high capacity surge protective devices for switchboards · high capacity surge protective devices...
TRANSCRIPT
High capacity surge protective devices for switchboards
BSPD surge protective devices
Delivers reliable surge protection with high surge current capacity for system switchboards and power distribution panels.
Product description:
The Bussmann™ series BSPD Surge Protective Devices (SPDs) help protect electrical and electronic equipment from overvoltage surges. What’s more, they enable compliance with 2014 NEC® 700.8 that requires a listed SPD to be installed in or on all emergency system switchboards and panelboards.
The RoHS compliant BSPD uses thermally protected Bussmann SurgePOD™ technology to safely shunt overvoltages to ground while its thermal disconnect capability eliminates the need for additional fusing.
Features and benefits:
• 120kA to 400kA surge current capacity ratings (Imax) meet the requirements of larger switchboards and electrical panels.
• UL maximum 20kA nominal discharge current rating (In) and 200kA Short-Circuit Current Rating (SCCR) meet most system requirements.
• easyID™ LED status indicators provide surge protection at a glance.
• Available Form C contact, EMI/RFI filtering and surge counter options to meet specific application requirements.
NEMA 1 enclosure
Prewired and factory sealed for easy installation and enhanced electrical safety.
NEMA 4X enclosure
304 Stainless steel housing meets the needs of demanding environments and also comes prewired and factory sealed for easy installation and enhanced electrical safety.
BUSSMANNSERIES
Value features:
All BSPD units are UL Listed 1449 4th Edition SPDs with Bussmann’s SurgePOD™ thermally protected MOV technology that delivers reliable surge protection with high surge current capacity.
Every BSPD unit is factory sealed to enhance safety by preventing access to energized parts, and eliminate arc flash and shock hazards.
All units are prewired with a conduit interface — just make conduit runs, mount the unit and make all wire connections.
They are available in NEMA 1 and 4X enclosures that are up to 50% smaller than other products with comparable ratings.
Enhanced protection status indication is provided by green and red LEDs that show the true surge protection status on a phase, not the power status on the phase. This is more reliable and accurate than many surge protective devices that only have single color indicators that simply show if power is applied to a phase, not the protection status on the phase.
There are also green and red LED indicators for Wye units to show the N-G mode surge protection status.
Three configurations:
• Basic• Cost-effective solution• This Type 1 SPD can be
installed on the lineside or loadside of the service entrance panel overcurrent protective device
• Standard• This Type 2 SPD can be
installed anywhere on the loadside of the service entrance panel overcurrent protective device
• Audible alarm with silence button
• EMI/RFI filtering for up to 50dB of noise attenuation from 10 kHz to 100 MHz
• Form C contact relay for easy integration into a remote monitoring system
• Standard with surge counter• Everything the Standard con-
figuration has, plus a six-digit surge counter (held in battery-free nonvolatile memory) with reset button
Specifications*
Description Ratings
System voltages available (Vac)
Three-phase Wye (4 wires plus ground) 120/208, 277/480, 600
Three-phase Delta (3 wires plus ground) 240, 480, 600
Input power frequency 50/60Hz
SPD typeType 1 (Basic configuration, can also be used in Type 2 applications)
Type 2 (Standard and Standard with Surge Counter configurations)
Short-Circuit Current Rating (SCCR) 200kA
Nominal discharge current (In) 20kA
Surge current capacity per phase (Imax) 120kA, 200kA, 300kA and 400kA
Protection modes
Three-phase Wye L-N, L-G, L-L, N-G
Three-phase Delta L-G, L-L
Conductor length/gauge 48” (1.22m) 10AWG stranded copper
Enclosures NEMA 1 or NEMA 4X
Operating temperature and humidity –40°C to 50°C (–40°F to 122°F) , 5% through 95%, non-condensing
Agency information
- Basic, Standard and Standard with surge counter configurations UL® Listed 1449 4th Edition File E316410 Guide VZCA, CSA® Certified Notice 516 File 243397
- Standard and Standard with surge counter configurations are also UL Recognized 1283 5th Edition File E316410 Guide VZCA2, CSA Component Acceptance Std. C22.2 No. 8-M1986 File 243397
Warranty 10 years (see warranty statement 3A1502 for details at www.cooperbussmann.com/surge)
* Complete specifications available in data sheet No. 10209.
BSPD catalog number system
Build-a-code catalog numbering system permits specifying any configuration for an SPD that best meets your requirements.
BSPD
kA Ratingper phase
120kA200kA300kA400kA
Voltage/system type code
Configurations
1 = Basic Green and red LEDs per phase to indicate protection status Green and red LEDs on Wye units to indicate protection status of the Neutral-to-Ground mode2 = Standard Green and red LEDs per phase to indicate protection status Green and red LEDs on Wye units to indicate protection status of the Neutral-to-Ground mode Audible alarm with Silence button Form C contact relay. See Table 3, Specifications EMI/RFI filtering providing up to 50dB of noise attenuation from 10kHz to 100MHz3 = Standard With Surge Counter Green and red LEDs per phase to indicate protection status Green and red LEDs on Wye units to indicate protection status of the Neutral-to-Ground mode Audible alarm with silence button Form C contact relay EMI/RFI filtering providing up to 50dB of noise attenuation from 10kHz to 100MHz Surge counter with reset button
208Y = 120/208 Wye (4W + G)480Y = 277/480 Wye (4W + G)600Y = 347/600 Wye (4W + G)240D = 240 Delta (3W + G)480D = 480 Delta (3W + G) 600D = 600 Delta (3W + G)
Enclosure rating
K = NEMA 1P = NEMA 4X
BSPD 200 480D 2 K
Series
Eaton and Bussmann are valuable trade-marks of Eaton in teh US and other countries. You are not permitted to use the DEaton trademarks without prior written consent of Eaton.is a registered trademark.
CSA is a registered tardemark of the Canadian Standards Group.NEC is a registered trademark of the National Fire Protection Association, Inc.UL is a registered trademark of the Underwriters Laboratories, Inc.
Eaton1000 Eaton BoulevardCleveland, OH 44122United StatesEaton.com
Eaton’s Bussmann Business
Bussmann Division114 Old State RoadEllisville, MO 63021United StatesEaton.com/bussmannseries
© 2017 EatonAll Rights ReservedPrinted in the USAPublication No. 10208March 2017
Follow us on social media to get the latest product and support information.
For Eaton’s Bussmann series product information, call 1-855-287-7626 or visit:Eaton.com/bussmannseries