• This course is split into three sections

1. Copper Certification (DSX-5000 CableAnalyzer)

2. Tier 1 Fiber Certification (CertiFiber Pro)

3. Tier 2 Fiber Certification (OptiFiber Pro)

• At the end of the course you will be able to

1. Setup DSX-5000, CertiFiber Pro and OptiFiber Pro

2. Test using a DSX-5000, CertiFiber Pro and OptiFiber Pro

3. Troubleshoot copper and fiber links

4. Download results into LinkWare for warranty application

IN THIS COURSE

© 2014 Fluke Corporation. All rights reserved

Page 3: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 3/199

• Versiv introduction and common settings

- Exporting configuration and results

• Copper test limits/standards

• Adapter types

• Configuring for a twist pair test

• Making a measurement and reviewing the result

• New test parameters

- DC Resistance Unbalance, TCL, ELTCTL

• DSX diagnostics

- HDTDX and HDTDR

• Single test

• Patch cord certification

• Alien Crosstalk

DSX-5000 CABLEANALYZER TESTING

© 2014 Fluke Corporation. All rights reserved

Page 4: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 4/199

• Basic fiber theory

• Encircled flux

• Configuring the CertiFiber Pro

• Fiber inspection

- Automated analysis

• Setting a reference for a duplex link

- LC to LC duplex

• Creating a custom test limit

• ISO/IEC 14763-3

- Understanding how the different connector losses differ from other standards

• Setting a reference for a simplex link

- SC/APC to SC/APC

CERTIFIBER PRO TESTING

© 2014 Fluke Corporation. All rights reserved

Page 5: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 5/199

• Basic OTDR theory

• OTDR event types

- Reflective, no reflective, ghosts

• Launch fiber compensation

- Four different types

• Custom OTDR limits- Walk through the process of creating a custom limit

• OptiFiber Pro link testing

• OptiFiber Pro results analysis

• Bi-directional averaging

OPTIFIBER PRO TESTING

© 2014 Fluke Corporation. All rights reserved

Page 6: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 6/199

Versiv introduction

© 2014 Fluke Corporation. All rights reserved.

Page 7: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 7/199

• The languages available to you will depend on where you

purchased your Versiv

1. North America

2. Europe and Middle East

3. -4. Asia Pacific

5. Peoples Republic on China

LANGUAGE

© 2014 Fluke Corporation. All rights reserved

Page 8: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 8/199

• Changing the language is simple

• From the HOME screen, tap:

- TOOLS

- Swiped up to see Language

- Language

- We’ll keep it English here

• Additional information

- If you do not see your language, the

Versiv was not sold thru an authorized

Fluke Networks distributor – you mayhave no warranty

- You can change the language on the

reports in LinkWare – independent

of where you got your Versiv

LANGUAGES

© 2014 Fluke Corporation. All rights reserved

Page 9: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 9/199

• Doing this will wipe ALL test results and settings in the Versiv

• There is no undoing this, no secret “back door”

• You should copy your ProjX and results to a thumb drive first

RESTORE VERSIV BACK TO FACTORY DEFAULT

Memory Stick – Not Wiped

Main Frame - Wiped© 2014 Fluke Corporation. All rights reserved

Page 10: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 10/199

• Doing this will wipe ALL test results and settings in the Versiv

• There is no undoing this, no secret “back door”

• You should copy your ProjX and results to a thumb drive first

RESTORE VERSIV BACK TO FACTORY DEFAULT

Thumb Drive – Not Wiped

Main Frame - Wiped© 2014 Fluke Corporation. All rights reserved

Page 11: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 11/199

• From the HOME screen, tap:

- PROJECT:

- TRANSFER

- Export

- SELECT ALL

- EXPORT

EXPORT PROJECTS

© 2014 Fluke Corporation. All rights reserved

Page 12: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 12/199

• From the HOME screen, tap:

- RESULTS:

- TRANSFER

- USB Flash Drive

- Export

- SELECT ALL

- EXPORT

EXPORT RESULTS

© 2014 Fluke Corporation. All rights reserved

Page 13: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 13/199

• Your Versiv was made in Everett, WA – USA

• Unless you are on the west coast of 

America, you need to change the

TIME – the date too if you are in Asia

• From the TOOLS screen, tap:

- Date/Time- Date:

- DONE to save your date

SETTING THE DATE

Cannot be changed in LinkWare after you

have saved a test result 

© 2014 Fluke Corporation. All rights reserved

Page 14: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 14/199

• From the DATE/TIME screen, tap:

- Time

- Done to save your time

SETTING THE TIME

Cannot be changed in LinkWare after you

have saved a test result 

© 2014 Fluke Corporation. All rights reserved

Page 15: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 15/199

• Not a critical setting

• Your test report DATE/TIME format is driven by your LinkWare

Software settings

DATE/TIME FORMAT

LinkWare Software

© 2014 Fluke Corporation. All rights reserved

Page 16: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 16/199

• Critical to keep you Versiv current

- Results have been known to be rejected

• From the DATE/TIME screen, tap:

- (Back)

- Version Information

• This is the MAIN FRAME information

VERSION INFORMATION

© 2014 Fluke Corporation. All rights reserved

Page 17: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 17/199

• From the VERSION INFORMATION screen, tap:

- MODULE

• This is the MODULE information

• It has it’s own software

• Automatically updated when you

insert into a Versiv main frame

VERSION INFORMATION

© 2014 Fluke Corporation. All rights reserved

Page 18: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 18/199

• Only the modules are subject to an annual calibration

• Warranties can be denied if modules are not calibrated

CALIBRATION

No Cal Required

Cal Required

Cal Required

Cal Required© 2014 Fluke Corporation. All rights reserved

Page 19: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 19/199

• From the VERSION INFORMATION screen, tap:

- ADAPTER

• This is the ADAPTER information

- Stored in the adapters

VERSION INFORMATION

© 2014 Fluke Corporation. All rights reserved

Page 20: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 20/199

• When you change the tip on your DSX-PLA004, you can reset the

counter to monitor how many testshave been carried out with the

replacement tip

VERSION INFORMATION

DTX-PLA002PRP (Pack of two)© 2014 Fluke Corporation. All rights reserved

Page 21: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 21/199

• Download the update file from www.flukenetworks.com

• Connect your Versiv to the PC and in LinkWare, click on:- Utilities > DSX CableAnalyzer > Software Update

- Select the file you downloaded and click ok

• Repeat again for the remote unit

• Any updates to the modules will take place when you insert them

(Unlike the DTX Compact OTDR Module)

UPDATING THE VERSIV

© 2014 Fluke Corporation. All rights reserved

Page 22: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 22/199

• Main unit will update the remote unit but not the same

way as the DTX CableAnalyzer

UPDATES

You can use the supplied USB cable

with the DSX CableAnalyzer to do this

Adds 2 minutes to the update time,

for a total update time of 7 minutes.

© 2014 Fluke Corporation. All rights reserved

BATTERY STATUS

Page 23: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 23/199

• Versiv

- 39 Watt Hour Lithium Ion battery

- 4 hours to charge with unit off 

- 6 hours to charge with unit on

- Expect to see more than 10 hours of battery life

- No re-training of battery needed

BATTERY STATUS

Unlike the DTX, the DSX can be used if

the battery has failed by plugging the

power in

© 2014 Fluke Corporation. All rights reserved

BATTERY STATUS

Page 24: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 24/199

• Indicates the status of the battery on the main unit

BATTERY STATUS

© 2014 Fluke Corporation. All rights reserved

BATTERY STATUS

Page 25: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 25/199

• You can see the approximate battery status on the remote unit

when you power it up

BATTERY STATUS

© 2014 Fluke Corporation. All rights reserved

BATTERY STATUS

Page 26: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 26/199

• You can see the battery status on the remote unit when they are

connected in any configuration- Connect the main and remote units as shown below

- Power on the remote

BATTERY STATUS

DSX-PLA004

Perm. Link Adapter

DSX-CHA004

Channel Adapter

© 2014 Fluke Corporation. All rights reserved

BATTERY STATUS

Page 27: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 27/199

• From the TOOLS screen, tap:

- Battery Status

• Additional information

- Time remaining caps out at 24 Hr.

- Running the battery to 0 % does not

degrade the battery

- If you remove the battery, tape over the

contacts to avoid a short circuit

BATTERY STATUS

© 2014 Fluke Corporation. All rights reserved

MEMORY

Page 28: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 28/199

• From the TOOLS screen, tap:

- Memory Status

• Additional information

- Store ≈ 12,700 Cat 6A results

- With full graphs

- Including HDTDX and HDTDR

- Cannot recover deleted results

- Back up to a thumb drive / memory

stick whenever you take a break

MEMORY

© 2014 Fluke Corporation. All rights reserved

NUMBER FORMAT

Page 29: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 29/199

• From the TOOLS screen, tap:

- Number

NUMBER FORMAT

Can be changed in LinkWare after you

have saved a test result 

© 2014 Fluke Corporation. All rights reserved

LENGTH FORMAT

Page 30: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 30/199

• From the TOOL screen, tap:

- Length

LENGTH FORMAT

Can be changed in LinkWare after you

have saved a test result 

© 2014 Fluke Corporation. All rights reserved

TIMEOUT PERIOD

Page 31: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 31/199

• From the TOOLS screen, tap:

- Timeout Period

• Backlight

- Disabled

- 5, 10 or 15 minutes

• Power Down

- Disabled

- 10, 20 or 30 minutes

TIMEOUT PERIOD

Do NOT disable. Then if you put the Versiv back in the case powered on -

you will still have a charge the next time you use it

© 2014 Fluke Corporation. All rights reserved

TIMEOUT PERIOD

Page 32: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 32/199

• The smart remote unit will power off 

- After 60 minutes- Not adjustable

TIMEOUT PERIOD

© 2014 Fluke Corporation. All rights reserved

AUDIBLE TONE

Page 33: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 33/199

• From the TOOLS screen, tap:

- Audible Tone

• Disables tones on the main unit only

 AUDIBLE TONE

© 2014 Fluke Corporation. All rights reserved

POWER LINE FREQUENCY

Page 34: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 34/199

• From the TOOLS screen, tap:

- Power Line Frequency

• Isolates noise from power supplies that

may interfere with the Wire Map

POWER LINE FREQUENCY

© 2014 Fluke Corporation. All rights reserved

DISPLAY

Page 35: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 35/199

• From the TOOLS screen, tap:

- Display

DISPLAY

Task:

Increase the brightness and view your battery status

© 2014 Fluke Corporation. All rights reserved

REVIEW #1

Page 36: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 36/199

• What does the Reset Series feature do?

• Can you disable the calibration date in LinkWare?

• How often should your Versiv be calibrated?

• What is the default power down time of the Versiv Smart Remote

and how do you change it?

• What setting has the most impact on your battery life?

© 2014 Fluke Corporation. All rights reserved

FIELD TESTER STANDARDS SUMMARY

Page 37: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 37/199

• ANSI/TIA-1152

- Defined accuracies for field testers- Level IIe, up to Category 5e (100 MHz)

- Level III, up to Category 6 (250 MHz)

- Level IIIe, up to Category 6A (500 MHz)

• IEC 61935-1 Edition 3- Defined accuracies for field testers

- Level IIe, up to Class D (100 MHz)

- Level III, up to Class E (250 MHz)

- Level IIIe, up to Class EA (500 MHz)

- Level IV, up to Class F (600 MHz)

- Level V (Draft Edition 4), up to Class FA (1 GHz) DSX-5000

© 2014 Fluke Corporation. All rights reserved

LOCATING A PERMANENT LINK LIMIT #1

Page 38: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 38/199

• Cat 5e Permanent Link

• From the HOME screen, tap:

- The test limit

- EDIT

- Test Limit

- MORE

- TIA

© 2014 Fluke Corporation. All rights reserved

LOCATING A PERMANENT LINK LIMIT #2

Page 39: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 39/199

• Cat 5 Permanent Link

• From the HOME screen, tap:

- The test limit

- EDIT

- Test Limit

- MORE

- TIA

- Swipe up the screen to see Cat 5

• TSB-67: Original Category 5 test- BL = Basic Link includes test leads

- No Permanent Link, did not exist back then

© 2014 Fluke Corporation. All rights reserved

LOCATING A PERMANENT LINK LIMIT #2

Page 40: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 40/199

• Cat 5 Permanent Link

• From the HOME screen, tap:

- The test limit

- EDIT

- Test Limit

- MORE

- TIA

- Swipe up the screen to see Cat 5

• TSB-95: 1000BASE-T test- BL = Basic Link includes test leads

- Adds ACR-F (ELFEXT) and Return Loss to TSB-67 test to support 1000BASE-T

© 2014 Fluke Corporation. All rights reserved

LOCATING A PERMANENT LINK LIMIT #3

Page 41: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 41/199

• (+PoE)

- Power over Ethernet- Standard test with the addition of

- Resistance

- Resistance Unbalance

• Resistance Unbalance- An important parameter for the successful

deployment of PoE devices such as cameras

and wireless access points

- More on this “new” measurement later

© 2014 Fluke Corporation. All rights reserved

LOCATING A PERMANENT LINK LIMIT #4

Page 42: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 42/199

• (+TCL)

• From the HOME screen, tap:

- The test limit

- EDIT

- Test Limit

- MORE

- Balance Measurements

• Balance measurements

- Standard test with the addition of- Transverse Conversion Loss

- Equal Level Transverse Conversion Transfer Loss

- More on these new measurements later

© 2014 Fluke Corporation. All rights reserved

LOCATING A PERMANENT LINK LIMIT #5

Page 43: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 43/199

• Category 7A Permanent Link

• From the HOME screen, tap:

- The test limit

- EDIT

- Test Limit

- MORE

- ISO

• PL3 and PL2?

- PL3 – consolidation point included- PL2 – no consolidation point

- Different NEXT limits

Class FA

© 2014 Fluke Corporation. All rights reserved

LOCATING A PERMANENT LINK LIMIT #5

Page 44: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 44/199

• (1 GHz) or (600 MHz)

- The field testing standard IEC 61935-1Edition 3 only supports field testing to

600 MHz for Class FA links

- There is a draft IEC 61935-1 Edition 4

which supports field testing of Class FA

links to 1 GHz

- So two options are given

- A published standard (600 MHz)

- A draft standard (1 GHz)

- Check with your cabling vendor to see

which one they require

© 2014 Fluke Corporation. All rights reserved

CLASS F A ADAPTERS

Page 45: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 45/199

• Siemon TERA

- You need at least one Channel & Permanent Link Adapter set a reference- You cannot makes a measurement without setting a reference first

DSX-PLA011

DSX-CHA011

© 2014 Fluke Corporation. All rights reserved

REVIEW #2

Page 46: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 46/199

• Why is a Channel test typically not done by installers?

• Which test limit do I use for Category 5?

• What causes the message “Bad Patch Cord”?

• What are the three link definitions found in the DSX?

• What does the (+PoE) limit add to the test?

• What does the (+TCL) limit add to the test?

© 2014 Fluke Corporation. All rights reserved

Page 47: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 47/199

Configuring for a twisted pair test

© 2014 Fluke Corporation. All rights reserved.

PROJX™

Page 48: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 48/199

• Allows you to configure the unit in advance

• The more you configure up front, the greaterthe time savings down the road

• Configuring upfront also allows the analyzer

to be handed off to a level entry technician

• You can track the PASS/FAILs within the unit

- Tell you what % of testing has been done

• You can have up to 100 projects in a Versiv

main frame

• Per project, you can pre-configure

- up to 10 separate tests per project

- 5,000 Cable IDs in total

© 2014 Fluke Corporation. All rights reserved

WHAT YOU CAN SET UP IN ADVANCE

Page 49: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 49/199

• For each project, you to configure the following

- Test Limit- Cable Type (Nominal Velocity of Propagation)

- Outlet Configuration

- Plot Data

- HDTDX/HDTDR

- AC Wire Map- Cable IDs (Using up to 60 characters)

- Operator name

• Projects can be saved to a thumb drive and loaded into other Versiv

main frames

© 2014 Fluke Corporation. All rights reserved

PROJECT CCTT 1

Page 50: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 50/199

• We’re going to create a new project called “CCTT 1” for:

- Category 5e cable

- NVP of 70 %

- Category 5e Permanent Link test limit

- T568A outlet configuration

- Plot Data enabled

- No AC Wire Map

- Cable ID:

- 20AL.B.1-36 TO 20AS.C.01 to 20AL.B.1-36 TO 20AS.C.48

- 20AL.C.1-36 TO 20AR.C.01 to 20AL.C.1-36 TO 20AR.C.48

© 2014 Fluke Corporation. All rights reserved

PROJECT CCTT 1

Page 51: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 51/199

• Let’s go ahead and create a new project called “CCTT 1”

• From the HOME screen, tap:- PROJECT:

- CHANGE PROJECT

- NEW PROJECT

- Enter CCTT 1

- DONE

© 2014 Fluke Corporation. All rights reserved

PROJECT CCTT 1

Page 52: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 52/199

• Enter an Operator Name

• From the PROJECT screen, tap:- Operator:

- NEW OPERATOR

- Enter Your Name

- DONE

- Your Name

• You can have 20 OPERATORs

© 2014 Fluke Corporation. All rights reserved

PROJECT CCTT 1

Page 53: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 53/199

• Let’s go ahead and change the TEST SETUP

• From the PROJECT screen, tap:- TIA Cat 6A Perm. Link:

- Cable Type

U/UTP

- Individual pairs are unshielded

- No overall shield

F/UTP

- Individual pairs are unshielded

- Overall shield

S/FTP- Individual pairs are shielded

- Overall shield

© 2014 Fluke Corporation. All rights reserved

PROJECT CCTT 1

Page 54: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 54/199

• For DTX CableAnalyzer users

F/UTPS/FTP

U/UTP

© 2014 Fluke Corporation. All rights reserved

PROJECT CCTT 1

Page 55: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 55/199

• Let’s go ahead and change the TEST SETUP

• From the PROJECT screen, tap:- TIA Cat 6A Perm. Link:

- Cable Type:

- Cat 5e U/UTP

• The NVP changed!

• ALWAYS check on the vendor’s

website to see the NVP

• NVP affects your length reading

- It does not affect any other parameter

• We’ll cover other methods later

© 2014 Fluke Corporation. All rights reserved

PROJECT CCTT 1

Page 56: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 56/199

• Let’s go ahead and change the NVP:

• From the TEST SETUP screen, tap:- NVP:

- Change to 70%

- DONE

© 2014 Fluke Corporation. All rights reserved

PROJECT CCTT 1

Page 57: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 57/199

• Let’s go ahead and change the Test Limit:

• From the TEST SETUP screen, tap:- Test Limit:

- TIA Cat 5e Perm. Link

© 2014 Fluke Corporation. All rights reserved.

PROJECT CCTT 1

Page 58: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 58/199

• When Store Plot Data is On

- Stores graphs

- Most customers expect this

- Most cabling vendors expect this

- HDTDR/HDTDX diagnostics are saved

- Store 12,700 Cat 6A tests

© 2014 Fluke Corporation. All rights reserved

PROJECT CCTT 1

Page 59: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 59/199

• HDTDR

- High Def. Time Domain Reflectometer

- Troubleshoot Return Loss issues

• HDTDX

- High Def. Time Domain Xtalk

- Troubleshoot NEXT issues

• Go ahead and tap:

- HDTDR/HDTDX:

- Two options to run

- When the link fails or is marginal

- All the time (adds ≈ 3 to 5 seconds)

- We’ll leave it on Fail/Pass* only

© 2014 Fluke Corporation. All rights reserved

PROJECT CCTT 1

Page 60: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 60/199

• Let’s go ahead and change the Outlet Configuration:

• From the TEST SETUP screen, tap:- Outlet Configuration:

- T568A

- USE SELECTED

• Two Pair Cat 5e?- We’ll do that in Project CCTT 2

© 2014 Fluke Corporation. All rights reserved

PROJECT CCTT 1

Page 61: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 61/199

• When AC Wire Map is On

- Resistance is not measured

- Shield is not checked

• Only used if testing through a

mid-span 1000BASE-T PoE device

• You will receive a warning when

running a test that these two

measurements are not made

© 2014 Fluke Corporation. All rights reserved

PROJECT CCTT 1

Page 62: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 62/199

• Don’t tap this

- This is the cancel key

• Tap SAVE followed by USE SELECTED

© 2014 Fluke Corporation. All rights reserved

PROJECT CCTT 1

Page 63: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 63/199

• Let’s go ahead and set our Cable ID schemes

• From the HOME screen, tap:- PROJECT:

- Delete the default Cable ID Set

- Confirm DELETE

- NEW ID SET

- Enter the First ID- 20AL.B.1-48 TO 20AS.C.01

- Enter the Last ID

- 20AL.B.1-48 TO 20AS.C.48

- DONE

- SAVE

© 2014 Fluke Corporation. All rights reserved

Page 64: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 64/199

IMPORTING CABLE ID SCHEMES

Page 65: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 65/199

• Create them in LinkWare

- Utilities > DSX CableAnalyzer > Cable ID List

- Build Sequence

- Enter First ID and Last ID

- OK

- Send to DSX

- Name the ID scheme- OK

© 2014 Fluke Corporation. All rights reserved

PROJECT CCTT 1

Page 66: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 66/199

• From the HOME screen, tap:

- PROJECT

- NEW ID SET

- IMPORT

- Your ID scheme

- IMPORT

- OK- Back

- Back

© 2014 Fluke Corporation. All rights reserved

PROJECT CCTT 2

Page 67: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 67/199

• We’re going to create a new project called “CCTT 2” for:

- Category 5e cable- NVP of 70 %

- Category 5e Permanent Link test limit

- Two Pair Ethernet outlet configuration

- Plot Data enabled- No AC Wire Map

- Cable ID:

- FLOOR 1 / RACK 1 / 001 to FLOOR 1 / RACK 1 /096

© 2014 Fluke Corporation. All rights reserved

PROJECT CCTT 2

Page 68: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 68/199

• Let’s go ahead and create a new project called “CCTT 2”

• From the HOME screen, tap:- PROJECT:

- CHANGE PROJECT

- NEW PROJECT

- Enter CCTT 2

- DONE

• To change the Operator, tap:

- Operator:

- Your name

© 2014 Fluke Corporation. All rights reserved

PROJECT CCTT 2

Page 69: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 69/199

• Let’s go ahead and change the TEST SETUP

• From the PROJECT screen, tap:- TIA Cat 6A Perm. Link:

- Cable Type:

- Cat 5e U/UTP

- NVP:

- Change it to 70%- Done

- Test Limit:

- MORE

- TIA

- Swipe up to see TIA 1005 Cat 5e ……..

- TIA 1005 Cat 5e Perm. Link

© 2014 Fluke Corporation. All rights reserved

PROJECT CCTT 2

Page 70: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 70/199

• Let’s go ahead and change the Outlet Configuration

• From the PROJECT screen, tap:- Outlet Configuration

- Ethernet Two-Pair

- Sample (Check the Wire Map)

- Cancel

- USE SELECTED- SAVE

© 2014 Fluke Corporation. All rights reserved

PROJECT CCTT 2

Page 71: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 71/199

• Let’s go ahead and set our Cable ID Sets:

• From the PROJECT screen, tap:- X to delete the default set

- DELETE to confirm

- NEW ID SET

- Enter the First ID

- FLOOR 1 / RACK 1 / 001- Enter the LAST ID

- FLOOR 1 / RACK 1 / 096

- DONE

- SAVE

© 2014 Fluke Corporation. All rights reserved

SAVE CCTT 1 & 2 TO A THUMB DRIVE

Page 72: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 72/199

• Let’s copy these to a thumb drive

• Insert a thumb drive• From the PROJECT screen, tap:

- TRANSFER

- Export

- Select CCTT 2 and CCTT 1

- EXPORT

- OK

© 2014 Fluke Corporation. All rights reserved

Page 73: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 73/199

RESTORE CCTT 2 FROM THUMB DRIVE

Page 74: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 74/199

• Let’s put CCTT 2 back into the Versiv

•From the HOME screen, tap:

- PROJECT:

- TRANSFER

- Import

- Check CCTT 2

- IMPORT- OK

• Now lets see if it is back!

- to go back

- CHANGE PROJECT

- CCTT 2

© 2014 Fluke Corporation. All rights reserved

SAVING A PROJECT TO A PC

Page 75: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 75/199

• You can also download your project into LinkWare

© 2014 Fluke Corporation. All rights reserved

EXPORTING/IMPORTING QUIRK

Page 76: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 76/199

• When you download a project to a PC, the file format is:

- *.vps

• When you export a project to a thumb drive, the file format is:

- *.sql

• If you wish to push a thumb drive project *.sql to a Versiv usingLinkWare, you will need to first Import from USB, save it as a *.vps

and then Write Project Setup using the new *.vps file

• If you copy a *.vps file to a thumb drive, Versiv will not see that fileif you try to import it, you will need to Export to USB first

© 2014 Fluke Corporation. All rights reserved

Page 77: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 77/199

Page 78: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 78/199

Making a measurement and

reviewing the results

© 2014 Fluke Corporation. All rights reserved.

SETTING A REFERENCE

Page 79: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 79/199

• It is recommended to do this for each testing shift

- Synchronizes the remote unit to the main unit

- You can reference up to eight remote units

- Units should be left on ≈ 5 minutes before setting a reference

- Connect using a Permanent Link Adapter and Channel Adapter

DSX-PLA004

Perm. Link Adapter

DSX-CHA004

Channel Adapter

© 2014 Fluke Corporation. All rights reserved

SETTING A REFERENCE

Page 80: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 80/199

• From the HOME screen, tap:

- TOOLS:

- Set Reference

- TEST

- DONE

DSX-PLA004

Perm. Link Adapter

DSX-CHA004

Channel Adapter

© 2014 Fluke Corporation. All rights reserved

Ch h j CCTT 1

REVIEWING A TEST

Page 81: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 81/199

• Change the project to CCTT 1

• Connect to the link in front of you

• Press TEST

© 2014 Fluke Corporation. All rights reserved

Page 82: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 82/199

C t j t ll d “CCTT 3” f

TASK #1

Page 83: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 83/199

• Create a new project called “CCTT 3” for:

- Category 5e cable

- NVP of 65 %

- Category 5e Permanent Link test limit

- With Resistance Unbalance

- T568A outlet configuration

- Plot Data enabled

- No AC Wire Map

- Cable ID:

- B.1-01

- …….

- B.1-96

© 2014 Fluke Corporation. All rights reserved

• Create a new project called “CCTT 4” for

TASK #1

Page 84: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 84/199

• Create a new project called “CCTT 4” for:

- Category 3 cable

- NVP of 65 %

- Length/Wire Map test

- 4,5 Pair only

- Plot Data enabled

- No AC Wire Map

- Cable ID:

- V.1-01A to V.1-96B

© 2014 Fluke Corporation. All rights reserved

Page 85: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 85/199

Page 86: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 86/199

DSX Diagnostics

© 2014 Fluke Corporation. All rights reserved.

• HDTDX

TIME DOMAIN DIAGNOSTIC

Page 87: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 87/199

• HDTDX

- High Definition Time Domain Xtalk

- Allows you to look down the cable and see where the Xtalk is

- Used for troubleshooting NEXT issues

• HDTDR

- High Definition Time Domain Reflectometer- Allows you to look down the cable and see impedance anomalies

- Excessive impedance anomalies cause Return Loss issues

- Used for troubleshooting Return Loss issues

© 2014 Fluke Corporation. All rights reserved

Page 88: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 88/199

DSX HDTDX Diagnostics

© 2014 Fluke Corporation. All rights reserved.

• New HDTDX schemed where DSX is better at higher frequencies

NEW VS. OLD TDX

Page 89: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 89/199

New HDTDX schemed where DSX is better at higher frequencies

Old TDX

New TDX

© 2014 Fluke Corporation. All rights reserved

Page 90: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 90/199

• Where the connections are, ideally ≤ 35%

HDTDX GUIDE #1

Page 91: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 91/199

Where the connections are, ideally ≤ 35%

35% 35%

© 2014 Fluke Corporation. All rights reserved

• In the cable, ideally no more than four events ≥ 10%

HDTDX GUIDE #2

Page 92: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 92/199

In the cable, ideally no more than four events ≥ 10%

Cable not an issue in this example

© 2014 Fluke Corporation. All rights reserved

• Let’s view the HDTDX plot

NEXT FAILURE #1

Page 93: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 93/199

p

• From the Results screen, tap:

- DIAGNOSTIC

- HDTDX ANALYZER

- Select the worst NEXT pair (3,6-4,5)

• With a value of 46.1%, that exceeds ourguideline of 35% by some margin

• Clearly there is an issue at the remote

connection

© 2014 Fluke Corporation. All rights reserved

Page 94: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 94/199

• Here we see NEXT failed

NEXT FAILURE #2

Page 95: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 95/199

• Let’s look at the plot

• Find the worst pair

- 3,6-4,5

© 2014 Fluke Corporation. All rights reserved

Page 96: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 96/199

Page 97: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 97/199

DSX HDTDR Diagnostics

© 2014 Fluke Corporation. All rights reserved.

• In the cable, ideally events ≤ |0.8|

HDTDR GUIDE #1

Page 98: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 98/199

0.8%

-0.8%

Multiple events in cable

exceeding |0.8| suggests a

cable issue

At 13.6 m, the anomaly is as

much as you would expect

for a connection, this should

be visible damage

© 2014 Fluke Corporation. All rights reserved

Page 99: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 99/199

• What is HDTDX used for?

REVIEW #6

Page 100: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 100/199

• What is HDTDR used for?

• What is the ideal limit for an HDTDX event at a connection?

• What is the ideal limit for a series of HDTDX events in the cable?

• What is the ideal limit for a series of HDTDR events in the cable?

• Using the Diagnostics menu can result in ……………….?

© 2014 Fluke Corporation. All rights reserved

Page 101: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 101/199

Patch cord certification

© 2014 Fluke Corporation. All rights reserved.

CHANNEL ADAPTERS

• The channel measurement excludes the connection to the adapters

Page 102: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 102/199

• For patch cords, we want to measure that RJ45 connection

• This is not a valid test

• You are only measuring the cable

• Patch cord testing is found in

- ANSI/TIA-568-C.2

- ISO/IEC 11801:2010 and IEC 61935-2

© 2014 Fluke Corporation. All rights reserved

PATCH CORD ADAPTERS

• The patch cord measurement includes the connection to the adapters

Page 103: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 103/199

• Using patch cord adapters, DSX includes that RJ45 connection

• A special laboratory tested RJ45 Jack is used

- Called out in standards for patch cord certification

• The patch cord limits are tighter than the Channel limits as well

© 2014 Fluke Corporation. All rights reserved

• Same patch cord, different adapters/limits

CHANNEL VS PATCH CORD TESTING

Page 104: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 104/199

Margin looks too good? You are only measuring the cable, nothing else, so yes!

© 2014 Fluke Corporation. All rights reserved

• DSX-PC5e

F i ISO/IEC 11801 d ANSI/TIA 568 C 2 C 5

THREE PATCH CORD ADAPTERS

Page 105: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 105/199

- For testing to ISO/IEC 11801 and ANSI/TIA-568-C.2 Category 5e

• DSX-PC6- For testing to ISO/IEC 11801 and ANSI/TIA-568-C.2 Category 6

• DSX-PC6A

- For testing to ISO/IEC 11801 Category 6A and ANSI/TIA-568-C.2 Category 6A*

• The DSX-PC6A is not backward compatible with Cat 6 or 5e

* ANSI/TIA currently specifies a jack with a different performance to ISO/IEC.

However, ANSI/TIA is in the process of allowing the jack specified in ISO/IEC for patch

cord certification, so the DSX contains the proposed limits for Cat 6A testing

© 2014 Fluke Corporation. All rights reserved

• Why can’t we use the patch cord adapter for channel testing too?

b l d d i h i

WHY TWO ADAPTERS?

Page 106: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 106/199

• FEXT cannot be excluded using DSP techniques

• Need an adapter with excellent FEXT

• The patch cord adapter does not have excellent FEXT

- It must meet specific FEXT requirements of ANSI/TIA and IEC

• The channel adapter has excellent FEXT

- But as a result, it has poor NEXT

- That’s ok, because it can be gated out using DSP techniques

Excellent FEXT FEXT limited by standards requirement© 2014 Fluke Corporation. All rights reserved

• Give two reasons why you cannot use Channel Adapters to certify

patch cords

REVIEW #7

Page 107: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 107/199

patch cords

• How is the DSX patch cord testing different to the DTX patch cord

testing?

• What categories can patch cords be certified to using the DSX-PC6?

• What is the typical life of a patch cord adapter?

© 2014 Fluke Corporation. All rights reserved

Page 108: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 108/199

Alien Crosstalk(Exogenous Crosstalk)

© 2014 Fluke Corporation. All rights reserved.

WHAT IS ALIEN CROSSTALK?

• Alien crosstalk is the coupling of noise from one link to the other

h bl b h bl f h bl

Page 109: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 109/199

• When a cable is surrounded by other cables, noise from those cables

will impact its ability to transmit data – we call that Alien Crosstalk

• The cable we wish to measure for Alien Crosstalk is called the

Disturbed (Victim) and the adjacent cables are called the DisturbersDisturbers

Disturbed (Victim)

© 2014 Fluke Corporation. All rights reserved.

 ALIEN CROSSTALK INSTALLATION TESTING

• ANSI/TIA-568-C.2 and ANSI/TIA-1152

Th i t t t ti PS ANEXT d PS AACR F t ti i ti l

Page 110: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 110/199

- There is no text stating PS ANEXT and PS AACR-F testing is optional

- PS ANEXT and PS AACR-F are required for compliance

- Values and methodology are found in ANSI/TIA-568-C.2

• ISO/IEC 11801:2010 and IEC 61935-1

- PS ANEXT and PS AACR-F is normative for field testing

- Specified in section A.2.11 …………… if not met by design

- If the coupling attenuation of Class EA or F permanent links or CP links is at least

10 dB better than the corresponding channel coupling attenuation requirements

(see Clause 6), and Class FA permanent links or CP links are at least 25 dB better

than the corresponding channel coupling attenuation requirements (see Clause 6),

then the requirements of A.2.11 are met by design.

- No way for you to know the coupling attenuation, not a field test

© 2014 Fluke Corporation. All rights reserved.

SHIELDED CABLING SYSTEMS

• Shielded cabling systems should perform better than unshielded

cabling systems if installed correctly

Page 111: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 111/199

cabling systems – if installed correctly

Shield terminated correctly Shield terminated incorrectly

Both links pass the TIA Cat 6A Permanent Link requirements with good margin© 2014 Fluke Corporation. All rights reserved.

 ALIEN CROSSTALK MEASUREMENTS

• There are 16 ANEXT measurements between a disturbed (victim) cable

and a disturber cable

Page 112: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 112/199

and a disturber cable

PS ANEXT 1,2

PS ANEXT 4,5

PS ANEXT 7,8

PS ANEXT 4,5

© 2014 Fluke Corporation. All rights reserved.

Page 113: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 113/199

Fiber testing

Tier 1 and Tier 2

© 2014 Fluke Corporation. All rights reserved.

TIER 1 AND TIER 2

• Tier 1

- Often referred to as OLTS or Optical Loss Test Set

Page 114: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 114/199

p

- Uses a source and power meter- Reports the difference between power in and power out in dB

- Duplex (two fiber) testers can also measure length

• Tier 2

- Often referred to as OTDR or Optical Time Domain Reflectometer testing

- Injects a series of light pulses into a fiber and measures the backscatter

returned to the OTDR port

- Single ended test but must be done in both directions

- Implies loss based on change in backscatter between events

- Depends on good reflectance which field polishing often fails to achieve

© 2014 Fluke Corporation. All rights reserved

EQUIPMENT REQUIRED FOR THIS COURSE

• Versiv main and remote units

• CertiFiber Pro Modules

Page 115: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 115/199

• CertiFiber Pro Modules

• EF-TRCs

• One LC to LC Duplex Cord

- This will be our link to test

• Four LC couplers/adapters

• FiberInspector

• OptiFiber Pro Module

• Three SC Multimode Launch Fibers

• Two SC Singlemode couplers/adapters

© 2014 Fluke Corporation. All rights reserved.

FOREWORD

• Many of the fiber (fibre) calculations you do today will be in meters

(metres)

Page 116: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 116/199

(metres)

• ANSI/TIA-568-C.3 cable requirements are expressed as dB/km

• Where calculations are not involved, screen shots will be in the units

appropriate for your region

• This course will also cover ISO/IEC 14763-3

© 2014 Fluke Corporation. All rights reserved.

IMPORTANT SAFETY NOTE

• Under NO circumstances should you ever look into a fiber

Page 117: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 117/199

• The wavelength being used cannot be seen by the naked eye

• Light from an active fiber if powerful enough, can do permanent damage toyour eye sight

• The equipment you are using today cannot do permanent damage to your

eye sight if exposed occasionally

• If you are told a fiber is not active, treat it as if it is

• NEVER stand in front of a fiber patch panel unless ALL of the fiber connectors

have a protective cap on them

• Wash your hands BEFORE and AFTER going to the bathroom

© 2014 Fluke Corporation. All rights reserved.

NO POINT IN LOOKING INTO A FIBER

YOU WILL NOT SEE ANYTHING!

Page 118: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 118/199

© 2014 Fluke Corporation. All rights reserved.

DESIGNATION

• The following applies to ANSI/TIA-568-C and ISO/IEC 11801:2010

Page 119: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 119/199

- OM1: 62.5 µm multimode fiber with a MBW of 200 MHz.km

- OM2: 50 µm multimode fiber with a MBW of 500 MHz.km

- OM3: 50 µm multimode fiber with a MBW of 2000 MHz.km

- OM4: 50 µm multimode fiber with a MBW of 4700 MHz.km

- OS1: 9 µm singlemode fiber

- OS2: 9 µm Low Water Peak singlemode fiber

© 2014 Fluke Corporation. All rights reserved.

DESIGNATION

• OM1 Orange jacket

Page 120: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 120/199

• OM2 Orange jacket

• OM3/OM4. Aqua jacket

• OS1 /OS2 Yellow jacket

© 2014 Fluke Corporation. All rights reserved.

MULTIMODE FIBERS

• Mode: from the Latin “path”; so it means multi-paths

Page 121: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 121/199

• The modes arrive at different times causing the signal to spread

125 µm62.5 µm

© 2014 Fluke Corporation. All rights reserved.

 APPLICATIONS LIMITED BY DISPERSION/LOSS

• Modal Bandwidth (MBW)

- is the unit to classify dispersion in the cable

Page 122: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 122/199

• 50 /125 µm has less dispersion

-  – it’s core is smaller than 62.5/125 µm fiber

• Your loss may be lower than the allowed fixed loss, but if it exceeds

the length found here (IEEE 802.3) there may be errors on the network

• IEEE 802.3ae specifies 400 m, cabling vendors may specify 550 m

© 2014 Fluke Corporation. All rights reserved.

SINGLEMODE FIBERS

• Mode: from the Latin “path”; so it means single-path

Page 123: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 123/199

125 µm9 µm

• There is only one mode, so no signal spreading this time

© 2014 Fluke Corporation. All rights reserved.

MIXING MULTIMODE FIBERS

• What happens when you connect a 62.5/125 µm to a 50/125 µm?

Page 124: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 124/199

• Many of the modes will disappear into the cladding – forever!

• There will be a significant loss (as large as 4 dB)

• Also known as a coupling loss

• This happens a great deal as users migrate from 62.5 to 50 µm fiber

125 µm50 µm

© 2014 Fluke Corporation. All rights reserved.

Page 125: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 125/199

Encircled Flux (EF)

© 2014 Fluke Corporation. All rights reserved.

• Test equipment #1, loss is 1.06 dB

LAUNCH CONDITIONS

Page 126: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 126/199

© 2014 Fluke Corporation. All rights reserved

• Diagrams shown to visualize the issue as best as possible

LAUNCH CONDITIONS

Page 127: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 127/199

Source 1

Over filled

Source 2

Under filled

© 2014 Fluke Corporation. All rights reserved

CPR ASSESSMENT SHORTFALLANSI/TIA-526-14-A (Obsolete Standard)

Coupled Power Ratio compares power in center to total power

Page 128: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 128/199

Source 1

Over filled

Source 2

Under filled

Coupled Power Ratio compares power in center to total power.

It can’t provide assessment of mode power distribution in the outer radii

which is critical to obtain good agreement with different test instruments.

© 2014 Fluke Corporation. All rights reserved

EF ASSESSMENT IMPROVEMENT

EF specifies power throughout core using multiple control radii.

ANSI/TIA-526-14-B August 2010 (Current Standard)

Page 129: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 129/199

Source 1

Over filled

Source 2

Under filled

EF provides tight tolerance on mode power distribution in the outer radii

enabling improved agreement between EF-compliant test instruments.

© 2014 Fluke Corporation. All rights reserved

REVIEW #9

• Why should you never look into a fiber?

Page 130: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 130/199

• What’s the difference between OM2 and OM3 fiber?

• What is the maximum length you can run 10GBASE-SR to?

• Why is it important to know which OM fiber you are testing?

• What does having a EF compliant source do for you?

© 2014 Fluke Corporation. All rights reserved.

Page 131: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 131/199

Configuring the CertiFiber Pro

© 2014 Fluke Corporation. All rights reserved.

• From the HOME screen, tap:

- PROJECT

DUPLEX FIBER TESTING - CONFIGURATION

Page 132: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 132/199

- CHANGE PROJECT- NEW PROJECT

- Enter CCTT 5

- DONE

© 2014 Fluke Corporation. All rights reserved

• From the PROJECT screen, tap:

- Test limit name

DUPLEX FIBER TESTING - CONFIGURATION

Page 133: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 133/199

- Test Type:- BACK

   L   o   o   p   B   a   c

    k

   F   a   r   E   n    d   S   o   u

   r   c   e

   S   m   a   r   t   R   e   m

   o   t   e

© 2014 Fluke Corporation. All rights reserved

Page 134: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 134/199

• Fiber Type Setting

- Shows the Index of Refraction for the

cable type you selected previously

DUPLEX FIBER TESTING - CONFIGURATION

Page 135: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 135/199

- Not changeable

- If you want to change it, create a custom

cable type

© 2014 Fluke Corporation. All rights reserved

• Test Limit:

- Most common will show on the last used

DUPLEX FIBER TESTING - CONFIGURATION

Page 136: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 136/199

- For more options, tap MORE

© 2014 Fluke Corporation. All rights reserved

Page 137: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 137/199

• Test Limit:

- Most common will show on the last used

F i O

DUPLEX FIBER TESTING - CONFIGURATION

Page 138: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 138/199

- For more options, tap MORE- Today we will use TIA, tap TIA

- If you wanted singlemode to appear,

you would need the change the cable

type to a singlemode one

- Tap TIA-568-C Multimode

© 2014 Fluke Corporation. All rights reserved

• Reference Method:

- Tap Reference Method

A i t DTX i th bilit

DUPLEX FIBER TESTING - CONFIGURATION

Page 139: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 139/199

- An improvement over DTX is the abilityto change all these options on one screen

© 2014 Fluke Corporation. All rights reserved

• Reference Method:

- Tap Reference Method

A i t DTX i th bilit

DUPLEX FIBER TESTING - CONFIGURATION

Page 140: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 140/199

- An improvement over DTX is the abilityto change all these options on one screen

- Change it from 1 Jumper Reference to a

2 Jumper Reference

- Tap DONE

- Change it back to 1 Jumper

WARNING:Applying for a cabling warranty? They will reject any results where a 2 Jumper Reference is used.

© 2014 Fluke Corporation. All rights reserved

• Connector Type:

- Tap Connector Type

N t V i 2 3

DUPLEX FIBER TESTING - CONFIGURATION

Page 141: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 141/199

- New to Version 2.3- If bi-directional is turned on, the auto

continue feature will be disabled if you

select General , ST or FC here

- Does not affect the outcome of the test

- We’ll leave it as LC today

© 2014 Fluke Corporation. All rights reserved

• Connector Type: MPO Module

- An MPO Module consists of an LC and MPO/MTP connector

- In TIA, this is two connections

DUPLEX FIBER TESTING - CONFIGURATION

Page 142: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 142/199

- In the real world, the vendors treat this as one connection

© 2014 Fluke Corporation. All rights reserved

• TEST SETUP:

- Now completed

- Tap SAVE!!!!!!!

DUPLEX FIBER TESTING - CONFIGURATION

Page 143: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 143/199

- Don’t tap

this will cancel your changes

© 2014 Fluke Corporation. All rights reserved

• TEST SETUP:

- Now completed

- Tap SAVE!!!!!!!

DUPLEX FIBER TESTING - CONFIGURATION

Page 144: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 144/199

- Don’t tap

this will cancel your changes

- Press the HOME key

© 2014 Fluke Corporation. All rights reserved

Page 145: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 145/199

Page 146: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 146/199

Fiber end face inspection

© 2014 Fluke Corporation. All rights reserved.

Page 147: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 147/199

CLEANING KIT

• Isopropyl Alcohol (IPA) is typically used

- It should be better than 98% (rubbing alcohol is 70%)

- Local pharmacy stocks no better than 91% (not good enough)

Page 148: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 148/199

Local pharmacy stocks no better than 91% (not good enough)• There are disadvantages to IPA

- Over time, absorbs water and is no longer 98%

- Will not remove non ionic compounds

- Tends to leave a residue behind if you are not careful

• Hybrid cleaners are better, such as the Fluke Networks Fiber Optic Pen

• There are significant advantages with these new hybrid cleaners

- Aggressive cleaner, better than IPA

- Evaporates very quickly, less likely to leave residue behind

- Has antistatic properties so dust in the air is less likely to be attracted to the endface of the connector

© 2014 Fluke Corporation. All rights reserved.

CLEANING KITS

Page 149: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 149/199

Wet to dry cleaning is ALWAYS better

Click pens ideal for ports, not for cleaning

patch cords where end faces are subject

to grease from fingers

© 2014 Fluke Corporation. All rights reserved.

• Click Cleaners for cleaning different end

faces/connectors — no training required

- 1.25 mm LC and MU connector and end faces

2 5 mm SC ST FC E2000 connector and end faces

CLEANING WITH CLICK CLEANERS

Page 150: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 150/199

- 2.5 mm SC, ST, FC, E2000 connector and end faces

- MPO/MTP connector and end faces

• Cleans Ports on devices and patch panels

as well as Cords ….with an adapter

• Dry cleaning is less efficient for cleaning

grease (dried skin oil) than wet cleaning

with a solvent and swabs/cleaning cubes

© 2014 Fluke Corporation. All rights reserved

• Peel cover from unused “N.”

• Apply a minimal amount of solvent from the Solvent Pen

• Place end-face perpendicular to card in first corner of unused “N”

OPTIMAL CLEANING METHOD

Page 151: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 151/199

• Swipe through “N” shape using gentle pressure and moving from

wet to dry• Check end-face with microscope, place cap on test reference cord

© 2014 Fluke Corporation. All rights reserved

• Examinations and measurements – Fibre optic connector endface

visual and automated inspection

• With Version 3 or later code, your Versiv mainframe with theoptional FiberInspector can inspect the endface of a connector and

IEC 61300-3-35

Page 152: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 152/199

With Version 3 or later code, your Versiv mainframe with theoptional FiberInspector can inspect the endface of a connector and

grade it per this standard

• Four limits to choose from:

- IEC 61300-3-35 MM

- IEC 61300-3-35 SM RL>=45dB

- IEC 61300-3-35 SM RL>=26dB

- IEC 61300-3-35 SM APC

© 2014 Fluke Corporation. All rights reserved

• Multimode – both field and factory polished

IEC 61300-3-35 MM

Page 153: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 153/199

A B

C

D

© 2014 Fluke Corporation. All rights reserved

• Singlemode– field polished

IEC 61300-3-35 RL>=26dB

Page 154: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 154/199

A B

C

D

© 2014 Fluke Corporation. All rights reserved

• Here is your nice newly installed fiber optic connector

CROSS CONTAMINATION

Page 155: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 155/199

IEC 61300-3-35

Page 156: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 156/199

• Here is your nice newly installed fiber optic connector after it was

tested with the “typical” test cord

CROSS CONTAMINATION

Page 157: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 157/199

IEC 61300-3-35

• From the HOME screen, tap:

- PROJECT

- NEW TEST

- Test Type

 AUTOMATED FIBER INSPECTION

Page 158: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 158/199

yp

- FiberInspector

- SAVE

- Press the HOME key

© 2014 Fluke Corporation. All rights reserved

• From the HOME screen, tap:

- Smart Remote

- FiberInspector

- USE SELECTED

 AUTOMATED FIBER INSPECTION

Page 159: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 159/199

© 2014 Fluke Corporation. All rights reserved

• Using the FiberInspector camera

- Connect to your first TRC

- Tap TEST & ANALYZE

INSPECT AND CLEAN ALL TRCS

Page 160: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 160/199

• Gently place caps back on after inspecting and cleaning

© 2014 Fluke Corporation. All rights reserved

REVIEW #10

• What are the three test types the CertiFiber Pro can do?

• Is bi-directional testing required?

Page 161: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 161/199

• Selecting General, ST or FC as a connector type does what?

• Give one limitation of the Click fiber cleaning pens?

• How many fiber inspection limits are there in Versiv?

© 2014 Fluke Corporation. All rights reserved.

Page 162: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 162/199

Setting a duplex reference

(Dual fiber OLTS)

© 2014 Fluke Corporation. All rights reserved.

• From the HOME screen, tap:

- FiberInspector

- Smart Remote

- USE SELECTED

DUPLEX FIBER TESTING - REFERENCE

Page 163: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 163/199

© 2014 Fluke Corporation. All rights reserved

Page 164: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 164/199

• Press the TEST button

- Two fibers at the same time are tested

- Both 850 nm and 1300 nm covered

- Length is from round trip delay

DUPLEX FIBER TESTING - MEASUREMENT

Page 165: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 165/199

- Does not use OTDR technique for length

© 2014 Fluke Corporation. All rights reserved

• Tap SETTINGS

- Recorded with every result

- Can be recalled later on

- Swipe up to see more

DUPLEX FIBER TESTING – ANALYSIS

Page 166: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 166/199

© 2014 Fluke Corporation. All rights reserved

• Tap DONE

• Tap SAVE

• New to Version 2.3

DUPLEX FIBER TESTING – ANALYSIS

Page 167: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 167/199

New to Version 2.3

- Allows you to reverse IDs

• Tap SAVE to save the two fibers

© 2014 Fluke Corporation. All rights reserved

• Connected to a bad fiber

- Let’s retest

• Two options

DUPLEX FIBER TESTING – ANALYSIS

Page 168: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 168/199

- Fix the link now and tap TEST AGAIN

- Tap FIX LATER which saves the result

and allows you to continue testing

- We’ll tap FIX LATER

© 2014 Fluke Corporation. All rights reserved

Page 169: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 169/199

• Tap RESULTS

- ProjX allows you to track what has

been tested and which links failed

DUPLEX FIBER TESTING – ANALYSIS

Page 170: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 170/199

© 2014 Fluke Corporation. All rights reserved

• Tap failing result

- With our link fixed, we can TEST AGAIN

DUPLEX FIBER TESTING – ANALYSIS

Page 171: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 171/199

© 2014 Fluke Corporation. All rights reserved

• Tap failing result

- With our link fixed, we can TEST AGAIN

DUPLEX FIBER TESTING – ANALYSIS

Page 172: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 172/199

© 2014 Fluke Corporation. All rights reserved

REVIEW #11

• What is the maximum TRC check verification value for multimode?

• What is the maximum TRC check verification value for singlemode?

Page 173: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 173/199

• How does the CertiFiber Pro measure length?

• Name the two types of custom test limits you can create

• Why is it important to be able to measure length?

© 2014 Fluke Corporation. All rights reserved.

b

Page 174: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 174/199

Tier 2 Fiber Testing

(OTDR)

© 2014 Fluke Corporation. All rights reserved.

WHAT IS AN OTDR?

• Optical – measurements carried out using pulses of light.

• Time Domain – signal is plotted against time delay.

•Reflectometer - signal we’re looking at is caused by reflections

(and scattering) in the fiber.

Page 175: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 175/199

• The OTDR launches a very short pulse of light into a fiber and then

looks at the very low levels of light which come back out of the

same end of the fiber.

• This returned light comes from reflections where there is a change

of refractive index in the light path (called Fresnel reflections) and

from a scattering effect which takes place within the fiber calledRayleigh Scattering.

© 2014 Fluke Corporation. All rights reserved

WHAT IS AN OTDR?

• The OTDR produces a trace of the returning light level against the

time delay compared to when the pulse of light was launched.

Page 176: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 176/199

© 2014 Fluke Corporation. All rights reserved

WHAT IS AN OTDR?

• With suitable processing and interpretation, this trace can then be

used to provide information about every portion of the fiber being

measured

• EventMap™ interprets the trace for you

Page 177: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 177/199

© 2014 Fluke Corporation. All rights reserved

• Although the fiber is tested in the factory, it can be

damaged during delivery or storage on site

• It is standard practice to use an OTDR to ensure no

breaks in the cable – but requires “expertise” to review the traces

CAN BE USED TO TEST A REEL OF FIBER

Page 178: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 178/199

Mechanical splice*

*Could be a mechanical connector© 2014 Fluke Corporation. All rights reserved

REVIEW #12

• OTDR is short for?

• How are Fresnel reflections caused?

Page 179: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 179/199

• What is a reflective event?

• What is a non reflective event?

• What is a ghost and how is it caused?

© 2014 Fluke Corporation. All rights reserved.

L h Fib C ti

Page 180: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 180/199

Launch Fiber Compensation

© 2014 Fluke Corporation. All rights reserved.

• The launch cable allows the OptiFiber Pro trace to settle down after

the test pulse is sent into the fiber so

you can analyze the first connection

• OptiFiber Pro gives you four options

to eliminate the length and loss of the

LAUNCH AND TAIL FIBERS

Page 181: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 181/199

g

launch/tail fibers from your

measurement

   L   a   u   n   c    h   F   i    b   e   r

© 2014 Fluke Corporation. All rights reserved

Page 182: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 182/199

Page 183: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 183/199

• From the Project screen, tap:

- Test Limit

- MORE

- Custom

- MANAGE

CUSTOM LIMITS

Page 184: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 184/199

- Create

© 2014 Fluke Corporation. All rights reserved

• From the NEW CUSTOM LIMIT screen, tap:

- Enter New Limit Name

- Enter FNET MM

- DONE

- Length

CUSTOM LIMITS

Page 185: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 185/199

- Enter 300 m

- DONE

© 2014 Fluke Corporation. All rights reserved

• From the NEW CUSTOM LIMIT screen, tap:

- Limits for 850 nm

- Max: 0.75

- Enter 0.5

- DONE

CUSTOM LIMITS

Page 186: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 186/199

- Max: 0.30

- Enter 0.2

- DONE

- Swipe up to Segment Attenuation……

- Max: N/A

- Enter 3

- DONE

- DONE

© 2014 Fluke Corporation. All rights reserved

• From the NEW CUSTOM LIMIT screen, tap:

- Limits for 1300 nm

- Max: 0.75

- Enter 0.5

- DONE

CUSTOM LIMITS

Page 187: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 187/199

- Max: 0.30

- Enter 0.2

- DONE

- Swipe up to Segment Attenuation……

- Max: N/A

- Enter 1

- DONE

- DONE

© 2014 Fluke Corporation. All rights reserved

Page 188: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 188/199

• From the NEW CUSTOM LIMIT screen, tap:

- SAVE

- *FNET MM* to select it

- Launch Compensation ON

- SAVE

CUSTOM LIMITS

Page 189: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 189/199

© 2014 Fluke Corporation. All rights reserved

REVIEW #13

• Name the four types of launch compensation

•What does pulse width affect?

• Increasing averaging does what?

Page 190: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 190/199

• Increasing averaging does what?

• What is the default loss threshold on the OptiFiber Pro?

• Reducing the loss threshold will also require what to be changed??

© 2014 Fluke Corporation. All rights reserved.

Tier 2 Link Testing

Page 191: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 191/199

Tier 2 Link Testing

© 2014 Fluke Corporation. All rights reserved.

Page 192: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 192/199

• For every OTDR measurement you make, OptiFiber Pro will assess

your port connection quality

• We want to see it in the green

OTDR PORT CONNECTION QUALITY

Page 193: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 193/199

• Anything less could affect your

OTDR measurement

© 2014 Fluke Corporation. All rights reserved

• The OTDR Port Connection Quality is recorded with every test

result and viewable in LinkWare

OTDR PORT CONNECTION QUALITY

Page 194: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 194/199

• It cannot be turned off 

• It is critical to know that the launch was good

© 2014 Fluke Corporation. All rights reserved

• From the SET LAUNCH COMP screen tap:

- SAVE

LAUNCH + TAIL COMPENSATION

Page 195: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 195/199

© 2014 Fluke Corporation. All rights reserved

• From the SET LAUNCH COMP screen tap:

- OK

LAUNCH + TAIL COMPENSATION

Page 196: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 196/199

© 2014 Fluke Corporation. All rights reserved

• From the TOOLS screen, press the HOME key

• We’re going to check our fibers first by

tapping:

- TEST

- Ignore this warning

OK

LAUNCH + TAIL COMPENSATION

Page 197: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 197/199

- OK

© 2014 Fluke Corporation. All rights reserved

Page 198: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 198/199

REVIEW #14

• How do you ensure your launch fibers are good?

• Is this Port Connection Quality acceptable?

• What’s the standard for fiber inspection?

Page 199: Versiv CCTT Version 1.0 n

8/11/2019 Versiv CCTT Version 1.0 n

http://slidepdf.com/reader/full/versiv-cctt-version-10-n 199/199

p

• Why is it good to set a reflectance limit?

• When would you want to set a segment attenuation limit?

© 2014 Fluke Corporation. All rights reserved.