CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number # CL16-HT-0037 Introduction The University of Massachusetts Lowell (UML) invites bids on the purchase of an Emergency Generator for North Quad Infrastructure. Bid Specifications 1. Please see Technical Specifications Section 263213-Engine Generators, Section 263214- Installation of Engine Generators, Section 263600 Transfer Switches and North Quad Drawings. Bid Rejection The University reserves the right to reject any or all bids received in whole or in part if it is deemed such action is in the best interest of The University and the Commonwealth of Massachusetts. Preparation of Bids Bids must be signed, where instructed. Bidders are cautioned that errors, alterations, or corrections on the submitted bid must be initialed by the person signing the bid proposal or his/her authorized designee. Failure to do so may result in rejection of the bid for those items erased, altered, or corrected and not initialed. Telephone and or Fax bids will not be accepted. Selection Criteria UML shall enter into an agreement with the Bidder who submits the proposal that meets the minimum requirements, proof of quality and performance of previous work, ability to meet the time frame set by the University, is financially beneficial to UML and demonstrated ability to service the product in a timely and satisfactory manner. Prevailing Wage Law All services solicited through this RFB are subject to the Massachusetts Prevailing Wage Laws. A list is provided as part of the RFB indicating the trades for which a contractor is mandated by law to pay the prevailing wage rates. Applicable Prevailing Wage Rates are issued with this RFB and will become a part of any Contract resulting from this solicitation. It is the responsibility of the Contractor to adhere to the Prevailing Wage Laws. All Electrical Connections must be done by a Licensed Electrical Contractor. It is University of Massachusetts Lowell

Upload: others

Post on 26-Apr-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

CL16-HT-0037 Pre-Purchase Emergency Generator Page 1

BID REQUEST

Pre-Purchase of Emergency Generator

Bid Number # CL16-HT-0037

Introduction

The University of Massachusetts Lowell (UML) invites bids on the purchase of an Emergency Generator for North Quad Infrastructure.

Bid Specifications

1. Please see Technical Specifications Section 263213-Engine Generators, Section 263214-Installation of Engine Generators, Section 263600 Transfer Switches and North Quad Drawings.

Bid Rejection

The University reserves the right to reject any or all bids received in whole or in part if it is deemed such action is in the best interest of The University and the Commonwealth of Massachusetts.

Preparation of Bids

Bids must be signed, where instructed. Bidders are cautioned that errors, alterations, or corrections on the submitted bid must be initialed by the person signing the bid proposal or his/her authorized designee. Failure to do so may result in rejection of the bid for those items erased, altered, or corrected and not initialed. Telephone and or Fax bids will not be accepted.

Selection Criteria

UML shall enter into an agreement with the Bidder who submits the proposal that meets the minimum

requirements, proof of quality and performance of previous work, ability to meet the time frame set by the

University, is financially beneficial to UML and demonstrated ability to service the product in a timely and

satisfactory manner.

Prevailing Wage Law

All services solicited through this RFB are subject to the Massachusetts Prevailing Wage Laws. A list is

provided as part of the RFB indicating the trades for which a contractor is mandated by law to pay the

prevailing wage rates. Applicable Prevailing Wage Rates are issued with this RFB and will become a part

of any Contract resulting from this solicitation. It is the responsibility of the Contractor to adhere to the

Prevailing Wage Laws. All Electrical Connections must be done by a Licensed Electrical Contractor. It is

University of

Massachusetts

Lowell

Page 2: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

CL16-HT-0037 Pre-Purchase Emergency Generator Page 2

the responsibility of the Vendor to obtain a City of Lowell Electrical Permit. The Vendor is also

responsible for the Cost of any and all necessary permits.

Certification of Tax Status

Pursuant to Massachusetts General Law, Chapter 62C, Section 49 A, the bidder certifies under penalties of perjury that to the best of the bidder's knowledge and belief, they have filed all state tax returns and paid all state taxes required by law.

Certification of Non-Collusion

Pursuant to Massachusetts General Law, Chapter 7, Section 22 (20), the bidder certifies under penalties of perjury that their bid is in all respects bona fide, fair, and made without collusion or fraud with any person, joint venture, partnership, corporation or other business or legal entity.

Bidder's Representations

Each bidder by submitting its bid represents that:

a) The bid document and specifications have been read and understood by the bidder, b) The bid is based upon the items described in the bidding documents and specifications without

exceptions, c) The bid has been arrived at independently and is submitted without collusion,

Bid Documents

Proposal may be submitted via email to [email protected] or hard copy sent to Purchasing at the address below.

Bid Opening

Bids will be opened and publicly read on, Monday, December 14, 2015 at 11:00 AM EST

at the Purchasing Department:

Wannalancit Business Center 600 Suffolk St. Rm 415

Lowell, MA 01854

It is vital that bids be in the Purchasing Office by the due date and time.

Late bids will not be considered, and will be placed, unopened, in the bid file.

We strongly encourage you to contact the Purchasing Office by telephone or e-mail prior to the bid opening to confirm that your bid has been received by the Purchasing Department. The general Purchasing Office phone number is (978) 934-3500 or email address is [email protected]. All communication should reference RFB No. CL16-HT-0037.

Page 3: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

CL16-HT-0037 Pre-Purchase Emergency Generator Page 3

Questions/Contact Person

Prospective Bidders may submit questions to UML regarding this solicitation via email to [email protected]

Amendments

The Purchasing Department reserves the right to amend, alter, or cancel the bid at any time prior to the deadline for submissions of bids. If such action is necessary, all potential bidders who have received or requested a copy of the bid will be notified of the changes to be made in writing and whether the bid opening date will be extended.

Debriefing

Any Vendor may request a debriefing within one (1) week after receiving notification of award, to discuss the Selection Committee's evaluation of its bid proposal. Request for debriefing shall be made in writing to the Purchasing Manager. Debriefing shall not include discussions of any competing bids.

Massachusetts Public Record Law

All bids and related documents submitted in response to this RFP are subject to the Massachusetts Public Records Law, Massachusetts General Law Chapter 66, Section 10 and to M.G.L. Chapter 4, Section 7, Subsection 26, regarding public access to such documents. Statements in the bid response that are inconsistent with those statutes will be disregarded. Any additional questions regarding the Public Records Law should be directed to the Public Records Division at: (617) 727-2832 during regular business hours. You may also access various Public Records Division publications through the Internet at: www.sec.state.ma.us/pre.

Transfers and Subcontracting

The Vendor may not subcontract, in whole or in part, any portion of this contract without the written consent of the University.

Nondiscrimination in Employment and Affirmative Action

The Contractor shall not discriminate against any qualified employee or applicant for employment because of race, color, national origin, ancestry, age, sex, religion, physical or mental handicap, or sexual orientation. The Contractor agrees to comply with all applicable Federal and State statutes, rules and regulations prohibiting discrimination in employment including but not limited to: Title VII of the Civil Rights Act of 1964; the Age Discrimination in Employment Act of 1967; Section 504 of the Rehabilitation Act of 1973; the Americans with Disabilities Act of 1990; and M.G.L. c.151B.

Vendor Not Employee of UML

The Vendor, or his employees or agents performing under the agreement, are not to be deemed to be employees of UML nor to be agents of UML in any manner whatsoever. The Vendor will not hold himself out as, nor claim to be, an officer or employee of UML and will not make any claim, demand, or application to or for right or privilege applicable to an officer or employee of UML, including, but not limited to, workmen's compensation coverage, unemployment insurance benefits, social security benefits, or retirement membership or credit.

Page 4: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

CL16-HT-0037 Pre-Purchase Emergency Generator Page 4

Company information and signature required

Company Name:

Company Address:

Tel. # Fax #

Are you

() Woman Owned Business () Minority Owned Business () Individual/Sole Proprietorship () Partnership () Government () Non-profit Organization () Corporation

() Disadvantaged Business () Other (specify)

Tax I.D./ FEIN # ____-___-_____ or S.S.N.# (if individual) ____-___-_____.

Signature of owner or authorized officer*:

Please print name: ______________________________

Title: __________________________

Date submitted: ___/___/___

Page 5: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

CL16-HT-0037 Pre-Purchase Emergency Generator Page 5

Certification of Non Collusion

The undersigned certifies under penalties of perjury that this Bid or Proposal has been made and

submitted in good faith and without collusion or fraud with any other person. As used in this

certification, the word "person" shall mean any natural person, business, partnership,corporation,

union, committee, club, or other organization, entity, or group of individuals.

______________________________

Authorized Signature*

______________________________

Printed Name of person signing bid or proposal*)

___________________________

(Name of business)

Page 6: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

CL16-HT-0037 Pre-Purchase Emergency Generator Page 6

Business Reference Form

Company Name:___________________________________________________

1. Reference Name:______________________ Contact Person:_______________

Address:_____________________________ Tel Number:________________

Description and Dates of Services Provided: ________________________

____________________________________________________________________________________

____________________________________________________________________________________

__________________________________________________________________

2. Reference Name: _____________________ Contact Person:_______________

Address: _____________________________ Tel Number:________________

Description and Dates Services Provided: ________________________

____________________________________________________________________________________

____________________________________________________________________________________

__________________________________________________________________

3. Reference Name:______________________ Contact Person:_______________

Address:_____________________________ Tel Number:________________

Description and Dates of Services Provided: ________________________

____________________________________________________________________________________

____________________________________________________________________________________

__________________________________________________________________

Must list all jobs performed in a similar scope in the past 3 years. References will be contacted to

confirm Bidder’s abilities, qualifications and performance. The University may deem the Bidder’s

response unresponsive if a reference is not obtainable from listed reference after reasonable attempts.

Page 7: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

CL16-HT-0037 Pre-Purchase Emergency Generator Page 7

ATTACHMENT A

BID FORM – BID # CL16-HT-0037

UNIVERSITY OF MASSACHUSETTS LOWELL

Pricing:

Emergency Generator System with accessories $___________

$___________

TOTAL PRICE $___________

*Total Price must include the delivery and warranty as stated in the bid*

The Bid includes Addenda numbered ________________

In addition to the bid amounts stated above, we agree to abide by all the terms and

conditions set out in the Bid.

_______________________________________________

Vendor

_______________________________________________

Address

_______________________________________________

The awarding Contractor must agree to comply with all applicable Prevailing Wage Rates. By signing this form, the Contractor agrees to pay the applicable Prevailing Wage Rate.

Page 8: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

CL16-HT-0037 Pre-Purchase Emergency Generator Page 8

VENDOR BIDDER CHECK LIST

AS A QUALIFIED BIDDER, HAVE YOU INCLUDED:

____ Company information and signature

____ Certificate of non-collusion and tax compliance

____ Business Reference

____ Completed Form for General Bid Attachment A

____ Bids must be delivered No later than 11:00 AM EST., Monday December 14, 2015. Bids

received after this date and time will not be accepted.

Page 9: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

North Quad Infrastructure Renewal ICON architecture, inc.UMass Lowell, Lowell, MA September 17, 2015UMBA Project No. UMBA 13-L2

ENGINE GENERATORS 263213 - 1

SECTION 263213 - ENGINE GENERATORS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and SupplementaryConditions and Division 01 Specification Sections, apply to this Section.

B. UMass Lowell Campus Electrical Standards; request most up to date standards at time of bid.

1.2 SUMMARY

A. This Section includes packaged engine-generator sets for [emergency] power supply with thefollowing features:

1. [Diesel] engine.2. [Unit-mounted] cooling system.3. [Unit-mounted] control and monitoring.4. Load banks.5. Outdoor enclosure.

B. Related Sections include the following:

1. Section 263214 “Installation of Engine Generators” for installation requirements ofowner furnished contractor installed engine generators.

2. Section 263600 "Transfer Switches" for transfer switches including sensors and relays toinitiate automatic-starting and -stopping signals for engine-generator sets.

1.3 DEFINITIONS

A. Operational Bandwidth: The total variation from the lowest to highest value of a parameterover the range of conditions indicated, expressed as a percentage of the nominal value of theparameter.

1.4 ACTION SUBMITTALS

A. Product Data: For each type of packaged engine generator indicated. Include rated capacities,operating characteristics, and furnished specialties and accessories. In addition, include thefollowing:

1. Thermal damage curve for generator.2. Time-current characteristic curves for generator protective device.

Page 10: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

North Quad Infrastructure Renewal ICON architecture, inc.UMass Lowell, Lowell, MA September 17, 2015UMBA Project No. UMBA 13-L2

ENGINE GENERATORS 263213 - 2

B. Shop Drawings: Detail equipment assemblies and indicate dimensions, weights, loads, requiredclearances, method of field assembly, components, and location and size of each fieldconnection.

1. Dimensioned outline plan and elevation drawings of engine-generator set and othercomponents specified.

2. Design Calculations: Signed and sealed by a qualified professional engineer. Calculaterequirements for selecting vibration isolators and for designing vibration isolation bases.

3. Vibration Isolation Base Details: Signed and sealed by a qualified professional engineer.Detail fabrication, including anchorages and attachments to structure and to supportedequipment. Include base weights.

4. Wiring Diagrams: Power, signal, and control wiring.

1.5 INFORMATIONAL SUBMITTALS

A. Qualification Data: For [manufacturer]

B. Source quality-control test reports.1. Certified Summary of Performance Tests: Certify compliance with specified requirement

to meet performance criteria for sensitive loads.2. Report of factory test on units to be shipped for this Project, showing evidence of

compliance with specified requirements.3. Report of sound generation.4. Report of exhaust emissions showing compliance with applicable regulations.

C. Field quality-control test reports.

D. Warranty: Special warranty specified in this Section.

1.6 CLOSEOUT SUBMITTALS

A. Operation and Maintenance Data: For packaged engine generators to include in emergency,operation, and maintenance manuals. In addition to items specified in Section 011000"Operation and Maintenance Data," include the following:

1. List of tools and replacement items recommended to be stored at Project for ready access.Include part and drawing numbers, current unit prices, and source of supply.

1.7 MAINTENANCE MATERIAL SUBMITTALS

A. Furnish extra materials described below that match products installed and that are packagedwith protective covering for storage and identified with labels describing contents.

1. Fuses: One for every 10 of each type and rating, but no fewer than one of each.2. Indicator Lamps: Two for every six of each type used, but no fewer than two of each.3. Filters: One set each of lubricating oil, fuel, and combustion-air filters.

Page 11: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

North Quad Infrastructure Renewal ICON architecture, inc.UMass Lowell, Lowell, MA September 17, 2015UMBA Project No. UMBA 13-L2

ENGINE GENERATORS 263213 - 3

1.8 QUALITY ASSURANCE

A. Installer Qualifications: Manufacturer's authorized representative who is trained and approvedfor installation of units required for this Project.

1. Maintenance Proximity: Not more than [four] hours' normal travel time from Installer'splace of business to Project site.

2. Engineering Responsibility: Preparation of data for vibration isolators restraints ofengine skid mounts, including Shop Drawings, based on testing and engineering analysisof manufacturer's standard units in assemblies similar to those indicated for this Project.

B. Manufacturer Qualifications: A qualified manufacturer. Maintain, within [200 miles (321 km)]of Project site, a service center capable of providing training, parts, and emergency maintenancerepairs.

C. Source Limitations: Obtain packaged generator sets and auxiliary components through onesource from a single manufacturer.

D. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked forintended use.

E. Comply with ASME B15.1.

F. Comply with NFPA 37.

G. Comply with NFPA 70.

H. Comply with NFPA 110 requirements for Level [1] emergency power supply system.

I. Comply with UL 2200.

J. Engine Exhaust Emissions: Comply with applicable state and local government requirements.

K. Noise Emission: Comply with [applicable state and local government requirements] formaximum allowable sound level at property line due to sound emitted by generator setincluding engine, engine exhaust, engine cooling-air intake and discharge, and othercomponents of installation.

1.9 PROJECT CONDITIONS

A. Interruption of Existing Electrical Service: Do not interrupt electrical service to facilitiesoccupied by Owner or others unless permitted under the following conditions and then onlyafter arranging to provide temporary electrical service according to requirements indicated:

1. Notify [Construction Manager] no fewer than [seven] days in advance of proposedinterruption of electrical service.

2. Do not proceed with interruption of electrical service without [Construction Manager's]written permission.

Page 12: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

North Quad Infrastructure Renewal ICON architecture, inc.UMass Lowell, Lowell, MA September 17, 2015UMBA Project No. UMBA 13-L2

ENGINE GENERATORS 263213 - 4

B. Environmental Conditions: Engine-generator system shall withstand the followingenvironmental conditions without mechanical or electrical damage or degradation ofperformance capability:1. Altitude: Sea level to [1000 feet (300 m)]

1.10 COORDINATION

A. Coordinate size and location of concrete bases for package engine generators. Cast anchor-boltinserts into bases. Concrete, reinforcement, and formwork requirements are specified withconcrete.

1.11 WARRANTY

A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair orreplace components of packaged engine generators and associated auxiliary components thatfail in materials or workmanship within specified warranty period.

1. Warranty Period: two years from date of Substantial Completion.

1.12 MAINTENANCE SERVICE

A. Initial Maintenance Service: Beginning at Substantial Completion, provide [24] months' fullmaintenance by skilled employees of manufacturer's designated service organization. Includequarterly exercising to check for proper starting, load transfer, and running under load. Includeroutine preventive maintenance as recommended by manufacturer and adjusting as required forproper operation. Provide parts and supplies same as those used in the manufacture andinstallation of original equipment.

1.13 ADDITIONAL SITE VISIT UPON GENERATOR INSTALLATION

A. This generator unit will be purchased by the owner for installation by others. This generator willform part of an NEC article 700 listed life safety power system, and as such requires selectivecoordination between all life safety circuit breakers. Include cost to return to the site post installand adjust and reprogram the generator controller, and electronic trip output circuit breakersettings based on the outcome of the contractors overcurrent selective coordination study. Inadditional to a return visit, the generator vendor shall provide the electrical contractor who willbe installing the generator, all information required to include the generator system in a powerflow study to determine selective coordination settings.

Page 13: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

North Quad Infrastructure Renewal ICON architecture, inc.UMass Lowell, Lowell, MA September 17, 2015UMBA Project No. UMBA 13-L2

ENGINE GENERATORS 263213 - 5

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Manufacturers: Subject to compliance with requirements, provide products by one of thefollowing:

1. Caterpillar; Engine Div.2. Generac Power Systems, Inc.3. Kohler Co.

2.2 ENGINE-GENERATOR SET

A. Factory-assembled and -tested, engine-generator set.

B. Mounting Frame: Maintain alignment of mounted components without depending on concretefoundation; and have lifting attachments.

1. Rigging Diagram: Inscribed on metal plate permanently attached to mounting frame toindicate location and lifting capacity of each lifting attachment and generator-set centerof gravity.

C. Capacities and Characteristics:

1. Power Output Ratings: Nominal ratings as indicated – 200kW.2. Output Connections: Three-phase, [four] wire.3. Nameplates: For each major system component to identify manufacturer's name and

address, and model and serial number of component.

D. Generator-Set Performance:

1. Steady-State Voltage Operational Bandwidth: 3 percent of rated output voltage from noload to full load.

2. Transient Voltage Performance: Not more than 20 percent variation for 50 percent step-load increase or decrease. Voltage shall recover and remain within the steady-stateoperating band within three seconds.

3. Steady-State Frequency Operational Bandwidth: 0.5 percent of rated frequency from noload to full load.

4. Steady-State Frequency Stability: When system is operating at any constant load withinthe rated load, there shall be no random speed variations outside the steady-stateoperational band and no hunting or surging of speed.

5. Transient Frequency Performance: Less than 5 percent variation for 50 percent step-loadincrease or decrease. Frequency shall recover and remain within the steady-stateoperating band within five seconds.

6. Output Waveform: At no load, harmonic content measured line to line or line to neutralshall not exceed 5 percent total and 3 percent for single harmonics. Telephone influencefactor, determined according to NEMA MG 1, shall not exceed 50 percent.

H40014
Highlight
Page 14: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

North Quad Infrastructure Renewal ICON architecture, inc.UMass Lowell, Lowell, MA September 17, 2015UMBA Project No. UMBA 13-L2

ENGINE GENERATORS 263213 - 6

7. Sustained Short-Circuit Current: For a 3-phase, bolted short circuit at system outputterminals, system shall supply a minimum of 250 percent of rated full-load current for notless than 10 seconds and then clear the fault automatically, without damage to generatorsystem components.

8. Start Time: Comply with NFPA 110, Type 10, system requirements.

a. Provide permanent magnet excitation for power source to voltage regulator.

9. Start Time: Comply with NFPA 110, Type 10, system requirements.

2.3 ENGINE

A. Fuel: [Fuel oil, Grade DF-2, Ultra Low Sulfer 15PPM]

B. Rated Engine Speed: 1800 rpm.

C. Maximum Piston Speed for Four-Cycle Engines: 2250 fpm (11.4 m/s).

D. Lubrication System: The following items are mounted on engine or skid:

1. Filter and Strainer: Rated to remove 90 percent of particles 5 micrometers and smallerwhile passing full flow.

2. Thermostatic Control Valve: Control flow in system to maintain optimum oiltemperature. Unit shall be capable of full flow and is designed to be fail-safe.

3. Crankcase Drain: Arranged for complete gravity drainage to an easily removablecontainer with no disassembly and without use of pumps, siphons, special tools, orappliances.

E. Engine Fuel System:

1. Main Fuel Pump: Mounted on engine. Pump ensures adequate primary fuel flow understarting and load conditions.

2. Relief-Bypass Valve: Automatically regulates pressure in fuel line and returns excessfuel to source.

F. Coolant Jacket Heater: Electric-immersion type, factory installed in coolant jacket system.Comply with NFPA 110 requirements for Level 1 equipment for heater capacity.

G. Governor: [Electronic].

H. Cooling System: Closed loop, liquid cooled, with radiator factory mounted on engine-generator-set mounting frame and integral engine-driven coolant pump.

1. Coolant: Solution of 50 percent ethylene-glycol-based antifreeze and 50 percent water,with anticorrosion additives as recommended by engine manufacturer.

2. Size of Radiator: Adequate to contain expansion of total system coolant from cold startto 110 percent load condition.

3. Expansion Tank: Constructed of welded steel plate and rated to withstand maximumclosed-loop coolant system pressure for engine used. Equip with gage glass and petcock.

Page 15: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

North Quad Infrastructure Renewal ICON architecture, inc.UMass Lowell, Lowell, MA September 17, 2015UMBA Project No. UMBA 13-L2

ENGINE GENERATORS 263213 - 7

4. Temperature Control: Self-contained, thermostatic-control valve modulates coolant flowautomatically to maintain optimum constant coolant temperature as recommended byengine manufacturer.

5. Coolant Hose: Flexible assembly with inside surface of nonporous rubber and outercovering of aging-, ultraviolet-, and abrasion-resistant fabric.

a. Rating: 50-psig (345-kPa) maximum working pressure with coolant at 180 deg F(82 deg C), and noncollapsible under vacuum.

b. End Fittings: Flanges or steel pipe nipples with clamps to suit piping andequipment connections.

I. Muffler/Silencer: Critical type, sized as recommended by engine manufacturer and selectedwith exhaust piping system to not exceed engine manufacturer's engine backpressurerequirements.

1. Minimum sound attenuation of 25 dB at 500 Hz.2. Sound level measured at a distance of 23 feet (7 m) from exhaust discharge after

installation is complete shall be [71] dBA or less.3. Provide flanged connector for connection of exhaust piping by another project. Intent is

for exhaust to discharge 10’ above roofline. Provide details on how to connect additionalexhaust piping with generator submittal.

J. Air-Intake Filter: [Heavy]-duty, engine-mounted air cleaner with replaceable dry-filter elementand "blocked filter" indicator.

K. Starting System: [24]-V electric, with negative ground.

1. Components: Sized so they will not be damaged during a full engine-cranking cycle withambient temperature at maximum specified in Part 1 "Project Conditions" Article.

2. Cranking Motor: Heavy-duty unit that automatically engages and releases from engineflywheel without binding.

3. Cranking Cycle: [As required by NFPA 110 for system level specified].4. Battery: Adequate capacity within ambient temperature range specified in Part 1 "Project

Conditions" Article to provide specified cranking cycle at least [three times] withoutrecharging.

5. Battery Cable: Size as recommended by engine manufacturer for cable length indicated.Include required interconnecting conductors and connection accessories.

6. Battery Compartment: Factory fabricated of metal with acid-resistant finish and thermalinsulation. Thermostatically controlled heater shall be arranged to maintain battery above10 deg C regardless of external ambient temperature within range specified in Part 1"Project Conditions" Article. Include accessories required to support and fasten batteriesin place.

7. Battery-Charging Alternator: Factory mounted on engine with solid-state voltageregulation and 35-A minimum continuous rating.

8. Battery Charger: Current-limiting, automatic-equalizing and float-charging type. Unitshall comply with UL 1236 and include the following features:

a. Operation: Equalizing-charging rate of 10 A shall be initiated automatically afterbattery has lost charge until an adjustable equalizing voltage is achieved at battery

Page 16: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

North Quad Infrastructure Renewal ICON architecture, inc.UMass Lowell, Lowell, MA September 17, 2015UMBA Project No. UMBA 13-L2

ENGINE GENERATORS 263213 - 8

terminals. Unit shall then be automatically switched to a lower float-chargingmode and shall continue to operate in that mode until battery is discharged again.

b. Automatic Temperature Compensation: Adjust float and equalize voltages forvariations in ambient temperature from minus 40 deg C to plus 60 deg C to preventovercharging at high temperatures and undercharging at low temperatures.

c. Automatic Voltage Regulation: Maintain constant output voltage regardless ofinput voltage variations up to plus or minus 10 percent.

d. Ammeter and Voltmeter: Flush mounted in door. Meters shall indicate chargingrates.

e. Safety Functions: Sense abnormally low battery voltage and close contactsproviding low battery voltage indication on control and monitoring panel. Sensehigh battery voltage and loss of ac input or dc output of battery charger. Eithercondition shall close contacts that provide a battery-charger malfunction indicationat system control and monitoring panel.

f. Enclosure and Mounting: NEMA 250, Type 1, wall-mounted cabinet.

2.4 FUEL OIL STORAGE

A. Comply with NFPA 30.

B. Base-Mounted Fuel Oil Tank: Factory installed and piped, complying with UL 142 fuel oiltank. Features include the following:

1. Tank level indicator.2. Capacity: Fuel for [24] hours' continuous operation at 100 percent rated power output.3. Vandal-resistant fill cap.4. Containment Provisions: Comply with requirements of authorities having jurisdiction.5. The fuel tank shall be a double-walled, steel construction, and include leak detection

provisions, wired to the generator set controller for local and remote alarm indication.6. The fuel tank shall be constructed of high strength carbon steel.

2.5 CONTROL AND MONITORING

A. Automatic Starting System Sequence of Operation: When mode-selector switch on the controland monitoring panel is in the automatic position, remote-control contacts in one or moreseparate automatic transfer switches initiate starting and stopping of generator set. When mode-selector switch is switched to the on position, generator set starts. The off position of sameswitch initiates generator-set shutdown. When generator set is running, specified system orequipment failures or derangements automatically shut down generator set and initiate alarms.Operation of a remote emergency-stop switch also shuts down generator set.

B. Configuration: Operating and safety indications, protective devices, basic system controls, andengine gages shall be grouped in a common wall-mounted control and monitoring panel locatedin the main Pod 2 electrical room.

C. Indicating and Protective Devices and Controls: As required by NFPA 110 for Level [1]system, and the following:

H40014
Highlight
Page 17: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

North Quad Infrastructure Renewal ICON architecture, inc.UMass Lowell, Lowell, MA September 17, 2015UMBA Project No. UMBA 13-L2

ENGINE GENERATORS 263213 - 9

1. AC voltmeter.2. AC ammeter.3. AC frequency meter.4. DC voltmeter (alternator battery charging).5. Engine-coolant temperature gage.6. Engine lubricating-oil pressure gage.7. Running-time meter.8. Ammeter-voltmeter, phase-selector switch(es).9. Generator-voltage adjusting rheostat.10. Fuel tank high-level shutdown of fuel supply alarm.11. Generator overload.

D. Supporting Items: Include sensors, transducers, terminals, relays, and other devices and includewiring required to support specified items. Locate sensors and other supporting items on engineor generator, unless otherwise indicated.

E. Connection to Data Link: A separate terminal block, factory wired to Form C dry contacts, foreach alarm and status indication is reserved for connections for data-link transmission ofindications to remote data terminals.

F. Common Remote Audible Alarm: Comply with NFPA 110 requirements for Level 1 systems.Include necessary contacts and terminals in control and monitoring panel.

1. Overcrank shutdown.2. Coolant low-temperature alarm.3. Control switch not in auto position.4. Battery-charger malfunction alarm.5. Battery low-voltage alarm.

G. Remote Emergency-Stop Switch: Flush; wall mounted, unless otherwise indicated; and labeled.Push button shall be protected from accidental operation.

2.6 GENERATOR OVERCURRENT AND FAULT PROTECTION

A. Generator Circuit Breaker: Molded-case, electronic-trip type; 100 percent rated; complyingwith UL 489.

1. Tripping Characteristics: Adjustable long-time, short-time delay and instantaneous.2. Trip Settings: Selected to coordinate with generator thermal damage curve.3. Shunt Trip: Connected to trip breaker when generator set is shut down by other

protective devices.4. Mounting: Adjacent to or integrated with control and monitoring panel.

B. Generator Disconnect Switch: Molded-case type, 100 percent rated.

1. Rating: Matched to generator output rating.2. Shunt Trip: Connected to trip switch when signaled by generator protector or by other

protective devices.

Page 18: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

North Quad Infrastructure Renewal ICON architecture, inc.UMass Lowell, Lowell, MA September 17, 2015UMBA Project No. UMBA 13-L2

ENGINE GENERATORS 263213 - 10

C. Generator Protector: Microprocessor-based unit shall continuously monitor current level ineach phase of generator output, integrate generator heating effect over time, and predict whenthermal damage of alternator will occur. When signaled by generator protector or othergenerator-set protective devices, a shunt-trip device in the generator disconnect switch shallopen the switch to disconnect the generator from load circuits. Protector shall perform thefollowing functions:

1. Initiates a generator overload alarm when generator has operated at an overloadequivalent to 110 percent of full-rated load for 60 seconds. Indication for this alarm isintegrated with other generator-set malfunction alarms.

2. Under single or three-phase fault conditions, regulates generator to 300 percent of ratedfull-load current for up to 10 seconds.

3. As overcurrent heating effect on the generator approaches the thermal damage point ofthe unit, protector switches the excitation system off, opens the generator disconnectdevice, and shuts down the generator set.

4. Senses clearing of a fault by other overcurrent devices and controls recovery of ratedvoltage to avoid overshoot.

2.7 GENERATOR, EXCITER, AND VOLTAGE REGULATOR

A. Comply with NEMA MG 1.

B. Drive: Generator shaft shall be directly connected to engine shaft. Exciter shall be rotatedintegrally with generator rotor.

C. Electrical Insulation: Class H or Class F.

D. Stator-Winding Leads: Brought out to terminal box to permit future reconnection for othervoltages if required.

E. Construction shall prevent mechanical, electrical, and thermal damage due to vibration,overspeed up to 125 percent of rating, and heat during operation at 110 percent of ratedcapacity.

F. Enclosure: Dripproof.

G. Instrument Transformers: Mounted within generator enclosure.

H. Voltage Regulator: Solid-state type, separate from exciter, providing performance as specified.

1. Adjusting rheostat on control and monitoring panel shall provide plus or minus 5 percentadjustment of output-voltage operating band.

I. Strip Heater: Thermostatically controlled unit arranged to maintain stator windings above dewpoint.

Page 19: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

North Quad Infrastructure Renewal ICON architecture, inc.UMass Lowell, Lowell, MA September 17, 2015UMBA Project No. UMBA 13-L2

ENGINE GENERATORS 263213 - 11

2.8 LOAD BANK

A. Description: Permanent, outdoor, weatherproof, remote-controlled, forced-air-cooled, [resistiveand reactive] unit capable of providing a balanced 3-phase, delta-connected load to generatorset at [50] percent rated-system capacity, at [80] percent power factor, lagging. Unit may becomposed of separate resistive and reactive load banks controlled by a common control panel.Unit shall be capable of selective control of load in 25 percent steps and with minimum stepchanges of approximately 5 and 10 percent available.

B. Resistive Load Elements: Corrosion-resistant chromium alloy with ceramic and steel supports.Elements shall be double insulated and designed for repetitive on-off cycling. Elements shall bemounted in removable aluminized-steel heater cases.

C. Reactive Load Elements: Epoxy-encapsulated reactor coils.

D. Load-Bank Heat Dissipation: Integral fan with totally enclosed motor shall provide uniformcooling airflow through load elements. Airflow and coil operating current shall be such that, atmaximum load, with ambient temperature at the upper end of specified range, load-bankelements operate at not more than 50 percent of maximum continuous temperature rating ofresistance elements.

E. Load Element Switching: Remote-controlled contactors switch groups of load elements.Contactor coils are rated 120 V. Contactors shall be located in a separate NEMA 250, Type 3Renclosure within load-bank enclosure, accessible from exterior through hinged doors withtumbler locks.

F. Contactor Enclosures: Heated by thermostatically controlled strip heaters to preventcondensation.

G. Load-Bank Enclosures: NEMA 250, Type 3R, complying with NEMA ICS 6. Louvers atcooling-air intake and discharge openings shall prevent entry of rain and snow. Openings forairflow shall be screened with 1/2-inch- (13-mm-) square, galvanized-steel mesh. Reactive loadbank shall include automatic shutters at air intake and discharge.

H. Protective Devices: Power input circuits to load banks shall be fused, and fuses shall beselected to coordinate with generator circuit breaker. Fuse blocks shall be located in contactorenclosure. Cooling airflow and overtemperature sensors shall automatically shut down and lockout load bank until manually reset. Safety interlocks on access panels and doors shalldisconnect load power, control, and heater circuits. Fan motor shall be separately protected byoverload and short-circuit devices. Short-circuit devices shall be noninterchangeable fuses with200,000-A interrupting capacity.

I. Remote-Control Panel: Separate from load bank in NEMA 250, Type 1 enclosure with acontrol power switch and pilot light, and switches controlling groups of load elements.

J. Control Sequence: Control panel may be preset for adjustable single-step loading of generatorduring automatic exercising.

Page 20: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

North Quad Infrastructure Renewal ICON architecture, inc.UMass Lowell, Lowell, MA September 17, 2015UMBA Project No. UMBA 13-L2

ENGINE GENERATORS 263213 - 12

2.9 OUTDOOR GENERATOR-SET ENCLOSURE

A. Description: Vandal-resistant, weatherproof steel housing, wind resistant up to 100 mph (160km/h). Multiple panels shall be lockable and provide adequate access to components requiringmaintenance. Panels shall be removable by one person without tools. Instruments and controlshall be mounted within enclosure.

B. Description: Prefabricated or preengineered enclosure with the following features:

1. Construction: Galvanized-steel, metal-clad, integral structural-steel-framed buildingerected on concrete foundation.

2. Structural Design and Anchorage: Comply with ASCE 7 for wind loads.3. Space Heater: Thermostatically controlled and sized to prevent condensation.4. Louvers: Equipped with bird screen and filter arranged to permit air circulation when

engine is not running while excluding exterior dust, birds, and rodents.5. Hinged Doors: With padlocking provisions.6. Ventilation: Louvers equipped with bird screen and filter arranged to permit air

circulation while excluding exterior dust, birds, and rodents.7. Thermal Insulation: Manufacturer's standard materials and thickness selected in

coordination with space heater to maintain winter interior temperature within operatinglimits required by engine-generator-set components.

8. Muffler Location: [External to] enclosure.

C. Engine Cooling Airflow through Enclosure: Maintain temperature rise of system componentswithin required limits when unit operates at 110 percent of rated load for 2 hours with ambienttemperature at top of range specified in system service conditions.

1. Louvers: Fixed-engine, cooling-air inlet and discharge. Storm-proof and drainablelouvers prevent entry of rain and snow.

2. Automatic Dampers: At engine cooling-air inlet and discharge. Dampers shall be closedto reduce enclosure heat loss in cold weather when unit is not operating.

D. Convenience Outlets: Factory wired[, GFCI]. Arrange for external electrical connection.

2.10 VIBRATION ISOLATION DEVICES

A. Elastomeric Isolation Pads:

1. Manufacturers: Subject to compliance with requirements, [available manufacturersoffering products that may be incorporated into the Work include, but are notlimited to, the following]:

a. Ace Mountings Co., Inc.b. California Dynamics Corporation.c. Isolation Technology, Inc.d. Kinetics Noise Control, Inc.e. Mason Industries, Inc.f. Vibration Eliminator Co., Inc.g. Vibration Isolation.

Page 21: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

North Quad Infrastructure Renewal ICON architecture, inc.UMass Lowell, Lowell, MA September 17, 2015UMBA Project No. UMBA 13-L2

ENGINE GENERATORS 263213 - 13

h. Vibration Mountings & Controls, Inc.

2. Fabrication: Single or multiple layers of sufficient durometer stiffness for uniformloading over pad area.

3. Size: Factory or field cut to match requirements of supported equipment.4. Pad Material: Oil and water resistant with elastomeric properties.5. Surface Pattern: [Smooth] [Ribbed] [Waffle] pattern.6. Infused nonwoven cotton or synthetic fibers.7. Load-bearing metal plates adhered to pads.8. Sandwich-Core Material: [Resilient] [and] [elastomeric]

a. Surface Pattern: [Smooth] [Ribbed] [Waffle] pattern.b. Infused nonwoven cotton or synthetic fibers.

B. Restrained Spring Isolators: Freestanding, Steel, Open-Spring Isolators with Vertical-LimitStop Restraint in Two-Part Telescoping Housing:

1. Manufacturers: Subject to compliance with requirements, [available manufacturersoffering products that may be incorporated into the Work include, but are notlimited to, the following]:

a. Ace Mountings Co., Inc.b. California Dynamics Corporation.c. Isolation Technology, Inc.d. Kinetics Noise Control, Inc.e. Mason Industries, Inc.f. Vibration Eliminator Co., Inc.g. Vibration Isolation.h. Vibration Mountings & Controls, Inc.

2. Two-Part Telescoping Housing: A steel top and bottom frame separated by anelastomeric material and enclosing the spring isolators. Housings are equipped with[adjustable] snubbers to limit vertical movement.

a. Drilled base housing for bolting to structure with an elastomeric isolator padattached to the underside. Bases shall limit floor load to 500 psig (3447 kPa).

b. Threaded top housing with adjustment bolt and cap screw to fasten and levelequipment.

3. Outside Spring Diameter: Not less than 80 percent of the compressed height of thespring at rated load.

4. Minimum Additional Travel: 50 percent of the required deflection at rated load.5. Lateral Stiffness: More than 80 percent of rated vertical stiffness.6. Overload Capacity: Support 200 percent of rated load, fully compressed, without

deformation or failure.

Page 22: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

North Quad Infrastructure Renewal ICON architecture, inc.UMass Lowell, Lowell, MA September 17, 2015UMBA Project No. UMBA 13-L2

ENGINE GENERATORS 263213 - 14

2.11 FINISHES

A. Indoor and Outdoor Enclosures and Components: Manufacturer's standard finish overcorrosion-resistant pretreatment and compatible primer.

2.12 SOURCE QUALITY CONTROL

A. Prototype Testing: Factory test engine-generator set using same engine model, constructed ofidentical or equivalent components and equipped with identical or equivalent accessories.

1. Tests: Comply with NFPA 110, Level 1 Energy Converters and with IEEE 115.

B. Project-Specific Equipment Tests: Before shipment, factory test engine-generator set and othersystem components and accessories manufactured specifically for this Project. Perform tests atrated load and power factor. Include the following tests:

1. Test components and accessories furnished with installed unit that are not identical tothose on tested prototype to demonstrate compatibility and reliability.

2. Full load run.3. Maximum power.4. Voltage regulation.5. Transient and steady-state governing.6. Single-step load pickup.7. Safety shutdown.8. Provide 14 days' advance notice of tests and opportunity for observation of tests by

Owner's representative.9. Report factory test results within 10 days of completion of test.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine areas, equipment bases, and conditions, with Installer present, for compliance withrequirements for installation and other conditions affecting packaged engine-generatorperformance.

B. Examine roughing-in of piping systems and electrical connections. Verify actual locations ofconnections before packaged engine-generator installation.

C. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 DEMONSTRATION

A. Engage a factory-authorized service representative to train Owner's maintenance personnel toadjust, operate, and maintain packaged engine generators. Refer to Section 017900"Demonstration and Training."

Page 23: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

North Quad Infrastructure Renewal ICON architecture, inc.UMass Lowell, Lowell, MA September 17, 2015UMBA Project No. UMBA 13-L2

ENGINE GENERATORS 263213 - 15

3.3 FUEL

A. Provide all fuel required for testing.

B. Hand over generator system to owner after all acceptance testing is complete with all generatorfuel tanks fully filled.

3.4 RETURN VISIT POST INSTALL

A. Generator vendor shall return to site post installation by the electrical contractor. The vendorshall adjust the generator controller and output circuit breakers to selectively coordinate thegenerator circuit breaker with the rest of the life safety system, as per NEC article 700requirements. Where the provided circuit breaker cannot be coordinated with the emergencypower system, the generator vendor shall work with the electrical contractor to find a suitablecircuit breaker, and shall replace the breaker on the unit with no additional labor cost. Thecircuit breaker, where required, shall be furnished by the project electrical contractor.

END OF SECTION 263213

Page 24: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

100% CONSTRUCTION DOCUMENT SETJULY 17, 2015

CLIENTUniversity of Massachusetts Building Authority (UMBA)225 Franklin Street, 12th FloorBoston, MA 02110

University of Massachusetts Lowell (UML)600 Suffolk Street, Suite 450Lowell, MA 01854

OWNER'S PROJECT MANAGERHill International330 Congress Street, 6th FloorBoston, MA 02210

OPM'S CODE CONSULTANTHughes Associates, Inc.5 Mount Royal Avenue, Suite 240Marlborough, MA 01752

ARCHITECTICON architecture, inc.101 Summer StreetBoston, MA 02110

CIVIL ENGINEER/SURVEYORNitsch Engineering2 Center Plaza, Suite 430Boston, MA 02108

GEOTECHNICAL ENGINEERHaley & Aldrich465 Medford Street, Suite 2200Charlestown, MA 02129

STRUCTURAL ENGINEERLim Consultants, Inc.6 Pleasant Street, Suite 520Malden, MA 02148

MEP/FP ENGINEERARUP USA, Inc.955 Massachusetts AvenueCambridge, MA 02139

BUILDING CODE CONSULTANTCosentini Associates, Inc.Building 200, 2nd FloorOne Kendall SquareCambridge, MA 02139

COST ESTIMATING CONSULTANTV.J. Associates of New England, Inc.60 Dedham AvenueNeedham, MA 02492

HARDWARE CONSULTANTASSA ABLOY110 Sargent DriveNew Haven, CT 06511

SPECIFICATIONS WRITERKalin Associates, Inc.1121 Washington StreetNewton, MA 02465

SHEET TITLE

LOCUS PLAN CAMPUS PLAN

RIVERSIDE

UN

IVE

RS

ITY

VFW HIGHWAY

(UMBA 13-L2)

7/20

/201

5 2:

57:4

9 P

M

UMass Lowell North QuadInfrastructure RenewalLowell, MA

G-001

COVER SHEET

NN

Page 25: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

ARCHITECT

CONSULTANT

STAMP

MARK DATE DESCRIPTION

PROJECT NUMBER:DRAWN BY:CHECKED BY:

SHEET TITLE

RD

JM

100% CONSTRUCTIONDOCUMENTS SET

06/10/14 FEASIBILITY STUDY SET

08/29/14 SCHEMATIC DESIGN SET

(UMBA 13-L2)

12/18/14 50% DESIGN DEVELOPMENT SET

01/15/15 100% DESIGN DEVELOPMENT SET

04/06/15 60% CONSTRUCTION PERMIT SET

04/22/15 TIER 1 PHASE 1 (EARLY PACKAGE)PERMIT SET

05/07/15 90% CONSTRUCT. DOC. SET

06/30/15 TIER 1 PHASE 1 PERMIT SET

7/17/15 100% CONSTRUCT. DOC. SET

7/20

/201

5 2:

57:5

0 P

M

G-002

DRAWING LIST

UMass Lowell NorthQuad Infrastructure

Renewal

21332

Lowell, MA

University of Massachusetts Building AuthorityUniversity of Massachusetts Lowell

FA-402 FIRE ALARM LEVEL 1 - KEY PLANFA-403 FIRE ALARM LEVEL 1.5 - KEY PLANFA-404 FIRE ALARM LEVEL 2 - KEY PLANFA-405 FIRE ALARM LEVEL 3 - KEY PLANFA-406 FIRE ALARM LEVEL 4 - KEY PLANFA-701 FIRE ALARM POD 1 ENLARGED FLOOR PLANS - LEVEL 1FA-702 FIRE ALARM POD 1 ENLARGED FLOOR PLANS - LEVEL 1.5FA-703 FIRE ALARM POD 1 ENLARGED FLOOR PLANS - LEVEL 2FA-704 FIRE ALARM POD 1 ENLARGED FLOOR PLANS - LEVEL 3FA-705 FIRE ALARM POD 1 ENLARGED FLOOR PLANS - LEVEL 4FA-707 FIRE ALARM POD 2 ENLARGED FLOOR PLANS - LEVEL 1 (KITSON

HALL)FA-710 FIRE ALARM POD 2 ENLARGED FLOOR PLANS - LEVEL 2FA-711 FIRE ALARM POD 2 ENLARGED FLOOR PLANS - LEVEL 3FA-800 FIRE ALARM DETAILS SHEET 1FA-801 FIRE ALARM DETAILS SHEET 2FP-000 FIRE PROTECTION SYMBOLS & ABBREVIATIONSFP-201 FIRE PROTECTION LEVEL 1 DEMOLITION PLANFP-300 FIRE PROTECTION RISER DIAGRAMFP-400 FIRE PROTECTION LEVEL 1 - KEY PLANFP-403 FIRE PROTECTION LEVEL 1.5 - KEY PLANFP-404 FIRE PROTECTION LEVEL 2 - KEY PLANFP-405 FIRE PROTECTION LEVEL 3 - KEY PLANFP-406 FIRE PROTECTION LEVEL 4 - KEY PLANFP-407 FIRE PROTECTION ROOF - KEY PLANFP-701 FIRE PROTECTION POD 1 ENLARGED FLOOR PLANS - LEVEL 1FP-702 FIRE PROTECTION POD 1 ENLARGED FLOOR PLANS - LEVEL 1.5FP-703 FIRE PROTECTION POD 1 ENLARGED FLOOR PLANS - LEVEL 2FP-704 FIRE PROTECTION POD 1 ENLARGED FLOOR PLANS - LEVEL 3FP-705 FIRE PROTECTION POD 1 ENLARGED FLOOR PLANS - LEVEL 4FP-707 FIRE PROTECTION POD 2 ENLARGED FLOOR PLANS - LEVEL 1

(KITSON HALL)FP-709 FIRE PROTECTION KITSON MEZZ ENLARGED PLANFP-710 FIRE PROTECTION POD 2 ENLARGED FLOOR PLANS - LEVEL 2FP-711 FIRE PROTECTION POD 2 ENLARGED FLOOR PLANS - LEVEL 3FP-800 FIRE PROTECTION DETAILS SHEET 1FP-801 FIRE PROTECTION DETAILS SHEET 2

TELECOMMUNICATIONST-000 TELECOMS SYMBOLS & ABBREVIATIONST-300 TELECOMS RISER ONE LINE DIAGRAMT-402 TELECOMMS LEVEL 1 - KEY PLANT-403 TELECOMMS LEVEL 1.5 - KEY PLANT-404 TELECOMMS LEVEL 2 - KEY PLANT-405 TELECOMMS LEVEL 3 - KEY PLANT-406 TELECOMMS LEVEL 4 - KEY PLANT-701 L TELECOMMS POD 1 ENLARGED FLOOR PLANS - LOW LEVEL 1T-702 H TELECOMMS POD 1 ENLARGED FLOOR PLANS - HIGH LEVEL 1.5T-702 L TELECOMMS POD 1 ENLARGED FLOOR PLANS - LOW LEVEL 1.5T-703 H TELECOMMS POD 1 ENLARGED FLOOR PLANS - HIGH LEVEL 2T-703 L TELECOMMS POD 1 ENLARGED FLOOR PLANS - LOW LEVEL 2T-704 H TELECOMMS POD 1 ENLARGED FLOOR PLANS - HIGH LEVEL 3T-704 L TELECOMMS POD 1 ENLARGED FLOOR PLANS - LOW LEVEL 3T-705 H TELECOMMS POD 1 ENLARGED FLOOR PLANS - HIGH LEVEL 4T-705 L TELECOMMS POD 1 ENLARGED FLOOR PLANS - LOW LEVEL 4T-707 H TELECOMMS POD 2 ENLARGED FLOOR PLANS - HIGH LEVEL 1

(KITSON HALL)T-707 L TELECOMMS POD 2 ENLARGED FLOOR PLANS - LOW LEVEL 1 (KITSON

HALL)T-710 H TELECOMMS POD 2 ENLARGED FLOOR PLANS - HIGH LEVEL 2T-710 L TELECOMMS POD 2 ENLARGED FLOOR PLANS - LOW LEVEL 2T-711 H TELECOMMS POD 2 ENLARGED FLOOR PLANS - HIGH LEVEL 3T-711 L TELECOMMS POD 2 ENLARGED FLOOR PLANS - LOW LEVEL 3T-800 TELECOMMS DETAILS SHEET 1T-801 TELECOMMS DETAILS SHEET 2T-802 TELECOMMS DETAILS SHEET 3

M-711 MECHANICAL POD 2 ENLARGED FLOOR PLANS - LEVEL 3M-712 MECHANICAL POD 2 ENLARGED FLOOR PLANS - ROOFM-801 MECHANICAL DETAILS SHEET 1M-802 MECHANICAL DETAILS SHEET 2M-803 MECHANICAL DETAILS SHEET 3M-901 MECHANICAL CONTROLS SHEET 1M-902 MECHANICAL CONTROLS SHEET 2M-903 MECHANICAL CONTROLS SHEET3

ELECTRICALE-000 ELECTRICAL SYMBOLS & ABBREVIATIONSE-001 ELECTRICAL SCHEDULE OF PANELBOARDSE-002 ELECTRICAL SCHEDULE PLAN SHEET 1E-003 ELECTRICAL SCHEDULE PLAN SHEET 2E-004 ELECTRICAL SCHEDULE PLAN SHEET 3E-005 ELECTRICAL SCHEDULE PLAN SHEET 4E-006 ELECTRICAL SCHEDULE PLAN SHEET 5E-007 ELECTRICAL SCHEDULE PLAN SHEET 6E-008 ELECTRICAL SCHEDULE PLAN SHEET 7E-201 ELECTRICAL POD 1 DEMOLITION PART PLANS - LEVEL 1 & 1.5E-202 ELECTRICAL POD 1 DEMOLITION PART PLANS - LEVEL 2 & 3E-203 ELECTRICAL POD 1 DEMOLITION PART PLANS - LEVEL 4 & ROOFE-204 ELECTRICAL POD 2 DEMOLITION PART PLANS - LEVEL 1 & MEZZE-205 ELECTRICAL POD 2 DEMOLITION PART PLANS - LEVEL 2 & 3E-300 ELECTRICAL RISER ONE LINE DIAGRAME-301 ELECTRICAL RISER TWO LINE DIAGRAME-402 ELECTRICAL LEVEL 1 - KEY PLANE-403 ELECTRICAL LEVEL 1.5 - KEY PLANE-404 ELECTRICAL LEVEL 2 - KEY PLANE-405 ELECTRICAL LEVEL 3 - KEY PLANE-406 ELECTRICAL LEVEL 4 - KEY PLANE-407 ELECTRICAL ROOF - KEY PLANE-701 ELECTRICAL POD 1 ENLARGED FLOOR PLANS - LEVEL 1E-702 ELECTRICAL POD 1 ENLARGED FLOOR PLANS - LEVEL 1.5E-703 ELECTRICAL POD 1 ENLARGED FLOOR PLANS - LEVEL 2E-704 ELECTRICAL POD 1 ENLARGED FLOOR PLANS - LEVEL 3E-705 ELECTRICAL POD 1 ENLARGED FLOOR PLANS - LEVEL 4E-706 ELECTRICAL POD 1 ENLARGED FLOOR PLANS - ROOFE-707 ELECTRICAL POD 2 ENLARGED FLOOR PLANS - LEVEL 1 (KITSON

HALL)E-710 ELECTRICAL POD 2 ENLARGED FLOOR PLANS - LEVEL 2E-711 ELECTRICAL POD 2 ENLARGED FLOOR PLANS - LEVEL 3E-712 ELECTRICAL POD 2 ENLARGED FLOOR PLANS - ROOFE-720 ELECTRICAL POD 1 ENLARGED LIGHTING PLANS - LEVEL 1E-721 ELECTRICAL POD 1 ENLARGED LIGHTING PLANS - LEVEL 1.5E-722 ELECTRICAL POD 1 ENLARGED LIGHTING PLANS - LEVEL 2E-723 ELECTRICAL POD 1 ENLARGED LIGHTING PLANS - LEVEL 3E-724 ELECTRICAL POD 1 ENLARGED LIGHTING PLANS - LEVEL 4E-725 ELECTRICAL POD 2 ENLARGED LIGHTING PLANS - LEVEL 1E-726 ELECTRICAL POD 2 ENLARGED LIGHTING PLANS - LEVELS 2 & 3E-800 ELECTRICAL DETAILS PLAN SHEET 1E-801 ELECTRICAL DETAILS PLAN SHEET 2E-802 ELECTRICAL DETAILS PLAN SHEET 3E-803 ELECTRICAL DETAILS PLAN SHEET 4

PLUMBINGP-000 PLUMBING LEGEND & GENERAL NOTESP-001 PLUMBING SCHEDULESP-201 PLUMBING LEVEL 1 DEMOLITION KEY PLANP-202 PLUMBING POD 1 DEMOLITION PART PLANS - LEVEL 1 & 5P-300 PLUMBING DOMESTIC WATER RISER DIAGRAM - PASTEURP-301 PLUMBING DOMESTIC WTAER RISER DIAGRAM - KITSONP-302 PLUMBING SANTARY RISER DIAGRAM PASTEURP-303 PLUMBING SANTARY RISER DIAGRAM KITSONP-401 PLUMBING BASEMENT - KEY PLANP-402 PLUMBING LEVEL 1 - KEY PLANP-403 PLUMBING LEVEL 1.5 - KEY PLANP-404 PLUMBING LEVEL 2 - KEY PLANP-405 PLUMBING LEVEL 3 - KEY PLANP-406 PLUMBING LEVEL 4 - KEY PLANP-407 PLUMBING ROOF - KEY PLANP-700 PLUMBING POD 1 ENLARGED FLOOR PLANS - BASEMENTP-701 PLUMBING POD 1 ENLARGED FLOOR PLANS - LEVEL 1P-702 PLUMBING POD 1 ENLARGED FLOOR PLANS - LEVEL 1.5P-703 PLUMBING POD 1 ENLARGED FLOOR PLANS - LEVEL 2P-704 PLUMBING POD 1 ENLARGED FLOOR PLANS - LEVEL 3P-705 PLUMBING POD 1 ENLARGED FLOOR PLANS - LEVEL 4P-706 PLUMBING POD 1 ENLARGED FLOOR PLANS - ROOFP-708 PLUMBING, POD 2 UNDERSLABP-709 PLUMBING POD 2 ENLARGED FLOOR PLANS - LEVEL 1P-711 PLUMBING POD 2 ENLARGED FLOOR PLANS - LEVEL 2P-712 PLUMBING POD 2 ENLARGED FLOOR PLANS - LEVEL 3P-713 PLUMBING POD 2 ENLARGED FLOOR PLANS - ROOFP-800 PLUMBING DETAILSP-801 PLUMBING DETAILS

FIRE PROTECTIONFA-000 FIRE ALARM SYMBOLS & ABBREVIATIONSFA-201 FIRE ALARM POD 1 DEMOLITION PARTS PLANS - LEVEL 1 & 1.5FA-204 FIRE ALARM POD 2 DEMOLITION PART PLANS - LEVEL 1 & MEZZFA-300 FIRE ALARM RISER DIAGRAMFA-301 FIRE ALARM SEQUENCE OF OPERATIONS

A-712 POD 1 LEVELS 2-4 PLAN DETAILSA-713 POD 1 LEVELS 2-4 PLAN DETAILSA-714 POD 2 PLAN DETAILSA-715 POD 2 PLAN DETAILSA-716 TYPICAL COMPOSITE METAL PANEL SYSTEM DETAILSA-717 TYPICAL COMPOSITE METAL PANEL SYSTEM DETAILSA-718 COMPOSITE METAL PANEL INFILL DETAILSA-719 TYPICAL CURTAIN WALL DETAILSA-720 TYPICAL CURTAIN HEAD AND SILL DETAILSA-721 TYPICAL CURTAIN JAMB DETAILS @ LEVEL 1.5A-722 TYPICAL EXPANSION JOINT DETAILSA-723 TYPICAL ROOF DETAILSA-724 DOOR DETAILS AT CMP INFILL WALLA-801 DOOR TYPES, SCHEDULE & DETAILSA-802 DOOR TYPES, SCHEDULE & DETAILSA-803 CURTAIN WALL TYPES & SCHEDULEA-804 TYPICAL PARTITION TYPESA-805 TYPICAL PARTITION TYPESA-806 ROOM FINISH SCHEDULE

STRUCTURALS-001 GENERAL NOTESS-002 GENERAL NOTESS-003 TYPICAL CONCRETE DETAILSS-004 TYPICAL CONCRETE DETAILSS-005 TYPICAL CONCRETE DETAILSS-006 TYPICAL CONCRETE DETAILSS-007 TYPICAL CMU DETAILSS-008 TYPICAL CMU DETAILSS-009 TYPICAL STEEL DETAILSS-010 TYPICAL STEEL DETAILSS-011 TYPICAL STEEL DETAILSS-012 TYPICAL STEEL DETAILSS-013 TYPICAL STEEL DETAILSS-101 LEVEL 1 KEY PLANS-102 LEVEL 1.5 KEY PLANS-103 LEVEL 2 KEY PLANS-104 LEVEL 3 KEY PLANS-105 LEVEL 4 KEY PLANS-106 ROOF KEY PLANS-201 COLUMN SCHEDULE POD 1S-202 COLUMN SCHEDULE POD 2S-203 BASE PLATE DETAILSS-204 LATERAL RESISTING FRAME ELEVATIONS POD 1S-205 LATERAL RESISTING FRAME ELEVATIONS POD 2S-206 BRACED FRAME DETAILSS-301 PILASTER DETAILS POD 1S-302 FOUNDATION SECTIONS & DETAILS POD 1S-303 FOUNDATION SECTIONS & DETAILS POD 1S-304 FOUNDATION SECTIONS & DETAILS POD 1S-310 FOUNDATION SECTIONS & DETAILS POD 2S-311 FOUNDATION SECTIONS & DETAILS POD 2S-312 FOUNDATION SECTIONS & DETAILS POD 2S-401 SECTIONS & DETAILSS-402 SECTIONS & DETAILSS-501 POD 1 ENLARGED FRAMING PLAN - LEVEL 1/FOUNDATIONS-502 POD 1 ENLARGED FRAMING PLAN - LEVEL 1.5S-503 POD 1 ENLARGED FRAMING PLAN - LEVEL 2S-504 POD 1 ENLARGED FRAMING PLAN - LEVEL 3S-505 POD 1 ENLARGED FRAMING PLAN - LEVEL 4S-506 POD 1 ENLARGED FRAMING PLAN - ROOFS-507 POD 2 ENLARGED FRAMING PLAN - LEVEL 1/FOUNDATIONS-508 POD 2 ENLARGED FRAMING PLAN - LEVEL 2S-509 POD 2 ENLARGED FRAMING PLAN - LEVEL 3S-510 POD 2 ENLARGED FRAMING PLAN - ROOF

MECHANICALM-000 MECHANICAL SYMBOLS & ABBREVIATIONSM-001 MECHANICAL SCHEDULES SHEET 1M-002 MECHANICAL SCHEDULES SHEET 2M-201 MECHANICAL POD 1 DEMOLITION PART PLANS - LEVEL 1 & 1.5M-202 MECHANICAL POD 1 DEMOLITION PART PLANS - LEVEL 2 & 3M-203 MECHANICAL POD 1 DEMOLITION PART PLANS - LEVEL 4 & ROOFM-204 MECHANICAL POD 2 DEMOLITION PART PLANS - LEVEL 1 & MEZZM-205 MECHANICAL POD 2 DEMOLITION PART PLANS - LEVEL 2 & 3M-300 MECHANICAL SUPPLY AND EXHAUST AIR LINE DIAGRAMM-301 MECHANICAL SUPPLY AIR AND REFRIGERANT LINE DIAGRAMM-302 MECHANICAL REFRIGERANT LINE DIAGRAMM-402 MECHANICAL LEVEL 1 - KEY PLANM-403 MECHANICAL LEVEL 1.5 - KEY PLANM-404 MECHANICAL LEVEL 2 - KEY PLANM-405 MECHANICAL LEVEL 3 - KEY PLANM-406 MECHANICAL LEVEL 4 - KEY PLANM-407 MECHANICAL LEVEL ROOF - KEY PLANM-701 MECHANICAL POD 1 ENLARGED FLOOR PLANS - LEVEL 1M-702 MECHANICAL POD 1 ENLARGED FLOOR PLANS - LEVEL 1.5M-703 MECHANICAL POD 1 ENLARGED FLOOR PLANS - LEVEL 2M-704 MECHANICAL POD 1 ENLARGED FLOOR PLANS - LEVEL 3M-705 MECHANICAL POD 1 ENLARGED FLOOR PLANS - LEVEL 4M-706 MECHANICAL POD 1 ENLARGED FLOOR PLANS - ROOFM-708 MECHANICAL POD 2 ENLARGED FLOOR PLANS - LEVEL 1M-710 MECHANICAL POD 2 ENLARGED FLOOR PLANS - LEVEL 2

GENERALG-001 COVER SHEETG-002 DRAWING LISTG-003 SITE PLAN ACCESSIBLE ROUTE

CIVIL DEMOLITIONCD-100 SITE DEMOLITION PLAN

CIVILC-101 SITE UTILITY PLANC-102 SITE GRADING PLANC-103 SITE LAYOUT & MATERIALS PLANC-201 SITE DETAILS & GENERAL NOTESC-202 UTILITY DETAILS IC-203 UTILITY DETAILS IIC-204 UTILITY DETAILS III

DEMOLITIOND-101 POD 1 DEMOLITION PART PLANS - LEVEL 1 & LEVEL 1.5D-102 POD 1 DEMOLITION PART PLANS - LEVEL 2 & LEVEL 3D-103 POD 1 DEMOLITION PART PLANS - LEVEL 4 & ROOFD-104 POD 2 DEMOLITION PART PLANS - LEVEL 1 & MEZZD-105 POD 2 DEMOLITION PART PLANS - LEVEL 2 & LEVEL 3D-201 POD 1 DEMOLITION ELEVATIONSD-202 POD 2 DEMOLITION ELEVATIONS

ARCHITECTURALA-101 BASEMENT KEY PLANA-102 LEVEL 1 KEY PLANA-103 LEVEL 1.5 KEY PLANA-104 LEVEL 2 KEY PLANA-105 LEVEL 3 KEY PLANA-106 LEVEL 4 KEY PLANA-107 ROOF KEY PLANA-201 POD 1 BUILDING ELEVATIONSA-202 POD 1 BUILDING ELEVATIONSA-203 POD 2 BUILDING ELEVATIONSA-204 NEW CONSTRUCTION W/ EXISTING BUILDING SECTIONS - POD 1A-205 NEW CONSTRUCTION W/ EXISTING BUILDING SECTIONS - POD 2A-301 POD 1 BUILDING SECTIONSA-302 POD 1 BUILDING SECTIONSA-303 POD 2 BUILDING SECTIONSA-304 POD 2 BUILDING SECTIONSA-305 KITSON MEZZ BUILDING SECTIONSA-401 TYPICAL WALL SECTIONS - POD 1A-402 TYPICAL WALL SECTIONS - POD 1A-403 TYPICAL WALL SECTIONS - POD 1A-404 TYPICAL WALL SECTIONS - POD 2A-405 TYPICAL WALL SECTIONS - POD 2A-501 POD 1 ENLARGED FLOOR PLANS - LEVEL 1A-502 POD 1 ENLARGED FLOOR PLANS - LEVEL 1.5A-503 POD 1 ENLARGED FLOOR PLANS - LEVEL 2A-504 POD 1 ENLARGED FLOOR PLANS - LEVEL 3A-505 POD 1 ENLARGED FLOOR PLANS - LEVEL 4A-506 POD 1 ENLARGED FLOOR PLANS - ROOFA-507 POD 2 ENLARGED FLOOR PLANS - LEVEL 1 (KITSON HALL)A-508 POD 2 ENLARGED FLOOR PLANS - LEVEL 1A-509 KITSON MEZZ ENLARGED PLANA-510 POD 2 ENLARGED FLOOR PLANS - LEVEL 2A-511 POD 2 ENLARGED FLOOR PLANS - LEVEL 3A-512 POD 2 ENLARGED FLOOR PLANS - ROOFA-520 POD 1 REFLECTED CEILING PLANS - LEVEL 1A-521 POD 1 REFLECTED CEILING PLANS - LEVEL 1.5A-522 POD 1 REFLECTED CEILING PLANS - LEVEL 2A-523 POD 1 REFLECTED CEILING PLANS - LEVEL 3A-524 POD 1 REFLECTED CEILING PLANS - LEVEL 4A-525 POD 2 REFLECTED CEILING PLANS - LEVEL 1A-526 POD 2 REFLECTED CEILING PLANS - LEVELS 2 & 3A-530 RESTROOM TYPESA-531 RESTROOM TYPESA-532 RESTROOM TYPESA-534 POD 1 & 2 INTERIOR ELEVATIONSA-535 POD 1 & 2 INTERIOR ELEVATIONSA-536 KITSON INTERIOR ELEVATIONSA-601 EXISTING SOUTHWICK STAIR 1 MODIFICATIONSA-602 EXISTING PASTEUR STAIR 1 MODIFICATIONSA-603 EXISTING KITSON STAIR 2 MODIFICATIONSA-604 POD 1 ELEVATORA-605 KITSON EXISTING ELEVATORA-606 INTERIOR RAMP PLANS & SECTIONSA-607 INTERIOR STAIR PLANS & SECTIONSA-701 TYPICAL DETAILSA-702 POD 1 TYPICAL DETAILSA-703 POD 1 - TYPICAL EXTERIOR WALL DETAILSA-704 POD 1 TYPICAL ENLARGED EXTERIOR DETAILSA-705 POD 2 TYPICAL DETAILSA-706 TYPICAL INTERIOR DETAILSA-707 ENTRY DETAILSA-708 TYPICAL RAILING DETAILSA-709 POD 1 LEVEL 1 PLAN DETAILSA-710 POD 1 LEVEL 1.5 PLAN DETAILSA-711 POD 1 LEVELS 2-4 PLAN DETAILS

1

2

H40014
Rectangle
H40014
Rectangle
H40014
Rectangle
H40014
Rectangle
H40014
Rectangle
H40014
Rectangle
H40014
Rectangle
H40014
Text Box
Highlighted Drawings are excerpt from 100% Construction Documents Dated 7/17/2015. Highlighted drawings included in this package pertain to Pre - Purchase Generator;
Page 26: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

WB-50

AASHTO 2004 (US)

WB-50

AASHTO 2004 ( US)

WB-50

AASHTO 2004 ( US)

DN

115

115

115

120

111

111

112

112

113

113

114

114

116

117118

119

COMP.

STEAM

STEAM

STEAM

ST

EA

MS

TE

AM

ST

EA

M

STEAM

STEAM

ST

EA

M

ST

EA

MS

TE

AM

ST

EA

M

ST

EA

M

ST

EA

M

ST

EA

M

HVACHVAC

HVAC

HVAC

HVAC110.90

CO

NC

RA

MP

CONC CONC

CONC CO

NC

CO

NC

CO

NC

BIT CONC

BIT CONC

BIT CONC

BIT CONC

BIT CONC

BIT CONC

BIT CONC

BIT CONC

GM

PEDESTRIAN BRIDGE

OVERHEAD

HYDRANT "X

" CUT B

OLT

117.52

HYDRANT "X

" CUT B

OLT

113.90

P

P

P

P

PPP

PP P

P

8" D

POSS AC

6" DPOSS AC

4"D(R)

4"PVC

4"MET

8"RCP

DR

AIN

NO

T O

BS

.

D

D

D

D

D

15 "SE

WE

R12 "S

EW

ER

SEW(R)

6" SE

WE

RP

OS

S A

C

8"PVC

8"PVC

8"PVC

6"SEWER(R)

5"SEW(R)

SEWER(R)

8"SEWER(R)

12 "SE

WE

R

ELEC

ELEC

ELEC

ELE

C

ELEC

ELE

CE

LEC

ELE

C

ELEC

ELEC

ELEC

ELEC

ELEC

DL

DL

DL

ELE

C

114.72

GR

GR

GR

GR

GR

GR

GR

GR

V

V

VV

V

V V

PB

MC

MC

HYD

HYD

WG

WG

WG

WG

GG

CBR=110.70

I=108.9±(A)

B NOT OBS.

CBR=112.61

I=109.6±

CBR=112.49

CBR=114.29

I=107.8

AB

SMHR=112.84

I=106.9(A)

I=109.4(B)

I=106.6(C)

D=NOT OBS.

SMHR=113.26

I=110.3±

I=106.4(BC)

SMHR=113.90

I=106.3(ABC)

AB

CA

BC

DAB C

MHR=113.42

I=107.9

CC

CC

GC

GC

GC

GC

GC

GC

GC

GC

GC

GC

GC

GC

GC

GC

GC

GC

CROSS WALK

PA

RK

ING

ST

RIP

E(typical)

PA

RK

ING

ST

RIP

E(typical)

SWINGGATE

SWINGGATE

INTER-COM

114.69

111.09

118.75

119.56

119.79

120.67

118.54

118.76118.16

116.06

115.46

115.15

114.54

BE

RM

BE

RM

114.77

115.04

CONC AT

DOOR=117.86CONC AT

DOOR=117.74

112.88

112.46

112.40112.93112.03

111.85

112.30

TW

=120.01115.18

TW=121.60

120.90

120.67

TW=121.79

TW=121.79

115.14

115.90

117.63

115.42

115.33

115.16115.07

115.09115.23 115.32

115.34

114.70114.75

114.55

114.34114.62

114.82114.73

114.72

114.56114.56

115.57114.77

110.94

110.92

110.92

110.92

111.44

112.48

116.24

111.69

112.14112.21

112.16

111.96

111.27

111.05

110.81

110.90

110.96

111.55

112.67

113.87

114.53

113.80

114.71

112.30

114.73115.63

116.24

112.92

112.90

112.79

114.17

113.73

113.34

115.74

115.34114.95

114.37

114.27

113.37

115.17

114.45

114.79

114.70

114.76

115.02115.10

115.45

115.67

115.97116.38

111.48

111.54

111.68

112.01

112.12

112.16

112.77

112.78

112.64

112.33

112.82

113.10

113.21

113.64

113.30

113.38

113.73

113.45113.41

113.87

114.02113.92

113.69

113.79113.74

113.67

113.55

113.41

113.28

113.52

113.63

113.88113.74

113.81

113.90

114.04

113.89

113.97

114.12

111.02

113.61

111.35

117.86

119.91

119.67119.48

120.03120.36

120.45

120.36

120.73

117.76

117.61118.21

119.35

119.52119.02

119.38

115.15

115.38

112.52

112.46112.29

112.03

111.61

111.58111.68

111.69

112.18

112.32

112.59

112.56

113.07

113.20

113.54

113.93

113.60

113.40

113.91

113.88

112.61

114.07

114.21

114.44

113.69

114.60114.41

114.33

115.77

115.39114.58

114.58

114.41

113.78

GAS

GAS

GA

SG

AS

GA

S

GA

S

GAS

GAS

GAS

GA

S

GATE

GRAVELGRAVEL

GRAVELGRAVEL

GR

AV

EL

CO

NC

WA

LL

CO

NC

BLO

CK

RE

T W

ALL

CONCWALL

DUMPSTERAREA

RE

T W

ALL

HA

ND

RA

IL

CLF

SLID

ING

GA

TE

SLID

ING

GA

TE

8" WA

TE

R8" W

AT

ER

8" WA

TE

R8" W

AT

ER

WATER

SSSS

SSSSSS S S S S

S

S

SS

SSS

S

SS

SS

3 STORY

"ENGINEERING BUILDING"

4 STORY

1 STORY

1 STORY

"KITSON"

4 STORY

"BALL BUILDING"

FALMOUTH STREET

8"T 8"T 12"T

16"T

4"T

6"T

6"T

18"T

18"T

RIPRAP

RIP

RA

PR

IP R

AP

LP

BENCHMARK

ELEV

=

BENCHMARK

ELEV

=

STAIR

PLANT

212.68sf

100S1

KITSON

PASTEUR

SO

UTH

WIC

K

FALM

OU

TH

PERRY

POD 1ADDITION

POD 2ADDITION

LIMIT OF WORK

POD 1

LIMIT OF SITE WORK

MAINTENANCEBUILDING

REMOVE EXISTINGASPHALT PAVEMENT;EXCAVATE & PROVIDEBACKFILL FOR NEWSUBGRADE, TOP SOIL/LOAM& SEED, WALKWAYS ANDPADS, SITE LIGHTING,SPRINKLER IRRIGATION

WALL MOUNTEDLED FIXTURES

WALL MOUNTEDLED FIXTURES

WALL MOUNTEDLED FIXTURES

13'-0" X 20'-0"PAD

LESS THAN5% SLOPE

10'-0" WIDEWALKWAY

FOR REFERENCE ONLY(NOT IN SCOPE)5'-0" WIDE WALKWAYACCESSIBLE ROUTENOT TO EXCEED5% SLOPE

16'-0" X 22'-0"PAD

DRY LAB

RESTOREPAVEMENTWITHIN LIMIT OFWORK

BALL HALL CROSSWALK AND THEPROPOSED EAST ENTRANCE (SERVICEYARD) TO KITSON HALLTHE GRADE DROPS VERTICALLY 4.93’OVER A HORIZONTAL DISTANCE OF 257’,OR 1:52.13, WELL BELOW THE MAXIMUM1:20 SLOPE. UNLESS THERE ARE LOCALCONDITIONS ALONG THAT PATH THATEXCEED A 1:20 SLOPE, THE EXISTINGDRIVEWAY CAN PROVIDE AN ACCESSIBLEPATH BETWEEN THE CROSSWALK AND THENEW KITSON ENTRANCE. IF THE EXISTINGDRIVEWAY WIDTH ALLOWS, CONSIDERPAINTING A PEDESTRIAN ZONE ALONG THEPERRY HALL BERM/RETAINING WALL &INSTALLING A GUARDRAIL TO SEPARATETHIS ZONE FROM THE VEHICULAR LANES.

ACCESSIBLE ROUTE FROMUNIVERSITY AVE

ACCESSIBLE ROUTE FROMBALL HALL

GENERAL NOTES:

1. REFER TO ENLARGED PLANS(A-501 THROUGH A-512) FORINTERIOR SCOPE OF WORK

2. REFER TO DEMOLITION PLANS& ELEVATIONS (D-101 THROUGHD-202) FOR DEMO SCOPE AT SITE

3. REFER TO CIVIL DWGS (C-101THROUGH C-204) & SPECS FORFULL EXTERIOR IMPROVEMENTS

SEE ENLARGED PLANS

POD 2SEE ENLARGED PLANS

EXISTING GENERATOR

WALLMOUNTED

EMERG. PHONEO.F.O.I.

WALL MOUNTEDLED FIXTURES

NEWGENERATOR

RELOCATED DUMPSTER& TRASH COMPACTOR

FALMOUTHPROJECT LIMITLINE

REFER TO DEMO PLANSD-101 THROUGH D-103FOR DEMO AREA(ALL LEVELS)

REFER TO DEMO PLANSD-104 THROUGH D-105

FOR DEMO AREA(ALL LEVELS)

1D-201

2D-201

1D-202

2D-202

ARCHITECT

CONSULTANT

STAMP

MARK DATE DESCRIPTION

PROJECT NUMBER:DRAWN BY:CHECKED BY:

SHEET TITLE

RD

JM

100% CONSTRUCTIONDOCUMENTS SET

06/10/14 FEASIBILITY STUDY SET

08/29/14 SCHEMATIC DESIGN SET

(UMBA 13-L2)

12/18/14 50% DESIGN DEVELOPMENT SET

01/15/15 100% DESIGN DEVELOPMENT SET

04/06/15 60% CONSTRUCTION PERMIT SET

04/22/15 TIER 1 PHASE 1 (EARLY PACKAGE)PERMIT SET

05/07/15 90% CONSTRUCT. DOC. SET

06/30/15 TIER 1 PHASE 1 PERMIT SET

7/17/15 100% CONSTRUCT. DOC. SET

7/20

/201

5 2:

57:5

2 P

M

G-003

SITE PLANACCESSIBLE ROUTE

UMass Lowell NorthQuad Infrastructure

Renewal

21332

Lowell, MA

University of Massachusetts Building AuthorityUniversity of Massachusetts Lowell

1" = 30'-0"1 SITE PLAN

0 60 90 12030

GRAPHIC SCALE N

PROJECT ABREVIATIONS:

ID INSIDE DIMENSIONOD OUTSIDE DIMENSIONCONC. CONCRETETYP. TYPICALSTL. STEELDIA. DIAMETERMAX. MAXIMUMMIN. MINIMUMA.F.F. ABOVE FINISH FLOORCL CENTER LINESIM SIMILARRCP REFLECTED CEILING PLANFACP FIRE ALARM CONTROL PANELCT CERAMIC TILEGWB GYPSUM WALL BOARDGYP GYPSUMFD FLOOR DRAINPTD PAINTEDEQ. EQUALAPPROX. APPROXIMATELYELEV. ELEVATORSTD STUDENTSTF STAFFWWC WOMENS WATER CLOSETMWC MENS WATER CLOSETPLUMB PLUMBINGEXIST. EXISTINGELEC. ELECTRICJAN. JANITORIDF/IT INTERMEDIATE DISTRIBUTION FRAME /

INFORMATION TECHNOLOGYEXP. EXPANSIONMR MACHINE ROOM (ELEVATOR)FR FIRE RATEDEE EMERGENCY ELECTRICSTR. STAIRMEP MECHANICAL, ELECTRICAL, PLUMBINGCORR. CORRIDORVTR VENT THROUGH ROOFRD ROOF DRAINDF DRINKING FOUNTAINLOC'N LOCATIONTBD TO BE DETERMINEDGSF GROSS SQUARE FEETNSF NET SQUARE FEETHR HOURO.C. ON CENTERREG REGULARRTU ROOF TOP UNITEMER. EMERGENCYENT ENTRANCEPRIM. PRIMARYMEZZ MEZZANINESTRUCT. STRUCTURESS STAINLESS STEELF.P.M FEET PER MINUTECLR CLEARFEC FIRE EXTINGUISHER CABINETFRR FIRE RESISTANCE RATINGOTA OPEN TO ABOVEOTB OPEN TO BELOWMANUF. MANUFACTURERW/ WITHAVB AIR VAPOR BARRIER

Page 27: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number
Page 28: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number
Page 29: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number
Page 30: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number
Page 31: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

US

IS

UG

BW

S

S

S

S

S

S

S

S

- 'a' DENOTES SWITCHED CIRCUIT- SHADED AREA FIXTURE ON EMERGENCY CIRCUIT

BOX.CEILING MOUNTED LIGHTING FIXTURE AND OUTLET

- 'F' DENOTES FIXTURE TYPE- '2' DENOTES BRANCH CIRCUIT NUMBER

LIGHTINGDESCRIPTIONSYMBOL

- 'a' DENOTES SWITCHED CIRCUIT- SHADED AREA FIXTURE ON EMERGENCY CIRCUIT

WALL MOUNTED LIGHTING FIXTURE AND OUTLET

- 'F' DENOTES FIXTURE TYPE- '2' DENOTES BRANCH CIRCUIT NUMBER

BOX.

F

2,a

F

2 a

CEILING/WALL EXIT LIGHT AND OUTLET BOX,LED TYPE, SELF CONTAINED, WITH BATTERY PACK:- SHADED AREA INDICATES ILLUMINATED FACE(S)- ARROW INDICATES DIRECTION

EMERGENCY UNIT EQUIPMENT, 90 MINUTEBATTERY PACK, CHARGER AND TEST SWITCH.

NOTE: SEE LIGHT FIXTURE SCHEDULE AND SPECIFICATIONSFOR COMPLETE FIXTURE DESCRIPTION.

DESCRIPTIONSYMBOL

WIRING DEVICES

20A SPST TOGGLE SWITCH U.O.N.:-LOWER CASE LETTER DENOTES LIGHTINGFIXTURE SWITCHING ARRANGEMENT- '3' DENOTES THREE-WAY- '4' DENOTES FOUR-WAY- 'K' KEY OPERATED

SPDT MOMENTARY CONTACT SWITCH

WALL DIMMER SWITCH

WEATHERPROOF SWITCH

EXPLOSION PROOF SWITCH

WALL SWITCH OCCUPANCY SENSOR

WALL MOUNTED PHOTOCELL CONTROLLER

LIGHTING CONTACTOR

TIME CLOCK

PUSH BUTTON

JUNCTION BOX RECESSED WALL MOUNTED:

ELECTRICALLY ILLUMINATED SIGNAGE- 'SG' DENOTES JUNCTION BOX FOR

RECESSED CEILING MOUNTED JUNCTION BOX

FLUSH FLOOR MOUNTED JUNCTION BOX

J

PLUG MOLD

SURFACE RACEWAY

TRACK BUSWAY

ABBREVIATIONSDESCRIPTIONSYMBOL

L

LTG

C

A,AMP AMPERE

AMPS INTERRUPTING CAPACITYAIC

AC ALTERNATING CURRENT

ABOVE FINISHED FLOORAFF

ATC AUTOMATIC TEMPERATURE CONTROL

AUTOMATIC TRANSFER SWITCHATS

BAS BUILDING AUTOMATION SYSTEM

BUILDING MANAGEMENT SYSTEMBMS

BFG BELOW FINISHED GRADE

C, CDT CONDUIT

CIRCUIT BREAKERCB

CKT CIRCUITCONDUIT ONLYC.O., CO

CONFIG. CONFIGURATION

CENTERLINE

CONVENIENCECONV

CM CONSTRUCTION MANAGER

DIGITAL DATA CONTROLDDC

DWG DRAWING

ELECTRICAL CONTRACTORE.C.

ELEC ELECTRICAL

EMERGENCYEM

EMT ELECTRICAL METALLIC TUBING

ELECTRICALLY OPERATED 'ON-OFF'E.O.

EQUALEQ

EWC ELECTRIC WATER COOLER

FIRE ALARMFA

FAI FURNISH AND INSTALL

FULL LOAD AMPSFLA

FSD FIRE SMOKE DAMPER

GROUNDG, GND

GEN GENERATOR

GROUND FAULT CIRCUIT INTERRUPTERGFCI

HORSE POWERHP

INSTALLED BY ELECTRICAL CONTRACTORIBEC

FURNISHED BY OTHERSFBO

JB,J JUNCTION BOX

KILO VOLT- AMPEREKVA

KW KILO WATT

LCP LIGHTING CONTROL PANEL

LIGHTING

LOW VOLTAGELV

LVR LOW VOLTAGE RELAY

MANUFACTURERMFRR

MIN MINIMUM

MAIN LUGS ONLYMLO

MSB MAIN SWITCHBOARD

MOUNTEDMTD

N NEUTRALNOT APPLICABLENA,N/A

NEMANATIONAL ELECTRICALMANUFACTURERS ASSOCIATION

N.C. NORMALLY CLOSED

NOT IN CONTRACTNIC

# NUMBER

NORMALLY OPENN.O.

NTS NOT TO SCALE

ON CENTEROC

POLESP

PB PULL BOX

POWER FACTOR CORRECTIONPFC

PH, PHASEPANELPNL

POWERPWR

RECEPTACLERECPT

RM ROOM

SIGNAGESG

SHT SHEET

SPECIFICATIONSSPEC

SPDT SINGLE POLE DOUBLE THROW

SINGLE POLE SINGLE THROW

SWITCH

SPST

SW

SWBD

SWGR

SWITCHBOARD

SWITCHGEAR

TIME CLOCKTC

TYP TYPICAL

UNDERGROUNDUG

MISCELLANEOUSDESCRIPTIONSYMBOL

FEEDER SIZE, SEE FEEDER SCHEDULE

REFERENCE NOTE

DIGITAL REFERENCE:- DETAIL DESIGNATION- SHEET NUMBER REFERENCE

EQUIPMENT REFERENCE. COORDINATE EQUIPMENTWITH MECHANICAL/PLUMBING TRADES. SEEMECHANICAL/PLUMBING DRAWINGS FOR LOCATIONS.SEE E-008 FOR SCHEDULE OF REQUIREMENTS.

#

AE-3

EF1

ANNOTATION FOR RECEPTACLE WIRING DEVICES:- SOLID CENTER HATCH DENOTES GFI TYPE- CT - DENOTES COUNTER TOP- EM EMERGENCY TYPE

DUPLEX RECEPTACLE WALL MOUNTED20A, 125V, 2P, 3W GROUNDING

SPECIAL RECEPTACLE WALL MOUNTEDNEMA CONFIGURATION AS INDICATED ON PLANS

SIMPLEX RECEPTACLE FLUSH FLOOR MOUNTED20A, 125V, 2P, 3W GROUNDING

PC CEILING MOUNTED PHOTOCELL CONTROLLER

REMOTE CONTROL SWITCH

SIMPLEX RECEPTACLE WALL MOUNTED20A, 125V, 2P, 3W GROUNDING

QUAD RECEPTACLE WALL MOUNTED20A, 125V, 2P, 3W GROUNDING

SIMPLEX RECEPTACLE CEILING MOUNTED20A, 125V, 2P, 3W GROUNDING

DUPLEX RECEPTACLE CEILING MOUNTED20A, 125V, 2P, 3W GROUNDING

QUAD RECEPTACLE CEILING MOUNTED20A, 125V, 2P, 3W GROUNDING

SPECIAL RECEPTACLE CEILING MOUNTEDNEMA CONFIGURATION AS INDICATED ON PLANS

DUPLEX RECEPTACLE FLUSH FLOOR MOUNTED20A, 125V, 2P, 3W GROUNDING

QUAD RECEPTACLE FLUSH FLOOR MOUNTED20A, 125V, 2P, 3W GROUNDING

SPECIAL RECEPTACLE FLUSH FLOOR MOUNTEDNEMA CONFIGURATION AS INDICATED ON PLANS

O

CEILING MOUNTED OCCUPANCY SENSOR.

- 'US' DENOTES ULTRASONIC- 'PIR' DENOTES PASSIVE INFRARED

- 'DT' DENOTES DUAL TECHNOLOGY- 'a' DENOTES SWITCHING ARRANGEMENT

O

WALL MOUNTED OCCUPANCY SENSOR.- 'PIR' DENOTES PASSIVE INFRARED- 'DT' DENOTES DUAL TECHNOLOGY- 'a' DENOTES SWITCHING ARRANGEMENT

POWERDESCRIPTIONSYMBOL

MOTOR LOAD.SEE E008 FOR REQUIREMENTS.

UNFUSED DISCONNECT SWITCH WITH RATING=> UPSTEAM PROTECTIVE DEVICE- '4x' DENOTES NEMA ENCLOSURE IF INDICATED

VARIABLE FREQUENCY DRIVE CONTROLLER

TRANSFORMER, SEE SCHEDULE FOR RATING

RELAY - NUMERAL DENOTES NUMBER OF POLES

SURFACE MOUNTED LTG/APPLIANCE PANELBOARD

FLOOR MOUNTED DISTRIBUTION/SWITCHBOARD

HOMERUN TO PANELBOARD "LP-3A":- NUMERALS DENOTE CIRCUIT NUMBERS- DESIGNATION DENOTES CIRCUIT NUMBERS, 3#12 + 1#10N-3/4" EMT, U.O.N.

NEW CONDUIT OR EQUIPMENT

CONDUIT TURNING UP

CONDUIT TURNING DOWN

CONDUIT CAPPED

FLEXIBLE CONNECTION

EXISTING CONDUIT AND WIRING TO REMAIN

EXISTING CONDUIT AND WIRING TO BE REMOVED

1,3,5LP-3A/

CONDUIT UNDER SLAB

CONDUIT IN SLAB

CONDUIT UNDERGROUND

CONDUIT IN DUCTBANK

FUSED DISCONNECT SWITCH- NUMERICAL DENOTES FUSE SIZE- '4x' DENOTES NEMA ENCLOSURE IF INDICATED

ENCLOSED CIRCUIT BREAKER- NUMERICAL DENOTES TRIP SIZE- '4x' DENOTES NEMA ENCLOSURE IF INDICATED

COMBINATION DISCONNECT SWITCH/CONTROLER- NUMERICAL DENOTES FUSE/TRIP SIZE- '4x' DENOTES NEMA ENCLOSURE IF INDICATED

COMBINATION DISCONNECT SWITCH/CONTROLLERVARIABLE FREQUENCY DRIVE- '4x' DENOTES NEMA ENCLOSURE IF INDICATED

- '4x' DENOTES NEMA ENCLOSURE IF INDICATED

AUTOMATIC TRANSFER SWITCH, SEE RISERDIAGRAM FOR RATING

MANUAL MOTOR STARTER WITH THERMALOVERLOAD AND PILOT LIGHT

FLUSH MOUNTED LTG/APPLIANCE PANELBOARD

PULLBOX

SURFACE MOUNTED POWER PANELBOARD

R

SINGLE LINE DIAGRAMDESCRIPTIONSYMBOL

PANELBOARD, SEE PANEL SCHEDULE FOR RATING

MOLDED CASE CIRCUIT BREAKER:- 'TEXT' DENOTES CB ACCESSORIES

LOW VOLTAGE DRAW OUT CIRCUIT BREAKER:

MEDIUM VOLTAGE DRAW OUT CIRCUIT BREAKER

AUTOMATIC TRANSFER SWITCH

GENERATOR

UTILITY METER

DIGITAL MULTIFUNCTION METER WITHCURRENT/POTENTIAL TRANSFORMER AS REQUIRED

ST, ET. GFP, EO, LSI TRIP FUNCTIONS- NUMERICAL DENOTES TRIP SIZE

- 'TEXT' DENOTES CB ACCESSORIES- NUMERICAL DENOTES TRIP SIZE

WITH INTEGRAL TRIP UNIT

LOW VOLTAGE FUSE/SWITCH UNIT- 'TEXT' DENOTES FUSE ACCESSORIES

ST, GFR, EO, LO, LOCK OUT PROVISIONS- NUMERICAL DENOTES FUSE SIZE

MEDIUM VOLTAGE DRAWOUT FUSE/SWITCH UNIT- 'TEXT' DENOTES FUSE ACCESSORIES- NUMERICAL DENOTES FUSE SIZE

ENCLOSED CIRCUIT BREAKER- 'TEXT' DENOTES CB ACCESSORIES- NUMERICAL DENOTES TRIP SIZE

ENCLOSED SAFETY DISCONNECT SWITCH- 'TEXT' DENOTES FUSE ACCESSORIES- NUMERICAL DENOTES SWITCH SIZE

ENCLOSED FUSED DISCONNECT SWITCH- 'TEXT' DENOTES FUSE ACCESSORIES- NUMERICAL DENOTES SWITCH SIZE

INTERMEDIATE CLASS MOV SURGE ARRESTER- NUMERICAL DENOTES ARRESTER RATING

MOTOR

SPARE SWITCH IN DISTRIBUTION EQUIPMENT

SPACE IN DISTRIBUTION EQUIPMENT

KEY INTERLOCK

RELAY NUMERICAL INDICATES TYPE

CURRENT TRANSFORMER:- '200/5' DENOTES CT RATIO IF INDICATED

POTENTIAL TRANSFORMER:- NUMERICAL DENOTES QUANTITY OF FUSES

DELTA CONNECTION

WYE CONNECTION

EMERGENCY LIGHTING INVERTER

BATTERY

TRANSFORMER WITH PRIMARYAND SECONDARY CONNECTIONSAS INDICATED ON RISER DIAGRAM.208/120

4 POLEATS-1

600A

KI

M

75KVAXMFR-1

480V-

(1)

200/5

M VA

M

51

G

N E

L

ST

400

ST225

225ST

12KVSA

SPACE255

SPARE200

52

GFP

TRIP

GFP

TRIP

GFPTRIP

LSITRIP

PANEL

6

ATS

T4

PB

TPM

VFD4X

4X 400

4X

VFD4X

4X

CB4X 225

F4X 200

bDT

aPIR

L6-20R

GFI

RC

EM

DM

aOS

MC

WP

TC

LC

PC

XP

P380D

J

SGJ

L6-20R

bK4

a3

F

2 a

F

2,a

FEEDER

BUSWAY

OWNER FURNISHED, CONTRACTOR INSTALLEDOFCI

INV

UON, U.O.N. UNLESS OTHERWISE NOTED

UNF UNFUSED

VOLTV

VA VOLT-AMPERES

W WATT

WEATHERPROOFWP

XFMR TRANSFORMER

EQUIPMENT GROUNDING CONNECTION.

GROUND ROD. SEE E8XX SERIES DETAILS FOR MOREINFORMATION.

ARCHITECT

CONSULTANT

STAMP

MARK DATE DESCRIPTION

PROJECT NUMBER:DRAWN BY:CHECKED BY:

SHEET TITLE

100% CONSTRUCTIONDOCUMENT SET

(UMBA 13-L2)

www.arup.com

955 Massachusetts Avenue4th Floor

Cambridge, MA 02139T 617 864 2987 F 617 864 6178

Arup USA Inc

7/17

/201

5 1:

57:5

8 PM

E-000

ELECTRICALSYMBOLS &

ABBREVIATIONS

UMass Lowell NorthQuad Infrastructure

Renewal

21332

Lowell, MA

University of Massachusetts Building AuthorityUniversity of Massachusetts Lowell

JAIT

ELECTRICAL DRAWING LISTSheet

Number Sheet Name Scale

E-000 ELECTRICAL SYMBOLS & ABBREVIATIONSE-001 ELECTRICAL SCHEDULE OF PANELBOARDSE-002 ELECTRICAL SCHEDULE PLAN SHEET 1E-003 ELECTRICAL SCHEDULE PLAN SHEET 2E-004 ELECTRICAL SCHEDULE PLAN SHEET 3E-005 ELECTRICAL SCHEDULE PLAN SHEET 4E-006 ELECTRICAL SCHEDULE PLAN SHEET 5E-007 ELECTRICAL SCHEDULE PLAN SHEET 6E-008 ELECTRICAL SCHEDULE PLAN SHEET 7E-201 ELECTRICAL POD 1 DEMOLITIONLITION PART PLANS - LEVEL 1 & 1.5E-202 ELECTRICAL POD 1 DEMOLITION PART PLANS - LEVEL 2 & 3E-203 ELECTRICAL POD 1 DEMOLITION PART PLANS - LEVEL 4 & ROOFE-204 ELECTRICAL POD 2 DEMOLITION PART PLANS - LEVEL 1 & MEZZE-205 ELECTRICAL POD 2 DEMOLITION PART PLANS - LEVEL 2 & 3E-300 ELECTRICAL RISER ONE LINE DIAGRAM AE-301 ELECTRICAL RISER ONE LINE DIAGRAM BE-402 ELECTRICAL LEVEL 1 - KEY PLANE-403 ELECTRICAL LEVEL 1.5 - KEY PLANE-404 ELECTRICAL LEVEL 2 - KEY PLANE-405 ELECTRICAL LEVEL 3 - KEY PLANE-406 ELECTRICAL LEVEL 4 - KEY PLANE-407 ELECTRICAL ROOF - KEY PLANE-701 ELECTRICAL POD 1 ENLARGED FLOOR PLANS - LEVEL 1E-702 ELECTRICAL POD 1 ENLARGED FLOOR PLANS - LEVEL 1.5E-703 ELECTRICAL POD 1 ENLARGED FLOOR PLANS - LEVEL 2E-704 ELECTRICAL POD 1 ENLARGED FLOOR PLANS - LEVEL 3E-705 ELECTRICAL POD 1 ENLARGED FLOOR PLANS - LEVEL 4E-706 ELECTRICAL POD 1 ELARGED FLOOR PLANS - ROOFE-707 ELECTRICAL POD 2 ENLARGED FLOOR PLANS - LEVEL 1 (KITSON HALL)E-710 ELECTRICAL POD 2 ENLARGED FLOOR PLANS - LEVEL 2E-711 ELECTRICAL POD 2 ENLARGED FLOOR PLANS - LEVEL 3E-712 ELECTRICAL POD 2 ENLARGED FLOOR PLANS - ROOFE-720 ELECTRICAL POD 1 ENLARGED LIGHTING PLANS - LEVEL 1E-721 ELECTRICAL POD 1 ENLARGED LIGHTING PLANS - LEVEL 1.5E-722 ELECTRICAL POD 1 ENLARGED LIGHTING PLANS - LEVEL 2E-723 ELECTRICAL POD 1 ENLARGED LIGHTING PLANS - LEVEL 3E-724 ELECTRICAL POD 1 ENLARGED LIGHTING PLANS - LEVEL 4E-725 ELECTRICAL POD 2 ENLARGED LIGHTING PLANS - LEVEL 1E-726 ELECTRICAL POD 2 ENLARGED LIGHTING PLANS - LEVELS 2&3E-800 ELECTRICAL DETAILS PLAN SHEET 1E-801 ELECTRICAL DETAILS PLAN SHEET 2E-802 ELECTRICAL DETAILS PLAN SHEET 3E-803 ELECTRICAL DETAILS PLAN SHEET 4

GENERAL NOTES:

1. ALL MATERIAL AND WORKMANSHIP SHALL CONFORM TO THE NATIONAL ELECTRICAL CODE AND APPLICABLE LOCAL CODES ANDREGULATIONS.2. ALL PANELS, SWITCHES, AND WIRING TROUGHS SHALL HAVE SUFFICIENT GUTTER SPACE AND LUGS TO ACCOMMODATE CONDUCTORSSHOWN.3. WHERE WIRE SIZES ARE INDICATED ON PLANS, FOR INDIVIDUAL CIRCUITS, THE WIRE SIZE INDICATED SHALL APPLY TO THE COMPLETE CIRCUIT,UNLESS OTHERWISE NOTED.4. ALL JUNCTION BOXES AND PULL BOXES SHALL BE CODE GAUGE AND SIZE TO ACCOMMODATE NUMBER OF CONDUITS/CONDUCTORS SHOWN.5. ALL PULL BOXES IN FINISHED AREAS SHALL HAVE FACTORY APPLIED PRIMER COAT OF PAINT.ELECTRICAL CONTRACTOR SHALL VERIFY THE EXACT LOCATION OF ALL MECHANICAL, PLUMBING AND OTHER EQUIPMENT REQUIRINGELECTRICAL POWER, PRIOR TO PERFORMANCE OF ANY WORK.6. ELECTRICAL CONTRACTOR SHALL VERIFY THE EXACT LOCATION OF ALL MECHANICAL, PLUMBING AND OTHER EQUIPMENT REQUIRINGELECTRICAL POWER, PRIOR TO PERFORMANCE OF ANY WORK.7. ALL PANELBOARDS SHALL HAVE LOCKING DOORS AND BE KEYED ALIKE UNLESS OTHERWISE NOTED.8. ALL MOUNTING HEIGHTS FOR DEVICES SHALL BE AS PER ELECTRICAL DETAILS (E8.XX SERIES).9. DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS AND WORK INCLUDED. FOLLOW DRAWINGS IN LAYINGOUT WORK AND CHECK DRAWINGS OF OTHER TRADES TO VERIFY SPACE IN WHICH WORK WILL BE INSTALLED. MAINTAIN HEADROOM AND SPACECONDITIONS AT ALL TIMES.10. ELECTRICAL CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL WALL OUTLET BOXES FOR CLOCKS, SWITCHES, FIRE ALARM DEVICES,RECEPTACLES ETC. WITH MILLWORK AND FURNITURE.11. ELECTRICAL CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL WALL OUTLET BOXES FOR CLOCKS, SWITCHES, FIRE ALARM DEVICES,RECEPTACLES ETC. WITH MILLWORK AND FURNITURE.12. WHERE ELECTRIC MOTORS OR HEATERS ARE INSTALLED IN HUNG CEILINGS, PROVIDE DISCONNECT SWITCH IN HUNG CEILING WITHIN REACHFROM ACCESS POINT.13. EXPOSED RACEWAYS (WHEN INDICATED ON DRAWINGS) SHALL BE RUN PARALLEL WITH OR AT RIGHT ANGLES TO WALLS.14. FURNISH APPROVED EXPANSION FITTINGS WHERE RACEWAY CROSSES BUILDING EXPANSION JOINTS.15. FURNISH FISH WIRE IN EACH RACEWAY RUN OVER 10' IN LENGTH, IN WHICH PERMANENT WIRING IS NOT INSTALLED.16. NOT MORE THAN THREE LIGHTING OR CONVENIENCE OUTLET CIRCUITS ARE PERMITTED IN ONE CONDUIT, UNLESS OTHERWISE INDICATED.ALL CIRCUITS SHALL HAVE A DEDICATED NEUTRAL UON.17. PROVIDE PULL BOXES WHEREVER NECESSARY TO FACILITATE PULLING OF CONDUCTORS. COORDINATE LOCATIONS OF BOXES WITH OTHERTRADES TO AVOID CONFLICT.18. OUTLET BOXES FOR LIGHT FIXTURES RECESSED IN HUNG CEILING SHALL BE ACCESSIBLE THROUGH OPENING CREATED BY REMOVAL OFSUCH FIXTURES.19. ELECTRICAL CONTRACTOR SHALL VERIFY POWER REQUIREMENTS AND LOCATIONS FOR HVAC, PLUMBING AND FIRE PROTECTIONEQUIPMENT WITH RELEVANT CONTRACTOR PRIOR TO PERFORMANCE OF ANY WORK.20. ALL EXTERIOR ELECTRICAL DEVICES AND EQUIPMENT SHALL BE WEATHERPROOF TYPE, NEMA 4X.21. CONDUIT RUNS ARE NOT PERMITTED IN OR BELOW CONCRETE SLAB. ALL CONDUITS WILL BE PLACED IN THE HUNG CEILING UNLESSSPECIFICALLY INDICATED OTHERWISE.22. LIGHTING, POWER, VOICE/DATA OUTLETS SHALL NOT BE INSTALLED BACK TO BACK.23. WHERE MORE THAN ONE LIGHT SWITCH OCCURS AT SAME LOCATION, SWITCHES SHALL BE MOUNTED IN A MULTIPLE GANG BOX WITH ASINGLE COVER PLATE.24. ALL HOMERUNS SHALL BE (2)#12+#12G THHW/THWN COPPER UON. MC CABLE IS ALLOWED BUT SHALL NOT BE CONNECTED DIRECTLY TOPANELBOARDS. ALL PANELBOARD CONNECTIONS SHALL BE IN CONDUIT.25. ALL EQUIPMENT SCHEDULED THROUGHOUT THESE DRAWINGS AND SPECIFICATIONS IS ON AN "OR APPROVED EQUAL" BASIS.26. PERFORM MEGGER OHM TESTING ON ALL EXISTING TO BE REUSED FEEDERS (EXISTING 4160V LOOP FEEDERS IN CAMPUS NETWORK).FOLLOW ANSI/NETA ATS, “Standard for Acceptance Testing Specifications” ON ALL FEEDERS AFFECTED BY THIS WORK. PERFORM CONTINUTITYTESTS ON ALL EXTENDED BRANCH AND FEEDER CIRCUITS.27. DEMOLITION SHALL INCLUDE BUT NOT BE LIMITED TO ALL CONDUIT, WIRE, LIGHT FIXTURES, RECEPTACLES, JUNCTION BOXES, BATTERIES,DISCONNECT SWITCHES, CIRCUIT BREAKERS, WIREWAYS, FITTINGS, HANGERS ETC. CONTRACTOR SHALL REMOVE ALL ASSOCIATED CONDUT,WIRE AND ASSOCIATED COMPONENTS BACK TO THE PANEL SERVING THE EQUIPMENT. NO CONDUIT OR WIRE SHALL BE LEFT ABANDONED.28. AN IMPAIRMENT PLAN FOR THE FIRE ALARM SYSTEM AND ELECTRICAL DISTRIBUTION SYSTEMS SHALL BE DEVELOPED AND APPROVED BYTHE OWNER PRIOR TO IMPAIRING ANY SYSTEMS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A CONTINUOUS FIRE WATCHWHEN THE FIRE PROTECTION OR FIRE ALARM SYSTEM IS IMPAIRED. ALL OUTAGES SHALL BE APPROVED BY THE OWNERS CONSTRUCTIONMANAGER. OUTAGES SHALL BE SCHEDULED AT THE DISCRETION OF THE OWNERS CONSTRUCTION MANAGER, AND SHALL BE LIMTED TO "OFFHOURS", AS DEFINED BY UMASS LOWELL OR THEIR REPRESENTATIVE. POD 2 NEW SERVICE REQUIRES CHANGING 4160V LOOP OPEN POINT.SCHEDULE MODIFICATIONS TO LOOP NO LESS THAN 30 DAYS IN ADVANCE WITH THE SCHOOLS CONSTRUCTION MANAGER. DO NOT OPERATELOOP WITHOUT AN OPEN POINT, SYSTEM FAULT LEVEL WITH EXCEED SYSTEM CAPACITY.29. DEMOLITION AND REMOVAL WORK SHALL BE PERFORMED TO THE EXTENT INDICATED PLUS SUCH ADDITIONAL DEMOLITION AND REMOVALAS NECESSARY FOR THE INSTALLATION OF NEW WORK AND REMODELING OF EXISTING WORK. THE CONTRACTOR MAY DEMOLISH AND REMOVEMORE THAN THAT IS INDICATED WHERE SUCH VARIATION WILL EXPEDITE THE WORK AND RESTORE ALL AREAS TO THE ORIGINAL CONDITION,SUBJECT TO THE OWNER'S REPRESENTATIVE'S APPROVAL, AND WITHOUT ADDITIONAL COST TO THE OWNER.30. THE INFORMATION ON THESE DRAWINGS WAS OBTAINED FROM THE BEST SOURCES AVAILABLE BUT IT IS NOT ASSUMED TO REFLECTACTUAL "AS-BUILT" CONDITIONS. THE CONTRACTOR IS RESPONSIBLE FOR CONFIRMING ALL AS BUILT CONDITIONS.31. THE CONTRACTOR SHALL VERIFY IN THE FIELD ALL EXISTING CONDITIONS. NOTIFY THE ARCHITECT AND ENGINEER OF ANY DISCREPANCIESOR CONFLICTS PRIOR TO COMMENCING WORK. DO NOT PROCEED WITHOUT APPROVAL BY THE ARCHITECT OR ENGINEER, FOR ANY CHANGES,IF REQUIRED.32. REFER TO MECHANICAL, PLUMBING, FIRE PROTECTION AND ARCHITECTURAL DEMOLITION DRAWINGS FOR ADDITIONAL INFORMATION ANDLOCATIONS.33. THE INTENT OF THE DEMOLITION IS FOR THE CONTRACTOR TO DEMOLISH AND REMOVE FROM THE SITE ALL EXISTING ELEMENTSNECESSARY TO CONSTRUCT NEW WORK IN THE CONSTRUCTION DOCUMENTS.34. ALL FINAL EQUIPMENT CONNECTIONS FROM ALL JUNCTIONBOXES AND DISCONNECTION DEVICES BY ELECTRICAL CONTRACTOR UNLESSNOTED OTHERWISE.

1 06/10/14 FEASIBILITY STUDY SET2 08/29/14 SCHEMATIC DESIGN SET3 12/18/14 50% DESIGN DEVELOPMENT SET4 01/15/15 100% DESIGN DEVELOPMENT SET5 04/06/15 60% CONSTRUCTION PERMIT SET6 05/07/15 90% CONSTRUCT. DOC. SET7 06/30/15 TIER 1 PHASE 1 PERMIT SET8 07/17/15 100% CONSTRUCT. DOC. SET

Page 32: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

ARCHITECT

CONSULTANT

STAMP

MARK DATE DESCRIPTION

PROJECT NUMBER:DRAWN BY:CHECKED BY:

SHEET TITLE

100% CONSTRUCTIONDOCUMENT SET

(UMBA 13-L2)

www.arup.com

955 Massachusetts Avenue4th Floor

Cambridge, MA 02139T 617 864 2987 F 617 864 6178

Arup USA Inc

7/17

/201

5 1:

58:0

0 PM

E-001

ELECTRICALSCHEDULE OFPANELBOARDS

UMass Lowell NorthQuad Infrastructure

Renewal

21332

Lowell, MA

University of Massachusetts Building AuthorityUniversity of Massachusetts Lowell

JAIT

SCHEDULE OF PANELBOARD SCHEDULESPanel Name On Sheet

EP-FK-1A E-002EP-FK-1B E-002EP-FK-2 E-004EP-FK-3 E-006LP-FK-1 E-002LP-FK-2 E-004LP-FK-3 E-005MP-FK-1 E-002MP-FK-3 E-006MP-SP-1 E-007

OEP-FK-1A E-003OEP-FK-1B E-003OEP-FK-2 E-005OEP-FK-3 E-006OP-SP-1 E-004OP-SP-3 E-007RP-F-1 E-003RP-F-2 E-005RP-F-3 E-007RP-K-1 E-003RP-K-2 E-005RP-K-3 E-006SP-P1 E-004

SP-P1(TUB 2) E-004SP-P3 E-0071. REFER TO THE FOLLOWING E00X SHEETS FOR PANELBOARD SCHEDULES.

1 06/10/14 FEASIBILITY STUDY SET2 08/29/14 SCHEMATIC DESIGN SET3 12/18/14 50% DESIGN DEVELOPMENT SET4 01/15/15 100% DESIGN DEVELOPMENT SET5 04/06/15 60% CONSTRUCTION PERMIT SET6 05/07/15 90% CONSTRUCT. DOC. SET7 06/30/15 TIER 1 PHASE 1 PERMIT SET8 07/17/15 100% CONSTRUCT. DOC. SET

Page 33: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

ARCHITECT

CONSULTANT

STAMP

MARK DATE DESCRIPTION

PROJECT NUMBER:DRAWN BY:CHECKED BY:

SHEET TITLE

100% CONSTRUCTIONDOCUMENT SET

(UMBA 13-L2)

www.arup.com

955 Massachusetts Avenue4th Floor

Cambridge, MA 02139T 617 864 2987 F 617 864 6178

Arup USA Inc

7/17

/201

5 1:

58:0

2 PM

E-002

ELECTRICALSCHEDULE PLAN

SHEET 1

UMass Lowell NorthQuad Infrastructure

Renewal

21332

Lowell, MA

University of Massachusetts Building AuthorityUniversity of Massachusetts Lowell

JAIT

NOTES:

TOTAL NEC AMPS: 19 ATOTAL CONNECTED AMPS: 17 A

TOTAL NEC LOAD: 16165 VATOTAL CONNECTED LOAD: 14.3 kVA

*MOTOR LOAD 14317 VA 112.91% 16165 VALOAD CLASSIFICATION CONNECTED... DEMAND FACTOR CALC. NEC LOAD PANEL TOTALS

TOTAL CONNECTED AMPS: 9 A 9 A 34 ATOTAL CONNECTED LOAD: 2464 VA 2464 VA 9389 VA

41 SPACE -- -- 0 VA 0 VA -- -- SPACE 42

39 SPACE -- -- 0 VA 0 VA -- -- SPACE 40

37 SPACE -- -- 0 VA 0 VA -- -- SPACE 38

35 SPACE -- -- 0 VA 0 VA -- -- SPACE 36

33 SPACE -- -- 0 VA 0 VA -- -- SPACE 34

31 SPACE -- -- 0 VA 0 VA -- -- SPACE 32

29 SPARE 20 A 1 0 VA 0 VA -- -- SPACE 30

27 SPARE 20 A 1 0 VA 0 VA -- -- SPACE 28

25 SPARE 20 A 1 0 VA 0 VA -- -- SPACE 26

23 SPARE 20 A 1 0 VA 0 VA -- -- SPACE 24

21 SPARE 20 A 1 0 VA 0 VA -- -- SPACE 22

19 SPARE 20 A 1 0 VA 0 VA -- -- SPACE 20

17 SPARE 20 A 1 0 VA 0 VA -- -- SPACE 18

15 SPARE 20 A 1 0 VA 0 VA -- -- SPACE 16

13 SPARE 20 A 1 0 VA 0 VA -- -- SPACE 14

11 -- -- -- 2464 VA 0 VA -- -- SPACE 12

9 -- -- -- 2464 VA 0 VA -- -- -- 10

7 MOTOR - CUH-2 25 A 3 2464 VA 0 VA -- -- -- 8

5 MOTOR - DWH-1 50 A 1 6925 VA 0 VA 3 20 A MOTOR - PLATFORM LIFT 6

3 SPACE -- -- 0 VA 0 VA -- -- SPACE 4

1 SPACE -- -- 0 VA 0 VA -- -- SPACE 2

CKT CIRCUIT DESCRIPTION TRIP PO... A B C PO... TRIP CIRCUIT DESCRIPTION CKT

BUS RATING: 225 AMP-FK-1 ENCLOSURE: Type 1 WIRES: 4 MCB RATING: 225 AMOUNTING: Surface PHASES: 3 MAINS TYPE: MCBPANEL NAME:FED FROM: USS-FK VOLTS: 480/277 Wye A.I.C. RATING: 22kA

NOTES: INTEGRAL SPD. PROVIDE WITH MAIN DISCONNECT SWITCH. SEE E3.01 FOR ADDITIONAL BREAKER COORDINATION REQUIREMENTS AND BASIS OF DESIGN CIRCUIT BREAKERS. 20ABREAKERS AS PER SQUARE D ED FRAME. 125A BREAKERS AS PER E3.01 SINGLE LINE.

*CONTINUOUS 1100 VA 125.00% 1375 VA TOTAL NEC AMPS: 6 A*MOTOR LOAD 200 VA 112.50% 225 VA TOTAL CONNECTED AMPS: 6 A*NON-CONTINUOUS 1700 VA 100.00% 1700 VA TOTAL NEC LOAD: 5365 VA*RECEPTACLE 1000 VA 100.00% 1000 VA TOTAL CONNECTED LOAD: 4.9 kVA*LIGHTING 852 VA 125.00% 1065 VALOAD CLASSIFICATION CONNECTED... DEMAND FACTOR CALC. NEC LOAD PANEL TOTALS

TOTAL CONNECTED AMPS: 6 A 4 A 8 ATOTAL CONNECTED LOAD: 1580 VA 1118 VA 2154 VA

41 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 42

39 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 40

37 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 38

35 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 36

33 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 34

31 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 32

29 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 30

27 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 28

25 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 26

23 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 24

21 -- -- -- 1100 VA 0 VA 1 20 A SPARE 22

19 -- -- -- 1300 VA 0 VA 1 20 A SPARE 20

17 TX3 30 A 3 1600 VA 0 VA 1 20 A SPARE 18

15 -- -- -- 0 VA 0 VA 1 20 A SPARE 16

13 -- -- -- 0 VA 0 VA 1 20 A SPARE 14

11 EP-FK-3 125 A 3 277 VA 0 VA 1 20 A SPARE 12

9 -- -- -- 0 VA 0 VA 1 20 A SPARE 10

7 -- -- -- 12 VA 0 VA 1 20 A SPARE 8

5 EP-FK-2 125 A 3 277 VA 0 VA 1 20 A SPARE 6

3 LIGHTING 20 A 1 18 VA 0 VA 1 20 A SPARE 4

1 POD 2 LEVEL 1 EM LIGHTING - UTILITY 20 A 1 268 VA 0 VA 1 20 A SPARE 2

CKT CIRCUIT DESCRIPTION TRIP PO... A B C PO... TRIP CIRCUIT DESCRIPTION CKT

BUS RATING: 225 AEP-FK-1A ENCLOSURE: Type 1 WIRES: 4 MCB RATING: 225 AMOUNTING: Surface PHASES: 3 MAINS TYPE: MCBPANEL NAME:FED FROM: ATS3 VOLTS: 480/277 Wye A.I.C. RATING: 22kA

NOTES: INTEGRAL SPD. SEE E3.01 FOR ADDITIONAL BREAKER COORDINATION REQUIREMENTS AND BASIS OF DESIGN CIRCUIT BREAKERS. 20A BREAKERS AS PER SQUARE D ED FRAME.

TOTAL NEC AMPS: 12 A*CONTINUOUS 1100 VA 125.00% 1375 VA TOTAL CONNECTED AMPS: 11 A*MOTOR LOAD 200 VA 112.50% 225 VA TOTAL NEC LOAD: 4300 VA*NON-CONTINUOUS 1700 VA 100.00% 1700 VA TOTAL CONNECTED LOAD: 4 kVA*RECEPTACLE 1000 VA 100.00% 1000 VALOAD CLASSIFICATION CONNECTED... DEMAND FACTOR CALC. NEC LOAD PANEL TOTALS

TOTAL CONNECTED AMPS: 14 A 11 A 9 ATOTAL CONNECTED LOAD: 1600 VA 1300 VA 1100 VA

41 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 42

39 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 40

37 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 38

35 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 36

33 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 34

31 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 32

29 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 30

27 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 28

25 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 26

23 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 24

21 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 22

19 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 20

17 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 18

15 MOTOR - FSDs 20 A 1 200 VA 0 VA 1 20 A SPARE 16

13 NON-CONTINUOUS - FSDs 20 A 1 1000 VA 0 VA 1 20 A SPARE 14

11 EMER. ELEC. 172A - POWER FOR FIRE ALARM 20 A 1 1000 VA 0 VA 1 20 A SPARE 12

9 EMER. ELEC. 172A - POWER FOR FIRE ALARM 20 A 1 1000 VA 0 VA 1 20 A SPARE 10

7 NON-CONTINUOUS - FSDs 20 A 1 100 VA 0 VA 1 20 A SPARE 8

5 EE 371A - F/A BOOSTER POWER SUPPLY 20 A 1 100 VA 0 VA 1 20 A SPARE 6

3 CONTINUOUS - FA BOOSTER 20 A 1 100 VA 0 VA 1 20 A SPARE 4

1 NON-CONTINUOUS 20 A 1 500 VA 0 VA 1 20 A SPARE 2

CKT CIRCUIT DESCRIPTION TRIP PO... A B C PO... TRIP CIRCUIT DESCRIPTION CKT

BUS RATING: 100 AEP-FK-1B ENCLOSURE: Type 1 WIRES: 4 MCB RATING: 50 AMOUNTING: Surface PHASES: 3 MAINS TYPE: MCBPANEL NAME:FED FROM: TX3 VOLTS: 120/208 Wye A.I.C. RATING: 10 kA

NOTES:

TOTAL NEC AMPS: 0 ATOTAL CONNECTED AMPS: 0 A

TOTAL NEC LOAD: 225 VATOTAL CONNECTED LOAD: 0.2 kVA

*LIGHTING 180 VA 125.00% 225 VALOAD CLASSIFICATION CONNECTED... DEMAND FACTOR CALC. NEC LOAD PANEL TOTALS

TOTAL CONNECTED AMPS: 1 A 0 A 0 ATOTAL CONNECTED LOAD: 180 VA 0 VA 0 VA

41 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 42

39 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 40

37 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 38

35 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 36

33 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 34

31 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 32

29 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 30

27 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 28

25 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 26

23 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 24

21 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 22

19 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 20

17 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 18

15 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 16

13 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 14

11 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 12

9 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 10

7 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 8

5 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 6

3 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 4

1 LIGHTING 20 A 1 180 VA 0 VA 1 20 A SPARE 2

CKT CIRCUIT DESCRIPTION TRIP PO... A B C PO... TRIP CIRCUIT DESCRIPTION CKT

BUS RATING: 100 ALP-FK-1 ENCLOSURE: Type 1 WIRES: 4 MCB RATING: 100 AMOUNTING: Surface PHASES: 3 MAINS TYPE: MCBPANEL NAME:FED FROM: USS-FK VOLTS: 480/277 Wye A.I.C. RATING: 22k

1 06/10/14 FEASIBILITY STUDY SET2 08/29/14 SCHEMATIC DESIGN SET3 12/18/14 50% DESIGN DEVELOPMENT SET4 01/15/15 100% DESIGN DEVELOPMENT SET5 04/06/15 60% CONSTRUCTION PERMIT SET6 05/07/15 90% CONSTRUCT. DOC. SET7 06/30/15 TIER 1 PHASE 1 PERMIT SET8 07/17/15 100% CONSTRUCT. DOC. SET

Page 34: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

ARCHITECT

CONSULTANT

STAMP

MARK DATE DESCRIPTION

PROJECT NUMBER:DRAWN BY:CHECKED BY:

SHEET TITLE

100% CONSTRUCTIONDOCUMENT SET

(UMBA 13-L2)

www.arup.com

955 Massachusetts Avenue4th Floor

Cambridge, MA 02139T 617 864 2987 F 617 864 6178

Arup USA Inc

7/17

/201

5 1:

58:0

4 PM

E-003

ELECTRICALSCHEDULE PLAN

SHEET 2

UMass Lowell NorthQuad Infrastructure

Renewal

21332

Lowell, MA

University of Massachusetts Building AuthorityUniversity of Massachusetts Lowell

JAIT

NOTES:

TOTAL NEC AMPS: 47 A*CONTINUOUS 1300 VA 125.00% 1625 VA TOTAL CONNECTED AMPS: 43 A*MOTOR LOAD 33035 VA 109.81% 36278 VA TOTAL NEC LOAD: 39123 VA*NON-CONTINUOUS 500 VA 100.00% 500 VA TOTAL CONNECTED LOAD: 35.6 kVA*RECEPTACLE 720 VA 100.00% 720 VALOAD CLASSIFICATION CONNECTED... DEMAND FACTOR CALC. NEC LOAD PANEL TOTALS

TOTAL CONNECTED AMPS: 45 A 44 A 40 ATOTAL CONNECTED LOAD: 12418 VA 12118 VA 11018 VA

41 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 42

39 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 40

37 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 38

35 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 36

33 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 34

31 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 32

29 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 30

27 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 28

25 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 26

23 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 24

21 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 22

19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20

17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18

15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16

13 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 14

11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12

9 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 10

7 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 8

5 -- -- -- 11018 VA 0 VA 1 20 A SPARE 6

3 -- -- -- 12118 VA 0 VA 1 20 A SPARE 4

1 TX2 100 A 3 12418... 0 VA 1 20 A SPARE 2

CKT CIRCUIT DESCRIPTION TRIP PO... A B C PO... TRIP CIRCUIT DESCRIPTION CKT

BUS RATING: 225 AOEP-FK-1A ENCLOSURE: Type 1 WIRES: 4 MCB RATING: 225 AMOUNTING: Surface PHASES: 3 MAINS TYPE: MCBPANEL NAME:FED FROM: ATS1 VOLTS: 480/277 Wye A.I.C. RATING: 22kA

NOTES:

TOTAL NEC AMPS: 109 A*CONTINUOUS 1300 VA 125.00% 1625 VA TOTAL CONNECTED AMPS: 99 A*MOTOR LOAD 33035 VA 109.81% 36278 VA TOTAL NEC LOAD: 39123 VA*NON-CONTINUOUS 500 VA 100.00% 500 VA TOTAL CONNECTED LOAD: 35.6 kVA*RECEPTACLE 720 VA 100.00% 720 VALOAD CLASSIFICATION CONNECTED... DEMAND FACTOR CALC. NEC LOAD PANEL TOTALS

TOTAL CONNECTED AMPS: 105 A 102 A 92 ATOTAL CONNECTED LOAD: 12418 VA 12118 VA 11018 VA

41 NON-CONTINUOUS - DRY VALUE 20 A 1 500 VA 0 VA 1 20 A SPARE 42

39 CONTINUOUS - HEAT TRACE 20 A 1 500 VA 0 VA 1 20 A SPARE 40

37 CONTINUOUS - HEAT TRACE 20 A 1 500 VA 0 VA 1 20 A SPARE 38

35 -- -- -- 52 VA 0 VA 1 20 A SPARE 36

33 MOTOR - AC 2-1 15 A 2 52 VA 0 VA 1 20 A SPARE 34

31 -- -- -- 0 VA 0 VA 1 20 A SPARE 32

29 RECEPTACLE - L6-30 20 A 2 180 VA 0 VA 1 20 A SPARE 30

27 -- -- -- 1352 VA 0 VA 1 20 A SPARE 28

25 MOTOR - AC 3-1/3-2 20 A 2 1352 VA 0 VA 1 20 A SPARE 26

23 -- -- -- 0 VA 0 VA 1 20 A SPARE 24

21 RECEPTACLE - L6-30 20 A 2 180 VA 0 VA 1 20 A SPARE 22

19 MOTOR - EF 2-1 20 A 1 528 VA 0 VA 1 20 A SPARE 20

17 MOTOR - EF 2-2 20 A 1 528 VA 0 VA 1 20 A SPARE 18

15 CONTINUOUS - DDC PANEL 20 A 1 100 VA 0 VA 1 20 A SPARE 16

13 CONTINUOUS - SECURITY SYSTEM 20 A 1 100 VA 0 VA 1 20 A SPARE 14

11 -- -- -- 9706 VA 0 VA 1 20 A SPARE 12

9 -- -- -- 9306 VA 0 VA 1 20 A SPARE 10

7 OEP-FK-3 150 A 3 9358 VA 0 VA 1 20 A SPARE 8

5 -- -- -- 52 VA 0 VA 1 20 A SPARE 6

3 -- -- -- 628 VA 0 VA 1 20 A SPARE 4

1 OEP-FK-2 100 A 3 580 VA 0 VA 1 20 A SPARE 2

CKT CIRCUIT DESCRIPTION TRIP PO... A B C PO... TRIP CIRCUIT DESCRIPTION CKT

BUS RATING: 225 AOEP-FK-1B ENCLOSURE: Type 1 WIRES: 4 MCB RATING: 225 AMOUNTING: Surface PHASES: 3 MAINS TYPE: MCBPANEL NAME:FED FROM: TX2 VOLTS: 120/208 Wye A.I.C. RATING: 10kA

NOTES:

TOTAL NEC AMPS: 21 A*CONTINUOUS 1000 VA 125.00% 1250 VA TOTAL CONNECTED AMPS: 20 A*MOTOR LOAD 2200 VA 109.09% 2400 VA TOTAL NEC LOAD: 7710 VA*NON-CONTINUOUS 1000 VA 100.00% 1000 VA TOTAL CONNECTED LOAD: 7.3 kVA*RECEPTACLE 3060 VA 100.00% 3060 VALOAD CLASSIFICATION CONNECTED... DEMAND FACTOR CALC. NEC LOAD PANEL TOTALS

TOTAL CONNECTED AMPS: 21 A 20 A 20 ATOTAL CONNECTED LOAD: 2500 VA 2380 VA 2380 VA

41 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 42

39 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 40

37 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 38

35 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 36

33 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 34

31 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 32

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28

25 CORR. 100C6 - POWER FOR VAV/HVAC... 20 A 1 100 VA 0 VA 1 20 A SPARE 26

23 MOTOR - HAIR DRYER 20 A 1 800 VA 0 VA 1 20 A SPARE 24

21 -- -- -- 500 VA 0 VA 1 20 A SPARE 22

19 *GEN HEATER 60 A 2 500 VA 0 VA 1 20 A SPARE 20

17 RECEPTACLE 20 A 1 540 VA 0 VA 1 20 A SPARE 18

15 MOTOR - HAIR DRYER 20 A 1 800 VA 0 VA 1 20 A SPARE 16

13 CONTINUOUS - GEN CHARGER 20 A 1 1000 VA 0 VA 1 20 A SPARE 14

11 RECEPTACLE 20 A 1 540 VA 0 VA 1 20 A SPARE 12

9 RECEPTACLE 20 A 1 720 VA 0 VA 1 20 A SPARE 10

7 RECEPTACLE 20 A 1 720 VA 0 VA 1 20 A SPARE 8

5 MOTOR - COOLER 20 A 1 500 VA 0 VA 1 20 A SPARE 6

3 RECEPTACLE 20 A 1 360 VA 0 VA 1 20 A SPARE 4

1 RECEPTACLE - L5-30 20 A 1 180 VA 0 VA 1 20 A SPARE 2

CKT CIRCUIT DESCRIPTION TRIP PO... A B C PO... TRIP CIRCUIT DESCRIPTION CKT

BUS RATING: 225 ARP-K-1 ENCLOSURE: Type 1 WIRES: 4 MCB RATING: 225 AMOUNTING: Surface PHASES: 3 MAINS TYPE: MCBPANEL NAME:FED FROM: DP-FK1 VOLTS: 120/208 Wye A.I.C. RATING: 10kA

NOTES:

TOTAL NEC AMPS: 19 ATOTAL CONNECTED AMPS: 19 A

TOTAL NEC LOAD: 6860 VA*NON-CONTINUOUS 6500 VA 100.00% 6500 VA TOTAL CONNECTED LOAD: 6.9 kVA*RECEPTACLE 360 VA 100.00% 360 VALOAD CLASSIFICATION CONNECTED... DEMAND FACTOR CALC. NEC LOAD PANEL TOTALS

TOTAL CONNECTED AMPS: 31 A 4 A 28 ATOTAL CONNECTED LOAD: 3360 VA 500 VA 3000 VA

41 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 42

39 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 40

37 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 38

35 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 36

33 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 34

31 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 32

29 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 30

27 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 28

25 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 26

23 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 24

21 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 22

19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20

17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18

15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16

13 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 14

11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12

9 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 10

7 -- -- -- 3000 VA 0 VA 1 20 A SPARE 8

5 GENERATOR AUX POWER CONNECTION 60 A 2 3000 VA 0 VA 1 20 A SPARE 6

3 GENERATOR BATTERY CHARGER 20 A 1 500 VA 0 VA 1 20 A SPARE 4

1 RECEPTACLE 20 A 1 360 VA 0 VA 1 20 A SPARE 2

CKT CIRCUIT DESCRIPTION TRIP PO... A B C PO... TRIP CIRCUIT DESCRIPTION CKT

BUS RATING: 225 ARP-F-1 ENCLOSURE: Type 1 WIRES: 4 MCB RATING: 225 AMOUNTING: Surface PHASES: 3 MAINS TYPE: MCBPANEL NAME:FED FROM: DP-FK1 VOLTS: 120/208 Wye A.I.C. RATING: 10kA

1 06/10/14 FEASIBILITY STUDY SET2 08/29/14 SCHEMATIC DESIGN SET3 12/18/14 50% DESIGN DEVELOPMENT SET4 01/15/15 100% DESIGN DEVELOPMENT SET5 04/06/15 60% CONSTRUCTION PERMIT SET6 05/07/15 90% CONSTRUCT. DOC. SET7 06/30/15 TIER 1 PHASE 1 PERMIT SET8 07/17/15 100% CONSTRUCT. DOC. SET

Page 35: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

ARCHITECT

CONSULTANT

STAMP

MARK DATE DESCRIPTION

PROJECT NUMBER:DRAWN BY:CHECKED BY:

SHEET TITLE

100% CONSTRUCTIONDOCUMENT SET

(UMBA 13-L2)

www.arup.com

955 Massachusetts Avenue4th Floor

Cambridge, MA 02139T 617 864 2987 F 617 864 6178

Arup USA Inc

7/17

/201

5 1:

58:0

6 PM

E-004

ELECTRICALSCHEDULE PLAN

SHEET 3

UMass Lowell NorthQuad Infrastructure

Renewal

21332

Lowell, MA

University of Massachusetts Building AuthorityUniversity of Massachusetts Lowell

JAIT

*CONTINUOUS 500 VA 125.00% 625 VA*MOTOR LOAD 23941 VA 107.52% 25742 VA TOTAL NEC AMPS: 115 A*NON-CONTINUOUS 50 VA 100.00% 50 VA TOTAL CONNECTED AMPS: 114 A*RECEPTACLE 14180 VA 85.26% 12090 VA TOTAL NEC LOAD: 41411 VAReceptacle 360 VA 100.00% 360 VA TOTAL CONNECTED LOAD: 41 kVA*LIGHTING 2035 VA 125.00% 2544 VALOAD CLASSIFICATION CONNECTED... DEMAND FACTOR CALC. NEC LOAD PANEL TOTALS

TOTAL CONNECTED AMPS: 114 A 116 A 112 ATOTAL CONNECTED LOAD: 13700 VA 13919 VA 13448 VA

83 SPACE -- -- 0 VA 0 VA -- -- SPACE 84

81 SPACE -- -- 0 VA 0 VA -- -- SPACE 82

79 SPACE -- -- 0 VA 0 VA -- -- SPACE 80

77 SPACE -- -- 0 VA 0 VA -- -- SPACE 78

75 SPACE -- -- 0 VA 0 VA -- -- SPACE 76

73 SPACE -- -- 0 VA 0 VA -- -- SPACE 74

71 SPACE -- -- 0 VA 0 VA -- -- SPACE 72

69 SPACE -- -- 0 VA 0 VA -- -- SPACE 70

67 SPACE -- -- 0 VA 0 VA -- -- SPACE 68

65 SPACE -- -- 0 VA 0 VA -- -- SPACE 66

63 SPACE -- -- 0 VA 0 VA -- -- SPACE 64

61 SPACE -- -- 0 VA 0 VA -- -- SPACE 62

59 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 60

57 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 58

55 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 56

53 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 54

51 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 52

49 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 50

47 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 48

45 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 46

43 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 44

41 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 42

39 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 40

37 RECEPTACLE 20 A 1 720 VA 800 VA 1 20 A MOTOR - HAND DRYER 38

35 NON-CONTINUOUS - HAND DRYER 20 A 1 800 VA 800 VA 1 20 A MOTOR - HAND DRYER 36

33 RECEPTACLE 20 A 1 720 VA 540 VA 1 20 A RECEPTACLE 34

31 NON-CONTINUOUS - COOLER 20 A 1 500 VA 720 VA 1 20 A RECEPTACLE 32

29 RECEPTACLE 20 A 1 540 VA 540 VA 1 20 A RECEPTACLE 30

27 RECEPTACLE - L5-30 30 A 1 500 VA 500 VA 1 20 A MOTOR - COOLER 28

25 RECEPTACLE 20 A 1 360 VA 500 VA 1 20 A MOTOR - HAND DRYER 26

23 MOTOR - HAND DRYER 20 A 1 500 VA 500 VA 1 20 A NON-CONTINUOUS - COOLER 24

21 RECEPTACLE 20 A 1 360 VA 360 VA 1 20 A RECEPTACLE 22

19 RECEPTACLE 20 A 1 360 VA 360 VA 1 20 A RECEPTACLE 20

17 LIGHTING 20 A 1 305 VA 360 VA 1 20 A RECEPTACLE 18

15 CONTINUOUS - CONTROL PANEL 20 A 1 100 VA 100 VA 1 20 A CONTINUOUS - DDC PANEL 16

13 NON-CONTINUOUS - HAND DRYER 20 A 1 800 VA 100 VA 1 20 A CONTINUOUS - DDC PANEL 14

11 LIGHTING 20 A 1 170 VA 180 VA 1 20 A RECEPTACLE - L5-30 12

9 MOTOR - EF 1-2 20 A 1 528 VA 900 VA 1 20 A RECEPTACLE 10

7 LIGHTING 20 A 1 336 VA 500 VA 1 20 A MOTOR -COOLER 8

5 -- -- -- 8225 VA 528 VA 1 20 A MOTOR - EF 1-1 6

3 -- -- -- 9176 VA 135 VA 1 20 A LIGHTING 4

1 SP-P3 100 A 3 7518 VA 126 VA 1 20 A LIGHTING 2

CKT CIRCUIT DESCRIPTION TRIP PO... A B C PO... TRIP CIRCUIT DESCRIPTION CKT

BUS RATING: 225 ASP-P1 ENCLOSURE: Type 1 WIRES: 4 MCB RATING: 150 AMOUNTING: Surface PHASES: 3 MAINS TYPE: MCBPANEL NAME:FED FROM: VOLTS: 120/208 Wye A.I.C. RATING: 22kA

NOTES:

*CONTINUOUS 700 VA 125.00% 875 VA TOTAL NEC AMPS: 60 A*MOTOR LOAD 14289 VA 122.69% 17532 VA TOTAL CONNECTED AMPS: 50 A*NON-CONTINUOUS 900 VA 100.00% 900 VA TOTAL NEC LOAD: 21549 VA*RECEPTACLE 1040 VA 100.00% 1040 VA TOTAL CONNECTED LOAD: 17.9 kVA*LIGHTING 962 VA 125.00% 1203 VALOAD CLASSIFICATION CONNECTED... DEMAND FACTOR CALC. NEC LOAD PANEL TOTALS

TOTAL CONNECTED AMPS: 53 A 50 A 47 ATOTAL CONNECTED LOAD: 6331 VA 5933 VA 5624 VA

41 -- -- -- 0 VA 52 VA -- -- -- 42

39 -- -- -- 0 VA 52 VA 2 15 A MOTOR - AC 1-2 40

37 INV 20 A 3 0 VA 100 VA 1 20 A CONTINUOUS - FA BOOSTER 38

35 SPARE 20 A 1 0 VA 0 VA -- -- SPACE 36

33 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 34

31 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 32

29 POWER PROVISION FOR FIRE ALARM 20 A 1 100 VA 0 VA 1 20 A SPARE 30

27 POWER PROVISION FOR FIRE ALARM 20 A 1 100 VA 52 VA -- -- -- 28

25 LIGHTING 20 A 1 30 VA 52 VA 2 15 A MOTOR - AC 1-1 26

23 LIGHTING 20 A 1 18 VA 209 VA 1 20 A LIGHTING (VIA INV3) 24

21 LIGHTING (VIA INV1) 20 A 1 70 VA 0 VA -- -- SPACE 22

19 NON-CONTINUOUS - FSDs 20 A 1 100 VA 0 VA -- -- SPACE 20

17 NON CONTINUOUS - FSDs 20 A 1 200 VA 255 VA 1 20 A LIGHTING (VIA INV2) 18

15 NON-CONTINUOUS - FSDs 20 A 1 200 VA 0 VA -- -- SPACE 16

13 -- -- -- 52 VA 0 VA -- -- SPACE 14

11 MOTOR - AC 1-3 15 A 2 52 VA 0 VA -- -- SPACE 12

9 CONTINUOUS - SECURITY SYSTEM 20 A 1 100 VA 0 VA 1 20 A MOTOR - ELEVATOR CABIN FAN 10

7 RECEPTACLE 20 A 1 180 VA 100 VA 1 20 A CONTINUOUS - FACU 8

5 -- -- -- 4738 VA 0 VA -- -- -- 6

3 -- -- -- 4859 VA 500 VA 2 30 A RECEPTACLE - L6-30 4

1 OP-SP-3 100 A 3 5717 VA 2

CKT CIRCUIT DESCRIPTION TRIP PO... A B C PO... TRIP CIRCUIT DESCRIPTION CKT

BUS RATING: 225 AOP-SP-1 ENCLOSURE: Type 1 WIRES: 4 MCB RATING: 200 AMOUNTING: Surface PHASES: 3 MAINS TYPE: MCBPANEL NAME:FED FROM: VOLTS: 120/208 Wye A.I.C. RATING: 22kA

TOTAL NEC AMPS: 0 ATOTAL CONNECTED AMPS: 0 A

TOTAL NEC LOAD: 0 VATOTAL CONNECTED LOAD: 0 kVA

LOAD CLASSIFICATION CONNECTED... DEMAND FACTOR CALC. NEC LOAD PANEL TOTALS

TOTAL CONNECTED AMPS: 0 A 0 A 0 ATOTAL CONNECTED LOAD: 0 VA 0 VA 0 VA

41 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 42

39 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 40

37 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 38

35 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 36

33 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 34

31 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 32

29 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 30

27 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 28

25 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 26

23 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 24

21 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 22

19 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 20

17 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 18

15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16

13 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 14

11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12

9 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 10

7 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 8

5 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 6

3 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 4

1 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 2

CKT CIRCUIT DESCRIPTION TRIP PO... A B C PO... TRIP CIRCUIT DESCRIPTION CKT

BUS RATING: 100 ALP-FK-2 ENCLOSURE: Type 1 WIRES: 4 MCB RATING: 100 AMOUNTING: Surface PHASES: 3 MAINS TYPE: MCBPANEL NAME:FED FROM: USS-FK VOLTS: 480/277 Wye A.I.C. RATING: 22kA

NOTES: INTEGRAL SPD. PROVIDE WITH MAIN DISCONNECT SWITCH. SEE E3.01 FOR ADDITIONAL BREAKER COORDINATION REQUIREMENTS AND BASIS OF DESIGN CIRCUIT BREAKERS. 20ABREAKERS AS PER SQUARE D ED FRAME.

TOTAL NEC AMPS: 0 ATOTAL CONNECTED AMPS: 0 A

TOTAL NEC LOAD: 361 VATOTAL CONNECTED LOAD: 0.3 kVA

*LIGHTING 289 VA 125.00% 361 VALOAD CLASSIFICATION CONNECTED... DEMAND FACTOR CALC. NEC LOAD PANEL TOTALS

TOTAL CONNECTED AMPS: 1 A 0 A 0 ATOTAL CONNECTED LOAD: 277 VA 12 VA 0 VA

41 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 42

39 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 40

37 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 38

35 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 36

33 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 34

31 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 32

29 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 30

27 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 28

25 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 26

23 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 24

21 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 22

19 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 20

17 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 18

15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16

13 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 14

11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12

9 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 10

7 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 8

5 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 6

3 LIGHTING 20 A 1 12 VA 0 VA 1 20 A SPARE 4

1 LIGHTING 20 A 1 277 VA 0 VA 1 20 A SPARE 2

CKT CIRCUIT DESCRIPTION TRIP PO... A B C PO... TRIP CIRCUIT DESCRIPTION CKT

BUS RATING: 125 AEP-FK-2 ENCLOSURE: Type 1 WIRES: 4 MCB RATING: N/AMOUNTING: Surface PHASES: 3 MAINS TYPE: MLOPANEL NAME:FED FROM: EP-FK-1A VOLTS: 480/277 Wye A.I.C. RATING: 22kA

DP-S DP-P

1 06/10/14 FEASIBILITY STUDY SET2 08/29/14 SCHEMATIC DESIGN SET3 12/18/14 50% DESIGN DEVELOPMENT SET4 01/15/15 100% DESIGN DEVELOPMENT SET5 04/06/15 60% CONSTRUCTION PERMIT SET6 05/07/15 90% CONSTRUCT. DOC. SET7 06/30/15 TIER 1 PHASE 1 PERMIT SET8 07/17/15 100% CONSTRUCT. DOC. SET

Page 36: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

ARCHITECT

CONSULTANT

STAMP

MARK DATE DESCRIPTION

PROJECT NUMBER:DRAWN BY:CHECKED BY:

SHEET TITLE

100% CONSTRUCTIONDOCUMENT SET

(UMBA 13-L2)

www.arup.com

955 Massachusetts Avenue4th Floor

Cambridge, MA 02139T 617 864 2987 F 617 864 6178

Arup USA Inc

7/17

/201

5 1:

58:0

8 PM

E-005

ELECTRICALSCHEDULE PLAN

SHEET 4

UMass Lowell NorthQuad Infrastructure

Renewal

21332

Lowell, MA

University of Massachusetts Building AuthorityUniversity of Massachusetts Lowell

JAIT

NOTES:

TOTAL NEC AMPS: 4 ATOTAL CONNECTED AMPS: 3 A

TOTAL NEC LOAD: 1417 VA*CONTINUOUS 100 VA 125.00% 125 VA TOTAL CONNECTED LOAD: 1.3 kVA*MOTOR LOAD 1160 VA 111.38% 1292 VALOAD CLASSIFICATION CONNECTED... DEMAND FACTOR CALC. NEC LOAD PANEL TOTALS

TOTAL CONNECTED AMPS: 6 A 6 A 0 ATOTAL CONNECTED LOAD: 580 VA 628 VA 52 VA

41 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 42

39 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 40

37 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 38

35 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 36

33 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 34

31 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 32

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28

25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26

23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24

21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22

19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20

17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18

15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16

13 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 14

11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12

9 CONTINUOUS - DDC PANEL 20 A 1 100 VA 0 VA 1 20 A SPARE 10

7 -- -- -- 52 VA 0 VA 1 20 A SPARE 8

5 MOTOR - AC 2-3 15 A 2 52 VA 0 VA 1 20 A SPARE 6

3 MOTOR - EF 2-3 15 A 1 528 VA 0 VA 1 20 A SPARE 4

1 MOTOR - SF-1 15 A 1 528 VA 0 VA 1 20 A SPARE 2

CKT CIRCUIT DESCRIPTION TRIP PO... A B C PO... TRIP CIRCUIT DESCRIPTION CKT

BUS RATING: 100 AOEP-FK-2 ENCLOSURE: Type 1 WIRES: 4 MCB RATING: 100 AMOUNTING: Surface PHASES: 3 MAINS TYPE: MCBPANEL NAME:FED FROM: OEP-FK-1B VOLTS: 120/208 Wye A.I.C. RATING: 10kA

NOTES:

TOTAL NEC AMPS: 1 ATOTAL CONNECTED AMPS: 1 A

TOTAL NEC LOAD: 360 VATOTAL CONNECTED LOAD: 0.4 kVA

*RECEPTACLE 360 VA 100.00% 360 VALOAD CLASSIFICATION CONNECTED... DEMAND FACTOR CALC. NEC LOAD PANEL TOTALS

TOTAL CONNECTED AMPS: 2 A 2 A 0 ATOTAL CONNECTED LOAD: 180 VA 180 VA 0 VA

41 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 42

39 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 40

37 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 38

35 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 36

33 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 34

31 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 32

29 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 30

27 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 28

25 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 26

23 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 24

21 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 22

19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20

17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18

15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16

13 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 14

11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12

9 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 10

7 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 8

5 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 6

3 RECEPTACLE - L5-30 20 A 1 180 VA 0 VA 1 20 A SPARE 4

1 RECEPTACLE 20 A 1 180 VA 0 VA 1 20 A SPARE 2

CKT CIRCUIT DESCRIPTION TRIP PO... A B C PO... TRIP CIRCUIT DESCRIPTION CKT

BUS RATING: 225 ARP-K-2 ENCLOSURE: Type 1 WIRES: 4 MCB RATING: 225 AMOUNTING: Surface PHASES: 3 MAINS TYPE: MCBPANEL NAME:FED FROM: DP-FK1 VOLTS: 120/208 Wye A.I.C. RATING: 10kA

NOTES:

TOTAL NEC AMPS: 17 ATOTAL CONNECTED AMPS: 17 A

TOTAL NEC LOAD: 6240 VA*MOTOR LOAD 3700 VA 105.41% 3900 VA TOTAL CONNECTED LOAD: 6 kVA*RECEPTACLE 2340 VA 100.00% 2340 VALOAD CLASSIFICATION CONNECTED... DEMAND FACTOR CALC. NEC LOAD PANEL TOTALS

TOTAL CONNECTED AMPS: 16 A 16 A 18 ATOTAL CONNECTED LOAD: 1960 VA 1940 VA 2140 VA

41 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 42

39 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 40

37 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 38

35 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 36

33 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 34

31 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 32

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28

25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26

23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24

21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22

19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20

17 MOTOR - HAIR DRYER 20 A 1 800 VA 0 VA 1 20 A SPARE 18

15 MOTOR - COOLER 20 A 1 500 VA 0 VA 1 20 A SPARE 16

13 MOTOR - HAIR DRYER 20 A 1 800 VA 0 VA 1 20 A SPARE 14

11 RECEPTACLE 20 A 1 540 VA 0 VA 1 20 A SPARE 12

9 RECEPTACLE 20 A 1 900 VA 0 VA 1 20 A SPARE 10

7 MOTOR - HAIR DRYER 20 A 1 800 VA 0 VA 1 20 A SPARE 8

5 MOTOR - HAIR DRYER 20 A 1 800 VA 0 VA 1 20 A SPARE 6

3 RECEPTACLE 20 A 1 540 VA 0 VA 1 20 A SPARE 4

1 RECEPTACLE 20 A 1 360 VA 0 VA 1 20 A SPARE 2

CKT CIRCUIT DESCRIPTION TRIP PO... A B C PO... TRIP CIRCUIT DESCRIPTION CKT

BUS RATING: 225 ARP-F-2 ENCLOSURE: Type 1 WIRES: 4 MCB RATING: 225 AMOUNTING: Surface PHASES: 3 MAINS TYPE: MCBPANEL NAME:FED FROM: DP-FK1 VOLTS: 120/208 Wye A.I.C. RATING: 10kA

NOTES:

TOTAL NEC AMPS: 1 ATOTAL CONNECTED AMPS: 0 A

TOTAL NEC LOAD: 465 VATOTAL CONNECTED LOAD: 0.4 kVA

*LIGHTING 372 VA 125.00% 465 VALOAD CLASSIFICATION CONNECTED... DEMAND FACTOR CALC. NEC LOAD PANEL TOTALS

TOTAL CONNECTED AMPS: 1 A 0 A 0 ATOTAL CONNECTED LOAD: 360 VA 12 VA 0 VA

41 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 42

39 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 40

37 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 38

35 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 36

33 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 34

31 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 32

29 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 30

27 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 28

25 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 26

23 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 24

21 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 22

19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20

17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18

15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16

13 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 14

11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12

9 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 10

7 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 8

5 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 6

3 LIGHTING 20 A 1 12 VA 0 VA 1 20 A SPARE 4

1 LIGHTING 20 A 1 360 VA 0 VA 1 20 A SPARE 2

CKT CIRCUIT DESCRIPTION TRIP PO... A B C PO... TRIP CIRCUIT DESCRIPTION CKT

BUS RATING: 100 ALP-FK-3 ENCLOSURE: Type 1 WIRES: 4 MCB RATING: 100 AMOUNTING: Surface PHASES: 3 MAINS TYPE: MCBPANEL NAME:FED FROM: USS-FK VOLTS: 480/277 Wye A.I.C. RATING: 22kA

1 06/10/14 FEASIBILITY STUDY SET2 08/29/14 SCHEMATIC DESIGN SET3 12/18/14 50% DESIGN DEVELOPMENT SET4 01/15/15 100% DESIGN DEVELOPMENT SET5 04/06/15 60% CONSTRUCTION PERMIT SET6 05/07/15 90% CONSTRUCT. DOC. SET7 06/30/15 TIER 1 PHASE 1 PERMIT SET8 07/17/15 100% CONSTRUCT. DOC. SET

Page 37: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

ARCHITECT

CONSULTANT

STAMP

MARK DATE DESCRIPTION

PROJECT NUMBER:DRAWN BY:CHECKED BY:

SHEET TITLE

100% CONSTRUCTIONDOCUMENT SET

(UMBA 13-L2)

www.arup.com

955 Massachusetts Avenue4th Floor

Cambridge, MA 02139T 617 864 2987 F 617 864 6178

Arup USA Inc

7/17

/201

5 1:

58:1

1 PM

E-006

ELECTRICALSCHEDULE PLAN

SHEET 5

UMass Lowell NorthQuad Infrastructure

Renewal

21332

Lowell, MA

University of Massachusetts Building AuthorityUniversity of Massachusetts Lowell

JAIT

NOTES: PROVIDE MAIN BREAKER AS LSI ELECTRONIC TRIP.

TOTAL NEC AMPS: 33 ATOTAL CONNECTED AMPS: 28 A

TOTAL NEC LOAD: 27709 VATOTAL CONNECTED LOAD: 23.6 kVA

*MOTOR LOAD 23552 VA 117.65% 27709 VALOAD CLASSIFICATION CONNECTED... DEMAND FACTOR CALC. NEC LOAD PANEL TOTALS

TOTAL CONNECTED AMPS: 20 A 45 A 20 ATOTAL CONNECTED LOAD: 5542 VA 12467 VA 5542 VA

41 SPACE -- -- 0 VA 0 VA -- -- SPACE 42

39 SPACE -- -- 0 VA 0 VA -- -- SPACE 40

37 SPACE -- -- 0 VA 0 VA -- -- SPACE 38

35 SPACE -- -- 0 VA 0 VA -- -- SPACE 36

33 SPACE -- -- 0 VA 0 VA -- -- SPACE 34

31 SPACE -- -- 0 VA 0 VA -- -- SPACE 32

29 SPACE -- -- 0 VA 0 VA -- -- SPACE 30

27 SPACE -- -- 0 VA 0 VA -- -- SPACE 28

25 SPACE -- -- 0 VA 0 VA -- -- SPACE 26

23 SPACE -- -- 0 VA 0 VA -- -- SPACE 24

21 SPACE -- -- 0 VA 0 VA -- -- SPACE 22

19 SPACE -- -- 0 VA 0 VA -- -- SPACE 20

17 SPARE 20 A 1 0 VA 0 VA -- -- SPACE 18

15 SPARE 20 A 1 0 VA 0 VA -- -- SPACE 16

13 SPARE 20 A 1 0 VA 0 VA -- -- SPACE 14

11 SPARE 20 A 1 0 VA 0 VA -- -- SPACE 12

9 SPARE 20 A 1 0 VA 0 VA -- -- SPACE 10

7 SPARE 20 A 1 0 VA 0 VA -- -- SPACE 8

5 -- -- -- 5542 VA 0 VA -- -- SPACE 6

3 -- -- -- 5542 VA 6925 VA 1 50 A MOTOR - POD 2 L3 DWH-1 4

1 MOTOR - POD 1 ROOF RTU 2 25 A 3 5542 VA 0 VA -- -- SPACE 2

CKT CIRCUIT DESCRIPTION TRIP PO... A B C PO... TRIP CIRCUIT DESCRIPTION CKT

BUS RATING: 600 AMP-FK-3 ENCLOSURE: Type 1 WIRES: 4 MCB RATING: 600 AMOUNTING: Surface PHASES: 3 MAINS TYPE: MCBPANEL NAME:FED FROM: USS-FK VOLTS: 480/277 Wye A.I.C. RATING: 35kA

NOTES: INTEGRAL SPD. PROVIDE WITH MAIN DISCONNECT SWITCH. SEE E3.01 FOR ADDITIONAL BREAKER COORDINATION REQUIREMENTS AND BASIS OF DESIGN CIRCUIT BREAKERS. 20ABREAKERS AS PER SQUARE D ED FRAME.

TOTAL NEC AMPS: 0 ATOTAL CONNECTED AMPS: 0 A

TOTAL NEC LOAD: 346 VATOTAL CONNECTED LOAD: 0.3 kVA

*LIGHTING 277 VA 125.00% 346 VALOAD CLASSIFICATION CONNECTED... DEMAND FACTOR CALC. NEC LOAD PANEL TOTALS

TOTAL CONNECTED AMPS: 1 A 0 A 0 ATOTAL CONNECTED LOAD: 277 VA 0 VA 0 VA

41 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 42

39 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 40

37 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 38

35 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 36

33 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 34

31 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 32

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28

25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26

23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24

21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22

19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20

17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18

15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16

13 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 14

11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12

9 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 10

7 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 8

5 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 6

3 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 4

1 LIGHTING 20 A 1 277 VA 0 VA 1 20 A SPARE 2

CKT CIRCUIT DESCRIPTION TRIP PO... A B C PO... TRIP CIRCUIT DESCRIPTION CKT

BUS RATING: 125 AEP-FK-3 ENCLOSURE: Type 1 WIRES: 4 MCB RATING: N/AMOUNTING: Surface PHASES: 3 MAINS TYPE: MLOPANEL NAME:FED FROM: EP-FK-1A VOLTS: 480/277 Wye A.I.C. RATING: 22kA

NOTES:

TOTAL NEC AMPS: 88 ATOTAL CONNECTED AMPS: 79 A

TOTAL NEC LOAD: 31614 VA*MOTOR LOAD 28011 VA 111.57% 31254 VA TOTAL CONNECTED LOAD: 28.4 kVA*RECEPTACLE 360 VA 100.00% 360 VALOAD CLASSIFICATION CONNECTED... DEMAND FACTOR CALC. NEC LOAD PANEL TOTALS

TOTAL CONNECTED AMPS: 78 A 78 A 81 ATOTAL CONNECTED LOAD: 9358 VA 9306 VA 9706 VA

41 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 42

39 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 40

37 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 38

35 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 36

33 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 34

31 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 32

29 -- -- -- 2402 VA 0 VA 1 20 A SPARE 30

27 -- -- -- 2402 VA 0 VA 1 20 A SPARE 28

25 MOTOR - ACCU-3 CONNECTION 2 30 A 3 2402 VA 0 VA 1 20 A SPARE 26

23 MOTOR - SF-2 20 A 1 528 VA 0 VA 1 20 A SPARE 24

21 RECEPTACLE 20 A 1 180 VA 0 VA 1 20 A SPARE 22

19 -- -- -- 2402 VA 0 VA 1 20 A SPARE 20

17 -- -- -- 2402 VA 0 VA 1 20 A SPARE 18

15 MOTOR - ACCU-2 30 A 3 2402 VA 0 VA 1 20 A SPARE 16

13 -- -- -- 52 VA 0 VA 1 20 A SPARE 14

11 MOTOR - AC 2-6 20 A 2 52 VA 0 VA 1 20 A SPARE 12

9 -- -- -- 4323 VA 0 VA 1 20 A SPARE 10

7 -- -- -- 4323 VA 0 VA 1 20 A SPARE 8

5 MOTOR - ACCU-3 CONNECTION 1 50 A 3 4323 VA 0 VA 1 20 A SPARE 6

3 -- -- -- 0 VA 0 VA 1 20 A SPARE 4

1 RECEPTACLE - L6-30 20 A 2 180 VA 0 VA 1 20 A SPARE 2

CKT CIRCUIT DESCRIPTION TRIP PO... A B C PO... TRIP CIRCUIT DESCRIPTION CKT

BUS RATING: 225 AOEP-FK-3 ENCLOSURE: Type 1 WIRES: 4 MCB RATING: 150 AMOUNTING: Surface PHASES: 3 MAINS TYPE: MCBPANEL NAME:FED FROM: OEP-FK-1B VOLTS: 120/208 Wye A.I.C. RATING: 10kA

NOTES:

TOTAL NEC AMPS: 5 ATOTAL CONNECTED AMPS: 5 A

TOTAL NEC LOAD: 1900 VA*MOTOR LOAD 800 VA 125.00% 1000 VA TOTAL CONNECTED LOAD: 1.7 kVA*RECEPTACLE 900 VA 100.00% 900 VALOAD CLASSIFICATION CONNECTED... DEMAND FACTOR CALC. NEC LOAD PANEL TOTALS

TOTAL CONNECTED AMPS: 5 A 7 A 3 ATOTAL CONNECTED LOAD: 540 VA 800 VA 360 VA

41 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 42

39 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 40

37 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 38

35 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 36

33 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 34

31 SPACE -- -- 0 VA 0 VA 1 20 A SPARE 32

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28

25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26

23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24

21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22

19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20

17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18

15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16

13 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 14

11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12

9 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 10

7 RECEPTACLE - L5-30 20 A 1 180 VA 0 VA 1 20 A SPARE 8

5 RECEPTACLE 20 A 1 360 VA 0 VA 1 20 A SPARE 6

3 MOTOR - HAIR DRYER 20 A 1 800 VA 0 VA 1 20 A SPARE 4

1 RECEPTACLE 20 A 1 360 VA 0 VA 1 20 A SPARE 2

CKT CIRCUIT DESCRIPTION TRIP PO... A B C PO... TRIP CIRCUIT DESCRIPTION CKT

BUS RATING: 225 ARP-K-3 ENCLOSURE: Type 1 WIRES: 4 MCB RATING: 225 AMOUNTING: Surface PHASES: 3 MAINS TYPE: MCBPANEL NAME:FED FROM: DP-FK1 VOLTS: 120/208 Wye A.I.C. RATING: 10kA

1 06/10/14 FEASIBILITY STUDY SET2 08/29/14 SCHEMATIC DESIGN SET3 12/18/14 50% DESIGN DEVELOPMENT SET4 01/15/15 100% DESIGN DEVELOPMENT SET5 04/06/15 60% CONSTRUCTION PERMIT SET6 05/07/15 90% CONSTRUCT. DOC. SET7 06/30/15 TIER 1 PHASE 1 PERMIT SET8 07/17/15 100% CONSTRUCT. DOC. SET

Page 38: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

ARCHITECT

CONSULTANT

STAMP

MARK DATE DESCRIPTION

PROJECT NUMBER:DRAWN BY:CHECKED BY:

SHEET TITLE

100% CONSTRUCTIONDOCUMENT SET

(UMBA 13-L2)

www.arup.com

955 Massachusetts Avenue4th Floor

Cambridge, MA 02139T 617 864 2987 F 617 864 6178

Arup USA Inc

7/17

/201

5 1:

58:1

3 PM

E-007

ELECTRICALSCHEDULE PLAN

SHEET 6

UMass Lowell NorthQuad Infrastructure

Renewal

21332

Lowell, MA

University of Massachusetts Building AuthorityUniversity of Massachusetts Lowell

JAIT

NOTES:

TOTAL NEC AMPS: 17 ATOTAL CONNECTED AMPS: 16 A

*CONTINUOUS 100 VA 125.00% 125 VA TOTAL NEC LOAD: 6113 VA*MOTOR LOAD 3628 VA 105.51% 3828 VA TOTAL CONNECTED LOAD: 5.9 kVA*RECEPTACLE 2160 VA 100.00% 2160 VALOAD CLASSIFICATION CONNECTED... DEMAND FACTOR CALC. NEC LOAD PANEL TOTALS

TOTAL CONNECTED AMPS: 20 A 16 A 14 ATOTAL CONNECTED LOAD: 2300 VA 1928 VA 1660 VA

41 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 42

39 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 40

37 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 38

35 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 36

33 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 34

31 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 32

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28

25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26

23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24

21 MOTOR - HAIR DRYER 20 A 1 500 VA 0 VA 1 20 A SPARE 22

19 MOTOR - COOLER 20 A 1 500 VA 0 VA 1 20 A SPARE 20

17 MOTOR - HAIR DRYER 20 A 1 500 VA 0 VA 1 20 A SPARE 18

15 RECEPTACLE 20 A 1 540 VA 0 VA 1 20 A SPARE 16

13 RECEPTACLE 20 A 1 900 VA 0 VA 1 20 A SPARE 14

11 MOTOR - HAIR DRYER 20 A 1 800 VA 0 VA 1 20 A SPARE 12

9 RECEPTACLE 20 A 1 360 VA 0 VA 1 20 A SPARE 10

7 ROOF - RTU CONTROL POWER 20 A 1 800 VA 0 VA 1 20 A SPARE 8

5 RECEPTACLE 20 A 1 360 VA 0 VA 1 20 A SPARE 6

3 MOTOR - POD 2 L3 EF 2-4 20 A 1 528 VA 0 VA 1 20 A SPARE 4

1 CONTINUOUS - DDC PANEL 20 A 1 100 VA 0 VA 1 20 A SPARE 2

CKT CIRCUIT DESCRIPTION TRIP PO... A B C PO... TRIP CIRCUIT DESCRIPTION CKT

BUS RATING: 225 ARP-F-3 ENCLOSURE: Type 1 WIRES: 4 MCB RATING: 225 AMOUNTING: Surface PHASES: 3 MAINS TYPE: MCBPANEL NAME:FED FROM: DP-FK1 VOLTS: 120/208 Wye A.I.C. RATING: 10kA

NOTES:

*CONTINUOUS 200 VA 125.00% 250 VA TOTAL NEC AMPS: 52 A*MOTOR LOAD 13977 VA 123.20% 17220 VA TOTAL CONNECTED AMPS: 43 A*NON-CONTINUOUS 400 VA 100.00% 400 VA TOTAL NEC LOAD: 18703 VA*RECEPTACLE 360 VA 100.00% 360 VA TOTAL CONNECTED LOAD: 15.3 kVA*LIGHTING 379 VA 125.00% 474 VALOAD CLASSIFICATION CONNECTED... DEMAND FACTOR CALC. NEC LOAD PANEL TOTALS

TOTAL CONNECTED AMPS: 48 A 41 A 39 ATOTAL CONNECTED LOAD: 5718 VA 4859 VA 4739 VA

41 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 42

39 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 40

37 ROOF - ELEVATOR SHAFT DAMPER 20 A 1 800 VA 0 VA 1 20 A SPARE 38

35 NON-CONTINUOUS - FSDs 20 A 1 200 VA 0 VA 1 20 A SPARE 36

33 NON-CONTINUOUS - FSDs 20 A 1 200 VA 0 VA 1 20 A SPARE 34

31 -- -- -- 4323 VA 0 VA 1 20 A SPARE 32

29 -- -- -- 4323 VA 0 VA 1 20 A SPARE 30

27 MOTOR - ACCU-1 50 A 3 4323 VA 0 VA 1 20 A SPARE 28

25 LIGHTING (VIA INV4) 20 A 1 171 VA 0 VA 1 20 A SPARE 26

23 -- -- -- 52 VA 0 VA 1 20 A SPARE 24

21 MOTOR - AC 1-4 15 A 2 52 VA 0 VA 1 20 A SPARE 22

19 LIGHTING 20 A 1 12 VA 0 VA 1 20 A SPARE 20

17 LIGHTING 20 A 1 12 VA 0 VA 1 20 A SPARE 18

15 CONTINUOUS - FA BOOSTER 20 A 1 100 VA 0 VA 1 20 A SPARE 16

13 RECEPTACLE 20 A 1 180 VA 0 VA 1 20 A SPARE 14

11 CONTINUOUS - FA BOOSTER 20 A 1 100 VA 0 VA 1 20 A SPARE 12

9 LIGHTING (VIA INV5) 20 A 1 184 VA 0 VA 1 20 A SPARE 10

7 -- -- -- 52 VA 0 VA 1 20 A SPARE 8

5 MOTOR - AC 1-5 15 A 2 52 VA 0 VA 1 20 A SPARE 6

3 -- -- -- 0 VA 0 VA 1 20 A SPARE 4

1 RECEPTACLE - L6-30 20 A 2 180 VA 0 VA 1 20 A SPARE 2

CKT CIRCUIT DESCRIPTION TRIP PO... A B C PO... TRIP CIRCUIT DESCRIPTION CKT

BUS RATING: 100 AOP-SP-3 ENCLOSURE: Type 1 WIRES: 4 MCB RATING: 100 AMOUNTING: Surface PHASES: 3 MAINS TYPE: MCBPANEL NAME:FED FROM: OP-SP-1 VOLTS: 120/208 Wye A.I.C. RATING: 22kA

NOTES:

TOTAL NEC AMPS: 108 ATOTAL CONNECTED AMPS: 98 A

TOTAL NEC LOAD: 90148 VA*CONTINUOUS 6925 VA 125.00% 8656 VA TOTAL CONNECTED LOAD: 81.1 kVA*MOTOR LOAD 74217 VA 109.80% 81491 VALOAD CLASSIFICATION CONNECTED... DEMAND FACTOR CALC. NEC LOAD PANEL TOTALS

TOTAL CONNECTED AMPS: 99 A 108 A 89 ATOTAL CONNECTED LOAD: 27066 VA 29503 VA 24573 VA

41 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 42

39 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 40

37 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 38

35 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 36

33 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 34

31 MOTOR - POD 1 L4 FTR 2 & FTR 3 20 A 1 2742 VA 0 VA 1 20 A SPARE 32

29 MOTOR - POD 1 L4 FTR 2 & FTR 2 20 A 1 1994 VA 0 VA 1 20 A SPARE 30

27 MOTOR - POD 1 L4 FTR 1 & FTR 2 & FTR 3 20 A 1 3490 VA 0 VA 1 20 A SPARE 28

25 MOTOR - POD 1 L3 FTR 1 & FTR 2 & FTR 3 25 A 1 3490 VA 0 VA 1 20 A SPARE 26

23 -- -- -- 2464 VA 0 VA 1 20 A SPARE 24

21 -- -- -- 2464 VA 0 VA 1 20 A SPARE 22

19 MOTOR - CUH-1 20 A 3 2464 VA 0 VA 1 20 A SPARE 20

17 MOTOR - POD 1 L 2 FTR 1 & FTR 2 & FTR 3 25 A 1 3490 VA 0 VA 1 20 A SPARE 18

15 CONTINUOUS - POD 1 L4 DWH 1 30 A 1 6925 VA 0 VA 1 20 A SPARE 16

13 -- -- -- 9699 VA 0 VA 1 20 A SPARE 14

11 -- -- -- 9699 VA 0 VA 1 20 A SPARE 12

9 MOTOR - POD 1 ROOF RTU 1 60 A 3 9699 VA 0 VA 1 20 A SPARE 10

7 MOTOR - POD 1 L1.5 DWH 1 50 A 1 6925 VA 0 VA 1 20 A SPARE 8

5 MOTOR - POD 1 L2 DWH-1 50 A 1 6925 VA 0 VA 1 20 A SPARE 6

3 MOTOR - POD 1 L3 DWH-1 50 A 1 6925 VA 0 VA 1 20 A SPARE 4

1 MOTOR - POD 1 L1.5 FTR 1 & FTR 2 15 A 1 1745 VA 0 VA 1 20 A SPARE 2

CKT CIRCUIT DESCRIPTION TRIP PO... A B C PO... TRIP CIRCUIT DESCRIPTION CKT

BUS RATING: 100 AMP-SP-1 ENCLOSURE: Type 1 WIRES: 4 MCB RATING: 100 AMOUNTING: Surface PHASES: 3 MAINS TYPE: MCBPANEL NAME:FED FROM: VOLTS: 480/277 Wye A.I.C. RATING: 35kA

OP-SP-1NOTES:

*CONTINUOUS 200 VA 125.00% 250 VA*MOTOR LOAD 16685 VA 110.80% 18486 VA TOTAL NEC AMPS: 75 A*NON-CONTINUOUS 50 VA 100.00% 50 VA TOTAL CONNECTED AMPS: 69 A*RECEPTACLE 6840 VA 100.00% 6840 VA TOTAL NEC LOAD: 27010 VAReceptacle 180 VA 100.00% 180 VA TOTAL CONNECTED LOAD: 25 kVA*LIGHTING 963 VA 125.00% 1204 VALOAD CLASSIFICATION CONNECTED... DEMAND FACTOR CALC. NEC LOAD PANEL TOTALS

TOTAL CONNECTED AMPS: 63 A 77 A 69 ATOTAL CONNECTED LOAD: 7518 VA 9176 VA 8225 VA

59 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 60

57 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 58

55 RECEPTACLE 20 A 1 360 VA 0 VA 1 20 A SPARE 56

53 RECEPTACLE 20 A 1 360 VA 0 VA 1 20 A SPARE 54

51 RECEPTACLE 20 A 1 360 VA 0 VA 1 20 A SPARE 52

49 MOTOR - COOLER 20 A 1 500 VA 0 VA 1 20 A SPARE 50

47 -- -- -- 156 VA 0 VA 1 20 A SPARE 48

45 MOTOR - AC 5-4/5-5/5-6 15 A 2 156 VA 0 VA 1 20 A SPARE 46

43 NON-CONTINUOUS - ELEV DAMPER 20 A 1 50 VA 0 VA 1 20 A SPARE 44

41 RECEPTACLE 20 A 1 360 VA 0 VA 1 20 A SPARE 42

39 RECEPTACLE - L5-30 20 A 1 180 VA 0 VA 1 20 A SPARE 40

37 MOTOR - HAIR DRYER 20 A 1 800 VA 0 VA 1 20 A SPARE 38

35 MOTOR - HAIR DRYER 20 A 1 800 VA 0 VA 1 20 A SPARE 36

33 RECEPTACLE 20 A 1 900 VA 180 VA 1 20 A RECEPTACLE - L6-30 34

31 RECEPTACLE 20 A 1 360 VA 170 VA 1 20 A LIGHTING 32

29 RECEPTACLE 20 A 1 360 VA 305 VA 1 20 A LIGHTING 30

27 RECEPTACLE 20 A 1 720 VA 318 VA 1 20 A LIGHTING 28

25 RECEPTACLE 20 A 1 180 VA 156 VA -- -- -- 26

23 LIGHTING 20 A 1 170 VA 156 VA 2 15 A MOTOR - AC 5-1/5-2 24

21 RECEPTACLE 20 A 1 900 VA 2402 VA -- -- -- 22

19 MOTOR - COOLER 20 A 1 800 VA 2402 VA -- -- -- 20

17 MOTOR - HAIR DRYER 20 A 1 800 VA 2402 VA 3 30 A MOTOR - ACCU-5 18

15 MOTOR - HAIR DRYER 20 A 1 800 VA 180 VA 1 20 A RECEPTACLE 16

13 RECEPTACLE 20 A 1 360 VA 500 VA 1 20 A MOTOR - COOLER 14

11 MOTOR - HAIR DRYER 20 A 1 500 VA 528 VA 1 15 A MOTOR - EF 1-4 12

9 RECEPTACLE 20 A 1 720 VA 500 VA 1 20 A MOTOR - COOLER 10

7 CONTINUOUS - DDC PANEL 20 A 1 100 VA 100 VA 1 20 A CONTINUOUS - DDC PANEL 8

5 MOTOR - EF 1-3 15 A 1 528 VA 800 VA 1 20 A ROOF - POWER FOR RTU CONTROLS 6

3 RECEPTACLE 20 A 1 360 VA 500 VA 1 20 A MOTOR - HAIR DRYER 4

1 RECEPTACLE 20 A 1 180 VA 500 VA 1 20 A MOTOR - HAIR DRYER 2

CKT CIRCUIT DESCRIPTION TRIP PO... A B C PO... TRIP CIRCUIT DESCRIPTION CKT

BUS RATING: 100 ASP-P3 ENCLOSURE: Type 1 WIRES: 4 MCB RATING: 100 AMOUNTING: Surface PHASES: 3 MAINS TYPE: MCBPANEL NAME:FED FROM: SP-P1 VOLTS: 120/208 Wye A.I.C. RATING:

USS-S

1 06/10/14 FEASIBILITY STUDY SET2 08/29/14 SCHEMATIC DESIGN SET3 12/18/14 50% DESIGN DEVELOPMENT SET4 01/15/15 100% DESIGN DEVELOPMENT SET5 04/06/15 60% CONSTRUCTION PERMIT SET6 05/07/15 90% CONSTRUCT. DOC. SET7 06/30/15 TIER 1 PHASE 1 PERMIT SET8 07/17/15 100% CONSTRUCT. DOC. SET

Page 39: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

TYPE MANUFACTURER MODEL NUMBER DESCRIPTION WATTAGE VOLTAGE COMMENTS

R1 PHILIPS L5RAE1-L5R10835-L5RDW 5" LED DOWNLIGHT 13 277V

R2 PHILIPS HLS22GLR33L35ULAG LED RECESSED 2X2 31 277V

R3 PHILIPS PDK (4)523-000004-32 12" COLOR LED LINEAR COVE 6 277V LENGTH AS PER ARCHITECTS PLANS.

S1 PHILIPS OWL440L840-UNV-DIM LED 1X4 STRIPLIGHT 38 277V

S2 PHILIPS SLTLED434KDRBSSL PIT LIGHT 39 120/277V

W1 PHILIPS LP7 LED DOWNWARD WALL SCONCE 13 120V

EXIT PHILIPS CA6RCA1IC CHLORIDE EXIT 5 277V FACE QTY, ARROWS AND MOUNTING HARDWARE TO SUIT FIELD CONDITIONS

EX1 PHILIPS VCXL-26-HFL-EB-4 EXTERIOR CFL MAINTENANCE LIGHT 26 120V PROVIDE ONE SPARE LAMP PER FIXTURE

R4 LITHONIA OLVTWM VAPOR TIGHT LED JAR LIGHT 15 120V (OR APPROVED EQUAL) REFER TO SHEETS E-706 & E-712 FOR QUANTITIES AND LOCATIONS

ARCHITECT

CONSULTANT

STAMP

MARK DATE DESCRIPTION

PROJECT NUMBER:DRAWN BY:CHECKED BY:

SHEET TITLE

100% CONSTRUCTIONDOCUMENT SET

(UMBA 13-L2)

www.arup.com

955 Massachusetts Avenue4th Floor

Cambridge, MA 02139T 617 864 2987 F 617 864 6178

Arup USA Inc

7/17

/201

5 1:

58:1

6 PM

E-008

ELECTRICALSCHEDULE PLAN

SHEET 7

UMass Lowell NorthQuad Infrastructure

Renewal

21332

Lowell, MA

University of Massachusetts Building AuthorityUniversity of Massachusetts Lowell

JAIT

MOTOR EQUIPMENT SCHEDULE

EQUIPMENT MOTORBRANCHCIRCUIT

BRANCH WIRING (COPPERTHHN/THWN) STARTER/DISCONNECT TYPE

NOTESTAG NO.VOLT

S PH HP KVA FLA PANEL

CIRCUIT

NUMBER

SETS

CONDUCTOR SIZE

GROUND

SIZECONDUIT SIZE TYPE

NEMATYPE RATING

FURNISHED BY

AC 1-1 208 1 0.1 0.5 OP-SP-1 26,28 1 #12 #12 3/4" DISCONNECT 1 20 EC PROVIDE 3/4 INCH CONDUIT BETWEEN INDOOR UNIT AND OUTDOOR UNIT FOR CONTROLS. PROVIDE #12 PULL WIREAC 1-2 208 1 0.1 0.5 OP-SP-1 40,42 1 #12 #12 3/4" DISCONNECT 1 20 EC PROVIDE 3/4 INCH CONDUIT BETWEEN INDOOR UNIT AND OUTDOOR UNIT FOR CONTROLS. PROVIDE #12 PULL WIREAC 1-3 208 1 0.1 0.5 OP-SP-1 11,13 1 #12 #12 3/4" DISCONNECT 1 20 EC PROVIDE 3/4 INCH CONDUIT BETWEEN INDOOR UNIT AND OUTDOOR UNIT FOR CONTROLS. PROVIDE #12 PULL WIREAC 1-4 208 1 0.1 0.5 OP-SP-3 21,23 1 #12 #12 3/4" DISCONNECT 1 20 EC PROVIDE 3/4 INCH CONDUIT BETWEEN INDOOR UNIT AND OUTDOOR UNIT FOR CONTROLS. PROVIDE #12 PULL WIREAC 1-5 208 1 0.1 0.5 OP-SP-3 5,7 1 #12 #12 3/4" DISCONNECT 1 20 EC PROVIDE 3/4 INCH CONDUIT BETWEEN INDOOR UNIT AND OUTDOOR UNIT FOR CONTROLS. PROVIDE #12 PULL WIREAC 2-1 208 1 0.1 0.5 OEP-FK-1B 33,35 1 #12 #12 3/4" DISCONNECT 1 20 EC PROVIDE 3/4 INCH CONDUIT BETWEEN INDOOR UNIT AND OUTDOOR UNIT FOR CONTROLS. PROVIDE #12 PULL WIREAC 2-2 208 1 0.1 0.5 OEP-FK-2 5,7 1 #12 #12 3/4" DISCONNECT 1 20 EC PROVIDE 3/4 INCH CONDUIT BETWEEN INDOOR UNIT AND OUTDOOR UNIT FOR CONTROLS. PROVIDE #12 PULL WIREAC 2-3 208 1 0.1 0.5 OEP-FK-3 11,13 1 #12 #12 3/4" DISCONNECT 1 20 EC PROVIDE 3/4 INCH CONDUIT BETWEEN INDOOR UNIT AND OUTDOOR UNIT FOR CONTROLS. PROVIDE #12 PULL WIREAC 3-1 208 1 1.4 6.5 OEP-FK-1B 25,27 1 #12 #12 3/4" DISCONNECT 1 20 EC PROVIDE 3/4 INCH CONDUIT BETWEEN INDOOR UNIT AND OUTDOOR UNIT FOR CONTROLS. PROVIDE #12 PULL WIREAC 3-2 208 1 1.4 6.5 OEP-FK-1B 25,27 1 #12 #12 3/4" DISCONNECT 1 20 EC PROVIDE 3/4 INCH CONDUIT BETWEEN INDOOR UNIT AND OUTDOOR UNIT FOR CONTROLS. PROVIDE #12 PULL WIREAC 5-1 208 1 0.1 0.5 SP-P3 24,26 1 #12 #12 3/4" DISCONNECT 1 20 EC PROVIDE 3/4 INCH CONDUIT BETWEEN INDOOR UNIT AND OUTDOOR UNIT FOR CONTROLS. PROVIDE #12 PULL WIREAC 5-2 208 1 0.1 0.5 SP-P3 24,26 1 #12 #12 3/4" DISCONNECT 1 20 EC PROVIDE 3/4 INCH CONDUIT BETWEEN INDOOR UNIT AND OUTDOOR UNIT FOR CONTROLS. PROVIDE #12 PULL WIREAC 5-3 208 1 0.1 0.5 SP-P3 24,26 1 #12 #12 3/4" DISCONNECT 1 20 EC PROVIDE 3/4 INCH CONDUIT BETWEEN INDOOR UNIT AND OUTDOOR UNIT FOR CONTROLS. PROVIDE #12 PULL WIREAC 5-4 208 1 0.1 0.5 SP-P3 45,47 1 #12 #12 3/4" DISCONNECT 1 20 EC PROVIDE 3/4 INCH CONDUIT BETWEEN INDOOR UNIT AND OUTDOOR UNIT FOR CONTROLS. PROVIDE #12 PULL WIREAC 5-5 208 1 0.1 0.5 SP-P3 45,47 1 #12 #12 3/4" DISCONNECT 1 20 EC PROVIDE 3/4 INCH CONDUIT BETWEEN INDOOR UNIT AND OUTDOOR UNIT FOR CONTROLS. PROVIDE #12 PULL WIREAC 5-6 208 1 0.1 0.5 SP-P3 45,47 1 #12 #12 3/4" DISCONNECT 1 20 EC PROVIDE 3/4 INCH CONDUIT BETWEEN INDOOR UNIT AND OUTDOOR UNIT FOR CONTROLS. PROVIDE #12 PULL WIRE

ACCU 1 208 3 13.0 36.0 OP-SP-3 27,29,31 1 #6 #10 1 1/4" DISCONNECT 1 50 ECACCU 2 208 3 7.2 20.0 OEP-FK-3 15,17,19 1 #10 #10 1" DISCONNECT 1 30 ECACCU 3-1 208 3 13.0 36.0 OEP-FK-3 5,7,9 1 #6 #10 1 1/4" DISCONNECT 1 50 EC ACCU 3 RQUIRES TWO CONNECTION POINTS - ACCU 3-1 AND ACCU 3-2ACCU 3-2 208 3 7.2 20.0 OEP-FK-3 25,27,29 1 #10 #10 1" DISCONNECT 1 30 EC ACCU 3 RQUIRES TWO CONNECTION POINTS - ACCU 3-1 AND ACCU 3-2ACCU 5 208 3 7.2 20.0 SP-P3 18,20,22 1 #10 #10 1" DISCONNECT 1 30 ECCUH 1 480 1 7.4 15.4 MP-SP-1 19,21,23 1 #12 #12 3/4" DISCONNECT 1 20 ECCUH 2 480 1 7.4 15.4 MP-FK-1 7,9,11 1 #12 #12 3/4" DISCONNECT 1 20 ECDWH 1 277 1 6.9 25.0 MP-SP-1 7 1 #10 #10 3/4" DISCONNECT 1 50 EC POD 1 LEVEL 1.5DWH 1 277 1 6.9 25.0 MP-FK-1 5 1 #10 #10 3/4" DISCONNECT 1 50 EC POD 2 LEVEL 1DWH 1 277 1 6.9 25.0 MP-SP-1 3 1 #10 #10 3/4" DISCONNECT 1 50 EC POD 1 LEVEL 3DWH 1 277 1 6.9 25.0 MP-FK-3 4 1 #10 #10 3/4" DISCONNECT 1 50 EC POD 2 LEVEL 3DWH 1 277 1 6.9 25.0 MP-SP-1 15 1 #10 #10 3/4" DISCONNECT 1 50 EC POD 1 LEVEL 4DWH 1 277 1 6.9 25.0 MP-SP-1 5 1 #10 #10 3/4" DISCONNECT 1 50 EC POD 1 LEVEL 2EF 1-1 120 1 0.5 4.4 SP-P1 6 1 #12 #12 3/4" DISCONNECT/STARTER 1 20 MC STARTER FURNISHED BY MC (ECM MOTOR).EF 1-2 120 1 0.5 4.4 SP-P1 9 1 #12 #12 3/4" DISCONNECT/STARTER 1 20 MC STARTER FURNISHED BY MC (ECM MOTOR).EF 1-3 120 1 0.5 4.4 SP-P3 5 1 #12 #12 3/4" DISCONNECT/STARTER 1 20 MC STARTER FURNISHED BY MC (ECM MOTOR).EF 1-4 120 1 0.5 4.4 SP-P3 12 1 #12 #12 3/4" DISCONNECT/STARTER 1 20 MC STARTER FURNISHED BY MC (ECM MOTOR).EF 2-1 120 1 0.5 4.4 OEP-FK-1B 19 1 #12 #12 3/4" DISCONNECT/STARTER 1 20 MC STARTER FURNISHED BY MC (ECM MOTOR).EF 2-2 120 1 0.5 4.4 OEP-FK-1B 17 1 #12 #12 3/4" DISCONNECT/STARTER 1 20 MC STARTER FURNISHED BY MC (ECM MOTOR).EF 2-3 120 1 0.5 4.4 OEP-FK-2 3 1 #12 #12 3/4" DISCONNECT/STARTER 1 20 MC STARTER FURNISHED BY MC (ECM MOTOR).EF 2-4 120 1 0.5 4.4 RP-F-3 3 1 #12 #12 3/4" DISCONNECT/STARTER 1 20 MC STARTER FURNISHED BY MC (ECM MOTOR).

FTR 1 277 1 0.7 2.7 MP-SP-1 1 1 #12 #12 3/4" MOTOR RATED SWITCH 1 20 ECFTR 1 277 1 0.7 2.7 MP-SP-1 17 1 #12 #12 3/4" MOTOR RATED SWITCH 1 20 ECFTR 1 277 1 0.7 2.7 MP-SP-1 25 1 #12 #12 3/4" MOTOR RATED SWITCH 1 20 ECFTR 1 277 1 0.7 2.7 MP-SP-1 27 1 #12 #12 3/4" MOTOR RATED SWITCH 1 20 ECFTR 2 277 1 1.0 3.6 MP-SP-1 1 1 #12 #12 3/4" MOTOR RATED SWITCH 1 20 ECFTR 2 277 1 1.0 3.6 MP-SP-1 17 1 #12 #12 3/4" MOTOR RATED SWITCH 1 20 ECFTR 2 277 1 1.0 3.6 MP-SP-1 25 1 #12 #12 3/4" MOTOR RATED SWITCH 1 20 ECFTR 2 277 1 1.0 3.6 MP-SP-1 27 1 #12 #12 3/4" MOTOR RATED SWITCH 1 20 ECFTR 2 277 1 1.0 3.6 MP-SP-1 29 1 #12 #12 3/4" MOTOR RATED SWITCH 1 20 ECFTR 2 277 1 1.0 3.6 MP-SP-1 31 1 #12 #12 3/4" MOTOR RATED SWITCH 1 20 ECFTR 2 277 1 1.0 3.6 MP-SP-1 29 1 #12 #12 3/4" MOTOR RATED SWITCH 1 20 ECFTR 3 277 1 1.7 6.3 MP-SP-1 17 1 #12 #12 3/4" MOTOR RATED SWITCH 1 20 ECFTR 3 277 1 1.7 6.3 MP-SP-1 25 1 #12 #12 3/4" MOTOR RATED SWITCH 1 20 ECFTR 3 277 1 1.7 6.3 MP-SP-1 27 1 #12 #12 3/4" MOTOR RATED SWITCH 1 20 ECFTR 3 277 1 1.7 6.3 MP-SP-1 31 1 #12 #12 3/4" MOTOR RATED SWITCH 1 20 ECRTU 1 480 3 29.1 35.0 MP-SP-1 9,11,13 1 #6 #10 1 1/4" DISCONNECT/VFD 4X 60 MC SINGLE CONNECTION PTRTU 2 480 3 16.6 20.0 MP-FK-3 1,3,5 1 #10 #10 1" DISCONNECT/VFD 4X 25 MC SINGLE CONNECTION PTSF 1 120 1 0.5 4.4 OEP-FK-2 1 1 #12 #12 3/4" DISCONNECT/STARTER 1 20 MC STARTER FURNISHED BY MC (ECM MOTOR).SF 2 120 1 0.5 4.4 OEP-FK-3 23 1 #12 #12 3/4" DISCONNECT/STARTER 1 20 MC STARTER FURNISHED BY MC (ECM MOTOR).

1. ALL LIGHTING SPECIFIED ABOVE IS ON AN "OR APPROVED EQUAL BY LITHONIA, COOPER OR COLUMBIA LIGHTING.2. PROVIDE ALL MOUNTING HARDWARE AND COMPONENTS TO MATCH INSTALLATION REQUIREMENTS.3. POD 1 LIGHTS ARE 120V, POD 2 LIGHTS ARE 277V.4. POD 1 EMERGENCY LIGHTING VIA BODINE ELI-S-250 MICRO INVERTERS, OR APPROVED EQUAL. POD 2 EMERGENCY LIGHTING VIAEMERGENCY GENERATOR.

1. REFER TO ELECTRICAL PLANS FOR APPROXIMATE EQUIPMENT LOCATION. REFER TO HVAC DRAWINGS FOR SPECIFIC LOCATIONS OF AC, ACCU, CUH, EF, FTR AND RTUS. REFER TO PLUMBING DRAWINGS FOR EXACT LOCATIONS OF DWHS.2. U.O.N. FINAL CONNECTIONS TO EQUIPMENT SHALL BE BY THE EC.

NTS1 LIGHTING FIXTURE SCHEDULE

1 06/10/14 FEASIBILITY STUDY SET2 08/29/14 SCHEMATIC DESIGN SET3 12/18/14 50% DESIGN DEVELOPMENT SET4 01/15/15 100% DESIGN DEVELOPMENT SET5 04/06/15 60% CONSTRUCTION PERMIT SET6 05/07/15 90% CONSTRUCT. DOC. SET7 06/30/15 TIER 1 PHASE 1 PERMIT SET8 07/17/15 100% CONSTRUCT. DOC. SET

Page 40: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

CONDUIT AND CONDUCTOR SIZES ARE BASED ON EMT CONDUIT WITH COPPER XHHW. 600V RATED CONDUCTORS. CONTRACTOR IS RESPONSIBLE FOR CONFIRMING CONDUIT AND CONDUCTOR SIZES IF OTHER MATERIALS ARE USED.

TAGP30AP30BP30CP30DP30EP30FP40AP40BP40CP40DP40EP40FP55AP55BP55CP55DP55EP55FP70AP70BP70CP70DP70EP70F

CONDUIT & WIRE3#10 - 3/4"C3#10 + #10G - 3/4"C4#10 - 3/4"C4#10 + #10G - 3/4"C3#10 + #6N - 3/4"C3#10 + #6N+10G - 3/4"C3#8 - 1"C3#8 + #10G - 1"C4#8 - 1"C4#8 + #10G - 1"C3#8 + #3N - 1"C3#8 + #3N+#10G - 1"C3#6 - 1-1/4"C3#6 + #8G - 1-1/4"C4#6 - 1-1/4"C4#6 + #8G - 1-1/4"C3#6 + #1/0N - 1-1/4"C3#6 + #1/0N+#8G - 1-1/4"C3#4 - 1-1/4"C3#4 + #8G - 1-1/4"C4#4 - 1-1/4"C4#4 + #8G - 1-1/4"C3#4 + #2/0N - 1-1/4"C3#4 + #2/0N+#8G - 1-1/2"C

TAGP85AP85BP85CP85DP85EP85FP95AP95BP95CP95DP95EP95F

P110AP110BP110CP110DP110EP110FP150AP150BP150CP150DP150EP150F

CONDUIT & WIRE3#3 - 1-1/4"C3#3 + #8G - 1-1/2"C4#3 - 1-1/2"C4#3 + #8G - 1-1/2"C3#3 + #3/0N - 1-1/2"C3#3 + #3/0N+#8G - 1-1/2"C3#2 - 1-1/2"C3#2 + #6G - 1-1/4"C4#2 - 1-1/2"C4#2 + #6G - 1-1/2"C3#2 + 2#2N - 1-1/2"C3#2 + 2#2N+#6G - 1-1/2"C3#1 - 1-1/2"C3#1 + #6G - 1-1/2"C4#1 - 1-1/2"C4#1 + #6G - 2"C3#1 + 2#1N - 2"C3#1 + 2#1N+#6G - 2"C3#1/0 - 2"C3#1/0 + #6G - 2"C4#1/0 - 2"C4#1/0 + #6G - 2"C3#1/0 + 2#1/0N - 2"C3#1/0 + 2#1/0N+#6G - 2"C

EGC FOR MULTIPLE SETSX2

1#4G

1#4G

1#4G

X3

1#2G

1#2G

1#2G

X4

1#1G

1#1G

1#1G

X5

1#1/0G

1#1/0G

1#1/0G

FEEDER SCHEDULE

TAGP175AP175BP175CP175DP175EP175FP200AP200BP200CP200DP200EP200FP230AP230BP230CP230DP230EP230FP255AP255BP255CP255DP255EP255F

CONDUIT & WIRE3#2/0 - 2"C3#2/0 + #4G - 2"C4#2/0 - 2"C4#2/0 + #4G - 2"C3#2/0 + 2#2/0N - 2"C3#2/0 + 2#2/0N+#4G- 2-1/2"C3#3/0 - 2"C3#3/0 + #2G - 2"C4#3/0 - 2"C4#3/0 + #2G - 2-1/2"C3#3/0 + 2#3/0N - 2-1/2"C3#3/0 + 2#3/0N+#2G- 2-1/2"C3#4/0 - 2-1/2"C3#4/0 + #2G - 2-1/2"C4#4/0 - 2-1/2"C4#4/0 + #2G - 2-1/2"C3#4/0 + 2#4/0N - 2-1/2"C3#4/0 + 2#4/0N+#2G - 2-1/2"C(3)250kcmil - 2-1/2"C(3)250kcmil + #2G - 2-1/2"C(4)250kcmil - 3"C(4)250kcmil + #2G - 3-1/2"C(3)250kcmil + (2)250kcmil N - 3-1/2"C(3)250kcmil + (2)250kcmil N+#2G - 3-1/2"C

EGC FOR MULTIPLE SETSX2

1#3G

1#3G

1#3G

1#3G

1#3G

1#3G

1#2G

1#2G

1#2G

1#1G

1#1G

1#1G

X3

1#1G

1#1G

1#1G

1#1G

1#1G

1#1G

1#1/0G

1#1/0G

1#1/0G

1#1/0G

1#1/0G

1#1/0G

X4

1#1/0G

1#1/0G

1#1/0G

1#1/0G

1#1/0G

1#1/0G

1#2/0G

1#2/0G

1#2/0G

1#3/0G

1#3/0G

1#3/0G

X5

1#2/0G

1#2/0G

1#2/0G

1#2/0G

1#2/0G

1#2/0G

1#3/0G

1#3/0G

1#3/0G

1#4/0G

1#4/0G

1#4/0G

TAGP285AP285BP285CP285DP285EP285FP310AP310BP310CP310DP310EP310FP335AP335BP335CP335DP335EP335FP380AP380BP380CP380DP380EP380F

CONDUIT & WIRE(3)300kcmil - 3"C(3)300kcmil + #2G - 3"C(4)300kcmil - 3"C(4)300kcmil + #2G - 3-1/2"C(3)300kcmil + (2)300kcmil N- 3-1/2"C(3)300kcmil + (2)300kcmil N+#2G- 4"C(3)350kcmil - 3"C(3)350kcmil + #2G - 3"C(4)350kcmil - 3"C(4)350kcmil + #2G - 3-1/2"C(3)350kcmil + (2)350kcmil N - 3-1/2"C(3)350kcmil + (2)350kcmil N+#2G - 3-1/2"C(3)400kcmil - 3-1/2"C(3)400kcmil + #1/0G - 3-1/2"C(4)400kcmil - 3-1/2"C(4)400kcmil + #1/0G - 4"C(3)400kcmil + (2)400kcmil N- 4"C(3)400kcmil + (2)400kcmil N+#1/0G- 4"C(3)500kcmil - 3-1/2"C(3)500kcmil + #1/0G - 3-1/2"C(4)500kcmil - 3-1/2"C(4)500kcmil + #1/0G - 4"C(3)500kcmil + (2)500kcmil N- 4"C(3)500kcmil + (2)500kcmil N+#1/0G- 4"C

EGC FOR MULTIPLE SETSX2

1#1G

1#1G

1#1G

1#1/0G

1#1/0G

1#1/0G

1#1/0G

1#1/0G

1#1/0G

1#1/0G

1#1/0G

1#1/0G

X3

1#2/0G

1#2/0G

1#2/0G

1#2/0G

1#2/0G

1#2/0G

1#3/0G

1#3/0G

1#3/0G

1#3/0G

1#3/0G

1#3/0G

X4

1#3/0G

1#3/0G

1#3/0G

1#4/0G

1#4/0G

1#4/0G

1#4/0G

1#4/0G

1#4/0G

1#4/0G

1#4/0G

1#4/0G

X5

1#4/0G

1#4/0G

1#4/0G

1#4/0G

1#4/0G

1#4/0G

1#250G

1#250G

1#250G

1#250G

1#250G

1#250G

X6

1#250G

1#250G

1#250G

1#250G

1#250G

1#250G

1#350G

1#350G

1#350G

1#350G

1#350G

1#350G

X8

1#250G

1#250G

1#250G

1#350G

1#350G

1#350G

1#400G

1#400G

1#400G

1#500G

1#500G

1#500G

X10

1#250G

1#250G

1#250G

1#350G

1#350G

1#350G

1#400G

1#400G

1#400G

1#500G

1#500G

1#500G

X12

1#250G

1#250G

1#250G

1#350G

1#350G

1#350G

1#400G

1#400G

1#400G

1#500G

1#500G

1#500G

1

1 1

CONT

GROUNDING DIAGRAM

LV GROUND CONNECTION

#3 IN 1"C

CONT

200% SPARE WAYS

LEP-FK-1

LEP-FK-2

LEP-FK-3

1

2

3

2

4

4

5

31

6

5

7

7 71 7 7118

8

9

9

10

10 10

11

11

12

12

12

12

NGNG

TO M

AIN

INCO

MING

CONN

ECTIO

N TO

SERV

ICE

WAT

ER P

IPE

GROU

ND B

AR

#250 IN 1"C

MDF R

M

#3/0 IN 1"C

GEN-

1 (SE

E FE

EDER

TAG

)

CONN

ECTIO

N TO

GROU

ND B

ARS

(TYP

OF

3)ID

F RM

G

CONN

ECTIO

N TO

GROU

ND R

ODS

#2 IN 1"C

PS-F

KGR

OUND

BAR

#3/0 IN 1"C

(SEE

E4.0

2)

TO B

UIDI

NG S

TEEL

(SEE

E4.0

2)

DUCT

BANK

GRO

UND

LAY

IN 20

' OF G

ROUN

DW

IRE

AND

TIE

TO R

EBAR

250AF225AT

250AF225AT

250AF225AT

250AF225AT

250AF225AT

250AF225AT

1200AF1000AT

250AF225AT

600AF600AT

250AF225AT

600AF450AT

125AF100AT

250AF225AT

250AF225AT

1200AF250AT

1200AF250AT

250AF225AT

400AF400AT

125AF100AT

125AF100AT

600AF600AT

1200AF400AT

LP-FK-1

LP-FK-2

LP-FK-3 MP-FK-3

KITSONDP-K600A

RP-K-1

RP-K-2

RP-K-3

RP-F-1

RP-F-2

RP-F-3

EP-FK-1ASPDMLO

OEP-FK-1B

EP-FK-2SPD

EP-FK-3SPD

OEP-FK-2

OEP-FK-3

MP-FK-1

OEP-FK-1A

EP-FK-1BSPD

3P 3P 3P 3P 3P 3P3P 3P

LEVEL 1

LEVEL 2

LEVEL 3

TX1480/208-120V

300kVA115c Rise

3P 3P 3P3P3P

USS-FK

ROOF

ATS1480/277V

260ALIFE SAFETY

ATS3480/277V

260AOPTIONAL

3P 3P3P3P

EDP-FK

480/277V, 400A, 3-PH. 4W, 35kAICSEPARATE SECTIONS PER BREAKER.

3P 3P 3P

TX2480/208-120V75kVA115c Rise

GEN1480/277V

200kW/250kVASTANDBY/EM

4160V/480-277V, 1500KVA,2000A, 3-PH. 4W, 35kAICUNIT SUB STATION - POD 2 MAIN ELECTRICAL ROOM

208/120V, 1000A, 3-PH. 4W, 35kAICPOD 2 MAIN ELECTRICAL ROOM

PS-FK

SPARE SPARE

NEW 15kV TO MANHOLE

"UG" ADJACENT TO FEEDER TAG INDICATES CONDUIT RUN UNDERGROUND TO ENTER EQUIPMENT FROM BELOW.

DP-FK1

POD 2 EMERGENCY ELECTRICAL ROOM

SEP DERIVED

P110D

SPD

P110D

P110D (2)P310D

(2)P335D

P230D

P255D P230D

P230D

P110B

P230D

P110D

P230D

P150D

P255D

3P

EXISTING

(2)SPARE 225A(2)SPARE 100A

(2)P230B

(3)P335D

(2)P200DFR

FR

FUTURE SPACE ONLY:EQUIPMENT SHOWN ON PLANS FORSPACE PLANNING

FR

FR

OFCI

KEYED NOTES:

GENERAL NOTES1. REFER TO DRAWING E0.00 FOR ELECTRICAL LEGEND, ABBREVIATIONS

AND NOTES.2. THIS DRAWING SHALL BE READ IN CONJUNCTION WITH THE MEP/

ARCHITECTURAL DRAWINGS AND SPECIFICATIONS3. PROVIDE POWER MONITORING ELECTRONIC TRIP BREAKER FOR

USS-FK MAIN BREAKER.4. UNLESS OTHERWISE NOTED PROVIDE 25% SPARE CB'S AND 25% SPACE

IN ALL PANELBOARDS. PROVIDE SPARE CB'S AND SPACE ONLY INSWITCHBOARDS AS SHOWN ON THE RISER DIAGRAMS.

5. AS A MINIMUM, DISCONNECT SWITCHES SHALL BE RATED AT FRAMESIZE OF THE DOWN STREAM PROTECTION DEVICE.

6. MATERIAL AND EQUIPMENT SHALL BE UL, NEMA, ANSI, IEEE, ADA ANDCBM APPROVED FOR INTENDED SERVICE. MATERIAL AND INSTALLATIONSHALL MEET REQUIREMENTS OF MASS STATE ELECTRIC CODE.

7. ALL WIRING SHALL BE TYPE THWN RATED 75°C MIN.,600 VOLT, WET ORDRY LOCATIONS. .

8. ALL MAIN CIRCUIT BREAKERS SHALL HAVE ADJUSTABLE THERMAL ANDMAGNETIC TRIPS.

9. BREAKERS SHALL BE 3P UNLESS INDICATED OTHERWISE.10. CONNECTIONS SHOWN DO NOT IDENTIFY ENTRY/EXIT OR LUG

LOCATIONS. CONNECTIONS SHOWN ARE DIAGRAMMATIC SHOWINGSYSTEM TOPOLOGY ONLY.

11. CONTRACTOR TO ADJUST TRANSFORMER TAP SETTINGS AS REQUIRED.12. ALL TRANSFER SWITCHES SHALL BE 4 POLE. GENERATOR TO BE

SEPARATELY DERIVED SOURCE.13. ALL LIFE SAFETY PANELBOARDS TO BE PROVIDED WITH INTEGRAL 150kA

SPD'S.14. GENERATOR TO BE OWNER FURNISHED, CONTRACTOR INSTALLED.15. LIFE SAFETY SYSTEM TO COORDINATE DOWN TO 0.01 SECONDS.

CONTRACTOR TO PROVIDE COORDINATED CIRCUIT BREAKERS, WITHSETTINGS AS PER CONTRACTORS SHORT COORDINATION STUDYRECOMMENDATIONS.

ELECTRONIC ADJUSTABLE LSI CIRCUIT BREAKER.

SWITCHBOARD GRADE BOARD WITH PHYSICALSEPARATION BETWEEN BREAKERS.

BASIS OF DESIGN BREAKER: SQUARE DMASTERPACT NW LF 5.0, LSIG FUNCTION. LIFESAFETY SYSTEM TO COORDINATE AS PER NEC 700.28

SYSTEM TO SELECTIVELY COORDINATE TO 0.01S.GENERATOR CIRCUIT BREAKER TO COORDINATEWITH THE REST OF THE EMERGENCY POWERSYSTEM. ELECTRICAL CONTRACTOR ANDGENERATOR MANUFACTURER TO COORDINATECORRECT SELECTION AND SETTING OF UNITMOUNTED CIRCUIT BREAKER BASED ONCOORDINATION WITH THE REST OF THEDISTRIBUTION SYSTEM. INCLUDE GENERATORCIRCUIT BREAKER IN "CONTRACTORSCOORDINATION STUDY" TO ENSURE CORRECTBREAKER SETTING ARE PROVIDED. ADJUSTSETTINGS AS PER CONTRACTORS SHORT CIRCUITCOORDINATION STUDY.

CIRCUIT BREAKER TO HAVE POWER MONITORINGFUNCTION WITH CURRENT PER PHASE DISPLAYEDON BREAKER LCD SCREEN.

AS PER SQUARE D "MINI BREAK" OR APPROVEDEQUAL. REFER TO SPECIFICATION SECTION 261300.

BASIS OF DESIGN BREAKER: SQUARE D POWERPACTPG 5.0. LSI FUNCTION. LIFE SAFETY SYSTEM TOCOORDINATE TO 0.01S.

BASIS OF DESIGN: SUBFEED BREAKERS AS PERSQUARE D POWERPACT LD LSI 3.3S, 125A. LIFESAFETY SYSTEM TO COORDINATE TO 0.01S.

PROVIDE PANEL WITH MAIN DISCONNECT SWITCH.

BREAKER SIZED PER MANUFACTURERSREQUIREMENTS.

CLOSE COUPLED CONNECTION.

PROVIDE SLEEVES IN BETWEEN FLOORS TOACCOMMODATE 3" CONDUITS.

TX3480/208-120V15kVA115c Rise

P55D

P30BFR

FR

P200A

"MV" ADJACENT TO FEEDER TAG INDICATES 15kV RATED MEDIUM VOLTAGE CABLE.

MV

250kA SPD 150kA

2200ATGFP

2400AF

200A, 4160V

3PSPACE ONLY

1200AF250AF

P255DFR

3P

1200AF250AF

SPACE ONLY

FURNISHED BY OWNER.INSTALLED BY EC.

#2/0 FEEDERSNEW 15kV TO MANHOLE#2/0 FEEDERS

225A

P200AMVUG

P175D

200A

1500kVA

"FR" ADJACENT TO FEEDER TAG INDICATES 2 HOUR FIRE RATED FEEDER TYP RHH AND UL LISTED AS FHIT. REFER TO RHH CONDUIT FILL TABLE IN NEC AND UPSIZE AS REQUIRED.

480/277V260A

ATS2

REFER TODRAWING E-402FOR LOCATION

ARCHITECT

CONSULTANT

STAMP

MARK DATE DESCRIPTION

PROJECT NUMBER:DRAWN BY:CHECKED BY:

SHEET TITLE

100% CONSTRUCTIONDOCUMENT SET

(UMBA 13-L2)

www.arup.com

955 Massachusetts Avenue4th Floor

Cambridge, MA 02139T 617 864 2987 F 617 864 6178

Arup USA Inc

7/17

/201

5 1:

58:3

4 PM

E-301

ELECTRICAL RISERONE LINE DIAGRAM B

UMass Lowell NorthQuad Infrastructure

Renewal

21332

Lowell, MA

University of Massachusetts Building AuthorityUniversity of Massachusetts Lowell

JAIT

1 06/10/14 FEASIBILITY STUDY SET2 08/29/14 SCHEMATIC DESIGN SET3 12/18/14 50% DESIGN DEVELOPMENT SET4 01/15/15 100% DESIGN DEVELOPMENT SET5 04/06/15 60% CONSTRUCTION PERMIT SET6 05/07/15 90% CONSTRUCT. DOC. SET7 06/30/15 TIER 1 PHASE 1 PERMIT SET8 07/17/15 100% CONSTRUCT. DOC. SET

Page 41: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

DN

JCPLAN

T

21sf

RS LAB

CIVIL

659sf

OFF

CIVIL

196sf

CONF

CIVIL

269sf

OFF

CIVIL

388sf

CORR

PLAN

T

500sf

OF SV

CIVIL

46sf

OF SV

CIVIL

66sf

OFF

CIVIL

169sf

OFF

CIVIL

152sf

OFF

CIVIL

202sf

CL LAB

CIVIL

1004sf

CORR

PLAN

T

450sf

MERCH

BKSTR

5878sf

STAIR

PLAN

T

259sf

U/M

PLAN

T

61sf

DOCK

PLAN

T

818sf

ELEV

PLAN

T

36sf

MR SV

BKSTR

741sf

CORR

PLAN

T

242sf

CORR

PLAN

T

73sf

CORR

PLAN

T

62sf

MR SV

BKSTR

414sf

MR SV

BKSTR

538sf

C SERV

PURCH

1005sf

106

104

108A

108B

108

100C4

107D

107

107C

107B

107A

105

100C3

102

100S1

100A

100

100E1

101

100C1

100C2

100C5

102B

103

102A

STAIRPLANT

212.68sf

RS LABMECH

316.07sf

CORRPLANT

305.17sf

RS LABMECH

742.68sf

CORRPLANT

761.34sf

CL LABMECH

552.35sf

CL LABMECH

1552.32sf

RS LABMECH

644.92sf

RS LABMECH

101.25sf

RS LABMECH

824.76sf

RLB SVMECH

50.76sf

RLB SVMECH

154.69sf

CORRPLANT

254.97sf

STAIRPLANT

190.76sf

U/MPLANT

465.73sf

RS LABMECH

531.66sf

RS LABMECH

550.8sf

RS LABMECH

865.63sf

U/MPLANT

156.13sf

MENPLANT

335.88sf

RS LABMECH

886.77sfRS LABMECH

459.2sf

OFFMECH

414.78sf

ELEVPLANT

107.41sf

CORRPLANT

613.71sf

CORRPLANT

822.08sfU/MPLANT

2.36sf

CORRPLANT

243.05sf

100S1

101A

100C2

101

100C3

102A 102 104

104A

106

106A

106B

100C5 100S2112

103 105 107

111A

111B

111113 115

100E1

100C4 100C6

105A

100C1

CL LAB

DN ENGR

1646sf

CLASS

REG

538sf

CL LAB

CIVIL

216sf

RS LAB

MECH

261sf

OFF

CIVIL

305sf

CL LAB

CIVIL

723sf

CMP/TEL

IT

88sf

U/M

PLANT

437sf

CLB SV

CIVIL

70sf

CLB SV

CIVIL

266sf

FD SV

DINING

101sf

U/M

PLANT

53sf

U/M

PLANT

53sf

U/M

PLANT

249sf

FD SV

DINING

52sf

U/M

PLANT

34sf

UNISEX

PLANT

57sf

FD SV

DINING

214sf

FD SV

DINING

39sf

FD SV

DINING

249sf

FD SV

DINING

1960sf

JCPLANT

31sf

U/M

PLANT

40sf

STAIR

PLANT

263sf

STAIR

PLANT

273sf

MEN

PLANT

56sf

CORR

PLANT

817sf

CORR

PLANT

305sf

U/M

PLANT

86sf

CORR

PLANT

276sf

CORR

PLANT

407sf

RLB SV

CIVIL

192sf

CL LAB

CIVIL

1027sf

FOOD

DINING

3293sf

WOMEN

PLANT

223sf

122

121

120

130A

129

130

132A

132C

125

126

143

141A

140D

140C

140A

140B

152A

152

146

148

150

133A

145A

100S1

100S2

132D

100C1

100C2

132B

100C4

100C3

123

127

145

133

STAIRPLANT

227sf

RLB SVGSE

339sf

CORRPLANT

96sf

OF SVCIVIL

219sf

OFFCIVIL

133sf

U/MPLANT

292sf

OFFP&T

75sf

OFFDINING

127sf

FOODDINING

1958sf

RS LABCIVIL

181sf

JCPLANT

35sf

MENPLANT

112sf

CORRPLANT

117sf

OF SVCIVIL

115sfCL LABCIVIL

330sf

OFFCIVIL

178sf

OFFCIVIL

241sfRS LABCIVIL

481sf

CORRPLANT

457sf

U/MPLANT

235sf

OFFGSE

145sf

OFFGSE

109sf

OFFGSE

61sf

OFFGSE

168sf

OFFCIVIL

287sf

OFFCIVIL

253sf

OF SVCIVIL

223sf

OFFCIVIL

251sf

OFFCIVIL

214sf

CMP/TELIT

43sf

RS LABCIVIL

259sf

OFFCIVIL

279sf

OFFCIVIL

348sf

OFFCIVIL

273sf

CORRPLANT

469sf

RS LABDN ENGR

622sf

OF SVCIVIL

125sf

ELEVPLANT

37sf

U/MPLANT

15sf

100S1

106G

100C1

103A

105D

101

100B

100A

100

105E

107C 107B

100C4

107A103

105A

105B

105C

100C2

106E

106D

106C106B

106A

107 109

109A

111 113

115

114112110108

100C3

106

105

100E1

106F

UP DN

U/M

PLAN

T

163sf

U/M

PLAN

T

426sf

CL LAB

CHEM E

568sfOFF

CHEM E

232sf

OFF

CHEM E

141sf

U/M

PLAN

T

243sf

101A

101

103102

104

101B

CORR.

DINING & STD WWC

DINING & STD MWC

CORR.

STD WWCSTD MWC

NEW EMER. ELEC.

NEW PRIM. ELEC.

ELEC IDF/ITELEV LOBBY

2

A

B

4

D

E

51 1.5

1' 2' 3'

A'

B'

C'

3

C

A.5

C.5

0.5

PS-FK

DP-S

USS-SATS-S

DP-P

1 2

1 2

21

EXISTING SOUTHWICK ELECTRICAL RM

EX

EXEXEX

EXISTING PERRY ELECTRICAL RMS

EX

EXISTING TO REMAIN PERRYPRIMARY LOAD BREAK SWITCH

DP-K

EX

USS-FK

EDP-FK

3 1

GEN-14

NEW GENERATOR FEEDERS. SEEE301 FOR FEEDER INFORMATION.SEE CIVIL DRAWINGS FOR MORE

INFORMATION ON ROUTE.

E

5

EXISTING DUCTBANK AND FEEDER TOREMAIN.

67

8

9

10TYP OF 3

E-7201

E-7011

E-7071

E-7251

ARCHITECT

CONSULTANT

STAMP

MARK DATE DESCRIPTION

PROJECT NUMBER:DRAWN BY:CHECKED BY:

SHEET TITLE

100% CONSTRUCTIONDOCUMENT SET

(UMBA 13-L2)

www.arup.com

955 Massachusetts Avenue4th Floor

Cambridge, MA 02139T 617 864 2987 F 617 864 6178

Arup USA Inc

7/17

/201

5 1:

58:3

9 PM

E-402

ELECTRICAL LEVEL 1 -KEY PLAN

UMass Lowell NorthQuad Infrastructure

Renewal

21332

Lowell, MA

University of Massachusetts Building AuthorityUniversity of Massachusetts Lowell

JAIT

1/16" = 1'-0"1 ELECTRICAL - KEY PLAN - LEVEL 1

KEYNOTES

1 METER EXISTING EQUIPMENT FOR A MINIMUM OF 30 DAYS.SUBMIT METERING REPORT TO OWNERS CONSTRUCTIONMANAGER FOR REVIEW PRIOR TO CARRYING OUT ANYWORK. COMPLY WITH NEC 220.87 METERINGREQUIREMENTS. INTENT OF METERING IS TO CONFIRMAVAILABLE CAPACITY IN SYSTEM TO ACCEPT NEW LOADS ASINDICATED.

2 EXISTING PANEL TO BE PROVIDED WITH ADDITIONAL CIRCUITBREAKERS. SEE E300 FOR MORE INFORMATION. FIELDVERIFY EXISTING EQUIPMENT REQUIREMENTS AND PROVIDENEW BREAKERS COMPATIBLE WITH EXISTING EQUIPMENT.

3 EXISTING PANEL TO BE CONNECTED TO NEW POD 2DISTRIBUTION SYSTEM.

4 COORDINATE EXACT GENERATOR LOCATION WITH CIVILDRAWINGS. GENERATOR IS OWNER FURNISHED,CONTRACTOR INSTALLED. PROVIDE 60A/2P/208V AUXCIRCUIT CONNECTION (3#4,#10G) FROM PANEL RP-F-1 IN1-1/4" CONDUIT FOR JACKET HEATER. PROVIDE 20A/1P (2#12)CIRCUIT IN 1"C FOR BATTERY CHARGER FROM PANEL RP-F-1.PROVIDE SEPARATE 1" GENERATOR CONTROL WIRINGCONDUIT FROM GENERATOR INDICATOR PANELCONNECTION AND ATS CONTROL WIRES. PROVIDEDEDICATED 1" CONTROL CONDUIT FOR LIFE SAFETY ATSCONTROL WIRING.

5 RELOCATED SECURITY CAMERA. PROVIDE NEW 1" CONDUITFROM INTERCEPT LOCATION TO POD 2 EXTERIOR.COORDINATE EXACT LOCATION OF CAMERA IN FIELD WITHUML FACILITIES. PROVIDE #12 PULL WIRE FOR CAMERAREINSTALLTION BY OTHERS. SEE E2.01 FOR MOREINFORMATION.

6 NEW DUCTBANK FOR PRIMARY LOOP IN/LOOP OUT FEEDERS.REFER TO CIVIL DRAWINGS FOR MORE INFORMATION.

7 NEW 5kV LOOPED FEEDERS WORK: BREAK INTO EXISTINGMANHOLE AND EXTEND FEEDERS INTO POD 2 ELECTRICALROOM (RM116A). INTERCEPT EXISTING PERRY PRIMARYFEEDERS (3#2/0), CUT, SPLICE AND EXTEND LOOPEDCONNECTION TO NEW POD 2 PRIMARY SWITCH. TESTFEEDERS AND SPICE AS PER GENERAL NOTES ON E000.PROVIDE ADDITIONAL CABLE RACKS AS REQUIRED BY FIELDINSTALLATION.

8 POD2 GROUNDING CONNECTION TO INCOMING WATER PIPE.GROUNDING CLAMP. SEE E3.01 FOR MORE INFORMATION.

9 POD2 GROUNDING CONNECTION TO BUILDING STEEL.EXOTHERMIC WELD. CONSEAL INSIDE NEW PODSTRUCTURE, CONNECTION SHOULD NOT BE VISIBLE FROMBELOW. SEE E3.01 FOR MORE INFORMATION. COORDINATE INFIELD.

10 10'x3/4" COPPER CLAD STEEL GROUNDING ELECTRODES.REFER TO E8XX SERIES DETAILS AND E301 FOR MOREINFORMATION. COORDINATE LOCATION WITH CIVILCONTRACTOR.

GENERAL NOTES1. THIS DRAWING SHOWS THE NEW CAMPUS ELECTRICAL DISTRIBUTION SYSTEMS ONLY. SEEENLARGED ELECTRICAL SHEETS FOR MORE POD DISTRIBUTION EQUIPMENT AND POWERDEVICES.2. DO NOT SCALE FROM THIS DRAWING, REFER TO ARCHITECTURAL DRAWINGS FOR MOREINFORMATION.3. REFER TO ARCHITECTURAL AND CIVIL DRAWINGS AND SCHEDULES FOR MOREINFORMATION AND EXACT EQUIPMENT LOCATIONS.4. COORDINATE ALL DOWNTIME FOR MAIN 4160V FEEDERS WITH UMASS LOWELL NO LESSTHAN FOUR WEEKS BEFORE SHUTDOWN. CAMPUS LOOP FEEDS ADJACENT BUILDINGS.SHUTDOWN SHALL BE RESTRICTED TO "OFF HOURS" AND A DAY OF THE WEEK AS DEFINEDBY UMASS LOWELL OR THEIR REPRESENTATIVE.5. COORDINATE WITH CIVIL DRAWINGS FOR SPECIFIC DUCT BANK ROUTES AND MANHOLELOCATIONS. THIS DRAWING IS DIAGRAMATIC ONLY. SEE E800 DETAIL 1 FOR ADDITIONALDUCTBANK REQUIREMENTS.

1 06/10/14 FEASIBILITY STUDY SET2 08/29/14 SCHEMATIC DESIGN SET3 12/18/14 50% DESIGN DEVELOPMENT SET4 01/15/15 100% DESIGN DEVELOPMENT SET5 04/06/15 60% CONSTRUCTION PERMIT SET6 05/07/15 90% CONSTRUCT. DOC. SET7 06/30/15 TIER 1 PHASE 1 PERMIT SET8 07/17/15 100% CONSTRUCT. DOC. SET

Page 42: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

U/M

PLANT

61sf

DOCK

PLANT

818sf

ELEV

PLANT

36sf

CORR

PLANT

73sf

100A

100

100E1

100C2

CORRPLANT

254.97sf

STAIRPLANT

190.76sf

U/MPLANT

465.73sf

RS LABMECH

459.2sf

OFFMECH

414.78sf

ELEVPLANT

107.41sf

CORRPLANT

822.08sf

100C5 100S2112

113 115

100E1

100C6

CORRPLANT

254.97sf

STAIRPLANT

190.76sf

U/MPLANT

465.73sf

RS LABMECH

459.2sf

OFFMECH

414.78sf

ELEVPLANT

107.41sf

CORRPLANT

822.08sf

100C5 100S2112

113 115

100E1

100C6

J

L6-30

L5-30

J J

J

J

J

JF 225A

J

F 4X

J

JJ

J J

J

JJ

STD MWC171

STD WWC170

NEW PRIM. ELEC.172

NEW EMER. ELEC.172A

IDF/IT174

ELEC173

CORR.100C6

ELEV LOBBY1L1

ACCESS TOKITSON MEZZ 2

100S3

A'

B'

C'

1

22

3

4

LEP-FK-1RP-F-1

MP-FK-1

OEP-FK-1A

LP-FK-1

RP-K-1

OEP-FK-1B

5

6

EP-FK-1A EP-FK-1B

RP-K-1/11

RP-K-1/17

OEP-FK-1B/15

EP-FK-1B/1

RP-K-1/9

RP-K-1/23

RP-K-1/5

RP-K-1/9

RP-K-1/7

RP-K-1/7 RP-F-1/1

RP-K-1/17RP-K-1/3

RP-K-1/3

RP-K-1/7 RP-K-1/7

RP-K-1/11

RP-K-1/17

RP-K-1/11

RP-K-1/9

RP-K-1/9

RP-F-1/1

RP-K-1/15

CUH2

RP-K-1/13/4"C,(2)#10,(1)#10G

OEP-FK-1B/13

AC2-1

EF2-1

+63"

AC3-1

AC3-2

EF2-2

OEP-FK-1B/29,313/4"C,(2)#10,(1)#10G

3/4"C,2#10,#10G

DP-FK1TX1

PS-FK

TX2

TX3

ATS3

ATS2

ATS1

USS-FK

EDP-FK

7

7

7

7

7

8

OEP-FK-1B/39

MP-FK-1/6,8,10

9

10

11

FACU

12

13

TRANSFORMERSECTION

SWITCHBOARDSECTION

OEP-FK-1B/41

8

OEP-FK-1B/37

15

EP-FK-1B/13 EP-FK-1B/13

1616

17

RP-K-1/2518

17

19

17

EP-FK-1B/9

19

17

EP-FK-1B/11

ARCHITECT

CONSULTANT

STAMP

MARK DATE DESCRIPTION

PROJECT NUMBER:DRAWN BY:CHECKED BY:

SHEET TITLE

100% CONSTRUCTIONDOCUMENT SET

(UMBA 13-L2)

www.arup.com

955 Massachusetts Avenue4th Floor

Cambridge, MA 02139T 617 864 2987 F 617 864 6178

Arup USA Inc

7/17

/201

5 1:

59:2

4 PM

E-707

ELECTRICAL POD 2ENLARGED FLOOR

PLANS - LEVEL 1(KITSON HALL)

UMass Lowell NorthQuad Infrastructure

Renewal

21332

Lowell, MA

University of Massachusetts Building AuthorityUniversity of Massachusetts Lowell

JAIT

KEYNOTES

1 POWER FOR SECURITY SYSTEM. INSTALLED BY OTHERS,WIRED BY EC.

2 HAND DRYER. WIRED BY EC, INSTALLED BY OTHERS.3 DRY VALVE. INSTALLED BY OTHERS, EC TO PROVIDE

DISCONENCT SWITHC AND INSTALL ASSOCIATED WIRING.3/4HP.

4 POWER FOR DDC PANEL. FINAL CONNECTION OF DDC PANELBY CONTROLS CONTRACTOR.

5 L5-30 OUTLET MOUNTED IN OVERHEAD CABLE TRAY.LOCATE BETWEEN TWO NEW RACKS INDICATED ONTELECOMS DRAWINGS.

6 L6-30 OUTLET MOUNTED IN OVERHEAD CABLE TRAY. LOCATEBETWEEN TWO NEW RACKS INDICATED ON TELECOMSDRAWINGS.

7 PROVIDE 4" CONCRETE HOUSEKEEPING PAD.8 HEAT TRACE SYSTEM. FINAL CONNECTION TO HEAT

TRACING CONTROL PANEL BY EC, CONNECTION OF HEATTRACING CABLE TO CONTROL PANEL BY HEAT TRACINGINSTALLER.

9 NEW PLATFORM LIFT. PROVIDE FUSE SIZE AS PERMANUFACTURERS RECOMENDATION. FINAL CONNECTION TOLIFT BY EC.

10 PRIMARY AND SECONDARY TRANSFORMER DISCONNECTS.11 COORDINATE EXACT UNIT SUBSTATION LOCATION WITH

EXISTING STRUCTURAL BEAMS. TRANSFORMER SECTION TOBE LOCATED BETWEEN BEAMS TO ENSURE ADEQUATECLEARANCE. MAIN 4160V FEEDERS TO ENTER UNITSUBSTATION FROM BELOW.

12 MAIN GROUNDBAR. SEE E3.01 FOR MORE INFORMATION.13 CONDUITS BELOW SLAB. TURN TO ENTER PRIMARY SWITCH

FROM BELOW. COORDINATE EXACT CONDUIT STUB UPLOCATION WITH EQUIPMENT SUBMITAL PRIOR TO ROUGH IN.SEE E4.02 FOR DUCTBANK CONTINUATION. REFER TO CIVILDRAWINGS FOR ROUTING OF DUCTBANK ON SITE, SEESTRUCTURAL DRAWINGS FOR FLOOR TRENCHINGINFORMATION.

14 POWER FOR FSD. INSTALLED BY OTHERS, WIRED BY EC.15 WATER COOLER. WIRED BY EC, INSTALLED BY OTHERS.16 POWER FOR FSD LOCATED WITHIN FLOOR SLAB. INSTALLED

BY OTHERS, WIRED BY EC.1718 120V POWER IN CEILING MOUNTED JUNCTION BOX FOR

CONNECTION TO VAV/HVAC DEVICES.19 POWER PROVISION FOR FIRE ALARM.

GENERAL NOTES

1. SEE E4.02 FOR MORE INFORMATION ON SITE ELECTRICALDISTRIBUTION.2. AC SYSTEM INDOOR UNITS POWERED SEPARATELY FROMOUTDOOR UNITS.3. EXHAUST FANS ARE ELECTRICALLY COMMUTATED MOTORSWITH INTEGRAL TOGGLE SWITCHES. PROVIDED BY MC, WIREDBY EC.4. 120V POWER PROVIDED FOR DDC PANELS (PANEL WIRED ANDCONNECTED TO DOWNSTREAM EQUIPMENT BY DDCCONTRACTOR).5. SEE E0.00 FOR ADDITIONAL GENERAL NOTES.

1/4" = 1'-0"1 POWER - LEVEL 1 ENLARGED/KITSON STAIR 1 PLAN (POD 2)

NOT USED

1 06/10/14 FEASIBILITY STUDY SET2 08/29/14 SCHEMATIC DESIGN SET3 12/18/14 50% DESIGN DEVELOPMENT SET4 01/15/15 100% DESIGN DEVELOPMENT SET5 04/06/15 60% CONSTRUCTION PERMIT SET6 05/07/15 90% CONSTRUCT. DOC. SET7 06/30/15 TIER 1 PHASE 1 PERMIT SET8 07/17/15 100% CONSTRUCT. DOC. SET

Page 43: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

12"

CONDUIT (TYP.)

COMPACT BACKFILL(95%) SITE WORKSPECIFICATIONS

CONTINUOUSWARNING TAPE

FINISH GRADEOR PAVEMENT

COLORED CONCRETEENCASED, SEE SPECS

30"MIN. TO TOP OFCONDUIT DUCT BANK

3"MIN.3"MIN.

3"MIN. .3"MIN. .

. .

.

12"

24"MIN. COVERFROM TOP SURFACEOF CONDUIT TO TOPSURFACE OFFINISHED GRADE

FINISH GRADEOR PAVEMENT

CONTINUOUSWARNING TAPE

COMPACT BACKFILL(95%) SITE WORKSPECIFICATIONS

CONDUIT (TYP.)

.

1/4" CAST IRON WITHLEGEND "GROUND"

12" DIAMETER X 2'-0"STANDARDCONCRETEPIPE WITH HUB

GROUND ROD(SIZE AS SPECIFIED)

GROUND CONNECTOR(BURNDY TYPE "GAR")

BARE GROUNDING CABLE(SIZE AS SHOWN ON PLANS)

TO NEXT GROUND ROD

CONCRETESLAB

C

MMOUNT IN NEMA 1

ENCLOSURE

MANUAL STARTER WITH THERMAL

OVERLOAD CONTROL RELAY(COORDINATE COILVOLTAGE WITHHVAC CONTROLS)

TO HVACCONTROLS

LINE VOLTAGE

MOTOR

24"ROOF

UNISTRUT P2072A POST BASE

TO NEXT 120 RECEPTACLE OR FIXTURE

WEATHERPROOF GFI RECEPTACLE ANDLIGHT SWITCH

VAPORTIGHT FIXTURE PER LUMINAIRESCHEDULE

UNISTRUT P1000 HS. STEEL POST OFEQUIPMENT SCREEN FRAME

36"

TYPE EX1

SECURE LIGHT FIXTURE SUPPORT WIRESTO MOUNTING TABS, IF LIGHT FIXTURENOT FURNISHED WITH MOUNTING TABS.PROVIDE 4-EYE BOLTS WITH ALLNECESSARY HARDWARE

#12 GA (MIN) LIGHT SUPPORT WIRE,4-PER 4-FOOT LENGHT OF LIGHTFIXTURE. SECURE TO BUILDINGSTRUCTURE SIMILAR TO CEILINGSUPPORT WIRES

#12 GA (MIN) LIGHT SUPPORTWIRE, 4-PER 4-FOOT LENGTHOF LIGHT FIXTURE. SECURE TOBUILDING STRUCTURE SIMILARTO CEILING SUPPORT WIRES

SECURE LIGHT FIXTURESUPPORT WIRES TO MOUNTINGTABS, IF LIGHT FIXTURE NOTFURNISHED WITH MOUNTINGTABS. PROVIDE 4-EYE BOLTSWITH ALL NECESSARYHARDWARE

TYPICAL CROSS "T" BAR

TYPICAL ACOUSTICALTILE CEILING

TYPICAL GYPSUMCEILING

TYPICAL RECESSEDLIGHT FIXTURE

TYPICAL RECESSEDLIGHT FIXTURE

TYPICAL FLEX CONDUIT WITH ALLNECESSARY FITTINGS TO JUNCTION BOX.PROVIDE #12 BRANCH CIRCUIT WIRESAND #12 GROUND WIRE BOND TO LIGHTFIXTURES

"T" BAR CLIP, ALL LIGHT FIXTURES (ORROWS) SHALL HAVE TWO CLIPS ATEACH END. PROVIDE 2#8-32 BOLTSWITH LARGE FLAT WASHERS AND NUTSBETWEEN LIGHT FIXTURES INCONTINUOUS ROW INSTALLATION

TYPICAL MAIN"T" RUNNER

ARCHITECT

CONSULTANT

STAMP

MARK DATE DESCRIPTION

PROJECT NUMBER:DRAWN BY:CHECKED BY:

SHEET TITLE

100% CONSTRUCTIONDOCUMENT SET

(UMBA 13-L2)

www.arup.com

955 Massachusetts Avenue4th Floor

Cambridge, MA 02139T 617 864 2987 F 617 864 6178

Arup USA Inc

7/17

/201

5 2:

00:0

0 PM

E-800

ELECTRICAL DETAILSPLAN SHEET 1

UMass Lowell NorthQuad Infrastructure

Renewal

21332

Lowell, MA

University of Massachusetts Building AuthorityUniversity of Massachusetts Lowell

JAIT

NTS1 CONCRETE ENCASED UNDERGROUND DUCT BANKNTS2 BRANCH CIRCUIT DIRECT BURIAL CONDUIT

NTS3 GROUND ROD AND WELL

NTS4 120V/277V SINGLE PHASE MOTOR CONTROL DIAGRAMNTS5 ROOFTOP LIGHT AND RECEPTACLE

NTS6 RECESSED LIGHT FIXTURE MOUNTING DETAIL1. PROVIDE TYPE EX1 OUTLET AT ALL ROOFTOP MAINTENENCE OUTLET LOCATIONS. PROVIDE LOCAL WEATHER PROOF SWITCH.

1. APPLIES TO NEW GENERATOR AND NEW PRIMARY FEEDERS AS SHOWN ON E-402. 1. TYPICAL FOR ALL EXTERIOR BRANCH CIRCUITS. FEEDERS TO BE CONCRETE ENCASED PER DETAIL 1. 1. TYPICAL FOR ALL GROUND RODS SHOWN ON E402 AND E301.

1. TYPICAL DETAIL. REFER TO MECHNICAL DRAWINGS AND COORDINATE WITH MECHANICAL CONTRACTOR FOR SPECIFICEQUIPMENT REQUIREMENTS. E008 SHOWS TABLE OF MECHANICAL EQUIPMENT.

1. DETAIL SHOWN IS TYPICAL FOR RECESSED LIGHT FIXTURES. FOLLOW MANUFACTURERS SPECIFIC INSTALLATION INSTRUCTIONS FOR ALL FIXTURES.

1 06/10/14 FEASIBILITY STUDY SET2 08/29/14 SCHEMATIC DESIGN SET3 12/18/14 50% DESIGN DEVELOPMENT SET4 01/15/15 100% DESIGN DEVELOPMENT SET5 04/06/15 60% CONSTRUCTION PERMIT SET6 05/07/15 90% CONSTRUCT. DOC. SET7 06/30/15 TIER 1 PHASE 1 PERMIT SET8 07/17/15 100% CONSTRUCT. DOC. SET

Page 44: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

STRUT SUPPORT

LOCKNUT (TYP.)

HANGER ROD (TYPICAL)

3" CONDUIT (TYPICAL)

PIPE CLAMP

3'-2"3'-2"3'-2" 3'-6"

24" 24"

CERAMIC FIBER)

DAMMING MATERIAL

CONDUIT

(MINERAL WOOL OR FIRE RATED CONCRETE FLOOR SLAB

3M FIRE BARRIERFS-195 WRAP/STRIP

CP 25 CAULK3M FIRE BARRIER

WALL PENETRATION FIRE STOPS MUST BE INSTALLED ON BOTH SIDES OF THE WALL.

FS-195 WRAP/STRIPS REQUIRED PER INSULATION THICKNESS. SEE TABLE 1 BELOW.

FS-195 WRAP/STRIPS ARE FRICTION FIT INTO THE OPENING OR SECURED WITH 16MINIMUM ANNULAR SPACE IS 3/4".

GAUGE STEEL TIE WIRE OR ALUMINUM FOIL TAPE AND SLID INTO THE OPENING

THE MINIMUM ANNULAR SPACE MUST ACCOMADATE THE MINIMUM NUMBER OFWITH A MINIMUM 1/4" BEAD OF CP 25 CAULK.

THE MAXIMUM ANNULAR SPACE TO BE FILLED IN THE WALL IS 3", AND THE

1 WRAP2 WRAP3 WRAP

WRAP

3" DEPTH

CAULK1" DEPTH

TABLE 1

2" DEPTH

2.

3.

4.

NOTES

1.

3" THICK

INSULATION1" THICK2" THICK

INSULATED METAL PIPE

3M FIRE BARRIERCP 25 CAULK

FIRE RATED CONCRETE WALL

3M FIRE BARRIERFS-195 WRAP/STRIP

BATTERY CHARGER OUTPUT CONNECTTO BATTERY 2#10 IN 3/4"C.

SIGNAL WIRING TO REMOTE ANNUN. 2#10& 4#14 INSTALL IN 2" GENERATOR BRANCHCIRCUIT CONDUIT

ANNUNCIATORPANEL

EXH.INT.

EMERGENCYGENERATOR SET VENT DAMPER CONTROL WIRING 2#12,

2#12 GND. IN 1/2"C.

BATTERYCHARGER

POWER WIRING FOR ENGINE JACKET WATERHEATER, 60A-2P.

ENGINE START CONTROL WIRING 2#14INSTALL IN 2" GENERATOR BRANCHCIRCUIT CONDUIT

JSIGNAL WIRING TO ATS 4#14IN 1/2"C.

AUTOMATICTRANSFER

SWITCH

ATS EMERGENCY FEEDER (VIAMSB-GEN, NOT SHOWN) FOR REQUIREMENTSREFER TO ELECTRICAL SINGLE LINE DIAGRAM

1.

NOTES:

ATS NORMAL POWER SOURCE,FOR REQUIREMENTS REFERTO ELECTRICAL RISER DIAGRAM

ATS OUTPUT FEEDER TOEMERGENCY DISTRIBUTIONPANELBOARD, FORREQUIREMENTS REFER TOELECTRICAL RISER DIAGRAM

CONTRACTOR SHALL COORDINATE ALL CONTROLS, CONTROL WIRING AND ALL OTHER REQUIREMENTS WITH THEAPPROVED MANUFACTURER, ADJUST ALL WIRING ACCORDINGLY.

SIGNAL WIRING TO REMOTEANNUNCIATOR 2#10 & 4#14 IN3/4"C.

BATTERY CHARGER 120V 20A-1P DEDICATEDCIRCUIT 2#12 & 1#12 GND.INSTALL IN 2" GENERATOR BRANCH CIRCUIT CONDUIT

WIRING FOR ONE ATS IS SHOWN, REFER TO RISER DIAGRAM FOR EXACT REQUIREMENTS, QUANTITIES OF ATS'S,CIRCUIT BREAKERS, ETC.

2.

REMOTE

WITH BLOCK HEATER AND VENT DAMPER BRANCH CIRCUITS

ENGINE START WIRING FOR LIFE SAFETY AND LEGALLY REQUIRED SYSTEMS TO BE 2 HOUR FIRE RATED AND SEPARATEFROM OTHER WIRING.

3.

ENGINE JACKET AND OTHER AUX LOAD CONNECTIONS SHOWN ARE MANUFACTURER SPECIFIC. CONTRACTOR ISRESPONSIBLE FOR COORDINATING REQUIREMENTS WITH CHOSEN MANUFACTURER.

4.

FA INTERFACE.

POD 2 EM ELEC RM

BELLY TANK HIGH/LOW LEVEL SWITCHES WIRED

BY OTHERS.

CONTRACTOR TO ENGAGE GENERATOR MANUFACTURER TO REPROGRAM GENERATOR AND SET OUTPUT CIRCUIT BREAKER5.AS PER RESULTS OF CONTRACTORS OVERCURRENT PROTECTION STUDY. LIFE SAFETY SYSTEM TO COORDINATE DOWN TO 0.01S.

OWNER FURNISHED,CONTRACTOR INSTALLED

NOTE 5

AOMNEUTRAL

HOT

RELAY IF REQUIRED

GENERAL NOTES1. PROVIDE A RELAY MODULES TO OPERATE FAN STARTER.2. LOCATE ACTIVATION RELAYS WITHIN 3 FT OF DEVICE BEING CONTROLLED INACCORDANCE WITH NFPA 72.

TO/FROM FIRE ALARMSLC

(POWER TO OPERATE SMOKE HATCH)

RELAY 1

DAMPER

3. WIRE THERMOSTAT SO BOTH THERMOSTAT AND FIRE ALARM CAN START FAN.

SWITCH-PACK

PHOTO

OCC

MODE OPERATION :1. TYPICAL FOR ALL CIRCULATION, BATHROOM AND OTHER

SPACES SHOWN WITH CEILING OCC SENSORS.2. FIXTURES ARE TO OPERATE AS AUTO ON/AUTO

OFF (OCCUPANCY DETECTION).3. PROVIDE QUANTITY OF SWITCHING PACKS AS REQUIRED

FOR CONTROL ZONES AS INDICATED ON PLANS.

4. EM LIGHTING CIRCUITS REQUIRE UL924 BYPASS RELAY TOACTIVATE ON LOSS OF MAINS POWER.AS PER SENSOR SWITCH "NLIGHT" SYSTEM OPERATING INSTAND ALONE ROOM CONTROLLER MODE. ALTERNATESOLUTIONS AS PER WATT STOPPER "DLM" AND LUTRON"ECOSYSTEM".

RJ45 IN/OUT JACKS PER DEVICE.

LIGHTING BRANCH CIRCUIT AS INDICATED ON PLANS

SWITCHED LIGHTING CIRCUIT PER CONTROL ZONE.

CAT5e DATA CABLE TO MANUFACTURERS REQUIREMENTS.

ARCHITECT

CONSULTANT

STAMP

MARK DATE DESCRIPTION

PROJECT NUMBER:DRAWN BY:CHECKED BY:

SHEET TITLE

100% CONSTRUCTIONDOCUMENT SET

(UMBA 13-L2)

www.arup.com

955 Massachusetts Avenue4th Floor

Cambridge, MA 02139T 617 864 2987 F 617 864 6178

Arup USA Inc

7/17

/201

5 2:

00:0

3 PM

E-802

ELECTRICAL DETAILSPLAN SHEET 3

UMass Lowell NorthQuad Infrastructure

Renewal

21332

Lowell, MA

University of Massachusetts Building AuthorityUniversity of Massachusetts Lowell

JAIT

NTS1 Emergency Generator DetailNTS2 Hoistway Vent Interface

NTS3 Ceiling Occupancy Sensor Detail

NTS4 Typical Conduit Rack DetailNTS5 Typical Conduit Through Floor Detail

NTS6 Typical Conduit Through Wall Detail

1 06/10/14 FEASIBILITY STUDY SET2 08/29/14 SCHEMATIC DESIGN SET3 12/18/14 50% DESIGN DEVELOPMENT SET4 01/15/15 100% DESIGN DEVELOPMENT SET5 04/06/15 60% CONSTRUCTION PERMIT SET6 05/07/15 90% CONSTRUCT. DOC. SET7 06/30/15 TIER 1 PHASE 1 PERMIT SET8 07/17/15 100% CONSTRUCT. DOC. SET

Page 45: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

DN

JCPLAN

T

21sf

RS LAB

CIVIL

659sf

OFF

CIVIL

196sf

CONF

CIVIL

269sf

OFF

CIVIL

388sf

CORR

PLAN

T

500sf

OF SV

CIVIL

46sf

OF SV

CIVIL

66sf

OFF

CIVIL

169sf

OFF

CIVIL

152sf

OFF

CIVIL

202sf

CL LAB

CIVIL

1004sf

CORR

PLAN

T

450sf

MERCH

BKSTR

5878sf

STAIR

PLAN

T

259sf

U/M

PLAN

T

61sf

DOCK

PLAN

T

818sf

ELEV

PLAN

T

36sf

MR SV

BKSTR

741sf

CORR

PLAN

T

242sf

CORR

PLAN

T

73sf

CORR

PLAN

T

62sf

MR SV

BKSTR

414sf

MR SV

BKSTR

538sf

C SERV

PURCH

1005sf

106

104

108A

108B

108

100C4

107D

107

107C

107B

107A

105

100C3

102

100S1

100A

100

100E1

101

100C1

100C2

100C5

102B

103

102A

STAIRPLANT

212.68sf

RS LABMECH

316.07sf

CORRPLANT

305.17sf

RS LABMECH

742.68sf

CORRPLANT

761.34sf

CL LABMECH

552.35sf

CL LABMECH

1552.32sf

RS LABMECH

644.92sf

RS LABMECH

101.25sf

RS LABMECH

824.76sf

RLB SVMECH

50.76sf

RLB SVMECH

154.69sf

CORRPLANT

254.97sf

STAIRPLANT

190.76sf

U/MPLANT

465.73sf

RS LABMECH

531.66sf

RS LABMECH

550.8sf

RS LABMECH

865.63sf

U/MPLANT

156.13sf

MENPLANT

335.88sf

RS LABMECH

886.77sfRS LABMECH

459.2sf

OFFMECH

414.78sf

ELEVPLANT

107.41sf

CORRPLANT

613.71sf

CORRPLANT

822.08sfU/MPLANT

2.36sf

CORRPLANT

243.05sf

100S1

101A

100C2

101

100C3

102A 102 104

104A

106

106A

106B

100C5 100S2112

103 105 107

111A

111B

111113 115

100E1

100C4 100C6

105A

100C1

CL LAB

DN ENGR

1646sf

CLASS

REG

538sf

CL LAB

CIVIL

216sf

RS LAB

MECH

261sf

OFF

CIVIL

305sf

CL LAB

CIVIL

723sf

CMP/TEL

IT

88sf

U/M

PLANT

437sf

CLB SV

CIVIL

70sf

CLB SV

CIVIL

266sf

FD SV

DINING

101sf

U/M

PLANT

53sf

U/M

PLANT

53sf

U/M

PLANT

249sf

FD SV

DINING

52sf

U/M

PLANT

34sf

UNISEX

PLANT

57sf

FD SV

DINING

214sf

FD SV

DINING

39sf

FD SV

DINING

249sf

FD SV

DINING

1960sf

JCPLANT

31sf

U/M

PLANT

40sf

STAIR

PLANT

263sf

STAIR

PLANT

273sf

MEN

PLANT

56sf

CORR

PLANT

817sf

CORR

PLANT

305sf

U/M

PLANT

86sf

CORR

PLANT

276sf

CORR

PLANT

407sf

RLB SV

CIVIL

192sf

CL LAB

CIVIL

1027sf

FOOD

DINING

3293sf

WOMEN

PLANT

223sf

122

121

120

130A

129

130

132A

132C

125

126

143

141A

140D

140C

140A

140B

152A

152

146

148

150

133A

145A

100S1

100S2

132D

100C1

100C2

132B

100C4

100C3

123

127

145

133

STAIRPLANT

227sf

RLB SVGSE

339sf

CORRPLANT

96sf

OF SVCIVIL

219sf

OFFCIVIL

133sf

U/MPLANT

292sf

OFFP&T

75sf

OFFDINING

127sf

FOODDINING

1958sf

RS LABCIVIL

181sf

JCPLANT

35sf

MENPLANT

112sf

CORRPLANT

117sf

OF SVCIVIL

115sfCL LABCIVIL

330sf

OFFCIVIL

178sf

OFFCIVIL

241sfRS LABCIVIL

481sf

CORRPLANT

457sf

U/MPLANT

235sf

OFFGSE

145sf

OFFGSE

109sf

OFFGSE

61sf

OFFGSE

168sf

OFFCIVIL

287sf

OFFCIVIL

253sf

OF SVCIVIL

223sf

OFFCIVIL

251sf

OFFCIVIL

214sf

CMP/TELIT

43sf

RS LABCIVIL

259sf

OFFCIVIL

279sf

OFFCIVIL

348sf

OFFCIVIL

273sf

CORRPLANT

469sf

RS LABDN ENGR

622sf

OF SVCIVIL

125sf

ELEVPLANT

37sf

U/MPLANT

15sf

100S1

106G

100C1

103A

105D

101

100B

100A

100

105E

107C 107B

100C4

107A103

105A

105B

105C

100C2

106E

106D

106C106B

106A

107 109

109A

111 113

115

114112110108

100C3

106

105

100E1

106F

UP DN

U/M

PLAN

T

163sf

U/M

PLAN

T

426sf

CL LAB

CHEM E

568sfOFF

CHEM E

232sf

OFF

CHEM E

141sf

U/M

PLAN

T

243sf

101A

101

103102

104

101B

VD

VD

VD

VDVDBF

P

FSD

FSD

FSD

FSD

M

VDCORR.

DINING & STD WWC

DINING & STD MWC

CORR.

STD WWCSTD MWC

NEW EMER. ELEC.

NEW PRIM. ELEC.

ELEC IDF/ITELEV LOBBY

2

A

B

4

D

E

51 1.5

1' 2' 3'

A'

B'

C'

3

C

A.5

C.5

0.5

M-7011

M-7081

2" LPS

1 1/2" CD

2"LPS UP1 1/2" CD UP (N)

4"LPS3"CD (E)

6" FLUE UP

6" FLUE FROM GENERATOR

ARCHITECT

CONSULTANT

STAMP

MARK DATE DESCRIPTION

PROJECT NUMBER:DRAWN BY:CHECKED BY:

SHEET TITLE

100% CONSTRUCTIONDOCUMENT SET

(UMBA 13-L2)

www.arup.com

955 Massachusetts Avenue4th Floor

Cambridge, MA 02139T 617 864 2987 F 617 864 6178

Arup USA Inc

7/20

/201

5 3:

01:3

4 PM

M-402

MECHANICAL LEVEL 1- KEY PLAN

UMass Lowell NorthQuad Infrastructure

Renewal

21332

Lowell, MA

University of Massachusetts Building AuthorityUniversity of Massachusetts Lowell

--

1/16" = 1'-0"1 MECHANICAL - KEY PLAN - LEVEL 1

1 06/10/14 FEASIBILITY STUDY SET2 08/29/14 SCHEMATIC DESIGN SET3 12/18/14 50% DESIGN DEVELOPMENT SET4 01/15/15 100% DESIGN DEVELOPMENT SET5 04/06/15 60% CONSTRUCTION PERMIT SET6 05/07/15 90% CONSTRUCT. DOC. SET7 06/30/15 TIER 1 PHASE 1 PERMIT SET8 07/17/15 100% CONSTRUCT. DOC. SET

Page 46: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

10sf

UP

UP

STAIRPLANT

212.68sf

190.76sf

ELEVPLANT

107.41sf

100S1

100S2

100E1

VDVD

VD

FSD

FD

FD

FD

MR

CORR.

IDF/IT ELEC.

EE

JC

LIGHTWELL

MEZZANINE 1[UNASSIGNED]

MEZZANINE 2[UNASSIGNED]

ENTRY LOBBY

2

A

B

4

D

E

51 1.5

1' 2' 3'

A'

B'

C'

3

C

A.5

C.5

0.5

M-7021

X-M-7091

6" FLUE UP & DN

ARCHITECT

CONSULTANT

STAMP

MARK DATE DESCRIPTION

PROJECT NUMBER:DRAWN BY:CHECKED BY:

SHEET TITLE

100% CONSTRUCTIONDOCUMENT SET

(UMBA 13-L2)

www.arup.com

955 Massachusetts Avenue4th Floor

Cambridge, MA 02139T 617 864 2987 F 617 864 6178

Arup USA Inc

7/20

/201

5 3:

01:3

8 PM

M-403

MECHANICAL LEVEL1.5 - KEY PLAN

UMass Lowell NorthQuad Infrastructure

Renewal

21332

Lowell, MA

University of Massachusetts Building AuthorityUniversity of Massachusetts Lowell

--

1/16" = 1'-0"1 MECHANICAL - KEY PLAN - LEVEL 1.5

1 06/10/14 FEASIBILITY STUDY SET2 08/29/14 SCHEMATIC DESIGN SET3 12/18/14 50% DESIGN DEVELOPMENT SET4 01/15/15 100% DESIGN DEVELOPMENT SET5 04/06/15 60% CONSTRUCTION PERMIT SET6 05/07/15 90% CONSTRUCT. DOC. SET7 06/30/15 TIER 1 PHASE 1 PERMIT SET8 07/17/15 100% CONSTRUCT. DOC. SET

Page 47: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

UPUP

200C1

207

207H

OFF

MGMT

128sf

OFF

MGMT

142sf

OFF

MGMT

178sf

OFF

MGMT

99sf

OFF

MGMT

100sf

OFF

MGMT

95sf

OFF

MGMT

103sf

CLAS

SREG

855sf

OFF

DN ENGR

213sf

OFF

DN ENGR

527sf

OFF

ECE

125sf

OFF

ECE

134sf

RS LAB

ECE

1679sf

OFF

MMIS

155sf

OFF

MGMT

111sf

OFF

MGMT

111sf

OFF

MGMT

155sf

CONF

MGMT

434sf

OFF

MGMT

194sf

RLB SV

DN ENGR

236sf

RS LAB

ECE

372sf

RS LAB

DN ENGR

175sf

RS LAB

DN ENGR

218sf

JCPLANT

114sf

WOMEN

PLANT

189sf

CS

PLANT

79sf

CLAS

SREG

1457sf

RS LAB

DN ENGR

115sf

RS LAB

DN ENGR

113sf

RS LAB

DN ENGR

325sf

RS LAB

DN ENGR

653sf

RLB SV

DN ENGR

70sf

STAIR

PLANT

284sf

RS LAB

DN ENGR

315sf

ELEV

PLANT

36sf

OFF

MGMT

110sf

CORR

PLANT

190sf

CORR

PLANT

186sf

CORR

PLANT

538sf

RLB SV

ECE

169sf

RLB SV

ECE

152sf

OF SV

DN ENGR

431sf

OF SV

DN ENGR

95sf

MEET

DN ENGR

194sf

CORR

PLANT

1009sf

CONF

MGMT

383sf

OF SV

MGMT

90sf

207G

207F

207E

207D

207C

207B

207A

205

203B

203A

203D

203E

203

202E

202C

202D

202A

202

202B

204D

204B

204A

208A

210

214

212

209

206A

208B

208

206

204C

200S1

204

200E1

202F

200C2

200C4

200C3

203C

203F

201

201B

201A

200C1

207

207H

201

201DSTAIRPLANT

234.69sf

CORRPLANT

197.62sf

CORRPLANT

136.52sf

OFFU ADV

133.44sf

CORRPLANT

778.77sf

OFFWRK ENV

172.06sf

OFFWRK ENV

69.26sf

OFFWRK ENV

194.28sfOFF

WRK ENV

195.18sf

U/MPLANT

244.47sf

ELEVPLANT

111.26sfOFF

WRK ENV

103.64sf

OFFWRK ENV

182.26sf

OFFWRK ENV

190.84sf

OFFWRK ENV

190.84sf

CL LABWRK ENV

197.6sf

OFFU ADV

128.39sf

OFFU ADV

97.66sf

OFFWRK ENV

98.46sf

OFFWRK ENV

99.24sf

OFFWRK ENV

97.65sf

OFFWRK ENV

109.56sf

OFFWRK ENV

118.3sf

OFFWRK ENV

97.92sf

OF SVWRK ENV

140.63sf

OFFWRK ENV

188.97sf

OFFWRK ENV

249.68sf

RS LABWRK ENV

537.76sf

C SERVPURCH

827.14sf

C SERVPURCH

973.78sf

OFFWRK ENV

88.84sf

OFFWRK ENV

86.78sf

OFFWRK ENV

91.45sf

OFFWRK ENV

90.92sf

U/MPLANT

170.43sfU/MPLANT

36.21sf

STAIRPLANT

225sf

CORRPLANT

196.66sf

CORRPLANT

505.23sf

OFFWRK ENV

101.82sf

OFFLCSP

128.86sf

OFFLCSP

134.78sf

OFFLCSP

105.64sf

OFFLCSP

109.11sf

OFFLCSP

117.76sf

OFFLCSP

117.54sf

OFFLCSP

85.61sf

OFFLCSP

73.34sf

OF SVLCSP

344.11sf

CLASSREG

533sf

OFFWRK ENV

105.58sf

OF SVWRK ENV

109.68sf

OFFWRK ENV

127.7sf

OFFWRK ENV

133.4sf

OFFWRK ENV

204.22sf

OF SVWRK ENV

119.83sf

OFFWRK ENV

180.25sf

OFFWRK ENV

183.52sf

OF SVWRK ENV

111.26sf

OFFWRK ENV

104.95sf

OFFWRK ENV

111.19sf

CORRPLANT

773.06sf

OFFWRK ENV

175.19sf

OFFWRK ENV

1212.04sf

LOUNGEWRK ENV

256.7sf

CONFWRK ENV

303.82sfOFF

U ADV

173.67sf

CMP/TELIT

19.83sf

200S1

200C1 200C2

201C

200C3

202D202C

204C204B 214

200E1200U

200S200Q200P

200A

201A 201B 200J 200K 200L 200M 200N 200O

200R 200T

200V 213

216

215

200F 200E 200D 200C

212212A

200S2

200C5200C4

200W

210C

210D210E210F210G210H

210B210A

210

208

206A

206

206B

206C204A

204

204D

202E

202

202A 204E

200C6

202B

200

200X200Y

201

201D

OFF

U ADV

304sf

OFF

U ADV

247sf

OFF

U ADV

102sf

OFF

U ADV

102sf

OFF

U ADV

284sf

OFF

U ADV

96sf

OFF

U ADV

133sf

OFF

U ADV

102sf

OFF

U ADV

105sf

OFF

U ADV

105sf

OFF

U ADV

101sf

OFF

U ADV

102sf

OFF

U ADV

103sf

OF SV

U ADV

115sf

U/M

PLANT

35sf

OFF

U ADV

120sf

OF SV

U ADV

74sf

OFF

MMIS

104sf

OFF

MMIS

80sf OFF

MMIS

104sf

OFF

MMIS

104sf

OFF

MMIS

104sf

OFF

MMIS

102sf

OFF

MMIS

137sf

OF SV

MMIS

89sf

OF SV

MMIS

54sf

OFF

MMIS

112sf

OFF

MMIS

120sf

OFF

U ADV

145sf

OFF

U ADV

96sf

CONF

U ADV

316sf

OFF

U ADV

104sf

OFF

U ADV

275sf

OFF

U ADV

608sf

OFF

U ADV

235sf

OFF

U ADV

184sf

MEET

U ADV

748sf

STAIR

PLANT

391sf

JCPLANT

27sf

WOMEN

PLANT

227sf

OFF

U ADV

501sf

OFF

U ADV

280sf

STAIR

PLANT

381sf

CONF

MMIS

553sf

CONF

MMIS

174sf

OF SV

U ADV

883sf

STAIR

PLANT

353sf

STAIR

PLANT

352sf

OFF

119sf

OFF

119sf

119sf

OFF

CCE

119sf

OFF

CCE

177sf

OF SV

CCE

130sf

OFF

CCE

121sf

OFF

CCE

101sf

OFF

CCE

111sf

OFF

CCE

102sf

OFF

CCE

105sf

OFF

CCE

105sf

OFF

CCE

1023sf

OFF

CCE

136sf

OFF

CCE

219sf

CONF

CCE

358sf

CORR

PLANT

639sf

OFF

CCE

727sf

OFF

CCE

105sf

250M

250N

254B

254C

254D

254E

250L

250K

250I

250A

250H

250G

250C

250D

242

256B

258

201G

201F

201E

201D

201C

201B

201A

201K

201L

201J

201I

254A

254F

252

250B

250J

256

256A

256C

240

200S2

260

262

250

254

200S1

201

201H

250P

200S4

200S3

202A

202B

202C

202D

202E

202F

203A

203B

203C

203D

203E

203F

203

203H

203I

204

200C1

202

203G

DN

UP

UP

UP

ELEVPLANT

37sf

U/MPLANT

34sf

CORRPLANT

434sf

OFFMGMT

180sf

OFFMGMT

230sf

OFFMGMT

229sf

OFFMGMT

162sf

CLASSREG

631sf

CLASSREG

1106sf

STAIRPLANT

330sf

JCPLANT

10sf

OFFMGMT

191sf

OFFMGMT

134sf

OFFMGMT

148sf

OFFMGMT

165sf

OFFSOB ORG

254sfMENPLANT

162sf

OP LABMGMT

789sf

OLB SVMGMT

109sf

OP LABMGMT

1201sf

CORRPLANT

613sf

OFFMGMT

364sf

OFFMGMT

383sf

OFFMGMT

269sf

CONFSOB ORG

130sf

CONFSOB ORG

126sf

CONFSOB ORG

179sf

CMP/TELIT

80sf

CORRPLANT

338sf

OLB SVMGMT

126sf

LOUNGESOB ORG

327sf

OFFMGMT

319sf

OF SVMGMT

41sf

OFFMGMT

133sf

LOUNGESOB ORG

418sf

200E1

215A

200C3

224222220218

213 215

200S1

208B

216214212210208

208A

205

209

207

200C2

206

204202

203A201B201A

200

200C1

207A

203

211

211A

211B

201

UPDNUP

OFF

CHEM E

223.60sf

CL LAB

CHEM E

138.93sf

CL LAB

CHEM E

1101.19sf

202

204 201

FD

VD

VDVDVD

VD

VDVD

VD

VD

VD VDVD

VDVD

VD

VD

FDFS

D

FSD

FD

VD VD

VD VD

FSD

FSD

FD

FD

FD

FD

FD

CORR.

2

A

B

4

D

E

51 1.5

1' 2' 3'

A'

B'

C'

3

C

A.5

C.5

0.5

M-7031

M-7101

2"LPS DN1 1/2" CD DN

6" GENERATOR FLUE UP/DN

ARCHITECT

CONSULTANT

STAMP

MARK DATE DESCRIPTION

PROJECT NUMBER:DRAWN BY:CHECKED BY:

SHEET TITLE

100% CONSTRUCTIONDOCUMENT SET

(UMBA 13-L2)

www.arup.com

955 Massachusetts Avenue4th Floor

Cambridge, MA 02139T 617 864 2987 F 617 864 6178

Arup USA Inc

7/20

/201

5 3:

01:4

8 PM

M-404

MECHANICAL LEVEL 2- KEY PLAN

UMass Lowell NorthQuad Infrastructure

Renewal

21332

Lowell, MA

University of Massachusetts Building AuthorityUniversity of Massachusetts Lowell

--

1/16" = 1'-0"1 MECHANICAL - KEY PLAN - LEVEL 2

1 06/10/14 FEASIBILITY STUDY SET2 08/29/14 SCHEMATIC DESIGN SET3 12/18/14 50% DESIGN DEVELOPMENT SET4 01/15/15 100% DESIGN DEVELOPMENT SET5 04/06/15 60% CONSTRUCTION PERMIT SET6 05/07/15 90% CONSTRUCT. DOC. SET7 06/30/15 TIER 1 PHASE 1 PERMIT SET8 07/17/15 100% CONSTRUCT. DOC. SET

Page 48: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

CORR

PLAN

T

357.35sf

OFF

MGMT

141.78sf

OFF

MGMT

148.35sf

OF SV

MGMT

141.95sf

OFF

MGMT

270.30sf

OFF

MGMT

155.56sf

OFF

MGMT

119.03sf

OFF

MMIS

115.13sf

OFF

MGMT

139.84sf

OFF

ENGLIS

H

145.04sf

OFF

ENGLIS

H

152.42sf

OF SV

MGMT

74.89sf

OF SV

ENGLIS

H

89.67sf

OF SV

ENGLIS

H

244.07sf

OFF

ENGLIS

H

151.19sf

OFF

ENGLIS

H

257.71sf

WOMEN

PLAN

T

404.45sf

CONF

DN ENGR

702.64sf

CORR

PLAN

T

1312.12sf

OFF

ECON

132.71sf

OFF

ECON

133.25sf

OFF

ECON

131.63sf

OFF

ECON

128.92sf

CONF

ECON

308.75sf

OF SV

ECON

47.83sf

OFF

ECON

166.25sf

OFF

ECON

128.25sf

OFF

ECON

128.78sf

OFF

ECON

129.83sf

OFF

ECON

130.89sf

OFF

ECON

127.02sf

OFF

ECON

266.00sf

OFF

ECON

886.85sf

OFF

MGMT

418.41sf

JCPLAN

T

30.93sf

CORR

PLAN

T

223.64sf

OF SV

DN MGMT

211.26sf

MEN

PLAN

T

451.19sf

CLAS

SREG

869.60sf

CORR

PLAN

T

809.73sf

CLAS

SREG

1323.01sf

CLAS

SREG

870.20sf

OFF

ECON

122.92sf

OFF

ECON

131.75sf

OFF

ECON

130.24sf

OFF

ECON

136.16sf

STAIR

PLAN

T

285.25sf

300C2

305B

305A

305H

305

305G

305F

305E

305D

301C

301D

305C

301E

301

301B

301A

300A

300

300C1

302Q

302O

302P

302N

302M

302L

302K

302J

302I

302H

302G

302F

302E

302

306

308B

300C4

308

308A

309300C3

313

311

302A

302B

302D

302C

300S1

CORRPLANT

269sf

CORRPLANT

506sf

CORRPLANT

513sf

JCPLANT

24sf

JCPLANT

37sf

U/MPLANT

137sf

OF SVDN ENGR

151sf

MENPLANT

445sf

CL SVREG

115sf

CL SVREG

113sf

CLASSREG

1280sf

CLASSREG

1353sf

CLASSREG

1065sf

CLASSREG

1100sf

OFFGSA

283sf

CLASSREG

779sf

CLASSREG

511sf

CLASSREG

771sf

CLASSREG

512sf

OFFECE

287sf

CLASSREG

1021sf

OFFDN ENGR

198sf

OF SVDN ENGR

201sf

STAIRPLANT

235sf

STAIRPLANT

226sf CORRPLANT

942sf

ELEVPLANT

107sf

CORRPLANT

204sf

CORRPLANT

335sf

CONFDN ENGR

220sf

OFFDN ENGR

300sf

OF SVDN ENGR

20sf

OFFDN ENGR

892sf300C2 300C3 300C4314A

314

316A

316

309C

309B309A

309305303301

300 302 304 306308

312310

313A313

300S1

300S2

300C6

300E1

300C1 300C5

311B 311A

311C

311

326D

OFF

CLASS

124sf

OF SV

CLASS

79sf

OFF

CLASS

93sf

STAIR

PLANT

399sf

OFF

CLASS

131sf

OFF

CLASS

96sf

OFF

CLASS

158sf

CL LAB

CLASS

720sf

LOBBY

PLANT

321sf

CL LAB

CLASS

831sf

OFF

CLASS

91sf

CL LAB

CLASS

799sf

OFF

CLASS

154sf

OFF

CLASS

223sf

OFF

CLASS

112sf

OFF

CLASS

74sf

JCPLANT

30sf

WOMEN

PLANT

239sf

STAIR

PLANT

399sf

OFF

PROV

121sf

OFF

PROV

98sf

CORR

PLANT

520sf

LOBBY

PLANT

309sf

CORR

PLANT

366sf

OP LAB

CLASS

536sf

OLB SV

CLASS

115sf

OP LAB

CLASS

549sf

OF SV

CLASS

16sf

OFF

CLASS

264sf

CORR

PLANT

258sf

OFF

CAREER

743sf

CONF

CAREER

210sf

OFF

CAREER

136sf

OFF

CAREER

120sf

OFF

CAREER

189sf

OFF

CAREER

114sf

OFF

CAREER

162sf

OFF

CAREER

118sf

OFF

CAREER

148sf

OFF

CAREER

198sf

OFF

CAREER

167sf

OFF

CAREER

103sf

OFF

CAREER

120sf

OF SV

CAREER

92sf

OF SV

CAREER

125sf

OFF

CAREER

72sf

OFF

CAREER

74sf

OFF

CAREER

74sf

OFF

CCE

1186sf

OF SV

CCE

170sf

OF SV

CCE

40sf

CONF

CCE

218sf

OFF

CCE

96sf

OFF

CCE

120sf

OFF

CCE

247sf

OFF

CCE

93sf

OFF

CCE

93sf

OFF

CCE

93sf

OFF

CCE

93sf

OFF

CCE

93sf

OFF

CCE

96sf

OFF

CCE

90sf

OFF

CCE

68sf

OFF

CCE

84sf

OFF

CCE

84sf

OF SV

CCE

66sf

OF SV

CCE

62sf

OF SV

CCE

33sf

OF SV

CCE

56sf

OFF

CCE

127sf

OFF

CCE

96sf

OFF

CCE

127sf

OFF

PROV

525sf

OF SV

PROV

31sf

OP LAB

CLASS

799sf

CORR

PLANT

576sf

OFF

CCE

253sf

OF SV

CCE

31sf

OFF

CCE

68sf

OP LAB

CLASS

92sf

OFF

CCE

80sf

OFF

CCE

80sf

CCE

83sf

CCE

83sf

OF SV

CCE

206sf

OF SV

CAREER

63sf

OFF

CLASS

448sf

310

310A

310D

310C

300S1

311

311A

315A

302

300L2

317

321A

309

308B

308A

310B

311B

314

312

300S2

320A

320B

300C3

300L1

300C4

313

315

319

310E

308

300C5

328

328L

328K

328J

328I

328H

328G

328F

328E

328D

328C

328B

328A

324

326

326A

326B

326C

303

303A

303B

303C

303D

303E

303F

303G

303H

303I

303J

303K

303L

303M

303N

303P

303Q

303R

303S

301E

301A

301B

301C

301D

320

320C

321

300C1

301

301F

330O

321B

304A

304B

304

326D

310

310

UP

DN

DN

UP

UP

UP

DN

DN

DN

STAIRPLANT

223sf

ELEVPLANT

37sf

OFF

180sf

OFFMGMT

215sf

OFFMGMT

225sf

CORRPLANT

323sf

OFFSOB ORG

463sf

OFFSOB ORG

160sf

OFFSOB ORG

205sf

OFFSOB ORG

1096sf

OFFSOB ORG

216sf

CORRPLANT

349sf

OFFMGMT

166sf

OFFMGMT

152sf

OFFMGMT

151sf

OFFMGMT

152sf

WOMENPLANT

141sf

OFFMGMT

244sf

CORRPLANT

289sf

OFFSOB ORG

340sf

U/MPLANT

44sf

CF SVMGMT

49sf

CL SVMGMT

48sf

CLASSREG

878sf

CORRPLANT

439sf

OFFMGMT

163sf

OFFMGMT

230sf

OF SVMGMT

113sf

OFFMGMT

214sf

CSPLANT

74sf

CLASSREG

1797sf

CONFMGMT

682sf

CF SVSOB ORG

15sf

CF SVSOB ORG

33sf

CONFSOB ORG

342sf U/MPLANT

14sf

300 302 304

300C1

303

303A

305H

305

305F

300C3

316314312310

306

308

300C2

305E

309A

307A

307

300C4

318 320 322 324

326

301

309

305B

300S1

300E1

300 302 304

300C1

303

303A 305H

305

305F

300C3

316314312310306

308

300C2

305E

309A309B307A

307

300C4

318 320 322 324 326

301 309

305C

305D

305B

305G

DN

OFF

CHEM E

180sf

OFF

CHEM E

193sf

RS LAB

CHEM E

543sf

RS LAB

CHEM E

148sf

SHFT

PLANT

22sf

302

304

301

301A

301B

FD

VD

VDVDVD

VD

VDVD

VD

VD

VD

VD

VD

VD VD

FSD

FSD

FSD

FSD

VD

FDFD

FD

VDVD

VD

VD

VD

VD

VDVD

VD

FD

VDVD

CORR.

2

A

B

4

D

E

51 1.5

1' 2' 3'

A'

B'

C'

3

C

A.5

C.5

0.5

M-7041

M-7111

6" FLUE UP & DN

ARCHITECT

CONSULTANT

STAMP

MARK DATE DESCRIPTION

PROJECT NUMBER:DRAWN BY:CHECKED BY:

SHEET TITLE

100% CONSTRUCTIONDOCUMENT SET

(UMBA 13-L2)

www.arup.com

955 Massachusetts Avenue4th Floor

Cambridge, MA 02139T 617 864 2987 F 617 864 6178

Arup USA Inc

7/20

/201

5 3:

01:5

8 PM

M-405

MECHANICAL LEVEL 3- KEY PLAN

UMass Lowell NorthQuad Infrastructure

Renewal

21332

Lowell, MA

University of Massachusetts Building AuthorityUniversity of Massachusetts Lowell

--

1/16" = 1'-0"1 MECHANICAL - KEY PLAN - LEVEL 3

1 06/10/14 FEASIBILITY STUDY SET2 08/29/14 SCHEMATIC DESIGN SET3 12/18/14 50% DESIGN DEVELOPMENT SET4 01/15/15 100% DESIGN DEVELOPMENT SET5 04/06/15 60% CONSTRUCTION PERMIT SET6 05/07/15 90% CONSTRUCT. DOC. SET7 06/30/15 TIER 1 PHASE 1 PERMIT SET8 07/17/15 100% CONSTRUCT. DOC. SET

Page 49: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

DN

DN

UP

DN

CLASSREG

454sf

CLASSREG

520sf

OFFMGMT

278sf

JCPLANT

14sf

CLASSREG

769sf

STAIRPLANT

233sf

ELEVPLANT

37sf

CLASSREG

531sf

CORRPLANT

278sf

CORRPLANT

154sf

CLASSREG

758sf

OFFMGMT

181sf

CORRPLANT

649sf

OFFMGMT

225sf

CLASSREG

1100sf

CLASSREG

973sf

CLASSMGMT

439sf

CLASSREG

415sf

OFFENGLISH

135sf

OFFENGLISH

102sf

OFFENGLISH

110sf

CORRPLANT

619sf

CLASSREG

499sf

CLASSREG

660sf

400 401 403

406A

406

400S1

400E1404

400C2400C1

408 410

400C3

409407405

411 413

416

415

414

400C4

417412

ROOF

ROOF

JCPLANT

17sf

STAIR

PLANT

395sf

CL SV

REG

14sfJCPLANT

6sf

CLASS

REG

651sf

CLASS

REG

642sf

STAIR

PLANT

393sf

CORR

PLANT

643sf

CLASS

REG

1094sf

CLASS

REG

804sf

CLASS

REG

816sf

CLASS

REG

1012sf

408

400S2

402B

402C

404

402

400S1

400C1

407

405

403

401

DN

DN

VD

VDVDVD

VD

VDVD

VD

VD

FSDFSD

FSD

FSD

FSD

FSD

FD

FD

FD

VD

VD

CORR.

2

A

B

4

D

E

51 1.5

1' 2' 3'

A'

B'

C'

3

C

A.5

C.5

0.5

M-7051

M-7121

6" GENERATOR FLUETERMINATE MIN. 10'-0"ABOVE ROOF LEVEL

ARCHITECT

CONSULTANT

STAMP

MARK DATE DESCRIPTION

PROJECT NUMBER:DRAWN BY:CHECKED BY:

SHEET TITLE

100% CONSTRUCTIONDOCUMENT SET

(UMBA 13-L2)

www.arup.com

955 Massachusetts Avenue4th Floor

Cambridge, MA 02139T 617 864 2987 F 617 864 6178

Arup USA Inc

7/20

/201

5 3:

02:0

4 PM

M-406

MECHANICAL LEVEL 4- KEY PLAN

UMass Lowell NorthQuad Infrastructure

Renewal

21332

Lowell, MA

University of Massachusetts Building AuthorityUniversity of Massachusetts Lowell

--

1/16" = 1'-0"1 MECHANICAL - KEY PLAN - LEVEL 4

1 06/10/14 FEASIBILITY STUDY SET2 08/29/14 SCHEMATIC DESIGN SET3 12/18/14 50% DESIGN DEVELOPMENT SET4 01/15/15 100% DESIGN DEVELOPMENT SET5 04/06/15 60% CONSTRUCTION PERMIT SET6 05/07/15 90% CONSTRUCT. DOC. SET7 06/30/15 TIER 1 PHASE 1 PERMIT SET8 07/17/15 100% CONSTRUCT. DOC. SET

Page 50: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

ELEVPLANT

107.41sf

CORRPLANT

822.08sf

100E1

100C6

FD

FD

FSD

FSD

FD

FD

STD MWC171

STD WWC170

NEW PRIM. ELEC.172

NEW EMER. ELEC.172A

IDF/IT174

ELEC173

CORR.100C6

ELEV LOBBY1L1

ACCESS TOKITSON MEZZ 2

100S3

A'

B'

12"x8" SA

8"ø

SA

8x4 SA

8"x6

" SA

8"x6

" SA

8"x4" SA

CD-1(100)

CD-2(200)

CD-1(100)

CD-2(200)

12"x8

" EA

8"x6" EA8"ø EA

EG-1(150)

EG-1(150)

AC3-1

AC3-2

AC2-1

CUH2

12"x8" SA UP12"x8" EA UP

RHG UP(TYP 2)

RL UP(TYP 2)

VAV6

T

T

T

T

EF2-2

EF2-1

W/WMS10"x10" EA(150)

10"x10" EA(150)

2" CD

3/4" CD 1 1/4" CD

2" CD DN

10"x10" EA(150)

10"x10" EAW/WMS

W/WMS

UC

UC

TG-1

TG-1

6" FLUE UP

6" FLUE FROMGENERATOR

T

W/WMS

ARCHITECT

CONSULTANT

STAMP

MARK DATE DESCRIPTION

PROJECT NUMBER:DRAWN BY:CHECKED BY:

SHEET TITLE

100% CONSTRUCTIONDOCUMENT SET

(UMBA 13-L2)

www.arup.com

955 Massachusetts Avenue4th Floor

Cambridge, MA 02139T 617 864 2987 F 617 864 6178

Arup USA Inc

7/20

/201

5 3:

02:3

4 PM

M-708

MECHANICAL POD 2ENLARGED FLOOR

PLANS - LEVEL 1

UMass Lowell NorthQuad Infrastructure

Renewal

21332

Lowell, MA

University of Massachusetts Building AuthorityUniversity of Massachusetts Lowell

--

1/4" = 1'-0"1 MECHANICAL - LEVEL 1 ENLARGED PLAN (POD 2)

1 06/10/14 FEASIBILITY STUDY SET2 08/29/14 SCHEMATIC DESIGN SET3 12/18/14 50% DESIGN DEVELOPMENT SET4 01/15/15 100% DESIGN DEVELOPMENT SET5 04/06/15 60% CONSTRUCTION PERMIT SET6 05/07/15 90% CONSTRUCT. DOC. SET7 06/30/15 TIER 1 PHASE 1 PERMIT SET8 07/17/15 100% CONSTRUCT. DOC. SET

Page 51: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

36sf

OF SV

431sf

200E1

201

FD

FSD

FSD

FD

CORR.200C4

IDF/IT270

EE271A

ELEC.271

JC272

STD MWC274

STF WWC273

STF MWC276

STD WWC275

1' 2' 3'

A'

B'

C'

12"x8" EA DN12"x8" SA DN

12"x8

" EA

12"x8

" SA

12"x8" SA

12"x8" EA

14"x8

" SA

10"x8" SA

8"x6

" SA

6"ø SA

10"x8

" SA

6"ø SA6"ø SA

CD-2(150)

CD-2(150)

CD-1(100)

CD-2(150)

EG-2(150)

EG-2(200)

EG-2(200)

8"ø EA

8"ø EA

6"x6" EA4"

ø EA

EG-1(50)

14"x8

" EA6"ø EA

EG-1(50)

EF2-3

AC2-2

VAV7 14"x12" EA UP

12"x12" SA UP

3/4" CD

3/4" CDDISCHARGE OVER JANITORS

SINK

RHG DN(TYP 2)

RL DN(TYP 2)

TT

T

T

1 1/2" CD UP2" LPS UP

RL UP(TYP 2)

RHG UP(TYP 2)

6"ø FL UP&DN

EG-1(150)

8"x8

"

UC UC

TG-1

8"x6

" SA

CD-2(150)

ARCHITECT

CONSULTANT

STAMP

MARK DATE DESCRIPTION

PROJECT NUMBER:DRAWN BY:CHECKED BY:

SHEET TITLE

100% CONSTRUCTIONDOCUMENT SET

(UMBA 13-L2)

www.arup.com

955 Massachusetts Avenue4th Floor

Cambridge, MA 02139T 617 864 2987 F 617 864 6178

Arup USA Inc

7/20

/201

5 3:

02:3

7 PM

M-710

MECHANICAL POD 2ENLARGED FLOOR

PLANS - LEVEL 2

UMass Lowell NorthQuad Infrastructure

Renewal

21332

Lowell, MA

University of Massachusetts Building AuthorityUniversity of Massachusetts Lowell

--

1/4" = 1'-0"1 MECHANICAL - KITSON MEZZ

1 06/10/14 FEASIBILITY STUDY SET2 08/29/14 SCHEMATIC DESIGN SET3 12/18/14 50% DESIGN DEVELOPMENT SET4 01/15/15 100% DESIGN DEVELOPMENT SET5 04/06/15 60% CONSTRUCTION PERMIT SET6 05/07/15 90% CONSTRUCT. DOC. SET7 06/30/15 TIER 1 PHASE 1 PERMIT SET8 07/17/15 100% CONSTRUCT. DOC. SET

Page 52: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

WOMEN

PLANT

404.45sf

CONF

DN ENGR

702.64sf

300A

300

OFFDN ENGR

198sf

OF SVDN ENGR

201sf

CORRPLANT

942sf

ELEVPLANT

107sf

CONFDN ENGR

220sf

OFFDN ENGR

300sf

OF SVDN ENGR

20sf

OFFDN ENGR

892sf

313A313

300C6

300E1 311B 311A

311C

311

FD

FSD

FSD

VDVD

VD

VD

VD

VD

VD

VD

VD

FD

VD

CORR.300C4

IDF/IT370

EE371A

ELEC.371

JC372

STF WWC376

STF MWC373

STD MWC374

STD WWC375

1' 2' 3'

A'

B'

C'8"

x6" S

A

6"ø SA6"ø SACD-2(150)

CD-2(150)

CD-2(100)

EG-2(150)

EG-2(200)

EG-2(200)

6"x6" EA

4ø EA

EG-1(50)

6"ø EA

EG-1(50)

EF2-4

AC2-3

VAV8

8"ø SA

14"x8

" EA

16"x16" EA UP

16"x16" SA UP

14"x12" EA DN

12"x12" SA DN1 1/2" CD DN2" LPS DN

3/4" CD

6ø SA

12"x8

" SA

1 1/2" CD UP2" LPS UP

T

T

T

T

8ø EA

8"x8

" EA

8ø EA

CD-2(150)

14"x8" SA

6x6 EA

UCUC

TG-1

RG-1(150)

6" FLUE UP & DN

0' - 7"

CD-2(150)

ARCHITECT

CONSULTANT

STAMP

MARK DATE DESCRIPTION

PROJECT NUMBER:DRAWN BY:CHECKED BY:

SHEET TITLE

100% CONSTRUCTIONDOCUMENT SET

(UMBA 13-L2)

www.arup.com

955 Massachusetts Avenue4th Floor

Cambridge, MA 02139T 617 864 2987 F 617 864 6178

Arup USA Inc

7/20

/201

5 3:

02:4

1 PM

M-711

MECHANICAL POD 2ENLARGED FLOOR

PLANS - LEVEL 3

UMass Lowell NorthQuad Infrastructure

Renewal

21332

Lowell, MA

University of Massachusetts Building AuthorityUniversity of Massachusetts Lowell

--

1/4" = 1'-0"1 MECHANICAL - LEVEL 3 ENLARGED PLAN (POD 2)

1 06/10/14 FEASIBILITY STUDY SET2 08/29/14 SCHEMATIC DESIGN SET3 12/18/14 50% DESIGN DEVELOPMENT SET4 01/15/15 100% DESIGN DEVELOPMENT SET5 04/06/15 60% CONSTRUCTION PERMIT SET6 05/07/15 90% CONSTRUCT. DOC. SET7 06/30/15 TIER 1 PHASE 1 PERMIT SET8 07/17/15 100% CONSTRUCT. DOC. SET

Page 53: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

1' 2' 3'

A'

B'

C'

ACCU3

ACCU2

RTU2

16"x16" EA

16"x16" SA

1 1/2" CD DN2" LPS DN

RHG UP(TYP 2)RL UP(TYP 2)

SA-4

SA-3

ARCHITECT

CONSULTANT

STAMP

MARK DATE DESCRIPTION

PROJECT NUMBER:DRAWN BY:CHECKED BY:

SHEET TITLE

100% CONSTRUCTIONDOCUMENT SET

(UMBA 13-L2)

www.arup.com

955 Massachusetts Avenue4th Floor

Cambridge, MA 02139T 617 864 2987 F 617 864 6178

Arup USA Inc

7/20

/201

5 3:

02:4

3 PM

M-712

MECHANICAL POD 2ENLARGED FLOOR

PLANS - ROOF

UMass Lowell NorthQuad Infrastructure

Renewal

21332

Lowell, MA

University of Massachusetts Building AuthorityUniversity of Massachusetts Lowell

--

1/4" = 1'-0"1 MECHANICAL - ROOF ENLARGED PLAN (POD 2)

1 06/10/14 FEASIBILITY STUDY SET2 08/29/14 SCHEMATIC DESIGN SET3 12/18/14 50% DESIGN DEVELOPMENT SET4 01/15/15 100% DESIGN DEVELOPMENT SET5 04/06/15 60% CONSTRUCTION PERMIT SET6 05/07/15 90% CONSTRUCT. DOC. SET7 06/30/15 TIER 1 PHASE 1 PERMIT SET8 07/17/15 100% CONSTRUCT. DOC. SET

Page 54: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

VB

VB

5 SINGLE STEAM COIL CONNECTION DETAIL

1 TYPICAL DIFFUSER TAKE-OFF DETAIL

6 INLINE EXHAUST FANDETAIL

DUCT PENETRATION GOOSENECKTERMINATION DETAIL

DUCT THROUGH ROOF DETAIL

MIN.

24"

H

C

F T

LPS MAIN

HEATING COIL

CONDENSATE RETURN MAIN

10" M

IN

6" M

IN

6" MIN

DI-ELECTRIC CONNECTIONIF REQUIRED

TF

KEY NOTES:1. INSULATED FLEXIBLE DUCT - SHALL BE PRE-STRETCHED BEFORE INSTALLATION LENGTH NOT TO EXCEED 5 FEET. DIAMETER TO BE EQUAL TO DIFFUSER INLET SIZE.

2. SUPPORT FLEX DUCT SUCH THAT R=D/2 MIN.

MIN. L

D

R

150mm MIN.

DRAWBAND CONNECTION(TYP)

VOLUME DAMPER WITHLOCKING QUADRANT

"MINI" BELLMOUTH FITTING

DUCT

CEILING

OPPOSED BLADE DAMPER

PLENUM TRANS. FROMROUND TO SQUARECONNECTION.

TYPICAL CEILINGDIFFUSER

ADJUSTMENT HANDLE

DUCT TRANSITION

FLOWAIR

FLEXIBLECONNECTION

THREADED ROD

FAN SUSPENSIONBRACKET

15° MAX(TYP)

BELT-DRIVEMOTOR

EXHAUST FAN(INLINE TYPE)

ALTERNATE HANGINGLOCATION WITH 2"x 3

4" CHANNELOR UNISTRUT SUPPORT

THREADED HANGER ROD UPTO STRUCTURE

INTERMEDIATEUNISTRUT IF FAN ISBELOW FINISHEDCEILING

PROVIDE ANGLE SUPPORT BETWEENSTRUCTURAL MEMBERS. SAME AS PERDUCTWORK DETAIL (OVER 60" SIZE)

NUTS W/LOCKWASHERSTYP. OF BOTH SIDES

SPRING VIBRATIONISOLATOR- REFER TOSPECIFICATIONS FORSTATIC DEFLECTIONREQUIREMENTS (TYP 4)

NOTES:

1. PROVIDE ACCESS PANEL IN HARD CEILING LOCATIONS FOR FAN, MOTOR AND BACKDRAFT DAMPER ACCESS.

2. PROVIDE ADEQUATE SERVICE SPACE AROUND FAN FOR FAN REMOVAL MOTOR, BELT & DRIVE ACCESS.

3. PROVIDE MINIMUM 3 DUCT DIAMETERS OF STRAIGHT DUCT ON INLET AND OUTLET OF FAN.

(WHERE SCHEDULED)

TO SUPPORT BEAM2"x2"x1/4" ANGLE WELDED

BACK DRAFT DAMPEREXHAUST DUCT

ATTACH ANGLE TO PLENUM WITHSHEET METAL SCREWS AT 10" O.C.

ROOF CURB

1/2 D

R = 1/2 D

DFLASHING. SEE ARCHITECTURALDRAWINGS FOR DETAILS.

SCREENEDINLET

AIR DUCT FOR SIZESSEE FLOOR PLAN

LAG SCREWS

CURBED ROOF OPENINGBY GENERAL CONTR.SEE PLANS FOR SIZES

1/2" MIN. CLEAR ALL AROUND

DUCT LINING WHERE INDICATED

BY MECHANICAL CONTR.

ROOF

20 GAGE SHEETMETAL FLASHING SHEET 3" MIN.

STANDING SEAM

3" MINIMUM

MASTIC SEALANT

KEY NOTES:1. FABRICATE IN ACCORDANCE WITH SMACNA LOW PRESSURE DUCT CONSTRUCTION STANDARDSOF MINIMUM 18 GAGE GALVANIZED STEEL.2. MOUNT ON MINIMUM 12 INCH HIGH CURB BASE WHERE SIZE EXCEEDS 9" X 9".3. ANGLE OF OPENING SHALL BE NO GREATER THAN 45° FROM THE HORIZONTAL.

PROVIDE WEATHER/STORMCOLLAR

45°

8

4

1

2 TRANSFER DUCT DETAIL

PI

UP TO 400

601 TO 800

401 TO 600

801 TO 1000

1001 TO 1500

OVER 2000

* UNLESS OTHERWISE NOTED

1501 TO 2000

SIZING CHART

TD-4

TD-6

TD-5

TD-3

TD-1

TD-2

MARK CFM

20" OR 30x12

28" OR 34x20

24" OR 30x16

USE MULT TRD'S

SIZE (IN)

14" OR 12x12

18" OR 24x12

16" OR 18x12

*

9"

5'-8" MIN.

W

DUCT WITH 1" ACOUSTICALLINING, SIZE AS NOTED ONCHART UNLESS OTHERWISENOTED ON PLAN

FULL HEIGHTACOUSTIC PARTITION

SEAL, ALL SIDES

UNVANED ELBOW (TYP. 2)

ROOF

MIN.10'-0" ABOVEROOF

GUY WIRE

DISCHARGE FROMGENERATOR W/RAINCAP

3 GENERATOR FLUE ROOF INSTALLATION DETAIL

7 ELEVATOR VENT PENTHOUSE

DAMPER ACTUATOROCI UNIT

1/8" ANNEALED CLEAR GLASS

1" THK INSULATION

SMOKE DAMPERCLASS 1 LEAKAGE

4" MOUNTINGFLANGE

DAMPER TRAY

ARCHITECT

CONSULTANT

STAMP

MARK DATE DESCRIPTION

PROJECT NUMBER:DRAWN BY:CHECKED BY:

SHEET TITLE

100% CONSTRUCTIONDOCUMENT SET

(UMBA 13-L2)

www.arup.com

955 Massachusetts Avenue4th Floor

Cambridge, MA 02139T 617 864 2987 F 617 864 6178

Arup USA Inc

7/20

/201

5 3:

02:4

7 PM

M-803

MECHANICAL DETAILSSHEET 3

UMass Lowell NorthQuad Infrastructure

Renewal

21332

Lowell, MA

University of Massachusetts Building AuthorityUniversity of Massachusetts Lowell

--

1 06/10/14 FEASIBILITY STUDY SET2 08/29/14 SCHEMATIC DESIGN SET3 12/18/14 50% DESIGN DEVELOPMENT SET4 01/15/15 100% DESIGN DEVELOPMENT SET5 04/06/15 60% CONSTRUCTION PERMIT SET6 05/07/15 90% CONSTRUCT. DOC. SET7 06/30/15 TIER 1 PHASE 1 PERMIT SET8 07/17/15 100% CONSTRUCT. DOC. SET

Page 55: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

D

DAIN

WALL SUPPORT

WALL GUIDE

EXPANSION BELLOWS

WALL SUPPORT

FLEXIBLE

GENERATOR STEEL HOUSING

GENERATOR EXHAUST SILENCER

FLUE EXHAUST

FALMOUTH HALL

SEE M8.03 DETAIL #4 FORFLUE PIPE ROOF SUPPORT

CONCRETE PAD

SUPPORT

ROOF

GENERATOR FLUE

GENERATOR FLUE

CONNECTION

ARCHITECT

CONSULTANT

STAMP

MARK DATE DESCRIPTION

PROJECT NUMBER:DRAWN BY:CHECKED BY:

SHEET TITLE

100% CONSTRUCTIONDOCUMENT SET

(UMBA 13-L2)

www.arup.com

955 Massachusetts Avenue4th Floor

Cambridge, MA 02139T 617 864 2987 F 617 864 6178

Arup USA Inc

7/20

/201

5 3:

15:2

0 PM

M-804

MECHANNICALDETAILS SHEET 4

UMass Lowell NorthQuad Infrastructure

Renewal

21332

Lowell, MA

University of Massachusetts Building AuthorityUniversity of Massachusetts Lowell

--

1 06/10/14 FEASIBILITY STUDY SET2 08/29/14 SCHEMATIC DESIGN SET3 12/18/14 50% DESIGN DEVELOPMENT SET4 01/15/15 100% DESIGN DEVELOPMENT SET5 04/06/15 60% CONSTRUCTION PERMIT SET6 05/07/15 90% CONSTRUCT. DOC. SET7 06/30/15 TIER 1 PHASE 1 PERMIT SET8 07/17/15 100% CONSTRUCT. DOC. SET

NTS1 GENERATOR FLUE ELEVATION

Page 56: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

North Quad Infrastructure Renewal ICON architecture, inc.

UMass Lowell, Lowell, MA July 17, 2015

UMBA Project No. UMBA 13-L2

INSTALLATION OF ENGINE GENERATORS 263214 - 1

(Part of Work of Section 260002 – ELECTRICAL, Trade Bid Required)

SECTION 263214 – INSTALLATION OF ENGINE GENERATORS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary

Conditions and Division 01 Specification Sections, apply to this Section.

B. UMass Lowell Campus Electrical Standards; request most up to date standards at time of bid.

1.2 SUMMARY

A. This Section includes installation of packaged engine-generator sets for [emergency] power

supply with the following features:

1. [Diesel] engine.

2. [Unit-mounted] cooling system.

3. [Unit-mounted] control and monitoring.

4. Load banks.

5. Outdoor enclosure.

B. Related Sections include the following:

1. Section 263213 “Engine Generators” for owner furnished contractor installed generator

equipment requirements.

2. Section 263600 "Transfer Switches" for transfer switches including sensors and relays to

initiate automatic-starting and -stopping signals for engine-generator sets.

1.3 DEFINITIONS

A. Operational Bandwidth: The total variation from the lowest to highest value of a parameter

over the range of conditions indicated, expressed as a percentage of the nominal value of the

parameter.

B. LP: Liquid petroleum.

Page 57: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

North Quad Infrastructure Renewal ICON architecture, inc.

UMass Lowell, Lowell, MA July 17, 2015

UMBA Project No. UMBA 13-L2

INSTALLATION OF ENGINE GENERATORS 263214 - 2

1.4 CLOSEOUT SUBMITTALS

A. Operation and Maintenance Data: For packaged engine generators to include in emergency,

operation, and maintenance manuals. In addition to items specified in Section 011000

"Operation and Maintenance Data," include the following:

1. List of tools and replacement items recommended to be stored at Project for ready access.

Include part and drawing numbers, current unit prices, and source of supply.

1.5 QUALITY ASSURANCE

A. Installer Qualifications: Manufacturer's authorized representative who is trained and approved

for installation of units required for this Project.

1. Maintenance Proximity: Not more than [four] hours' normal travel time from Installer's

place of business to Project site.

2. Engineering Responsibility: Preparation of data for vibration isolators restraints of

engine skid mounts, including Shop Drawings, based on testing and engineering analysis

of manufacturer's standard units in assemblies similar to those indicated for this Project.

B. Manufacturer Qualifications: A qualified manufacturer. Maintain, within [200 miles (321 km)]

of Project site, a service center capable of providing training, parts, and emergency maintenance

repairs.

C. Source Limitations: Obtain packaged generator sets and auxiliary components through one

source from a single manufacturer.

D. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,

Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for

intended use.

E. Comply with ASME B15.1.

F. Comply with NFPA 37.

G. Comply with NFPA 70.

H. Comply with NFPA 110 requirements for Level [1] emergency power supply system.

I. Comply with UL 2200.

1.6 PROJECT CONDITIONS

A. Interruption of Existing Electrical Service: Do not interrupt electrical service to facilities

occupied by Owner or others unless permitted under the following conditions and then only

after arranging to provide temporary electrical service according to requirements indicated:

Page 58: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

North Quad Infrastructure Renewal ICON architecture, inc.

UMass Lowell, Lowell, MA July 17, 2015

UMBA Project No. UMBA 13-L2

INSTALLATION OF ENGINE GENERATORS 263214 - 3

1. Notify [Construction Manager] no fewer than [seven] days in advance of proposed

interruption of electrical service.

2. Do not proceed with interruption of electrical service without [Construction Manager's]

written permission.

B. Environmental Conditions: Engine-generator system shall withstand the following

environmental conditions without mechanical or electrical damage or degradation of

performance capability:

1. Altitude: Sea level to [1000 feet (300 m)]

1.7 COORDINATION

A. Coordinate size and location of concrete bases for package engine generators. Cast anchor-bolt

inserts into bases. Concrete, reinforcement, and formwork requirements are specified with

concrete.

1.8 WARRANTY

A. Special Warranty: Generator is pre purchased and comes with a 2 year warranty. All work

carried out under this section shall be warrantied as per the general conditions of the project.

1.9 MAINTENANCE SERVICE

A. Generator unit comes with 24 months maintenance contract. Engage the maintenance contractor

at the end of installation to carry out all required maintenance.

PART 2 - PRODUCTS

2.1 Generator shall be owner furnished, contractor installed. Unit shall be 200kW, diesel fueled

with level II acoustic weatherproof enclosure. Coordinate all information with the construction

manager.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Formally receive pre purchased generator. Engage the generator manufacturer to perform pre

start up checks on the unit prior to accepting for installation. Once accepted, store and handle

unit as detailed in part 3 of this specification.

B. Examine areas, equipment bases, and conditions, with Installer present, for compliance with

requirements for installation and other conditions affecting packaged engine-generator

performance.

Page 59: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

North Quad Infrastructure Renewal ICON architecture, inc.

UMass Lowell, Lowell, MA July 17, 2015

UMBA Project No. UMBA 13-L2

INSTALLATION OF ENGINE GENERATORS 263214 - 4

C. Examine roughing-in of piping systems and electrical connections. Verify actual locations of

connections before packaged engine-generator installation.

D. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 INSTALLATION

A. Comply with packaged engine-generator manufacturers' written installation and alignment

instructions and with NFPA 110.

B. Install packaged engine generator to provide access, without removing connections or

accessories, for periodic maintenance.

C. Install packaged engine generator on cast-in-place concrete equipment bases. Comply with

requirements for equipment bases and foundations specified in [Section 033000 "Cast-in-Place

Concrete."] [Section 033053 "Miscellaneous Cast-in-Place Concrete."]

1. Comply with requirements for vibration isolation devices specified in this section.

D. Install Schedule 40, black steel piping with welded joints and connect to engine muffler. Install

thimble at wall. Piping shall be same diameter as muffler outlet. Flexible connectors and steel

piping materials and installation requirements are specified in Section 232116 Hydronic Piping

Specialties."

1. Install condensate drain piping to muffler drain outlet full size of drain connection with a

shutoff valve, stainless-steel flexible connector, and Schedule 40, black steel pipe with

welded joints. Flexible connectors and piping materials and installation requirements are

specified in Section 232116 Hydronic Piping Specialties."

E. Electrical Wiring: Install electrical devices furnished by equipment manufacturers but not

specified to be factory mounted.

3.3 CONNECTIONS

A. Piping installation requirements are specified in other Sections. Drawings indicate general

arrangement of piping and specialties.

B. Connect fuel, cooling-system, and exhaust-system piping adjacent to packaged engine generator

to allow service and maintenance. Coordinate extended generator flue with flue installer.

Generator flue shall discharge 10’ above roof level.

C. Connect engine exhaust pipe to engine with flexible connector.

D. Connect fuel piping to engines with a gate valve and union and flexible connector.

E. Ground equipment according to Section 260526 "Grounding and Bonding for Electrical

Systems." Generator shall be a separately derived power source.

Page 60: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

North Quad Infrastructure Renewal ICON architecture, inc.

UMass Lowell, Lowell, MA July 17, 2015

UMBA Project No. UMBA 13-L2

INSTALLATION OF ENGINE GENERATORS 263214 - 5

F. Connect wiring according to Section 260519 "Low-Voltage Electrical Power Conductors and

Cables."

3.4 IDENTIFICATION

A. Identify system components according to Section 230553 "Identification for HVAC Piping and

Equipment" and Section 260553 "Identification for Electrical Systems."

3.5 FIELD QUALITY CONTROL

A. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect,

test, and adjust components, assemblies, and equipment installations, including connections.

Report results in writing.

B. Perform tests and inspections and prepare test reports.

1. Manufacturer's Field Service: Engage a factory-authorized service representative to

inspect components, assemblies, and equipment installations, including connections, and

to assist in testing.

C. Tests and Inspections:

1. NFPA 110 Acceptance Tests: Perform tests required by NFPA 110 that are additional to

those specified here including, but not limited to, single-step full-load pickup test.

2. Battery Tests: Equalize charging of battery cells according to manufacturer's written

instructions. Record individual cell voltages.

a. Measure charging voltage and voltages between available battery terminals for

full-charging and float-charging conditions. Check electrolyte level and specific

gravity under both conditions.

b. Test for contact integrity of all connectors. Perform an integrity load test and a

capacity load test for the battery.

c. Verify acceptance of charge for each element of the battery after discharge.

d. Verify that measurements are within manufacturer's specifications.

3. Battery-Charger Tests: Verify specified rates of charge for both equalizing and float-

charging conditions.

4. System Integrity Tests: Methodically verify proper installation, connection, and integrity

of each element of engine-generator system before and during system operation. Check

for air, exhaust, and fluid leaks.

5. Exhaust-System Back-Pressure Test: Use a manometer with a scale exceeding 40-inch

wg (120 kPa). Connect to exhaust line close to engine exhaust manifold. Verify that

back pressure at full-rated load is within manufacturer's written allowable limits for the

engine.

6. Exhaust Emissions Test: Comply with applicable government test criteria.

D. Coordinate tests with tests for transfer switches and run them concurrently.

Page 61: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

North Quad Infrastructure Renewal ICON architecture, inc.

UMass Lowell, Lowell, MA July 17, 2015

UMBA Project No. UMBA 13-L2

INSTALLATION OF ENGINE GENERATORS 263214 - 6

E. Test instruments shall have been calibrated within the last 12 months, traceable to standards of

NIST, and adequate for making positive observation of test results. Make calibration records

available for examination on request.

F. Leak Test: After installation, charge system and test for leaks. Repair leaks and retest until no

leaks exist.

G. Operational Test: After electrical circuitry has been energized, start units to confirm proper

motor rotation and unit operation.

H. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and

equipment.

I. Remove and replace malfunctioning units and [retest] as specified above.

J. Retest: Correct deficiencies identified by tests and observations and retest until specified

requirements are met.

K. Report results of tests and inspections in writing. Record adjustable relay settings and measured

insulation resistances, time delays, and other values and observations. Attach a label or tag to

each tested component indicating satisfactory completion of tests.

L. Infrared Scanning: After Substantial Completion, but not more than 60 days after Final

Acceptance, perform an infrared scan of each power wiring termination and each bus

connection. Remove all access panels so terminations and connections are accessible to

portable scanner.

1. Follow-up Infrared Scanning: Perform an additional follow-up infrared scan 11 months

after date of Substantial Completion.

2. Instrument: Use an infrared scanning device designed to measure temperature or to

detect significant deviations from normal values. Provide calibration record for device.

3. Record of Infrared Scanning: Prepare a certified report that identifies terminations and

connections checked and that describes scanning results. Include notation of deficiencies

detected, remedial action taken, and observations after remedial action.

M. Output circuit breaker settings: Life safety power systems are to selectively coordinate to 0.01s.

Select and set generator main circuit breaker based on outcome from “26057 -

OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY”. Engage vendor for

information on circuit breaker to include in overcurrent protective study, and then follow up

with vendor to come to site and reset any circuit breaker settings, or generator controller settings

requiring adjustment prior to completion.

3.6 DEMONSTRATION

A. Engage a factory-authorized service representative to train Owner's maintenance personnel to

adjust, operate, and maintain packaged engine generators. Refer to Section 017900

"Demonstration and Training."

Page 62: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

North Quad Infrastructure Renewal ICON architecture, inc.

UMass Lowell, Lowell, MA July 17, 2015

UMBA Project No. UMBA 13-L2

INSTALLATION OF ENGINE GENERATORS 263214 - 7

3.7 FUEL

A. Provide all fuel required for testing.

B. Hand over generator system to owner after all acceptance testing is complete with all generator

fuel tanks fully filled.

END OF SECTION 263213

Page 63: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

North Quad Infrastructure Renewal ICON architecture, inc.

UMass Lowell, Lowell, MA July 17, 2015

UMBA Project No. UMBA 13-L2

TRANSFER SWITCHES 263600 - 1

SECTION 263600 - TRANSFER SWITCHES

(Part of Work of Section 260002 – ELECTRICAL, Trade Bid Required)

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary

Conditions and Division 01 Specification Sections, apply to this Section.

B. UMass Lowell Campus Electrical Standards; request most up to date standards at time of bid.

1.2 SUMMARY

A. Section includes transfer switches rated 600 V and less, including the following:

1. Automatic transfer switches.

2. Remote annunciation systems.

1.3 ACTION SUBMITTALS

A. Product Data: For each type of product indicated. Include rated capacities, weights, operating

characteristics, furnished specialties, and accessories.

B. Shop Drawings: Dimensioned plans, elevations, sections, and details showing minimum

clearances, conductor entry provisions, gutter space, installed features and devices, and material

lists for each switch specified.

1.4 INFORMATIONAL SUBMITTALS

A. Qualification Data: For [manufacturer].

1.5 CLOSEOUT SUBMITTALS

A. Operation and Maintenance Data: For each type of product to include in emergency, operation,

and maintenance manuals. In addition to items specified in Section 017823 "Operation and

Maintenance Data," include the following:

1. Features and operating sequences, both automatic and manual.

2. List of all factory settings of relays; provide relay-setting and calibration instructions,

including software, where applicable.

Page 64: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

North Quad Infrastructure Renewal ICON architecture, inc.

UMass Lowell, Lowell, MA July 17, 2015

UMBA Project No. UMBA 13-L2

TRANSFER SWITCHES 263600 - 2

1.6 QUALITY ASSURANCE

A. Manufacturer Qualifications: Maintain a service center capable of providing training, parts, and

emergency maintenance repairs within a response period of less than eight hours from time of

notification.

B. Testing Agency Qualifications: An independent agency, with the experience and capability to

conduct the testing indicated, that is a member company of the InterNational Electrical Testing

Association or is a nationally recognized testing laboratory (NRTL) as defined by OSHA in

29 CFR 1910.7, and that is acceptable to authorities having jurisdiction.

1. Testing Agency's Field Supervisor: Person currently certified by the InterNational

Electrical Testing Association or the National Institute for Certification in Engineering

Technologies to supervise on-site testing specified in Part 3.

C. Source Limitations: Obtain [automatic transfer switches] and [remote annunciators]

through one source from a single manufacturer.

D. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,

by a qualified testing agency, and marked for intended location and application.

E. Comply with NEMA ICS 1.

F. Comply with NFPA 70.

G. Comply with NFPA 110.

H. Comply with UL 1008 unless requirements of these Specifications are stricter.

1.7 FIELD CONDITIONS

A. Interruption of Existing Electrical Service: Do not interrupt electrical service to facilities

occupied by Owner or others unless permitted under the following conditions and then only

after arranging to provide temporary electrical service:

1. Notify [Construction Manager] no fewer than [seven] days in advance of proposed

interruption of electrical service.

2. Do not proceed with interruption of electrical service without [Construction Manager's]

written permission.

1.8 COORDINATION

A. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases. Concrete,

reinforcement, and formwork requirements are specified in Section 033000 "Cast-in-Place

Concrete."

Page 65: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

North Quad Infrastructure Renewal ICON architecture, inc.

UMass Lowell, Lowell, MA July 17, 2015

UMBA Project No. UMBA 13-L2

TRANSFER SWITCHES 263600 - 3

PART 2 - PRODUCTS

2.1 MANUFACTURED UNITS

A. Contactor Transfer Switches:

1. Manufacturers: Subject to compliance with requirements, [provide products by the

following]

a. AC Data Systems, Inc.

b. Caterpillar; Engine Div.

c. Emerson; ASCO Power Technologies, LP.

d. Generac Power Systems, Inc.

e. GE Zenith Controls.

f. Kohler Power Systems; Generator Division.

g. Onan/Cummins Power Generation; Industrial Business Group.

h. Russelectric, Inc.

i. Spectrum Detroit Diesel.

2.2 GENERAL TRANSFER-SWITCH PRODUCT REQUIREMENTS

A. Indicated Current Ratings: Apply as defined in UL 1008 for continuous loading and total

system transfer, including tungsten filament lamp loads not exceeding 30 percent of switch

ampere rating, unless otherwise indicated.

B. Tested Fault-Current Closing and Withstand Ratings: Adequate for duty imposed by protective

devices at installation locations in Project under the fault conditions indicated, based on testing

according to UL 1008.

C. Solid-State Controls: Repetitive accuracy of all settings shall be plus or minus 2 percent or

better over an operating temperature range of minus 20 to plus 70 deg C.

D. Resistance to Damage by Voltage Transients: Components shall meet or exceed voltage-surge

withstand capability requirements when tested according to IEEE C62.41. Components shall

meet or exceed voltage-impulse withstand test of NEMA ICS 1.

E. Electrical Operation: Accomplish by a nonfused, momentarily energized solenoid or electric-

motor-operated mechanism, mechanically and electrically interlocked in both directions.

F. Switch Characteristics: Designed for continuous-duty repetitive transfer of full-rated current

between active power sources.

1. Switch Action: Double throw; mechanically held in both directions.

2. Contacts: Silver composition or silver alloy for load-current switching. Conventional

automatic transfer-switch units, rated 225 A and higher, shall have separate arcing

contacts.

G. Neutral Switching. Where four-pole switches are indicated, provide [neutral pole switched

simultaneously with phase poles].

Page 66: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

North Quad Infrastructure Renewal ICON architecture, inc.

UMass Lowell, Lowell, MA July 17, 2015

UMBA Project No. UMBA 13-L2

TRANSFER SWITCHES 263600 - 4

H. Annunciation, Control, and Programming Interface Components: Devices at transfer switches

for communicating with remote programming devices, annunciators, or annunciator and control

panels shall have communication capability matched with remote device.

I. Factory Wiring: Train and bundle factory wiring and label, consistent with Shop Drawings,

either by color-code or by numbered or lettered wire and cable tape markers at terminations.

Color-coding and wire and cable tape markers are specified in Section 260553 "Identification

for Electrical Systems."

1. Designated Terminals: Pressure type, suitable for types and sizes of field wiring

indicated.

2. Power-Terminal Arrangement and Field-Wiring Space: Suitable for top, side, or bottom

entrance of feeder conductors as indicated.

3. Control Wiring: Equipped with lugs suitable for connection to terminal strips.

J. Enclosures: General-purpose NEMA 250, Type [1] complying with NEMA ICS 6 and UL 508,

unless otherwise indicated.

2.3 AUTOMATIC TRANSFER SWITCHES

A. Comply with Level 1 equipment according to NFPA 110.

B. Switching Arrangement: Double-throw type, incapable of pauses or intermediate position stops

during normal functioning, unless otherwise indicated.

C. Manual Switch Operation: Under load, with door closed and with either or both sources

energized. Transfer time is same as for electrical operation. Control circuit automatically

disconnects from electrical operator during manual operation.

D. Manual Switch Operation: Unloaded. Control circuit automatically disconnects from electrical

operator during manual operation.

E. Signal-Before-Transfer Contacts: A set of normally open/normally closed dry contacts operates

in advance of retransfer to normal source. Interval is adjustable from 1 to 30 seconds.

F. Digital Communication Interface: Matched to capability of remote annunciator or annunciator

and control panel.

G. Automatic Transfer-Switch Features:

1. Undervoltage Sensing for Each Phase of Normal Source: Sense low phase-to-ground

voltage on each phase. Pickup voltage shall be adjustable from 85 to 100 percent of

nominal, and dropout voltage is adjustable from 75 to 98 percent of pickup value.

Factory set for pickup at 90 percent and dropout at 85 percent.

2. Adjustable Time Delay: For override of normal-source voltage sensing to delay transfer

and engine start signals. Adjustable from zero to six seconds, and factory set for one

second.

Page 67: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

North Quad Infrastructure Renewal ICON architecture, inc.

UMass Lowell, Lowell, MA July 17, 2015

UMBA Project No. UMBA 13-L2

TRANSFER SWITCHES 263600 - 5

3. Voltage/Frequency Lockout Relay: Prevent premature transfer to generator. Pickup

voltage shall be adjustable from 85 to 100 percent of nominal. Factory set for pickup at

90 percent. Pickup frequency shall be adjustable from 90 to 100 percent of nominal.

Factory set for pickup at 95 percent.

4. Time Delay for Retransfer to Normal Source: Adjustable from 0 to 30 minutes, and

factory set for 10 minutes to automatically defeat delay on loss of voltage or sustained

undervoltage of emergency source, provided normal supply has been restored.

5. Test Switch: Simulate normal-source failure.

6. Switch-Position Pilot Lights: Indicate source to which load is connected.

7. Source-Available Indicating Lights: Supervise sources via transfer-switch normal- and

emergency-source sensing circuits.

a. Normal Power Supervision: Green light with nameplate engraved "Normal Source

Available."

b. Emergency Power Supervision: Red light with nameplate engraved "Emergency

Source Available."

8. Unassigned Auxiliary Contacts: Two normally open, single-pole, double-throw contacts

for each switch position, rated 10 A at 240-V ac.

9. Transfer Override Switch: Overrides automatic retransfer control so automatic transfer

switch will remain connected to emergency power source regardless of condition of

normal source. Pilot light indicates override status.

10. Engine Starting Contacts: One isolated and normally closed, and one isolated and

normally open; rated 10 A at 32-V dc minimum.

11. Engine Shutdown Contacts: Time delay adjustable from zero to five minutes, and factory

set for five minutes. Contacts shall initiate shutdown at remote engine-generator controls

after retransfer of load to normal source.

12. Engine-Generator Exerciser: Solid-state, programmable-time switch starts engine

generator and transfers load to it from normal source for a preset time, then retransfers

and shuts down engine after a preset cool-down period. Initiates exercise cycle at preset

intervals adjustable from 7 to 30 days. Running periods are adjustable from 10 to 30

minutes. Factory settings are for 7-day exercise cycle, 20-minute running period, and 5-

minute cool-down period. Exerciser features include the following:

a. Exerciser Transfer Selector Switch: Permits selection of exercise with and without

load transfer.

b. Push-button programming control with digital display of settings.

c. Integral battery operation of time switch when normal control power is not

available.

2.4 REMOTE ANNUNCIATOR SYSTEM

A. Functional Description: Remote annunciator panel shall annunciate conditions for indicated

transfer switches. Annunciation shall include the following:

1. Sources available, as defined by actual pickup and dropout settings of transfer-switch

controls.

2. Switch position.

3. Switch in test mode.

Page 68: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

North Quad Infrastructure Renewal ICON architecture, inc.

UMass Lowell, Lowell, MA July 17, 2015

UMBA Project No. UMBA 13-L2

TRANSFER SWITCHES 263600 - 6

4. Failure of communication link.

B. Annunciator Panel: LED-lamp type with audible signal and silencing switch.

1. Indicating Lights: Grouped for each transfer switch monitored.

2. Label each group, indicating transfer switch it monitors, location of switch, and identity

of load it serves.

3. Mounting: Flush, modular, steel cabinet, unless otherwise indicated.

4. Lamp Test: Push-to-test or lamp-test switch on front panel.

2.5 REMOTE ANNUNCIATOR AND CONTROL SYSTEM

A. Functional Description: Include the following functions for indicated transfer switches:

1. Indication of sources available, as defined by actual pickup and dropout settings of

transfer-switch controls.

2. Indication of switch position.

3. Indication of switch in test mode.

4. Indication of failure of digital communication link.

5. Key-switch or user-code access to control functions of panel.

6. Control of switch-test initiation.

7. Control of time-delay bypass for transfer to normal source.

B. Malfunction of annunciator, annunciation and control panel, or communication link shall not

affect functions of automatic transfer switch. In the event of failure of communication link,

automatic transfer switch automatically reverts to stand-alone, self-contained operation.

Automatic transfer-switch sensing, controlling, or operating function shall not depend on

remote panel for proper operation.

2.6 SOURCE QUALITY CONTROL

A. Factory test and inspect components, assembled switches, and associated equipment. Ensure

proper operation. Check transfer time and voltage, frequency, and time-delay settings for

compliance with specified requirements. Perform dielectric strength test complying with

NEMA ICS 1.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Annunciator and Control Panel Mounting: Flush in wall, unless otherwise indicated.

B. Identify components according to Section 260553 "Identification for Electrical Systems."

C. Set field-adjustable intervals and delays, relays, and engine exerciser clock.

Page 69: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

North Quad Infrastructure Renewal ICON architecture, inc.

UMass Lowell, Lowell, MA July 17, 2015

UMBA Project No. UMBA 13-L2

TRANSFER SWITCHES 263600 - 7

3.2 CONNECTIONS

A. Wiring to Remote Components: Match type and number of cables and conductors to control

and communication requirements of transfer switches as recommended by manufacturer.

Increase raceway sizes at no additional cost to Owner if necessary to accommodate required

wiring.

B. Ground equipment according to Section 260526 "Grounding and Bonding for Electrical

Systems."

C. Connect wiring according to Section 260519 "Low-Voltage Electrical Power Conductors and

Cables."

3.3 FIELD QUALITY CONTROL

A. Perform the following tests and inspections[ with the assistance of a factory-authorized

service representative]:

1. After installing equipment and after electrical circuitry has been energized, test for

compliance with requirements.

2. Perform each visual and mechanical inspection and electrical test stated in NETA

Acceptance Testing Specification. Certify compliance with test parameters.

3. Measure insulation resistance phase-to-phase and phase-to-ground with insulation-

resistance tester. Include external annunciation and control circuits. Use test voltages

and procedure recommended by manufacturer. Comply with manufacturer's specified

minimum resistance.

a. Check for electrical continuity of circuits and for short circuits.

b. Inspect for physical damage, proper installation and connection, and integrity of

barriers, covers, and safety features.

c. Verify that manual transfer warnings are properly placed.

d. Perform manual transfer operation.

4. After energizing circuits, demonstrate interlocking sequence and operational function for

each switch at least three times.

a. Simulate power failures of normal source to automatic transfer switches and of

emergency source with normal source available.

b. Simulate loss of phase-to-ground voltage for each phase of normal source.

c. Verify time-delay settings.

d. Verify pickup and dropout voltages by data readout or inspection of control

settings.

e. Perform contact-resistance test across main contacts and correct values exceeding

500 microhms and values for 1 pole deviating by more than 50 percent from other

poles.

f. Verify proper sequence and correct timing of automatic engine starting, transfer

time delay, retransfer time delay on restoration of normal power, and engine cool-

down and shutdown.

Page 70: University of Massachusetts Lowell BID REQUEST Pre ... Emergency... · CL16-HT-0037 Pre-Purchase Emergency Generator Page 1 BID REQUEST Pre-Purchase of Emergency Generator Bid Number

North Quad Infrastructure Renewal ICON architecture, inc.

UMass Lowell, Lowell, MA July 17, 2015

UMBA Project No. UMBA 13-L2

TRANSFER SWITCHES 263600 - 8

5. Ground-Fault Tests: Coordinate with testing of ground-fault protective devices for power

delivery from both sources.

a. Verify grounding connections and locations and ratings of sensors.

B. Coordinate tests with tests of generator and run them concurrently.

C. Report results of tests and inspections in writing. Record adjustable relay settings and measured

insulation and contact resistances and time delays. Attach a label or tag to each tested

component indicating satisfactory completion of tests.

D. Remove and replace malfunctioning units and retest as specified above.

E. Prepare test and inspection reports.

F. Infrared Scanning: After Substantial Completion, but not more than 60 days after Final

Acceptance, perform an infrared scan of each switch. Remove all access panels so joints and

connections are accessible to portable scanner.

1. Follow-up Infrared Scanning: Perform an additional follow-up infrared scan of each

switch 11 months after date of Substantial Completion.

2. Instrument: Use an infrared scanning device designed to measure temperature or to

detect significant deviations from normal values. Provide calibration record for device.

3. Record of Infrared Scanning: Prepare a certified report that identifies switches checked

and that describes scanning results. Include notation of deficiencies detected, remedial

action taken, and observations after remedial action.

3.4 DEMONSTRATION

A. [Engage a factory-authorized service representative to train] Owner's maintenance

personnel to adjust, operate, and maintain transfer switches and related equipment as specified

below. Refer to Section 017900 "Demonstration and Training."

B. Coordinate this training with that for generator equipment.

END OF SECTION 263600