VAMP 300 IED
VAMP 300 IED functionality- Feeder relay- Motor relay
Schneider Electric 2- Vamp – PH – 12.2.2013
VAMP 300 IEDProduct launch
• Vamp 300 series concept was launched to Finnish customers on November 7th, 2012. Vamp partners are given marketing release message of this product within November, 2012. Delivery release follows January 1st, 2013.
• Vamp 300 will be shown also in the Eskom exhibition in November 2012.
Schneider Electric 3- Vamp – PH – 12.2.2013
VAMP 300 IEDInnovations through years
2009-2012
• Partly modular design• Flexible relay range• The first ever low end relay with IEC
61850• Can operate together with arc
protection system• Arc protection with three point
sensors provide 7ms operation time
2013...VAMP 300 IED
• Fully modular design with option for new menu structure and bigger display
• Flexible relay range, fits to many applications
• Multible protocol possibilities simultaneously including IEC 61850
• Can operate together with arc protection system
• Integrated arc protection with 2 point sensors provide 7 ms operation time
VAMP 50 series relays
Schneider Electric 4- Vamp – PH – 12.2.2013
VAMP 300 IEDFunctionality generally
• Vamp 300 IED features a modular design that allows user-defined conventional protection and arc flash protection solutions both in new and existing power distribution systems.
• New password protected and easy to use push buttons for breaker controlling.
• Class IP54 casing as a default with optional conformal coated PCB:s provide reliability in demanding environment.
• New improved integrated arc protection. Binary input and output channels provide possibility to build arc system between the protection relays.
-With 2 point sensors fast operation time within 7 milliseconds is achieved. -Upcoming 3 point sensor and 1 fiber loop option, brings the integrated arc protection operation time to 2 milliseconds. Option will be launched at the end of 2013.• Optional bigger LCD display with new improved and user adjustable menu
design coming later.• VAMP 300 IED has wide selection of communication protocols, including IEC
61850, Profibus DP, Modbus TCP, Modbus RTU, DNP 3.0, DeviceNet, IEC 60870-5-101, 60870-5-103 and SPA-Bus.
Schneider Electric 5- Vamp – PH – 12.2.2013
VAMP 300 IEDFamiliar firmware
• Non volatile capacitor backed up memory is storing events, fault logs and disturbance recordings for 7 days
• IED stores 8 latest faults in every protection stage• Up to 2000 events• User programmable logic with 20 logical nodes. Logic is configured by using
the Vampset relay setting and configuration tool• Among regular protections stages 1-8 user configurable programmable
stages can be used• Disturbance recorder with 1600 Hz sample rate is able to record data with
maximum 32 samples per cycle. Disturbance recorder files are common comtrade format
• Vamp 300 IED includes virtual signal injection called virtual measurement. It is possible to generate virtual sequences to test the relay. It is also possible to do playback with comtrade files.
Vamp 300 IED has familiar firmware, similar to Vamp 50 and 200 –series relays.
Schneider Electric 6- Vamp – PH – 12.2.2013
VAMP 300 IEDFully modular design
Schneider Electric 7- Vamp – PH – 12.2.2013
VAMP 300 IEDHW options
F = FeederM = Motor
-Adjusts the firmware of the IED to a certain desired mode.
Schneider Electric 8- Vamp – PH – 12.2.2013
VAMP 300 IED
-80…265VAC/DC with 6 output relays, 1 alarm contact and IRF relay-18…48VDC with 6 output relays, 1 alarm contactand IRF relay (Q2/2013)
F = FeederM = Motor
HW options
Schneider Electric 9- Vamp – PH – 12.2.2013
-2 x Arc option (7ms)-6 x DI + 4 x DO-10 x DI (Q2/2013)
VAMP 300 IED F = FeederM = Motor
HW options
Schneider Electric 10- Vamp – PH – 12.2.2013
VAMP 300 IED
No options time being here
F = FeederM = Motor
HW options
Schneider Electric 11- Vamp – PH – 12.2.2013
VAMP 300 IED
Future extensions
F = FeederM = Motor
HW options
Schneider Electric 12- Vamp – PH – 12.2.2013
VAMP 300 IED
-3 x I + 3I0 + U
-3 x I + 3I0 + 4 x U (Q2/2013)
F = FeederM = Motor
HW options
Schneider Electric 13- Vamp – PH – 12.2.2013
VAMP 300 IED
-RS232 interface-RS232 + RJ45 ethernet interface-RS232 + LC ethernet fiber interface
F = FeederM = Motor
HW options
Schneider Electric 14- Vamp – PH – 12.2.2013
VAMP 300 IED 128 x 64 LCD or128 x 128 LCD (Q3/2013)
-Default 128 x 64 LCD display-Optional 128 x 128 LCD display (Q3/2013)
F = FeederM = Motor
HW options
Schneider Electric 15- Vamp – PH – 12.2.2013
VAMP 300 IED 128 x 64 LCD or128 x 128 LCD (Q3/2013)
Digital input activation voltage level
F = FeederM = Motor
-24VDC/110VAC
-110VDC/220VAC
-220VAC
HW options
Schneider Electric 16- Vamp – PH – 12.2.2013
VAMP 300 IED
Launch schedule:• Vamp channel: November 2012• Schneider Electric: April, 2013
128 x 64 LCD matrix display 128 x 128 LCD matrix display
Launch schedule:• Q3, 2013
Display options
Schneider Electric 17- Vamp – PH – 12.2.2013
VAMP 300 IEDProgrammable mimic display and logic
• User configurable real time mimic with freely selectable measurements
• Pop-up screen for events, reclosing and synchro-check information
• Internal logic for up to 20 output nodes
Schneider Electric 18- Vamp – PH – 12.2.2013
VAMP 300 IEDFault data and event recording• Stored in non-volatile memory• Capacitor back-up for 7 days• No maintenance required as for solutions
with battery back-up
• Disturbance recorder• Waveform or trend mode possible• 32 samples/cycle max sampling rate• Upload to VAMPSET DR analyzing tool• Output in standard COMTRADE format
Inrush current captured in waveform mode (32, 16 or 8 samples/cycle)
Start current of an induction motor captured in trend mode (e.g. 10 ms, 20 ms, 200 ms)
Schneider Electric 19- Vamp – PH – 12.2.2013
VAMP 300 IEDVirtual measurement and fault data injection• Possibility to create virtual current and
voltage injection with harmonics and phase shift
• Possible to do disturbance recorder playbacks
Schneider Electric 20- Vamp – PH – 12.2.2013
0..8 x mA output/input0...20 x RTD
0 – 20 mA (step < 6 µA)Pt100, Ni100, Ni120, Cu10, Pt250
Communication ports 1 x local USB front0-2 COM port(s) back
Internal communication interfaces
-RS-232-Ethernet (RJ-45)-Ethernet (LC fiber)
External communication interfaces
-RS-485-DeviceNet-Serial fiber (GG/PP/GP/PG)-Profibus
Communication protocols -IEC-101-IEC-103-Modbus-Profibus DP-Spabus-Ethernet IP-Modbus TCP-DNP 3.0-IEC-61850-DeviceNet
Applications: -Feeder/incomer protection-Line protection-Motor protection
3 x I (IN = 5A) 0.05...50 x IN (45 – 65 Hz)
1...4 x U (UN = 100 V) 0.5...260 V (45 – 65 Hz)
1 x 3I0 (IN = 5/1) 0.003...10 x IN (45 – 65 Hz)
UAUX 80...265 VAC/DC
18...48 VDC
0...44 x DI A: 24 VDC / 110 VAC
B: 110 VDC / 220 VAC
C: 220 VDC
6...45 x trip contacts (T1-T45) Making 250VAC/DC
2 alarm contacts (A1 & IRF) Change-over 250VAC/DC
Arc option -2 point sensors + 3 x BIO channels (7ms)-3 point sensors + fiber sensor + BIO channel (2ms) ready at the end of 2013
• Fully modular design, flexible option cards• Arc-option (7 ms) 2ms end of 2013
VAMP 300 IEDMechanics
Schneider Electric 21- Vamp – PH – 12.2.2013
VAMP 300 IEDProtection functions
Note:1. Available functions with 3xI + Io + U
measurement card2. Ramaining functions when 3xI + 2xIo
+ 4xU measurement is ready with Q2/2013
Schneider Electric 22- Vamp – PH – 12.2.2013
VAMP 300 IEDArc protection options
Vamp relays measure fault current and with optional arc protection, also measure light via arc sensor channels, which provide monitoring for the whole switchgear. Should and arc fault occur in the switchgear the arc protection system provides extremely fast tripping of the circuit breaker. The fault will be prevented from spreading and quickly isolated, which may save human lives and valuable assets.
Schneider Electric 23- Vamp – PH – 12.2.2013
VAMP 300 IEDCommunication
Schneider Electric 24- Vamp – PH – 12.2.2013
VAMP 300 IEDVEPROHardware available February, 2013
Schneider Electric 25- Vamp – PH – 12.2.2013
VAMP 300 IEDVEPROHardware available February, 2013
Schneider Electric 26- Vamp – PH – 12.2.2013
VAMP 300 IEDAccessories list
Schneider Electric 27- Vamp – PH – 12.2.2013
VAMP 300 IEDType tests
The first released version of Vamp 300 IED is mechanically identical to Vamp 321 arc master. Therefore Vamp 321 tests and environmental apply for 300 IED as well.
Vamp 300F and Vamp 300M have UL certificate
Vamp 300 IED will be retested before new hardware options are released.
Schneider Electric 28- Vamp – PH – 12.2.2013
VAMP 300 IEDDimensionsVamp 300 IED mechanical dimensions and assembly instructions with torque limits are presented in this slide.
Schneider Electric 29- Vamp – PH – 12.2.2013
Thank You !
VAMP 300 IED