t uch - agrivent.com

178
i T uch series Installation / User’s Guide ATTENTION ELECTRICIAN SEE WIRING DETAILS ON PAGES A-3 TO A-28 AND ADDITIONAL INFORMATION IN SECTION B USER’S GUIDE INSTALLATION GUIDE INDEX / WARRANTY WIRING DIAGRAM

Upload: others

Post on 19-May-2022

12 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: T uch - agrivent.com

iT uchseries

Installation / User’s Guide

ATTENTION ELECTRICIAN

SEE WIRING DETAILS ON PAGES A-3 TO A-28 AND

ADDITIONAL INFORMATION IN SECTION B

US

ER

’S G

UID

E

INS

TA

LL

AT

ION

GU

IDE

IN

DE

X /

WA

RR

AN

TY

W

IRIN

G D

IAG

RA

M

Page 2: T uch - agrivent.com

WIRING DIAGRAM

Section A-2

WARNINGS AND PRECAUTIONS

Although the manufacturer has made every effort to ensure the accuracy of the

information contained herein, this document is subject to change without notice due to

ongoing product development.

WARNINGS AND PRECAUTIONS

Equipment, probe failure, blown fuses and/or tripped breakers may prove harmful to the

contents of the building. Therefore it is strongly recommended to install backup devices

and alarm or warning devices. Spare equipment should also be available at the owner’s

site. Equipment manufactured by the manufacturer is protected against normal line

surges. High surges caused by thunderstorms or power supply equipment may damage

this equipment. For added security against line voltage surges it is recommended that

surge and noise suppression devices be installed at the electrical distribution panel. Use

of shielded cable for probes is recommended for protection against lightning. These

devices are available from most electrical supply distributors.

RECOMMENDATIONS

The manufacturer recommends that all installation procedures described herein be

performed by a qualified electrician or installation technician. Furthermore the

manufacturer recommends testing all the functions and equipment connected to the

controller, including the alarm system and backup devices, after installation, after

changes to the installation and every month after that.

Fuse verification and replacement, as well as the proper setting of control values shall be

the responsibility of the owner of this equipment.

Page 3: T uch - agrivent.com

WIRING DIAGRAM

Section A-3

WIRING DIAGRAM

SECTION A

Page 4: T uch - agrivent.com

WIRING DIAGRAM

Section A-4

BOX AND BOARD LAYOUT*

* Some board may not be present depending on your setup.

** This board must be ordered separately.

RE

LA

Y B

OA

RD

RE

LA

Y B

OA

RD

RE

LA

Y B

OA

RD

VA

R.

BO

AR

D

TRANSFO12 VDC

RE

LA

Y B

OA

RD

VA

R.

BO

AR

D

VA

RIA

BL

E C

ON

TR

OL

F

C

SW

ITC

H B

OA

RD

SW

ITC

H B

OA

RD

E1

RELAY CONTROL

D

E2

E3

E4

SW

ITC

H B

OA

RD

SW

ITC

H B

OA

RD

C1

C3

B

MA

IN B

OA

RD

I-T

OU

CH

AX

13

83

X1

21

1

X11

92

X11

92

X11

92

X11

92

X1

20

6

X1

20

4X

12

04

X1

18

4X

11

84

X1

18

4X

11

84

PO

T B

OA

RD

DX

12

05

X1193

C

JP1

ST

AN

DA

RD

PR

B1

4 =

4

-20

mA

JP2

SE

NS

OR

& C

OM

M. B

OA

RD

J

MP

1

JM

P2

(P

RB

15

)

(P

RB

16

)

AX

1199

OU

TP

UT

BO

AR

D

X12

01**

C1

C2

US

B 1

-2

US

B

-3

4

HD

MI

SDC

ARD

4 i, 2 i20 20 , 415i, 215i, 410i, 210iB

8IN

PU

T B

OA

RD

-

JP1

STA

ND

AR

D

4-20m

A

JP

2

JP

1 JP

2(PR

B7) (P

RB8

)

X1

20

0*

*

8 C

OM

M.

PO

RT

CX

21

76

Page 5: T uch - agrivent.com

WIRING DIAGRAM

Section A-5

** This board must be ordered separately.

RE

LA

Y B

OA

RD

RE

LA

Y B

OA

RD

RE

LA

Y B

OA

RD

TRANSFO12 VDC

RE

LA

Y B

OA

RD

SW

ITC

H B

OA

RD

SW

ITC

H B

OA

RD

E1

RELAY CONTROL

D

E2

E3

E4

SW

ITC

H B

OA

RD

SW

ITC

H B

OA

RD

X11

92

X11

92

X11

92

X11

92

X1

18

4X

11

84

X1

18

4X

11

84

PO

T B

OA

RD

DX

12

05

X1193

JP1

ST

AN

DA

RD

PR

B1

4 =

4

-2

0m

A

JP2

SE

NS

OR

& C

OM

M. B

OA

RD

J

MP

1

J

MP

2

(PR

B1

5)

(PR

B1

6)

AX

1199

C

OU

TP

UT

BO

AR

D

X1

201

**

SW

ITC

H B

OA

RD

SW

ITC

H B

OA

RD

X11

92

X11

92

RE

LA

Y B

OA

RD

RE

LA

Y B

OA

RD

X1

18

4X

11

84

C1

C3

B

MA

IN B

OA

RD

I-T

OU

CH

AX

13

83

X1

21

1

C1

C2

US

B 1-2

US

B

-3

4

HD

MI

SD

CA

RD

ST25i, ST30i

B

8IN

PU

T B

OA

RD

-

JP

1

STA

NDA

RD

4-2

0m

A

JP

2

JP

1 JP

2(PR

B7) (P

RB8

)

X1

20

0*

*

8 C

OM

M.

PO

RT

CX

21

76

Page 6: T uch - agrivent.com

WIRING DIAGRAM

Section A-6

** This board must be ordered separately.

RELAY BOARD RELAY BOARD

RELAY BOARD

VAR. BOARD

TR

AN

SF

O

12

VD

C

RELAY BOARD

VAR. BOARD

VARIABLE CONTROL F

C

SWITCH BOARD SWITCH BOARD

E1

RE

LA

Y C

ON

TR

OL

D

E2

E3

E4

SWITCH BOARD SWITCH BOARD

X1192

X1192

X1192

X1192

X1206

X1204 X1204

X1184 X1184

X1184 X1184

X1

193

SWITCH BOARD SWITCH BOARD

X1192X1192

RELAY BOARD RELAY BOARD

X1184 X1184

J P1

STAN DARDPR B14 = 4-20m A

JP 2

S E NS OR & COMM. BOARD

JMP1 JMP2(PR B15) (P RB16)

AX1199

OUTPUT. BOARD

C

X1201

POT BOARD

DX1205B

8 INPUT BOARD-

JP1

STA ND AR D4- 20m A

JP2

JP 1 JP 2(P RB 7) ( PR B8)

X1200**

C1

C3

B

MAIN BOARD I-TOUCHA

X121 1

C1C2

USB 1-2

USB -3 4

H D M I

SDC AR D

4 i, 2 i30 30 , 425i, 225i

8 COMM. PORT

C X 21 76

Page 7: T uch - agrivent.com

WIRING DIAGRAM

Section A-7

** This board must be ordered separately.

RELAY BOARD RELAY BOARD

RELAY BOARD

TR

AN

SF

O

12

VD

C

RELAY BOARD

SWITCH BOARD SWITCH BOARD

E1

RE

LA

Y C

ON

TR

OL

D

E2

E3

E4

SWITCH BOARD SWITCH BOARD

X1192

X1192

X1192

X1192

X1184 X1184

X1184 X1184

X1

19

3

SWITCH BOARD SWITCH BOARD

X1192X1192

RELAY BOARD RELAY BOARD

X1184 X1184

J P1

STAN DARDPR B14 = 4-20m A

JP 2

S E NS OR & COMM. BOARD

JMP1 JMP2(PR B15) (P RB16)

A

X1199

OUTPUT. BOARD

C

X1201

POT BOARD

D X1205B

8 INPUT BOARD-

JP1

STA ND AR D

4- 20m A

JP2

JP 1 JP 2

(P RB 7) ( PR B8)

X1200**

C1

C3

B

MAIN BOARD I-TOUCH

A

X121 1

C1C2

USB 1-2

USB -3 4

H D M I

SD

C AR D

ST40i, ST35i

8 COMM. PORT

C X 21 76

RELAY BOARD RELAY BOARD

X1184 X1184

SWITCH BOARD SWITCH BOARD

X1192X1192

Page 8: T uch - agrivent.com

WIRING DIAGRAM

Section A-8

WIRING DIAGRAM SENSOR AND COMM. BOARD

Page 9: T uch - agrivent.com

WIRING DIAGRAM

Section A-9

WIRING DIAGRAM 8-INPUT BOARD

Page 10: T uch - agrivent.com

WIRING DIAGRAM

Section A-10

WIRING DIAGRAM 8-INPUT MGCB BOARD

Page 11: T uch - agrivent.com

WIRING DIAGRAM

Section A-11

Page 12: T uch - agrivent.com

WIRING DIAGRAM

Section A-12

Page 13: T uch - agrivent.com

WIRING DIAGRAM

Section A-13

WIR

ING DIAGRAM 8 COMM. PORT BOARD

Page 14: T uch - agrivent.com

WIRING DIAGRAM

Section A-14

WIRING DIAGRAM RELAY BOARD (REL-5)

Page 15: T uch - agrivent.com

WIRING DIAGRAM

Section A-15

Page 16: T uch - agrivent.com

WIRING DIAGRAM

Section A-16

WIRING DIAGRAM AIR INLETS

Page 17: T uch - agrivent.com

WIRING DIAGRAM

Section A-17

WIRING DIAGRAM VARIABLE BOARD (VAR-2)

Page 18: T uch - agrivent.com

WIRING DIAGRAM

Section A-18

WIRING DIAGRAM OUTPUT BOARD (0-10V)

Page 19: T uch - agrivent.com

WIRING DIAGRAM

Section A-19

WIRING DIAGRAM V4

Page 20: T uch - agrivent.com

WIRING DIAGRAM

Section A-20

WIRING DIAGRAM OPTI-GAIN 1

Page 21: T uch - agrivent.com

WIRING DIAGRAM

Section A-21

WIRING DIAGRAM FBT / LIM

Page 22: T uch - agrivent.com

WIRING DIAGRAM

Section A-22

TYPICAL INSTALLATION LAYOUT

Page 23: T uch - agrivent.com

WIRING DIAGRAM

Section A-23

WIRING DIAGRAM MS10

Page 24: T uch - agrivent.com

WIRING DIAGRAM

Section A-24

WIRING DIAGRAM SORT MASTER

Page 25: T uch - agrivent.com

WIRING DIAGRAM

Section A-25

WIRING DIAGRAM SL20 POT BOARD AND RELAY CONTROL

Page 26: T uch - agrivent.com

WIRING DIAGRAM

Section A-26

WIRING DIAGRAM SL20 RELAY BOARD

Page 27: T uch - agrivent.com

WIRING DIAGRAM

Section A-27

ELECTRICIAN’S NOTES

(PROBE WIRING) SHIELDED WIRE AWG #22 WITH 16/30 STRANDING, 500ft

(150m) MAXIMUM LENGTH (Ex.: DECA 73-310).

For other probe, refer to specific probe manual for appropriate maximum length and

wire size or use AWG #22, 500ft (150m) MAXIMUM LENGTH.

(COMMUNICATION WIRING) SHIELDED, TWISTED PAIR (8 TWIST/FT). MAX

LENGTH FOR 350PF/M CABLE : 500FT (150M). MAX LENGTH FOR 89PF/M

CABLE : 820FT (250M).

HIGH VOLTAGE WIRE INSTALLED ACCORDING TO LOCAL WIRING CODE.

INSTALL LOW VOLTAGE WIRES (PROBES, COMPUTER LINK OR

POTENTIOMETER WIRES) AT LEAST 12 INCHES (30cm) AWAY FROM HIGH

VOLTAGE WIRES (120/230VAC, 24VDC). ALWAYS CROSS HIGH AND LOW

VOLTAGE WIRES AT A 90-DEGREE ANGLE.

RELAYS : 20A @250 VAC RESISTIVE, MOTOR 2HP @250 VAC, 1HP 120 VAC

AT EACH OUTPUT.

TRIAC : THE CURRENT SHALL NOT EXCEED 8A AT EACH OUTPUT.

MAXIMUM 2 WIRES OF SAME SIZE PER BLACK TERMINAL, NO BIGGER

THAN AWG #12, NO SMALLER THAN AWG #22.

1 WIRE ONLY PER GREEN TERMINAL. USE WIRE CONNECTOR IF YOU

WANT TO CONNECT MORE THAN 1 WIRE, NO BIGGER THAN AWG #12, NO

SMALLER THAN AWG #28.

CHECK INSTALLATION SECTION FOR ALARM WIRING.

USE SHIELD FOR SHIELDING PURPOSE ONLY. CONNECT 1 END AND 1 END

ONLY OF THE SHIELD TO THE CONTROL CIRCUIT COMMON END . NEVER

LEAVE BOTH ENDS OF THE SHIELD UNCONNECTED. NEVER CONNECT

BOTH ENDS OF THE SHIELD TO COMMON . THE USE OF A SHIELD FOR

ALL PROBES AND POTENTIOMETERS IS MANDATORY.

REFER TO FIGURE 14 FOR WIRING DETAILS.

JP1 – JUMPER MUST BE INSTALLED ON PIN 1-2 =ID1 JP1 – JUMPER MUST BE INSTALLED ON PIN 2-3 = 4-20mA AND

JP2 – JUMPER MUST BE INSTALLED ON PIN 1-2 =STANDARD.

VARIABLE BOARDS (X1279) OF THE V4 MODULE REQUIRE THE SAME

PHASE AND VOLTAGE AS THE MAIN BOARD (X1335) OF THE MODULE.

THE CURRENT SHALL NOT EXCEED 10A (FAN) OR 15A (LIGHTS) AT EACH

OUTPUT (OUT 1-2).

2

3

5

6

9

4

8

7

12

1

13

14

15

10

11

Page 28: T uch - agrivent.com

WIRING DIAGRAM

Section A-28

JP1 – JUMPER MUST BE INSTALLED ON PIN 1-2 = ID-1 AND

JP2 – JUMPER MUST BE INSTALLED ON PIN 1-2 = 19200bps.

JP1 – JUMPER MUST BE INSTALLED ON PIN 2-3 = ID-2

REFER TO OPTI-GAIN 1 MANUAL FOR WIRING DETAILS.

REFER TO THE FEED BIN SCALE INSTALLATION MANUAL FOR MORE

DETAILS OF THE FEED BIN TRANSMITTER MODULE.

A JUMPER MUST BE PLACED ON POSITION 1-2 (ID=1) AT JP4.

JP1 – JUMPER MUST BE INSTALLED ON PIN 2-3 = ID-2 AND

JP2 – JUMPER MUST BE INSTALLED ON PIN 1-2 = 19200bps.

JP3 – JUMPER MUST BE INSTALLED ON PIN 1-2 = ID-1 AND

JP4 - JUMPER MUST BE INSTALLED ON PIN 1-2 = 19200bps

JP1 - JUMPER MUST BE INSTALLED ON PIN 1-2 = STANDARD AND

JP2 - JUMPER MUST BE INSTALLED ON PIN 1-2 = STANDARD

16

17

18

20

19

21

22

23

Page 29: T uch - agrivent.com

INSTALLATION

Section B-29

INSTALLATION

SECTION B

Page 30: T uch - agrivent.com

INSTALLATION

Section B-30

This section will inform the electrician on proper wiring and installation procedures for

the controller.

The manufacturer recommends that the following installation instructions be followed to

as closely as possible, and that all work be performed by a certified electrician. Failure to

do so may void the warranty.

Unpacking Unpack the controller and inspect contents for damage. Should the contents appear to be

damaged, contact your local distributor to return the equipment.

The package should contain the following standard items:

1 Controller

4 Brackets / 4 Screws

1 Installation / User’s Guide

Mounting hardware required This is the list of the mounting hardware needed, which is not included with the product:

Shielded two-wire cable, AWG #22 (to extend probes)

Shielded two-wire twisted pair cable, AWG #22 (used for communication) see

electrician note for capacitance selection.

4 screws (to hang the unit onto the wall)

Screwdrivers

Soldering iron kit or approved sealed connectors

Drill and hole saw kit

Page 31: T uch - agrivent.com

INSTALLATION

Section B-31

General installation guidelines

Controller - It is recommended to install the unit in a hallway to limit the controller exposure to

noxious gases.

- In order to avoid condensation problems inside the controller, it is recommended to

install the controller on an inside wall. If it is not possible, use spacers to have an air

gap between the wall and the controller.

- It is required to install the controller right side up with the cable entry holes facing

down.

- The enclosure is watertight, but do not spray water or submerge the controller in

water. Cover it carefully with plastic when cleaning the room.

- The controller should be installed in easy-access location but away from damaging

elements (heat, cold, water, direct sunlight, …).

- Do not drill the face, the side, the top or the underside of the control.

- Do not install the controller near high-voltage equipment, power supply or

transformer.

Electrical cables - All electrical cables must be installed according to local wiring codes.

- All cable shields must be connected to the shield terminal on the cord to which the

cable is connected, except for the cable connected to the optional PC interface. The

shield is needed to protect the controller and the modules against any electromagnetic

interference generated by lightning or nearby operating machinery.

- Never use the shield as a conductor.

- Connect only one end of the shield to the controller.

- Use separate conduits for the low voltage cables (communication and probes) and the

high voltage cables. There must be at least 1 foot (30 cm) between low-voltage and

high-voltage conduits.

- If a low voltage cable has to cross over a high voltage cable, make this crossing at

90°.

- All cable connections must be soldered or done with approved sealed connectors.

- Probe cables must be 500’ (150m) or less.

- Communication cables must be 820’ (250m) or less.

- It is prohibited to use overhead cables outside the building.

Electrical power - Protection from electrical surges should be included in the planning of each

installation.

- Every module should have a separate breaker to avoid unwanted consequences.

- The V2 and V1 modules require the same voltage and phase as the VAR BOARD

(X1204) power source.

- The OUT1 and OUT2 outputs require the same phase and same voltage as the

controller to operate.

- It is strongly recommended to have a backup power source to ensure life-sustaining

conditions in case of power failure (see figure 11).

Page 32: T uch - agrivent.com

INSTALLATION

Section B-32

- It is also strongly recommended to install a backup thermostat system parallel to the

controller module output (see figures 12 and 13) to supply sufficient airflow and

heating.

- The backup system and alarm must be thoroughly tested and verified as working

properly before using the ventilation system.

Mounting - The enclosure must be mounted in a location that will allow the cover to be

completely opened.

- Fasten the four brackets to the four mounting holes on the back of the enclosure using

the four screws provided with the brackets.

- Then mount the enclosure on the wall by inserting screws through the brackets’

adjustment slots, into the wall. Make sure to position the enclosure so that all wires

extend out of the bottom section of the enclosure.

- The bracket slots serve to adjust the position of the controller.

- Once you have adjusted the controller position, tighten the four mounting screws. (see

figure 1).

FIGURE NO. 1 Mounting Position and Devices

Page 33: T uch - agrivent.com

INSTALLATION

Section B-33

Connection procedure

Detailed wiring diagrams

Typical Sensor Wiring for Probes

An inside temperature sensor should be located in the area which gives the most accurate

temperature reading to achieve optimum ventilation. The sensor should be connected to

the controller with a shielded two-wire cable. It should be located in an area protected

from operating machinery, animal bites, personnel or anything that could damage the

sensor.

The outside temperature sensor should be installed in a location which is not influenced

by heat generated from inside the building or direct sunlight. It should also be protected

from physical damage.

FIGURE NO. 2 Typical Temperature Probe Wiring

PRB3PRB1 PRB2

FIGURE NO. 3 Typical Humidity Probe Wiring

Page 34: T uch - agrivent.com

INSTALLATION

Section B-34

Page 35: T uch - agrivent.com

INSTALLATION

Section B-35

FIGURE NO. 4 Typical Static Pressure Probe Wiring

JP1

STANDARD

4-20mA

JP2

JP1 JP2

(PRB15) (PRB16)

(Jumper 2 (JP2) must be correctly placed in order to use the 4-20mA SP1 static pressure

probe.)

Typical Water Meter Wiring

This function allows the user to measure the amount of consumed water measured in

pulses by the water meter (Example: Kent model C-700 water meter with B-Pulser

interface). The water meter interface must have a N.O. contact.

FIGURE NO. 5 Typical Water Meter Wiring

PRB9 PRB10 PRB11

Page 36: T uch - agrivent.com

INSTALLATION

Section B-36

Typical Feed Sensor Wiring

Feed sensors (ex.: CSD-1 Current Switch Detector) should be mounted inside the

controller enclosure with the feeder power wire running through the sensor loop. If a

single sensor monitors multiple feeder circuit, run the wires from all feeder groups the

same direction through the sensor loop.

The best use for a single feed sensor is monitoring your silo auger motor. This provides a

clear indication of all feed entering the building and it provides an alarm when the feed

silo is empty.

FIGURE NO. 6 Typical Feed Counter Wiring

SENSOR & COMM. BOARD

X1199

RELAY BOARD

X1184

Page 37: T uch - agrivent.com

INSTALLATION

Section B-37

Typical Variable Stage Wiring

FIGURE NO. 7 Typical Variable Stage Wiring

VAR. BOARD

F X1204

FIGURE NO. 8 Other Variable Stage Wiring

VAR. BOARD

F X1204

Note : For this wiring, the power source of the variable stage must be in phase with the

power source of the X1204 board.

Page 38: T uch - agrivent.com

INSTALLATION

Section B-38

Typical Actuator Wiring

Follow the calibration procedure in the user guide; otherwise the actuator positioning will

be erratic.

FIGURE NO. 9 Typical 115VAC-Actuator Wiring

POT BOARD RELAY BOARD

FIGURE NO. 10 Typical 24VDC-Actuator Wiring

TR

AN

SF

OR

ME

R

Page 39: T uch - agrivent.com

INSTALLATION

Section B-39

Typical Power Backup Wiring

A backup relay (DPDT) is connected to the power source 1 in normal operation but will

switch to the power source 2 if source 1 is disabled. The backup relay should be selected

to ensure it is able to support the required power load.

FIGURE NO. 11 Typical Power Backup Wiring

8 PIN RELAY DPDT(OMRON model MK2EP-UA-AC120)

3

4

5

6

2

1

8

7 NO 2

NO 1

NC 1

NC 2COM 2

COM 1

L2/N GND

L1

3

4

5

6

2

1

8

7

L2 L1 GND

source 1

DISTRIBUTIONPANEL

L2 L1

NLINE115/230 VAC

source 2

DISTRIBUTIONPANEL

LINE115/230 VAC

Page 40: T uch - agrivent.com

INSTALLATION

Section B-40

Typical Backup Thermostat Wiring

If the controller or a module fails, the backup thermostats will activate the dedicated fan

or heater as soon as temperature reaches the set point of the thermostat. The thermostat

must be accessible for adjustment and must be set at 3 to 5 degrees above the fan’s set

point or 3 to 5 degrees under the heater set point.

FIGURE NO. 12 Typical Backup Thermostat Wiring on ON/OFF Stage

L2L1

RELAY BOARD

T15WD1 2 P

FIGURE NO. 13 Typical Backup Thermostat Wiring on Variable Stage

L2 L1

VAR BOARD

OUT1LINE

115/230

T15WD1 2 P

OUT2

Page 41: T uch - agrivent.com

INSTALLATION

Section B-41

Typical V1 or V2 Module Wiring

Those modules are used to add one or two variable outputs. The added outputs will

follow the existing variable outputs of the VAR BOARD (X1204).

FIGURE NO. 14 Typical V1 and V2 Module Wiring

VAR. BOARD

1 2

OUT 1115 / 230VINPUT

1 2

OUT 2115 / 230V

The module V# require the same phase and same voltage as the VAR. BOARD to operate

1

1

2

Use a wire connector to connect the ground wire to the ground of the electrical installation.2

3

Communication wiring shielded, twisted pair (8 twist/ft). Max length for 350pf/m cable : 160 ft (50m).max length for 89pf/m cable : 650 ft (200m).

3

Page 42: T uch - agrivent.com

INSTALLATION

Section B-42

Typical Alarm Connection Wiring

The controller provides a normally open and normally closed dry contact to set off an

alarm in case low or high temperature condition occurs. Moreover, this same contact can

be used to signal a power failure or other malfunctions. It may be connected to an alarm

system or directly to a siren and/or auto-dialer.

Make the normally closed (NC) or normally open (NO) connections as indicated in

figures 15 and 16.

The relay will activate about 30 seconds after an alarm is triggered.

FIGURE NO. 15 Typical Alarm Connection Wiring

ALARM SYSTEM /AUTO DIALER

ALARM

P1

HUM(P6) 12 VDC

NC C NO

FIGURE NO. 16 Siren Connection Wiring

Normally closed manual OFF switch

ALARM

P1

HUM(P6) 12 VDC

NC C NO

Page 43: T uch - agrivent.com

INSTALLATION

Section B-43

Powering up procedure Once the controller is properly mounted on the wall and all modules and sensors are

connected to the terminal block, perform the following steps:

Verify all connections Seal all cable entry holes.

Hermetically close the controller Close the front panel and the lower access cover.

Put the power on

Secure the front panel with a lock

Controller compatible probes This is the list of all compatible probes that can be connected with the controller and a

short description of their function.

Temperature probe 2004-10K (black cap)

Temperature probe with a temperature range of -58.0 to 140.0 °F (-50.0 to 60.0 °C).

Relative humidity probe

Relative humidity probe with a measuring range of 0 to 100 RH% (red connector).

Static pressure probe

Static pressure probe with a measuring range of -0.500”WC to 0.500”WC (-99Pa to

99Pa).

Controller compatible modules This is the list of all the compatible modules that can be connected with the controller

with a short description of their function.

Variable module

V1 (1 variable output)

V2 (2 variable outputs)

V4 (4 variable outputs)

Relay slave module

SL## (Add up to 20 relays and 8 inlets)

Scale module

FBT / LIM (Bin Scale)

Opti-Gain 1 (Poultry Scale)

Sort Master (Hog Scale)

Computer interface

Communication card X1202 (Board placed into the controller to communicate with

the computer interface)

RF-IN2 Communication Module (Module inserted into the controller for a wireless

communication with the computer interface)

Page 44: T uch - agrivent.com

INSTALLATION

Section B-44

Specifications

CONTROLLER Storage temperature -20°C to 55°C (-4°F to 131°F) Operating temperature 0°C to 50°C (32°F to 122°F) Humidity 90% maximum Non-condensing

NORMS CSA (NRTL/C) Weight 12.4 kg (27.2 lb) Size 50.2 cm x 40.6 cm x 20.3 cm

(19 3/4 x 16 x 8) Protection index IP 66 Warranty 2 years

POWER SUPPLY Operational voltage range 90 to 250 VAC Operational frequency range 45 to 65 Hz Power supply circuit consumption (CPU

Board) 65 W maximum

SENSOR & COMM. BOARD (X1199)

INPUTS (PRB1- PRB20)

Input measuring range 0 Ohm, open circuit

0-5000 mV

0-20 mA (PRB 15 and 16) Maximum frequency for the water meter

(50% cycle) 4 Hz

Maximum wire length 150 m (500 feet) Recommended wires 2 strands, shielded, AWG #22

12 VDC SOURCE (12VDC)

Maximum current allowed 100 mA

COMMUNICATIONS PORTS (P1, P2,

HUM)

Maximum wire length (2400 bps) 250 m (820 feet) Maximum wire length (19200 bps) 2 m (6.5 feet) Recommended wire 2 strands, twisted pair, low capacity, shielded,

AWG #22

ALARM RELAY (ALARM)

Maximum current 1 A at 30 VDC Delay before switching 30 seconds (approximate) Fuse 1A 250VAC

Page 45: T uch - agrivent.com

INSTALLATION

Section B-45

RELAY BOARD (X1184)

OUTPUT RELAYS

Maximum Power 20A @ 240VAC Maximum Current 2HP @ 240VAC, 1HP @ 120VAC Caution Notice These relays are rated by UL and CSA at 20A

or 2HP. However, for outputs requiring

frequent activation (ex : minimum ventilation

fans working on a timer) it is recommended

not to use more than 1 HP per relay (at 250

VAC)

POT BOARD (X1205)

INLET POTENTIOMETER

(POT 1 TO POT 8)

Inlet potentiometer 0-10K ohms Maximum wire length 150 m (500 feet) Recommended wire 3 strands, shielded, AWG #22

OUTPUT BOARD (X1201)

COMMUNICATIONS PORTS (P3 - P4) Maximum wire length (2400 bps) 250 m (820 feet) Maximum wire length (19200 bps) 2 m (6.5 feet) Recommended wire 2 strands, twisted pair, low capacity, shielded,

AWG #22

SOURCE 12 VDC (12VDC) Maximum current allowed 100 mA

0-10V OUTPUT

(0-10V OUTPUT 1 AND 0-10V OUTPUT 2)

Output 0-10Volts, 2% precision Maximum load 10mA Maximum wire length 30 m (100 feet) Recommended wire 2 strands, shielded, AWG #22

VAR. BOARD (X1204)

TRIAC OUTPUT Maximum Allowable Current (Fuse value) 8A, 120 / 208 / 240VAC Recommended maximum current for

incandescent lighting 7A, 120 / 208 / 240VAC

Recommended maximum current for fans 6A, 120 / 208 / 240VAC Maximum wire length

(Var. Communication) 200 m (650 feet)

Recommended wire 2 strands, twisted pair, low

capacity,(Capacitance between conductors @

1Khz = 24pF/ft), shielded, AWG #22

Page 46: T uch - agrivent.com

INSTALLATION

Section B-46

PC COM. BOARD (X1202)

COMMUNICATIONS PORT (P0) Maximum wire length A loop must not exceed 750 m (2400 feet). If

not using recommended wiring, total length

must be lesser than 5 m (16 feet). Recommended wire 1 wire with 2 pairs, twisted pair, RS-485.

8 COMM. PORT (X1399)

COMMUNICATIONS PORT (P9-P16) Maximum wire length (2400 bps) 820 feet (250m) Maximum wire length (19200 bps) 6.5 feet (2m) Recommended wire 2 strands, twisted pair, low capacity,

shielded, AWG #22

SOURCE 12 VDC (12VDC)

Maximum current allowed 100mA

8-INPUT MGCB BOARD (X1276)

PROBE INPUTS

Input measuring range 0 Ohm, open circuit

0-5000 mV

0-20 mA (PRB 7 and 8) Maximum frequency for the water meter

(50% cycle) 4 Hz

Maximum wire length 150 m (500 feet) Recommended wires 2 strands, shielded, AWG #22

SOURCE 12 VDC (12VDC) Maximum current allowed 100mA

Important Notice: - It is important to have a backup system in case of a system failure.

- Low-voltage and high-voltage wires must be passed through different conduits at

least 1 foot (30 cm) apart. If low-voltage and high-voltage conduits must be

crossed, the crossing must be at a 90-degree angle.

- All wiring must be made by a certified electrician and conform to local electrical

regulations.

Page 47: T uch - agrivent.com

INSTALLATION

Section B-47

Troubleshooting

SYMPTOM CAUSE SOLUTION

Temperature probe reads

LO

Temperature is below -58°F

(-50°C).

Probe is disconnected or

defective.

Check all connections. If the

problem persists, and the

temperature is within normal

range, replace the probe.

Temperature probe reads

HI

Temperature is above 140°F

(60°C).

Probe is short circuited or

defective.

Check all connections. If the

problem persists, and the

temperature is within normal

range, replace the probe.

Screen is blank Controller is not powered.

The connector between the top

and the main boards or

between the relay control and

the main boards of the

controller is disconnected.

Make sure the control is

powered.

Make sure both connectors

are properly connected.

Page 48: T uch - agrivent.com

USER’S GUIDE

Section C-48

USER’S

GUIDE

SECTION C

Page 49: T uch - agrivent.com

USER’S GUIDE

Section C-49

Control Description

[4]

[3] [1]

[2]

[5]

[6]

[5]

[7]

[7]

[7]

Page 50: T uch - agrivent.com

USER’S GUIDE

Section C-50

1. Back Button

The Back button allows the users to return to the previous screen.

2. Home Button

The Home button allows the user to return to the home screen and opens the list of recent

applications (press and hold).

3. List Button

The List button allows the user to open the list of options available on the current screen

or open the virtual keyboard (press and hold).

4. Touch Screen

The Touch screen lets you easily select items or perform functions. Control the touch

screen by tapping, tapping and holding, or dragging across it.

5. Toggle for ON/OFF Relay

Allows the user to set the outputs to ON, OFF or AUTO. When set to AUTO, the outputs

operate according to the configuration.

6. Toggle for Variable Stage

Allows the user to set the outputs to ON, OFF or AUTO. When set to AUTO, the outputs

operate according to the configuration.

7. Output LED

These LEDs will come ON whenever the respective relay is active. The LED may flash if

the toggle switch is not set to AUTO depending on the BLINK ON TOGGLE SWITCH

MANUAL MODE option.

Page 51: T uch - agrivent.com

USER’S GUIDE

Section C-51

GLOSSARY

Throughout this document, the following terminology is used. All of the terms mentioned

below will appear regularly and will be in Bold to indicate that the full description is in

the glossary.

Target Temperature This is the temperature goal for the room and it is also the

reference temperature for all relative settings. Note that

the Target Temperature may be affected by the

Ramping Function.

Growth Day This is the reference day used for Ramping Function. It

may be set to OFF, deactivating all Ramping Function. If

it is adjusted to a value other than OFF, it will be

incremented each day.

Growth Curve The Growth Curve is composed of value points and day

points. It is used for the Ramping Function. When the

Growth Day is equal to a given day point, the associated

value point will be the value taken by the parameter

affected by the Ramping Function.

Ramping Function The Ramping Function is used to modify a parameter

value automatically. When the Ramping Function is

activated, the affected parameter will be updated each

hour according to its Growth Curve and the Growth

Day.

RSP Relative Set Point: Number of degrees relative to the

Target Temperature where a function begins.

Differential Number of degrees changed before stopping the output.

For example, with a Differential of 1.0F, the control

turns on a fan at 70.0F when temperature increases, but it

will shut it off only at 70.0F - 1.0F when temperature

decreases. The Differential is necessary to avoid

oscillations.

Modulation Band Number of degrees a variable output takes to reach its full

intensity.

Average Temperature This is the temperature calculated using all probes selected

in PROBES FOR AVERAGE.

Outside Temperature This is the temperature read by the outside temperature

probe.

Page 52: T uch - agrivent.com

USER’S GUIDE

Section C-52

Inputs/Outputs Table

Inputs Quantity Outputs Quantity

Inside Temperature 1 to 16 Variable Stage Up to 12

Outside Temperature Up to 1 Variable Stir Fan Up to 4

Humidity Up to 1 On/Off Stir Fan Up to 4

Static Pressure Up to 1 On/Off Stage Up to 24

Water Meter Up to 12 Heater Up to 10

Feed Up to 12 Variable Heater Up to 2

Proximity Switch Up to 6 Sprinkler/Mist Up to 1

Egg Counter Up to 12 Clock Up to 4

Bin Scale Up to 2 Inflatable Inlet Up to 6

Sort Master Up to 2 Air Inlet Up to 16

Poultry Scale Up to 2 Light Up to 2

Feeder Up to 12

Feed Auger Up to 12

High Water Alarm Up to 12

High Temperature Alarm Up to 1

Chimney Up to 2

Heating Floor Up to 1

Water Flush Up to 12

Alarm 1

Standard Equipment

Quantity Description

1 Controller

Up to 6* Relay Board (X1184)

Up to 6* Switch Board (X1192)

Up to 1* Variable Control (X1206)

Up to 2* Var. Board (X1204)

1 Sensor & Comm. Board (X1199)

1 2004-10k Probe

* The amount of boards required varies according to the controller module used.

Page 53: T uch - agrivent.com

USER’S GUIDE

Section C-53

Additional Equipment

Quantity Description

1 PC Com. Board

1 Interface PC

16 2004-10k Probe

1 Humidity Probe

12 Water Meter

12 Feeder

12 Feed Augers

6 Proximity Switches

12 CSD-1

2 Sort Master

1 MS-10

1 SL20, SL15 or SL10

2 Opti-Gain 1

2 FBT / LIM

1 RF-IN2

1 Pot Board (X1205)

1 8 Comm. Board (X1276)

1 8-Input Board (X1200)

3 MGCB 8 Input Board (X1399)

2 V1 (1 Variable Output Module)

2 V2 (2 Variable Output Module)

2 V4 (4 Variable Output Module)

1 Output Board [0-10V] (X1201)

1 Static Pressure Probe

Configuration Version

Version Date Min. Proc.

Version

Modification

CA2iT01V0 13/06/2012 1 - New.

CA2iT01V1 07/02/2013 1 - Corrections on display.

- Static pressure can now use the Pascal or

"WC unit.

- Add High Water Meter Alarm 1-4 relay

type that activates on a high water meter

alarm.

- Change model names for generic terms "#

Variables, # Relays".

- Add 4 heaters.

Page 54: T uch - agrivent.com

USER’S GUIDE

Section C-54

CA2iT01V2 06/05/2013 2 - Add 2 feeder outputs.

- Add 5 feed auger outputs.

- Six feed inputs can now be assigned to any

feeder or feed auger.

- Add the group feature.

- Add parameters to reinitialize all actual

values for heaters, feeders, feed augers and

water meters.

- Add 2 bin scales.

- Modification on variable stage 1 behaviour

in timer mode under its activation

temperature.

CA2iT01V3 06/05/2013 2 - Add 2 air inlets.

- Add 2 variable heaters that can be used on

0-10V outputs.

- Add 4 variable stages (8 total).

- Add 4 variable stir fans.

- Add fan delay for air inlet positioning.

- Add pressure mode for air inlets.

- Add cycle repetition mode for clock, feed

and feed auger outputs.

- Pressure and temperature alarms can now be

set tot OFF.

- Add support for a second V4 module.

- Change frequency drive relays for generic

0-10V relays.

- Alarm history can be erased from iControl

Mode.

- Add lock and unlock feature for iControl

mode.

- Add a warning for alarm relay activation

and deactivation.

- Control mode no longer supported.

Page 55: T uch - agrivent.com

USER’S GUIDE

Section C-55

CA2iT01V4 08/02/2013 2 - Add support for 4 Variables 30 Relays and

0 Variables 30 Relays models.

- Add 2 chimney outputs.

- Add 4 On/Off stir fans.

- Add a absolute minimum opening for

natural potentiometer air inlets.

- Separate start and finish light modulation

times.

- Clock, feed and feed auger run times are

now in mm:ss.

- Add support for MS-10 module.

- Add support for Sort Master module.

- Add an activation period for sprinkler.

- Add an option to allow or prevent heating in

natural mode.

- Add a natural mode only option.

- Add a group consumption recorded value.

CA2iT01V5 09/30/2013 2 - Add 8 air inlets (total 16).

- Add support for SL20.

- Add 8 on/off ventilation stages (total 24).

- Add 4 variable ventilation stages (total 12).

- Add models 0V35R, 2V25R & 4V25R.

- Make bin Load Cell Gain and Maximum

Weight parameters adjustable.

- Add light intensity when light system is off.

- Add a critical low temperature alarm.

- Combine all growth days in one.

- Add a mortality percentage.

- Correction on stop cycle filter times with a

value of 0 for feeders and feed augers.

- Add history for sprinkler activation time.

- Reduce hysteresis and bandwidth parameter

minimums to 0.3°.

- Add a heating floor output.

- Add a 9th

inside temperature probe.

- Add an option to have high water alarm

relays NO or NC.

- Add an option to close pressure mode inlets

outside of tunnel mode.

- Add alarm status for FarmQuest.

- Combine all growth days in one.

Page 56: T uch - agrivent.com

USER’S GUIDE

Section C-56

CA2iT01V6 04/12/2013 2 - Add a logic to allow a position mode inlet to

follow a natural potentiometer inlet in

natural mode.

- Correction on display of scale 2 parameters.

- Correction on high water alarm after night.

- Correction on heater total batch quantity.

- Add 7 inside temperature probes on the

MGCB 8-Input board (X1399).

- Move inside temperature probe 9.

- Add a function to copy settings of one

position mode air inlet to another one.

- Add a parameter to reinitialize all water

meters.

- Allow Protection Minimum Speed to be

applied on dehumidification.

- Add a growth day for each group.

- Add support for a second Sort Master.

- Add support for SL15, SL10 external relay

modules.

- Add the possibility to have many types of

feed (type 1,2,3,4,5). For each type of feed,

a different calibration can be set.

- Add a number of Shipped, Transferred and

Added animals.

- Add the values for the last 5 days in

Building view for average temperature,

sprinkler, bird weight, feed and heating.

- Add an option to activate the alarm relay or

not when a maximum feed or feed auger

alarm condition occurs.

- Add a total mortality value.

- Add 24-hour values for water per animal

and feed per animal.

- Correction on fill evaluation when a bin

scale is activated.

- Group feed consumption is now based on

that group's feed inputs or on the bin scale

consumption, according to a set option.

Page 57: T uch - agrivent.com

USER’S GUIDE

Section C-57

CA2iT01V7 11/02/2014 2 - Correction on the values of the last five

days for feed and feed auger.

- Correction on negative values on the 8-

probe MGCB module.

- Add Tech Param.

- Add turkey scale support.

- Add an adjustable number of cycles for

clocks, feeders and feed augers.

- Add defrost logic for all variable stages.

Preceding stage stops during defrost.

- Add an option to close inflatable inlets in

tunnel mode.

- Correction on the subtraction feature on a

feed input on a maximum alarm.

- Add a feed distribution mode for feed

augers.

- Add feed consumption system for increased

accuracy.

- Add an option to select which probes to

check for high/low temperature probes.

- Options for minimum speed protection on

dehumidification are now individual for

each variable stage.

- Add the possibility to stop a variable

ventilation stage on minimum speed

protection.

- Add a second level of dehumidification with

relative set point and added speed for

variable stage 1-4.

- Correction on minimum and maximum

average temperatures.

Page 58: T uch - agrivent.com

USER’S GUIDE

Section C-58

CA2iT01V8 18/08/2014 2 - Add 8 water meters (total 12) and 11 egg

counters (total 12) that share 12

configurable inputs.

- Add manual count for egg counters.

- Add 6 feed inputs (total 12).

- Add a time period within which bird

weighing is allowed or not.

- Add an icon that displays the humidity set

point in building view.

- Add parameters to reinitialize all elements

of a group.

- Add the type of breeding for that the

controller manages.

- Add an absolute maximum winter opening

for position mode air inlets.

- Add a growth curve for critical high alarm

temperature.

- Add zoned position mode for air inlets.

- Add a stage at which temperature

compensation is allowed for position mode

air inlets.

- Add start and end weight for different types

of breeding.

- Add idle back function between the last

variable state and the first on/off stage.

- Add first ventilation stage activation when

heating is activated.

- Add a growth curve for heater high

temperature shutoff.

- Add a growth curve for maximum opening

temperature for position mode air inlets.

- Add a delay that allows a feeder or feed

auger to restart after having been shutoff by

its proximity switch.

- Air inlet calibration messages now appear

for 1 hour

- Light cycle parameters now disappear for

24-hour periods.

- Chicken scales, turkey scales, bin scales and

Sort Masters can now be assigned or

combined in groups.

- Mortality percentage is now displayed to the

nearest one hundredth of a percent.

- Separate the alarm relay option for feeders

and feed augers.

Page 59: T uch - agrivent.com

USER’S GUIDE

Section C-59

CA2iT01V8 18/08/2014 2 - Night Setpoint Synchronized with Lights

will now be preserved after an update

following V8.

- Correction on 24-hour values.

- Correction on position mode air inlet

settings copy if less than 9 air inlets are

used.

- Correction on feed bin maximum weight

calibration when a tare is made.

- Correction on relay state displayed in

building and Farmquest for some types of

controllers.

- Add a selection for bin scale consumption

measuring method.

- Add 12 water flush outputs.

- Add a selection for naturel mode air inlets

and inflatable inlets that will trigger natural

mode.

- Add an option for LED blink on toggle

switch manual mode.

- Add an option to close before natural mode

or in tunnel mode for natural air inlets.

Page 60: T uch - agrivent.com

USER’S GUIDE

Section C-60

Ventilation System Overview

The different models will determine the amount of variable and relay outputs available on

the controller.

For the controller models using variable outputs, the variables can be used as a

ventilation stage, variable stir fan or as a light output. 0-10 Volt outputs can also be used

as a variable heater or as a chimney.

For all controller models, the relays can be used as a ventilation stage, stir fan, heater,

clock output, a feeder output, a feed auger output, sprinkler, inflatable inlet, 0-10V relay,

a high water alarm or air inlet.

The controller can work with up to 16 inside temperature probes that it can use to

compute an inside average. All outputs will follow the probes selected by the user. When

one temperature probe is defective (short or open circuit), the controller does not consider

it to compute the average and the alarm is triggered. An Outside Temperature can be

used to override the inside temperature alarm if it is too hot outside in order to reduce

false alarms. The outside temperature can also increase ventilation and affect water meter

alarms.

The controller can monitor up to 12 water meters, 12 feeders and 12 feed augers

quantities and trigger alarms in the case of abnormal readings.

The controller can also operate up to 2 light zones, 2 bird scales, 2 bin scales and 2 Sort

Master modules.

Other features, including night set point, Ramping Function and history for alarms,

probes, heaters, feeders, feed augers, water meter, main set point, inlet positions, water

consumption per animal, feed consumption per animal and group consumption are

included in all controller types.

Page 61: T uch - agrivent.com

USER’S GUIDE

Section C-61

ACTUAL CONDITIONS

AVERAGE TEMPERATURE

This parameter displays the average temperature of the probes selected in AVERAGE

PROBES. The average temperature is displayed to the nearest 0.1° from -58.0°F to

140.0°F (-50.0°C to 60.0°C).

TEMPERATURE (1-16)

These parameters display the actual temperature read by the respective probe. Probes that

are not used will not be displayed. Temperatures are displayed to the nearest 0.1° from

-58.0°F to 140.0°F (-50.0°C to 60.0°C).

OUTSIDE TEMPERATURE

This parameter displays the current outside temperature when the outside probe is

activated by OUTSIDE PROBE ACTIVE. The outside temperature is displayed to the

nearest 0.1° from -58.0°F to 140.0°F (-50.0°C to 60.0°C).

HUMIDITY

This parameter displays the actual humidity when the humidity probe is activated by

HUMIDITY PROBE ACTIVE. ERROR will be displayed if the humidity probe has not

communicated with the controller for 5 minutes. The humidity is displayed to the nearest

1RH% from 0RH% to 100RH%.

STATIC PRESSURE

This parameter displays the actual static pressure when this sensor is activated by

STATIC PRESSURE PROBE ACTIVE. The static pressure is displayed to the nearest

0.001”WC (1Pa) from -0.500”WC to 0.500”WC (-99Pa to 99Pa).

WATER METER (1-12)

These parameters display the amount of water counted for each water meter for the

current day. If a water meter is activated in INPUT CONFIGURATION WATER/EGG (1-

12) its count will appear here, otherwise it will not. The amount of water read is

displayed to the nearest unit (litre or gallon) from 0 to 30000 units (litres or gallons).

WATER METER (1-12) 24 HOURS

This parameter displays the amount of units counted in the last 24 hours that the

controller was powered up. This count does not consider the current hour or the time for

which the controller was powered down. Furthermore, changing the time of day will not

affect this count. The amount of water read is displayed to the nearest unit (litre or

gallon) from 0 to 30000 units (litres or gallons).

WATER METER TOTAL GROUP (A-B)

These parameters display the amount of water counted by the total for all water meters of

the respective group for the current day. If at least one water meter is assigned to the

respective group, this value will be visible, otherwise it will not appear.

Page 62: T uch - agrivent.com

USER’S GUIDE

Section C-62

ACTUAL CONDITIONS (CONTINUED…)

WATER METER TOTAL 24 HOURS GROUP (A-B)

These parameters display the amount of units counted in the last 24 hours that the

controller was powered up. This count does not consider the current hour or the time for

which the controller was powered down. Furthermore, changing the time of day will not

affect this count. The amount of water read is displayed to the nearest unit (litre or

gallon) from 0 to 120000 units (litres or gallons).

WATER METER BATCH TOTAL QUANTITY GROUP (A-B)

These parameters display the amount of water counted by the total for all water meters of

the respective group since the batch has started. If at least one water meter is assigned to

the respective group, this value will be visible, otherwise it will not appear. The amount

of water is displayed to the nearest unit (litre or gallon) from 0 to 7999999 units (litres or

gallons).

WATER PER ANIMAL GROUP (A-B)

These parameters display the amount of water counted today per animal for the

respective group. This value is the result of WATER METER TOTAL GROUP (A-B)/

REMAINING ANIMALS GROUP (A-B). The amount of water read is displayed to the

nearest 0.001 unit (litres or gallons) per animal from 0.000 to 999.999 (litres or gallons)

per animal.

FEEDER (1-12) QUANTITY

These parameters display the count for each feeder. If a feeder is selected in a RELAY

TYPE (1-40) parameter and has an associated feed input, its count will be shown,

otherwise it will not appear. The amount of feed is displayed to the nearest unit (kg or lb)

from 0 to 9999 units (kg or lb).

FEEDER (1-12) 24 HOURS

These parameters display the amount of units counted in the last 24 hours that the

controller was powered up. This count does not consider the current hour or the time for

which the controller was powered down. Furthermore, changing the time of day will not

affect this count. The amount of feed is displayed to the nearest unit (kg or lb) from 0 to

9999 units (kg or lb).

FEEDER TOTAL QUANTITY GROUP (A-B)

These parameters display the count for the total of all feeders of the respective group for

the current day. This parameter will be visible if at least one feeder is assigned to the

respective group, otherwise it will not appear.

FEED TOTAL QUANTITY 24 HOURS GROUP (A-B)

These parameters display the amount of units counted in the last 24 hours that the

controller was powered up. This count does not consider the current hour or the time for

which the controller was powered down. Furthermore, changing the time of day will not

affect this count.

Page 63: T uch - agrivent.com

USER’S GUIDE

Section C-63

ACTUAL CONDITIONS (CONTINUED…)

FEED BATCH TOTAL QUANTITY GROUP (A-B)

These parameters display the count for the total of all feeders of the respective group

since the beginning of the batch. This parameter will be visible if at least one feeder is

assigned to the respective group, otherwise it will not appear. The amount of feed read is

displayed to the nearest unit from 0 to 999999 units (kg or lb).

FEED AUGER (1-12) QUANTITY

These parameters display the count for each feed auger. If a feed auger is selected in a

RELAY TYPE (1-40) parameter and has an associated feed input, its count will be shown,

otherwise it will not appear. The amount of feed is displayed to the nearest unit (kg or lb)

from 0 to 9999 units (kg or lb).

FEED AUGER (1-12) 24 HOURS

These parameters display the amount of units counted in the last 24 hours that the

controller was powered up. This count does not consider the current hour or the time for

which the controller was powered down. Furthermore, changing the time of day will not

affect this count. The amount of feed is displayed to the nearest unit (kg or lb) from 0 to

9999 units (kg or lb).

FEED CONSUMPTION (A-B)

These parameters display the quantity of feed counted for each group. The feed

consumption of a group can be the sum of all feed inputs selected in FEED

CONSUMPTION INPUTS (A-B) if no feed bin is used in the respective group, or BIN (1-

2) CONSUMPTION, if one or more feed bins are used in the respective group.

FEED PER ANIMAL GROUP (A-B)

These parameters display the amount of units (lb or kg) counted today per animal for the

respective group. This value is the result of FEED TOTAL QUANTITY GROUP (A-B)/

REMAINING ANIMALS GROUP (A-B). These values are displayed to the nearest

0.001 unit (lb or kg) per animal from 0.000 to 999.999 units (lb or kg) per animal.

EGG COUNTER (1-12)

These parameters display or allow the user to adjust the amount of eggs counted by the

respective egg counter. If an egg counter is selected in INPUT CONFIGURATION

WATER/EGG (1-12), its count will be shown. If an egg counter is used in manual mode

using the INPUT CONFIGURATION EGG COUNTER (1-12) MANUAL MODE, this

value will be adjustable from 0 to 999999 eggs. If an egg counter is used in automatic

mode, the amount of eggs counted is displayed from 1 egg from 0 to 999999 eggs.

EGG COUNTER TOTAL GROUP (A-B)

These parameters display the amount of eggs counted by the total for all egg counters of

the respective group for the current day. If at least one egg counter is assigned to the

respective group, this value will be visible, otherwise it will not appear.

EGG COUNTER BATCH TOTAL QUANTITY GROUP (A-B)

These parameters display the amount of eggs counted by the total for all egg counters of

the respective group since the batch has started. If at least one egg counter is assigned to

the respective group, this value will be visible, otherwise it will not appear. The amount

of eggs is displayed from 0 to 7999999 units (litres or gallons).

Page 64: T uch - agrivent.com

USER’S GUIDE

Section C-64

ACTUAL CONDITIONS (CONTINUED…)

SCALE (1-2) ACTUAL AVERAGE WEIGHT

These parameters display the average weight of the respective scale for the current day. If

a scale at NUMBER OF POULTRY SCALES is active, its average weight will appear,

otherwise it won’t. The weight values are displayed according to the POULTRY WEIGHT

UNIT with a precision of 1 unit from 1 to 9998 units.

ACTUAL VARIABLE STAGE (1-12) SPEED

These parameters display the actual speed of the variable stages. An unused stage will not

appear. Each stage can display OFF, or a speed from 0% to 100%.

ACTUAL VARIABLE STIR FAN (1-4) SPEED

These parameters display the actual speed of the variable stir fans. An unused variable

stir fan will not appear. Each stage can display OFF, or a speed from 0% to 100%.

ACTUAL STIR FAN (1-4) STATE

These parameters display the actual state of the on/off stir fans. An unused stir fan will

not appear. Each stage can display OFF or 100%.

AIR INLET (1-16) ACTUAL POSITION

These parameters display the actual position of the air inlets used in Position Mode or

Natural Pot. The actual positions are displayed to the nearest 1% from -99% to 127%.

However, if the controller cannot read the position, the corresponding parameter will

display ERROR.

AIR INLET (1-7, 9-15) ACTUAL STATUS

These parameters display the actual position of the air inlets used in Natural Timer mode.

The respective parameter displays the actual demanded state, which may be OPEN,

CLOSE, or HOLD.

ACTUAL LIGHT (1-2) INTENSITY

These parameters display the current intensity of the light outputs. An unused light output

will not appear. Each light output can display OFF or an intensity from 1% to 100%.

INFLATABLE INLET (1-16) STATUS

These parameters display the actual situation of the Inflatable Inlets. Each inflatable inlet

can be OPENING when it is opening (relay deactivated) or CLOSING when it is closing

(relay activated).

CLOCK (1-4) ACTUAL STATUS

These parameters display the actual situation of the clock outputs. Each clock output can

be ON or OFF.

BIN (1-2) ACTUAL WEIGHT

These parameters display the current weight measured for the respective bin. The current

weight is the gross weight of the bin, minus the tare weight of that bin. If the tare weight

has never been established, this value will be equal to the gross weight. If there is a

communication problem with the bin’s module, the weight read is not stable enough or a

load cell is defective, the associated parameter will display ---. These parameters are

displayed to the nearest 1kg (1lb) and have a maximum display value of 30000kg

(67000lb).

Page 65: T uch - agrivent.com

USER’S GUIDE

Section C-65

ACTUAL CONDITIONS (CONTINUED…)

FEED AUGER TOTAL QUANTITY GROUP (A-B)

These parameters display the count for the total of all feed augers of the respective group

for the current day. This parameter will be visible if at least one feed auger is assigned to

the respective group, otherwise it will not appear. The amount of feed read is displayed to

the nearest unit (kg or lb) from 0 to 59994 units (kg or lb) for the total.

FEED AUGER TOTAL QUANTITY 24 HOURS GROUP (A-B)

These parameters display the amount of units counted in the last 24 hours that the

controller was powered up. This count does not consider the current hour or the time for

which the controller was powered down. Furthermore, changing the time of day will not

affect this count. The amount of feed auger read is displayed to the nearest unit (kg or lb)

from 0 to 59994 units (kg or lb) for the total.

FEED AUGER BATCH TOTAL QUANTITY GROUP (A-B)

These parameters display the count for the total of all feed augers of the respective group

since the beginning of the batch. This parameter will be visible if at least one feed auger

is assigned to the respective group, otherwise it will not appear. The amount of feed

auger read is displayed to the nearest unit from 0 to 999999 units (kg or lb).

AVERAGE SCALES 1 AND 2

This parameter displays the average of both scales for the actual day. If two scales are

activated at NUMBER OF POULTRY SCALES use the same type of poultry at POULTRY

TYPE SCLAE (1-2), this average weight will appear, otherwise it won’t. This value is

displayed according to the POULTRY WEIGHT UNIT with a precision of 1 unit from 1 to

9998 units.

GROWTH DAY

This parameter is used to adjust the Growth Day. The Growth Day affects all

parameters that are using their Growth Curve. The Growth Day may be adjusted to any

value from OFF, day 0 to day 365 using 1-day increments.

REQUESTED POSITION CHIMNEY (1-2)

These parameters display the requested position of the chimneys. The requested positions

are displayed to the nearest 1% from 0% to 100%.

DEHUMIDIFICATION ACTIVE

This parameter displays the dehumidification state. If a variable ventilation stage or a

heater has a dehumidification demand, this parameter will display NO. Otherwise, it will

display OFF.

Page 66: T uch - agrivent.com

USER’S GUIDE

Section C-66

SET POINTS

MAIN SETPOINT (Curve Available)

This parameter is used to adjust the MSP. This value sets the temperature goal for the

building. This parameter will be affected by its Ramping Function when the MAIN

SETPOINT CURVE is set to ON and the GROWTH DAY is not set to OFF. The MSP can

be adjusted in 0.1° increments from 0.0°F to 120.0°F (0.0°C to 40.0°C).

ACTUAL MAIN SETPOINT

This parameter displays the MSP actually used by the controller. This value can be either

MAIN SETPOINT, the NIGHT SETPOINT or, while a transition delay, a value between

these two set points. This set point is displayed the nearest 0.1° from 0.0°C to 40.0°C

(0.0°F to 120.0°F).

MAIN SETPOINT CURVE

This parameter is used to activate or deactivate the MSP Ramping Function. If this

option is set to ON and the GROWTH DAY is not set to OFF, the MAIN SETPOINT will

change according to its Growth Curve programmed in its curve.

NIGHT SETPOINT ACTIVE

This parameter is used to activate or deactivate the night compensation. If this parameter

is set to No, the MAIN SETPOINT will be the value used anytime. If this parameter is set

to Yes, when the NIGHT SETPOINT TIME BEGIN, the ACTUAL MAIN SETPOINT

will modulate from MAIN SETPOINT to reach NIGHT SETPOINT when the NIGHT

SETPOINT TRANSITION delay is done. When time reaches NIGHT SETPOINT TIME

END – NIGHT SETPOINT TRANSITION, the ACTUAL MAIN SETPOINT will

modulate to reach MAIN SETPOINT when time reaches NIGHT SETPOINT TIME END.

NIGHT SETPOINT SYNCHRONIZED WITH LIGHTS

This parameter is used to synchronize the night set point with the light program zone. If

this parameter is not set to OFF, transition value, start and end values will be used as light

program zone instead of NIGHT SETPOINT TIME BEGIN, NIGHT SETPOINT TIME

END and NIGHT SETPOINT TRANSITION. The NIGHT SETPOINT will be used when

lights are at LIGHT (1-2) INTENSITY BETWEEN CYCLES. The set point will modulate

between NIGHT SETPOINT and MAIN SETPOINT at the beginning of light program and

vice-versa at the end of light program.

NIGHT SETPOINT

This parameter is used to adjust the night set point. This value sets the temperature goal

during the night period. This setting is relative to the MAIN SETPOINT. The night set

point is adjusted in 0.1° increments from MAIN SETPOINT - 40.0° to MAIN SETPOINT

+ 40.0°.

NIGHT SETPOINT TIME BEGIN

This parameter is used to adjust the time at which the night period will begin. When this

time is reached, the ACTUAL MAIN SETPOINT will begin to modulate towards the

NIGHT SETPOINT if NIGHT SETPOINT ACTIVE is set to Yes.

Page 67: T uch - agrivent.com

USER’S GUIDE

Section C-67

SET POINTS (CONTINUED…)

NIGHT SETPOINT TIME END

This parameter is used to adjust the time at which the day period will end. When this time

reaches NIGHT SETPOINT TIME BEGIN, the ACTUAL MAIN SETPOINT will

modulate to the MAIN SETPOINT if it had been modified for night compensation.

NIGHT SETPOINT TRANSITION

This parameter is used to adjust the time the ACTUAL MAIN SETPOINT will take to go

from the MAIN SETPOINT to the NIGHT SETPOINT or vice versa. The transition time is

adjusted in 1 minute increments from 0 to 60 minutes.

Example of night compensation:

GROWTH DAY

This parameter is used to adjust the Growth Day. The Growth Day affects all

parameters that are using their Growth Curve. The Growth Day may be adjusted to any

value from OFF, day 0 to day 365 using 1-day increments.

HUMIDITY SETPOINT

This parameter is used to set the humidity set point at which the variable stage 1

ventilation stage dehumidification logic will be activated. This is also the reference value

for other variable stage dehumidification set points. When the actual humidity reaches

this value, the variable stage 1’s minimum speed is increased by VARIABLE STAGE 1 ADD MINIMUM SPEED FOR HUMIDITY and if the VARIABLE STAGE 1 START

TEMPERATURE isn’t reached, the variable stage 1 will activate continuously at its new

minimum speed. There is a fixed Differential of 3RH% on this logic. Setting this set

point to OFF will deactivate the dehumidification logic for both variable ventilation

stages. These parameters are adjusted in 1RH% increments from 0RH% to 99%RH, OFF.

Transition Time

Transition Time

Night SP

Start Time End Time

MSP

Page 68: T uch - agrivent.com

USER’S GUIDE

Section C-68

VARIABLE STAGES

ACTUAL SPEED

These parameters display the actual speed of the variable stages. Each stage can display

OFF, or a speed from 0% to 100%.

START TEMPERATURE

These parameters are used to set the temperature at which the respective variable stage

will be activated continuously to VARIABLE STAGE (1-12) MINIMUM SPEED. A fixed

Differential of 0.3° is used with this logic. As the average temperature of the probes

selected in selected in VARIABLE STAGE (1-12) PROBES increases, the variable stage’s

speed will increase until VARIABLE STAGE (1-12) END TEMPERATURE is reached.

The variable stage 1’s behaviour may change, depending on the mode chosen at

VARIABLE STAGE 1 MODE. These parameters may be adjusted in 0.1° increments from

MAIN SET POINT - 10.0° to MAIN SET POINT + 40.0° except for VARIABLE 1 START

TEMPERATURE, which is always equal to the MAIN SET POINT.

END TEMPERATURE

These parameters are used to set the temperature at which the respective variable stage

will be activated at VARIABLE STAGE (1-12) MAXIMUM SPEED. The variable stage

1’s behaviour may change, depending on the chosen mode on the mode chosen at

VARIABLE STAGE 1 MODE. These parameters adjusted in 0.1° increments from

VARIABLE STAGE (1-12) START TEMPERATURE + 0.5° to VARIABLE STAGE (1-12)

START TEMPERATURE + 40.0°.

MINIMUM SPEED (Curve Available for variable stage 1)

These parameters are used to adjust the minimum speed of variable stages. This speed is

the base value used to calculate the actual minimum speed. The OUTSIDE

TEMPERATURE and humidity may affect variable stages’ actual minimum speed. If the

minimum speed Growth Function for variable stage 1 is activated, that stage’s minimum

speed will not be adjustable. The minimum speed settings are adjusted in 1% increments

from 12% to 100% or 0% to 100% if the respective stage is used on 0-10 Volts output.

MINIMUM SPEED CURVE

This parameter is used to activate or deactivate the Ramping Function on VARIABLE

STAGE 1 MINIMUM SPEED. If set to ON and the GROWTH DAY is not set to OFF, the

VARIABLE STAGE 1 MINIMUM SPEED will follow its programmed curve.

MAXIMUM SPEED

These parameters are used to adjust the maximum speed of the respective variable stage.

This speed will be reached when the average temperature of the probes selected in

VARIABLE STAGE (1-12) PROBES reaches the corresponding VARIABLE STAGE (1-12)

END TEMPERATURE. These parameters are adjusted in 1% increments from 12% to

100%.

Page 69: T uch - agrivent.com

USER’S GUIDE

Section C-69

VARIABLE STAGES (CONTINUED…)

TIMER

These parameters are used to set the timer used by the respective variable stage when it is

not activated on temperature demand. If one of these parameters is set to OFF, the

respective stage will not use any timer. The variable stage 1’s behaviour may change,

depending on the mode chosen at VARIABLE STAGE 1 MODE. These parameters can be

adjusted from OFF, 1 to 4.

NATURAL SHUTOFF

These parameters are used to activate or deactivate the natural shutoff logic for the

respective variable ventilation stage. If a natural shutoff option is set to YES,

corresponding ventilation stage will deactivate when natural mode is entered. If it is set to

NO, natural mode will not affect the respective ventilation stage.

TUNNEL SHUTOFF

These parameters are used to activate or deactivate the tunnel shutoff logic for the

respective ventilation stage. If a tunnel shutoff option is set to YES, corresponding

variable ventilation stage will deactivate when tunnel mode is entered. If it is set to NO,

tunnel mode will not affect the respective ventilation stage. The stage that is selected to

start tunnel mode cannot be shut off by tunnel mode even if the corresponding tunnel shut

off option is set to YES.

FULL SPEED START

These parameters are used to determine if the respective variable stage will perform a full

start upon activation. If this option is set to ON the corresponding variable output will be

activated at full speed for the first few seconds following an activation demand. This

option is not available if the variable stage is used on 0-10 Volts output.

ADD MINIMUM SPEED OUTSIDE TEMPERATURE COMPENSATION

These parameters are used to adjust the amount by which the respective variable stage’s

minimum speed will increase when OUTSIDE TEMPERATURE COMPENSATION option is set to ON and the OUTSIDE TEMPERATURE is equal to or above OUTSIDE

TEMPERATURE COMPENSATION SET POINT. Setting one of these parameters to 0%

will deactivate the speed increase for the associated variable stage. These parameters are

adjusted in 1% increments from 0% to 100%.

PROTECTION MINIMUM SPEED

These parameters are used to set the respective minimum variable speed when activated

by the timer and by the protection option on the minimum speed and the protection

minimum speed function is activated. The respective variable stage will be active at the

speed adjusted here when active by its timer and its temperature is equal or under to the

TEMPERATURE PROTECTION UNDER. If VARIABLE STAGE (1-12) PROTECTION

MINIMUM SPEED is set to Stop, the variable stage will deactivate instead of reducing its

speed. If VARIABLE STAGE (1-12) PROTECTION MINIMUM SPEED is set to OFF, this

function will be deactivated. This speed can also be used for dehumidification if the

VARIABLE STAGE (1-12) PROTECTION MINIMUM SPEED ON

DEHUMIDIFICATION option is set to Yes. These parameters are adjusted in 1% from

Stop, OFF, 12% to 100%.

Page 70: T uch - agrivent.com

USER’S GUIDE

Section C-70

VARIABLE STAGES (CONTINUED…)

PROTECTION MINIMUM SPEED ON DEHUMIDIFICATION

These parameters are used to determine if VARIABLE STAGE (1-12) PROTECTION

MINIMUM SPEED will be used on a dehumidification demand on the respective variable

stage. If this option is set to Yes, the corresponding variable stage will use that speed

when activated for dehumidification. If this option is set to No, the variable stage will not

be affected by the minimum speed protection when activated for dehumidification.

MINIMUM SPEED AFFECTS INLET

These parameters are used to activate the VARIABLE STAGE (1-12) MINIMUM SPEED

REFERENCE FOR INLET on the inlet positioning. If this option is set to Yes, inlet will

associate the VARIABLE STAGE (1-12) MINIMUM SPEED REFERENCE FOR INLET

to the position AIR INLET (1-16) VARIABLE (1-12) START POSITION. If this option is

set to No, inlet will associate the VARIABLE STAGE (1-12) MINIMUM SPEED (including Outside Temperature affects, but excluding humidity affects) to AIR INLET

(1-16) VARIABLE (1-12) START POSITION. These parameters can be adjusted to No or

Yes.

MINIMUM SPEED REFERENCE FOR INLET

These parameters are used to set the reference speed used by Position Mode inlets for the

beginning of the Modulation Band of the respective variable stage. The inlets positions

in Position Mode will modulate from de AIR INLET (1-16) VARIABLE (1-12) START

POSITION when variable stage is activated at VARIABLE STAGE (1-12) MINIMUM

SPEED REFERENCE FOR INLET. The inlet opening will increase proportionally to the

variable stage speed to reach AIR INLET (1-16) VARIABLE (1-12) END POSITION when

the variable stage is active to VARIABLE STAGE (1-12) MAXIMUM SPEED. These

parameters are adjusted in 1% increments from 12% to 100%.

AFFECTED BY HUMIDITY

These options are used to determine if variable stage (2-12) may be activated for

dehumidification. If this option is set to Yes, variable stage (2-12) will be activated at its

increased minimum speed when the actual humidity reaches the HUMIDITY SET POINT + VARIABLE STAGE (2-12) HUMIDITY RELATIVE SET POINT even if VARIABLE

STAGE (2-12) START TEMPERATURE hasn’t been reached. If this option is set to No,

variable stage (2-12) will never be activated by humidity.

ADD MINIMUM SPEED FOR HUMIDITY

These parameters are used to adjust the speed increase that will be applied on the

respective variable stage for the dehumidification logic. When the actual humidity

reaches the HUMIDITY SET POINT, VARIABLE STAGE 1 MINIMUM SPEED will be

increased by this value and, if VARIABLE STAGE 1 START TEMPERATURE isn’t

reached, it will activate continuously at its new minimum speed. When the actual

humidity reaches the HUMIDITY SET POINT + VARIABLE STAGE (2-12) HUMIDITY

RELATIVE SETPOINT, variable stage (2-12)’s will be increased by VARIABLE STAGE

(2-12) ADD MINIMUM SPEED FOR HUMIDITY and, if VARIABLE STAGE (2-12)

START TEMPERATURE isn’t reached, it will activate continuously at its new minimum

speed. These parameters are adjusted in 1% increments from 0% to 100%.

Page 71: T uch - agrivent.com

USER’S GUIDE

Section C-71

VARIABLE STAGES (CONTINUED…)

HUMIDITY RELATIVE SET POINT

This relative set point is used to set the humidity level at which VARIABLE STAGE (2-

12) will be activated for dehumidification. If the VARIABLE STAGE (2-12) AFFECTED

BY HUMIDITY option is set to Yes, variable stage (2-4) will be activated at its minimum

speed when the actual humidity reaches the HUMIDITY SET POINT + VARIABLE

STAGE (2-12) HUMIDITY RELATIVE SET POINT even if VARIABLE STAGE (2-12)

START TEMPERATURE hasn’t been reached. There is a fixed Differential of 3RH% on

this logic. This parameter is adjusted in 1RH% increments from 0RH% to 100RH%.

AFFECTED BY HUMIDITY LEVEL 2

These options are used to determine if variable stage (1-4) may be activated for level 2

dehumidification. If this option is set to Yes, variable stage (1-4) will be activated at its

increased minimum speed when the actual humidity reaches the HUMIDITY SET POINT + VARIABLE STAGE (1-4) HUMIDITY RELATIVE SET POINT LEVEL 2 even if

VARIABLE STAGE (1-4) START TEMPERATURE hasn’t been reached. If this option is

set to No, variable stage (1-4) will never be activated by level 2 dehumidification.

PROBES

These parameters are used to select the probes the respective variable stage will use to

determine activation and deactivation according to temperature demand. To If there are

no probes selected, the temperature used will be equal to the actual MAIN

SETPOINT.

MODE

This parameter is used to set the mode used by the variable stage 1. If this parameter is

set to Variable Timer, the variable stage 1 will activate with the timer of this screen when

temperature probes selected in VARIABLE STAGE 1 PROBES reaches VARIABLE

STAGE 1 START TEMPERATURE. In this mode, activation time will modulate between

VARIABLE STAGE 1 VARIABLE TIMER MODE MINIMUM ON TIME and VARIABLE

STAGE 1 VARIABLE TIMER MODE MAXIMUM ON TIME and the deactivation time

will modulate between VARIABLE STAGE 1 VARIABLE TIMER MODE MINIMUM

OFF TIME and VARIABLE STAGE 1 VARIABLE TIMER MODE MAXIMUM OFF TIME depending on VARIABLE STAGE 1 START TEMPERATURE and VARIABLE STAGE 1

START END TEMPERATURE temperatures. If this parameter is adjusted to Variable

Speed, variable stage 1 will continuously activate by its VARIABLE STAGE 1 MINIMUM

SPEED and VARIABLE STAGE 1 MAXIMUM SPEED when temperature probes selected

in VARIABLE STAGE 1 PROBES reaches VARIABLE STAGE 1 START

TEMPERATURE. If this parameter is set to Variable Timer/Spd, variable stage 1 will

modulate between these two modes explained above depending on the AVERAGE

TEMPERATURE and VARIABLE STAGE 1 OUTSIDE SETPOINT TIMER MODE and

VARIABLE STAGE 1 OUTSIDE TEMP SPEED MODE. Variable stage 1 is always on

speed mode if another ventilation stage is activated on temperature.

Page 72: T uch - agrivent.com

USER’S GUIDE

Section C-72

VARIABLE STAGES (CONTINUED…)

OUTSIDE SETPOINT TIMER MODE This parameter is used to adjust the outside temperature at which variable stage mode

will be the timer mode if MODE is set to Variable Timer/Spd. When Outside

Temperature is equal or under this set point, variable stage 1 will change to variable

timer mode. This parameter is adjusted in 0.1° increments from -40.0°C to 40.0°C

(-40.0°F to 120.0°F).

OUTSIDE SETPOINT SPEED MODE This parameter is used to adjust the outside temperature at which variable stage mode

will be the variable speed mode if OPERATING MODE is set to Min/Spd Variable.

When Outside Temperature is equal or above this set point, variable stage 1 will change

to speed variable mode. This parameter is adjusted in 0.1° increments from -40.0°C to

40.0°C (-40.0°F to 120.0°F).

OUTSIDE SETPOINT VARIABLE TIMER MODE MINIMUM SPEED

This parameter is used to adjust the outside temperature at which variable stage 1 speed

will equal to VARIABLE STAGE 1 VARIABLE TIMER MODE MINIMUM SPEED in

variable timer mode. When OUTSIDE TEMPERATURE is equal or under this set point

and the variable stage 1 is in variable timer mode, it will activate at VARIABLE STAGE 1

VARIABLE TIMER MODE MINIMUM SPEED on active time of its timer. Between this

temperature and VARIABLE STAGE 1 OUTSIDE SETPOINT VARIABLE TIMER MODE

MAXIMUM SPEED, speed will modulate between VARIABLE STAGE 1 VARIABLE

TIMER MODE MINIMUM SPEED and VARIABLE STAGE 1 VARIABLE TIMER MODE

MAXIMUM SPEED. This parameter is adjusted in 0.1° increments from -40.0°C to

40.0°C (-40.0°F to 120.0°F).

OUTSIDE SETPOINT VARIABLE TIMER MODE MAXIMUM SPEED

This parameter is used to adjust outside temperature at which variable stage 1 speed will

equal to VARIABLE STAGE 1 VARIABLE TIMER MODE MAXIMUM SPEED in variable

timer mode. When the OUTSIDE TEMPERATURE is equal or above this set point and

the variable stage 1 is in variable timer mode, it will activate at its VARIABLE TIMER

MODE MAXIMUM SPEED on the active time of its timer. Between VARIABLE STAGE

1 OUTSIDE SETPOINT VARIABLE TIMER MODE MINIMUM SPEED and this

temperature, speed will modulate between VARIABLE STAGE 1 VARIABLE TIMER

MODE MINIMUM SPEED and VARIABLE STAGE 1 VARIABLE TIMER MODE

MAXIMUM SPEED. This parameter is adjusted in 0.1° increments from -40.0°C to

40.0°C (-40.0°F to 120.0°F.

VARIABLE TIMER MODE MINIMUM SPEED

This parameter is used to adjust the variable stage 1 speed when OUTSIDE

TEMPERATURE is equal or under VARIABLE STAGE 1 OUTSIDE SETPOINT

VARIABLE TIMER MODE MINIMUM SPEED in variable timer mode. This parameter

is adjusted in 1% increments from 12% to 100%.

Page 73: T uch - agrivent.com

USER’S GUIDE

Section C-73

VARIABLE STAGES (CONTINUED…)

VARIABLE TIMER MODE MAXIMUM SPEED

This parameter is used to adjust the variable stage 1 speed when Outside Temperature is

equal or under VARIABLE STAGE 1 OUTSIDE SETPOINT VARIABLE TIMER MODE

MAXIMUM SPEED in variable timer mode. This parameter is adjusted in 1% increments

from 12% to 100%.

VARIABLE TIMER MODE MINIMUM ON TIME (Curve available)

This parameter is used to adjust the amount of activation time of the variable stage 1

timer when temperature probes selected in VARIABLE STAGE 1 PROBES reaches

VARIABLE STAGE 1 START TEMPERATURE in variable timer mode. This value will

follow a Growth Curve if VARIABLE TIMER MODE MINIMUM TIME CURVE and

GROWTH DAY are not set to OFF. This parameter is adjustable from 0:00 to 99:59

minutes.

VARIABLE TIMER MODE MAXIMUM ON TIME (Curve available)

This parameter is used to adjust the amount of activation time of variable stage 1 timer

when temperature probes selected in VARIABLE STAGE 1 PROBES reaches VARIABLE

STAGE 1 END TEMPERATURE in variable timer mode. This value will follow a

Growth Curve if VARIABLE TIMER MODE MAXIMUM TIME CURVE and GROWTH

DAY are not set to OFF. This parameter is adjustable from 0:00 to 99:59 minutes.

VARIABLE TIMER MODE MINIMUM OFF TIME (Curve available)

This parameter is used to set the deactivation time of the variable stage 1 when

temperature probes selected in VARIABLE STAGE 1 PROBES reaches VARIABLE

STAGE 1 START TEMPERATURE in variable timer mode. This value will follow a

Growth Curve if VARIABLE TIMER MODE MINIMUM TIME CURVE and GROWTH

DAY are not set to OFF. This parameter is adjustable from 0:00 to 99:59 minutes.

VARIABLE TIMER MODE MAXIMUM OFF TIME (Curve available)

This parameter is used to set the deactivation time of the variable stage 1 when

temperature probes selected in VARIABLE STAGE 1 PROBES reaches VARIABLE

STAGE 1 END TEMPERATURE in variable timer mode. This value will follow a

Growth Curve if VARIABLE TIMER MODE MAXIMUM TIME CURVE and GROWTH

DAY are not set to OFF. This parameter is adjustable from 0:00 to 99:59 minutes.

VARIABLE TIMER MODE MINIMUM TIME CURVE

This parameter is used to activate or deactivate the Ramping Function of variable stage

1 minimum timer when variable timer mode is used. If this option is set to ON and the

GROWTH DAY is not set to OFF, VARIABLE STAGE 1 VARIABLE TIMER MODE

MINIMUM ON TIME and VARIABLE STAGE 1 VARIABLE TIMER MODE MINIMUM

OFF TIME will follow their Growth Curve.

VARIABLE TIMER MODE MAXIMUM TIME CURVE

This parameter is used to activate or deactivate the Ramping Function of variable stage

1 maximum timer when variable timer mode is used. If this option is set to ON and the

GROWTH DAY is not set to OFF, VARIABLE STAGE 1 VARIABLE TIMER MODE

MAXIMUM ON TIME and VARIABLE STAGE 1 VARIABLE TIMER MODE MAXIMUM

OFF TIME will follow their Growth Curve.

Page 74: T uch - agrivent.com

USER’S GUIDE

Section C-74

VARIABLE STAGES (CONTINUED…)

DEFROST

These parameters are used to activate or deactivate the defrost logic on the respective

variable stage. When this parameter is set to Yes, the defrost logic on the respective

variable stage will be applied. This parameter is adjusted to No or Yes.

DEFROST TIME

These parameters are used to set the on time of the defrost cycle. When defrost cycle of a

variable stage is in its active portion, the preceding variable stage will deactivate.

Furthermore, only one variable stage can be activated for defrosting at any given time.

These parameters are adjusted in 1-second increments from 1 second to 900 seconds.

DEFROST CYCLE

These parameters are used to set the off time of the defrost duration. This amount of time

determines the maximum time of the respective variables stage’s inactivity. If a variable

stage has not been activated for a consecutive period of time equal to this parameter, it

will activate at its minimum speed for VARIABLE STAGE (1-12) DEFROST TIME.

When defrost cycle of a variable stage is in its active portion, the preceding variable stage

will deactivate. Furthermore, only one variable stage can be activated for defrosting at

any given time. This parameter is adjusted in 1-minute increments from 0 minute to 720

minutes.

OUTSIDE TEMPERATURE DEFROST

This parameter is used to adjust when the temperature set point will be applied on the

variable stages. There is a fixed Differential of 0.3° on this logic. This parameter is

adjusted in 0.1° increments from -50.0°C to 60.0°C (-58.0°F to 140.0°F).

HUMIDITY RELATIVE SET POINT LEVEL 2

This relative set point is used to set the humidity level at which variable stage (1-4) will

be activated for level 2 dehumidification. If the VARIABLE STAGE (1-4) AFFECTED BY

HUMIDITY LEVEL 2 option is set to Yes, variable stage (1-4) will be activated at its

minimum speed when the actual humidity reaches the HUMIDITY SET POINT +

VARIABLE STAGE (2-12) HUMIDITY RELATIVE SET POINT even if VARIABLE

STAGE (2-12) START TEMPERATURE hasn’t been reached. There is a fixed

Differential of 3RH% on this logic. This parameter is adjusted in 1RH% increments

from 0RH% to 100RH%.

ADD MINIMUM SPEED FOR HUMIDITY LEVEL 2

These parameters are used to adjust the speed increase that will be applied on the

respective variable stage for the level 2 dehumidification logic. When the actual humidity

reaches HUMIDITY SET POINT + VARIABLE STAGE (1-4) HUMIDITY RELATIVE

SETPOINT LEVEL 2, variable stage (1-4)’s will be increased by VARIABLE STAGE (1-

4) ADD MINIMUM SPEED FOR HUMIDITY LEVEL 2 and, if VARIABLE STAGE (1-4)

START TEMPERATURE isn’t reached, it will activate continuously at its new minimum

speed. These parameters are adjusted in 1% increments from 0% to 100%.

Page 75: T uch - agrivent.com

USER’S GUIDE

Section C-75

VARIABLE STAGES (CONTINUED…)

SPEED WHEN NEXT STAGE ON

These parameters are used to set the speed a variable stage will take when the next

variable stage activates on temperature demand. For example, variable stage 1’s speed

will be equal to VARIABLE STAGE 1 SPEED WHEN NEXT STAGE ON when the

average temperature of the probes selected in VARIABLE STAGE 2 PROBES reaches

VARIABLE STAGE 2 START TEMPERATURE. As the temperature continues to increase,

variable stage 1 will modulate according to variable stage 2’s temperature adjustments.

When there is no longer a temperature demand for variable stage 2, variable stage 1 will

return to the speed calculated by its own settings. Setting one of these parameters to

STOP will deactivate the respective variable stage when the next one activates on

temperature demand. If one of these parameters is set to OFF will deactivate the above-

mentioned function for the respective variable stage. These parameters are adjusted in 1%

increments from OFF, STOP, 0% to 100%.

OUTSIDE TEMPERATURE COMPENSATION

This parameter is used to activate or deactivate the increase of the minimum speed of the

variable stages when the OUTSIDE TEMPERATURE is equal to or above VARIABLE

STAGE OUTSIDE TEMPERATURE SET POINT. If this parameter is set to OFF, the

OUTSIDE TEMPERATURE will not affect the minimum speed of the variable stages. If

this parameter is set to ON, VARIABLE STAGE (1-12) ADD MINIMUM SPEED

OUTSIDE TEMPERATURE COMPENSATION will be added to the associated variable

stage’s minimum speed when the OUTSIDE TEMPERATURE is equal to or above

VARIABLE STAGE OUTSIDE TEMPERATURE COMPENSATION SET POINT.

TEMPERATURE PROTECTION UNDER

This parameter allows the user to set the temperature set point that will activate the

protection on variable stages minimum speed. If VARIABLE STAGE (1-12) PROTECTION MINIMUM SPEED is not set to OFF, the respective variable stage will be

activated to the adjusted speed when it is activated by the timer or dehumidification and

its temperature is equal or under the temperature adjusted here This parameter is adjusted

in 0.1° increments from MAIN SETPOINT - 40.0° to MAIN SETPOINT.

OUTSIDE TEMPERATURE COMPENSATION SET POINT

This parameter sets the OUTSIDE TEMPERATURE at which the minimum speed of the

variable stages will be increased if the VARIABLE STAGE OUTSIDE TEMPERATURE

COMPENSATION option is set to ON. When the OUTSIDE TEMPERATURE is equal

to or above this value, VARIABLE STAGE (1-12) ADD MINIMUM SPEED OUTSIDE

TEMPERATURE COMPENSATION will be added to the associated variable stage’s

minimum speed. A fixed Differential of 0.3° is used with this logic. This parameter is

adjusted in 0.1° increments from 0.0°C to 40.0°C (0.0°F to 120.0°F).

Page 76: T uch - agrivent.com

USER’S GUIDE

Section C-76

VARIABLE STAGES (CONTINUED…)

NATURAL MODE REACTIVATION TEMPERATURE

This parameter is used to set the temperature at which temperature the natural shutoff

function will be overridden. When a ventilation stage that would be activated by

temperature or otherwise is deactivated because the controller is in natural mode, it may

reactivate when the associated temperature reaches this set point. A fixed Differential of

1.0° is used with this logic. If natural mode is not used, this parameter will not appear.

The value of this parameter is adjusted in 0.1° increments from 0.0°C to 40.0°C (0.0°F to

120.0°F).

TUNNEL MODE REACTIVATION TEMPERATURE

This parameter is used to set the temperature at which temperature the tunnel shutoff

function will be overridden. When a ventilation stage that would be activated by

temperature or otherwise is deactivated because the controller is in tunnel mode, it may

reactivate when the associated temperature reaches this set point. A fixed Differential of

1.0° is used with this logic. If tunnel mode is not used, this parameter will not appear.

The value of this parameter is adjusted in 0.1° increments from 0.0°C to 40.0°C (0.0°F to

120.0°F).

LAST VARIABLE IDLE BACK ON FIRST ON/OFF STAGE

This parameter is used to set the speed the last variable stage will take when the first

on/off stage activates on temperature demand. For example, variable stage 4’s speed will

be equal to LAST VARIABLE IDLE BACK ON FIRST ON/OFF STAGE when the average

temperature of the probes selected in ON/OFF STAGE 5 PROBES reaches ON/OFF

STAGE 5 ON TEMPERATURE. As the temperature continues to increase, variable stage

4 will modulate according to its own modulation band (VARIABLE STAGE 4 END

TEMPERATURE - VARIABLE STAGE 4 START TEMPERATURE). When there is no

longer a temperature demand for on/off stage 5, variable stage 4 will return to the speed

calculated by its own settings. Setting one of these parameters to STOP will deactivate

the last variable stage when the first on/off stage activates on temperature demand.

Setting this parameter to OFF will deactivate the above-mentioned function for the

respective variable stage. This parameter is adjusted in 1% increments from OFF, STOP,

0% to 100%.

Page 77: T uch - agrivent.com

USER’S GUIDE

Section C-77

ON/OFF STAGES

ACTUAL STATUS

These parameters display the actual status of the on/off stage outputs. Each on/off stage

output can be 100% or OFF.

ON TEMPERATURE

These parameters are used to set the temperature at which the respective on/off stage will

be activated. When the temperature selected in ON/OFF STAGE (1-24) PROBES reaches

this temperature, the respective on/off cooling stage will be activated continuously. These

parameters may be adjusted in 0.1° increments from MAIN SETPOINT - 10.0° to MAIN

SETPOINT + 40.0°.

OFF TEMPERATURE

These parameters are used to set the temperature at which the respective on/off stage will

be deactivated. When the temperature selected in ON/OFF STAGE (1-24) PROBES drops

to this temperature, the respective on/off cooling stage will be deactivated. These

parameters may be adjusted in 0.1° increments from ON/OFF STAGE (1-24) ON

TEMPERATURE - 0.5° to ON/OFF STAGE (1-24) ON TEMPERATURE - 40.0°.

TIMER

These parameters are used to set the timer used by the respective on/off stage when it is

not activated on temperature demand. If one of these parameters is set to OFF, the

respective stage will not use any timer. These parameters can be adjusted from OFF, 1 to

4.

NATURAL SHUTOFF

These parameters are used to activate or deactivate the natural shutoff logic for the

respective ventilation stage. If a natural shutoff option is set to YES, corresponding

ventilation stage will deactivate when natural mode is entered. If it is set to NO, natural

mode will not affect the respective ventilation stage.

TUNNEL SHUTOFF

These parameters are used to activate or deactivate the tunnel shutoff logic for the

respective stage. If a tunnel shutoff option is set to YES, corresponding variable

ventilation stage will deactivate when tunnel mode is entered. If it is set to NO, tunnel

mode will not affect the respective ventilation stage. The stage that is selected to start

tunnel mode cannot be shut off by tunnel mode even if the corresponding tunnel shut off

option is set to YES.

PROBES

These parameters are used to select the probes the respective on/off stage will use to

determine activation and deactivation according to temperature demand. To If there are

no probes selected, the temperature used will be equal to the actual MAIN

SETPOINT.

Page 78: T uch - agrivent.com

USER’S GUIDE

Section C-78

ON/OFF STAGES (CONTINUED…)

NATURAL MODE REACTIVATION TEMPERATURE

This parameter is used to set the temperature at which temperature the natural shutoff

function will be overridden. When a ventilation stage that would be activated by

temperature or otherwise is deactivated because the controller is in natural mode, it may

reactivate when the associated temperature reaches this set point. A fixed Differential of

1.0° is used with this logic. If natural mode is not used, this parameter will not appear.

The value of this parameter is adjusted in 0.1° increments from 0.0°C to 40.0°C (0.0°F to

120.0°F).

TUNNEL MODE REACTIVATION TEMPERATURE

This parameter is used to set the temperature at which temperature the tunnel shutoff

function will be overridden. When a ventilation stage that would be activated by

temperature or otherwise is deactivated because the controller is in tunnel mode, it may

reactivate when the associated temperature reaches this set point. A fixed Differential of

1.0° is used with this logic. If tunnel mode is not used, this parameter will not appear.

The value of this parameter is adjusted in 0.1° increments from 0.0°C to 40.0°C (0.0°F to

120.0°F).

Page 79: T uch - agrivent.com

USER’S GUIDE

Section C-79

HEATERS

ACTUAL STATUS

These parameters display the actual status of the heater outputs. Each heater output can

be ON or OFF.

RUN TIME

These parameters display the time for which the current heat output has been activated

for the corresponding day. These time values are displayed to the nearest 1 minute from

0:00 hour to 24:00 hours.

CONSUMPTION

These parameters display the respective heat consumption for the current day. These

values are displayed the nearest 1 BTU (0.01 m³h) from 0 to 7999999 BTU (7999.99

m³h).

YESTERDAY CONSUMPTION

These parameters display the respective heat consumption for yesterday. These values are

displayed the nearest 1 BTU (0.01 m³h) from 0 to 7999999 BTU (7999.99 m³h).

ON TEMPERATURE

These parameters are used to set the temperature at which the respective heater stage will

be activated. When the temperature of the probes selected in the corresponding HEATER

(1-10) PROBES parameter drops to this temperature, the respective heater will be

activated. These parameters are relative to the MAIN SETPOINT and may be adjusted in

0.1° increments from MAIN SETPOINT - 40.0° to MAIN SETPOINT + 10.0°.

OFF TEMPERATURE

These parameters are used to set the temperature at which the respective heater stage will

be deactivated. When the temperature of the probes selected in the corresponding

HEATER (1-10) PROBES parameter rises to this temperature, the respective heater will

be deactivated. These parameters are relative to the HEATER (1-10) ON

TEMPERATURE and may be adjusted in 0.1° increments from HEATER (1-10) ON

TEMPERATURE + 0.5° to HEATER (1-10) ON TEMPERATURE + 10.0°.

PROBES

These parameters are used to select the probes the respective heater will use to determine

activation and deactivation according to temperature demand. If there are no probes

selected, the temperature used will be equal to the actual MAIN SETPOINT.

HOURLY CONSUMPTION

These parameters are used to adjust the consumption of each heater. The consumption is

the amount of units (BTU or m³h) that heater consumes in one day. This value will affect

the heat record if the additional unit is used. These values are adjusted in 1-BTU/hour

(0.01 m³h/hour) from 0 to 999999 BTU/hour (99.99 m³h/hour).

Page 80: T uch - agrivent.com

USER’S GUIDE

Section C-80

HEATERS (CONTINUED…)

HIGH TEMPERATURE SHUTOFF

This parameter sets the temperature of the probes selected in the corresponding HEATER

(1-10) PROBES at which a heater will deactivate in all modes. Temperature,

dehumidification, manual mode and even the toggle switches will not be permitted to

activate a heater whose temperature has risen to this set point. A fixed Differential of

1.0° is used with this logic. This parameter is adjusted in 0.1° increments from 0.0°C to

40.0°C, OFF (0.0°F to 120.0°F, OFF).

HUMIDITY INFLUENCE

This option is used to determine if the heaters may be activated by the humidity. If this

option is set to Yes, the heater dehumidification logic will begin when humidity is above

HUMIDITY SETPOINT and OUTSIDE TEMPERATURE is below OUTSIDE

SETPOINT HUMIDITY DEACTIVATION. If variable stage 2 is used, the heater

dehumidification will be cancelled. If this option is set to No, heaters will not be affected

by humidity.

HUMIDITY SETPOINT

This parameter is used to set the humidity level at which heater dehumidification will be

activated. When the actual humidity rises to this set point, OUTSIDE TEMPERATURE

is below OUTSIDE SETPOINT HUMIDITY DEACTIVATION and the respective heater’s

temperature is below the second ventilation stage’s activation temperature, that heater

will be activated for HUMIDITY TIMER ON TIME and deactivated for HUMIDITY

TIMER OFF TIME. A fixed Differential of 3RH% is used with this logic. This parameter

is adjusted in 1RH% increments from 0RH% to 100RH%.

HUMIDITY TIMER ON TIME

This parameter is used to set the on time of the heater dehumidification timer. When

heater dehumidification logic is activated, the heaters with their activation set point is

under the second ventilation stage will be activated for this amount of time and

deactivated for HUMIDITY TIMER OFF TIME. This parameter is adjusted from 0:00

minutes to 99:59 minutes.

HUMIDITY TIMER OFF TIME

This parameter is used to set the off time of the heater dehumidification timer. When

heater dehumidification logic is activated, the heaters whose respective heater’s

temperature is under ventilation stage 2 set point will be activated for HUMIDITY TIMER

ON TIME and deactivated for this amount of time. This parameter is adjusted from 0:00

minutes to 99:59 minutes.

OUTSIDE SETPOINT HUMIDITY DEACTIVATION

This parameter is used to set the OUTSIDE TEMPERATURE at which heater

dehumidification will not be allowed. When the OUTSIDE TEMPERATURE rises to this

temperature, all heaters will not be allowed to activate for dehumidification. A fixed

Differential of 0.3° is used with this logic. This parameter is adjusted in 0.1° increments

from -40.0°C to 40.0°C (-40.0°F to 120.0°F).

Page 81: T uch - agrivent.com

USER’S GUIDE

Section C-81

HEATERS (CONTINUED…)

VENTILATION STAGE STOP DEHUMIDIFICATION

This parameter is used to select which ventilation stage’s activation temperature will be

used to stop a heater’s dehumidification function. When a heater’s temperature reaches

the activation temperature of the stage selected here, that heater’s dehumidification

function will cease. Adjusting this parameter to None will remove dehumidification

deactivation by the heater’s temperature.

REINITIALISE HEATING ACTUAL VALUES

This parameter is used to reinitialise all heater actual values, the zoned heater actual

values and the total batch value. To reinitialise all these values, press on this parameter.

ASSIGNATION HEATERS ZONE (1-2)

These parameters are used to assign heaters to a zone. Combination of heaters selected

will have consumption history of this group. If no heater is selected in a zone, this zone

and its history will be deactivated.

ZONE (1-2) RUN TIME

These parameters display the time for which the current heat zone has been activated for

the corresponding day. These time values are displayed to the nearest minute from 0:00

hours to 240:00 hours.

ZONE (1-2) CONSUMPTION

These parameters display the respective heater zone consumption for the current day.

These values are displayed the nearest BTU (0.01 m³h) from 0 to 7999999 BTU (0.00 to

79999.99 m³h).

YESTERDAY ZONE (1-2) CONSUMPTION

These parameters display the respective heater zone consumption for yesterday. These

values are displayed the nearest BTU (0.01 m³h) from 0 to 7999999 BTU (0.00 to

79999.99 m³h).

SUPPLEMENTARY HISTORY FORMAT

This parameter is used to set the additional unit saved in heat records. If this parameter is

set to OFF, no unit will be saved for heat records. If this parameter is set to BTU (British

Thermal Unit) or M3h (Cubic Metre per hour), the heat consumption will be saved in the

record depending on HEATER (1-10) HOURLY CONSUMPTION and the respective run

time of heaters.

TOTAL RUN TIME

This parameter displays the time for which all heaters have been activated for the

corresponding day. These time values are displayed to the nearest minute from 0:00 hours

to 240:00 hours.

TOTAL CONSUMPTION

This parameter displays the respective heat consumption for all heaters for the current

day. These values are displayed the nearest BTU (0.01 m³h) from 0 to 7999999 BTU

(0.00 to 79999.99 m³h).

Page 82: T uch - agrivent.com

USER’S GUIDE

Section C-82

HEATERS (CONTINUED…)

YESTERDAY TOTAL CONSUMPTION

This parameter displays the respective heat consumption for all heaters for yesterday.

These values are displayed the nearest BTU (0.01 m³h) from 0 to 7999999 BTU (0.00 to

79999.99 m³h).

TOTAL BATCH CONSUMPTION

This parameter displays the batch total of heater’s consumption since the beginning of the

batch. This parameter is displayed to the nearest 1000 BTU (0.0.1m³h) near from 0

x1000BTU to 7999999 x1000BTU (0.00m³h to 79999.99 m³h).

RUN IN NATURAL

This parameter is used to determine if the heaters are allowed to be activated when the

Natural Mode is active. If this parameter is set to No, the heaters will never be allowed to

activate when the system is in Natural Mode. If this parameter is set to Yes, the heaters

will be allowed to activate when the system is in Natural Mode.

ACTIVATES FIRST VENTILATION STAGE

This parameter is used to determine if the first ventilation stage will activate when a

heater is activated. If this option is set to Yes, the first ventilation stage will activate

continuously as long as a heater is activated. If a variable stage is used, it will run at

minimum speed when this function activated. A ventilation stage that is deactivated by

tunnel or natural mode will not be activated by heaters. If this option is set to No,

ventilation will not be affected by heaters.

Page 83: T uch - agrivent.com

USER’S GUIDE

Section C-83

SPRINKLER

ACTUAL STATUS

This parameter displays the actual status of the sprinkler output. The sprinkler output can

be ON or OFF.

ACTUAL TIMER

This parameter displays the current timer used by the sprinkler output. This parameter

can display OFF, 1, 2 or Soak.

ACTUAL TIMER ON TIME LEFT

This parameter displays the remaining on time of the timer used by the sprinkler output.

This value is displayed to the nearest second from 00:00 minutes to 99:59 minutes.

ACTUAL TIMER ON TIME PERIOD

This parameter displays the total on time of the timer used by the sprinkler output. This

value is displayed to the nearest second from 00:00 minutes to 99:59 minutes.

ACTUAL TIMER OFF TIME LEFT

This parameter displays the remaining off time of the timer used by the sprinkler output.

This value is displayed to the nearest second from 00:00 minutes to 99:59 minutes.

ACTUAL TIMER OFF TIME PERIOD

This parameter displays the total off time of the timer used by the sprinkler output. This

value is displayed to the nearest second from 00:00 minutes to 99:59 minutes.

TIMER 1 ON TEMPERATURE

This parameter is used to adjust the first sprinkler timer’s activation temperature. Timer 1

will be activated when the temperature selected in SPRINKLER PROBES is equal to or

above this set point and under TIMER 2 ON SPRINKLER TIMER 1 ON TIME TEMPERATURE. When this temperature is reached, the sprinkler will be activated for

and deactivated for SPRINKLER TIMER 1 OFF TIME. This parameter is adjusted in 0.1°

increments from MAIN SETPOINT - 10.0° to MAIN SETPOINT + 40.0°.

TIMER 1 OFF TEMPERATURE

This parameter is used to adjust the first sprinkler timer’s deactivation temperature. When

the temperature selected in SPRINKLER PROBES drops to this temperature, the timer 1

logic will no longer be effective. This parameter is adjusted in 0.1° increments from the

SPRINKLER TIMER 1 ON TEMPERATURE - 0.5° to SPRINKLER TIMER 1 ON

TEMPERATURE - 10.0°.

TIMER 1 ON TIME

This parameter is used to adjust the on time of the first sprinkler timer. When the

SPRINKLER TIMER 1 ON TEMPERATURE is reached the sprinkler will be activated for

this amount of time and deactivated for SPRINKLER TIMER 1 OFF TIME. This

parameter is adjusted in 1-second increments from 0:00 minutes to 99:59 minutes.

TIMER 1 OFF TIME

This parameter is used to adjust the off time of the first sprinkler timer. When the TIMER

1 ON TEMPERATURE is reached the sprinkler will be activated for SPRINKLER TIMER

1 ON TIME and deactivated for this amount of time. This parameter is adjusted in 1-

second increments from 0:00 minutes to 99:59 minutes.

Page 84: T uch - agrivent.com

USER’S GUIDE

Section C-84

SPRINKLER (CONTINUED…)

TIMER 2 ON TEMPERATURE

This parameter is used to adjust the second sprinkler timer’s activation temperature.

Timer 2 will be activated when the temperature selected in SPRINKLER PROBES is

equal to or above this set point. When this temperature is reached, the sprinkler will be

activated for SPRINKLER TIMER 2 ON TIME and deactivated for SPRINKLER TIMER 2

OFF TIME. This parameter is adjusted in 0.1° increments from MAIN SETPOINT - 10.0°

to MAIN SETPOINT + 40.0°.

TIMER 2 OFF TEMPERATURE

This parameter is used to adjust the second sprinkler timer’s deactivation temperature.

When the temperature selected in SPRINKLER PROBES drops to this temperature, the

timer 2 logic will no longer be effective. This parameter is adjusted in 0.1° increments

from the SPRINKLER TIMER 2 ON TEMPERATURE - 0.5° to SPRINKLER TIMER 2

ON TEMPERATURE - 10.0°.

TIMER 2 ON TIME

This parameter is used to adjust the on time of the second sprinkler timer. When the

SPRINKLER TIMER 2 ON TEMPERATURE is reached the sprinkler will be activated for

this amount of time and deactivated for SPRINKLER TIMER 2 OFF TIME. This

parameter is adjusted in 1-second increments from 0:00 minutes to 99:59 minutes.

TIMER 2 OFF TIME

This parameter is used to adjust the off time of the second sprinkler timer. When the

SPRINKLER TIMER 2 ON TEMPERATURE is reached the sprinkler will be activated for

SPRINKLER TIMER 2 ON TIME and deactivated for this amount of time. This parameter

is adjusted in 1-second increments from 0:00 minutes to 99:59 minutes.

ACTIVATION PERIOD START

This parameter is used to set the beginning of the sprinkler activation period. When the

time of day reaches the time set here, the sprinkler output will be allowed to activate

according to temperature. Setting this value to the same value as the SPRINKLER

ACTIVATION PERIOD END will cancel the deactivation period. This parameter can be

set to any value from 12:00A to 11:59P (0:00 to 23:59).

ACTIVATION PERIOD END

This parameter is used to set the end of the sprinkler activation period. When the time of

day reaches the time set here, the sprinkler output will no longer be allowed to activate

according to temperature. Setting this value to the same value as the SPRINKLER

ACTIVATION PERIOD START will cancel the deactivation period. This parameter can be

set to any value from 12:00A to 11:59P (0:00 to 23:59).

HUMIDITY INFLUENCE

This option is used to determine if the sprinkler will be deactivated by the actual

humidity. If this option is set to ON the sprinkler will be deactivated if humidity is above

the SPRINKLER HUMIDITY SETPOINT. If this option is set to OFF the sprinkler will

not be affected by humidity.

Page 85: T uch - agrivent.com

USER’S GUIDE

Section C-85

SPRINKLER (CONTINUED…)

HUMIDITY SETPOINT

This parameter is used to adjust the humidity level at which the sprinkler may not be

activated by temperature demand. If the SPRINKLER HUMIDITY INFLUENCE option is

set to ON, the sprinkler will be deactivated if humidity is above this set point. A fixed

Differential of 3RH% is used with this logic. This parameter is adjusted in 1RH%

increments from 0RH% to 100RH%.

SOAKING CYCLE

This parameter is used to activate or deactivate the soak cycle. As soon as this option is

set to ON, the sprinkler will be activated for the SPRINKLER SOAKING TIME ON and

will be deactivated for the SPRINKLER SOAKING TIME OFF. This cycle will continue

for a period of time equal to the SPRINKLER SOAKING DURATION. As soon as the

SPRINKLER SOAKING DURATION has elapsed, this parameter will automatically be

reset to OFF. The user may also cancel the soak cycle at any time by adjusting this option

to OFF before the SPRINKLER SOAKING DURATION has elapsed. The soak cycle has

priority over all other sprinkler timers.

SOAKING DURATION

This parameter is used to determine the amount of time for which the soak cycle will be

active after the SPRINKLER SOAKING CYCLE option has been set to ON. As soon as

this period of time has elapsed, the SPRINKLER SOAKING CYCLE option will

automatically be reset to OFF. This parameter is adjusted in 1-minute increments from

0:00 hours to 99:59 hours.

SOAKING ON TIME

This parameter is used to adjust the on time of the soak timer. When the SPRINKLER

SOAKING CYCLE option has been set to ON, the sprinkler will be activated for this

amount of time and deactivated for the SPRINKLER SOAKING TIME OFF. Setting this

parameter to 0 will deactivate the soak timer. This parameter is adjusted in 1-second

increments from 0:00 minutes to 99:59 minutes.

SOAKING OFF TIME

This parameter is used to adjust the off time of the soak timer. When the SPRINKLER

SOAKING CYCLE option has been set to ON, the sprinkler will be activated for the

SPRINKLER SOAKING TIME ON and deactivated for this amount of time. Setting this

parameter to 0 will activate the sprinkler continuously during the soak cycle. This

parameter is adjusted in 1-second increments from 0:00 minutes to 99:59 minutes.

SOAKING TIME LEFT

This parameter displays the remaining time of the soak cycle. After the SPRINKLER

SOAKING CYCLE option has been set to ON, this parameter will start to decrease as time

advances. The value displayed may vary from 0:00 hours to 99:59 hours.

PROBES

These parameters are used to select the probes the respective sprinkler will use to

determine activation and deactivation according to temperature demand. If there are no

probes selected, the temperature used will be equal to the actual MAIN SETPOINT.

Page 86: T uch - agrivent.com

USER’S GUIDE

Section C-86

AIR INLETS POSITION MODE

If the Position mode is used, the air inlet will take a position according to the

activation of ventilation stages using their own probes and will be able to use

temperature and static pressure compensation.

If the Zone Position mode is used, the air inlet will take a position according to the

activation the ventilation stages would have if they used the air inlet’s probes and will not

be able to use temperature and static pressure compensation.

ACTUAL POSITION

These parameters display the actual position of the air inlets used in Position Mode or

Natural Pot. The actual positions are displayed to the nearest 1% from -99% to 127%.

However, if the controller cannot read the position, the corresponding parameter will

display ERROR.

REQUESTED POSITION

These parameters display the requested position of the air inlets. The requested positions

are displayed to the nearest 1% from 0% to 100%.

MANUAL OVERRIDE

This parameter is used to manually operate the respective inlet. When this parameter is

set to a value other than AUTO, the corresponding inlet will take the corresponding

state/position. This parameter can be adjusted to AUTO, HALT, CLOSE, OPEN or any

value from 0% to 100%.

WINTER SETPOINT

This parameter is used to adjust the temperature at which calculated position (AIR INLET

(1-16) MINIMUM OPENING and AIR INLET (1-16) VARIABLE 1 START POSITION)

will respectively be equal to AIR INLET (1-16) WINTER MINIMUM OPENING and AIR

INLET (1-16) WINTER VARIABLE 1 START. When the Outside Temperature is

between AIR INLET (1-16) WINTER SETPOINT and AIR INLET (1-16) SUMMER SETPOINT, calculated positions will modulate according to settings. These calculated

positions are displayed to the parameter AIR INLET (1-16) MINIMUM OPENING and on

the AIR INLET (1-16) VARIABLE 1 START POSITION. This parameter is adjusted in

0.1° from -40.0°C to 40.0°C (-40.0°F to 120.0°F).

SUMMER SETPOINT

This parameter is used to adjust the temperature at which calculated position (AIR INLET

(1-16) MINIMUM OPENING and AIR INLET (1-16) VARIABLE 1 START POSITION)

will respectively be equal to AIR INLET (1-16) SUMMER MINIMUM OPENING and

AIR INLET (1-16) SUMMER VARIABLE 1 START POSITION. When the Outside

Temperature is between AIR INLET (1-16) WINTER SETPOINT and AIR INLET (1-16)

SUMMER SETPOINT, calculated positions will modulate according to settings. These

calculated positions are displayed to the parameter AIR INLET (1-16) MINIMUM

OPENING and on the AIR INLET (1-16) VARIABLE 1 START POSITION. This

parameter is adjusted in 0.1° from -40.0°C to 40.0°C (-40.0°F to 120.0°F).

Page 87: T uch - agrivent.com

USER’S GUIDE

Section C-87

AIR INLETS POSITION MODE (CONTINUED…)

WINTER MINIMUM OPENING

This parameter is used to adjust the minimum opening position when the OUTSIDE

TEMPERATURE is equal to or below AIR INLET (1-16) WINTER SETPOINT. When the

OUTSIDE TEMPERATURE is between AIR INLET (1-16) WINTER SETPOINT and AIR

INLET (1-16) SUMMER SETPOINT, the minimum opening position will modulate

accordingly. The calculated minimum opening is displayed at the parameter AIR INLET

(1-16) MINIMUM OPENING. This parameter is adjusted in 1% increments from 0% to

100%.

SUMMER MINIMUM OPENING

This parameter is used to adjust the minimum opening position when the OUTSIDE

TEMPERATURE is equal to or above AIR INLET (1-16) SUMMER SETPOINT. When

the OUTSIDE TEMPERATURE is between AIR INLET (1-16) WINTER SETPOINT and

AIR INLET (1-16) SUMMER SETPOINT, the minimum opening position will modulate

accordingly. The calculated minimum opening is the parameter AIR INLET (1-16)

MINIMUM OPENING. This parameter is adjusted in 1% increments from 0% to 100%.

WINTER VARIABLE 1 START POSITION

This parameter allows to adjust the variable stage 1 start position (AIR INLET (1-16)

VARIABLE 1 START POSITION) when OUTSIDE TEMPERATURE is equal or under

AIR INLET (1-16) WINTER SETPOINT and AIR INLET (1-16) SUMMER SETPOINT,

this position will modulate according to the adjustments. This calculated position is

displayed on parameter AIR INLET (1-16) VARIABLE 1 START POSITION. This

parameter is adjusted in 1% increments from 0% to 100%.

SUMMER VARIABLE 1 START POSITION

This parameter is used to adjust the position of variable stage 1 start (AIR INLET (1-16)

VARIABLE 1 START POSITION) when OUTSIDE TEMPERATURE is equal or above to

AIR INLET (1-16) SUMMER SETPOINT. When OUTSIDE TEMPERATURE is between

AIR INLET (1-16) WINTER SETPOINT and AIR INLET (1-16) SUMMER SETPOINT,

this position will modulate according to the settings. This position is displayed on the

parameter AIR INLET (1-16) VARIABLE 1 START POSITION. This parameter is adjusted

in 1% increments from 0% to 100%.

MINIMUM OPENING

This parameter is used to adjust the minimum opening position when no ventilation

stages are active. When the OUTSIDE TEMPERATURE is used, the calculated

minimum opening is shown here and this parameter is not adjustable. This parameter is

adjusted in 1% increments from 0% to 100%.

Page 88: T uch - agrivent.com

USER’S GUIDE

Section C-88

AIR INLETS POSITION MODE (CONTINUED…)

VARIABLE (1-12) START POSITION

These parameters allow the user to set the inlet opening position when variable stage is

activated at VARIABLE STAGE (1-12) MINIMUM SPEED REFERENCE FOR INLET or

VARIABLE STAGE (1-12) MINIMUM SPEED (including OUTSIDE TEMPERATURE

compensation, but excluding humidity compensation) according to VARIABLE STAGE

(1-12) MINIMUM SPEED AFFECTS INLET. Inlet opening will increase proportionally

to the variable stage speed to reach AIR INLET (1-16) VARIABLE (1-12) END

POSITION when variable stage is activated at VARIABLE STAGE (1-12) MAXIMUM

SPEED. Inlet will also be positioned when the respective variable stage is active on

minimum ventilation, for variable stages 1 to 4, or while dehumidification, for variable

stages 1 and 2. If the outside temperature probe is used, AIR INLET (1-16) VARIABLE 1

START POSITION will reflect the minimum calculated position and will not be

adjustable. These positions are adjusted in 1% increments from 0% to 100%

VARIABLE (1-12) END POSITION

These parameters allow adjusting the opening position the inlet will take when variable

stage is activated at VARIABLE STAGE (1-12) MAXIMUM SPEED. These positions are

adjusted in 1% increments from 0% to 100%.

POSITION AFTER VENT STAGE (1-24)

This parameter is used to set the position that inlet will take when the idle back function

between the last variable stage and the first on/off stage is used. When LAST VARIABLE

IDLE BACK ON FIRST ON/OFF STAGE is set to a value other than OFF or STOP, the ai

inlet will modulate from the first on/off stage’s position to this position throughout the

last variable stage’s modulation band. This parameter is adjusted in 1% increments from

0% to 100%.

STAGE (1-24) POSITION

These parameters are used to set the opening position that inlet will take when respective

stage is activated. These positions are adjusted in 1% increments from 0% to 100%.

POSITION CONFIGURATION

These parameters are used to activate or deactivate the configuration sequence. When this

parameter is set to ON, all ventilation outputs will activate and all inlets set in Position

Mode will be positioned according to the AIR INLET (1-16) POSITION ADJUSTMENT CONFIGURATION parameter. The configuration sequence overrides on all instructions

but manual override. This option will be reset to OFF after AIR INLET (1-16) POSITION

ADJUSTMENT CONFIGURATION parameter has been unchanged for 10 minutes.

POSITION ADJUSTMENT CONFIGURATION

These parameters allow the user to modify the actual configuration sequence of the inlet.

The modification is effective when this parameter is pressed. When there is a change, the

text of this parameter will change to become the one of next inlet positioning. Ventilation

outputs will activate as if the temperatures values were exactly equal to required

temperature for inlet to take this position. Only active ventilation stages will be

considered in the configuration sequence.

Page 89: T uch - agrivent.com

USER’S GUIDE

Section C-89

AIR INLETS POSITION MODE (CONTINUED…)

MAXIMUM OPENING TEMPERATURE (Curve Available)

This parameter allows the user to set the temperature at which inlet will take the AIR

INLET (1-16) MAXIMUM OPENING position. When related temperature to the inlet

reaches this set point, the inlet will be positioned to AIR INLET (1-16) MAXIMUM

OPENING. A fixed Differential of 0.3° is used with this logic. This parameter is

adjusted in 0.1° increments from 0°C to 40.0°C (0.0°F to 120.0°F).

MAXIMUM OPENING TEMPERATURE CURVE OPTION

This parameter is used to activate or deactivate the AIR INLET (1-16) MAXIMUM

OPENING TEMPERATURE Growth Function. If curve option is set to ON and

GROWTH DAY is not set to OFF the AIR INLET (1-16) MAXIMUM OPENING

TEMPERATURE will follow its Growth Curve.

MAXIMUM OPENING

This parameter is used to set the position that inlet will take when related temperature

reaches AIR INLET (1-16) MAXIMUM OPENING TEMPERATURE. This parameter is

adjusted in 1% increments from 0% to 100%.

ABSOLUE MAXIMUM OPENING WINTER

This parameter is used to set the maximum position that inlet can take when OUTSIDE

TEMPERATURE drops to or below AIR INLET (1-16) WINTER SET POINT. If the air

inlet is in winter mode, it will never take an opening above this setting except if manual

override is used. This parameter is adjusted in 1% increments from 0% to 100%.

COLD CLOSING TEMPERATURE

This parameter is used to set the temperature at which the inlet will close, regardless of

ventilation demand. When the inlet’s temperature drops to this set point, the air inlet will

close without considering other requests. A locked Differential of 0.3° is used with this

set point. Setting this parameter to OFF deactivates the cold closing function. This

parameter is adjusted in 0.1° increments from OFF, MAIN SET POINT - 20.0° to MAIN

SET POINT.

POSITION IN TUNNEL

This parameter is used to determine the position the inlet will take in tunnel mode. If this

parameter is set to OFF, the inlet will position itself according to stage position and the

selected temperature. If the parameter is set to any value from 0% to 100%, this will be

the position the inlet will take when in tunnel mode. This parameter is adjusted in 1%

increments from OFF, 0% to 100%.

CLOSE IN NATURAL

This parameter allows the user to set if the respective inlet closes in natural mode. When

this parameter is set to Yes, the inlet will completely close when controller begins a

tunnel mode. This parameter will not be available if the natural mode is not used or if the

inlet is used as an inlet in natural.

Page 90: T uch - agrivent.com

USER’S GUIDE

Section C-90

AIR INLETS POSITION MODE (CONTINUED…)

NATURAL REACTIVATION TEMPERATURE

This parameter is used to reactivate the inlet in natural mode if it is closed by the AIR

INLET (1-16) CLOSE IN NATURAL. When inlet temperature reaches this parameter,

inlet will not be forced to close in natural mode. A fixed Differential of 1.0° is used with

this logic. This parameter is adjusted in 0.1° increments from 0.0° to 40.0°C, OFF (0.0°F

to 120.0°F, OFF).

POSITION ON TIMER/HEATING

This parameter determines the behavior of the inlet for its positioning when a ventilation

stage is activated by its timer or by a heater. When this parameter is set to V1Str, in

minimum ventilation, no matter which stage is activated by its timer or by a heater, the

inlet will position itself at the AIR INLET (1-16) VARIABLE 1 START POSITION if no

stage is activated by temperature. When a stage is activated by temperature, the inlet will

position itself according to the opening position of the last stage which is activated by

temperature. If this parameter setting is between 0% and 100% inclusive, the inlet will act

as the previous case, replacing the V1Str position by the position adjusted in this

parameter. When this parameter is set to Stages, the inlet will position itself according to

the opening position of the last stage which is activated by temperature, its timer or by a

heater. This parameter can be set to V1Str, Stages or adjusted in 1% increments from 0%

to 100%

TEMPERATURE COMPENSATION

This parameter is used to adjust the compensation that will be applied to the inlet for each

degree of difference between its temperature and the AIR INLET (1-16) PROBES temperature. When the inlet’s temperature is greater than the AIR INLET (1-16) PROBES,

the inlet’s opening will be increased by this value for every degree of difference. When

the AIR INLET (1-16) PROBES temperature is less than the AVERAGE

TEMPERATURE the inlet’s opening will be decreased by this value for every degree of

difference. This compensation will be applied only if the inlet is positioned for the stage

selected at AIR INLET (1-16) MINIMUM STAGE TEMPERATURE COMPENSATION or

a higher stage. Temperature compensation is not available for zone position mode inlets.

This parameter is adjusted in 1% increments from 0% to 99%.

MINIMUM STAGE TEMPERATURE COMPENSATION

This parameter is used to adjust the minimum stage that must for which the inlet must be

positioned in order to apply temperature compensation. If the air inlet has a position of a

stage lower than the one selected here, temperature compensation will not be applied.

ACTUAL TEMPERATURE COMPENSATION

This parameter displays the current compensation temperature applied on the inlet.

STATIC PRESSURE COMPENSATION OPTION

This parameter allows the user to activate or deactivate static pressure compensation on

the inlet. If this option is set to Yes, inlet position will be increased or reduced according

to the static pressure reading and parameters. If this option is set to No, inlet position will

not be influenced by static pressure. Static pressure compensation is not available for

zone position mode inlets.

Page 91: T uch - agrivent.com

USER’S GUIDE

Section C-91

AIR INLETS POSITION MODE (CONTINUED…)

ACTUAL STATIC PRESSURE COMPENSATION

This parameter displays the actual temperature compensation applied to the inlet's

position. The compensation is displayed to the nearest 1% from -100% to 100%.

STATIC PRESSURE COMPENSATION

This parameter is used to adjust the compensation that will be applied to the inlet when

the static pressure is not under AIR INLET LOW STATIC PRESSURE SETPOINT or not

above AIR INLET HIGH STATIC PRESSURE SETPOINT. When the static pressure is

greater than AIR INLET HIGH STATIC PRESSURE SETPOINT, the inlet’s opening will

be increased by this value every time AIR INLET STATIC PRESSURE COMPENSATION

DELAY has expired. When the static pressure is less than AIR INLET LOW STATIC

PRESSURE SETPOINT, the inlet’s opening will be decreased by this value every time

AIR INLET STATIC COMPENSATION PRESSURE DELAY has expired. Static pressure

compensation will be applied only when the inlet is using the position of a stage who’s

corresponding AIR INLET VARIABLE STAGES/STAGES AFFECTED BY STATIC

PRESSURE COMPENSATION and the position added or reduced is reset each time a

ventilation stage is activated. Pressure compensation will be checked each time the AIR

INLET STATIC PRESSURE COMPENSATION DELAY has expired. This parameter is

adjusted in 1% increments from 0% to 99%.

LOW STATIC PRESSURE SETPOINT

This parameter is used to adjust the value at which inlet static pressure compensation will

begin to reduce the inlet’s opening. When the static pressure is less than this parameter,

the inlet’s opening will be decreased by AIR INLET STATIC PRESSURE

COMPENSATION for every 0.010”WC of difference. Pressure compensation will be

checked each time the AIR INLET STATIC PRESSURE COMPENSATION DELAY has

expired. Static pressure compensation will be applied only when the inlet is using the

position of a stage whose corresponding AIR INLET VARIABLE STAGES/STAGES

AFFECTED BY STATIC PRESSURE COMPENSATION option is selected. This

parameter is adjusted in 0.001”WC (1Pa) from -0.500”WC to 0.500”WC (-99Pa to 99Pa).

HIGH STATIC PRESSURE SETPOINT

This parameter is used to adjust the value at which inlet static pressure compensation will

begin to increase the inlet’s opening. When the static pressure is greater than this

parameter, the inlet’s opening will be increased by AIR INLET STATIC PRESSURE

COMPENSATION for every 0.010”WC of difference. Pressure compensation will be

checked each time the AIR INLET STATIC PRESSURE COMPENSATION DELAY

expires. Static pressure compensation will be applied only when the inlet is using the

position of a stage whose corresponding AIR INLET VARIABLE STAGES/STAGES

AFFECTED BY STATIC PRESSURE COMPENSATION option is selected. This

parameter is adjusted in 0.001”WC (1Pa) from -0.500”WC to 0.500”WC (-99Pa to 99Pa).

Page 92: T uch - agrivent.com

USER’S GUIDE

Section C-92

AIR INLETS POSITION MODE (CONTINUED…)

STATIC PRESSURE COMPENSATION DELAY

This parameter is used to adjust the time after which static pressure will be checked to

evaluate static pressure compensation on the inlet’s position. When the static pressure is

not within AIR INLET LOW STATIC PRESSURE SETPOINT and AIR INLET HIGH

STATIC PRESSURE SETPOINT, this delay will start. Once the delay has expired, the

compensation will be evaluated and applied. Once the compensation is evaluated, the

delay starts once again and compensation will be evaluated and applied again when the

delay expires once more. This cycle continues as long as the static pressure is outside the

AIR INLET LOW STATIC PRESSURE SETPOINT and AIR INLET HIGH STATIC

PRESSURE SETPOINT limits. Static pressure compensation will be applied only when

the inlet is using the position of a stage whose corresponding AIR INLET VARIABLE

STAGES/STAGES AFFECTED BY STATIC PRESSURE COMPENSATION option is

selected. This parameter is adjusted in 1-second increments from 0 second to 999

seconds.

STATIC PRESSURE COMPENSATION LIMIT

This parameter is used to set the limit for the static pressure compensation. The static

pressure compensation will not alter the inlet’s position by a value greater than the one

set here. This parameter is adjusted in 1% increments from 0% to 100%.

VARIABLE STAGES AFFECTED BY STATIC PRESSURE COMPENSATION

This parameter is used to activate or deactivate static pressure compensation for the

respective variable stage’s position. If a variable stage is not selected at this parameter,

static pressure compensation will not be applied for that variable stage’s position.

STAGES AFFECTED BY STATIC PRESSURE COMPENSATION

This parameter is used to activate or deactivate static pressure compensation for the

respective on/off stage’s position. If an on/off stage is not selected at this parameter,

static pressure compensation will not be applied for that variable stage’s position.

PRESSURE COMPENSATION WITH TIMER

This parameter is used to allow if static pressure compensation will be applied on a

ventilation stage using timer. If set to No, the static pressure compensation will not be

used as long as variable, stage or inlet uses minimum ventilation timer. If this parameter

is set to Yes, the static pressure compensation will be applied when outputs use minimum

ventilation timer.

FAN DELAY FOR POSITIONNING

This parameter is used to set the time for which the fans will wait before activating to

allow inlets to position themselves. When a ventilation stage receives an activation

demand, the position mode air inlets will take that stage’s position, the pressure mode air

inlets will open continuously and, once this delay has expired, the ventilation stage will

activate. Setting this value to OFF deactivates this delay. This parameter is adjusted in 1-

second increments from OFF, 1 to 300 seconds.

Page 93: T uch - agrivent.com

USER’S GUIDE

Section C-93

AIR INLETS POSITION MODE (CONTINUED…)

FOLLOW NATURAL POT IONLET IN NATURAL

This parameter is used to choose if the air inlet will follow a natural potentiometer air

inlet when the system is in natural mode. If this parameter is set to a number that

corresponds to a natural potentiometer air inlet, this air inlet will follow the requested

position of the selected natural potentiometer inlet when in natural mode. Adjusting this

parameter to OFF or a number that does not correspond to a natural potentiometer air

inlet will deactivate this function.

COPY PARAMETERS FROM INLET

This parameter is used to choose another position mode air inlet to later copy its

adjustments. If this parameter is set to a number corresponding to a position mode air

inlet, the parameters of that air inlet will be copied when the PERFORM COPY

parameter is pressed.

PERFORM COPY

This parameter is used to copy all adjustments of the position mode air inlet selected at

COPY PARAMETERS FROM INLET to the parameters of the position mode air inlet

belongs to.

Page 94: T uch - agrivent.com

USER’S GUIDE

Section C-94

AIR INLETS NATURAL POTENTIOMETER

ACTUAL POSITION

These parameters display the actual position of the air inlets used in Position Mode or

Natural Pot. The actual positions are displayed to the nearest 1% from -99% to 127%.

However, if the controller cannot read the position, the corresponding parameter will

display ERROR.

REQUESTED POSITION

These parameters display the requested position of the air inlets. The requested positions

are displayed to the nearest 1% from 0% to 100%.

MANUAL OVERRIDE

This parameter is used to manually operate the respective inlet. When this parameter is

set to a value other than AUTO, the corresponding inlet will take the corresponding

state/position. This parameter can be adjusted to AUTO, HALT, CLOSE, OPEN or any

value from 0% to 100%.

OPENING TEMPERATURE

This parameter is used to set the temperature at which the inlet will position itself at its

AIR INLET (1-16) MINIMUM OPENING. The inlet will close completely when the

inlet’s selected temperature drops to AIR INLET (1-16) OPENING TEMPERATURE -

AIR INLET (1-16) DIFFERENTIAL. If temperature continues to increase, the inlet’s

opening will increase proportionally to reach AIR INLET (1-16) MAXIMUM OPENING

when the selected temperature is equal to or above the AIR INLET (1-16) OPENING

TEMPERATURE + AIR INLET (1-16) MODULATION BAND. This temperature is

adjusted in 0.1° increments from MAIN SETPOINT - 20.0° to MAIN SETPOINT + 20.0°.

DIFFERENTIAL

This parameter is used to set the Differential used with the INLET (1-16) OPENING

TEMPERATURE. When temperature decreases, the inlet will close completely when the

inlet’s selected temperature drops to INLET (1-16) OPENING TEMPERATURE - INLET

(1-16) DIFFERENTIAL. This temperature is adjusted in 0.1° increments from 0.3° to

20.0°.

MODULATION BAND

This parameter is used to set the range of temperature within which the inlet’s opening

will modulate from its INLET (1-16) MINIMUM OPENING to its INLET (1-16)

MAXIMUM OPENING. When the inlet’s temperature reaches INLET (1-16) OPENING

TEMPERATURE + INLET (1-16) MODULATION BAND, the inlet will open at its INLET

(1-16) MAXIMUM OPENING. This temperature is adjusted in 0.1° increments from 0.5°

to 20.0°.

MINIMUM OPENING

This parameter is used to set the position the inlet will take when its temperature reaches

its INLET (1-16) OPENING TEMPERATURE. The inlet’s opening will modulate from

this position to its INLET (1-16) MAXIMUM OPENING throughout the INLET (1-16)

MODULATION BAND. This parameter is adjusted in 1% increments from 0% to 100%.

Page 95: T uch - agrivent.com

USER’S GUIDE

Section C-95

AIR INLETS NATURAL POTENTIOMETER (CONTINUED…)

ABSOLUTE MINIMUM OPENING

This parameter is used to set the absolute minimum of the inlet. The positioning of the

inlet will not be under this parameter. This parameter is adjusted in 1% increments from

0% to 100%.

MAXIMUM OPENING

This parameter is used to set the position the inlet will take when its temperature reaches

its INLET (1-16) OPENING TEMPERATURE + INLET (1-16) MODULATION BAND.

The inlet’s opening will modulate from its INLET (1-16) MINIMUM OPENING to this

position throughout the INLET (1-16) MODULATION BAND. This parameter is adjusted

in 1% increments from 0% to 100%.

POSITION DIFFERENCE BEFORE MOVEMENT

This parameter is used to set the minimum difference between the actual demanded

position and the last demanded position before requesting a movement from the inlet. If

the difference between the actual demanded position and the last demanded position is

less than this parameter, the inlet will not move. When the inlet’s demanded position is

0%, INLET (1-16) MINIMUM OPENING or INLET (1-16) MAXIMUM OPENING, the

inlet will not consider this parameter. This parameter is adjusted in 1% increments from

1% to 100%.

CLOSE BEFORE NATUREL

This parameter allows the user to set if the respective inlet closes when the system is not

yet in natural mode. When this parameter is set to Yes, the inlet will completely close

before controller is not in natural mode.

CLOSE IN TUNNEL

This parameter allows the user to set if the respective inlet closes in tunnel mode. When

this parameter is set to Yes, the inlet will completely close when controller begins tunnel

mode. This parameter will not be available if the tunnel mode is not used.

Page 96: T uch - agrivent.com

USER’S GUIDE

Section C-96

AIR INLETS NATURAL TIME

ACTUAL STATUS

These parameters display the actual position of the air inlets used in Natural Timer mode.

The respective parameter displays the actual demanded state, which may be OPEN,

CLOSE, or HOLD.

OPENING TEMPERATURE

This parameter is used to set the temperature at which the inlet will begin to open

according to its opening timer. When the assigned temperature reaches this relative set

point, the ON portion of the opening timer will be equal to the INLET (1-7, 9-15)

MINIMUM OPENING parameter. As temperature increases, the opening time will

increase proportionally to reach the INLET (1-7, 9-15) MAXIMUM OPENING time when

the assigned temperature reaches the INLET (1-7, 9-15) PROGESSIVE OPENING

temperature. This parameter can be adjusted in 0.1° increments from MAIN SETPOINT -

20.0° to MAIN SETPOINT + 20.0°.

PROGRESSIVE OPENING

This parameter is used to set the temperature at which the ON portion of the opening

timer will be equal to the INLET (1-7, 9-15) MAXIMUM OPENING parameter. This

parameter can be adjusted in 0.1° increments from INLET (1-7, 9-15) OPENING

TEMPERATURE to INLET (1-7, 9-15) OPENING TEMPERATURE + 20.0°.

CLOSING TEMPERATURE

This parameter is used to set the temperature at which the inlet will begin to close

according to its closing timer. When the assigned temperature reaches this relative set

point, the ON portion of the closing timer will be equal to the INLET (1-7, 9-15)

MINIMUM CLOSING parameter. As the temperature decreases, the closing time will

increase proportionally to reach the INLET (1-7, 9-15) MAXIMUM CLOSING time when

the assigned temperature drops to the INLET (1-7, 9-15) PROGESSIVE CLOSING temperature. This parameter can be adjusted in 0.1° increments from MAIN SETPOINT -

20.0° to MAIN SETPOINT + 20.0°.

PROGRESSIVE CLOSING

This parameter is used to set the temperature at which the ON portion of the closing timer

will be equal to the INLET (1-7, 9-15) MAXIMUM CLOSING parameter. This parameter

can be adjusted in 0.1° increments from INLET (1-7, 9-15) CLOSING TEMPERATURE - 20.0° to INLET (1-7, 9-15) CLOSING TEMPERATURE.

DIFFERENTIAL

This parameter is used to set the Differential used on both the opening and closing set

points. Once a movement temperature (INLET (1-7, 9-15) OPENING TEMPERATURE or

INLET (1-7, 9-15) CLOSING TEMPERATURE) is reached, the respective timer will only

be deactivated when temperature reaches INLET (1-7, 9-15) OPENING TEMPERATURE - INLET (1-7, 9-15) DIFFERENTIAL or INLET (1-7, 9-15) CLOSING TEMPERATURE + INLET (1-7, 9-15) DIFFERENTIAL. This parameter is adjusted in 0.1° increments from

0.5° to 10.0°.

Page 97: T uch - agrivent.com

USER’S GUIDE

Section C-97

AIR INLETS NATURAL TIME (CONTINUED…)

CYCLE TIME

This parameter is used to set the total period of both the opening and the closing timers.

An inlet will open or close according to the actual calculated opening or closing time and

stay put for the rest of the period. If the calculated opening or closing time is equal to or

greater than this parameter, the inlet will continuously be in movement. This parameter is

adjusted in 1-minute increments from 1 to 15 minutes.

MINIMUM CLOSING TIME

This parameter is used to set the minimum active portion of the closing timer. When the

assigned temperature reaches the INLET (1-7, 9-15) CLOSING TEMPERATURE set

point, the ON portion of the closing timer will be equal to this value. This parameter is

adjusted in 1-second increments from 0 to 999 seconds.

MAXIMUM CLOSING TIME

This parameter is used to set the maximum active portion of the closing timer. When the

assigned temperature reaches the INLET (1-7, 9-15) PROGESSIVE CLOSING set point,

the ON portion of the closing timer will be equal to this value. This parameter is adjusted

in 1-second increments from 0 to 999 seconds.

MINIMUM OPENING TIME

This parameter is used to set the minimum active portion of the opening timer. When the

assigned temperature reaches the INLET (1-7, 9-15) OPENING TEMPERATURE set

point, the ON portion of the opening timer will be equal to this value. This parameter is

adjusted in 1-second increments from 0 to 999 seconds.

MAXIMUM OPENING TIME

This parameter is used to set the maximum active portion of the opening timer. When the

assigned temperature reaches the INLET (1-7, 9-15) PROGESSIVE OPENING set point,

the ON portion of the opening timer will be equal to this value. This parameter is

adjusted in 1-second increments from 0 to 999 seconds.

CLOSE BEFORE NATUREL

This parameter allows the user to set if the respective inlet closes when the system is not

yet in natural mode. When this parameter is set to Yes, the inlet will completely close

before controller is not in natural mode.

CLOSE IN TUNNEL

This parameter allows the user to set if the respective inlet closes in tunnel mode. When

this parameter is set to Yes, the inlet will completely close when controller begins tunnel

mode. This parameter will not be available if the tunnel mode is not used.

Page 98: T uch - agrivent.com

USER’S GUIDE

Section C-98

AIR INLETS NATURAL TIME (CONTINUED…)

Example of inlet natural timer:

INLET (1-7, 9-15) OPENING TEMPERATURE = 72.0°F

INLET (1-7, 9-15) PROGRESSIVE OPENING = 80.0°F

INLET (1-7, 9-15) CLOSING TEMPERATURE = 68.0°F

INLET (1-7, 9-15) PROGRESSIVE CLOSING = 60.0°F

INLET (1-7, 9-15) DIFFÉRENTIAL = 1.0°F

INLET (1-7, 9-15) CYCLE TIME = 5 min

INLET (1-7, 9-15) MINIMUM CLOSING TIME = 10 sec

INLET (1-7, 9-15) MAXIMUM CLOSING TIME = 60 sec

INLET (1-7, 9-15) MINIMUM OPENING TIME = 10 sec

INLET (1-7, 9-15) MAXIMUM OPENING TIME = 80 sec

Timer (sec)

Temp

70

50

40

30

Inlet Close

Open Temp

60 64 68 69 76 80 72 71 Close Prog

Close Temp

Open Prog

0

10

20

60

80 Close 60

Idle 240

Close 35 Idle 265

Close 10 Idle 290

Open 45

Idle 255

Open 80 Idle 220

Open 10

Idle 290

Inlet Stop Inlet Open

D

i

f

f

D

i

f

f

Page 99: T uch - agrivent.com

USER’S GUIDE

Section C-99

AIR INLETS STATIC PRESSURE

ACTUAL STATUS

These parameters display the actual position of the air inlets used in Natural Timer mode.

The respective parameter displays the actual demanded state, which may be OPEN,

CLOSE, or HOLD.

LOW STATIC PRESSURE

This parameter is used to set the inlet’s low static pressure set point. When static pressure

is below this set point, the inlet will close according to its static pressure timer. As soon

as static pressure rises to or above this set point, the inlet will stop closing. This

parameter is adjusted in 0.001WC” increments from -0.500”WC to 0.500”WC (-99Pa to

99Pa).

HIGH STATIC PRESSURE

This parameter is used to set the inlet’s high static pressure set point. When static

pressure is above this set point, the inlet will open according to the static pressure timer.

As soon as static pressure drops to or below this set point, the inlet will stop opening.

This parameter is adjusted in 0.001WC” increments from -0.500”WC to 0.500”WC (-

99Pa to 99Pa).

RUN TIME

This parameter is used to set the active portion of the static pressure timer. When static

pressure is not within the INLET (1-7, 9-15) HIGH STATIC PRESSURE and INLET (1-7,

9-15) LOW STATIC PRESSURE set points, the inlet will open or close for this amount of

time and remain immobile for the INLET (1-7, 9-15) DELAY. This parameter is adjusted

in 1-second increments from 0 to 999 seconds.

DELAY

This parameter is used to set the idle portion of the static pressure timer. When static

pressure is not within the INLET (1-7, 9-15) HIGH STATIC PRESSURE and INLET (1-7,

9-15) LOW STATIC PRESSURE set points, the inlet will open or close for the INLET (1-

7, 9-15) RUN TIME and remain immobile for this amount of time. This parameter is

adjusted in 1-second increments from 0 to 999 seconds.

CLOSE IN TUNNEL

This parameter allows the user to set if the respective inlet closes in tunnel mode. When

this parameter is set to Yes, the inlet will completely close when controller begins tunnel

mode. This parameter will not be available if the tunnel mode is not used.

CLOSE WHEN NOT IN TUNNEL

This parameter allows the user to set if the respective inlet closes when the system is not

in tunnel mode. When this parameter is set to Yes, the inlet will completely close when

controller is not in tunnel mode. This parameter will not be available if the tunnel mode

is not used.

CLOSE IN NATURAL

This parameter allows the user to set if the respective inlet closes in natural mode. When

this parameter is set to Yes, the inlet will completely close when controller begins a

tunnel mode. This parameter will not be available if the natural mode is not used or if the

inlet is used as an inlet in natural.

Page 100: T uch - agrivent.com

USER’S GUIDE

Section C-100

AIR INLETS STATIC PRESSURE (CONTINUED…)

FORCED OPENING TEMPERATURE

This parameter is used to set the temperature at which the respective inlet will be forced

to open continuously. When the assigned temperature reaches this set point, the inlet will

open continuously, without regard to static pressure. Adjusting this parameter to OFF will

deactivate this forced opening. This parameter is adjusted in 0.1° increments from MAIN

SET POINT - 10.0° to MAIN SET POINT + 40.0°, OFF.

DIFFERENTIAL

This parameter is used to set the Differential used with the INLET (1-7, 9-15) FORCED

OPENING TEMPERATURE. After receiving a continuous opening demand, the inlet will

only follow its static pressure set points when the assigned temperature drops to INLET

(1-7, 9-15) FORCED OPENING TEMPERATURE - INLET (1-7, 9-15) DIFFERENTIAL.

This parameter is adjusted in 0.1° increments from 0.5° to 40.0°.

FAN DELAY FOR POSITIONNING

This parameter is used to set the time for which the fans will wait before activating to

allow inlets to position themselves. When a ventilation stage receives an activation

demand, the position mode air inlets will take that stage’s position, the pressure mode air

inlets will open continuously and, once this delay has expired, the ventilation stage will

activate. Setting this value to OFF deactivates this delay. This parameter is adjusted in 1-

second increments from OFF, 1 to 300 seconds.

Page 101: T uch - agrivent.com

USER’S GUIDE

Section C-101

AIR INLETS SETUP

TYPE

These parameters are used to set the mode according to which the respective inlet will

operate. When this parameter is set to No Mode, the associated inlet will not move unless

the manual override or toggle switches are used. Otherwise, inlets may operate according

to five modes. In Position Mode or Zone Position Mode, the inlet will position itself

according to the position mode settings. In Position Mode, the inlet will follow

ventilation stage activation according to their own probes and will be able to use

temperature and static pressure compensation. In Zone Position Mode, the inlet will

follow the ventilation stages as if they used the air inlet’s probes and will not be able to

use temperature and static pressure compensation. In Natural Pot the inlet can trigger

natural mode and will position itself according to the assigned temperature and the

parameter adjustments of that mode. In Natural Time mode, the inlet can trigger natural

mode and will position itself according to the assigned temperature and the parameter

adjustments of that mode. In Static Pressure mode, the inlet will position itself according

to the static pressure, assigned temperature and the parameter adjustments of that mode.

Inlets 8 and 16 cannot be assigned to Natural Time or Static Pressure mode.

PRECISION

This parameter is used to adjust the precision of the inlet. If the inlet performs

unnecessary small movements, increase this value until acceptable stability is obtained.

This parameter is adjusted in 1% increments from 1% to 20%.

POTENTIOMETER ALARM

This parameter is used to determine if the alarm will be activated when the inlet’s

potentiometer value cannot be read. If this option is set to ON and the inlet’s

potentiometer has an out of range reading, the alarm relay will activate. If this option is

set to OFF, only an alarm message will be logged in the alarm history in the case of a

potentiometer problem.

MAXIMUM RUN TIME

This parameter is used to set the maximum run time of the inlet within a ten-minute

period. When an inlet has moved for a time greater than the value of this parameter

within a ten-minute period, the module will not activate the open or close relays until the

inlet has had time to cool down and an alarm message will be logged in the alarm history.

This value should be set according to the manufacturer’s specifications. Setting this value

to OFF will deactivate the module cool down function. If the air inlet is already in cool

down mode when this parameter is set to OFF, it will finish the cool down period before

deactivating the function. It is possible to cancel the cool down sequence immediately by

powering off the controller and the powering it back on. Make sure this parameter is set

to OFF before powering down to cancel cool down sequence. This parameter is adjusted

in 1-minute increments from 1 minute to 9 minutes, OFF.

PROBES

This is used to select the inside temperature probes that will be used by the inlet. The

average of the selected probes will dictate inlet position. If there are no probes selected,

the temperature used will be equal to the MAIN SETPOINT.

Page 102: T uch - agrivent.com

USER’S GUIDE

Section C-102

AIR INLETS SETUP (CONTINUED…)

LOW LIMIT CALIBRATION

This parameter is used to set the low potentiometer limit for the inlet. This will define the

lowest value the inlet’s potentiometer can reach. To obtain this value, completely close

the inlet using the manual override switch. Once the inlet is completely closed, press on

this parameter. At this moment, the displayed text will change for Low Limit Saved, if

the operation was successful, Cannot Save Low Limit, if the potentiometer value could

not be saved, or Error, Check Potentiometer if the potentiometer has an out of range

value. In the two last cases, the calibration must be performed again once the situation is

corrected.

HIGH LIMIT CALIBRATION

This parameter is used to set the low potentiometer limit for the inlet. This will define the

lowest value the inlet’s potentiometer can reach. To obtain this value, completely open

the inlet using the manual override switch. Once the inlet is completely closed, press on

this parameter. At this moment, the displayed text will change for High Limit Saved, if

the operation was successful, Cannot Save High Limit, if the potentiometer value could

not be saved, or Error, Check Potentiometer if the potentiometer has an out of range

value. In the two last cases, the calibration must be performed again once the situation is

corrected.

Page 103: T uch - agrivent.com

USER’S GUIDE

Section C-103

ALARMS

RELAY

This parameter is used to activate or deactivate the alarm relays. If this setting is set to

OFF, no alarm relay will be activated but messages will still appear in the alarm history.

If this parameter is set to ON, alarm relays will activate when alarm condition occurs. A

message will be logged every time the alarm relay is activated or deactivated. It is not

recommended to deactivate the alarm relay.

ALARME STATE

This parameter displays the actual state of the alarm relay. When ALARM RELAY is set to

OFF, This parameter will display Deactivated. Otherwise, this parameter will display the

state of the alarm, either ON or OFF.

CLEAR HISTORY

This parameter is used to clear the alarm history. When this parameter is pressed, a

confirmation question will appear. When the confirmation is performed, the alarm history

will be erased.

PROBES CHECKED FOR HIGH/LOW ALARM

This parameter is used to check which probes will be checked for the high and low

temperature alarms. A probe that is selected in this parameter will trigger the alarm if it is

outside the ALARM LOW ACTUAL TEMPERATURE and ALARM HIGH ACTUAL

TEMPERATURE or ALARM LOW CRITICAL TEMPERATURE and ALARM HIGH

CRITICAL TEMPERATURE. A probe that is not selected here will not be checked for

high and low temperature alarms.

LOW RELATIVE TEMPERATURE

This parameter adjusts the low temperature alarm RSP. If the temperature is under this

setting, an alarm will occur. Setting this parameter to OFF deactivates the low

temperature alarm. This parameter is adjusted in 0.1 from OFF, -40.0 to 0.0.

LOW ACTUAL TEMPERATURE

This parameter displays the low temperature set point. When AVERAGE

TEMPERATURE or the temperature of a probe is under this parameter, an alarm will

occur.

LOW DAY TEMPERATURE

This parameter displays the low set point temperature when MAIN SETPOINT is not

affected by NIGHT SET POINT. Because MAIN SETPOINT is changing depending on

hour of the day, it is important to know which temperature alarm will occur at different

periods.

LOW NIGHT TEMPERATURE

This parameter displays the low set point temperature when MAIN SETPOINT is affected

by NIGHT SET POINT. Because MAIN SETPOINT is changing depending on hour of

the day, it is important to know which temperature alarm will occur at different periods.

Page 104: T uch - agrivent.com

USER’S GUIDE

Section C-104

ALARMS (CONTINUED…)

HIGH RELATIVE TEMPERATURE

This parameter adjusts the high temperature alarm RSP. If the temperature is above this,

an alarm will occur. Setting this parameter to OFF deactivates the high temperature

alarm. This parameter is adjusted in 0.1 from 1.0 to 40.0, OFF.

HIGH ACTUAL TEMPERATURE

This parameter displays the high temperature set point. When AVERAGE

TEMPERATURE or when a used inside probe’s temperature is above this parameter, an

alarm will occur.

HIGH DAY TEMPERATURE

This parameter displays the high temperature set point when MAIN SETPOINT is not

affected by NIGHT SET POINT. Because MAIN SETPOINT is changing depending on

hour of the day, it is important to know which temperature alarm will occur at different

periods.

HIGH NIGHT TEMPERATURE

This parameter displays the high temperature set point when MAIN SETPOINT is

affected by NIGHT SET POINT. Because MAIN SETPOINT is changing depending on

hour of the day, it is important to know which temperature alarm will occur at different

periods.

CRITICAL

This parameter is used to activate or deactivate the critical high/low temperature alarm.

When this parameter is set to ON, the alarm will be activated when a used inside probe’s

temperature is higher/lower than ALARM HIGH/LOW CRITICAL TEMPERATURE.

When this parameter is set to OFF ALARM HIGH/LOW CRITICAL TEMPERATURE will

not trigger the alarm.

HIGH CRITICAL TEMPERATURE (Curve Available)

This parameter is used to set the temperature at which a critical high temperature alarm

condition will occur. If the CRITICAL option is set to ON, the alarm will be activated

when the AVERAGE TEMPERATURE is higher than this parameter. The critical high

temperature alarm does not consider the OUTSIDE TEMPERATURE or the MAIN SET

POINT Ramping Function. This parameter is adjusted in 0.1° increments from -58.0°F

to 140.0°F (-50.0°C to 60.0°C).

HIGH CRITICAL TEMPERATURE CURVE

This parameter is used to activate or deactivate the HIGH CRITICAL TEMPERATURE

Ramping Function. If this option is set to ON and the GROWTH DAY is not set to OFF,

the HIGH CRITICAL TEMPERATURE will change according to its Growth Curve

programmed in its curve.

LOW CRITICAL TEMPERATURE

This parameter is used to set the temperature at which a critical low temperature alarm

condition will occur. If the CRITICAL option is set to ON, the alarm will be activated

when the AVERAGE TEMPERATURE is lower than this parameter. The critical low

temperature alarm does not consider the MAIN SET POINT Ramping Function. This

parameter is adjusted in 0.1° increments from -58.0°F to 140.0°F (-50.0°C to 60.0°C).

Page 105: T uch - agrivent.com

USER’S GUIDE

Section C-105

ALARMS (CONTINUED…)

OUTSIDE TEMPERATURE INFLUENCE

This parameter is used to set the value that will be added to the OUTSIDE

TEMPERATURE to calculate the high alarm set point when the OUTSIDE

TEMPERATURE exceeds the MAIN SETPOINT. When the OUTSIDE

TEMPERATURE exceeds the MAIN SETPOINT, the high alarm threshold will be equal

to the OUTSIDE TEMPERATURE + ALARM HIGH RELATIVE TEMPERATURE.

REINITIALISATION STATIC PRESSURE

This parameter is used to reinitialize the high and low static pressure alarms. When a high

or low static pressure alarm situation occurs, it will remain active even if the static

pressure reading returns within the ALARM LOW STATIC PRESSURE and ALARM

HIGH STATIC PRESSURE alarm limits. The only way to reset a high or low static

pressure alarm is by pressing on this parameter. When there is no static pressure alarm,

pressing on this parameter will only reinitialize the static pressure alarm delay (see

ALARM STATIC PRESSURE DELAY).

LOW STATIC PRESSURE

This parameter is used to set the low static pressure alarm set point. When static pressure

drops below this set point, the ALARM STATIC PRESSURE DELAY will be activated. If

static pressure remains below this set point throughout the ALARM STATIC PRESSURE

DELAY, a low static pressure alarm will occur. There is an alarm satisfy time that allows

static pressure to return above this limit for 5 seconds without resetting the ALARM

STATIC PRESSURE DELAY. This parameter is adjusted in 0.001WC (1Pa) increments

from OFF, -0.500”WC to 0.500”WC (OFF, -99Pa to 99Pa).

HIGH STATIC PRESSURE

This parameter is used to set the high static pressure alarm set point. When static pressure

rises above this set point, the ALARM STATIC PRESSURE DELAY will be activated. If

static pressure remains above this set point throughout the ALARM STATIC PRESSURE

DELAY, a high static pressure alarm will occur. There is an alarm satisfy time that allows

static pressure to return below this limit for 5 seconds without resetting the ALARM

STATIC PRESSURE DELAY. This parameter is adjusted in 0.001WC (1Pa) increments

from -0.500”WC to 0.500”WC, OFF (-99Pa to 99Pa, OFF).

STATIC PRESSURE DELAY

This parameter is used to set the amount of time for which the static pressure must remain

outside the ALARM LOW STATIC PRESSURE and ALARM HIGH STATIC PRESSURE limits before activating the alarm. There is an alarm satisfy time that allows static

pressure to return below within the high/low limits for 5 seconds without resetting this

delay. This parameter is adjusted in 1-second increments from 0 to 999 seconds.

FEEDER (1-12) STOP LIMIT (Curve available)

These parameters are used to set the amount of time after which a respective feeder can

be inactive for a cycle. If the feeder is not activated for the time set here during a feeder

activation period, an alarm will occur. Setting this parameter to OFF deactivates the

respective alarm. These parameters are adjusted in 1-minute increments, from OFF 1

minute to 9999 minutes.

Page 106: T uch - agrivent.com

USER’S GUIDE

Section C-106

ALARMS (CONTINUED…)

FEEDER (1-12) MAXIMUM LIMIT

These parameters are used to set the amount of time after which the respective feeder will

activate the alarm if it is activated continuously. If the feeder is active for the time set

here, an alarm will occur. Furthermore, when this alarm occurs, respective feeder relays

will be deactivated. Setting this parameter to OFF deactivates the respective alarm. These

parameters are adjusted in 1-minute increments, from OFF 1 minute to 500 minutes.

REINITIALISATION FEEDER (1-12)

This parameter is used to reinitialize the respective feeder alarms. When a feeder alarm

situation occurs, it will remain active until this parameter is pressed. When there is no

feeder alarm, pressing on this parameter will only reinitialize the feeder alarm’s actual

counts and timers.

FEEDER (1-12) STOP LIMIT CURVE

These parameters are used to activate or deactivate the respective ALARM FEEDER (1-

12) STOP LIMIT Growth Function. If curve option is set to ON and GROWTH DAY is

not set to OFF the ALARM FEEDER (1-12) STOP LIMIT will follow its Growth Curve.

FEED AUGER (1-12) STOP LIMIT (Curve available)

These parameters are used to set the amount of time after which a respective feed auger

can be inactive for a cycle. If the feed auger is not activated for the time set here during a

feed auger activation period, an alarm will occur. Setting this parameter to OFF

deactivates the respective alarm. These parameters are adjusted in 1-minute increments,

from OFF 1 minute to 9999 minutes.

FEED AUGER (1-12) MAXIMUM LIMIT

These parameters are used to set the amount of time after which the respective feed auger

will activate the alarm if it is activated continuously. If the feed auger is active for the

time set here, an alarm will occur. Furthermore, when this alarm occurs, respective feed

auger relays will be deactivated. Setting this parameter to OFF deactivates the respective

alarm. These parameters are adjusted in 1-minute increments, from OFF 1 minute to 500

minutes.

REINITIALISATION FEED AUGER (1-12)

This parameter is used to reinitialize the respective feed auger alarms. When a feed auger

alarm situation occurs, it will remain active until this parameter is pressed. When there is

no feed auger alarm, pressing on this parameter will only reinitialize the feed auger

alarm’s actual counts and timers.

FEED AUGER (1-12) STOP LIMIT CURVE

These parameters are used to activate or deactivate the respective ALARM FEED AUGER

(1-12) STOP LIMIT Growth Function. If curve option is set to ON and GROWTH DAY

is not set to OFF the ALARM FEED AUGER (1-12) STOP LIMIT will follow its Growth

Curve.

Page 107: T uch - agrivent.com

USER’S GUIDE

Section C-107

ALARMS (CONTINUED…)

DEACTIVATE LOW FEED ALARM AT NIGHT

This parameter is used to set if light program can deactivate the feeder stop alarm. If this

parameter is set to Zone1 or Zone2, feeder stop alarm when the zone is not in a light

activation cycle. If this parameter is set to OFF, feeder stop alarm will always be

calculated.

ACTION FEED INPUT MAXIMUM ALARM

This parameter allows the user to set what act will be done on a feeder/feed augers output

when this one triggers the alarm by exceeding the FEEDER (1-12)/FEED AUGER (1-12)

MAXIMUM LIMIT. If this parameter is set to Reduce, FEEDER (1-12)/FEED AUGER

(1-12) MAXIMUM LIMIT time will be subtracted of respective feeder/feed augers count

when alarm occurs, then the output will be stopped. If this parameter is set to Stop, output

will stop when this alarm occurs. If this parameter is set to Nothing, the output will not be

influenced by the alarm.

ALARM RELAY FOR MAX FEEDER/FEED AUGER ALARM

This parameter is used to determine if the alarm relay will be activated when a maximum

feeder or feed auger alarm condition occurs. If this option is set to ON, the alarm relay

will activate on this condition. If this option is set to OFF, the alarm relay will not

activate on this condition. In both cases, the concerned output that has triggered the alarm

will deactivate and a message will be logged in the alarm history.

WATER METER (1-12) CONSUMPTION (Curve available)

These parameters are used to set the water consumption at which alarm limits of water

meter will be based. The adjusted percentage of low limit will be reduced of this value

and the adjusted percentage of the limit will be added to this value to form the high/low

limits. This parameter is influenced by its Growth Function when WATER METER (1-

12) CURVE OPTION is set to ON and GROWTH DAY is not set to OFF. These

parameters are adjusted in 1 unit (litre or gallon) increments from 1 to 9999 units (litres

or gallons).

WATER METER (1-12) CURVE OPTION

These parameters are used to activate or deactivate the water meter alarm Growth

Function. If this curve option is set to ON and the Growth Day is not set to OFF, the

ALARM WATER METER (1-12) CONSUMPTION will follow its Growth Curve.

WATER METER (1-12) LOW LIMIT

These parameters are used to adjust the minimum number of gallons or litres in

percentage. The adjusted value is a percentage that will be added to the ALARM WATER

METER (1-12) CONSUMPTION to form the minimum unit quantity (litres or gallons) the

controller may count within a time period of ALARM WATER METER LOW CHECK

RATE without activating the alarm. Adjusting this parameter to OFF deactivates the

respective low consumption alarm. This parameter is adjusted in 1% increments from

OFF, 1% to 100%.

WATER METER (1-12) CALCULATED LOW LIMIT

These parameters display the calculated low water alarm limit. If the number of units is

under this limit, the alarm will activate for the respective water meter.

Page 108: T uch - agrivent.com

USER’S GUIDE

Section C-108

ALARMS (CONTINUED…)

WATER METER (1-12) HIGH LIMIT

These parameters are used to adjust the maximum number of gallons or litres in

percentage. The adjusted value is a percentage that will be added to the ALARM WATER

METER (1-12) CONSUMPTION to form the maximum unit quantity (litres or gallons)

the controller may count within a time period of ALARM WATER METER HIGH CHECK

RATE without activating the alarm. Adjusting this parameter to OFF deactivates the

respective high consumption alarm. This parameter is adjusted in 1% increments from

OFF, 1% to 999%.

WATER METER (1-12) CALCULATED HIGH LIMIT

These parameters display the calculated high water alarm limit. If the number of units

exceeds this limit, the alarm will activate for the respective water meter.

REINITIALISATION WATER METER (1-12)

This parameter is used to reinitialize the respective water meter alarms. When there is

water alarm, press on this parameter. This reinitialisation does not affect other alarms.

WATER METER HIGH CHECK RATE

This parameter is used to adjust the time period for the respective high limit consumption

alarm. If the number of units exceeds the WATER METER (1-12) CALCULATED

HIGH LIMIT within this time period, the alarm will activate. This parameter is

adjustable from 0:00 to 24:59.

WATER METER LOW CHECK RATE

This parameter is used to adjust the time period for the respective low limit consumption

alarm. If the number of units is below the WATER METER (1-12) CALCULATED

LOW LIMIT within this time period, the alarm will activate. This parameter is adjustable

from 0:00 to 24:59.

OUTSIDE TEMPERATURE FOR WATER METER HIGH INCREASE

This parameter is used to set the OUTSIDE TEMPERATURE at which high limit of

water consumption will be increased by WATER METER HIGH INCREASE FOR

OUTSIDE TEMPERATURE. This increase will not be displayed in the calculated limit. A

fixed Differential of 1.0° is used with this logic. This parameter is adjusted in 0.1°

increments from 0.0°C to 75.0°C (0.0°F to 12.0°F).

WATER METER HIGH INCREASE FOR OUTSIDE TEMPERATURE

This parameter allows the user to set the increase that will be applied on high limit

consumption of water meters when OUTSIDE TEMPERATURE is equal or above

OUTSIDE TEMPERATURE FOR WATER METER HIGH INCREASE. This increase will

not be displayed in calculated limit. This parameter is adjusted in 1% increments from

0% to 100%.

DEACTIVATE LOW WATER METER ALARM AT NIGHT

This parameter allows the user to deactivate the low water consumption alarm when

lights of selected zone are not in an activation cycle. If this parameter is adjusted to Lgt

Z1 or Lgt Z2, the low water consumption alarm will be suspended when the selected zone

is not in an activation cycle. If this parameter is adjusted to OFF, the low water

consumption alarm will not be affected by lights programs.

Page 109: T uch - agrivent.com

USER’S GUIDE

Section C-109

ALARMS (CONTINUED…)

DEACTIVATE LOW WATER METER ALARM BEFORE DAY

This parameter allows the user to deactivate the low water consumption alarm when

GROWTH DAY is lower than the value adjusted here. If GROWTH DAY is under the

value set here, the low water consumption alarm will not be checked. If this parameter is

set to OFF, the low water consumption alarm will not be affected by GROWTH DAY.

HIGH WATER METER ALARM INCREASE AFTER NIGHT

This parameter allows the user to set the increase that will be applied on the high water

consumption limit on water meter when a night period ends. When lights begin in a

activation cycle, this increase will be applied on high consumption limit of water meter.

This change lasts for DURATION HIGH WATER METER ALARM INCREASE AFTER

NIGHT. At the end of this delay, the count and high consumption limit delay will be

reinitialized. This increase will ne be displayed in the calculated limit. This parameter is

adjusted in 1% increments from 0% to 100%.

DURATION HIGH WATER METER ALARM INCREASE AFTER NIGHT

This parameter allows the user to set the time at which the increase will be applied on the

high consumption limits of water meter when a night period ends. This parameter is

adjusted in 1-minute increments from 1 to 999 minutes.

WATER ALARM RELAY NORMAL STATE

This parameter is used to set the normal state of the water alarm relays. If this parameter

is set to NO (Normally Open) the relays that are set to the High Wat Alm (1-4) will be

open in a normal situation and close when required to activate for a high water alarm. If

this parameter is set to NC (Normally Closed) the relays that are set to the High Wat Alm

(1-4) will be closed in a normal situation and open when required to activate for a high

water alarm.

Page 110: T uch - agrivent.com

USER’S GUIDE

Section C-110

CLOCKS

ACTUAL STATUS

These parameters display the actual status of the clock outputs. Each clock output can be

ON or OFF.

NUMBER OF CYCLES

This parameter is used to set the number of cycles that are used and displayed when using

mode 1. The cycles with a number lower than the number adjusted here will disappear

and not be considered. This parameter can be adjusted from 1 to 15 cycles.

START TIME CYCLE (1-15)

These parameters are used to set the time at which the respective clock cycle will begin.

When the time of day reaches this time, the clock outputs will activate. These parameters

are adjusted in 1-minute increments from 0:00 to 23:59 (12:00A to 11:59P).

STOP TIME CYCLE (1-15)

These parameters are used to set the time at which the respective clock cycle will end.

When the time of day reaches this time, the clock output will deactivate. These

parameters are adjusted in 1-minute increments from 0:00 to 23:59 (12:00A to 11:59P).

RUN TIME CYCLE (1-15)

These parameters are used to set the time for which the respective clock cycle will run.

When the time of day reaches CLOCK (1-4) START TIME CYCLE (1-15) + CLOCK (1-

4) RUN TIME CYCLE (1-15), the clock output will deactivate. These parameters are

adjusted in 1-second increments from 0:00 to 300:59 minutes.

OPTION CYCLE (1-15)

These parameters are used to activate or deactivate the associated clock cycle. If one of

these options is set to OFF, that cycle will not be considered when determining clock

output activation. If one of these options is set to Time, that cycle will be activated when

time is between CLOCK (1-4) START TIME CYCLE (1-15) and CLOCK (1-4) STOP

TIME CYCLE (1-15). If one of these options is set to Run, that cycle will be activated

when time reaches CLOCK (1-4) START TIME CYCLE (1-15) and will remain active for

CLOCK (1-4) RUN TIME CYCLE (1-15).

OPERATING MODE

This parameter is used to choose the operating mode for the respective clock output. If

Mode 1 is chosen, the clock output will activate according to START TIME CYCLE (1-

15), STOP TIME CYCLE (1-15) or RUN TIME CYCLE (1-15) and OPTION CYCLE (1-

15). If Mode 2 is chosen, the clock output will activate according to START TIME

CYCLE (1-3), DURATION CYCLE (1-3), REPETITION CYCLE(1-3) et NUMBER OF

REPETITIONS CYCLE (1-3).

START TIME CYCLE (1-3)

These parameters are used to set the time at which the first repetition of the respective

cycle will start when Mode 2 is used. When the time of day reaches this time, the

respective cycle will activate for the first time. These parameters are adjusted in 1-minute

increments from 0:00 to 23:59 (12:00A to 11:59P).

Page 111: T uch - agrivent.com

USER’S GUIDE

Section C-111

CLOCKS (CONTINUED…)

DURATION CYCLE (1-3)

These parameters are used to set the time for which the respective clock cycle will last in

Mode 2. Each repetition of the respective cycle will have a duration equal to the value

adjusted here. These parameters are adjusted in 1-minute increments from 0:00 to 23:59

hours.

REPETITION CYCLE (1-3)

These parameters are used to set the time after which the respective clock cycle will

repeat itself in Mode 2. Each time a number of hours equal to the value adjusted here

have elapsed after CLOCK (1-4) START TIME CYCLE (1-3), the cycle repetition will

begin. All repetition must begin at 23:59 (11:59P) at the latest, or else they will be

cancelled. These parameters are adjusted in 1-minute increments from 0:00 to 23:59

hours.

NUMBER OF REPETITIONS CYCLE (1-3)

These parameters are used to set the number of times the respective cycle will repeat

itself each day. Adjusting this value to 0 deactivates the respective cycle. These

parameters are adjustable from 0 to 12.

Page 112: T uch - agrivent.com

USER’S GUIDE

Section C-112

FEEDERS

ACTUAL STATUS

These parameters display the actual status of the feeder outputs. Each feeder output can

be ON or OFF.

QUANTITY

These parameters display the count for each feeder for the current day. The amount of

feed is displayed to the nearest unit (kg or lb) from 0 to 9999 units (kg or lb).

QUANTITY YESTERDAY

These parameters display the count for each feeder for yesterday. The amount of feed is

displayed to the nearest unit (kg or lb) from 0 to 9999 units (kg or lb).

QUANTITY 24 HOURS

These parameters display the amount of units counted in the last 24 hours that the

controller was powered up. This count does not consider the current hour or the time for

which the controller was powered down. Furthermore, changing the time of day will not

affect this count. The amount of feed is displayed to the nearest unit (kg or lb) from 0 to

9999 units (kg or lb).

RUN TIME

These parameters display the amount of time for which the respective feeder has been

activated for the current day. The run time is displayed to the nearest minute from 0:00

hours to 24:00 hours.

NUMBER OF CYCLES

This parameter is used to set the number of cycles that are used and displayed when using

mode 1. The cycles with a number lower than the number adjusted here will disappear

and not be considered. This parameter can be adjusted from 1 to 15 cycles.

START TIME CYCLE (1-15)

These parameters are used to set the time at which the respective feeder cycle will begin.

When the time of day reaches this time, the feeder outputs will activate. These parameters

are adjusted in 1-minute increments from 0:00 to 23:59 (12:00A to 11:59P).

STOP TIME CYCLE (1-15)

These parameters are used to set the time at which the respective feeder cycle will end.

When the time of day reaches this time, the feeder output will deactivate. These

parameters are adjusted in 1-minute increments from 0:00 to 23:59 (12:00A to 11:59P).

RUN TIME CYCLE (1-15)

These parameters are used to set the time for which the respective feeder cycle will run.

When the time of day reaches FEEDER (1-12) START TIME CYCLE (1-15) + FEEDER

(1-12) RUN TIME CYCLE (1-15), the feeder output will deactivate. These parameters are

adjusted in 1-second increments from 0:00 to 300:59 minutes.

Page 113: T uch - agrivent.com

USER’S GUIDE

Section C-113

FEEDERS (CONTINUED…)

OPTION CYCLE (1-15)

These parameters are used to activate or deactivate the associated feeder cycle. If one of

these options is set to OFF, that cycle will not be considered when determining feeder

output activation. If one of these options is set to Time, that cycle will be activated when

time is between FEEDER (1-12) START TIME CYCLE (1-15) and FEEDER (1-12) STOP

TIME CYCLE (1-15). If one of these options is set to Run, that cycle will be activated

when time reaches FEEDER (1-12) START TIME CYCLE (1-15) and will remain active

for FEEDER (1-12) RUN TIME CYCLE (1-15).

OPERATING MODE

This parameter is used to choose the operating mode for the respective feed output. If

Mode 1 is chosen, the feed output will activate according to START TIME CYCLE (1-15),

STOP TIME CYCLE (1-15) or RUN TIME CYCLE (1-15) and OPTION CYCLE (1-15). If

Mode 2 is chosen, the feed output will activate according to START TIME CYCLE (1-3),

DURATION CYCLE (1-3), REPETITION CYCLE(1-3) et NUMBER OF REPETITIONS

CYCLE (1-3).

START TIME CYCLE (1-3)

These parameters are used to set the time at which the first repetition of the respective

cycle will start when Mode 2 is used. When the time of day reaches this time, the

respective cycle will activate for the first time. These parameters are adjusted in 1-minute

increments from 0:00 to 23:59 (12:00A to 11:59P).

DURATION CYCLE (1-3)

These parameters are used to set the time for which the respective feed cycle will last in

Mode 2. Each repetition of the respective cycle will have a duration equal to the value

adjusted here. These parameters are adjusted in 1-minute increments from 0:00 to 23:59

hours.

REPETITION CYCLE (1-3)

These parameters are used to set the time after which the respective feed cycle will repeat

itself in Mode 2. Each time a number of hours equal to the value adjusted here have

elapsed after FEED (1-4) START TIME CYCLE (1-3), the cycle repetition will begin. All

repetition must begin at 23:59 (11:59P) at the latest, or else they will be cancelled. These

parameters are adjusted in 1-minute increments from 0:00 to 23:59 hours.

NUMBER OF REPETITIONS CYCLE (1-3)

These parameters are used to set the number of times the respective cycle will repeat

itself each day. Adjusting this value to 0 deactivates the respective cycle. These

parameters are adjustable from 0 to 12.

ASSOCIATED FEED INPUT

These parameters are used to select if a feed input will be associated to the respective

feeder. If an input is associated to a feeder, its count will be the result of that input’s

activation time and the respective FEED (1-12) 1-MINUTE CALIBRATION.

Furthermore, all alarm checks on the feeder will be made according to the associated

input. When an input is associated to a feeder, that feeder can be assigned to a group to

calculate totals of that group.

Page 114: T uch - agrivent.com

USER’S GUIDE

Section C-114

FEEDERS (CONTINUED…)

ASSOCIATED PROXIMITY SWITCH

These parameters are used to select if a proximity switch will be associated to the

respective feeder. If a proximity switch input is associated to a feeder, that feeder’s

activation cycles can be ended when that input is activated.

CYCLE START NON-DETECTION TIME

These parameters are used to set the time for which proximity switch will not be checked

when a cycle begins. When a cycle starts, the proximity switch input will not be checked

for the time adjusted here. Once this delay has expired, the system will check the

proximity switch input and a cycle will end if that input has been activated for FEEDER

(1-12) STOP CYCLE FILTRE DETECTION. These parameters are adjustable from 0:00

to 99:59 minutes.

STOP CYCLE FILTRE DETECTION

These parameters are used to set the time for which proximity switch needs to be

activated to end a cycle. When a cycle starts, the proximity switch input will not be

checked for FEEDER (1-12) CYCLE START NON-DETECTION TIME. Once this delay

has expired, the system will check the proximity switch input and a cycle will end if that

input has been activated for the time adjusted here. These parameters are adjusted in 1-

second increments from 1 second to 0 à 999 seconds.

RESTARTCYCLE DETECTION FILTRE

These parameters are used to set the time for which proximity switch needs to be

deactivated to restart a cycle. When a cycle has been deactivated by its proximity switch,

it will restart when the proximity switch has not been activated for this amount of time. If

this parameter is set to Never, a cycle will not restart once it has been deactivated by its

proximity switch. These parameters are adjusted in 1-second increments from 1 second to

Never, 0 à 999 seconds.

TOTAL QUANTITY GROUP (A-B)

These parameters display the count for the total of all feeders of the respective group for

the current day.

TOTAL QUANTITY YESTERDAY GROUP (A-B)

These parameters display the count for the total of all feeders of the respective group for

yesterday.

TOTAL QUANTITY 24-HOURS GROUP (A-B)

These parameters display the amount of units counted in the last 24 hours that the

controller was powered up. This count does not consider the current hour or the time for

which the controller was powered down. Furthermore, changing the time of day will not

affect this count.

BATCH TOTAL QUANTITY GROUP (A-B)

These parameters display the count for the total of all feeders of the respective group

since the beginning of the breeding. The amount of feed read is displayed to the nearest

unit from 0 to 999999 units (kg or lb).

Page 115: T uch - agrivent.com

USER’S GUIDE

Section C-115

FEED AUGERS

ACTUAL STATUS

These parameters display the actual status of the feed auger outputs. Each feed auger

output can be ON or OFF.

QUANTITY

These parameters display the count for each feed auger for the current day. The amount

of feed is displayed to the nearest unit (kg or lb) from 0 to 9999 units (kg or lb).

QUANTITY YESTERDAY

These parameters display the count for each feed auger for yesterday. The amount of feed

is displayed to the nearest unit (kg or lb) from 0 to 9999 units (kg or lb).

QUANTITY 24 HOURS

These parameters display the amount of units counted in the last 24 hours that the

controller was powered up. This count does not consider the current hour or the time for

which the controller was powered down. Furthermore, changing the time of day will not

affect this count. The amount of feed is displayed to the nearest unit (kg or lb) from 0 to

9999 units (kg or lb).

RUN TIME

These parameters display the amount of time for which the respective feed auger has

been activated for the current day. The run time is displayed to the nearest minute from

0:00 hours to 24:00 hours.

NUMBER OF CYCLES

This parameter is used to set the number of cycles that are used and displayed when using

mode 1. The cycles with a number lower than the number adjusted here will disappear

and not be considered. This parameter can be adjusted from 1 to 15 cycles.

START TIME CYCLE (1-15)

These parameters are used to set the time at which the respective feed auger cycle will

begin. When the time of day reaches this time, the feed auger outputs will activate. These

parameters are adjusted in 1-minute increments from 0:00 to 23:59 (12:00A to 11:59P).

STOP TIME CYCLE (1-15)

These parameters are used to set the time at which the respective feed auger cycle will

end. When the time of day reaches this time, the feed auger output will deactivate. These

parameters are adjusted in 1-minute increments from 0:00 to 23:59 (12:00A to 11:59P).

RUN TIME CYCLE (1-15)

These parameters are used to set the time for which the respective feed auger cycle will

run. When the time of day reaches FEED AUGER (1-12) START TIME CYCLE (1-15) +

FEED AUGER (1-12) RUN TIME CYCLE (1-15), the feed auger output will deactivate.

These parameters are adjusted in 1-second increments from 0:00 to 300:59 minutes.

Page 116: T uch - agrivent.com

USER’S GUIDE

Section C-116

FEED AUGERS (CONTINUED…)

STOP QUANTITY CYCLE (1-15)

These parameters are used to adjust the amount of feed that must be distributed for the

feed auger cycle to stop. When the bins using the same feed inputs as the feed auger have

distributed the quantity adjusted for the respective cycle since the beginning of the cycle,

the feed auger output will deactivate. Each feed auger using a feed input can be

associated to a group. This values can use the Growth Function if FEED AUGER (1-2)

CURVE OPTION WEIGHT CYCLE (1-15) is set to ON and the GROWTH DAY is not set

to OFF. These parameters are adjusted in 1kg (1lb) increments from 100kg (100lb) to

999kg (999lb). Only feed augers 1 and 2 can have the Weight option.

CURVE OPTION WEIGHT CYCLE (1-15)

These parameters are used to activate or deactivate feed auger stop quantity the Growth

Function for the corresponding cycle. If this curve option is set to ON and the Growth

Day is not set to OFF, the FEED AUGER (1-2) STOP QUANTITY CYCLE (1-15) will

follow its Growth Curve.

OPTION CYCLE (1-15)

These parameters are used to activate or deactivate the associated feed auger cycle. If one

of these options is set to OFF, that cycle will not be considered when determining feed

auger output activation. If one of these options is set to Time, that cycle will be activated

when time is between FEED AUGER (1-12) START TIME CYCLE (1-15) and FEED

AUGER (1-12) STOP TIME CYCLE (1-15). If one of these options is set to Run, that

cycle will be activated when time reaches FEED AUGER (1-12) START TIME CYCLE

(1-15) and will remain active for FEED AUGER (1-12) RUN TIME CYCLE (1-15). If one

of these options is set to Weight, that cycle will be activated when time reaches FEED

AUGER (1-2) START TIME CYCLE (1-15) and will remain active until the bin(s) using

the same feed input as the feed auger has distributed the mount of feed adjusted in the

associated FEED AUGER (1-2) STOP QUANTITY CYCLE (1-15). Only feed augers 1

and 2 can have the Weight option.

OPERATING MODE

This parameter is used to choose the operating mode for the respective feed auger output.

If Mode 1 is chosen, the feed auger output will activate according to START TIME

CYCLE (1-15), STOP TIME CYCLE (1-15) or RUN TIME CYCLE (1-15) and OPTION

CYCLE (1-15). If Mode 2 is chosen, the feed auger output will activate according to

START TIME CYCLE (1-3), DURATION CYCLE (1-3), REPETITION CYCLE(1-3) et

NUMBER OF REPETITIONS CYCLE (1-3).

START TIME CYCLE (1-3)

These parameters are used to set the time at which the first repetition of the respective

cycle will start when Mode 2 is used. When the time of day reaches this time, the

respective cycle will activate for the first time. These parameters are adjusted in 1-minute

increments from 0:00 to 23:59 (12:00A to 11:59P).

Page 117: T uch - agrivent.com

USER’S GUIDE

Section C-117

FEED AUGERS (CONTINUED…)

DURATION CYCLE (1-3)

These parameters are used to set the time for which the respective feed auger cycle will

last in Mode 2. Each repetition of the respective cycle will have a duration equal to the

value adjusted here. These parameters are adjusted in 1-minute increments from 0:00 to

23:59 hours.

REPETITION CYCLE (1-3)

These parameters are used to set the time after which the respective feed auger cycle will

repeat itself in Mode 2. Each time a number of hours equal to the value adjusted here

have elapsed after FEED AUGER (1-4) START TIME CYCLE (1-3), the cycle repetition

will begin. All repetition must begin at 23:59 (11:59P) at the latest, or else they will be

cancelled. These parameters are adjusted in 1-minute increments from 0:00 to 23:59

hours.

NUMBER OF REPETITIONS CYCLE (1-3)

These parameters are used to set the number of times the respective cycle will repeat

itself each day. Adjusting this value to 0 deactivates the respective cycle. These

parameters are adjustable from 0 to 12.

ASSOCIATED FEED INPUT

These parameters are used to select if a feed input will be associated to the respective

feed auger. If an input is associated to a feed auger, its count will be the result of that

input’s activation time and the respective FEED (1-12) 1-MINUTE CALIBRATION.

Furthermore, all alarm checks on the feed auger will be made according to the associated

input. When an input is associated to a feed auger, that feed auger can be assigned to a

group to calculate totals of that group.

ASSOCIATED PROXIMITY SWITCH

These parameters are used to select if a proximity switch will be associated to the

respective feed auger. If a proximity switch input is associated to a feed auger, that feed

auger’s activation cycles can be ended when that input is activated.

CYCLE START NON-DETECTION TIME

These parameters are used to set the time for which proximity switch will not be checked

when a cycle begins. When a cycle starts, the proximity switch input will not be checked

for the time adjusted here. Once this delay has expired, the system will check the

proximity switch input and a cycle will end if that input has been activated for FEED

AUGER (1-12) STOP CYCLE FILTRE DETECTION. These parameters are adjustable

from 0:00 to 99:59 minutes.

STOP CYCLE DETECTION FILTRE

These parameters are used to set the time for which proximity switch needs to be

activated to end a cycle. When a cycle starts, the proximity switch input will not be

checked for FEED AUGER (1-12) CYCLE START NON-DETECTION TIME. Once this

delay has expired, the system will check the proximity switch input and a cycle will end

if that input has been activated for the time adjusted here. These parameters are adjusted

in 1-second increments from 1 second to 0 à 999 seconds.

Page 118: T uch - agrivent.com

USER’S GUIDE

Section C-118

FEED AUGERS (CONTINUED…)

RESTARTCYCLE DETECTION FILTRE

These parameters are used to set the time for which proximity switch needs to be

deactivated to restart a cycle. When a cycle has been deactivated by its proximity switch,

it will restart when the proximity switch has not been activated for this amount of time. If

this parameter is set to Never, a cycle will not restart once it has been deactivated by its

proximity switch. These parameters are adjusted in 1-second increments from 1 second to

Never, 0 à 999 seconds.

TOTAL QUANTITY GROUP (A-B)

These parameters display the count for the total of all feed augers of the respective group

for the current day. The amount of feed read is displayed to the nearest unit (kg or lb)

from 0 to 59994 units (kg or lb) for the total.

TOTAL QUANTITY YESTERDAY GROUP (A-B)

These parameters display the count for the total of all feed augers of the respective group

for yesterday.

TOTAL QUANTITY 24-HOURS GROUP (A-B)

These parameters display the amount of units counted in the last 24 hours that the

controller was powered up. This count does not consider the current hour or the time for

which the controller was powered down. Furthermore, changing the time of day will not

affect this count.

BATCH TOTAL QUANTITY GROUP (A-B)

These parameters display the count for the total of all feed augers of the respective group

since the beginning of the breeding. The amount of feed read is displayed to the nearest

unit from 0 to 999999 units (kg or lb).

Page 119: T uch - agrivent.com

USER’S GUIDE

Section C-119

LIGHTS

ACTUAL INTENSITY

These parameters display the current intensity of the light outputs. Each light output can

display OFF or an intensity from 1% to 100%.

SYSTEM

This parameter is used to activate or deactivate light program of the zone. To avoid

activating lights when settings are adjusted, it is recommended to adjust this parameter to

OFF. When this parameter is set to OFF, lights zone will be deactivated and timer will be

reset. As soon as this parameter is set to ON, controller will re-evaluate all light settings

of the zone.

ACTUAL PERIOD

This parameter displays the current light period. The value displayed may be OFF, 1 to

10.

NUMBER OF PERIODS

This parameter is used to adjust the amount of periods used by the zone. Deactivated

periods will not be visible thorough the configuration. A zone might use up to 10

periods.

NUMBER OF CYCLES

This parameter is used to adjust the amount of cycles used by the zone. Deactivated

cycles will not be visible thorough the configuration. A zone might use up to 5 cycles.

SYSTEM OFF INTENSITY

This parameter is used to set the intensity lights will use when LIGHT (1-2) SYSTEM is

set to OFF. This parameter is adjusted in 1% increments from 0% to 100%.

INTENSITY BETWEEN CYCLES

This parameter is used to set the intensity lights will use when they are activated but no

cycle is active. Lights will modulate from LIGHT (1-2) PERIOD (1-10) MAXIMUM

INTENSITY to this intensity at the end cycle. This parameter is adjusted in 1%

increments from OFF, 1% to 100%.

START MODULATION TIME

This parameter is used to set the time for which lights will take to go from LIGHT (1-2)

PERIOD (1-10) CYCLE (1-5) MINIMUM INTENSITY to LIGHT (1-2) PERIOD (1-10)

MAXIMUM INTENSITY. If this parameter is set to 0, lights will go directly from LIGHT

(1-2) INTENSITY BETWEEN CYCLES to intensity LIGHT (1-2) PERIOD (1-10)

MAXIMUM INTENSITY, at the beginning of a cycle. This parameter is adjusted in 1-

minute increments from 0 minute to 50 minutes.

Page 120: T uch - agrivent.com

USER’S GUIDE

Section C-120

LIGHTS (CONTINUED…)

END MODULATION TIME

This parameter is used to set the time for which lights will take to go from LIGHT (1-2)

PERIOD (1-10) MAXIMUM INTENSITY to LIGHT (1-2) PERIOD (1-10) CYCLE (1-5)

MINIMUM INTENSITY at the end of a cycle. If this parameter is set to 0, lights will go

directly from LIGHT (1-2) MAXIMUM INTENSITY to intensity LIGHT (1-2) PERIOD

(1-10) INTENSITY BETWEEN CYCLES, at the end of a cycle. This parameter is adjusted

in 1-minute increments from 0 minute to 50 minutes.

NUMBER OF STIMULATIONS

This parameter is used to set the amount of stimulations that will be performed in each

cycle of each period. Stimulations will be distributed evenly throughout the cycle. A

stimulation is performed by increasing light intensity for a short period of time within the

cycle. This parameter is adjusted in 1-stimulation increments from OFF, 1 stimulation to

10 stimulations.

STIMULATION INTENSITY

This parameter is used to set the intensity lights of will take during a stimulation. This

parameter is adjusted in 1% increments from 0% to 100.

STIMULATION DURATION

This parameter is used to set the amount of time for which each stimulation will last and

determines if stimulation modulates or goes directly to from LIGHT (1-2) PERIOD (1-

10) MAXIMUM INTENSITY to LIGHT (1-2) STIMULATION INTENSITY. When a

stimulation begins, lights will modulate from LIGHT (1-2) PERIOD (1-10) MAXIMUM

INTENSITY to LIGHT (1-2) STIMULATION INTENSITY throughout a 20-second period,

which is included in the duration. Lights will remain at LIGHT (1-2) STIMULATION

INTENSITY for the rest of the duration and will then modulate to LIGHT (1-2) PERIOD

(1-10) MAXIMUM INTENSITY throughout the 20-seconds period, which is not included

in the duration. If this setting is adjusted to any value less than the 20 seconds, no

modulation will be performed. This parameter is adjusted in 1-second increments from 10

seconds to 900 seconds.

PERIOD (1-10) OPTION 24-HOUR

These parameters are used to set this period in 24-hour cycle. When one of these

parameters is set to ON results a 24-hour cycle that will not perform any transition start,

but will perform its ending transition when its ending day is reached to finish at 23:59 of

this day. Note that all other cycles will be overcome by a 24-hour cycle. These

parameters can be adjusted to ON or OFF.

PERIOD (1-10) MAXIMUM INTENSITY

These parameters are used to adjust the maximum intensity for the respective period.

When hour of the day reaches LIGHT (1-2) PERIOD (1-10) CYCLE (1-5) ON TIME

associated to LIGHT (1-2) ACTUAL PERIOD, lights will activate to LIGHT (1-2)

PERIOD (1-10) CYCLE (1-5) MINIMUM INTENSITY and will modulate to this value for

an amount of time equal to LIGHT (1-2) START MODULATION TIME. These

parameters are adjusted in 1 % increment from 0% to 100%

Page 121: T uch - agrivent.com

USER’S GUIDE

Section C-121

LIGHTS (CONTINUED…)

PERIOD (1-10) END DAY

These parameters are used to adjust the end day for the respective period. This day is the

last day at which the controller will consider to be in its related period. The last activated

period does not have end day and will be continuously used when the last day is reached.

These parameters are adjusted in 1-day increment from day 0 to day 365.

PERIOD (1-10) CYCLE (1-5) MINIMUM INTENSITY

These parameters are used to adjust the minimum cycle intensity. When hour of the day

reaches LIGHT (1-2) PERIOD (1-10) CYCLE (1-5) ON TIME related to LIGHT (1-2)

ACTUAL PERIOD, lights will activate to this intensity and will modulate to LIGHT (1-

2) PERIOD (1-10) MAXIMUM INTENSITY for an amount of time equal to LIGHT (1-2)

START MODULATION TIME. These parameters are adjusted in 1% increments from 0%

to 100%.

PERIOD (1-10) CYCLE (1-5) ON TIME

These parameters are used to set the time at which the respective cycle will start. When

hour of the day reaches hour of the start related to the respective LIGHT (1-2) ACTUAL

PERIOD cycle, this cycle begins. These parameters are adjusted in 1-minute increments

from 12:00A to 11:59P (0:00 to 23:59).

PERIOD (1-10) CYCLE (1-5) OFF TIME

These parameters are used to set the time at which the respective cycle will start. When

hour of the day reaches hour of the stop related to the respective LIGHT (1-2) ACTUAL

PERIOD cycle, this cycle ends. These parameters are adjusted in 1-minute increments

from 12:00A to 11:59P (0:00 to 23:59).

COPY ZONE 1 > ZONE 2

This parameter is used to copy all settings made in zone 1 to zone 2. To copy these

settings, press on this parameter. At this moment, the message will change for Settings

copied for few seconds and settings of every parameters of zone 2 will be changed for

zone 1 values.

Page 122: T uch - agrivent.com

USER’S GUIDE

Section C-122

Logic diagrams and examples

Logic Diagram 1: Light cycle operation

CYCLE 1 START = 12:30A CYCLE 2 START = 3:15A

CYCLE 1 STOP = 2:45A CYCLE 2 STOP = 5:30A

CYCLE 1 MIN = 30% CYCLE 2 MIN = 35%

MAXIMUM INTENSITY = 55%

START/END MODULATION TIME = 45 minutes

INTENSITY BETWEEN CYCLES = 20%

If two or more light cycles overlap, the active light cycle will finish before the new one activates. This situation may be caused by unusual programming or by a period change.

Logic Diagram 2: Programmed overlapping light cycle operation

CYCLE 1 START = 6:00A CYCLE 2 START = 11:00A

CYCLE 1 STOP = 12:00P CYCLE 2 STOP = 5:00P

Real Cycle

Programmed Cycle

12:00A 2:00A 4:00A 6:00A 8:00A 10:00A 12:00P 2:00P 4:00P

6:00P

10:00P

8:00P

Maximum Intensity

Intensity Between

Cycles

Modulation Modulation Modulation Modulation Intensity Between

Cycles

Intensity Between

Cycles

Maximum Intensity

12:00A 12:30A 1:00A 1:30A

2:00A 2:30A

3:00A 3:30A

4:00A

4:30A

5:30A

5:00A

10

20

30

40

50

60

0

Page 123: T uch - agrivent.com

USER’S GUIDE

Section C-123

Real Cycle

Programmed Cycle

12:00P 2:00P 4:00P 6:00P 8:00P 10:00P 12:00A 2:00A 4:00A

6:00A

10:00A

8:00A

Period changes

during the cycle

Stimulation

Intensity

Cycle

Start

Stimulation

Duration

60 sec

90%

Stimulation 1

Cycle

Stop

Maximum

Intensity

45%

25%

90%

Stimulation 2

90%

Stimulation 3

Stimulation

Duration

60 sec

Stimulation

Duration

60 sec

Minimum

Intensity

Logic Diagram 3: Period change overlapping light cycle operation

PERIOD 1 CYCLE 1 START = 6:00P

PERIOD 1 CYCLE 1 STOP = 4:00A

PERIOD 2 CYCLE 1 START = 1:00A

PERIOD 2 CYCLE 1 START = 4:30A

START/END MODULATION TIME = 45 min

Logic Diagram 4: Light stimulation with duration greater than 20 seconds

MAXIMUM INTENSITY = 45% MINIMUM INTENSITY = 25%

STIMULATION INTENSITY = 90% STIMULATION DURATION = 60 sec

NUMBER OF STIMULATIONS = 3

Page 124: T uch - agrivent.com

USER’S GUIDE

Section C-124

Stimulation

Duration

15 sec

Stimulation

Duration

15 sec

Stimulation

Duration

15 sec

Stimulation

Intensity

Cycle

Start

90%

Stimulation 1

Cycle Stop

Maximum

Intensity

45%

25%

90%

Stimulation 2

90%

Stimulation 3

Minimum

Intensity

Stimulation

Duration

20 sec

Stimulation

Duration

20 sec

Stimulation

Duration

20 sec

Stimulation

Intensity

Cycle

Start

90

%

Stimulation 1

Cycle

Stop

Maximum

Intensity

45%

25%

90

%

Stimulation 2

90

%

Stimulation 3

Minimum

Intensity

Logic Diagram 5: Light stimulation with duration of 20 seconds

MAXIMUM INTENSITY = 45% MINIMUM INTENSITY = 25%

STIMULATION INTENSITY = 90% STIMULATION DURATION = 20 sec

NUMBER OF STIMULATIONS = 3

Logic Diagram 6: Light stimulation with duration lesser than 20 seconds

MAXIMUM INTENSITY = 45% MINIMUM INTENSITY = 25%

STIMULATION INTENSITY = 90% STIMULATION DURATION = 15 sec

NUMBER OF STIMULATIONS = 3

Page 125: T uch - agrivent.com

USER’S GUIDE

Section C-125

INFLATABLE INLETS

ACTUAL STATUS

These parameters display the actual status of the feeder auger. The feeder auger can be

ON or OFF.

OPENING TEMPERATURE

This parameter is used to set temperature at which the inflatable inlet will activate (relay

deactivated). When AVERAGE TEMPERATURE of the probes selected in INFLATABLE INLET (1-16) PROBES is equal or above to this value, the respective

inflatable inlet will open. These parameters are adjustable in 0.1° increments from MAIN

SETPOINT – 10.0° to MAIN SETPOINT + 50.0°.

CLOSING TEMPERATURE

This parameter is used to set temperature at which the inflatable inlet will deactivate

(relay activated). When AVERAGE TEMPERATURE of the probes selected in INFLATABLE INLET (1-16) PROBES is equal or above to this value, the respective

inflatable inlet will open. These parameters are adjusted in 0.1° increments from

INFLATABLE INLET (1-16) OPENING TEMPERATURE - 20.0° to INFLATABLE

INLET (1-16) OPENING TEMPERATURE + 0.5°.

PROBES

This is used to select the inside temperature probes that will be used by the inflatable

inlet. The average of the selected probes will dictate opening and closing. If there are no

probes selected, the temperature used will be equal to the MAIN SETPOINT.

DEFLATE IN WINTER

This parameter is used to activate or deactivate the possibility of deflating inlets in

winter. When this parameter is set to Yes, inflatable inlets will deflate even if OUTSIDE

TEMPERATURE FOR NATURAL is not reached according to the following parameters.

This parameter can be set to Yes or No.

DEFLATE SETPOINT

This parameter is used to set the set point temperature at which selected inflatable inlets

will deflate during winter. When AVERAGE TEMPERATURE reaches this value,

inflatable inlets selected at parameter AFFECTED INFLATABLE INLETS will deflate

and ventilation stages will be deactivated for a period equal to DELAY STOP

VENTILATION. A fixed Differential of 0.3° is used with this logic. This parameter is

adjusted in 0.1° increments from -50.0°C to 50.0°C (-58.0°F to 140.0°F).

DELAY STOP VENTILATION

This parameter is used to adjust the period duration at which ventilation stage will be

deactivated when one or more inflatable inlets are deactivated during winter. When

inflatable inlet is deflated during winter, ventilation stages are deactivated for a period

equal to this parameter. This parameter is adjusted in 1-second increments from OFF, 1

second to 300 seconds.

Page 126: T uch - agrivent.com

USER’S GUIDE

Section C-126

INFLATABLE INLETS (CONTINUED….)

AFFECTED INFLATABLE INLETS

This parameter is used to select inflatable inlets affected by deflate logic during winter. If

DEFLATE IN WINTER is set to Yes, when AVERAGE TEMPERATURE reaches

DEFLATE SETPOINT, selected inflatable inlets by this parameter will deflate. Only

inflatable inlets used by the configuration can be selected.

CLOSE IN TUNNEL

This parameter allows the user to set if the inflatable inlets will close in tunnel mode.

When this parameter is set to Yes, the inflatable inlets will completely close when

controller begins tunnel mode. This parameter will not be available if the tunnel mode is

not used.

Page 127: T uch - agrivent.com

USER’S GUIDE

Section C-127

MINIMUM VENTILATION

ON TIME (Curve available)

These parameters are used to adjust the on time of the minimum ventilation timer used by

ventilation stages when not activated on temperature demand. The minimum ventilation

cycle is used to reduce humidity and insure adequate airflow is provided for the room.

These parameters can be adjusted from 0:00 minutes to 99:59 minutes.

OFF TIME (Curve available)

These parameters are used to adjust the off time of the minimum ventilation timer used

by ventilation stages when not activated on temperature demand. The minimum

ventilation cycle is used to reduce humidity and insure adequate airflow is provided for

the room. These parameters can be adjusted from 0:00 minutes to 99:59 minutes.

CURVE

These parameters are used to activate or deactivate the growth curve of the respective

ventilation timer. If this option is set to ON and the GROWTH DAY is not set to OFF,

values of MINIMUM VENTILATION TIMER (1-4) ON/OFF TIME will follow their

Growth Curve will not be adjustable anymore. Is this value is set to OFF, timers will not

be affected by the GROWTH DAY.

Page 128: T uch - agrivent.com

USER’S GUIDE

Section C-128

MANUAL OVERRIDE

VAR OUT(1-4) (Type)

These parameters are used to manually control the respective VAR2 output. When one of

these parameters is set to AUTO, the corresponding output will take the speed calculated

by the configuration according to user settings. When one of these parameters is set to

OFF, the corresponding output will be deactivated. When one of these parameters is set

to a value from 0%-100%, the corresponding output will take the adjusted speed. These

parameters are adjusted in 1% increments from AUTO, OFF, 12% to 100% for

ventilation output or 0% to 100% for light output.

RELAY (1-40) (Type)

These parameters are used to manually override the calculated activation demand to

activate the respective relay output at the value adjusted here. When the value is AUTO,

the associated relay output will be activated according to the configuration’s parameters

and the temperature read. When the value is OFF, the respective relay output will be

deactivated. When the value is ON, the respective relay output will be activated.

SL## RELAY (1-20) (Type)

These parameters are used to manually override the calculated activation demand to

activate the respective SL## relay output at the value adjusted here. When the value is

AUTO, the associated SL## relay output will be activated according to the

configuration’s parameters and the temperature read. When the value is OFF, the

respective SL## relay output will be deactivated. When the value is ON, the respective

SL## relay output will be activated.

V4 ID (1-2) OUT(1-4) (Type)

These parameters are used to manually control the respective V4 module output. When

one of these parameters is set to AUTO, the corresponding output will take the speed

calculated by the configuration according to user settings. When one of these parameters

is set to OFF, the corresponding output will be deactivated. When one of these

parameters is set to a value from 0%-100%, the corresponding output will take the

adjusted speed. These parameters are adjusted in 1% increments from AUTO, OFF, 12%

to 100% for ventilation output or 0% to 100% for light output.

0-10V OUT(1-2) (Type)

These parameters are used to manually control the respective 0-10 Volt output. When one

of these parameters is set to AUTO, the corresponding output will take the speed

calculated by the configuration according to user settings. When one of these parameters

is set to OFF, the corresponding output will be deactivated. When one of these

parameters is set to a value from 0%-100%, the corresponding output will take the

adjusted speed. These parameters are adjusted in 1% increments from AUTO, 0% to

100%.

Page 129: T uch - agrivent.com

USER’S GUIDE

Section C-129

MANUAL OVERRIDE (CONTINUED...)

MS-10 OUT(1-2) (Type)

These parameters are used to manually control the respective MS-10 output. When one of

these parameters is set to AUTO, the corresponding output will take the speed calculated

by the configuration according to user settings. When one of these parameters is set to

OFF, the corresponding output will be deactivated. When one of these parameters is set

to a value from 0%-100%, the corresponding output will take the adjusted speed. These

parameters are adjusted in 1% increments from AUTO, 0% to 100%.

Page 130: T uch - agrivent.com

USER’S GUIDE

Section C-130

PROBE CALIBRATION

TEMPERATURE (1-16)

These parameters display the respective probe reading with its corresponding calibration.

These temperatures are displayed to the nearest 0.1 from -50.0°C to 60.0°C (-58.0°F to

140.0°F).

TEMPERATURE (1-16) ADJUSTMENT

These parameters are used to adjust the respective probe reading. These values are

adjusted in 0.1 increments from -20.0 to 20.0.

WATER METER (1-12)

These parameters display the actual water amount with its calibration. The amount of

water is displayed to the nearest unit from 0 to 30000 units (litres or gallons).

WATER METER (1-12) ADJUSTMENT

These parameters are used to adjust the water meter by adding or reducing percentage.

These parameters are adjusted in 1% increments from -100% to 100%.

WATER METER (1-12) 1-PULSE CALIBRATION

These parameters are used to set the number of units (litres or gallons) counted each time

a pulse is read at the water counter input. This number may be set to any value from 1

unit (litre or gallon) from 0.01 to 99.99 units (litres or gallons).

OUTSIDE TEMPERATURE

This parameter displays the outside probe reading with its corresponding calibration. This

temperature is displayed to the nearest 0.1 from -50.0°C to 60.0°C (-58.0°F to 140.0°F).

OUTSIDE TEMPERATURE ADJUSTMENT

This parameter is used to adjust the outside probe reading. This value is adjusted in 0.1

increments from -20.0 to 20.0.

HUMIDITY

This parameter displays the actual humidity with its calibration. The humidity is

displayed to the nearest 1RH% from 0RH% to 100RH%. The control may also display

ERR if the humidity probe has not responded for five minutes.

HUMIDITY ADJUSTMENT

This parameter is used to adjust the humidity reading. This value is adjusted in 1RH%

increments from -20RH% to 20RH%.

STATIC PRESSURE

This parameter displays the actual static pressure probe with its calibration. This

parameter is displayed to the nearest 0.001WC (1Pa) from -0.500”WC to 0.500”WC

(-99Pa to 99Pa).

STATIC PRESSURE ADJUSTMENT

This parameter is used to adjust the static pressure probe reading. This parameter is

adjusted in 0.001WC (1Pa) increments from -0.500”WC to 0.500”WC (-99Pa to 99Pa).

Page 131: T uch - agrivent.com

USER’S GUIDE

Section C-131

PROBE CALIBRATION (CONTINUED…)

FEED (1-12) 1-MINUTE CALIBRATION

These parameters are used to calibrate the feed input when OPTION FEED TYPE

GROUP (A-B) is set to No. Each minute of activation read by the feed input will add the

amount of units (kg or lb) adjusted here to the associated feeder or feed auger count. The

unit (kg or lb)/minute relation is adjusted in 0.1 unit (kg or lb) increments from 0.1 to

499.99 units (kg or lb).

FEED (1-12) 1-MINUTE CALIBRATION TYPE (1-5)

These parameters are used to calibrate the feed input for each type when OPTION FEED

TYPE GROUP (A-B) is set to Yes. Each minute of activation read by the feed input will

add the amount of units (kg or lb) adjusted for parameter corresponding to the type

selected in FEED TYPE GROUP (A-B) to the associated feeder or feed auger count. The

unit (kg or lb)/minute relation is adjusted in 0.1 unit (kg or lb) increments from 0.1 to

499.99 units (kg or lb).

Page 132: T uch - agrivent.com

USER’S GUIDE

Section C-132

BACKUP PROBES

BACKUP FOR PROBE (1-16)

These parameters are used to select the probe that will be used as a backup when the

associated inside temperature probe reading is not valid. The backup probes will be used

only if less than three sensors are used (or left) in the temperature calculation. If three or

more sensors are used (or left) in the temperature calculation, the non-valid probe will

simply be eliminated from the calculation. If a temperature calculation originally has

more than two probes, but, due to non-valid readings, probes are eliminated and there are

two or less left, the control will use backup probes.

A probe will be eliminated or replaced from a temperature calculation if:

The probe is an open-circuit or a short-circuit.

The probe reading is not within an acceptable temperature range (-4.0°F to

131.0°F) or (-20.0°C to 55.0°C).

The probe is used to calculate a temperature that is 20.0° above or below the

probe’s reading. This particular situation does not trigger the alarm.

Page 133: T uch - agrivent.com

USER’S GUIDE

Section C-133

TEST MODE

OPTION

This parameter is used to activate or deactivate the test mode. When this parameter is set

to ON, all inside probe readings will be replaced by the TEST MODE TEMPERATURE.

This parameter will reset itself to OFF if TEST MODE TEMPERATURE is not changed

throughout a 10-minute delay.

TEMPERATURE

This parameter is used to adjust the test mode temperature; all temperature sensors will

be overridden by this parameter if TEST MODE OPTION is set to ON. This parameter is

adjusted in 0.1 increments from -3.9°F to 139.9°F (-19.9C to 54.9C).

Page 134: T uch - agrivent.com

USER’S GUIDE

Section C-134

SYSTEM CONFIGURATION

TYPE OF BREEDING

This parameter is used to select the type of breeding that will be managed by the

controller. The type of breeding will determine which options will appear throughout the

configuration. The type of breeding can be Finisher Pig, Nursery Piglet, Broiler Chicken,

Layer Chicken, Turkey, Turkey Poult, Cow or Other.

CONFIGURATION VERSION

This parameter displays the configuration version currently used.

PROCESSOR VERSION

This parameter displays the processor version currently used.

UNIT ID

This parameter is used to set the identification number of the controller when used with

remote access software. When RF CHANNEL is not set to OFF, this parameter will

disappear. The unit identification number may be adjusted to any number from 1 to 250.

RF CHANNEL

This parameter is used to select one of the 16 frequencies of the WiFarm network or

deactivates wireless communication mode. If this parameter is set to OFF, other wireless

communication parameters will disappear. This parameter can be adjusted to OFF, 1 to

16.

RF NETWORK

This parameter is used to identify a WiFarm network. A WiFarm network is formed

when the RF NETWORK is set to the same value as the of the RF communication card of

the controller designated as the network master (ex. WebGate in most installations).

Other controllers can join the existing network by adjusting RF NETWORK to the RF

ADDRESS of that same network. When RF CHANNEL is set to OFF, this parameter will

disappear. This parameter can be adjusted to any value from 00000 to 39999.

RF ADDRESS

This parameter displays the number (address) associated to the RF card inserted in the

controller. A unique number is given to each RF card of the WiFarm network. The RF

ADDRESS also appears on the sticker present on the RF card. When RF CHANNEL is

set to OFF, this parameter will disappear. The address can be any value from 0 to 32767.

AVERAGE PROBES

This parameter allows the user to select the temperature probes for the AVERAGE

TEMPERATURE.

ACTIVE PROBES

This parameter is used to adjust the number of inside probes that will be used by the

controller. Probes that are not selected here will not appear in inside probe selection

parameters. This parameter is adjusted in 1-probe increments from 1 to 16 probes.

WATER METER UNIT

This parameter is used to select the water unit that will be used by the controller. The

water meter unit can be either Litres or Gallons.

Page 135: T uch - agrivent.com

USER’S GUIDE

Section C-135

SYSTEM CONFIGURATION (CONTINUED…)

REINITIALISE WATER METER

This parameter is used to reinitialise all water meter actual values. When this parameter is

pressed, all water meter actual values will be reinitialised.

FEEDING COUNTER UNIT

This parameter is used to select the weight unit that will be used by the feed counters and

bin scales. The feeding counter unit can be either kg or lb.

SCALE WEIGHT UNIT

This parameter is used to select the weight unit that will be used by the scales. The

weight unit can be either gram or pound.

Note on the weight-measuring unit:

The weight-measuring unit may change according to user preferences and the type of

poultry weighed by the scale. The user may select the metric measuring unit (g or kg) or

the imperial measuring unit (lb). The maximum value depends on the type of poultry.

Type of

poultry

Metric Measuring Unit

(1g or 0.01kg)

Imperial Measuring Unit

(0.001lb or 0.01lb)

Chicken

1 unit = 1g 1 unit = 0.001lb

Display format Weight: 0000g

Standard Deviation: 0000.0g

Display format Weight: 0.000lb

Standard Deviation:

0.0000lb

Turkey

1 unit = 0.01kg 1 unit = 0.001lb

Display format Weight: 00.00kg

Standard Deviation:

00.000kg

Display format Weight: 00.00lb

Standard Deviation:

00.000lb

HUMIDITY PROBE ACTIVE

This parameter is used to enable or disable humidity. If humidity is disabled, all

humidity-related readings and logics will be removed.

OUTSIDE PROBE ACTIVE

This parameter is used to activate or deactivate the Outside Temperature probe along

with all its associated logics.

STATIC PRESSURE PROBE ACTIVE

This parameter is used to activate or deactivate the static pressure probe along with all its

associated logics.

NUMBER OF BIN SCALES

This parameter is used to set the amount of bin scales that will be used by the controller.

A deactivated bin scale will not be shown trough the configuration. The controller can

use up to 2 bin scales.

Page 136: T uch - agrivent.com

USER’S GUIDE

Section C-136

SYSTEM CONFIGURATION (CONTINUED…)

SORT MASTER

This parameter is used to select the number of Sort Master modules that will be used by

the configuration. Up to 2 sort master modules can be used.

SL## MODULE USED

This parameter is used to select the model of the relay slave module that is used, or

deactivate it completely. The available models are SL20, SL15 and SL10. The number of

relays will be increased according to the model of SL## used.

NUMBER OF POULTRY SCALES

This parameter is used to set the amount of poultry scales that will be used by the

controller. A deactivated poultry scale will not be shown trough the configuration. The

controller can use up to 2 poultry scales.

TUNNEL START STAGE

This parameter is used to set the on/off ventilation stage that will activate the tunnel

ventilation mode. When the selected on/off ventilation is activated by temperature

demand, tunnel mode will be activated. Tunnel mode will end when that same stage no

longer has a temperature activation demand. The on/off ventilation stage selected here

must have an associated relay to make tunnel mode available. Setting this parameter to

OFF will deactivate tunnel mode. This parameter is adjustable from OFF, 1 to 24.

However, depending on system setup, some of the values will not be available.

NATURAL MODE ONLY

This parameter is used to activate the natural mode and its associated logics. If this

parameter is set to Yes, natural mode will effectively begin and all related options will no

longer be considered. If this parameter is set to No, the behaviour of the ventilation

system will act according to its parameters and associated logics and the natural mode

will only be activated when # INLETS ACTIVE FOR NATURAL is reached.

# INLETS ACTIVE FOR NATURAL

This parameter is used to set the amount of inlet using natural mode and selected in AIR

INLETS FOR NATURAL MODE that must have an opening demand before natural mode

is activated. When a number of inlet using natural mode equal to this parameter have an

opening demand, the NATURAL MODE TRANSITION DELAY will start. Once the

NATURAL MODE TRANSITION DELAY has elapsed, natural mode will effectively

begin. At this point, cool stages set to shutoff in natural mode will shutoff and inlets set

to close in natural mode will close. This parameter is adjustable from 1 to 21, ALL.

However, depending on system setup, some of the values will not be available.

OUTSIDE TEMPERATURE FOR NATURAL

This parameter is used to set the OUTSIDE TEMPERATURE at which inlet in natural

mode and inflatable inlets will open. When OUTSIDE TEMPERATURE is above this

parameter, these inlets will stop continuously close and will be allowed to open. When

the option OUTSIDE PROBE ACTIVE is set to No or the outside probe is defective, this

restriction will not be applied. A fixed Differential of 0.3° is used with this logic. This

parameter is adjusted in 0.1° increments from OFF, -9.9°C to 30.0°C (15.1°F to 90.0°F).

Page 137: T uch - agrivent.com

USER’S GUIDE

Section C-137

SYSTEM CONFIGURATION (CONTINUED…)

NATURAL MODE TRANSITION DELAY

This parameter is used to set the amount of time for which cooling stages that will shutoff

in natural mode and inlets that close in natural mode will continue to operate. When a

number of inlets using natural mode equal to # INLETS ACTIVE FOR NATURAL have an

opening demand, this delay will start. Once this delay has elapsed, natural mode will

effectively begin. At this point, cool stages set to shutoff in natural mode will shutoff and

inlets set to close in natural mode will close. This parameter is adjusted in 1-minute

increments from OFF, 1 minute to 99 minutes.

AIR INLETS FOR NATURAL MODE

This parameter is used to select which natural mode air inlets will trigger natural mode.

An air inlet that is not selected here will not be counted in the # INLETS ACTIVE FOR

NATURAL. Only natural mode air inlets will be selectable in this parameter.

INFLATABLE INLETS FOR NATURAL MODE

This parameter is used to select which inflatable inlets will trigger natural mode. An

inflatable inlet that is not selected here will not be counted in the # INLETS ACTIVE FOR

NATURAL.

NUMBER OF SOLARWALLS

This parameter is used to set the amount of poultry solarwalls that will be used by the

controller. A deactivated solarwall will not be shown trough the configuration. The

controller can use up to 2 solarwalls.

BLINK ON TOGGLE SWITCH MANUAL MODE

This parameter is used to select if the output LEDs will blink when an output is operated

manually using its toggle switch. If this option is set to Yes, an output’s LED will blink

when the toggle switch in a position other than AUTO. If this option is set to No, an

output’s LED will light up when the toggle switch in the ON position and will shut off

when the toggle switch in the OFF position.

MODEL

This parameter is used to select the control type that will be used with the configuration.

The first digit of the number represents the number of variable outputs physically

installed on the controller, while the last two represent the amount of on/off outputs used.

The available control types are 2 Variables 10 Relays, 2 Variables 15 Relays, 2 Variables

20 Relays, 2 Variables 25 Relays, 2 Variables 30 Relays, 4 Variables 10 Relays, 4

Variables 15 Relays, 4 Variables 20 Relays, 4 Variables 25 Relays, 4 Variables 30

Relays, 0 Variables 40 Relays, 0 Variables 35 Relays, 0 Variables 30 Relays, 0 Variables

25 Relays, 0 Variables 20 Relays, 0 Variables 15 Relays et 0 Variables 10 Relays..

CHANGE TEMPERATURE UNIT

This parameter is used to proceed with the temperature unit change. When the value of

this parameter is changed, a confirmation question will appear. If the modification is

confirmed, temperature unit change will be performed.

Page 138: T uch - agrivent.com

USER’S GUIDE

Section C-138

CHANGE STATIC PRESSURE UNIT

This parameter is used to proceed with the static pressure unit change. When the value of

this parameter is changed, a confirmation question will appear. If the modification is

confirmed, static pressure unit change will be performed.

Page 139: T uch - agrivent.com

USER’S GUIDE

Section C-139

OUTPUT CONFIGURATION

VAR-2-(1-2) OUT(1-2)

This parameter is used to assign outputs to the VAR-2 boards. The variable outputs that

are not activated and their logics will be removed. The available outputs on this board

are: Unused, Variable Stage 1-12, Variable Stir Fan 1-4 or Zone 1-2 Lights.

CURVE VAR-2-(1-2) OUT(1-2)

These parameters are used to change the motor curve of the respective variable output

located on the VAR-2 board. Refer to annex section for more information on motor

curves. Each of these parameters can be adjusted from 1 to 9.

V4 ID (1-2) OUT(1-4)

This parameter is used to assign outputs to the respective V4 module output. The variable

outputs that are not activated and their logics will be removed. The available outputs on

this board are: Unused, Variable Stage 1-12, Variable Stir Fan 1-4 or Zone 1-2 Lights.

CURVE V4 ID(1-2) OUT(1-4)

These parameters are used to change the motor curve of the respective variable output

located on the respective V4 module board. Refer to annex section for more information

on motor curves. Each of these parameters can be adjusted from 1 to 9.

0-10V OUT(1-2)

This parameter is used to assign outputs to the 0-10 Volts outputs, located on the Output

Board. The variable outputs that are not activated ad their logics will be removed. The

available outputs on this board are: Unused, Variable Stage 1-12, Variable Stir Fan 1-4,

Zone 1-2 Lights, Variable Heater 1-2 or Chimney 1-2.

MS-10 OUT(1-2)

This parameter is used to assign outputs to the MS-10 outputs, located on the MS-10

module. The variable outputs that are not activated and their logics will be removed. The

available outputs on this board are: Unused, Variable Stage 1-12, Variable Stir Fan 1-4,

Zone 1-2 Lights, Variable Heater 1-2 or Chimney 1-2.

RELAY (1-40) TYPE

These parameters are used to assign the output type to the respective relay. The relay

outputs that are not activated and their logics will be removed. The available outputs on

all relays are: None, Vent Stage 1-24, Stir Fan 1-4, Heater 1-10, Clock 1-4, Sprinkler,

Feed 1-6, Feed Auger 1-6, Inflatable Inlet 1-6, 0-10V Relay 1-2, High Wat Alm 1-4,

High Temp Alarm and Heating Floor. Odd numbered relays will also have Inlet 1-8 Open

as available output types, while even numbered relays will also have: Inlet 1-8 Close as

available output types. However, depending on system setup, some of the values will not

be available. 0-10V Relay 1-2 will activate when the associated 0-10V output receives an

activation demand. Chimneys will never activate the 0-10V relay outputs.

Page 140: T uch - agrivent.com

USER’S GUIDE

Section C-140

OUTPUT CONFIGURATION (CONTINUED...)

SL## RELAY (1-20) TYPE

These parameters are used to assign the output type to the respective relay. The relay

outputs that are not activated and their logics will be removed. The available outputs on

all relays are: None, Vent Stage 1-24, Stir Fan 1-4, Heater 1-10, Clock 1-4, Sprinkler,

Feeder 1-6, Feed Auger 1-6, Inflatable Inlet 1-6, 0-10V Relay 1-2, High Wat Alm 1-4,

High Temp Alarm and Heating Floor. Odd numbered relays will also have Inlet 9-16

Open as available output types, while even numbered relays will also have: Inlet 9-16

Close as available output types. However, depending on system setup, some of the values

will not be available. 0-10V Relay 1-2 will activate when the associated 0-10V output

receives an activation demand. Chimneys will never activate the 0-10V relay outputs.

LOAD DELAY

This parameter is used to adjust the load delay of all relays set to the types on/off

ventilation stage, sprinkler, clock, feeder, feed auger or stir fan,. The load management

prevents any two relays from activating at the same time. The amount of time adjusted

for the load delay will separate the activation of two or more relays. This parameter is

adjusted in 1-second increments from OFF, 1 to 60 seconds.

Page 141: T uch - agrivent.com

USER’S GUIDE

Section C-141

GROUP MANAGEMENT

GROWTH DAY GROUP (A-B)

These parameters are used to adjust the Growth Day of the respective group. These

Growth Days do not affect any Growth Curves. The Growth Day may be adjusted to

any value from OFF, day 0 to day 365 using 1-day increments.

REINITIALIZE GROUP (A-B)

These parameters are used to reinitialize all elements of the respective group. When this

parameter is pressed, the animal total quantity of the respective group will be

reinitialized.

MORTALITIES OPTION GROUP (A-B)

These parameters are used to activate or deactivate the animals count and mortality along

with all its associated logics for the respective group.

MORTALITIES GROUP (A-B)

These parameters are used to adjust the mortalities number of the respective group for the

current day. The value adjusted here will be saved in the history and will reduce the

REMAINING ANIMALS GROUP (A-B) value. These values will be automatically reset

to zero at each day change.

SHIPPED ANIMALS GROUP (A-B)

These parameters are used to adjust the shipped animals number of the respective group

for the current day. The value adjusted here will be saved in the history and will reduce

the REMAINING ANIMALS GROUP (A-B) value. These values will be automatically

reset to zero at each day change.

START WEIGHT (A-B)

These parameters are used to set the weight the animals have at the beginning of the

batch. These values will appear only if MORTALITIES OPTION GROUP (A-B) is set to

ON and the TYPE OF BREEDING is Broiler Chicken, Finisher Pig, Nursery Piglet,

Turkey or Cow.

END WEIGHT (A-B)

These parameters are used to set the weight the animals have at the end of the batch.

These values will appear only if MORTALITIES OPTION GROUP (A-B) is set to ON and

the TYPE OF BREEDING is Broiler Chicken, Finisher Pig, Nursery Piglet, Turkey or

Cow.

MORTALITY PERCENTAGE GROUP (A-B)

These parameters display the mortality percentage for the respective group for the batch.

This value represents the relation between TOTAL AMOUNT OF ANIMALS GROUP (A-

B) and REMAINING ANIMALS GROUP (A-B). This value is displayed to the nearest

1% from 0% to 100%.

TOTAL MORTALITIES GROUP (A-B)

These parameters display the total amount of mortalities since the batch has started. This

value can be reinitialized along with REMAINING ANIMALS GROUP (A-B) using the REINITIALIZE REMAINING ANIMALS GROUP (A-B) parameter.

Page 142: T uch - agrivent.com

USER’S GUIDE

Section C-142

GROUP MANAGEMENT (CONTINUED…)

REMAINING ANIMALS GROUP (A-B)

These parameters are used to keep track of the livestock according to the TOTAL

AMOUNT OF ANIMALS GROUP (A-B) and the cumulative of all days of MORTALITIES

GROUP (A-B) of the respective group. This value can be reset to TOTAL AMOUNT OF

ANIMALS GROUP (A-B) with the REINITIALIZE REMAINING ANIMALS GROUP

(A-B) parameter.

TOTAL AMOUNT OF ANIMALS GROUP (A-B)

These parameters are used to adjust the amount of animals in the livestock at the

beginning of the breeding for the respective group. This value will be used as the initial

value for the remaining animals for the respective group. These parameters are adjustable

from 0 to 99999 animals.

REINITIALIZE REMAINING ANIMALS GROUP (A-B)

These parameters are used to reinitialize the remaining number of animals of the

respective group to TOTAL AMOUNT OF ANIMALS GROUP (A-B). When this

parameter is pressed, the animal total quantity of the respective group will be

reinitialized.

REINITIALISE WATER METER ACTUAL VALUES GROUP (A-B)

These parameters are used to reinitialise all water meter actual values as well as the total

and batch total of the respective group. When this parameter is pressed, all water meter

actual values of the respective group will be reinitialised.

REINITIALISE EGG COUNTER ACTUAL VALUES GROUP (A-B)

These parameters are used to reinitialise all egg counter actual values as well as the total

and batch total of the respective group. When this parameter is pressed, all egg counter

actual values of the respective group will be reinitialised.

REINITIALISE FEEDER ACTUAL VALUES GROUP (A-B)

These parameters are used to reinitialise all feeder actual values as well as the total and

batch total of the respective group. When this parameter is pressed, all feeder actual

values of the respective group will be reinitialised.

REINITIALISE FEED AUGER ACTUAL VALUES GROUP (A-B)

These parameters are used to reinitialise all feed auger actual values as well as the total

and batch total of the respective group. When this parameter is pressed, all feed auger

actual values of the respective group will be reinitialised.

REINITIALISE BIN SCALE ACTUAL VALUES GROUP (A-B)

These parameters are used to reinitialise all bin scale actual values as well as the total and

batch total of the respective group. When this parameter is pressed, all bin scale actual

values of the respective group will be reinitialised.

REINITIALISE POULTRY SCALE ACTUAL VALUES GROUP (A-B)

These parameters are used to reinitialise all poultry scale actual values as well as the total

and batch total of the respective group. When this parameter is pressed, all poultry scale

actual values of the respective group will be reinitialised.

Page 143: T uch - agrivent.com

USER’S GUIDE

Section C-143

GROUP MANAGEMENT (CONTINUED…)

FEED CONSUMPTION INPUTS

These parameters are used to select which feed inputs will be counted for the group

consumption. A feed input selected here will have its count included in the group

consumption.

WATER METER

These parameters are used to assign a group to the respective water meter. When one of

these parameters is set to a value other than None, the corresponding water meter will be

assigned to the chosen group. A group’s total will include all water meters assigned to

that group.

EGG COUNTER

These parameters are used to assign a group to the respective egg counter. When one of

these parameters is set to a value other than None, the corresponding egg counter will be

assigned to the chosen group. A group’s total will include all egg counters assigned to

that group.

FEEDER

These parameters are used to assign a group to the respective feeder. When one of these

parameters is set to a value other than None, the corresponding feeder will be assigned to

the chosen group. A group’s total will include all feeders assigned to that group.

FEED AUGER

These parameters are used to assign a group to the respective feed auger. When one of

these parameters is set to a value other than None, the corresponding feed auger will be

assigned to the chosen group. A group’s total will include all feed augers assigned to that

group.

BIN SCALE

These parameters are used to assign a group to the respective bin scale. When one of

these parameters is set to a value other than None, the corresponding bin scale will be

assigned to the chosen group. A group’s total will include all bin scales assigned to that

group.

POULTRY SCALE

These parameters are used to assign a group to the respective poultry scale. When one of

these parameters is set to a value other than None, the corresponding poultry scale will be

assigned to the chosen group. A group’s total will include all poultry scales assigned to

that group.

Page 144: T uch - agrivent.com

USER’S GUIDE

Section C-144

PASSWORD

CHANGE PARAMETER STATE

This parameter is used to change the parameter state from locked to unlocked or vice

versa. When this parameter is pressed, ENTER PASSWORD will appear and the text

displayed here will change to Validate Password. If the correct password is entered and

this parameter is pressed, the parameter state will change from locked to unlocked or vice

versa and the result of the operation will be displayed here. If an incorrect password is

entered at ENTER PASSWORD, this parameter will display Wrong Password.

ENTER PASSWORD

This parameter is used to enter the password that is used to lock or unlock the parameters.

When the user wants to change the parameter state, the password must be entered here

and validated using CHANGE PARAMETER STATE. The default password is 0.

CHANGE PASSWORD

This parameter is used to change the password that is used to lock or unlock the

parameters. When this parameter is pressed, ENTER NEW PASSWORD, CONFIRM NEW

PASSWORD and ENTER ACTUAL PASSWORD will appear and the text displayed here

will change to Validate Changes. If the passwords entered at ENTER NEW PASSWORD

and CONFIRM NEW PASSWORD are identical and the value entered at ENTER

ACTUAL PASSWORD corresponds to the actual password, the password will be changed

when this parameter is pressed. If the passwords entered at ENTER NEW PASSWORD

and CONFIRM NEW PASSWORD are different or the value entered at ENTER ACTUAL

PASSWORD is not the actual password, this parameter will display Wrong Password.

ENTER NEW PASSWORD

This parameter is used to enter the new password that will be recorded if the change is

correctly completed.

CONFIRM NEW PASSWORD

This parameter is used to confirm the new password that will be recorded if the change is

correctly completed.

ENTER ACTUAL PASSWORD

This parameter is used to validate the password change by entering the actual password.

Page 145: T uch - agrivent.com

USER’S GUIDE

Section C-145

TURKEY/CHICKEN SCALES

STATUS

This parameter displays the actual status of the scale.

NUMBER WEIGHED

This parameter displays the amount of birds weighed recorded by the controller for the

current day. A weight is only recorded if it is between respective SCALE (1-2) TARGET

WEIGHT +/- SCALE (1-2) HIGH/LOW TOLERANCE. The amount of birds weighed is

displayed to the nearest 1 birds weighed from 0 to 9999 birds weighed.

ACTUAL AVERAGE WEIGHT

These parameters display the average weight of the respective scale recorded for the

actual day. If a scale has not recorded a weight during the actual day, the respective

parameter will display ----. This value is displayed according to the POULTRY WEIGHT

UNIT with a precision of 1 unit from 1 to 9998 units.

YESTERDAY AVERAGE WEIGHT

These parameters display the average weight of the respective scale recorded for the past

day. If a scale has not recorded a weight during the actual day, the respective parameter

will display ----. This value is displayed according to the POULTRY WEIGHT UNIT

with a precision of 1 unit from 1 to 9998 units.

ACTUAL GAIN

This parameter displays the weight gain. The weight gain is the difference between

SCALE (1-2) YESTERDAY AVERAGE WEIGHT and today’s SCALE (1-2)

AVERAGE WEIGHT. If a scale has not recorded a weight during the actual day or the

preceding one, the gain cannot be calculated and the respective parameter will display

----. This value is displayed according to the POULTRY WEIGHT UNIT with a precision

of 1 unit from -9998 to 9998 units.

YESTERDAY GAIN

This parameter displays the weight gain for the past day. This gain is the difference

between the SCALE (1-2) YESTERDAY AVERAGE WEIGHT and the average weight

of the past day. If a scale has not recorded a weight during the actual day or the

preceding one, the gain cannot be calculated and the respective parameter will display

----. This value is displayed according to the POULTRY WEIGHT UNIT with a precision

of 1 unit from -9998 to 9998 units.

UNIFORMITY

This parameter displays the uniformity calculated by the respective OPTI-GAIN 1

module for the current day. The uniformity represents the percentage of the birds that are

within 10% of the SCALE (1-2) TARGET WEIGHT. If no birds have been weighed

during the current day, this parameter displays ---. Otherwise, the uniformity is displayed

to the nearest 1% from 0% to 100%.

Page 146: T uch - agrivent.com

USER’S GUIDE

Section C-146

CHICKEN/TURKEY SCALES (CONTINUED…)

STANDARD DEVIATION

This parameter displays the standard deviation calculated by the respective scale. The

standard deviation is a measure of the uniformity of a group of birds. For example, if a

standard deviation of 30.0 grams is calculated, this indicates that 68% of the birds have a

weight within 30.0 grams of the SCALE (1-2) AVERAGE WEIGHT. This value also

indicates that 95% have a weight within 60.0 grams (standard deviation x2) of the

SCALE (1-2) AVERAGE WEIGHT. If less than two birds have been weighed during the

current day, this parameter displays -----. Otherwise, this value is displayed according to

the POULTRY WEIGHT UNIT with a precision of 1 unit from -0 to 33000 units.

AGE

This parameter displays the actual growth age. The age is incremented each time the time

of day goes from 23:59 to 0:00 (11:59P to 12:00A).

ACTUAL WEIGHT

This parameter displays the actual weight read by the OPTI-GAIN 1 module. The scale

must have been calibrated to obtain a significant value. This value is displayed according

to the POULTRY WEIGHT UNIT with a precision of 1 unit from -9999 to 32767 units.

TARGET WEIGHT

This parameter displays the target weight of the actual day. The target weight is

determined by the growth curve if the SCALE (1-2) EVALUATION OF WEIGHT

METHOD is set to Chart. If the SCALE (1-2) EVALUATION OF WEIGHT METHOD is

set to Evolution, the target weight will be equal to SCALE (1-2) AVERAGE WEIGHT (or the SCALE (1-2) START WEIGHT adjusted by the user when flock is started)

increased according to the respective SCALE (1-2) ADD WEIGHT AGE (0-249) parameter. This value will be evaluated at a frequency determined by SCALE (1-2)

TARGET EVALUATION FREQUENCY. If the flock of the respective scale has not been

started, this parameter will display ----. Otherwise, this value is displayed according to

the POULTRY WEIGHT UNIT with a precision of 1 unit from 1 to 9999 units.

LAST WEIGHT

This parameter displays the last weight recorded by the OPTI-GAIN 1 module. For a

weight to be recorded, it must be within the respective SCALE (1-2) TARGET WEIGHT +/- the corresponding SCALE (1-2) HIGH TOLERANCE / SCALE (1-2) LOW

TOLERANCE. The weight recorded by the OPTI-GAIN 1 module is the difference

between the last stable weight and the new actual weight. Ex: If two birds weighing 500

grams each are already on the scale and a third bird weighing 630 grams is added, the

OPTI-GAIN 1 module will record a weight of 630 grams, but the actual weight displayed

will be 1630 grams. If no correct weight has been recorded, this parameter will display

---. Otherwise, this value is displayed according to the POULTRY WEIGHT UNIT with a

precision of 1 unit from 1 to 9999 units.

START AGE

This parameter allows the user to set the birds’ age when the flock is started. When a

flock is started, its actual age will be set to this value. This parameter is adjusted in 1-day

increments from day 0 to day 249.

Page 147: T uch - agrivent.com

USER’S GUIDE

Section C-147

CHICKEN/TURKEY SCALES (CONTINUED…)

START WEIGHT

This parameter allows the user to set the birds’ SCALE (1-2) TARGET WEIGHT when

the flock is started. When a flock is started, its SCALE (1-2) TARGET WEIGHT will be

set to this value if the Evolution SCALE (1-2) EVALUATION OF WEIGHT METHOD is

used. When the Chart SCALE (1-2) EVALUATION OF WEIGHT METHOD is used, this

parameter will not appear. This value is adjusted according to the POULTRY WEIGHT

UNIT in 1-unit increments from 10 to 9999 units.

LOW TOLERANCE

This parameter is used to set the valid low weight limits for the scale. To make sure all

weights recorded are valid, the scale will only record weights that are within the actual

target weight - SCALE (1-2) TOLERANCE LOW and the actual target weight + SCALE

(1-2) TOLERANCE HIGH. This parameter is adjusted in 1% increments from 20% to

40%

HIGH TOLERANCE

This parameter is used to set the valid high weight limits for the scale. To make sure all

weights recorded are valid, the scale will only record weights that are within the actual

target weight - SCALE (1-2) TOLERANCE LOW and the actual target weight + SCALE

(1-2) TOLERANCE HIGH. This parameter is adjusted in 1% increments from 20% to

40%

CORRECTION FACTOR

This parameter is used to fix the percentage that will be added to the average weight

measured by the respective scale when flock age reaches SCALE (1-2) CORRECTION

FACTOR AGE. This parameter is adjusted in 1% increments from 1% to 99%.

CORRECTION FACTOR AGE

This parameter is used to set the age at which SCALE (1-2) CORRECTION FACTOR will

be applied on average weight measured by the scale. When flock reaches this age, the

average weight recorded will be the weight measured by the scale, added by this

percentage. This parameter is adjusted in 1-day increments from day 0 to day 500.

TARGET EVALUATION FREQUENCY

These parameters are used to set the time rate at which the SCALE (1-2) TARGET

WEIGHT of the respective scale will be evaluated during the day. The day will be

divided into periods defined by the respective parameter. If the SCALE (1-2) NUMBER

WEIGHED has reached the SCALE (1-2) MINIMUM NUMBER WEIGHED TARGET

EVALUATION, the SCALE (1-2) TARGET WEIGHT will be evaluated according to the

actual SCALE (1-2) AVERAGE WEIGHT and the corresponding SCALE (1-2) ADD

WEIGHT AGE (0-249). Each time a new period of the day is entered, the evaluation will

be performed once again. These parameters can be set to 1h, 2h, 4h, 6h, 12h or 24h.

Page 148: T uch - agrivent.com

USER’S GUIDE

Section C-148

CHICKEN/TURKEY SCALES (CONTINUED…)

MINIMUM NUMBER WEIGHED TARGET EVALUATION

These parameters are used to set the minimum number of weights required to evaluate the

SCALE (1-2) TARGET WEIGHT during the day. If the SCALE (1-2) NUMBER

WEIGHED has not reached this amount, the SCALE (1-2) TARGET WEIGHT will not

be evaluated when a new time period, defined by SCALE (1-2) TARGET EVALUATION

FREQUENCY is reached. These parameters are adjusted in 1-weight increments from 5

weights to 100 weights.

CALIBRATION WEIGHT

This parameter allows the user to set the weight used for the calibration process. When

calibrating the gain, the weight on the scale must be exactly the same as the one set here.

The heavier the weight is, the better the precision will be. This parameter is adjusted

according to the POULTRY WEIGHT UNIT in 1-unit increments from 1 to 22000 units.

ZERO CALIBRATION

This parameter allows the user to start a calibration process that will determine the weight

at which the scale will consider the weight to be zero (grams or pounds). To correctly

evaluate the weight on the scale, the exact weight read when nothing is on the scale must

be known. The scale must be emptied of all matter and press on this parameter. At this

moment, the message located immediately below this parameter will appear to indicate

the status of the zero calibration sequence.

GAIN CALIBRATION

This parameter allows the user to start a calibration process that will determine the gain

of the scale. To correctly evaluate the gain of the scale, the variation of the electrical

signal according to two known weights must be known; i.e. weight when the scale is

empty and the SCALE (1-2) CALIBRATION WEIGHT. A weight precisely equal to the

SCALE (1-2) CALIBRATION WEIGHT must be placed on the scale and press on this

parameter to start a gain calibration sequence. At this moment, the message located

immediately beneath this parameter will appear to indicate the status of the gain

calibration.

EVALUATION OF WEIGHT METHOD

This parameter is used to select the method used to determine the SCALE (1-2) TARGET

WEIGHT. If the Evolution method is used, the target weight will be equal to yesterday’s

average weight (or the target weight adjusted by the user when flock is started) plus the

respective SCALE (1-2) ADD WEIGHT AGE (0-249). If the Chart method is used, the

target weight for a given age will be determined by the corresponding weight adjusted in

the growth curve of the respective scale. This parameter may only be adjusted when all

scales are deactivated.

FLOCK GENDER

This parameter allows the user to choose the target weight chart that will be used. There

are two pre-programmed charts with typical weights for male and female birds.

Page 149: T uch - agrivent.com

USER’S GUIDE

Section C-149

CHICKEN/TURKEY SCALES (CONTINUED…)

FLOCK MANAGEMENT

This parameter is used to start or stop a flock for the respective scale. When the value of

this parameter is changed, a confirmation screen will appear, warning the user that all

data and histories will be reinitialised. When the flock is stopped, all histories will cease

to record data.

WEIGHING START TIME

This parameter is used to set the time at which weighing will be allowed for the

respective poultry scale. When the time of day reaches this value, the poultry scale will

register weights and will cease to record them when time of day reaches

CHICKEN/TURKEY SCALE (1-2) WEIGHING END TIME. Setting this value to the sane

value as CHICKEN/TURKEY SCALE (1-2) WEIGHING END TIME, will remove

weighing time restrictions.

WEIGHING END TIME

This parameter is used to set the time at which weighing will no longer be allowed for the

respective poultry scale. When the time of day reaches this value, the poultry scale will

cease to register weights. It will record weights once again when time of day reaches

CHICKEN/TURKEY SCALE (1-2) WEIGHING START TIME. Setting this value to the

sane value as CHICKEN/TURKEY SCALE (1-2) WEIGHING START TIME, will remove

weighing time restrictions.

AVERAGE SCALES 1 AND 2

This parameter displays the average of both scales for the actual day. If two scales are

activated at NUMBER OF POULTRY SCALES, this average weight will appear,

otherwise it won’t. This value is displayed according to the POULTRY WEIGHT UNIT

with a precision of 1 unit from 1 to 9998 units.

Page 150: T uch - agrivent.com

USER’S GUIDE

Section C-150

CURVE CHICKEN/TURKEY SCALE (1-2)

TARGET WEIGHT MALE AGE (0-249)

These parameters allow the user to adjust the SCALE (1-2) TARGET WEIGHT of a

male flock for a given age. Each weight can be individually adjusted to allow the user to

create his customized target weight chart. If the SCALE (1-2) EVALUATION OF

WEIGHT METHOD is set to Evolution, this chart will only be used as a reference if the

user desires so. However, if the SCALE (1-2) EVALUATION OF WEIGHT METHOD is

set to Chart, the SCALE (1-2) TARGET WEIGHT of a male birds of given age will be

determined by this chart. These values are adjusted according to the POULTRY WEIGHT

UNIT in 1-unit increments from 10 to 9999 units.

TARGET WEIGHT FEMALE AGE (0-249)

These parameters allow the user to adjust the SCALE (1-2) TARGET WEIGHT of a

female flock for a given age. Each weight can be individually adjusted to allow the user

to create his customized target weight chart. If the SCALE (1-2) EVALUATION OF

WEIGHT METHOD is set to Evolution, this chart will only be used as a reference if the

user desires so. However, if the SCALE (1-2) EVALUATION OF WEIGHT METHOD is

set to Chart, the SCALE (1-2) TARGET WEIGHT of a female birds of given age will be

determined by this chart. These values are adjusted according to the POULTRY WEIGHT

UNIT in 1-unit increments from 10 to 9999 units.

ADD WEIGHT MALE AGE (0-249)

These parameters are used to calculate the SCALE (1-2) TARGET WEIGHT for male

birds when the SCALE (1-2) EVALUATION OF WEIGHT METHOD is set to Evolution.

These values will be added to the SCALE (1-2) AVERAGE WEIGHT of the last

evaluation period to define the new SCALE (1-2) TARGET WEIGHT for the actual day.

If SCALE (1-2) TARGET EVALUATION FREQUENCY is set to a value other than 24h,

the added weight will be divided by the number of evaluations per day. Each value

should represent the anticipated weight increase for the respective day for male birds.

These values are adjusted according to the POULTRY WEIGHT UNIT in 1-unit

increments from 0 to 999 units.

ADD WEIGHT FEMALE AGE (0-249)

These parameters are used to calculate the SCALE (1-2) TARGET WEIGHT for female

birds when the SCALE (1-2) EVALUATION OF WEIGHT METHOD is set to Evolution.

These values will be added to the SCALE (1-2) AVERAGE WEIGHT of the last

evaluation period to define the new SCALE (1-2) TARGET WEIGHT for the actual day.

If SCALE (1-2) TARGET EVALUATION FREQUENCY is set to a value other than 24h,

the added weight will be divided by the number of evaluations per day. Each value

should represent the anticipated weight increase for the respective day for female birds.

These values are adjusted according to the POULTRY WEIGHT UNIT in 1-unit

increments from 0 to 999 units.

Page 151: T uch - agrivent.com

USER’S GUIDE

Section C-151

BIN SCALES

ACTUAL WEIGHT

These parameters display the current weight measured for the respective bin. The current

weight is the gross weight of the bin, minus the tare weight of that bin. If the tare weight

has never been established, this value will be equal to the gross weight. If there is a

communication problem with the bin’s module, the weight read is not stable enough or a

load cell is defective, the associated parameter will display ---. These parameters are

displayed to the nearest 1kg (1lb) and have a maximum display value of 30000kg

(67000lb).

FILL DATE

These parameters display the date at which the last fill occurred for the respective bin. If

no fill has been detected since the last initialization, this parameter will display --/--/--.

FILL TIME OF DAY

These parameters display the time of day at which the last fill occurred for the respective

bin. If no fill has been detected since the last initialization, this parameter will display

--/--/--.

FILL WEIGHT

This parameter displays the total amount that has been measured for all fills that were

done at the FILL DATE. If no fill has been detected since the last initialization, this

parameter will display ---.

TOTAL BATCH FILL WEIGHT

This parameter displays the total amount that has been measured for all fills since the

beginning of the batch for the respective bin. If no fill has been detected since the last

initialization, this parameter will display ---.

FILL %

These parameters display the fill percentage of each bin. This percentage is calculated by

dividing the actual weight of the bin by its MAXIMUM WEIGHT parameter. If there is a

communication problem with the bin’s module or if the MAXIMUM WEIGHT value is set

to ---, the associated parameter will display ---.

MAXIMUM WEIGHT

This parameter is used to set the maximum weight the bin can hold. This value will be

used to calculate the fill percentage of the bin. If this value is set to ---, FILL % will not

be calculated and will also display ---. This parameter is adjusted in 0.1kgx1000

(0.1lbx1000) increments from ---, 1.0kgx1000 (1.0lbx1000) to 70.0kgx10000

(70.0lbx1000).

LOW LIMIT ALARM

This parameter is used to set the low weight limit for the bin. When the weight measure

for the bin is less than this value, the low limit alarm will activate. Adjusting this value to

OFF will deactivate the low limit alarm. This parameter is adjusted in 0.1kgx1000

(0.1lbx1000) increments from OFF, 0.5 kgx1000 (0.5 lbx1000) to 30.0 kgx1000 (30.0

lbx1000).

Page 152: T uch - agrivent.com

USER’S GUIDE

Section C-152

BIN SCALES (CONTINUED…)

TOLERANCE

This parameter is used to set the tolerance of the bin. The tolerance is the value used to

validate a tare sequence, to end a fill sequence and accept an unexpected weight increase.

This parameter is adjusted in 1kg (1lb) increments from 10kg (10lb) to 999kg (999lb).

FILL THRESHOLD

This parameter is used to set the weight increase that will trigger a fill sequence. When

the weight of the bin increases by this value within a time period of FILL TIME, the fill

sequence will begin. This parameter is adjusted in 1kg (1lb) increments from 50kg (50lb)

to 999kg (999lb).

FILL TIME

This parameter is used to set the time within which the weight must increase to trigger a

fill sequence, or remain stable to end the fill sequence. When the weight of the bin

increases by FILL THRESHOLD within this time period, the fill sequence will begin.

When the weight of the bin does not increase by TOLERANCE within this time period,

the fill sequence will end. This parameter is adjusted in 1-minute increments from 5 to 10

minutes.

ASSOCIATED FEED INPUTS

These parameters are used to determine which feed inputs will be associated to the

respective bin. The quantity read by the feed input will be considered when calculating

fill values.

TARE

These parameters are used to activate the tare sequence on the respective bin. If this

parameter is pressed, the tare sequence will begin. This parameter displays the state of the

tare sequence. When the tare sequence begins, this message will appear and display

PLEASE WAIT..., indicating that the tare sequence is being performed. If a

communication error occurs during the tare sequence this message will display

ERROR(Comm.). If a load cell is defective during the tare sequence this message will

display ERROR(LC). When the tare sequence ends, this message will display

ERROR(Tol.), if the weight variation was too great during the tare sequence, or

SUCCESS, if the tare sequence has successfully been completed. This message will

remain displayed for a few seconds after the tare sequence ends. When the tare sequence

has successfully been completed, the tare weight will be recorded in the controller and

used to calculate the actual weight of the contents of the bin.

LAST TARE DATE

This parameter displays the date of the last tare sequence. When a tare sequence has been

successfully completed, this parameter will display the date at which it was performed. If

no tare has been performed since the last initialization, this parameter will display --/--/--.

LAST TARE TIME

This parameter displays the time of the last tare sequence. When a tare sequence has been

successfully completed, this parameter will display the time at which it was performed. If

no tare has been performed since the last initialization, this parameter will display --.

Page 153: T uch - agrivent.com

USER’S GUIDE

Section C-153

BIN SCALES (CONTINUED…)

WEIGHT MAXIMUM CALIBRATION

This parameter is used to set the weight for the maximum calibration. The actual weight

will become the weight adjusted here when MAXIMUM WEIGHT CALIBRATION is

pressed. This parameter is adjusted in 1 unit increments from 0 to 99999 units (kg or lb)

MAXIMUM WEIGHT CALIBRATION

This parameter is used to calibrate the maximum weight by assigning WEIGHT

MAXIMUM CALIBRATION as the actual weight. All further weight measures will

consider this calibration to calculate the actual weight.

MAXIMUM WEIGHT CALIBRATION REINITIALISATION

This parameter is used to return to the default gain of the FBT module. When this

parameter is pressed, the user’s maximum weight calibration will be cancelled.

LOAD CELL (1-6)

These parameters display the percentage of the weight measured on each load cell. If

there is a communication problem with the bin’s module or one of the load cells is not

operating properly, the concerned parameters will display ---.

LOAD CELL GAIN

These parameters are used to set the gain of the load cells of the respective bin scale. This

value is the gain in mV for each Volt of excitement and must correspond to the load cell

manufacturer's specifications. These parameters are adjusted in 1mV increments from

0mV to 781mV.

LOAD CELL MAXIMUM WEIGHT

These parameters are used to set the maximum weight of the load cells of the respective

bin scale. This value is the greatest weight the load cell can read and must correspond to

the load cell manufacturer's specifications. These parameters are adjusted in 1kg

increments from 0kg to 32767kg.

CONSUMPTION

These parameters display the consumption of the respective bin. These parameters are

displayed to the nearest 100kg (100lb) and have a maximum value of 99999kg (99999lb).

REINITALISE CONSUMPTION

These parameters are used to reinitialise the respective bin consumption value. When this

parameter is pressed, the BIN (1-2) CONSUMPTION value will be reset to zero.

STOP FEEDER/FEED AUGER ON FILL

This parameter is used to determine if the feeders and feed augers associated to the feed

inputs that are used with the respective bin will stop when a fill is detected on that bin. If

this option is set to Yes, all feeders and feed augers using a feed input selected in BIN (1-

2) ASSOCIATED FEED INPUTS will deactivate for the duration of the fill operation.

Page 154: T uch - agrivent.com

USER’S GUIDE

Section C-154

BIN SCALES (CONTINUED…)

CONSUMPTION MEASURING METHOD

This parameter is used to determine the consumption measuring method for the

respective bin scale. If the feed inputs associated to the feed bin activate many times per

day or there are no associated feed inputs for the bin scale, it is recommended to use

Method 1. If the feed inputs associated to the feed bin activate only a few times per day,

it is recommended to use Method 2.

Page 155: T uch - agrivent.com

USER’S GUIDE

Section C-155

VARIABLE HEATER

INTENSITY ACTUAL

These parameters display the actual intensity of the respective variable heater. These

parameters are displayed to the nearest 1% from OFF, 0% to 100%.

ON TEMPERATURE

These parameters are used to set the temperature at which the respective variable heater

will activate at VARIABLE HEATER (1-2) MINIMUM INTENSITY. When the variable

heater temperature is equal to this set point, the respective variable heater will activate at

VARIABLE HEATER (1-2) MINIMUM INTENSITY. When the variable heater

temperature is below this set point, the variable heater intensity will increase to reach

VARIABLE HEATER (1-2) MAXIMUM INTENSITY when the temperature reaches

VARIABLE HEATER (1-2) MAXIMUM TEMPERATURE. A fixed Differential of 0.3° is

used with this logic. These parameters are adjusted in 0.1° increments from MAIN SET

POINT - 40.0° to MAIN SET POINT + 20.0°.

MAXIMUM TEMPERATURE

These parameters are used to set the temperature at which the respective variable heater

will be activated at VARIABLE HEATER (1-2) MAXIMUM INTENSITY. When the

variable heater temperature drops and reaches this set point, the respective variable heater

will be activated at VARIABLE HEATER (1-2) MAXIMUM INTENSITY. These

parameters are adjusted in 0.1° increments from VARIABLE HEATER (1-2) ON

TEMPERATURE - 20.0° to VARIABLE HEATER (1-2) ON TEMPERATURE - 0.5°.

MINIMUM INTENSITY

These parameters are used to set the intensity that will take the respective variable heater

when its temperature is equal to VARIABLE HEATER (1-2) ON TEMPERATURE. These

parameters are adjusted in 1% increments from 0% to 100%.

MAXIMUM INTENSITY

These parameters are used to set the intensity that will take the respective variable heater

when its temperature is equal to VARIABLE HEATER (1-2) MAXIMUM

TEMPERATURE. These parameters are adjusted in 1% increments from 0% to 100%.

PROBES

This is used to select the inside temperature probes that will be used by the variable

heater. The average of the selected probes will dictate heater intensity. If there are no

probes selected, the temperature used will be equal to the MAIN SETPOINT.

Page 156: T uch - agrivent.com

USER’S GUIDE

Section C-156

VARIABLE STIR FANS

ACTUAL SPEED

These parameters display the actual speed of the variable stir fans. Each variable stir fan

can display OFF, or a speed from 0% to 100%.

START TEMPERATURE

These parameters are used to set the temperature at which the respective variable stir fan

will be activated continuously to VARIABLE STIR FAN (1-4) MINIMUM SPEED. A

fixed Differential of 0.3° is used with this logic. As the average temperature of the

probes selected in selected in VARIABLE STIR FAN (1-4) PROBES increases, the

variable stir fan’s speed will increase until VARIABLE STIR FAN (1-4) END TEMPERATURE is reached. These parameters may be adjusted in 0.1° increments from

MAIN SET POINT - 10.0° to MAIN SET POINT + 40.0°.

END TEMPERATURE

These parameters are used to set the temperature at which the respective variable stir fan

will be activated at VARIABLE STIR FAN (1-4) MAXIMUM SPEED. These parameters

adjusted in 0.1° increments from VARIABLE STIR FAN (1-4) START TEMPERATURE +

0.5° to VARIABLE STIR FAN (1-4) START TEMPERATURE + 40.0°.

MINIMUM SPEED

These parameters are used to adjust the minimum speed of variable stir fans. This speed

is the base value used to calculate the actual minimum speed. The OUTSIDE

TEMPERATURE and humidity may affect variable stir fans’ actual minimum speed. If

the minimum speed Growth Function for variable stir fan 1 is activated, that stage’s

minimum speed will not be adjustable. The minimum speed settings are adjusted in 1%

increments from 12% to 100% or 0% to 100% if the respective stage is used on 0-10

Volts output.

MAXIMUM SPEED

These parameters are used to adjust the maximum speed of the respective variable stir

fan. This speed will be reached when the average temperature of the probes selected in

VARIABLE STIR FAN (1-4) PROBES reaches the corresponding VARIABLE STIR FAN

(1-4) END TEMPERATURE. These parameters are adjusted in 1% increments from 12%

to 100%.

NATURAL SHUTOFF

These parameters are used to activate or deactivate the natural shutoff logic for the

respective variable stir fan. If a natural shutoff option is set to YES, corresponding

variable stir fan will deactivate when natural mode is entered. If it is set to NO, natural

mode will not affect the respective variable stir fan.

TUNNEL SHUTOFF

These parameters are used to activate or deactivate the tunnel shutoff logic for the

respective variable stir fan. If a tunnel shutoff option is set to YES, corresponding

variable stir fan will deactivate when tunnel mode is entered. If it is set to NO, tunnel

mode will not affect the respective variable stir fan.

Page 157: T uch - agrivent.com

USER’S GUIDE

Section C-157

VARIABLE STIR FANS (CONTINUED…)

FULL SPEED START

These parameters are used to determine if the respective variable stir fan will perform a

full start upon activation. If this option is set to ON the corresponding variable output will

be activated at full speed for the first few seconds following an activation demand. This

option is not available if the variable stir fan is used on 0-10 Volts output.

PROBES

These parameters are used to select the probes the respective variable stir fan will use to

determine activation and deactivation according to temperature demand. To If there are

no probes selected, the temperature used will be equal to the actual MAIN

SETPOINT.

Page 158: T uch - agrivent.com

USER’S GUIDE

Section C-158

ON/OFF STIR FANS

ACTUAL STATUS

These parameters display the actual status of the stir fan outputs. Each stir fan output can

be 100% or OFF.

ON TEMPERATURE

These parameters are used to set the temperature at which the respective stir fan will be

activated. When the temperature selected in STIR FAN (1-4) PROBES reaches this

temperature, the respective stir fan will be activated according to its timer. These

parameters may be adjusted in 0.1° increments from 0.0°F to 120.0°F (0.0°C to 40.0°C).

OFF TEMPERATURE

These parameters are used to set the temperature at which the respective stir fan will be

deactivated. When the temperature selected in STIR FAN (1-4) PROBES drops to this

temperature, the respective stir fan will be deactivated. These parameters may be adjusted

in 0.1° increments from STIR FAN (1-4) ON TEMPERATURE - 0.5° to STIR FAN (1-4)

ON TEMPERATURE - 40.0°.

NATURAL SHUTOFF

These parameters are used to activate or deactivate the natural shutoff logic for the

respective stir fan. If a natural shutoff option is set to YES, corresponding stir fan will

deactivate when natural mode is entered. If it is set to NO, natural mode will not affect

the respective stir fan.

TUNNEL SHUTOFF

These parameters are used to activate or deactivate the tunnel shutoff logic for the

respective stage. If a tunnel shutoff option is set to YES, corresponding variable stir fan

will deactivate when tunnel mode is entered. If it is set to NO, tunnel mode will not affect

the respective stir fan.

ON TIME

These parameters are used to set the on time of the respective stir fan’s timer. The stir fan

will activate for this amount of time and deactivate for STIR FAN (1-4) OFF TIME when

its temperature reaches STIR FAN (1-4) ON TEMPERATURE. These parameters are

adjusted from 0:00 to 500:59 minutes.

OFF TIME

These parameters are used to set the off time of the respective stir fan’s timer. The stir fan

will activate for STIR FAN (1-4) ON TIME and deactivate for this amount of time when

its temperature reaches STIR FAN (1-4) ON TEMPERATURE. These parameters are

adjusted from 0:00 to 500:59 minutes.

PROBES

These parameters are used to select the probes the respective stir fan will use to

determine activation and deactivation according to temperature demand. To If there are

no probes selected, the temperature used will be equal to the actual MAIN

SETPOINT.

Page 159: T uch - agrivent.com

USER’S GUIDE

Section C-159

CHIMNEYS

REQUESTED POSITION

This parameter displays the requested position of the respective chimney. Note that this

position is not the physical position of the chimney, but the position requested by the

controller. This position is displayed to the nearest 1% from 0% to 100%.

MANUAL OVERRIDE

This parameter is used to manually operate the respective inlet. When this parameter is

set to a value other than AUTO, the respective chimney will take the corresponding

position. This parameter can be adjusted to AUTO, 0% to 100%.

WINTER SETPOINT

This parameter is used to set the temperature at which minimum opening position will be

equal to CHIMNEY 1 WINTER MINIMUM OPENING. When the OUTSIDE

TEMPERATURE is between CHIMNEY 1 WINTER SETPOINT and CHIMNEY

1SUMMER SETPOINT, the minimum opening position will modulate accordingly. The

calculated minimum opening is displayed at the CHIMNEY 1 POSITION 1 parameter.

This parameter is adjusted in 0.1° increments from -40.0°F to 120.0°F (-40.0°C to

40.0°C).

SUMMER SETPOINT

This parameter is used to set the temperature at which minimum opening position will be

equal to CHIMNEY 1 SUMMER MINIMUM OPENING. When the OUTSIDE

TEMPERATURE is between CHIMNEY 1 WINTER SETPOINT and CHIMNEY 1

SUMMER SETPOINT, the minimum opening position will modulate accordingly. The

calculated minimum opening is displayed at the CHIMNEY 1 POSITION 1 parameter.

This parameter is adjusted in 0.1° increments from -40.0°F to 120.0°F (-40.0°C to

40.0°C).

WINTER MINIMUM OPENING

This parameter is used to adjust the minimum opening position when the OUTSIDE

TEMPERATURE is equal to or below CHIMNEY 1 WINTER SETPOINT. When the

OUTSIDE TEMPERATURE is between CHIMNEY 1 WINTER SETPOINT and

CHIMNEY 1 SUMMER SETPOINT, the minimum opening position will modulate

accordingly. The calculated minimum opening is displayed at the CHIMNEY 1

POSITION 1 parameter. This parameter is adjusted in 1% increments from 0% to 100%.

SUMMER MINIMUM OPENING

This parameter is used to adjust the minimum opening position when the OUTSIDE

TEMPERATURE is equal to or above CHIMNEY 1 SUMMER SETPOINT. When the

OUTSIDE TEMPERATURE is between CHIMNEY 1 WINTER SETPOINT and

CHIMNEY 1 SUMMER SETPOINT, the minimum opening position will modulate

accordingly. The calculated minimum opening is displayed at the CHIMNEY 1

POSITION 1 parameter. This parameter is adjusted in 1% increments from 0% to 100%.

Page 160: T uch - agrivent.com

USER’S GUIDE

Section C-160

CHIMNEYS (CONTINUED…)

REFERENCE SPEED (1-5)

These parameters are used to set the reference positions for chimney positioning. When

variable stage of the same number as the chimney is activated at a speed equal to one of

these parameters, the chimney will take the opening associated to that reference speed.

As soon as the variable stage is activated, the chimney will open at CHIMNEY (1-2)

POSITION 1, even if the variable stage’s speed is lower than all speed references. When

the variable stage’s speed is between two reference speeds, the opening will modulate

according to the two associated positions. These parameters are adjusted in 1%

increments from 1% to 100%.

POSITION (1-5)

These parameters are used to set the positions associated to each reference speed for the

variable stage of the same number adjusted at CHIMNEY (1-2) REFERENCE SPEED.

This allows the user to create a non-linear opening according to the variable stage’s

speed. These parameters are adjusted in 1% increments from 0% to 100%.

OPEN 100% IF VARIABLE TOGGLE SWITCH ON

This parameter is used to open or not the chimney at 100% when variable stage of the

same number is controlled manually by its toggle switch on the Variable Control. If this

parameter is set to Yes, when variable stage is controlled manually by a toggle switch,

the chimney will open at 100%. This parameter can be adjusted to Yes or No.

Page 161: T uch - agrivent.com

USER’S GUIDE

Section C-161

SORT MASTER

AVERAGE WEIGHT (1-3) (A-B)

These parameters display the average weight of each group read by the Sort Master

module(s). Each weight is displayed to the nearest kg from 0 to 32767kg.

DAILY HITS (1-3) (A-B)

These parameters display the number of hits of each group read by the Sort Master

module(s). Each value is displayed to the nearest hit from 0 to 32767 hits.

TOTAL WEIGHT (1-3) (A-B)

These parameters display the total weight of each group read by the Sort Master

module(s). Each weight is displayed to the nearest kg from 0 to 32767kg.

AVERAGE TOTAL WEIGHT (1-3) (A-B)

These parameters display the average total weight of all groups read by the Sort Master

module(s). This weight is displayed to the nearest kg from 0 to 32767kg.

GRAND TOTAL WEIGHT (A-B)

These parameters display the total weight of all groups read by the Sort Master

module(s). This weight is displayed to the nearest kg from 0 to 32767kg.

TOTAL DAILY HITS (A-B)

These parameters display the total number of hits of all groups read by the Sort Master

module(s). This value is displayed to the nearest hit from 0 to 32767 hits.

Page 162: T uch - agrivent.com

USER’S GUIDE

Section C-162

HEATING FLOOR

ACTUAL STATUS

This parameter displays the actual status of the heating floor output. The heating floor

output can be ON or OFF.

ON TEMPERATURE (Curve Available)

This parameter is used to set the temperature at which the heating floor will be activated.

When the temperature of the probes selected in the corresponding HEATING FLOOR

PROBES parameter drops to this temperature, the heating floor will be activated. This

parameter is relative to the MAIN SETPOINT and may be adjusted in 0.1° increments

from 0.0°F to 120.0°F (0.0°C to 40.0°C).

OFF TEMPERATURE

This parameter is used to set the temperature at which the heating floor will be

deactivated. When the temperature of the probes selected in the corresponding HEATING

FLOOR PROBES parameter rises to this temperature, the heating floor will be

deactivated. This parameter is relative to the HEATING FLOOR ON TEMPERATURE

and may be adjusted in 0.1° increments from HEATING FLOOR ON TEMPERATURE +

0.3° to HEATING FLOOR ON TEMPERATURE + 10.0°.

PROBES

This parameter is used to select the probes the heating floor will use to determine

activation and deactivation according to temperature demand. If there are no probes

selected, the temperature used will be equal to the actual MAIN SETPOINT.

Page 163: T uch - agrivent.com

USER’S GUIDE

Section C-163

TECH PARAM

CODE 1-4

These parameters are reserved for the manufacturer’s technical support personnel.

TECH PARAM

These parameters are reserved for the manufacturer’s technical support personnel.

Page 164: T uch - agrivent.com

USER’S GUIDE

Section C-164

SOLARWALLS

TEMPERATURE

This parameter displays the actual temperature read by the respective solarwall probe.

This temperature is displayed to the nearest 0.1° from -58.0°F to 140.0°F

(-50.0°C to 60.0°C).

PROBE

This parameter allows the user to select the temperature probe for the respective solarwall

temperature. This parameter can be adjusted to any probe value from probe 1 to probe 11.

SETPOINT

These parameters are used to set the temperature at which an adjustment will be applied

on the selected output(s) temperature set point. When the SOLARWALL (1-2)

TEMPERATURE reaches this temperature, output(s) selected in SOLARWALL (1-2)

AFFECTED VARIABLE STAGES will progressively drop their activation temperature by

SOLARWALL (1-2) INFLUENCE for every degree of difference between the

SOLARWALL (1-2) TEMPERATURE and this temperature. If more than one solarwall

affects the same variable stage, the greatest difference will be applied on that stage’s

activation temperature. The maximum variable stage activation temperature adjustment is

limited to 20.0°. This parameter is adjusted in 0.1° increments from MAIN SET POINT -

10.0° to MAIN SET POINT + 10.0°.

AFFECTED VARIABLE STAGES

These parameters are used to select which variable stages will be affected by the

solarwall logic. Stages selected in one of these parameters will progressively drop their

activation temperature by SOLARWALL (1-2) INFLUENCE for every degree of

difference between the SOLARWALL (1-2) TEMPERATURE and SOLARWALL (1-2)

SETPOINT. If more than one solarwall affects the same variable stage, the greatest

difference will be applied on that stage’s activation temperature.

Page 165: T uch - agrivent.com

USER’S GUIDE

Section C-165

SOLARWALLS (CONTINUED...)

INLFUENCE

This parameter is used to set the influence value of the solarwall’s adjustment. When the

SOLARWALL (1-2) TEMPERATURE reaches SOLARWALL (1-2) SETPOINT,

output(s) selected in SOLARWALL (1-2) AFFECTED VARIABLE STAGES will

progressively drop their temperature set point activation by SOLARWALL (1-2)

INFLUENCE per degree between the SOLARWALL (1-2) TEMPERATURE and

SOLARWALL (1-2) SETPOINT. This parameter is adjusted in 0.1° increments from 0.1°

to 1.0°.

Solarwall effect on variable stage activation temperature with Solarwall Influence at 1.0°

Variable Stage On Temp is not decreased when Solarwall Temperature is below Solarwall

Setpoint. 1

2

3

Variable Stage On Temp is decreased by the difference between the Solarwall Setpoint and the

Solarwall Temperature.

Variable Stage On Temp is decreased by a maximum of 20.0° even if the difference between the

Solarwall Setpoint and the Solarwall Temperature is greater than 20.0°.

Solarwall

Temperature

Solarwall

Setpoint

Set Variable Stage On

Temp

Modified Variable

Stage On Temp

1

2

2

3

3

50

60

70

80

90

100

Temperatu

re

Page 166: T uch - agrivent.com

USER’S GUIDE

Section C-166

INPUT CONFIGURATION

WATER/EGG 1-12

These parameters are used to determine which type is used on the mentioned input. Each

input can be an egg counter or a water meter. It is important not to assign the same input

type and number twice. An input assigned to None will not be used. The inputs can be

assigned as Water Meter (1-12) and Egg Counter (1-12).

WATER/EGG 1-12

These parameters are used to activate or deactivate the manual mode for the respective

egg counter. Each input can be used in manual mode, in which case the user will have to

enter the egg quantity in EGG COUNTER (1-12) manually. If this parameter is set to

ON, manual mode will be used for the respective egg counter. If this parameter is set to

OFF, EGG COUNTER (1-12) will reflect the count of the egg counter input.

Page 167: T uch - agrivent.com

USER’S GUIDE

Section C-167

WATER FLUSH

ACTUAL STATUS

These parameters display the actual status of the water flush outputs. Each water flush

output can be ON or OFF. When a water flush output is ON, the water alarms for the

water counter of the same number will not be checked.

START TIME

These parameters are used to set the time at which the respective water flush output will

activate. When the time of day reaches this time, the respective water flush output will

activate. These parameters are adjusted in 1-minute increments from 0:00 to 23:59

(12:00A to 11:59P).

STOP TIME CYCLE (1-15)

These parameters are used to set the time at which the respective water flush output will

deactivate. When the time of day reaches this time, the respective water flush output will

deactivate. These parameters are adjusted in 1-minute increments from 0:00 to 23:59

(12:00A to 11:59P).

Page 168: T uch - agrivent.com

USER’S GUIDE

Section C-168

Alarm Message Table

Situational Warning Message List

These alarms will activate the alarm relay when the condition is present and when the situation is

corrected. A specific action must be performed to deactivate the alarm.

Message Cause

Average Temp. Too High

- The AVERAGE TEMPERATURE is above the ALARM HIGH

ACTUAL TEMPERATURE.

- The AVERAGE TEMPERATURE is above OUTSIDE

TEMPERATURE + ALARM HIGH RELATIVE TEMPERATURE and

OUTSIDE TEMPERATURE is above the MAIN SETPOINT.

- The AVERAGE TEMPERATURE is above ALARM HIGH CRITICAL

TEMPERATURE and the ALARM CRITICAL option is set to ON.

Average Temp. Too Low - The AVERAGE TEMPERATURE is under ALARM LOW ACTUAL

TEMPERATURE.

Probe # Too High

- The respective probe is above the ALARM HIGH ACTUAL

TEMPERATURE.

- The respective probe is above the OUTSIDE TEMPERATURE +

ALARM HIGH RELATIVE TEMPERATURE and the OUTSIDE

TEMPERATURE is above the MAIN SETPOINT.

- The respective probe is above the ALARM HIGH CRITICAL

TEMPERATURE and the ALARM CRITICAL option is set to ON.

Probe # Too Low - The respective prove is under the ALARM LOW ACTUAL

TEMPERATURE.

Probe # Defective - The probe is absent, not connected properly, or defective (short-circuit

or open circuit).

Out Probe Defect. - The outside temperature probe is absent, not connected properly or

defective (short-circuit or open circuit).

Inlet # Check Pot

- The mentioned inlet’s potentiometer has an out of range value or is

unreadable and the INLET (1-16) POTENTIOMETER ALARM is set to

ON.

No Probe Assigned - At least one activated output or the Average Temperature has no

probes assigned in its probe selection parameter.

Problem Relay Control - The relay output control board has not communicated with the

controller for 5 minutes.

8-Input MGCB Board Not

Responding

- The 8-Input MGCB Board has not communicated with the controller

for 5 minutes.

Var Control Not Resp. - Variable Board module is defective.

- Communication wiring is incorrect.

V4 ID(1-2) Module Not

Resp.

- The V4 module has not communicated with the controller for 5

minutes.

0-10V ID(1-2) Not

Responding

- 0-10V ID (1-2) chip is missing.

- Output board is defective or unplugged.

Page 169: T uch - agrivent.com

USER’S GUIDE

Section C-169

Communication Error Bin

#

- The mentioned bin module is activated and has not communicated

with the main controller for a 5-minute period.

Problem Bin # - The mentioned bin’s FBT module cannot provide a stable weight

value.

Bin # Level Too Low - The mentioned bin’s measured weight is lower than LOW ALARM

LIMIT.

Load Cell # Bin # Defect - The mentioned load cell of the mentioned bin is defective or

unplugged for a 5-minute period.

MS-10 Not Responding - The MS-10 module has not communicated with the controller for 5

minutes.

Sort Master (1-2) Not

Responding

- The Sort Master module has not communicated with the controller for

5 minutes.

Backup Power In Use - The controller’s main power supply is interrupted and the controller is

using its backup power.

Error Code 1

- The system has rebooted 5 times within a 3-minute period or 10 times

within a 15-minute period. This situation will be considered resolved if

system does not reboot for 15 minutes. If this situation persists, contact

your distributor.

Error Code 2-5 - If one or more of these error codes appear, contact your distributor.

Page 170: T uch - agrivent.com

USER’S GUIDE

Section C-170

Continuous Warning Message List

These alarms will activate the alarm relay when the condition is present and when the situation is

corrected. A specific action must be performed to deactivate the alarm relay.

Message Cause

Overflow Water # Alarm

- The amount of units counted by the water meter has exceeded the

ALARM WATER METER (1-12) CALCULATED HIGH LIMIT

within the ALARM WATER METER HIGH CHECK RATE.

Low Alarm Water Meter #

- The amount of units counted by the water meter is under the ALARM WATER METER (1-12) CALCULATED LOW LIMIT within the

ALARM WATER METER LOWCHECK RATE.

Feeder # Max Limit - The feeder input has detected feed for more than ALARM FEED (1-12)

MAXIMUM LIMIT during a feeder activation period.

Feeder # Min Limit - The feeder input has not detected feed for more than ALARM FEED

(1-12) STOP LIMIT during a feeder activation period.

Feed Auger # Max Limit - Feed auger input has detected a consecutive amount of time above to

the ALARM FEED AUGER (1-12) MAXIMUM LIMIT.

Feed Auger # Min Limit - Feed auger input has not detected a consecutive amount of time equal

to the ALARM FEED AUGER (1-12) STOP LIMIT.

Static Press Too High - The static pressure has been above the ALARM HIGH STATIC

PRESSURE throughout the ALARM STATIC PRESSURE DELAY.

Static Press Too Low - The static pressure has been under the ALARM HIGH STATIC

PRESSURE throughout the ALARM STATIC PRESSURE DELAY.

Page 171: T uch - agrivent.com

USER’S GUIDE

Section C-171

Event Message List

These entries are not alarms, but events that occurred at a given time and date.

Message Cause

Humidity Probe Not

Responding

- Humidity probe is unplugged. Check wiring.

- Sensor & Comm. board is defective or unplugged.

Relay Board Test Mode

ON - The test mode of the relay board was activated.

Relay Board Test Mode

OFF - The test mode of the relay board was deactivated.

Inlet # Cool Down - The mentioned inlet’s cool down function was activated at the

specified date and time.

Scale # Not Responding - The scale is active and has not communicated with the controller for 5

minutes.

Inlet Setup Activated - The setup sequence of the mentioned inlet was activated.

Inlet Setup Deactivated - The setup sequence of the mentioned inlet was deactivated.

Inlet # Pot Defective

- The mentioned inlet’s potentiometer has an out of range value or is

unreadable and the INLET (1-16) POTENTIOMETER ALARM is set to

OFF.

Power Failure - The controller has recovered from a power failure at the mentioned

date and time.

Alarm Relay Activated - The ALARM RELAY was set to ON.

Alarm Relay Deactivated - The ALARM RELAY was set to OFF.

Temp Test Mode

Activated - The TEST MODE OPTION was set to ON.

Temp Test Mode

Deactivated - The TEST MODE OPTION was set to OFF.

Page 172: T uch - agrivent.com

USER’S GUIDE

Section C-172

Motor curve table

TYPE OF MOTOR

CURVE BRAND MODEL VOLTAGE HEIGHT

1 Multifan 4E40 230 V. 16

2 Multifan 2E20 230 V. 8

2 Multifan 4E35 230 V. 14

2 Multifan 4E50 230 V. 20

2 Multifan AF24M’E 230 V. 24

2 Multifan 6E63 230 V. 24

2 Multifan 6E71 230 V. 28

2 Multifan 8E92 230 V. 36

2 Ziehl 230 V.

2 Performa V52-7105P 230 V. 18

3 Multifan 2E30 230 V. 12

3 Multifan 4E45 230 V. 18

3 Multifan 6E56 230 V. 22

3 Multifan/AF AF36M 230 V. 36

3 Aerotech-F AT242 230 V. 24

3 Performa V52-7106P 230 V. 20

3 Performa V52-7108P 230 V. 24

4 Multifan 2E25 230 V. 10

4 Marathon 1/4HP 230 V. 16

4 Marathon 1/3HP 230 V. 18

4 Performa V52-7102P 230 V. 12

5 GE Motor 5KCP39… 230 V. 12

5 Leeson 1/4HP AF12L 230 V. 12

5 GE Motor 5KCP39… 230 V. 14

5 Emerson K55HXJ… 230 V. 14

6 Oversized motors

7 Multifan 4E30 230 V. 12

7 Multifan 2E35 230 V. 14

7 Performa V52-7104P 230 V. 16

8 Multifan 4E25 230 V. 10

8 Performa V52-7103P 230 V. 14

Page 173: T uch - agrivent.com

INDEX / WARRANTY

Section D-173

INDEX /

WARRANTY

SECTION D

Page 174: T uch - agrivent.com

INDEX / WARRANTY

Section D-174

TABLE OF CONTENTS

Section A

WARNINGS AND PRECAUTIONS ................................................................................. 2 Box and Board Layout* ...................................................................................................... 3

Wiring Diagram Sensor and Comm. Board ........................................................................ 8 Wiring Diagram 8-INPUT BOARD ................................................................................... 9 Wiring Diagram 8-INPUT MGCB BOARD .................................................................... 10 Wiring Diagram 8 Comm. Port BOARD.......................................................................... 13 Wiring Diagram Relay Board (REL-5) ............................................................................ 14

Wiring Diagram Air Inlets ................................................................................................ 16 Wiring Diagram Variable Board (VAR-2) ....................................................................... 17 Wiring Diagram Output Board (0-10V) ........................................................................... 18 Wiring Diagram V4 .......................................................................................................... 19

Wiring Diagram Opti-Gain 1 ............................................................................................ 20 Wiring Diagram FBT / LIM ............................................................................................. 21

Typical Installation Layout ............................................................................................... 22 Wiring Diagram MS10 ..................................................................................................... 23

Wiring Diagram Sort Master ............................................................................................ 24 Wiring Diagram SL20 Pot Board and Relay Control ....................................................... 25 Wiring Diagram SL20 Relay Board ................................................................................. 26

Electrician’s notes ............................................................................................................. 27

TABLE OF CONTENTS

Section B

Unpacking ......................................................................................................................... 30

Mounting hardware required ............................................................................................ 30

General installation guidelines .......................................................................................... 31 Controller .................................................................................................................................. 31 Electrical cables ........................................................................................................................ 31 Electrical power ........................................................................................................................ 31

Mounting ........................................................................................................................... 32

Connection procedure ....................................................................................................... 33 Detailed wiring diagrams .......................................................................................................... 33

Typical Sensor Wiring for Probes ........................................................................................................33 Typical Water Meter Wiring ................................................................................................................35 Typical Feed Sensor Wiring ................................................................................................................36 Typical Variable Stage Wiring ............................................................................................................37 Typical Actuator Wiring ......................................................................................................................38 Typical Power Backup Wiring .............................................................................................................39 Typical Backup Thermostat Wiring .....................................................................................................40 Typical V1 or V2 Module Wiring ........................................................................................................41 Typical Alarm Connection Wiring ......................................................................................................42

Powering up procedure ..................................................................................................... 43 Verify all connections ............................................................................................................... 43 Hermetically close the controller .............................................................................................. 43 Put the power on ....................................................................................................................... 43 Secure the front panel with a lock ............................................................................................. 43

Controller compatible probes ............................................................................................ 43 Controller compatible modules ......................................................................................... 43

Page 175: T uch - agrivent.com

INDEX / WARRANTY

Section D-175

Specifications .................................................................................................................... 44

Troubleshooting ................................................................................................................ 47

TABLE OF FIGURES

Section B

FIGURE NO. 1 Mounting Position and Devices ............................................................. 32 FIGURE NO. 2 Typical Temperature Probe Wiring ....................................................... 33 FIGURE NO. 3 Typical Humidity Probe Wiring ............................................................ 33 FIGURE NO. 4 Typical Static Pressure Probe Wiring .................................................... 35

FIGURE NO. 5 Typical Water Meter Wiring ................................................................. 35 FIGURE NO. 6 Typical Feed Counter Wiring ................................................................ 36 FIGURE NO. 7 Typical Variable Stage Wiring .............................................................. 37 FIGURE NO. 8 Other Variable Stage Wiring ................................................................. 37

FIGURE NO. 9 Typical 115VAC-Actuator Wiring ........................................................ 38 FIGURE NO. 10 Typical 24VDC-Actuator Wiring ........................................................ 38

FIGURE NO. 11 Typical Power Backup Wiring ............................................................ 39 FIGURE NO. 12 Typical Backup Thermostat Wiring on ON/OFF Stage ...................... 40

FIGURE NO. 13 Typical Backup Thermostat Wiring on Variable Stage ....................... 40 FIGURE NO. 14 Typical V1 and V2 Module Wiring ..................................................... 41 FIGURE NO. 15 Typical Alarm Connection Wiring ...................................................... 42

FIGURE NO. 16 Siren Connection Wiring ..................................................................... 42

TABLE OF CONTENTS

Section C

Control Description ........................................................................................................... 49 Inputs/Outputs Table ................................................................................................................. 52 Standard Equipment .................................................................................................................. 52 Additional Equipment ............................................................................................................... 53 Configuration Version ............................................................................................................... 53 Ventilation System Overview ................................................................................................... 60 Actual Conditions ..................................................................................................................... 61 Set Points .................................................................................................................................. 66 Variable Stages ......................................................................................................................... 68 On/Off Stages ............................................................................................................................ 77 Heaters ...................................................................................................................................... 79 Sprinkler .................................................................................................................................... 83 Air Inlets Position Mode ........................................................................................................... 86 Air Inlets Natural Potentiometer ............................................................................................... 94 Air Inlets Natural Time ............................................................................................................. 96 Air Inlets Static Pressure ........................................................................................................... 99 Air Inlets Setup ....................................................................................................................... 101 Alarms ..................................................................................................................................... 103 Clocks...................................................................................................................................... 110 Feeders .................................................................................................................................... 112 Feed Augers ............................................................................................................................ 115 Lights ...................................................................................................................................... 119 Inflatable Inlets ....................................................................................................................... 125 Minimum Ventilation .............................................................................................................. 127

Page 176: T uch - agrivent.com

INDEX / WARRANTY

Section D-176

Manual Override ..................................................................................................................... 128 Probe Calibration .................................................................................................................... 130 Backup Probes ......................................................................................................................... 132 Test Mode .............................................................................................................................. 133 System Configuration ............................................................................................................. 134 Output Configuration .............................................................................................................. 139 Group Management ................................................................................................................. 141 Password ................................................................................................................................. 144 Turkey/Chicken Scales............................................................................................................ 145 Curve Chicken/Turkey Scale (1-2) ......................................................................................... 150 Bin Scales ................................................................................................................................ 151 Variable Heater ....................................................................................................................... 155 Variable Stir Fans .................................................................................................................... 156 On/Off Stir Fans ...................................................................................................................... 158 Chimneys ................................................................................................................................ 159 Sort Master .............................................................................................................................. 161 Heating Floor .......................................................................................................................... 162 Tech Param ............................................................................................................................ 163 Solarwalls ................................................................................................................................ 164 Input Configuration ................................................................................................................. 166 Water Flush ............................................................................................................................. 167 Alarm Message Table ............................................................................................................. 168 Situational Warning Message List .......................................................................................... 168 Continuous Warning Message List ......................................................................................... 170 Event Message List ................................................................................................................. 171 Motor curve table .................................................................................................................... 172

TABLE OF CONTENTS

Section D

Limited Warranty ............................................................................................................ 177

Page 177: T uch - agrivent.com

INDEX / WARRANTY

Section D-177

LIMITED WARRANTY

The manufactured equipment and supplied components have gone through rigorous inspection to

assure optimal quality of product and reliability. Individual controls are factory tested under load,

however the possibility of equipment failure and/or malfunction may still exist.

For service, contact your local retailer or supplier. The warranty period shall be for two years

from manufacturing date. Proof of purchase is required for warranty validation.

In all cases, the warranty shall apply only to defects in workmanship and specifically exclude any

damage caused by over-voltage, short circuit, misuse, acts of vandalism, lightning, fortuitous

events, acts of God, flood, fire, hail or any other natural disaster. Any unauthorized work,

modification or repair on this product automatically voids the warranty and disclaims the

manufacturer from all responsibility.

The manufacturer assumes only those obligations set forth herein, excluding all other warranties

or obligations. This warranty stipulates that in all cases the manufacturer shall be liable only for

the supply of replacement parts or goods and shall not be liable for any personal injury, damages,

loss of profits, interrupted operations, fines for infringement of the law or damages to the

production of the PURCHASER and the PURCHASER shall take up the defence and hold the

manufacturer faultless regarding any legal or extra legal proceedings, notice, or claim by the

customer or by a third party, and regarding any legal and extra legal expenses and fees brought

forward on by such damages.

Page 178: T uch - agrivent.com

VER: 1.8

October 31, 2014