Sterling Hydronic Unit Heaters. Steam and Hot Water Horizontal and Vertical. Horizontal Unit Standard (Header Type). Available in steam or hot water Casing constructed out of 20 gauge die-formed steel Standard with adjustable horizontal louvers Totally enclosed fan motor standard - PowerPoint PPT Presentation

TRANSCRIPT

Sterling Hydronic Unit Heaters

Sterling Hydronic Unit HeatersSteam and Hot WaterHorizontal and Vertical

1Horizontal Unit Standard (Header Type)Available in steam or hot waterCasing constructed out of 20 gauge die-formed steelStandard with adjustable horizontal louversTotally enclosed fan motor standard(19) Sizes 18-360 MBHCoil connections on top and bottom of unitETLc Certified

Size range vary from 395 CFM to 5,500 CFM. BTU Output/Temperature rise vary based on entering air and water temp/steam pressure.

2Horizontal Standard Coils Cast bronze saddles braised to copper headerCopper tubingAluminum finsFactory tested at 200 PSIMax working pressure 150 PSIMax steam temperature 366 FPipe connections have internal threads for ease of connection

Aluminum fins have a drawn collar to assure permanent bond.

I removed all but one louver when taking this photo to show the coil.3Horizontal Unit - Serpentine

Hot water onlyCasing constructed out of 20 gauge die-formed steelStandard with adjustable horizontal louversTotally enclosed fan motor standard(4) Sizes 8-36 MBH.Coil connections on side of unitOSHA fan guard is standardETLc CertifiedSize range vary from 395 CFM to 5,500 CFM. BTU Output/Temperature rise vary based on enter air and water temp.

Ideal for applications where there is not space to run pipe through the top and bottom of the unit.

4

Horizontal Serpentine Coils Coil is serpentine design with 3/8 copper tubing. Tubing connections shall be 3/8 copper tubing, type MAluminum finsFactory tested at 200 PSIMax working pressure 150 PSIPipe connections have internal threads for ease of connection

Aluminum fins have a drawn collar to assure permanent bond.

5Vertical Louvers (Horizontal Units)Vertical louvers are available as a field installed accessoryAllows for the adjustment of airflow for 4-way air control

6Vertical StandardAvailable in steam or hot waterCasing formed by two square steel platesTotally enclosed fan motor standard(15) Sizes 41-705 MBHCoil connections on top and bottom of unitETLc Certified

Size range vary from 595 CFM to 11,000 CFM. BTU Output/Temperature rise vary based on enter air and water temp.

7Vertical Unit CoilCopper coil with aluminum fins mechanically bonded to the tubesCoils are tested at 375 PSIMax working steam pressure of 75 PSI or hot water up to 225 PSI or 325 FThreaded steel pipe coil connections

8Vertical Low OutputField knock-outs(15) Sizes 34-620 MBHReduced temperature rise

Low Output is converted from a standard unit in the field by removing the knock outs.

Size range vary from 668 CFM to 11,900 CFM. BTU Output/Temperature rise vary based on enter air and water temp.

By opening the knock outs in the back you allow more CFM to flow threw the unit reducing your temperature rise.9Louvers (Vertical)OSHA Fan Guards

Louver Cone DiffuserOSHA Fan Guard is standard on HS serpentine units. Also Standard on HS size 18-48 header style units and optional on coil model HS 60-360 with single phase standard totally enclosed motors only. It is optional on all VS sizes. OSHA fan guards should be used when mounting units below 8 feet per CSA and OSHA requirements. It is also a good idea to use them in applications where someone may be able to touch the fan.

Louvered Cone Diffuser blades can be field adjusted. They are used to increase the maximum mounting height.

Note units can not be ordered with both an OSHA Fan Guard and Louvered Cone Diffuser. It has to be one or the other.

10MotorsExplosion ProofTotally Enclosed

Motors include thermal overload protection and ball bearings. Note depending on unit size and voltage, both motor types may not be available.

HS size 48-108, and 136A = McMillan Electric Compay 6 pole shaded, total enclosed, 1000 RPM.Marathon Electric Explosion proof motor (we dont have the junction box shown)

EXPLOSION PROOF MOTORSAn enclosed motor whose enclosure is designed and constructed to withstand an explosion of a specific gas or vapor which may occur within the motor and to prevent the ignition of this gas or vapor surrounding the machine.Sterling motors comply with the National Electrical Code classification as follows:Class I, Group D; all sizesClass II, Group F; all sizesClass II, Group G; all sizesDivision I & II Installations T-code (T3B)Explosion proof equipment is not generally available for Class I, Groups A and B and it is necessary to isolate motors from the hazardous area. All explosion proof motors are shelf mounted.

11Steam Pressure and Water ControlSteam Pressure ControlStrap on Hot Water Control

U6 - Steam Pressure Control (open on rise in pressure) is a Johnson Controls P47AA-1U7 - Steam Pressure Control (close on a rise in pressure) is a Johnson Controls P47BA-1The P47 steam pressure controls that open on rise are designed for high limit or operating control applications. A typical use is as a limit control on steamheating systems. Models that close on a pressure increase are used on steam unit heaters to avoid blower operation when steam pressure is below the point required for adequate heating.

U5 - Strap on Hot Water Control is a Johnson Controls A-19DAC-12CThis control features a single-pole, double-throw (SPDT) switch and is designed especially for mounting on hot water pipes. As a high temperature operatingcontrol, the contacts open on a rise in temperature. As a low temperature operating control for use on unit heaters, the contacts open on a falling temperature.12Starter and Speed Control SwitchManual Starter5.0 Amp Speed Control Switch

U9 Manual Starters 1 Phase is a General Electric CR101Y1 Manual Full Voltage Starter for single phaseU0 Manual Starters 3 Phase is a General Electric CR1062R3AAP2000 Manual Full Voltage Starter for 3 phase.Manual starters are used as on/off switches but have the added advantage of built in overload protection. It is used in applications where the unit will not be controlled by a Tstat or where additional overload protection is required. *Note: Manual starters ordered for explosion proof motors are not explosion proof, they come in an Nema 1 enclosure. The explosion proof version is just rated for the additional amp draw of the explosion proof motor and should not be located in a space with explosion proof requirements.

U8 5.0 Amp Speed Control Switch - is the KB Electronics KBWC-15K (Only available on HS 108A-136A and 18-108, VS 40-104)Speed control is used to reduce the fan speed resulting in a decrease in CFM and an increase temperature rise. Fans at lower speed will also be quieter. 13Phenolic CoatingV1 Phenolic Coating (Air Dried)The unit is coated with the Heresite VR-514 coating. It is a special primer-finish combination that is specifically designed for salt water services.It is ideal for use in building located on or near the ocean or other large bodies of salt water.

V2 Phenolic Coating (Baked)The unit is coated with the Libcote-7-9818 coating.It is specifically designed for use in moist, wet or damp environments. It is ideal for use in waste water treatment plants or in spaces with excessive amounts of steam or humidity in the air.

Phenolic coatings are used in corrosive environments that would normal shorten the life span of the equipment. The entire unit except the fan motor will be coated.

V5 is V1 applied to the vertical louvers.

V6 is V2 applied to the vertical louvers.14HS TstatsU1- Line Voltage Stat Off/Auto SwitchU2 Line Voltage Stat Auto/Off/Fan SwitchU3 Line Voltage Stat Auto/Off/ Fan Switch

U1 Line Voltage Stat Off/Auto Switch is a Honeywell T451B. Set point range from 50 F to 86 F. Size 4 x 2 15/16 x 1 . -Tstat is powered by line voltage (120 VAC 277 VAC). It has two settings, off and auto. Auto will automatically turn on the fan when the temperature drops below set point. When the temperature rises above the set point, the fan will turn off.

U2- Line Voltage Stat Auto/Off/Fan Switch is a Honeywell T4051A 1003. Temp range 50-80 F. Size 5 x 3 1/8 x 1 5/8. -Auto will automatically turn on the fan when the temperature drops below set point. When the temperature rises above the set point, the fan will turn off. The fan switch allows the user to force the fan on. Single Pole Single Throw. Includes Subbase Q651A1009.

U3- Line Voltage Stat Auto/Off/Fan Switch Heavy Duty is a Honeywell T6051A. Temp range 50-80 F. Size 6 3/8 x 5 13/16 x 6 1/16. -Same as U2 (120VAC or 240 VAC) but can also do cooling. Single Pole Double Throw. Includes Subbase Q651B1008

Both U2 and U3 are Heavy Duty15Tstats ContinuedU4 Celsius Line Voltage Thermostat(Fahrenheit version shown)W1 T6169C Line Voltage Thermostat w/Subbase (Light Duty) (VS Only)

U4 Celsius Line Voltage Thermostat is a Johnson Controls T46ABH-1C with face plate. The faceplate is what is Celsius (Johnson Controls p/n PLT333-5R). Size 4.84 x 4.71 x 1.75. Range 10-32 degrees Celsius.Has a auto-off-fan settings. -Auto will automatically turn on the fan when the temperature drops below setpoint. When the temperature rises above the set point, the fan will turn off. The fan switch allows the user to force the fan on. 120-277 VAC

W1 T6169C Line Voltage Thermostat w/ Subbase is a Honeywell T6169C4015. Size 4.488 x 4.606 X 1.732. Range 44-86 degree Fahrenheit. Unit runs off 120-270 VAC. Has Auto/Off setting. -Auto will automatically turn on the fan when the temperature drops below set point. When the temperature rises above the set point, the fan will turn off.

16VS TstatsW2 T4051A Line Voltage Thermostat (Heavy Duty)W4 Q651A1009 Stat Subbase Only (Used with T4051A1003 for Off/Auto Switch)

W2- Line Voltage Stat Auto/Off/Fan Switch is a Honeywell T4051A 1003. Temp range 50-80 F. S