Page 1: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

North American Water Loss Conference

2017

Expert Guidance on Automatic Meter Reading

(AMR) & Advanced Metering Infrastructure (AMI)

Don Schlenger, Don Schlenger & Associates

David Hughes, American Water

Page 2: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Topics

•Quick Overview of AMR/AMI

•Feasibility Study/Business Case

•Planning and Managing Successful Deployments

•AMI-Based Business Processes and Policies

•Using AMI/AMR to Help Manage Revenue Loss

•Using AMI/AMR to Help Manage Water Loss

Page 3: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Automatic Meter Reading (AMR)

• Handheld or mobile• Multiple reading stored with

some systems

• Some systems convertible to AMI

Page 4: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Fixed Network Radio AMI

• Redundant data collectors• Multiple readings per day• Some systems offer two way

communication w/MIU

• Sensors and controllers• Multi-point access to data• Analytics

Neighborhood

Data

Collection

Unit

Control Computer

(Head-End

System)

Encoder

Register

Meter

Interface

Unit

Meter

Data Mgt.

System

Ancillary

Device

(Leak Detector)

Interfaces

to other

Systems

CIS

Work

Order

Others

Data “Backhaul”

Customer

Portal

Meter

Base

Page 5: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Mesh Network Architecture Extends the Reach of AMI

MIU DCU

MIU

MIU

MIU

MIU

DCU

DCU

DCU

ControlComputerReceiver

MIU

MIU

MIU MIU

MIU

MIU

MIUMIU

MIUMIU

MIU

MIU

“Modified” or “partial” Mesh Network

“Full”MeshNetwork

T2 NetRelay

Device

Courtesy MuellerSystems

Page 6: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Cellular Communication Networks for AMI and Monitoring

• Some AMI vendors use existing cellular networks• Verizon, ATT developing utility services • New small-cell networks• Cloud data storage• Scalable• Two-way communication

Metron-Farnier/TT CDMA

integrated register

Technolog/Cello

Data Recorder

Badger Orion/Beacon

Cellular Endpoint

Page 7: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

• Comcast expands LoRaWAN™-based MachineQ network and service platform to Atlanta, Baltimore, Boston, Denver, Detroit, Indianapolis, Miami, Minneapolis/St. Paul, Oakland, Pittsburgh, Seattle, and Washington D.C.

• Itron has developed their own LPWAN (Riva) Two Way

• New technologies demanding new interoperability and standardization

AMI Services Part of the Internet of

Things (IOT)

Itron Open Way RIVA

Comcast MachineQ Coverage Philadelphia Area

Page 8: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Cloud Computing Is Enabling the “Virtualization” of AMI

• Lower capital costs

• Less utility IT support needed

• Lowers the barrier to entry

DCU

MIU

MIU

MIU

Communications

Server

Data and

Application

Servers

Utility CSRs and

Other Users

End

Customer

Portal

Utility

CIS

Page 9: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

North American Water Utility Market for AMR/AMI

Source: The Scott Report on AMR and AMI Deployments, 2015

*Includes AMI and AMI-capable devices

Page 10: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

North American Water Utilities Are Increasing Turning to AMI

• Almost all recent RFPs are for AMI, not mobile AMR

• Many RFPs include SmartCities, Internet of Things Components

Source: IMS Research

Page 11: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

AMI Projects Require Careful Consideration

•Expensive

•High profile

•High impact

•Technology and business risks

•Enable/require major changes

•Not always suitable, justifiable

•Require thorough planning, management and support

Page 12: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Most Water Utilities Require a Business

Case (Benefit /Cost) or Feasibility Study

Page 13: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

MIUs Repeaters

Fixed Data

Collection

Units

Head-End

Software

Meter Data

Mgt. System

Meter

RegistersMeters

Pressure

Sensors

Lids

Connectors

Endpoint

Installation

Project

Mgt.

Handheld

Programmers/

Testers

Network

Installation

Installation

Mgt. Software

Business

Process

Design;

Change Mgt.

Financing

Antennas

Performance

Contracting

Remote

Controlled

Shut-Off

Leak

Detectors

Leak

Detection

Software

Leak

Detection

Monitoring

Feasibility

Study

Network

O&M;

NaaS

Software,

Hosting.

SaaS

Application

Development

Meter

Reader

Routing

Marketing,

PR

Data

Analytics

Servers

Handheld

Mgt. System

Programming

Testing Software

Mobile

Data

Collectors

Handheld

Data

Collectors

Inventory

Control

Scrapping

Customer

Portal

CIS

GIS

FIS

CMMS

Asset

Mgt.

Utility

Systems

Advanced Metering Infrastructure Projects Contain Many Components

Project/

Program

Mgt.

Integration/

Testing

Page 14: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Hierarchy of Benefits

Enhance customer service, monthly billing,

proactive notification, meter mgt., revenue

protection, customer self-service 2nd – Tier Benefits from

Process Reengineering

Accurate bills. Reduce manual

meter reading, estimated bills,

rereads, final read visits

HIERARCHY OF AMI BENEFITS

1st – Tier Basic Benefits

From Automation

Service customization, sub-metering,

backflow monitoring, non-revenue water

analysis, distribution system optimization

3rd Tier

Benefits

Incorporating

Industry Best

Practices

Page 15: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

High Bill Dispute Call with AMI

Billing concern/

dispute call

IVR tells customer to look at Web

portal

Calldrops

Note: “Abandoned” call here is OK

Customer “self-serves”

Y

CSR accesses consumption history in MDMS, looks for leaks,

high consumption, reviews with customer

CSR reviews last bills, ABC, info in CIS, asks

customer about possible

explanations

Customersatisfied?

Customersatisfied?

SignedUp?

CSR checks if customer signed up for notifications

CSR encourages customer to enroll or enrolls customer

End of transaction

CSR offers to show customer how to access

consumption history

Customersatisfied?

CSR offers to mail customer detailed

consumption history

Customersatisfied?

End of transaction

End of transaction

FieldInvestigation

Required

End of transaction

Spvr/Mgr. creates Service

Order

N Y

Y

Y

Y

N

N

NY

N Y

N

Spvr./Mgr. reviews account

Spvr./Mgr. makes determination,

notifies customer

Letter Provided to Customer

End of transaction

End of transaction

•Fewer calls

•Longer calls

•Fewer truck rolls

•Fewer leak adjustments

Page 16: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

AMI Enables/ Requires Significant Changes

in Processes/Policies to Be Cost-Effective

Page 17: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Notifying Customers of Leak Before They Get High Bills

versus

Page 18: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Leak Notification Considerations

•Threshold – high flow, continuous flow, intermittent flow

•Threshold – high bill versus nuisance

•How long to wait before notification

•How often to notify

•How to notify

Page 19: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Example: Consumption Profile Doesn’t

Show Continuous Consumption

Page 20: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Fraction of Customers Use Web Portal

Registered Users, % Quarterly Active Users, %

Data courtesy WaterSmart Software

Page 21: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Other Things Needed to Make an AMI System Effective (e.g., Leak Notification)

• Ability to contact customers (technology, resources)

• Up-to-date customer contact info (email addresses, cell phone nos.)

• Rules, algorithms (thresholds, contact frequency, etc.)

• Access to detailed consumption data (web portal, etc.)

• Analytics (“deeper dive;” customers don’t just want data)

• Customer profile info (e.g., pool, irrigation system, humidifier)

• Customer choices and options (e.g., can set thresholds)

• Revised business processes and policies (e.g., final read)

• Education and outreach

• Employee and customer behavioral changes

• Maintenance

Page 22: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

AMI Can Support Non-Revenue Water Management

•Theft of service

•Consumption (e.g., leak) adjustments

•Loss of service and consumption charges during “vacant”

status

•Arrears/bad debt write-off

• Inaccurate meters

•Distribution system leaks

To be discussed in greater detail in the

second half of this learning module.

Page 23: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Recovering Lost Revenues from Move-out/Move-in Policies

• Part of water bill covers infrastructure to provide water, which is always there

• Service is to the property, not the person

• Move-out customer should not be allowed to retire from service without sign-

up from move-in customer

• With AMI (or AMR), utility has a meter reading on the date of property closing

• Recorded deed available

• Rental properties: require and enforce 3-party agreements, landlord

reversion clause

• Service stays on unless property owner wants it shut off

Page 24: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Reducing Revenues Lost Through “Courtesy” Adjustments

• AMI/MDMS can identify leaks and high usage close to when they occur

• Encourage customers to sign up to receive leak and high use notification

• Keep track of notifications

• Limit adjustments to those customers who have signed up for notification

• Limit adjustments to close to the point in time when the customer was notified

• Make sure property managers are aware of leaks/high usage in rentals

Page 25: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Using AMI to Help Reduce Arrears/Write-Offs

• Offer to move fixed income customers to end-of-month reading cycle to bill

comes at beginning of month

• Offer analysis of water usage to help customers avoid leaks and save money

• Many customers do not have same level of computer literacy or access

• “Bill the property;” use liens, 3-party agreements

Page 26: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Replacing Older Meters Can Recover Lost

Revenues to Offset Project Cost

Page 27: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

AMI-Based Acoustic Leak Detection Could Enhance Business Case

Page 28: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Incorporating Non-traditional Drivers Helps Build the Business Case

•Effective Utility

Management

•Customer Satisfaction

•Social Benefits

•Environmental Benefits

Page 29: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Advances in AMI and Metering Offer New Opportunities

•Remote shut-off

•Pressure, temperature sensors

• Irrigation control

•Distribution system monitoring

•AMI-based hydrant flushing

•Street lighting control, etc.

Photos courtesy

Mueller Systems

Backflow AnalysisPressure Monitoring Valve Position Sensor

Photos courtesy

Mueller Systems

Photo courtesy

Sensus

Remote

Shutoff

Page 30: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

AMI/AMR Procurement Considerations

•Procurement strategy: turnkey vs. multiple solicitations;

design-build; performance contracting

•Targeted/strategic vs. full-scale

•Own and operate vs. hosted and managed services

•Evaluated bid approach; weighted selection criteria

•Defensible selection process

•Performance specs (e.g., read success rate) vs. design specs

•Warranties (component and system)

•Testing and acceptance criteria

•Draft contract

•Scope of work distilled

from RFP and proposal

Page 31: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

AMI/AMR Implementation Considerations

•Data collector location

•Backhaul

•Connectors, lids

•Head-end software and hardware

•Meter data management system and customer

portal software and hardware

•Configuration, interfaces, integration

•Disaster recovery

• Installation procedures, dealing with anomalies

• Inspection and approval

•Sequencing of installations

•Data control and audit trailPhoto courtesy GridOne

Photo courtesy Neptune

Page 32: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Multi-part Implementation Plan

•Schedule

•Budget and financing

•Project staffing

•Human resources plan

•Change management

•Communications

•Meter reading transition

•Network deployment

• Installation procedures

• Installation control

system

•Materials handling

• IT interfaces

•QA/QC

•Policy and procedure

review and redesign

•Training

•Project governance

Page 33: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

IT Systems and Integration During AMI Deployment

Page 34: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Operation and Maintenance Protocols

•Maintaining system components and performance

•Response to missed reads (ability to estimate; tolerance for

estimates)

•System performance (trends, performance standards,

alert/alarm protocols, noise on frequency)

•Physical inspections

•Audits, manual reads, field inspection of meter sets

•Preventive maintenance on network

•Staffing

• Monitoring, maintaining system components and performance

• Production, data and database management

• Training, super-users

• Application development

Page 35: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Critical Success Factors After Implementation

•Triaged response to missing reads, alarms

•Active monitoring of system health

•Audits, manual reads

•System “owners:” operator, super users, etc.

•Change processes and policies

•Execute human resources plan

Page 36: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Using AMI to Reduce

Nonrevenue Water

David M Hughes

American Water

Page 37: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Overview

• Using AMI features to reduce apparent losses

– Tamper Alarms and Backflow Detection

– Comparative Analysis

– Selected “Spot AMI” Customer Interface

• Review AMI role with leakage management

– District Metering

– Conduit for acoustic monitors

– Conduit for pressure and flow monitors

Page 38: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Using AMI to Detect Tampering and Theft of Service

• Systems have different tamper measures– Cut wires

– Magnetic disruption

– Disconnected register

– Alignment

– Dewatered meter

– Loss of encoder signal

Meter register

displaced

Strong magnets

placed at meter

Page 39: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Using AMI to Detect Customer Issues

• Time stamping, frequent measurements identify time of activity, quantify of water unreported.

– Most AMI systems now look at 1 hour intervals (and some are as little as 5 minutes.

• Interface with customer service systems provide direct alerts to customers, comparative use feedback.

• New devices are coming on line as part of IOT to help customer provide even more control

Page 40: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Backflow Alarms

• Found in AMI, but available in some AMR systems

– Different AMR systems have different thresholds and durations

(as low as 0.1 gallons every 15 minutes).

– Requires granular reads as reverse flow is often small

– Research found evidence that flows up to 1.5 gallons might be

expansion of water from hot water heaters.

– Can help utility find operational and customer issues

Project # 4384

Page 41: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Backflow alarms in one time in multiple locations

• Often an indicator of operation issuesWhy would an area of meters have reverse flow?

– Main breaks

– Pressure surges

– Field operations

– System integrity issues

What is happening?

– Draining customer plumbing including hot water tanks

– Potential cross connection hazard

Project # 4384

Page 42: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Backflow alarms in one location multiple times

• Often an indicator of customer issuesWhy would one meter have reverse flow multiple times?

– Cross connection

– Meter error

– Meter set backwards

– Tampering

What is happening?

– Potential cross connection hazard

– Water is really running positive but registering negative

Project # 4384

Page 43: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Backflow Investigation Example

• Detect clusters from main breaks, suspicious

repeat activity

Page 44: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Using AMI to Find Unusual Changes in Use

• Consider grouping meters with common application (hotels, schools, or restaurants, for example)

– BWSC compared hotel use (gallons/month/rooms) and found water waste and under-registration of use

• Consider historical analysis of volume

– Month to month reduction may indicate an underperforming meter.

– But not always as occupants change, uses change

Page 45: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

45

Using AMI to Optimizing Meter Type and Size

• Underperforming meters with profiles Under-registration at low flows

Inappropriate meter type

Inappropriate meter size

• Site visit suggested Piping Issues

Open bypasses,

Inappropriate use of fire lines

Meter environment

Daily Breakdown of Water Use

Compound Meter

Page 46: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Individual Customer AMI

• Monitoring of individual accounts with cellular AMI

can improve service for customers, large or small– Reads at higher frequency,

– Customer may want (be willing to pay for) access

Page 47: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

AMR/AMI-Based Non Revenue

Water (NRW) Recovery• Authorized Uses

– Hydrant activity

• Apparent Losses– Meter Accuracy

– Tampering

– Bypassing

– Backflow

• Real Losses– Distribution System Leak Detection

Page 48: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Using AMI to Reduce Loss

Tamper Alarms and Backflow Detection

Comparative Analysis

Selected “Spot AMI” Customer Interface

• District Metering

• Distribution System Acoustic Leak Detection

• Distribution Sensors

Page 49: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Quantifying NRW

• 12 Month Rolling Average used for NRW

– Minimizes gap between reads and production meters

– Monthly difference between water delivery and versus

metered sales has variables

February had 29 days,

January and March 31

June 30 days, May and

July 31, hot end of June

September 30 days, July

and Oct 31 days, cool

end of September

Leaks may increase

toward year end

Page 50: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Monitoring NRW - District Metering

• District metering monitors

net flow into a small portion

of a large system (or an

entire small system or

zone)

• For many systems regular

comparison of minimum

night flow helps detect

leakage.

Page 51: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Finding leaks

• District (Subsystem) Metering

– Requires accurate master meter to capture full range

of flows

– Observing daily patterns and monitoring night flow

can help identify leakage events (and repair)

51

Pressure

Flow

Page 52: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

52

Pressure

Flow

Using AMI with District Metering

• Today’s AMI can provide reads at end of each day

and some every hour on the hour

– This will allow a DMA to analyze NRW by the day or

hour

– Calculation must include adjustments for any storage

– Knowing the hourly pattern of NRW can help

determine the type of NRW in the system.

– Can also help identify meter errors

and inaccuracy master meters

Page 53: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Characterizing Leakage NRW

53

Page 54: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Characterizing Apparent NRW

54

Page 55: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

District Metering Flow Anomalies

• Simple profiles of small zones can be effective at detecting

anomalies in water consumption

• Flow monitors can aid in large meter calibration and pump

efficiency

Page 56: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

District Metering Flow Anomalies

• Simple profiles of small zones can be effective at detecting

anomalies in system operations

Page 57: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Dynamic District Metering

• With a sufficient number of pressure

and flow nodes and a calibrated

hydraulic model, an entire system can

be assessed

– Lower than expected pressure at all times of

the day, a continuous unexpected demand is

suspected = leak.

– Lower than expected pressure during the day

only suggests an unaccounted for demand

that is present when other water use is

suspected = billing error, bad customer meter

or unauthorized use.

Page 58: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Dynamic System Monitoring

58ENABLING TECHNOLOGY

Networks, Compute, Storage, Integration, Cloud, Mobile, Security…..

SOURCE OF SUPPLY• Source water protection• Source water monitoring• Source water treatment

WASTE WATER TREATMENT• Remote, automated, &

connected sensors with operations

• Mobile Operator• Advanced treatment & Reuse

Environment & Water Quality• Integrated Environment, Health and

Safety system• Remote mobile water quality

management • Water quality system & dashboard

CUSTOMER• Customer usage management• One view of the customer with

more self service• Proactive outage, usage and

leak notification• Customer segmentation

FLEET• Vehicle analytics• Integrated digital

vehicle with systems• Location awareness

FIELD WORKER• Digital field worker• Field document access• Single view of the work• Mobile access to

visually mapped work, assets and customers

DISTRIBUTION• Geo Located (GIS)• Integrated connected sensors• Flexible AMI and District Metering • Leak detection• Automated demand planning

WATER TREATMENT• Remote, automated, & connected

sensors with operations• Mobile operator• Renewable energy optimization• Advanced integrated treatment• Plant analytics

REMOTE FACILITY• Integrated sensors• Real time hydraulic model• Asset management & predictive

maintenance• Redundant network connectivity

ENABLING CORPORATE SYSTEMS• Enterprise ERP, CIS and EAM• Automated Financial Planning• Seamless/automated procurement

EMPLOYEE / WORKFORCE• Safe Working Environment• Real-time Collaboration• Mobile Corporate Services

• Enterprise data management, reporting and analytics• Records management and archiving• Unified mobile email and collaboration systems

• Advanced revenue analytics• KRONOS Time Entry• Capital Project Planning• Automated Inventory Lifecycle Management

Page 59: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Using AMI for Distribution System

Acoustic Leak Detection

• Acoustic monitoring systems with AMI provide routine leak detection– FCS, Gutermann, Metrotech devices attaches to

valve nut in street, transmits separately from meters

– Mueller device is placed in hydrant cap

– Itron MLOG units attach to service line near meter

• Uses RF and cellular systems

• Find leaks sooner, easier to repair

• Reduce crews/improve service levels

Page 60: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Computing the Cost/Benefit of

Acoustic Monitoring

• Capital Expense (amortized over life of units)

• Operating Costs and Benefits

Operating Costs Operating Savings

Maintenance of System Reduction in Water Loss

Analyses of Data Reduction in Damage

Field Investigations Reduction in Repair Costs

Additional Repairs Improved Repair Environment

Page 61: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

DMAs vs Acoustic Monitoring

• District Metering indicator for large leaks

• District metering can help quantify NRW

• Acoustic monitoring identifies small leaks

with potential to reduce loss and damage

• Acoustic monitoring can better pinpoint

the area of investigation for the leak

Page 62: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Shutoff Valves

• Shutoff valves for individual customers can

be a service as well as a deterrent to non

paying customers

• The case of freezing pipes

• The case of common curb stops

• The concern for water quality compromise

during shutdowns and emergencies

Page 63: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Summary

• Features like Backflow Detection and Tampering, Flow Analysis reveals customer issues

• The use of cellular systems to deal with isolated cases is a consideration for non AMI networks

• District Metering works well with AMI with accurate metering

• AMI can facilitate the communication system for acoustic leak detection, system monitoring and shutoff valves

Page 64: North American Water Loss Conference 2017 · Data Collection Unit Control Computer (Head-End System) Encoder Register Meter Interface Unit Meter Data Mgt. System Ancillary ... Fixed

Questions

Dave Hughes

[email protected]

Don Schlenger, DS&A, LLC

[email protected]