d818/et minipurge manual · 2020. 4. 27. · the purge system commences the purge cycle: • the...

40
ML511 | v12 17-April-2020 D818/ET MiniPurge ® Manual ML 511 Important Note: It is essential for safety that the installer and user of the Expo system follow these instructions. Please refer to the standard for principles and definition. These instructions apply only to the pressurizing system. it is the responsibility of the manufacturer of the pressurized enclosure to provide instructions for the enclosure. Expo Technologies reserves the right to replace any component, with one of the equivalent functionality.

Upload: others

Post on 24-Aug-2020

20 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

ML511 | v12 17-April-2020

D818/ET MiniPurge®

ManualML 511

Important Note:It is essential for safety that the installer and user of the Expo system follow these instructions.Please refer to the standard for principles and definition.These instructions apply only to the pressurizing system. it is the responsibility of the manufacturer of the pressurized enclosure to provide instructions for the enclosure.Expo Technologies reserves the right to replace any component, with one of the equivalent functionality.

Page 2: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive
Page 3: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

ML511 | v12 i

Section 1: System Specification................................................................................................1MiniPurge® Control Unit Data...................................................................................................2Relief Valve Unit and Purge Outlet Valve with integral spark arrestor......................................3

Section 2: Quick User Guide......................................................................................................4Installation ................................................................................................................................4Operation of the System...........................................................................................................4

Section 3: Application Suitability ..............................................................................................5Section 4: Description and Principle of Operation ..................................................................6Section 5: Main Components .....................................................................................................7

Air Supply Filter / Regulator......................................................................................................7Logic Air Supply Regulator .......................................................................................................7Minimum Pressure Sensor .......................................................................................................7Purge Flow Sensor ...................................................................................................................7Intermediate Sensor .................................................................................................................8Electronic Purge Timer .............................................................................................................8Purge Complete Valve..............................................................................................................8OR Gate ...................................................................................................................................8Alarm Only Circuit (/AO) ...........................................................................................................8Visual Indicators .......................................................................................................................9Power Interlock Switch .............................................................................................................9Alarm / Pressurized Switch.......................................................................................................9System Purging Switch (Optional) ............................................................................................9Purge Valve ..............................................................................................................................9Purge Flow Restrictor ...............................................................................................................9CLAPS Sensor .........................................................................................................................9CLAPS Regulator .....................................................................................................................9Relief Valve Unit .....................................................................................................................10/PA Terminal Box....................................................................................................................10

Section 6: Installation of the System.......................................................................................10Relief Valve Unit .....................................................................................................................10Air Supply Quality ...................................................................................................................10Pipe Work ...............................................................................................................................11Multiple Enclosures ................................................................................................................11Provision and Installation of Alarm Devices ...........................................................................11Power Supplies and their Isolation .........................................................................................12Power Interlock Switch ...........................................................................................................12

Section 7: Commissioning .......................................................................................................13Commissioning the System ....................................................................................................13Normal Operation ...................................................................................................................14

Section 8: Maintenance of the System....................................................................................15General maintenance .............................................................................................................15Additional maintenance checks ..............................................................................................15Maintenance of Electronic Timer ............................................................................................15Re-calibration of the Relief Valve Unit ....................................................................................15Re-calibration of the Pressure Sensors..................................................................................16

Section 9: Fault Finding............................................................................................................17General Information................................................................................................................17System purges correctly but trips and auto re-purges at the end of the purge time. ..............17Relief Valve opens (continuously or intermittently).................................................................18System enters purging but purge indication does not occur...................................................18System begins purging but cycles fail to complete.................................................................18

Section 10: Recommended Spares List ..................................................................................19Section 11: Glossary.................................................................................................................19Section 12: Drawings and Diagrams .......................................................................................19Section 13: Certifications .........................................................................................................20

Page 4: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

Section 1: System Specification

3 X LC / ss / ET / OV / PC / PA

Size 3 = MiniPurge®

Purge flow rate:1000-1500 NI/min

Approval / Certification

Sira 01ATEX1295X 2813 II 2(2) GD

Ex [pxb] ia IIC T5 GbEx [pxb] ia IIIC T100ºC DbTamb -20ºC to +55ºC

IECEx SIR07.0027XEx [pxb] ia IIC T5 GbEx [pxb] ia IIIC T100ºC DbTamb -20ºC to +55ºC

TÜV 12.1462XEx [pxb] ia IIC T5 GbEx [pxb] ia IIIC T100ºC DbTamb -20ºC to +55ºC

PC = Pressurized Control. Automatic leakage compensation (CLAPS)

OV = Purge Outlet Valve is pneumatically operated

Timing MethodET = Electronic Timer

MiniPurge® Housingss = Stainless Steel 316L

Pressurization MethodLC = Leakage Compensation

ATEX Certificate:

IECEx Certificate:

TÜV INMETRO Certificate:

PA = Power and Alarm Switches. Integral /PA Terminal Box

Page1

ML511 | v12Expo Technologies UKT: +44 (0) 20 8398 8011

E: [email protected]

Expo Technologies UST: +1 (440) 247 5314

E:[email protected]

Expo Technologies ChinaT: +86 532 8906 9858

E: [email protected]

Page 5: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

MiniPurge® Control Unit DataAction on Pressure Failure: Alarm and Trip (isolate power to pressurized enclosure), user

adjustable Alarm Only.Type of Operation: Automatic leakage compensation using the Closed Loop Automatic

Pressurization System (CLAPS System).Leakage Compensation Capacity: 500 NI/min @ 4barg inlet pressureLeakage Compensation over capacity:

+40%(minimum) of the normal enclosure leakage

Enclosure Material: Stainless Steel 316L.Mounting Method Wall mounting straps. Fixing holes as per drawing.Temperature Limits: -20oC to +55oCCompressed Air Supply: Clean, dry, oil free air or inert gas. Refer to Air Supply Quality section

in Installation of the System.Supply Pressure: 4 to 8 barg (60 to 120 psi). Main Regulator: Set at 4 barg, 40 μm automatic drain supply inlet filter.Logic Regulator and Gauge: Fitted and set to 2.5 barg (36 psi).Process Connections: Purge supply and outlet to pressurized enclosure 1/2” NPT female.

Minimum supply line 13 mm (1/2”) ID tube, inlet sized appropriately for flow rate.Reference points & signals 1/8” NPT female, minimum 6 mm pipe to be used.

Visual Indicators: Alarm (Red ) / Pressurized (Green ).System Purging: 4 LEDs that flash sequentially to indicate elapsed time (black when not purging).

/PA Terminal Box: Stainless Steel, Ex e IIC T5 Gb / Ex tb IIIC T100ºC Db IP66 Tamb : -20ºC to +55ºC with terminals, front access cover & lower removable gland plate. Stainless Steel, Ex e IIC T4 Gb Tamb : -20ºC to +60ºC with terminals, front access cover & lower removable gland plate.

Power Interlock Switch: DPNO switch, contact ratings 250 Vac 4 Amps (AC-15) / 24V DC 4A, Ex d IIC T6 Gb / Ex tb IIIC T80ºC Db.

Alarm Switch: SPCO switch, contact ratings 250 Vac 4 Amps (AC-15) / 24V DC 4A, Ex d IIC T6 Gb / Ex tb IIIC T80ºC Db.

Minimum Pressure Sensor: Minimum: 0.5 mbarg.Maximum: 5.0 mbarg.Default Setting: 1.5 mbarg.Tolerance -0, +0.7 mbarg.

Purge Flow Sensor: Set at 6.4 mbarg (Tolerance: -0, +10%).CLAPS Sensor: Minimum: 5.0 mbarg.

Maximum:15 mbarg.Default Setting: 10 mbarg.Tolerance: -0, +10%

Note: there must be a 2.5 mbarg difference between the intermediate and CLAPS sensor calibration point. For example: Minimum pressure = 5 mbarg, intermediate pressure = 6.5 mbarg, CLAPS sensor = 9 mbarg.

Purge Time: User selectable, in 1 minute intervals, up to 99 minutes (tolerance -0, +3 seconds).

ML511 | v12 Page2

Expo Technologies UKT: +44 (0) 20 8398 8011E: [email protected]

Expo Technologies UST: +1 (440) 247 5314E:[email protected]

Expo Technologies ChinaT: +86 532 8906 9858E: [email protected]

Page 6: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

Relief Valve Unit and Purge Outlet Valve with integral spark arrestor

Note: Special settings are available on request, see Test and Inspection Sheet.

Default Setting 99 minutes.Weight: 16 kg (35lb).

Type: ARV-0528-107Bore: Purge Outlet Valve Ø 52 mm, Relief Valve Ø 52 mm.Relief Valve Lift-Off Pressure: Minimum: 20 mbarg.

Maximum: 50 mbarg.Default: 30 mbarg (+0, -20%).

Flow Rate: Range: 500, 1000 or 1500 NI/min.Default: 1500 NI/min.

Material: Housing: Stainless steel 316L.Gasket: Silicone.Spark arrestor: Stainless steel mesh.

Mounting Method: Rectangular cut-out and fixing holes as per drawing.Weight: 4 kg (8.8 lb).

Page3

ML511 | v12Expo Technologies UKT: +44 (0) 20 8398 8011

E: [email protected]

Expo Technologies UST: +1 (440) 247 5314

E:[email protected]

Expo Technologies ChinaT: +86 532 8906 9858

E: [email protected]

Page 7: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

Section 2: Quick User GuideInstallationThe MiniPurge® System must be installed by a competent engineer, in accordance with relevant standards,such as IEC / EN 60079-14 and any local codes or practice.

• Mount the purge system in accordance with the hook-up drawing.

• Ensure the system is installed according to the full instructions in the “Installation of the System” section of this manual.

• All pipings must be clean and free of dirt, condensation and debris prior to connection to the purge system or pressurized enclosure.

• It is strongly recommended that a local isolation valve is installed on the air supply upstream of the purge system.

Note: Most faults are due to restricted air supply, inadequate supply pipe work or drop in air supply pressure during the purge process.

Operation of the SystemOnce the system is installed correctly, turn on the air supply. Refer to Commissioning section.

The purge system commences the purge cycle:

• The purge air will enter the enclosure.

• The pressurized enclosure will obtain a positive pressure.

• The Purge Outlet Valve will open within the Relief Valve Unit.

• The air will then exit the Relief Valve Unit housing via the spark arrestor.

Open the Purge Flow Restrictor Valve until the air flow reaches the required rate; the system will initiate the timed purge cycle. Start a stopwatch when the purging indicator flashes yellow

On completion of an uninterrupted purge cycle of the required length, the system will indicate purge complete. Stop the stopwatch when the purging indicator stops flashing.

Indicator Colour Status

Alarm / Pressurized Red Low pressure alarm (enclosure pressure too low)

Purging Black Purge flow too low or not in purge mode

Indicator Colour Status

Alarm / Pressurized Green Pressurized (minimum enclosure pressure achieved)

Purging Black Purge flow too low

Indicator Colour Status

Alarm / Pressurized Green Pressurized

Purging Sequential flashing Yellow

Purge flow rate above minimum

Indicator Colour Status

Alarm / Pressurized Green Pressurized and in leakage compensation mode

ML511 | v12 Page4

Expo Technologies UKT: +44 (0) 20 8398 8011E: [email protected]

Expo Technologies UST: +1 (440) 247 5314E:[email protected]

Expo Technologies ChinaT: +86 532 8906 9858E: [email protected]

Page 8: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

Check stopwatch timing to verify that the actual purge time is equal to or greater than the required purge time.

Note: The recorded purge time must never be less than the required purge time.The system is now operating correctly in leakage compensation mode.

If the system has not performed as expected, check the installation thoroughly and ensure it has been carried out according to the instructions.

If an obvious problem has not been highlighted and corrected, follow the procedures in the Fault Finding section.

If all checks have been carried out and the system still does not perform as expected, contact your local distributor or Expo Technologies.

Section 3: Application SuitabilityMiniPurge® systems are certified for use in hazardous locations, where the hazardous location is non-mining (above ground) and the hazard is caused by flammable gasses, vapours or dust. Depending on the model the systems may be used in IECEx and ATEX Zone 1 and/or Zone 2 - Categories 2 and 3 respectively.

MiniPurge® systems may be used for hazards of any gas group. Apparatus associated with the MiniPurge® system, such as intrinsically safe signalling circuits and flameproof enclosures containing switching devices may be limited in their gas group. The certification documentation supplied with any such devices must be checked to ensure their suitability.

This system is primarily designed for use with compressed air. Where other inert compressed gasses are used (Nitrogen, for example) the user must take suitable precautions so that the build up of the inert gas does not present a hazard to health. Consult the Control of Substances Hazardous to Health (COSHH) data sheet for the gas used. Where a risk of asphyxiation exists, a warning label must be fitted to the pressurized enclosure.

The following materials are used in the construction of MiniPurge® systems. If substances that will adversely affect any of these materials are present in the surrounding environment, please consult Expo Technologies for further guidance.

Purging Black No longer in purge mode

Materials of Construction

Stainless Steel Aluminium Acrylic

Mild (Carbon) Steel Nylon Silicone

Brass Polyurethane Neoprene

ABS Polycarbonate Polyester (glass filled)

Indicator Colour Status

Page5

ML511 | v12Expo Technologies UKT: +44 (0) 20 8398 8011

E: [email protected]

Expo Technologies UST: +1 (440) 247 5314

E:[email protected]

Expo Technologies ChinaT: +86 532 8906 9858

E: [email protected]

Page 9: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

Section 4: Description and Principle of OperationThe MiniPurge® system is pneumatic in operation, with electrical interfaces.

Purge and pressurization is a method of protection used in Zone 1 (21) and/or Zone 2 (22) hazardous locations to ensure that the interior of an enclosure is free of flammable gas. Addition of a MiniPurge® system allows the electrical equipment within the enclosure to be used safely in a hazardous location.

The principle of purge and pressurization is as follows:

• Clean compressed air or inert gas is drawn from a non-hazardous location.

• The interior of the pressurized enclosure is flushed to remove any hazardous gas or dust.

• This is introduced into the pressurized enclosure to keep the internal pressure at least 0.5 mbarg abovethe external pressure.

• Whilst pressurized, flammable gas cannot enter the enclosure from the environment.

Prior to switching on the power to the electrical equipment, the enclosure must be purged to remove any flammable gas that might have entered the enclosure before pressurization. Purging is the process of removal contaminated air and replacement with air (or inert gas) known to be free from flammable gas. The duration of this purge process is normally ascertained by performing a purge test.

At the end of the purge cycle the system automatically switches to leakage compensation mode. The Purge Outlet Valve is closed and the airflow is reduced but remains high enough to compensate for the leakage of air from the enclosure whilst maintaining the minimum over pressure state.

In the event of pressure failure within the pressurized enclosure the system will raise an alarm in the form of visual indicators and a volt free contact depending on the specification of the system. The default action on loss of pressurization is alarm and automatic disconnect of power (A&T - Alarm and Trip). This can be changed by the customer to Alarm Only (/AO), please refer to section titled Main Components.

The MiniPurge® system incorporates a Closed Loop Automatic Pressurization System (CLAPS). This allows the system to detect a rise or fall of the enclosure’s internal pressure and adjust the leakage compensation rate accordingly. Pressure variations are more likely during sudden start up of large rotating electrical machines but can also be caused by changes in running temperature. This system has been specifically designed to maintain a stable internal pressure within the enclosure.

ML511 | v12 Page6

Expo Technologies UKT: +44 (0) 20 8398 8011E: [email protected]

Expo Technologies UST: +1 (440) 247 5314E:[email protected]

Expo Technologies ChinaT: +86 532 8906 9858E: [email protected]

Page 10: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

Pressure characteristics during purge and pressurization of a pressurized enclosure using a MiniPurge® system that incorporates a CLAPS system:

Section 5: Main ComponentsAir Supply Filter / RegulatorThe unit is provided with a 40 μm liquid / dust filter element as a precaution. The user of the MiniPurge® system must ensure that air supply is to the quality stated in Air Supply Quality paragraph found in the Installation of the System section. The regulator is factory set to 4 barg (60 psig) and regulates the pressure of an air supply between 4 and 8 barg (60 to 120 psig). A pressure gauge is fitted down stream of the filter; this should indicate no less than 4 barg (60 psig). During the purge cycle a pressure drop will be indicated on the gauge.

Logic Air Supply RegulatorThis device provides the system with a stable air supply pressure to the logic system and allows consistent operation. The pressure level is factory set to 2.5 barg (36 psig) and can be verified by means of the integral pressure gauge.

Minimum Pressure SensorThis monitors the pressure inside the pressurized enclosure. When the pressure is below the minimum required for safe operation, the pressure sensor causes the system to reset and the Alarm / Pressurized indicator turns Red . The sensor is factory calibrated and set to operate in falling pressure at or above the minimum specified pressure.

Purge Flow SensorThe Purge Flow Sensor monitors flow through the Purge Outlet Valve. At correct purge flow rates, above the minimum specified for purging, the sensor sends a signal that activates the purge timer. This sensor is factory calibrated to operate on falling flow rate at or above the minimum specified purge flow rate.

Intermediate PressureSensor Pressure

Power Interlock switchAlarm &Trip

Purge Time Machinery Start Normal Operation

CLAPS RegulatorPressure

Intermediate switch contactsopen. Intermediate sensorsends falling pressure signal

Fault Condition - loss of pressureoutside of CLAPS regulation

Minimum PressureSensor Pressure

Purging Pressure

Minimum pressure switch contactsopen. Minimum pressure sensor sendsa low pressure signal.Alarm indicator shows red (alarm only)Alarm indicator shows red and poweris disconnected (Alarm and Trip)

Minimumpressure switch

Intermediatepressure switch

Power Interlock switchAlarm Only

ContactsActive

Inactive

Page7

ML511 | v12Expo Technologies UKT: +44 (0) 20 8398 8011

E: [email protected]

Expo Technologies UST: +1 (440) 247 5314

E:[email protected]

Expo Technologies ChinaT: +86 532 8906 9858

E: [email protected]

Page 11: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

Intermediate SensorThis sensor monitors the pressure inside the pressurized enclosure. It senses when the pressure is drops and provides early warning before the low pressure sensor trips the system. The setting on this is user selectable.

Electronic Purge TimerWhen both the enclosure pressure and the purge flow rate are correct, the Purge Flow Sensor activates the timer and the electronic timer starts. The timing period is selected using switches mounted on the timer module.

Note: Setting the timer to 00 minutes will cause infinite purging; the cycle will never complete.During timing, the percentage of the purge cycle is indicated by four LEDs which flashes sequentially while the timer is running.

The Electronic Timer contains an intrinsically safe battery pack that needs regular replacement. See Commissioning section.

Purge Complete ValveThis valve receives a signal from the purge timer that indicates the completion of the purge cycle and verifies that the pressurization signal is still present. If both conditions are satisfied a signal is sent to indicate that the purge is complete. This performs two functions: to turn on the electrical supply to the pressurized enclosure and to reduce the high purge flow rate to leakage compensation mode. It also provides a hold-on signal that maintains the leakage compensation mode with the power switch on, even when the purge timer has reset ready for the next purge cycle.

OR GateThis device provides the Purge Complete Valve with the hold-on function referred to previously. When either the timed-out signal or the purge complete signal is present it allows the pilot signal to be sent to the purge complete valve.

Alarm Only Circuit (/AO)If the pressure in the pressurized enclosure is too low the system will normally cut off electrical power to it. In certain circumstances, where local codes of practice allow, the system can be altered to provide a hold-on circuit that will maintain the electrical power supply to the pressurized enclosure while also providing a pressure failure alarm. The user must respond to the alarm and either restore the pressure to the pressurized enclosure or otherwise make the installation safe; for example, cut off the electrical supply. The decision to use the Alarm Only facility, and the allowable length of time for non-pressurized operation, is the responsibility of the user.

Warning: It is potentially dangerous to energise the pressurized enclosure in an non-pressurized condition when it is known that there is potentially explosive gas or dust in the hazardous location.

LED 1

LED 2LED 3

LED 4 LED 1

LED 2LED 3

LED 4 LED 1

LED 2LED 3

LED 4 LED 1

LED 2LED 3

LED 4

0 to 25%of purge time

26 to 50%of purge time

51 to 75%of purge time

76 to 100%of purge time

ML511 | v12 Page8

Expo Technologies UKT: +44 (0) 20 8398 8011E: [email protected]

Expo Technologies UST: +1 (440) 247 5314E:[email protected]

Expo Technologies ChinaT: +86 532 8906 9858E: [email protected]

Page 12: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

Visual IndicatorsVisual indicators are fitted to provide status information to the operator.

* The Green / Black combination indicates normal operation of the pressurized enclosure after the initial purging cycle has been completed.

Power Interlock SwitchThis flameproof power switch is activated by the signal from the Purge Complete Valve. This activation can be used to turn on the electrical supply to the pressurized enclosure. The cable from the switch is terminated in the /PA terminal box.

Alarm / Pressurized SwitchThis flameproof switch is operated by the pressurized signal. It allows a remote electrical system status indicator to show either pressurized or a pressure failure alarm. The cable from the switch is terminated in the /PA terminal box.

System Purging Switch (Optional)This switch is operated by the purge flow signal that allows a remote electrical system status indicator to signal that the system is purging; sometimes referred to as purge in progress. The cable from the switch is terminated in the /PA terminal box.

Purge ValveThis changeover valve selects between purge air flow or leakage compensation. It is sized to allow sufficient air into the enclosure during purging based on: the specified air supply pressure range, the minimum specified purging outlet flow rate +10% and the expected leakage rate from the pressurized enclosure. At the end of the purge cycle, the purge valve closes in response to the “Purge Complete” signal; it remains in the closed position until the next purge cycle is initiated.

Purge Flow RestrictorThis valve restricts the purge flow to the minimum required flow rate. The Purge Flow Restrictor must be readjusted during commissioning.

CLAPS SensorThis sensor monitors the pressure within the pressurized enclosure and sends a control signal to the CLAPS Regulator. The normal running pressure must be determined prior to system start-up so that the CLAPS Sensor may be set to the level required to control the CLAPS Regulator.

CLAPS Regulator This is the regulator that controls the leakage compensation air flow into the enclosure after the purging is complete. It either increases or decreases the air flow into the enclosure as appropriate to maintain a stable running pressure. The CLAPS Regulator must be set at the time of commissioning.

Alarm / Pressurized Indicator

Green* Pressurized

Red Pressure Alarm (enclosure pressure low)

System Purging Indicator

Black* Purge flow too low (not in purge mode)

Yellow (flashing) Purging (flow above minimum)

Page9

ML511 | v12Expo Technologies UKT: +44 (0) 20 8398 8011

E: [email protected]

Expo Technologies UST: +1 (440) 247 5314

E:[email protected]

Expo Technologies ChinaT: +86 532 8906 9858

E: [email protected]

Page 13: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

Relief Valve UnitThe Relief Valve Unit allows the purge air to exit the enclosure safely via a built-in spark arrestor. This spark arrestor is designed to prevent the emission of arcs, sparks and incandescent particles produced within the pressurized enclosure.

Purge air passes through the Relief Valve Unit; the preset pressure differential across the appropriate orifice ensures that the purge flow sensor is activated once the selected purge flow has been attained.

During the purge cycle a pneumatic cylinder operates the Purge Outlet Valve that lets the air from inside the enclosure exhaust through the Relief Valve Unit. When the system changes to leakage compensation mode, the Purge Outlet Valve is closed and the enclosure sealed.

The Relief Valve Unit has an in-built relief valve. This is sized to ensure that, if the air supply pressure rises up from the specified maximum, the internal enclosure pressure will not exceed the specified maximum working pressure of the pressurized enclosure.

/PA Terminal BoxThe Terminal Box is increased safety (Ex e) certified and incorporates the terminal connection points for the alarm and interlock switches. All contacts provided are volt free (dry).

Cable entry methods (for example conduit or cable glands) must be certified to IECEx, ATEX or INMETRO standards. The main requirement is that IP66 (or better) ingress protection must be provided by use of seals or washers.

Section 6: Installation of the SystemThe MiniPurge® is designed for use under normal industrial conditions of ambient temperature, humidity and vibration. Please consult Expo before installing this equipment in conditions that may cause stresses beyond normal industrial conditions.The MiniPurge® system must be installed by a competent person in accordance with relevant standards, such as IEC / EN 60079-14, and any local codes of practice.

The MiniPurge® control unit should be installed either directly on, or close to the pressurized enclosure. It should be installed such that the system indicators and certification labels are in view.

All parts of the system carry a common serial number. If installing more than one system, ensure that this commonality is maintained within each system installed.

Relief Valve UnitTo achieve effective purging, the points where air enters and exits the pressurized enclosure should normally be at opposite ends of the enclosure. The RLV unit must be mounted vertically and there should be a minimum clearance of 300 mm (12") around the spark arrestor (purge outlet).

It is important that the interior and exterior of the spark arrestor is kept clean and debris is not allowed to accumulate; this might affect the calibration of the device. In particular the exterior of the spark arrestor should not be painted or blocked in any way.

Air Supply QualityThe MiniPurge® system should be connected to a protective gas supply, which is suitable for purging and pressurization.

The supply pipe connection to the MiniPurge® must be appropriate for the maximum input flow rate for the application.

The air supply must be regulated at a pressure less than the maximum stated inlet pressure.

ML511 | v12 Page10

Expo Technologies UKT: +44 (0) 20 8398 8011E: [email protected]

Expo Technologies UST: +1 (440) 247 5314E:[email protected]

Expo Technologies ChinaT: +86 532 8906 9858E: [email protected]

Page 14: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

The air supply must be: clean, non-flammable and from a non-hazardous location. The air should be of Instrument Air Quality. Although the purge control system will operate with lower air quality, its operational life will be adversely affected. The equipment that is being protected by the MiniPurge® may also suffer because of poor air quality.

With reference to BS ISO 8573-1: 2010, Instrument Air is typically specified as:

Particle Class 1

In each cubic metre of compressed air, the particulate count should not exceed 20,000 particles in the 0.1 to 0.5 micron size range, 400 particles in the 0.5 to 1 micron size range and 10 particles in the 1 to 5 micron size range.

Humidity or pressure dew point

The dew point, at line pressure, shall be at least 10 °C below the minimum local recorded ambient temperature at the plant site. In no case, should the dew point at line pressure exceed +3 °C.

Oil Class 2

In each cubic metre of compressed air, not more than 0.1mg of oil is allowed. This is a total level for liquid oil, oil aerosol and oil vapour.

When an inert gas is being used to supply the purge system, risk of asphyxiation exists. Refer to Application Suitability section.

Before connection of the air supply to the purge system, the supply pipe work should be flushed through with instrument quality air to remove any debris that may remain in the pipes. This must be carried out for at least 10 seconds for every meter of supply pipe.

Unless a supply shut-off valve has been fitted to the MiniPurge® system, an external shut-off valve with the same, or larger, thread size as the Control Unit inlet fitting should be fitted by the installer to prevent any restriction of purge flow.

The purge air from the MiniPurge® Control Unit should be piped within the pressurized enclosure to ensure purging of potential dead air spots.

The purge system is fitted with an internal regulator factory set to 3 bar feeding the logic.

Pipe WorkIf the MiniPurge® is not connected directly to the pressurized enclosure, pipe work and fittings used to connect the Control Unit to the pressurized enclosure should be either metallic or appropriate to the environment into which the system is installed. No valve may be fitted in any signal pipe connecting the Control Unit to the pressurized enclosure. This pipe work must be fitted in accordance with local codes of practice where relevant.

Multiple EnclosuresThis system is suitable for the purge and pressurization of the primary pressurized enclosure and its associated terminal boxes.

Provision and Installation of Alarm DevicesWhen the pressure inside the pressurized enclosure is above the minimum, the Minimum Pressure Sensor returns a positive (pressurized) signal causing the alarm indicator on the control unit to change from red to green.

Page11

ML511 | v12Expo Technologies UKT: +44 (0) 20 8398 8011

E: [email protected]

Expo Technologies UST: +1 (440) 247 5314

E:[email protected]

Expo Technologies ChinaT: +86 532 8906 9858

E: [email protected]

Page 15: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

When the pressure falls below the minimum permissible the positive (pressurized) signal is removed. This absence of signal indicates a low pressure alarm condition and causes the alarm indicator on the control unit to go from green to red.

There are volt free (dry) contacts available within the terminal box for remote usage.

The user must make use of this alarm facility in accordance with the local code of practice for Action on Pres-sure or Flow Failure. Most codes include the following recommendations:

• Zone 1 Installations: Alarm and Automatic Trip of Power.

• Zone 2 Installations: Alarm Only on pressure or flow failure with power being removed manually.

Power Supplies and their IsolationAll power entering the pressurized enclosure should have a means of isolation. This requirement also applies to any external power sources that are connected to the equipment such as volt-free (dry) contacts within the pressurized enclosure. This is commonly achieved using the Power Interlock Switch.

Power Interlock SwitchThis switch is a Double Pole Normally Open, double-break switch: it provides two independent contacts that should be connected in series and used to isolate the power. This can be achieved using switchgear or other suitable switching device. These contacts are terminated and accessible to the user in the Ex e terminal box.

It is the responsibility of the user to ensure that the switch is only operated within appropriate technical limits.

The switch must be replaced after any short circuit that occurs within the main circuit; the switch is a piece of encapsulated equipment and as such it is not possible to check the state of the contacts. Technical modifications to the switch are not permitted.

Prior to commissioning, check that the Ex e terminal box is clean, the connections have been made properly, the cables laid correctly and all screws in the terminals are secure.

In all cases the application and isolation of power must be controlled by the MiniPurge® system using the power interlock signal.

No switches are permitted between the power switch and the MiniPurge® system other than an authorized manual override circuit.

The safe use of this switch is the responsibility of the user, all electrical installations must conform to local codes of practice.

ExceptionPower to apparatus that is already suitable for use in hazardous locations need not be isolated by the MiniPurge® system.

ML511 | v12 Page12

Expo Technologies UKT: +44 (0) 20 8398 8011E: [email protected]

Expo Technologies UST: +1 (440) 247 5314E:[email protected]

Expo Technologies ChinaT: +86 532 8906 9858E: [email protected]

Page 16: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

Section 7: CommissioningCommissioning the SystemNote: The steps 11 and 15 to 21 represent detailed commissioning testsThe following equipment is needed for this process:• Continuity meter• Gauge manometer (0 to 200 mbarg)• Differential manometerIf, after commissioning, the system does not perform as expected, refer to the Fault Finding Section.Follow the steps as outlined:1. Check all connections and that the Relief Valve Unit is fitted correctly with an unobstructed path to the

purge exhaust.2. Close the Purge Flow Restrictor Valve.3. Fully open external supply shut-off valve where fitted.4. Check that the internal logic pressure gauge reads 2.5 barg / 36 psi / 250 kPag.5. Check that the pressure gauge on main air supply reads 4 barg / 60 psi / 400 kPag.6. Check that the Pressure Relief Valve is correctly set by disconnecting the minimum pressure sensing pipe

at the bulkhead fitting on the input to the MiniPurge®. This will disable all of the pressure sensors.• Using a 4 mm nylon tube, connect a manometer to the bulkhead fitting from which the minimum pressure sensing pipe was removed.• Open the Purge Flow Restrictor Valve very slowly, until the Pressure Relief Valve opens • Check the opening pressure is within calibration limits. • This test can be carried out several times to ensure repeatability and compliance.Refer to the Maintenance of the System section if the Relief Valve needs recalibrating.

7. Close the Purge Flow Restrictor Valve.8. Remove the manometer and reconnect the minimum pressure sensing pipe to the bulkhead fitting.9. Remove red plug from the top of the Minimum Pressure Sensor and connect a gauge manometer.10.Connect a differential manometer to the test points on the flow sensor.11.To check sensor calibration

• The internal pressure in the pressurized enclosure must be below Relief Valve lift off pressure and above the CLAPS pressure• At this time the pressurized indicator should be green.• gradually open Purge Flow Restrictor Valve until purging indicator flashes yellow.Note: For large volumes it may take a long time for the purge flow to start.• very slowly close Purge Flow Restrictor Valve until the purging indicator stops flashing yellow.• Take a reading from pressure gauge.

12.To set the purge flow rate:

• Turn on the compressed air to the MiniPurge®.• Gradually open the Purge Flow Restrictor Valve until the black / yellow indicator changes to yellow (flashing). • The flashing yellow indicator confirms the correct flow rate.• The differential pressure should be greater than 6.4 mbarg.

Page13

ML511 | v12Expo Technologies UKT: +44 (0) 20 8398 8011

E: [email protected]

Expo Technologies UST: +1 (440) 247 5314

E:[email protected]

Expo Technologies ChinaT: +86 532 8906 9858

E: [email protected]

Page 17: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

• The relief valve is supplied with different orifice plates for the specified flow rate. This orifice plate is held in position by two M3 screws and can easily be changed by removing the large cover plate from over the outlet valve assembly and screws.

Warning: When opening the Purge Flow Restrictor Valve, ensure the over pressure within the pres-surized enclosure does not exceed the pressure relief valve setting.13.The purge timer will start as soon as the Purging Indicator flashes yellow. Check that the time delay

between the indicator turning to yellow (flashing) and returning to black is not less than the minimum time required for complete purging of the pressurized enclosure. Times in excess of minimum are permitted.

14.After the purge has been completed, the Purge Valve will close and the air flow into the pressurized enclosure will be controlled by the CLAPS Regulator. The initial setting may be too high or too low.

15.Gradually turn the CLAPS Regulator anti-clockwise to reduce enclosure pressure.16.Reduce regulator until intermediate sensor causes contacts to open.17.Check the manometer on the minimum pressure sensor.18.Continue to reduce the CLAPS Regulator to test the minimum pressure sensor.19.To check operation of Minimum Pressure Sensor, check readings on manometer as system will

automatically re-purge when it reaches minimum pressure.20.While the system re-purges, return the CLAPS Regulator to the initial setting. 21.If minimum pressure is below the set point, refer to the Recalibration section22.If the setting is too high, continual rising and falling of the enclosure pressure will be seen as the CLAPS

Regulator automatically shuts off and reinstates the flow. The CLAPS Regulator should be adjusted to reduce the flow into the pressurized enclosure by turning the adjuster screw anti-clockwise.

23.If the initial setting is too low the CLAPS Regulator may not provide enough air flow causing a gradual decline in enclosure pressure. To increase the flow into the pressurized enclosure, adjust the CLAPS Regulator Relief Valve unit by turning the adjuster screw clockwise.

24.To test the CLAPS settings, create a leak in the system by removing a bolt or losening a gland plate in order to create a 15mm hole. Remember to replace bolt or retighten gland plate after testing.

25.The setting of the CLAPS Sensor is factory calibrated to the normal working pressure expected in the pressurized enclosure, typically 10 mbarg. The pressure in the pressurized enclosure should be stabilized as close as possible to this figure. This can be checked by a manometer attached to the minimum pressure sensor.

26.Remove the air supply to the system, remove all test equipment and replace all plugs.Normal OperationFor normal operation of the system, after commissioning has been carried out it is possible to turn the air supply valve on or off to start or stop the system. After this, the purge and pressurization sequence is automatic.

ML511 | v12 Page14

Expo Technologies UKT: +44 (0) 20 8398 8011E: [email protected]

Expo Technologies UST: +1 (440) 247 5314E:[email protected]

Expo Technologies ChinaT: +86 532 8906 9858E: [email protected]

Page 18: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

Section 8: Maintenance of the SystemGeneral maintenanceThe maintenance of the system outlined in this manual should be supplemented with any additional requirements set out in appropriate local codes of practice.The following checks should be carried out every 6 – 36 months dependent on environment according to IEC / EN 60079-17 • Tests outlined in the Detailed Commissioning section.• Ensure that the Relief Valve Unit is free from contamination prior to making any adjustment. To do this:

• Remove large cover plate using a 8 mm spanner (wrench).• Check that the interior and all components are clean and free from contamination.• Replace large cover plate.

• Check the condition of the air supply filter element. Clean or replace as necessary.Additional maintenance checksThe following additional checks are recommended at least every 3 years:Check that:• Apparatus is suitable for use in the hazardous location.• There are no unauthorised modifications.• The air supply is uncontaminated.• The interlocks and alarms function correctly.• Approval labels are legible and undamaged.• Adequate spares are carried.• The action on pressure failure is correct.

Maintenance of Electronic Timer

This should be carried out every 3 years.

• The intrinsically safe battery pack associated with the electronic timer should be replaced and the commissioning tests repeated.

• After the timing phase has elapsed, the battery may be hot-swapped in the hazardous location without affecting the operation of the MiniPurge® system

Re-calibration of the Relief Valve Unit

Warning

Incorrect adjustment of the Relief Valve Unit can lead to significant over pressure and result in damage to the enclosure.If maximum pressure setting is reached, stop adjustment and reduce the pressure.To perform the following adjustments, an 8 mm spanner (wrench) and a 2.5 mm hex key will be required.Ensure that the Relief Valve Unit is free from contamination prior to making any adjustment. To do this: • Remove large cover plate using a 8 mm spanner (wrench).• Check that the interior and all components are clean and free from contamination.• Replace large cover plateTo adjust the lift off pressure of the Relief Valve:• Attach test equipment as described in the Commissioning Section.

Page15

ML511 | v12Expo Technologies UKT: +44 (0) 20 8398 8011

E: [email protected]

Expo Technologies UST: +1 (440) 247 5314

E:[email protected]

Expo Technologies ChinaT: +86 532 8906 9858

E: [email protected]

Page 19: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

• Remove small cover plate.• Whilst holding the central adjustment screw in position using the hex key, loosen the retaining nut.• Adjust the hex key clockwise to increase, or anti-clockwise to reduce the lift off pressure.• Before testing, retighten the locking nut whilst holding the adjustment screw in place.• Carry out the commissioning tests to check the correct setting of the relief valve after adjustment.

• The adjustment is sensitive and it is recommended that a 1/4 turn (maximum) adjustments are applied between tests.

Re-calibration of the Pressure SensorsThe brass nozzle on the sensor is sealed into position using Loctite thread sealant. If the thread has seized up, remove to a safe area and heat slightly to soften prior to making any adjustment. This prevents potential damage to the brass of the nozzle.• Disconnect pipe work from the sensor, including pipe located below the sensor.• Remove sensor by unscrewing anti-clockwise.• The nozzle is located under the sensor.

• The adjustment is sensitive, turn the nozzle in 1/8 of a turn steps.• Turn clockwise to reduce the pressure setting and anti-clockwise to increase.• Replace sensor, screwing clockwise.• Reconnect all pipe work.

Orifice PlateAllen Screw and Lock NUT

Removing the small cover plate to set the RLV opening pressure

ML511 | v12 Page16

Expo Technologies UKT: +44 (0) 20 8398 8011E: [email protected]

Expo Technologies UST: +1 (440) 247 5314E:[email protected]

Expo Technologies ChinaT: +86 532 8906 9858E: [email protected]

Page 20: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

Section 9: Fault FindingGeneral InformationIf you are having problems that cannot be corrected using one of the methods described, please call Expo oryour supplier for further assistance. If the system is less than 12 months old, parts under warranty should bereturned to Expo for investigation. A full report of the fault and the system serial number should accompanythe parts.It is common for problems with the MiniPurge® system to be caused by contamination of the air supply withoil, water or dirt. To prevent these problems, the air supply must contain a dust filter and a water filter. Thiswill ensure that the air is instrument quality and protect both the purge system and the equipment beingpurged. This filtration system is not provided by Expo and must be sourced separately.Contamination can enter the system from a number of sources. To prevent this, it is essential that theprocedures described in the Installation section are carried out prior to first use of the system. Theseprocedures should also be carried out following any disconnection and re-connection of the pipe work. Failureto perform these procedures may cause damage to the system that will not be covered by the warranty.The system has been designed for ease of fault finding and many of the components fitted are plug-in orchassis mounted. Check components by substitution only after establishing that such action is necessary.Before carrying out the fault finding procedures, ensure that:• Both the main air pressure to the system and for Motor Purge Systems, the regulated pressure to the logic

manifold are as specified on the settings sheet.• Air pressure does not drop below the minimum supply pressure during purging; the majority of faults

reported are due to insufficient air supply during the purge cycle.

System purges correctly but trips and auto re-purges at the end of the purge time.This is a result of the pressure within the pressurized enclosure being below the minimum pressure sensor setting. The pressure can be checked using a manometer. The most common causes of this problem are outlined below.Fault Location Cause SolutionPressurized Enclosure There is debris on the face of the

Relief Valve disk held in place by the magnet.

• Remove debris and ensure RLV disk is clean.

Enclosure leaking excessively. • Ensure all doors and covers are closed and that all conduit and cable glands are properly sealed.

• Seal any other leaks.Pressure sensing tube damaged. • Replace tubing.

CLAPS Regulator The CLAPS Regulator setting is too low.

• Increase the setting of the CLAPS regulator to raise the pressure in the pressurized enclosure after purging.

• To do this, turn clockwise.MiniPurge® Control Unit the Minimum Pressure Sensor

setting has drifted above the CLAPS setting

The Minimum Pressure Sensor needs re-calibrating.

• Refer to Re-calibration of PressureSensors in the Maintenancesection

Page17

ML511 | v12Expo Technologies UKT: +44 (0) 20 8398 8011

E: [email protected]

Expo Technologies UST: +1 (440) 247 5314

E:[email protected]

Expo Technologies ChinaT: +86 532 8906 9858

E: [email protected]

Page 21: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

Relief Valve opens (continuously or intermittently)

System enters purging but purge indication does not occur

System begins purging but cycles fail to complete

Fault Location Cause SolutionPressurized Enclosure Enclosure pressure is too high

due to CLAPS Regulator being open to far.

Adjust the CLAPS Regulator.

Relief Valve Unit Debris on the Relief Valve disk allowing air to leak from the valve.

Remove Relief Valve cover and clean the valve disk.

Fault Location Cause SolutionAir Supply Insufficient flow rate due to

inadequate air supply pressure. Often due to pressure drop in the supply pipe.

Static pressure of 5 barg must bemaintained during purge• Check air supply pressure at the

inlet to the control unit. • Ensure that the supply pipe bore is

suitable for the flow ratePressurized Enclosure Excessive leakage from the

pressurized enclosure.• Check around the enclosure while

purging is taking place. • Total leakage at purge outlet valve

should not exceed 10% of purge flow sensor setting.

• Check for leakage down cables and conduit.

Pipe Work Tubing from Relief Valve flow sensing point not air tight.

• Ensure fitting nuts are tightened.• Check for tube damage.• Repair as necessary.

Relief Valve Unit Relief Valve opening during purge • Check enclosure pressure on start up is less than Relief Valve lift off pressure.

MiniPurge Control Unit Flow sensor setting incorrect • Check the pressure is correct on the flow sensor.

Fault Location Cause SolutionElectronic Timer Time set to 00 • Reset timer to correct purge

time.The intrinsically safe battery pack is discharged

• Replace as necessary .

ML511 | v12 Page18

Expo Technologies UKT: +44 (0) 20 8398 8011E: [email protected]

Expo Technologies UST: +1 (440) 247 5314E:[email protected]

Expo Technologies ChinaT: +86 532 8906 9858E: [email protected]

Page 22: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

Section 10: Recommended Spares List

Section 11: Glossary

Section 12: Drawings and Diagrams

Part Number DescriptionS0015/250 Filter kit for main air supply filter/regulatorS0030/606 Purge flow sensor factory set to 6.4 mbargS0030/016 Minimum Pressure sensor, must be factory set to the value as stated on the

Customer Test and Inspection SheetS0030/588 CLAPS Sensor must be factory set to the value as stated on the Customer Test

and Inspection SheetS0015/018 Pressure gauge (Air Supply Pressure), 0 - 10 bargS0015/135 Miniature gauge (Logic Pressure), 0-4 bargETM-IS31-001 IS battery pack for electronic timer moduleAGE-GE00-168 Electronic Timer Assembly c/w potted Timer Switch

Acronym DefinitionA&T Alarm and TripAO Alarm OnlyCLAPS Closed Loop Automatic Pressurization SystemCU Control UnitET Electronic TimerFCV Flow Control ValveIS Intrinsically SafeLC Leakage CompensationPA Power and Alarm RLV Relief Valve Unit

Title Drawing Number Number of SheetsD818 Control Unit Motorsys-E XBR-7TD0-068 2Motorpurg Hook-Up MOTOR-HU 1P and I Diagram XBR-7TD0-064 1D818 Circuit Diagram XBR-7TD0-071 1D818 Ex e Terminal Box Layout AGE-WC00-224 1Manual Override Switch Hook-up AGE-WC00-117 1Size 3 MotorPurge Relief Valve XBR-RTD0-010 1

Page19

ML511 | v12Expo Technologies UKT: +44 (0) 20 8398 8011

E: [email protected]

Expo Technologies UST: +1 (440) 247 5314

E:[email protected]

Expo Technologies ChinaT: +86 532 8906 9858

E: [email protected]

Page 23: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

Section 13: CertificationsCertificates can be found in the accompanying booklet (ML497) or download the certificates at www.expoworldwide.com/downloads.

*Certificates are attached to the manual.

Component Certificate NumberPurge System ATEX Certificate SIRA 01ATEX1295X

IECEx Certificate IECEx SIR07.0027XINMETRO/TÜV Certificate TÜV 12.1462X

MIU/e Ex e Terminal Box ATEX Certificate Sira 99ATEX3173X*IECEx Certificate IECEx SIR 06.0087X*

Electronic Timer ATEX Certificate FM 10 ATEX0003X IECEx Certificate IECEx FME 10.0001X

Electronic Switches Ex d limit switch IECEx EPS 14.0092XEx d limit switch EPS 14 ATEX 1766 X

ML511 | v12 Page20

Expo Technologies UKT: +44 (0) 20 8398 8011E: [email protected]

Expo Technologies UST: +1 (440) 247 5314E:[email protected]

Expo Technologies ChinaT: +86 532 8906 9858E: [email protected]

Page 24: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

Min

iPurg

e

NO

TES

1.

MIN

IPU

RG

EM

UST

BE

MO

UN

TED

INTH

EATTIT

UD

ESH

OW

N.

2.

WEIG

HT:

16

kg

MO

DEL

NO

.3XLC/s

s/E

T/P

A/O

V/P

C/D

818

EXPO

TECH

NO

LO

GIE

SPART

CO

DE:

D818M

OTO

RSYS-E

MATERIA

LS

SYSTEM

HO

USIN

G:

STAIN

LESS

STEEL

316

ALL

BU

LKH

EAD

FIT

TIN

GS:

STAIN

LESS

STEEL

304/3

16

210

72

430

400

250

215

120

400

110

56

A B

42

31

30

18

50

100

50

VIE

WO

N

ARRO

W'A

'

VIE

WO

NARRO

W'B

'

MA

TE

RIA

L

DR

'WN

AP

P'D

CH

K'D

DR

AW

ING

ST

AT

US

:

AP

PR

OV

ED

:

MO

D.N

o:

DA

TE

:

ISS

UE

:

3rd

AN

GLE

PR

OJE

CT

ION

DIM

EN

SIO

NS

INm

m

DO

NO

TS

CA

LE

Exp

oT

ech

no

log

ies

Lim

ited

JO

BN

o:

FIN

ISH

TIT

LE

CU

ST

OM

ER

:S

HE

ET

No.

OF

SU

RR

EY

TW

16

5D

B

UN

ITE

DK

ING

DO

M

DR

AW

ING

No.

SC

ALE

The

conte

nts

ofth

isdra

win

g/docum

entare

Copyrightã

Expo

Technolo

gie

sLim

ited.

They

are

tobe

treate

das

confidentialand

are

retu

rnable

upon

request.

They

are

notto

be

copie

dor

com

munic

ate

din

part

or

inw

hole

withoutw

ritten

consentfr

om

Expo

Technolo

gie

sLim

ited,neither

are

they

tobe

used

inany

way

again

stour

inte

rests

.

80

D.P

.LO

FRO

MRELIE

FVALVE

1/8

"N

PT

MO

TO

R

LO

WPRESSU

RE

ALARM

/PRESSU

RIZ

ED

IND

ICATO

R(R

ED

/G

REEN

)

SYSTEM

PU

RG

ING

IND

ICATO

R

(BLACK

/YELLO

W)

4H

OLES

Ø9.5

FO

RW

ALL

MO

UN

TIN

G

PU

RG

EAIR

SU

PPLY

1/2

"N

PT

MAIN

SYSTEM

DATA

LABEL

FIT

TED

INSID

ECO

VER

PU

RG

EAIR

OU

TLET

1/2

"N

PT

FIL

TER

DRAIN

1/8

"N

PT

MO

TO

REN

CLO

SU

RE

PRESSU

RE

CO

NN

ECTIO

N

1/8

"N

PT

D.P

.H

IFRO

MRELIE

FVALVE

1/8

"N

PT

OPEN

PU

RG

EO

UTLET

SIG

NAL

TO

RELIE

FVALVE

1/8

"NPT

MO

TO

REN

CLO

SU

RE

PRESSU

RE

CO

NN

ECTIO

N

1/8

"N

PT

535

M6

x25

LO

NG

EXTERN

AL

EARTH

STU

DS

Page 25: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

MA

TE

RIA

L

DR

'WN

AP

P'D

CH

K'D

DR

AW

ING

ST

AT

US

:

AP

PR

OV

ED

:

MO

D.N

o:

DA

TE

:

ISS

UE

:

3rd

AN

GLE

PR

OJE

CT

ION

DIM

EN

SIO

NS

INm

m

DO

NO

TS

CA

LE

Exp

oT

ech

no

log

ies

Lim

ited

JO

BN

o:

FIN

ISH

TIT

LE

CU

ST

OM

ER

:S

HE

ET

No.

OF

SU

RR

EY

TW

16

5D

B

UN

ITE

DK

ING

DO

M

DR

AW

ING

No.

SC

ALE

The

conte

nts

ofth

isdra

win

g/docum

entare

Copyrightã

Expo

Technolo

gie

sLim

ited.

They

are

tobe

treate

das

confidentialand

are

retu

rnable

upon

request.

They

are

notto

be

copie

dor

com

munic

ate

din

part

or

inw

hole

withoutw

ritten

consentfr

om

Expo

Technolo

gie

sLim

ited,neither

are

they

tobe

used

inany

way

again

stour

inte

rests

.

VIE

WO

FFRO

NT

OF

UN

ITW

ITH

DO

OR

REM

OVED

TO

SH

OW

INTERN

AL

LAYO

UT

SCRAP

VIE

WW

ITH

DO

OR

FIT

TED

TO

SH

OW

IND

ICATO

RS

NO

TES

CERTIF

ICATIO

NLABEL

FIT

TED

INSID

ED

OO

RO

FSYSTEM

EN

CLO

SU

RE.

MAIN

AIR

SU

PPLY

FIL

TER/R

EG

ULATO

R

FLO

WRESTRIC

TO

R(C

LAPS

SEN

SO

RSU

PPLY)

SYSTEM

PU

RG

ING

SW

ITCH

,250V

4A,

SPN

OEx

dII

(OPTIO

NAL)

27

22

24

25

26

23

21

20

19

17

GAU

GE,

MAIN

AIR

SU

PPLY

GAU

GE,

LO

GIC

AIR

SU

PPLY

LO

GIC

AIR

SU

PPLY

REG

ULATO

R

CLAPS

SEN

SO

R

MO

TO

RIN

TERLO

CK

SW

ITCH

,250V

4A,

DPN

OEx

dII

LEAKAG

ECO

MPEN

SATIO

N,

CLAPS

VALVE

INTERM

ED

IATE

PRESSU

RE

SEN

SO

R

MIN

IPU

RG

ED

OU

BLE

IND

ICATO

RLABEL

IND

ICATO

R,

ALARM

/PRESSU

RIZ

ED

ALARM

/PRESSU

RIZ

ED

SW

ITCH

,250V

4A,

SPN

OEx

dII

PU

RG

EO

UTLET

OPEN

SIG

NAL

VALVE

(1)

PU

RG

ECO

MPLETE

BO

OST

VALVE

12

14

16

15

13

11

10983 5 7641 2

REF

IND

ICATO

R,

SYSTEM

PU

RG

ING

PU

RG

EFLO

WSEN

SO

R

LO

GIC

MAN

IFO

LD

MIN

IMU

MPRESSU

RE

SEN

SO

R

ELECTRO

NIC

PU

RG

ETIM

ER

PU

RG

EFLO

WRESTRIC

TO

R

PU

RG

EVALVE

DESCRIP

TIO

N

-28

15

26

24

23

22

21

20

14

13

12

18

19

11

10

98

7

462

16

25

1

SCRAP

VIE

WO

FD

OO

RFRO

MIN

SID

E

27

35

TIM

ER

SELECTO

RSW

ITCH

ES

18

TERM

INAL

BO

X,

Ex

eII

T100°C

(Tam

b-2

0°C

-55°C)

IP64

I.S

BATTERY

PACK

29

PU

RG

ECO

MPLETE

VALVE

29

TIM

ER

VALVE

30

30

STAIN

LESS

STEEL

VIS

IWIN

KPRO

TECTO

R31

31

PU

RG

EO

UTLET

OPEN

SIG

NAL

VALVE

(2)

INTERM

ED

IATE

PRESSU

RE

SW

ITCH

,250V

4A,

SPN

OEx

dII

17

Page 26: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

RE

LIE

FV

ALV

EU

NIT

Air

inle

t

PU

RG

EO

UT

LET

VA

LVE

open

sign

al

Mea

surin

gpo

intf

orflo

wof

purg

eai

r

Air

outle

t

MO

TO

RC

OO

LER

MO

TO

R

Mea

surin

gpo

intf

orm

inim

umpr

essu

re

MIN

IPU

RG

E

PU

RG

EA

IRD

IST

RIB

UT

ION

AS

RE

QU

IRE

D

FLA

TN

ES

ST

OB

ELE

SS

TH

AN

0.4

mm

OV

ER

AN

Y100m

mLE

NG

TH

UN

SP

EC

IFIE

D

TO

LE

RA

NC

ES

MA

TE

RIA

L

DR

'WN

AP

P'D

CH

K'D

DR

AW

ING

ST

AT

US

:

AP

PR

OV

ED

:

MO

D.N

o:

DA

TE

:

ISS

UE

:

3rd

AN

GLE

PR

OJE

CT

ION

DIM

EN

SIO

NS

INm

m

DO

NO

TS

CA

LE

Exp

oT

ech

no

log

ies

Lim

ited

JO

BN

o:

FIN

ISH

TIT

LE

CU

ST

OM

ER

:S

HE

ET

No.

OF

SU

RR

EY

TW

16

5D

B

UN

ITE

DK

ING

DO

M

DR

AW

ING

No.

SC

ALE

The

conte

nts

ofth

isdra

win

g/docum

entare

Copyrightã

Expo

Technolo

gie

sLim

ited.

They

are

tobe

treate

das

confidentialand

are

retu

rnable

upon

request.

They

are

notto

be

copie

dor

com

munic

ate

din

part

or

inw

hole

withoutw

ritten

consentfr

om

Expo

Technolo

gie

sLim

ited,neither

are

they

tobe

used

inany

way

again

stour

inte

rests

.

NO

DE

CP

LA

CE

±0.5

1D

EC

PLA

CE

±0.2

2D

EC

PLA

CE

±0.1

PO

WE

RIN

TE

RLO

CK

cont

acts

INT

ER

ME

DIA

TE

PR

ES

SU

RE

cont

acts

ALA

RM

/PR

ES

SU

RIZ

ED

cont

acts

RE

FE

RT

O

CIR

CU

ITD

IAG

RA

M

SY

ST

EM

PU

RG

ING

cont

acts

(OP

TIO

NA

L)

Ens

ure

outle

tis

noto

bstr

ucte

d

BO

OS

TA

IR

CO

NT

RO

L

UN

IT

HIG

HP

RE

SS

UR

Eco

ntac

ts(O

PT

ION

AL)

Page 27: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

SU

PPLY

4-8

barg

INSTRU

MEN

T

AIR

/IN

ERT

GAS

1/2

"N

PT

H H

MO

TO

REN

CLO

SU

RE

1/2

"[1

2m

m]

I.D

.M

INIM

UM

PU

RG

EO

UTLET

VALVE

OPEN

CO

NTRO

LSIG

NAL

1/2

"[1

2m

m]

I.D

.RECO

MM

EN

DED

MIN

IMU

MSIZ

EFO

RPU

RG

EAIR

DIS

TRIB

UTIO

NPIP

EW

ORK

AU

TO

MATIC

LEAKAG

ECO

MPEN

SATIO

NVALVE

MAN

UALLY

SET

PU

RG

EFLO

WCO

NTRO

LVALVE

1/8

"N

PT

MIN

IPU

RG

ECO

NTRO

LLO

GIC

XC

1/4

"[6

mm

]I.

D.

1/8

"N

PT

MO

TO

RIN

TERLO

CK

ALARM

/PRESSU

RIZ

ED

RELIE

FVALVE

ASSEM

BLY

XIPAL

PI

PU

RG

ING

/PU

RG

ECO

MPLETE

LO

WPRESSU

RE

ALARM

MIN

IPU

RG

ESYSTEM

EN

CLO

SU

RE

1/8

"N

PT

1/4

"[6

mm

]I.

D.

D.P

.H

IFRO

MRELIE

FVALVE

1/8

"N

PT

1/8

"N

PT

TEST

PO

INT

NO

RM

ALLY

PLU

GG

ED

1/2

"N

PT

ELECTRIC

AL

SIG

NAL

VIA

Ex

eJU

NCTIO

NBO

X

OPTIO

NAL

1/8

"N

PT

D.P

.LO

FRO

MRELIE

FVALVE

1/4

"[6

mm

]I.

D.

1/8

"N

PT

SYSTEM

PU

RG

ING

(OPTIO

NAL)

INTERM

ED

IATE

PRESSU

RE

ALARM

1/8

"N

PT

PRIM

ARY

EN

CLO

SU

RE

PRESSU

RE

1/4

"[6

mm

]I.

D.

FLA

TN

ES

ST

OB

ELE

SS

TH

AN

0.4

mm

OV

ER

AN

Y100m

mLE

NG

TH

UN

SP

EC

IFIE

D

TO

LE

RA

NC

ES

MA

TE

RIA

L

DR

'WN

AP

P'D

CH

K'D

DR

AW

ING

ST

AT

US

:

AP

PR

OV

ED

:

MO

D.N

o:

DA

TE

:

ISS

UE

:

3rd

AN

GLE

PR

OJE

CT

ION

DIM

EN

SIO

NS

INm

m

DO

NO

TS

CA

LE

Exp

oT

ech

no

log

ies

Lim

ited

JO

BN

o:

FIN

ISH

TIT

LE

CU

ST

OM

ER

:S

HE

ET

No.

OF

SU

RR

EY

TW

16

5D

B

UN

ITE

DK

ING

DO

M

DR

AW

ING

No.

SC

ALE

The

conte

nts

ofth

isdra

win

g/docum

entare

Copyrightã

Expo

Technolo

gie

sLim

ited.

They

are

tobe

treate

das

confidentialand

are

retu

rnable

upon

request.

They

are

notto

be

copie

dor

com

munic

ate

din

part

or

inw

hole

withoutw

ritten

consentfr

om

Expo

Technolo

gie

sLim

ited,neither

are

they

tobe

used

inany

way

again

stour

inte

rests

.

NO

DE

CP

LA

CE

±0.5

1D

EC

PLA

CE

±0.2

2D

EC

PLA

CE

±0.1

Page 28: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

FLA

TN

ES

ST

OB

ELE

SS

TH

AN

0.4

mm

OV

ER

AN

Y100m

mLE

NG

TH

UN

SP

EC

IFIE

D

TO

LE

RA

NC

ES

MA

TE

RIA

L

DR

'WN

AP

P'D

CH

K'D

DR

AW

ING

ST

AT

US

:

AP

PR

OV

ED

:

MO

D.N

o:

DA

TE

:

ISS

UE

:

3rd

AN

GLE

PR

OJE

CT

ION

DIM

EN

SIO

NS

INm

m

DO

NO

TS

CA

LE

Exp

oT

ech

no

log

ies

Lim

ited

JO

BN

o:

FIN

ISH

TIT

LE

CU

ST

OM

ER

:S

HE

ET

No.

OF

SU

RR

EY

TW

16

5D

B

UN

ITE

DK

ING

DO

M

DR

AW

ING

No.

SC

ALE

The

conte

nts

ofth

isdra

win

g/docum

entare

Copyrightã

Expo

Technolo

gie

sLim

ited.

They

are

tobe

treate

das

confidentialand

are

retu

rnable

upon

request.

They

are

notto

be

copie

dor

com

munic

ate

din

part

or

inw

hole

withoutw

ritten

consentfr

om

Expo

Technolo

gie

sLim

ited,neither

are

they

tobe

used

inany

way

again

stour

inte

rests

.

NO

DE

CP

LA

CE

±0.5

1D

EC

PLA

CE

±0.2

2D

EC

PLA

CE

±0.1

Page 29: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

NO

TES

REFER

TO

CERTIF

ICATES

IECEx

10.0

003X

AN

DIT

S10ATEX37092X

FO

RRESTRIC

TIO

NS

AN

DPERM

ITTED

CO

NTEN

TS

FLA

TN

ES

ST

OB

ELE

SS

TH

AN

0.4

mm

OV

ER

AN

Y100m

mLE

NG

TH

UN

SP

EC

IFIE

D

TO

LE

RA

NC

ES

MA

TE

RIA

L

DR

'WN

AP

P'D

CH

K'D

DR

AW

ING

ST

AT

US

:

AP

PR

OV

ED

:

MO

D.N

o:

DA

TE

:

ISS

UE

:

3rd

AN

GLE

PR

OJE

CT

ION

DIM

EN

SIO

NS

INm

m

DO

NO

TS

CA

LE

Exp

oT

ech

no

log

ies

Lim

ited

JO

BN

o:

FIN

ISH

TIT

LE

CU

ST

OM

ER

:S

HE

ET

No.

OF

SU

RR

EY

TW

16

5D

B

UN

ITE

DK

ING

DO

M

DR

AW

ING

No.

SC

ALE

The

conte

nts

ofth

isdra

win

g/docum

entare

Copyrightã

Expo

Technolo

gie

sLim

ited.

They

are

tobe

treate

das

confidentialand

are

retu

rnable

upon

request.

They

are

notto

be

copie

dor

com

munic

ate

din

part

or

inw

hole

withoutw

ritten

consentfr

om

Expo

Technolo

gie

sLim

ited,neither

are

they

tobe

used

inany

way

again

stour

inte

rests

.

NO

DE

CP

LA

CE

±0.5

1D

EC

PLA

CE

±0.2

2D

EC

PLA

CE

±0.1

ALARM

/PRESSU

RIS

ED

CO

NTACTS

BLACK

101

MO

TO

RIN

TERLO

CK

CO

NTACTS

BROWN

103

GREY

102

108

107

BLACK

BLUE

110

GREY

109

BROWN

INTERM

ED

IATE

PRESSU

RE

SW

ITCH

BLACK

BROWN

GREY

BLACK

BROWN

GREY

104

105

106

111

112

113

PN

EU

MATIC

TIM

ER

XBR-7

TD

0-0

60

CIR

CU

ITD

IAG

RAM

VERSIO

N

(OPTIO

NAL)

SYSTEM

PU

RG

ING

CO

NTACTS

ELECTRO

NIC

TIM

ER

XBR-7

TD

0-0

71

Page 30: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

FLA

TNE

SS T

O B

E LE

SS

THAN

0.4

mm

OVE

R A

NY

100m

m L

ENG

TH

UN

SPE

CIF

IED

TOLE

RAN

CES

MA

TER

IAL

DR'W

N

APP'

D

CHK'

D

DR

AWIN

G S

TATU

S:A

PPR

OVE

D:

MO

D. N

o:D

ATE

:

ISSU

E:

3rd

ANG

LEP

RO

JEC

TIO

ND

IMEN

SIO

NS

IN m

m

DO

NO

T SC

ALE

Expo

Tec

hnol

ogie

s Li

mite

d

JOB

No:

FIN

ISH

TITL

E

CU

STO

MER

:S

HEE

T N

o.O

F

SU

RR

EY

KT7

0R

HU

NIT

ED

KIN

GD

OM

DR

AWIN

G N

o.

SC

ALE

The

cont

ents

of t

his

draw

ing

/ doc

umen

t are

Cop

yrig

ht �

Exp

o Te

chno

logi

es L

imite

d. T

hey

are

to b

e tre

ated

as

conf

iden

tial a

nd a

re re

turn

able

upon

requ

est.

The

y ar

e no

t to

be c

opie

d or

com

mun

icat

ed in

par

t or i

n w

hole

with

out w

ritte

n co

nsen

t fro

m E

xpo

Tech

nolo

gies

Lim

ited,

nei

ther

are

they

to b

e us

ed in

any

way

aga

inst

our

inte

rest

s.

NO

DEC

PLA

CE

±0.

51

DE

C P

LAC

E ±0

.22

DE

C P

LAC

E ±0

.1

MA

NU

AL O

VE

RR

IDE

SW

ITC

H S

UPP

LIED

LO

OS

E.

GLA

ND

PLA

TE IN

PU

RG

E S

YSTE

M IS

UN

DR

ILLE

D.

CA

BLE

GLA

ND

S A

RE

NO

T S

UPP

LIE

D.

* TE

RM

INA

L N

UM

BE

R A

CC

OR

DIN

G T

O M

OTO

R S

YS

TEM

Page 31: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive
Page 32: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

Sira

Cer

tific

atio

n Se

rvic

e R

ake

Lan

e,

Eccle

sto

n, C

he

ste

r, C

H4

9JN

, E

ngla

nd

Te

l:+

44 (

0)

12

44

670

90

0

Fax:

+4

4 (

0)

12

44

681

33

0

Em

ail:

info

@sira

cert

ific

ation

.co

mW

eb:

ww

w.s

ira

cert

ific

ation

.co

m

CE

RT

IF

IC

AT

IO

N

Proj

ect

Num

ber

7000

4712

C El

laby

D

eput

y Ce

rtifi

catio

n M

anag

er

This

cer

tific

ate

and

its s

ched

ules

may

onl

y be

re

prod

uced

in it

s en

tiret

y an

d w

ithou

t ch

ange

.

Page

1 o

f 6

Form

9400

Iss

ue 1

1EC

TY

PE-

EXA

MIN

ATI

ON

CER

TIFI

CA

TE2

Equi

pmen

t in

tend

edfo

rus

e in

Pot

entia

lly E

xplo

sive

Atm

osph

eres

Dire

ctiv

e94

/9/E

C

3Ce

rtifi

cate

Num

ber:

Sir

a 99

ATE

X31

73X

Issu

e:11

4Eq

uipm

ent:

BP

G R

ang

e o

f Ju

ncti

on

Box

es

5Ap

plic

ant:

AB

TEC

HLi

mit

ed

6Ad

dres

s:Sa

nder

son

Stre

etLo

wer

Don

Val

ley

Shef

field

S92U

AU

K

7Th

iseq

uipm

ent

and

any

acce

ptab

leva

riatio

nth

eret

ois

spec

ified

inth

esc

hedu

leto

this

cert

ifica

tean

dth

e do

cum

ents

the

rein

ref

erre

d to

.

8Si

raCe

rtifi

catio

nSe

rvic

e,no

tifie

dbo

dynu

mbe

r05

18in

acco

rdan

cew

ithAr

ticle

9of

Dire

ctiv

e94

/9/E

Cof

23M

arch

1994

,cer

tifie

sth

atth

is e

quip

men

t ha

s be

enfo

und

to c

ompl

y w

ith t

he E

ssen

tial H

ealth

and

Safe

tyRe

quire

men

tsre

latin

gto

the

desi

gnan

dco

nstr

uctio

nof

equi

pmen

tin

tend

edfo

rus

ein

pote

ntia

lly e

xplo

sive

atm

osph

eres

giv

en in

Ann

ex I

I to

the

Dire

ctiv

e.

The

exam

inat

ion

and

test

res

ults

are

rec

orde

d in

the

con

fiden

tial r

epor

ts li

sted

inSe

ctio

n14

.2.

9Co

mpl

ianc

ew

ithth

eEs

sent

ial

Hea

lthan

dSa

fety

Requ

irem

ents

,w

ithth

eex

cept

ion

ofth

ose

liste

din

the

sche

dule

to

this

cer

tific

ate,

has

bee

n as

sure

d by

com

plia

nce

with

the

fol

low

ing

docu

men

ts:

EN 6

0079

-0:2

012

EN 6

0079

-7:2

007

EN 6

0079

-11:

2012

EN

600

79-2

6:20

07

EN 6

0079

-31:

2009

The

abov

elis

tof

docu

men

tsm

ayde

tail

stan

dard

sth

atdo

not

appe

aron

the

UKA

SSc

ope

ofAc

cred

itatio

n,bu

tha

vebe

enad

ded

thro

ugh

Sira

’s fl

exib

le s

cope

of a

ccre

dita

tion,

whi

ch is

ava

ilabl

e on

req

uest

.

10If

the

sign

‘X’i

spl

aced

afte

rth

ece

rtifi

cate

num

ber,

itin

dica

tes

that

the

equi

pmen

tis

subj

ect

tosp

ecia

lco

nditi

ons

for

safe

use

spec

ified

in t

he s

ched

ule

to t

his

cert

ifica

te.

11Th

isEC

type

-exa

min

atio

nce

rtifi

cate

rela

tes

only

toth

ede

sign

and

cons

truc

tion

ofth

esp

ecifi

edeq

uipm

ent.

Ifap

plic

able

, fu

rthe

rre

quire

men

tsof

this

Dire

ctiv

eap

ply

toth

em

anuf

actu

rean

dsu

pply

ofth

is e

quip

men

t.

12Th

e m

arki

ngof

the

equ

ipm

ent

shal

l inc

lude

the

follo

win

g:

II2

GD

orII

1G

DEx

e I

ICT6

Gb

(Ta

=-6

5°C

to+

#°C

)Ex

ia I

ICT6

Ga

(Ta

= -

65°C

to+

#°C

)Ex

e I

ICT5

Gb

(Ta

=-6

5°C

to+

#°C

)Ex

ia I

ICT5

Ga

(Ta

= -

65°C

to+

#°C

)Ex

e I

ICT4

Gb

(Ta

=-6

5°C

to+

#°C

)Ex

ia I

ICT4

Ga

(Ta

= -

65°C

to+

#°C

)Ex

ib I

IC T

6G

b(T

a=

-65°

C to

+#

°C)

Ex t

a II

ICT8

5°C

Da

(Ta

=-6

5°C

to+

#°C

Ex ib

IIC

T5

Gb

(Ta

=-6

5°C

to+

#°C

)Ex

ta

IIIC

T100

°C D

a (T

a=

-65°

C to

+#

°CEx

ib I

IC T

4G

b(T

a=

-65°

C to

+#

°C)

Ex t

b II

IC T

85°C

Db

(Ta

= -

65°C

to+

#°C

Ex t

b II

IC T

100°

CD

b(T

a =

-65

°C to

+#

°C

Sira

Cer

tific

atio

n Se

rvic

e R

ake

Lan

e,

Eccle

sto

n, C

he

ste

r, C

H4

9JN

, E

ngla

nd

Te

l:+

44 (

0)

12

44

670

90

0

Fax:

+4

4 (

0)

12

44

681

33

0

Em

ail:

info

@sira

cert

ific

ation

.co

mW

eb:

ww

w.s

ira

cert

ific

ation

.co

m

CE

RT

IF

IC

AT

IO

N

SCH

EDU

LE

EC T

YP

E-EX

AM

INA

TIO

N C

ERTI

FIC

ATE

Sir

a 99

ATE

X31

73X

Issu

e 11

This

cer

tific

ate

and

its s

ched

ules

may

onl

y be

re

prod

uced

in it

s en

tiret

y an

d w

ithou

t ch

ange

.

Page

2 o

f 6

Form

9400

Iss

ue1

13D

ESC

RIP

TIO

NO

FEQ

UIP

MEN

T

The

BPG

rang

eof

junc

tion

boxe

sut

ilise

sa

BPG

encl

osur

eco

vere

dby

cert

ifica

tenu

mbe

rSi

ra 9

9ATE

X317

2U a

nd a

refit

ted

with

an

arra

ngem

ent

of s

uita

bly

cert

ified

ter

min

als.

BPG

ref.

12

34

56

78

910

1112

1313

.5

1415

Leng

th80

110

160

190

230

122

220

160

260

360

560

255

400

400

600

400

Wid

th75

7575

7575

120

120

160

160

160

160

250

250

250

250

405

Hei

ght

5555

5555

5590

9090

9090

9012

012

016

012

012

0(A

ll di

men

sion

s ar

e in

mm

)

Befo

reth

eJu

nctio

nBo

xis

inst

alle

d,its

tota

ldis

sipa

ted

pow

erfo

rth

epa

rtic

ular

appl

icat

ion

will

beca

lcul

ated

inac

cord

ance

with

EN 6

0079

-7:2

003,

Anne

xE,

E.2

and

will

note

xcee

dth

eva

lues

give

nin

the

tabl

esbe

low

(Jun

ctio

nbo

xes

ofsi

zeno

tsp

ecifi

edin

the

tabl

esm

aybe

man

ufac

ture

dsu

bjec

tto

the

max

imum

diss

ipat

edpo

wer

bein

g ba

sed

ona

smal

ler

encl

osur

e):

EPL

Ga

Gb

Db

BPG

ref

.M

axim

um P

ower

Dis

sipa

tion

(W)

T6/T

85°C

Ta+

40°C

(max

)

T6/T

85°C

Ta+

55°C

(max

)

T6/T

85°C

Ta+

60°C

(max

)

T6/T

85°C

Ta+

65°C

(max

)

T5/T

100°

CTa

+55

°C(m

ax)

T4/T

100°

CTa

+90

°C(m

ax)

18.

390

2.23

1.73

1.45

8.39

08.

390

28.

551

2.00

1.70

1.45

8.55

18.

551

38.

833

2.00

1.70

1.45

8.83

38.

833

49.

012

2.07

1.80

1.29

9.01

29.

012

59.

260

2.00

1.70

1.10

9.26

09.

260

69.

378

2.00

1.70

1.45

9.37

89.

378

710

.500

2.30

1.70

1.10

10.5

0010

.500

810

.348

2.00

1.70

1.10

10.3

4810

.348

911

.933

2.30

1.70

1.10

11.9

3311

.933

1013

.793

4.50

3.29

2.10

13.7

9313

.793

1118

.338

6.68

5.20

4.00

18.3

3818

.338

1215

.474

2.30

1.70

1.10

15.4

7415

.474

1320

.867

5.20

4.00

3.00

20.8

6720

.867

13.5

20.8

675.

204.

003.

0020

.867

20.8

6714

30.3

847.

976.

594.

7930

.384

30.3

8415

31.3

508.

266.

004.

4031

.350

31.3

50

Page 33: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

Sira

Cer

tific

atio

n Se

rvic

eR

ake

Lan

e,

Eccle

sto

n, C

he

ste

r, C

H4

9JN

, E

ngla

Te

l:+

44 (

0)

12

44

670

90

0

Fax:

+4

4 (

0)

12

44

681

33

0

Em

ail:

info

@sira

cert

ific

ation

.co

mW

eb:

ww

w.s

ira

cert

ific

ation

.co

m

CE

RT

IF

IC

AT

IO

N

SCH

EDU

LE

EC T

YP

E-EX

AM

INA

TIO

N C

ERTI

FIC

ATE

Sir

a 99

ATE

X31

73X

Issu

e 11

This

cer

tific

ate

and

its s

ched

ules

may

onl

y be

re

prod

uced

in it

s en

tiret

y an

d w

ithou

t ch

ange

.

Page

3 o

f 6

Form

9400

Iss

ue1

EPL

Da

BPG

ref

.M

axim

um P

ower

Dis

sipa

tion

(W)

T6/T

85°C

Ta+

40°C

(max

)

T6/T

85°C

Ta+

55°C

(max

)

T6/T

85°C

Ta+

60°C

(max

)

T6/T

85°C

Ta+

65°C

(max

)

T5/T

100°

CTa

+55

°C(m

ax)

T4/T

100°

CTa

+90

°C(m

ax)

14.

195

1.11

50.

865

0.72

54.

195

4.19

52

4.27

551

0.85

0.72

54.

2755

4.27

553

4.41

651

0.85

0.72

54.

4165

4.41

654

4.50

61.

035

0.9

0.64

54.

506

4.50

65

4.63

10.

850.

554.

634.

636

4.68

91

0.85

0.72

54.

689

4.68

97

5.25

1.15

0.85

0.55

5.25

5.25

85.

174

10.

850.

555.

174

5.17

49

5.96

651.

150.

850.

555.

9665

5.96

6510

6.89

652.

251.

645

1.05

6.89

656.

8965

119.

169

3.34

2.6

29.

169

9.16

912

7.73

71.

150.

850.

557.

737

7.73

713

10.4

335

2.6

21.

510

.433

510

.433

513

.510

.433

52.

62

1.5

10.4

335

10.4

335

1415

.192

3.98

53.

295

2.39

515

.192

15.1

9215

15.6

754.

133

2.2

15.6

7515

.675

Var

iati

on 1

-Th

isva

riatio

n in

trod

uced

the

follo

win

gch

ange

s:

i.Th

eBP

Gra

nge

of ju

nctio

nbo

xes

wer

epe

rmitt

edto

have

alte

rnat

ive

pow

erdi

ssip

atio

nra

tings

that

enab

leth

emto

beus

edin

anup

per

ambi

ent

tem

pera

ture

ofei

ther

+40

°Cor

+55

°Cor

+60

°Cor

+65

°C,t

he a

ssoc

iate

d ra

tings

and

mar

king

s w

ere

reco

gnis

ed.

Var

iati

on 2

-Th

isva

riatio

n in

trod

uced

the

follo

win

gch

ange

s:

i.Th

e re

cogn

ition

of a

min

orre

visi

onof

the

info

rmat

ion

mar

ked

on t

he la

bel.

Var

iati

on3

-Th

is v

aria

tion

intr

oduc

edth

e fo

llow

ing

chan

ges:

i.W

hen

cert

ified

,int

rinsi

cally

safe

term

inal

s ar

eus

ed,a

ltern

ativ

e m

arki

ng, ‘

ia’ a

nd ‘i

b’, w

as r

ecog

nise

d.

Var

iati

on 4

-Th

isva

riatio

n in

trod

uced

the

follo

win

gch

ange

s:

i.Th

eBP

G13

.5ju

nctio

nbo

xco

vere

dby

cert

ifica

tenu

mbe

rSi

ra99

ATEX

3172

Uw

asad

ded

toth

era

nge.

Var

iati

on 5

-Th

isva

riatio

n in

trod

uced

the

follo

win

gch

ange

s:

i.Th

e op

tion

tofit

slo

tted

tru

nkin

g in

side

the

Jun

ctio

n Bo

xes,

thi

s tr

unki

ng m

ay b

esi

ted

as r

equi

red.

Th

ein

stru

ctio

ns w

ere

mod

ified

to

reco

gnis

e ad

ditio

nal r

estr

ictio

ns a

ssoc

iate

d w

ithth

isch

ange

and

a

new

Con

ditio

n of

Man

ufac

ture

was

intr

oduc

ed.

ii.Th

e re

cogn

ition

of m

inor

dra

win

g m

odifi

catio

nsin

clud

ing

the

intr

oduc

tion

of a

new

com

pany

logo

;th

ese

amen

dmen

ts a

re a

dmin

istr

ativ

e or

invo

lve

chan

ges

to t

he d

esig

n th

at d

o no

t af

fect

the

aspe

cts

of t

he p

rodu

ct t

hat

are

rele

vant

to

expl

osio

n sa

fety

.

Sira

Cer

tific

atio

n Se

rvic

e R

ake

Lan

e,

Eccle

sto

n, C

he

ste

r, C

H4

9JN

, E

ngla

nd

Te

l:+

44 (

0)

12

44

670

90

0

Fax:

+4

4 (

0)

12

44

681

33

0

Em

ail:

info

@sira

cert

ific

ation

.co

mW

eb:

ww

w.s

ira

cert

ific

ation

.co

m

CE

RT

IF

IC

AT

IO

N

SCH

EDU

LE

EC T

YP

E-EX

AM

INA

TIO

N C

ERTI

FIC

ATE

Sir

a 99

ATE

X31

73X

Issu

e 11

This

cer

tific

ate

and

its s

ched

ules

may

onl

y be

re

prod

uced

in it

s en

tiret

y an

d w

ithou

t ch

ange

.

Page

4 o

f 6

Form

9400

Iss

ue1

Var

iati

on 6

-Th

isva

riatio

n in

trod

uced

the

follo

win

gch

ange

s:

i.Fo

llow

ing

appr

opria

tere

-ass

essm

ent

tode

mon

stra

teco

mpl

ianc

ew

ithth

ere

quire

men

tsof

the

EN60

079

serie

sof

stan

dard

s,th

edo

cum

ents

prev

ious

lylis

ted

inse

ctio

n9,

EN50

014:

1997

(am

endm

ents

A1to

A2),

EN50

019:

1994

,EN

5002

0:20

02an

dEN

5028

1-1-

1:19

98,w

ere

repl

aced

byth

ose

curr

ently

liste

d.As

part

ofth

isch

ange

,th

em

arki

ngs

inse

ctio

n12

wer

eup

date

dac

cord

ingl

yan

dth

e‘ia

’m

arki

ngpr

evio

usly

incl

uded

asVa

riatio

n1

(dat

ed30

Mar

ch20

05)

was

rem

oved

.ii.

The

Cond

ition

ofCe

rtifi

catio

nth

atde

fined

the

ambi

ent

tem

pera

ture

rang

eof

spec

ific

type

sof

gask

ets

was

rem

oved

beca

use

only

silic

one

rubb

erga

sket

sar

eno

wus

edin

the

cons

truc

tion

ofth

ese

Junc

tion

Boxe

s.iii

.It

was

reco

gnis

edth

ata

new

proc

edur

efo

rse

lect

ing

term

inal

sha

sbe

enad

opte

dby

the

man

ufac

ture

r;th

isal

low

sth

ete

rmin

als

tobe

chos

enfr

oman

Appr

oved

Com

pone

ntD

ocum

ent,

Sira

12AC

087,

that

isis

sued

and

cont

rolle

dby

Sira

.Th

ere

leva

ntCo

nditi

onof

Cert

ifica

tion

was

amen

ded

to r

ecog

nise

thi

sch

ange

.iv

.Th

ere

cogn

ition

ofdr

awin

gm

odifi

catio

nsre

quire

dfo

rus

ew

ithot

her

cert

ifica

tion

asso

ciat

edw

ithth

ese

prod

ucts

.v.

The

Cond

ition

of

Cert

ifica

tion

deal

ing

with

pow

er d

issi

patio

n w

as m

odifi

ed.

vi.

ACo

nditi

onof

Cert

ifica

tion

that

requ

ires

the

man

ufac

ture

rto

mon

itor

the

stat

usof

prev

ious

lyce

rtifi

ed d

evic

es w

as a

dded

.

Var

iati

on 7

-Th

isva

riatio

n in

trod

uced

the

follo

win

gch

ange

s:

R30

711A

/00

i.U

sing

EN60

079-

26,

the

junc

tion

boxe

sw

ere

allo

wed

tobe

mar

ked

with

‘Ex

ia’

and

‘Ex

ta’

conc

epts

for

EPL

leve

lsG

aan

dD

a,as

are

sult

ofth

isch

ange

,th

em

axim

umpo

wer

diss

ipat

ion

tabl

ew

asm

odifi

edan

da

Spec

ialC

ondi

tion

for

Safe

Use

was

intr

oduc

edne

cess

itatin

gth

ead

ditio

nof

an

‘X’ s

uffix

to

the

cert

ifica

te n

umbe

r.ii.

IEC

6007

9-0:

2011

was

rep

lace

d by

EN

6007

9-0:

2012

in t

he li

st o

f st

anda

rds.

R32

242A

/00

i.Th

eBP

Gra

nge

ofju

nctio

nbo

xes

wer

eal

low

edto

beus

edin

anup

per

ambi

ent

+55

°Cw

itha

tem

pera

ture

clas

s/su

rfac

ete

mpe

ratu

reof

T5/T

100°

C,th

eas

soci

ated

max

imum

pow

erdi

ssip

atio

nra

tings

(W

) an

d m

arki

ngs

wer

e re

cogn

ised

.

Var

iati

on 8

-Th

isva

riatio

n in

trod

uced

the

follo

win

gch

ange

s:

i.To

perm

itth

ere

plac

emen

tof

the

term

‘cer

amic

’w

ith‘th

ete

rmin

als

shal

lha

vean

insu

latio

nlim

iting

tem

pera

ture

of

130°

Cm

inim

um’i

nth

eCo

nditi

on o

fM

anuf

actu

re,

whe

n th

e ju

nctio

n bo

xes

are

mar

ked

for

T4/1

00°C

.

14D

ESC

RIP

TIV

E D

OC

UM

EN

TS

14.1

Dra

win

gs

Refe

r to

Cer

tific

ate

Anne

xe.

Page 34: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

Sira

Cer

tific

atio

n Se

rvic

eR

ake

Lan

e,

Eccle

sto

n, C

he

ste

r, C

H4

9JN

, E

ngla

Te

l:+

44 (

0)

12

44

670

90

0

Fax:

+4

4 (

0)

12

44

681

33

0

Em

ail:

info

@sira

cert

ific

ation

.co

mW

eb:

ww

w.s

ira

cert

ific

ation

.co

m

CE

RT

IF

IC

AT

IO

N

SCH

EDU

LE

EC T

YP

E-EX

AM

INA

TIO

N C

ERTI

FIC

ATE

Sir

a 99

ATE

X31

73X

Issu

e 11

This

cer

tific

ate

and

its s

ched

ules

may

onl

y be

re

prod

uced

in it

s en

tiret

y an

d w

ithou

t ch

ange

.

Page

5 o

f 6

Form

9400

Iss

ue1

14.2

Ass

ocia

ted

Sir

aR

epo

rts

and

Cer

tifi

cate

His

tory

Issu

eD

ate

Repo

rt/F

ile n

o.Co

mm

ent

019

Jan

uary

2000

R51X

6055

ETh

e re

leas

e of

the

prim

e ce

rtifi

cate

.1

25 M

ay20

01R5

1A67

46A

The

intr

oduc

tion

of V

aria

tion

1.2

28 S

epte

mbe

r20

0153

V793

6Th

ein

trod

uctio

nof

Var

iatio

n 2.

323

Jul

y20

02R5

3A90

09A

The

prim

ece

rtifi

cate

was

re-is

sued

tope

rmit

the

follo

win

g:•

The

inco

rpor

atio

nof

pre

viou

s va

riatio

ns 1

and

2.

•Th

e lo

wer

am

bien

t te

mpe

ratu

re r

ange

was

con

firm

edas

–65

°C.

•Th

ein

trod

uctio

nof

the

chan

ges

incl

uded

in S

ira r

epor

tnu

mbe

r R5

3A90

09A.

430

Mar

ch20

05R5

3V10

438A

The

intr

oduc

tion

of V

aria

tion

3.5

10 M

arch

2008

R51A

1788

1ATh

isIs

sue

cove

rs t

he f

ollo

win

gch

ange

s:•

All p

revi

ousl

y is

sued

cer

tific

atio

n w

as r

atio

nalis

ed in

to

a si

ngle

cer

tific

ate,

Iss

ue 5

, Iss

ues

0 to

4 r

efer

ence

dab

ove

are

only

inte

nded

to

refle

ct t

he h

isto

ryof

the

prev

ious

cert

ifica

tion

and

have

not

bee

n is

sued

as

docu

men

ts in

thi

sfo

rmat

.•

The

chan

geof

the

App

lican

t’s n

ame,

firs

t re

cogn

ised

31 J

anua

ry20

07, w

as r

e-co

nfirm

ed.

•Th

ein

trod

uctio

nof

Var

iatio

n 4.

603

Apr

il20

12R2

6585

A/00

The

intr

oduc

tion

of V

aria

tion

5.7

11 J

une

2012

R265

85A/

01Re

port

R26

585A

/01

repl

aced

rep

ort

R26

585A

/00.

824

Oct

ober

2012

R251

64A/

00Th

isIs

sue

cove

rs t

he f

ollo

win

gch

ange

s:•

The

intr

oduc

tion

of V

aria

tion

6.•

Beca

use

this

cert

ifica

te w

as r

e-is

sued

,som

eVa

riatio

ns 1

and

2 w

ere

dupl

icat

ed, t

his

has

been

cl

arifi

ed a

nd r

efle

cted

in t

he c

ertif

icat

e hi

stor

y; n

o te

chni

cal c

hang

es w

ere

invo

lved

.9

07 A

pril

2014

R307

11A/

00R3

2242

A/00

The

intr

oduc

tion

of V

aria

tion

7.

1008

Jul

y20

14R7

0004

712A

The

intr

oduc

tion

of V

aria

tion

8.11

30 J

uly

2014

N/A

Issu

ed t

oco

rrec

t a

typo

grap

hica

l err

or.

15S

PEC

IAL

CO

ND

ITIO

NS

FO

R S

AFE

US

E (d

enot

ed b

y X

afte

r th

e ce

rtifi

cate

num

ber)

15.1

Whe

nus

edin

anEP

Lta

(Da)

appl

icat

ion

the

pow

ersu

pply

toth

eeq

uipm

ent

isto

bera

ted

for

apr

ospe

ctiv

esh

ort

circ

uit

curr

ent

ofno

t m

ore

than

10kA

.

16ES

SEN

TIA

LH

EALT

H A

ND

SA

FETY

REQ

UIR

EMEN

TS O

F A

NN

EXII

(EH

SRs)

The

rele

vant

EHSR

sth

atar

eno

tad

dres

sed

byth

est

anda

rds

liste

din

this

cert

ifica

teha

vebe

enid

entif

ied

and

indi

vidu

ally

asse

ssed

in t

he r

epor

ts li

sted

in S

ectio

n14

.2.

Sira

Cer

tific

atio

n Se

rvic

e R

ake

Lan

e,

Eccle

sto

n, C

he

ste

r, C

H4

9JN

, E

ngla

nd

Te

l:+

44 (

0)

12

44

670

90

0

Fax:

+4

4 (

0)

12

44

681

33

0

Em

ail:

info

@sira

cert

ific

ation

.co

mW

eb:

ww

w.s

ira

cert

ific

ation

.co

m

CE

RT

IF

IC

AT

IO

N

SCH

EDU

LE

EC T

YP

E-EX

AM

INA

TIO

N C

ERTI

FIC

ATE

Sir

a 99

ATE

X31

73X

Issu

e 11

This

cer

tific

ate

and

its s

ched

ules

may

onl

y be

re

prod

uced

in it

s en

tiret

y an

d w

ithou

t ch

ange

.

Page

6 o

f 6

Form

9400

Iss

ue1

17C

ON

DIT

ION

SO

FC

ERTI

FIC

AT

ION

17.1

The

use

of t

his

cert

ifica

te is

sub

ject

to

the

Reg

ulat

ions

Appl

icab

le t

o H

olde

rsof

Sira

Cer

tific

ates

.

17.2

Hol

ders

ofEC

type

-exa

min

atio

nce

rtifi

cate

sar

ere

quire

dto

com

ply

with

the

prod

uctio

nco

ntro

lre

quire

men

ts d

efin

ed in

Art

icle

8 o

f di

rect

ive

94/9

/EC.

17.3

Whe

nth

em

anuf

actu

rer

has

equi

pped

the

junc

tion

boxe

sw

ithte

rmin

als,

aro

utin

eel

ectr

icst

reng

thte

stsh

allb

eca

rrie

dou

ton

lyif

the

com

pone

nts

are

wire

d.Th

iste

stsh

allb

eca

rrie

dou

tac

cord

ing

toth

efo

llow

ing

stan

dard

s:

- in

dust

rial c

ontr

ol e

quip

men

t: E

N60

947

- m

easu

rem

ent,

con

trol

and

labo

rato

ry u

se:

EN61

010

17.4

The

term

inal

sus

edin

thes

eJu

nctio

nBo

xes

will

beAT

EXap

prov

edde

vice

sch

osen

from

the

Appr

oved

Com

pone

ntD

ocum

ent

num

ber

Sira

12AC

087

that

isis

sued

bySi

ra.

All

term

inal

sw

illbe

inst

alle

din

acco

rdan

cew

ithth

eir

cert

ifica

teco

nditi

ons

and

the

rele

vant

code

sof

pra

ctic

e/w

iring

regu

latio

nspa

ying

part

icul

ar a

tten

tion

to t

hefo

llow

ing:

•Th

e m

axim

um s

ervi

ce t

empe

ratu

re r

ange

. •

The

min

imum

cree

page

and

cle

aran

ce d

ista

nces

sha

llbe

mai

ntai

ned.

•Th

e ra

ted

volta

ges

and

curr

ents

may

var

y if

cros

s-co

nnec

tion

faci

litie

s ar

e us

ed.

•Th

e re

duct

ion

in r

atin

gof

adja

cent

ter

min

als

shal

l be

obse

rved

, whe

re a

pplic

able

.

The

term

inal

sfit

ted

into

the

junc

tion

boxe

ssh

all a

lso

conf

orm

to

the

follo

win

g re

quire

men

ts:

Tem

pera

ture

cla

ss/

Dus

t m

arki

ngRe

quire

men

t

T6/T

85°C

The

term

inal

ssh

all h

ave

an in

sula

tion

limiti

ng t

empe

ratu

re o

f10

0°C

min

imum

T4/T

100°

CTh

e te

rmin

als

shal

l hav

e an

insu

latio

n lim

iting

tem

pera

ture

of

130°

C m

inim

um

17.5

Suita

bly

cert

ified

Exe

equi

pmen

tsu

chas

brea

thin

gde

vice

san

dbl

anks

may

befit

ted

toth

een

clos

ure

prov

idin

g th

e en

clos

ure

mai

ntai

ns c

ompl

ianc

e w

ith B

SEN

605

29co

de I

P64

or b

ette

r.

17.6

The

man

ufac

ture

rw

illta

keal

lrea

sona

ble

step

sto

ensu

reth

atth

epo

wer

diss

ipat

edby

the

Junc

tion

Box

does

not

exce

edth

em

axim

umva

lue

stip

ulat

edin

the

tabl

ede

taile

din

the

Des

crip

tion

ofEq

uipm

ent,

inad

ditio

n,th

em

anuf

actu

rer

will

supp

lyal

lth

ere

leva

ntin

form

atio

nth

atw

illen

able

the

user

/inst

alle

rto

calc

ulat

eth

e di

ssip

ated

pow

erin

Wat

ts fo

r eac

hJu

nctio

n Bo

x in

acco

rdan

cew

ithEN

600

79-7

Anne

xE,

E2.

17.7

Whe

nth

eju

nctio

nbo

xes

are

used

for

intr

insi

cally

safe

appl

icat

ions

,a

3m

mse

para

tion

dist

ance

betw

een

the

encl

osur

eis

requ

ired,

ther

esh

all

also

bea

min

imum

of6

mm

betw

een

diff

eren

tin

trin

sica

lly s

afe

circ

uits

.

17.8

Whe

n tr

unki

ngis

fitt

ed, i

tm

ay b

e si

ted

as r

equi

red

and

the

min

imum

cree

page

and

clea

ranc

e di

stan

ces

shal

l stil

l be

met

.

17.9

The

prod

ucts

cove

red

byth

isce

rtifi

cate

inco

rpor

ate

prev

ious

lyce

rtifi

edde

vice

s,it

isth

eref

ore

the

resp

onsi

bilit

yof

the

man

ufac

ture

rto

cont

inua

llym

onito

rth

est

atus

ofth

ece

rtifi

catio

nas

soci

ated

with

thes

ede

vice

s,an

dth

em

anuf

actu

rer

will

info

rmSi

raof

any

mod

ifica

tions

ofth

ede

vice

sth

atm

ayim

ping

e up

on t

he e

xplo

sion

saf

ety

desi

gn o

f th

eir

prod

ucts

.

Page 35: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

Sira

Cer

tific

atio

n Se

rvic

e R

ake

Lan

e,

Eccle

sto

n, C

he

ste

r, C

H4

9JN

, E

ngla

nd

Te

l:+

44 (

0)

12

44

670

90

0

Fax:

+4

4 (

0)

12

44

681

33

0

Em

ail:

info

@sira

cert

ific

ation

.co

mW

eb:

ww

w.s

ira

cert

ific

ation

.co

m

CE

RT

IF

IC

AT

IO

N

Cer

tifi

cate

An

nexe

Cer

tifi

cate

Num

ber

:S

ira

99A

TEX

3173

X

Equi

pmen

t:B

PG

Ran

ge

of

Junc

tio

nB

oxes

App

lican

t:A

BTE

CH

Lim

ited

This

cer

tific

ate

and

its s

ched

ules

may

onl

y be

re

prod

uced

in it

s en

tiret

y an

d w

ithou

t ch

ange

.

Page

1 o

f 1

Form

9400

Iss

ue 1

Issu

e0

to2:

The

draw

ings

ass

ocia

ted

with

the

se I

ssue

s w

ere

ratio

nalis

ed b

y th

ose

liste

d in

Iss

ue3.

Issu

e3

Num

ber

Shee

tRe

v.D

ate

Des

crip

tion

ABT

1026

01

of 1

C25

Jun

02Ex

tern

al L

abel

(BP

G)

ABT

1030

41

of 1

A16

Nov

99BP

G M

anuf

actu

ring

Spec

ifica

tion

Issu

e4

Num

ber

Shee

tRe

v.D

ate

Des

crip

tion

ABT

1484

21

of 1

-

01 F

eb05

BPG

Ran

ge E

Ex ia

Lab

el

ABT

1484

51

of 1

-

01 F

eb05

BPG

Ran

ge E

Ex ib

Lab

el

Issu

e5

:N

o ne

w d

raw

ings

wer

e in

trod

uced

.

Issu

e6

Dra

win

gSh

eets

Rev.

Dat

e(S

ira S

tam

p)Ti

tleAB

T10

260

1 of

1

D30

Mar

12BP

G E

xter

nal l

abel

–Ju

nctio

n Bo

xes

ABT

1030

41

of 1

B

30 M

ar12

BPG

Man

ufac

turin

gsp

ecifi

catio

nAB

T14

842

1 of

1

B30

Mar

12BP

G R

ange

EEx

ia L

abel

ABT

1484

51

of 1

B30

Mar

12BP

G R

ange

EEx

ib L

abel

Issu

e 7

(No

new

dra

win

gs w

ere

intr

oduc

ed.)

Issu

e8

Dra

win

gSh

eets

Rev.

Dat

e(S

ira S

tam

p)Ti

tleAB

T10

260

1 of

1

E30

Sep

12BP

GN

amep

late

–Ju

nctio

nBo

xAB

T10

304

1 of

1

C30

Sep

12BP

G M

anuf

actu

ring

spec

ifica

tion

ABT

1030

51

of 1

C

30 S

ep12

BPG

Ran

ge o

f Enc

losu

res

Issu

e9

R30

711A

/00

Dra

win

gSh

eets

Rev.

Dat

e(S

ira s

tam

p)Ti

tleAB

T102

601

of 1

F

30 O

ct13

BPG

Ran

ge E

x e

Labe

lAB

T148

421

of 1

C

10 O

ct13

BPG

Ran

ge E

x ia

Lab

el

R32

242A

/00

Dra

win

gSh

eets

Rev.

Dat

e(S

ira s

tam

p)Ti

tleAB

T265

281

of 1

A

19D

ec13

Exte

rnal

ATE

X La

bel (

BPG

)AB

T166

891

of 1

C

19D

ec13

BPG

Man

ufac

turin

gSp

ec

Issu

es 1

0 a

nd

11

(No

new

dra

win

gs w

ere

intr

oduc

ed.)

Page 36: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

IEC

Ex

Cer

tific

ate

of C

on

form

ity

INT

ER

NA

TIO

NA

L E

LE

CTR

OT

EC

HN

ICA

L C

OM

MIS

SIO

NIE

C C

ertif

icat

ion

Sch

eme

for

Exp

losi

ve A

tmos

phe

res

for

rule

s a

nd

deta

ils o

f th

e I

EC

Ex S

ch

em

e v

isit w

ww

.iecex.c

om

Ce

rtific

ate

No.:

IEC

Ex S

IR 0

6.0

087

Xis

sue

No

.:5

Sta

tus:

Cur

rent

Da

te o

f Is

sue

:20

14-0

7-30

Pa

ge

1 o

f 4

Ap

plican

t:

Ele

ctr

ical A

ppa

ratu

s:

BP

G R

ange

of

Junc

tion

Bo

xes

Op

tiona

l acc

esso

ry:

Typ

e o

f P

rote

ction

:In

crea

sed

Saf

ety

and

Du

st

Mark

ing

:E

x e

IIC

T6

Gb (

Ta

-6

5°C

to +

#°C

)o

rE

x ia

IIC

T6

Ga

(T

a -

65°C

to +

#°C

)E

x e

IIC

T5

Gb (

Ta

-6

5°C

to +

#°C

)E

x ia

IIC

T5

Ga

(T

a -

65°C

to +

#°C

)E

x e

IIC

T4

Gb (

Ta

-6

5°C

to +

#°C

)E

x ia

IIC

T4

Ga

(T

a -

65°C

to +

#°C

)E

x ib

IIC

T6 G

b (

Ta -

65

°C to

+#°C

)E

x ta

III

C T

85°C

Da (

Ta

-65°C

to

+#

°CE

x ib

IIC

T5 G

b (

Ta -

65

°C to

+#°C

)E

x ta

III

C T

100°C

Da

(T

a -

65

°C t

o +

#°C

Ex ib

IIC

T4 G

b (

Ta -

65

°C to

+#°C

)E

x tb

III

C T

85

°C D

b (

Ta

-6

5°C

to +

#°C

)E

x tb

III

C T

10

0°C

Db (

Ta -

65

°C to

+#°C

)(T

em

pe

ratu

re c

lass,

mark

ing f

or

du

st a

nd

Ta

ma

xim

um

dep

en

ds u

po

n t

he

ma

xim

um

pow

er

dis

sip

atio

n,

refe

r to

An

ne

xe

)

Ap

prov

ed fo

r is

sue

on

beha

lf of

the

IEC

Ex

Ce

rtifi

catio

n B

ody:

C E

llaby

Po

sitio

n:

Dep

uty

Cert

ific

ation

Man

ag

er

Sig

nat

ure

:(f

or p

rinte

d ve

rsio

n)

Da

te:

1. T

his

ce

rtific

ate

an

d s

che

du

le m

ay o

nly

be

re

pro

duced

in f

ull.

2. T

his

ce

rtific

ate

is n

ot tr

an

sfe

rab

le a

nd r

em

ain

s t

he p

rope

rty o

f th

e issu

ing b

ody.

3. T

he

Sta

tus a

nd a

uth

en

ticity o

f th

is c

ert

ific

ate

may b

e v

erified b

y v

isitin

g th

e O

ffic

ial IE

CE

x W

ebsite.

Cert

ific

ate

issu

ed

by:

SIR

A C

erti

ficat

ion

Ser

vice

Rak

e L

ane

Ecc

lest

on

Ch

este

rC

H4

9JN

Un

ited

Kin

gd

om

Ce

rtific

ate

his

tory

:

Issu

e N

o. 5 (

20

14

-7-3

0)

Issu

e N

o. 4 (

20

14

-5-2

0)

Issu

e N

o.

3 (

20

14

-5-8

)Is

sue

No

. 2

(2

01

2-1

0-

25)

Issu

e N

o. 1 (

20

10

-7-2

7)

Issue

No

. 0

(2

00

6-1

0-

25)

AB

TEC

H L

imit

edA

B C

ontr

ols

& T

echn

olo

gy

San

de

rso

n S

tre

et

Low

er

Don

Va

lle

yS

he

ffie

ld S

9 2

UA

Un

ited

Kin

gdo

m

IEC

Ex

Cer

tifi

cate

of

Co

nfo

rmit

yC

ert

ific

ate

No.:

IEC

Ex S

IR 0

6.0

087

X

Da

te o

f Is

su

e:

2014

-07-

30Is

su

e N

o.:

5

Pag

e 2

of

4

Man

ufa

ctu

rer:

Ad

ditio

nal M

an

ufa

ctu

rin

g loca

tio

n(s

):

Th

is c

ert

ific

ate

is issue

d a

s v

eri

fica

tio

n t

ha

t a s

am

ple

(s),

rep

resen

tative

of p

rod

uction

, w

as a

ssessed

and

te

ste

d a

nd

fo

un

d to

com

ply

with t

he

IE

C S

tanda

rd lis

t be

low

and

th

at

the m

anu

factu

rer's

quality

syste

m,

rela

tin

g t

o t

he

Ex p

rod

ucts

covere

d b

y t

his

ce

rtific

ate

, w

as a

sse

sse

d a

nd f

ou

nd

to c

om

ply

with

th

e I

EC

Ex Qu

ality

syste

m r

equir

em

ents

. T

his

cert

ific

ate

is g

rante

d s

ub

ject

to th

e c

ond

itio

ns a

s s

et o

ut

in IE

CE

x S

che

me R

ule

s, IE

CE

x 0

2 a

nd

Op

era

tion

al D

ocu

men

ts

as a

men

ded

.

ST

AN

DA

RD

S:

Th

e e

lectr

ical ap

pa

ratu

s a

nd

any a

cce

pta

ble

va

ria

tion

s t

o it

sp

ecifie

d in

th

e s

che

du

le o

f th

is c

ert

ific

ate

and t

he

id

en

tifie

d

docum

ents

, w

as f

ou

nd

to

com

ply

with t

he

follow

ing s

tand

ard

s:

IEC

6007

9-0

: 201

1E

ditio

n:

6.0

Explo

siv

e a

tmo

sph

ere

s -

Part

0:

Gen

era

l require

me

nts

IEC

6007

9-1

1 : 2

011

Editio

n:

6.0

Explo

siv

e a

tmo

sph

ere

s -

Part

11

: Equ

ipm

ent p

rote

ctio

n b

y intr

insic

sa

fety

"i"

IEC

6007

9-3

1 : 2

008

Editio

n:

1

Explo

siv

e a

tmo

sph

ere

s –

Part

31:

Equip

men

t d

ust

ignitio

n p

rote

ctio

n b

y e

nclo

su

re 't'

IEC

6007

9-7

: 200

6-0

7E

ditio

n:

4

Explo

siv

e a

tmo

sph

ere

s -

Part

7:

Equip

men

t pro

tection

by in

cre

ase

d s

afe

ty "

e"

Thi

s C

ertif

icat

e d

oes

not

indi

cate

com

plia

nce

with

ele

ctric

al s

afet

y an

d p

erfo

rma

nce

req

uire

me

nts

othe

r th

an th

ose

ex

pres

sly

incl

uded

in t

he S

tan

dard

s lis

ted

abov

e.

TE

ST

& AS

SE

SS

ME

NT

RE

PO

RTS

:A

sa

mpl

e(s)

of t

he e

quip

me

nt li

sted

has

suc

cess

fully

met

the

exam

ina

tion

and

test

req

uire

me

nts

as r

eco

rded

in

Te

st R

epo

rt:

uality

Assessm

en

t R

epo

rt:

GB/S

IR/E

xT

R06

.010

1/01

GB/S

IR/E

xT

R12

.024

5/0

0G

B/S

IR/E

xT

R14

.01

07/0

0

GB/S

IR/QA

R06

.004

6/00

GB/S

IR/QA

R06

.00

46/0

1G

B/S

IR/QA

R0

6.0

046/0

2G

B/S

IR/QA

R06

.004

6/03

GB/S

IR/QA

R06

.00

46/0

4

AB

TE

CH

Lim

ited

A B

Co

ntr

ols

& T

echn

olo

gy

Sa

nd

ers

on S

tre

et

Lo

we

r D

on V

alle

yS

heff

ield

S9

2U

A

Un

ited

Kin

gd

om

Page 37: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

IEC

Ex

Cer

tifi

cate

of

Co

nfo

rmit

yC

ert

ific

ate

No.:

IEC

Ex S

IR 0

6.0

087

X

Da

te o

f Is

su

e:

2014

-07-

30Is

su

e N

o.:

5

Pag

e 3

of

4

Sch

edul

e

EQU

IPM

EN

T:

Equ

ipm

ent

and

sys

tem

s co

vere

d b

y th

is c

ertif

ica

te a

re a

s fo

llow

s:

Th

e B

PG

Junction

Bo

xe

s c

om

pri

se a

poly

este

r, B

PG

En

clo

sure

, co

mpo

ne

nt

cert

ifie

d a

s I

EC

Ex S

IR 0

6.0

086

U, th

afitte

d w

ith

te

rmin

als

. R

efe

r to

cert

ific

ate

Ann

exe f

o a

full p

rodu

ct

de

scri

ptio

n.

CO

ND

ITIO

NS

OF C

ER

TIFIC

ATI

ON

:YE

S a

s sh

own

belo

w:

1.

Wh

en

use

d in a

n E

PL t

a (

Da)

ap

plication t

he

po

we

r sup

ply

to th

e equ

ipm

en

t is

to b

e r

ate

d f

or

a

pro

sp

ective s

hort

circuit c

urr

en

t o

f n

ot

more

tha

n 1

0 k

A.

IEC

Ex

Cer

tifi

cate

of

Co

nfo

rmit

yC

ert

ific

ate

No.:

IEC

Ex S

IR 0

6.0

087

X

Da

te o

f Is

su

e:

2014

-07-

30Is

su

e N

o.:

5

Pag

e 4

of

4

DE

TAIL

S O

F CE

RT

IFICA

TE

CH

AN

GE

S (fo

r is

sues

1 a

nd

above

):

Issu

e 1

–th

is Issue

in

tro

du

ced

th

e f

ollo

win

g c

han

ge

s:

1T

o a

llow

GB/S

IR/E

xT

R0

6.0

101/0

1 t

o r

ep

lace

GB/S

IR/E

xT

R06.0

10

1/00

Issu

e 2

–th

is Issue

in

tro

du

ced

th

e f

ollo

win

g c

han

ge

s:

1T

he

Descrip

tion

wa

s a

lign

ed w

ith

cert

ific

ate

no.

Sira

99A

TE

X3

17

3 a

ssocia

ted w

ith

th

is Ju

nctio

n B

ox,

this

in

clu

de

d r

ecog

nis

ing t

he

fo

llow

ing

cha

ng

es a

sse

sse

d a

s p

art

of

that

ce

rtific

ate

.*

Th

e B

PG

13

.5 e

nclo

sure

was a

dd

ed

to

th

e r

an

ge

.*

Th

e o

ption

to

fit s

lotte

d t

runkin

g in

sid

e th

e e

nclo

sure

s, th

is t

runkin

g m

ay b

e s

ited

as r

equir

ed

.T

he in

str

uction

s w

ere

mo

difie

d t

o r

eco

gn

ise a

dditio

na

l re

str

ictio

ns a

sso

cia

ted w

ith t

his

ch

an

ge

a

nd

a n

ew

Co

nd

itio

n o

f M

anu

factu

re w

as in

trodu

ce

d.

2Follow

ing

app

ropri

ate

re

-assessm

en

t to

dem

onstr

ate

com

plia

nce

with t

he

requ

ire

men

ts o

f th

e la

test

sta

nd

ard

s, th

e d

ocu

men

ts p

revio

usly

used

fo

r a

sse

ssm

en

t w

ere

re

pla

ced

by th

ose c

urr

ently lis

ted

, th

e

mark

ing

s w

ere

upd

ate

d a

ccord

ing

ly.

In a

dditio

n,

the e

nclo

sure

was a

llo

we

d t

o b

e u

sed f

or

intr

insic

ally

safe

app

lication

s a

nd I

EC

60

07

9-1

1:2

012

Ed

itio

n 6

wa

s in

clu

ded

in t

he

lis

t o

f sup

po

rtin

g s

tand

ard

s.

3T

he

Cond

itio

n o

f C

ert

ific

atio

n r

ela

ted t

o s

tatic w

as r

em

ove

d; in

add

itio

n th

e C

on

ditio

ns o

f M

anufa

ctu

re

we

re r

atio

na

lise

d t

o b

ring

th

em

into

lin

e w

ith

Sira

99

AT

EX

317

3.

4It

wa

s r

ecog

nis

ed

th

at

a n

ew

pro

cedu

re f

or

se

lectin

g t

erm

ina

ls h

as b

ee

n a

dop

ted b

y th

e m

anu

factu

rer;

this

allow

s the

te

rmin

als

to b

e c

ho

se

n f

rom

an

Ap

pro

ved

Co

mpo

ne

nt

Docu

me

nt,

Sira

12

AC

087

, th

at is

is

sue

d a

nd c

ontr

olle

d b

y S

ira.

Issu

e 3

–th

is Issue

in

tro

du

ced

th

e f

ollo

win

g c

han

ge

:

1Is

sue

d t

o c

orr

ect

the n

um

berin

g o

f th

e c

ha

ng

es in I

ssu

e 2

and

to e

dit c

han

ge

3.

GB/S

IR/E

xT

R14

.011

3/00

wa

s r

em

ove

d.

Issu

e 4

–th

is Issue

in

tro

du

ced

th

e f

ollo

win

g c

han

ge

:

1U

sin

g I

EC

60

07

9-2

6,

the ju

nctio

n b

oxes w

ere

allow

ed

to

be m

ark

ed

with ‘E

x ia’an

d ‘E

x ta

’co

nce

pts

for

EP

L leve

ls G

a a

nd D

a,

as a

re

su

lt o

f th

is c

ha

ng

e, th

e m

axim

um

po

wer

dis

sip

atio

n t

ab

le w

as m

od

ifie

d

and

a S

pecia

l C

on

ditio

n f

or

Sa

fe U

se

wa

s in

tro

du

ce

d n

ecessita

tin

g t

he a

dd

itio

n o

f a

n ‘X

’suff

ix to t

he

cert

ific

ate

num

ber.

2T

he

BP

G r

an

ge

of jun

ctio

n b

oxe

s w

ere

allow

ed t

o b

e u

se

d in a

n u

pp

er

am

bie

nt +

55°C

with

a

tem

pe

ratu

re c

lass/su

rfa

ce

te

mpe

ratu

re o

f T

5/T

10

0°C

, th

e a

sso

cia

ted

ma

xim

um

pow

er

dis

sip

ation

ra

tin

gs

(W)

and

mark

ing

s w

ere

re

cog

nis

ed.

Issu

e 5

–th

is Issue

in

tro

du

ced

th

e f

ollo

win

g c

han

ge

:

1Is

sue

d t

o c

orr

ect

a typo

gra

phic

al e

rro

r

Page 38: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive
Page 39: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

[This Page Intentionally Left Blank] 

Page 40: D818/ET MiniPurge Manual · 2020. 4. 27. · The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive

Expo Technologies USAExpo Technologies Inc.

9140 Ravenna Road Unit #3Twinsburg,

OH 440878, USAT: +1 440 247 5314F: +1 330 487 0611

E: [email protected]

Expo Technologies UKExpo Technologies Ltd.

Unit 2 The Summit, Hanworth RoadSunbury-On-Thames,

TW16 5DB, UKT: +44 20 8398 8011F: +44 20 8398 8014

E: [email protected]

Expo Technologies ChinaQingdao Expo M&E Technologies Co. Ltd

329 Huashan Er LuJimo City, Qingdao,

266200 ChinaT: +86 532 8906 9858F: +86 532 8906 9858

E: [email protected]

www.expoworldwide.com