water source system - acson international … · water source system by mcquay is the intelligent...

22
AP-MWSP-08 All Product Catalogue Water Source System

Upload: ledan

Post on 29-Jul-2018

257 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Water Source System - Acson International … · Water source system by McQuay is the intelligent choice ... or NIM PC (A/C Management ... Step Capacity Sequencing Control

AP-MWSP-08All Product Catalogue

Water Source System

Page 2: Water Source System - Acson International … · Water source system by McQuay is the intelligent choice ... or NIM PC (A/C Management ... Step Capacity Sequencing Control

CONTENTS:

Water Source SolutionAdvantage Of Water Source System ................................ 1

McQuay WSHP Working Principle .................................... 3

McQuay Water Source Products Lineup............................ 4

Split Type Product Features............................................... 4

Package Type Product Features........................................ 7

AquaPro ........................................................................... 8

Loop Water Controller ...................................................... 9

SpecificationsR410A Split Type ............................................................ S1

R22 Horizontal Water Cooled Package .......................... S4

R22 Split Type ............................................................ S5

R22 Vertical Water Cooled Package .............................. S7

Page 3: Water Source System - Acson International … · Water source system by McQuay is the intelligent choice ... or NIM PC (A/C Management ... Step Capacity Sequencing Control

MinneapolisMinneapolis

FaribaultFaribaultOwatonnaOwatonna

StauntanStauntan

Mexico CityMexico City

AuburnAuburn

CramlingtonCramlington

CecchinaCecchina SuZhouSuZhou

WuhanWuhan

ShenZhenShenZhen

Sungai BulohSungai Buloh

CikarangCikarang

Manufacturing Plant

GLOBAL DISTRIBUTION NETWORK

Americas• USA • Puerto Rico • Mexico • Paraguay • Uruguay • Guadaloupe •

Oceania• Australia • New Zealand •

Middle East & Africa• Jordan • Lebanon • Oman • Qatar • Saudi Arabia • Bahrain • Morocco • Iraq • U.A.E. •

• Mauritius • South Africa • Kenya • Madagascar • Ghana • Nigeria • Tanzania •

Europe• England • Greece • Hungary • Italy • Norway • Poland • Portugal • Russia • Spain •

• Belgium • Tunisia • Croatia • Cyprus • Lithuania • Malta • Slovenia • Ukraine •

• Turkey • Finland • Czech Republic • Romania •

Asia• Cambodia • China • Hong Kong • Indonesia • Maldives •

• Malaysia • Singapore • Thailand • Vietnam • Pakistan •

Page 4: Water Source System - Acson International … · Water source system by McQuay is the intelligent choice ... or NIM PC (A/C Management ... Step Capacity Sequencing Control

Product Overview

Model Range

Cooling Capacity (kW)

Heating Capacity (kW)

Electrical Supply

R22 MWSS 010/015/020/025 A

2.78 - 6.45

MWSS 030/040/050/060 A

Split Type Outdoor

8.21 - 15.83

R410A

R410A TandemCompressor

50Hz

Model Range

Cooling Capacity (kW)

Heating Capacity (kW)

Electrical Supply

R22

MWM-G MCK-A

R410A

R410A TandemCompressor

50Hz

2.37 - 7.45 4.68 - 15.08

2.58 - 7.45 4.83 - 15.96

Page 5: Water Source System - Acson International … · Water source system by McQuay is the intelligent choice ... or NIM PC (A/C Management ... Step Capacity Sequencing Control

Split Type Outdoor Package Type

MWV 015/020/025/030/040/050 A/AR

MWH 011/012/015/020/025/030/040/050/060/070 B/BR

2.37 - 15.77 10.84 - 15.53

M5WST 040/050/060 AR

3.30 - 22.40 4.20 - 14.00

2.58 - 17.00 11.72 - 16.71 3.7 - 22.40 4.50 - 15.50

M5WSS 007/010/015/016/020/025/030/040/050/060 AR

MCK-C MCC-C MCE-E

Split Type Indoor

2.34 - 6.44 2.37 - 15.77 5.54 - 6.98

2.34 - 6.64 2.58 - 17.00

Page 6: Water Source System - Acson International … · Water source system by McQuay is the intelligent choice ... or NIM PC (A/C Management ... Step Capacity Sequencing Control

Water source system by McQuay is the intelligent choice for lower costs while creating a comfortable work environment in today's office buildings.

The system utilises space-saving concepts that are interconnected by way of water loop rather than ductwork. No chiller, or air handler room is required. And unlike most other systems, McQuay water source heat pump systems actually recover energy that would otherwise be wasted and put it to work in other areas throughout the building.

The result of this design is more than just quiet, comfortable performance for tenants but it translates into greater cost efficiencies for building owners and property managers on four vital levels:

• Improved energy efficiency for lower operating costs.• Lower maintenance costs.• Easier, lower initial installation and expansion cost• Zoned comfort & control• Independent accountability

Advantage Of Water Source System

1

Lower Maintenance CostMcQuay water source product series has been designed with easier accessability, especially to the compressor, blower and control section. Removable top & side panel has greatly reduce the time required in any maintenance work.

MWH (Packaged) MWSS & M5WSS (Split)

Page 7: Water Source System - Acson International … · Water source system by McQuay is the intelligent choice ... or NIM PC (A/C Management ... Step Capacity Sequencing Control

Zoned Comfort & ControlMcQuay WSHP sytem provides space heating and space cooling for a large number of individual building zones such as individual dwelling units in a multi- units bulding. Individual MWSP are installed in each space or zone and are connected to a single circulating water loop.

Each of McQuay water source product is equipped by an individual room sensor and a temperature controller, which is used to monitor the different set temperature in a building. Unit will stop operation in case it has achieved the set temperature and it doesn’t affect the operation of other units even in the same system.

In addition to the control, McQuay split type WSP (MWSS & M5WSS series) can be monitored and controlled centrally by using Smart Manager (centrel controller) or NIM PC (A/C Management System).

Variety Of Product Combination Of The Split Type MWSS & M5WSSThe compact, lower profile cabinet as well as variety of indoor, outdoor combination make it easier to fix specific architechure and potential design construction of the building, or replacement application space requirement.

2

WSS & M5WSS System (Split)

MWH (Packaged)

Easier, Lower Initial Installation And Expansion CostLeft or right return piping and various ducting discharge configuration (horizontal unit) has contributed in towards optimizing job layouts with minimum ductwork and piping.

MWV

Page 8: Water Source System - Acson International … · Water source system by McQuay is the intelligent choice ... or NIM PC (A/C Management ... Step Capacity Sequencing Control

One advantage of water source system is either the split type or package type WSHP is normally concealed above the ceilling.

Each unit is connected to two hydronic pipes which receive and discharge water at two different temperature. The piping is integrated with the heat rejection equipment (cooling tower or dry cooler), and heat addition equipment (Boiler). Water is then circulating in the a closed water loop once a pump is switched on.

PumpsBoiler

WSHP

Bo

iler

Dry Cooler / Cooling Tower

Expansion Tank / Air Separator

Expansion Tank

Plate-And-FrameHeat Exchanger

WaterDistribution

Loop

McQuay WSHP Working Principle

Independent AccountabilityAs WSHP is installed independently in separate zone. Hence, each zone is accounted individually by its power consumption. This benefit is mostly exploited in application such as hotels, rented locations, and shopping complex as the owner of the building does not need to pay electricity bill for whole building.

3

Simultanueous Cooling & HeatingDifferent from the conventional air conditioning system, McQuay WSHP is able to perform both cooling and heating to a building simultanueously.

The primary advantage during this mode is to save the energy by reducing the operating time of the cooling tower and boiler, where heat dissipated by cooling mode unit will be transferred to the usage of heating operating mode unit. This is greatly reduce the operating cost of a water source system.

Page 9: Water Source System - Acson International … · Water source system by McQuay is the intelligent choice ... or NIM PC (A/C Management ... Step Capacity Sequencing Control

McQuay Water Source Products Lineup

Split Type Product Features

Getting the right level of comfort can be much less expensive than widely imagined, or at least less costly than makeshift or non-intergrated solutions.

Therefore, instead of independent product lineup, McQuay is prioritizing the complete McQuay Water Source Solution, which inclusive of series of products, AquaPro Selection software and last but not least, the Loop Water Controller in order to achieve the desired comfort level at minimal cost.

For this moment, McQuay is having a water source product series including split type and package type. In addition split type unit, various aesthetically attractive indoor units is also ready to suit to most of the interior design.

Quick overview of Product Specifications;

Higher Energy Efficiency RatingThe water condensation, the ability to recover and to move energy where required and the quality of components being used are among the key elements making the M5WSS and M5WST one of the most efficient systems now available in the market.

Split Type Indoor:

Model Refrigerant No.of Compressor Indoor

MWSS R22 1 MWM-G, MCE-E, MCC-C, MCK-A, MCK-C

M5WSS R410A 1 MWMWS-GR, MCCWS-CR, MCKWS-AR, MCKWS-CR

M5WST R410A 2 MWMWS-CR

Package Type Indoor:

Model Refrigerant Discharge

MWH R22 Horizontal Type

MWV R22 Vertical Type

4

Page 10: Water Source System - Acson International … · Water source system by McQuay is the intelligent choice ... or NIM PC (A/C Management ... Step Capacity Sequencing Control

Quiet DesignQuiet performance was a key developement criteria and now an unrivaled strength of McQuay WSP split. The design of the unit allows to achieve lower sound emission & vibration values: all cabinet lined with sound-proof insulation, with rotary & scroll compressors installed on the innovative double isolated anti vibration base pan.

Maximum Installation FlexibilityThe inherent characteristics of the split configuration allows to:

Install the units at the most convenient position thus minimizing costs and installation time as well as maintaining easy access for the future service operation.

Fit the unit with reduction of space utilization due to compactness size.

Technical Closet

False Closet

Wide Range Of Indoor OptionsVariety of combinations are available to be coupled with the condensing unit: wall mounted, cassette and ducted. This has enhance the possibility of with ceiling cassette, wall mounted and ducted indoor unit to choose from, various combination possibility has offered the better solution to blend into any architectural design and to meet any restriction.

Previous Series > 50% More Compact

5

Page 11: Water Source System - Acson International … · Water source system by McQuay is the intelligent choice ... or NIM PC (A/C Management ... Step Capacity Sequencing Control

Part Loading Capability (Only for M5WST- Tandem Compressor Series)Compared to M5WSS series, M5WST series is having a part loading capability during the low load situation as it has tandem compressor configuration, which resulting in better SEER.

R410A RefrigerantIn line with Montreal Protocol M5WSS/M5WST series utilise the new R410A refrigerant.

NIM (Network Interface Module), Smart Manager & NIM PCCommunication among indoor units of M5WSS & M5WST can be centralised by using the Smart Manager, or NIM PC through the NIM Bus.

Smart Manager• Up to 120 units of indoor units is able to be linked together by using NIM Bus

NIM PC• Up to 256 units of indoor units is able to be linked together by using NIM Bus

Among the control parameters that being included in both centralised controller are;• Fan Speed• Set Temperature• Room Temperature• Operating Mode• On / Off Status

6

NIM PCGateway

Control Panel Control Panel Control Panel Control Panel

5WSS IndoorMain Board

Master 0 Sleeve 1 to 15

NIM Bus

Master 1 Master N

NIM 5WSS IndoorMain Board

NIMNIM 5WSS IndoorMain Board

5WSS IndoorMain Board

Group 0 Group 1 Group N

NIMNIM NIMNIM

Page 12: Water Source System - Acson International … · Water source system by McQuay is the intelligent choice ... or NIM PC (A/C Management ... Step Capacity Sequencing Control

Double Isolation PanelThe complete series of MWH is using innovative double isalotion anti vibration base pan to reduce the compressor's vibration.

No Outdoor UnitThe packaged design concept eliminates the need for a separate outdoor unit. Also, the tube in tube heat exchangers in the MWH range do not need a fan to transfer heat load, resulting in a much quiet environment for building occupants.

Package Type Product Features

Packaged Unit. Compact & Low Height ProfileThe McQuay MWH series of horizontal water source heat pumps is a packaged unit consisting of compressor (2 off in MWH025 and above) coil, tube in tube heat exchanger, expansion device and forward curved centrifugal blower.

All units in this series is designed with low height profile, ranging from an amazing 250mm for the MWH011B/BR, which has a horizontal compressor, to the tallest unit, 500mm. 500070

475060

440050

440040

370030

340025

353020

337015

325012

250011

Height (mm)MWH-

Table 1

MWH

Operating Mode Entering Water Temperature

Cooling 13°C ≤ EWT ≤ 40°C

Heating 10°C ≤ EWT ≤ 32°C

Table 2

Application FlexibilityThe McQuay MWH B/BR series has a wider range of operational temperatures. This offer more flexibility to meet different applications requirement. The entering water temperatures can be adjusted as set out in table 2.

AccessoriesFlexible hose and spring mounting kit is offered as an optional accessories to minimize the viration in any field application.

50

0

100

Comp. Loading %

Step Capacity

Sequencing ControlFor MWH025B/BR to MWH070B/BR, the compressors are able to operate in sequencing mode. This will allow both compressors to cut in and out according to their accumulative operating times, which improves the compressor life span and reliability in results.

Partial Loading CapabilityFor MWH025B/BR to MWH070B/BR, which are having two compressors in their system, the capacity loading of compressors are able to controlled at 50% or 100%.

7

Page 13: Water Source System - Acson International … · Water source system by McQuay is the intelligent choice ... or NIM PC (A/C Management ... Step Capacity Sequencing Control

In addition to the water source product lineup, McQuay also provide you the AquaPro – selection software as it quicken the selection process.

User friendly screen interface, variety selection criteria, and broad printout data is the key advantage of this selection software as it is targeted to provide a better solution in any water source system application.

AquaPro

MWV

Flexible Installation.McQuay vertical water cooled package is designed for ease and flexiblility during installation, where its physical size of the unit is specially designed to achieve better space saving.

Easier In Service and Maintenance The structural design with more than one service panel contributes to easier work if there is any troubleshooting at site.

IC Remote ControlMWV unit is controlled by an IC Remote Controller. Individual thermal comfort is controlled precisely by the built in algorithm via this controller.

8

MWV

Page 14: Water Source System - Acson International … · Water source system by McQuay is the intelligent choice ... or NIM PC (A/C Management ... Step Capacity Sequencing Control

Other than products, and selection software, the newly developed water source system controller, Loop Water Controller has been introduced particularly to provide a system control feature for all water source heat pump equipments and an external control for the heat addition, heat rejection, as well as pump operation of any closed loop water source system.

Loop Water Controller is a stand alone device, mainly used to supervise the pump operation, as well as justifying number of either boiler or cooling tower to be switched on in order to achieve the load requirement of a multi stories building.

Loop Water Controller

Features:

Auto Lead & Lag Pump Control

Heat Addition or Heat Rejection Temperature Control Funtion

Emergency Protection – Low Supply Temperature, Loss of Waterflow, and Sensor Error

Manual Control System Simulation or Self Diagnostic

Error Code Define and Failure History Storage

Pump Switching Function

Temperature Display in degree F or degree C

Visible LED’s for alarm and emergency shutdown status

Alarm Buzzer located in LWC Panel

Remote Alarm Silence Capability

12 configurable outputs for heat add or heat reject stages

LED for each output relay to display status

Password Protection.

In short, McQuay Loop Water Controller has been designed to maximize the flexibility of installation, where contractor can easily select, install and commission a control system with all the provided sensor, relays and devices.

TANK

CONTROL ROOM

9

Page 15: Water Source System - Acson International … · Water source system by McQuay is the intelligent choice ... or NIM PC (A/C Management ... Step Capacity Sequencing Control

S1S1

M5WSS025AR - M5WSS060AR (Coupled With Ceilling Concealed)

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - INDOOR 27.0ºC DB / 19.0ºC WB; ENTERING WATER TEMPERATURE 30.0ºC, LEAVING WATER TEMPERATURE 35.0ºC b) HEATING - INDOOR 20.0ºC DB; ENTERING WATER TEMPERATURE 20.0ºC3) EFFECTIVE POWER INPUT IS USED IN THE RATED EER/COP CALCULATION, ACCORDING TO ISO STANDARD: ISO 5151 & ISO 13253.4) THE SOUND LEVEL ARE MEASURED IN AN ANECHOIC CHAMBER.

M5WSS007AR - M5WSS020AR (Coupled With Ceilling Concealed)

R410A Split Type Specifications

EXTERNAL STATIC PRESSURE (H/M/L)

UNIT WEIGHT

PIPE CONNECTION

UNIT WEIGHT

OU

TD

OO

R U

NIT

WATER FLOW RATE

WATER PRESSURE DROP

SOUND PRESSURE LEVEL

UNIT DIMENSION

SOUND PRESSURE LEVEL (H/M/L)

UNIT DIMENSION

REFRIGERANT TYPE / CONTROL

IND

OO

R U

NIT

CONTROL

AIR FLOW

EER

COP

POWER SOURCE

NOMINAL COOLING CAPACITY

NOMINAL HEATING CAPACITY

NOMINAL TOTAL INPUT POWER (COOLING)

NOMINAL TOTAL INPUT POWER (HEATING)

MODELM5CCWS020CR

M5WSS020AR

20500

6010

23000

6740

1505

1655

4.09

4.16

22 / 49

0.35 / 1.25

14.54

37

49 / 108

360 / 14.2

38 / 36 / 34

1065 / 41.9

293 / 620

330 / 700

321 / 680

M5CCWS020CR

M5WSS016AR

15800

4630

15800

4630

1115

1075

4.29

4.45

22 / 49

0.26 / 0.95

10.35

34

40 / 88

12.7 / 1/2

220-240 / 1 / 50

M5CCWS015CR

M5WSS015AR

12200

3580

12800

3750

1012

1002

3.62

3.83

241 / 510

208 / 440

170 / 360

37 / 34 / 29

21 / 46

0.21 / 0.75

8.12

30

36 / 78

FLARE VALVE

6.4 / 1/4

774 / 30.5

280 / 11.0

411 / 16.2

261 / 10.3

49 / 39 / 29 (0.2 / 0.2 / 0.1)

R410A / OUTDOOR CAPTUBE

DUCTED

SLM WIRED HANDSET

330 / 13.0

M5WSS010AR

10000

2930

10500

3080

707

727

4.25

4.34

0.14 / 0.51

5.88

31

35 / 77

765 / 30.1

9.5 / 3/8

17 / 38

33 / 30 / 26

104 / 220

142 / 300

123 / 260

220-240 / 1 / 50

M5CCWS010CR

M5WSS007AR

8100

2370

8800

2580

567

577

4.31

4.61

0.13 / 0.45

5.36

30

300 / 11.8

33 / 73

Btu/h

W

Btu/h

W

W

W

W/W

W/W

V/Ph/Hz

l/s / CFM

l/s / CFM

l/s / CFM

Pa (in.wg.)

dBA

mm/in

mm/in

mm/in

kg/lb

l/s / m3/hkPa

dBA

mm/in

mm/in

mm/in

kg/lb

mm/in

mm/inSIZE

WIDTH

DEPTH

HEIGHT

HEIGHT

WIDTH

DEPTH

LOW

HIGH

MEDIUM

AIR DISCHARGE

OPERATION

INDOOR UNIT

OUTDOOR UNIT

LIQUID

GAS

TYPE

EXTERNAL STATIC PRESSURE (SH/H/M/L)

UNIT WEIGHT

OU

TD

OO

R U

NIT

WATER FLOW RATE

WATER PRESSURE DROP

SOUND PRESSURE LEVEL

UNIT DIMENSION

UNIT WEIGHT

PIPE CONNECTION

SOUND PRESSURE LEVEL (SH/H/M/L)

UNIT DIMENSION

REFRIGERANT TYPE/ CONTROL

IND

OO

R U

NIT

CONTROL

AIR FLOW

COP

POWER SOURCE

NOMINAL HEATING CAPACITY

NOMINAL TOTAL INPUT POWER (COOLING)

NOMINAL TOTAL INPUT POWER (HEATING)

EER

MODEL

NOMINAL COOLING CAPACITY

M5CCWS060CR

M5WSS060AR

53800

15770

58000

17000

4191

3891

4.10

4.79

779 / 1650

722 / 1530

675 / 1430

609 / 1290147/127/98/88 (0.6/0.5/0.4/0.4)

55 / 53 / 50 / 47

1499 / 59.0

62 / 1370.88 / 3.17

18.84

40

123 / 272

504 / 19.8

1020 / 40.2

648 / 25.5

378 / 14.9

541 / 21.3

M5CCWS050CR

M5WSS050AR

50000

14650

51000

14950

3611

3551

4.43

4.60

750 / 1590651 / 1380

604 / 1280

571 / 1210

147/127/98/49 (0.6/0.5/0.4/0.2)

53 / 52 / 50 / 47

1299 / 51.1

54 / 119

0.71 / 2.55

9.59

47

120 / 264

19.1 / 3/4

380-415 / 3 / 50

9.5 / 3/8

R410A / OUTDOOR TXV

M5CCWS040CR

M5WSS040AR

39500

11580

40500

11870

2933

2923

4.37

4.50

519 / 1100 500 / 1060

467 / 990

425 / 900

51 / 49 / 45 / 41

1045 / 41.1

42 / 93

0.58 / 2.10

9.49

40

440 / 17.3

1020 / 40.2

549 / 21.6

96 / 211

FLARE VALVE

206/177/127/88 (0.8/0.7/0.5/0.4)

DUCTED

SLM WIRED HANDSET

541 / 21.3

378 / 14.9

M5CCWS030CR

M5WSS030AR

30500

8940

31000

9090

2322

2402

4.26

4.17

406 / 860

378 / 800

340 / 720

321 / 680

49 / 46 / 42 / 38

929 / 36.6

39 / 86

0.5 / 1.80

30.59

38

385 / 15.2

844 / 33.2

418 / 16.5

64 / 141

15.9 / 5/8

220-240 / 1 / 50

M5CCWS025CR

M5WSS025AR

26000

7620

28000

8210

1596

1746

4.92

4.83

R410A / OUTDOOR CAPTUBE

NA

345 / 730

340 / 720

274 / 580

55 / 39 / 29 (0.22 / 0.16 / 0.12)

40 / 39 / 36

261 / 10.3

1200 / 47.2

411 / 16.2

25 / 55

0.39 / 1.40

19.03

37

360 / 14.2

774 / 30.5

280 / 11.0

50 / 110

6.35 / 1/4

Btu/h

W

Btu/h

W

W

W

W/W

W/W

V/Ph/Hz

l/s / CFM

l/s / CFM

l/s / CFM

l/s / CFM

Pa (in.wg.)

dBA

mm/in

mm/in

mm/in

kg/lb

l/s / m3/h

kPa

dBA

mm/in

mm/in

mm/in

kg/lb

mm/in

mm/inSIZE

WIDTH

DEPTH

HEIGHT

TYPE

WIDTH

DEPTH

HEIGHT

HIGH

MEDIUM

LOW

AIR DISCHARGE

OPERATION

SUPER HIGH

INDOOR UNIT

OUTDOOR UNIT

LIQUID

GAS

Page 16: Water Source System - Acson International … · Water source system by McQuay is the intelligent choice ... or NIM PC (A/C Management ... Step Capacity Sequencing Control

S2

Btu/h

W

Btu/h

W

W

W

W/W

W/W

V/Ph/Hz

l/s / CFM

l/s / CFM

l/s / CFM

dBA

mm/in

mm/in

mm/in

kg/lb

l/s / m3/h

kPa

dBA

mm/in

mm/in

mm/in

kg/lb

LIQUID mm/in

GAS mm/in

UNIT WEIGHT

PIPE CONNECTION

TYPE

SIZE

DEPTH

UNIT WEIGHT (UNIT + PANEL)

OU

TD

OO

R U

NIT

WATER FLOW RATE

WATER PRESSURE DROP

SOUND PRESSURE LEVEL

UNIT DIMENSION

HEIGHT

WIDTH

UNIT DIMENSION ( )- With Panel

HEIGHT

WIDTH

DEPTH

LOW

SOUND PRESSURE LEVEL (H/M/L)

IND

OO

R U

NIT

CONTROLAIR DISCHARGE

OPERATION

AIR FLOW

HIGH

MEDIUM

REFRIGERANT TYPE / CONTROL

EER

COP

POWER SOURCE

NOMINAL COOLING CAPACITY

NOMINAL HEATING CAPACITY

NOMINAL TOTAL INPUT POWER (COOLING)

NOMINAL TOTAL INPUT POWER (HEATING)

MODELINDOOR UNIT

OUTDOOR UNIT

M5CKWS050AR

M5WSS050AR

51500

15080

54500

15958

3333

3273

4.52

4.88

491 / 1040

448 / 950

411 / 870

53 / 52 / 50

40 + 4 / 88 + 9

0.71 / 2.55

9.59

47

504 / 19.8

648 / 25.5

120 / 264

19.1 / 3/4

1020 / 40.2

380 - 415 / 3 / 50

R410A / OUTDOOR CAPTUBE & TXV

M5CKWS040AR

M5WSS040AR

38500

11273

41500

12152

2669

2659

4.22

4.57

467 / 990

406 / 860

359 / 760

51 / 48 / 46

38 + 4 / 84 + 9

0.58 / 2.10

9.49

40

440 / 17.3

549 / 21.6

96 / 211

9.5 / 3/8

M5CKWS030AR

M5WSS030AR

30000

8784

31000

9077

2120

2200

4.14

4.13

415 / 880

349 / 740

321 / 680

49 / 45 / 43

35 + 4 / 77 + 9

0.5 / 1.80

30.59

38

385 / 15.2

844 / 33.2

418 / 16.5

64 / 141

FLARE VALVE

335 (363) / 13.2 (14.3)

820 (930) / 32.2 (36.6)

820 (930) / 32.2 (36.6)

4 WAY AUTOMATIC LOUVER (UP & DOWN)

WIRELESS OR WIRED MICROCOMPUTER REMOTE CONTROL

220 - 240 / 1 / 50

M5CKWS025AR

M5WSS025AR

25000

7320

25500

7467

1582

1732

4.63

4.31

368 / 780

311 / 660

283 / 600

45 / 42 / 40

32 + 4 / 71 + 9

0.39 / 1.40

19.03

37

50 / 110

15.9 / 5/8

M5WSS020AR

20000

5856

20500

6003

1492

1642

3.92

3.66

R410A / OUTDOOR CAPTUBE

0.35 / 1.25

14.54

37

49 / 108

6.4 / 1/4

774 / 30.5

280 / 11.0

360 / 14.2

31 + 4 / 68 + 9

297 / 630

283 / 600

42 / 39 / 37

349 / 740

220-240 / 1 / 50

M5CKWS020AR

M5WSS016AR

16000

4685

16500

4831

1102

1062

4.25

4.55

0.26 / 0.95

10.35

34

40 / 88

12.7 / 1/2

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - INDOOR 27.0ºC DB / 19.0ºC WB; ENTERING WATER TEMPERATURE 30.0ºC, LEAVING WATER TEMPERATURE 35.0ºC b) HEATING - INDOOR 20.0ºC DB; ENTERING WATER TEMPERATURE 20.0ºC3) ALL SPECIFICATIONS ARE TENTATIVE SPECIFICATIONS AT THE TIME OF PRINTING. PLEASE CONSULT YOUR DEALER FOR CONFIRMATION.4) THE SOUND LEVEL ARE MEASURED IN AN ANECHOIC CHAMBER.

M5WSS007AR - M5WSS020AR (Coupled With Ceilling Cassette C Series)

R410A Split Type Specifications

M5WSS016AR - M5WSS050AR (Coupled With Ceilling Cassette A Series)

S2

Btu/h

W

Btu/h

W

W

W

W/W

W/W

V/Ph/Hz

l/s / CFM

l/s / CFM

l/s / CFM

dBA

mm/in

mm/in

mm/in

kg/lb

l/s / m3/h

kPa

dBA

mm/in

mm/in

mm/in

kg/lb

LIQUID mm/in

GAS mm/inSIZE

UNIT WEIGHT

PIPE CONNECTION

TYPE

DEPTH

UNIT WEIGHT (UNIT + PANEL)

OU

TD

OO

R U

NIT

WATER FLOW RATE

WATER PRESSURE DROP

SOUND PRESSURE LEVEL

UNIT DIMENSION

HEIGHT

WIDTH

SOUND PRESSURE LEVEL (H/M/L)

UNIT DIMENSION( )- With Panel

HEIGHT

WIDTH

DEPTH

MEDIUM

LOW

REFRIGERANT TYPE / CONTROL

IND

OO

R U

NIT

CONTROLAIR DISCHARGE

OPERATION

AIR FLOW

HIGH

COP

POWER SOURCE

NOMINAL HEATING CAPACITY

NOMINAL TOTAL INPUT POWER (COOLING)

NOMINAL TOTAL INPUT POWER (HEATING)

EER

MODELINDOOR UNIT

OUTDOOR UNIT

NOMINAL COOLING CAPACITY

M5CKWS020CR

M5WSS020AR

22000

6442

22000

6642

1414

1763

4.56

3.77

220 - 240 / 1 / 50

212 / 450

203 / 430

194 / 410

47 / 46 / 44

23 + 2 / 50.7 + 4.4

0.35 / 1.25

14.54

37

360 / 14.17

764 / 30.08

280 / 11.02

49.1/ 108.25

FLARE VALVE

M5CKWS020CR

M5WSS016AR

16500

4831

16500

4831

1011

1090

4.78

4.43

212 / 450

203 / 430

194 / 410

47 / 46 / 44

23 + 2 / 50.7 + 4.4

0.26 / 0.95

10.35

34

360 / 14.17

39.7 / 87.52

12.7 / 1/2

FLARE VALVE

764 / 30.08

280 / 11.02

220 - 240 / 1 / 50

M5CKWS015CR

M5WSS015AR

12500

3660

12000

3514

932

849

3.93

4.14

194 / 410

184 / 390

170 / 360

44 / 42 / 41

23.2 / 50.7 + 4.4

0.21 / 0.75

8.12

32

330 / 12.99

35.5/ 78.26

6.35 / 1/4

250 (295) / 9.8 (11.6

570 (640) / 22.4 (25.2)

570 (640) / 22.4 (25.2)

R410A / OUTDOOR CAP. TUBE

4 WAY AUTOMATIC LOUVER (UP & DOWN)

WIRELESS OR WIRED MICROCOMPUTER REMOTE CONTROL

M5CKWS010CR

M5WSS010AR

10000

2928

10000

2928

645

657

4.54

4.46

0.14 / 0.51

5.88

31

330 / 12.99

34.9 / 76.94

9.52 / 3/8

FLARE VALVE

280 / 11.02

22 + 2 / 48.5 + 4.4

764 / 30.08

44 / 43 / 42

189 / 400

184 / 390

175 / 370

220 - 240 / 1 / 50

M5CKWS010CR

M5WSS007AR

8000

2342

8000

2342

505

508

4.64

4.61

0.13 / 0.45

5.36

30

300 / 11.81

32.9/ 72.53

Page 17: Water Source System - Acson International … · Water source system by McQuay is the intelligent choice ... or NIM PC (A/C Management ... Step Capacity Sequencing Control

M5WST040AR - M5WST060AR (Coupled With Ceilling Concealed)

M5CCWS050CR

M5WST050AR

Btu/h 46000W 13480

Btu/h 50000W 14650W 4500

W 4150W/W 3.0

W/W 3.5

V/Ph/Hz

l/s / CFM 750 / 1590

l/s / CFM 651 / 1380

l/s / CFM 604 / 1280

l/s / CFM 571 / 1210

EXTERNAL STATIC PRESSURE (SH/H/M/L) Pa / in.wg

dBA

mm/in

mm/in 1299 / 51.14

mm/in

kg/lb 50 / 110.23

l/s / m3/h 0.81 / 2.9

kPa 15.50dBA 42

mm/inmm/inmm/inkg/lb

LIQUID mm/inGAS mm/in

WIDTH 1014 / 40.0

UNIT WEIGHT

SOUND PRESSURE LEVEL (SH/H/M/L)

EER

COP

WATER FLOW RATE

WATER PRESSURE DROPSOUND PRESSURE LEVEL

UNIT DIMENSIONHEIGHT

DEPTHUNIT WEIGHT

UNIT DIMENSION

HEIGHT 378 / 14.88WIDTH

DEPTH 541 / 21.30

LOW

CONTROLAIR DISCHARGE DUCTED

OPERATION SLM WIRED HANDSET (OPTIONAL AC5300 REMOTE CONTROLLER)

AIR FLOW

S.HIGHHIGH

MEDIUM

380-415 / 3 / 50

REFRIGERANT TYPE / CONTROL R410A / CAP. TUBE & TXV

POWER SOURCE

NOMINAL TOTAL INPUT POWER (HEATING)

NOMINAL COOLING CAPACITY

NOMINAL HEATING CAPACITY

NOMINAL TOTAL INPUT POWER (COOLING)

MODELINDOOR UNIT

OUTDOOR UNIT

PIPE CONNECTIONTYPE FLARE VALVE

SIZE9.52 / 3/8

15.88 / 5/8

IND

OO

R U

NIT

OU

TD

OO

R U

NIT

M5CCWS040CR

M5WST040AR

37000

10840

40000

117203403

36133.2

3.2

519 / 1100

500 / 1060

467 / 990

425 / 900

(206/176/127/88) / (0.83/0.71/0.51/0.35)

51 / 49 / 45 / 41

1045 / 41.14

44 / 97

0.64 / 2.3

12.0340

440 / 17.3

549 / 21.6105.0 / 231.0

648 / 25.5

504 / 19.8

53 / 52 / 50 / 47

(176/157/137/108) / (0.71/0.63/0.55/0.43)

134.0 / 294.8

M5CCWS060CR

M5WST060AR

53000

15530

5700016710

4691

4591

3.3

3.6

779 / 1650

722 / 1530

675 / 1430

609 / 1290

1499 / 59.02

56 / 123.46

0.96 / 3.45

22.2141

19.05 / 3/4

S3

R410A Split Type Specifications

M5WSS007AR - M5WSS025AR (Coupled With Wall Mounted)

IND

OO

R U

NIT

OU

TD

OO

R U

NIT

M5WMWS010GR M5WMWS015AR M5WMWS020AR M5WMWS020GR M5WMWS025GR

M5WSS010AR M5WSS015AR M5WSS016AR M5WSS020AR M5WSS025AR

Btu/h 10000 12000 15400 20000 25000

W 2930 3443 4505 5848 7450

Btu/h 10500 12800 14800 21000 25000

W 3080 3750 4327 6298 7448

W 668 945 1030 1420 1513

W 688 935 990 1570 1663

W/W 4.39 3.64 4.37 4.12 4.92

W/W 4.48 4.01 4.37 4.01 4.48

V/Ph/Hz

l/s / CFM 163 / 345 397 / 630

l/s / CFM 135 / 285 231 / 490

l/s / CFM 104 / 220 208 / 440

dBA 42 / 36 / 29 49 / 44 / 42

mm/in

mm/in

mm/in

kg/lb 12 / 26.46

l/s / m3/h 0.14 / 0.51 0.21 / 0.75 0.26 / 0.95 0.35 / 1.25 0.39 / 1.40

kPa 5.88 8.12 10.35 14.54 19.03

dBA 31 32 34

mm/in 330 / 12.99 330 / 12.99 360 / 14.17

mm/in

mm/in

kg/lb 34.9 / 76.94 35.5 / 78.26 39.7 / 87.52 49.1 / 108.25 50 / 110.23

LIQUID mm/in

GAS mm/in 15.88 /5/812.7 / 1/2

764 / 30.08 764 / 30.08

280 / 11.02 280 / 11.02

FLARE VALVE

6.35 / 1/4

DOUBLE LOUVER (UP & DOWN) & GRILLE (LEFT & RIGHT)

304 / 12.0

1062 / 41.8

222 / 8.7

37

360 / 14.17

16 / 35.27

WIRELESS OR WIRED MICROCOMPUTER REMOTE CONTROL

9.52 / 3/8

WIDTH

DEPTH

UNIT DIMENSION

HEIGHT

WATER PRESSURE DROP

SIZE

UNIT WEIGHT

UNIT WEIGHT

PIPE CONNECTION

TYPE

WATER FLOW RATE

SOUND PRESSURE LEVEL

SOUND PRESSURE LEVEL (H/M/L)

UNIT DIMENSION

HEIGHT 260 / 10.2

WIDTH 899 / 35.4

DEPTH 198 / 7.8

AIR FLOW

HIGH

MEDIUM

LOW

COP

POWER SOURCE

REFRIGERANT TYPE / CONTROL

220-240 / 1 / 50

R410A / OUTDOOR CAP. TUBE

NOMINAL HEATING CAPACITY

NOMINAL TOTAL INPUT POWER (COOLING)

NOMINAL TOTAL INPUT POWER (HEATING)

EER

MODELINDOOR UNIT

OUTDOOR UNIT

NOMINAL COOLING CAPACITY

12 / 26.46

764 / 30.08

280 / 11.02

CONTROLAIR DISCHARGE

OPERATION

142 / 300

118 / 250

94 / 200

39 / 34 / 28

160 / 340

193 / 410

231 / 490

43 / 39 / 36

M5WMWS010GR

M5WSS007AR

8094

2370

8800

2580

528

538

4.49

4.80

0.13 / 0.45

5.36

30

300 / 11.81

32.9 / 72.53

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - INDOOR 27.0°C DB / 19.0°C WB; ENTERING WATER TEMPERATURE 30.0°C, LEAVING WATER TEMPERATURE 35.0°C b) HEATING - INDOOR 20.0°C DB; ENTERING WATER TEMPERATURE 20.0°C3) ALL SPECIFICATIONS ARE TENTATIVE SPECIFICATIONS AT THE TIME OF PRINTING. PLEASE CONSULT YOUR DEALER FOR CONFIRMATION.4) THE SOUND LEVEL ARE MEASURED IN AN ANECHOIC CHAMBER.

Page 18: Water Source System - Acson International … · Water source system by McQuay is the intelligent choice ... or NIM PC (A/C Management ... Step Capacity Sequencing Control

S4

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - INDOOR 27.0°C DB / 19.0°C WB; ENTERING WATER TEMPERATURE 30.0°C, LEAVING WATER TEMPERATURE 35.0°C b) HEATING - INDOOR 20.0°C DB; ENTERING WATER TEMPERATURE 20.0°C3) ALL SPECIFICATIONS ARE TENTATIVE SPECIFICATIONS AT THE TIME OF PRINTING. PLEASE CONSULT YOUR DEALER FOR CONFIRMATION.4) THE SOUND LEVEL ARE MEASURED IN AN ANECHOIC CHAMBER.

MWH011BR MWH012BR MWH015BR MWH020BR MWH025BR MWH030BR MWH040BR MWH050BR MWH060BR MWH070BR

Btu/h 11300 11700 14400 19500 25500 29920 44870 49880 63160 76460

W 3300 3400 4200 5721 7400 8800 13200 14600 18500 22400

Btu/h 12800 12350 14800 17000 28700 31600 51520 56500 68140 76460

W 3700 3600 4300 4980 8400 9300 15100 16600 20000 22400

W 790 775 1210 1661 1894 2485 3897 4482 5505 6041

W 745 745 1119 1361 1844 2533 3995 4433 5846 6236

W/W 4.17 4.38 3.49 3.69 3.91 3.54 3.39 3.26 3.36 3.71

W/W 4.97 4.83 3.91 3.98 4.56 3.67 3.78 3.74 3.42 3.59

V/Ph/Hz

l/s / CFM 222 / 470 287 / 600 415 / 870 450 / 940 625 / 1325 710 / 1470 900 / 1910 915 / 1940

Pa (in.wg.) 60 (0.24) 120 (0.48) 129 (0.52) 190 / 0.76 270 / 1.08 290 / 1.16 210 / 0.84 270 / 1.08

dBA 42 37 41 45 47 51 53 53

l/s / m3/h 0.17 / 0.60 0.21 / 0.75 0.25 / 0.90 0.29 / 1.05 0.47 / 1.70 0.47 / 1.70 0.71 / 2.54 0.81 / 2.91 1.01 / 3.63 1.24 / 4.45

kPa 6.70 8.20 9.80 11.60 22.00 4.25 21.30 33.00 40.00 58.00

mm/in 250 / 9.80 325 / 12.80 337 / 13.3 353 / 13.9 340 / 13.4 370 / 14.6 434 / 17.1 434 / 17.1 500 / 19.7 500 / 19.7

mm/in 1040 / 40.90 1035 / 40.70 1074 / 42.3 1183 / 46.6 1328 / 52.3 1297 / 51.1 1376 / 54.2 1376 / 54.2 1576 / 62.0 1576 / 62.0

mm/in 495 / 19.50 500 / 19.70 500 / 19.7 540 / 21.3 540 / 21.3 745 / 29.3 792 / 31.2 792 / 31.2 843 / 33.2 843 / 33.2

kg/lb 58 / 128 61 / 134 68 / 150 71 / 157 101 / 223 107 / 238 146 / 322 150 / 331 215 / 474 225 / 496

N/A N/A

LIQUID mm/in N/A N/A

GAS mm/in N/A N/A

380-415 / 3 / 50

R22 / CAPILLARY TUBE

DUCTED

APW04A or SLM15A

220-240 / 1 / 50

N/A

SIZEN/A N/A N/A N/A

N/A N/A

TYPE N/A N/A

UNITDIMENSION

HEIGHT

WIDTH

UNIT WEIGHT

PIPECONNECTION

WATER PRESSURE DROP

DEPTH

WATER FLOW RATE

AIR FLOW

EXTERNAL STATIC PRESSURE

50

CONTROLAIR DISCHARGE

OPERATION

SOUND PRESSURE LEVEL

60 (0.24)

NOMINAL TOTAL INPUT POWER (COOLING)

REFRIGERANT TYPE / CONTROL

POWER SOURCE

NOMINAL TOTAL INPUT POWER (HEATING)

EER

COP

NOMINAL HEATING CAPACITY

NOMINAL COOLING CAPACITY

MODEL

N/A

N/A N/A

180 / 380

IND

OO

R U

NIT

OU

TD

OO

R U

NIT

MWH011BR - MWH070BR (Packaged Horizontal Type)

R22 Horizontal Water Cooled Package

MWH011B - MWH070B (Packaged Horizontal Type)

MWH011B MWH012B MWH015B MWH020B MWH025B MWH030B MWH040B MWH050B MWH060B MWH070B

Btu/h 11300 11700 14400 18500 25500 29920 44870 49880 63160 76460

W 3300 3400 4200 5400 7400 8800 13200 14600 18500 22400

W 790 775 1253 1661 1894 2485 3897 4482 5505 6041

W/W 4.17 4.38 3.35 3.25 3.91 3.54 3.39 3.26 3.36 3.71

V/Ph/Hz

l/s / CFM 222 / 470 287 / 600 415 / 870 450 / 940 625 / 1325 710 / 1470 900 / 1910 915 / 1940

Pa (in.wg.) 60 (0.24) 120 (0.48) 129 (0.52) 190 / 0.76 270 / 1.08 290 / 1.16 210 / 0.84 270 / 1.08

dBA 42 37 41 45 47 51 53 53

l/s / m3/h 0.17 / 0.60 0.21 / 0.75 0.25 / 0.90 0.29 / 1.05 0.47 / 1.70 0.47 / 1.70 0.71 / 2.54 0.81 / 2.91 1.01 / 3.63 1.24 / 4.45

kPa 6.70 8.20 9.80 11.60 22.00 4.25 21.30 33.00 40.00 58.00

mm/in 250 / 9.80 325 / 12.80 337 / 13.3 353 / 13.9 340 / 13.4 370 / 14.6 434 / 17.1 434 / 17.1 500 / 19.7 500 / 19.7

mm/in 1040 / 40.90 1035 / 40.70 1074 / 42.3 1183 / 46.6 1328 / 52.3 1297 / 51.1 1376 / 54.2 1376 / 54.2 1576 / 62.0 1576 / 62.0

mm/in 495 / 19.50 500 / 19.70 500 / 19.7 540 / 21.3 540 / 21.3 745 / 29.3 792 / 31.2 792 / 31.2 843 / 33.2 843 / 33.2

kg/lb 58 / 128 61 / 134 68 / 150 71 / 157 101 / 223 107 / 238 143 / 315 147 / 324 210 / 463 220 / 485

N/A N/A

LIQUID mm/in N/A N/A

GAS mm/in N/A N/A

EER

POWER SOURCE

AIR DISCHARGE

OPERATION

220-240 / 1 / 50

R22 / CAPILLARY TUBE

380-415 / 3 / 50

WATER PRESSURE DROP

DUCTED

50

APW04A or SLM15ACONTROL

SOUND PRESSURE LEVEL

WATER FLOW RATE

PIPECONNECTION

N/A

N/A

TYPE

180 / 380

60 (0.24)

N/ASIZE

EXTERNAL STATIC PRESSURE

WIDTH

UNIT WEIGHT

UNITDIMENSION

HEIGHT

DEPTH

N/A N/A

MODEL

AIR FLOW

NOMINAL CAPACITY

NOMINAL TOTAL INPUT POWER

REFRIGERANT TYPE / CONTROL

N/A

N/A

N/A

N/A N/A

N/A N/A

IND

OO

R U

NIT

OU

TD

OO

R U

NIT

Page 19: Water Source System - Acson International … · Water source system by McQuay is the intelligent choice ... or NIM PC (A/C Management ... Step Capacity Sequencing Control

S5

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - INDOOR 27.0°C DB / 19.0°C WB; ENTERING WATER TEMPERATURE 30.0°C, LEAVING WATER TEMPERATURE 35.0°C b) HEATING - INDOOR 20.0°C DB; ENTERING WATER TEMPERATURE 20.0°C3) ALL SPECIFICATIONS ARE TENTATIVE SPECIFICATIONS AT THE TIME OF PRINTING. PLEASE CONSULT YOUR DEALER FOR CONFIRMATION.4) THE SOUND LEVEL ARE MEASURED IN AN ANECHOIC CHAMBER.

MWSS010A - MWSS025A (Coupled With Ceilling Concealed)

MCC010C MCC015C MCC020C MCC025C MCC030C MCC040C

MWSS010A MWSS015A MWSS020A MWSS025A MWSS030A MWSS040A

Btu/h 9100 14350 19000 22100 28000 37500

W 2667 4206 5569 6924 8206 10991

W 746 1133 1616 1687 2330 2930

W/W 3.58 3.71 3.45 3.84 3.52 3.75

V/Ph/Hz 220-240 / 1 / 50

l/s / CFM NA NA NA NA 425 / 900 519 / 1100

l/s / CFM 142 / 300 241 / 510 330 / 700 345 / 730 392 / 830 500 / 1060

l/s / CFM 123 / 260 208 / 440 321 / 680 340 / 720 359 / 760 467 / 990

l/s / CFM 104 / 220 170 / 360 293 / 620 274 / 580 335 / 710 425 / 900

EXTERNAL STATIC PRESSURE(SH/H/M/L)

Pa (in.wg.)49 / 39 / 29

(0.20 / 0.16 / 0.12)49 / 39 / 20

(0.20 / 0.16 / 0.08)64 / 58 / 34

(0.26 / 0.24 / 0.14)55 / 39 / 29

(0.22 / 0.16 / 0.12)206 / 167 / 127 / 88

(0.83 / 0.67 / 0.51 / 0.35)206 / 176 / 127 / 93

(0.83 / 0.71 / 0.51 / 0.37)

SOUND PRESSURE LEVEL (SH/H/M/L) dBA 33 / 30 / 26 37 / 34 / 29 38 / 36 / 34 40 / 39 / 36 49 / 46 / 42 / 38 51 / 49 / 45 / 41

mm/in 261 / 10.28 261 / 10.28 378 / 14.88 378 / 14.88

mm/in 1065 / 41.93 1200 / 47.24 929 / 36.57 1045 / 41.14

mm/in 411 / 16.18 411 / 16.18 541 / 21.30 541 / 21.30

kg/lb

l/s / m3/h

17 / 37.5 21 / 46.3 22 / 48.5 25 / 55.1 39 / 85.98 42 / 92.59

0.17 / 0.6 0.25 / 0.9 0.28 / 1.0 0.38 / 1.4 0.50 / 1.8 0.57 / 2.05

kPa 18.50 24.50 30.90 49.70 66.90 40.70

dBA 32 34 36 37 39 39

mm/in 385 / 15.16 460 / 18.11

mm/in 884 / 33.23

mm/in 418 / 16.46 549 / 21.61

kg/lb 35.4 / 77.9 39.4 / 86.7 39.5 / 86.9 40.5 / 89.1 57.3 / 126.1 78.6 / 172.9

LIQUID mm/in 6.25 / (1/4) 6.25 / (1/4) 6.25 / (1/4) 9.52 / (3/8) 9.52 / (3/8) 9.52 / (3/8)

GAS mm/in 9.52 / (3/8) 12.7 / (1/2) 15.88 / (5/8) 15.88 / (5/8) 15.88 / (5/8) 19.05 / (3/4)

FLARE

220-240 / 1 / 50

R22 / CAPTUBE

DUCTED

SLM WIRED HANDSET

261 / 10.28

765 / 30.12

411 / 16.18

330 / 13.0 380 / 15.0

774 / 30.0

280 / 11.0

380-415 / 3 / 50

R22 / CAPTUBE

920 / 36.22

DUCTED

SLM WIRED HANDSET

648 / 25.51

TYPE

SIZE

OU

TD

OO

R U

NIT

WATER FLOW RATE

WATER PRESSURE DROP

SOUND PRESSURE LEVEL

UNIT WEIGHT

PIPE CONNECTION

UNIT DIMENSION

HEIGHT

HEIGHT

WIDTH

DEPTH

UNIT WEIGHT

UNIT DIMENSION

WIDTH

DEPTH

IND

OO

R U

NIT

CONTROLAIR DISCHARGE

OPERATION

AIR FLOW

S/HIGH

MEDIUM

LOW

HIGH

EER

POWER SOURCE

REFRIGERANT TYPE / CONTROL

NOMINAL COOLING CAPACITY

NOMINAL TOTAL INPUT POWER (COOLING)

MODELINDOOR UNIT

OUTDOOR UNIT

MCC050C MCC060C

MWSS050A MWSS060A

46500 54000

13628 15826

3830 3940

3.56 4.02

9.52 / (3/8) 12.7 / (1/2)

19.05 / (3/4) 4/17/07

750 / 1590 779 / 1650

651 / 1380 722 / 1530

604 / 1280 675 / 1430

571 / 1210 609 / 1290

176 / 157 / 137 / 108(0.71 / 0.63 / 0.55 / 0.43)

176 / 157 / 137 / 98(0.71 / 0.63 / 0.55 / 0.39)

53 / 52 / 50 / 4755 / 53 / 50 / 47

378 / 14.88 378 / 14.88

1299 / 51.14 1499 / 59.02

541 / 21.30 541 / 21.30

54 / 119.05 62 / 136.69

0.66 / 2.38 0.76 / 2.74

32.40 26.20

38 40

504 / 19.84

92.36 / 203.2 105.1 / 231.1

R22A Split Type Specifications

MWSS010A - MWSS025A (Coupled With Wall Mounted)

SIZE

OU

TD

OO

R U

NIT

WATER FLOW RATE

WATER PRESSURE DROP

SOUND PRESSURE LEVEL

UNIT DIMENSION

PIPE CONNECTION

HEIGHT

WIDTH

DEPTH

UNIT WEIGHT

TYPE

MEDIUM

LOW

IND

OO

R U

NIT

CONTROLAIR DISCHARGE

OPERATION

AIR FLOW

HIGH

DEPTH

UNIT WEIGHT

POWER SOURCE

REFRIGERANT TYPE / CONTROL

NOMINAL TOTAL INPUT POWER (COOLING)

EER

SOUND PRESSURE LEVEL (H/M/L)

UNIT DIMENSION

HEIGHT

WIDTH

MODELINDOOR UNIT

OUTDOOR UNIT

NOMINAL COOLING CAPACITYBtu/h

W

W

W/W

V/Ph/Hz

l/s / CFM

l/s / CFM

l/s / CFM

dBA

mm/in

mm/in

mm/in

kg/lb

l/s / m3/h

kPa

dBA

mm/in

mm/in

mm/in

kg/lb

mm/(in)

mm/(in)

MWM010G MWM015G MWM020G MWM025G

MWSS010A MWSS015A MWSS020A MWSS025A

9500 14000 19000 22000

2784 4103 5569 6448

717 1103 1550 1660

3.88 3.72 3.59 3.88

142 / 300 163 / 345 231 / 490 397 / 630

118 / 250 135 / 285 193 / 410 231 / 490

94 / 200 104 / 220 160 / 340 208 / 440

39 / 34 / 28 42 / 36 / 29 43 / 40 / 35 49 / 44 / 42

304 / 12.0 304 / 12.0

1062 / 41.8 1062 / 41.8

222 / 8.7 222 / 8.7

16 / 35.27 16 / 35.27

0.17 / 0.6 0.25 / 0.9 0.28 / 1.0 0.38 / 1.4

18.50 24.50 30.90 49.70

32 34 36 37

35.4 / 77.9 39.4 / 86.7 39.5 / 86.9 40.5 / 89.1

9.52 / (3/8)

9.52 / (3/8) 12.7 / (1/2) 15.88 / (5/8)

260 / 10.2

899 / 35.4

198 / 7.8

12/26.46

774 / 30.0

280 / 11.0

FLARE

6.25 / (1/4)

220-240 / 1 / 50

R22 / CAPTUBE

330 / 13.0 380 / 15.0

DOUBLE LOUVER (UP & DOWN) & GRILLE (LEFT & RIGHT)

LCD REMOTE CONTROL

LIQUID

GAS

Page 20: Water Source System - Acson International … · Water source system by McQuay is the intelligent choice ... or NIM PC (A/C Management ... Step Capacity Sequencing Control

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - INDOOR 27.0°C DB / 19.0°C WB; ENTERING WATER TEMPERATURE 30.0°C, LEAVING WATER TEMPERATURE 35.0°C b) HEATING - INDOOR 20.0°C DB; ENTERING WATER TEMPERATURE 20.0°C3) ALL SPECIFICATIONS ARE TENTATIVE SPECIFICATIONS AT THE TIME OF PRINTING. PLEASE CONSULT YOUR DEALER FOR CONFIRMATION.4) THE SOUND LEVEL ARE MEASURED IN AN ANECHOIC CHAMBER.

S6

R22A Split Type Specifications

MWSS010A - MWSS050A (Coupled With Ceilling Cassette)

MCK010C MCK015C MCK020C MCK020A MCK025A MCK030A

MWSS010A MWSS015A MWSS020A MWSS020A MWSS025A MWSS030A

Btu/h 9500 14500 19000 19400 22800 29800

W 2784 4250 5569 5686 6448 8734

W 746 1130 1622 1616 1685 2300

W/W 3.73 3.76 3.43 3.52 3.97 3.80

V/Ph/Hz

l/s / CFM 194 / 410 194 / 410 212 / 450 349 / 740 368 / 780 415 / 880

l/s / CFM 184 / 390 184 / 390 203 / 430 297 / 630 311 / 660 349 / 740

l/s / CFM 175 / 370 170 / 360 194 / 410 283 / 600 283 / 600 321 / 680

dBA 44 / 43 / 42 44 / 42 / 41 47 / 46 / 44 42 / 39 / 37 45 / 42 / 40 49 / 45 / 43

mm/in 250 (295) / 9.8 (11.6 335 (363) / 13.2 (14.3) 335 (363) / 13.2 (14.3) 335 (363) / 13.2 (14.3)

mm/in 570 (640) / 22.4 (25.2) 820 (930) / 32.2 (36.6) 820 (930) / 32.2 (36.6) 820 (930) / 32.2 (36.6)

mm/in 570 (640) / 22.4 (25.2) 820 (930) / 32.2 (36.6) 820 (930) / 32.2 (36.6) 820 (930) / 32.2 (36.6)

kg/lb 22 + 2 / 48.5 + 4.4 23.2 / 50.7 + 4.4 23 + 2 / 50.7 + 4.4 31 + 4 / 68.3 + 8.8

0.17 / 0.6 0.25 / 0.9 0.28 / 1.0 0.38 / 1.4 0.38 / 1.4 0.50 / 1.8

kPa 18.50 24.50 30.90 49.70 49.70 66.90

dBA 32 34 36 36 37 39

mm/in 380 / 15.0 385 / 15.16

mm/in 774 / 30.0 884 / 33.23

mm/in 280 / 11.0 418 / 16.46

kg/lb 35.4 / 77.9 39.4 / 86.7 40.5 / 89.1 57.3 / 126.1

LIQUID mm/in 6.25 / (1/4) 6.25 / (1/4) 6.25 / (1/4) 9.52 / (3/8) 9.52 / (3/8) 9.52 / (3/8)

GAS mm/in 9.52 / (3/8) 12.7 / (1/2) 15.88 / (5/8) 15.88 / (5/8) 15.88 / (5/8) 19.05 / (3/4)

R22 / CAPTUBE

220-240 / 1 / 50

250 (295) / 9.8 (11.6

32 + 4 / 70.5 + 8.8

39.5 / 86.9

FLARE

570 (640) / 22.4 (25.2)

774 / 30.0

280 / 11.0

NOMINAL COOLING CAPACITY

NOMINAL TOTAL INPUT POWER (COOLING)

MODELINDOOR UNIT

OUTDOOR UNIT

LOW

SOUND PRESSURE LEVEL (H/M/L)

UNIT DIMENSION

EER

POWER SOURCE

REFRIGERANT TYPE / CONTROL

HEIGHT

WIDTH

DEPTH

UNIT WEIGHT

TYPE

SIZE

IND

OO

R U

NIT

CONTROLAIR DISCHARGE

OPERATION

AIR FLOW

HIGH

MEDIUM

PIPE CONNECTION

UNIT WEIGHT

OU

TD

OO

R U

NIT

WATER FLOW RATE

WATER PRESSURE DROP

SOUND PRESSURE LEVEL

UNIT DIMENSION

HEIGHT

WIDTH

DEPTH

4 WAY AUTOMATIC LOUVER (UP & DOWN)

WIRELESS OR WIRED MICROCOMPUTER REMOTE CONTROL

330 / 13.0 380 / 15.0

570 (640) / 22.4 (25.2)

MCK040A MCK050A

MWSS040A MWSS050A

37200 46200

10903 13540

2900 3672

3.76 3.69

467 / 990 491 / 1040

406 / 860 448 / 950

359 / 760 411 / 870

51 / 48 / 46 53 / 52 / 50

335 (363) / 13.2 (14.3) 335 (363) / 13.2 (14.3)

820 (930) / 32.2 (36.6) 820 (930) / 32.2 (36.6)

820 (930) / 32.2 (36.6) 820 (930) / 32.2 (36.6)

0.57 / 2.05 0.66 / 2.38

40.70 32.40

38 40

460 / 18.11 504 / 19.84

549 / 21.61 648 / 25.51

78.6 / 172.9 92.36 / 203.2

38 + 4 / 83.8 + 8.8

920 / 36.22

9.52 / (3/8) 12.7 / (1/2)

19.05 / (3/4) 19.05 / (3/4)

l/s / m3/h

MWSS020A - MWSS025A (Coupled With Ceilling Exposed)

Btu/h

W

W

W/W

V/Ph/Hz

l/s / CFM

l/s / CFM

l/s / CFM

dBA

mm/in

mm/in

mm/in

kg/lb

kPa

dBA

mm/in

mm/in

mm/in

kg/lb

LIQUID mm/in

GAS mm/in

MODELINDOOR UNIT

OUTDOOR UNIT

NOMINAL COOLING CAPACITY

MEDIUM

LOW

SOUND PRESSURE LEVEL (H/M/L)

NOMINAL TOTAL INPUT POWER (COOLING)

EER

POWER SOURCE

HEIGHT

WIDTH

DEPTH

REFRIGERANT TYPE / CONTROL

IND

OO

R U

NIT

CONTROLAIR DISCHARGE

OPERATION

AIR FLOW

HIGH

OU

TD

OO

R U

NIT

WATER FLOW RATE

WATER PRESSURE DROP

SOUND PRESSURE LEVEL

UNIT DIMENSION

HEIGHT

DEPTH

UNIT WEIGHT

PIPE CONNECTION

TYPE

380 / 15.0

220-240 / 1 / 50

SIZE

R22 / CAPTUBE

774 / 30.0

280 / 11.0

FLARE

WIDTH

UNIT WEIGHT

UNIT DIMENSION

MCE20E

MWSS020A

18900

5539

1526

3.63

245 / 520

217 / 460

192 / 406

48 / 46 / 43

218 / 8.58

1080 / 42.52

630 / 24.80

27 / 60

0.28 / 1.0

30.90

36

39.5 / 86.9

6.25 / (1/4)

15.88 / (5/8)

AUTOMATIC LOUVER (UP & DOWN)

WIRELESS OR WIRED MICROCOMPUTER REMOTE CONTROL

MCE25E

MWSS025A

22200

6975

1687

3.86

274 / 580

250 / 530

231 / 490

50 / 47 / 46

218 / 8.58

1080 / 42.52

630 / 24.80

27 / 60

0.38 / 1.4

49.70

37

40.5 / 89.1

9.52 / (3/8)

15.88 / (5/8)

l/s / m3/h

Page 21: Water Source System - Acson International … · Water source system by McQuay is the intelligent choice ... or NIM PC (A/C Management ... Step Capacity Sequencing Control

S7

MODEL

NOMINAL CAPACITY

NOMINAL TOTAL INPUT POWER

EER

POWER SOURCE

REFRIGERANT TYPE / CONTROL

EV

AP

OR

AT

OR CONTROL

AIR DISCHARGE

OPERATION

AIR FLOW

EXTERNAL STATIC PRESSURE

SOUND PRESSURE LEVEL

CO

ND

EN

SE

R

WATER FLOW RATE

WATER PRESSURE DROP

UNIT DIMENSION

HEIGHT

WIDTH

DEPTH

UNIT WEIGHT

PIPE CONNECTION

TYPE

SIZELIQUID

GAS

MWV050A

47780

14004

4162

3.37

694 / 1470

56

8.28/2.3

34.45

1297 / 51.1

745 / 29.3

370 / 14.6

160/353

380-415 / 3 / 50

12.7/0.5

MWV040A

37540

11002

3576

3.08

555 / 1176

54

6.876/1.91

24.61

1328 / 52.3

540 / 21.3

340 / 13.4

150/331

120 (0.48)

9.52/0.375

MWV030A

30720

9004

2680

3.36

444 / 940

50

5.688/1.58

19.70

1183 / 46.6

540 / 21.3

353 / 13.9

125 / 276

R22 / CAPILLARY TUBE

DUCTED

APW04A or SLM15A

plain tube

MWV025A

23890

7002

1973

3.55

347 / 740

48

4.788/1.33

16.73

1074 / 42.3

500 / 19.7

337 / 13.3

115 / 254

220-240 / 1 / 50

9.52/0.375

MWV020A

19110

5601

1725

3.24

283 / 600

47

4.032/1.12

14.76

1035 / 40.70

500 / 19.70

325 / 12.80

95 / 210

100 (0.4)

12.7/0.5

MWV015A

14330

4200

1084

3.87

208 / 3.48

46

2.988/0.83

12.80

1040 / 40.90

495 / 19.50

250 / 9.80

93 / 205

Btu/h

W

W

W/W

V/Ph/Hz

l/s / CFM

Pa (in.wg.)

dBA

l/s / m3/h

Pa

mm/in

mm/in

mm/in

kg/lb

mm/in

mm/in

MODEL

NOMINAL COOLING CAPACITY

NOMINAL HEATING CAPACITY

NOMINAL TOTAL INPUT POWER (COOLING)

NOMINAL TOTAL INPUT POWER (HEATING)

EER

COP

POWER SOURCE

REFRIGERANT TYPE / CONTROL

EV

AP

OR

AT

OR CONTROL

AIR DISCHARGE

OPERATION

AIR FLOW

EXTERNAL STATIC PRESSURE

SOUND PRESSURE LEVEL

CO

ND

EN

SE

R

WATER FLOW RATE

WATER PRESSURE DROP

UNIT DIMENSION

HEIGHT

WIDTH

DEPTH

UNIT WEIGHT

PIPE CONNECTION

TYPE

SIZELIQUID

GAS

MWV050AR

47780

14004

52900

15504

4162

4572

3.37

3.39

694 / 1470

56

8.28/2.3

34.45

1297 / 51.1

745 / 29.3

370 / 14.6

160/353

380-415 / 3 / 50

12.7/0.5

19.05/0.75

MWV040AR

37540

11002

42660

12503

2576

3156

3.08

3.96

555 / 1176

54

6.876/1.91

24.61

1328 / 52.3

540 / 21.3

340 / 13.4

150/331

120 (0.48)

MWV030AR

30720

9004

34130

10003

2680

2950

3.36

3.39

444 / 940

50

5.688/1.58

19.70

1183 / 46.6

540 / 21.3

353 / 13.9

125 / 276

R22 / CAPILLARY TUBE

DUCTED

APW04A or SLM15A

plain tube

9.52/0.375

MWV025AR

23890

7002

25600

7503

1973

2133

3.55

3.52

347 / 740

48

4.788/1.33

16.73

1074 / 42.3

500 / 19.7

337 / 13.3

115 / 254

220-240 / 1 / 50

9.52/0.375

MWV020AR

19110

5601

20478

6002

1725

1845

3.24

3.25

283 / 600

47

4.032/1.12

14.76

1035 / 40.70

500 / 19.70

325 / 12.80

95 / 210

100 (0.4)

12.7/0.5

MWV015AR

14330

4200

15360

4502

1084

1214

3.87

3.71

208 / 3.48

46

2.988/0.83

12.80

1040 / 40.90

495 / 19.50

250 / 9.80

93 / 205

Btu/h

W

Btu/h

W

W

W

W/W

W/W

V/Ph/Hz

l/s / CFM

Pa (in.wg.)

dBA

l/s / m3/h

kPa

mm/in

mm/in

mm/in

kg/lb

mm/in

mm/in

R22 Vertical Water Cooled Package

MWV015A - MWV050A (Packaged Vertical Type)

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - INDOOR 27.0°C DB / 19.0°C WB; ENTERING WATER TEMPERATURE 30.0°C, LEAVING WATER TEMPERATURE 35.0°C b) HEATING - INDOOR 20.0°C DB; ENTERING WATER TEMPERATURE 20.0°C3) ALL SPECIFICATIONS ARE TENTATIVE SPECIFICATIONS AT THE TIME OF PRINTING. PLEASE CONSULT YOUR DEALER FOR CONFIRMATION.4) THE SOUND LEVEL ARE MEASURED IN AN ANECHOIC CHAMBER.

MWV015AR - MWV050AR (Packaged Vertical Type)

Page 22: Water Source System - Acson International … · Water source system by McQuay is the intelligent choice ... or NIM PC (A/C Management ... Step Capacity Sequencing Control

A Global Leader in System Solutions for Air Conditioning, Heating, Ventilating and Refrigeration.

Products manufactured in an ISO certified facility.This document contains the most current product information as of this printing.

For the most up-to-date product information, please go to www.mcquay.com.

©2008 McQuay International +1 (800) 432-1342 www.mcquay.com