stationary meter test system · meter position, to reality the automatic calibrate of electronic...

3
Stationary Meter Test System GENY's meter test systems adopt the most advanced electronic measurement technique and modular concept,combining the different reference standards and power amplifier to meet customers ' requirements in electric power departments, electric energy meter manufacturers,measuring and quality examining departments and factories or enterprises.  The meter test systems can measure mechanical meters, electronic watt-hour meter s and smart meters by the way of automatic, semi-automatic or manual operation.  Aluminum alloy material, light and strong and corrosion resistant.  Automatic positioning rotor mark of disc of mechanical meter, with more efficiency.  The swing together of the scanning heads simplifies the control.  Starting Test and Creeping Test.  Measuring different constants of meters synchronously.  With the protection function of overload, short voltage circuit and open current circuit.  The testing software with friendly Window 2000 and XP operation system, includes functional module of all kinds of modern energy meter needed, to reality error test, harmonic test, demand test , influence test etc.  The stored testing data can be transferred to multi-format for other program use. YC1891D Single Phase Meter Test System  Meters under testing: 3P4W, 3P3W, 1P2W  Testing mode: active power, reactive power, cross connected reactive power  Installing the ICT in each meter position to test three-phase meters with closed links between the current and voltage measuring circuits  Neutral current test  Installing RS232, Ethernet communication port in each meter position, to reality the automatic calibrate of electronic meter YC1893D Three Phase Meter Test System  Meters under testing: 1P2W  Testing mode: active power, reactive power  With MSVTcan test single-phase meters with closed links between the current and voltage measuring circuits (I-P links)  With current output switchcan calibrate 2- element metersoptional Installing Rs232, Ethernet communication ports in each meter positionto realize automatic calibration of electronic metersoptional1 Features & Functions: Features & Functions:

Upload: others

Post on 09-Feb-2020

6 views

Category:

Documents


0 download

TRANSCRIPT

Stationary Meter Test System

GENY's meter test systems adopt the most advanced electronic measurement technique and modular concept,combining the

different reference standards and power amplifier to meet customers ' requirements in electric power departments, electric

energy meter manufacturers,measuring and quality examining departments and factories or enterprises.

  The meter test systems can measure mechanical meters, electronic watt-hour meters and smart

meters by the way of automatic, semi-automatic or manual operation.

  Aluminum alloy material, light and strong and corrosion resistant.

  Automatic positioning rotor mark of disc of mechanical meter, with more efficiency.

  The swing together of the scanning heads simplifies the control.

  Starting Test and Creeping Test.

  Measuring different constants of meters synchronously.

  With the protection function of overload, short voltage circuit and open current circuit.

  The testing software with friendly Window 2000 and XP operation system, includes functional module of all

kinds of modern energy meter needed, to reality error test, harmonic test, demand test , influence test etc.

  The stored testing data can be transferred to multi-format for other program use.

YC1891D Single Phase Meter Test System

  Meters under testing: 3P4W, 3P3W, 1P2W

  Testing mode: active power, reactive power,

cross connected reactive power

  Installing the ICT in each meter position to test

three-phase meters with closed links between

the current and voltage measuring circuits

  Neutral current test

  Installing RS232, Ethernet communication port in each

meter position, to reality the automatic calibrate of

electronic meter

YC1893D Three Phase Meter Test System

  Meters under testing: 1P2W

  Testing mode: active power, reactive power

  With MSVT,can test single-phase meters with

closed links between the current and voltage

measuring circuits (I-P links)

  With current output switch,can calibrate 2-

element meters(optional)

  Installing Rs232, Ethernet communication ports

in each meter position,to realize automatic

calibration of electronic meters(optional)

1

Features & Functions:

Features & Functions:

YC1891D-6 YC1891D-12 YC1891D-24 YC1891D-48

Number of meter positions 6 12 24 48

Accuracy 0.02%

Power Source YCS-101-250 YCS-101-600 YCS-101-1200 YCS-101-2500

Standard Meter SZ01A-K3Е

MSVT HJ200G-6 HJ200G-12 HJ200G-24 HJ200G-48

Scanning Head YCG-2-series

Voltage

Test voltage output(Phase-Neutral) 24V – 288V (or customized)

Power of the voltage output 100VA 250VA 500VA 1000VA

Resolution Better than 0.01% of full scale value of range

Setting accuracy Better than 0.05% at the final range value

Stability Better than 0.005%/h (integration time 150 s)

Load regulation from 0-max. load Better than 0.01%

Distortion factor Better than 0.3% for linear resistance load

Harmonics 2nd– 21st free programmable

Current

Test current output 1mA – 100A(or customized,Max.200A)

Power of the current output Max.150VA Max.350VA Max.750VA Max.1500VA

Resolution Better than 0.01% of full scale value of range

Setting accuracy Better than 0.05% at the final range value

Stability Better than 0.005%/h (integration time 150 s)

Load regulation from 0-max. load Better than 0.01%

Distortion factor Better than 0.3% for linear resistance load

Harmonics 2nd–21st free programmable

Phase angle

Range 0 -- 360°

Resolution 0.01°

Setting accuracy 0.1°

Frequency

Range 45Hz – 65Hz

Resolution 0.01Hz

Error display

Type of error display Red LED

Resolution of the error displays 8 digits

Other

Voltage Supply220V±10% or customized

50/60Hz±2Hz3x220/380V±10%

50/60Hz±2Hz

Ambient temperature -10°C -- +40°C

Relative humidity 35% -- 85%

2

Specifications:

Stationary Meter Test System

Accuracy 0.02%

Voltage

Test voltage output (Phase-Neutral) 3x(24V – 288V) (or customized )

Power of the voltage output Max.3x100VA Max.3x250VA Max.3x500VA Max.3x1000VA

Resolution Better than 0.01% of full scale value of range

Setting accuracy Better than 0.05% at the final range value

Stability Better than 0.005%/h (integration time 150 s)

Load regulation from 0-max. load Better than 0.01%

Distortion factor Better than 0.3% for linear resistance load

Harmonics 2nd – 21st free programmable

Current

Test current output 3x(1mA – 100A)

Power of the current output Max.3x150VA Max.3x350VA Max.3x750VA Max.3x1500VA

Resolution Better than 0.01% of full scale value of range

Setting accuracy Better than 0.05% at the final range value

Stability Better than 0.005%/h (integration time 150 s)

Load regulation from 0-max. load Better than 0.01%

Distortion factor Better than 0.3% for linear resistance load

Harmonics 2nd – 21st free programmable

Phase angle

Range 0 -- 360°

Resolution 0.01°

0.1°

Frequency

Range 45Hz – 65Hz

Resolution 0.01Hz

Error display

Type of error display Red LED

Resolution of the error displays 8 digits

Other

3x220/380V±10% (or customized)

50/60Hz±2Hz

Ambient temperature -10°C -- +40°C

Relative humidity 35% -- 85%

Power Source YCS-103-250 YCS-103-600 YCS-103-1200 YCS-103-2500

Standard Meter EMH SRS 400.3 / SZ03A-K8

Scanning Head YCG-S Series

YC1893D-6 YC1893D-12 YC1893D-24 YC1893D-48

Number of meter positions 6 12 24 48

Setting accuracy

Other

Voltage supply

3

Specifications:

Stationary Meter Test System