chapter 3 ps, psm, tms

Upload: kishansai

Post on 06-Jul-2018

241 views

Category:

Documents


2 download

TRANSCRIPT

  • 8/17/2019 Chapter 3 Ps, Psm, Tms

    1/32

    1

    Primary and backup protectionNeed of coordination

    Properties of protection systems

    Overload and overcurrent

    2

    • Three essential properties of the protective

    relaying schemes are:

    sensitivity

    selectivity and

    speed

    • These are not always the properties of the

    relays but are properties of  correct relaysetting and protection schemes

    application.

    Properties of protection schemes

  • 8/17/2019 Chapter 3 Ps, Psm, Tms

    2/32

    3

    Pickup and Sensitivity• Pick up (plug setting) → Minimum operating current of the relay.

    • Lower the pick up of the relay, higher will be the sensitivity.

    • Higher the sensitivity, fault currents of lower magnitudes can also be

    detected.

     – Primary operating current, P.O.C. = Pickup*CTR

     – % Sensitivity = (P.O.C./Fault current)*100 (S = 1/ PSM)

    4

    Sensitivity V/s Thermal capacity

    • In case of static relays and numerical relays: only

    thermal capability of relay  imposes restriction on

    the choice of the lowest setting.

    • For example, SPAJ 140C, of ABB/7SJ600 of Asea

    Brown / Micom P120 of Areva make relays have

    thermal capacity of  100*In for 1 second, where, In

    is relay rated current.

    • In case of electro-mechanical relay: (1) lower the

    setting of the relay, more will be the burden on theCT resulting into large exciting current drawn by

    CT and (2) more heating of the relay element.

  • 8/17/2019 Chapter 3 Ps, Psm, Tms

    3/32

    5

    • Consider a relay connected to 1000 / 1 CT. Let thefault current be 20 kA. Assume thermal capacity of 

    relay be 100 A for 1second.

    • If relay is set for 10% , relay current at fault =

    20,000 / (1000 x 0.1) = 200 IN

    • I2 t Criteria: (200IN)2 (t) = (100IN)

    2 x 1 sec

    t = 0.25 sec

    • If operating time of the relay is less than 0.25 sec,

    the 10% pick up is permissible, otherwise relaymay get damaged.

    Sensitivity V/s Thermal capacity

    6

    SelectivityIt refers to the selective tripping of the

    protective gears and also called as the

    discrimination.

    The three methods to achieve the

    discrimination are:

     A. Discrimination by Time,

    B. Discrimination by current andC. Discrimination both by Time & Current

  • 8/17/2019 Chapter 3 Ps, Psm, Tms

    4/32

    7

    Discrimination by Time

    8

    DMT relay (Definite Minimum Time)(50/2) is a goodexample of achieving discrimination by time. If thecurrent exceeds the set value, operating time isindependent of current magnitude.

     A. Discrimination by Time (50/2)

  • 8/17/2019 Chapter 3 Ps, Psm, Tms

    5/32

    9

    • Assume the discrimination time between successiverelays, in fig.1, is say 0.3 sec.

    • let the fault current be above the pick up values for allthe relays. For fault on MCC – 1 outgoing feeder, fuseoperates in 10 miliSec, relay R7 operates in 0.31 secand relay R6 operates in 0.61 sec. All upstream relaysare grades accordingly.

    • The disadvantage of using DMT relays is that theoperating time of the upstream relays will be very high.

    • The fault closest to the source takes longest time toclear.

    • The advantage of using DMT relays is that the operatingtime is   well defined   for variable source operatingconditions.

    Discrimination by Time (50/2)

    10

    B. Discrimination by current (50 or 50N)• Applicable only when substantial difference between the

    fault current magnitudes exists at a given location (L1)

    for the fault on the two ends (F1 and F2) of the

    equipments.

  • 8/17/2019 Chapter 3 Ps, Psm, Tms

    6/32

    11

    • The impedance of the equipment shall besubstantial that will create the above differencelike transformer or long cable.

    • For illustration consider a fault on LT side of transformer TR2 in fig.1.

    • The fault current is 39,227 A on 415 V side andthe reflected current on 6.6 kV side is 2467 A.

    • If the fault is on 6.6 kV side, the fault current is16kA. By setting the pick up current for relay R4above 2467 A, the relay R4 will not pick up for fault on the LT side but will pick up for the fault

    on HT side.• The disadvantage is that   discrimination is

    obtained but no back up is ensured.

    Discrimination by current (50 or 50N)

    12

    C. Discrimination both by time and current (51/ 51N)

    • IDMT (Inverse Definite Minimum Time) (51 and51N) relays are used to obtain discrimination byboth time & current.

    • The operating time of IDMT relay is inverselyproportional to current magnitude.

    • Even for highest current, time for operation is notinstantaneous but a minimum time.

    • For the same fault current and specified pick up,relay operating time can be varied by adjustingtime dial.

  • 8/17/2019 Chapter 3 Ps, Psm, Tms

    7/32

    13

    Discrimination both by time and current: NI characteristics

    14

  • 8/17/2019 Chapter 3 Ps, Psm, Tms

    8/32

    15

    Discrimination both by time and current

    16

    • Assume the discrimination time between successive relaysis say 0.3 sec.

    • Let the fault current be above the pick up values for all therelays.

    • For fault on MCC – 1 outgoing feeder(F1):

     – fuse operates in 10 msec, relay R7 operates in 0.32 secand relay R6 operates in 0.63 sec and relay R4operates in 0.94 sec.

    • For fault on HT side(F2):

     – of transformer TR2, the fault current is 16 kA and relayR4 operates in 0.73 sec.

    • Reduced operating time of relay R4 for 6.6kV faults resultin reduced operating time of upstream relays R2 & R3 for HT fault.

    Discrimination both by time and current

  • 8/17/2019 Chapter 3 Ps, Psm, Tms

    9/32

    17

    IDMT(51)• The advantage gained by using IDMT relay is that:

     – With the same pick up and time dial setting:

    • lower time of operation for near end fault and higher 

    operating times for far end fault inherently achieved.

     – In case of same fault current magnitude along the

    system:

    • desired operating time can be achieved in IDMT

    relays by adjusting Pick up (PS) & time dial.

    DMT(50/2)

    • In case of difference in fault current magnitudes at one

    point along the system: – DMT relays are superior to the IDMT relays.

    DMT and IDMT compared

    18

    Speed: Fault clearing time and Critical Clearing

    Time

    • If the fault clearing time is less than 100 msec,it is considered as high speed tripping.

    • High speed tripping minimizes the damage tothe equipments, increases stability margin for synchronous machines and avoids unwarrantedtripping of voltage sensitive loads.

    • Critical Clearing Time (CCT)   is the minimumtime before which fault has to be cleared.

    • Typically it varies between 200 msec to 1second and depends upon location of fault.

    • System becomes unstable, when fault clearingtime is more than the CCT.

  • 8/17/2019 Chapter 3 Ps, Psm, Tms

    10/32

    19

    Speed

    20

    Speed

    • Speed without selectivity leads to poor co-ordination.

    Small

    fault clearing time

  • 8/17/2019 Chapter 3 Ps, Psm, Tms

    11/32

    21

    Radial Power Systems

    • Radial Power System is a system in which power flowsin the direction from the distribution substation to an

    individual customer.

    • Radial system looks like a branch of a tree with a main

    line connected to a series of a smaller circuit.

    • From the smaller circuit, the circuit will branch off to

    contain the customer need. Radial system will have one

    source of power or a group of power sources in the

    same area.

    • Power failure, short circuit, down the power line will

    cause disruption to the system and the system cannot be

    restored until the fault is fixed.

    22

    Methods to achieve high speed tripping

    1.Unit protection: (Generator, transformer, bus, feeder,

    motor).

    Protection is provided to trip instantaneously for faults

    only within the unit under protection. No co-ordination

    with external protection is required.

    Examples of unit protection are: bus differential

    protection, feeder pilot wire protection, transformer or 

    motor differential protection.

    2.Directional protections for multi source / non redialsystems.

  • 8/17/2019 Chapter 3 Ps, Psm, Tms

    12/32

    23

    • Speed must be weighed against economy.• In LT distribution networks, loads are connected

    at radial end of system, fault clearance time is

    shorter and hence need of speedy clearance is

    not critical.

    • Unit Protection in LT system are generally not

    employed.

    • In generating plants, M.V. & H.V. systems high

    speed tripping is essential to maintain system

    stability and voltage stability.

    Unit protection

    24

    Example of Unit protection

  • 8/17/2019 Chapter 3 Ps, Psm, Tms

    13/32

    25

    DISCRIMINATION TIME

    The time margin between the settings of these relays must take intoaccount three factors:

    • The operating time of the circuit breakers. Modern medium voltagebreakers are rated for 5 cycle interrupting time, and the time allowanceis traditionally 0.1 second.

    • Overtravel, which is the tendency for a relay to continue to time after the fault current is interrupted by a downstream circuit breakers.Overtravel is a natural characteristic of the inertia of electromechanicalinduction disk relays, and while exact values vary widely, thetraditional allowance is 0.1 seconds. Most static analog and digitalrelays are designed to have no practical overtravel. If the backup relayhas an overtravel tendency, it’s time delay must be long enough toaccount for that overtravel.

    • Margin to account for imponderables such as the uncertainties inthe magnitude of fault current, inaccuracies in instrument transformers,manufacturing and calibration variations in relays, etc. The amount of 

    margin allowed depends upon how much risk the relay engineer iswilling to assume; typical values range from 0.1 to 0.3 seconds.

    • The total “coordinating time margin” is the sum of these three factorsand ranges from 0.2 to 0.5 seconds; a 0.3 second margin is oftentaken as a reasonable compromise between the objectives of speedand security.

    26

    DISCRIMINATION TIME (CO-ORDINATION INTERVAL) - Speed

    • This refers to the time interval between the operation of two

    adjacent breakers or fuse and breaker.

  • 8/17/2019 Chapter 3 Ps, Psm, Tms

    14/32

    27

    Circuit Breaker Interrupting Time

    • The circuit breaker interrupting the fault musthave completely interrupted the current before

    the discriminating relay ceases to be energized.

    • The time taken is dependent on the type of 

    circuit breaker used and the fault current to be

    interrupted. Manufacturers normally provide the

    fault interrupting time at rated interrupting

    capacity and this value is invariably used in the

    calculation of grading margin.

    28

    Circuit breaker operating time

  • 8/17/2019 Chapter 3 Ps, Psm, Tms

    15/32

    29

    Relay Timing Error 

    • All relays have errors in their timingcompared to the ideal characteristic asdefined in IEC 60255.

    • For a relay specified to IEC 60255, a relayerror index is quoted that determines themaximum timing error of the relay.

    • The timing error must be taken intoaccount when determining the grading

    margin.

    30

    Overshoot• When the relay is de-energized, operation may continue

    for a little longer until any stored energy has beendissipated. For example, an induction disc relay will havestored kinetic energy in the motion of the disc; staticrelay circuits may have energy stored in capacitors.

    • Relay design is directed to minimizing and absorbingthese energies, but some allowance is usuallynecessary.

    • The overshoot time is defined as the difference betweenthe operating time of a relay at a specified value of inputcurrent and the maximum duration of input current,which when suddenly reduced below the relay operatinglevel, is insufficient to cause relay operation.

  • 8/17/2019 Chapter 3 Ps, Psm, Tms

    16/32

    31

    CT Errors

    • Current transformers have phase and ratioerrors due to the exciting current required tomagnetize their cores.

    • The result is that the CT secondary current is notan identical scaled replica of the primary current.

    • This leads to errors in the operation of relays,especially in the time of operation.

    • CT errors are not relevant when independentdefinite-time delay over current relays are being

    considered.

    32

    Final Margin• After the above allowances have been

    made, the discriminating relay must just

    fail to complete its operation.

    • Some extra allowance, or safety margin, is

    required to ensure that relay operation

    does not occur.

  • 8/17/2019 Chapter 3 Ps, Psm, Tms

    17/32

    33

    Co-ordination interval shall incorporate the following

    time periods:

    A. Interrupting time of downstream breaker:

     Approximately 100 mSec. (Though the actual operating time is muchsmaller, say 50 mSec).

    B. Relay error factor:

    Refers to negative or positive errors in operating time of the upstream+ Downstream relays / fuse involved in grading.

     For Co-ordination time between Fuse & Breaker = 0.4t

     For Co-ordination time between Breaker & Breaker = 0.25t

    Where, t = operating time of Downstream Fuse / Relay

    C. Overshoot time of upstream relay:

    Operating time more than set value due to contact over travel etc. it isabout 50msec  for electro-mechanical relays. This is  not relevant for modern numerical relays.

    D. Safety Margin:

    Refers to the extra allowance to ensure a satisfactory gap betweenoperating time of two breakers or breaker and fuse. It can be about100msec for electro-mechanical relays. If numerical relays are used for both upstream and downstream, this can be reduced, to even 50msec.

    34

    EMPIRICAL FORMULAS FOR CO-ORDINATION TIME

    For Fuse – Breaker IDMT (Conventional Relays)/ Fuse – IDMT/INST - IDMT relay/fuse-DMT

    Discrimination Time = 0.4t + 0.15,   where

    Fuse operating time = t

    Downstream Inst. Relay Error / Fusing Factor = 0.4t

    Upstream Relay overshoot Time = 50 m Sec.

    Safety Margin = 100 m Sec.

    Interrupting time of Downstream Breaker = 0 m Sec (N.A.)

    For Breaker – Breaker (Conventional Relays) / IDMT - IDMTrelays

    Discrimination Time = 0.25t + 0.25,where

    Downstream Relay operating Time = tRelay Error Factor = 0.25t

    Upstream Relay overshoot Time = 50 m Sec.

    Safety Margin = 100 m Sec.

    Interrupting time of Downstream Breaker = 100 m Sec.

  • 8/17/2019 Chapter 3 Ps, Psm, Tms

    18/32

    35

    Present Scenario for Discrimination Time Formula

    Following changes can be done in discrimination timeformula:

    a) Relay error factor for numerical relays : 0.1t (instead of 0.25t)

    b) Overshoot time : Static Relay = 50 mSec: Numerical Relay = 0 mSec

    c) Modern VCB / SF6 CB operating time:50 mSec, (insteadof 100msec)

    d) Safety margin can be reduced (from 100msec.) to50mSec, if relays are accurately set.

    36

    IDMT NI Characteristics• The IDMT relay

    operates with a

    fixed time for PSM

    > 20.

    • Also the relay

    characteristic is

    defined for PSM >

    2.

    • Relay has no

    definedcharacteristic for 

    PSM < 2.

  • 8/17/2019 Chapter 3 Ps, Psm, Tms

    19/32

    37

    Overload and over current

    • Over load withstand capacity of equipment in generalvarious from – many seconds to minutes. For Example,

    a)Generator overload capacity

    b)Transformer overload capability

    Time (Sec)   120 60 30 10

    Stator current (%)   116 130 154 226

    Time (Minutes)   120 80 45 20 10 2

    Current (%)   130 145 160 175 200 300

    38

    Overload and over current• Over current is short circuit current and fault has to be removed within 1

    sec, where as overload can be sustained in minutes / hours. Hence, over 

    current relay with any characteristic cannot be used for over load

    protection.

  • 8/17/2019 Chapter 3 Ps, Psm, Tms

    20/322

    39

    Overload and over current

    40

    Overload and over current

    • If over current persists for more than 1 sec, it will result in loss of 

    synchronism (angle instability) or motor stalling (Voltage instability).

    • Conceptually over current relays cannot be used for over load protection.

  • 8/17/2019 Chapter 3 Ps, Psm, Tms

    21/322

    41

    Setting DMT Relays

    Primary Operating Currento Must lie above maximum running load current

    and largest drive starting current by safety

    margin.

    o Max. Running Load current includes motor full

    load current. Hence, it is subtracted.

    o Must lie below the lowest through fault current.

    o Relevant for generally used motor with DOL

    starting.

    42

    IF > P.O.C. > (IRL – IFLM + ISTM)

    Where,

    IF   = Minimum fault current relay to sense.

    P.O.C = Desired Primary Load Current of relay

    IRL   = Max. Running Load Current

    IFLM   = Highest Rating Drive Full Load Current

    ISTM   = Highest Rating Drive Starting Current

    Remark:   The First Comparison IF  > P.O.C is generally

    satisfied in most of the cases, since fault currentmagnitude is generally very high. The only critical case in

    which this comparison is important is when source fault

    level is low.

    Setting DMT Relays

  • 8/17/2019 Chapter 3 Ps, Psm, Tms

    22/322

    43

    Desired Pick Upo PICK UP ≥  Primary Operating

    Current (P.O.C) / C.T. Ratio

     DMT relay – independent of fault

    current, hence, plug setting

    multiplier applicable for IDMT

    relays not relevant for DMT

    relays.

    I > ISETIf ISET = 5000A

    I = 5001A or I = 20000A,

    operating time is same.

    Setting DMT Relays

    44

    DMT relay calculations

    Example of DMT Relays:Electromechanical relays: CTU, CAG + VTT. All numerical relays have

    inbuilt DMT feature.

  • 8/17/2019 Chapter 3 Ps, Psm, Tms

    23/322

    45

    Setting IDMT Relays

    Primary Operating Current

    • P.O.C Must lie above (Maximum running load current -

    Highest drive full load current of motor + Largest drive

    starting current).

    • Max. running load current includes motor full load current

    of started motor. Hence, it is subtracted.

    • P.O.C Must lie below the lowest through fault current.

    Formula: IF > P.O.C. >= IRL – IFLM + ISTM

    Where, P.O.C. = Desired primary operating current

    IRL = Max. running load current

    ISTM = Highest drive starting current of motor 

    IFLM =Highest drive full load current of motor 

    46

    Desired Relay Pick up – PS (Plug Setting)

    Ratio of primary Operating Current of relay to C.T. Ratio

    (C.T.R.)

    PS = P.O.C.

    C.T.R.

    = (IRL – IFLM + ISTM)

    C.T.R.

    Selected pick up setting:

    Select the next higher available step.

     Actual Primary operating current (P.O.C.)

     Actual P.O.C. = Selected Pick up x C.T.R.Plug Setting Multiplier – PSM

    P.S.M = Fault Current

     Actual P.O.C.

    Setting IDMT Relays

  • 8/17/2019 Chapter 3 Ps, Psm, Tms

    24/322

    47

    Desired relay operating time t1

    t1 = t + td

    where, t = Downstream Relay / Fuse Operating Time

    td = Discrimination Time.

    Desired Time Dial Set Point – TMS (TIME MULTIPLIER

    SETTING)

    Desired TMS Setting =

    Desired Relay Operating Time t1 (OT)/ Relay Operating

    Time @ Selected PSM and TMS 1.0 (OT1)

    Desired Relay Operating Time t1 = Desired TMS setting*

    Relay Operating time @ selected PSM and TMS = 1.0

    Selected Time Dial (TMS) SettingNearest Higher Time Dial setting selected.

    Setting IDMT Relays

    48

    IDMT Setting: Plug Setting (PS),

    Plug Setting Multiplier (PSM) and

    Time Multiplier Setting (TMS)

    PS : Plug Setting (Current Setting /Pickup Setting)= (IRL - IFLM + ISTM) / CTR

    PS = (583 - 145 + 869) /1600

    = 0.816Set P.S. =0.9APrimary Operating Current (P.O.C)

    =C.T.R. x P.S.

    =1600 x 0.9 = 1440 APlug Setting Multiplier (P.S.M.)= Fault Current / Actual P.O.C.= 38872 / 1440 = 26.99PSM will be used to find operatingtime as per next slide.

    0.4

    Notation: PS(TMS)

  • 8/17/2019 Chapter 3 Ps, Psm, Tms

    25/322

    49

    Desired operating Time t1:Downstream fuse blow – off time t = 0.01 Sec

    Co- ordination interval td = 0.4 t + 0.15

    = 0.154 Sec

    Desired operating time t1 = t + td

    = 0.01 + 0.154

    = 0.164 Sec

    Relay R7 : Location : Incomer of MCC-1(415 V)

    50

    Relay R7 : Location : Incomer of MCC-1(415 V)

    Choose normal inverse characteristic.

    TMS = Required Time Setting = OT/OT1

    = Desired Operating Time / Operating Time @ TMS = 1.0

    OT   ⇒ From Coordination Requirement

    OT1 ⇒ From Equation or Standard Graphs

    Operating time @ PSM > 20 & time dial 1.0 = Operating Time @ PSM =

    20 (For PSM>20, Take PSM = 20) & time dial 1.0:

    Operating Time of R7 (OT1)

    = 0.14/ (PSM)0.02 -1 = 2.267

    (For NI @ Time dial 1.0)

    TMS = Desired Operating Time t1

    Operating Time @ TMS 1.0 & PSM 20

    = 0.164

    2.267

    = 0.072

    Set Time Dial at 0.08.   [Time Dial =0.05 – 1.00, Step = 0.01]

     Actual operating Time = 0.181 Sec for fault. [2.267x 0.08]

  • 8/17/2019 Chapter 3 Ps, Psm, Tms

    26/322

    51

    IDMT Setting: Time dial V/s operating time

    From graph:

    OT1 = 2.267

    OT

    0.08

    52

    Time dial V/s operating time

    IDMT Relay Equation/IECequation

    OT = TMS * β / (PSM)α -1.0

    OT1 = β / (PSM)α -1.0

    OT: Operating Time in sec

    TMS: Time Multiplier Setting

    PSM: Plug Setting Multiplier 

    IDMT Characteristics ß αNormal Inverse (NI) 0.14 0.02

    Very Inverse (VI) 13.5 1.0

    Extremely Inverse (EI) 80.0 2.0

    Long Time Inverse (LI) 120.0 1.0

  • 8/17/2019 Chapter 3 Ps, Psm, Tms

    27/322

    53

    54

    IDMT relay typesExtremely inverse (EI)

    Generally used to back up

    fuse

    Very Inverse (VI)

    Preferred on upstream

    side of transformer 

    Normal inverse (NI)

    If in doubt, use NI

    Used in majority of  

    applicationsLong time inverse (LI)

    To protect NGR

  • 8/17/2019 Chapter 3 Ps, Psm, Tms

    28/322

    55

    IDMT relay types

    There are a number of characteristics in common use. Each

    of these exists to address specific application needs.Following is a list of the most common characteristicstogether with their usual applications and also the codenumber which GE uses to identify each curve shape:

    • Inverse medium time (51) -  best suited for applicationswhere the variations in the magnitude of fault current arerelated primarily to switching of sources on the system, suchas in paper mill systems with a number of smallhydroelectric generators which are switched on and off depending on water conditions.

    • Very inverse medium time (53)  - best suited for generalapplications where the variations in the magnitude of faultcurrent are primarily determined by system impedance andfault location. This relay characteristic is the best choice for most industrial and commercial applications.

    56

    IDMT relay types• Inverse medium-long time (57)   - best suited for 

    applications as backup ground fault protection on complexlow-resistance grounded medium voltage systems.

    • Inverse long time (66)   - best suited for overload andlocked rotor protection of motors.

    Extremely inverse medium time (77)   - best suited for application on utility residential distribution circuits whereselectivity with distribution fuse cutouts and reclosers is arequirement, and where “cold load pickup” is aconsideration.

    Inverse short time (95) - best suited for backup ground fault

    protection applications on solidly grounded low voltagesystems where the feeders have instantaneous groundfault protection.

  • 8/17/2019 Chapter 3 Ps, Psm, Tms

    29/322

    57

    58

    Very Inverse (VI): CDG13   Operating Time @ PSM = 10 & TMS =

    1.0 => 1.5 sec

      Operating Time

    = TMS x 13.5 / [ ( PSM – 1.0) ]

      2 < PSM < 20

      Used on H.V. Side of transformer to co-ordinate with NI Characteristic relay onL.V. side.

      Very inverse characteristic is usefulwhere substantial reduction in faultcurrent occurs due to large impedance of protected object, e.g. on upstream side

    of transformer.   Advantage of NI and VI combination is

    that for L.T faults, operating timeincreases to coordinate with downstreamfaults and for HT faults, operating time isminimum to clear faults within CCT.

  • 8/17/2019 Chapter 3 Ps, Psm, Tms

    30/323

    59

    Extremely Inverse (EI)

    Application of EI characteristics Fuse – Relay Co-ordination :

    Depending on cable size, cable length and fuse

    rating, co-ordination between fuse and certain

    characteristics of relays may not be achievable.

    Sending end fault level : 35 kA (say).

    Ground fault occurs at motor end.

    60

     Example : For 300 sq.mm cable (Motor Rating – 110 kW,DOL) Point ‘R’ : Length > 108 m, fault current reduces below

    5kA Point ‘Q’ : Length > 184 m, fault current reduces below

    3kA Point ‘P’ : Length > 564 m, fault current reduces below

    1kA Depending on fuse rating, the fault at receiving end may

    be cleared in much more than normal operating time of 10 to 20 milliseconds.

     Fig shown is with fault impedance zero. If fault

    impedance is also considered, fault current will stillfurther go down. Co-ordination between fuse and upstream relay become

    critical.

    Extremely Inverse (EI)

  • 8/17/2019 Chapter 3 Ps, Psm, Tms

    31/323

    61

    62

  • 8/17/2019 Chapter 3 Ps, Psm, Tms

    32/32

    63

    64

     Breaking capacity of contactor 

    Rating AC3 AC4

    100A 6 Ith 8 Ith

     Over load relay shall trip

     Contactor, in case of switch – fuse – contactor module.

     Contactor again!, in case of MCCB – contactor module.

     Too frequent opening of MCCB not good for its life.

    Extremely Inverse (EI)