TRANSFORMATION CABIN 2500kVA
MAIN FEATURESMedium voltage transformer substations equipped in container, complete withLow Voltage switches and Medium Voltage cells, ready for an immediateconnection. They are manufactured on 20 or 40 feet container’s structuresproperly modified, by planning the passing of inlet and outlet cables, by mountingspecific windows with extruded steel counter-frames. They are equipped alsowith internal lighting system, grounding, ventilation or cooling system. They arearranged for a parallel connection on the medium voltage side of the container,through an additional identical transformer station. The transformer substationscan be used in a double manner, both as voltage booster and as transformervoltage reducer.
1.2Visa S.p.A. via I° Maggio, 55 31043 Fontanelle (TV) Italy Tel: +39 0422 5091 Fax: +39 0422 509350Mail: [email protected] Web: www.visa.it SAP 109000000049-001-00 19-03-2015
N.A.= not available; O.R. = on request. Reference conditions standard ISO8528-1: temperature 25 °C, altitude 1-1000 m. A.M.S.L., 30% relative humidity, 100 kPa atmospheric pressure (1 bar), 0.8delayed power factor, load applied balanced not distorting. The data provided is subject to variation without prior notice.
GENERAL DATA
Mounting arrangement Container 20" length 6085 mm width 2438 mmheight 2591 mm
Total weight 10.500 kg
Colour RAL1223 yellow ochre
Compartments 2
External power supply circuits UPS 230V 1 kVA autonomy 90 minutes
Lighting inside 2 lamps 36W
Access Front side
ENVIRONMENTAL DATA
Installation outdoors
Ambient temperature / Humidity -20°C +45°C / 80%
Altitude Minor or equal 100 mt a.s.l.
REFERENCE STANDARDS CEI 64-8, CEI 17-6, CEI 14-4, CEI 11-18, CEI 016transformer station, CEI –EN 60439-1 low voltageelectrical panels, CEI-EN 62271-200 mediumvoltage electrical panels
GENERAL ELECTRICAL DATA MV
Nominal power / Frequency 2500kVA / 50 Hz
Distribution system TN
Neutral connected to the earth Direct
IP level of protection IP54
TRANSFORMER
Transformer power 2500 kVA
Type of insulation Resin englobing
Vectorial group Dyn 11
Primary nominal voltage LV 0.4 kV
Primary current LV 3608A
Secondary nominal voltage MV 20-15-11-6-3 kV
Primary current MV 72-96-131-240-481 A
TRANSFORMATION CABIN 2500kVA
MAIN FEATURES
2.2 Visa S.p.A. via I° Maggio, 55 31043 Fontanelle (TV) Italy Tel: +39 0422 5091 Fax: +39 0422 509350Mail: [email protected] Web: www.visa.it SAP 109000000049-001-00 19-03-2015
N.A.= not available; O.R. = on request. Reference conditions standard ISO8528-1: temperature 25 °C, altitude 1-1000 m. A.M.S.L., 30% relative humidity, 100 kPa atmospheric pressure (1 bar), 0.8delayed power factor, load applied balanced not distorting. The data provided is subject to variation without prior notice.
MV CELL
Rated voltage Ue 20-15-11-6-3 kV
Rated current In 72-96-131-240-481 A
Insulation voltage Ui 25 kV
Rated short-time current Icw 16 kA
Connection points screw 12MA (1)
Maximum cables connection 185sqmm (2)
Access from the bottom and side of the container
MV CELL SWITCH DATA
Rated current In 630A
Insulation SF6
Protections Thytronic NA 30 (50-51-51N-67N)
Earthing disconnector cables-output side
LV PANEL
Rated voltage Ue 400V
Rated current In 3608A
Insulation voltage Ui 690V
Rated short-time current Icw 60kA
Connection points screw 12 MA(15)
Maximum cables connection 30 measuring 300sqmm
Access from the bottom and side of the container
MV SWITCH DATA
Rated current In 4000A
Poles 4
Model 4000A
Protections ABB PR121/P LSI (50-51)
Interrupt rating 75kA