL ERRORS AND OMISSIONS PRIOR TO COMMENCING WORK.THIS DRAWING IS NOT TO BE SCALED.

STONEWALL RCMP DETACHMENT

STONEWALL, MB

--

24/04/2017

SEE NOTED

--

MJ

JC

ARCHITECTURE

REFLECTED CEILING PLAN

A1033

0

1 24/04/2017 ISSUED FOR REVIEW2 12/05/2017 ISSUED FOR TENDER

ISSUED FOR TENDER

Page 4: WALL TYPES: LEGEND · wall types: p1 c1 ew1 stc 50 16 mm type x gypsum board 60 acoustic batt insulation 31 x 64 25 ga steel studs, 600 o.c. max. min. 25 mm air space between existing

C2

WD-1

GB RETURN

PROVIDE PEEL & STICK TRANSITION MEMBRANE.OVERLAP & SEAL TO WINDOW FRAME & AIR/VAPOUR

BARRIER TO PROVIDE CONTINUOUSAIR/VAPOUR BARRIER.

NEW 19 SOLIDBIRCH SEAT

19 SOLIDBIRCH BASE

PROVIDE PEEL & STICK TRANSITION MEMBRANE.OVERLAP & SEAL TO WINDOW FRAME & AIR/VAPOUR

BARRIER TO PROVIDE CONTINUOUSAIR/VAPOUR BARRIER.

P1

EW2

W4

OUTSIDE

VEST.101

INTERVIEW RM.103

3A104

10A104

7A104

8A104

6A104

WD-1 WD-2

9A104

C

C

C

C

A

E

F

C

D

B

1235 4678910

1235 4678910

A

E

F

C

D

B

SEAL:

CLIENT:

PROJECT:

CLIENT REF. #:

ISSUED FOR - REVISION:

DESCRIPTIONDATERV.IS.

ISSUE:

DATE OF:

ORIGINAL SCALE:

CHECKED BY:

DRAWN BY:

RV. #

SHEET #: OF

TITLE:

DISCIPLINE:

1"

IF THIS BAR IS NOT 1"LONG, ADJUST YOUR

PLOTTING SCALE.

PROJECT NO: DATE:

SHEET NUMBER:

DESIGNED BY:

F

F

F F

F F

F

F

F

F

F

F

KEYPLAN:

Arch D-BLG, D:\2014 PROJECTS\149-12549-13 RCMP 5 Detachments\Stonewall\5 Project Documents\5_4 CAD Drawings\08_Architectural\03_Sheet\1_Plans\Stonewall_A101-106.dwg , 12/05/2017 5:22:27 PM

--

1600 BUFFALO PLACEWINNIPEG, MANITOBA R3T 6B8

TEL: 204-477-1260 | FAX: 204-477-6346 | architecture49.com

CONSULTANT - SUB-CONSULTANT:

COPYRIGHT:

COPYRIGHT IN THIS ELECTRONIC DOCUMENT BELONGS TO ARCHITECTURE49 INC. THIS ELECTRONICDOCUMENT MAY NOT BE FORWARDED TO OTHERS, TRANSMITTED, DOWNLOADED, OR REPRODUCED INANY FORMAT, WHETHER PRINT OR ELECTRONIC, WITHOUT THE EXPRESS, WRITTEN PERMISSION OF THECOPYRIGHT OWNER.

DISCLAIMER:

THE CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND UTILITY LOCATIONS AND REPORTALL ERRORS AND OMISSIONS PRIOR TO COMMENCING WORK.THIS DRAWING IS NOT TO BE SCALED.

--

3

SEE NOTED

--

MJ

JC

ARCHITECTURE

SECOND FLOOR REFLECTED CEILINGPLAN & DETAILS

A1044

0

STONEWALL RCMP DETACHMENT

STONEWALL, MB

1 24/04/2017 ISSUED FOR REVIEW2 12/05/2017 ISSUED FOR TENDER

ISSUED FOR TENDER

Page 5: WALL TYPES: LEGEND · wall types: p1 c1 ew1 stc 50 16 mm type x gypsum board 60 acoustic batt insulation 31 x 64 25 ga steel studs, 600 o.c. max. min. 25 mm air space between existing

CONSTRUCTION KEYNOTES:PATCH AND MAKE GOOD BIRCH SIDING.PROVIDE SOLID BIRCH BASEBOARD.PROVIDE RUBBER BASEBOARD.SECURITY BARRIER, CABINETS & COUNTER. C/W BIRCH

SIDING.PATCH AND MAKE GOOD GB WHERE BIRCH SIDING WAS

REMOVED.PUSH BUTTON DOOR OPERATOR.REINSTALLED BIRCH SIDING.SLIDING PANEL.SPEAKER PORT.EXISTING ALARM PANEL.STORAGE CUBBIES.FULL HEIGHT PARTITION WALL C/W POWERSTORAGE SHELF.PHOTOCOPIER, NOT IN CONTRACT.

1.2.3.4.

5.

6.7.8.9.10.11.12.13.14.

12A105

3A104

14A105

11105

12A105

13A105

9A105

10A105

C2

2A102

P1

C1

18A105

GYM106

PROVIDE PEEL & STICK AIR/VAPOUR BARRIER.OVERLAP & SEAL TO METAL FLASHING & WALL

AIR/VAPOUR BARRIER TO PROVIDECONTINUOUS AIR/VAPOUR BARRIER

C2

VEST.101

THERMALLY BROKEN HMI DOOR FRAME

ALUMINUM THRESHOLD25 mm SAW CUT IN EXISTING

SLAB TO PROVIDE THERMAL BREAKSPRAY FOAM INSULATION

THERMALLY BROKENHMI FRAME BEYOND

19A105

C

C

C

C

A

E

F

C

D

B

1235 4678910

1235 4678910

A

E

F

C

D

B

SEAL:

CLIENT:

PROJECT:

CLIENT REF. #:

ISSUED FOR - REVISION:

DESCRIPTIONDATERV.IS.

ISSUE:

DATE OF:

ORIGINAL SCALE:

CHECKED BY:

DRAWN BY:

RV. #

SHEET #: OF

TITLE:

DISCIPLINE:

1"

IF THIS BAR IS NOT 1"LONG, ADJUST YOUR

PLOTTING SCALE.

PROJECT NO: DATE:

SHEET NUMBER:

DESIGNED BY:

F

F

F F

F F

F

F

F

F

F

F

KEYPLAN:

Arch D-BLG, D:\2014 PROJECTS\149-12549-13 RCMP 5 Detachments\Stonewall\5 Project Documents\5_4 CAD Drawings\08_Architectural\03_Sheet\1_Plans\Stonewall_A101-106.dwg , 12/05/2017 5:22:27 PM

--

1600 BUFFALO PLACEWINNIPEG, MANITOBA R3T 6B8

TEL: 204-477-1260 | FAX: 204-477-6346 | architecture49.com

CONSULTANT - SUB-CONSULTANT:

COPYRIGHT:

COPYRIGHT IN THIS ELECTRONIC DOCUMENT BELONGS TO ARCHITECTURE49 INC. THIS ELECTRONICDOCUMENT MAY NOT BE FORWARDED TO OTHERS, TRANSMITTED, DOWNLOADED, OR REPRODUCED INANY FORMAT, WHETHER PRINT OR ELECTRONIC, WITHOUT THE EXPRESS, WRITTEN PERMISSION OF THECOPYRIGHT OWNER.

DISCLAIMER:

THE CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND UTILITY LOCATIONS AND REPORTALL ERRORS AND OMISSIONS PRIOR TO COMMENCING WORK.THIS DRAWING IS NOT TO BE SCALED.

--

SEE NOTED

--

MJ

JC

ARCHITECTURE

INTERIOR ELEVATIONS & SECTIONS

A1055

0

STONEWALL RCMP DETACHMENT

STONEWALL, MB

1 24/04/2017 ISSUED FOR REVIEW2 12/05/2017 ISSUED FOR TENDER

ISSUED FOR TENDER

Page 6: WALL TYPES: LEGEND · wall types: p1 c1 ew1 stc 50 16 mm type x gypsum board 60 acoustic batt insulation 31 x 64 25 ga steel studs, 600 o.c. max. min. 25 mm air space between existing

ELECTRICAL DRAWINGS

FL01A-12b

A-14

E

A-16c

d

D600

e

A-1,3,51

SF-1

A-2,4,6

A-7,9H10

T1

LPN-102

1

#10

ELECTRICAL SYMBOL NOTESTHE LIGHTING FIXTURE TYPE IS INDICATED BY UPPER CASE LETTERS AND NUMBERS.THE CIRCUIT DESIGNATION IS INDICATED BY LETTERS AND NUMBERS SEPERATED BY DASH.THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.EXAMPLE 1: LIGHTING FIXTURE TYPE "FL01" IS CONNECTED TO PANEL A, CIRCUIT 12 AND CONTROLLED BY SWITCH "b".

EXAMPLE 2: THE FIXTURE TYPE SHOWN AS A NUMERATOR INDICATES ALL LIGHTING FIXTURES IN THE ROOM OR SPACE ARE THE SAME TYPE. THE CIRCUIT NUMBER ANDSWITCH DESIGNATION SHOWN AS A DENOMINATOR INDICATES ALL LIGHTING FIXTURES INTHE ROOM OR SPACE ARE CONNECTED TO THE SAME CIRCUIT, CONTROLLED BY THE SAMESWITCHES, CENTER/OUTBOARD MULTILEVEL SWITCHING.

EXIT LIGHTS. STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING MOUNTING.SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES DIRECTIONAL ARROWON ILLUMINATED FACE(S). THE SIGNAGE TYPE IS INDICATED BY UPPER CASE LETTERS AND NUMBERS PRECEDING THE "/". THE ASSOCIATED BATTERY BANK IS INDICATED BY UPPERCASE LETTERS AND NUMBERS FOLLOWING THE "/". THE AC CIRCUIT DESIGNATION IS INDICATED BY A NUMBER. EXAMPLE: THE WALL MOUNTED EXIT LIGHT TYPE "EX1" WITH SINGLE FACE AND DIRECTIONAL ARROW IS CONNECTED TO BATTERY BANK "BU1" AND AC CIRCUIT 14 FROM PANEL A .

DEVICES. THE CIRCUIT DESIGNATION IS INDICATED BY A NUMBER. THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER. EXAMPLE: SPLIT DUPLEXRECEPTACLE IS CONNECTED TO PANEL A, CIRCUIT 16 AND ONE RECEPTACLE OUTLET ISCONTROLLED BY SWITCH "c".THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER. EXAMPLE:SINGLE POLE SWITCH "d" TO CONTROL LIGHTING FIXTURES INDICATED BY "d".

WALL BOX DIMMER WITH SIZE AS INDICATED AT DEVICE. EXAMPLE: 600 WATT WALL BOXDIMMER TO CONTROL LIGHTING FIXTURES INDICATED BY "e". SEE SPECIFICATIONS FORWATTAGE IF NOT INDICATED.SPECIAL CONNECTIONS. THE EQUIPMENT IS INDICATED BY A NUMBER IN A CIRCLE. SEETHE MOTOR AND EQUIPMENT SCHEDULE FOR THE LOAD DESCRIPTION AND TYPE OFCONNECTION. THE CIRCUIT DESIGNATION IS INDICATED BY A NUMBER(S) ADJACENT TOTHE SYMBOL. EXAMPLE: EQUIPMENT NO. 1; 3 PHASE CONNECTION TO PANEL A, CIRCUITS 1, 3, 5.

MOTOR CONNECTIONS. THE MOTOR IS INDICATED BY A NUMBER WITHIN ORCHARACTERS ADJACENT TO THE MOTOR SYMBOL. SEE THE MOTOR AND EQUIPMENTSCHEDULE FOR THE MOTOR DESCRIPTION AND ELECTRICAL REQUIREMENTS. THECIRCUIT DESIGNATION IS INDICATED BY A NUMBER(S) ADJACENT TO THE SYMBOL.EXAMPLE: MOTOR SF-1; 3 PHASE CONNECTION TO PANEL A, CIRCUITS 2, 4, 6.ELECTRIC HEATER CONNECTIONS. THE HEATER TYPE IS INDICATED BY A NUMBERFOLLOWING THE UPPER CASE LETTER "H". SEE THE HEATER SCHEDULE FORELECTRICAL REQUIREMENTS. THE CIRCUIT DESIGNATION IS INDICATED BY A NUMBER(S) ADJACENT TO THE HEATER. EXAMPLE: ELECTRIC BASEBOARD HEATERTYPE "H10" CONNECTED TO PANEL A, CIRCUITS 7, 9.TRANSFORMERS. THE TRANSFORMER TYPE IS INDICATED BY A NUMBER FOLLOWINGTHE UPPER CASE LETTER "T". SEE THE TRANSFORMER SCHEDULE OR THE SINGLE LINEDIAGRAM FOR THE TRANSFORMER DESCRIPTION AND REQUIREMENTS. EXAMPLE:TRANSFORMER TYPE "T1".PANELBOARDS. PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING SIDE OFRECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR DESIGNATIONCODES.KEYNOTE. SEE THE KEYED NOTES ON THAT SHEET FOR THE NOTE NUMBERINDICATED.CONDUIT SHOWN WITHOUT SLASH MARKS SHALL CONTAIN 2 # 12 CONDUCTORS IN 3/4"CONDUIT UNLESS SPECIFIC EQUIPMENT REQUIRES A DIFFERENT SIZE.CONDUIT SHOWN WITH SLASH MARKS SHALL CONTAIN 1 # 12 CONDUCTOR PER SLASHMARK IN 3/4" CONDUIT UNLESS A CONDUCTOR AND CONDUIT SIZE IS SHOWN ADJACENTTO THE SLASH MARKS. SLASH MARK INDICATORS ARE: SHORT STRAIGHT=PHASECONDUCTOR, LONG STRAIGHT=NEUTRAL CONDUCTOR, SHORT BENT ENDED=SWITCH LEGS, LONG STRAIGHT WITH A DOT=GROUND CONDUCTOR, CHEVRON=CATEGORY 6,HALF CHEVRON=CATEGORY 3, TWIST=SHIELDED TWISTED PAIR, CONCENTRIC CIRCLEAND DOT=COAX CABLE.HOME RUN TO BRANCH CIRCUIT PANELBOARD. THE PANELBOARD DESIGNATION ISSHOWN ADJACENT TO THE HOME RUN ARROW AS A NUMERATOR AND THE CIRCUITDESIGNATION IS SHOWN AS THE DENOMINATOR. CIRCUIT BREAKER SIZES(AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANELBOARD SCHEDULE WITH THECORRESPONDING PANELBOARD AND CIRCUIT DESIGNATION. EXAMPLE: HOME RUN TOPANELBOARD LPN-102; CIRCUITS 1, 3, 5.SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE A UNITTYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.

* P2D/I *A-2aba

LPN-1021,3,5

EX1/BU1

FIRE PROTECTION REQUIREMENTS

A. PENETRATIONS IN WALLS REQUIRING PROTECTED OPENINGS MUST BE FIRESTOPPED WITH AN APPROVED MATERIAL.

1. CONDUITS MAY PENETRATE WALLS OR PARTITIONS, PROVIDED THEY ARE FIRE-STOPPED.

2. OPENINGS FOR STEEL ELECTRICAL BOXES NOT EXCEEDING 16 SQUARE INCHES ARE PERMITTED PROVIDED OPENINGS DO NOT AGGREGATE MORE THAN 100 SQUARE INCHES FOR ANY 100 SQUARE FEET OF WALL OR PARTITION.

3. OUTLET BOXES ON OPPOSITE SIDES OF WALLS OR PARTITIONS MUST BE SEPARATED BY A HORIZONTAL DISTANCE OF 24 INCHES.

B. LIGHT FIXTURES AND OTHER APPARATUS INSTALLED IN AN ACOUSTICAL CEILING GRID SHALL BE INDEPENDENTLY SUPPORTED.

C. RECESSED LIGHTING FIXTURES INSTALLED IN FIRE RATED CEILING ASSEMBLIES SHALL BE FIRE RATED FIXTURES BEARING THE ULC FIRE RATED LABEL. FIXTURES SHALL BE INSTALLED IN ACCORDANCE WITH THE ULC FIRE RESISTANCE DIRECTORY, AND SHALL INCLUDE A FIRE RATED ENCLOSURE INSTALLED OVER THE FIXTURE THAT MEETS THE REQUIREMENTS OF THE ULC FIRE RESISTANCE DIRECTORY.

SPECIFIC CODE NOTES

A. THE GENERAL NOTES AS DESCRIBED HEREIN, APPLY TO ALL DRAWINGS IN THIS PACKAGE WHERE APPLICABLE.

B. PENETRATIONS IN WALLS OR SEPERATIONS, REQUIRING PROTECTED OPENINGS SHALL BE FIRESTOPPED WITH AN APPROVED MATERIAL.

C. EXPOSED WIRING SHALL NOT BE PERMITTED. WIRING SHALL BE RECESSED IN WALL, OR WHERE WALLS ARE NOT ACCESSIBLE DUE TO WALL CONSTRUCTION (CONCRETE BLOCK, CONCRETE, BRICK, ETC), PROVIDE CONDUIT AS REQUIRED TO CONCEAL SAME.

D. REFER TO ARCHITECTURAL FLOOR PLANS, ELEVATIONS AND DETAILS, INCLUDING MILLWORK DETAILS AND SHOP DRAWINGS FOR COORDINATION OF ELECTRICAL DEVICE LOCATIONS, METHOD OF INSTALLATION & MOUNTING HEIGHTS. ARCHITECTURAL FLOOR PLANS, ELEVATIONS AND DETAILS TAKE PRECEDENCE OVER LOCATIONS SHOWN ON ELECTRICAL DRAWINGS.

E. UNLESS NOTED OTHERWISE, THE CIRCUITING INDICATED ON THE DRAWINGS IS REPRESENTATIONAL ONLY. CONFIRM CIRCUITING REQUIREMENTS ON SITE.

F. CIRCUIT NUMBERS AT DEVICES CORRESPOND TO PANELBOARD BREAKERS (SEE PANELBOARD SCHEDULE). BRANCH CIRCUITS SHALL BE SIZED ACCORDING TO THE CIRCUIT BREAKER RATING AND VOLTAGE DROP REQUIREMENTS, UNLESS INDICATED OTHERWISE ON THE ELECTRICAL EQUIPMENT SCHEDULE.

G. MINIMUM CONDUIT SIZE SHALL BE 21mm (3/4") UNLESS NOTED OTHERWISE.H. CONDUIT AND WIRE SHALL NOT BE INSTALLED BELOW FLOOR SLAB UNLESS

INDICATED ON PLAN BY DASHED CONDUIT/LINE.I. EMPTY CONDUIT SHALL BE C/W PULL WIRE AND PLASTIC BUSHINGS.J. ALL RECESSED LIGHTING FIXTURES IN LAY-IN CEILINGS SHALL BE INSTALLED

WITH 6' LONG FLEXIBLE METAL CONDUIT.K. WHERE CONNECTED TO A 20A. BRANCH CIRCUIT SUPPLYING AN INDIVIDUAL

RECEPTACLE (SIMPLEX OR DUPLEX), THE RECEPTACLE SHALL BE RATED AT 20A.L. CONTRACTOR SHALL BE RESPONSIBLE FOR WIRING ALL ELECTRICAL ITEMS

SHOWN ON THE DRAWINGS, INCLUDING THE FOLLOWING, UNLESS NOTED OTHERWISE:

M. REFER TO ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR PHASES OF DEMOLITION AND CONSTRUCTION. COORDINATE WITH GENERAL CONSTRUCTION.

N. AS INDICATED IN THE GENERAL NOTES, DEMOLITION NOTES, AND KEYNOTES IN THIS DRAWING PACKAGE, UNLESS NOTED OTHERWISE, THE TERM "DEMOLISH" SHALL INCLUDE THE COMPLETE REMOVAL OF THE EXISTING ITEM IDENTIFIED, C/W ASSOCIATED WIRING, CONDUIT AND JUNCTION BOXES BACK TO LAST REMAINING DEVICE OR SOURCE. CIRCUITS FREED UP FROM DEMOLISHED ELECTRICAL, SHALL BECOME SPARE. REFER TO THE RENOVATION DRAWING KEY NOTES FOR FURTHER REQUIREMENTS.

O. AS INDICATED IN THE GENERAL NOTES, DEMOLITION NOTES, AND KEYNOTES IN THIS DRAWING PACKAGE, UNLESS NOTED OTHERWISE, THE TERM "REMOVE & REPLACE" SHALL INCLUDE THE COMPLETE REMOVAL & REPLACEMENT OF THE EXISTING ITEM IDENTIFIED IN ITS CURRENT LOCATION, WITH A NEW ITEM, UTILIZING THE EXISTING OUTLET BOX AND WIRING. REFER TO THE RENOVATION DRAWING KEY NOTES FOR FURTHER REQUIREMENTS.

P. AS INDICATED IN THE GENERAL NOTES, DEMOLITION NOTES, AND KEY NOTES, UNLESS NOTED OTHERWISE, THE TERM "RELOCATE" SHALL INCLUDE THE COMPLETE RELOCATION OF THE EXISTING ITEM IDENTIFIED IN ITS CURRENT LOCATION ON THE DEMOLITION DRAWINGS, TO THE NEW LOCATION AS INDICATED ON THE RENOVATION DRAWINGS. INCLUDE ALL LABOUR AND MATERIALS TO REROUTE/EXTEND/REFEED THE EXISTING CIRCUITRY AS REQUIRED TO ACCOMMODATE THE RELOCATION. REFER TO THE RENOVATION DRAWING KEY NOTES FOR FURTHER REQUIREMENTS.

Q. SITE CONFIRM ANY ELECTRICAL WITHIN AREAS OF RENOVATION REQUIRING RELOCATION TO ACCOMMODATE THE RENOVATION.

R. PROVIDE WIRE AND CONDUIT AS REQUIRED FOR CONTINUITY OF ANY FEEDERS OR BRANCH CIRCUITS ORIGINATING OUTSIDE THE DEMOLITION AREA THAT SERVES ANY ELECTRICAL EQUIPMENT OR DEVICES TO REMAIN AFTER DEMOLITION. MODIFY OR REPLACE AS REQUIRED.

S. PROVIDE CONDUIT AND/OR COMMUNICATIONS/DATA WIRING AS NECESSARY FOR CONTINUITY OF ANY COMMUNICATIONS/DATA SYSTEMS ORIGINATING OUTSIDE THE DEMOLITION AREA THAT SERVES ANY COMMUNICATIONS/DATA EQUIPMENT OR DEVICES TO REMAIN AFTER DEMOLITION. MODIFY OR REPLACE AS REQUIRED.

T. PROVIDE BLANK COVERPLATES OVER ALL EXISTING UNUSED OPENINGS.U. DEMOLISH ALL ELECTRICAL DEVICES IN WALLS TO BE DEMOLISHED. WALLS TO BE

DEMOLISHED ARE SHOWN DASHED. DISCONNEC AND REMOVE ASSOCIATED.V. ALL NEW WIRING SHALL BE CONCEALED WHERE POSSIBLE. UTILIZE CRAWLSPACE

AND/OR ACCESSIBLE CEILING SPACE TO RUN NEW WIRING AS REQUIRED AND FISH INTO WALLS/MILLWORK.

W. WHERE EXISTING WALLS ARE TO BE OPENED FOR INSTALLATION OF NEW WIRING, COORDINATE WITH GENERAL CONTRACTOR ROUTING OF SAME. ARRANGE AND PAY FOR ALL CUTTING/REPAIR/PATCHING AS REQUIRED.

X. WHERE BRANCH CIRCUIT BREAKERS ARE REMOVED, PROVIDE FILLER PLATES FOR BREAKER SPACES.

Y. CIRCUIT BREAKERS SHALL MATCH EXISTING. CONFIRM SHORT CIRCUIT RATING AND TYPE ON SITE, PRIOR TO FINALIZING PRICING.

Z. UTILIZE SPARE/FREED UP CIRCUITS FROM DEMOLITION AS REQUIRED TO ACCOMODATE THE ADDITIONAL CIRCUITING REQUIREMENTS IN THE RENOVATION.

AA. PROVIDE NEW TYPEWRITTEN PANEL DIRECTORIES TO ACCOMMODATE UPDATED CIRCUITING. NEW BREAKERS IN DISTRIBUTION PANELS SHALL BE LABELLED USING LAMACOIDS.

GENERAL ELECTRICAL NOTES

1P 1 POLE (2P, 3P, 4P, ETC.)

A AMPEREADO AUTOMATIC DOOR OPENERAFF ABOVE FINISHED FLOORANNUN ANNUNCIATORAPPROX APPROXIMATELYARCH ARCHITECT, ARCHITECTURALAUTO AUTOMATICAUX AUXILIARYAWG AMERICAN WIRE GAUGE

BLDG BUILDING

C CONDUITCAB CABINETCB CIRCUIT BREAKERCKT CIRCUITCLG CEILINGCONN CONNECTIONCONST CONSTRUCTIONCONT CONTINUATION OR CONTINUOUSCONTR CONTRACTORCTR CENTERCU COPPERC/W COMPLETE WITH

DET DETAILDIA DIAMETERDISC DISCONNECTDIST DISTRIBUTIONDN DOWNDWG DRAWING

EC ELECTRICAL CONTRACTORELEC ELECTRIC, ELECTRICALEM EMERGENCYEMT ELECTRICAL METALLIC TUBINGEQUIP EQUIPMENTEXIST EXISTING

FA FIRE ALARMFACP FIRE ALARM CONTROL PANELFIXT FIXTURE

FLR FLOORFR REFRIGERATOR

GC GENERAL CONTRACTORGFI GROUND FAULT CIRCUIT

INTERRUPTERGYP BD GYPSUM BOARD

HORIZ HORIZONTALHT HEIGHT

HTR HEATERHVAC HEATING, VENTILATING AND

AIR CONDITIONING

INCAND INCANDESCENTIPLC INTELLIGENT PARKING LOT

CONTROLLER

J-BOX JUNCTION BOX

KW KILOWATT

LOC LOCATE OR LOCATIONLT LIGHTLTG LIGHTING

MAX MAXIMUMMCB MAIN CIRCUIT BREAKERMDC MAIN DISTRIBUTION CENTERMDP MAIN DISTRIBUTION PANELMEC MECHANICAL CONTRACTORMFR MANUFACTURERMFS MAIN FUSED DISCONNECT SWITCHMIN MINIMUMMISC MISCELLANEOUSMLO MAIN LUGS ONLYMT MOUNTMTD MOUNTEDMW COORDINATED IN MILLWORK

NEC NATIONAL ELECTRICAL CODENIC NOT IN CONTRACTNL NIGHT LIGHT

NTS NOT TO SCALE

PB PULL BOX OR PUSHBUTTONPED PEDESTALPH PHASEPNL PANELPVC POLYVINYL CHLORIDE (CONDUIT)PWR POWER

QUAN QUANTITY

R RELOCATEDRCPT RECEPTACLEREQD REQUIRED

SC SURFACE CONDUITSHT SHEETSIM SIMILARSPEC SPECIFICATIONSP SPARESU SUMP PUMPSURF SURFACE MOUNTEDSW SWITCHSYM SYMMETRICALSYS SYSTEMTEL/DATA TELEPHONE/DATAT-STAT THERMOSTATTYP TYPICAL

UC UNDER COUNTERUH UNIT HEATERUTIL UTILITY

V VOLTVA VOLT-AMPERESVERT VERTICAL

W WATTW/ WITHWG WIRE GUARDW/O WITHOUTWP WEATHERPROOF

ELECTRICAL ABBREVIATIONS LIST

SYMBOL

*** DISTANCE TO HIGHEST OPERABLE PART OF EQUIPMENT

78"** CIRCUIT BREAKER PANEL

2 POLE SINGLE THROW SW.SINGLE POLE SW.

DIMMER SWITCHOCCUPANCY SENSOR SWITCHPUSH BUTTON

DUPLEX RECEPT.

ALL DISTANCES ARE TO CENTER OF DEVICE OR EQUIPMENT UNLESS OTHERWISE NOTED. DEVICES INDICATED AT 47" MAY NOT BE INSTALLED WITH ANY OPERABLE PART HIGHER THAN 47". DEVICES MAY BE INSTALLED IN CONCRETE MASONRY UNITS WITH THE TOP OF THE DEVICE AT 47".* DISTANCE ABOVE TOP OF DOOR FRAME

47"47"

2

3 3-WAY SW.4-WAY SW.

** DISTANCE TO TOP OF EQUIPMENT OR DEVICE

DASHED SYMBOL INDICATES REMOVEDLIGHT SYMBOL INDICATES EXISTING

AS NOTED

IRSO

78"**78"**

SF-1

LIGHT LEVEL SENSOR - TYPE DENOTEDPHOTOCELL

POWER OR DISTRIBUTION PANEL

MOTOR (SEE SCHEDULE)SPECIAL CABINET (TYPE DENOTED)

16"16"

DESCRIPTION

WALL MOUNTED FLOODLIGHT (TYPE DENOTED)

SURFACE INCANDESCENT LIGHT (TYPE DENOTED)

POLE MOUNTED LIGHT (TYPE DENOTED)RECESSED LIGHT (TYPE DENOTED)

SURFACE LIGHT (TYPE DENOTED)

EXIT SIGN (TYPE DENOTED)

SUSPENDED OR PENDANT LIGHT (TYPE DENOTED)SURFACE LIGHT (TYPE DENOTED)

STRIP LIGHT (TYPE DENOTED)EMERGENCY BATTERY LIGHT (TYPE DENOTED)

RECESSED LIGHT (TYPE DENOTED)

PER SCHED

12"*

96"

P2P1

E E

EM

H

ST1

G

AA

R

AS NOTED

HT AFF

AS NOTED

SYMBOL

A

C

B

D AS NOTEDAS NOTED

J J

1

HT AFF SYMBOL

SPECIAL RECEPT. OR CONN. (SEE SCHEDULE)JUNCTION BOXPULL BOX

DESCRIPTION HT AFF

**** DISTANCE BELOW CEILING ***** DISTANCE TO BOTTOM OF DEVICE

COMMUNICATION OUTLET (TYPE DENOTED)TELEPHONE OUTLET (TYPE DENOTED)

TELEVISION OUTLET

DOOR CONTACTS

CARD READER

ELECTRIC STRIKEES

KEYPAD

F.A. PULLSTATION

F.A. DOOR CLOSERF.A. DOOR HOLDER

END OF LINE RESISTORELR

F P

HEAT DETECTOR (TYPE & TEMP DENOTED)

HT AFFDESCRIPTION

FIRE ALARM BELL

SMOKE DETECTOR (TYPE & CO DENOTED)

FIRE ALARM STROBE (CANDELAS)

R/F135

P

R/F135

DESCRIPTION

FIRE ALARM HORNFIRE ALARM HORN W/STROBE (CANDELAS)

SYMBOL

F

110cd

F

ELECTRICAL SYMBOL LEGEND

AS NOTED 47"47"47"47"47"

16"

4

D

OS

PB

ASL

CP

OCCUPANCY SENSOR - TYPE DENOTED

16"

47"***47"***

47"***

8"****

92"**92"**92"**92"**

110cd

F

F

F

8"**** SELF-CONTAINED SMOKE ALARM (CO DENOTES COMBO)CO

8"**** SELF-CONTAINED AV SMOKE ALARM

P

72"** FIRE ALARM REMOTE ANNUNCIATOR FA ANNUN

DC

CR

MAGNETIC LOCKML

COMBINATION LOCKCL

IR

# KEYED NOTE (SEE SCHEDULE)

LIGHTING LIGHTING CONTROL

RECEPTACLES

EQUIPMENT

COMMUNICATION

SECURITY

FIRE ALARM

GENERAL ELECTRICAL

DUPLEX RECEPT MTD ABOVE COUNTERDUPLEX RECEPT MTD IN MILLWORKDUPLEX RECEPT C/W WET LOCATION COVERPLATE DUPLEX RECEPT C/W INTEGRAL GFIDUPLEX RECEPT NEMA 5-20R CONFIG

AUTOMATIC DOOR OPERATOR PUSHBUTTON

EMERGENCY LIGHT - DOUBLE REMOTE HEADEMERGENCY LIGHT - SINGLE REMOTE HEAD

36"36"

****** DISTANCE ABOVE COUNTER

# DEMOLITION NOTE (SEE SCHEDULE)## REVISION TAG

8"**** SELF-CONTAINED CO ALARM

CO

Certificate of Authorization

Epp Siepman Engineering Inc.

No. 4035

10 9 8 7 6 5 4 3 2 1

10 9 8 7 6 5 4 3 2 1

F

E

D

C

B

A

F

E

D

C

B

A

F F C F F

F

C

F

FFCFF

F

C

F

CONSULTANT - SUB-CONSULTANT:

KEYPLAN:

SEAL:

CLIENT:

CLIENT REF. #:

PROJECT:

DISCLAIMER: COPYRIGHT:

ISSUED FOR - REVISION:

THIS DRAWING AND DESIGN IS COPYRIGHT PROTECTED WHICH SHALL NOT BE USED, REPRODUCED OR REVISED WITHOUT WRITTEN PERMISSION BY WSP CANADA INC. THE CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND UTILITY LOCATIONS AND REPORT ALL ERRORS AND OMISSIONS PRIOR TO COMMENCING WORK. THIS DRAWING IS NOT TO BE SCALED.

GGH-46-10

RV. DATE DESCRIPTION

PROJECT NO.

ORIGINAL SCALE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

DISCIPLINE:

TITLE:

SHEET NUMBER:

ISSUE:

SHEET #:

DATE OF:

IF THIS BAR IS NOT 1"LONG, ADJUST YOUR

PLOTTING SCALE.

1"

--

--

-- OF --

RV. #

0

NTS

ELECTRICAL

As indicated

STONEWALL, MB

17042

ELECTRICAL SYMBOLS ANDABBREVIATIONS

STONEWALL RCMPDETACHMENT

E0.1

ML/MM

ML/MM

JF/MP

400 - 136 Market AvenueWinnipeg, MB R3B 0P4

T 204 453 1080

RCMP OFFICE - STONEWALL E0.1 ELECTRICAL SYMBOLS AND ABBREVIATIONS E1.1 ELECTRICAL SITE PLAN ED1.1 ELECTRICAL SITE DEMOLITION PLAN ED2.1 MAIN FLOOR - DEMOLITION PLAN ED2.2 SECOND FLOOR - DEMOLITION PLAN EL2.1 MAIN FLOOR - LIGHTING PLAN EL2.2 SECOND FLOOR - LIGHTING PLAN EP2.1 MAIN FLOOR - POWER PLAN EP2.2 SECOND FLOOR - POWER PLAN E6.1 ELECTRICAL SCHEDULES

0 May 12, 2017 Issued for Tender

1 10

Page 7: WALL TYPES: LEGEND · wall types: p1 c1 ew1 stc 50 16 mm type x gypsum board 60 acoustic batt insulation 31 x 64 25 ga steel studs, 600 o.c. max. min. 25 mm air space between existing

(TYP)1

(TYP)1

(TYP)2

(TYP)2

(TYP)3

(TYP)3

PL1 PL1

EXT02

PL1 PL1

PL1

EXT01EXT01

EXT01 EXT01

EXT02

EXT02

EXT01 EXT01 EXT01

N

Certificate of Authorization

Epp Siepman Engineering Inc.

No. 4035

10 9 8 7 6 5 4 3 2 1

10 9 8 7 6 5 4 3 2 1

F

E

D

C

B

A

F

E

D

C

B

A

F F C F F

F

C

F

FFCFF

F

C

F

CONSULTANT - SUB-CONSULTANT:

KEYPLAN:

SEAL:

CLIENT:

CLIENT REF. #:

PROJECT:

DISCLAIMER: COPYRIGHT:

ISSUED FOR - REVISION:

THIS DRAWING AND DESIGN IS COPYRIGHT PROTECTED WHICH SHALL NOT BE USED, REPRODUCED OR REVISED WITHOUT WRITTEN PERMISSION BY WSP CANADA INC. THE CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND UTILITY LOCATIONS AND REPORT ALL ERRORS AND OMISSIONS PRIOR TO COMMENCING WORK. THIS DRAWING IS NOT TO BE SCALED.

GGH-46-10

RV. DATE DESCRIPTION

PROJECT NO.

ORIGINAL SCALE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

DISCIPLINE:

TITLE:

SHEET NUMBER:

ISSUE:

SHEET #:

DATE OF:

IF THIS BAR IS NOT 1"LONG, ADJUST YOUR

PLOTTING SCALE.

1"

--

--

-- OF --

RV. #

0

NTS

ELECTRICAL

1 : 100

STONEWALL, MB

17042

ELECTRICAL SITE PLAN

STONEWALL RCMPDETACHMENT

E1.1

ML/MM

ML/MM

JF/MP

400 - 136 Market AvenueWinnipeg, MB R3B 0P4

T 204 453 1080

E1.1 SCALE: 1 : 100

2 SITE PLAN - ELECTRICAL - STONEWALL

0 May 12, 2017 Issued for Tender

2 10

KEY NOTES1 EXISTING POLE TO REMAIN. REMOVE AND REPLACE LIGHT FIXTURE ONLY.

UTILIZE EXISTING CONTROL.2 CONFIRM DIMENSIONS OF EXISTING EXTERIOR SOFFIT LIGHT FIXTURES

AND NEW SOFFIT LIGHT FIXTURES BEFORE DEMOLITION.3 REMOVE AND REPLACE WALL LIGHT FIXTURES. UTILIZE EXISTING

CONTROL.

Page 8: WALL TYPES: LEGEND · wall types: p1 c1 ew1 stc 50 16 mm type x gypsum board 60 acoustic batt insulation 31 x 64 25 ga steel studs, 600 o.c. max. min. 25 mm air space between existing

A. DRAWING RECORDS OF THE EXISTING FLOOR PLANS HAVE BEEN COMPILED FROM INFORMATION SUBMITTED BY THE OWNER AND FROM SITE OBSERVATIONS AS NOTED BY THE CONSULTANT. THE ACCURACY OF THESE DRAWING RECORDS IS LIMITED TO THE EXTENT OF KNOWN CONSTRUCTION INFORMATION.

B. WIRING OF LIGHT FIXTURES TO BE MODIFIED AND EXTENDED AS REQUIRED. UTILIZE EXISTING CIRCUITS AND CONTROL UNLESS OTHERWISE NOTED.

GENERAL NOTES

(TYP)1

(TYP)1

(TYP)2

(TYP)2

(TYP)3

(TYP)3

(TYP)3

N

Certificate of Authorization

Epp Siepman Engineering Inc.

No. 4035

10 9 8 7 6 5 4 3 2 1

10 9 8 7 6 5 4 3 2 1

F

E

D

C

B

A

F

E

D

C

B

A

F F C F F

F

C

F

FFCFF

F

C

F

CONSULTANT - SUB-CONSULTANT:

KEYPLAN:

SEAL:

CLIENT:

CLIENT REF. #:

PROJECT:

DISCLAIMER: COPYRIGHT:

ISSUED FOR - REVISION:

THIS DRAWING AND DESIGN IS COPYRIGHT PROTECTED WHICH SHALL NOT BE USED, REPRODUCED OR REVISED WITHOUT WRITTEN PERMISSION BY WSP CANADA INC. THE CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND UTILITY LOCATIONS AND REPORT ALL ERRORS AND OMISSIONS PRIOR TO COMMENCING WORK. THIS DRAWING IS NOT TO BE SCALED.

GGH-46-10

RV. DATE DESCRIPTION

PROJECT NO.

ORIGINAL SCALE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

DISCIPLINE:

TITLE:

SHEET NUMBER:

ISSUE:

SHEET #:

DATE OF:

IF THIS BAR IS NOT 1"LONG, ADJUST YOUR

PLOTTING SCALE.

1"

--

--

-- OF --

RV. #

0

NTS

ELECTRICAL

As indicated

STONEWALL, MB

17042

ELECTRICAL SITE DEMOLITIONPLAN

STONEWALL RCMPDETACHMENT

ED1.1

ML/MM

ML/MM

JF/MP

400 - 136 Market AvenueWinnipeg, MB R3B 0P4

T 204 453 1080

KEY NOTES1 DEMOLISH LIGHT FIXTURE FROM POLE. EXISTING POLE TO REMAIN.2 CONFIRM DIMENSIONS OF EXISTING EXTERIOR SOFFIT LIGHT FIXTURES

AND NEW SOFFIT LIGHT FIXTURES BEFORE DEMOLITION.3 REMOVE AND REPLACE WALL LIGHT FIXTURES. UTILIZE EXISTING

CONTROL.

ED1.1 SCALE: 1 : 100

1 SITE DEMOLITION PLAN - ELECTRICAL - STONEWALL

3 10

0 May 12, 2017 Issued for Tender

Page 9: WALL TYPES: LEGEND · wall types: p1 c1 ew1 stc 50 16 mm type x gypsum board 60 acoustic batt insulation 31 x 64 25 ga steel studs, 600 o.c. max. min. 25 mm air space between existing

(TYP)1

2

2

22

A. DRAWING RECORDS OF THE EXISTING FLOOR PLANS HAVE BEEN COMPILED FROM INFORMATION SUBMITTED BY THE OWNER AND FROM SITE OBSERVATIONS AS NOTED BY THE CONSULTANT. THE ACCURACY OF THESE DRAWING RECORDS IS LIMITED TO THE EXTENT OF KNOWN CONSTRUCTION INFORMATION.

B. WIRING OF LIGHT FIXTURES TO BE MODIFIED AND EXTENDED AS REQUIRED. UTILIZE EXISTING CIRCUITS AND CONTROL UNLESS OTHERWISE NOTED.

GENERAL NOTES

N

Certificate of Authorization

Epp Siepman Engineering Inc.

No. 4035

10 9 8 7 6 5 4 3 2 1

10 9 8 7 6 5 4 3 2 1

F

E

D

C

B

A

F

E

D

C

B

A

F F C F F

F

C

F

FFCFF

F

C

F

CONSULTANT - SUB-CONSULTANT:

KEYPLAN:

SEAL:

CLIENT:

CLIENT REF. #:

PROJECT:

DISCLAIMER: COPYRIGHT:

ISSUED FOR - REVISION:

THIS DRAWING AND DESIGN IS COPYRIGHT PROTECTED WHICH SHALL NOT BE USED, REPRODUCED OR REVISED WITHOUT WRITTEN PERMISSION BY WSP CANADA INC. THE CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND UTILITY LOCATIONS AND REPORT ALL ERRORS AND OMISSIONS PRIOR TO COMMENCING WORK. THIS DRAWING IS NOT TO BE SCALED.

GGH-46-10

RV. DATE DESCRIPTION

PROJECT NO.

ORIGINAL SCALE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

DISCIPLINE:

TITLE:

SHEET NUMBER:

ISSUE:

SHEET #:

DATE OF:

IF THIS BAR IS NOT 1"LONG, ADJUST YOUR

PLOTTING SCALE.

1"

--

--

-- OF --

RV. #

0

NTS

ELECTRICAL

As indicated

STONEWALL, MB

17042

MAIN FLOOR - DEMOLITION PLAN

STONEWALL RCMPDETACHMENT

ED2.1

ML/MM

ML/MM

JF/MP

400 - 136 Market AvenueWinnipeg, MB R3B 0P4

T 204 453 1080

KEY NOTES1 REMOVE EXISTING LAMP AND REPLACE WITH A19 LED LAMP WITH MEDIUM BASE.2 REMOVE AND REPLACE EXIT SIGNS WITH PICTOGRAM STYLE EXIT SIGNS,

ED2.1 SCALE: 1 : 50

1 MAIN FLOOR - DEMOLITION - STONEWALL

0 May 12, 2017 Issued for Tender

4 10

Page 10: WALL TYPES: LEGEND · wall types: p1 c1 ew1 stc 50 16 mm type x gypsum board 60 acoustic batt insulation 31 x 64 25 ga steel studs, 600 o.c. max. min. 25 mm air space between existing

(TYP)1

(TYP)2

3

4

A. DRAWING RECORDS OF THE EXISTING FLOOR PLANS HAVE BEEN COMPILED FROM INFORMATION SUBMITTED BY THE OWNER AND FROM SITE OBSERVATIONS AS NOTED BY THE CONSULTANT. THE ACCURACY OF THESE DRAWING RECORDS IS LIMITED TO THE EXTENT OF KNOWN CONSTRUCTION INFORMATION.

B. WIRING OF LIGHT FIXTURES TO BE MODIFIED AND EXTENDED AS REQUIRED. UTILIZE EXISTING CIRCUITS AND CONTROL UNLESS OTHERWISE NOTED.

GENERAL NOTES

N

Certificate of Authorization

Epp Siepman Engineering Inc.

No. 4035

10 9 8 7 6 5 4 3 2 1

10 9 8 7 6 5 4 3 2 1

F

E

D

C

B

A

F

E

D

C

B

A

F F C F F

F

C

F

FFCFF

F

C

F

CONSULTANT - SUB-CONSULTANT:

KEYPLAN:

SEAL:

CLIENT:

CLIENT REF. #:

PROJECT:

DISCLAIMER: COPYRIGHT:

ISSUED FOR - REVISION:

THIS DRAWING AND DESIGN IS COPYRIGHT PROTECTED WHICH SHALL NOT BE USED, REPRODUCED OR REVISED WITHOUT WRITTEN PERMISSION BY WSP CANADA INC. THE CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND UTILITY LOCATIONS AND REPORT ALL ERRORS AND OMISSIONS PRIOR TO COMMENCING WORK. THIS DRAWING IS NOT TO BE SCALED.

GGH-46-10

RV. DATE DESCRIPTION

PROJECT NO.

ORIGINAL SCALE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

DISCIPLINE:

TITLE:

SHEET NUMBER:

ISSUE:

SHEET #:

DATE OF:

IF THIS BAR IS NOT 1"LONG, ADJUST YOUR

PLOTTING SCALE.

1"

--

--

-- OF --

RV. #

0

NTS

ELECTRICAL

As indicated

STONEWALL, MB

17042

SECOND FLOOR - DEMOLITIONPLAN

STONEWALL RCMPDETACHMENT

ED2.2

ML/MM

ML/MM

JF/MP

400 - 136 Market AvenueWinnipeg, MB R3B 0P4

T 204 453 1080

KEY NOTES1 REMOVE EXISTING LAMP AND REPLACE WITH A19 LED LAMP WITH MEDIUM BASE.2 REMOVE AND REPLACE LIGHT FIXTURE ONLY. USE EXISTING CHAIN HANGERS,

WIRING AND CONTROL.3 REMOVE AND REPLACE EXIT SIGNS WITH PICTOGRAM STYLE EXIT SIGNS,4 REMOVE AND REPLACE ALL EXISTING EMERGENCY LIGHTING REMOTE HEADS.

ED2.2 SCALE: 1 : 50

1 SECOND FLOOR - DEMOLITION - STONEWALL

0 May 12, 2017 Issued for Tender

5 10

Page 11: WALL TYPES: LEGEND · wall types: p1 c1 ew1 stc 50 16 mm type x gypsum board 60 acoustic batt insulation 31 x 64 25 ga steel studs, 600 o.c. max. min. 25 mm air space between existing

OS OS

OS

OS

OSOS

OS OS

OSOS

OS

OS

EXT01

SL03

SL03

SL03

WL02

RL03 a

RL03 aRL03 a

RL03 a

RL03 a RL03 b

RL03 b RL03 b

RL03 bRH01

SL08

RL03 RL03

SL08

SL08

WL02

RL02 RL02 RL02RL05

RL03

SL01

EB20H6V

RL03 aSL03

SL03

WL02

RL03RL03RL03 RL03

SL08

SL08

RL03

EX1

EX1

SL06RH03

SL01

RH01

EX1

SL08

SL08

SL06

EXT01

EXT01 EXT01

EXT01

EXT01

EXT02

EXT02

EXT02

EXT02

EXT02

SL01 SL01

SL01SL01 SL01

SL08

WL01

WL01

SL06 SL06SL06SL06

EX1

SL08

RL03RL03

EXT01

EX1EX1

SL08 SL08

SL02 SL02 SL02

SL02SL02SL02

OS1 OS1 SL08

WL01

WL01

WL01WL01

WL01WL01

WL01

OS1 OS1 OS1

OS2 OS2

OS1

OS2

OS2

1

1

(TYP)1

2

3 3 3

4

5

5

5

RH01

5

SL08

SL08

3

EB20H6V

RL05

1

RH03

SL09 d

SL09 d SL09 d

SL09 d

SL10 dSL10 d

SL10 c SL10 c

a b

abc

OS3a

OS3b

d

SL10 d SL10 d

A. WHERE NEW TOGGLE SWITCHES, OR DIMMER CONTROLS ARE ADJACENT EACH OTHER, PROVIDE GANGED SWITCHING TO ACCOMODATE TOTAL NUMBER OF SWITCHES, UNLESS NOTED OTHERWISE.

B. ALL RECESSED LIGHTING FIXTURES IN LAY-IN CEILINGS SHALL BE INSTALLED WITH 6' LONG FLEXIBLE METAL CONDUIT.

C. ALL MOUNTING HEIGHTS FOR LUMINAIRES ARE TO THE BOTTOM OF THE LUMINAIRE UNLESS NOTED OTHERWISE.

D. REFER TO ARCHITECTURAL ELEVATIONS FOR MOUNTING HEIGHTS OF EXTERIOR OR INTERIOR LUMINAIRES.

E. WIRING OF LIGHT FIXTURES TO BE MODIFIED AND EXTENDED AS REQUIRED. UTILIZE EXISTING CIRCUITS AND CONTROL UNLESS OTHERWISE NOTED.

GENERAL NOTES

N

Certificate of Authorization

Epp Siepman Engineering Inc.

No. 4035

10 9 8 7 6 5 4 3 2 1

10 9 8 7 6 5 4 3 2 1

F

E

D

C

B

A

F

E

D

C

B

A

F F C F F

F

C

F

FFCFF

F

C

F

CONSULTANT - SUB-CONSULTANT:

KEYPLAN:

SEAL:

CLIENT:

CLIENT REF. #:

PROJECT:

DISCLAIMER: COPYRIGHT:

ISSUED FOR - REVISION:

THIS DRAWING AND DESIGN IS COPYRIGHT PROTECTED WHICH SHALL NOT BE USED, REPRODUCED OR REVISED WITHOUT WRITTEN PERMISSION BY WSP CANADA INC. THE CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND UTILITY LOCATIONS AND REPORT ALL ERRORS AND OMISSIONS PRIOR TO COMMENCING WORK. THIS DRAWING IS NOT TO BE SCALED.

GGH-46-10

RV. DATE DESCRIPTION

PROJECT NO.

ORIGINAL SCALE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

DISCIPLINE:

TITLE:

SHEET NUMBER:

ISSUE:

SHEET #:

DATE OF:

IF THIS BAR IS NOT 1"LONG, ADJUST YOUR

PLOTTING SCALE.

1"

--

--

-- OF --

RV. #

0

NTS

ELECTRICAL

As indicated

STONEWALL, MB

17042

MAIN FLOOR - LIGHTING PLAN

STONEWALL RCMPDETACHMENT

EL2.1

ML/MM

ML/MM

JF/MP

400 - 136 Market AvenueWinnipeg, MB R3B 0P4

T 204 453 1080

KEY NOTES1 REMOVE EXISTING LAMP AND REPLACE WITH A19 LED LAMP WITH MEDIUM

BASE.2 PROVIDE CEILING MOUNTED OCCUPANCY CENSORS AND DIMMING WALL

SWITCHES FOR MAIN OPEN OFFICE AREA.3 NEW LIGHT FIXTURES IN CELLS TO UTILIZE EXISTING ON/OFF/NIGHT LIGHT

CONTROL SWITCHES.4 PROVIDE SWITCH WITH ON/OFF/NIGHT LIGHT CONTROL TO MATCH EXISTING.5 CONNECT LIGHTING CIRCUITS THIS AREA TO ZONE SENSING RELAY FOR

CORRESPONDING EMERGENCY LIGHTING BATTERY UNIT.

EL2.1 SCALE: 1 : 50

1 MAIN FLOOR - LIGHTING - STONEWALL

0 May 12, 2017 Issued for Tender

6 10

Page 12: WALL TYPES: LEGEND · wall types: p1 c1 ew1 stc 50 16 mm type x gypsum board 60 acoustic batt insulation 31 x 64 25 ga steel studs, 600 o.c. max. min. 25 mm air space between existing

SL01 SL01EX1

SL02 SL02 SL02EX1

SL08 SL08 SL08

SL08

SL06SL02

1

2

2RH01

3

A. WHERE NEW TOGGLE SWITCHES, OR DIMMER CONTROLS ARE ADJACENT EACH OTHER, PROVIDE GANGED SWITCHING TO ACCOMODATE TOTAL NUMBER OF SWITCHES, UNLESS NOTED OTHERWISE.

B. ALL RECESSED LIGHTING FIXTURES IN LAY-IN CEILINGS SHALL BE INSTALLED WITH 6' LONG FLEXIBLE METAL CONDUIT.

C. ALL MOUNTING HEIGHTS FOR LUMINAIRES ARE TO THE BOTTOM OF THE LUMINAIRE UNLESS NOTED OTHERWISE.

D. REFER TO ARCHITECTURAL ELEVATIONS FOR MOUNTING HEIGHTS OF EXTERIOR OR INTERIOR LUMINAIRES.

E. WIRING OF LIGHT FIXTURES TO BE MODIFIED AND EXTENDED AS REQUIRED. UTILIZE EXISTING CIRCUITS AND CONTROL UNLESS OTHERWISE NOTED.

GENERAL NOTES

N

Certificate of Authorization

Epp Siepman Engineering Inc.

No. 4035

10 9 8 7 6 5 4 3 2 1

10 9 8 7 6 5 4 3 2 1

F

E

D

C

B

A

F

E

D

C

B

A

F F C F F

F

C

F

FFCFF

F

C

F

CONSULTANT - SUB-CONSULTANT:

KEYPLAN:

SEAL:

CLIENT:

CLIENT REF. #:

PROJECT:

DISCLAIMER: COPYRIGHT:

ISSUED FOR - REVISION:

THIS DRAWING AND DESIGN IS COPYRIGHT PROTECTED WHICH SHALL NOT BE USED, REPRODUCED OR REVISED WITHOUT WRITTEN PERMISSION BY WSP CANADA INC. THE CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND UTILITY LOCATIONS AND REPORT ALL ERRORS AND OMISSIONS PRIOR TO COMMENCING WORK. THIS DRAWING IS NOT TO BE SCALED.

GGH-46-10

RV. DATE DESCRIPTION

PROJECT NO.

ORIGINAL SCALE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

DISCIPLINE:

TITLE:

SHEET NUMBER:

ISSUE:

SHEET #:

DATE OF:

IF THIS BAR IS NOT 1"LONG, ADJUST YOUR

PLOTTING SCALE.

1"

--

--

-- OF --

RV. #

0

NTS

ELECTRICAL

As indicated

STONEWALL, MB

17042

SECOND FLOOR - LIGHTING PLAN

STONEWALL RCMPDETACHMENT

EL2.2

ML/MM

ML/MM

JF/MP

400 - 136 Market AvenueWinnipeg, MB R3B 0P4

T 204 453 1080

KEY NOTES1 REMOVE EXISTING LAMP AND REPLACE WITH A19 LED LAMP WITH MEDIUM

BASE.2 REMOVE AND REPLACE LIGHT FIXTURE ONLY. USE EXISTING CHAIN HANGERS,

WIRING AND CONTROL.3 CONNECT LIGHTING CIRCUITS THIS AREA TO ZONE SENSING RELAY FOR

CORRESPONDING EMERGENCY LIGHTING BATTERY UNIT.

EL2.2 SCALE: 1 : 50

1 SECOND FLOOR - LIGHTING - STONEWALL

0 May 12, 2017 Issued for Tender

7 10

Page 13: WALL TYPES: LEGEND · wall types: p1 c1 ew1 stc 50 16 mm type x gypsum board 60 acoustic batt insulation 31 x 64 25 ga steel studs, 600 o.c. max. min. 25 mm air space between existing

CR

CR

CR

Pnl A

Pnl B

UH-1PP-40,42

ERVPP-38

FF-1PP-39,41

ADOPP-36

PP-34 PP-34

DH-1PP-35,37

1

2

3

4

PP-33

(TYP)5

6

6

PP-29 PP-29

PP-31

PP-31PP-32 PP-32

PP-27

7

(TYP)7

FACP

8

7 8

8

4

2

297

A. FINAL CONNECTION TO ALL MECHANICAL EQUIPMENT SHALL BE FLEXIBLE. CONFIRM FINAL CIRCUIT BREAKER AND WIRE SIZE WITH MECHANICAL EQUIPMENT SHOP DRAWINGS. ADJUST CIRCUIT BREAKER AND WIRE SIZE AS REQUIRED WITHOUT ADDITIONAL COST TO OWNER.

B. PROVIDE RE-VERIFICATION OF FIRE ALARM SYSTEM FOR ALL NEW AND MODIFIED DEVICES.

GENERAL NOTES

N

Certificate of Authorization

Epp Siepman Engineering Inc.

No. 4035

10 9 8 7 6 5 4 3 2 1

10 9 8 7 6 5 4 3 2 1

F

E

D

C

B

A

F

E

D

C

B

A

F F C F F

F

C

F

FFCFF

F

C

F

CONSULTANT - SUB-CONSULTANT:

KEYPLAN:

SEAL:

CLIENT:

CLIENT REF. #:

PROJECT:

DISCLAIMER: COPYRIGHT:

ISSUED FOR - REVISION:

THIS DRAWING AND DESIGN IS COPYRIGHT PROTECTED WHICH SHALL NOT BE USED, REPRODUCED OR REVISED WITHOUT WRITTEN PERMISSION BY WSP CANADA INC. THE CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND UTILITY LOCATIONS AND REPORT ALL ERRORS AND OMISSIONS PRIOR TO COMMENCING WORK. THIS DRAWING IS NOT TO BE SCALED.

GGH-46-10

RV. DATE DESCRIPTION

PROJECT NO.

ORIGINAL SCALE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

DISCIPLINE:

TITLE:

SHEET NUMBER:

ISSUE:

SHEET #:

DATE OF:

IF THIS BAR IS NOT 1"LONG, ADJUST YOUR

PLOTTING SCALE.

1"

--

--

-- OF --

RV. #

0

NTS

ELECTRICAL

As indicated

STONEWALL, MB

17042

MAIN FLOOR - POWER PLAN

STONEWALL RCMPDETACHMENT

EP2.1

ML/MM

ML/MM

JF/MP

400 - 136 Market AvenueWinnipeg, MB R3B 0P4

T 204 453 1080

KEY NOTES1 PROVIDE NEW FORCE FLOW HEATER.2 THIS ROOM TO BE RE-DRYWALLED. RELOCATE ALL EXISTING ELECTRICAL AND

DATA TO NEW WALLS.3 WIRE AND CONNECT BARRIER FREE DOOR OPERATORS C/W ASSOCIATED

CONTROLS. CONFIRM REQUIREMENTS WITH DOOR HARDWARE CONTRACTORAND DOOR OPERATOR EQUIPMENT SHOP DRAWINGS.

4 WIRE AND CONNECT DOOR HOLD-OPEN DEVICE. WIRE AND CONNECT TO FIREALARM SYSTEM. PROVIDE NEW SMOKE DETECTORS WITHIN 1.5 M OF DOOR ONBOTH SIDES. HOLD-OPEN SHALL RELEASE ON FIRE ALARM. PROVIDERE-VERIFICATION OF FIRE ALARM SYSTEM FOR ALL NEW AND RELOCATEDDEVICES.

5 PROVIDE ADDITIONAL CIRCUITS FOR GYM EQUIPMENT. COORDINATE EXACTLOCATION ON SITE WITH NCO.

6 PROVIDE ROUGHIN FOR ADDITIONAL DATA AND TV OUTLETS FOR GYMEQUIPMENT. COORDINATE EXACT LOCATION ON SITE WITH NCO. PROVIDEPATHWAY TO ACCESSIBLE AREA.

7 PROVIDE ROUGH IN ONLY FOR DATA OUTLET COMPLETE WITH 4"X4" BOX ANDCONDUIT TO ACCESSIBLE CEILING SPACE.

8 PROVIDE ROUGH IN ONLY FOR CARD ACCESS COMPLETE WITH CONDUIT TOACCESSIBLE CEILING SPACE.

9 WIRE AND CONNECT NEW RECEPTACLES TO EXISTING CIRCUIT.

EP2.1 SCALE: 1 : 50

1 MAIN FLOOR - POWER & SYSTEMS - STONEWALL

0 May 12, 2017 Issued for Tender

8 10

Page 14: WALL TYPES: LEGEND · wall types: p1 c1 ew1 stc 50 16 mm type x gypsum board 60 acoustic batt insulation 31 x 64 25 ga steel studs, 600 o.c. max. min. 25 mm air space between existing

METER

Pnl CDPPnl PP Pnl C Pnl D

A. FINAL CONNECTION TO ALL MECHANICAL EQUIPMENT SHALL BE FLEXIBLE. CONFIRM FINAL CIRCUIT BREAKER AND WIRE SIZE WITH MECHANICAL EQUIPMENT SHOP DRAWINGS. ADJUST CIRCUIT BREAKER AND WIRE SIZE AS REQUIRED WITHOUT ADDITIONAL COST TO OWNER.

B. PROVIDE RE-VERIFICATION OF FIRE ALARM SYSTEM FOR ALL NEW AND MODIFIED DEVICES.

GENERAL NOTES

N

Certificate of Authorization

Epp Siepman Engineering Inc.

No. 4035

10 9 8 7 6 5 4 3 2 1

10 9 8 7 6 5 4 3 2 1

F

E

D

C

B

A

F

E

D

C

B

A

F F C F F

F

C

F

FFCFF

F

C

F

CONSULTANT - SUB-CONSULTANT:

KEYPLAN:

SEAL:

CLIENT:

CLIENT REF. #:

PROJECT:

DISCLAIMER: COPYRIGHT:

ISSUED FOR - REVISION:

THIS DRAWING AND DESIGN IS COPYRIGHT PROTECTED WHICH SHALL NOT BE USED, REPRODUCED OR REVISED WITHOUT WRITTEN PERMISSION BY WSP CANADA INC. THE CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND UTILITY LOCATIONS AND REPORT ALL ERRORS AND OMISSIONS PRIOR TO COMMENCING WORK. THIS DRAWING IS NOT TO BE SCALED.

GGH-46-10

RV. DATE DESCRIPTION

PROJECT NO.

ORIGINAL SCALE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

DISCIPLINE:

TITLE:

SHEET NUMBER:

ISSUE:

SHEET #:

DATE OF:

IF THIS BAR IS NOT 1"LONG, ADJUST YOUR

PLOTTING SCALE.

1"

--

--

-- OF --

RV. #

0

NTS

ELECTRICAL

As indicated

STONEWALL, MB

17042

SECOND FLOOR - POWER PLAN

STONEWALL RCMPDETACHMENT

EP2.2

ML/MM

ML/MM

JF/MP

400 - 136 Market AvenueWinnipeg, MB R3B 0P4

T 204 453 1080

EP2.2 SCALE: 1 : 50

1 SECOND FLOOR - POWER & SYSTEMS - STONEWALL

0 May 12, 2017 Issued for Tender

9 10

Page 15: WALL TYPES: LEGEND · wall types: p1 c1 ew1 stc 50 16 mm type x gypsum board 60 acoustic batt insulation 31 x 64 25 ga steel studs, 600 o.c. max. min. 25 mm air space between existing

LIGHTING FIXTURE SCHEDULE

A. EMERGENCY LIGHTING MODEL NUMBERS ARE BASED ON AIMLITE PRODUCT LINE. EMERGILITE, BEGHELLIE, AND LUMACELL MEETING PERFORMANCE SPECIFICATIONS ARE APPROVED EQUAL.B. FIXTURES ABOVE ARE A BASIS OF DESIGN, ALTERNATES MUST BE SUBMITTED AS A SUBSTITUTION FOR APPROVAL PRIOR TO BID SUBMISSION.

GENERAL NOTES:

1. PROVIDE WET LOCATION RATED LIGHT FIXTURE IN WASHROOMS AND SHOWERS. 2. ADJUST OPTICS FOR WIDE DISTRIBUTION.

SCHEDULE NOTES:

LIGHTING CONTROL DEVICE SCHEDULE

SCHEDULE NOTES:

1. PROVIDE DEVICE TO MATCH OPERATING VOLTAGE OF LOADS CONTROLLED.

ELECTRICAL HEATER SCHEDULE

A. HEATER OUTPUT SHALL BE AS INDICATED AT SPECIFIED VOLTAGE.B. BASEBOARD HEATERS AND FORCE FLOW HEATERS SHALL BE WHITE IN COLOUR. CONFIRM FINISH WITH ARCHITECT.C. OUELLET, CHROMALOX, STELPRO, AND Q-MARK MEETING ABOVE SPECIFICATIONS ARE APPROVED EQUAL MANUFACTURERS.D. WHERE BASEBOARD HEATERS ARE SPECIFIED, LINEAR CONVECTORS ARE NOT APPROVED EQUAL.E. ALL DRAFT BARRIER HEATERS SHALL BE COMPLETE WITH FINISHED BACK AND PEDESTAL MOUNTS.F. ALL LOW-VOLTAGE CONTROLLED HEATERS SHALL BE COMPLETE WITH LOW VOLTAGE RELAY AND TRANSFORMER KIT FOR LOW VOLTAGE THERMOSTAT CONNECTION.

GENERAL NOTES:

1. SUSPEND FROM STRUCTURE.

NOTES:

LN-IT LINE VOLTAGE INTERNAL TAMPERPROOF BI-METAL THERMOSTAT T-STATLN-ID LINE VOLTAGE INTERNAL DIAL BI-METAL THERMOSTAT LN-R LINE VOLTAGE REMOTE BI-METAL THERMOSTAT

CONTROL DEVICES:LW-IT LOW VOLTAGE INTERNAL TAMPERPROOF BI-METAL THERMOSTAT LW-ID LOW VOLTAGE INTERNAL DIAL THERMOSTAT LW-R LOW VOLTAGE REMOTE BI-METAL THERMOSTAT

IT INTERNAL TAMPERPROOF THERMOSTAT ID INTERNAL DIAL THERMOSTAT

EMERGENCY BATTERY BANK SCHEDULE

A. EMERGENCY LIGHTING MODEL NUMBERS ARE BASED ON AIMLITE AIMLITE PRODUCT LINE. EMERGILITE, BEGHELLIE, AND LUMACELL MEETING PERFORMANCE SPECIFICATIONS ARE APPROVED EQUAL.

B. WHERE "APPROVED EQUAL" IS LISTED IN THE MANUFACTURER COLUMN, FIXTURES MUST BE SUBMITTED AS A SUBSTITUTION FOR APPROVAL PRIOR TO BID SUBMISSION.

GENERAL NOTES:

1. N/ASCHEDULE NOTES:

MECHANICAL EQUIPMENT SCHEDULE

FVNR FULL VOLTAGE NON-REVERSINGFVR FULL VOLTAGE REVERSING2-SPD TWO SPEEDVFD VARIABLE FREQUENCY DRIVERVS REDUCED VOLTAGEPKG PACKAGED UNIT

STARTER TYPES:FS FUSED SWITCHNFS NON-FUSED SWITCHMCP MOTOR CIRCUIT PROTECTORCB CIRCUIT BREAKER

COMBINATION DISCONNECT TYPES:MAG MAGNETICMAN MANUALHOA HAND-OFF-AUTO SWITCHRP RED (RUN) PILOT LIGHTGP GREEN (POWER) PILOT LIGHT0/0 ON-OFF SELECTOR SWITCHS/S STOP-START PUSHBUTTONS

STARTER OPTIONS:EC ELECTRICAL CONTRACTORMC MECHANICAL CONTRACTORAS AQUASTATDCP DUPLEX CONTROLLERGC GENERAL CONTRACTORHS HUMIDSTATINT INTERLOCKED (WITH)

ABBREVIATIONS:

A. CIRCUITING IS REPRESENTATIONAL ONLY. CONFIRM CIRCUITING ARRANGEMENTS ON SITE WITH EXISTING CONDITIONS.B. WIRING BETWEEN VSDS AND MOTORS SHALL BE RATED FOR VSD USE.C. INPUT AND OUTPUT CONDUCTORS TO AND FROM VFD'S SHALL BE INSTALLED IN SEPARATE RACEWAYS, INDEPENDENT FROM ANY OTHER CONDUCTORS, AND SHALL NOT PASS THRU ANY COMMON WIREWAY OR

RACEWAY

GENERAL NOTES:

1. N/A

NOTES:

SC SPEED CONTROLTC TIME CLOCKTS THERMOSTATOWN OWNER

Certificate of Authorization

Epp Siepman Engineering Inc.

No. 4035

10 9 8 7 6 5 4 3 2 1

10 9 8 7 6 5 4 3 2 1

F

E

D

C

B

A

F

E

D

C

B

A

F F C F F

F

C

F

FFCFF

F

C

F

CONSULTANT - SUB-CONSULTANT:

KEYPLAN:

SEAL:

CLIENT:

CLIENT REF. #:

PROJECT:

DISCLAIMER: COPYRIGHT:

ISSUED FOR - REVISION:

THIS DRAWING AND DESIGN IS COPYRIGHT PROTECTED WHICH SHALL NOT BE USED, REPRODUCED OR REVISED WITHOUT WRITTEN PERMISSION BY WSP CANADA INC. THE CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND UTILITY LOCATIONS AND REPORT ALL ERRORS AND OMISSIONS PRIOR TO COMMENCING WORK. THIS DRAWING IS NOT TO BE SCALED.

GGH-46-10

RV. DATE DESCRIPTION

PROJECT NO.

ORIGINAL SCALE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

DISCIPLINE:

TITLE:

SHEET NUMBER:

ISSUE:

SHEET #:

DATE OF:

IF THIS BAR IS NOT 1"LONG, ADJUST YOUR

PLOTTING SCALE.

1"

--

--

-- OF --

RV. #

0

NTS

ELECTRICAL

1 : 96

STONEWALL, MB

17042

ELECTRICAL SCHEDULES

STONEWALL RCMPDETACHMENT

E6.1

ML/MM

ML/MM

JF/MP

400 - 136 Market AvenueWinnipeg, MB R3B 0P4

T 204 453 1080

TYPE Description LENS-LOUVER MOUNTING LAMPBALLAST /

DRIVER VOLT WATT MFR CATALOG SERIES NOTEEX1 LED UNIVERSAL MOUNT, UNIVERSAL

VOLTAGE, UNIVERSAL SINGLE/DOUBLEFACE PICTOGRAM STYLE EXIT SIGN WITHWHITE ALUMINUM HOUSING ANDCHEVRON ARROWS AS SHOWN ONPLANS.

--- UNIVERSAL < 3W LEDMIN 50000

HR

--- 120 V 3 W AIMLITE RPST-U-M

EXT01 SURFACE MOUNTED SQUARE, WETLOCATION, COLOUR TO MATCH EXISTING.

OPALPOLYCARBONAT

E

SOFFIT 1000 LUMEN4200K

LED DRIVER 120 V 18 W NEWSTAR AGV-11-OP-UN-42

EXT02 EXTERIOR LED WALL LIGHT FIXTURE WALL 20 LED4000K

LED DRIVER 120 V 47 W LITHONIA DSXW1LED-20C-700-40K-T3

M-MVOLT-DDBXDRH01 DOUBLE HEAD EMERGENCY LIGHTING

REMOTE. DIE CAST ALL METALCONSTRUCTION. WHITE

WALL 2 x 6W LED50000HR

540 LUMENS

--- 12 V 12 W AIMLITE RMQVD 2

RH03 SINGLE HEAD EMERGENCY LIGHTINGRECESSED REMOTE. ALUMINUMCONSTRUCTION. WHITE

RECESSED 1 x 4W LED50000HR

540 LUMENS

--- 12 V 4 W AIMLITE RMRG 2

RL02 610mm x 610mm (2 Foot X 2 Foot) LEDVOLUMETRIC SPECIFICATION GRADE.

CURVEDRIBBED

VOLUMETRICACRYLIC

DIFFUSOR

RECESSEDIN T-BAR

LED3000lm80+CRI4000K

60000HR

(1) LEDDRIVER0-10V

DIMMING

120 V 30 W LITHONIA 2BLT2

RL03 610mm x 1220mm (2 Foot X 4 Foot) LEDVOLUMETRIC SPECIFICATION GRADE.

CURVEDRIBBED

VOLUMETRICACRYLIC

DIFFUSOR

RECESSEDIN T-BAR

LED6000lm80+CRI4000K

60000HR

(1) LEDDRIVER0-10V

DIMMING

120 V 53 W LITHONIA 2BLT4

RL05 A19 LED LAMP WITH MEDIUM BASE LED 850LUMEN4000K

120 V 10 W LED LAMP LED LAMP

SL01 A19 LED LAMP WITH MEDIUM BASE LED 850LUMEN4000K

120 V 10 W LED LAMP LED LAMP

SL02 LED STRIP LIGHT SNAP ONFROSTEDDIFFUSER

CHAINSUSPENDED

LED3000lm80+CRI4000K

60000HR

0-10 VDCDIMMABLE

LED DRIVER

120 V 60 W LITHONIA ZL1N

SL03 7" ROUND LED FLUSH MOUNT SURFACE 660 LUMENSLED

4000K50,000 HR

LED DRIVER 120 V 9 W LITHONIA FMML-7-8-40 1

SL06 610mm x 610mm (2' X 2') SURFACE MOUNTLED

ACRYLICVOLUMETRIC

DIFFUSER

SURFACE 3000LUMENS

LED82+CRI4000K

0-10 VDCDIMMABLE

LED DRIVER

120 V 29 W LITHONIA 2BLTX2-30L-ADP--EZ1-LP840

SL08 254mm x 1220mm (10" X 4') LOW PROFILECURVED BASKET LED WRAP AROUND

CURVEDPRISMATICDIFFUSER

SURFACE 4600LUMENS

LED82+CRI4000K

0-10 VDCDIMMABLE

LED DRIVER

120 V 41 W LITHONIA LBL4LP840

SL09 4" ROUND RECESSED LED FIXTURE DIFFUSINGOPTICAL LENS

RECESSED LED 1500LUMENS

4000K50000 HR

120 V 31 W LITHONIA LDN4-40/15-AR-LSS-120-EZ10

SL10 6" ROUND RECESSED LED FIXTURE DIFFUSINGOPTICAL LENS

RECESSED LED 1500LUMENS

4000K50000 HR

120 V 31 W LDN6-40/15-LO6-AR-LSS-120-EZ10

WL01 CORNER LUMINAIRE NON-CLAMSHELLFOR MAX SECURITY USE COMPLETEWITH NIGHTLIGHT

SURFACEWALL

LED DRIVER 120 V 50 W NEWSTAR 554-A-L2-LED40-1-A-12-LN

WL02 SURFACE WALL MOUNT 2' LED LINEARREFRACTOR

SURFACEWALL

1800LUMENS

LED82+CRI4000K

50,000 HR

0-10 VDCDIMMABLE

LED DRIVER

120 V 18 W LITHONIA WL2

TYPE DESCRIPTION MANUFACTURER CATALOG No. WATTS VOLTS NOTESOS1 COMBINATION ULTRASONIC OCCUPANCY

SENSOR/SWITCH, WALL MOUNTED, LINEVOLTAGE, WITH ON-OFF PUSHBUTTON WITHDIMMING.

SENSORSWITCH

WSX PDT D 0 W 0 V 1

OS2 COMBINATION ULTRASONIC OCCUPANCYSENSOR/SWITCH, WALL MOUNTED, LINEVOLTAGE, WITH ON-OFF PUSHBUTTON.

SENSORSWITCH

WSX PDT 0 W 0 V 1

OS3 ULTRASONIC OCCUPANCY SENSOR, CEILINGMOUNTED 360° COVERAGE, MINIMUM 1100SQUARE FEET.

SENSORSWITCH

CM PDT 9 0 W 0 V 1

MARK DESCRIPTION WATTAGE VOLTAGE LENGTH MANUFACTURER MODEL SERIES

CONTROL DEVICE

NOTESCOMPONENTFURN.INST.

FA8.04B ARCHITECTURAL FORCED-AIR WALL HEATER 4,000 W 208 V OUELLET OAWH ID DIV 26DIV 26

U6.60I ELECTRIC UNIT HEATER COMPLETE WITH 24V REMOTE THERMOSTAT 5,000 W 208 V OUELLET OAS LW-ID DIV 26DIV 26

1

PANEL PP IS AN EXISTING WESTINGHOUSE PANEL. PROVIDE NEW CIRCUIT BREAKERS ARE REQUIRED.NOTES:

EST. DEMAND CURRENT: 43 ACONNECTED CURRENT: 43 A

HEAT 9000 VA 100.00% 9000 VA ESTIMATED DEMAND: 15640 VASPEC 5000 VA 100.00% 5000 VA CONNECTED LOAD: 15640 VARCPT 1800 VA 100.00% 1800 VALOAD CLASSIFICATION CONNECTED DEMAND ESTIMATED PANEL TOTALS

TOTAL AMPS: 26 A 46 A 64 ATOTAL LOAD: 3 kVA 5 kVA 7 kVA

PP-41 2.0 2.5 PP-42HEAT Space 12 30 A 2 PP-39 2.0 2.5 PP-40 2 30 A HEAT Space 6

PP-37 2.5 0.0 PP-38 1 15 A SPEC Space 6SPEC Space 6 30 A 2 PP-35 2.5 0.0 PP-36 1 15 A SPEC Space 12RCPT 20 A 1 PP-33 0.2 0.4 PP-34 1 15 A RCPT Space 7RCPT Space 6 20 A 1 PP-31 0.4 0.4 PP-32 1 20 A RCPT Space 6RCPT Space 6 20 A 1 PP-29 0.4 0.0 PP-30 -- -- EXISTINGRCPT Space 10 20 A 1 PP-27 0.2 0.0 PP-28 -- -- EXISTINGEXISTING -- -- PP-25 0.0 0.0 PP-26 -- -- EXISTINGEXISTING -- -- PP-23 0.0 0.0 PP-24 -- -- EXISTINGEXISTING -- -- PP-21 0.0 0.0 PP-22 -- -- EXISTINGEXISTING -- -- PP-19 0.0 0.0 PP-20 -- -- EXISTINGEXISTING -- -- PP-17 0.0 0.0 PP-18 -- -- EXISTINGEXISTING -- -- PP-15 0.0 0.0 PP-16 -- -- EXISTINGEXISTING -- -- PP-13 0.0 0.0 PP-14 -- -- EXISTINGEXISTING -- -- PP-11 0.0 0.0 PP-12 -- -- EXISTINGEXISTING -- -- PP-9 0.0 0.0 PP-10 -- -- EXISTINGEXISTING -- -- PP-7 0.0 0.0 PP-8 -- -- EXISTINGEXISTING -- -- PP-5 0.0 0.0 PP-6 -- -- EXISTINGEXISTING -- -- PP-3 0.0 0.0 PP-4 -- -- EXISTINGEXISTING -- -- PP-1 0.0 0.0 PP-2 -- -- EXISTING

LOAD DESCRIPTION BKR P CKT A B C CKT P BKR LOAD DESCRIPTION

BUS AMPS: 200 AMPSMAIN DEVICE: 60 A MLO SPECIAL:

MOUNTING: SURFACE NEMA1 A.I.C. RATING: 10,000 AMPS SYMMETRICALLOCATION: Space 122 VOLTAGE: 120/208 V. 3 ø 4 W.

PANELBOARD: PP

ID MARK TYPE DESCRIPTION LAMP AC VOLT DC VOLT WATT MFR CATALOG SERIES NOTEBU-12 EB20H6V BATTERY BANK, STEEL CABINET COMPLETE

WITH INTEGRAL VOLTAGE SENSINGRELAYS, DOUBLE EMERGENCY LIGHTINGHEADS AND DC TERMINAL BLOCKS.

2 x 6W LED50000HR

540 LUMENS

120 V 12 V 200 W AIMLITE EBST

BU-54 EB20H6V BATTERY BANK, STEEL CABINET COMPLETEWITH INTEGRAL VOLTAGE SENSINGRELAYS, DOUBLE EMERGENCY LIGHTINGHEADS AND DC TERMINAL BLOCKS.

2 x 6W LED50000HR

540 LUMENS

120 V 12 V 200 W AIMLITE EBST

NO. DESCRIPTION ROOM

LOAD

VOLT PH CIRCUITCONDUIT & WIRE

SIZE

STARTER CONTROL DEVICE DISCONNECT

NOTESHP A W COMPONENT

FURN.INST.

WIRED COMPONENT

FURN.INST.

WIRED COMPONENT

FURN.INST.

WIREDADO AUTOMATIC DOOR OPERATOR 0 A 0 W 120 V 1 PP-36 21(3/4'')C-2#12,

#12 GND---- ---- INTERGRAL ---- NFS DIV. 26

DIV. 26DIV. 26

DH-1 DUCT HEATER 6 0 A 5000 W 208 V 1 PP-35,37 21(3/4'')C-2#8,#10 GND

---- ---- TEMP.CONTROL

DIV. 23DIV. 23DIV. 23

NFS DIV. 26DIV. 26DIV. 26

ERV ENERGY RECOVERY VENTILATOR 6 0 A 0 W 120 V 1 PP-38 21(3/4'')C-2#12,#12 GND

INTERGRAL DIV. 23DIV. 23DIV. 23

DIGITALCONTROL

DIV. 23DIV. 23DIV. 23

NFS DIV. 26DIV. 26DIV. 26

0 May 12, 2017 Issued for Tender

10 10

Page 16: WALL TYPES: LEGEND · wall types: p1 c1 ew1 stc 50 16 mm type x gypsum board 60 acoustic batt insulation 31 x 64 25 ga steel studs, 600 o.c. max. min. 25 mm air space between existing

A. CONFORM TO APPLICABLE CODE FOR DEMOLITION WORK, DUST CONTROL, PRODUCTS REQUIRING ELECTRICAL DISCONNECTION OR RECONNECTION.

B. CONFORM TO APPLICABLE REGULATORY PROCEDURES WHEN DISCOVERING HAZARDOUS OR CONTAMINATED MATERIALS.

C. PROTECT EXISTING MATERIALS, EQUIPMENT, AND SYSTEMS WHICH ARE NOT TO BE DEMOLISHED. PROVIDE A MINIMUM MERV 8 FILTRATION ON EXISTING INLETS AND RETURN AIR DUCTS AND SYSTEMS.

D. CONDUCT DEMOLITION TO MINIMIZE INTERFERENCE WITH OCCUPIED BUILDING AREAS.E. DISCONNECT, REMOVE, CAP, AND IDENTIFY DESIGNATED UTILITIES WITHIN DEMOLITION

AREAS.F. REMOVE, CUT, AND PATCH WORK IN A MANNER TO MINIMIZE DAMAGE AND TO PROVIDE

MEANS OF RESTORING SYSTEMS TO ORIGINAL CONDITION.G. CAREFULLY DISMANTLE EXISTING MECHANICAL EQUIPMENT TO BE REMOVED OR

RELOCATED. TEMPORARILY DISCONNECT, REMOVE, AND REINSTALL EXISTING EQUIPMENT, PIPING, DUCTWORK, CONDUIT, LIGHT FIXTURES, AND SIMILAR ITEMS, WHICH INTERFERE WITH THE NEW INSTALLATION AFTER COMPLETION OF NEW WORK OR OF EXISTING INSTALLATIONS TO BE DEMOLISHED. STORE EQUIPMENT AND MATERIALS ON THE PREMISES AS DIRECTED BY THE OWNER.

H. DEMOLISH IN AN ORDERLY AND CAREFUL MANNER. REMOVE DEMOLISHED MATERIALS FROM SITE EXCEPT WHERE SPECIFICALLY NOTED OTHERWISE. UPON COMPLETION OF WORK, LEAVE AREAS IN CLEAN CONDITION.

I. ALL USABLE SALVAGED EQUIPMENT AND MATERIALS SHALL REMAIN THE PROPERTY OF THE OWNER UNLESS SPECIFICALLY NOTED OTHERWISE.

J. FIRESTOP ALL MECHANICAL PENETRATIONS THROUGH FIRE-RATED FLOOR AND WALL ASSEMBLIES WHERE PIPES OR DUCTS WERE REMOVED. SEE ARCHITECTURAL DRAWINGS FOR LOCATION AND TYPE OF RATINGS.

K. THE ABANDONMENT OF EXISTING EQUIPMENT AND MATERIAL IN PLACE IS NOT ACCEPTABLE. ALL REDUNDANT SERVICES ARE TO BE REMOVED BACK TO ACTIVE MAINS, WHICH SHALL THEN BE CAPPED AT EXISTING POINT OF CONNECTION.

MECHANICAL DEMOLITION GENERAL NOTES

1

2

3

3

4

4

4

N

Certificate of Authorization

Epp Siepman Engineering Inc.

No. 4035

10 9 8 7 6 5 4 3 2 1

10 9 8 7 6 5 4 3 2 1

F

E

D

C

B

A

F

E

D

C

B

A

F F C F F

F

C

F

FFCFF

F

C

F

CONSULTANT - SUB-CONSULTANT:

KEYPLAN:

SEAL:

CLIENT:

CLIENT REF. #:

PROJECT:

DISCLAIMER: COPYRIGHT:

ISSUED FOR - REVISION:

THIS DRAWING AND DESIGN IS COPYRIGHT PROTECTED WHICH SHALL NOT BE USED, REPRODUCED OR REVISED WITHOUT WRITTEN PERMISSION BY WSP CANADA INC. THE CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND UTILITY LOCATIONS AND REPORT ALL ERRORS AND OMISSIONS PRIOR TO COMMENCING WORK. THIS DRAWING IS NOT TO BE SCALED.

GGH-46-10

RV. DATE DESCRIPTION

PROJECT NO.

ORIGINAL SCALE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

DISCIPLINE:

TITLE:

SHEET NUMBER:

ISSUE:

SHEET #:

DATE OF:

IF THIS BAR IS NOT 1"LONG, ADJUST YOUR

PLOTTING SCALE.

MECHANICAL

1"

--

--

-- OF --

RV. #

0

NTSAs indicated

STONEWALL, MB

17042

MAIN FLOOR - MECHANICALDEMOLITION PLAN - STONEWALL

STONEWALL RCMPDETACHMENT

M2.1

TD

TD

SD

KEY NOTES1 EXISTING EXHAUST FAN AND ASSOCIATED DUCTWORK TO REMAIN.2 DEMOLISH EXISTING GRILLES. DEMOLISH ASSOCIATED DUCTWORK BACK TO MAIN. CAP AND

SEAL MAIN DUCTS WHERE DUCT BRANCHES HAVE BEEN REMOVED. REINSULATE AND MAKEGOOD INSULATION WHERE DUCTWORK HAS BEEN REMOVED.

3 DEMOLISH EXISTING TRANSFER AIR GRILLE, ASSOCIATED DUCTWORK AND HANGERS.4 REMOVE EXISTING GRILLES AND DIFFUSERS TO ALLOW FOR ROOM REFINISHING. GRILLES TO

BE REUSED IN RENOVATION WHERE INDICATED.

400 - 136 Market AvenueWinnipeg, MB R3B 0P4

T 204 453 1080

M2.1 SCALE: 1 : 50

1 MAIN FLOOR - MECHANICAL DEMOLITION PLAN - STONEWALL

MECHANICAL DRAWINGS

RCMP OFFICE - STONEWALLM2.1 MAIN FLOOR - MECHANICAL DEMOLITION PLAN - STONEWALLM2.2 MAIN FLOOR - MECHANICAL RENOVATION PLAN - STONEWALLM2.3 SECOND FLOOR - MECHANICAL DEMOLITION & RENOVATION PLAN - STONEWALLM2.4 MECHANICAL DETAILS & SCHEDULES - STONEWALL

O May 12, 2017 Issued for Tender

Page 17: WALL TYPES: LEGEND · wall types: p1 c1 ew1 stc 50 16 mm type x gypsum board 60 acoustic batt insulation 31 x 64 25 ga steel studs, 600 o.c. max. min. 25 mm air space between existing

1

S -194

S -194200Ø200Ø

200Ø

200Ø

HD

1HD

2

DH

1

1

ERV

2

200 X 200--1R

--2R

3

-235

S

3

4

5

6

A. FIRESTOP ALL MECHANICAL PENETRATIONS THROUGH FIRE-RATED FLOOR AND WALL ASSEMBLIES. SEE ARCHITECTURAL DRAWINGS FOR LOCATION AND TYPE OF RATINGS.

B. DUCT TRANSITIONS MAY NOT BE SHOWN IN DETAIL ON PLAN. REFER TO DETAILS SHEETS AND SMACNA - HVAC DUCT CONSTRUCTION STANDARDS FOR REQUIRED DUCT TRANSITIONS AND FITTINGS. ALL DUCT TAPS TO BRANCH DUCTS SHALL HAVE 45 DEGREE ENTRY FITTINGS.

C. INSTALL FIRE DAMPERS ON ALL DUCTS PENETRATING FIRE RATED WALL ASSEMBLIES, COMPLETE WITH ACCESS DOORS, SEE STANDARD DETAIL. REFER TO ARCHITECTURAL DRAWING FOR WALL TYPES.

D. COORDINATE FINAL THERMOSTAT & TIMER INSTALLATION HEIGHT AND DISTANCE FROM DOOR WITH ARCHITECT.

E. DUCT INSULATION MATERIALS SHALL MEET SMOKE AND FLAME SPREAD REQUIREMENTS FOR PLENUM INSULATION.

F. DUCT INSULATION SHALL FOLLOW THE SCHEDULES IN THE SPECIFICATION AS A MINIMUM REQUIREMENT. THESE REQUIREMENTS SHALL APPLY REGARDLESS OF WHETHER OR NOT DUCT INSULATION IS SHOWN ON THE DRAWINGS.

G. WHERE DUCT INSULATION IS SHOWN ON THE DRAWINGS (EITHER WITH THE HATCHING CONVENTION OR BY MEANS OF A KEY NOTE) AND EXCEEDS THE REQUIREMENTS OF THE SCHEDULES IN THE SPECIFICATION, THE ADDITIONAL INSULATION REQUIREMENTS SHALL BE MET.

H. PROVIDE MANUAL BALANCE DAMPERS FOR EACH EXHAUST, SUPPLY, AND RETURN GRILLE WHERE AN AIR VOLUME HAS BEEN PROVIDED.

I. INSTALL BALANCE DAMPERS AS FAR AWAY FROM GRILLES OR DIFFUSERS SERVED AS PRACTICALLY POSSIBLE AND IN AN EASILY ACCESSIBLE LOCATION.

J. CONTRACTOR SHALL SCAN FOR REBAR AND CONDUIT AND PROVIDE RESULTS OF SCAN IN WRITING TO OWNER PRIOR TO CORING OR DRILLING IN ANY CONCRETE WALL OR FLOOR.

K. THE INTERRUPTION OF ANY SERVICES SHALL BE COORDINATED WITH THE BUILDING OWNER AND SHALL BE KEPT TO A MINIMUM.

MECHANICAL RENOVATION GENERAL NOTES

N

Certificate of Authorization

Epp Siepman Engineering Inc.

No. 4035

10 9 8 7 6 5 4 3 2 1

10 9 8 7 6 5 4 3 2 1

F

E

D

C

B

A

F

E

D

C

B

A

F F C F F

F

C

F

FFCFF

F

C

F

CONSULTANT - SUB-CONSULTANT:

KEYPLAN:

SEAL:

CLIENT:

CLIENT REF. #:

PROJECT:

DISCLAIMER: COPYRIGHT:

ISSUED FOR - REVISION:

THIS DRAWING AND DESIGN IS COPYRIGHT PROTECTED WHICH SHALL NOT BE USED, REPRODUCED OR REVISED WITHOUT WRITTEN PERMISSION BY WSP CANADA INC. THE CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND UTILITY LOCATIONS AND REPORT ALL ERRORS AND OMISSIONS PRIOR TO COMMENCING WORK. THIS DRAWING IS NOT TO BE SCALED.

GGH-46-10

RV. DATE DESCRIPTION

PROJECT NO.

ORIGINAL SCALE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

DISCIPLINE:

TITLE:

SHEET NUMBER:

ISSUE:

SHEET #:

DATE OF:

IF THIS BAR IS NOT 1"LONG, ADJUST YOUR

PLOTTING SCALE.

MECHANICAL

1"

--

--

-- OF --

RV. #

0

NTSAs indicated

STONEWALL, MB

17042

MAIN FLOOR - MECHANICALRENOVATION PLAN - STONEWALL

STONEWALL RCMPDETACHMENT

M2.2

TD

TD

SD

KEY NOTES1 PROVIDE NEW ERV AT HIGH LEVEL ALONG EXTERIOR WALL. PROVIDE OUTDOOR AIR INTAKE AND

EXHAUST HOODS AT HIGH LEVEL ON EXTERIOR WALL, ENSURE A MINIMUM DISTANCE OF 3METERS SEPARATION IS MAINTAINED.

2 REINSTALL EXISTING SUPPLY GRILLE IN SAME LOCATION AFTER ROOM FINISHING HAS BEENCOMPLETED.

3 PROVIDE NEW SECURITY SUPPLY AND RETURN AIR GRILLES WITHIN HARD INTERVIEW ROOM.CONNECT DUCTWORK INTO EXISTING SECURE SIDE FURNACE WITHIN ROOF SPACE ABOVEROOM. REWORK EXISTING INSULATION AT TIE IN LOCATIONS TO ENSURE A CONTINUOUS VAPORBARRIER IS ACHIEVED.

4 PROVIDE NEW ELECTRONIC PREHEAT COIL ON OUTDOOR AIR DUCT UPSTREAM OF THE ERV.5 PROVIDE ACOUSTIC RETURN ELBOW WITHIN DROPPED CEILING. ELBOW SHALL HAVE 25MM

THICK ACOUSTIC LINING AND BE CONFIGURED AS SHOWN.6 ERV TIMER TO BE MOUNTED ON WALL. COORDINATE EXACT LOCATION WITH ARCHITECT.

400 - 136 Market AvenueWinnipeg, MB R3B 0P4

T 204 453 1080

M2.2 SCALE: 1 : 50

1 MAIN FLOOR - MECHANICAL RENOVATION - STONEWALL

O May 12, 2017 Issued for Tender

Page 18: WALL TYPES: LEGEND · wall types: p1 c1 ew1 stc 50 16 mm type x gypsum board 60 acoustic batt insulation 31 x 64 25 ga steel studs, 600 o.c. max. min. 25 mm air space between existing

150Ø

400 X 250

1

2

3

200 X 200

200Ø

3

4

5

6

A. FIRESTOP ALL MECHANICAL PENETRATIONS THROUGH FIRE-RATED FLOOR AND WALL ASSEMBLIES. SEE ARCHITECTURAL DRAWINGS FOR LOCATION AND TYPE OF RATINGS.

B. DUCT TRANSITIONS MAY NOT BE SHOWN IN DETAIL ON PLAN. REFER TO DETAILS SHEETS AND SMACNA - HVAC DUCT CONSTRUCTION STANDARDS FOR REQUIRED DUCT TRANSITIONS AND FITTINGS. ALL DUCT TAPS TO BRANCH DUCTS SHALL HAVE 45 DEGREE ENTRY FITTINGS.

C. INSTALL FIRE DAMPERS ON ALL DUCTS PENETRATING FIRE RATED WALL ASSEMBLIES, COMPLETE WITH ACCESS DOORS, SEE STANDARD DETAIL. REFER TO ARCHITECTURAL DRAWING FOR WALL TYPES.

D. COORDINATE FINAL THERMOSTAT & TIMER INSTALLATION HEIGHT AND DISTANCE FROM DOOR WITH ARCHITECT.

E. DUCT INSULATION MATERIALS SHALL MEET SMOKE AND FLAME SPREAD REQUIREMENTS FOR PLENUM INSULATION.

F. DUCT INSULATION SHALL FOLLOW THE SCHEDULES IN THE SPECIFICATION AS A MINIMUM REQUIREMENT. THESE REQUIREMENTS SHALL APPLY REGARDLESS OF WHETHER OR NOT DUCT INSULATION IS SHOWN ON THE DRAWINGS.

G. WHERE DUCT INSULATION IS SHOWN ON THE DRAWINGS (EITHER WITH THE HATCHING CONVENTION OR BY MEANS OF A KEY NOTE) AND EXCEEDS THE REQUIREMENTS OF THE SCHEDULES IN THE SPECIFICATION, THE ADDITIONAL INSULATION REQUIREMENTS SHALL BE MET.

H. PROVIDE MANUAL BALANCE DAMPERS FOR EACH EXHAUST, SUPPLY, AND RETURN GRILLE WHERE AN AIR VOLUME HAS BEEN PROVIDED.

I. INSTALL BALANCE DAMPERS AS FAR AWAY FROM GRILLES OR DIFFUSERS SERVED AS PRACTICALLY POSSIBLE AND IN AN EASILY ACCESSIBLE LOCATION.

J. CONTRACTOR SHALL SCAN FOR REBAR AND CONDUIT AND PROVIDE RESULTS OF SCAN IN WRITING TO OWNER PRIOR TO CORING OR DRILLING IN ANY CONCRETE WALL OR FLOOR.

K. THE INTERRUPTION OF ANY SERVICES SHALL BE COORDINATED WITH THE BUILDING OWNER AND SHALL BE KEPT TO A MINIMUM.

MECHANICAL RENOVATION GENERAL NOTES

N

Certificate of Authorization

Epp Siepman Engineering Inc.

No. 4035

10 9 8 7 6 5 4 3 2 1

10 9 8 7 6 5 4 3 2 1

F

E

D

C

B

A

F

E

D

C

B

A

F F C F F

F

C

F

FFCFF

F

C

F

CONSULTANT - SUB-CONSULTANT:

KEYPLAN:

SEAL:

CLIENT:

CLIENT REF. #:

PROJECT:

DISCLAIMER: COPYRIGHT:

ISSUED FOR - REVISION:

THIS DRAWING AND DESIGN IS COPYRIGHT PROTECTED WHICH SHALL NOT BE USED, REPRODUCED OR REVISED WITHOUT WRITTEN PERMISSION BY WSP CANADA INC. THE CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND UTILITY LOCATIONS AND REPORT ALL ERRORS AND OMISSIONS PRIOR TO COMMENCING WORK. THIS DRAWING IS NOT TO BE SCALED.

GGH-46-10

RV. DATE DESCRIPTION

PROJECT NO.

ORIGINAL SCALE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

DISCIPLINE:

TITLE:

SHEET NUMBER:

ISSUE:

SHEET #:

DATE OF:

IF THIS BAR IS NOT 1"LONG, ADJUST YOUR

PLOTTING SCALE.

MECHANICAL

1"

--

--

-- OF --

RV. #

0

NTSAs indicated

STONEWALL, MB

17042

SECOND FLOOR - MECHANICALDEMOLITION & RENOVATION

PLAN - STONEWALL

STONEWALL RCMPDETACHMENT

M2.3

TD

TD

SD

KEY NOTES1 EXISTING SECURE SIDE FURNACE TO REMAIN.2 CONNECT NEW DUCTWORK INTO EXISTING SECURE SIDE FURNACE WITHIN MECHANICAL

ROOM. REWORK INSULATION AT THIS LOCATION TO ENSURE A PROPER VAPOR BARRIER ISMAINTAINED.

3 DUCT DROP TO AIR TERMINAL BELOW.4 CONNECT RETURN DUCT FOR NEW INTERVIEW ROOM INTO SECURE SIDE FURNACE RETURN

DUCT.5 PROVIDE ACOUSTIC SECTION OF DUCTWORK AS SHOWN. DUCTWORK SHALL BE COMPLETE

WITH 25MM ACOUSTIC LINING.6 OFFSET DUCTWORK TO AVOID EXISTING SERVICES WITHIN MECHANICAL ROOM.

400 - 136 Market AvenueWinnipeg, MB R3B 0P4

T 204 453 1080

M2.3 SCALE: 1 : 50

1 SECOND FLOOR - MECHANICAL DEMOLITION & RENOVATION - STONEWALL

O May 12, 2017 Issued for Tender

Page 19: WALL TYPES: LEGEND · wall types: p1 c1 ew1 stc 50 16 mm type x gypsum board 60 acoustic batt insulation 31 x 64 25 ga steel studs, 600 o.c. max. min. 25 mm air space between existing

Θ

STEEL RETAINING ANGLESSHALL BE INSTALLED

AROUND ALL FOUR SIDES OFDUCT. (REFER TO SCHEDULE

FOR MINIMUM SIZE)

WALL OR FLOOR

DAMPER SLEEVE SHALL BETHE SAME GAUGE OR

HEAVIER AS THE DUCT TOWHICH IT IS ATTACHED

FIRE DAMPER WITH BLADESAND FRAME OUTSIDE OF THE

AIR STREAM

EXPANSION CLEARANCE SHALLBE A MINIMUM OF 3mm (1/8") PER

FOOT OF WIDTH OR HEIGHT OFTHE SLEEVE TO A MAXIMUM OF

38mm (1 1/2") AND A MINIMUM OF6.25mm (1/4")

SECURE ANGLES TO SLEEVEAS PER MANUFACTURERS

SPECIFICATIONS

FIRESTOP AROUNDEXTERIOR OF DUCT. FIRERATING OF FIRESTOPPING

SYSTEM SHALL MEET OREXCEED THAT OF WALL

ASSEMBLY. INSTALLATIONSHALL BE AS PER

MANUFACTURERSSPECIFICATIONS

ACCESS DOOR SHALL BE OFSUFFICIENT SIZE TO SERVICEAND INSPECT FIRE DAMPER.

38mm (1 1/2") X 38 (1 1/2")X 16 GAUGE

UNDER 2250mm (90")IN HEIGHT OR WIDTH

RETAINING ANGLES SIZE

OVER 2250mm (90") INHEIGHT OR WIDTH

50mm (2") X 50mm (2")X 10 GAUGE

SIZE OF FIRE DAMPER

EXTEND SLEEVE PAST WALL OR FLOOR TOALLOW PROPER FASTENING OF RETAININGANGLES TO A MAXIMUM LENGTH OF 150mm(6"). (REFER TO MANUFACTURERSSPECIFICATIONS FOR EXCEPTIONS)

MINIMUM25mm (1")

W

L

CLOSE OPENINGSAT CORNERS

L=W/4, 4" (102mm) MIN.

D2

D1

45 DEGREE ENTRY Θ 45°

D1 NOT LESS THEN D245° LEAD IN

DO NOT USE CONNECTIONS WITH SCOOPS.

SCALE: N.T.S.

FIRE DAMPER - FUSIBLE LINKSCALE: N.T.S.

BRANCH CONNECTIONS

Certificate of Authorization

Epp Siepman Engineering Inc.

No. 4035

10 9 8 7 6 5 4 3 2 1

10 9 8 7 6 5 4 3 2 1

F

E

D

C

B

A

F

E

D

C

B

A

F F C F F

F

C

F

FFCFF

F

C

F

CONSULTANT - SUB-CONSULTANT:

KEYPLAN:

SEAL:

CLIENT:

CLIENT REF. #:

PROJECT:

DISCLAIMER: COPYRIGHT:

ISSUED FOR - REVISION:

THIS DRAWING AND DESIGN IS COPYRIGHT PROTECTED WHICH SHALL NOT BE USED, REPRODUCED OR REVISED WITHOUT WRITTEN PERMISSION BY WSP CANADA INC. THE CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND UTILITY LOCATIONS AND REPORT ALL ERRORS AND OMISSIONS PRIOR TO COMMENCING WORK. THIS DRAWING IS NOT TO BE SCALED.

GGH-46-10

RV. DATE DESCRIPTION

PROJECT NO.

ORIGINAL SCALE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

DISCIPLINE:

TITLE:

SHEET NUMBER:

ISSUE:

SHEET #:

DATE OF:

IF THIS BAR IS NOT 1"LONG, ADJUST YOUR

PLOTTING SCALE.

MECHANICAL

1"

--

--

-- OF --

RV. #

0

NTS

STONEWALL, MB

17042

MECHANICAL DETAILS &SCHEDULES - STONEWALL

STONEWALL RCMPDETACHMENT

M2.4

TD

TD

SD

400 - 136 Market AvenueWinnipeg, MB R3B 0P4

T 204 453 1080

HEAT/ENERGY RECOVERY VENTILATION UNIT SCHEDULE

MARKMAKE MODEL

SUPPLY AIRFLOW EXHAUST AIRFLOW SUPPLY FAN E.S.P. SUPPLY FAN POWER EXHAUST FAN E.S.P. EXHAUST FAN POWERFILTERS

MAXIMUM DIMENSIONS MAXIMUM WEIGHT ELECTRICALNOTES(cfm) (L/s) (cfm) (L/s) (" w.c.) (Pa) (hp) (kW) ("w.c.) (Pa) (hp) (kW) HEIGHT LENGTH WIDTH (lbs) (kg) VOLTAGE PHASE

ERV 1 RenewAire EV200 200 94 200 CFM 94 L/s 0.2 37 0.10 0.07 0.2 in-wg 37 Pa 0.10 hp 0.07 kW 2 X MERV 8 559 864 610 110 50 120 V 1

1. Unit to be provided with manufacturer support system and unit controls, refer to specification.

HOOD & WALL CAP SCHEDULE

MARKMANUFACTURER MODEL

WIDTH / DIAMETER HEIGHTDESCRIPTIONin mm in mm

HD 1 Broan 643FA 8" 203 8" 203 GALVANIZED WALL CAP WITH BIRD SCREEN.HD 2 Broan 643EA 8" 203 8" 203 GALVANIZED WALL CAP WITH BIRD SCREEN, BACK DRAFT DAMPER.

ELECTRIC DUCT HEATER SCHEDULE

MARKMAKE MODEL ZONE SERVED

DUCT SIZE CONNECTIONS HEAT OUTPUT AIR FLOW ELECTRICALCONTROL NOTESWidth/Diameter Height (kW) (BTUh) (cfm) (L/s) VOLTAGE PHASE

DH 1 Thermolec FC ERV Intake 8" 0 5.0 17061 200 94.4 240 V 1 SCR Control with Duct Thermostat

DIFFUSER & GRILLES SCHEDULE - STONEWALL

MARKMODEL NOTES

S 1 12X6/520/F/L/A/B12S EX 12x4/LBP 1R 1 10X10/80/F/A/B12R 2 8x8/MSBL/6/B12 2

1. Existing grille to be reused in renovation where indicated.2. Contractor to field verify ceiling thickness prior to ordering grille.

O May 12, 2017 Issued for Tender