vamp 220 / 220r - saesae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  ·...

68
VAMP 220 / 220R Arc protection system User manual

Upload: phamcong

Post on 29-Apr-2018

251 views

Category:

Documents


10 download

TRANSCRIPT

Page 1: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP 220 / 220R Arc protection system

User manual

Page 2: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP 220 / 220R Arc protection system User manual

VAMP Ltd

2 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004

Page 3: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP Ltd Arc protection system User manual

VAMP 220 / 220R

VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 3

Table of Content

Preface .........................................................................................5 1. Introduction ............................................................................6 2. System description.................................................................8

2.1. Master unit VAMP 220/220R...............................................8 2.1.1. General .........................................................................8 2.1.2. Functional description.................................................9

2.2. Slave unit VAM 12 CD...................................................... 11 2.3. Arc sensor VA 1 DA .......................................................... 12 2.4. Portable sensor VA 1 DP.................................................. 13 2.5. Trip multiplier relay VAR 4 CE .......................................... 14 2.6. Systems with multiple master units ................................. 15 2.7. Selective arc protection ................................................. 15

3. Technical data .....................................................................17 3.1. Master unit VAMP 220/220R............................................ 17 3.2. Slave unit VAM 12 CD...................................................... 19 3.3. Arc sensor VA 1 DA .......................................................... 20 3.4. Portable sensor VA 1 DP.................................................. 20 3.5. Trip multiplier relay VAR 4 CE .......................................... 20

4. Product handling..................................................................21 4.1. Receiving goods .............................................................. 21

4.1.1. Unpacking and transportation ............................... 21 4.1.2. Checking the consignment .................................... 21 4.1.3. Complaints................................................................. 21

4.2. Warranty ............................................................................ 21 5. System installation................................................................23

5.1. Safety notes....................................................................... 23 5.2. Preparing for installation ................................................. 23 5.3. Installing master unit VAMP 220/220R ........................... 24

5.3.1. Mounting master unit VAMP 220/220R .................. 24 5.3.2. Wiring the master unit, overview ............................ 24 5.3.3. Wiring secondary circuits of current transformers 25 5.3.4. Wiring trip circuits of circuit breakers ..................... 26 5.3.5. Wiring alarm circuits ................................................. 27 5.3.6. Protective earthing................................................... 27 5.3.7. Wiring auxiliary supply .............................................. 27

5.4. Installing slave units .......................................................... 29 5.4.1. Mounting slave unit VAM 12 CD............................. 29 5.4.2. Wiring between master and slave ......................... 29 5.4.3. Wiring separate power supply to VAM 12 CD...... 30

5.5. Installing sensors................................................................ 31 5.5.1. Mounting arc sensor VA 1 DA................................. 31 5.5.2. Connecting sensors to slave units .......................... 32 5.5.3. Connecting portable sensor ................................... 33 5.5.4. Arc sensor wiring over long distances ................... 33

5.6. Installing trip multiplier VAR 4 CE.................................... 33

Page 4: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP 220 / 220R Arc protection system User manual

VAMP Ltd

4 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004

5.7. Wiring multiple master systems....................................... 35 5.8. Wiring systems with selective arc protection ............... 36 5.9. Checking wirings .............................................................. 36

5.9.1. Visual inspection ....................................................... 36 5.9.2. Control by measuring............................................... 37

6. Commissioning.....................................................................38 6.1. Using master unit control panel ..................................... 38

6.1.1. General ...................................................................... 38 6.1.2. Control modes........................................................... 39 6.1.3. Fast guide of the function menu............................ 40 6.1.4. Push-button functions............................................... 41

6.2. Using slave unit panel ...................................................... 41 6.3. Setting addresses of slave units...................................... 42 6.4. System configuration ....................................................... 43 6.5. Setting overcurrent values .............................................. 45 6.6. Relay output settings ....................................................... 47 6.7. Testing the arc sensors..................................................... 54

7. Operational measures.........................................................55 7.1. Arc faults............................................................................ 55

7.1.1. Arc fault tripping alarm............................................ 55 7.1.2. Reading arc fault information ................................ 55

7.2. Supervision of phase currents......................................... 56 7.2.1. Overcurrent warning ................................................ 56 7.2.2. Reading current values............................................ 56

7.3. Handling self-supervision faults....................................... 57 7.3.1. Error indications ......................................................... 57 7.3.2. Reading and erasing error messages.................... 58 7.3.3. Fault codes ................................................................ 59 7.3.4. VAM 12 CD TEST/ERROR indication........................ 60

7.4. Checking system configuration ..................................... 61 8. Application examples .........................................................62

8.1. System with two master units.......................................... 62 9. Product information .............................................................63

9.1. Dimensional drawing....................................................... 63 9.2. Panel mounting ................................................................ 64 9.3. Semi-flush mounting......................................................... 64

Ordering code VAMP220/220R ................................................65 11. Reference information.........................................................67

Page 5: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP Ltd Arc protection system User manual

VAMP 220 / 220R

VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 5

Preface This user’s manual provides information for handling, mounting, wiring, commissioning and operating the VAMP 220 arc protection system. It also includes a system description, technical data and some application examples. The first chapter introduces the VAMP arc protection system and its modules. Chapter 2, SYSTEM DESCRIPTION, describes the system modules and their functions. Chapter 3 provides technical data in table format, and chapter 4 gives general product handling information for new owners. Chapter 5, SYSTEM INSTALLATION, gives instructions for mounting and wiring the VAMP 220 modules, while chapter 6, COMMISSIONING, describes how to do the address setting, system configuration and parameter setting necessary for making the system work in the desired way. In chapter 6 you will also find instructions for using the control panel of the master unit. Chapter 7, OPERATIONAL MEASURES, deals with measures that can be taken during operation. It shows how to handle alarm signals, how to read measured values, and how to interpret internal fault signals. In chapter 8 some application examples with illustrative pictures are given, and in chapter 9 ordering information and contact information. In this manual, we use the following styles of presentation to notify the reader of important, critical or risky factors and situations:

NOTE! Note text is used to stress and draw attention to facts and cir-cumstances that should be specially noted.

CAUTION! Caution text is used to draw attention to factors that may cause damage on the equipment.

WARNING! Warning text is used to draw attention to situations and circumstances that may cause personal injury. When a warning appears, follow the instructions in the text thoroughly.

Page 6: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP 220 / 220R Arc protection system User manual

VAMP Ltd

6 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004

1. Introduction VAMP 220 is a state-of-the-art arc protection system for electrical power distribution systems. By using VAMP 220 in switchgears considerable safety improvements are obtained in the form of minimized injury and damage in case of an arc fault. VAMP 220 uses modern microprocessor technology and provides numerous new features previously not found in similar devices. Key features of VAMP 220: a total operating time of 7 milliseconds exact location of the activating arc sensor self-supervision of the entire system system wiring using standard copper cables self configuration. In addition to the high-level requirements set for protective relays, VAMP 220 meets the most recent EMC-standards.

Figure 1-1 VAMP 220 arc protection system.

VAMP 220 is a modular system composed of a master unit, slave units, arc sensors, temperature sensors, and possible trip multiplying units and interface units. The master unit VAMP 220 includes all the main functions of the arc protection system, such as overcurrent, arc and temperature supervision. Up to 10 slave units can be connected to a master unit. The slave unit VAM 12 CD serve as a link between the sensors and the master unit. Each slave unit can be connected to ten fixed arc sensors, one temperature sensor and one portable arc sensor.

Page 7: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP Ltd Arc protection system User manual

VAMP 220 / 220R

VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 7

The arc sensor VA 1 DA is activated by strong light which it transforms to a current signal. The signal is tranferred via the slave to the master unit. The portable sensor VA 1 DP is an arc sensor that can be temporarily connected to a slave. Attached to persons it improves the personal safety during work in live switchgears. The master unit provides up to four trip output channels for tripping circuit-breakers. By connecting the trip multiplying relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard sensor cable length is 6m. Arc sensors can be con-nected over longer distances, up to 20 m, using a sensor with a shielded cable. Thanks to the modularity, the system can be flexibly adapted to a variety of arc protection applications, ranging from simple systems with one master unit and one slave unit to complex solutions comprising multiple master units, for instance, in applications with selective arc protection. VAMP220 suits both low voltage and medium voltage switchgears. It can be installed in new as well as existing switchgears.

Page 8: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP 220 / 220R Arc protection system User manual

VAMP Ltd

8 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004

2. System description

2.1. Master unit VAMP 220/220R

2.1.1. General The master unit, which can be mounted into the infeeder cubicle of the switchgear or in any other suitable space, includes all the main functions of the arc protection system. It comprises the following integrated subunits:

• a 3-phase overcurrent unit • an arc protection unit • a circuit-breaker failure protection unit • a temperature supervision unit • input and output elements • arc and overcurrent BI/O unit • a self-supervision un it.

VY

05

6A

VY03

6A

VAMP 220 R

S

E

TRIP 1

TRIP 3

TRIP 5

TRIP 2

TRIP 4

TRIP 6

POWER

ERROR

COM

INSTALL

CURRENT

RUN

TEMP

INFO

ERROR

TEMP SET

Latch

II

I

> 1A> 5A

Figure 2.1.1-1 Master unit VAMP 220/220R.

When the conditions for an arc short circuit occur (simultaneous overcurrent and arc signal), the master unit trips the circuit-breaker(s) of the incoming feeder(s). A master unit can trip up to four circuit breakers. If more than four parallel trip outputs are required, the trip multiplier relay VAR 4 CE can be used.

Page 9: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP Ltd Arc protection system User manual

VAMP 220 / 220R

VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 9

The tripping of the arc protection system can be backed up by employing the built-in circuit breaker failure protection subunit. This unit trips another breaker, for instance, the upstream circuit breaker, in case the main circuit breaker should fail to operate. Thus, it gives the system redundancy and increased security. The master unit includes a unidirectional arc input, a unidirectional current dependent arc output, and a bi-directional arc in/output. Furthermore, the master unit is equipped with a unidirectional overcurrent output and a bi-directional overcurrent in/output. With these properties a selective arc protection can be built even in complex distribution systems. Any voltage within the range 40 - 265 V ac or dc (or optionally 18 - 36 V dc) can be used as auxiliary supply voltage for the master unit. All internal supply voltages required by the system are derived from the auxiliary supply voltage of the master unit. NOTE! It is recommended that the auxiliary voltage is fed from a secured source, which is unaffected by a possible arc fault.

2.1.2. Functional description The current inputs of the three-phase overcurrent subunit (220) or two-phase overcurrent and E/F subunits (220R) are connected in series with any other possible protective devices of the switchgear. The start value of the overcurrent (220) / overcurrent + E/F (220R) subunits are set according to the preconditions determined by the arc short circuit and/or E/F current (220R) , independently of the settings of any other protection systems within the switchgear. The start value is set with a potentiometer knob on the control panel of the master unit (220). VAMP 220R has a separate E/F setting. The arc protection unit obtains its measuring signals from the slave units, to which the arc sensors of the system are connected. The unit starts when one or more of the system's arc sensors are activated. At a simultaneous activation of the overcurrent unit (220) / overcurrent or/and E/F unit (220R) and the arc protection unit, the arc protection system operates and the output elements trip the circuit-breakers.

NOTE! No operation takes place if only one unit (either the overcurrent or arc protection unit) is activated.

Page 10: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP 220 / 220R Arc protection system User manual

VAMP Ltd

10 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004

NOTE! The arc, overcurrent and E/F (220R) stages can also be activated from external BI/O signals. The circuit breaker failure protection subunit (CBFP) starts if the preconditions for the operation of the arc protection unit have not disappeared when a set operate time (80, 100 or 150 ms) has elapsed since the arc fault trip. The CBFP, which is optional, trips its own circuit breaker. When not used, its trip contacts are left unwired. If not used for circuit breaker failure protection, the CBFP output contact (TRIP3) can be set to operate in parallel with the actual trip circuit (TRIP1), if two circuit breakers are to be tripped simultaneously. The desired function for the third trip circuit (TRIP3) is to be specified when ordering the master unit. By default, TRIP3 is programmed for CBFP function with a time delay of 80 ms. Figure 2.1.2-1 shows the TRIP signalling block diagram of VAMP 220.

Page 11: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP Ltd Arc protection system User manual

VAMP 220 / 220R

VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 11

L> I> L>

I>

L>

L>

I>

I> L>

TR1

TR1

TR1

L>

I>

VAMP 220 R Trip Signalling Block Diagram

SW2

SW5

BIO option PCB

Power/Trafo/Trip PCB from ARC sensorfrom Slave

3 x

t

La>

80ms100ms150ms

Lb>

Ia>

&

Ib>

I> L>

Temp Alarm

L>

I>LOC

LOC

La>

Lc> L4>

TR4

TR4

I>

T5T6

T6

T5

T5T6

TR2

I>LOC

L>LOC

TRIP 2

TRIP 3

TempAl/TRIP4

TRIP 1

>1

L>

I>

>1

>1

T1T2T3

L

SW3

T3

LL

SW2

T2

L

SW1

T1

>1

SW7

SW8

int.sw.

&

&

&

+48V (BIO)+5V (GND)

TRIP 6

TRIP 5

1

1

TR loc

TR loc

I>

L>

L

L

L> >1

1

2

3

4

5

6

7

8

9

10

11,12,13

14

1516

1718

L4>

0ms

>1

SW6

int.sw.

SW4

L

Figure 2.1.2-1 Trip signalling block diagram of VAMP 220.

2.2. Slave unit VAM 12 CD The slave units, which can be mounted into suitable places in the switchgear compartments, serve as links between the sensors and the master unit. Each slave unit can be connected to ten arc sensors and one portable arc sensor. Up to 10 slave units can be connected to one master unit. The master unit and the slave units are interconnected by means of modular cables. The slave units contain, for instance, the self-supervision of the connected arc sensors.

Page 12: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP 220 / 220R Arc protection system User manual

VAMP Ltd

12 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004

VAM 12 CD POWER

COM

TEST/ERROR

SENSOR ADDR. COM1 COM2 VY0

05A

ARC SENSORS 1 ... 10 24 V

1 2 3 4 5 6 7 8 9 10

Made in FinlandTEMP

SSI

+ +

Figure 2.2-1 Slave unit VAM 12 CD.

When the system operates due to an arc fault, information of the sensor that caused the operation is forwarded by the slave unit to the master unit. The slave number and sensor number is then displayed by the master unit. The slave unit supervises all its sensors continuously. In an internal fault situation the fault information is transferred to the master unit and the fault can be viewed on the display of the master unit. A fault alarm is also given if an arc sensor connected to the slave unit remains in active state for more than 7 s. This can happen, for instance, if the arc sensor is exposed to direct sun light. At the same time the corresponding slave unit is disconnected from the master unit in order to prevent false circuit-breaker trippings. When the interference light disappears, the function of the slave unit is restored.

2.3. Arc sensor VA 1 DA The arc sensor is a light sensitive element, which is activated by strong light. Arc sensors should be mounted in the switchgear cubicles in such a way that they cover the space to be protected as completely as possible.

Page 13: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP Ltd Arc protection system User manual

VAMP 220 / 220R

VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 13

Figure 2.3-1 Arc sensor VA 1 DA.

A sudden increase of the light intensity is interpreted as an arc fault. The electronic circuits of the sensor transforms the light message into a current message and transmits it to the slave unit, which forwards it to the master unit. The sensitivity of the sensor is nearly equal over the front side. At the rear side the sensitivity decreases remarkably. See Figure 2.3-2. In a switchgear, however, the light caused by an arc is reflected from the walls. Therefore, the mounting position of the sensor is not critical. The standard sensor cable length is 6 m. As an option, a shielded cable can be used for distances up to 20 m.

40 30 20 10 0

50

60

70

80

90

100

120

130

140

100%

80

60

40

20

Figure 2.3-2 The sensitivity of the arc sensor to light from different directions.

2.4. Portable sensor VA 1 DP This module is a portable sensor element which can be temporarily connected to the slave units. It is used to improve personal safety during work, for instance during maintenance work, in a live switchgear. The sensor should be located close to the place where work is done. It can, for instance, be attached to the breast pocket of the service man's shirt or boiler suit. The function of the portable arc sensor equals that of the fix-mounted arc sensors. The difference is that the portable arc sensor can be moved around within the reach of the connection cable.

Page 14: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP 220 / 220R Arc protection system User manual

VAMP Ltd

14 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004

Figure 2.4-1 Portable sensor VA 1 DP in use.

The connector of the portable arc sensor can be plugged into the SENSOR connector of any slave unit of the arc protection system. The portable sensor should be attached in such a way that the sight is clear towards the working place.

NOTE! To avoid false activations, the portable arc sensor must be dis-connected from the slave unit immediately after use.

2.5. Trip multiplier relay VAR 4 CE With the VAR 4 CE multiplying relay the TRIP signals can be multiplied. Each multiplying relay has four ultra fast trip outputs, each of which can trip its own circuit breaker. Any combination of NO and NC contacts is available (to be specified in the order, see Figure 5.6-1 and table 9.3-1).

Figure 2.5-1 Trip multiplier relay VAR 4 CE.

Page 15: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP Ltd Arc protection system User manual

VAMP 220 / 220R

VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 15

Up to four trip functions are available by connecting TRIP1 and/or TRIP2 output to the control inputs of the trip multiplier relay. Auxiliary supply voltage is available from the 24 V OUT terminals of the master unit.

2.6. Systems with multiple master units Especially in medium-voltage switchgears the power may be fed from two or more infeeders. At an arc fault situation, each infeeder that can supply short circuit power must be tripped. In these applications, the arc protection system may include several master units, that is, one master unit per infeeder. In applications with multiple master units, the master units are interconnected via the BI/O connectors. When an arc sensor in the system is activated, information is transferred over the BI/O lines to all master units in the system. As a consequense, all master units with the overcurrent subunit activated will trip their respective circuit breakers. If a master unit connected to the BI/O lines is tripping, and the arc or overcurrent activation comes from a BI/O connection, the identifier of the activated BI/O line will be shown on the display.

2.7. Selective arc protection The master unit facilitates a selective arc protection even in more complex electricity distribution systems. As mentioned earlier, it includes the following input/output modules:

• unidirectional arc input • unidirectional arc output (current dependent) • bidirectional arc in/output • unidirectional overcurrent output • bidirectional overcurrent in/output.

By utilizing these features, complex busbar systems can be divided into separate zones. Each zone includes the parts of the distribution system that are limited by two or more circuit-breakers. See the example in Figure 2.7-1. Selective arc protection means that all zones are protected independently of each other. In the example in Figure 2.7-1, VAMP 220 master units are used for tripping the circuit-breakers K4, K5, K6 and K7 as well as the actual infeeding circuit-breakers K1, K2 and K3.

Page 16: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP 220 / 220R Arc protection system User manual

VAMP Ltd

16 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004

Suppose that an arc fault occurs in switchgear B in Figure 2.7-1, in a situation where circuit-breaker K3 is closed and the other two infeeding circuit-breakers are open. The arc fault power is fed via K3 to switchgear C and further to switchgear B by bus ducts E, A and D. The master unit of the bus duct D (which trips the circuit-breaker K6) obtains the unidirectional arc information from the B I/ O bus of the master unit in switchgear B. In other words, when an arc occurs in switchgear B, the arc information is forwarded to all master units that limits that particular zone, independently on their physical location. In the described infeeding arrangements the pre-conditions for an arc fault (arc signal and overcurrent) are fulfilled only in the master unit tripping the circuit-breaker K6. Therefore, K6 is the only circuit breaker that is tripped. In this example, the overcurrent BI/O lines are not used.

Figure 2.7-1 Selective arc protection using VAMP 220 master unit (example).

Page 17: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP Ltd Arc protection system User manual

VAMP 220 / 220R

VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 17

3. Technical data

3.1. Master unit VAMP 220/220R Power supply Us 40…265V ac/dc

(option): 18…36V dc) Rated current In Rated frequency fn

1A / 5A 45…65Hz

Power consumption ≤ 0.3VA

Three phase overcurrent stages (220) Two phase overcurrent and E/F stage (220R)

Thermal withstand capability - continuous - for 1s

4 x In 100 x In

IL> Inaccuracy

0.9…6.0 x In ± 10%

Io> Inaccuracy

0.01…0.1 x In

± 10% or 5mA Reset ratio 0.95

Operating settings, phase overcurrent stage

t> t> CBFP

7ms 7, 80, 100, 150ms

TRIP contacts Normally open 4 pcs (standard) + 2 pcs (option)

Rated voltage ≤ 250V ac/dc Continuous carry 5A Make and carry for 0.5s 30A Make and carry for 3s 15A Breaking capacity DC, when time constant L/R=40ms

50W

Contact material AgCdO2

Tripping contacts

Operating time - TRIP1, 2, 3, 4, 5, 6 - CBFP (TRIP3)

7ms 7, 80, 100, 150ms

SF (error) alarm Change-over contact Trip alarm Normally open Rated voltage ≤ 250V ac/dc Continuous carry 5A Make and carry for 0.5s 10A Make and carry for 3s 8A Breaking capacity DC, when time constant L/R=40ms for - 48 Vdc - 110 Vdc - 220Vdc

1A 0.25A 0.05A

Signal / alarm contacts

Contact material AgCdO2

Page 18: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP 220 / 220R Arc protection system User manual

VAMP Ltd

18 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004

Rated voltage Rated current

+48Vdc 20mA

L> BIO line (IN/OUT) L> UIO line (dependent OUT) L> UIO line (IN)

1 pcs (La>) 1 pcs (Lb>) 1 pcs (Lc>)

I> UIO line (OUT) I> BIO line (IN/OUT)

1 pcs (Ia>) 1 pcs (Ib>)

BIO inputs / Outputs

Optional: L> UIO (IN) L> UIO (OUT) I> UIO (IN) I> UIO (OUT)

5 pcs 2 pcs 3 pcs 1 pcs

Slave units 10 pcs / 100 sensors ARC inputs BIO Input/Output channels ARC information (+48Vdc) 3

channels + 7 channels (option) Slave port Transfer protocol Electrical connection Transfer rate

Multi drop (to slave units) I2C RS485 (15kV) 20 kbit/s

Communication

Programming port baud rate 9600 b/s EMC tests CE approved and tested

according to EN 20081-2, EN 50082-2

Voltage tests Insulation test voltage acc. to IEC 255-5 Impulse test voltage acc. to IEC 255-5

2kV, 50Hz, 1min 5kV, 1.2/50 µs, 0.5J

Emission tests Radiated and conducted emission according to EN55011 class A

High-frequency (1MHz) disturbance test according to IEC 255-22-1, class III - common mode - differential mode

2.5kV 1.0kV

Fast transient according to IEC 255-22-4, class III and IEC 801-4, level 4 - power supply input - other inputs

4kV, 5/50ns 2kV, 5/50ns

Immunity tests

Electronic discharge test acc. to IEC 255-22-2 and IEC 801-2, class III - air discharge - contact discharge

8kV 6kV

Page 19: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP Ltd Arc protection system User manual

VAMP 220 / 220R

VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 19

RF electromagnetic field test acc. to IEC 1000-4-3 and ENV 50140 f = 90…1000MHz

10V / m

Conducted RF disturbance test acc. to ENV 50141 and IEC 1000-4-6 f = 150kHz…80MHz

10V / m

Vibration test 2…13.2Hz, ± 1.0mm 13.2…100Hz, ±0.7g

Mechanical tests

Shock/bimp test acc. to IEC 255-21-2

20g, 1000 bumps/dir.

Specified ambient temperature range

0…+55 °C Environmental conditions

Transport and storage temperature range

-40…+70 °C

Protection by enclosure IP20 Weight About 4 kg Dimensions (HxWxD) 155 x 208 x 223 mm

Housing

Panel cut-out (H x W) 139 x 193 mm

3.2. Slave unit VAM 12 CD Power supply Voltage from the master unit

(via modular cable VX010 or separate cable)

24 Vdc

Sensor connections Number, total: - arc sensors - portable sensors

11 10 1

Indications LEDs: - green - yellow - red

Power Communication Test/Error

Transfer protocol I2C Electrical connection RS485

Serial bus

Transfer rate 20 kbit/s Operating temperature -10…+55 °C Storage temperature -40…+70 °C Relative humidity < 95%, 40 °C, 56 days Vibration IEC 60721-3-3

Environmental conditions

Shock IEC 60068-2-27 Protection by enclosure IP21 Weight About 0.4 kg

Housing

Dimensions (H x W x D) 90 x 140 x 60 mm

Page 20: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP 220 / 220R Arc protection system User manual

VAMP Ltd

20 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004

3.3. Arc sensor VA 1 DA Voltage from slave unit 12 Vdc Supply voltage Power consumption ≤ 2.5 mA Operating temperature -10…+55 °C Storing temperature -40…+70 °C Relative humidity < 95%, 40 °C, 56 days Vibration IEC 60721-3-3

Environmental conditions

Shock IEC 60068-2-27 Protection by enclosure IP21 Enclosure Weight About 0.01 kg

Connection cable Between master – slave - VX010 Between slave – slave - VX001

6 m (standard cable) 20m (shielded cable) 6 m (standard cable) 20m (shielded cable)

3.4. Portable sensor VA 1 DP See table in section 3.3.

3.5. Trip multiplier relay VAR 4 CE Power supply Voltage from the master unit

(via separate cable) 24 Vdc

Inputs TRIP signals from the master unit

1 NO contact

Number 4 NO contacts Rated voltage ≤ 250V ac/dc Rated current 5A Make and carry for 0.3s ≤ 30A

TRIP signals

Breaking capacity DC, when time constant L/R=40ms for - 48 Vdc - 110 Vdc - 220 Vdc

5A 3A 1A

Operation temperature -10…+55 °C Protection by enclosure IP21

Environmental conditions

Dimensions (H x W x D) 90 x 140 x 60 mm

Page 21: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP Ltd Arc protection system User manual

VAMP 220 / 220R

VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 21

4. Product handling

4.1. Receiving goods

4.1.1. Unpacking and transportation The packings can be stored and reused when needed. The packing itself is not a suitable transport envelope, but the unit must be further packed according to the requirements set by the means of transport to be used. The packing material is recyclable and can be disposed of or recycled according to separate recycling instructions.

4.1.2. Checking the consignment Check the delivered goods immediately after delivery: Check the device visually for possible external damage or loose parts inside it. Check that the device complies with the order:

• unit type and serial number • other possible order-related structural matters.

4.1.3. Complaints Possible complaints of manufacturing faults should be directed in writing to the unit manufacturer or the authorized dealer from which the product was acquired. Complaints of transport damages must be sent to the accountable transport or insurance company.

4.2. Warranty The guarantee period of VAMP 220 is 12 months from the date of commissioning, yet not more than 18 months from the date of delivery, provided that the unit has been stored in an unopened package before mounting. The guarantee covers verifiable manufacturing defects. The warranty does not cover damages caused by:

• transportation • mounting • commissioning

Page 22: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP 220 / 220R Arc protection system User manual

VAMP Ltd

22 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004

• misuse • abnormal environmental conditions • electrical quantities in excess of the rated values.

Further, the guarantee does not cover any consequential damage caused by fault situations.

Page 23: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP Ltd Arc protection system User manual

VAMP 220 / 220R

VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 23

5. System installation WARNING! Read through the handling instructions of this manual carefully before undertaking any mounting or wiring work.

5.1. Safety notes National electrical safety regulations must be obeyed when work is carried out under live conditions. The unit manufacturer takes no responsibility for accidents caused by incorrect working or protection practice. The correct handling of the unit under all mounting and operating conditions forms the foundation for a safe use of the product.

WARNING! All separately marked notes and warnings must be observed. The wiring work must be performed according to national standards and possible requirements set by the customer.

CAUTION! Do not connect the auxiliary supply voltage as long as installa-tion work is going on.

5.2. Preparing for installation Before installing the system, make sure that the environmental requirements are fulfilled. See the environmental conditions specified in the TECHNICAL DATA chapter.

CAUTION! The product contains components, which are liable to damage by electrostatic discharge (ESD). The unit must not be opened, unless necessary protective measures against ESD have been taken.

WARNING! Operational safety cannot be guaranteed in environments that do not fulfill the specified environmental conditions.

Page 24: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP 220 / 220R Arc protection system User manual

VAMP Ltd

24 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004

5.3. Installing master unit VAMP 220/220R

5.3.1. Mounting master unit VAMP 220/220R The master unit is designed for door mounting. It can be delivered with optional spacing adapters if the installation depth is critical.

Figure 5.3.1-1 Mounting the master unit.

5.3.2. Wiring the master unit, overview The master unit requires the following wirings:

• secondary circuits of the current transformers of the switchgear

• trip circuits of the circuit-breakers • alarm circuits • auxiliary supply circuits • protective earthing • connections to slave units (data communication and

possibly separate auxiliary supply) • connections to other master units (if the system

comprises several communicating master units). The five first mentioned connections are described in the next sub-sections. The connections to slave units and other master units will be described in sections 5.4 and 5.7 respectively. See the example in Figure 5.3.2-1, and the block diagram in Figure 5.3.7-1.

Page 25: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP Ltd Arc protection system User manual

VAMP 220 / 220R

VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 25

UsCTs

TRIP1

To slave

Trip alarmSF Alarm

Figure 5.3.2-1 Connections of the master unit (example).

5.3.3. Wiring secondary circuits of current transformers Connect the secondary circuits of the current transformers to the following screw terminals at the rear of the master unit (see Figure 5.3.3-1 ): X1-1, X1-2 (L1) X1-3, X1-4 (L2) (E/F (220R)) X1-5, X1-6 (L3) (see Figure 5.3.7-2 for E/F schemes using VAMP 220R) The arc protection system can also be two-phase or single-phase connected. But for obtaining optimal operating speed, a three-phase connection is recommended.

NOTE! The specified 7 ms operating time can be guaranteed only if three-phase current measurement or two-phase current + E/F (220R) is used.

Page 26: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP 220 / 220R Arc protection system User manual

VAMP Ltd

26 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004

X2X3

X2 is optional

X1

Current Transformer, Trip / Alarm PCB Power , Slave transceiver and BIO PCB

X1-1, X1-2 IL1 X3-1, X3-2 Us (24 Vdc; 1:+, 2:-)

X1-3, X1-4 IL2 / Io X3-3

X1-5, X1-6 IL3 X3-4

X1-7, X1-8 TRIP1 X3-5, X3-6 +24, GND to Slave

X1-9, X1-10 TRIP2 X3-7, X3-8, X3-9, X3-10 COM

X1-11, X1-12 TRIP3 X3-11

X1-13, X1-14 TEMP / TRIP4 X3-12 La> in/out

X1-15, X1-16 TRIP ALARM X3-13 Lb> (I< dependent) out

X1-17, X1-18, X1-19 SF (17-18 NO; 18-19 NC) X3-14 Lc> in

X1-20 X3-15 Ia> out

X3-16 Ib> in/out

X3-17, X3-18 BI/O GND

OPTION PCB Communication to Slave unit VAM 12 CD

X2-1 L> in TR2 X6 VX010

X2-2 I> in

X2-3 L> in TR6

X2-4 L> in

X2-5 I> in

X2-6 L> in TR5

X2-7 L> in

X2-8 I> in

X2-9 L> out

X2-10 I> out

X2-11, X2-12, X2-13 GND

X2-14

X2-15, X2-16 TRIP5

X2-17, X2-18 TRIP6

Us

Pe

+24VGND

COM

Sla

ve

BIO

Co

nne

ctio

ns

BIO

Co

nne

ctio

ns

TRIP5

TRIP6

IL1

IL2/Io

IL3

TRIP1

TRIP2

TRIP3

TRIP4

TR AL

SF

X6

Figure 5.3.3-1 Terminal blocks of the master unit.

5.3.4. Wiring trip circuits of circuit breakers Connect the circuit-breaker trip circuits to the following terminals (max. four separate trip outputs): TRIP1: X1-7, X1-8 TRIP2: X1-9, X1-10 TRIP3: X1-11, X1-12 TRIP4: X1-13, X1-14 The output contact will close within 7 ms at an arc fault, provided that three-phase current measurement is used. If TRIP RELAY 3 is programmed for circuit-breaker failure protection (CBFP) (see section ), the trip signal is obtained after a set operate time of 80, 100 or 150 ms from the main trip signal in case the preconditions of an arc fault still exist.

NOTE! The function of the TRIP3 circuit must be specified when order-ing.

Page 27: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP Ltd Arc protection system User manual

VAMP 220 / 220R

VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 27

If more than 4 parallel trip circuits are required, the separate trip multiplier relay VAR 4 CE can be used. See section 5.6.

5.3.5. Wiring alarm circuits The alarm signals generated by the arc protection system (trip alarm, self-supervison alarm) can be forwarded to higher level switchgear supervison and control systems through the alarm output contacts.

Self-supervision alarms A self-supervision alarm is issued when the self supervision system detects a fault in the internal functions of the master unit or in the number of connected sensors. Connect the self-supervision alarm output to an SF change-over contact, either terminals X1-17, X1-18 (normally open) or X1-18, X1-19 (normally closed). See Figure 5.3.3-1. Under no-internal fault (healthy) conditions with auxiliary supply connected, the contact X1-17, X1-18 will be open and X1-18, X1-19 closed.

Trip alarms Trip alarms are generated when the arc fault system trips. Connect the trip alarm output to the NO terminals X1-15, X1-16.

5.3.6. Protective earthing Connect the arc protection system to the earth from the PE terminal marked on the back plate.

5.3.7. Wiring auxiliary supply Connect the auxiliary supply voltage to the Us-input, terminals X3-1, X3-2. Option 24 Vdc, polarity of wiring: X3-1: + and X3-2: -. NOTE! If possible, the auxiliary supply should be taken from a power source that is not interrupted when the arc protection system operates. CAUTION! Keep the auxiliary supply disconnected as long as mounting or wiring work is going on.

Page 28: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP 220 / 220R Arc protection system User manual

VAMP Ltd

28 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004

TRIP1

TRIP2

Alarm (L>) 1

3

5

L1

L2

L3

u

X3-16 Ib>

X3-17 BIO GND

X3-1X3-2

Alarm(SF)

PE3

X1-17X1-19

X1-15X1-16

+_ X3-5

X3-6

L>

L>

2

4

6

Auxiliary supply

COM 1Serial communicationand auxiliary supply to the slave unit

COM 2Serial communicationand auxiliary supplyto the slave unit

Self-supervisionalarm

Trip signal (5ms) / Temperature alarm

24V outputsto the slave units

Trip signal (5ms)

X5

X3-5...10

X1

X1

X1

TRIP3

TRIP4

X1-7X1-8

X1-9X1-10

X1-11X1-12

X1-13X1-14

Trip signal (5ms)

Trip signal (5ms) / CBFP

X1-18Trip Alarm

OC stageX3-15 Ia>

X3-14 Lc>

X3-12 La> ARC stage

X3-13

BIO GNDX3-18

Lb> (dependent on I>)

Figure 5.3.7-1 Block diagram of master unit VAMP 220.

Earth Fault protection with VAMP220R

VAMP 220RL1

L2/Io

L3P2

P1

100/1 to 2000/1CTs

- Phase setting 1.3 x In- E/F setting 5% of primary ratio

=> if CT ratio 2000/1 primary setting = 100A=> setting = 0.33 x In

L1

L2

L3

300/1Maximum earth faultcurrent 300...650 AEarth Compensator

Figure 5.3.7-2 Scheme for VAMP220R with E/F measurement

Page 29: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP Ltd Arc protection system User manual

VAMP 220 / 220R

VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 29

5.4. Installing slave units

5.4.1. Mounting slave unit VAM 12 CD Fix the slave unit on the 35 mm DIN rail in the switchgear cubicle in such a way that the indicators of the front panel are visible. The slave units should be placed in such a way that the sensor wiring can be made as easily as possible.

140 60

VAM 12 CD

1 2 3 4 5 6 7 8 9 10

90

ERROR/TEST

COMPOWER

+ +

35 mm DIN rail

Figure 5.4.1-1 Dimensions and mounting of the slave unit VAM 12 CD.

5.4.2. Wiring between master and slave The master unit and the slave units are connected together with a modular cable type VX 010. The modular cable carries all information between the master and the slave units, i.e. data in serial form and arc fault messages, as well as the auxiliary supply of the slave units. Connect the VX 010 cable to the X5 outlet (COM2) or the connector X3-5...10 (COM1) of the master unit. Both COM ports can be used simultaneously. CAUTION! If the connector X3-5...10 is used, pay special attention to the wiring of the signals. Faulty wiring may damage the communi-cation between the master and the slaves. Connect the cable to COM1 or COM2 on the first slave unit. Route the cable from the free connector of the first slave unit (COM2 or COM1) to the COM1 (or COM2) connector of the next slave unit, and so forth. See Figure 5.4.2-1.

Page 30: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP 220 / 220R Arc protection system User manual

VAMP Ltd

30 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004

All the COM1 and COM2 connectors are mutually identical, i.e., the modular cable can always be connected to one or another. The maximum total length of the modular cable, when taking into account all slave units connected to the master unit, is 100 m.

VAM VAM

SLAVE UNIT 1 SLAVE UNIT 2

MODULAR CABLE

VX010

VX001 VX001

Figure 5.4.2-1 Wiring between the master unit and the slave unit, using modular cable.

5.4.3. Wiring separate power supply to VAM 12 CD When routing modular cables over very long distances, or when the system contains more than five slave units, it is recommended that a separate auxiliary voltage cable is used in parallel with the modular cable. Connect the auxiliary voltage cable to the 24 V terminals X3-5, X3-6 in the master unit and the 24V inputs in the slave units. See Figure 5.3.3-1 and Figure 5.4.3-1 .

NOTE! Pay special attention to the polarity of the connections.

Page 31: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP Ltd Arc protection system User manual

VAMP 220 / 220R

VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 31

VAM 12 CD

1

2

10

.

.

.

TEMP

SSI

Serial link

240V240V

COM 1 Serial communication1 to the master unit

COM 2 Serial communication2 to the master unit

Temperature sensorinput

Arc sensor10 inputs

24V inputs fromthe master unit

Portable sensorinput

Figure 5.4.3-1 Connections of the slave unit VAM 12 CD.

5.5. Installing sensors

5.5.1. Mounting arc sensor VA 1 DA Mount the sensors in the switchgear cubicles in such a way that the detecting surface covers the space to be supervised as completely as possible. The sight must be free between the sensor and the supervised area. In open spaces (e.g. bus bar sections) there should be an arc sensor approximately every 5 meters. Due to the wide detection range of the sensors and the light reflection inside the switchgear, the mounting position is not very critical. The arc sensor can be mounted from the outside on a partition wall of the switchgear. Fit the active part of the sensor into a 10 mm hole in the wall and fasten the sensor with one 4 mm screw, see Figure 5.5.1-2. The arc sensor can also be surface mounted on a wall using the optional mounting plates VYX 01 or VYX 02.

NOTE! The arc sensor must not be exposed to direct sun light or any other strong light. Do not mount the arc sensor directly under a light source.

Page 32: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP 220 / 220R Arc protection system User manual

VAMP Ltd

32 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004

25

14

22

4

10

Figure 5.5.1-1 Dimensions of the arc sensor VA 1 DA.

10mm

Fastening screw 4 x 15

Active part of the sensor

Anchoring

Sensor cable

Figure 5.5.1-2 Mounting of the arc sensor.

5.5.2. Connecting sensors to slave units The sensors are delivered with 6 m long standard cables or 20 m long shielded cables (to be specified in the order). After mounting the sensors, connect them to slave units as follows: Draw the wire through the shortest possible path to the nearest slave unit and cut cables to a suitable length. Connect arc sensors to the screw connectors ARC SENSORS 1 - 10. Connect temperature sensors (max. one per slave) to the screw connectors TEMP. The polarity of the arc sensor cables is free. See Figure 5.5.2-1.

Page 33: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP Ltd Arc protection system User manual

VAMP 220 / 220R

VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 33

VAM 12 CDPOWER

COM

TEST/ERROR

SENSOR ADDR. COM1 COM2 VY0

05

A

ARC SENSORS 1 ... 10 24 V

1 2 3 4 5 6 7 8 9 10

Made in Finland

T

E

M

P

S

S

I+ +

Arcsensor 1

Arcsensor 1

Arcsensor 2

SLAVE UNIT 1 SLAVE UNIT 2

MODULAR CABLE

VAM 12 CDPOWER

COM

TEST/ERROR

SENSOR ADDR. COM1 COM2 VY0

05

A

ARC SENSORS 1 ... 10 24 V

1 2 3 4 5 6 7 8 9 10

Made in Finland

T

E

M

P

S

S

I+ +

Arcsensor 2

Figure 5.5.2-1 The connection between the sensors and the slave units.

5.5.3. Connecting portable sensor The portable arc sensor can be connected to any slave unit in the system. When connected the portable sensor functions as a part of the arc protection system. Connect the portable arc sensor to the SENSOR plug-in type modular connector of the slave. Attach the sensor to personnel in such a way that the sight against the working object is free all the time. NOTE! Disconnect the portable arc sensor from the slave unit immedi-ately after use. If the sensor is left connected, it may cause false activations.

5.5.4. Arc sensor wiring over long distances If the standard cable of the arc sensor (6 m) is too short, a shielded arc sensor cable can be used for distances up to 20 m (arc sensor VA 1 DA -20S).

5.6. Installing trip multiplier VAR 4 CE If more than four trip outputs are needed at a time, the trip multiplier relay VAR 4 CE can be used. Attach the trip multiplier relay to a DIN rail close to the place where the master unit is mounted.

Page 34: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP 220 / 220R Arc protection system User manual

VAMP Ltd

34 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004

Connect supply voltage from the terminals X3-5 (+) and X3-6 (GND) of the master unit to the terminals 1 (+) and 3 (GND) or 2 (+) and 4 (GND) in the trip multiplier relay. Note the polarity of the wires. Connect the required trip output to the terminals 5, 7 or 6, 8 in the trip multiplier relay. Connect the necessary trip controls to the terminals TRIP1 - TRIP4 in the trip multiplier relay, see Figure 5.6-2.

140 60

90

35 mm DIN rail

VAR 4 CE

VAR 4 CE 4/0 NO NO NO NO

VAR 4 CE 2/2 NO NO NC NC

VAR 4 CE 3/1 NO NO NO NC

VAR 4 CE 1/3 NO NC NC NC

VAR 4 CE 0/4 NC NC NC NC

TRIP1 TRIP2 TRIP3 TRIP4

Figure 5.6-1 Trip multiplier relay VAR 4 CE.

TRIP1

TRIP

GND

+24V

TRIP4

TRIP3

TRIP2

11,12

13,14

17,18

19,20

23,24

25,26

29,30

31,32

POWER1,2

3,4

5,6

7,8

VAR 4CE

Figure 5.6-2 The connections of VAR 4 CE.

Page 35: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP Ltd Arc protection system User manual

VAMP 220 / 220R

VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 35

5.7. Wiring multiple master systems In applications comprising several master units, the master units can be interconnected for transfer of arc and overcurrent information via the BI/O (binary input/output) ports. The following BI/O ports are available as standard delivery (see also Figure 2.1.2-1): La> X3: 12 Arc input / output Lb> X3: 13 Arc output. Conditional. No activation if Ib> input

activated at the same time. Lc> X3: 14 Arc input. Controls TRIP RELAY 4 provided that

front dip switch 7 is ON and dip switch 8 is OFF. See section 6.7.

Ia> X3: 15 Overcurrent output Ib> X3: 16 Overcurrent input / output GND X3: 17

X3: 18 Ground for all BI/O signals

Table 5.7-1 BI/O ports.

To obtain transfer of arc information between two master units: • Connect the systems through the BI/O terminals X3-

12, 13 or 14 (+). • Connect the terminals X3-17 or 18 (GND). • To obtain transfer of overcurrent information between

two master units: • Connect the systems through the BI/O terminals X3-15

or 16 (+). • Connect the terminals X3-17 or 18 (GND).

NOTE! Note the polarity of the wires. In the example in Figure 5.7-1 arc information is transferred in both directions between the two master units. See also the application example in section 8.1. The slave units of the system should be connected to master units in the same zone.

Page 36: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP 220 / 220R Arc protection system User manual

VAMP Ltd

36 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004

X2X3 X1

X6

X2X3 X1

X6

123456789

10

11

12

13

14

15

1617

18

123456

89

10

11

14

15

1617

18

1 2

3 4

5 6

7 8

910

11 12

13 14

15 16

17 18

19 20

123456789

10

11

12

13

14

15

1617

18

123456

89

10

11

14

15

1617

18

La> BIO

123456789

10

11

12

13

14

15

1617

18

123456

89

10

11

14

15

1617

18

1 2

3 4

5 6

7 8

910

11 12

13 14

15 16

17 18

19 20

123456789

10

11

12

13

14

15

1617

18

123456

89

10

11

14

15

1617

18

Figure 5.7-1 Arc protection system with two master units (example).

5.8. Wiring systems with selective arc protection Wire the system as follows: • Connect the arc sensors of one certain zone in normal way

to the slave units. • Connect each slave unit to a master unit belonging to the

zone. • Connect the bidirectional arc information La via the BI/O

bus (terminal X3-12,17) to all master units in that zone. The unidirectional arc information (terminals X3-14,17, Lc>) can be fed from the master unit (terminals X3-12,17, La>) of the next zone. By doing so, the system will trip also the circuit breakers which feed the next zone. See Figure 2.7-1.

5.9. Checking wirings Check the secondary wiring by visual inspection and, when needed, by measuring, to eliminate possible incorrect wirings, which may cause malfunction of the system or associated devices.

5.9.1. Visual inspection Perform a visual inspection of the wiring. Especially check the wire bunches for adequate slack where needed over hinges. Check the screw terminals for correct tightness. Check, that no wire strands are protruding from the terminals.

Page 37: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP Ltd Arc protection system User manual

VAMP 220 / 220R

VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 37

5.9.2. Control by measuring Check the connections between the units and associated devices by using a circuit indicator lamp or buzzer. Check other possible connections by using recognized and reliable working practice.

Page 38: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP 220 / 220R Arc protection system User manual

VAMP Ltd

38 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004

6. Commissioning

6.1. Using master unit control panel

6.1.1. General The functions of the arc protection system can be supervised and controlled by means of the control panel of the master unit. The control panel has a number of indication leds, six flat push buttons, a 5 digit 7-segment display, dip switches, a selector switch and an outlet contact.

VY

056

A

1 2

3

4 5

6

7

8

9

10

11

12

13

Figure 6.1.1-1 The control panel of the master unit.

1. Push-buttons for choosing function 2. SET push-button for activating functions 3. ENTER push-button for executing functions 4. Display 5. POWER LED, indicates that all the supply voltages of the

system are in order 6. COM LED, indicates that serial communication is going on 7. ERROR LED, indicates that an internal fault has been

detected in the master unit 8. Mode indicator LEDs 9. Switch selector for setting the rated current of the

overcurrent unit 10. Setting knob for setting the start current of the overcurrent

unit. Separate setting knob for E/F setting (220R) 11. Dip switches for setting trip relay matrix 12. Trip indicators

Page 39: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP Ltd Arc protection system User manual

VAMP 220 / 220R

VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 39

13. Communication port for software programming

6.1.2. Control modes The following control modes are available on the control panel of the master unit: RUN Normal operation INSTALL System configuration INFO Checking the system configuration TEMP SET Setting and checking temperature limits TEMP Reading measured temperatures CURRENT Setting and reading start value and measured

values of the overcurrent unit ERROR Reading and resetting internal fault memory Choose a control mode by browsing up and down among the modes using the up and down arrow buttons on the control panel. The selected mode is indicated by the LED at the left edge of the control panel.

NOTE! The arc protection system is always ready for operation as long as the auxiliary supply is switched on, independently of the control mode of the master unit. The master unit automatically returns to RUN mode in about 60 seconds after the last push of a button. The modes RUN, INSTALL, INFO, TEMP SET and ERROR can be set into an active state, where various measures can be taken, such as setting system parameters, erasing messages, etc. In normal state, system information can be read, but no measures can be taken. In active state, the display is flashing to indicate that the system is waiting for a command from the operator. To switch from normal to active state, press the S button. To return from active state to normal state, press the S button once again. Figure 6.1.3-1 shows a fast guide to the functions available in different control modes, in normal state as well as active state.

Page 40: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP 220 / 220R Arc protection system User manual

VAMP Ltd

40 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004

6.1.3. Fast guide of the function menu

RUN

INFO

TEMP SET

TEMP

CURRENT

ERROR

INFO

TEMP SET

ERROR

E

RUNUse push-buttonto reset the arc faultmemory

Total number of slave units and sensors

INSTALL INSTALL

Use push-button to set the system configuration

Use push-button to checkthe number of sensorsat the slave unit

Slave unit No. /number of sensors

Temp. alarm setpointper slave unit 0...99°C Slave No. / Temp. setpoint display

Use push-buttons to set the temperature alarm setpoint of the slave unitsUse push-button to acceptthe set value

Slave unit No. / Tempactual value display

Start current setting& actual current display (L1 , L2 & L3)

Use knob to set thestart current value

Slave unit No. /internal fault code

Use push-button to reset internal fault memory one fault code at a time

Information about3 last arc activations(slave and sensor No.)

Figure 6.1.3-1 Function menu chart.

Page 41: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP Ltd Arc protection system User manual

VAMP 220 / 220R

VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 41

6.1.4. Push-button functions The up and down push-buttons are used to move

from one control mode to another. S The S push-button is used for switching between

active state and normal state. E The E push-button executes a function in active

state. It is also used for confirming new settings. The left and right arrow buttons are used for mov-

ing from one slave unit to another, when dealing with slave information. They are also used for dis-playing current values in CURRENT mode.

6.2. Using slave unit panel The functions accessible via the front panel of the slave unit are mainly needed during the commissioning (address setting). During normal operation the system is controlled from the master unit.

12 CDPOWER

COM

TEST/ERROR

SENSOR ADDR. COM1 COM2 VY00

5A

24 V

1 2 3 4 5 6 7 8 9 10

Made in FinlandARC SENSORS 1 ... 10 T

EMP

SS I + +

1 2

6

3

4

5

7 8 9 10 Figure 6.2-1 The front panel of the slave unit VAM 12 CD.

1. Input connector for the portable sensor 2. DIP switches for address setting 3. POWER LED, indicates that all the supply voltages of the

system are in order 4. COM LED, indicates that the serial communication is going

on 5. TEST/ERROR LED, indicates an internal fault or sensor

activation either during an arc fault or testing 6. Connectors for modular cable (data transfer and auxiliary

supply voltage) 7. Connectors for 10 arc sensors 8. Connector for temperature sensor 9. No connection.

Page 42: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP 220 / 220R Arc protection system User manual

VAMP Ltd

42 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004

10. Separate 24 V connectors for auxiliary supply voltage from master unit

6.3. Setting addresses of slave units The communication between the master unit and the slave units will not work until the slave units have been given addresses. By means of the addresses, the master unit, for instance, identifies the sensor, which caused tripping. The slave addresses are numbers within the range 1 - 24. The addresses can be freely set, e.g. so that they comply with the numbers of the switchgear cubicles. NOTE! The slave addresses must be unique among the slaves connected to the same master unit, i.e., two slaves cannot have the same address. Set the addresses with the DIP switches situated on the front panels of the slave units. The address is formed by the sum of the weight factors of the switches set in ON position. The weight factors of the switches are listed in the table below. See the examples in Figure 6.3-2. Switch no. Weight factor 1 1 2 2 3 4 4 8 5 16 6 Not in use Table 6.3-1Weight factors of the DIP switches.

If the address of a slave unit is changed after the system configuration has been defined (see section ), the slave unit must be reset for the new address to take effect. The slave unit is reset by switching off the power supply, either by switching off the auxiliary voltage of the system or by disconnecting the modular cable (and a possible separate supply cable).

Page 43: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP Ltd Arc protection system User manual

VAMP 220 / 220R

VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 43

VAADDR.

1 2

3

4

5

6

ON

VAM

Figure 6.3-1 DIP switches of the slave unit.

8

1

ON

13

16

2

18

4

ON

ON

12

34

56

12

34

56

ON Figure 6.3-2 Examples of address settings (address 13 and 18 respectively).

6.4. System configuration After the sensors have been wired, and the slaves have been given addresses, the system configuration is to be read into the memory of the master unit. Do as follows: Choose INSTALL mode using the up and down push-buttons. Activate the mode with the S push-button. The display starts to flash. Start reading the system configuration by pressing the E push-button.

Page 44: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP 220 / 220R Arc protection system User manual

VAMP Ltd

44 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004

The master unit reads the physical system configuration, which takes about a minute or less. When done, the total numbers of slave units and arc sensors appear on the display.

NOTE! A slave unit without arc sensors is not counted.

NOTE! Portable sensors are not regarded. After reading the system configuration the master unit auto-matically moves to normal state. Check that the displayed configuration equals the physical system layout. Use the INFO mode as described in section to check the number of arc sensors connected to each slave.

INSTALL

INSTALL

SLAVES SENSORS

SLAVES SENSORS

TOTAL NUMBER OF SLAVEUNITS AND SENSORS

TOTAL NUMBER OF SLAVEUNITS AND SENSORS

Use push-button to read thetotal number of slave units andsensors

S

E

S

Figure 6.4-1 Reading the system configuration into the memory of the master unit.

Page 45: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP Ltd Arc protection system User manual

VAMP 220 / 220R

VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 45

NOTE! If arc sensors are added or removed later, a new system configuration must be done. Otherwise, the system will interpret the change as an internal fault.

6.5. Setting overcurrent values Select the rated current, 1 A or 5 A, with the selector switch on the front panel of the master unit, see Figure 6.5-1. Enter CURRENT mode using the up and down arrow buttons. Set the start current value, 1...6 x In and the start E/F value (220R), 0.01...0.1 x In, with the start current setting knob on the control panel, see Figure 6.5-1a and b.

-> 1A -> 5A

1...6 In

TR1TR2TR3TR4TR1 -> TR2TR1 -> TR3Temp / TR4All / TR4

Latch12345678

off on

Figure 6.5-1a Setting rated current and start current on VAMP 220.

Page 46: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP 220 / 220R Arc protection system User manual

VAMP Ltd

46 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004

-> 1A-> 5A

TR1TR2TR3TR4TR1 -> TR2TR1 -> TR3Temp / TR4All / TR4

Latch12345678

off on

I L1I L3I 0

0,01

0,6

0,1

12

34

56

Figure 6.5-1b Setting rated current and start current on VAMP 220R

In CURRENT mode, the set start current value can be read on the display of the master unit. In addition, the actual values of the three phase currents (220) / two phase and E/F (220R) measured by the overcurrent subunit can be read on the display. To move between the set value and the measured actual values, use the left and right arrow buttons. See Figure 6.5-2.

NOTE! The current values read on the display are expressed in units of the rated current. For instance, the reading 1.5 means a current of 1.5 x In, i.e. 1.5 x 1 A = 1.5 A or 1.5 x 5 A = 7.5 A depending on the rated current selected according to the nominal secondary current of the current transformer. The setting of the start value of the overcurrent subunit can be changed even if the master unit is not in the CURRENT mode. However, it is recommended that the start current is set in the CURRENT mode, since then the accurate set value can be viewed on the display during the procedure.

Page 47: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP Ltd Arc protection system User manual

VAMP 220 / 220R

VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 47

CURRENT

USE KNOB TO SETTHE START CURRENTVALUE

CURRENT IN PHASE 1

CURRENT IN PHASE 2

CURRENT IN PHASE 3

Figure 6.5-2 Setting the start current and reading the actual measured currents in the CURRENT mode.

The overcurrent subunit measures all three phase currents (provided that all three phases are connected to the system, which is recommended, see page 27) and starts if one of them exceeds the set start current value. When the actual current in one (or several) phases exceeds the level 0.8 x set value, the display shows the warning code 200.

6.6. Relay output settings The relay outputs are configurable from the dip switch on the front panel of the master unit. See Figure 6.6-1. Switches 1 to 4 determine the latching/non latching feature of the corresponding trip relays. When a switch is turned on, latch is on for the corresponding relay, which means that the relay remains in drawn (conducting) state at an arc fault until is is reset. Switch 5 determines the function of trip relay 2. If switch 5 is in ON position, trip relay 2 will function in parallel with trip relay 1 and, in addition, trip on the BI/O trip signals from the BIO option board (if installed). See the example in Figure 6.6-3. If the switch is in OFF position, the trip relay 2 is exclusively dedicated to BI/O trip signals from the BIO option board. See Figure 2.1.2-1 and Figure 6.6-2.

Page 48: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP 220 / 220R Arc protection system User manual

VAMP Ltd

48 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004

-> 1A -> 5A

1...6 In

TR1TR2TR3TR4TR1 -> TR2TR1 -> TR3Temp / TR4All / TR4

Latch12345678

off on

Figure 6.6-1 The DIP switches on the front panel of the master unit.

Switch 6 defines the function of trip relay 3. If switch 6 is in OFF position, the trip relay 3 will function in parallel with trip relay 1. However, only local overcurrent and ARC signals will activate this stage (no BI/O lines). If the switch is ON, trip relay 3 will funcion as an CBFP relay to trip relay 1. The possible time delay settings are fast, 80, 100 or 150 ms. These must be specified when ordering. See the example in Figure 6.6-4. Switches 7 and 8 determine the function of trip relay 4. When switch 7 is turned ON, and switch 8 OFF, relay 4 becomes a trip relay which is tripping on any OC signal if a dedicated arc BIO line (Lc>) is activated (see also the function of switch 8). See Figure 6.6-5. To use relay 4 for external temperature alarm, set switch 7 in OFF position. If switch 7 and 8 both are turned ON, all trip signals will be routed to trip relay 4, which means that relay 4 will trip if one or more of the trip relays 1 ... 3 trip. See Figure 6.6-6.

Page 49: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP Ltd Arc protection system User manual

VAMP 220 / 220R

VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 49

TRIP

ARC / OC active signals

I>

L>

L>

I>

TR1

SW5

from Slave

3 x

t

80ms100ms150ms

Lb>

Ia>

&

Ib>

LL

L

Temp Alarm

La>

Lc>

L

I>LOC

L>LOC

TRIP 2

TRIP 3

TempAl/TRIP4

TRIP 1

SW1

SW2

SW3

>1T1T2T3

T3

T2

T1

>1

SW7SW8

1

1

TR loc

0ms

>1

SW6

int.sw.

SW4

L

TRIP

TR1TR2TR3TR4TR1 -> TR2TR1 -> TR3Temp / TR4All / TR4

Latch

off on12345678

Figure 6.6-2 Relay setting example.

Page 50: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP 220 / 220R Arc protection system User manual

VAMP Ltd

50 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004

TRIP

TRIP

I>

L>

L>

I>

TR1

SW5

from Slave

3 x

t

80ms100ms150ms

Lb>

Ia>

&

Ib>

LL

L

Temp Alarm

La>

Lc>

L

I>LOC

L>LOC

TRIP 2

TRIP 3

TempAl/TRIP4

TRIP 1

SW1

SW2

SW3

>1T1T2T3

T3

T2

T1

>1

SW7SW8

1

1

TR loc

0ms

>1

SW6

int.sw.

SW4

L

TRIP

TR1TR2TR3TR4TR1 -> TR2TR1 -> TR3Temp / TR4All / TR4

Latch

off on

ARC / OC active signals

12345678

Figure 6.6-3 Relay setting example.

Page 51: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP Ltd Arc protection system User manual

VAMP 220 / 220R

VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 51

TRIP

ARC / OC active signal

I>

L>

L>

I>

TR1

SW5

from Slave

3 x

t

80ms100ms150ms

Lb>

Ia>

&

Ib>

LL

L

Temp Alarm

La>

Lc>

L

TRIP

I>LOC

L>LOC

TRIP 2

TRIP 3

TempAl/TRIP4

TRIP 1

SW1

SW2

SW3

>1T1T2T3

T3

T2

T1

>1

SW7SW8

1

1

TR loc

0ms

>1

SW6

int.sw.

SW4

L

TRIP

TR1TR2TR3TR4TR1 -> TR2TR1 -> TR3Temp / TR4All / TR4

Latch

off on12345678

Figure 6.6-4 Relay setting example.

Page 52: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP 220 / 220R Arc protection system User manual

VAMP Ltd

52 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004

TRIP

TRIP

ARC / OC Active signal

I>

L>

L>

I>

TR1

SW5

from Slave

3 x

t

80ms100ms150ms

Lb>

Ia>

&

Ib>

LL

L

Temp Alarm

La>

Lc>

L

TRIP

I>LOC

L>LOC

TRIP 2

TRIP 3

TempAl/TRIP4

TRIP 1

SW1

SW2

SW3

>1T1T2T3

T3

T2

T1

>1

SW7SW8

1

1

TR loc

0ms

>1

SW6

int.sw.

SW4

L TRIP

TR1TR2TR3TR4TR1 -> TR2TR1 -> TR3Temp / TR4All / TR4

Latch

off on12345678

Figure 6.6-5 Relay setting example.

Page 53: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP Ltd Arc protection system User manual

VAMP 220 / 220R

VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 53

TRIP

TRIP

ARC / OC Active signal

I>

L>

L>

I>

TR1

SW5

from Slave

3 x

t

80ms100ms150ms

Lb>

Ia>

&

Ib>

LL

L

Temp Alarm

La>

Lc>

L

TRIP

I>LOC

L>LOC

TRIP 2

TRIP 3

TempAl/TRIP4

TRIP 1

SW1

SW2

SW3

>1T1T2T3

T3

T2

T1

>1

SW7SW8

1

1

TR loc

0ms

>1

SW6

int.sw.

SW4

L TRIP

TR1TR2TR3TR4TR1 -> TR2TR1 -> TR3Temp / TR4All / TR4

Latch

off on12345678

Figure 6.6-6 Relay setting example.

Page 54: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP 220 / 220R Arc protection system User manual

VAMP Ltd

54 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004

6.7. Testing the arc sensors After the arc sensors have been mounted and connected to the slave units, and the system configuration has been read to the memory of the master unit, the function of the arc sensors and the data transfer between the slaves and the master unit must be tested. Before starting the testing, ensure that no trip signal will be generated when the arc sensors are activated. Tripping of the circuit-breaker can be avoided by disconnecting the circuit-breaker trip circuit, or alternatively by increasing the start value of the overcurrent subunit to a level where it cannot start in any circumstances. Verify proper operation of the sensors and the data transfer by performing the following test on each arc sensor: Expose the active part of the sensor to strong light, for instance, from an electric torch. Check that the arc sensor is activated. The TEST/ERROR indicator of the slave unit should be lit, and the address of the tested arc sensor (slave address and connector number) should appear on the display of the master unit.

NOTE! Remember to restore the trip circuits and the start value of the overcurrent unit after completing the test if changes were made.

Page 55: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP Ltd Arc protection system User manual

VAMP 220 / 220R

VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 55

7. Operational measures

7.1. Arc faults

7.1.1. Arc fault tripping alarm When an arc fault trip occurs, an alarm signal is obtained via the trip alarm output contact (see section 5.3.5). At the same time, the leds of the tripping relays are lit on the control panel of the master unit, thus, showing which trip outputs that were activated. In the RUN mode of the master unit, the display shows the information of the last sensor that was activated. If one or more BI/O lines were activated, the display will show the identifiers of the activated BI/O lines. To reset a trip alarm, push any button on the control panel. The trip alarm will remain active until it is reset.

7.1.2. Reading arc fault information Each time an arc sensor is activated, the address of the sensor is stored in the memory of the master unit. Up to three addresses are stored, that is, the addresses of the three sensor that last were activated. When an arc or overcurrent signal is received from a BI/O line, the identifier of the BI/O line is stored instead. To read the recorded arc fault information: 1. Enter RUN mode (if not already active) using the up and

down arrow buttons. 2. Browse through the stored codes using the left and right

push-buttons. See Figure 7.1.2-1. A sensor address is given as slave address and connector number of the sensor. The BIO lines are given by their identifiers, that is, La, Lc and Ib (see section 5.7. ) along with the word BIO. The recorded values can be erased from the memory as follows: 1. Activate the RUN mode by pushing the S button. 2. Push the E button. If the operator does not erase the display codes from the memory, they will be erased automatically within two hours.

Page 56: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP 220 / 220R Arc protection system User manual

VAMP Ltd

56 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004

RUN

S

E MEMORYERASION

Figure 7.1.2-1 Reading arc information and resetting the memory.

7.2. Supervision of phase currents

7.2.1. Overcurrent warning The warning code 200 appears in the display when one or more phase currents exceed 0.8 x the start value of the overcurrent unit. The code remains on the display until all phase currents are below the mentioned limit.

7.2.2. Reading current values To read the current values measured by the overcurrent subunit: Enter the CURRENT mode using the up and down arrow but-tons. The display first shows the set start value of the overcurrent subunit. Browse to the measured phase current values (1, 2, 3) using the left and right push-buttons. See Figure 7.2.2-1.

Page 57: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP Ltd Arc protection system User manual

VAMP 220 / 220R

VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 57

CURRENT

USE KNOB TO SETTHE START CURRENTVALUE

CURRENT IN PHASE 1

CURRENT IN PHASE 2

CURRENT IN PHASE 3

Figure 7.2.2-1 Reading the measured current values in CURRENT mode.

7.3. Handling self-supervision faults

7.3.1. Error indications The self-supervision system supervises the function of the arc protection system continuously. When it detects an internal fault, an alarm signal is issued via the SF alarm contact of the master unit, and the ERROR indicator on the front panel of the master unit will remain lit to indicate an internal fault. A fault message is generated. The three last fault messages are stored in the memory of the master unit. Due to continuous selftesting of the internal circuitry, a weak rapid light pulse occurs on the ERROR indicator. This is because the test pulse is checking that the internal connections are intact, no actions need to be taken.

Page 58: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP 220 / 220R Arc protection system User manual

VAMP Ltd

58 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004

7.3.2. Reading and erasing error messages To read the error messages: 1. Enter the ERROR mode using the up and down arrow

buttons. 2. Scroll through the error messages using the left and right

arrow buttons. If the internal fault can be related to one of the slave units, the address of the actual slave unit is displayed in the left display box and the fault code (see below) in the right. At general faults, e.g. communication faults, the display shows no slave address, only a fault code.

ERROR

S

E MEMORYERASION

Figure 7.3.2-1 Reading and resetting the fault memory.

To reset the error and erase the stored fault messages: Activate the ERROR mode by pushing the S button. Push the E button. This will erase the fault message which is presently being dis-played and the next fault message will appear on the display. This again can be erased by pressing the E button, and so on. The fault messages originating from faults that have disappeared by themselves are automatically erased from the fault memory within two hours.

Page 59: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP Ltd Arc protection system User manual

VAMP 220 / 220R

VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 59

7.3.3. Fault codes The following table lists the fault codes with brief explanations. Below the table is a more extensive descripiton with advice about measures to take. Fault code Fault type Fault reason 10 Configuration

fault The number of sensors changed

11 Slave unit fault Faulty slave unit in the system

12 Long BIO activation

Faulty sensor or overcurrent module in the system, or setting too low

13 Communication fault

Faulty communication line

Table 7.3.3-1 Self supervision fault codes.

Fault code 10 indicates that the number of sensors in the system has changed. Sensors have been added to the system without setting the system configuration in the INSTALL mode or the connection wires of a sensor have become loose. To locate the fault, check the number of sensors of the slave unit indicated in the fault message as described in section 7.4. Check the sensor wirings of the slave unit. Fault code 11 indicates that a fault has been detected in one of the slave units of the system.

NOTE! When this fault has occurred, no activation of the sensors con-nected to the faulty slave unit will be transferred to the master unit. To locate the fault, check the connection of the modular cable of the slave unit indicated in the fault message. Check the wiring of a possible separate auxiliary power supply. Observe the indicators on the front panel. In case the green POWER indicator is off, the possible reason for the malfunction is in the auxiliary supply voltage. If the red TEST/ERROR indicator is lit without arc sensor activation, the fault is possibly either in the internal functions of the slave unit or in the sensor cables. See also the note to fault code 12 below. Fault code 12 indicates that one or more BI/O lines have been activated.

Page 60: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP 220 / 220R Arc protection system User manual

VAMP Ltd

60 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004

To locate the fault, check in RUN mode which BI/O lines has been activated (see page 57). Check the wirings of the BI/O lines.

NOTE! The fault codes 11 and 12 can also be the result of an interfer-ence light detected by an arc sensor. If a sensor remains acti-vated for more than 7 seconds, the slave unit to which it is connected will be disconnected from the system. At the same time a fault alarm is given. Once the interference light disap-pears the slave unit restores its normal function and the fault alarm is reset.

NOTE! Fault code 12 can also be a result of a too low overcurrent set-ting in the alarming master unit or any master unit connected to the alarming unit via the Ib> BIO line. Fault code 13 indicates that an error has been detected in the system communication. The fault message does not include any slave unit address number. Check the modular cables and their connectors.

NOTE! In case the fault codes keep appearing after cutting the auxil-iary supply of the arc protection system, and the mentioned measures do not solve the problem, please, contact the manufacturer or his nearest representative.

7.3.4. VAM 12 CD TEST/ERROR indication The TEST/ERROR indicator of VAM 12 CD will remail lit during an internal fault of the slave unit. The master unit will show a fault code 11, see page 61 for description. The TEST/ERROR indicator will also lit up during arc sensor activation. The indicator will remain lit only the time that the sensor is detecting an arc. Due to continuous self testing of the system configuration the TEST/ERROR indicator is lit up for couple of seconds once in every 2 or 3 minutes, no actions need to be taken.

Page 61: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP Ltd Arc protection system User manual

VAMP 220 / 220R

VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 61

7.4. Checking system configuration The system configuration can be checked in the INFO mode of the master unit as follows: 1. Enter the INFO mode. 2. The display shows the address of a slave unit and the

number of sensors connected to it according to the system configuration done earlier.

3. Use the left and right push buttons to move between the slave units.

4. Activate the INFO mode at the desired slave unit by pushing the S push-button.

5. Push the E button to execute the check connected sensors. The display shows the number of sensors connected to the slave unit. If the shown system configuration differs from the system configuration set earlier, the difference may be due to an internal system fault.

NOTE! Checking the system configuration will not affect the configura-tion settings. If the system configuration is to be modified, it must be done in INSTALL mode. See section .

INFO

S

E

Number Slave unit of sensors

Number Slave unit of sensors

Number Slave unit of sensors

Use push-button tocheck the numberof sensors at the slave unit( 1 sensor missing )

Figure 7.4-1 Checking the system configuration in the INFO mode.

Page 62: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP 220 / 220R Arc protection system User manual

VAMP Ltd

62 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004

8. Application examples

8.1. System with two master units The figure 8.1-1 illustrates an arc protection system with two master units. It shows the transmission lines, the trip circuits, and how the system operates under different fault conditions.

VAMPVAMP

B

X1 X2

X1 X2 CB1 CB2 CB3 Ib T1 T2

CB1

CB3

CB2 T2T1 V2

VAMVAM

La Lb Ib

1 2 3

VAMP220R

La (Light BIO) is a bidirectional line which transmits/receives arc inforemation between VAMP units. (not used inthis application)

Lb (Light BIO) is a unidirectional condition line. If the VAMP unit receives overcurrent information Ib> simultanously as an arc condition occures, the light information be transmitted through this BIO line. (not used inthis application)

Ib Is a bidirectional line which transmits/receives overcurrent information between VAMP units. Ia Is an overcurrent transmiting line (one direction), not used in this application.

See also VAMP 220 R Trip Signalling Block Diagram !!

WILL NOT

Section 1 Section 2

A

T1 T2

Ib>

3 3

*

*

*

*

*

* *) = no affect to function

Figure 8.1-1 An application example with two master units.

Page 63: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP Ltd Arc protection system User manual

VAMP 220 / 220R

VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 63

9. Product information

9.1. Dimensional drawing 208.0

155.0

27.0181.028.0

137.0

190.0

193.0 >20.0

1.0-10.0

139.0

P200_ulkomitat_kannella

PANELCUT-OUT

Figure 9.1-1 Dimensional drawing and panel cut-out dimensions.

Page 64: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP 220 / 220R Arc protection system User manual

VAMP Ltd

64 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004

9.2. Panel mounting

Figure 9.2-1 Flush mounting of protection relay in panel.

9.3. Semi-flush mounting 27.0181.028.0

13

7.0

P200_semi-flush

b a

21.0

Figure 9.3-1Semi-flush mounting of protection relay.

Depth with raising frames Type designation a b

VYX076 40 mm 169.0 mm VYX077 60 mm 149.0 mm

Page 65: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP Ltd Arc protection system User manual

VAMP 220 / 220R

VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 65

10. Ordering code VAMP220/220R

VAMP 220 - 3

Nominal Current [A]3 = 1A / 5A

Trip 3 operation time [ms]A = FASTB = 80msC = 100msD = 150ms

Trip 4 operation3 = Normal4 = Trip 4 -> CBFP

Supply Voltage [V]A = 40.. 265Vac/dcB = 18.. 36Vdc

Optional Hardware 1A = None B = T1 & T2 relays NC, T3 & T4 relays NO

Optional Hardware 2A = NoneB = B I/O Option Card

Accessories :

Order Code Explanation Note

VAM 12 CD Slave Unit (VAMP220) 10 Sensor InputsVAR 4 CE 4/0 Trip Multiplier Relay 1xNO -> 4xNOVAX 2 CB Interface Unit ( use vx002 cable ) For Sensor Cable Extension

VA 1 DA-6 Arc Sensor Cable length 6mVA 1 DA-20s Arc Sensor Cable length 20m (Shielded)VA 1 DT-6 Temperature Sensor Cable length 6mVA 1 DP-5 Portable Arc Sensor Cable length 5mVX001-xx Modular Cable VAM <-> VAM ( xx = Cable length [m] ) Note 1. Preferred Cable LenghtsVX002-xx Shielded Sensor Cable ( xx = Cable Length [m] ) Example: JAMAKVX010-xx Modular Cable VAMP <-> VAM ( xx = Cable length [m] ) Note 1. Preferred Cable Lenghts

VYX001 Surface Mounting Plate for Sensors L-shapedVYX002 Surface Mounting Plate for Sensors Z-shapedVYX076 Raising Frame Height 40mmVYX077 Raising Frame Height 60mmVA 1 EH-6 Arc Sensor (Pipe type) Cable length 6m

Page 66: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP 220 / 220R Arc protection system User manual

VAMP Ltd

66 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004

VAMP 220 R ORDERING CODE

VAMP 220 R - 3

Nominal Current [A]3 = 1A / 5A

Trip 3 operation time [ms]A = FASTB = 80msC = 100msD = 150ms

Trip 4 operation3 = Normal4 = Trip 4 -> CBFP

Supply Voltage [V]A = 40.. 265Vac/dcB = 18.. 36Vdc

Optional Hardware 1A = None B = Slave Unit Option Card

Optional Hardware 2A = NoneB = B I/O Option Card

Accessories :

Order Code Explanation Note

VAM 12 CD Slave Unit (VAMP220) 10 Sensor InputsVAR 4 CE 4/0 Trip Multiplier Relay 1xNO -> 4xNOVAX 2 CB Interface Unit ( use vx002 cable ) For Sensor Cable Extension

VA 1 DA-6 Arc Sensor Cable length 6mVA 1 DA-20 Arc Sensor Cable length 20mVA 1 DT-6 Temperature Sensor Cable length 6mVA 1 DP-5 Portable Arc Sensor Cable length 5mVX001-xx Modular Cable VAM <-> VAM ( xx = Cable length [m] ) Note 1. Preferred Cable LenghtsVX002-xx Shielded Sensor Cable ( xx = Cable Length [m] ) Example: JAMAKVX010-xx Modular Cable VAMP <-> VAM ( xx = Cable length [m] ) Note 1. Preferred Cable Lenghts

VYX001 Surface Mounting Plate for Sensors Z-shapedVYX002 Surface Mounting Plate for Sensors L-shapedVYX076 Raising Frame Height 40mmVYX077 Raising Frame Height 60mm

Note 1. Cable lengths 1, 3, 5, 7, 10, 15, 20, 25 & 30

Page 67: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VAMP Ltd Arc protection system User manual

VAMP 220 / 220R

VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 67

11. Reference information Manufacturer data: VAMP Ltd P.O.Box 5 FIN-65381 Vaasa, Finland Visiting address: Runsorintie 7 Phone: +358 (0)6-2121 118 Fax: +358 (0)6-2121 105 24h support: +358 40 5736 316 Email: [email protected] URL: http://www.vamp.fi

Service: VAMP Ltd P.O.Box 5 FIN-65381 Vaasa, Finland Visiting address: Runsorintie 7 Phone: +358 (0)6-2121 118 Fax: +358 (0)6-2121 105

24h support phone: Tel . +358 (0)40 573 6316 Email: [email protected] During office hours 6.00 - 14.00 GMT, please use the following telephone number +358 (0)6-2121 100.

Page 68: VAMP 220 / 220R - SAEsae.com.pl/userfiles/products/1481635860/afd0b09179ff... ·  · 2016-12-13relay VAR 4 CE to the outputs, up to 16 trip outputs can be obtained. The standard

VM220.EN004

VAMP Ltd Street address: Runsorintie 7 Phone: +358 6 212 1100 Post address: Fax: +358 6 212 1105 Box 5, FIN 65381 Vaasa, Internet: www.vamp.fi Finland Email: [email protected]

We reserve the rights to changes without prior notice