designing a gas detection system

32
Designing a Gas Detection System

Upload: rollo

Post on 29-Jan-2016

43 views

Category:

Documents


1 download

DESCRIPTION

Designing a Gas Detection System. Why Gas Detection?. Safeguard Life and Property. Provide Early Warning of Hazardous Conditions. Provide Opportunity for Evacuation and Notification from Re-entry Provide Time for Intervention and Correction. Trigger Facility Protection Systems. - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: Designing a Gas Detection System

Designing a Gas Detection System

Page 2: Designing a Gas Detection System

Honeywell Proprietary

Honeywell.com

2

Why Gas Detection?

• Safeguard Life and Property.– Provide Early Warning of Hazardous Conditions.– Provide Opportunity for Evacuation and Notification from Re-entry– Provide Time for Intervention and Correction.

• Trigger Facility Protection Systems.– Ventilation, Water Mist, Fire Suppression.

• Satisfy Local Fire Code and Provide Insurability.• Address Real and Perceived Safety Concerns.• Note: Gas Detection is “Recommended Practice,” “Required by Code,”

or “Required by Law.”

Page 3: Designing a Gas Detection System

Honeywell Proprietary

Honeywell.com

3

Points to Consider

• Understand the application• Identify potential danger points• Establish design goals• Determine gas characteristics• Profile the plant and potential release scenarios• Other elements in selecting gas detection systems• Actual placement of detection

– Indoors– Outdoors

Page 4: Designing a Gas Detection System

Honeywell Proprietary

Honeywell.com

4

Understand The Application

• The gases to be monitored– Toxic (STEL, TLV, TWA)– Combustible (LEL, UEL)– Exposure limits– Density and Other Gas Properties

• Local and federal regulations– Uniform Fire Code– Code of Federal Regulations– Local Fire Marshal

Page 5: Designing a Gas Detection System

Honeywell Proprietary

Honeywell.com

5

Identify Potential Danger Points

– Release Points – sensors should be placed as close as possible to potential leak sources.

– Seals and flanges, fittings and welds– Expansion joints and gaskets– Engine combustion– Storage, loading and unloading areas– Runoff areas– Decomposing materials

– Receptor Points – a gas detection notification system should protect any person, property or equipment that may come in contact with harmful gases.

– Wind direction– Ventilation systems– Run off areas– Confined spaces– Communities and facilities

Page 6: Designing a Gas Detection System

Honeywell Proprietary

Honeywell.com

6

Establish Design Goals

Initiate a response based on an early warning of a potential problem.

Notification or annunciation – method of warning Ventilation control Process shutdown

Evacuation and emergency response Amount of confinement - over pressurization and accumulation

Run-up distance – speed of flame increases with distance Amount of congestion or obstacles

Fuel quantity and mixing Margin of safety – distance between leak source and receptors

Plant safety process Insurance requirements

Page 7: Designing a Gas Detection System

Honeywell Proprietary

Honeywell.com

7

Determine Gas Characteristics

• LEL, UEL, Toxicity• Vapor density

– Density differences with temperature• Cryogenic liquids, flammable liquids

– Low density gases displacing ambient density gases (helium vs. oxygen)– Gases under pressure will condense in areas where vented first

• Gases changing composition – dry ice• Toxicity vs. flammability (MTBE 40 PPM 1.6% LEL)• Hydrolyzed (BF3, F2)• Pyrolyzed (NF3)• Flash point - the lowest temperature at which a liquid can form an ignitable

mixture in air near the surface of the liquid. The lower the flash point, the easier it is to ignite the material.

• Rate of evaporation and dispersion characteristics• Gas mixing (fuel, oxygen, ignition source)• Oxygen enriched environments

Page 8: Designing a Gas Detection System

Honeywell Proprietary

Honeywell.com

8

Gas Hazards

There are three main types of gas hazard

1. Flammable – Risk of fire and or explosion,

e.g. Methane, Butane, Propane

2. Toxic– Risk of poisoning,

e.g. Carbon Monoxide, Hydrogen Sulfide, Chlorine

3. Asphyxiant– Risk of suffocation,

e.g. Oxygen deficiency, Nitrogen, Carbon Dioxide

Page 9: Designing a Gas Detection System

Honeywell Proprietary

Honeywell.com

9

Flammable Risk

• Fire TriangleThree factors are always needed to cause combustion:

1. A source of ignition

2. Oxygen

3. Fuel in the form of a gasor vapour

fuel

oxyg

en

heatFIRE

Page 10: Designing a Gas Detection System

Honeywell Proprietary

Honeywell.com

10

Flammable Risk

• The operation of a car’s choke illustrates an important part of flammable gas hazards

• All flammable gases are only ignitable over their flammable range

• Flammable gases tend to be measured in percentage of their explosive Limit (%LEL)

L.E.L. (lower explosive limit)

U.E.L. (upper explosive limit)

0% v/v gas 100% v/v air

too lean

flammable range

too rich

100% v/v gas 0% v/v air

Page 11: Designing a Gas Detection System

Honeywell Proprietary

Honeywell.com

11

Toxic Risk

• Some gases are poisonous and can be dangerous to life at very low concentrations.

• Some toxic gases have strong smells like the distinctive ‘rotten eggs’ smell of H2S

• Others are completely odourless like Carbon Monoxide

Page 12: Designing a Gas Detection System

Honeywell Proprietary

Honeywell.com

12

Toxic Risk

• The measurement most often used for the concentration of toxic gases is parts per million (ppm).

• For example 1ppm would be equivalent to a room filled with a total of 1 million balls and 1 of those balls being red. The red ball would represent 1ppm.

1 million balls

1 red ball

Page 13: Designing a Gas Detection System

Honeywell Proprietary

Honeywell.com

13

Profile the Plant and Potential Release Scenarios

Gas sensors should be placed to ensure that a quantity of gas will past by them in all normal release scenarios.

• Identify physical features of plant• Identify ventilation tracks• Identify escape routes• Protect entrances to areas• Mark escape routes• Identify wind directions

Page 14: Designing a Gas Detection System

Honeywell Proprietary

Honeywell.com

14

Other Elements

• Accessibility for calibration and maintenance• Wiring and installation• Environmental conditions• EMI and RFI• Alarm levels• Exposure limits• Oxygen levels – some toxic gas electrochemical sensors require a

minimum oxygen level to function. All catalytic bead combustible detectors require oxygen to work.

• Be aware of poisoning and inhibiting factors

Page 15: Designing a Gas Detection System

Honeywell Proprietary

Honeywell.com

15

Interior Detector Placement Guidelines

• Operate Detectors Within their Temperature Limits. Use Sample Draw or Duct Mount Configurations When Needed

• Water, Moisture, Dust and Dirt May Affect Performance. Minimize Exposure and Protect From Adverse Conditions

• Locate Detectors With Respect to Grade, Floor, or Operating Level - According to Building Design, HVAC System, Characteristics of Potential Leak

• When Monitoring Specific Equipment, Place Detectors Near (12 Inches) Pump, Seal, Tank, Valve, etc.

• Sensitivity of Detector Depends on Proximity to Leak. Adjust Alarms if Earlier Annunciation is Required

• Mount Detectors Securely, Independent of Vibration, With Weather Shield Facing Downward

• Conduct Smoke Trace Behavior Studies If in Doubt

Page 16: Designing a Gas Detection System

Honeywell Proprietary

Honeywell.com

16

Detector Spacing Indoors

• There are Few Published Guidelines and No Standards Indicating Area or Volume Effectively Protected By a Diffusion Sensor. There is a Corollary in Fire Protection

• UL Suggests a 900 Ft2 Ceiling Space Per Smoke Detector, Which is a 30 Ft. Square or 15 Ft. Radius

• Using This Base Guideline, the Total Number of Detectors Must be Based on – Gas Dispersion Characteristics and Air Movement– Potential Leak Source Locations and Characteristics, – Sources of Ignition Locations– Interior Space Division by Walls or Barriers– Economics of the Procurement

Page 17: Designing a Gas Detection System

Honeywell Proprietary

Honeywell.com

17

Detector Spacing Indoors, Cont’d.

• UL Suggests a 900 Ft2 Ceiling Space Per Smoke Detector

30 Feet

30 Feet

15 Feet15 Feet

ReferencesNFPA 72 E, Standard On Automatic Fire DetectorsSchaeffer, M.J., “The Use of Combustible Detectors in Protecting Facilities from Flammable Hazards,” ISA Transactions, Volume 20, No. 2, Instrument Society of America 1981

Detector Detector

Page 18: Designing a Gas Detection System

Honeywell Proprietary

Honeywell.com

18

Indoors

Window

Door

LN2

Cl2

Door

40 feet

20 ft

Ceiling Ventilation Natural Gas

Lab Bench

STORAGE

Page 19: Designing a Gas Detection System

Honeywell Proprietary

Honeywell.com

19

Outdoor Detector Location Guidelines

• Use same considerations outdoors as indoors.

• Consider Angle and Direction of Prevailing Wind

• The Orientation of Structures and Surrounding Terrain with Regard to Shielding Affects

• The Proximity of Large Quantities of Toxics to Personnel and Equipment, Which May Require Added Detectors to Isolate the Two

Page 20: Designing a Gas Detection System

Honeywell Proprietary

Honeywell.com

20

Outdoor Detector Location Guidelines

Possible Entrapment of Leaking Gases and Vapors Within Columns, Low Lying Areas or Confined Spaces

Sources of Ignition and Processes With Fugitive Leak Potential Are Considered for Detector Placement

Page 21: Designing a Gas Detection System

Honeywell Proprietary

Honeywell.com

21

Outdoor Detector Location, Cont’d.

• Heavier Than Air Gases or Vapors: Vapor Density >1– The Preferred Location for Detectors is ~18 Inches Above Grade. For

Liquid Spills, As Close to the Vapor/Liquid Interface as Possible, and Still Allow for Detector Calibration

• Lighter Than Air Gases and Vapors: Vapor Density <1– The Preferred Location for Detectors is About 6 to 8 Feet Above Grade or

Operating Level, With Special Attention Being Paid to Air Currents, Structures, Roofed Areas, Etc.

Page 22: Designing a Gas Detection System

Honeywell Proprietary

Honeywell.com

22

Detector Spacing Outdoors

• Few Guidelines Exist for Detector Placement• An Increased Grid Density is Used Outdoor Presumably

Because of the Greater Potential for Leak Dilution• Thus, More Detectors Are Required, and Potential Leaks Are

Encircled, to Account for Wind Shifts

Page 23: Designing a Gas Detection System

Honeywell Proprietary

Honeywell.com

23

Detector Spacing Outdoors

20-30 Feet

20-30 Feet

10-15 Feet10-15 FeetDetector Detector

Repeat Outdoor Grid Pattern as Conditions Warrant. Focus on Potential Leak Sources for Additional Detectors if Required

Page 24: Designing a Gas Detection System

Honeywell Proprietary

Honeywell.com

24

General Location Considerations

• Toxic Gases and Vapors:– Identify Potential Leak Sources, Work Areas, and Exit Points. Understand Where

People are Performing Their Work and Place Detectors Between Probable Release Points and the Work Area

Page 25: Designing a Gas Detection System

Honeywell Proprietary

Honeywell.com

25

General Location Considerations

• Allow Access for Sensor Calibration and Replacement.– Sensors Have a Finite Life - Calibrate and Maintain Regularly!

• Always Locate Detectors Using “Local Conditions Knowledge,” and Lighter or Heavier Than Air Principles

Page 26: Designing a Gas Detection System

Honeywell Proprietary

Honeywell.com

26

General Location Considerations

• Locate Detectors Within Their Temperature Rating

– Avoid Exposure to Sources of High Radiant Heat

• Keep Detectors Away From Moisture and Chemicals

– Avoid Vibration and Mechanical Shock Hazards

• Observe Recommended Wiring and Tagging Practices

• Use Shielded Cable Whenever Possible and Follow Correct Grounding Practices (NFPA 70)

• Observe Proper Detector Mounting Orientation

Page 27: Designing a Gas Detection System

Honeywell Proprietary

Honeywell.com

27

DETECTORS SHOULD BE LOCATED BELOW TOP OF DYKE WALL FOR VAPORS THAT ARE HEAVIER THAN AIR. Sensor should be approx 12-18 in above grade. These vapor densities are greater than air.

IMPORTANTDetectors should be located close to any potential leak

source and between leak source and any potential source of ignition existing at the monitored site.

TOP VIEW OF STORAGE TANK

Detector Location and Area Coverage Map

SIDE VIEW OF STORAGE TANK

FILL LINE

OUT FLOW

XNX-Optima

DETECTOR LOCATED ONTOP OF TANK NEAR VALVEOR FLANGE ON FILL LINE

FILL LINE

TANK SUPPORT LEGS

Page 28: Designing a Gas Detection System

Honeywell Proprietary

Honeywell.com

28

DETECTORS SHOULD BE LOCATED BELOW TOP OF DYKE WALL FOR VAPORS THAT ARE HEAVIER THAN AIR. Sensor should be approx 12-18 in above grade. These vapor densities are greater than air.

IMPORTANTDetectors should be located close to any potential leak

source and between leak source and any potential source of ignition existing at the monitored site.

TOP VIEW OF STORAGE TANK

SIDE VIEW OF STORAGE TANK

FILL LINE

OUT FLOW

XNX-Optima

DETECTOR LOCATED ONTOP OF TANK NEAR VALVEOR FLANGE ON FILL LINE

FILL LINE

TANK SUPPORT LEGS

Detector Location and Area Coverage Map

Page 29: Designing a Gas Detection System

Honeywell Proprietary

Honeywell.com

29

IMPORTANT: This is intended as a General Application Note and NOT as the sole source of information in determining quantity and location for detector placement. Consult additional resources when developing a monitoring system. Additional information is available for developing Combustible Gas Detection systems, such as: The National Fire Protection Association, NFPA 52 and the Instrument Society of America, ISA-RP12.13-Part II-1987. Services are also available from Professional Safety Engineering Firms and should be utilized whenever necessary

IMPORTANTDetectors should be located close to

any potential leak source and between leak source and any potential source ofignition existing at the monitored site.

4 5 6

7

8

TOP VIEW OF THREE AND TWO TANK AREA

DETECTORS SHOULD BELOCATED BELOW TOP OF DYKE WALL FOR VAPORSTHAT ARE HEAVIER THAN AIR.Sensor should be approx 12-18 in. above grade..

SIDE VIEW OF TANK

Detector Location and Area Coverage Map

Page 30: Designing a Gas Detection System

Honeywell Proprietary

Honeywell.com

30

IMPORTANTDetectors should be located close to any potential leak source and between

leak source and any potential source of ignition existing at the monitored site.

NOTE: DETECTORS SHOULD BE LOCATED LOW, CLOSE TO GRADE FOR VAPORS THAT ARE HEAVIER THAN AIR.NOTE: Sensor should be approx.12-18 in. above grade. These vapor densities are heavier than air.

SIDE VIEW OF UNLOADING FACILITY

I I I I

NOTE: IF PIPING FUNCTIONS OR VALVES ARE

ABOVE THE TANK CAR A DETECTOR MAY BE

MOUNTED PART WAY DOWN THE WALL TO DETECT

FALLING VAPORS FROM A LEAK SOURCE

R.R. SPUR NO. 13

R.R. SPUR NO. 12

TOP VIEW OF UNLOADING FACILITY

Detector Location and Area Coverage Map

Page 31: Designing a Gas Detection System

Honeywell Proprietary

Honeywell.com

31

Publications to Reference

• Chemical Weekly, 2008, “Key Considerations when Designing a Gas Detection System”• ISA Recommended Practices • ACGIH: Annual TLV and BEI Guide

– 1330 Kemper Meadow Drive, Cincinnati OH 45240-1634• NFPA/ANSI Guides, Standards and Practices

– 1 Batterymarch Park, Quincy MA 02269-9101• NIOSH: Pocket Guide to Chemical Hazards

– Available by FAX Request to (513) 533-8573• OSHA, CFR 29, Section 1910.1000, Subpart Z“Working in Confined Spaces.”

– NIOSH1 Publication 80-106• “A Guide to Safety in Confined Spaces.”

– NIOSH Publication 87-113• “ALERT: Request for Assistance in Preventing Occupational Fatalities in Confined Spaces.”

– NIOSH Publication 86-110

Page 32: Designing a Gas Detection System

Honeywell Proprietary

Honeywell.com

32

The End

Questions?