MODEL 1003 TYPE Y OR Z RAPID EXCHANGE ® PURGING SYSTEM PROCESS AUTOMATION INSTALLATION AND OPERATION MANUAL

Upload: dangtruc

Post on 06-Mar-2018

222 views

Category:

Documents


5 download

TRANSCRIPT

Page 1: Installation and Operation Manual: Model 1003 Type Y or Z ...files.pepperl-fuchs.com/selector_files/navi/productInfo/doct/tdoct... · Page 23 Systems identification & application

MODEL 1003 TYPE Y OR ZRAPID EXCHANGE® PURGING SYSTEM

PROCESS AUTOMATION

INSTALLATION AND OPERATION MANUAL

Page 2: Installation and Operation Manual: Model 1003 Type Y or Z ...files.pepperl-fuchs.com/selector_files/navi/productInfo/doct/tdoct... · Page 23 Systems identification & application

Model 1003 Installation and Operation Manual

2

Par

t No.

511

967

Dra

win

g N

o. 1

29-0

195b

03/

09

Subject to modifications without notice

Pepperl+Fuchs Groupwww.pepperl-fuchs.com

USA: +1 330 486 [email protected] [email protected]

Singapore: +65 6779 [email protected]

Copyright Pepperl+Fuchs

Germany: +49 621 776 2222

Table of Contents

Page 2 System Purpose and Description Purpose,Systemdescription,Importantnotes

Page 3 Identifying Your System Definesspecificfeaturesofthesystem

Page 3 General Information System&materialspecifications,Spareparts,Tools

&testequipment,Systemaccessories

Page 4 Enclosure and Device Design Designrequirements,Adjacentenclosures,Device

ventilation,Temperaturelimitations

Page 5 Installation Overview Installationdiagram

Page 6 Getting Started Establishingconnectionsizes,Determiningenclosure

inlet&outletconnectionlocations

Page 7 System Mounting LH,RH,TM,BM&WMconfigurations,FM&PM

configurations

Page 8 Hardware Mounting Requiredenclosureprotectionvent,Warning

nameplates

Page 9 Mounting Plate Dimensions Mountingplatedimensiondiagrams

Page 11 Pneumatic Tubing Requirements Protectivegassupplyrequirements,Pneumatic

connectionrequirements

Page 12 Tubing Installation LH,RH,TM,BM,WM,FM&PMtubing

configurations

Page 13 Tubing Connection Diagrams LH,RH,TM,BM,WM,FM,&PMconfiguration

connectionpoints,Pneumaticdiagram

Page 14 Electrical Supply Requirements Wiringrequirements,Enclosurepower&alarmsignal,

Enclosurewiringmethods&connections

Page 15 Conduit Installation Electrical&WPSstyleconduitandconnectionparts

Page 16 Set-Up Procedure ClassIpurgingset-up

Page 17 Operating Sequence ClassIpurgingoperation

Page 18 Troubleshooting Procedures Troubleshootingchart

Page 19 Warranty and Liability Statement Warrantynotes,Generalterms,Limitations

Page 20 Customer notes

Page 22 System Maintenance Regularmaintenance,Long-termmaintenance,

Maintenanceschedule

Page 23 Systems identification & application information

Purpose and Description

PurposePepperl+Fuchs'BebcoEPSSystemallowstheuseofgeneral-purposeornonratedelectricalorelectronicdevices,withexceptiontodevicesthatproduceexcessiveheat,utilizecombustiblegas,orexposearcingcontactstothehazardousatmosphere,inNEMA(NationalElectricalManufacturersAssociation)4or12enclosuresintheplaceofexplosionproofNEMA7enclosures.Otherpurposesincludeheat,moistureanddustcontaminationprevention.

DescriptionModel1003isaRapidExchangepurgingsystemthatoperatesonasupplyofcompressedinstrumentairorinertgas.Itregulatesandmonitorspressurewithinoneormoresealed(protected)enclosures,inordertorapidlyremoveandpreventflammablevaporaccumulationwithintheenclosure(s).Thesystemaccomplishesfourairexchangesandmaintainsa"safe"(0.25")pressureononeormoreenclosuresnotexceedingatotalvolumeof75cubicfeet.AnEPV-3enclosureprotectionventisrequiredforproperoperation.Thisprocessreducesthehazardous(classified)arearatingwithintheenclosure(s),inaccordancewiththeNEC-NFPA70,Article500,NFPA496andISA2.4.

Important NotesOne(1)permanentfilecopyandone(1)operationscopyofthismanualmustbestudiedandretainedbytheoperatorofthissystem.User’sagentsareresponsiblefortransferringthismanualtotheuser,priortostart-up.

Thecontentsofthismanualhavebeenarrangedtoallowtheuseofthisproductasastand-alonedeviceonequipmentandenclosuressuppliedbytheuseroritsagents.Themanual’sparametersencompassacombinationofbothNationalFireProtectionAssociation(NFPA)requirementsandPepperl+Fuchs,Inc.requirements.Pepperl+FuchsthereforeacknowledgestheuseofNFPA496asaguideline,thatwehaveenhancedcertainNFPArequirementsandthatadditionalinformationhasbeencompiledtocompletethisdocument.Themanualisintendedasacompleteguideandmustbeconsidered,unlessspecificallystatedotherwise,thatalldirectivescontainedhereinarerequirementsforsafe,practicalandefficientuseofthisproduct.

Thissystemisnotintendedforusetoprotectenclosuresordevicesthatcontainignitableconcentrationsofgasesorvapors.Thisexclusiongenerallyappliestoprocessorproductanalyzingsystemsequipment.

All specifications are subject to change without notice.

Page 3: Installation and Operation Manual: Model 1003 Type Y or Z ...files.pepperl-fuchs.com/selector_files/navi/productInfo/doct/tdoct... · Page 23 Systems identification & application

Model 1003 Installation and Operation Manual

3

Par

t No.

511

967

Dra

win

g N

o. 1

29-0

195b

03/

09

Subject to modifications without notice

Pepperl+Fuchs Groupwww.pepperl-fuchs.com

USA: +1 330 486 [email protected] [email protected]

Singapore: +65 6779 [email protected]

Copyright Pepperl+Fuchs

Germany: +49 621 776 2222

Identifying Your System

Thisenclosureprotectionsystemisofferedinvariousstyles.Forproperinstallationandoperation,examinethesystemmodelnumbernameplatetoidentifythesystemstyle,areaclassification,andtype,asnotedbelow.

General Information

System SpecificationsSystemdimensions: Seepages9&10Shippingweight(lbs.): LPS-12,WPS-17Operatingtemp.range: -20°Fto+120°FSupplypressurerange: 80-120psimax.

Whenusingtheoptionalinlinefilter,max.supplypressureis80psiCapacity&filtration: 3.8oz.40micronsSupplyrequirements: CleanairorinertgasSafepressuresetpoint: 0.25"Safepressureflowrate: **0.1-3.5SCFHExchangepressure: *3"-5"Exchangeflowrate: **10SCFM/600SCFHExchangetime: 1minute/2.5ft3

Systemsupplyport: 3/8"FPTEnclosuresupplyfitting: 3/8"tubefittingEnclosurereferencefitting: 1/4"tubefittingSwitchsetting(WPS&WPSAonly): 0.15"±0.02"WPS&WPSApressureswitchwiring: 1/2"FPTSwitchcontactratings:WPSStyle: 120VAC@15AmpsWPSAStyle: ***120/220VAC, 24VDC@10Amps,125VDC@50mA

* Enclosureintegritydeterminesactualflowandpressure**Withregulatorsetto60psimin.duringexchange***Supplyvoltages24VDCand240VACavailableuponrequest

Exchangeflowratingisbasedonsafetyfactorsconsideredafterextensivefactorytestinganddoesnotreflectactualflow.Flowwasmeasuredupstreamofsystemwithanelectronicflowmeterona5ft3enclosure.Thesystemwasinstalledwithtubingthatexceededthemaximumallowablelinearlengthandquantityofbendslistedinthismanualforsystemsupply,enclosuresupplyandenclosurereferenceconnections.ThesystemwastestedinconjunctionwiththeEPV-3-SA-00enclosureprotectionvent,mounteddirectlyonthetestenclosure.

ABS Traceable Certified Exchange Flow Measurements with System regulator set at 60 psi, ambient temperature of 75° F

100psisupplypressure: 15.76scfm/945.67scfh80psisupplypressure: 15.64scfm/938.34scfh

Material SpecificationsRegulatorbody: Zincw/enamelfinishRegulatorhandle: PolycarbonateEnclosurepressuregauge: Aluminumw/enamelfinishRapidExchangegauge: Polycase&brasstubeTubefittings: 316SSforgedbodyTubing: 316SS1/4".035weldedSystemnameplates: SilkscreenedLexan®&SSFastenerhardware: Aluminum&stainlesssteelMountingplate: 31614ga#3brushSSEXPpressureswitchbody: Anodizedcastalum.Enclosurewarningnameplate: SilkscreenedSS

Lexan®isaregisteredtrademarkoftheGeneralElectricCompany

Recommended Spare PartsQty Description Part#(supercedes)1 Enclosurepressureindicator-CI 510023(001000)1 Systemfilteredregulator 510064(002090)1 RapidExchangepressuregauge 510078(002300)1 Enclosurepressurecontrolvalvebody 510131(003660)1 RapidExchangecontrolvalvebody-PM 510133(003680)1 RapidExchangecontrolvalvebody 510155(003940)1 Installation&operationmanual 129-01951 GroupC-Dpressureswitch-CI 510044(001080)1 GroupA-Dpressureswitch-CI 510045(001085)1 Enclosurewarningnameplate-CI 513008(EWN-1)

Pleasecallandreferencetheabovepartnumberforcurrentsparepartspricing.Immediatepricingisavailabletoallconfirmedcustomers.

Installation Tools & Testing Equipment1/2"chuckdrill

Completesetofdrillbits

1.25"conduitknockoutpunchor1.75"holesaw

Completesetoftubing,conduitbending,instrumentfittingandelectricalcraftsmanhandtools

0-10"differentialpressureindicatorormanometer(connectedtotheprotectedenclosuretomeasuremaximumpressure)

1003 - LPS - CI - YZ - LH - ##

Series Model NumberSystem Style LPS - less pressure switch WPS - with pressure switch WPSA - with pressure switchArea Classifi cation CI - Class I AreaSystem Type YZ - Div. 1 to Div. 2, Div. 2 to NonhazardousMounting Confi guration LH - left hand left side of enclosure RH - right hand right side of enclosure TM - top mount top of enclosure BM - bottom mount bottom of enclosure WM - wall mount wall surface FM - frame mount external frame or rack PM - panel mount enclosure surface cutout (Not available in WPS Style)

## - Additional factory installed accessories

Confidential according to ISO 16016

sheet

respons.

approved

norm 1 of 1

scale: 1:1

Label for 1003-[LPS or WPSA or WPS]-CI Type Y or Z

date: 2004-Feb-03Only valid as long as released in EDM or with a valid production documentation!

Twinsburg

1003 LPS UL Y or Z UL ID NP SS1003 WPS UL Y or Z ID NP SS1003 WPSA UL Y or Z UL ID NP S

125-0838Achange notice.

Dieses Dokument enthält sicherheitsrelevante Angaben. Es darf nicht ohne Absprache mit dem Normenfachmann geändert werden!

This document contains safety-relevant information. It must not be altered without the authorization of the norm expert!

TECHNICAL INFORMATION:

POLYCARB 0.01”MUST BE UL/CSA APPROVED

BLACK COPY ON WHITE BACKGROUNDFULL INFORMATION PERTAINING TO PRINT FONTS,DIMENSIONS AND COLOR SCHEMES ARE CONTAINED INTHIS COREL DRAW (.CDR) FILENAME UNDER DRAWINGNUMBER 125-0838A

LABEL MATERIAL:

ADHESIVE:

COLOR:

NOTE:

US.JMB

US.SSJ

US.WDB150-0355

2.50

1.50

SCALE = 1X

All dimensions are in inches.All outside corners R=0.13

Tolerances: 2-place dec. +/- .01

APPROVED BY FM APPROVALS AS ASSOCIATED TYPE Y & Z PRESSURIZATION CONTROL

EQUIPMENT FOR USE IN HAZARDOUS LOCATIONS. REDUCES THE INTERNAL AREA

OF A CONNECTED ENCLOSURE IN ACCORDANCE WITH DRAWING NUMBER 1003-IOM.

APPROVED BY FM APPROVALS AS ASSOCIATED TYPE Y & Z PRESSURIZATION CONTROL

EQUIPMENT FOR USE IN HAZARDOUS LOCATIONS. REDUCES THE INTERNAL AREA

OF A CONNECTED ENCLOSURE IN ACCORDANCE WITH DRAWING NUMBER 1003-IOM.

APPROVED BY FM APPROVALS AS ASSOCIATED TYPE Y & Z PRESSURIZATION CONTROL

EQUIPMENT FOR USE IN HAZARDOUS LOCATIONS. REDUCES THE INTERNAL AREA

OF A CONNECTED ENCLOSURE IN ACCORDANCE WITH DRAWING NUMBER 1003-IOM.

REDUCES INTERNAL AREA CLASSIFICATION AS FOLLOWS:TYPE Y: CL. I, DIV. 1, GR. A-D / ZONE 1, GR. IIC TO DIV. 2 /ZONE 2

TYPE Z: CL. I, DIV. 2, GR. A-D / ZONE 2, GR. IIC TO NONHAZARDOUS

REDUCES INTERNAL AREA CLASSIFICATION AS FOLLOWS:TYPE Y: CL. I, DIV. 1, GR. A-D / ZONE 1, GR. IIB+H2 TO DIV. 2 /ZONE 2

TYPE Z: CL. I, DIV. 2, GR. A-D / ZONE 2, GR. IIB+H2 TO NONHAZARDOUS

REDUCES INTERNAL AREA CLASSIFICATION AS FOLLOWS:TYPE Y: CL. I, DIV. 1, GR. C & D / ZONE 1, GR. IIB TO DIV. 2 /ZONE 2

TYPE Z: CL. I, DIV. 2, GR. C & D / ZONE 2, GR. IIB TO NONHAZARDOUS

Model 1003-LPS-CI Type Y or Z Model 1003-WPSA-CI Type Y or Z

Model 1003-WPS-CI Type Y or Z

C

LASSIFIED

®

C

LASSIFIED

®

C

LASSIFIED

®

PURGE CONTROL FOR USE IN HAZARDOUS LOCATIONS IN ACCORDANCE WITH THE NATIONAL FIRE

PROTECTION ASSOCIATION STANDARD FOR PURGED AND PRESSURIZED ENCLOSURES FOR ELECTRICAL

EQUIPMENT NFPA 496-1996 4S11

PURGE CONTROL FOR USE IN HAZARDOUS LOCATIONS IN ACCORDANCE WITH THE NATIONAL FIRE

PROTECTION ASSOCIATION STANDARD FOR PURGED AND PRESSURIZED ENCLOSURES FOR ELECTRICAL

EQUIPMENT NFPA 496-1996 4S11

PURGE CONTROL FOR USE IN HAZARDOUS LOCATIONS IN ACCORDANCE WITH THE NATIONAL FIRE

PROTECTION ASSOCIATION STANDARD FOR PURGED AND PRESSURIZED ENCLOSURES FOR ELECTRICAL

EQUIPMENT NFPA 496-1996 4S11

75 CUBIC FEET MAXIMUM ENCLOSURE VOLUME 75 CUBIC FEET MAXIMUM ENCLOSURE VOLUME

75 CUBIC FEET MAXIMUM ENCLOSURE VOLUME

LABEL P/N: 510926 LABEL P/N: 510929

LABEL P/N: 510931

Released EDM checkout 2008-JUL-17

Page 4: Installation and Operation Manual: Model 1003 Type Y or Z ...files.pepperl-fuchs.com/selector_files/navi/productInfo/doct/tdoct... · Page 23 Systems identification & application

Model 1003 Installation and Operation Manual

4

Par

t No.

511

967

Dra

win

g N

o. 1

29-0

195b

03/

09

Subject to modifications without notice

Pepperl+Fuchs Groupwww.pepperl-fuchs.com

USA: +1 330 486 [email protected] [email protected]

Singapore: +65 6779 [email protected]

Copyright Pepperl+Fuchs

Germany: +49 621 776 2222

Model 1003 System AccessoriesEnclosure Protection Vents(onerequiredwitheachsystem)EPV-3-SA-00 Straightw/sparkarrestorEPV-3-SA-90 Rtanglew/sparkarrestor

Additional ItemsSMK-2or-8 SystemmountingkitEPSK-1 ClassI,GroupC-DpressureswitchkitEPSK-1A ClassI,GroupA-DpressureswitchkitGPSK-1 ClassI,general-purposeswitchkitRAH Div.1remotealarmhornRAB-1 Div.1remotealarmbeaconRAB-2 Div.2remotealarmbeaconLCK LfittingconduitkitTCK TfittingconduitkitEFC-4 1/4"flushconnectorEFC-6 3/8"flushconnectorEBC-6 3/8"bulkheadconnectorEPC-13 1"pipeconnectorNC-6 3/8"ninetyconnectorSC-6 3/8"straightconnectorETW Enclosuretemperaturewarning

Enclosure & Device Design

1. Allwindowsmustbeshatterproofandsizedassmallaspossible.

2. AllNFPA496requiredmarkingsmustbeplacedonornearallenclosuredoorsandcovers.

3. Theenclosuremustwithstandaninternalpressureoften(10)inchesofwaterwithoutsustainingpermanentdeformationandresistallcorrosiveelementsinthesurroundingatmosphere.

4. Alllightweightobjectsintheenclosure,suchaspaperorinsulation,mustbefirmlysecured.

5. Theenclosureshouldbeconstructedfrommaterialssuchasmetaloranti-staticpolycarbonatetomeetorexceedNEMA4or12performancerequirements,butdoesnotrequirethirdpartyapproval.

6. Theinstallationofobstructionsorotherbarriersthatblockorimpedetheflowofprotectivegasmustbeavoided.

7. Thecreationofairpocketsorotherareasthattrapflammablegaseswithintheenclosureordevicesmustbeavoided.

8. Theenclosureshouldbelocatedinanareawhereimpacthazardsareminimal.

9. Iftheenclosureisnonmetallicandcontainsequipmentthatutilizesorswitchespowerloadsgreaterthan2500VA,itmustbeconstructedfromsubstantiallynoncombustiblematerials,suchasmaterialsdesignedtomeetorexceedANSI/UL94ratingsof94V-0or945V.

Adjacent Enclosures1. Adjacentenclosuresmustbeprotectedbyoneofthe

followingmeans:

a) purgedorpressurizedinserieswiththeprotectedenclosure

b) purgedorpressurizedseparatelyor

c) protectedbyothermeans;e.g.,explosionproofenclosures,hermeticallysealeddevicesorintrinsicsafecircuits

2. Adjacentpurgedorpressurizedenclosuresmustbedesignedtomeetallconstructionrequirementsabove.

Total Volume Calculation1. Thetotalvolumeofallpressurizedenclosures,devicesand

wirewaysmustbeconsidered.

2. Allenclosure,device,andwirewayvolumesmustbecalculatedwithoutconsiderationofinternallyconsumedspace.

Device Ventilation1. Encloseddeviceswithintheprotectedenclosurewhichdo

notexceed1.22in3offreevolumedonotrequireventilationtotheprotectedenclosure.

2. Ifthefreevolumeofaninternaldeviceexceeds1.22in3itmustbeprotectedbyoneofthefollowingmeans:

a) ventilatedonthetopandbottomsideswith1in2ofopeningforeach400in3ofvolumewithintheinternalprotectedenclosure,ataminimumdiameterof1/4"

b) purgedinserieswiththeprotectedenclosureorbepurgedseparatelyor

c) protectedbyothermeans;e.g.,explosionproofenclosures,hermeticallysealeddevices,orintrinsicsafecircuits.

Temperature Limitations1. Theenclosuremusthavenosurfaceareathatexceeds80

percentoftheflammableorignitablesubstance’sauto-ignitiontemperature.

2. Internaldevicesthatexceedthistemperaturemustbeprotectedbyoneofthefollowingmanners:

a) ThedeviceisenclosedinachamberthatisCULUSorFMlistedasahermeticallysealeddevicethatprohibitstheentranceofaflammableorignitablesubstance,andmaintainsasurfacetemperaturebelowtemperaturelimits.

b) Itcanbeprovenbytestingthatthedeviceswillnotignitethesubstanceinvolved.

c) ThedeviceispurgedinaseparateenclosurethatbearsanETW(enclosuretemperaturewarningnameplate).Devicesmaybeaccessedonlyafterpowerhasbeenremovedandthedevicehasbeenallowedtocooltosafetemperature,ortheareaispositivelyknowntobenonhazardous.

Page 5: Installation and Operation Manual: Model 1003 Type Y or Z ...files.pepperl-fuchs.com/selector_files/navi/productInfo/doct/tdoct... · Page 23 Systems identification & application

Model 1003 Installation and Operation Manual

5

Par

t No.

511

967

Dra

win

g N

o. 1

29-0

195b

03/

09

Subject to modifications without notice

Pepperl+Fuchs Groupwww.pepperl-fuchs.com

USA: +1 330 486 [email protected] [email protected]

Singapore: +65 6779 [email protected]

Copyright Pepperl+Fuchs

Germany: +49 621 776 2222

Installation Overview

Model 1002-WPS-LH Shown

PROTECTIVE GAS SUPPLY

SYSTEM SUPPLY TUBING

ELECTRICAL ALARM WIRING CONDUIT & SEAL

SERVICE VALVE

SYSTEM SUPPLY FITTING

ENCLOSURE PROTECTION

SYSTEM

SYSTEM MOUNTING

BOLT

ENCLOSURE SUPPLY TUBING

ENCLOSURE PROTECTION

VENT(required)

PROTECTED ENCLOSURE

ENCLOSURE CONNECTION

FITTINGS

ENCLOSURE REFERENCE

TUBING

ENCLOSURE WARNING

NAMEPLATE

Page 6: Installation and Operation Manual: Model 1003 Type Y or Z ...files.pepperl-fuchs.com/selector_files/navi/productInfo/doct/tdoct... · Page 23 Systems identification & application

Model 1003 Installation and Operation Manual

6

Par

t No.

511

967

Dra

win

g N

o. 1

29-0

195b

03/

09

Subject to modifications without notice

Pepperl+Fuchs Groupwww.pepperl-fuchs.com

USA: +1 330 486 [email protected] [email protected]

Singapore: +65 6779 [email protected]

Copyright Pepperl+Fuchs

Germany: +49 621 776 2222

Getting Started

Typical Single Protected Enclosure Connections

HELPFUL HINTSIfflammablegasesarelighterthanair,theinletconnectiontoeachenclosuremustenternearabottomcorner.Theoutletconnection,fortherequiredenclosureprotectionventorpipingtoanadjacentprotectedenclosure,mustexitnearanextremeoppositetopcorner.

Ifflammablegasesareheavierthanair,inletandoutletconnectionsmustbereversed.

Inallcases,themostprevalentgasmustdeterminethelocationofinletandoutletconnections.

HELPFUL HINTSToensureadequateprotectivegasflowtotheprotectedenclosure(s),allpipingandtubingmustbefullyreamed.

Precautionsmustbetakentopreventcrimpingandotherdamagetoprotectivegaspipingandtubing.

Whenprotectingmultipleenclosureswithasingleenclosureprotectionsystem,theenclosuresmustbeconnectedinseriesfromthesmallesttothelargesttoensureadequateprotectivegasflow.

PROTECTED ENCLOSURE

C

B

ENCLOSURE PROTECTION VENT(Required)

E

SUPPLY

REFERENCE

1/2" PROTECTIVE GAS SUPPLY

HEADER

ENCLOSURE PROTECTION

SYSTEM

Maximum tubing / pipe length and maximum number of bends / elbows

3/8"O.D.tubingfullyreamed

20feet10bends

3/8"O.D.tubingfullyreamed

Description

Tubing or pipe diameter

Enclosure supply

System supply tubing

Enclosure reference

1/4"O.D.tubingfullyreamed

5feet5bends

20feet10bends

Multi - enclosure connections

1"I.D.pipefullyreamed

10feet5elbows

Optional remote venting

1"I.D.pipefullyreamed

30feet5elbows

A B EDC

ENCLOSURE PROTECTION

SYSTEM

PROTECTED ENCLOSURE

PROTECTED ENCLOSURE

D

SUPPLY

REFERENCE

B

TYPICAL MULTIPLE PROTECTED ENCLOSURE CONNECTIONS

1/2" PROTECTIVE GAS SUPPLY

HEADER

A

A

D

C

PROTECTED ENCLOSURE

*NOTE:Tubeandpipesizesaretradesizesandarenotequalininsidediameter. DONOTsubstitutetubeforpipewithsametradesize.

INLET

INLET

Connectionsforheavierthanairgasesandvapors

OUTLET

OUTLET

Connectionsforlighterthanairgasesandvapors

Determining Enclosure Inlet & Outlet Connection Locations

Page 7: Installation and Operation Manual: Model 1003 Type Y or Z ...files.pepperl-fuchs.com/selector_files/navi/productInfo/doct/tdoct... · Page 23 Systems identification & application

Model 1003 Installation and Operation Manual

7

Par

t No.

511

967

Dra

win

g N

o. 1

29-0

195b

03/

09

Subject to modifications without notice

Pepperl+Fuchs Groupwww.pepperl-fuchs.com

USA: +1 330 486 [email protected] [email protected]

Singapore: +65 6779 [email protected]

Copyright Pepperl+Fuchs

Germany: +49 621 776 2222

IMPORTANT NOTEShe system should be mounted at EYE LEVEL.

Care must be taken to ensure the system and all protruding components are clear of all enclosure accesses (doors and covers) and conduit, pipe, tubing or cable entries.

LH, RH, TM, BM and WM configurations are intended for mounting adjacent to the protected enclosure.

LH, RH, TM & BM configurations are also suitable for 2" schedule 40 pipe mounting.

Determine the mounting configuration of your system using the diagrams on pages 9 & 10.

Remove and save the manila envelope (containing the enclosure warning nameplate) which may be taped to the outer surface of the mounting flange.

Although all purge systems are factory tested and calibrated, we strongly suggest a bench test of basic functions prior to installation.

Mounting LH, RH, TM, BM & WM ConfigurationsSurface mounting systems

1.Transferholepatternofsystemmountingplatetointendedsurface.

2. Checkforobstructionshinderingboltfastening,drillandreamthemountingholesbeforemountingthesystem.

3. Securethesystemtotheenclosure,orothermountingsurface,usingone(1)SMK-2mountingkitorequivalent-four(4)3/8"x3/4"stainlesssteelbolts,nutsandlockwashers.

Pipe mounting systems

1. Locate2"schedule40pipe,(verticalforLH&RH,horizontalforTM&BM)withinfive(5)feetofprotectedenclosure.

2. Ensuresystemismountedinatrueverticalposition,securethesystemtopipe,usingone(1)PMK-2mountingkitorequivalent-two(2)3/8"x2"stainlesssteel“U”bolts,nutsandlockwashers.

Mounting FM & PM Configurations

1. Transferpanelcutoutpatterntotheintendedsurface.

2. Checkforobstructionswhichcouldprohibitboltfasteningorsystempneumaticconnections.

3. Cutpanelcutoutpatternontheintendedsurface.

4. Deburrallcutoutsurfaces.

5. SecuresystemtoenclosureusingSMK-8mountingkit,orequivalent-eight(8)1/4"x3/4"stainlesssteelnuts,bolts,mountingclipsandlockwashers.

HELPFUL HINTSFMandPMconfigurationsaredesignedtomountthroughapanelcutoutone(1)inchsmallerthantheoverallheightandwidthofthesystemmountingplate,usingclipsandfastenersprovidedwiththeSMK-8mountingkit.Thisdesignfeatureeliminatestheneedtodrillthesystemmountingboltholesintheprotectedenclosure.PMconfigurationsdonotrequireanddonotincludeaventuriorificeontheenclosurereferenceconnection.

FMconfigurationsareintendedformountingadjacenttotheprotectedenclosure.

PMconfigurationsareintendedformountingthroughacutoutintheprotectedenclosuresurface.

Typical Examples of Surface, Pipe, Panel & Frame Mounted Systems

System Mounting

Typical Surface Mounted System(Model 1002-LPS-CI-Z-LH shown)

Typical Pipe Mounted System(Model 1002-LPS-CI-Z-LH shown)

Typical Panel/Frame Mounted System(Model 1002-LPS-CI-Z-PM shown)

Page 8: Installation and Operation Manual: Model 1003 Type Y or Z ...files.pepperl-fuchs.com/selector_files/navi/productInfo/doct/tdoct... · Page 23 Systems identification & application

Model 1003 Installation and Operation Manual

8

Par

t No.

511

967

Dra

win

g N

o. 1

29-0

195b

03/

09

Subject to modifications without notice

Pepperl+Fuchs Groupwww.pepperl-fuchs.com

USA: +1 330 486 [email protected] [email protected]

Singapore: +65 6779 [email protected]

Copyright Pepperl+Fuchs

Germany: +49 621 776 2222

Hardware Mounting

Required Enclosure Protection VentAllconfigurationsmustbemountedinatrueverticalposition.

Theventmustbelocatedtoprovideaccessforroutinetestingofthevent’sflapperassembly.Aminimum8"clearanceisrequiredbelowtheventopening.

1. Determinethevent’smountingconfiguration,i.e.,-00verticalmountor-90sidemount.Seephotosbelow.

2.Determineventlocationandlayoutventmountingholeontheprotectedenclosure(asdeterminedonpage6,“GettingStarted”).

3. Usinga1.75"holesawor1.25"conduitpunch,drillanddeburrtheenclosureprotectionventmountinghole.

4. Removethehubmountingnutfromtheventhubandplacethehub,withO-ringintact,throughthemountinghole.TheO-ringmustbeontheoutsideoftheprotectedenclosure.

5. Reinstallthehubmountingnuttothemountinghubfrominsidetheprotectedenclosureandtighten.

Warning Nameplate(s)AnEWN(enclosurewarningnameplate)mustbelocatedinaprominentpositiononornearallenclosureaccesses(doorsandcovers).

One(1)EWNisprovidedwitheachsystem,locatedinthemanilaenvelopetapedtothemountingflangeofthesystem.AdditionalEWNsareavailablefromPepperl+Fuchs.

AllEWNsprovidelabeledspacesallowingthecustomertomarktheprotectedenclosurewith:1)aTCode(temperatureidentificationnumber),2)Class,GroupandDivisionofsurroundingarea,and3)NFPApressurizationTypeX,YorZ,asmayberequiredbyplantandlocalcodesandisrequiredbyNFPA496section2-11.

AnETW(enclosuretemperaturewarningnameplate)mustbelocatedinaprominentpositiononornearallenclosureaccesses(doorsandcovers)whenthetemperatureofaninternalcomponentexceeds80percentoftheignitiontemperatureoftheflammablevapor,gasordustinvolved.

TheETWwarnstheoperatortodeenergizeallequipmentforaspecifiedlengthoftime,allowingtheprotectedequipmenttocoolbeforeopeningtheprotectedenclosure.Thelengthoftimerequiredisdeterminedbythecustomerandcanbefactoryorfieldengraved.

AllEWNsandETWsarefurnishedwithanadhesiveback,butshouldalsoberivetedorscrewedtotheprotectedenclosure.

EPV - 3 - SA - 00Vertical Mount

EPV - 3 - SA - 90Side Mount

Enclosure Temperature Warning Nameplate

Enclosure Warning Nameplate - Class I

Page 9: Installation and Operation Manual: Model 1003 Type Y or Z ...files.pepperl-fuchs.com/selector_files/navi/productInfo/doct/tdoct... · Page 23 Systems identification & application

Model 1003 Installation and Operation Manual

9

Par

t No.

511

967

Dra

win

g N

o. 1

29-0

195b

03/

09

Subject to modifications without notice

Pepperl+Fuchs Groupwww.pepperl-fuchs.com

USA: +1 330 486 [email protected] [email protected]

Singapore: +65 6779 [email protected]

Copyright Pepperl+Fuchs

Germany: +49 621 776 2222

Mounting Plate Dimensions

4.25"

7.5"

14.5625"

.68

75

"

.375" O.D.TYP. 4

3.5

62

5"

15.25"

12"

1003-LPS-LH(Left hand configuration)

1003-WPS & WPSA-LH(Left hand configuration)

1003-WPS & WPSA-RH(Right hand configuration)

1003-LPS-RH(Right hand configuration)

1003-LPS-TM(Top mount configuration)

1003-WPS & WPSA-TM(Top mount configuration)

4.25"6"

.6875"3.5625"

11.3125"

.375" O.D.TYP. 4

12"

11.5"

15"

11.5"

4.25"7.5"

.6875"3.5625"

14.3125"

.375" O.D.TYP. 4

4.25"7.5"

.6875"3.5625"

14.3125"

.375" O.D.TYP. 4

15"

11.5"

4.25"6"

.6875"3.5625"

11.3125"

.375" O.D.TYP. 4

12"

11.5"

12"

11.5"

6"

10.8125"

.68

75

"3

.56

25

"

4.25"

.375" O.D.TYP. 4

Page 10: Installation and Operation Manual: Model 1003 Type Y or Z ...files.pepperl-fuchs.com/selector_files/navi/productInfo/doct/tdoct... · Page 23 Systems identification & application

Model 1003 Installation and Operation Manual

10

Par

t No.

511

967

Dra

win

g N

o. 1

29-0

195b

03/

09

Subject to modifications without notice

Pepperl+Fuchs Groupwww.pepperl-fuchs.com

USA: +1 330 486 [email protected] [email protected]

Singapore: +65 6779 [email protected]

Copyright Pepperl+Fuchs

Germany: +49 621 776 2222

Mounting Plate Dimensions (continued)

1003-WPS & WPSA-WM(Wall mount configuration)

1003-LPS-BM(Bottom mount configuration)1003-WPS & WPSA-BM

(Bottom mount configuration)

6"

10.8125"

.68

75

"3

.56

25

"

4.25"

.375" O.D.TYP. 4

12"

11.5"

15"

11.5"

13"

6"

9.25"

17"

Panel Cutout12.5"

Panel Cutout16"

13.5"

.25" O.D.TYP. 8

4" 3.25"

1003-WPS & WPSA -FM(Frame mount configuration)

Panel Cutout12.5"

14"

13.5"

Panel Cutout13"

.25" O.D.TYP. 8

4" 1.75"

1003-LPS-FM & 1003-LPS-PM(Frame & panel mount configuration)

15.25"

12"

4.25"

7.5"

14.5625"

.68

75

"

.375" O.D.TYP. 4

3.5

62

5"

1003-LPS-WM(Wall mount configuration)

9.5"

2" 1"

.375" O.D.TYP. 4

6"

10"

7.75"

12"

11.5"

TYPICAL -WMMOUNTING FLANGE

Page 11: Installation and Operation Manual: Model 1003 Type Y or Z ...files.pepperl-fuchs.com/selector_files/navi/productInfo/doct/tdoct... · Page 23 Systems identification & application

Model 1003 Installation and Operation Manual

11

Par

t No.

511

967

Dra

win

g N

o. 1

29-0

195b

03/

09

Subject to modifications without notice

Pepperl+Fuchs Groupwww.pepperl-fuchs.com

USA: +1 330 486 [email protected] [email protected]

Singapore: +65 6779 [email protected]

Copyright Pepperl+Fuchs

Germany: +49 621 776 2222

Pneumatic Tubing Requirements

Protective Gas Supply RequirementsTheprotectivegassupplytotheprotectionsystemmustbeaclean,instrumentqualitycompressedairornitrogenandmustcontainnomorethantraceamountsofflammablegas,vaporordust.

Theprotectivegassupplycompressorintakemustoriginateinanonhazardouslocation.Suctionductpassingthroughahazardouslocationandtheprotectionsystemtubingandpipingmustbefabricatedfromnoncombustiblematerialssuitableforprevailinghazardsandenvironmentalconditions.

Theprotectivegassupplymustoriginatefromadedicatedinstrumentqualitycompressedairheader(1/2"pipeorlarger),nofartherthantwenty(20)feetfromtheprotectionsystem.LocalcompressorsandgascylindersshouldnotbeusedbeforeconsultingwithPepperl+Fuchs.

Theprotectivegassupplytotheprotectionsystemmustberegulatedfrom120psimaximumto80psiminimum.

Pneumatic Connection RequirementsALLFITTINGSMAYBECUSTOMERORFACTORYFURNISHED

1. Forsystemsupply,one(1)SC-63/8"malestraightconnectororone(1)NC-63/8"maleelbowconnectororequivalentfittingpersystem.

One(1)similarfittingwhichwillconnecttheinertgassupplytubingtotheinertgassupplyheaderconnectionpointandone(1)lotof3/8"O.D.,.035"wallthickness,weldedorseamlessstainlesssteeltubing.

2. Forenclosuresupply,one(1)EFC-63/8"flushconnector,orone(1)EBC-63/8"feed-throughconnectororequivalentfittingpersystem.

3.Forenclosurereference,one(1)modelEFC-41/4"flushconnector,orone(1)EBC-41/4"feed-throughconnectororequivalentfittingpersystem.

4.One(1)lotof1/4"O.D.,.035"wallthickness,weldedorseamlessstainlesssteeltubing.

5.Formultipleenclosureconnections,two(2)EPC-131.25"pipemountinghubsorequivalentand1.25"150#ratedpipecouplings&unionsperinterconnection.

One(1)lot150#rating1.25"galvanizedoraluminumpipeandfittings,fullyreamedandunrestricted.

PM Pneumatic Connection RequirementsInadditiontoitemnumbers1,4and5above,thefollowingfittingsarerequiredforallPMconfigurations.

1. ForsystemsupplyonPMconfigurations,one(1)additionalEBC-6orequivalent3/8"throughbulkheadfittingpersystemisrequired.

2. Foratmosphericreference,one(1)PRB-4orequivalent1/4"femalebulkheadfittingandstainlesssteelsinteredelementisrequired.

SYSTEM SUPPLY FITTINGSSC-6 NC-6

ENCLOSURE SUPPLY & REFERENCE FITTINGSEBC-4 & EBC-6EFC-4 & EFC-6

EPC-13

SYSTEM ATMOSPHERIC REFERENCE FITTINGPRB-4

MULTIPLE ENCLOSURE CONNECTION FITTING

Page 12: Installation and Operation Manual: Model 1003 Type Y or Z ...files.pepperl-fuchs.com/selector_files/navi/productInfo/doct/tdoct... · Page 23 Systems identification & application

Model 1003 Installation and Operation Manual

12

Par

t No.

511

967

Dra

win

g N

o. 1

29-0

195b

03/

09

Subject to modifications without notice

Pepperl+Fuchs Groupwww.pepperl-fuchs.com

USA: +1 330 486 [email protected] [email protected]

Singapore: +65 6779 [email protected]

Copyright Pepperl+Fuchs

Germany: +49 621 776 2222

HELPFUL HINTSAllworkmustbeperformedbytechniciansqualifiedinpneumatictubingandelectricalconduitinstallation.

Pepperl+Fuchsrecommendstheuseof.035"wallthickness,weldedorseamlessstainlesssteeltubing.

Ifflexibletubingisused,itmustbeinstalledinamannerthatprotectsitfromdamageandcorrosion.

Tubing Installation

Tubing LH, RH, TM, BM, WM & FM ConfigurationsSystem supply connections

1. Selectorinstallaprotectivegassupplyheadertap,fittedwiththepropertubesizefittingandlocatedwithintwenty(20)feetoftheenclosureprotectionsystem.

2. Ifaservicevalveisplacedbetweentheprotectivegassupplyheaderandtheenclosureprotectionsystem,itmustbeinstalledincloseproximityoftheprotectedenclosureandbelabeledinaccordancewithsection2-11.4oftheNFPA496,1998edition.

3. Selecttheappropriatefittingsrequiredtoconnecttheprotectivegassupplytotheprotectionsystemregulatorasdeterminedonpage11,“PneumaticConnectionRequirements.”

4. Determineappropriatetubingroutefromtheprotectivegassupplyheadertotheprotectionsystemregulator.

5. Bendtubingusingindustrialgradebenders,checktubingfittoensureproperseatingbetweenthetubingandfittings.Fullyreamalltubingends.

6. Installtubingandtightenallfittingstofittingmanufacturer’sspecifications.Securetubingtoappropriatestructuralsupportsasrequired.

Enclosure supply & reference connections

1.Chooselocationfortheenclosuresupplyconnection(s)basedontherequirementsonpage6,“GettingStarted.”

2. Placetheenclosurereferenceconnectionfittingdirectlybehindtheenclosureprotectionsystemandatleastonefootawayfromtheenclosuresupplyandenclosureprotectionventconnections,wheneverpossible.Forsystemsprotectingmultipleenclosuresinseries,theenclosurereferenceconnectionfittingmustbeplacedonthelastenclosureintheseries.Seepage6,“GettingStarted.”

3. Drillanddeburrenclosuresupplyandreferencefittingholesontheprotectedenclosure.Mountthefittings.

4. Determineappropriateroutefortheenclosuresupplyandreferencetubing.

5. Bendtubingusingindustrialgradebenders,checktubingfittoensureproperseatingbetweenthetubingandfittings.Fullyreamalltubingends.

6. Installtubingandtightenallfittingstofittingmanufacturer’sspecifications.Securetubingtoappropriatestructuralsupportsasrequired.

Tubing PM ConfigurationsEnclosure Bulkhead Fittings

1. Selectthefittingsrequiredtoinstallthesystemsupply,systemsupplybulkheadfittingandatmosphericreferencebulkheadfitting.Seepage11,“PneumaticTubingRequirements.”

2.Chooselocationforthesystemsupplybulkheadfitting.Thisfittingallowstheprotectivegassupplytopassthroughthewallofaprotectedenclosuretotheprotectionsystem’sregulatorsupplyinletconnection.

3. Chooselocationfortheatmosphericreferencebulkheadfitting.Thisfittingallowstheenclosurepressuregaugetoreferenceatmosphericpressure.

4. Drillanddeburrsystemsupplyandreferencebulkheadfittingholesintheprotectedenclosure.Mountthefittings.

System supply & reference connections

1. Selectorinstallaprotectivegassupplyheadertap,fittedwiththepropertubesizefittingandlocatedwithintwenty(20)feetoftheenclosureprotectionsystem.

2. Ifaservicevalveisplacedbetweentheprotectivegassupplyheaderandtheprotectionsystem,itmustbeincloseproximityoftheprotectedenclosureandlabeledinaccordancewiththeNFPA496.

3. Determineappropriatetubingroutefromtheprotectivegassupplyheadertothesystemsupplybulkheadfitting.

4. Determineappropriatetubingroutefromthesystemsupplybulkheadfittingtotheprotectionsystemregulator.

5. Determineappropriatetubingroutefromtheatmosphericreferencebulkheadfittingtotheenclosurepressuregauge’sreferenceinletconnection.

6. Bendtubingusingindustrialgradebenders,checktubingfittoensureproperseatingbetweenthetubingandfittings.Fullyreamalltubingends.

7. Installtubingandtightenallfittingstofittingmanufacturer’sspecifications.Securetubingasrequired.

Page 13: Installation and Operation Manual: Model 1003 Type Y or Z ...files.pepperl-fuchs.com/selector_files/navi/productInfo/doct/tdoct... · Page 23 Systems identification & application

Model 1003 Installation and Operation Manual

13

Par

t No.

511

967

Dra

win

g N

o. 1

29-0

195b

03/

09

Subject to modifications without notice

Pepperl+Fuchs Groupwww.pepperl-fuchs.com

USA: +1 330 486 [email protected] [email protected]

Singapore: +65 6779 [email protected]

Copyright Pepperl+Fuchs

Germany: +49 621 776 2222

Tubing Connection Diagrams

LH, RH, TM, BM, WM & FM Configuration Connection Points & Pneumatic Diagram

PM Configuration Connection Points & Pneumatic Diagram

RapidExchange

controlvalve

Regulator

System supplyinlet

Enclosure supply outlet

Enclosurepressuregauge

Enclosurereference

inlet

Venturiorifice

Enclosurepressurecontrolvalve

Mountingplate

LPS Style

ProtectedEnclosure

WPS & WPSA Style

Inlet

Enclosurepressuregauge

OptionalEXPpressureswitch

Sinteredvent

Sinteredvent

Regulator

Venturiorifice

Systemsupply

Reference Enclosurereferencebulkheadfitting

EnclosuresupplybulkheadfittingSupply

Requiredenclosureprotectionvent

RapidExchang-pressuregauge

RapidExchange

controlvalve

Enclosurepressurecontrolvalve

Enclosurepressuregauge

Atmosphericreference

inlet

Enclosurepressure

controlvalve

Mountingplate

Enclosureprotectionvent

Protectedenclosure

RapidExchange

controlvalve

Regulator

System supply inlet

Systemsupply

InletSystemsupply

bulkhead

AtmosphericreferencebulkheadEnclosure

supply outlet

Enclosurepressuregauge

Regulator

RapidExchange

pressuregauge

Sinteredvent

RapidExchange

controlvalve

Enclosurepressurecontrolvalve

HELPFUL HINTPneumaticconnectionsarebolded.

Page 14: Installation and Operation Manual: Model 1003 Type Y or Z ...files.pepperl-fuchs.com/selector_files/navi/productInfo/doct/tdoct... · Page 23 Systems identification & application

Model 1003 Installation and Operation Manual

14

Par

t No.

511

967

Dra

win

g N

o. 1

29-0

195b

03/

09

Subject to modifications without notice

Pepperl+Fuchs Groupwww.pepperl-fuchs.com

USA: +1 330 486 [email protected] [email protected]

Singapore: +65 6779 [email protected]

Copyright Pepperl+Fuchs

Germany: +49 621 776 2222

Electrical Supply Requirements

General Wiring RequirementsWARNING!This device contains electrical parts that can cause shock or injury.

Allelectricalconnections,conduitandfittingsontheprotectedenclosuremustbesuitableforthehazardouslocationinwhichtheyareinstalled.Inaddition,allconduitandwiremustbeinstalledinaccordancewithNECasrequiredandallrelevantplantandlocalcodes.

Note:Donotusesealsonconduitusedasaprotected“wireway”tosupplyprotectivegastoadjacentprotectedenclosures.Thesameconduitcanbeutilizedforbothelectricalandpneumaticservicetoanadjacentprotectedenclosure(s),providedtheconduitisoversizedtoallowaminimumfreeclearanceequaltoorlargerthanthepipesizerequiredbetweenmultipleenclosuresasstatedonpage6,“GettingStarted.”

Enclosure Power RequirementsTheprotectedenclosure(s)electricalpowersourcemustoriginatefromacircuitbreakerorfuseddisconnectsuitableforthehazardouslocationinwhichitisinstalled.Theswitchmustbelocatedwithinfifty(50)feetoftheprotectedenclosure(s)andtheprotectionsystemandbeproperlymarked.

Alarm Signal RequirementsTheWPSAstylepressureswitchrequiresa120VACpowersupplyinadditiontothealarmsignal.TheWPSandWPSAstylesystemsalarmsignalmayoriginatefromtheprotectedenclosureifthealarmsignalisdisconnectedbytheprotectedenclosure’scircuitbreakerorfuseddisconnectasstatedinenclosurepowerrequirementsabove.

Theprotectedenclosure(s)alarmsignalpowermayalsooriginatefromoutsideoftheprotectedenclosure.Inthisapplication,theprotectedenclosuremaybeusedasa“wireway”topassalarmsignalwiringfromthepowersourcetothealarmdevice,ifthewiringisisolatedandproperlylabeled.Inaddition,appropriateconduitsealsmustbeprovidedoutsideoftheprotectedenclosureseparately.

IMPORTANT NOTE: NFPA 496 requires the use of an alarm or an indicator to detect the loss of safe enclosure pressure. In addition, the NFPA 496 requires that if an indicator alone is utilized, a protective gas supply alarm must also be installed between the last valve in the protective gas supply and the protected enclosure. Therefore, the protective gas supply to all LPS Style systems must be equipped with the above mentioned protective gas supply alarm. Exception: systems utilizing either an EPSK or GPSK enclosure pressure loss alarm switch accessory will satisfy the above mentioned NFPA requirement.

Typical Enclosure Wiring MethodsProtectedenclosuresshouldbewiredsimilartoexplosionproofenclosures,inaccordancewithArticle500oftheNationalElectricCode-NFPA70.

Singleconductorwiringshouldbeplacedinrigidmetalconduit,seal-flexconduitorothermediumsapprovedforuseinthehazardouslocationsurroundingtheprotectedenclosure.Additionally,NFPA496requirestheuseofapprovedsealsonallpressurizedenclosureconduitwiringentries,inaccordancewithNFPA70.Furthermore,theuseofanapprovedsealissimplythemostpracticalwaytopreventexcessiveleakagethroughconduitconnections.

However,whileexplosionproofenclosuresrequireconduitsealsonallcableentries,inaccordancewithNFPA70.Othermethodsofsealedcableentriesthataresuitableforhazardouslocationscanbeused,suchascompressionglands.

Inconclusion,therearetwoprimarygoals.First,theinstallershouldensurethatallassociatedwiringandcableisprotectedbypressurizationorothermeans,suchasexplosionproofconduitorintrinsicsafetybarriers.Secondly,theinstallershouldensurethatallassociatedconduitandwirewaysaresealedtoconserveprotectivegas,unlesstheyareusedtosupplyprotectivegastootherenclosuresordevices.

Typical Enclosure Wiring Connections

Explosionproofdevice

Seal

Intrinsicallysafeorfiberopticdevice

Adjacentpressurized

device

Independentlypressurized

device

Intrinsicallysafeorfiberopticdevice

Seal

Conduit

Conduit

Conduit

Glandfitting

Cable

Seal

Pressurizedraceway

Protectedenclosureordevice

Page 15: Installation and Operation Manual: Model 1003 Type Y or Z ...files.pepperl-fuchs.com/selector_files/navi/productInfo/doct/tdoct... · Page 23 Systems identification & application

Model 1003 Installation and Operation Manual

15

Par

t No.

511

967

Dra

win

g N

o. 1

29-0

195b

03/

09

Subject to modifications without notice

Pepperl+Fuchs Groupwww.pepperl-fuchs.com

USA: +1 330 486 [email protected] [email protected]

Singapore: +65 6779 [email protected]

Copyright Pepperl+Fuchs

Germany: +49 621 776 2222

Conduit Installation

Electrical Conduit1.Choosethelocationfortheenclosure’selectricalconduit

connection(s)basedontherequirementsonpage14,“ElectricalSupplyRequirements.”

2. Drillanddeburrenclosureconduitfittingholesintheprotectedenclosure.Mountthefittings.

3. Determineappropriateroutefortheenclosureelectricalandpoweralarmsignalconduit.

4. Measure,cutandthreadconduit,checkconduitfittoinsureproperseating.Fullyreamallconduit.

5. Installconduitandtightenallfittingstofittingmanufacturersspecifications.Secureconduittoappropriatestructuralsupportsasrequired.

6. Sealallconduitwithanapprovedcompoundpriortooperationoftheprotectionsystem.

WPS & WPSA Style ConduitWPSandWPSAstylesystemsprovideelectricalcontactsforaudibleorvisualalarmdevicesthatsignalalossofprotectedenclosurepressure.WPSandWPSAstylesystemsarecalibratedtoalarmat0.15"forClassIapplications.Theswitchesaresuitableforhazardous(classified)outdoorlocations.Wiringmustbeinstalledwithasealandconduitfittingssuitableforthearea.Alarmcircuitpowermaybederivedfromtheprotectedenclosurepowersourceoranintrinsicallysafealarmsignalsource.Allassociatedalarmdevicesmustbeprotectedbysuitablemeans(explosionproof,purgedorintrinsicallysafe).

WPS & WPSA Style Conduit Connection PartsFittingKitsCanBeFactoryFurnished

1. ForWPSandWPSAstyleEXPpressurelossalarmswitchconnectedtoanenclosuremountedalarm,one(1)LCK(Lfittingconduitkit)orequivalentconduitelbow,couplingandsealfittings.

2. ForWPSandWPSAstyleEXPpressurelossalarmswitchconnectedtoaremotemountedalarm,one(1)TCK(Tfittingconduitkit)orequivalentconduittee,couplingandsealfittings.

3. One(1)lot150#rating1/2”galvanizedoraluminumpipe.

HELPFUL HINTItmaybeimpracticaltopourallelectricalconduitsealspriortoinstallationinthefield.However,allconduitconnectionsmustbesealedforpropertestingandoperationoftheenclosureprotectionsystem.Therefore,theuseoftemporarysealssuchasductsealormaskingtapeforbenchorshoptesting,priortofinalfieldinstallationmaybeused.

LCK “L” Fitting Conduit Kit

TCK “T” Fitting Conduit Kit

WPS Style EXP Pressure SwitchWith Cover Removed

Switchbody

Setpointcalibration

screw

Groundingscrew

1/2"conduitport

Electricalswitch

contacts

Lowportsintered

vent

Highporttubefitting

WPSA Style EXP Pressure SwitchWith Cover Removed

Switchbody

Setpointcalibration

screw

Groundingscrew

1/2"conduitport

Lowportsintered

vent

120VACpower&electricalswitch

contacts

Highporttubefitting

Page 16: Installation and Operation Manual: Model 1003 Type Y or Z ...files.pepperl-fuchs.com/selector_files/navi/productInfo/doct/tdoct... · Page 23 Systems identification & application

Model 1003 Installation and Operation Manual

16

Par

t No.

511

967

Dra

win

g N

o. 1

29-0

195b

03/

09

Subject to modifications without notice

Pepperl+Fuchs Groupwww.pepperl-fuchs.com

USA: +1 330 486 [email protected] [email protected]

Singapore: +65 6779 [email protected]

Copyright Pepperl+Fuchs

Germany: +49 621 776 2222

Set-up Procedure

Class I Purging Set-up1.ClosetheenclosurepressureandRapidExchangecontrol

valvesfullybyturningclockwise(CW).

2.ConnecttheinertgassupplytothesystemsupplyinletandsettheRapidExchangepressuregaugeto60psi.

3. Temporarilyconnecta0-10inchwatercolumnpressuregaugeormanometertotheprotectedenclosure.

4.Checkoperationofenclosureprotectionventasdetailedabove.See"HelpfulHint."

5.Sealenclosure(s)andadjustenclosurepressurecontrolvalvebyopeningslowlycounterclockwise(CCW)toseta“safe”pressureontheenclosurepressuregauge.

NOTE:Ifpressuresettingisdifficulttostabilizeorset,seepage18,“TroubleshootingProcedures.”

6.OpenRapidExchangecontrolvalvefullybyturning90°CCWandquicklyensuretheenclosureprotectionventopens.Note:Theenclosurepressuregaugeshouldmovequicklyoffscaletotheright,thisisnormalforallRapidExchangepurgingsystems.

7. Readjusttheregulatorto60psiminimum,whileinducingRapidExchange,untilthetestgaugereadsapproximately2inchesofpressureanddoesnotfluctuate.(insufficientenclosurepressurewillcausetheenclosureprotectionventto"shuttle")DONOTexceed10inchesofpressurewithintheprotectedenclosure.

8. Installandtightenallboltsonthepressurelossalarmswitch(ifutilized).Ensuretheconduitissealedwithapprovedcompounds.Energizepowertoswitchandalarmsystem(ifutilized)andtestthefunctionofthealarmsystem.

9.Ceasetestingandremovetestequipment.

Pepperl+FuchsRapidExchangepurgingsystemsprovideapre-calibratedandcertifiedvolumeexchangerate.WiththeRapidExchangepressuregaugesetat60psiminimum,themodel1003willaccomplishtherequiredvolumeexchangesatarateofONEMINUTEPER2.5CUBICFEETofenclosurevolume.

NOTE:Thevolumeexchangerateisbasedonafour(4)enclosurevolumeexchange.Multiplytherequiredexchangetimeby2.5forapplicationsrequiringaten(10)volumeexchange(motors).

Regardlessofenclosurevolumeorsystemflowrate,itisrequiredthatoperatorswithholdpowertotheenclosurewhileinducingtheClassIenclosurevolumeexchange,foratleastfive(5)minutes.Normalexchangetimesshouldbedoublediflargeobstructionsblockinertgasflow.

Thestart-upinstructionnameplateexchangetimeslotwillfeaturethestandardfactorforthissystem"ONEMINUTEPER2.5CUBICFEET,"buttheunitmayfeatureasetofdirectfactornameplateswithself-adhesivebackingsuchas“TENMINUTES,”forapplicationtothestart-upinstructions,dependentonhowthesystemwasspecifiedandpurchased.Fieldmodificationofthisnameplate,toshowadirectfactor,isacceptableasnotedaboveifthemethodusedtomarkthenameplatedoesnotdefacetheinstructionslisted.Materialsusedforthemarkingmustbeindelibleandwithstandprevailingenvironmentalconditions.

IMPORTANT NOTE: Operators must secure wrist or stop watch to manually time exchange cycle for all applications.

HELPFUL HINTSTheterm“safe”pressureforpurposesofthismanualisdefinedasaminimum.25inchofwatercolumnpressure.

Regulatormaybeinthelockedpositionuponarrival.Toadjustregulator,pullhandletooutwardposition.

Totestthevent’soperation,gentlyprodtheventflapperopenwithasoft-pointedobject,(example:eraserendofapencil)ensuringthattheventvalveworksfreely.Onverticallyconfiguredvents,thiscanbeaccomplishedfromwithintheprotectedenclosure.Sidemounted-90configuredventscanbetestedbyremovingtheconduitplugatthebottomofthemountingtee.Multipleoperationsrequireonlyonetestperdayifenclosureisnotopenedorleftunattended.

Page 17: Installation and Operation Manual: Model 1003 Type Y or Z ...files.pepperl-fuchs.com/selector_files/navi/productInfo/doct/tdoct... · Page 23 Systems identification & application

Model 1003 Installation and Operation Manual

17

Par

t No.

511

967

Dra

win

g N

o. 1

29-0

195b

03/

09

Subject to modifications without notice

Pepperl+Fuchs Groupwww.pepperl-fuchs.com

USA: +1 330 486 [email protected] [email protected]

Singapore: +65 6779 [email protected]

Copyright Pepperl+Fuchs

Germany: +49 621 776 2222

Operating Sequence

WARNING! Do not exceed "safe" pressure with the enclosure pressure control valve. Operators must

follow step-by-step sequence of the start-up instructions nameplate on the protection system.

Class I Purging OperationWiththeinertgassupplyconnected,enclosurepowerdeenergizedandalarmsystemenergized(ifutilized).

1.Carefullyreadstart-upinstructionnameplateonsystem.

2.Checkoperationoftheenclosureprotectionvent(modelEPV-3),openingitmanuallyseveraltimes.Seepage16,“HelpfulHint.”

3.Sealprotectedenclosure(s).

4.Openenclosurepressurecontrolvalve,byturningCCW,tosetenclosurepressuregaugeat“safe”pressure,thepressurelossalarmswitchshouldthenactivatetosilencethealarmsystem(ifutilized).

5.Ensuretheprotectionsystemenclosurepressuregaugemaintainsa“safe”pressureforone(1)minute.

6.OpenRapidExchangecontrolvalvefullybyturning90°CCWandquicklyensuretheenclosureprotectionventopens.Note:Theenclosurepressuregaugeshouldmovequicklyoffscaletotheright,thisisnormalforallRapidExchangepurgingsystems.

7. Standbyfortheexchangetimeasspecifiedonthestart-upinstructionnameplate(fiveminutesminimum),thenclosetheRapidExchangecontrolvalvefully.

8. Waitfortheenclosurepressuregaugetoreturntoa"safe"pressureandenergizetheprotectedenclosure(s)powerviathelocaldisconnectswitch.

9.Ensuretheenclosurepressureindicatormaintainsa“safe”pressurebeforeleavingsystemunattended.

Model identification

nameplate

Model 1003-LPS front view

Model 1003-WPS & WPSA front view

Enclosure pressure control valve

EXP pressure loss alarm

switch

Enclosure pressure

gauge

Rapid Exchange

pressure gauge

Rapid Exchange

control valve

Start - up instruction nameplate

Page 18: Installation and Operation Manual: Model 1003 Type Y or Z ...files.pepperl-fuchs.com/selector_files/navi/productInfo/doct/tdoct... · Page 23 Systems identification & application

Model 1003 Installation and Operation Manual

18

Par

t No.

511

967

Dra

win

g N

o. 1

29-0

195b

03/

09

Subject to modifications without notice

Pepperl+Fuchs Groupwww.pepperl-fuchs.com

USA: +1 330 486 [email protected] [email protected]

Singapore: +65 6779 [email protected]

Copyright Pepperl+Fuchs

Germany: +49 621 776 2222

Troubleshooting Procedures

Problem or Fault Possible Causes Corrective Action

Enclosurepressurecontrolvalvewillnotholda"safe".25inchpressure.

Leakagearoundgasketing,covers,seams,pipingandtubingconnections,conduitconnectionsandelectricalconduitsealsoftheenclosure.

Tightenenclosurelatches:Wheretighteningisnotfeasible,andgasketingmaterialsarenotpractical,holesorgapscanbeclosedwithsiliconesealantappliedfrominsidetheprotectedenclosure.

Enclosurepressuregaugereadingisdifficulttostabilize.

Insufficientenclosureleakageoropeningoftheventuriorificeiscrimpedtosmall.

Removetheorifice,cutoffthecrimpedendandreamthetube,thenrecrimpandreinstallthetubetonoteeffect.Astubeisshortened,reamed,andrecrimped,sensitivitydecreases,allowingeasieradjustmentofsetpointontheenclosurepressuregauge.

Enclosurepressurelossalarmswitchdoesnotappeartobeoperating.

Pressureswitchisoutofcalibration.

Pressureswitchhasnotbeenenergized(WPSAstylesystemsonly)

Calibratebyslowlyadjustingcounterclockwisetodecreasethesetpoint,andclockwisetoraisethesetpoint.(Donotattempttocalibratetheswitchuntilalleffortstomaketheswitchrespondproperlyhavefailed)

Verify120VAChasbeenappliedtopowercontactsofWPSAstylesystem.

Problemspersists,orifthesystemdoesnotappeartobeoperatingproperly.

Problemspersist ContactPepper+Fuchsapplications/customerservicedepartmentat330-486-0002

Thissectioncoversthemostcommonproblemsdocumentedwiththissystem.Anyproblemsnotcoveredinthissectionshouldbeaddresseddirectlytoourfactory.Pleaseaddressallserviceneedsto:

Pepperl+Fuchs, Inc. Customer Service Department

Page 19: Installation and Operation Manual: Model 1003 Type Y or Z ...files.pepperl-fuchs.com/selector_files/navi/productInfo/doct/tdoct... · Page 23 Systems identification & application

Model 1003 Installation and Operation Manual

19

Par

t No.

511

967

Dra

win

g N

o. 1

29-0

195b

03/

09

Subject to modifications without notice

Pepperl+Fuchs Groupwww.pepperl-fuchs.com

USA: +1 330 486 [email protected] [email protected]

Singapore: +65 6779 [email protected]

Copyright Pepperl+Fuchs

Germany: +49 621 776 2222

PEPPERL+FUCHS STANDARD 24-MONTH WARRANTY1. LimitedWarranty.Pepperl+Fuchs,Inc.(“P+F")warrantsPurgeUnitsandcomponentsforPurgeUnitsmanufacturedbyP+F

(“Product"or“Products")tobefreefromdefectsinmaterialandworkmanshipunderNormalUseforaperiodoftwenty-four(24)monthsfromthedateofshipmentofsuchProductsfromP+F’swarehouseorplaceofmanufacture(orfromP+F’sauthorizedrepresentativeordistributor).OnlytheoriginalpurchaserofsuchProducts(the“Customer")shallbeentitledtothebenefitoftheforegoingLimitedWarranty.Norepresentative,agentorsalesmanofP+FisauthorizedtogiveorprovideanywarrantyormakeanyrepresentationcontrarytoorinadditiontotheforegoingLimitedWarranty.

2. InspectionandClaims.CustomermustinspectandtestallProductsuponreceipt.AllclaimsundertheLimitedWarrantyprovidedhereinmustbemadewithinthirty(30)daysofthediscoveryofthedefect.CustomermustobtainshippinginstructionsfromP+FpriortoreturninganyProduct,whichProductmustbereturnedatCustomer’sexpenseinaccordancewithP+F’sinstructions.

3. LimitationsandExclusions.“NormalUse"shallmeanuseandoperationwithinratedcapacities,atthecorrectvoltage,andwithanyrequiredmaintenanceasprovidedintheapplicableP+FOperatingManuals.TheLimitedWarrantyprovidedhereindoesnotapplyto(i)anyProductswhichhavebeenalteredormodifiedinanywayordisassembledbytheCustomeroranyoneelse,(ii)anyProductswhichhavebeensubjecttomisuse,negligenceoraccident,orimproperlyinstalled,changed,substitutedorreplaced,(iii)anypartorcomponentnotmanufacturedbyP+F,or(iv)anypartorcomponentthatissubjecttowearorconsumption.ForpartsorcomponentsnotmanufacturedbyP+F,theCustomeroranyotheruserorownershallhaveonlythewarrantyprovidedbythemanufacturerofsuchpartorcomponent.TheLimitedWarrantysetforthhereinisalsosubjecttothefollowing:

(1) TheLimitedWarrantyislimitedtoelectronicandmechanicalperformanceonly,asexpresslydetailedintheproductspecifications,anddoesnotapplytocosmeticappearance;

(2) TheLimitedWarrantyshallnotapplytoanycablesattachedto,orintegratedwith,anyProducts.

(3) TheLimitedWarrantyshallnotapplytoanyProductswhicharestored,orutilized,inharshenvironmentalorelectricalconditionsoutsideP+F’swrittenspecifications.

THELIMITEDWARRANTYSETFORTHHEREINISTHEONLYWARRANTYMADEBYP+FWITHRESPECTTOTHEPRODUCTS.ITISEXPRESSLYAGREEDANDUNDERSTOODTHATP+FMAKESNOWARRANTYOFMERCHANTABILITYORFITNESSFORAPARTICULARPURPOSE.EXCEPTFORTHELIMITEDWARRANTYSETFORTHHEREIN,THEREISNOOTHERWARRANTY,EXPRESS,IMPLIEDORSTATUTORY;ANDTHEREISNOAFFIRMATIONOFFACTORPROMISEBYP+FWITHREFERENCETOTHEPRODUCTS.INNOEVENTSHALLP+FBELIABLEFORACTUALORANTICIPATEDLOSTPROFITSORFORINCIDENTALORCONSEQUENTIALORPUNITIVEDAMAGESORFORDAMAGESRESULTINGFROMBUSINESSINTERRUPTION,ORINJURYORDEATHOFPERSONS,ORINJURYTOPROPERTY.P+F’SLIABILITYONANYCLAIMOFANYKINDARISINGOUTOF,CONNECTEDWITHORRESULTINGFROMTHEDESIGN,MANUFACTURE,SALE,REPAIROROPERATIONOFAPRODUCT,SHALLNOTEXCEEDTHEPRICEALLOCABLETOTHATPRODUCTORTHEPARTTHEREOFWHICHGIVESRISETOTHECLAIM.THEREMEDYSETFORTHINTHISLIMITEDWARRANTYCONSTITUTESTHESOLEANDEXCLUSIVEREMEDYOFTHECUSTOMER.P+FSHALLNOTBELIABLEFORPENALTIESOFANYDESCRIPTION.

4. LimitationofRemedies.IntheeventofP+F’sliability,whetheronthisLimitedWarrantyorbasedoncontract,tort(including,butnotlimitedto,negligenceandstrictliability)orotherwise,Customer’ssoleandexclusiveremedywillbelimitedto,atP+F’soption,therepairorreplacement(f/o/bP+F’splaceofmanufacture)byP+Fofanynon-conformingitemsforwhichclaimismadebyCustomerinaccordancewithparagraph2,ortherepaymentoftheportionofthepurchasepricepaidbyCustomerattributabletothenon-conformingitem.

5. ResponsibilityofCustomer:SafetyandProtectionPrecautions.P+FtakesgreatcaretodesignandbuildreliableanddependableProducts;however,someProductscanfaileventually.Customermusttakeprecautionstodesignitsequipmenttopreventpropertydamageandpersonalinjuryintheunlikelyeventofafailure.ASAMATTEROFPOLICY,P+FDOESNOTRECOMMENDTHEINSTALLATIONOFPRODUCTSASTHESOLEDEVICEFORTHEPROTECTIONOFPERSONNELORPROPERTYAND,THEREFORE,THECUSTOMERSHOULDBUILDINREDUNDANCYORDUALCONTROLUSINGAPPROVEDSAFETYDEVICESFORTHESEAPPLICATIONS.

6. Conflicts.IntheeventthereisanyconflictbetweentheprovisionsofthisLimitedWarrantyandanyprovisionscontainedinanyorders,offers,acceptancesorotherwritingsorstatementsprovidedormadebyCustomertoP+F,theprovisionsofthisLimitedWarrantyshallprevail,andthecontractbetweenP+FandtheCustomershallbedeemedformedonlyupontheprovisionssetforthinthisLimitedWarranty,andanyadditionalorconflictingprovisioninsertedbyCustomershallbeofnoforceoreffect.

Warranty Terms and Conditions

Page 20: Installation and Operation Manual: Model 1003 Type Y or Z ...files.pepperl-fuchs.com/selector_files/navi/productInfo/doct/tdoct... · Page 23 Systems identification & application

Model 1003 Installation and Operation Manual

20

Par

t No.

511

967

Dra

win

g N

o. 1

29-0

195b

03/

09

Subject to modifications without notice

Pepperl+Fuchs Groupwww.pepperl-fuchs.com

USA: +1 330 486 [email protected] [email protected]

Singapore: +65 6779 [email protected]

Copyright Pepperl+Fuchs

Germany: +49 621 776 2222

Notes

Page 21: Installation and Operation Manual: Model 1003 Type Y or Z ...files.pepperl-fuchs.com/selector_files/navi/productInfo/doct/tdoct... · Page 23 Systems identification & application

Model 1003 Installation and Operation Manual

21

Par

t No.

511

967

Dra

win

g N

o. 1

29-0

195b

03/

09

Subject to modifications without notice

Pepperl+Fuchs Groupwww.pepperl-fuchs.com

USA: +1 330 486 [email protected] [email protected]

Singapore: +65 6779 [email protected]

Copyright Pepperl+Fuchs

Germany: +49 621 776 2222

Notes

Page 22: Installation and Operation Manual: Model 1003 Type Y or Z ...files.pepperl-fuchs.com/selector_files/navi/productInfo/doct/tdoct... · Page 23 Systems identification & application

Model 1003 Installation and Operation Manual

22

Par

t No.

511

967

Dra

win

g N

o. 1

29-0

195b

03/

09

Subject to modifications without notice

Pepperl+Fuchs Groupwww.pepperl-fuchs.com

USA: +1 330 486 [email protected] [email protected]

Singapore: +65 6779 [email protected]

Copyright Pepperl+Fuchs

Germany: +49 621 776 2222

System Maintenance

Regular MaintenanceDraintheprotectionsystemregulatorfrequentlyandcleansystemwithnonsolventcleaningagentsonly.

Long-Term MaintenanceCalibratetheenclosurepressureindicatorto0inchesbyventingthepurgepressurereferenceportandtheprotectedenclosuretoatmosphereandadjustingthecalibrationscrewinthelowercenterportionoftheindicator’sface.

Fullyopentheenclosurepressurecontrolregulator,toblowoutanydepositsaroundthetipofthevalveandtoensurethattheenclosureprotectionventisoperatingproperly,thencarefullyreadjustsystemaccordingtotheset-upprocedureandoperatingsequenceonpages16and17.Replaceortightenstempackingnutasrequiredtoprohibitstempackingleakage.

Carefullydisassembletheenclosureprotectionventbylooseningthetwobottomhexnutsthatholdtheunittogether.

(DO NOT REMOVE CAP NUTS ON TOP OF VENT BODY)

Carefullycleantheflappervalveandventbodyseatswithwarmsoapandwater,beingcarefulnottoextendtheventvalvebeyonditsnormalopeningpoint,andbeingcarefulnottoexertanystressonthevalvehinge.

Examinetheentireprotectionsystemandtheprotectedenclosure(s),andreplaceanydefectivepartsduringroutineshutdownoftheprotectedenclosure(s).PartsareavailablefromPepperl+Fuchsonimmediatenoticeasrequired.

MAINTENANCE SCHEDULEDate Work performed Performed by

Page 23: Installation and Operation Manual: Model 1003 Type Y or Z ...files.pepperl-fuchs.com/selector_files/navi/productInfo/doct/tdoct... · Page 23 Systems identification & application

Model 1003 Installation and Operation Manual

23

Par

t No.

511

967

Dra

win

g N

o. 1

29-0

195b

03/

09

Subject to modifications without notice

Pepperl+Fuchs Groupwww.pepperl-fuchs.com

USA: +1 330 486 [email protected] [email protected]

Singapore: +65 6779 [email protected]

Copyright Pepperl+Fuchs

Germany: +49 621 776 2222

Systems Identification & Application Information

Date of installation _____________________________________________________

Unit serial #____________________________________________________________

Item ___________________________________________________________________

Customer P.O.# ________________________________________________________

Customer project# _____________________________________________________

Service ________________________________________________________________

Type __________________________________________________________________

Features ______________________________________________________________

Application ____________________________________________________________

Notes: _______________________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

Page 24: Installation and Operation Manual: Model 1003 Type Y or Z ...files.pepperl-fuchs.com/selector_files/navi/productInfo/doct/tdoct... · Page 23 Systems identification & application

5 1

8

4

2

6

7

3

PROCESS AUTOMATION – PROTECTING YOUR PROCESS

For over a half century, Pepperl+Fuchs has provided new concepts for the world of process automation. Our company sets standards in quality and innovative technology. We develop, produce, and distribute electronic interface modules, Human-Machine Interfaces and hazardous location protection equipment on a global scale, meeting the most demanding needs of industry. Resulting from our world-wide presence and our high flexibility in production and customer service, we are able to offer complete individual solutions – wherever and whenever you need us. We are the recognized experts in our technologies – Pepperl+Fuchs has earned a strong reputation by supplying the world’s largest process industry companies with the broadest line of proven components for a diverse range of applications.

www.pepperl-fuchs.com

Worldwide/German Headquarters Pepperl+Fuchs GmbH Mannheim · GermanyTel. +49 621 776 2222E-Mail: [email protected]

1

Asia Pacific HeadquartersPepperl+Fuchs PTE Ltd. SingaporeCompany Registration No. 199003130ETel. +65 6779 9091E-Mail: [email protected]

2

Central/Western Europe & Africa HeadquartersPepperl+Fuchs N.V. Schoten/Antwerp · BelgiumTel. +32 3 6442500E-Mail: [email protected]

3

Middle East HeadquartersPepperl+Fuchs M.E (FZE) Dubai · UAETel. +971 4 883 8378E-Mail: [email protected]

4

North/Central America Headquarters Pepperl+Fuchs Inc. Twinsburg · Ohio · USATel. +1 330 486 0002E-Mail: [email protected]

5

Northern Europe HeadquartersPepperl+Fuchs GB Ltd. Oldham · EnglandTel. +44 161 6336431E-Mail: [email protected]

6

Southern/Eastern Europe HeadquartersPepperl+Fuchs Elcon srl Sulbiate · ItalyTel. +39 039 62921E-Mail: [email protected]

7

South America HeadquartersPepperl+Fuchs Ltda. São Bernado do Campo · SP · BrazilTel. +55 11 4339 9935E-Mail: [email protected]

8

Subject to modifications • © 2009 PEPPERL+FUCHS, INC. • Printed in USA • Part No. 511967 Drawing No. 129-0195b (TDOCT-1356_ENG) 03/09