ventilation intake.pdf
TRANSCRIPT
-
8/10/2019 Ventilation Intake.pdf
1/5
1- Fan Capacity
( Air changes Per Hour )
Length Width Hight Air Louvers For supply air
Pump House Volume 10.25 4.75 6.3 306.7313 m
Air Changes / Hour 6 Exhaust air = 1840 m/hr >>>>> 0.511111 m/s
6:8 Times in hour Velocity on face Louver = 8 m/s
Ventilation air Flow rate 1840 m/hr Then Area Required to Get Fresh Air = 0.063889 m
Let No of Louvers = 4 No.
No. Of Fans 0.92 Fan
Then Louver Area = 0.015972 mCapacity of Fan 2000 m/hr Put Length = 0.6 m
Then Width = 0.02662 m
Then No. Of Fans = 1 Fans
2- Fan Capacity
( Air changes Per Hour )
Length Width Hight Air Louvers For supply air
Pump House Volume 5 5 6.3 157.5 m
Air Changes / Hour 10 Exhaust air = 1575 m/hr >>>>> 0.4375 m/s
8:10 Times in hour Velocity on face Louver = 8 m/s
Ventilation air Flow rate 1575 m/hr Then Area Required to Get Fresh Air = 0.054688 m
Let No of Louvers = 4 No.
No. Of Fans 0.875 Fan
Then Louver Area = 0.013672 m
Capacity of Fan 1800 m/hr Put Length = 0.6 m
Then Width = 0.022786 m
Then No. Of Fans = 1 Fans
TRANSFORMER ROOMS VENTILATION ( INTAKE )
6
M.L.T.S.G Room
Egyption Code
TR1
Egyption Code
-
8/10/2019 Ventilation Intake.pdf
2/5
TRANSFORMER ROOMS VENTILATION ( INTAKE )
6
3- Fan Capacity
( Air changes Per Hour )
Length Width Hight Air Louvers For supply air
Pump House Volume 5 5 6.3 157.5 m
Air Changes / Hour 10 Exhaust air = 1575 m/hr >>>>> 0.4375 m/s
8:10 Times in hour Velocity on face Louver = 8 m/s
Ventilation air Flow rate 1575 m/hr Then Area Required to Get Fresh Air = 0.054688 m
H Hight of room Let No of Louvers = 4 No.
No. Of Fans 0.875 Fan as per Drawings
Then Louver Area = 0.013672 mCapacity of Fan 1800 m/hr Put Length = 0.6 m
Then Width = 0.022786 m
Then No. Of Fans = 1 Fans
4- Fan Capacity
( Air changes Per Hour )
Length Width Hight Air Louvers For supply air Pump House Volume 10 16.25 6.3 1023.75 m
Air Changes / Hour 7 Exhaust air = 7166.25 m/hr >>>>> 1.990625 m/s
6:8 Times in hour Velocity on face Louver = 8 m/s
Ventilation air Flow rate 7166.25 m/hr Then Area Required to Get Fresh Air = 0.248828 m
Let No of Louvers = 4 No.
No. Of Fans 1.990625 Fan
Then Louver Area = 0.062207 m
Capacity of Fan 3600 m/hr Put Length = 0.6 m
Then Width = 0.103678 m
Then No. Of Fans = 2 Fans
TR2
Egyption Code
First Stage M.V.S.G Room
Egyption Code
-
8/10/2019 Ventilation Intake.pdf
3/5
TRANSFORMER ROOMS VENTILATION ( INTAKE )
6
5- Fan Capacity
( Air changes Per Hour )
Length Width Hight Air Louvers For supply air
Pump House Volume 21.5 10 6.3 1354.5 m
Air Changes / Hour 6 Exhaust air = 8127 m/hr >>>>> 2.2575 m/s
6:8 Times in hour Velocity on face Louver = 8 m/s
Ventilation air Flow rate 8127 m/hr Then Area Required to Get Fresh Air = 0.282188 m
Let No of Louvers = 4 No.
No. Of Fans 4.0635 Fan
Then Louver Area = 0.070547 mCapacity of Fan 2000 m/hr Put Length = 0.6 m
Then Width = 0.117578 m
Then No. Of Fans = 4 Fans
6- Fan Capacity
( Air changes Per Hour )
Length Width Hight Air Louvers For supply air Pump House Volume 10 16.25 6.3 1023.75 m
Air Changes / Hour 7 Exhaust air = 7166.25 m/hr >>>>> 1.990625 m/s
6:8 Times in hour Velocity on face Louver = 8 m/s
Ventilation air Flow rate 7166.25 m/hr Then Area Required to Get Fresh Air = 0.248828 m
Let No of Louvers = 2 No.
No. Of Fans 1.990625 Fan
Then Louver Area = 0.124414 m
Capacity of Fan 3600 m/hr Put Length = 0.6 m
Then Width = 0.207357 m
Then No. Of Fans = 2 Fans
M.V.S.G For Electrical util ity r oom
Second Stage M.V.S.G Room
Egyption Code
Egyption Code
-
8/10/2019 Ventilation Intake.pdf
4/5
TRANSFORMER ROOMS VENTILATION ( INTAKE )
6
7- Fan Capacity
( Air changes Per Hour )
Length Width Hight Air Louvers For supply air
Pump House Volume 10 8 6.3 504 m
Air Changes / Hour 10 Exhaust air = 5040 m/hr >>>>> 1.4 m/s
8:10 Times in hour Velocity on face Louver = 8 m/s
Ventilation air Flow rate 5040 m/hr Then Area Required to Get Fresh Air = 0.175 m
Let No of Louvers = 4 No.
No. Of Fans 2.8 Fan
Then Louver Area = 0.04375 m
Capacity of Fan 1800 m/hr Put Length = 0.6 m
Then Width = 0.072917 m
Then No. Of Fans = 3 Fans
8- Fan Capacity
( Air changes Per Hour )
Length Width Hight Air Louvers For supply air Pump House Volume 10 8 6.3 504 m
Air Changes / Hour 10 Exhaust air = 5040 m/hr >>>>> 1.4 m/s
8:10 Times in hour Velocity on face Louver = 8 m/s
Ventilation air Flow rate 5040 m/hr Then Area Required to Get Fresh Air = 0.175 m
Let No of Louvers = 4 No.
No. Of Fans 2.8 Fan
Then Louver Area = 0.04375 m
Capacity of Fan 1800 m/hr Put Length = 0.6 m
Then Width = 0.072917 m
Then No. Of Fans = 3 Fans
Egyption Code
Second Stage 22/11 Trans 01
Egyption Code
Second Stage 22/11 Trans 02
-
8/10/2019 Ventilation Intake.pdf
5/5
TRANSFORMER ROOMS VENTILATION ( INTAKE )
6
9- Fan Capacity
( Air changes Per Hour )
Length Width Hight Air Louvers For supply air
Pump House Volume 10.25 10 6.3 645.75 m
Air Changes / Hour 6 Exhaust air = 3874.5 m/hr >>>>> 1.07625 m/s
6:8 Times in hour Velocity on face Louver = 8 m/s
Ventilation air Flow rate 3874.5 m/hr Then Area Required to Get Fresh Air = 0.134531 m
Let No of Louvers = 4 No.
No. Of Fans 3.8745 Fan
Then Louver Area = 0.033633 m
Capacity of Fan 1000 m/hr Put Length = 0.6 m
Then Width = 0.056055 m
Then No. Of Fans = 4 Fans
10- Fan Capacity
( Air changes Per Hour )
Length Width Hight Air Louvers For supply air Pump House Volume 9.9 5 6.3 311.85 m
Air Changes / Hour 6 Exhaust air = 1871.1 m/hr >>>>> 0.51975 m/s
6:8 Times in hour Velocity on face Louver = 8 m/s
Ventilation air Flow rate 1871.1 m/hr Then Area Required to Get Fresh Air = 0.064969 m
Let No of Louvers = 4 No.
No. Of Fans 0.93555 Fan
Then Louver Area = 0.016242 m
Capacity of Fan 2000 m/hr Put Length = 0.6 m
Then Width = 0.02707 m
Then No. Of Fans = 1 Fans
Battary Charger room
Egyption Code
Black Start Generator ro om
Egyption Code