Page 1: VEGAPULS 61

Operating InstructionsRadar sensor for continuous level measurement of liquids

VEGAPULS 614 … 20 mA/HART - two-wire

Document ID: 36499

Page 2: VEGAPULS 61

2

Contents

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

Contents1 About this document

1.1 Function ........................................................................................................................... 41.2 Target group ..................................................................................................................... 41.3 Symbols used................................................................................................................... 4

2 For your safety2.1 Authorised personnel ....................................................................................................... 52.2 Appropriate use ................................................................................................................ 52.3 Warning about incorrect use ............................................................................................. 52.4 General safety instructions ............................................................................................... 52.5 CE conformity ................................................................................................................... 62.6 NAMUR recommendations .............................................................................................. 62.7 Radio license for Europe .................................................................................................. 62.8 Radio license for USA/Canada ......................................................................................... 62.9 Environmental instructions ............................................................................................... 7

3 Product description3.1 Configuration .................................................................................................................... 83.2 Principle of operation........................................................................................................ 93.3 Packaging, transport and storage ................................................................................... 103.4 Accessories and replacement parts ............................................................................... 10

4 Mounting4.1 General instructions ....................................................................................................... 134.2 Collaroradapterflange .................................................................................................. 144.3 Mounting preparations, mounting strap .......................................................................... 144.4 Mounting instructions ..................................................................................................... 154.5 Measurement setup - Pipes ........................................................................................... 214.6 Measurement setup - Flow ............................................................................................. 26

5 Connecting to power supply5.1 Preparing the connection ............................................................................................... 285.2 Connecting ..................................................................................................................... 295.3 Wiring plan, single chamber housing.............................................................................. 305.4 Wiring plan, double chamber housing ............................................................................ 315.5 Wiring plan, double chamber housing Ex d ia ................................................................ 335.6 Double chamber housing with DISADAPT ..................................................................... 345.7 Wiring plan - version IP 66/IP 68, 1 bar ........................................................................... 355.8 Switch-on phase............................................................................................................. 35

6 Set up with the display and adjustment module6.1 Insert display and adjustment module ............................................................................ 366.2 Adjustment system ......................................................................................................... 376.3 Measured value indication - Selection national language ............................................... 386.4 Parameter adjustment .................................................................................................... 396.5 Saving the parameter adjustment data ........................................................................... 58

7 Setup with PACTware7.1 Connect the PC .............................................................................................................. 597.2 Parameter adjustment .................................................................................................... 607.3 Saving the parameter adjustment data ........................................................................... 61

Page 3: VEGAPULS 61

3

Contents

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

8 Set up with other systems8.1 DD adjustment programs ............................................................................................... 628.2 Field Communicator 375, 475 ........................................................................................ 62

9 Diagnosis, asset management and service9.1 Maintenance .................................................................................................................. 639.2 Measured value and event memory ............................................................................... 639.3 Asset Management function ........................................................................................... 649.4 Rectify faults ................................................................................................................... 679.5 Exchanging the electronics module ................................................................................ 719.6 Software update ............................................................................................................. 729.7 How to proceed if a repair is necessary .......................................................................... 72

10 Dismount10.1 Dismounting steps.......................................................................................................... 7310.2 Disposal ......................................................................................................................... 73

11 Supplement11.1 Technical data ................................................................................................................ 7411.2 Dimensions .................................................................................................................... 81

Safety instructions for Ex areasTakenoteoftheExspecificsafetyinstructionsforExapplications.These instructions are attached as documents to each instrument with Ex approval and are part of the operating instructions manual.

Editing status: 2015-06-17

Page 4: VEGAPULS 61

4

1 About this document

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

1 About this document

1.1 FunctionThis operating instructions manual provides all the information you need for mounting, connection and setup as well as important instruc-tionsformaintenanceandfaultrectification.Pleasereadthisinforma-tion before putting the instrument into operation and keep this manual accessible in the immediate vicinity of the device.

1.2 Target groupThis operating instructions manual is directed to trained specialist personnel. The contents of this manual should be made available to these personnel and put into practice by them.

1.3 Symbols usedInformation, tip, noteThis symbol indicates helpful additional information.Caution: If this warning is ignored, faults or malfunctions can result.Warning: If this warning is ignored, injury to persons and/or serious damage to the instrument can result.Danger: If this warning is ignored, serious injury to persons and/or destruction of the instrument can result.

Ex applicationsThis symbol indicates special instructions for Ex applications.

• ListThe dot set in front indicates a list with no implied sequence.

→ ActionThis arrow indicates a single action.

1 Sequence of actionsNumbers set in front indicate successive steps in a procedure.

Battery disposalThis symbol indicates special information about the disposal of bat-teries and accumulators.

Page 5: VEGAPULS 61

5

2 For your safety

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

2 For your safety

2.1 Authorised personnelAll operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator.During work on and with the device the required personal protective equipment must always be worn.

2.2 Appropriate useVEGAPULS 61 is a sensor for continuous level measurement.Youcanfinddetailedinformationabouttheareaofapplicationinchapter "Product description".Operational reliability is ensured only if the instrument is properly usedaccordingtothespecificationsintheoperatinginstructionsmanual as well as possible supplementary instructions.

2.3 Warning about incorrect useInappropriate or incorrect use of the instrument can give rise to application-specifichazards,e.g.vesseloverfillordamagetosystemcomponents through incorrect mounting or adjustment. Also the pro-tectivecharacteristicsoftheinstrumentcanbeinfluenced.

2.4 General safety instructionsThis is a state-of-the-art instrument complying with all prevailing regulations and guidelines. The instrument must only be operated in a technicallyflawlessandreliablecondition.Theoperatorisresponsiblefor the trouble-free operation of the instrument.During the entire duration of use, the user is obliged to determine the compliance of the necessary occupational safety measures with the current valid rules and regulations and also take note of new regula-tions.The safety instructions in this operating instructions manual, the na-tional installation standards as well as the valid safety regulations and accident prevention rules must be observed by the user.For safety and warranty reasons, any invasive work on the device beyond that described in the operating instructions manual may be carried out only by personnel authorised by the manufacturer. Arbi-traryconversionsormodificationsareexplicitlyforbidden.The safety approval markings and safety tips on the device must also be observed.Depending on the instrument version, the emitting frequencies are in the C, K or W band range. The low emitting frequencies are far below the internationally approved limit values. When used correctly, the device poses no danger to health.

Page 6: VEGAPULS 61

6

2 For your safety

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

2.5 CE conformityThedevicefulfillsthelegalrequirementsoftheapplicableECguide-lines.ByaffixingtheCEmarking,weconfirmsuccessfultestingoftheproduct.YoucanfindtheCECertificateofConformityinthedownloadsectionof our homepage.

Electromagnetic compatibilityInstruments in four-wire or Ex-d-ia version are designed for use in an industrial environment. Nevertheless, electromagnetic interference from electrical conductors and radiated emissions must be taken into account, as is usual with class A instruments according to EN 61326-1.Iftheinstrumentisusedinadifferentenvironment,theelectromag-netic compatibility to other instruments must be ensured by suitable measures.

2.6 NAMUR recommendationsNAMUR is the automation technology user association in the process industry in Germany. The published NAMUR recommendations are acceptedasthestandardinfieldinstrumentation.ThedevicefulfillstherequirementsofthefollowingNAMURrecom-mendations:

• NE 21 – Electromagnetic compatibility of equipment• NE 43 – Signal level for malfunction information from measuring

transducers• NE53–Compatibilityoffielddevicesanddisplay/adjustment

components• NE107–Self-monitoringanddiagnosisoffielddevicesFor further information see www.namur.de.

2.7 Radio license for EuropeThe instrument is approved according to EN 302372-1/2 (2006-04) for use in closed vessels.

2.8 Radio license for USA/CanadaThe instrument is in conformity with part 15 of the FCC regulations. Take note of the following two regulations:

• This device may not cause interference, and• This device must accept any interference, including interference

that may cause undesired operation of the device

Modificationsnotexpresslyapprovedbythemanufacturerwillleadtoexpiry of the operating licence according to FCC/IC.The instrument is in conformity with RSS-210 of the IC regulations.The instrument may only be used in closed vessels made of metal, concrete,orfibre-reinforcedplastic.

Page 7: VEGAPULS 61

7

2 For your safety

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

2.9 Environmental instructionsProtection of the environment is one of our most important duties. That is why we have introduced an environment management system with the goal of continuously improving company environmental pro-tection.Theenvironmentmanagementsystemiscertifiedaccordingto DIN EN ISO 14001.Pleasehelpusfulfillthisobligationbyobservingtheenvironmentalinstructions in this manual:

• Chapter "Packaging, transport and storage"• Chapter "Disposal"

Page 8: VEGAPULS 61

8

3 Product description

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

3 Product description

3.1 ConfigurationThetypelabelcontainsthemostimportantdataforidentificationanduse of the instrument:

2

1

14

15

16

17

13

12

11

5

3

6

4

78910

Fig. 1: Layout of the type label (example)1 Instrument type2 Product code3 Approvals4 Power supply and signal output, electronics5 Protection rating6 Measuring range7 Process and ambient temperature, process pressure8 Material, wetted parts9 Hardware and software version10 Order number11 Serial number of the instrument12 Data-Matrix-Code for smartphone app13 Symbol of the device protection class14 ID numbers, instrument documentation15 Reminder to observe the instrument documentation16 NotifiedauthorityforCEmarking17 Approval directive

The type label contains the serial number of the instrument. With it youcanfindthefollowinginstrumentdataonourhomepage:

• Product code (HTML)• Delivery date (HTML)• Order-specificinstrumentfeatures(HTML)• Operating instructions and quick setup guide at the time of ship-

ment (PDF)• Order-specificsensordataforanelectronicsexchange(XML)• Testcertificate(PDF)-optionalGo to www.vega.com, "VEGATools" and "Instrument search". Enter the serial number.Alternatively, you can access the data via your smartphone:

Type label

Serial number - Instru-ment search

Page 9: VEGAPULS 61

9

3 Product description

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

• Download the smartphone app "VEGATools" from the "Apple App Store" or the "GooglePlayStore"

• Scan the Data Matrix code on the type label of the instrument or• Enter the serial number manually in the app

This operating instructions manual applies to the following instrument versions:

• Hardware version from 2.1.0• Software version from 4.5.1

Theinstrumentisavailableintwodifferentelectronicsversions.Eachversioncanbeidentifiedviatheproductcodeonthetypelabelaswell as on the electronics.

• Standard electronics type PS60HK.-• Electronics with increased sensitivity type PS60HS.-

The scope of delivery encompasses:

• Radar sensor• Optional mounting accessory• Documentation

– Quick setup guide VEGAPULS 61 – Instructions for optional instrument features – Ex-specific"Safety instructions" (with Ex versions) – ifnecessary,furthercertificates

• DVD "Software", included therein – PACTware/DTM Collection – Driver software

Information:In the operating instructions manual, the optional instrument features are described. The respective scope of delivery results from the order specification.

3.2 Principle of operationThe VEGAPULS 61 is a radar sensor for continuous level measure-ment of liquids under simple process conditions.Dependentontheapplicationrange,differentversionsareused:

• Level measurement of aggressive liquids in small vessels: encap-sulated antenna system

• Flowmeasurementinopenflumesorgaugemeasurementofbod-ies of water: Plastic horn antenna

• Productswithanεrvalue≥1.8:Standard electronics• Productswithanεrvalue≥1.5,<1.8;applicationswithverypoor

reflectiveproperties:Electronics with increased sensitivity

The actual values that can be reached depend on the measurement conditions, the antenna system or the standpipe or bypass.

Scope of this operating instructions manual

Versions

Scope of delivery

Application area

Page 10: VEGAPULS 61

10

3 Product description

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

The antenna of the radar sensor emits short radar pulses with a durationofapprox.1ns.Thesepulsesarereflectedbytheproductand received by the antenna as echoes. The transit time of the radar pulses from emission to reception is proportional to the distance and hence to the level. The determined level is converted into an appropri-ate output signal and outputted as measured value.

3.3 Packaging, transport and storageYour instrument was protected by packaging during transport. Its capacity to handle normal loads during transport is assured by a test based on ISO 4180.The packaging of standard instruments consists of environment-friendly, recyclable cardboard. For special versions, PE foam or PE foil is also used. Dispose of the packaging material via specialised recycling companies.

Transport must be carried out in due consideration of the notes on the transport packaging. Nonobservance of these instructions can cause damage to the device.

The delivery must be checked for completeness and possible transit damage immediately at receipt. Ascertained transit damage or con-cealed defects must be appropriately dealt with.

Up to the time of installation, the packages must be left closed and stored according to the orientation and storage markings on the outside.Unless otherwise indicated, the packages must be stored only under the following conditions:

• Not in the open• Dry and dust free• Not exposed to corrosive media• Protected against solar radiation• Avoiding mechanical shock and vibration

• Storage and transport temperature see chapter "Supplement - Technicaldata-Ambientconditions"

• Relative humidity 20 … 85 %

3.4 Accessories and replacement partsThe display and adjustment module PLICSCOM is used for measured value indication, adjustment and diagnosis. It can be inserted into the sensor or the external display and adjustment unit and removed at any time.Youcanfindfurtherinformationintheoperatinginstructions"Display and adjustment module PLICSCOM" (Document-ID 27835).

The interface adapter VEGACONNECT enables the connection of communication-capable instruments to the USB interface of a PC. For

Functional principle

Packaging

Transport

Transport inspection

Storage

Storage and transport temperature

PLICSCOM

VEGACONNECT

Page 11: VEGAPULS 61

11

3 Product description

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

parameter adjustment of these instruments, the adjustment software PACTware with VEGA-DTM is required.Youcanfindfurtherinformationintheoperatinginstructions"Interface adapterVEGACONNECT" (Document-ID 32628).

The VEGADIS 81 is an external display and adjustment unit for VEGA plics® sensors.For sensors with double chamber housing the interface adapter "DISADAPT" is also required for VEGADIS 81.Youcanfindfurtherinformationintheoperatinginstructions"VE-GADIS81" (Document-ID 43814).

The adapter "DISADAPT" is an accessory part for sensors with dou-ble chamber housings. It enables the connection of VEGADIS 81 to the sensor housing via an M12 x 1 plug.Youcanfindfurtherinformationinthesupplementaryinstructions"AdapterDISADAPT" (Document-ID 45250).

VEGADIS 82 is suitable for measured value indication and adjustment of sensors with HART protocol. It is looped into the 4 … 20 mA/HART signal cable.Youcanfindfurtherinformationintheoperatinginstructions"VE-GADIS82" (Document-ID 45300).

PLICSMOBILE T61 is an external GSM/GPRS radio unit for transmis-sion of measured values and for remote parameter adjustment of plics® sensors. Adjustment is carried out via PACTware/DTM and the integrated USB connection.Youcanfindfurtherinformationinthesupplementaryinstructions"PLICSMOBILET61" (Document-ID 37700).

PLICSMOBILE is an internal GSM/GPRS radio unit for transmission of measured values and for remote parameter adjustment of plics® sensors. Adjustment is carried out via PACTware/DTM and the inte-grated USB connection.Youcanfindfurtherinformationinthesupplementaryinstructions"PLICSMOBILEGSM/GPRSradiomodule" (Document-ID 36849).

The protective cover protects the sensor housing against soiling and intense heat from solar radiation.Youwillfindadditionalinformationinthesupplementaryinstructionsmanual "Protective cover" (Document-ID 34296).

Electronics module "VEGAPULS series 60" is a replacement part for radarsensorsofVEGAPULSseries60.Adifferentversionisavailablefor each type of signal output.Youcanfindfurtherinformationintheoperatinginstructions"Elec-tronicsmoduleVEGAPULSseries60" (Document-ID 36801).

VEGADIS 81

DISADAPT

VEGADIS 82

PLICSMOBILE T61

PLICSMOBILE

Protective cap

Electronics module

Page 12: VEGAPULS 61

12

3 Product description

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

The supplementary electronics is a replacement part for sensors with double chamber housing and 4 … 20 mA/HART - two-wire.Youcanfindfurtherinformationintheoperatinginstructions"Supple-mentaryelectronicsfor4…20mA/HART-two-wire" (Document-ID 42764).

Supplementary electron-ics for double chamber housing

Page 13: VEGAPULS 61

13

4 Mounting

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

4 Mounting

4.1 General instructionsOninstrumentswithprocessfittingthread,thehexagonmustbetight-enedwithasuitablewrench.Fortheproperwrenchsizeseechapter"Dimensions".

Warning:The housing must not be used to screw the instrument in! Applying tightening force can damage internal parts of the housing.

Protect your instrument against moisture ingress through the following measures:

• Use the recommended cable (see chapter "Connecting to power supply")

• Tighten the cable gland• Whenmountinghorizontally,turnthehousingsothatthecable

gland points downward• Loop the connection cable downward in front of the cable gland

This applies particularly to:

• Outdoor mounting• Installations in areas where high humidity is expected (e.g. through

cleaning processes)• Installations on cooled or heated vessels

Make sure that all parts of the instrument exposed to the process are suitable for the existing process conditions.These are mainly:

• Active measuring component• Processfitting• Process seal

Process conditions are particularly:

• Process pressure• Process temperature• Chemical properties of the medium• AbrasionandmechanicalinfluencesYoucanfinddetailedinformationontheprocessconditionsinchapter"Technicaldata" as well as on the type label.

In the case of instrument housings with self-sealing NPT threads, it is not possible to have the cable entries screwed in at the factory. The free openings for the cable glands are therefore covered with red dust protection caps as transport protection.Prior to setup you have to replace these protective caps with ap-proved cable glands or close the openings with suitable blind plugs.

Screwing in

Protection against mois-ture

Suitability for the process conditions

Cable entries - NPT thread

Page 14: VEGAPULS 61

14

4 Mounting

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

4.2 CollaroradapterflangeFormountingtheinstrumentonasocket,acombicompressionflangeforDN80(ASME3"orJIS80)isalsoavailableforretrofitting.Option-ally,theinstrumentcanbealsoequippedwithanadapterflangefromDN 100 (ASME 4" or JIS 100).With the housing versions plastic, aluminium single chamber and stainlesssteel,thecollarflangecanbeplaceddirectlyoverthehous-ing. With the aluminium double chamber housing, retroactive mount-inginthiswayisnotpossible-themountingtypemustbespecifiedwith the order.Youcanfinddrawingsofthesemountingoptionsinchapter"Dimen-sions".

Fig. 2: Flange mounting of the radar sensor

4.3 Mounting preparations, mounting strapThe mounting strap enables simple mounting on the vessel wall or silo top. It is suitable for wall, ceiling or boom mounting. Especially in openvesselsthisisaveryeasyandeffectivewaytoalignthesensorto the bulk solid surface.The strap is supplied unassembled and must be screwed to the sensor before setup with three hexagon socket screws M5 x 10 and spring washers. Max. torque, see chapter "Technicaldata". Required tools:Allenwrenchsize4.There are two ways to screw the strap onto the sensor. Depending on the selected version, the sensors can be swivelled in the strap as follows:

• Single chamber housing – Angleofinclination180°,infinitelyvariable – Angle of inclination in three steps 0°, 90° and 180°

Page 15: VEGAPULS 61

15

4 Mounting

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

• Double chamber housing – Angleofinclination90°,infinitelyvariable – Angle of inclination in two steps 0° and 90°

Fig. 3: Adjustment of the angle of inclination

Fig.4:Turningbyfasteninginthecentre

4.4 Mounting instructionsFor tight installation of the version with plastic horn antenna with com-pressionoradapterflange,thefollowingconditionsmustbefulfilled:1. Usesuitableflatseal,e.g.ofEPDMwithShorehardness25or502. Makesurethenumberofflangescrewscorrespondstothenum-

berofflangeholes3. Tighten all screws with the torque stated in the technical data

The emitted radar impulses of the radar sensor are electromagnetic waves. The polarisation is the direction of the electrical wave compo-nent.Byturningtheinstrumentintheconnectionflangeormountingboss,thepolarisationcanbeusedtoreducetheeffectsoffalseechoes.Thepositionofthepolarisationismarkedontheprocessfittingoftheinstrument.

Tight installation of the plastic horn antenna

Polarisation

Page 16: VEGAPULS 61

16

4 Mounting

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

1 2

Fig. 5: Position of the polarisation1 Marking with version with plastic horn antenna2 Marking with version with encapsulated antenna system

When mounting the sensor, keep a distance of at least 200 mm (7.874 in) to the vessel wall. If the sensor is installed in the center of dished or round vessel tops, multiple echoes can arise. These can, however, be suppressed by an appropriate adjustment (see chapter "Setup").If you cannot maintain this distance, you should carry out a false signal storage during setup. This applies particularly if buildup on the vessel wall is expected. In such cases, we recommend repeating the false signal storage at a later date with existing buildup.

> 200 mm(7.87")

Fig. 6: Mounting of the radar sensor on round vessel tops

In vessels with conical bottom it can be advantageous to mount the sensor in the center of the vessel, as measurement is then possible down to the lowest point of the vessel bottom.

Installation position

Page 17: VEGAPULS 61

17

4 Mounting

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

Fig. 7: Mounting of the radar sensor on vessels with conical bottom

Donotmounttheinstrumentsinorabovethefillingstream.Makesurethatyoudetecttheproductsurface,nottheinflowingproduct.

Fig.8:Mountingoftheradarsensorwithinflowingmedium

The socket piece should be dimensioned in such a way that the an-tenna end protrudes at least 10 mm (0.4 in) out of the socket.

Inflowingmedium

Socket with encapsulated antenna system

Page 18: VEGAPULS 61

18

4 Mounting

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

ca. 1

0 m

m

Fig. 9: Recommended socket mounting

Ifthereflectivepropertiesofthemediumaregood,youcanmountVEGAPULS 61 on sockets which are higher than the length of the antenna.Youwillfindrecommendedvaluesforsocketheightsinthefollowing illustration. The socket end should be smooth and burr-free, if possible also rounded. After installation you must carry out a false echo storage.

d

h

Fig. 10: Deviating socket dimensions

The below charts specify the max. socket length h depending on the diameter d.

Socket diameter d Socket length h

40 mm ≤200mm

50 mm ≤250mm

80 mm ≤300mm

100 mm ≤400mm

150 mm ≤500mm

Socket diameter d Socket length h

1½" ≤7.9in

2" ≤9.9in

3" ≤11.8in

Page 19: VEGAPULS 61

19

4 Mounting

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

Socket diameter d Socket length h

4" ≤15.8in

6" ≤19.7in

AcorrespondingcollarflangeforDN80(ASME3"orJIS80)aswellasasuitableadapterflangeareavailableformountingVEGAPULS61.With the housing versions plastic, aluminium single chamber and stainlesssteel,thecollarflangecanbeplaceddirectlyoverthehous-ing. With the aluminium double chamber housing, retroactive mount-inginthiswayisnotpossible-themountingtypemustbespecifiedwith the order.

Information:The mounting socket should be as short as possible and its end rounded. This reduces false echoes from the vessel mounting socket.

Fig. 11: Recommended socket mounting

Ifthemediumhasgoodreflectiveproperties,VEGAPULS61canalso be mounted on a longer socket piece. Recommended values forsocketheightsarespecifiedinthefollowingillustration.Youmustcarry out a false echo storage afterwards.

d

h

The below charts specify the max. socket length h depending on the diameter d.

Socket diameter d Socket length h

80 mm ≤300mm

Socket with plastic horn antenna

Page 20: VEGAPULS 61

20

4 Mounting

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

Socket diameter d Socket length h

100 mm ≤400mm

150 mm ≤500mm

Socket diameter d Socket length h

3" ≤11.8in

4" ≤15.8in

6" ≤19.7in

In liquids, direct the sensor as perpendicular as possible to the prod-uct surface to achieve optimum measurement results.

Fig. 13: Alignment in liquids

The mounting location of the radar sensor should be a place where no otherequipmentorfixturescrossthepathoftheradarsignals.Vessel installations, such as e.g. ladders, limit switches, heating spi-rals, struts, etc., can cause false echoes and impair the useful echo. Make sure when planning your measuring point that the radar sensor has a "clear view" to the measured product.In case of existing vessel installations, a false echo storage should be carried out during setup.If large vessel installations such as struts or supports cause false echoes, these can be attenuated through supplementary measures. Small,inclinedsheetmetalbafflesabovetheinstallationsscattertheradarsignalsandpreventdirectinterferingreflections.

Fig.14:Coverflat,large-areaprofileswithdeflectors

If there are agitators in the vessel, a false signal storage should be carried out with the agitators in motion. This ensures that the interfer-ingreflectionsfromtheagitatorsaresavedwiththebladesindifferentpositions.

Sensor orientation

Vessel installations

Agitators

Page 21: VEGAPULS 61

21

4 Mounting

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

Fig. 15: Agitators

Throughtheactionoffilling,stirringandotherprocessesinthevessel,compact foams that considerably damp the emitted signals may form on the product surface.If foams are causing measurement errors, the biggest possible radar antennas, the electronics with increased sensitivity or low frequency radar sensors (C band) should be used.As an alternative, sensors with guided microwave can be used. These areunaffectedbyfoamgenerationandarebestsuitedforsuchap-plications.

4.5 Measurement setup - PipesByusingasurgepipeinthevessel,theinfluenceofvesselinstalla-tions and turbulence can be excluded. Under these prerequisites, the measurementofproductswithlowdielectricvalues(εrvalue≤1.6)ispossible.Note the following illustrations and instructions for measurement in a surge pipe.

Information:Measurement in a surge pipe is not recommended for extremely adhesive products.

Foam generation

Measurement in a surge pipe

Page 22: VEGAPULS 61

22

4 Mounting

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

15°

45°

12

3

100%

4

5

7

6

0%

8

9

10

Fig.16:ConfigurationsurgepipeVEGAPULS611 Radar sensor2 Polarisation marking3 Threadorflangeontheinstrument4 Vent hole5 Holes6 WeldingconnectionthroughU-profile7 Ball valve with complete opening8 Surge pipe end9 Reflectorsheet10 Fastening of the surge pipe

Configurationsurgepipe

Page 23: VEGAPULS 61

23

4 Mounting

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

ø 88,9 mm(3.5")

d x

2

26 mm(1.02")

2 mm(0.08")

5 mm(0.20")

80 m

m(3

.15"

)

75°

4 m

m(0

.16"

)8

mm

(0.3

2")

ø 88,9 mm(3.5")

1

Fig.17:Weldingconnectionwithsurgepipeextensionfordifferentexamplediameters1 Position of the welded joint with longitudinally welded pipes

Instructions of orientation of the polarisation:• Note marking of the polarisation on the sensor• Withthreadedversions,themarkingisonthehexagon,withflange

versionsbetweentwoflangeholes• The marking must be in one plane with the holes in the surge pipe

Instructions for the measurement:• The 100 % point must be below the upper vent hole and the

antenna edge• The 0 % point is the end of the surge pipe• During parameter adjustment, select "Application standpipe" and

enter the tube diameter to compensate for errors due to running time shift

• A false signal suppression with the installed sensor is recom-mended but not mandatory

• The measurement through a ball valve with unrestricted channel is possible

Surge pipe extension

Instructions and require-ments, surge pipe

Page 24: VEGAPULS 61

24

4 Mounting

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

Constructive requirements:• Material metal, smooth inner surface• Preferably pultruded or straight beaded stainless steel tube• Welded joint should be straight and lie in one axis with the holes• Flanges are welded to the tube according to the orientation of the

polarisation• Whenusingaballvalves,alignthetransitionsontheinsideandfix

accurately• Gapsizewithjunctions≤0.1mm• Surge pipes must extend all the way down to the requested min.

level, as measurement is only possible within the tube• Diameterofholes≤5mm,anynumberOK,ononesideorcom-

pletely through• The antenna diameter of the sensor should correspond to the

inner diameter of the tube• Diameter should be constant over the complete length

Instructions for surge pipe extension:• The ends of the extension tubes must be bevelled and exactly

aligned• WeldedconnectionviaexternalUprofilesaccordingtoillustration

above.LengthoftheUprofilesshouldbeatleastdoublethetubediameter

• Do not weld through the pipe wall. The surge pipe must remain smooth inside. Roughness and beads on the inside caused by unintentional penetration should be removed since they cause strong false echoes and encourage buildup

• Anextensionviaweldingneckflangesorpipecollarsisnotrecom-mended.

An alternative to measurement in a surge pipe is measurement in a bypass tube outside of the vessel.

Measurement in the bypass tube

Page 25: VEGAPULS 61

25

4 Mounting

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

0 %

100 %

12

5

4

3

6

Fig.18:Configurationbypass1 Radar sensor2 Polarisation marking3 Instrumentflange4 Distance sensor reference plane to upper tube connection5 Distance of the tube connections6 Ball valve with complete opening

Instructions of orientation of the polarisation:• Note marking of the polarisation on the sensor• Withthreadedversions,themarkingisonthehexagon,withflange

versionsbetweentwoflangeholes• The marking must be in one plane with the tube connections to the

vessel

Instructions for the measurement:• The 100 % point may not be above the upper tube connection to

the vessel• The 0 % point may not be below the lower tube connection to the

vessel• Min. distance, sensor reference plane to upper edge of upper tube

connection > 300 mm• During parameter adjustment, select "Application standpipe" and

enter the tube diameter to compensate for errors due to running time shift

• A false signal suppression with the installed sensor is recom-mended but not mandatory

• The measurement through a ball valve with unrestricted channel is possible

Configurationbypass

Instructions and require-ments, bypass

Page 26: VEGAPULS 61

26

4 Mounting

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

Constructional requirements on the bypass pipe:• Material metal, smooth inner surface• In case of an extremely rough tube inner surface, use an inserted

tube (tube in tube) or a radar sensor with tube antenna• Flanges are welded to the tube according to the orientation of the

polarisation• Gapsizewithjunctions≤0.1mm,forexample,whenusingaball

valveorintermediateflangeswithsinglepipesections• The antenna diameter of the sensor should correspond to the

inner diameter of the tube• Diameter should be constant over the complete length

4.6 Measurement setup - FlowTheshortexamplesgiveyouintroductoryinformationontheflowmeasurement.Detailedplanninginformationisavailablefromflumemanufacturers and in special literature.

3 ... 4 hmax

≥ 50 mm

90°

2 3

1h m

axd m

in≥

2 m

m x

hm

ax90°

42 3

Fig.19:Flowmeasurementwithrectangularflume:dmin. = min. distance of the sensor(seechapter"Technicaldata");hmax.=max.fillingoftherectangularflume1 Overfloworifice(sideview)2 Headwater3 Tailwater4 Overfallorifice(viewfrombottomwater)

In general, the following points must be observed:

• Install the sensor on the headwater side• Installationinthecentreoftheflumeandverticaltotheliquid

surface• Distancetotheoverfallorifice• Distanceoforificeopeningaboveground• Min.distanceoftheorificeopeningtobottomwater• Min. distance of the sensor to max. storage level

Flow measurement with rectangularflume

Page 27: VEGAPULS 61

27

4 Mounting

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

2

3 ... 4 x hmax

90°

hmax

d

B1

Fig.20:FlowmeasurementwithKhafagi-Venturiflume:d=Min.distancetosen-sor;hmax.=max.fillingoftheflume;B=tightestconstrictionintheflume1 Position sensor2 Venturiflume

In general, the following points must be observed:

• Installation of the sensor at the inlet side• Installationinthecentreoftheflumeandverticaltotheliquid

surface• DistancetotheVenturiflume• Min. distance of the sensor to max. storage level

Flow measurement with KhafagiVenturiflume

Page 28: VEGAPULS 61

28

5 Connecting to power supply

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

5 Connecting to power supply

5.1 Preparing the connectionAlways keep in mind the following safety instructions:

Warning:Connect only in the complete absence of line voltage.

• The electrical connection must only be carried out by trained personnel authorised by the plant operator.

• If overvoltage surges are expected, overvoltage arresters should be installed.

Power supply and current signal are carried on the same two-wire cable.Theoperatingvoltagecandifferdependingontheinstrumentversion.Thedataforpowersupplyarespecifiedinchapter"Technicaldata".Provide a reliable separation between the supply circuit and the mains circuits according to DIN EN 61140 VDE 0140-1.Keepinmindthefollowingadditionalfactorsthatinfluencetheoperat-ing voltage:

• Lower output voltage of the power supply unit under nominal load (e.g. with a sensor current of 20.5 mA or 22 mA in case of fault)

• Influenceofadditionalinstrumentsinthecircuit(seeloadvaluesinchapter "Technicaldata")

The instrument is connected with standard two-wire cable without screen. If electromagnetic interference is expected which is above the test values of EN 61326-1 for industrial areas, screened cable should be used.Use cable with round cross section for instruments with housing and cablegland.Toensurethesealeffectofthecablegland(IPprotectionrating),findoutwhichcableouterdiameterthecableglandissuitablefor.Useacableglandfittingthecablediameter.We generally recommend the use of screened cable for HART multi-drop mode.

With plastic housing, the NPT cable gland or the Conduit steel tube must be screwed without grease into the threaded insert.Max. torque for all housings see chapter "Technicaldata".

If screened cable is required, we recommend connecting the cable screen on both ends to ground potential. In the sensor, the screen must be connected directly to the internal ground terminal. The ground terminal on the outside of the housing must be connected to the ground potential (low impedance).In Ex systems, the grounding is carried out according to the installa-tion regulations.

Safety instructions

Voltage supply

Connection cable

Cable gland ½ NPT

Cable screening and grounding

Page 29: VEGAPULS 61

29

5 Connecting to power supply

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

5.2 ConnectingThe voltage supply and signal output are connected via the spring-loaded terminals in the housing.Connection to the display and adjustment module or to the interface adapter is carried out via contact pins in the housing.

Information:The terminal block is pluggable and can be removed from the electronics. To do this, lift the terminal block with a small screwdriver and pull it out. When reinserting the terminal block, you should hear it snap in.

Proceed as follows:1. Unscrew the housing lid2. If a display and adjustment module is installed, remove it by turn-

ing it slightly to the left.3. Loosen compression nut of the cable entry gland4. Remove approx. 10 cm (4 in) of the cable mantle, strip approx.

1 cm (0.4 in) of insulation from the ends of the individual wires5. Insert the cable into the sensor through the cable entry

Fig. 21: Connection steps 5 and 6 - Single chamber housing

Connection technology

Connection procedure

Page 30: VEGAPULS 61

30

5 Connecting to power supply

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

Fig. 22: Connection steps 5 and 6 - Double chamber housing

6. Insert the wire ends into the terminals according to the wiring plan

Information:Solidcoresaswellasflexiblecoreswithwireendsleevesareinsert-eddirectlyintotheterminalopenings.Incaseofflexiblecoreswithoutend sleeves, press the terminal from above with a small screwdriver, the terminal opening is then free. When the screwdriver is released, the terminal closes again.Youcanfindfurtherinformationonthemax.wirecross-sectionunder"Technicaldata/Electromechanicaldata"

7. Check the hold of the wires in the terminals by lightly pulling on them

8. Connect the screen to the internal ground terminal, connect the outer ground terminal to potential equalisation

9. Tighten the compression nut of the cable entry gland. The seal ring must completely encircle the cable

10. Reinsert the display and adjustment module, if one was installed11. Screw the housing lid back onTheelectricalconnectionisfinished.

5.3 Wiring plan, single chamber housingThe following illustration applies to the non-Ex as well as to the Ex-ia version.

Page 31: VEGAPULS 61

31

5 Connecting to power supply

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

51 2+( ) (-) 6 7 8

4...20mA

2

3

41

Fig.23:Electronicsandterminalcompartment,singlechamberhousing1 Voltage supply, signal output2 For display and adjustment module or interface adapter3 For external display and adjustment unit4 Groundterminalforconnectionofthecablescreen

5.4 Wiring plan, double chamber housingThe following illustrations apply to the non-Ex as well as to the Ex-ia version.

5 6 7 8

4...20mA

1 2+( ) (-)

2

1 1

Fig.24:Electronicscompartment,doublechamberhousing1 Internal connection to the terminal compartment2 For display and adjustment module or interface adapter

Electronics and terminal compartment

Electronics compartment

Page 32: VEGAPULS 61

32

5 Connecting to power supply

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

51 2+( ) (-) 6 7 8

4...20mA Display

2

3

41

Fig.25:Terminalcompartment,doublechamberhousing1 Voltage supply, signal output2 For display and adjustment module or interface adapter3 For external display and adjustment unit4 Groundterminalforconnectionofthecablescreen

Information:Parallel use of an external display and adjustment unit and a display and adjustment module in the terminal compartment is not supported.

1

USB

Status

TestSIM-Card

1 2+( ) (-)

Fig.26:Terminalcompartment,radiomodulePLICSMOBILE1 Voltage supply

Youcanfinddetailedinformationonconnectioninthesupplementaryinstructions "PLICSMOBILEGSM/GPRSradiomodule".

Terminal compartment

Terminal compartment - Radio module PLICS-MOBILE

Page 33: VEGAPULS 61

33

5 Connecting to power supply

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

5.5 Wiring plan, double chamber housing Ex d ia

31

2

5 6 7 81 2( ) (-)+

4...20mA

Fig.27:Electronicscompartment,doublechamberhousingExdia1 Internal connection to the terminal compartment2 For display and adjustment module or interface adapter3 Internal connection to the plug connector for external display and adjust-

ment unit (optional)

Note:HART multidrop mode is not possible when using an Ex-d-ia instru-ment.

4...20mA

1 2+( ) (-) 2

1

Fig.28:Terminalcompartment,doublechamberhousingExdia1 Voltage supply, signal output2 Groundterminalforconnectionofthecablescreen

34

1 2

Fig.29:Topviewoftheplugconnector1 Pin 12 Pin 23 Pin 34 Pin 4

Electronics compartment

Terminal compartment

Plug M12 x 1 for external display and adjustment unit

Page 34: VEGAPULS 61

34

5 Connecting to power supply

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

Contact pin Colour connection ca-ble in the sensor

Terminal, electronics module

Pin 1 Brown 5

Pin 2 White 6

Pin 3 Blue 7

Pin 4 Black 8

5.6 Double chamber housing with DISADAPT

3

1

2

Fig.30:ViewtotheelectronicscompartmentwithDISADAPTforconnectionofthe external display and adjustment unit1 DISADAPT2 Internal plug connection3 Plug connector M12 x 1

34

1 2

Fig. 31: View to the plug connector M12 x 11 Pin 12 Pin 23 Pin 34 Pin 4

Contact pin Colour connection ca-ble in the sensor

Terminal, electronics module

Pin 1 Brown 5

Pin 2 White 6

Pin 3 Blue 7

Pin 4 Black 8

Electronics compartment

Assignment of the plug connector

Page 35: VEGAPULS 61

35

5 Connecting to power supply

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

5.7 Wiring plan - version IP 66/IP 68, 1 bar

1

2

Fig. 32: Wire assignment in permanently connected connection cable1 brown (+) and blue (-) to power supply or to the processing system2 Shielding

5.8 Switch-on phaseAfter connecting the instrument to power supply or after a voltage recurrence, the instrument carries out a self-check for approx. 30 s:

• Internal check of the electronics• Indication of the instrument type, hardware and software version,

measurement loop name on the display or PC• Indication of the status message "F 105 Determine measured

value" on the display or PC• The output signal jumps to the set fault current

As soon as a plausible measured value is found, the corresponding current is outputted to the signal cable. The value corresponds to the actual level as well as the settings already carried out, e.g. factory setting.

Wire assignment, con-nection cable

Page 36: VEGAPULS 61

36

6 Set up with the display and adjustment module

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

6 Set up with the display and adjustment module

6.1 Insert display and adjustment moduleThe display and adjustment module can be inserted into the sensor andremovedagainatanytime.Youcanchooseanyoneoffourdiffer-ent positions - each displaced by 90°. It is not necessary to interrupt the power supply.Proceed as follows:1. Unscrew the housing lid2. Place the display and adjustment module on the electronics in the

desired position and turn it to the right until it snaps in.3. Screw housing lid with inspection window tightly back onDisassembly is carried out in reverse order.The display and adjustment module is powered by the sensor, an ad-ditional connection is not necessary.

Fig. 33: Installing the display and adjustment module in the electronics compart-ment of the single chamber housing

Page 37: VEGAPULS 61

37

6 Set up with the display and adjustment module

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

1 2

Fig. 34: Installing the display and adjustment module in the double chamber housing1 In the electronics compartment2 In the terminal compartment

Note:Ifyouintendtoretrofittheinstrumentwithadisplayandadjustmentmodule for continuous measured value indication, a higher lid with an inspection glass is required.

6.2 Adjustment system

1

2

Fig. 35: Display and adjustment elements1 LC display2 Adjustment keys

• [OK] key:Key functions

Page 38: VEGAPULS 61

38

6 Set up with the display and adjustment module

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

– Move to the menu overview – Confirmselectedmenu – Edit parameter – Save value

• [->] key: – Presentation, change measured value – Select list entry – Select menu items in the quick setup – Select editing position

• [+] key: – Change value of the parameter

• [ESC] key: – Interrupt input – Jump to next higher menu

You adjust the instrument via the four keys of the display and adjust-ment module. The individual menu items are shown on the LC display. Youcanfindthefunctionsoftheindividualkeysinthepreviousillustration.

By pushing the [+] and [->] keys once, the edited value or the cursor changes by one position. By pushing the keys longer than 1 s the change will be continuously.By pushing the [OK] and [ESC] keys simultaneously for more than 5 s, a return to the basic menu is caused. The menu language is then switched over to "English".Approx. 60 minutes after the last pressing of a key, an automatic reset tomeasuredvalueindicationistriggered.Anyvaluesnotconfirmedwith [OK] will not be saved.

6.3 Measured value indication - Selection national language

With the [->]keyyoumovebetweenthreedifferentindicationmodes.Inthefirstview,theselectedmeasuredvalueisdisplayedinlargedigits.In the second view, the selected measured value and a correspond-ing bar graph presentation are displayed.In the third view, the selected measured value as well as a second se-lectable value, e.g. the temperature of the electronics, are displayed.

During the initial setup of an instrument shipped Ex works,use the "OK" key to get to the menu "National language".

Adjustment system

Time functions

Measured value indica-tion

Page 39: VEGAPULS 61

39

6 Set up with the display and adjustment module

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

This menu item is used to select the national language for further pa-rameter adjustment. You can change the selection via the menu item "Setup - Display, Menu language".

With the "OK" key you move to the main menu.

6.4 Parameter adjustmentThe instrument is adapted to the application conditions via the pa-rameter adjustment. The parameter adjustment is carried out with an adjustment menu.

Themainmenuisdividedintofivesectionswiththefollowingfunc-tions:

Setup: Settings, e.g., for measurement loop name, medium, applica-tion, vessel, adjustment, signal outputDisplay: Settings, e.g., for language, measured value display, lightingDiagnosis: Information, e.g. on instrument status, pointer, measure-ment certainty, simulation, echo curveFurther settings: Instrument unit, false signal suppression, linearisa-tion curve, reset, date/time, reset, copy functionInfo: Instrument name, hardware and software version, date of manu-facture, instrument features

Information:Inthisoperatinginstructionsmanual,theinstrument-specificparam-eters in the menu sections "Setup", "Diagnosis" and "Additional set-tings" are described. The general parameters in these menu section are described in the operating instructions manual "Indicating and adjustment module".Youcanfindintheoperatinginstructionsmanual"Display and adjust-ment module" also the description of the menu sections "Display" and "Info".

In the main menu point "Setup", the individual submenu points should be selected one after the other and provided with the correct parameters to ensure optimum adjustment of the measurement. The procedure is described in the following.

In the menu item "SensorTAG" you edit a twelve digit measurement loop designation label.You can enter an unambiguous designation for the sensor, e.g. the measurement loop name or the tank or product designation. In digital systems and in the documentation of larger plants, a singular desig-

Selection of national language

Main menu

Setup - Measurement loop name

Page 40: VEGAPULS 61

40

6 Set up with the display and adjustment module

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

nationmustbeenteredforexactidentificationofindividualmeasuringpoints.The available digits comprise:

• Letters from A … Z• Numbers from 0 … 9• Special characters +, -, /, -

Eachmediumhasdifferentreflectionproperties.Withliquids,furtherinterferingfactorsarefluctuationproductsurfaceandfoamgenera-tion. With bulk solids, these are dust generation, material cone and additional echoes from the vessel wall.Toadaptthesensortothesedifferentmeasuringconditions,theselection "Liquid" or "Bulk solid" should be made in this menu item.

Through this selection, the sensor is adapted perfectly to the product andmeasurementreliability,particularlyinproductswithpoorreflec-tive properties, is considerably increased.Enter the requested parameters via the appropriate keys, save your settings with [OK] and jump to the next menu item with the [ESC] and the [->] key.

In addition to the medium, also the application, i.e. the measuring site, caninfluencethemeasurement.With this menu item, the sensor can be adapted to the applications. The adjustment possibilities depend on the selection "Liquid" or "Bulk solid" under "Medium".

The following options are available when "Liquid" is selected:

Setup - Medium

Setup - Application

Page 41: VEGAPULS 61

41

6 Set up with the display and adjustment module

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

The selection "Standpipe" opens a new window in which the inner diameter of the applied standpipe is entered.

The following features form the basis of the applications:

Storage tank:• Setup: large-volumed, upright cylindrical, spherical• Productspeed:slowfillingandemptying• Process/measurement conditions:

– Condensation – Smooth product surface – High requirements to the measurement accuracy

• Properties, sensor: – Slight sensitivity against sporadic false echoes – Stable and reliable measured values through averaging – High accuracy – Short reaction time of the sensor not required

Storage tank with product circulation:• Setup: large-volumed, upright cylindrical, spherical• Productspeed:slowfillingandemptying• Installations: small laterally mounted or large top mounted stirrer• Process/measurement conditions:

– Relatively smooth product surface – High requirements to the measurement accuracy – Condensation – Slight foam generation – Overfillingpossible

• Properties, sensor: – Slight sensitivity against sporadic false echoes – Stable and reliable measured values through averaging – High accuracy because not adjusted for max. speed – False signal suppression recommended

Storage tank on ships (Cargo Tank):• Productspeed:slowfillingandemptying• Vessel:

– Installations in the bottom section (bracers, heating spirals) – High sockets 200 … 500 mm, also with large diameters

• Process/measurement conditions: – Condensation, buildup by movement – Max. requirement on measurement accuracy from 95 %

• Properties, sensor: – Slight sensitivity against sporadic false echoes – Stable and reliable measured values through averaging

Page 42: VEGAPULS 61

42

6 Set up with the display and adjustment module

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

– High accuracy – False signal suppression required

Stirrer vessel (reactor):• Setup:allvesselsizespossible• Product speed:

– Fasttoslowfillingpossible – Vesselisveryoftenfilledandemptied

• Vessel: – Socket available – Large agitator blades of metal – Vortex breakers, heating spirals

• Process/measurement conditions: – Condensation, buildup by movement – Strong spout generation – Very agitated surface, foam generation

• Properties, sensor: – Higher measurement speed through lower averaging – Sporadic false echoes are suppressed

Dosing vessel:• Setup:allvesselsizespossible• Product speed:

– Fastfillingandemptying – Vesselisveryoftenfilledandemptied

• Vessel: narrow installation situation• Process/measurement conditions:

– Condensation, buildup on the antenna – Foam generation

• Properties, sensor: – Measurementspeedoptimizedbyvirtuallynoaveraging – Sporadic false echoes are suppressed – False signal suppression recommended

Standpipe:• Productspeed:veryfastfillingandemptying• Vessel:

– Vent hole – Joinslikeflanges,weldjoints – Shifting of the running time in the tube

• Process/measurement conditions: – Condensation – Buildup

• Properties, sensor: – Measurementspeedoptimizedthroughlittleaveraging – Entering the tube inside diameter takes the running time shift

into consideration – Echo detection sensitivity reduced

Bypass:• Product speed:

– Fastuptoslowfillingwithshortuptolongbypasstubepossible – Often the level is hold via a control facility

Page 43: VEGAPULS 61

43

6 Set up with the display and adjustment module

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

• Vessel: – Lateral outlets and inlets – Joinslikeflanges,weldjoints – Shifting of the running time in the tube

• Process/measurement conditions: – Condensation – Buildup – Separation of oil and water possible – Overfillingintotheantennapossible

• Properties, sensor: – Measurementspeedoptimizedthroughlittleaveraging – Entering the tube inside diameter takes the running time shift

into consideration – Echo detection sensitivity reduced – False signal suppression recommended

Plastic tank:• Vessel:

– Measurementfixmountedorintegrated – Measurement depending on the application through the vessel

top – With empty vessel, the measurement can be carried out

through the bottom• Process/measurement conditions:

– Condensation on the plastic ceiling – In outside facilities water and snow on the vessel top possible

• Properties, sensor: – False signals outside the vessel are not taken into consideration – False signal suppression recommended

Transportable plastic tank:• Vessel:

– Materialandthicknessdifferent – Measurement through the vessel top

• Process/measurement conditions: – Measured value jump with vessel change

• Properties, sensor: – Quickadaptationtochangingreflectionconditionsthrough

vessel change – False signal suppression required

Open water (gauge measurement):• Gauge rate of change: slow gauge change• Process/measurement conditions:

– Distance sensor to water surface to big – Extreme damping of output signal due to wave generation – Ice and condensation on the antenna possible – Spiders and insect nestle in the antennas – Floating material and animals sporadically on the water surface

• Properties, sensor: – Stable and reliable measured values through high averaging – Insensitive in the close range

Page 44: VEGAPULS 61

44

6 Set up with the display and adjustment module

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

Openflume(flowmeasurement):• Gauge rate of change: slow gauge change• Process/measurement conditions:

– Ice and condensation on the antenna possible – Spiders and insect nestle in the antennas – Smooth water surface – Exact measurement result required – Distance to the water surface normally relatively high

• Properties, sensor: – Stable and reliable measured values through high averaging – Insensitive in the close range

Rain water overfall (weir):• Gauge rate of change: slow gauge change• Process/measurement conditions:

– Ice and condensation on the antenna possible – Spiders and insect nestle in the antennas – Turbulent water surface – Sensorfloodingpossible

• Properties, sensor: – Stable and reliable measured values through high averaging – Insensitive in the close range

Demonstration:• Adjustment for all applications which are not typically level meas-

urement – Instrument demonstration – Object recognition/monitoring (additional settings required)

• Properties, sensor: – Sensor accepts all measured value changes within the measur-

ing range immediately – High sensitivity against interferences, because virtually no

averaging

Caution:Ifliquidswithdifferentdielectricconstantsseparateinthevessel,forexample through condensation, the radar sensor can detect under certain circumstances only the medium with the higher dielectric constant. Keep in mind that layer interfaces can cause faulty meas-urements.If you want to measure the total height of both liquids reliably, please contact our service department or use an instrument specially de-signed for interface measurement.

The following options are available when "Bulk solid" is selected:

The following features form the basis of the applications:

Page 45: VEGAPULS 61

45

6 Set up with the display and adjustment module

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

Silo (slender and high):• Vessel of metal: weld joints• Process/measurement conditions:

– Filling aperture too close to the sensor – System noise in completely empty silo increased

• Properties, sensor: – Stable measured values through higher averaging – False signal suppression during setup recommended, required

for automatic false signal suppression – Automaticfalsesignalsuppressionwithpartlyfilledvessel

Bunker (large-volume):• Vessel of concrete or metal:

– Structured vessel walls – Installations present

• Process/measurement conditions: – Large distance to the medium – Large angles of repose

• Properties, sensor: – Mean averaging – High measured value jumps are accepted

Bunkerwithfastfilling:• Vessel of concrete or metal, also multiple chamber silo:

– Structured vessel walls – Installations present

• Process/measurement conditions: – Measured value jumps, e.g. through truck loading – Large distance to the medium – Large angles of repose

• Properties, sensor: – Lower averaging – Very high measured value jumps are accepted

Heap:• Sensor mounting on movable conveyor belts• Detectionoftheheapprofile• Heightdetectionduringfilling• Process/measurement conditions:

– Measuredvaluejumps,e.g.bytheprofileoftheheaportrav-erses

– Large angles of repose – Measurementnearthefillingstream

• Properties, sensor: – Mean averaging – High measured value jumps are accepted

Crusher:• Vessel: installations, wear and protective facilities available• Process/measurement conditions:

– Measured value jumps, e.g. through truck loading – Fast reaction time – Large distance to the medium

Page 46: VEGAPULS 61

46

6 Set up with the display and adjustment module

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

• Properties, sensor: – Little averaging – Max. reaction speed, very high measured value jumps are

accepted

Demonstration:• Adjustment for all applications which are not typically level meas-

urement – Instrument demonstration – Object recognition/monitoring (additional settings required)

• Properties, sensor: – Sensor accepts all measured value changes within the measur-

ing range immediately – High sensitivity against interferences, because virtually no

averaging

Through this selection, the sensor is adapted optimally to the applica-tion or the location and measurement reliability under the various basic conditions is increased considerably.Enter the requested parameters via the appropriate keys, save your settings with [OK] and jump to the next menu item with the [ESC] and the [->] key.

Alsothevesselformcaninfluencethemeasurementapartfromthemedium and the application. To adapt the sensor to these measure-mentconditions,thismenuitemoffersyoudifferentoptionsforvesselbottom and ceiling in case of certain applications.

Enter the requested parameters via the appropriate keys, save your settings with [OK] and jump to the next menu item with the [ESC] and the [->] key.

With this selection, the operating range of the sensor is adapted to thevesselheightandthereliabilitywithdifferentframeconditionsisincreased considerably.The min. adjustment must be carried out independently of this.

Enter the requested parameters via the appropriate keys, save your settings with [OK] and jump to the next menu item with the [ESC] and the [->] key.

Since the radar sensor is a distance measuring instrument, the distance from the sensor to the product surface is measured. For indication of the real level, an allocation of the measured distance to the percentage height must be carried out.

Setup - Vessel form

Setup - Vessel height, measuring range

Setup - Adjustment

Page 47: VEGAPULS 61

47

6 Set up with the display and adjustment module

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

To perform the adjustment, enter the distance with full and empty ves-sel, see the following example:

100%

0%

0,5

m(1

9.68

")5

m(1

96.9

")

2

1

3

Fig.36:Parameteradjustmentexamplemin./max.adjustment1 Min. level = max. measuring distance2 Max. level = min. measuring distance3 Reference plane

If these values are not known, an adjustment with the distances of for example 10 % and 90 % is possible. Starting point for these distance specificationsisalwaysthesealsurfaceofthethreadorflange.Youcanfindspecificationsofthereferenceplaneinchapter"Technicaldata". By means of these settings, the real level will be calculated.The real product level during this adjustment is not important, be-cause the min./max. adjustment is always carried out without chang-ing the product level. These settings can be made ahead of time without the instrument having to be installed.

Proceed as follows:1. Select the menu item "Setup" with [->]andconfirmwith[OK].

Now select with [->] the menu item "Min. adjustment"andconfirmwith [OK].

2. Edit the percentage value with [OK] and set the cursor to the requested position with [->].

Setup - Min. adjustment

Page 48: VEGAPULS 61

48

6 Set up with the display and adjustment module

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

3. Set the requested percentage value with [+] and save with [OK]. The cursor jumps now to the distance value.

4. Enter the suitable distance value in m for the empty vessel (e.g. distance from the sensor to the vessel bottom) corresponding to the percentage value.

5. Save settings with [OK] and move with [ESC] and [->] to the max. adjustment.

Proceed as follows:1. Select with [->]themenuitemMax.adjustmentandconfirmwith

[OK].

2. Prepare the percentage value for editing with [OK] and set the cursor to the requested position with [->].

3. Set the requested percentage value with [+] and save with [OK]. The cursor jumps now to the distance value.

4. Enter the appropriate distance value in m (corresponding to the percentage value) for the full vessel. Keep in mind that the max. level must lie below the min. distance to the antenna edge.

5. Save settings with [OK]

Todampprocess-dependentmeasuredvaluefluctuations,setanintegration time of 0 … 999 s in this menu item.

Depending on the sensor type, the factory setting is 0 s or 1 s.

Setup - Max. adjustment

Setup - Damping

Page 49: VEGAPULS 61

49

6 Set up with the display and adjustment module

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

In the menu item "Current output mode" you determine the output characteristics and reaction of the current output in case of failure.

The default setting is output characteristics 4 … 20 mA, failure mode <3.6mA.

In the menu item "CurrentoutputMin./Max.", you determine the reac-tion of the current output during operation.

The default setting is min. current 3.8 mA and max. current 20.5 mA.

In this menu item, the PIN is activated/deactivated permanently. Enteringa4-digitPINprotectsthesensordataagainstunauthorizedaccessandunintentionalmodifications.IfthePINisactivatedperma-nently, it can be deactivated temporarily (i.e. for approx. 60 min.) in any menu item.

Only the following functions are permitted with activated PIN:

• Select menu items and show data• Read data from the sensor into the display and adjustment mod-

ule.

Caution:With active PIN, adjustment via PACTware/DTM as well as other systems is also blocked.

In delivery status, the PIN is "0000".

This menu item enables the setting of the requested national lan-guage.

Setup - Current output mode

Setup - Current output Min./Max.

Lock setup - adjustment

Display - Language

Page 50: VEGAPULS 61

50

6 Set up with the display and adjustment module

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

In the delivery status, the sensor is set to the ordered national lan-guage.

Inthismenuitemyoucandefinetheindicationofthemeasuredvalueon the display.

The default setting for the indication value is e.g. distance with radar sensors.

The optionally integrated background lighting can be adjusted via the adjustment menu. The function depends on the level of the supply voltage, see operating instructions of the respective sensor.

In delivery status, the lighting is switched on.

In this menu item, the device status is displayed.

The respective min. and max. measured value is saved in the sensor. The values are displayed in the menu item "Peak values".

Display - Displayed value

Display - Backlight

Diagnostics - Device status

Diagnosis - Peak value

Page 51: VEGAPULS 61

51

6 Set up with the display and adjustment module

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

The respective min. and max. measured value of the electronics temperature is saved in the sensor. These values as well as the actual temperature value are displayed in the menu item "Peak values".

When non-contact level sensors are used, the measurement can be influencedbytherespectiveprocessconditions.Inthismenuitem,the measurement reliability of the level echo is displayed as dB value. The measurement reliability equals signal strength minus noise. The higher the value, the more reliable the measurement. With a function-ing measurement, the values are > 10 dB.

In this menu item you can simulate measured values via the current output. This allows the signal path to be tested, e.g. through down-stream indicating instruments or the input card of the control system.

How to start the simulation:1. Push [OK]2. Select the requested simulation variable with [->]andconfirm

with [OK].3. With [OK]youstartthesimulation,firstofalltheactualmeasured

value is displayed in %4. Start the editing mode with [OK]5. Set the requested numerical value with [+] and [->].6. Push [OK]

Note:During simulation, the simulated value is outputted as 4 … 20 mA cur-rent value and digital HART signal.

Diagnosis - Electronics temperature

Diagnosis - Measurement reliability

Diagnosis - Simulation

Page 52: VEGAPULS 61

52

6 Set up with the display and adjustment module

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

How to interrupt the simulation:

→ Push [ESC]

Information:The simulation is automatically terminated 10 minutes after the last pressing of a key.

The "Echocurve" shows the signal strength of the echoes over the measuring range in dB. The signal strength enables an evaluation of the quality of the measurement.

The "False signal suppression" displays the saved false echoes (see menu "Additional settings") of the empty vessel with signal strength in "dB" over the measuring range.A comparison of echo curve and false signal suppression allows a more detailed statement of the reliability.

Theselectedcurveiscontinuouslyupdated.Asubmenuwithzoomfunctions is opened with the [OK] key:

• "X-Zoom":Zoomfunctionforthemeas.distance• "Y-Zoom":1,2,5and10xsignalmagnificationin"dB"• "Unzoom":Resetthepresentationtothenominalmeasuringrange

withoutmagnification

With the function "Echocurvememory" the echo curve can be saved atthetimeofsetup.Thisisgenerallyrecommended;forusingtheAs-set Management functions it is absolutely necessary. If possible, the curve should be saved with a low level in the vessel.With the adjustment software PACTware and the PC, the high resolu-tionechocurvecanbedisplayedandusedtorecognizesignalchanges over the operating time. In addition, the echo curve of the setup can be also displayed in the echo curve window and compared with the actual echo curve.

In this menu item you select the measured variable of the system and the temperature unit.

Diagnoses - Curve indica-tion

Diagnostics - Echo curve memory

Additional adjustments - Device units

Page 53: VEGAPULS 61

53

6 Set up with the display and adjustment module

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

Thefollowingcircumstancescauseinterferingreflectionsandcaninfluencethemeasurement:

• High sockets• Vessel installations such as struts• Agitators• Buildup or welded joints on vessel walls

Note:A false signal suppression detects, marks and saves these false signals so that they are no longer taken into account in the level measurement.

This should be done with a low level so that all potential interfering reflectionscanbedetected.Proceed as follows:1. Select with [->] the menu item "False signal suppression" and

confirmwith[OK].

2. Confirmagainwith[OK].

3. Confirmagainwith[OK].

4. Confirmagainwith[OK] and enter the actual distance from the sensor to the product surface.

5. All interfering signals in this section are detected by the sensor andstoredafterconfirmingwith[OK].

Note:Check the distance to the product surface, because if an incorrect (too large) value is entered, the existing level will be saved as a false signal. The level would then no longer be detectable in this area.

Additional adjustments - False signal suppression

Page 54: VEGAPULS 61

54

6 Set up with the display and adjustment module

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

If a false signal suppression has already been saved in the sensor, the following menu window appears when selecting "False signal suppression":

Delete: An already created false signal suppression will be com-pletely deleted. This is useful if the saved false signal suppression no longer matches the metrological conditions in the vessel.Extend: is used to extend an already created false signal suppres-sion. This is useful if a false signal suppression was carried out with a too high level and not all false signals could be detected. When selecting "Extend", the distance to the product surface of the created false signal suppression is displayed. This value can now be changed and the false signal suppression can be extended to this range.

Alinearizationisnecessaryforallvesselsinwhichthevesselvolumedoesnotincreaselinearlywiththelevel-e.g.ahorizontalcylindri-cal or spherical tank - and the indication or output of the volume is required.Correspondinglinearizationcurvesarepreprogrammedfor these vessels. They represent the correlation between the level percentage and vessel volume.By activating the appropriate curve, the volume percentage of the vessel is displayed correctly. If the volume should not be displayed in percent but e.g. in l or kg, a scaling can be also set in the menu item "Display".

Enter the requested parameters via the appropriate keys, save your settings and jump to the next menu item with the [ESC] and [->] key.

Caution:Note the following if instruments with appropriate approval are used aspartofanoverfillprotectionsystemaccordingtoWHG:If a linearisation curve is selected, the measuring signal is no longer necessarilylineartothefillingheight.Thismustbeconsideredbytheuser especially when adjusting the switching point on the limit signal transmitter.

Enteringa4-digitPINprotectsthesensordataagainstunauthorizedaccessandunintentionalmodification.Inthismenuitem,thePINisdisplayed or edited and changed. However, this menu item is only available if adjustment is enabled in the menu "Setup".

Additional adjustments - Linearization curve

Additional settings - PIN

Page 55: VEGAPULS 61

55

6 Set up with the display and adjustment module

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

In delivery status, the PIN is "0000".

In this menu item, the internal clock of the sensor is adjusted.

With a reset, certain parameter adjustments carried out by the user are reset.

The following reset functions are available:Delivery status: Restoring the parameter settings at the time of ship-mentfromthefactoryincl.theorder-specificsettings.Acreatedfalsesignalsuppression,user-programmablelinearizationcurveaswellasthe measured value memory will be deleted.Basic settings: Resetting of the parameter settings, incl. special parameters, to the default values of the respective instrument. Any stored false signal suppression or user programmable linearisation curve, as well as the measured value memory, is deleted.Setup: Resetting of the parameter settings to the default values of the respective instrument in the menu item Setup. User-generated false signal suppression, user-programmed linearisation curve, measured value memory as well as event memory remain untouched. The linearisation is set to linear.False signal suppression: Deleting a previously created false signal suppression. The false signal suppression created in the factory remains active.Peak values, measured value: Resetting of the measured min. and max. distances to the actual measured value.The following table shows the default values of the instrument. De-pending on the instrument version, not all menu items are available or somemaybedifferentlyassigned:

Additional adjustments - Date/Time

Additional adjustments - Reset

Page 56: VEGAPULS 61

56

6 Set up with the display and adjustment module

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

Menu Menu item Default value

Setup Measurement loop name

Sensor

Medium Liquid/WaterBulk solids/Crushed stones, gravel

Application Storage tankSilo

Vessel form Vessel bottom, dished boiler endVessel top, dished boiler end

Vessel height/Measuring range

Recommended measuring range, see "Technicaldata" in the supplement

Min. adjustment Recommended measuring range, see "Technicaldata" in the supplement

Max. adjustment 0,000 m(d)

Damping 0.0 s

Current output mode

4…20mA,<3.6mA

Current output Min./Max.

Min. current 3.8 mA, max. current 20.5 mA

Lock adjustment Released

Display Language Like order

Displayed value Distance

Display unit m

Scalingsize Volumel

Scaling 0.00 lin %, 0 l100.00 lin %, 100 l

Backlight Switched on

Additional adjust-ments

Distance unit m

Temperature unit °C

Probe length Length of the standpipe Ex factory

Linearisation curve

Linear

HART mode StandardAddress 0

ThesensorofferstheHARTmodesstandardandMultidrop.Inthismenu item you determine the HART modes and enter the address with Multidrop.

Additional adjustments - HART mode

Page 57: VEGAPULS 61

57

6 Set up with the display and adjustment module

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

Themodestandardwiththefixedaddress0meansoutputofthemeasured value as 4 … 20 mA signal.In Multidrop mode, up to 63 sensors can be operated on one two-wire cable. An address between 1 and 63 must be assigned to each sen-sor.1)

The default setting is standard with address 0.

The instrument settings are copied with this function. The following functions are available:

• Store data from the sensor into the indicating/adjustment module.• Store data from the display and adjustment module in the sensor

The following data or settings for adjustment of the display and ad-justment module are saved:

• All data of the menu "Setup" and "Display"• In the menu "Additional settings" the items "Distance unit, tem-

perature unit and linearization"• Thevaluesoftheuserprogrammablelinearizationcurve

The copied data are permanently saved in an EEPROM memory in the display and adjustment module and remain there even in case of power failure. From there, they can be written into one or more sen-sors or kept as backup for a possible sensor exchange.The type and the volume of the copied data depend on the respective sensor.

Note:Before the data are stored in the sensor, a check is carried out to determineifthedatafitthesensor.Ifthedatadonotfit,afaultsignalis triggered or the function is blocked. When data are being written into the sensor, the display shows which instrument type the data originate from and which TAG-no. this sensor had.

In this menu, you read out the instrument name and the instrument serial number:

In this menu item, the hardware and software version of the sensor is displayed.

Additional adjustments - Copy instrument settings

Info - Instrument name

Info - Instrument version

1) The4…20mAsignaloftheHARTsensorisswitchedoff.Thesensorconsumes a constant current of 4 mA. The measuring signal is transmitted exclusively as digital HART signal.

Page 58: VEGAPULS 61

58

6 Set up with the display and adjustment module

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

In this menu item, the date of factory calibration of the sensor as well as the date of the last change of sensor parameters are displayed via the display and adjustment module or via the PC.

In this menu item, the features of the sensor such as approval, pro-cessfitting,seal,measuringrange,electronics,housingandothersare displayed.

6.5 Saving the parameter adjustment dataWe recommended noting the adjusted data, e.g. in this operating instructions manual, and archiving them afterwards. They are thus available for multiple use or service purposes.If the instrument is equipped with a display and adjustment module, the data in the sensor can be saved in the display and adjustment module. The procedure is described in the operating instructions manual "Display and adjustment module" in the menu item "Copy sensor data". The data remain there permanently even if the sensor power supply fails.The following data or settings for adjustment of the display and ad-justment module are saved:

• All data of the menu "Setup" and "Display"• In the menu "Additional settings" the items "Sensor-specificunits,

temperature unit and linearization"• ThevaluesoftheuserprogrammablelinearizationcurveThe function can also be used to transfer settings from one instru-ment to another instrument of the same type. If it is necessary to exchange a sensor, the display and adjustment module is inserted into the replacement instrument and the data are likewise written into the sensor via the menu item "Copy sensor data".

Info - Date of manufacture

Instrument features

Page 59: VEGAPULS 61

59

7 Setup with PACTware

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

7 Setup with PACTware

7.1 Connect the PC

3

1

2

Fig. 37: Connection of the PC directly to the sensor via the interface adapter1 USBcabletothePC2 InterfaceadapterVEGACONNECT3 Sensor

1

5

2 4

3 OPEN

TWIST

USB

LOCK

Fig.38:ConnectingthePCviaHARTtothesignalcable1 Sensor2 HARTresistance250Ω(optionaldependingonprocessing)3 Connection cable with 2 mm pins and terminals4 Processingsystem/PLC/Voltagesupply5 Interfaceadapter,forexampleVEGACONNECT4

Note:With power supply units with integrated HART resistance (internal resistanceapprox.250Ω),anadditionalexternalresistanceisnotnecessary. This applies, e.g. to the VEGA instruments VEGATRENN 149A, VEGAMET 381, VEGAMET 391. Common Ex separators are alsousuallyequippedwithasufficientcurrentlimitationresistance.In

Via the interface adapter directly on the sensor

Via the interface adapter and HART

Page 60: VEGAPULS 61

60

7 Setup with PACTware

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

such cases, the interface converter can be connected parallel to the 4 … 20 mA cable (dashed line in the previous illustration).

7.2 Parameter adjustmentFor parameter adjustment of the instrument via a Windows PC, the configurationsoftwarePACTwareandasuitableinstrumentdriver(DTM) according to FDT standard are required. The latest PACTware version as well as all available DTMs are compiled in a DTM Collec-tion. The DTMs can also be integrated into other frame applications according to FDT standard.

Note:To ensure that all instrument functions are supported, you should always use the latest DTM Collection. Furthermore, not all described functionsareincludedinolderfirmwareversions.Youcandownloadthe latest instrument software from our homepage. A description of the update procedure is also available in the Internet.

Further setup steps are described in the operating instructions manu-al "DTMCollection/PACTware" attached to each DTM Collection and which can also be downloaded from the Internet. Detailed descrip-tions are available in the online help of PACTware and the DTMs.

Fig.39:ExampleofaDTMview

All device DTMs are available as a free-of-charge standard version and as a full version that must be purchased. In the standard version, all functions for complete setup are already included. An assistant for simpleprojectconfigurationsimplifiestheadjustmentconsiderably.Saving/printing the project as well as import/export functions are also part of the standard version.In the full version there is also an extended print function for complete project documentation as well as a save function for measured value

Prerequisites

Standard/Full version

Page 61: VEGAPULS 61

61

7 Setup with PACTware

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

and echo curves. In addition, there is a tank calculation program as well as a multiviewer for display and analysis of the saved measured value and echo curves.The standard version is available as a download under www.vega.com/downloads and "Software". The full version is avail-able on CD from the agency serving you.

7.3 Saving the parameter adjustment dataWe recommend documenting or saving the parameter adjustment data via PACTware. That way the data are available for multiple use or service purposes.

Page 62: VEGAPULS 61

62

8 Set up with other systems

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

8 Set up with other systems

8.1 DD adjustment programsDevice descriptions as Enhanced Device Description (EDD) are available for DD adjustment programs such as, for example, AMS™ and PDM.Thefilescanbedownloadedatwww.vega.com/downloads under "Software".

8.2 Field Communicator 375, 475Device descriptions for the instrument are available as EDD for pa-rameter adjustment with the Field Communicator 375 or 475.For the integration of the EDD in the Field Communicator 375 or 475, the software "Easy Upgrade Utility" is required which is available from the manufacturer. This software is updated via the Internet and new EDDs are automatically taken over into the device catalogue of this software after they are released by the manufacturer. They can then be transferred to a Field Communicator.

Page 63: VEGAPULS 61

63

9 Diagnosis, asset management and service

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

9 Diagnosis, asset management and service

9.1 MaintenanceIf the device is used correctly, no maintenance is required in normal operation.

9.2 Measured value and event memoryThe instrument has several memories which are available for diagno-sis purposes. The data remain even with voltage interruption.

Up to 100,000 measured values can be stored in the sensor in a ring memory. Each entry contains date/time as well as the respective measured value. Storable values are for example:

• Distance• Filling height• Percentage value• Lin. percent• Scaled• Current value• Meas. reliability• Electronics temperature

When the instrument is shipped, the measured value memory is active and stores distance, measurement certainty and electronics temperature every 3 minutes.The requested values and recording conditions are set via a PC with PACTware/DTM or the control system with EDD. Data are thus read out and also reset.

Up to 500 events are automatically stored with a time stamp in the sensor (non-deletable). Each entry contains date/time, event type, event description and value. Event types are for example:

• Modificationofaparameter• Switch-onandswitch-offtimes• Status messages (according to NE 107)• Error messages (according to NE 107)

The data are read out via a PC with PACTware/DTM or the control system with EDD.

The echo curves are stored with date and time and the corresponding echo data. The memory is divided into two sections:Echo curve of the setup: This is used as reference echo curve for the measurement conditions during setup. Changes in the measure-ment conditions during operation or buildup on the sensor can thus berecognized.Theechocurveofthesetupisstoredvia:

• PC with PACTware/DTM • Control system with EDD • Display and adjustment module

Measured value memory

Event memory

Echo curve memory

Page 64: VEGAPULS 61

64

9 Diagnosis, asset management and service

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

Further echo curves: Up to 10 echo curves can be stored in a ring bufferinthismemorysection.Furtherechocurvesarestoredvia:

• PC with PACTware/DTM • Control system with EDD

9.3 Asset Management functionThe instrument features self-monitoring and diagnostics according to NE 107 and VDI/VDE 2650. In addition to the status messages in the following tables, detailed error messages are available under menu item "Diagnostics" via the display and adjustment module, PACTware/DTM and EDD.

The status messages are divided into the following categories:

• Failure• Function check• Outofspecification• Maintenance requirement

and explained by pictographs:

41 2 3Fig. 40: Pictographs of the status messages1 Failure - red2 Outofspecification-yellow3 Function check - orange4 Maintenance - blue

Failure: Due to a malfunction in the instrument, a failure message is outputted.This status message is always active. It cannot be deactivated by the user.Function check: The instrument is in operation, the measured value is temporarily invalid (for example during simulation).This status message is inactive by default. It can be activated by the user via PACTware/DTM or EDD.Outofspecification: The measured value is unstable because the instrumentspecificationisexceeded(e.g.electronicstemperature).This status message is inactive by default. It can be activated by the user via PACTware/DTM or EDD.Maintenance:Duetoexternalinfluences,theinstrumentfunctionislimited.Themeasurementisaffected,butthemeasuredvalueisstill valid. Plan in maintenance for the instrument because a failure is expected in the near future (e.g. due to buildup).

Status messages

Page 65: VEGAPULS 61

65

9 Diagnosis, asset management and service

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

This status message is inactive by default. It can be activated by the user via PACTware/DTM or EDD.

The following table shows the error codes in the status message "Failure"andgivesinformationonthereasonandrectification.Keepin mind that some information is only valid with four-wire instruments.

CodeText message

Cause Rectification DevSpec State in CMD 48

F013no measured value available

– Sensor does not detect an echo during operation

– Antenna system dirty or defective

– Check or correct installation and/or parameter adjust-ment

– Clean or exchange process compo-nent or antenna

Bit 0 of Byte 0…5

F017Adjustment span too small

– Adjustment not withinspecification

– Change adjust-ment accord-ing to the limit values(differencebetween min. and max.≥10mm)

Bit 1 of Byte 0…5

F025Error in the lin-earizationtable

– Index markers are not continuously rising, for example illogical value pairs

– Checklineariza-tion table

– Delete table/Cre-ate new

Bit 2 of Byte 0…5

F036No operable software

– Failed or inter-rupted software update

– Repeat software update

– Check electronics version

– Exchanging the electronics

– Send instrument for repair

Bit 3 of Byte 0…5

F040Error in the electronics

– Hardware defect – Exchanging the electronics

– Send instrument for repair

Bit 4 of Byte 0…5

F080General soft-ware error

– General software error

– Disconnect operat-ingvoltagebriefly

Bit 5 of Byte 0…5

F105Determine measured value

– The instrument is still in the start phase, the measured value could not yet be determined

– Wait for the end of the switch-on phase

– Duration depend-ing on the version and parameter adjustment up to approximately 3 min.

Bit 6 of Byte 0…5

Failure

Page 66: VEGAPULS 61

66

9 Diagnosis, asset management and service

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

CodeText message

Cause Rectification DevSpec State in CMD 48

F113Communica-tion error

– EMC interference – Transmission error

with the external communication with 4-wire power supply unit

– Remove EMC influences

– Exchange 4-wire power supply unit or electronics

Bit 12 of Byte 0…5

F125Impermissi-ble electronics temperature

– Temperature of the electronics in thenon-specifiedrange

– Check ambient temperature

– Isolate electronics – Use instrument

with higher tem-perature range

Bit 7 of Byte 0…5

F260Error in the cal-ibration

– Error in the calibra-tion carried out in the factory

– Error in the EEPROM

– Exchanging the electronics

– Send instrument for repair

Bit 8 of Byte 0…5

F261Error in the instrument set-tings

– Error during setup – False signal sup-

pression faulty – Error when carry-

ing out a reset

– Repeat setup – Carry out a reset

Bit 9 of Byte 0…5

F264Installation/Set-up error

– Adjustment not within the vessel height/measuring range

– Max. measuring range of the instru-mentnotsufficient

– Check or correct installation and/or parameter adjust-ment

– Use an instrument with bigger meas-uring range

Bit 10 of Byte 0…5

F265Measurement function dis-turbed

– Sensor no longer carries out a measurement

– Operating voltage too low

– Check operating voltage

– Carry out a reset – Disconnect operat-ingvoltagebriefly

Bit 11 of Byte 0…5

The following table shows the error codes and text messages in the status message "Function check" and provides information on causes as well as corrective measures.

CodeText message

Cause Rectification DevSpec State in CMD 48

C700Simulation active

– A simulation is active – Finish simulation – Wait for the automatic end

after 60 mins.

"Simulation Active" in"StandardizedSta-tus 0"

The following table shows the error codes and text messages in the status message "Outofspecification" and provides information on causes as well as corrective measures.

Function check

Outofspecification

Page 67: VEGAPULS 61

67

9 Diagnosis, asset management and service

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

CodeText message

Cause Rectification DevSpec State in CMD 48

S600Impermissible elec-tronics temperature

– Temperature of the electron-icsinthenon-specifiedrange

– Check ambient temperature – Isolate electronics – Use instrument with higher

temperature range

Bit 5 of Byte 14…24

S601Overfilling

– Dangerofvesseloverfilling – Make sure that there is no furtherfilling

– Check level in the vessel

Bit 6 of Byte 14…24

The following table shows the error codes and text messages in the status message "Maintenance" and provides information on causes as well as corrective measures.

CodeText message

Cause Rectification DevSpec State in CMD 48

M500Error with the reset de-livery status

– With the reset to delivery status, the data could not be restored

– Repeat reset – LoadXMLfilewithsensor

data into the sensor

Bit 0 of Byte 14…24

M501Error in the non-active linearizationtable

– Hardware error EEPROM – Exchanging the electronics – Send instrument for repair

Bit 1 of Byte 14…24

M502Error in the diagnosis memory

– Hardware error EEPROM – Exchanging the electronics – Send instrument for repair

Bit 2 of Byte 14…24

M503Meas. reliability too low

– The echo/noise ratio is too small for reliable measure-ment

– Check installation and process conditions

– Clean the antenna – Change polarisation direc-

tion – Use instrument with higher

sensitivity

Bit 3 of Byte 14…24

M504Error on an device in-terface

– Hardware defect – Check connections – Exchanging the electronics – Send instrument for repair

Bit 4 of Byte 14…24

M505No echo available

– Level echo can no longer be detected

– Clean the antenna – Use a more suitable

antenna/sensor – Remove possible false

echoes – Optimizesensorposition

and orientation

Bit 7 of Byte 14…24

9.4 Rectify faultsThe operator of the system is responsible for taking suitable meas-ures to rectify faults.

Thefirstmeasuresare:

Maintenance

Reaction when malfunc-tion occurs

Procedure for fault recti-fication

Page 68: VEGAPULS 61

68

9 Diagnosis, asset management and service

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

• Evaluation of fault messages, for example via the display and adjustment module

• Checking the output signal• Treatment of measurement errors

Further comprehensive diagnostics options are available with a PC with PACTware and the suitable DTM. In many cases, the reasons can bedeterminedinthiswayandfaultsrectified.

Connect a multimeter in the suitable measuring range according to the wiring plan. The following table describes possible errors in the current signal and helps to eliminate them:

Error Cause Rectification

4 … 20 mA signal not stable

– Fluctuations of the measured variable

– Set damping appropriate to the instrument via the display and adjustment module or PACTware/DTM

4 … 20 mA signal missing

– Electrical con-nection faulty

– Check connection according to chapter "Connection steps" and if necessary, correct according to chapter "Wiring plan"

– Voltage supply missing

– Checkcablesforbreaks;repairifnecessary

– Operating volt-age too low or load resistance too high

– Check, adapt if necessary

Current sig-nal greater than 22 mA or less than 3.6 mA

– Electronics module in the sensor defec-tive

– Exchange the instrument or send it in for repair

The below tables show typical examples of application-related meas-urementerrorswithliquids.Themeasurementerrorsaredifferentiatedaccording to the following:

• Constant level• Filling• Emptying

The images in column "Errorpattern" show the real level as a broken line and the level displayed by the sensor as a continuous line.

12

Leve

l

time0

1 Real level2 Level displayed by the sensor

Check the 4 … 20 mA signal

Treatment of measure-ment errors with liquids

Page 69: VEGAPULS 61

69

9 Diagnosis, asset management and service

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

Notes:• Wherever the sensor displays a constant value, the reason could

also be the fault setting of the current output to "Hold value"• If the level indication is too low, the reason could be a line resist-

ance that is too high

Measurement error with constant level

Fault description Error pattern Cause Rectification

1. Measured value shows a too low or too high level

Leve

l

time0

– Min./max. adjustment not correct

– Adapt min./max. adjustment

– Incorrectlinearizationcurve – Adaptlinearizationcurve

– Installation in a bypass tube or standpipe, hence running time error (small measurement error close to 100 %/large error close to 0 %)

– Check parameter "Application" with respect to vessel form, adapt if necessary (bypass, standpipe, diameter)

2. Measured value jumps towards 0 % Le

vel

time0

– Multiple echo (vessel top, product surface) with amplitude higher than the level echo

– Check parameter "Application", especially vessel top, type of medium, dished bottom, high dielectric constant, and adapt if necessary

3. Measured value jumps towards 100 % Le

vel

time0

– Due to the process, the ampli-tude of the level echo sinks

– A false signal suppression was not carried out

– Carry out a false signal sup-pression

– Amplitude or position of a false signal has changed (e.g. con-densation,buildup);falsesignalsuppression no longer matches actual conditions

– Determine the reason for the changed false signals, carry out false signal suppression, e.g. with condensation

Measurementerrorduringfilling

Fault description Error pattern Cause Rectification

4. Measured value re-mains unchanged duringfilling

Leve

l

time0

– False signals in the close range too big or level echo too small

– Strong foam or spout genera-tion

– Max. adjustment not correct

– Eliminate false signals in the close range

– Check measurement situation: Antenna must protrude out of the socket, installations

– Remove contamination on the antenna

– In case of interferences due to installations in the close range: Change polarisation direction

– Create a new false signal sup-pression

– Adapt max. adjustment

5. Measured value re-mains in the bottom sectionduringfilling

Leve

l

time0

– Echo from the tank bottom larger than the level echo, for example, with products with εr<2.5oil-based,solvents

– Check parameters Medium, Vessel height and Floor form, adapt if necessary

Page 70: VEGAPULS 61

70

9 Diagnosis, asset management and service

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

Fault description Error pattern Cause Rectification

6. Measured value re-mains momentarily unchangedduringfill-ing and then jumps to the correct level

Leve

l

time0

– Turbulence on the product surface,quickfilling

– Check parameters, change if necessary, e.g. in dosing ves-sel, reactor

7. Measured value jumps towards 0 % duringfilling

Leve

l

time0

– Amplitude of a multiple echo (vessel top - product surface) is larger than the level echo

– Check parameter "Application", especially vessel top, type of medium, dished bottom, high dielectric constant, and adapt if necessary

– The level echo cannot be distin-guished from the false signal at a false signal position (jumps to multiple echo)

– In case of interferences due to installations in the close range: Change polarisation direction

– Chose a more suitable installa-tion position

8. Measured value jumps towards 100 % duringfilling

Leve

l

time0

– Due to strong turbulence and foamgenerationduringfilling,the amplitude of the level echo sinks. Measured value jumps to the false signal

– Carry out a false signal sup-pression

9. Measured value jumps sporadically to 100%duringfilling

Leve

l

time0

– Varying condensation or con-tamination on the antenna

– Carry out a false signal sup-pression or increase false signal suppression with con-densation/contamination in the close range by editing

10. Measured value jumpsto≥100%or0 m distance

Leve

l

time0

– Level echo is no longer detected in the close range due to foam generation or false signals in the close range. The sensorgoesintooverfillprotec-tion mode. The max. level (0 m distance) as well as the status message"Overfillprotection"are outputted.

– Check measuring site: Antenna must protrude out of the socket

– Remove contamination on the antenna

– Use a sensor with a more suit-able antenna

Measurement error during emptying

Fault description Error pattern Cause Rectification

11. Measured value re-mains unchanged in the close range during emptying

Leve

l

time0

– False signal larger than the level echo

– Level echo too small

– Eliminate false signal in the close range. Check: Antenna must protrude from the socket

– Remove contamination on the antenna

– In case of interferences due to installations in the close range: Change polarisation direction

– After eliminating the false sig-nals, the false signal suppres-sion must be deleted. Carry out a new false signal suppression

Page 71: VEGAPULS 61

71

9 Diagnosis, asset management and service

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

Fault description Error pattern Cause Rectification

12. Measured value jumps towards 0 % during emptying

Leve

l

time0

– Echo from the tank bottom larger than the level echo, for example, with products with εr<2.5oil-based,solvents

– Check parameters Type of medium, Vessel height and Floor form, adapt if necessary

13. Measured value jumps sporadically to-wards 100 % during emptying

Leve

l

time0

– Varying condensation or con-tamination on the antenna

– Carry out false signal suppres-sion or increase false signal suppression in the close range by editing

– With bulk solids, use radar sen-sor with purging air connection

Depending on the reason for the fault and the measures taken, the steps described in chapter "Setup" must be carried out again or must be checked for plausibility and completeness.

Should these measures not be successful, please call in urgent cases the VEGA service hotline under the phone no. +49 1805 858550.The hotline is also available outside normal working hours, seven days a week around the clock.Sinceweofferthisserviceworldwide,thesupportisprovidedinEnglish. The service itself is free of charge, the only costs involved are the normal call charges.

9.5 Exchanging the electronics moduleIf the electronics module is defective, it can be replaced by the user.In Ex applications, only instruments and electronics modules with ap-propriate Ex approval may be used.

If there is no electronics module available on site, the electronics module can be ordered through the agency serving you. The electron-icsmodulesareadaptedtotherespectivesensoranddifferinsignaloutput or voltage supply.The new electronics module must be loaded with the default settings of the sensor. These are the options:

• In the factory• Or on site by the user

In both cases, the serial number of the sensor is needed. The serial numbers are stated on the type label of the instrument, on the inside of the housing as well as on the delivery note.Whenloadingonsite,firstofalltheorderdatamustbedownloadedfrom the Internet (see operating instructions manual "Electronicsmodule").

Caution:Alluser-specificsettingsmustbeenteredagain.Hence,youhavetocarry out a new setup after the electronics exchange.If you have stored the data of the parameter adjustment during the firstsetupofthesensor,youcantransferthesetothereplacementelectronics module. A new setup is no more necessary.

Reaction after fault recti-fication

24 hour service hotline

Page 72: VEGAPULS 61

72

9 Diagnosis, asset management and service

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

9.6 Software updateThe following components are required to update the instrument software:

• Instrument• Voltage supply• Interface adapter VEGACONNECT• PC with PACTware• CurrentinstrumentsoftwareasfileYoucanfindthecurrentinstrumentsoftwareaswellasdetailedinformation on the procedure under "www.vega.com/downloads" and "Software".

Caution:Instruments with approvals can be bound to certain software versions. Thereforemakesurethattheapprovalisstilleffectiveafterasoftwareupdate is carried out.Youcanfinddetailedinformationatwww.vega.com/downloads and "Approvals".

9.7 How to proceed if a repair is necessaryYoucanfindarepairformaswellasdetailedinformationonhowtoproceed at www.vega.com/downloads and "Formsandcertificates".By doing this you help us carry out the repair quickly and without hav-ing to call back for needed information.If a repair is necessary, please proceed as follows:

• Printandfilloutoneformperinstrument• Clean the instrument and pack it damage-proof• Attach the completed form and, if need be, also a safety data

sheet outside on the packaging• Please contact the agency serving you to get the address for

thereturnshipment.Youcanfindtheagencyonourhomepagewww.vega.com.

Page 73: VEGAPULS 61

73

10 Dismount

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

10 Dismount

10.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions such as e.g. pressure in the vessel or pipeline, high temperatures, cor-rosive or toxic products etc.

Take note of chapters "Mounting" and "Connecting to power supply" and carry out the listed steps in reverse order.

10.2 DisposalThe instrument consists of materials which can be recycled by spe-cialised recycling companies. We use recyclable materials and have designed the parts to be easily separable.Correctdisposalavoidsnegativeeffectsonhumansandtheenviron-ment and ensures recycling of useful raw materials.Materials: see chapter "Technicaldata"If you have no way to dispose of the old instrument properly, please contact us concerning return and disposal.

WEEE directive 2002/96/EGThis instrument is not subject to the WEEE directive 2002/96/EG and the respective national laws. Pass the instrument directly on to a spe-cialised recycling company and do not use the municipal collecting points. These may be used only for privately used products according to the WEEE directive.

Page 74: VEGAPULS 61

74

11 Supplement

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

11 Supplement

11.1 Technical dataGeneral data316L corresponds to 1.4404 or 1.4435Materials, wetted parts with encapsulated antenna system

Ʋ Processfitting PVDF, 316L Ʋ Process seal FKM (IDG FKM 13-75) Ʋ Antenna PVDF

Materials, wetted parts with plastic horn antenna Ʋ Adapterflange PP-GF30 black Ʋ Seal,adapterflange FKM (COG VI500), EPDM (COG AP310) Ʋ Antenna PBT-GF 30 Ʋ Focussing lense PP

Materials, non-wetted parts Ʋ Compressionflange PP-GF30 black Ʋ Mounting strap 316L Ʋ Fixing screws, mounting strap 316L Ʋ Fixingscrews,adapterflange 304 Ʋ Plastic housing plastic PBT (Polyester) Ʋ Aluminium die-casting housing Aluminium die-casting AlSi10Mg, powder-coated - basis:

Polyester Ʋ Stainless steel housing 316L Ʋ Seal between housing and housing cover

NBR (stainless steel housing, precision casting), silicone (aluminium/plastichousing;stainlesssteelhousing,electropolished)

Ʋ Inspection window in housing cover (optional)

Polycarbonate

Ʋ Ground terminal 316LProcessfittings

Ʋ Pipe thread, cylindrical (ISO 228 T1) G1½ Ʋ American pipe thread, conically 1½ NPT Ʋ Flanges DIN from DN 80, ASME from 3", JIS from DN 100 10K Ʋ Hygienicfittings Clamp, slotted nut according to DIN 11851, Tuchenha-

gen VariventWeightdependingonprocessfittingandhousing material

0.7 … 3.4 kg (1.543 … 7.496 lbs)

Max. torque, mounting screws - strap on the sensor housing

4 Nm

Max.torqueflangescrews Ʋ CompressionflangeDN80 5 Nm (3.689 lbf ft) Ʋ AdapterflangeDN100 7 Nm (5.163 lbf ft)

Page 75: VEGAPULS 61

75

11 Supplement

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

Max. torque for NPT cable glands and Conduit tubes Ʋ Plastic housing 10 Nm (7.376 lbf ft) Ʋ Aluminium/Stainless steel housing 50 Nm (36.88 lbf ft)

Input variableMeasured variable The measured quantity is the distance between process

fittingofthesensorandproductsurface.Thereferenceplane is the seal surface on the hexagon or the lower sideoftheflange.

3

4 2

1

Fig. 55: Data of the input variable1 Reference plane2 Measured variable, max. measuring range3 Antenna length4 Usefulmeasuringrange

Standard electronicsMax. measuring range 35 m (114.8 ft)Recommended measuring range

Ʋ Encapsulated antenna system up to 10 m (32.81 ft) Ʋ Plastic horn antenna up to 20 m (65.62 ft)

Electronics with increased sensitivityMax. measuring range 35 m (114.8 ft)Recommended measuring range

Ʋ Encapsulated antenna system up to 10 m (32.81 ft) Ʋ Plastic horn antenna up to 20 m (65.62 ft)

Output variableOutput signal 4 … 20 mA/HARTRange of the output signal 3.8 … 20.5 mA/HART (default setting)Signal resolution 0.3 µA

Page 76: VEGAPULS 61

76

11 Supplement

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

Resolution, digital <1mm(0.039in)Failure signal current output (adjustable) mA-valueunchanged20.5mA,22mA,<3.6mAMax. output current 22 mAStarting current ≤3.6mA;≤10mAfor5msafterswitchingonLoad see load diagram under Power supplyDamping (63 % of the input variable), adjustable

0 … 999 s

HART output values according to HART 7.02)

Ʋ PV (Primary Value) Lin. percent Ʋ SV (Secondary Value) Distance Ʋ TV (Third Value) Meas. reliability Ʋ QV (Fourth Value) Electronics temperature

FulfilledHARTspecification 7.0Further information on Manufacturer ID, Device ID, Device Revision

See website of HART Communication Foundation

Accuracy (according to DIN EN 60770-1)Process reference conditions according to DIN EN 61298-1

Ʋ Temperature +18 … +30 °C (+64 … +86 °F) Ʋ Relative humidity 45 … 75 % Ʋ Air pressure 860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Installation reference conditions Ʋ Min. distance to internal installations > 200 mm (7.874 in) Ʋ Reflector Flatplatereflector Ʋ Falsereflections Biggest false signal, 20 dB smaller than the useful signal

Deviation with liquids See following diagrams

0,5 m (1.6 ft)

10 mm (0.394 in)

- 10 mm (- 0.394 in)

2 mm (0.079 in)

- 2 mm (- 0.079 in)0

1 2 3

Fig. 56: Deviation under reference conditions - encapsulated antenna system1 Reference plane2 Antenna edge3 Recommended measuring range

2) Default values, can be assigned individually

Page 77: VEGAPULS 61

77

11 Supplement

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

0,5 m (1.6 ft)

10 mm (0.394 in)

- 10 mm (- 0.394 in)

2 mm (0.079 in)

- 2 mm (- 0.079 in)0

1 2 3

Fig. 57: Deviation under reference conditions - plastic horn antenna1 Reference plane2 Antenna edge3 Recommended measuring range

Repeatability ≤±1mmDeviation with bulk solids The values depend to a great extent on the application.

Bindingspecificationsarethusnotpossible.

VariablesinfluencingmeasurementaccuracySpecificationsapplytothedigitalmeasuredvalueTemperature drift - Digital output ±3mm/10K,max.10mmAdditional deviation through electromag-netic interference acc. to EN 61326

<±50mm

SpecificationsapplyalsotothecurrentoutputTemperature drift - Current output ±0.03%/10Krelatingtothe16mAspanmax.±0.3%Deviation on the current output through analogue/digital conversion

<±15µA

Deviation in the current output due to strong, high-frequency electromagnetic fieldsacc.toEN61326

<±150µA

Characteristics and performance dataMeasuring frequency K-band(26GHztechnology)Measuring cycle time

Ʋ Standard electronics approx. 450 ms Ʋ Electronics with increased sensitivity approx.

700 ms

Step response time3) ≤3sBeam angle4)

Ʋ Encapsulated antenna system 22° Ʋ Plastic horn antenna 10°

3) Time span after a sudden measuring distance change by max. 0.5 m in liquid applications, max 2 m with bulk solidsapplications,untiltheoutputsignalhastakenforthefirsttime90%ofthefinalvalue(IEC61298-2).

4) Outsidethespecifiedbeamangle,theenergyoftheradarsignalisreducedby50%(-3dB).

Page 78: VEGAPULS 61

78

11 Supplement

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

Emitted HF power (depending on the parameter adjustment)5)

Ʋ Average spectral transmission power density

-14dBm/MHzEIRP

Ʋ Max. spectral transmission power density

+43dBm/50MHzEIRP

Ʋ Max. power density at a distance of 1 m

<1µW/cm²

Ambient conditionsAmbient, storage and transport tempera-ture

-40 … +80 °C (-40 … +176 °F)

Process conditionsFortheprocessconditions,pleasealsonotethespecificationsonthetypelabel.Thelowervaluealways applies.Vessel pressure

Ʋ Encapsulated antenna system -1 … 3 bar (-100 … 300 kPa/-14.5 … 43.5 psi) Ʋ Plastic horn antenna -1 … 2 bar (-100 … 200 kPa/-14.5 … 29.0 psig) Ʋ VersionwithadapterflangefromDN100 PP or PP-GF 30

-1 … 1 bar (-100 … 100 kPa/-14.5 … 14.5 psig)

Process temperature (measured on the processfitting)

-40 … +80 °C (-40 … +176 °F)

Vibration resistance Ʋ Withadapterflange 2gat5…200HzaccordingtoEN60068-2-6(vibration

with resonance) Ʋ with mounting strap 1gat5…200HzaccordingtoEN60068-2-6(vibration

with resonance)Shock resistance 100 g, 6 ms according to EN 60068-2-27 (mechanical

shock)

Electromechanical data - version IP 66/IP 67 and IP 66/IP 68; 0.2 barCable gland M20 x 1.5 or ½ NPTWire cross-section (spring-loaded terminals)

Ʋ Massive wire, stranded wire 0.2…2.5mm²(AWG24…14) Ʋ Stranded wire with end sleeve 0.2…1.5mm²(AWG24…16)

Electromechanical data - version IP 66/IP 68 (1 bar)Options of the cable entry

Ʋ Cable gland with integrated connec-tion cable

M20 x 1.5 (cable: ø 5 … 9 mm)

Ʋ Cable entry ½ NPT Ʋ Blind plug M20x1.5;½NPT

Connection cable Ʋ Wire cross-section 0.5mm²(AWG20)

5) EIRP: Equivalent Isotropic Radiated Power.

Page 79: VEGAPULS 61

79

11 Supplement

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

Ʋ Wire resistance <0.036Ω/m Ʋ Tensile strength <1200N(270lbf) Ʋ Standard length 5 m (16.4 ft) Ʋ Max. length 180 m (590.6 ft) Ʋ Min. bending radius 25 mm (0.984 in) with 25 °C (77 °F) Ʋ Diameter approx. 8 mm (0.315 in) Ʋ Colour - Non-Ex version Black Ʋ Colour - Ex-version Blue

Display and adjustment moduleDisplay element Display with backlightMeasured value indication

Ʋ Number of digits 5 Ʋ Sizeofdigits W x H = 7 x 13 mm

Adjustment elements 4 keysProtection rating

Ʋ unassembled IP 20 Ʋ mounted in the housing without lid IP 40

Materials Ʋ Housing ABS Ʋ Inspection window Polyester foil

Interface to the external display and adjustment unitData transmission Digital(I²C-Bus)Connection cable Four-wire

Sensor version Configuration,connectioncable

Cable length Standard cable Special cable Screened

4 … 20 mA, 4 … 20 mA/HART 50 m ● – –

ProfibusPA,Founda-tion Fieldbus 25 m – ● ●

Integrated clockDate format Day.Month.YearTime format 12 h/24 hTimezoneExfactory CETRate deviation max. 10.5 min/year

Measurement electronics temeratureResolution 0.1 °C (1.8 °F)Accuracy ±1°C(1.8°F)Permissible temperature range -40 … +85 °C (-40 … +185 °F)

Page 80: VEGAPULS 61

80

11 Supplement

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

Voltage supplyOperating voltage UB

Ʋ Non-Ex instrument 9.6 … 35 V DC Ʋ Ex ia instrument 9.6 … 30 V DC Ʋ Ex-d-ia instrument 14 … 35 V DC Ʋ Ex-d-ia instrument with ship approval 15 … 35 V DC

Operating voltage UB - illuminated display and adjustment module Ʋ Non-Ex instrument 16 … 35 V DC Ʋ Ex ia instrument 16 … 30 V DC Ʋ Ex-d-ia instrument No lighting (integrated ia barrier)

Reverse voltage protection IntegratedPermissible residual ripple - Non-Ex, Ex-ia instrument

Ʋ for9.6V<UB<14V ≤0.7Veff(16…400Hz) Ʋ for18V<UB<36V ≤1.0Veff(16…400Hz)

Permissible residual ripple - Ex-d-ia instrument Ʋ for18V<UB<36V ≤1Veff(16…400Hz)

Load resistor Ʋ Calculation (UB - Umin)/0.022 A Ʋ Example - Non-Ex instrument with UB= 24 V DC

(24V-9.6V)/0.022A=655Ω

Electrical protective measuresProtection rating

Housing material Version IP-protection class NEMA protection

Plastic Single chamber IP 66/IP 67 NEMA4X

Double chamber IP 66/IP 67 NEMA4X

Aluminium Single chamber IP 66/IP 68 (0.2 bar)IP 68 (1 bar)

NEMA 6PNEMA 6P

Double chamber IP 66/IP 67IP 66/IP 68 (0.2 bar)IP 68 (1 bar)

NEMA4XNEMA 6PNEMA 6P

Stainless steel, electro-polished

Single chamber IP 66/IP 68 (0.2 bar) NEMA 6P

Stainless steel, precision casting

Single chamber IP 66/IP 68 (0.2 bar)IP 68 (1 bar)

NEMA 6PNEMA 6P

Double chamber IP 66/IP 67IP 66/IP 68 (0.2 bar)IP 68 (1 bar)

NEMA4XNEMA 6PNEMA 6P

Protection rating (IEC 61010-1) III

Page 81: VEGAPULS 61

81

11 Supplement

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

ApprovalsInstrumentswithapprovalscanhavedifferenttechnicalspecificationsdependingontheversion.For that reason the associated approval documents of these instruments have to be carefully noted. They come with the delivery or can be downloaded under www.vega.com, "VEGATools" and "Instrument search" as well as under www.vega.com/downloads and "Approvals".

Interface to the external display and adjustment unitData transmission Digital(I²C-Bus)Connection cable Four-wire

Sensor version Configuration,connectioncable

Cable length Standard cable Special cable Screened

4 … 20 mA, 4 … 20 mA/HART 50 m ● – –

ProfibusPA,Founda-tion Fieldbus 25 m – ● ●

11.2 DimensionsThe following dimensional drawings represent only an extract of all possible versions. Detailed dimensional drawings can be downloaded at www.vega.com/downloads under "Drawings".

Plastic housing~ 69 mm(2.72")

ø 79 mm(3.11")

112

mm

(4.4

1")

M20x1,5/½ NPT

~ 84 mm(3.31")

M16x1,5

112

mm

(4.4

1")

M20x1,5/½ NPT1 2

ø 79 mm(3.11")

Fig.58:HousingversionswithprotectionratingIP66/IP67-withintegrateddisplayandadjustmentmodulethehousingis9mm/0.35inhigher1 Single chamber version2 Double chamber version

Page 82: VEGAPULS 61

82

11 Supplement

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

Aluminium housing

21

ø 86 mm(3.39")

~ 116 mm(4.57")

116

mm

(4.5

7")

M20x1,5M20x1,5/½ NPT

~ 87 mm(3.43")

M16x1,5

ø 86 mm(3.39")

120

mm

(4.7

2")

M20x1,5/½ NPT

Fig.59:HousingversionswithprotectionratingIP66/IP68(0.2bar)-withintegrateddisplayandadjustmentmodulethehousingis9mm/0.35inhigher1 Single chamber version2 Double chamber version

Aluminium housing in protection rating IP 66/IP 68, 1 bar

120

mm

(4.7

2")

~ 105 mm(4.13")

116

mm

(4.5

7")

~ 150 mm(5.91")

ø 86 mm(3.39")

ø 86 mm(3.39")

M20x1,5/½ NPT

M16x1,5

2

M20x1,5M20x1,5

1

Fig.60:HousingversionwithprotectionratingIP66/IP68(1bar)-withintegrateddisplayandadjustmentmodulethehousingis9mm/0.35inhigher1 Single chamber version2 Double chamber version

Page 83: VEGAPULS 61

83

11 Supplement

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

Stainless steel housing~ 69 mm(2.72")

ø 79 mm(3.11")

117

mm

(4.6

1")

M20x1,5/½ NPT

~ 59 mm(2.32")

ø 80 mm(3.15")

112

mm

(4.4

1")

M20x1,5/½ NPT

~ 87 mm(3.43")

ø 86 mm(3.39")

120

mm

(4.7

2")

M20x1,5/½ NPT

M16x1,5

321

Fig.61:HousingversionswithprotectionratingIP66/IP68(0.2bar)-withintegrateddisplayandadjustmentmodulethehousingis9mm/0.35inhigher1 Single chamber version, electropolished2 Single chamber version, precision casting3 Double chamber version, precision casting

Stainless steel housing with protection rating IP 66/IP 68, 1 bar11

7 m

m(4

.61"

)

~ 103 mm(4.06") ø 79 mm

(3.11")

120

mm

(4.7

2")

~ 105 mm(4.13") ø 86 mm

(3.39")

M20x1,5

M20x1,5/½ NPT

M16x1,5

~ 93 mm(3.66") ø 80 mm

(3.15")

112

mm

(4.4

1")

M20x1,5/½ NPT

321

Fig.62:HousingversionwithprotectionratingIP66/IP68(1bar)-withintegrateddisplayandadjustmentmodulethehousingis9mm/0.35inhigher1 Single chamber version, electropolished2 Single chamber version, precision casting3 Double chamber version, precision casting

Page 84: VEGAPULS 61

84

11 Supplement

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

VEGAPULS 61, threaded version

SW 50 mm(1.97")

43 m

m(1

.69"

)20

mm

(0.7

9")

78 m

m (3

.07"

)

ø 39 mm (1.54")

G1½A / 1½ NPT

Fig.63:VEGAPULS61,threadedversionG1½and1½NPT

Page 85: VEGAPULS 61

85

11 Supplement

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

VEGAPULS61,hygienicfitting

1 2

3

1 2

3

SW 50 mm(1.97")

SW 50 mm(1.97")

SW 50 mm(1.97")

121

mm

(4.7

6")

121

mm

(4.7

6")

121

mm

(4.7

6")

ø 64 mm (2.52")ø 91 mm (3.58")

ø 78 mm (3.07")ø 95 mm (3.74")

ø 39 mm (1.54")

ø 68 mm (2.68")

ø 84 mm (3.31")

ø 39 mm (1.54")

Fig.64:VEGAPULS61,hygienicfitting1 Clamp2"(ø64mm)and3"(ø91mm)PN16DIN32676,ISO2852/316L2 Slotted nut according to DIN 11851 DN 50 and DN 803 TuchenhagenVariventDN32

Page 86: VEGAPULS 61

86

11 Supplement

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

VEGAPULS 61, version with mounting strap

125 mm(4.92")2,5 mm

(0.10")

75 mm(2.95")

107 mm(4.21")

115 mm(4.53")

300

mm

(11.

81")

19 m

m(0

.75"

)

98 m

m(3

.86"

)15

mm

(0.5

9")

8,5

mm

(0.3

4")

9 mm(0.35")

85 m

m(3

.35"

)

12 m

m(0

.47"

)9

mm

(0.3

5")

12 mm(0.47")

170

mm

(6.6

9")

Fig.65:VEGAPULS61,mountingstrapin170or300mmlength

Page 87: VEGAPULS 61

87

11 Supplement

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

VEGAPULS 61, version with mounting strap and clamps

9 mm(0.35")

85 m

m(3

.35"

)

12 m

m(0

.47"

)9

mm

(0.3

5") 12 mm

(0.47")

125 mm(4.92")2,5 mm

(0.10")

ø 75 mm(2.95")

ø 107 mm(4.21")

ø 115 mm(4.53")

300

mm

(11.

81")

19 m

m(0

.75"

)

117

mm

(4.6

1")

15 m

m(0

.59"

)

8,5

mm

(0.3

4")

170

mm

(6.6

9")

Fig.66:VEGAPULS61,mountingstrapin170or300mmlength

Page 88: VEGAPULS 61

88

11 Supplement

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

VEGAPULS61,versionwithmountingstrapandreflector

115,

5 m

m (4

.55"

)

218

mm

(8.5

8")

45°

71 m

m(2

.8")

17,5

mm

(0.6

9")

ø 9 mm(0.35")

107,5 mm(4.23")

117,5 mm(4.63")

110 mm(4.33")

160 mm(6.30")

60 mm(2.36")

Fig.67:VEGAPULS61,mountingstrapandreflector

Page 89: VEGAPULS 61

89

11 Supplement

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

VEGAPULS61,versionwithcompressionflange

126

mm

(4.9

6")

10,5

mm

(0.4

1")

19 m

m(0

.75"

)

ø 75 mm (2.95")

ø 115 mm (4.53")

ø 156 mm (6.14")

ø 200 mm (7.87")

ø 21 mm (0.83")

ø 107 mm (4.21")

Fig.68:VEGAPULS61,compressionflangesuitableforDN80PN16/ASME3"150lbs/JIS8010K

Page 90: VEGAPULS 61

90

11 Supplement

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

VEGAPULS61,versionwithcompressionflangeandrinsingconnection

126

mm

(4.9

6")

10,5

mm

(0.4

1")

15 m

m(0

.59"

)19 m

m(0

.75"

)

26,5

mm

(1.0

4")

ø 75 mm (2.95")

ø 156 mm (6.14")

ø 200 mm (7.87")

ø 21 mm (0.83")

ø 107 mm (4.21")

Fig.69:VEGAPULS61,compressionflangewithrinsingconnectionsuitableforDN80PN16/ASME3"150lbs/JIS8010K

Page 91: VEGAPULS 61

91

11 Supplement

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

VEGAPULS61,versionwithadapterflange

2

1

138

mm

(5.4

3")

31 m

m(1

.22"

)20

mm

(0.7

9")

8 m

m(0

.32"

)

ø 75 mm (2.95")

ø 98 mm (3.86")

Fig.70:VEGAPULS61,adapterflange1 Adapterflange2 Seal

Page 92: VEGAPULS 61

92

11 Supplement

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

VEGAPULS61,versionwithadapterflangeandrinsingconnection

3

21170

mm

(6.6

9")

62,5

mm

(2.4

6")

20 m

m(0

.79"

)

34,7

mm

(1.3

7")

ø 75 mm(2.95")

ø 98 mm(3.86")

Fig.71:VEGAPULS61,adapterflangeandairrinsing1 Rinsing connection2 Refluxvalve3 Adapterflange

Page 93: VEGAPULS 61

93

11 Supplement

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

11.3 Industrial property rightsVEGA product lines are global protected by industrial property rights. Further information see www.vega.com.Only in U.S.A.: Further information see patent label at the sensor housing.VEGA Produktfamilien sind weltweit geschützt durch gewerbliche Schutzrechte.Nähere Informationen unter www.vega.com.Les lignes de produits VEGA sont globalement protégées par des droits de propriété intellec-tuelle. Pour plus d'informations, on pourra se référer au site www.vega.com.VEGA lineas de productos están protegidas por los derechos en el campo de la propiedad indus-trial. Para mayor información revise la pagina web www.vega.com.Линии продукции фирмы ВЕГА защищаются по всему миру правами на интеллектуальную собственность. Дальнейшую информацию смотрите на сайте www.vega.com.VEGA系列产品在全球享有知识产权保护。进一步信息请参见网站<www.vega.com。

11.4 TrademarkAll the brands as well as trade and company names used are property of their lawful proprietor/originator.

Page 94: VEGAPULS 61

94

INDEX

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-150625

INDEX

AAdjustment 47, 48Agitators 20Application

– Bulk solid 44 – Liquid 40 – Standpipe 41

BBacklight 50

CCable entry 13Check output signal 68Connecting

– Electrically 29 – To the PC 59

Connection – Cable 28 – Steps 29 – Technology 29

Copy sensor settings 57Current output Min./Max. 49Current output mode 49Curve indication

– Echo curve 52 – False signal suppression 52

DDamping 48Date/Time 55Default values 55Deviation 68Device units 52

EEcho curve memory 63Echo curve of the setup 52EDD (Enhanced Device Description) 62Electronics and terminal compartment, single chamber housing 31Electronics temperature 51Error codes 66Event memory 63

FFalse signal suppression 53Faultrectification67Flow measurement 26, 27Foam generation 21

Functional principle 10

GGrounding 28

HHART

– Resistor 59HART mode 56

IIndication of the measured value 50Inflowingmedium17Installation position 16Instrument version 57

LLanguage 49Linearisation curve 54Lock adjustment 49

MMain menu 39Meas. reliability 51Measured value memory 63Measurement in a surge pipe 21Measurement in the bypass tube 24Measurement loop name 39

NNAMUR NE 107 65, 67

OOperation

– System 38OverfillprotectionaccordingtoWHG54

PPeak value indicator 50PIN 49, 54Polarisation 15

RRead out info 57Reflectionproperties40Repair 72Reset 55

SSensor orientation 20Sensor status 50

Page 95: VEGAPULS 61

95

INDEX

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

3649

9-EN

-150

625

Service hotline 71Shielding 28Simulation 51Socket 17, 19Status messages - NAMUR NE 107 64

TType label 8

VVessel form 46Vessel height 46Vessel installations 20

Page 96: VEGAPULS 61

Printing date:

VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany

3649

9-E

N-1

5062

5

All statements concerning scope of delivery, application, practical use and operat-ing conditions of the sensors and processing systems correspond to the information available at the time of printing.Subject to change without prior notice

© VEGA Grieshaber KG, Schiltach/Germany 2015

Phone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected]