    ABB STOTZ-KONTAKT

    Residual Current-operatedCircuit Breakers F 660

  • 7/31/2019 3089-99 RCCB F660

    2/16

    2

    Prior to connection of aluminium conductors ensurethat their contact points are cleaned, brushed andcoated with grease. The contact terminals must betightened up after six to eight weeks.

    Conditions of Delivery and SaleFor business conducted in domestic and foreign markets the following conditions intheir latest versions are valid:General conditions of Supply and Delivery for products and services of the electricalindustry: (ABB-Form 80060 German, 80061 German-English, 80062 German-French).General conditions of Sale for the products and services of the electrical industry:(ABB-Form 80175 German, 80160 English, 80174 French).Relevant to specific orders special conditions can be agreed upon.

    GuaranteeThe guarantee period is 6 months, in favour of the endbuyer, and commences whenthe is in possession of the products. In this connection, our valid guarantee conditions

    are included in the packing of our cordless tools.

    Technical ReservationsThe data and figures of this publication are subject to change as required by technicalprogress.

  • 7/31/2019 3089-99 RCCB F660

    3/16

    3

    General

    Description, Functions .............................................................................................................. 4 Application examples ............................................................................................................... 5Technical data........................................................................................................................... 7

    Mounting and operating instructions

    Mounting and operating instructions ........................................................................................ 8Dimensions ............................................................................................................................... 9Examples of protection against dangerous currents ................................................................ 10

    Selection tables

    Residual Current-operated F 660 Circuit-Breakers .................................................................. 11Busbars ..................................................................................................................................... 11Supplementary devices ............................................................................................................ 13Labeling accessories ................................................................................................................ 14

    Residual Current-operated Circuit-BreakersF 660

    Contents Page

  • 7/31/2019 3089-99 RCCB F660

    4/16

  • 7/31/2019 3089-99 RCCB F660

    5/16

  • 7/31/2019 3089-99 RCCB F660

    6/16

  • 7/31/2019 3089-99 RCCB F660

    7/16

    7

    Technical Data

    Standard specification: IEC 1008, EN 61 008, BS 4293

    No. of poles: 2- and 4-poleRated current In: 80, 100 A

    Rated residual operating current I n: 30, 100 and 300 mA

    Tripping range: 0.5 ... 1.0 I nTripping time at 1 In: 200 ms

    5 I n: 40 ms

    Surge current withstand capacity: 250 A (pulse waveshape 8/20)(Pulse waveshape see page 4) 200 A (Ring-ware 0.5 s/100 kHz)

    Rated residual breaking capacity I m: 1000 A

    Rated breaking capacity Im: 1000 A

    Rated short-circuit current Inc: 6000 A

    Rated residual short-circuit current I c: 6000 AShort-circuit withstand capacity: 10000 A, in combination with the STOTZ MCB S 700 E 100 A or

    with an upstream fuse gL 100 A

    Rated voltage Un: 2-pole 230 V ; 4-pole 230/400 V

    Frequency: 50 to 60 Hz

    Max. operating voltage UBmax: Un + 10%

    Operating voltage of test device UT: 100 V up to 264 V

    Insulation: acc. DIN VDE 0110 part 1 and 2 overvoltage category: IV pollution degree: 2 Dielectric impuls withstand voltage: 6 kV (1.2/50 s) Dielectric strength: 2,5 kV (50/60 Hz)

    Housing: Moulded plastic, grey (RAL 7035)Switch handle: blue

    Test button: white

    Degree of protection: IP 20, IP 40 in consumer unit

    Protection against unintentionaldirect touch: acc. to DIN VDE 0106 part 100

    Cover dimensions: acc. to DIN 43 880 size 1

    Depth: 67.5 mm

    Mounting position: optional

    Fixing: Snap-on to DIN rail EN 50 022, 35 mm

    Cable cross section bottom: 1.5 up to 50 mm2

    for flexible conductor must betop: 1.5 up to 50 mm2 used wire end ferrule or cable lug

    Connection: single connection or group connection via busbars

    Terminals bottom: combi frame terminals with screw M6top: frame terminal with screw M6

    Life expectancy: at least 5.000 operations

    Climatic resistance acc. to IEC 1008or IEC 68 part 2-30: damp heat, cyclic (28 cycles)

    Ambient temperature: Tmin 25 C, Tmax + 55 C

    Vibration resistance: acc. to IEC 1008

    Trip free: yes

    Contact position indicator: acc. to IEC 73: green = OFF, red = ON

    Weight: see selection tables

    Residual Current-operated Circuit-BreakersF 660

  • 7/31/2019 3089-99 RCCB F660

    8/16

    8

    Installation and operating instructions

    1. Installation: Installation in the desired position by means of snap-on fastening to DIN-rails acc. toEN 50 022, 35 mm

    Installation only allowedby an authorized electrician.

    2. ConnectionThe supply may be connected from above or below as required. Care should be taken to ensurea good, secure connection to the conductor. Maximum screwdriver torque 3 Nm.

    3. Operation The F 660 is switched ON and OFF by means of the blue switch handle

    4. Functional testThe functional test should be repeated For the funcitonal test, the switch must be in the ON position and the white test pushbuttonmonthly pressed. The RCCB must trip immediately; the blue switch handle jumps to the lower position

    with the switch position indication "0" and the contact position indicator turns from red to green.

    5. Testing the protective measures As well as the functional test of the RCCB, the effectiveness of the protective measures shouldbe tested for compliance with the relevant specifications. The maximum permissible earthingresistances for the residual current-operated protective switching are:

    Max. Max. permissible earthingpermissible resistance with ratedtouch residual operating currentvoltage UL 30 mA 100 mA 300 mA

    25 V 833 250 8350 V 1666 500 166

    6. Cleaning RCCBs which may have become soiled during assembly work in the consumer unit can becleaned with a clamp, soapy cloth. On no account should corrosive or similar solvents be used.

    7. Faults STOTZ Residual Current-operated Circuit-Breakers are high quality RCCBs which are subjectedto careful adjustment and testing in the factory.In the event of damage (e.g. due to transport or storage) no repairs should be undertaken.If the Residual Current-operated Circuit-Breaker trips immediately when being commissioned acheck should be made for connections to earth in the downstream electrical circuits and theappliances connected to them. Any insulation faults between the neutral conductor and theprotective conductor should be eliminated.If the Residual Current-operated Circuit-Breaker does not trip during the first functional test, acheck should then be made as to whether the test circuit has been correctly connected.If the installation is correct and the RCCB continues to tr ip or if the functional test has not beensuccessful the Residual Current-operated Circuit-Breaker must be replaced.In case of opening the RCD, the right to claim under guarantee expires.

    Residual Current-operated Circuit-BreakersF 660

    S K

    0 0 2 2 Z 9 4

    S K

    0 2 7 2 Z 9 8

    S K

    0 0 1 2 Z 9 6

    S K

    0 8 9 Z 9 5

    ON OFF

    Mounting

    Dismounting

  • 7/31/2019 3089-99 RCCB F660

    9/16

    9

    Dimension drawings Dimensions in mm

    Residual Current-operated Circuit-BreakersF 660

    F 662, F 664

    F 662 F 664

    S K

    0 0 5 0 Z 9 5

    Terminal covers with mounting plate

    SK 0136 Z 96PCD 2 N PCD 4 N PCD 6 N SK 0137 Z 96 PCD 8 N SK 0138 Z 96

    Insulating enclosure

    QES 4/3 N QES 6/3 N

    S K

    0 0 7 8 Z 9 8

    S K

    0 0 7 9 Z 9 8

    S K

    0 1 5 0 Z 9 3

    Mounting rails

    DSW 4 and 6

    Type A A1DSW 1 17.5 15DSW 2 35 20DSW 3 52.5 37.5DSW 4 70 55DSW 6 105 90

  • 7/31/2019 3089-99 RCCB F660

    10/16

    10

    Residual Current-operated Circuit-BreakersExamples of protection against dangerous currentsthrough the body

    TN-S system (neutralization)Neutral and protective earth conductorseparated in the whole system.

    TN-C systemNeutral and protective earth conductor (PEN)connected together in a part of the system

    Will only be indicated by means of theinsulation monitor

    IT systemThe Residual Current-operated Circuit Breaker trips if adouble earth fault is present, e.g. earth fault 1 andearth fault 2 as shown.

    TT System

    Explanation of the symbols

    L1, L2, L3 line External conductorsPE p rotection earth Protective earth conductorN neutral Neutral conductorPEN PE and N combinedT terre Direct bond to earth

    I isulation Insulated

    C c ombined PE and N (= PEN)combined in the system

    S s eparated PE and N separated in the system

    ... are terms in the IEC recommendations

    S K

    0 0 3 9 Z 9 4

    S K

    0 0 3 8 Z 9 4

    S K

    0 0 4 0 Z 9 4

    S K

    0 0 1 7 Z 9 5

  • 7/31/2019 3089-99 RCCB F660

    11/16

  • 7/31/2019 3089-99 RCCB F660

    12/16

    12

    Residual Current-operated Circuit-BreakersSupplementary devices

    Cross Length Poles Ordering details bbn Price Weight Packingsection 40 12233 1 pc. 1 piece unitmm2 mm No. Type No. Order code EAN DM kg pcs.

    for RCCBs: Type F 662, 2-pole End caps:Type F 662, 1 Phase + N PSB-END 3

    10 213 6 x 2 SZ-PSB 53 N GH V036 0874 R0031 54940 5 0.070 0.078 30

    10 1035 29 x 2 SZ-PSB 54 N GH V036 0874 R0032 54950 4 0.320 0.403 1016 213 6 x 2 SZ-PSB 55 N GH V036 0874 R0033 54960 3 0.115 0.106 3016 1035 29 x 2 SZ-PSB 56 N GH V036 0874 R0034 54970 2 0.545 0.534 10

    Type F 664, 4-pole End caps:Type F 664, 3 Phases + N PSB-END 4

    10 213 3 x 4 SZ-PSB 61 N GH V036 0874 R0039 55020 3 0.120 0.112 3010 1035 15 x 4 SZ-PSB 62 N GH V036 0874 R0040 55030 2 0.803 0.650 10

    16 213 3 x 4 SZ-PSB 63 N GH V036 0874 R0041 55040 1 0.241 0.156 3016 1035 15 x 4 SZ-PSB 64 N GH V036 0874 R0042 55050 0 1.205 0.884 10

    Type F 664, 4-pole + MCBs S 260/70/80 End caps:Type F 664, 3 Phases + N PSB-END 3

    10 213 3x3+2x1 SZ-PSB 97 N GH V036 0875 R0025 55490 4 0.100 0.099 3010 1035 19 x 3 SZ-PSB 98 N GH V036 0875 R0026 55500 0 0.500 0.480 10

    End caps for comb-busbars blocks SZ-PSBPSB-END 5 GH L520 1921 R0005 97410 8 0.001 50PSB-END 6 GH L520 1921 R0006 97420 7 50

    PSB-END 3 GH V036 1325 R0001 55630 4 50PSB-END 4 GH V036 1325 R0002 55640 3 50

    Comb-busbars blocks

    S K

    0 0 7 4 Z 9 1

    SZ-PSB 53 N

    SZ-PSB 61 N

    SZ-PSB 97 N

    PSB-END

    F 662 with Terminal coversM 662/100

    S K

    0 0 5 7 B

    9 6

    Insulating enclosure, degree of protection IP 55Moulded plastic with double-insulation with DIN rail EN 50022 and cable entry sockets

    Design enclosed Ordering details bbn Price Weight Packingknockouts cable 40 12233 1 pc. 1 piece uniton top entryon bottom sockets Type No. Order code EAN DM kg pcs.

    Unit for 4 modules1 x Pg 21 3 x Pg 21 QES 4/3 GH L111 2304 R0003 04620 1 0,330 202 x Pg 21

    Unit for 6 modules3 x Pg 21 5 x Pg 21 QES 6/3 GH L111 2306 R0003 04630 0 0,420 12

    3 x Pg 21

    S K

    0 1 1 9 Z 9 6

    S K

    0 1 2 0 Z 9 6

    S K

    0 1 2 1 Z 9 6

    S K

    0 1 0 4 Z 9 7

  • 7/31/2019 3089-99 RCCB F660

    13/16

    13

    Residual Current-operated Circuit-BreakersF 660Supplementary devices

    Locking device for RCCB'sFor securing single- or multi-pole RCCB's against unauthorized switching on or off.For padlock with hasp diameter max. 4 mm and lock width max. 17 mm.

    Application:

    Locking b Locking against undesired switching on during maintenance workagainst b Locking with commissioning noticeswitching on: b Locking when supply is being blockedLocking b Prevention of unwanted manual switching off, e.g. of Alarm, air conditioning,against b computer installations etc.switching off: b Reclosing after tripping only allowed by authorised persons.

    Description Ordering Details bbn Price Weight Packing40 12233 1 pc. 1 piece Unit

    Type No. Order code EAN DM kg pcs.

    Adapter SA 1 GJ F110 1903 R0001 58760 5 0.004 10Padlock with 2 keys SA 2 GJ F110 1903 R0002 58770 4 0.02 10

    Adapter and padlock SA 3 GJ F110 1903 R0003 58780 3 0.05 10with 3 keys in a box

    S K

    0 0 4 8 B

    9 6

    S K

    0 1 0 8 B

    9 1

    SA 1

    S K

    0 1 0 9 B

    9 1

    SA 2

    PCD 6 N

    PCD 4 N

    S K

    0 0 7 7 B

    9 6

    PCD 2 N

    S K

    0 0 7 6 B

    9 6

    S K

    0 0 7 8 B

    9 6

    QES 4/3 N

    S K

    0 0 1 9 B

    9 8

    QES 10/3 N

    S K

    0 0 1 8 B

    9 8

    Enclosure of moulded plastic, Protection cat. IP 55Complete with mounting DIN rail EN 50 022, 35 mm and cable entry sockets.

    Design Ordering details bbn Price Weight Packingenclosed 40 12233 1 pc. 1 piece unitcableentry

    knockouts sockets Type No. Order code EAN DM kg pcs.

    Unit for 4 modules2 x 27 2 QES 4/3 N GH L111 2304 R0013 12644 0 0.370 18

    Unit for 6 modules2 x 27 2 QES 6/3 N GH L111 2306 R0013 12646 4 0.440 12

    Unit for 10 modules6 x 32 3 QES 10/3 N GH L111 2310 R0013 12650 1 0.690 10

    Terminal coverswith base plate, degree of protection IP 20Terminal cover is snapped onto the base and is sealable. The base plate has an integrated mounting rail forsnap-onequipment such as M.C.B.'s, RCD's, manual motor starters an other modular installation equipment.

    for 2 Modules PCD 2 N GH S270 1921 R0002 38530 8 1for4 Modules PCD 4 N GH S270 1921 R0004 28540 7 1for6 Modules PCD 6 N GH S270 1921 R0006 28550 6 1for8 Modules PCD 8 N GH S270 1921 R0008 28560 5 1

    Earth (PE)-bar for subsequent mounting in terminal covers PCD ...

    ES GH S270 1912 R0001 36660 6 0.08 10

    Blanking plate with half division (1 Module = 17.5 mm)BP GH S270 1913 R0001 36670 5 0.005 10

  • 7/31/2019 3089-99 RCCB F660

    14/16

    14

    Labeling accessories

    S K 0 1 2 0 B

    9 1

    ST

    Description Ordering details bbn Price Weight Packing40 12233 1 piece 1 piece unit

    Type-No. Order Code EAN DM kg pcs.

    Single labelconsisting of transparent label carrier and labelled or unlabelled etiquettes which can be plugged in. Usedfor switches, pushbuttons, indicator lights, latching relays, installation relays as well as MCB's, RCCB's and

    ABB i-bus EIB components.

    Label carrier snap-on ST GH S210 1945 R0002 13820 3 10fixingDescription label ST-E GH S210 1946 R0002 13830 2 1 sheet1 sheet = 300 pcs.Description labelnumbering 1 - 100 ST-EN GH S210 1946 R0003 64530 5 1 sheet1 sheet = 5 x 1 - 100

    ST + STE

    S K

    0 1 8 7 B

    9 1

    Label mats 40 labels labelled or unlabelled. The unlabelled can be labelled by water-resistant and permanent markeror by means of computer-controlled labelling system (plotter).

    Label SZ-KZS GH S210 1946 R0004 00850 1 30unlabelledLabel SZ-KZS/1 GH S210 1946 R0005 00860 0 30numbering 1-40Label SZ-KZS/2 GH S210 1946 R0006 00870 9 30numbering 41-80Label SZ-KZS/3 GH S210 1946 R0007 00880 8 30numbering 81-120Label SZ-KZS/4 GH S210 1946 R0008 00890 7 30numbering 121-160Label SZ-KZS/5 GH S210 1946 R0009 00900 3 30with pictograms

    Label SZ-KZS/6 GH S210 1946 R0010 05080 7 30numbering 2 x 1-20Label SZ-KZS/9 GH S210 1946 R0013 39050 7 30numbering 4 x 1-10Label SZ-KZS/10 GH S210 1946 R0014 39060 6 30numbering 4 x 11-20

    bbn-No.: 40 16779

    S K

    0 0 0 4 Z 9 4

    S K

    0 1 6 2 Z 9 3

    S K

    0 1 6 3 Z 9 3

    S K

    0 1 6 4 Z 9 3

    S K

    0 1 6 5 Z 9 3

    S K

    0 1 6 6 Z 9 3

    S K

    0 2 0 2 B

    9 3

    S K

    0 0 1 8 Z 9 4

    SZ-KZS

  • 7/31/2019 3089-99 RCCB F660

    15/16

    15

    Notes

  • 7/31/2019 3089-99 RCCB F660

    16/16

    ABB STOTZ-KONTAKT develops, manufactures and distri-butes most modern systems for the electrical buildinginstallation.

    Moreover STOTZ products are produced and distributed inmany other countries of the world through associatedcompanies and licensees.

    Under the STOTZ quality mark the company offers completebuilding installation systems:

    System pro M

    For Universal UseThe universal, modular System pro M for DIN rail installationincludes a complete range of built-in devices for protection,switching, control and monitoring functions alongside Europesbest-selling miniature circuit breakers, not to mention time-saving wiring and installation tools.

    EIB- Installation Systems

    Intelligent Installation SystemsModern programmable installation systems using bustechnology based on the European EIB-Standards.

    ABB i-bus EIB

    The system using a dedicated 2-core bus cable: the preferencefor new buildings.

    ABB Powernet EIB

    The system for building modernisation. Information transfertakes place over the existing power network.