L.V Technical Data

Page 2: L.v tech presentation 2

Outline

Introduction about LV SWG.

Alfanar LV products.

Alfanar Terasaki.

Alfanar’s Approvals.

Page 3: L.v tech presentation 2
Page 4: L.v tech presentation 2

Introduction for LV electrical characteristics

Circuit-breakers:Disconnect and connect the power and provide protection for cable, load and human against overload and overcurrent.

The following are the type of the CB:MCB, RCCB, RCBO, MCCB, ICCB, ELCP, MCP, Power circuit and ACB.

Rated operational current (In, Ie): Continuous current Without overheating

Rated operational voltage (Ue):This is the voltage at which the equipment has been designed to operate, in normal (undisturbed) conditions

Page 5: L.v tech presentation 2

Rated insulation voltage (Ui) for Circuit-breakers:This is the value of voltage to which the dielectric tests voltage and Creepage distances are referred too. The Ue ≤ Ui

Rated impulse-withstand voltage (Uimp) for Circuit-breakers:This characteristic expresses, in kV peak, the value of voltage which the equipment is capable of withstanding without failure, under test conditions. Generally, for industrial circuit-breakers, Uimp=8kV and for domestic types, Uimp=6kV, and in special cases could be 12KV

Rated ultimate short-circuit breaking capacity (Icu):The maximum current, that can be broken across the contacts, twice times without being damage.

Introduction for LV electrical characteristics

Page 6: L.v tech presentation 2

Rated service short-circuit breaking capacity (Ics):The maximum current, that can be broken across the contacts, without being damage.

Rated short-time withstand current rating (Icw): Is the maximum current, that the B category CB can withstand, thermally and electro dynamically, without sustaining damage, for a period of time given by the manufacturer.

Category A: For which there is no calibrate delay in the operation of the “instantaneous” short-circuit magnetic tripping device.

Category B: For which, in order to discriminate with other circuit-breakers on a time basis, it is possible to delay the tripping of the CB, where the fault-current level is lower than, that of the short-time withstand current rating (Icw) of the CB.

Introduction for LV electrical characteristics

Page 7: L.v tech presentation 2

Co-ordination study:

Discrimination/Selectivity:Is the Co-ordination of protective device such that a fault is cleared by the protective device installed immediately upstream of the fault, and by that device alone.

Total Discrimination:Discrimination is said to be total if the downstream circuit breaker opens and the upstream circuit breaker remains closed. This ensure maximum availability of the system.

Partial Discrimination:Discrimination is partial if the above condition is not fulfilled up to the prospective short-circuit current, but to lesser value, above this value both circuit breakers could open, resulting in loss selectivity.

Cascading/Backup:Is a technique where the current limiting capability of upstream circuit breakers is used to permit the installation of lower circuit breakers downstream.

Introduction for LV electrical characteristics

Page 8: L.v tech presentation 2

Introduction for LV electrical characteristics

Discrimination/Selectivity:

Cascading/Backup:

Page 9: L.v tech presentation 2

Introduction for LV Mechanical characteristics

Ingrees of Protection (IP X X):Standard IEC 60529 (February 2001) indicates the degree of protection provided by electrical equipment enclosures against accidental direct contact with live parts and against the ingress of solid foreign objects or water.

Page 10: L.v tech presentation 2

IK Code “Mechanical Impact test:The European standard EN 50102 dated March 1995 defines a coding system(IK code) for indicating the degree of protection provided by electrical equipment enclosures against external mechanical impact.

Introduction for LV Mechanical characteristics

Page 11: L.v tech presentation 2

Separation Forms:

Introduction for LV Mechanical characteristics

Page 12: L.v tech presentation 2

Form IEC standard definition Specific recommendations

1 No Internal separation Protection over busbar for customer

safety

2a Separation of busbars from the functional units Terminals not separated from busbars

2b Separation of busbars from the functional units Terminals separated from busbars

3a Separation of busbars from the functional units

and of all functional units from each other.

Terminals not separated from busbars

3b Separation of busbars from the functional units

and of all functional units from each other.

Terminals separated from busbars

4a Separation of busbars from the functional units

and of all functional units from each other, also

separation of terminals from any functional unit

Terminals in the same compartment

as associated functional units.

4b Separation of busbars from the functional units

and of all functional units from each other, also

separation of terminals from any functional unit

Terminals are not in the same

compartment as the associated

functional units

Introduction for LV Mechanical characteristics

Page 13: L.v tech presentation 2

IEC 61439:Is a series of standard IEC 60439

Fundamental change:• The categories of TTA (Type Tested Assemblies) and PTTA (Partially

Type Tested Assemblies) have been discarded in favor of a design.

• The performance of assemblies is now determined by a “Design Verification”.

IEC 61439 Vs IEC 60439:

Page 14: L.v tech presentation 2

Arc Flash protection:International standards (IEC / ANSI) guidelines are different but the objectives are the same,i.e. defining minimum safety level for operators

Assessment criteria for the internal arc test:• Correctly secured doors, covers, etc. do not open.• Parts of the assembly (which may cause a hazard) do

not fly off.• Arcing does not cause holes in the external parts of

the enclosure.• Indicators do not ignite (made from black cretonne).• The protective circuit is still operational.• The arc is to be confined in the same area where it

was ignited.

If these criteria are achieved by the panel, then the test is a success.

Arc Flash protection:

Page 15: L.v tech presentation 2

Seismic :Proper mounting of the equipment is the single most important factor in withstanding a seismic event. The foundation must be level and continuous under the entire assembly. The foundation must be designed to withstand the reaction loads imposed on it by the equipment during a seismic event.

Earth quake protection (Seismic):

Page 16: L.v tech presentation 2

Product Portfolio :

Main Distribution Switchboards

ATS, Synch, 2 out of 3

Motor Control Center (MCC)

Control Panels & Panel Boards

Power Factor Correction Capacitors (PFC)

Switch rack

ICP

alfanar L.V Factory:

Page 17: L.v tech presentation 2

• Applicable standards IEC 61439-2

• Ie Up to 6300A (No derating up to 6100A, tested at 40° C)

• ICW 100kA/1 sec or 50kA/3 sec

• Ue 690Vac/600Vdc

• Ui 1000Vac

• Uimp 12KV

• Form Form 1 to Form 4B

• Internal Arc Withstand 65kA/300 mSec (Upon Request)

• Seismic Withstand 8 on Richter Scale (Standard Feature)

Alfanar-Terasaki

alfanar L.V SWG:

Page 18: L.v tech presentation 2

Who is TERASAKI ?

Alfanar Low Voltage equipment:

Page 19: L.v tech presentation 2

ALFANAR TERASAKI Breakers:

Tem Power-2 is ACB made in Japan up to 6300A/135kA.

TemBreak2 is MCCB made in Japan up to 1600A/200kA.

TemDin2 is MCB made in France up to 125A/15KA.

All ACBs & MCCBs tested under 50°C w/o derating.

Alfanar Low Voltage equipment:

Page 20: L.v tech presentation 2

Air Circuit Breakers (World Class Circuit Breakers): Ie=800A to 6300A Icu=Ics=Icw/1sec Ue=690Vac/600Vdc Ui=1000Vac Uimp=12KV Three frame size (800-2000A, 2500-4000A and 5000-6300A) Fixed or Withdrawable (Front, vertical or horizontal connection) Manual or Motor charging Comply with IEC 60947-2 Comply with ANSI C37.13 and NEMA PUB NO.SG3 3P or 4P Category B Trip Unit is AGR (L, R for general feeder or Transformer and S for

generator protection)

Alfanar Low Voltage equipment:

Page 21: L.v tech presentation 2

Protection Relays:The Tem Power-2 series is equipped with an RMS sensing over-current release AGRB AR Protection Relay samples& calculates the load current every (500 micro seconds).

Alfanar Low Voltage equipment:

Page 22: L.v tech presentation 2

Harmonic Monitoring:TemPower 2 AGRs can detect & protect up to the 31th Harmonic.

Protection Relays:The Phase Rotation Protection function detects the negative phase current occurring due to reverse phase or phase loss and prevents burnout of aMoto or damage to equipment.

Alfanar Low Voltage equipment:

Page 23: L.v tech presentation 2

Tempreture control:CONTACT TEMPERATURE MONITORING, This AGR protection function monitors the temperature of the ACBs main contacts.An alarm when the temperature exceeds 155°C. Continuous monitoring of the contact temperature provides valuable information for BMS, preventative and predictive maintenance programs.

Alfanar Low Voltage equipment:

Page 24: L.v tech presentation 2

Double break:The Tem Power-2 Air Circuit Breaker is the smallest depth Air Circuit Breaker in the world with a one second Short Circuit Withstand.

The unique “Double Break” main contact system ensures extremely fast interruption of short circuit currents. Conventional break time is 70msec, TemPower 2 breaking time is 25~30msec.

Alfanar Low Voltage equipment:

Page 25: L.v tech presentation 2

Eeasy maintenance:The unique design of Tem Power-2 incorporates itsisolating clusters and main contacts on the ACB body. Allowing for quick easy maintenance of the main electrical contact points and for maintenance to be completed without having to isolate the board.

Alfanar Low Voltage equipment:

Page 26: L.v tech presentation 2

Replacement of main contacts:The fixed and moving main contacts can easily be replaced in the field, thus prolonging the life on the circuit breaker. Changing each pole takes around 15 minutes.

Alfanar Low Voltage equipment:

Page 27: L.v tech presentation 2

Double opening and closing coils:Double Opening and Closing Coils provides extended control system redundancy to an ACB. Double coils allow designers to implement back-up tripping and closing systems. It provides the end user with ultimate reliability on critical UPS circuits connected to critical loads.

Alfanar Low Voltage equipment:

Page 28: L.v tech presentation 2

ACB accessories:

Alfanar Low Voltage equipment:

Page 29: L.v tech presentation 2

Moulded Case Circuit Breakers Circuit Breakers: Ie=125A to 1600A Ue=690Vac/600Vdc Ui=800Vac Uimp=8KV Fixed or Withdrawable (Front, vertical or horizontal connection) Manual or Motor charging Comply with IEC 60947-2 Comply with NEMA AB-1 1P, 3P or 4P Category A/B

Alfanar Low Voltage equipment:

Page 30: L.v tech presentation 2

Moulded Case Circuit Breakers (Thermal Magnetic):

6

8

12

100.8

0.63

1Ir (x ln) Ii (x ln)

125A

Alfanar Low Voltage equipment:

Page 31: L.v tech presentation 2

Moulded Case Circuit Breakers (Electronic):Electronic version with integrated monitoring and communication, data can be sent to integrated display local display and Modbus network simultaneously.

Alfanar Low Voltage equipment:

Page 32: L.v tech presentation 2

Direct opening “Yellow and red symbol “:This symbol located on the MCCB rating label, indicates that the MCCB has direct opening action.According to IEC 60204 provides a positive off.

Alfanar Low Voltage equipment:

Page 33: L.v tech presentation 2

Plug-in safety lock:MCCB can only be withdrawn when MCCB is switched off.

Alfanar Low Voltage equipment:

Page 34: L.v tech presentation 2

MCCB accessories:

Alfanar Low Voltage equipment:

Page 35: L.v tech presentation 2

Circuit breaker with integral Residual Current Protection “CBR”:

Alfanar Low Voltage equipment:

Page 36: L.v tech presentation 2

Al Imam Muhammed

ibn Saud Islamic

University

King Abdullah

Financial District -

KAFD

King Abdullah Sport

City –Jeddah (KASC)

Haramain High Speed Railway

King Abdullah Port

Alfanar Low Voltage equipment:

Reference projects in KSA:

Page 37: L.v tech presentation 2

Alfanar Low Voltage equipment:

Reference projects in overseas:

Page 38: L.v tech presentation 2

Alfanar Low Voltage equipment:

Reference projects in overseas: