designing a gas detection system
DESCRIPTION
Designing a Gas Detection System. Why Gas Detection?. Safeguard Life and Property. Provide Early Warning of Hazardous Conditions. Provide Opportunity for Evacuation and Notification from Re-entry Provide Time for Intervention and Correction. Trigger Facility Protection Systems. - PowerPoint PPT PresentationTRANSCRIPT
Designing a Gas Detection System
Honeywell Proprietary
Honeywell.com
2
Why Gas Detection?
• Safeguard Life and Property.– Provide Early Warning of Hazardous Conditions.– Provide Opportunity for Evacuation and Notification from Re-entry– Provide Time for Intervention and Correction.
• Trigger Facility Protection Systems.– Ventilation, Water Mist, Fire Suppression.
• Satisfy Local Fire Code and Provide Insurability.• Address Real and Perceived Safety Concerns.• Note: Gas Detection is “Recommended Practice,” “Required by Code,”
or “Required by Law.”
Honeywell Proprietary
Honeywell.com
3
Points to Consider
• Understand the application• Identify potential danger points• Establish design goals• Determine gas characteristics• Profile the plant and potential release scenarios• Other elements in selecting gas detection systems• Actual placement of detection
– Indoors– Outdoors
Honeywell Proprietary
Honeywell.com
4
Understand The Application
• The gases to be monitored– Toxic (STEL, TLV, TWA)– Combustible (LEL, UEL)– Exposure limits– Density and Other Gas Properties
• Local and federal regulations– Uniform Fire Code– Code of Federal Regulations– Local Fire Marshal
Honeywell Proprietary
Honeywell.com
5
Identify Potential Danger Points
– Release Points – sensors should be placed as close as possible to potential leak sources.
– Seals and flanges, fittings and welds– Expansion joints and gaskets– Engine combustion– Storage, loading and unloading areas– Runoff areas– Decomposing materials
– Receptor Points – a gas detection notification system should protect any person, property or equipment that may come in contact with harmful gases.
– Wind direction– Ventilation systems– Run off areas– Confined spaces– Communities and facilities
Honeywell Proprietary
Honeywell.com
6
Establish Design Goals
Initiate a response based on an early warning of a potential problem.
Notification or annunciation – method of warning Ventilation control Process shutdown
Evacuation and emergency response Amount of confinement - over pressurization and accumulation
Run-up distance – speed of flame increases with distance Amount of congestion or obstacles
Fuel quantity and mixing Margin of safety – distance between leak source and receptors
Plant safety process Insurance requirements
Honeywell Proprietary
Honeywell.com
7
Determine Gas Characteristics
• LEL, UEL, Toxicity• Vapor density
– Density differences with temperature• Cryogenic liquids, flammable liquids
– Low density gases displacing ambient density gases (helium vs. oxygen)– Gases under pressure will condense in areas where vented first
• Gases changing composition – dry ice• Toxicity vs. flammability (MTBE 40 PPM 1.6% LEL)• Hydrolyzed (BF3, F2)• Pyrolyzed (NF3)• Flash point - the lowest temperature at which a liquid can form an ignitable
mixture in air near the surface of the liquid. The lower the flash point, the easier it is to ignite the material.
• Rate of evaporation and dispersion characteristics• Gas mixing (fuel, oxygen, ignition source)• Oxygen enriched environments
Honeywell Proprietary
Honeywell.com
8
Gas Hazards
There are three main types of gas hazard
1. Flammable – Risk of fire and or explosion,
e.g. Methane, Butane, Propane
2. Toxic– Risk of poisoning,
e.g. Carbon Monoxide, Hydrogen Sulfide, Chlorine
3. Asphyxiant– Risk of suffocation,
e.g. Oxygen deficiency, Nitrogen, Carbon Dioxide
Honeywell Proprietary
Honeywell.com
9
Flammable Risk
• Fire TriangleThree factors are always needed to cause combustion:
1. A source of ignition
2. Oxygen
3. Fuel in the form of a gasor vapour
fuel
oxyg
en
heatFIRE
Honeywell Proprietary
Honeywell.com
10
Flammable Risk
• The operation of a car’s choke illustrates an important part of flammable gas hazards
• All flammable gases are only ignitable over their flammable range
• Flammable gases tend to be measured in percentage of their explosive Limit (%LEL)
L.E.L. (lower explosive limit)
U.E.L. (upper explosive limit)
0% v/v gas 100% v/v air
too lean
flammable range
too rich
100% v/v gas 0% v/v air
Honeywell Proprietary
Honeywell.com
11
Toxic Risk
• Some gases are poisonous and can be dangerous to life at very low concentrations.
• Some toxic gases have strong smells like the distinctive ‘rotten eggs’ smell of H2S
• Others are completely odourless like Carbon Monoxide
Honeywell Proprietary
Honeywell.com
12
Toxic Risk
• The measurement most often used for the concentration of toxic gases is parts per million (ppm).
• For example 1ppm would be equivalent to a room filled with a total of 1 million balls and 1 of those balls being red. The red ball would represent 1ppm.
1 million balls
1 red ball
Honeywell Proprietary
Honeywell.com
13
Profile the Plant and Potential Release Scenarios
Gas sensors should be placed to ensure that a quantity of gas will past by them in all normal release scenarios.
• Identify physical features of plant• Identify ventilation tracks• Identify escape routes• Protect entrances to areas• Mark escape routes• Identify wind directions
Honeywell Proprietary
Honeywell.com
14
Other Elements
• Accessibility for calibration and maintenance• Wiring and installation• Environmental conditions• EMI and RFI• Alarm levels• Exposure limits• Oxygen levels – some toxic gas electrochemical sensors require a
minimum oxygen level to function. All catalytic bead combustible detectors require oxygen to work.
• Be aware of poisoning and inhibiting factors
Honeywell Proprietary
Honeywell.com
15
Interior Detector Placement Guidelines
• Operate Detectors Within their Temperature Limits. Use Sample Draw or Duct Mount Configurations When Needed
• Water, Moisture, Dust and Dirt May Affect Performance. Minimize Exposure and Protect From Adverse Conditions
• Locate Detectors With Respect to Grade, Floor, or Operating Level - According to Building Design, HVAC System, Characteristics of Potential Leak
• When Monitoring Specific Equipment, Place Detectors Near (12 Inches) Pump, Seal, Tank, Valve, etc.
• Sensitivity of Detector Depends on Proximity to Leak. Adjust Alarms if Earlier Annunciation is Required
• Mount Detectors Securely, Independent of Vibration, With Weather Shield Facing Downward
• Conduct Smoke Trace Behavior Studies If in Doubt
Honeywell Proprietary
Honeywell.com
16
Detector Spacing Indoors
• There are Few Published Guidelines and No Standards Indicating Area or Volume Effectively Protected By a Diffusion Sensor. There is a Corollary in Fire Protection
• UL Suggests a 900 Ft2 Ceiling Space Per Smoke Detector, Which is a 30 Ft. Square or 15 Ft. Radius
• Using This Base Guideline, the Total Number of Detectors Must be Based on – Gas Dispersion Characteristics and Air Movement– Potential Leak Source Locations and Characteristics, – Sources of Ignition Locations– Interior Space Division by Walls or Barriers– Economics of the Procurement
Honeywell Proprietary
Honeywell.com
17
Detector Spacing Indoors, Cont’d.
• UL Suggests a 900 Ft2 Ceiling Space Per Smoke Detector
30 Feet
30 Feet
15 Feet15 Feet
ReferencesNFPA 72 E, Standard On Automatic Fire DetectorsSchaeffer, M.J., “The Use of Combustible Detectors in Protecting Facilities from Flammable Hazards,” ISA Transactions, Volume 20, No. 2, Instrument Society of America 1981
Detector Detector
Honeywell Proprietary
Honeywell.com
18
Indoors
Window
Door
LN2
Cl2
Door
40 feet
20 ft
Ceiling Ventilation Natural Gas
Lab Bench
STORAGE
Honeywell Proprietary
Honeywell.com
19
Outdoor Detector Location Guidelines
• Use same considerations outdoors as indoors.
• Consider Angle and Direction of Prevailing Wind
• The Orientation of Structures and Surrounding Terrain with Regard to Shielding Affects
• The Proximity of Large Quantities of Toxics to Personnel and Equipment, Which May Require Added Detectors to Isolate the Two
Honeywell Proprietary
Honeywell.com
20
Outdoor Detector Location Guidelines
Possible Entrapment of Leaking Gases and Vapors Within Columns, Low Lying Areas or Confined Spaces
Sources of Ignition and Processes With Fugitive Leak Potential Are Considered for Detector Placement
Honeywell Proprietary
Honeywell.com
21
Outdoor Detector Location, Cont’d.
• Heavier Than Air Gases or Vapors: Vapor Density >1– The Preferred Location for Detectors is ~18 Inches Above Grade. For
Liquid Spills, As Close to the Vapor/Liquid Interface as Possible, and Still Allow for Detector Calibration
• Lighter Than Air Gases and Vapors: Vapor Density <1– The Preferred Location for Detectors is About 6 to 8 Feet Above Grade or
Operating Level, With Special Attention Being Paid to Air Currents, Structures, Roofed Areas, Etc.
Honeywell Proprietary
Honeywell.com
22
Detector Spacing Outdoors
• Few Guidelines Exist for Detector Placement• An Increased Grid Density is Used Outdoor Presumably
Because of the Greater Potential for Leak Dilution• Thus, More Detectors Are Required, and Potential Leaks Are
Encircled, to Account for Wind Shifts
Honeywell Proprietary
Honeywell.com
23
Detector Spacing Outdoors
20-30 Feet
20-30 Feet
10-15 Feet10-15 FeetDetector Detector
Repeat Outdoor Grid Pattern as Conditions Warrant. Focus on Potential Leak Sources for Additional Detectors if Required
Honeywell Proprietary
Honeywell.com
24
General Location Considerations
• Toxic Gases and Vapors:– Identify Potential Leak Sources, Work Areas, and Exit Points. Understand Where
People are Performing Their Work and Place Detectors Between Probable Release Points and the Work Area
Honeywell Proprietary
Honeywell.com
25
General Location Considerations
• Allow Access for Sensor Calibration and Replacement.– Sensors Have a Finite Life - Calibrate and Maintain Regularly!
• Always Locate Detectors Using “Local Conditions Knowledge,” and Lighter or Heavier Than Air Principles
Honeywell Proprietary
Honeywell.com
26
General Location Considerations
• Locate Detectors Within Their Temperature Rating
– Avoid Exposure to Sources of High Radiant Heat
• Keep Detectors Away From Moisture and Chemicals
– Avoid Vibration and Mechanical Shock Hazards
• Observe Recommended Wiring and Tagging Practices
• Use Shielded Cable Whenever Possible and Follow Correct Grounding Practices (NFPA 70)
• Observe Proper Detector Mounting Orientation
Honeywell Proprietary
Honeywell.com
27
DETECTORS SHOULD BE LOCATED BELOW TOP OF DYKE WALL FOR VAPORS THAT ARE HEAVIER THAN AIR. Sensor should be approx 12-18 in above grade. These vapor densities are greater than air.
IMPORTANTDetectors should be located close to any potential leak
source and between leak source and any potential source of ignition existing at the monitored site.
TOP VIEW OF STORAGE TANK
Detector Location and Area Coverage Map
SIDE VIEW OF STORAGE TANK
FILL LINE
OUT FLOW
XNX-Optima
DETECTOR LOCATED ONTOP OF TANK NEAR VALVEOR FLANGE ON FILL LINE
FILL LINE
TANK SUPPORT LEGS
Honeywell Proprietary
Honeywell.com
28
DETECTORS SHOULD BE LOCATED BELOW TOP OF DYKE WALL FOR VAPORS THAT ARE HEAVIER THAN AIR. Sensor should be approx 12-18 in above grade. These vapor densities are greater than air.
IMPORTANTDetectors should be located close to any potential leak
source and between leak source and any potential source of ignition existing at the monitored site.
TOP VIEW OF STORAGE TANK
SIDE VIEW OF STORAGE TANK
FILL LINE
OUT FLOW
XNX-Optima
DETECTOR LOCATED ONTOP OF TANK NEAR VALVEOR FLANGE ON FILL LINE
FILL LINE
TANK SUPPORT LEGS
Detector Location and Area Coverage Map
Honeywell Proprietary
Honeywell.com
29
IMPORTANT: This is intended as a General Application Note and NOT as the sole source of information in determining quantity and location for detector placement. Consult additional resources when developing a monitoring system. Additional information is available for developing Combustible Gas Detection systems, such as: The National Fire Protection Association, NFPA 52 and the Instrument Society of America, ISA-RP12.13-Part II-1987. Services are also available from Professional Safety Engineering Firms and should be utilized whenever necessary
IMPORTANTDetectors should be located close to
any potential leak source and between leak source and any potential source ofignition existing at the monitored site.
4 5 6
7
8
TOP VIEW OF THREE AND TWO TANK AREA
DETECTORS SHOULD BELOCATED BELOW TOP OF DYKE WALL FOR VAPORSTHAT ARE HEAVIER THAN AIR.Sensor should be approx 12-18 in. above grade..
SIDE VIEW OF TANK
Detector Location and Area Coverage Map
Honeywell Proprietary
Honeywell.com
30
IMPORTANTDetectors should be located close to any potential leak source and between
leak source and any potential source of ignition existing at the monitored site.
NOTE: DETECTORS SHOULD BE LOCATED LOW, CLOSE TO GRADE FOR VAPORS THAT ARE HEAVIER THAN AIR.NOTE: Sensor should be approx.12-18 in. above grade. These vapor densities are heavier than air.
SIDE VIEW OF UNLOADING FACILITY
I I I I
NOTE: IF PIPING FUNCTIONS OR VALVES ARE
ABOVE THE TANK CAR A DETECTOR MAY BE
MOUNTED PART WAY DOWN THE WALL TO DETECT
FALLING VAPORS FROM A LEAK SOURCE
R.R. SPUR NO. 13
R.R. SPUR NO. 12
TOP VIEW OF UNLOADING FACILITY
Detector Location and Area Coverage Map
Honeywell Proprietary
Honeywell.com
31
Publications to Reference
• Chemical Weekly, 2008, “Key Considerations when Designing a Gas Detection System”• ISA Recommended Practices • ACGIH: Annual TLV and BEI Guide
– 1330 Kemper Meadow Drive, Cincinnati OH 45240-1634• NFPA/ANSI Guides, Standards and Practices
– 1 Batterymarch Park, Quincy MA 02269-9101• NIOSH: Pocket Guide to Chemical Hazards
– Available by FAX Request to (513) 533-8573• OSHA, CFR 29, Section 1910.1000, Subpart Z“Working in Confined Spaces.”
– NIOSH1 Publication 80-106• “A Guide to Safety in Confined Spaces.”
– NIOSH Publication 87-113• “ALERT: Request for Assistance in Preventing Occupational Fatalities in Confined Spaces.”
– NIOSH Publication 86-110
Honeywell Proprietary
Honeywell.com
32
The End
Questions?