Surge Protective Devices. Chris Martin Sales Manager Surge Protection Devices. 80% - Internal Disturbances Load switching Variable frequency drives Lighting and air handlers 20% - External Disturbances Utility load switching Smart grid Lighting strikes Cloud to cloud - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: Surge Protective Devices

Surge Protective Devices

Chris Martin Sales Manager

Surge Protection Devices

Page 2: Surge Protective Devices

80% - Internal Disturbances

• Load switching

• Variable frequency drives

• Lighting and air handlers

20% - External Disturbances

– Utility load switching• Smart grid

– Lighting strikes• Cloud to cloud• Cloud to ground• Cloud to man-made object

Where surges originate

Page 3: Surge Protective Devices

Isokeraunic Map

Page 4: Surge Protective Devices

1. Cause disruptions in computer signals and processors

2. Degrade component junctions causing “random” delayed failure

3. Cause instant damage to electrical components

Surge damage

Page 5: Surge Protective Devices

How SPDs work

• Cross Section of a MOV

• Clamped Voltage (depends on surge level)

• Turn on Voltage (always the same)

SourceLoad

SPDTurn on Voltage

Clamped Voltage

150v

1,500v

20,000v

Eliminated Voltage

Page 6: Surge Protective Devices

UL 1449 2nd Edition 2005

• 2nd Edition 2005 Revision (effective 2/9/2007)

• Expanded OVERVOLTAGE Testing

(2 x nominal voltage)

• Added 7 hour intermediate fault current levels10 amps100 amps500 amps1000 amps

• SPD manufacturers pass this new requirement by either adding fusing per MOV, thermal sensing technology, or requiring an external OCPD for the safe removal of the SPD

Page 7: Surge Protective Devices

Su

rge

Cu

rren

t

Impulse Duration (Microseconds)

12

10

10 2

10 3

10 4

10 5

10 6

Indef.

20 microseconds 5000 microseconds

20 mm MOV Surge Current Rating Curve20 mm MOV Surge Current Rating Curve

1

10

100

1000

10000

10 100 1000 10000

At 20 micro-seconds the MOV can protect up to 6500Amps (1 time) at 5000 micro-seconds that same MOV can only protect up to 30Amps

Page 8: Surge Protective Devices

UL 1449 3rd Edition

• Creates SPD types (Type1, Type2, Type3, Type4)– Surge Arrestor, Lightning Arrestor, TVSS

• New Nominal Discharge Surge Current test, In Thermal “stress” test

• Tested MCOV per mode. No longer a claimed value

• SVR 6kV, 500A replaced with VPR 6kV, 3kA

• Surge Arrestor incorporated into UL1449 as Type 1 device

Page 9: Surge Protective Devices

SPD Types - UL 1449 3rd Ed.

Type 1 SPD (LINE SIDE)Permanently Connected SPD – Installation between the secondary of the service transformer and the LINE side of the service disconnect over current device, as well as the LOAD side, including watt-hour meter socket enclosures. (Not exceeding 1000V)

Secondary Surge Arrestor

Competitors Surge Arrestor

Needs a breaker to pass UL testing

Page 10: Surge Protective Devices

SPD Types (Continued)

Type 2 SPD (LOAD SIDE)Permanently Connected SPD intended for installation on the LOAD side of the service disconnect over current device, including SPDs located at the branch panel.

Page 11: Surge Protective Devices

SPD Types (Continued)

Type 3 SPD Point of utilization SPDs, installed a minimum of 10 meters (30 feet)

from the electrical service panel, for example cord connected, direct plug-in (DPI), receptacle type and SPDs installed at the utilization

equipment being protected.

Page 12: Surge Protective Devices

SPD Types (Continued)

Type 4 SPDComponent SPDs, including discrete components as well as component assemblies.(Note: as proposed the 3rd Edition will allow Type 4 SPDs to be tested and applied where Types 1 and 2 are allowed)

Page 13: Surge Protective Devices

Measured Limiting Voltage (MLV)

• All SPD Types are to be tested to 6kV/3kA - 3 pulses per mode with applied voltage. VPR is determined by averaging results. (Per 34.9 and Table 34.1)

• SVR 6kV/500A Good reading 400v or 500v

• VPR 6kV/3kA Good reading 700v, 800v, 900v, or as high as 1000v

• Higher surge current results in higher clamping voltages

Page 14: Surge Protective Devices

• Type 1: Choose 10kA or 20kA/Mode

• Type 2: Choose 3kA, 5kA, 10kA, or 20kA

• Surge unit at chosen surge value

• Apply chosen over voltage to unit within 1s for 1min

Nominal Discharge Current Test (In)

Page 15: Surge Protective Devices

2008 NEC

• COPS - Critical Operations Power Systems

– NEC guideline to increase protection and reliability of the power infrastructure for critical facilities

• What are Critical Facilities?

– Government agency (Federal, state, municipal)

– Facility engineering

– Facilities that if destroyed may disrupt:

• National security, the economy, public health, or safety

• To include

– HVAC, fire alarm, security, communications, and signaling

Page 16: Surge Protective Devices

2008 NEC

• NEC Section 708.20 (D)

• Surge Protective Devices must be used to comply

• SPDs must be used for each voltage at the facility

– Service Entrance

– Distribution panels

Page 17: Surge Protective Devices
Page 18: Surge Protective Devices

Improving SPD Installed Performance

• How does lead length affect the installed performance of a surge protective device?

• Does an internally mounted SPD outperform an externally mounted SPD?

• Impact of upstream OCPDs

Page 19: Surge Protective Devices

How are SPDs Tested?

• 6 inches outside of the enclosure

Surge Protective Device

Phase A Phase B Phase C

6 inches

The surge is injected here

Clamping characteristics are recorded

by an Oscilloscope

• Phase length + Neutral length affect the performance of the SPD

Page 20: Surge Protective Devices

The surge must travel through the phase

through the SPDand through Neutral

Phase length + Neutral length = SPD clamping

voltage

Internally Mounted Lead Length

Page 21: Surge Protective Devices

Lead Length

• Lead length affects the installed performance of a SPD

• 10’ sections of cable (commonly used sizes)

– 14 AWG

– 10 AWG

– 6 AWG

• Apply IEEE defined 20kV/10kA surge

• Measure the voltage drop

Page 22: Surge Protective Devices

Wire size

• Voltage drop across 10 foot cable when exposed to a 20kV/10kA surge

– 14 AWG 2,650v

– 10 AWG 2,400v

– 6 AWG 2,350v

• What does this do to the installed performance of the SPD?

Page 23: Surge Protective Devices

Lead Length Impact

SPD LOAD

Lead length

VoltageSeen

At load

1' 2' 3' 4' 5' 7' 8' 9' 10'

1000v

2000v

3000v

4000v

Page 24: Surge Protective Devices

The Low Impedance Cable

Ground Cable Termination 30"

Neutral Cable Termination 30"

Top Insulation

LayerTop Braid

Layer (Ground)

Ground Coupler

Ground Split Ring

Internal Braid Layer (Neutral)

Neutral Coupler

Neutral Split Ring

Three colored leads

Middle Insulation

Layer

Inside View of one end of the Low Z Cable

Page 25: Surge Protective Devices

HPI Voltage Drop

• Voltage drop across 10 foot cable when exposed to a 20kV/10kA surge

– 10 AWG 560v

– 6 AWG 560v

Page 26: Surge Protective Devices

Lead Length Impact

SPD LOAD

Lead length

VoltageSeen

At load

1' 2' 3' 4' 5' 7' 8' 9' 10'

1000v

2000v

3000v

4000v

HPI Cable

#14 AWG

83% improvement

Page 27: Surge Protective Devices

Breaker Impact

• Does a breaker upstream of an SPD limit the effectiveness of the SPD?

• Breakers have surge trip and surge failure values: The SCCR value is based on 60Hz current, not surge current!

• Type 2 SPDs must be installed behind a breaker!CB Pulse Performance

0

20

40

60

80

100

120

140

160

15 30 40 60 100

CB Rating

Puls

e k

A

Trip kA

Fail kA

These values are based on testing

performed by Current Technology’s

Surge generator on commercially

available off the shelf breakers.

Page 28: Surge Protective Devices

The ISMIntegrated Suppression Module

Page 29: Surge Protective Devices

ISM Design

• Utilizes TPMOV technology

• Bus Bar construction

• N-G filter (removable)

• Improved L-N Filter

• 100% surge rated

• Reduced weight

• Individually monitored MOVs

• Advanced monitoring

300kA Model

Page 30: Surge Protective Devices

The TPMOV

Thermal spring

Barrier

50mm MOV

DRC switch

DRC contacts

Barrier spring

Page 31: Surge Protective Devices

Select3 (SL3)

• Listed by UL to UL1449 3rd Edition as a Type 1 SPD

• 50kA, 100kA, 150kA, 200kA, 250kA, 300kA per mode

• TPMOV/Selenium Hybrid

– Option for enhanced selenium

• Test reports for single and repetitive surge testing

• Surge rated disconnect with line side barrier

• DTS-2 internal test port option

• 6 levels of monitoring

• 20 year warranty

THE SERVICE ENTRANCE SURGE PROTECTOR OF CHOICE

Page 32: Surge Protective Devices

TransGuard3 (TG3)

• Listed by UL to UL1449 3rd Edition as a Type 1 SPD

• 50kA, 100kA, 150kA, 200kA, 250kA, 300kA per mode

• TPMOV Technology

• RoHS compliant

• Test reports for single and repetitive surge testing

• Surge rated disconnect with line side barrier

• DTS-2 internal test port option

• 6 levels of monitoring

• 15 year warranty

Page 33: Surge Protective Devices

Panel Extension (PX3)

• Listed by UL to UL1449 3rd Edition as a Type 1 SPD

• 50kA, 100kA, 150kA, 200kA per mode

• 9 inch height for 50kA-100kA units

• TPMOV Technology

• RoHS compliant

• Test reports for single and repetitive surge testing

• DTS-2 internal test port option

• 6 levels of monitoring

• 15 year warranty

Page 34: Surge Protective Devices

DTS-2 Tester

The ONLY proactive test kit for SPDs on the market

• Updated test card for both MOV and TPMOV based products with or without selenium

• Validates “health” of surge components

• Compares installed clamping performance to original factory values

• Detects and provides early warning for stressed components

• Can be used to evaluation competitive products performance

• Part of any startup or commissioning

• Validates integrity of upstream Xo bond

Page 35: Surge Protective Devices

M1 Standard Monitoring

• LED indication per phase

• Audible alarm

• Alarm silence switch

• 2 sets of dry relay contacts

• Tri-colored LED that reports on % protection

– Green = 75% or greater

– Orange = 75% - 40%

– Red = 40% or less

– Extinguished = Loss of protection

Page 36: Surge Protective Devices

M2 Monitoring Option

• All M1 monitoring options

• Surge counter

Page 37: Surge Protective Devices

M3 Option

• New Mastermind• Includes all M1 monitoring features• Time/Date stamp • Duration and Magnitude• User settable thresholds• Tracks

– Sags, swells surges, dropouts, outages, THD, frequency, Volts RMS, % protection

• Local character display• ModBus remote communications

M4E Option

• New Mastermind• Includes all M1 monitoring features• Time/Date stamp • Duration and Magnitude• User settable thresholds• Tracks

– Sags, swells surges, dropouts, outages, THD, frequency, Volts RMS, % protection

• Local character display• ModBus and Ethernet remote communications• Web based interface

Page 38: Surge Protective Devices

M5 Option

• Adds Large Graphics Display• Includes all M1 monitoring features• Time/Date stamp • Duration and Magnitude• User settable thresholds• Tracks

– Sags, swells surges, dropouts, outages, THD, frequency, Volts RMS, % protection

• Local character display• ModBus remote communications

M6E Option

• Adds Large Graphics Display• Includes all M1 monitoring features• Time/Date stamp • Duration and Magnitude• User settable thresholds• Tracks

– Sags, swells surges, dropouts, outages, THD, frequency, Volts RMS, % protection

• Local character display• ModBus and Ethernet remote communications• Web based interface

Page 39: Surge Protective Devices

Review

• Specs need to be Updated to include new requirements outlined in UL1449 3rd Edition

• Externally mounted SPDs offer a safer installed alternative without affecting performance

• External OCPDs can have an affect on the installed performance of the SPD

• Ask for documentation. Single surge, repetitive surge, and tested MCOV value