AC CONTACTOR
A
People Electric Appliance serves for people.
• ISO14001 OHSAS18001ISO9001
B A-01
AC CONTACTORPLC1-D AC CONTACTOR
SPECIFICATIONS
Rated insulation voltage(Ui)
Conforming to IEC 947-4-1,overvoltage category ,degree for pollution: 3
690V
6KV
1000V
8KV
1000V 1000V
8KV 8KV6KV
690V
Rated impulse withstandvoltage (Uimp)
Conforming to standards
Degree of protection (1)
(front face only)
protective treatment
Ambient air temperature
around the device
Maximum operating
altitude
Operating position
Flame resistance
Shock resistance (2)
1 / 2 sine wave = 11ms
Vibration resistance (2)
5...300 Hz
Power connection
Coil connection
Conforming to IEC 68
Storage
Operation
Permissible
Conforming to IEC 947
Without derating
Without derating
Conforming to IEC 695-2-1
Contactor open
Contactor closed
Contactor open
Contactor closed
IEC 60947-1, 60947-4-1, EN 60947-1, EN 60947-4-1
Protection against direct finger contact IP 2X
Protection against direct finger contact IP 2X (except CKYC1-D40...D80)
TH
-60...+80
-5...+60
-40...+70 ,for operation at Uc
3000m
30o possible, in relation to normal vertical mounting plane
960
10 gn
15 gn
2 gn
4 gn
8 gn
15 gn
2 gn
4 gn
8 gn
10 gn
2 gn
4 gn
8 gn
10 gn
2 gn
3 gn
6 gn
15 gn
2 gn
4 gn
(1) Protection ensured for the connection cross-sections shown on the next page and for connection via cable.(2) In the least favourable direction, without change of contact state (coil supplied at Ue)
PLC1-D 09/12/18
PLC1-D 25/32
Type of contactor D09...D18 D25...D38 D40 D50...D95 D115...D150PLC1-
AC CONTACTORPLC1-D AC CONTACTOR
PLC1-D 80/95
-
-
-
-
-
-
-
13
M5
No2
6
-
5
-
16
M6
No2
8
-
5
3x16
17
M6
-
8
10
9
5x25
25
M8
-
-
13
12
SPECIFICATIONS
CONNECTION VIA SPRING TERMINALS (2)
CONNECTION VIA BARS OR LUGS
Type of contactor PC1-D09 & D12
DT20 &T25
D18(3P) D25 D23 D38
Tightening
Flexible cable 1 conductor
Without cable end 2 conductors
Flexible cable 1 conductor
With cable end 2 conductors
Solid cable 1conductor
Without cable end 2 conductors
Screwdriver Head
flat screw/driver
6 sided key
Tightening torque
Screw clamps
2mm
2mm
2mm
2mm
2mm
2mm
N.m
1...4
1...4
1...4
1...2.5
1...4
1...4oN 2
6
-
1.7
1.5...6
1.5...6
1...6
1...4
1.5...6
1.5...6
No 2
6
-
1.7
1.5...10
1.5...6
1...6
1...4
1.5...6
1.5...6
No 2
6
-
2.5
2.5...10
2.5...10
1...10
1.5...6
1.5...10
1.5...10
No 2
6
-
2.5
D40 D50 &D65
D80 &D95 D115 & D150
Screwclamps
1-inputconnector
2-inputconnector
2.5...25
2.5...16
2.5...25
2.5...10
2.5...25
2.5...16
-
6... 8
-
5
2.5...25
2.5...16
2.5...25
2.5...10
2.5...25
2.5...16
-
6... 8
-
5
4...50
4...25
4...50
4...16
4...50
4...25
-
6... 8
4
9
10...120
10...120+10...50
10...120
10...120+10...50
10...120
10...120+10...50
-
-
4
12
Flexibl cablewithout cable end 1 conductor
2 conductors
2mm
2mm
2.5(4: DT25)
2.5(exceptDT25: -)
4
4
4
4
4
4
-
-
Bar cross-section
Lug external
of screw
Screw/driver Head
flat screwdriver
Key for hexagonal headed screw
Tightening torque
mm
mm
N.m
-
8
M3.5oN 2
6
-
1.7
-
8
M3.5
No2
6
-
1.7
-
10
M4
No2
6
-
2.5
-
10
M4
No2
6
-
2.5
PLC1-D 40/50/65
B A-02
AC CONTACTORPLC11-D AC CONTACTORS
SPECIFICATIONS
Type of contactor PLC11-D09 PLC11-D12 PLC11-D18 PLC11-D25 PLC11-D32 PLC11-D38
le max AC-3(Ue 440V)
le AC-1(0 60 )
2.2 KW4 KW4 KW5.5 KW5.5 KW-
9A
25A
690V
12A
220/240V380/4000V415/440V500V660/690V1000V
3 KW5.5 KW5.5 KW7.5 KW7.5 KW-
18A
32A
25A
40A
32A
50A
38A
4 KW7.5 KW9 KW10 KW10 KW-
5.5 KW11 KW11 KW15 KW15 KW-
7.5 KW15 KW15 KW18.5 KW18.5 KW-
9 KW18.5 KW18.5 KW18.5 KW18.5 KW-
Rated operational voltage
Rated opera-tional powerin AC-3
Auxiliary contacts
Compatible manual-auto thermaloverload relays
1 N/C and 1 N/O instantaneous incorporated in the contactors, with add-on blocks common to the whole
Class 10 A
Class 20
0.10...10A
2.5...10A
0.10...13A
2.5...13A
0.10...18A
2.5...18A
0.10...32A
2.5...32A
0.10...38A
-
0.10...38A
Suppressor modules
Interfaces
Contactor type
references
Reversing
contactor type
references
(d.c.and lowconsumptioncontactors havebuilt-in suppressionas standard)
Various
Diode
RC circuit
Bidirectional peak
limiting diode
Relay
Relay + voerlode function
Solid state
~ or 3P
~ 4P
4P
~ 3P
3P
~ 4P
4P
PLC11-09
PLC11-09
PLC11-09
PLC11-12
PLC11-12
PLC11-12
PLC11-12
PLC11-12
PLC11-12
PLC11-12
PLC11-18
PLC11-D18
PLC11-D18
PLC11-25
PLC11-25
PLC11-25
PLC11-D25
PLC11-D25
PLC11-D25
PLC11-D25
PLC11-32
PLC11-D32
PLC11-D32
PLC11-38
PLC11-D38
PLC11-D38
PLC11-09/12/18
PLC11-25/32/38
PLC11-40/50/65
B A-03
Type of contactor PLC11-D40 PLC11-D50 PLC11-D65 PLC11-D80 PLC11-D95 PLC11-D115
le max AC-3(Ue 440V)
le AC-1(0 60 )
220/240V380/4000V415/440V500V660/690V1000V
Rated operational voltage
Rated opera-tional powerin AC-3
Auxiliary contacts
Compatible manual-auto thermaloverload relays
Class 10 A
Class 20
Suppressor modules
Interfaces
Contactor type
references
Reversing
contactor type
references
(d.c.and lowconsumptioncontactors havebuilt-in suppressionas standard)
VariousDiodeRC circuitBidirectional peaklimiting diode
RelayRelay + voerlode functionSolid state
~ or 3P
~ 4P
4P
~ 3P
3P
~ 4P
4P
SPECIFICATIONS
PLC11-115
PLC11-150
PLC11-D AC CONTACTORS
PLC11-80,95
AC CONTACTOR
PLC11-D115
40 A 50 A 65 A 80 A 95 A 115 A 150 A
60 A
1000 V on ~ supply, 690 V on supply
80 A 125 A 200 A
11 KW18.5 KW22 KW22 KW30 KW22 KW
15 KW22 KW25/30 KW30 KW33 KW30 KW
18.5 KW30 KW37 KW37 KW37 KW37 KW
22 KW37 KW45 KW55 KW45 KW45 KW
25 KW45 KW45 KW55 KW45 KW45 KW
30 KW55 KW59 KW75 KW80 KW75 KW
40 KW75 KW80 KW90 KW100 KW90 KW
range comprising up to 4 N/C or N/O instan taneous, up to 1N/O + 1N/C time delay and up to 2 N/O or N/C protected contacts and 2 screencontinuity terminals
17...50 A
17...40 A
17...70 A
17...65 A
17...80 A
17...70 A
17...104 A
17...80 A
17...104 A 60...150 A
60...150 A
60...150 A
60...150 A
PLC11-40
PLC11-40
PLC11-40
PLC11-D40
PLC11-D40
PLC11-50
PLC11-D50
PLC11-65
PLC11-65
PLC11-65
PLC11-D65
PLC11-D65
PLC11-80
PLC11-80
PLC11-80
PLC11-D80
PLC11-D80
PLC11-95
PLC11-D95
PLC11-115
PLC11-115
PLC11-115
PLC11-D115
PC11-D115
PLC11-150
PLC11-D150
B A-04
APPLICATION
PLC1-F115
PLC1-F150
PLC1-F630
PLC1-F780 PLC1-F1154 PLC1-F2254
PLC1-F AC CONTACTOR
PLC1-F seriesAC Contactor is applicable to the circuits up to the rated voltage 1000V AC50Hz or 60Hz, rated current up to 780A, for long distance breaking circuit and frequently startingor controlling the motor. It also can be used for the control of distr ibut ion circuits of rated current from 200A to 1600A.
SPECIFICATIONS
Type
Rated operation
current(A)
Standard power
ratings of 3-phase
motors AC-3(KW)
AC-3
AC-1
220/230V
380/400V
415V
440V
500V
660/690V
1000V
115
200
30
55
59
59
75
80
65
150
250
40
75
80
80
90
100
65
185
275
55
90
100
100
110
110
100
225
315
63
110
110
110
129
129
100
225
350
75
132
140
140
160
160
147
PLC1-F115 PLC1-F150 PLC1-F185 PLC1-F225 PLC1-F265
Type
Rated operation
current(A)
Standard power
ratings of 3-phase
motors AC-3(KW)
AC-3
AC-1
220/230V
380/400V
415V
440V
500V
660/690V
1000V
330
400
100
160
180
200
200
200
160
400
500
110
200
200
250
257
280
185
500
700
147
250
280
295
355
335
335
630
1000
200
335
375
400
400
450
450
780
1600
220
400
425
425
450
475
450
PLC1-F330 PLC1-F400 PLC1-F500 PLC1-F630 PLC1-F780
AC CONTACTOR
PC1-F150
PC1-F115
PC1-F630
PC1-F1154 PC1-F2254
B A-05
SPECIFICATIONS
CJ16(19)SWITCH-OVER CAPACITOR CONTACTOR
Type
Controlled Capacity
Working current 1.3In AConventional heating current Ith A
Controlling capability to flash flow
Working voltage Us 50Hz
Operating rangeCoil
Consumed power(VA)
start holdingRated current for short-circuit
protected fuseRated insulation voltage
Ui 50Hz VConventional heating curent of
auxillary contacts AC 15AMechanical life ten thousand times
Elechanical life operating frequency
1201/h ten thousand timesWeight(kg)
400V Rated voltage(A)
CJ19-32
CJ16-32
18(16)
26(23)
33.8(30)
32
CJ19B-32
CJ16C-32
15
21.6
28
32
CJ19-32
CJ16-43
20
29
37.7
43
CJ19B-32
CJ19C-43
20
29
37.7
43
CJ19B-63
CJ19C-63
32
46
60
69
220,380 or according to user equirements0.85~1.1Us
68
12
115
11
200
20
1.5~2.5In
500 650
10
100 80
10 8
About0.58 About0.57 About0.6 About1.25
CJ16-32
CJ19-32
PLC4-D 4 POLE AC CONTACTOR
SPECIFICATIONS
AC-3 AC-1 440V40 (A)
Rated noncon-ductive voltage
Power poles Reference
Control circuit:a. c. ~
9
12
25
40
50
65
80
95
25
25
40
60
80
80
125
125
690
690
690
690
690
690
690
690
4242424242424242
-2-2-2-2-2-2-2-2
PLC4-D09004PLC4-D09008PLC4-D12004PLC4-D12008PLC4-D25004PLC4-D25008PLC4-D40004PLC4-D40008PLC4-D50004PLC4-D50008PLC4-D65004PLC4-D65008PLC4-D80004PLC4-D80008PLC4-D95004PLC4-D95008
PLC4-D09004
PLC4-D5004
AC CONTACTOR
B A-06
AC CONTACTORPLP1-D DC OPERATED AC CONTACTOR
SPECIFICATIONS
Type
RatedworkingcurrentA
IeA(AC-3)
Ratedheat
currentIth(A)
Ratedwork-
ingvoltageUe A
Ratedinsulat-
ingvoltage
Ui A
Controlled Power(KW)
Electri-cal life(AC-3)
410
Con-tactsNum-
ber
220V 380V 415V 440V 660VPLP1-D09
PLP1-D012
PLP1-D018
PLP1-D025
PLP1-D032
PLP1-D040
PLP1-D050
PLP1-D065
PLP1-D080
PLP1-D095
20
20
32
40
50
60
80
80
125
125
9
12
18
25
32
40
50
65
80
95
380V
660V
660V
2.2
3
4
5.5
7.5
11
15
18.5
22
25
4
5.5
7.5
11
15
18.5
22
30
37
45
4
5.5
9
11
15
22
30
37
45
45
4
5.5
9
11
15
22
25
37
45
45
5.5
7.5
9
15
18.5
30
33
37
45
45
660V
3P+NO
3P+NC
3P+NO
+NC
PLP1-D09
APPLICATION PLC1-P series DC OperatedAC contactor is suitable for using in the circuit up to rated voltage660VAC 50Hz or 60Hz, and in rated current 9-95A in AC-3/380V load circuits. For remotecontrolling circuit making,breaking and frequent cystarting AC motors. It can be also combinedwith the auxiliary contact group, air delayer, thermal relay devices etc. It has specialities ofequable & reliable action, quick while working.
PLP1-D18
PLP1-D32
PLP1-D65
PCA2 PLP2-D09
B A-07
PLC1-K06/09/1210
PLC2-K06/09/1210
PLC1-E03/09
PLC2-E03/09
PLC1-K AC CONTACTORAC CONTACTOR
SPECIFICATIONS
PLC1-EC SERIES AC CONTACTOR
SPECIFICATIONS
Type Rated workingcurrent A(380V)
PLC1-K06PLC1-K09PLC1-K12
6912
220V1.52.23
AC-3 use groupControl power KW
380/415V2.245
440/500V345
660V345
Contactdata(1)
3P+NC 3P+NO3P+NC 3P+NO3P+NC 3P+NO
TypeSpecificationUse group under AC-3Rated working current(Ie)AConventional thermal current(Ith)ARated working voltage(Ue)VRated insullation voltage(Ui)V
AC-3(6Ie Ie)AC-4
(6Ie Ie)Mechnical life
Auxiliarycontact
65
16
97.520
380 660690
0.5 1061200
10 104300
3 1066A
121020
Coilspecification
Electrical life(times)Operation frequency h-1
Electrical life(times)Operation frequencyh-1
Conventional thermal currentElectrical life
(times)AC-15(360VA)DC-13(13W)
Rated control voltage(Us)
Pick-up voltageReleasing voltage
Coil power VAPick-upRetain
ConsumptionPick-up time
Releasing timePower factor
PLC1-K06 PLC1-K09 PLC1-K12
AC:12,24,45,110,220,380DC:12,24,45,110,220
AC:0.85~1.1Us DC:0.85~1.1UsAC:0.1~0.75Us DC:0.2~0.75Us
404
1.2W6~18ms5~23ms
Making 0.8 Breaking 0.3
60.5 10
Basic reference.Complete with codeindicating controlcircuit voltage(2)
Fixing(1)
PLC1-EC03*PLC1-EC09*PLC1-EC03*PLC1-EC09*
For motor control, from 6 to 630A(AC-3)for the control of distribution circuits, from 16 to 1000A(AC-1)Control circuit: d.c.
Standard power ratings of3-phase motor50-60Hz in category AC-3220V 380V 660V203V 400V 415V 440V 500V 690V KW
1.5
2.2
KW
2.2
4
KW
2.2
4
KW
3
4
KW
3
4
KW
3
4
A
6
9
A
16
16
V
660
660
Rated operatingcurrent
AC-3 AC-1up to 40
440
Ratednon-
conductivevoltage
Instantaneousauxiliarycontacts
1-1-
-1-1
B A-08
CONTACT BLOCK
APPLICATION
PLA1-D series auxiliay contact blocks is installed on the top of PCA2-D control relay or PLC1-D AC contactor for expanding the couples of au xil iar y contacts points.Ow ing to adoptingthe contacting functions of sliding frictions, the item can be self-cl eanin g & ensure the electric circuit to be reliable.
SPECIFICATIONS
Type
Contactnumber
PLA1-DN02
PLA1-DN11
PLA1-DN20
PLA1-DN22
PLA1-DN40
PLA1-DN04
PLA1-DN13
PLA1-DN31
2NC NO+NC 2NO 2NO+2NC 4NO 1NO+3NC4NC
APPLICATION
PLA2-D timer delay auxiliary contact blocks are combined with PLC1-D AC contactor & PA1-DAuxiliary contact block into PLC3-D star-delta reduced volt-age starter is to start motor.
SPECIFICATIONS
TypePLA2-DT0PLA2-DT2PLA2-DT4PLA3-DR2PLA3-DR4PLA3-DR2
Delay range0.1~3s
0.1~30s10~180s0.1~30s10~180s0.1~3s
Number of the delay contacts
NO+NC
PLX1-D2:PLX1-D4:PLX1-D6:PLX1-FF:PLX1-FG:PLX1-FH:PLX1-FJ:PLX1-FK:PLX1-FL:PLX1-FK:
Used for ContactorUsed for ContactorUsed for ContactorUsed for ContactorUsed for ContactorUsed for ContactorUsed for ContactorUsed for ContactorUsed for ContactorUsed for Contactor
PLC1-D09 to PLC1-D18PLC1-D25 to PLC1-D32PLC1-D40 to PLC1-D95
PLC1-F115 to PLC1-F150PLC1-F185 to PLC1-F225PLC1-F265 to PLC1-F330
PLC1-F400PLC1-F500PLC1-F630PLC1-F780
PLX1-D06N PLX1-FK
CONTACTOR BLOCK
3NO+3NC
PLA1-DN11
PLA1-DN40
PLA2-DT2
PLA2-DT2
PLE4-11K
PLE4-22K
PLX1-D04 PLX1-D06PLX1-D02
B A-09
P3TF AC CONTACTOR
Type
RatedThermalcurrent
(A)
Ratedoperationcurrent(A)
380V 660V 660V380V 660V380V
Controllabe power of motor(KW)
AC-3 AC-4Type of
Auxiliarycontact
P3TF30
P3TF31
P3TF32
P3TF33
P3TF34
P3TF35
P3TF40
P3TF41
P3TF42
P3TF43
P3TF44
P3TF45
P3TF46
P3TF47
P3TF48
P3TF49
P3TF50
P3TF51
P3TF52
P3TF53
P3TF54
P3TF55
P3TF56
P3TF68
20
20
30
30
55
55
20
20
30
30
55
55
80
80
100
100
160
160
200
210
300
300
400
630
9
12
16
22
32
38
9
12
16
22
32
38
45
63
75
85
110
140
170
205
250
300
400
630
7
8.5
12.5
16.5
24
30
7
8.5
12.5
16.5
24
30
40
60
60
80
95
120
160
165
230
260
380
600
4
5.5
7.5
10
15
18.5
4
5.5
7.5
10
15
18.5
22
30
37
45
55
75
90
110
132
160
200
335
5.5
7.5
11
15
22
22
5.5
7.5
11
15
22
22
37
55
55
75
90
110
150
160
220
250
355
560
1.4
1.9
3.5
4
7.5
9
1.4
1.9
3.5
4
7.5
9
12
14
17
21
27
35
38
50
58
66
81
160
2.4
3.3
6
6.6
13
15.5
2.4
3.3
6
6.6
13
15.5
20.8
24.3
29.5
36
46.9
60
66
86
100
114
140
278
NONC
1NO+1NC2NO+2NC
2NC+2NO4NC+4NO
TECHNICAL SPECIFICATION:
P3TF30/31
P3TF-40
AC CONTACTOR
P3TF56
P3TF-46
P3TF-52B A-10
APPLICATION
The contactor is suitable for using in the circuits up to the rated voltage 660VAC 50 Hz or 60Hz,rated current 630A, for making and breaking, and for frequent starting and controlling the motor.After combined with the mechanical interlocking device, it becomes 3TD series convertiblecontactor for Contro lling, starting, breaking and reversing of the motor. The products comply withIEC947-2 & VDE0660.
P3TB-40
P3TB P3TH AC CONTACTOR
TypeRated
thermalcurrent (A)
Ratedoperatingcurrent at380V(A)
The power of con-trolled motor(KW)
380V
Type ofauxliliary
contact
Ratedoperatingcurrent at660V(A) 660V
P3TB40
P3TB41
P3TB42
P3TB43
P3TB44
22
22
35
35
55
9
12
16
22
32
7.2
9.5
13.5
13.5
18
4
5.5
7.5
11
15
5.5
7.5
11
11
15
1NO1NC
1NO+1NC2NO+2NC
2NC+2NO
SPECIFICATIONS
AC CONTACTOR
P3TB-44
APPLICATION
The auxiliary contactor is the auxiliary suited by controlled circuit whose voltage is AC 50/60Hz,660V and DC 660V. They control all kinds of m agnet ic coil and amplify or trasfer signal to relativecontrolled element simultaneously.They are characterized by high performance & long service life.
P3TH AC CONTACTOR
SPECIFICATIONSP3TH-80
P3TH-82
P3TH-80
P3TH-82
B A-11
INTERLOCKING CONTACTORAC CONTACTOR
SPECIFICATIONS
TypeRated thermal
current (A)
Rated operationcurrent (A)
Controllable power of motor (KW)AC-3 AC-4
P3TD40P3TD41P3TD42P3TD43P3TD44P3TD45P3TD46P3TD47P3TD48P3TD49P3TD50P3TD51P3TD52P3TD53P3TD54P3TD55P3TD56P3TD58
2020303055558080
100100160160200210300300400630
380V9
121622323845637585110140170205250300400630
660V7
8.512.516.524244060608095
120160165230260380600
380V4
5.57.51015
18.522303745557590110132160200335
660V5.57.5111522223755557590110150160220250355560
660V2.43.36
6.613
15.520.824.329.536
46.9606686
100114140278
380V1.41.93.54
7.59
1214172127353850586681
160
P3TD-50
SPECIFICATIONS
PLC2-D0901
PLC2-D1201
PLC2-D1801
PLC2-D2501
PLC2-D3201
PLC2-D4011
PLC2-D5011
PLC2-D6311
PLC2-D8011
PLC2-D9511
TypeRated current
AC-3(A)
9
12
18
25
32
40
50
63
80
95
Controlled power(KW)
220V
2.2
5.5
7.5
5.5
7.5
18.5
15
18.5
22
22
380V
4
5.5
7.5
11
15
18.5
22
30
37
45
415V
4
5.5
9
11
15
22
25
37
45
45
440V
4
5.5
9
11
15
22
25
37
45
45
660V
5.5
7.5
10
15
18.5
30
33
37
45
41
PLC2-D50
PLC2-D115
PLC2-D/F MECHANICAL
P3TD MECHANICAL
B A-12
PGMC AC CONTACTOR
Type
IEC-60947 AC1 dutyAC3 duty 200~240V
380~440V500~550V690V
UL Continuous current(th)
ACMotor
singlephase
Threephase
115V
230V
200V
230V
460V
575V
Aux.contact
Panel installation
External Dimension(mm)(W H D)
Rail & Screw
44 80 86.8 68 82 94.6
PGMC-9
20A
2.5KW 11A
4KW 9A
4KW 7A
4KW 5A
20A
0.5HP
1HP
2HP
2HP
5HP
7.5HP
AU-1
AU-2,AU-4
Side mounting
Top mounting
PGMC-12
20A
3.5KW 13A
5.5KW 12A
7.5KW 12A
7.5KW 9A
25A
0.5HP
2HP
3HP
3HP
7.5HP
10HP
AU-1
PGMC-18
25A
4.5KW 18A
7.5KW 18A
7.5KW 13A
7.5KW 9A
30A
1HP
3HP
5HP
5HP
10HP
15HP
AU-1
PGMC-22
32A
5.5KW 22A
11KW 22A
15KW 22A
15KW 18A
32A
2HP
3HP
7HP
7.5HP
10HP
15HP
AU-1
PGMC-32
50A
7.5KW 32A
15KW 32A
18.5KW 28A
18.5KW 21A
45A
2HP
5HP
7.5HP
10HP
20HP
20HP
AU-1
PGMC-40
60A
11KW 40A
18.5KW 40A
22KW 32A
22KW 25A
50A
3HP
5HP
10HP
10HP
25HP
25HP
AU-1
AU-2,AU-4 AU-2,AU-4 AU-2,AU-4 AU-2,AU-4 AU-2,AU-4
Type
IEC-60947 AC1 dutyAC3 duty 200~240V
380~440V500~550V690V
UL Continuous current(th)
ACMotor
singlephase
Threephase
115V
230V
200V
230V
460V
575V
Aux.contact
Panel installation
External Dimension(mm)(W H D)
Rail & Screw
94 123.5 117.4 100 157.4 146.5
PGMC-50
80A
15KW 55A
22KW 50A
30KW 43A
30KW 33A
70A
3HP
7.5HP
10HP
15HP
30HP
30HP
AU-1
AU-2,AU-4
Side mounting
Top mounting AU-2,AU-4 AU-2,AU-4 AU-2,AU-4
Screw
- -
PGMC-65
100A
18.5KW 65A
30KW 65A
37KW 60A
37KW 47A
80A
5HP
10HP
15HP
20HP
40HP
40HP
AU-1
PGMC-75
110A
22KW 75A
37KW 75A
45KW 64A
45KW 47A
90A
5HP
15HP
20HP
25HP
50HP
50HP
AU-1
PGMC-85
135A
25KW 85A
45KW 85A
45KW 75A
45KW 52A
100A
7.5HP
15HP
25HP
30HP
50HP
50HP
AU-1
PGMC-100
150A
30KW 105A
55KW 105A
55KW 85A
55KW 65A
160A
7.5HP
15HP
30HP
30HP
60HP
60HP
AU-100
PGMC-125
150A
35KW 125A
60KW 120A
60KW 90A
60KW 70A
160A
10HP
20HP
40HP
40HP
75HP
75HP
AU-100
PGMC 9-22
PGMC 32-40
PGMC 50-85
PGMC 100-125
AC CONTACTOR
B A-13
Type
The highest control power(kW)
Rated heating current lth (A)
Rated working currentAC2/AC3/AC4
Rated holding power of aholding coil/pull-in(VA/W)
220V
380V
500V
660V
380V
660V
PAB9
2.2
4
4
4
16
8.5
3.5
PAB12
3
5.5
5.5
5.5
20
11.5
4.9
PAB16
4
7.5
7.5
5.5
25
15.5
6.7
PAB25
6.5
11
11
11
40
22
13
PAB30
9
15
15
15
45
30
17.5
PAB37
10
18.5
18.5
18.5
45
37
21
PAB45
13
22
22
22
60
44
25
9/2.260/50
9/2.260/50
10/385/65
10/385/65
22/5175/125
22/5125
9/2.260/50
Type
The highest control power(kW)
Rated heating current lth(A)
Rated working currentAC2/AC3/AC4
Rated holding power of aholding coil/pull-in(VA/W)
220V
380V
500V
660V
380V
660V
PAB65
16
33
40
40
80
65
45
PAB85
20
45
50
50
100
85
55
PAB105
28
55
75
75
140
105
82
PAB170
46
90
110
110
230
170
118
PAB250
60
132
160
160
300
245
170
PAB370
32
200
250
250
400
370
268
30/8270/130
30/8270/130
32/9510/280
60/15790/460
66/161100/600
100/27900/350
APPLICATION
PAB AC CONTACTOR
PAB series AC contactors, mainly used in 50/60Hz electrical line of the rated voltage up to 660VAC and rated current up to 475A,are applicable for remote making and breaking of electrical linesor frequent control ov AC motors, having no-voltage protection. Usually, it can be combined with T series thermal relay to for m electromagnetic starters which have overload and open-phase protection. It complies with IEC60947 & VDE0660.
TECHNICAL SPECIFICATION
PAB9
PAB25
PAB37
AC CONTACTOR
B A-14
Type PB9
2.2
4
4
1
16
8.5
3.5
220V
380V
500V
660V
380V
660V
The highest controlpower (KW)
Rated heating current Ith (A)
Rated working currentAC2/AC3/AC4
Rated holding power of aholding coil/pull-in (VA/W)
PB12
3
5.5
5.5
5.5
20
11.5
4.9
PB16
4
7.5
7.5
5.5
25
15.5
6.7
PB25
6.5
11
11
11
40
22
13
PB30
9
15
15
15
45
30
17.5
PB37
10
18.5
18.5
18.5
15
37
21
PB45
13
22
22
22
60
44
25
9/2.260/50
9/2.260/50
9/2.260/50
10/385/65
10/385/65
22/5175/125
22/5125
Type PB65
16
33
40
40
80
65
45
220V
380V
500V
660V
380V
660V
The highest controlpower (KW)
Rated heating current Ith (A)
Rated working currentAC2/AC3/AC4
Rated holding power of aholding coil/pull-in (VA/W)
30/8270/130
PB85
20
45
50
50
100
85
55
PB105
28
55
75
75
140
105
82
PB170
46
90
110
110
230
170
118
PB250
60
132
160
160
300
245
170
PB370
32
200
250
250
400
370
268
30/8270/130
32/9510/280
60/15790/460
66/161100/600
100/27900/350
PB AC CONTACTOR
APPLICATION
PB series AC contactors is mainly used in 50/60Hz electrical line of the rated voltage up to 660VAC and rated current up to 475A, is applicable for remote making and breaking of electricallines or frequenty control in AC motors, having no-voltage protection. Usually, it can be combinedwith T series thermal relay to for electromagnetic starters which have overload and open-phaseprotection. It complies with IEC60947 & VDE0660.
TECHNICAL SPECIFICATION
PB12
PB25
PB37
PB65
AC CONTACTOR
B A-15
Rated current TYPE Voltage
S009A
P3RT1016-1AB01P3RT1016-1AK61P3RT1016-1AR11
24120220440
120220440
P3RT1026-1AB60P3RT1026-1AN20P3RT1026-1AR10
P3RT1034-1AJ16P3RT1034-1AN16P3RT1034-1AR16
S025 A
S232 A
S250 A
S380 A
P3RT1036-1AJ16P3RT1036-1AN16P3RT1036-1AR16
P3RT1045-1AJ16P3RT1045-1AN16P3RT1045-1AR16
115220440
115220440
115220440
9 A15 A22 A35 A
Rated current
Rated current
P3RT1016-1BB41P3RT1016-1BB40P3RT1016-1BB40P3RT1016-1BB40
24 V
TYPE No. The Ejecucion decontactors
P3RH1911-IFA22P3RH1921-1FA22
P3RH1911-1EA11
2NA+2NC2NA+2NC
2NA+2NC
P3RT SERIES AC CONTACTOR
P3RT-25
P3RT-50
P3RT-95
AC CONTACTOR
B A-16
PLC3-D183
PLC3-D503
PLC3-D803
PLC3-D STAR-DELTA REDUCED VOLTAGE STARTER
APPLICATION
SPECIFICATION
PLC3-D series star-delta reduced voltage starter is su itable for starting motor in t he circuit of AC 50/60Hz,voltage up to 660V and curren up to 95A. It is proided with a timer for automaticchangover of star-delta to reduce the voltage and current of motor starting.
9
12
18
25
32
40
50
65
80
95
7.5
11
22
22
30
37
59
59
75
80
7.5
11
22
22
33
37
59
59
75
80
7.5
11
18.5
22
25
37
55
55
75
80
4
5.5
11
11
15
18.5
30
32
37
45
PLC3-D093
PLC3-D123
PLC3-D183
PLC3-D253
PLC3-D323
PLC3-D403
PLC3-D503
PLC3-D653
PLC3-D803
PLC3-D953
Rated opertaing current(A)
AC3
3-phase motor capacity(KW)AC3 LoadedType
220V 380V 415V 440V
Wiring DiagramL1 L2 L3
1 3 5
2 4 6KM2
U2 V2 W2
Wireless ControlU1 V1 W1
1 3 5 1 3 5
2 4 6
1 3 5
2 4 6
U1 V1 W1U2 V2 W2
KM3 KM1
2 4 6 KM3.5
KM2 KM3KM1
95
96
11
12
13
14
R
O
I
55
53(3)
54(4)
56
21
22
67
68
2
1
13
14KM2
KM2
KM1KM3
KM3.1
22
21
22
1 1
KM1
KM7
STAR-DELTA SFARTER
B A-17
Enclosure
Control(2 pushbuttons mounted onenclosure cover)
Connections
Standard control circuit voltages
PLE-D18 and D25
PLE1-D32...D25
PLE1-D09...D95
PLE1-D09...D95
Double insulated,protected to IP 429(3) or to IP 659(4)
Double insulated,protected to IP 427(3) or to IP 557(4)
Metal,IP55 to Ip559
1 green Start button l1 red Stop/Reset button O
Pre-wired power and control circuitconnections
Volts
50/60Hz
24
B7
42
D7
48
E7
110
F7
220/230
M7
230
P7
240
U7
380/400
Q7
400
V7
415
N7
440
R7
PLE-D09 and D12
Maximum power AC3 duty(KW)
220V
230V
380V
400V415V 440V 500V
660V
690V
Rated
current
(A)
Type of
enclosure
1.1
2.2
3
4
5.5
7.5
11
15
18.5
22
25
2.2
4
5.5
7.5
11
15
18.5
22
30
37
45
22
4
5.5
9
11
15
22
25
37
45
45
22
4
5.5
9
11
15
22
30
37
45
45
-
5.5
7.5
10
15
18.5
22
30
37
55
55
-
5.5
7.5
10
15
18.5
30
33
37
45
45
6
9
12
18
25
32
40
50
65
80
95
-
IP42
IP65
IP42
IP65IP42
IP65IP42
IP65
IP55
IP55
IP55
IP55
IP55
IP55
Code Number
LL
(long life)
NL(3)
(normal life)
Suitable
Thermal
Relay(A)
-
PLE1 D094...
PLE1 D093...PLE1 D124...
PLE1 D123...PLE1 D188...
PLE1 D185...PLE1 D258...
PLE1 D255...
PLE1 D325...
PLE1 D405...
PLE1 D505...
PLE1 D655...
PLE1 D805...
PLE1 D955...
PLE1 EC135 PLE1 EC135
-
-
PLE1 D094...
PLE1 D093...PLE1 D124...
PLE1 D123...PLE1 D188...
PLE1 D185...
PLE1 D255...
PLE1 D325...
PLE1 D405...
PLE1 D505...
PLE1 D655...
PLE1 D805...
PLR2 D1312
PLR2 D1314
PLR2 D1316
PLR2 D1321
PLR2 D1322
PLR2 D2353
PLR2 D2355
PLR2 D3353
PLR2 D3355PLR2 D3357
PLR2 D3359
PLR2 D3361
PLR2 D3363
PLR2 D3365
PLR2 D3365
PLE1-D MAGNETIC STARTER
SPECIFICATION
APPLICATION
PLE1-D magnetic starter is mainly applied to circuit of AC 50 or 60Hz ,vol tage up to 550V for far distance making and breaking circuit and fre quent star t an d con trol motor. It has thefeatures of small volume, light weight, low power consumption, high efficiency, safe andreliable performance etc.
MAGNETIC STARTER
PLE1-09,12,18
PLE1-25,32
PLE1-40,95
B A-18
APPLICATIONS
PLE1-DN magnet ic starter is mainly applied to circuit of AC 50 or 60Hz,voltag e up to 550V forfar distance making and breaking circuit and frequentl y sta rtin g an d co ntro lli ng mot or .It hasthe features of small volume, light weitght, low power consumption, high efficiency, safe and reliableperformance etc.
SPECIFICATION
SPECIFICATION
PLE1-D09N and D12N
PLE1-D18 and D25N
PLE1-D32...N D95N
PLE1-D09...N D95N
PLE1-D09...N D95N
Enclosure
Control(2 pushbuttons mounted on enclosure cover)
connections
Standard control circuit voltages
2.2
3
4
5.5
7.5
11
15
18.5
22
25
9
12
18
25
32
40
50
65
80
95
4
5.5
7.5
11
15
18.5
22
30
37
45
4
5.5
9
11
15
22
25
37
45
45
4
5.5
9
11
15
22
25
37
45
45
5.5
7.5
10
5
18.5
22
30
37
55
55
5.5
7.5
10
5
18.5
22
30
37
45
45
IP42IP65
IP42IP55
IP42IP55
IP42IP55
IP55
IP55
IP55
IP55
IP55
IP55
Maximum power AC3 duty(KW) Rated
current
(A)
Type of
enclo-
sure220V230V
380V400V
415V 440V 500V660V690V
PLE1 D094..NPLE1 D093..N
PLE1 D124..NPLE1 D123..N
PLE1 D188..NPLE1 D185..N
PLE1 D258..NPLE1 D255..N
PLE1 D255..N
PLE1 D325..N
PLE1 D405..N
PLE1 D505..N
PLE1 D655..N
PLE1 D805..N
PLE1 D325..N
PLE1 D405..N
PLE1 D505..N
PLE1 D655..N
PLE1 D805..N
PLE1 D955..N
PLE1 D094..NPLE1 D093..N
PLE1 D124..NPLE1 D123..N
PLE1 D188..NPLE1 D185..N
PLR2 D1312PLR2 D1314
PLR2 D1316
PLR2 D1321
PLR2 D2355
PLR2 D3361
PLR2 D3365
PLR2 D1322PLR2 D2353
PLR2 D3353PLR2 D3355
PLR2 D3357PLR2 D3359
PLR2 D3363PLR2 D3365
Code number
LL
(long life)
NL(3)
(normal life)
Suitable
thermal
relay(A)
Volts
50/50Hz
24
B7
42
D7
48
E7
110
F7
220/230
M7
230
P7
240
U7
380/400
Q7400
V7
415
N7
440
R7
Metal IP55to IP427
1 green Start butto"I"1red Stop/Reset button"O"Pro-wired power and control circuit connections
Double insulated,protected to IP42(3) or to IP659(4)Double insulated,protected to IP427(3) or to IP557(4)
PLE1-DN MAGNETIC STARTERMAGNETIC STARTER
PLE1-D0901N
PLE1-D09N
PLE1-D18N
PLE1-D32N
B A-19
PMSB
SPECIFICATION
PMSB 9PMSB 12PMSB 16PMSB 25PMSB 30PMSB 37PMSB 45PMSB 65PMSB 80
45.55.51115
18.5224050
45.57.51115
18.5223345
2.234
6.59
10131620
45.57.51115
18.5224050
~220V ~380V ~500V ~660V
Control power AC2/AC3/AC4
kWT16 T45 T85 T105 T170 T250 T370
PMSB series electromagnet ic starte rs is used in a power line, AC 50-60Hz to start, stop and convert motors,and protect motors from overload and phase failure PMBS9-msb80 starters andconvertible starters have two types: open type and protcetive cover type
PMSB MAGNETIC STARTERAPPLICATIONS
PADS7 CONTACTOR STARTER,STAR-DELTA STARTER
SPECIFICATION
Type
Direct-on-line,surface mounting
Direct-on-line,flush mounting
Direct-on-line,surface mounting,reversing
Direct-on-line,surface mounting,with isolator
Rated curren
AC 415(A)3
3-phase motor capacity
AC load415V3
0.50HP
0.75HP
1.50HP
2.00HP
3.40HP
5.50HP
7.50HP
10.0HP
15.0HP
20.0HP
0.37KW
0.55KW
1.10KW
1.50KW
2.50KW
4.00KW
5.50KW
7.50KW
11.0KW
15.0KW
0.74-1.11A
1.11-1.66A
1.66-2.50A
2.50-3.70A
3.70-5.60A
5.60-8.40A
8.40-11.9A
11.4-16.0A
16.0-23.0A
22.0-33.0A
Type
Direct-on-line,surface mounting
Direct-on-line,flush mounting
Direct-on-line,surface mounting,reversing
Direct-on-line,surface mounting,with isolator
Rated curren
AC 415(A)3
3-phase motor capacity
AC load415V3
4HP
6.8HP
10.0HP
13.5HP
20.0HP
30.0HP
40.0HP
3.00KW
5.00KW
7.50KW
10.0KW
15.5KW
22.00KW
30.00KW
4.30-6.40A
6.40-9.70A
9.70-14.5A
14.5-20.6A
19.7-27.7A
26.0-38.0A
38.0-57.0A
PADE7
PADS7
PADE
CONTACTOR STARTER
B A-20
APPLICATIONS
MS-K11
MS-K21
MS-K25 MT-11 MT-21
MS-N MS-K MAGNETIC STARTER
MS-N & MS-K series magnetic starters is used in a circuit of voltage up to 600V, AC 50-60Hzto start, stop and convert motors, and protect motors from overload and phase failure.
11
13
18
22
22
30
40
55
65
85
105
9
12
16
22
22
30
40
50
62
85
105
4
5.5
7.5
7.5
7.5
11
15
22
30
45
55
2.5
3.5
4.5
5.5
5.5
7.5
11
15
18.5
22
30
4
5.5
7.5
11
11
15
18.5
22
30
45
55
4
5.5
7.5
11
11
15
18.5
22
30
45
55
-
-
-
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
MS-N10(MS-K10)
MS-N11(MS-K11)
MS-N18(MS-K18)
MS-N20(MS-K20)
MS-N21(MS-K21)
MS-N25(MS-K25
MS-N35(MS-K35)
MS-N50(MS-K50)
MS-N65(MS-K65)
MS-N80(MS-K80)
MS-N95(MS-K95)
Type
Ratedcurrent AC3
(A)Rated power(KW)
Aux
contacts Setting current(A)
220V 380V 220V 380V 550V 660V
0.24A 0.35A 0.5A0.7A 0.9A 1.3A1.7A 2.1A 2.5A
3.6A 5A 6.6A 9A
0.24A 0.35A 0.5A0.7A 0.9A 1.3A1.7A 2.1A 2.5A
3.6A 5A6.6A 9A11A 15A
19A22A29A 35A
15A 22A 29A35A 42A 54A
37A82A95A
SPECIFICATION
MAGNETIC STARTER
B A-21
Type
Rated power(kW) Rated current(A)
AC3 duty AC3 duty
220V~220V
380V~440V
500V~550V
220V~220V
380V~440V
500V~550V
AC1duty(A)
Settingcurrent
(A)
PMW-5CP 3.7 7.5 9 13 12 12 20 2-4,4-8,8-16
Type
Rated power(kW) Rated current(A) AC1duty
A
AC3 duty AC3 duty1 pole motor
110V 220V 220V~220V
220V~220V
380V~440V
380V~440V
500V~550V
500V~550V
PMW-9(B)PMW-12(B)PMW-18(B)PMW-22(B)PMW-32(B)PMW-40(B)PMW-50(B)PMW-65(B)PMW-75(B)PMW-85(B)PMW-100(B)PMW-125(B)
0.40.5
0.750.91.21.7
------
0.81
1.51.8
--------
2.53.54.55.57.51115
18.522253037
45.57.51115
18.5223037455560
47.57.515
18.522303745455560
11131822324055657585
105125
9121822324050657585
105120
71213222832436064758590
20202532506080
100110135150150
TypeRated power(kW) Rated current(A)
1 pole motor AC3 duty
AC1dutyAC3 duty
110V 220V 220V~220V
380V~440V
500V~550VWithout PB
Push buttontype
PMW-9M
PMW-112M
PMW-18M
PMW-22M
PMW-9MB
PM W-112MB
PMW-18MB
PMW-22MB
0.4
0.5
0.75
0.9
0.8
1
1.5
1.8
2.5
3.5
4.5
5.5
4
5.5
7.5
11
4
7.5
7.5
15
220V~220V
380V~440V
500V~550V
11
12
18
22
9
12
18
22
7
12
13
22
20
20
25
32
A
PMW ENCLOSED TYPE MAGNETIC STARTER
RATINGS
PMW-5CP
PMW 9-22B
PMW 32-40B
PMW50-85 PMW-22MB PMW-22M
MAGNETIC STARTER
PMW-22MB PMW-22M
B A-22
Type
PGV2-M01
PGV2-M02
PGV2-M03
PGV2-M04
PGV2-M05
PGV2-M06
PGV2-M07
PGV2-M08
PGV2-M10
PGV2-M14
PGV2-M16
PGV2-M20
PGV2-M21
PGV2-M22
PGV2-M32
PGV3-M06
PGV3-M07
PGV3-M08
PGV3-M10
PGV3-M14
PGV3-M20
PGV3-M25
PGV3-M40
PGV3-M63
PGV3-M80
Rated standard power of 3-phasemotors 50/60Hz in category AC-3
220V
KW
--
--
--
--
--
--
0.37
0.75
1.1
2.2
3
4
5.5
5.5
7.5
--
0.37
0.75
1.1
2.2
4
5.5
11
15
22
380V
KW
--
--
--
--
--
0.37
0.75
1.5
2.2
4
5.5
7.5
11
11
15
0.37
0.75
1.5
2.2
4
7.5
11
18.5
30
40
415V
KW
--
--
--
--
--
--
0.75
1.5
2.2
4
5.5
9
11
11
15
--
1.1
1.5
2.2
4
7.5
11
22
33
45
440V
KW
--
--
--
--
0.37
0.55
1.1
1.5
3
4
7.5
9
11
11
15
0.55
1.1
1.5
3
4
7.5
11
22
33
45
500V
KW
--
--
--
--
0.37
0.75
1.1
2.2
3.7
5.5
7.5
9
11
15
18.5
0.75
1.1
2.2
3.7
5.5
10
15
25
40
55
660V
KW
--
--
--
0.37
0.55
1.1
1.5
3
4
7.5
9
11
15
18.5
26
1.1
1.5
3
4
7.5
11
18.5
33
55
63
Setting range(A)
0.1-0.16
0.16-0.25
0.25-0.4
0.4-0.63
0.63-1
1-1.6
1.6-2.5
2.5-4
4-6.3
6-10
9-14
13-18
17-23
20-25
24-32
1-1.6
1.6-2.5
2.5-4
4-6
6-10
10-16
16-25
25-40
40-63
56-80
PGV MOTOR PROTECTION CIRCUIT BREAKER
APPLICATION
PGV series motor protection circuit breakers is mainly used for the overload and short circuit protection of the motor in AC 50/60Hz, up to 660V, 0.1-80A power circuit, a s a full voltage st arterto start and cut off the motor, under the AC3 load or for the overload and short circuit protection ofthe circuit and power equipment in the power distribution network.
SPECIFICATIONS
PGV2
PGV3
AUXILIARY
PGV2 BOX
MOTOR PROTECTION CIRCUIT BREAKER
B A-25
MOTOR PROTECTION CIRCUIT BREAKER
APPLICATIONS
PGV2 SERIES MOTOR PROTECTION CIRCUIT BREAKER
PGV2 series motor prote ct io n ci rc ui t breaker is mainly used for the overload and short circuit protection of the motor in AC 50/60Hz, up to 660V, 0.1-80A power circuit, as a full-voltage starter to start and cut off the motor, under the Ac3 load or for the overload and short circuit p rotection of the circuit and power equipment in the power distribution network.
SPECIFICATIONS:
PMS325 typeRated current:0.1upto 25ARated operation voltage: 660VACFrequency:50/60HzThe same usage as PGV2 model
TypeStandard power ratings of 3-phase
Setting range
PGV2-ME01/RS01
PGV2-ME02/RS02
PGV2-ME03/RS03
PGV2-ME04/RS04
PGV2-ME05/RS05
PGV2-ME06/RS06
PGV2-ME07/RS07
PGV2-ME08/RS08
PGV2-ME10/RS10
PGV2-ME14/RS14
PGV2-ME16/RS16
PGV2-ME20/RS20
PGV2-ME21/RS21
PGV2-ME22/RS22
PGV2-ME32/RS32
220V
KW
--
--
--
--
--
--
0.37
0.75
1.1
2.2
3
4
5.5
5.5
7.5
380V
KW
--
--
--
--
--
0.37
0.75
1.5
2.2
4
5.5
7.5
11
11
15
415V
KW
--
--
--
--
--
--
0.75
1.5
2.2
4
5.5
9
11
11
15
440V
KW
--
--
--
--
0.37
0.55
1.1
1.5
3
4
7.5
9
11
11
15
500V
KW
--
--
--
--
0.37
0.75
1.1
2.5
3.7
5.5
7.5
9
11
15
18.5
660V
KW
--
--
--
0.37
0.55
1.1
1.5
3
4
7.5
9
11
15
18.5
26
0.1-0.16
0.16-0.25
0.25-0.4
0.4-0.63
0.63-1
1-1.6
1.6-2.5
2.5-4
4-6.3
6-10
9-14
13-18
17-23
20-25
24-32
PGV2-MEwith water proof box
PMS325
PGV2 -ME
PMS325
B A-26
MOTOR PROTECTION CIRCUIT BREAKER
1.05le1.2le12le
TypePoleRated current(A)Rated Voltage(V)Rated Insulation Voltage(V)
Current Setting Range(A)
Power ofControlledMotor(KW)
4Mechanical(1 10 )
220V380V660V
ProtectiveFeature
P3VE13
20660660
P3VE33
32660750
P3VE43
63660750
0.1~0.16 0.16~0.250.25~0.4 0.4~0.63
0.63~1 1~1.61.6~2.5 2~3.22.5~4 3.2~54~6.3 5~8
6.3~10 8~12.510~6 14~20
1~1.6 1.6~2.52.5~4 4~6.3
6.3~10 8~12.510~16 12.5~2016~25 22~32
3.6~10 10~1616~25 22~3228~40 36~5045~63 45~56
5.5101310
9162610
1832583
Not Act Within 2hrsAct Within 2hrs
Action Snap
P3UV MOTOR PROTECTION CIRCUIT BREAKER
APPLICATION
The product is suitable to be used in circuit of rated voltage up toAC 660V 50/60Hz, rated current from 0.1A to 63A. It is applicable for protection of overload & short circuit of 3 phase squirrel-cagemotors. It also can be used as direct starter to start the motor and a switch for changeover the circuitunder normal conditions.
SPECIFICATIONS
Type
P3UV1300
P3UV1600
Current Setting Range(A)
0.1~0.16,0.16~0.24,0.24~0.4,0.4~0.6,0.6~1,1~16,1.6~2.4,2~3.2,2.4~4,3.2~5,4~6,5~8,6~10,8~13,10~16,14~20,18~25
1~1.6,1.6~2.4,2.4~4,4~6,6~10,10~16,16~25,22~32,28~40,36~52,45~63
P3VE MOTOR PROTECTION CIRCUIT BREAKER
APPLICATION
SPECIFICATIONS
P3VE Motor protection circuit breaker is suitable in AC circuit of 50H z or 60Hz, voltage up to660V and current up to 0.1~63A and used to prevent small capacity motor and circuits fromoverload and short circuit.It can be also used as direct starter for starting the motor and a switch forchangeover the circuit under normal conditions.
P3UV1300
P3UV1300
P3VE1
P3VE1
B A-27
P3VE1
K
W
Thermaltripping
electromagnetictripping
400200100
50302010
5321
402010
5321
0.5
0.20.1
0.05
0.020.01
0.0051.2 2 3 4 6 8 10 15 30 60 100
50 0.2460max
83
4.2 75max
7.5
61
111m
ax
PM611-16
50 0.2460max
83
4.2 75max
7.5
68
111m
ax
7
PM611-40
Rated current(A)Rated fixed current(A)
Rated current(A)Rated fixed current(A)
Rated current(A)Rated fixed current(A)
0.160.1~0.16
0.250.16~0.25
0.400.25~0.40
0.630.40~0.63
1.00.63~1.0
1.61.0~1.6
2.51.6~2.5
4.02.5~4.0
6.34.0~6.3
106.3~10
169.5~16
2013~20
2519~25
3220~32
4030~40
6340~63
PM611 MOTOR PROTECTION CIRCUIT BREAKER
APPLICATION
This product is suitable for using in circuit up to AC 660V or 440V and c urren t 0.1 to 6 3A.Itcan be used for protection of overload and short circuit of 3-phase squirrel-cage motors, andstarters of motors as well at full voltage. It is suitable to protect the motor with under voltage trip.It can also be used in operating AC single phase load or DC load. It can monitor the fuse of switchdisconnector to act as protection of phase failure. This prod uct includes basic t ype switch and 26 accessories with purposes of expanding usage. It complies with standard of IEC60947-2.
SPECIFICATIONS
CHARACTERISTIC CURVE
DIMENSIONS
PM611
PM611Enclosed type
MOTOR PROTECTION CIRCUIT BREAKER
PM611
PM611
B A-28
CPLC2-388 THRU CPLC2-3961/2POLE CONTACTORS (30A THRU 40A)
•••••••••••••••••• •••••••••••••••••••••••••••••••••••••••••••••••••••
••••••••••••••••••••••••••••••••••••
FEATURES
SPECIFICATIONS
•••••••••••••••••••••••••••••••••••••••••••••• ••
••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••
••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••
Temperature RangeMechanical Life (no load)Electrical Life
Weight (approximate)Coils FrequencyCoil InsulationTerminationOperate
Duty Cycle
o o-40 F to 150 FConforms to UL and ARI specificationsConforms to UL and ARI specifications94-388 thru 94-390 achieve 200,000 cycles, make LRAat. 5 pf, break 125% of FLA at. 75 pf at rated voltage, 10000 cycles make and break LRA at.5 pf at rated voltage94-394 thru 94-369 achieve 100,000 cycles, make LARat.5 pf at rated voltage 6,000 cycles make and breakLEA at .5 pf at rated voltage9.25 oz50/60 HzClass B (130 )Screw and Double• Q.C.85% of nominal coil voltage;110% maximum safe operateContinuous
COIL DATA
Type Number30 Amp 40 Amp
CPLC2-388 CPLC2-394CPLC2-389 CPLC2-395CPLC2-390 CPLC2-396
VoltageAC
Ress DCOHMS
CurrentMA
NominalVA
Max. InrushVA
24120
208/240
16.5420
1825
2084221
555
202020
Voltage277480600277480600
FLA LRA RESTypeCPL2-388
thruCPL2-390CPL2-394
thruCPL2-396
303030404040
1507550
20010080
404040505050
CONTACT RATINGS
2.4452.514
0.215TYP.41.625
2.000
0.87
51.
625
2.31
3
1P/20-40A
1P/20-40A
AC CONTACTOR
CPLC2
B A-29
CPLC2-244 THRU CPLC2-2522 POLE CONTACTORS (30A THRU 40A)
FEATURES
SPECIFICATIONS
Designed for Air Conditioning and Heating Equipment
Low VA coil for cooler operation and increased life. Quiet operation. Universal style mounting bracket fits existing mounting holes. Double break contacts ensure positive make and break. Screw terminals or pressure connectors and double••quick connects provided
on all models for easy installation.
Insulating Material
Temperature RangeMechanical LifeElectrical LifeWeight (approximate)Coils FrequencyCoil InsulationTerminationOperate
Duty Cycle
Contact block and carrier are high quality electrical-grade thermosetting resin
o o-40 F to 150 FConforms to UL and ARI specificationsConforms to UL and ARI specifications9.5 oz50/60 HzClass B (130 )Pressure connector and Double• ••••••••• ••••••• ••••••••••••••••••
•••• •• •••• •• •••••••••••••
••••••••••
COIL DATA
CONTACT RATINGS
Type Number30 Amp 40 Amp
CPL2-244 CPL2-247CPL2-245 CPL2-248CPL2-246 CPL2-249
VoltageAC
Res DCOHMS
CurrentMA
NominalVA
Max. InrushVA
24120
208/240
11224997
2505025
666
323232
Voltage277480600277480600
FLA LRA RESTypeCPL2-244
thruCPL2-246CPL2-247
thruCPL2-252
303030404040
1507550
20010080
404040505050
0.215TYP.41.625
2.000
0.87
5
1.62
5
2.31
3
2.4452.610
2P/20-40A
2P/20-40A(advanced)
AC CONTACTOR
CPLC2
B A-30
CPLC2-160 THRU CPLC2-1723 POLE CONTACTORS (25A THRU 40A)
FEATURES
SPECIFICATIONS
Designed for Air Conditioning and Heating Equipment
CONTACT RATINGS -25 and 30 Amp, 600 Volt Three Pole Normally Open (3 P.N.O.)
Any position mounting. Interchangeable mounting plate. Low voltage coil. Double break contacts ensure positive make and break.
Insulating Material
Temperature RangeMechanical LifeElectrical LifeWeight (approximate)Coils FrequencyCoil Insulation
TerminationOperate
Duty Cycle
Contact block and carrier are high quality electrical-grade thermosetting resin
-40 F to 150 FConforms to UL and ARI specificationsConforms to UL and ARI specifications16 oz50/60 HzClass B (130 )24 through 208/240 Volts ACPressure connector and Double• Q.C.85% of nominal coil voltage;110% maximum sate operateContinuous
COIL DATA -25 and 30 Amp, 600 Volt Three Pole Normally Open (3 P.N.O.)Type Number
25 Amp 30 AmpCPLC2-160 CPLC2-163CPLC2-161 CPLC2-164CPLC2-162 CPLC2-165
Coil Voltage AC(60 Hz)
Res DCOHMS
CurrentMA
NominalVA
Max. InrushVA
24120
208/240
7.2180720
1873719
4.54.54.5
525252
COIL DATA -40 Amp, 600 Volt Three Pole Normally Open (3 P.N.O.)
VoltageFull Load
Lock RotorResistiveFull Load
Lock RotorResistive
Type
CPLC2-160thru
CPLC2-162
CPLC2-163thru
CPL2-165
277 VAC25 A.
150 A.40 A.30 A.
180 A.50 A.
480 VAC25 A.
125 A.40 A.30 A.
150 A.50 A.
600 VAC25 A.
100 A.40 A.30 A.
120 A.50 A.
Type VoltageFull Load
Lock RotorResistive
277 VAC40 A.
240 A.50 A.
CPLC2-170thru
CPLC2-172
480 VAC40 A.
200 A.50 A.
600 VAC40 A.
160 A.50 A.
Type Number40 Amp
CPLC2-170CPLC2-171CPLC2-172
Coil Voltage AC(60 Hz)
Res DCOHMS
CurrentMA
NominalVA
Max. InrushVA
24120
208/240
525252
4.54.54.5
1873719
7.2180720
3P/30,40A
3P/30,40A
AC CONTACTOR
CPLC2
CPLC2
B A-31
CPLC2-459 THRU CPLC2-4733 POLE CONTACTORS (50A/90A)
FEATURES
SPECIFICATIONS
Interchangeable mounting. Double break contacts.
Coils, Voltages A.C.Coils, FrequencyCoils, TerminationContacts, Pole FormContacts, MaterialContacts, Termination
24 through 24050/60 Hz
1Single or Double / Q.C.4
3 PNOSilver cadmium oxide (50-90 amp)Box lugs and dual quick connect
COIL CHARACTERISTICSInductFLA50607590
FrequencyHz.
50/6050/6050/6050/60
Max. Inrush Sealed (Max.)VA
240/204240/204
300300
Watts100.8/84100.8/84
120120
VA50.4/36.550.4/36.5
2626
Watts10.8/810.8/8
8.58.5
StevecoModel Number
CPLC2-459CPLC2-460CPLC2-461
CoilVolts24V
120V208/240V
InductFLA
50 Amp50 Amp50 Amp
ResistivePer Pole65 Amp65 Amp65 Amp
LockedRotor
@ LineVoltage
300 Amp300 Amp200 Amp200 Amp
120V240V480V600V
StevecoModel Number
CPLC2-463CPLC2-464CPLC2-465
CoilVolts24V
120V208/240V
InductFLA
60 Amp60 Amp60 Amp
ResistivePer Pole75 Amp75 Amp75 Amp
LockedRotor
@ LineVoltage
360 Amp360 Amp300 Amp240 Amp
120V240V480V600V
StevecoModel Number
CPLC2-467CPLC2-468CPLC2-469CPLC2-471CPLC2-472CPLC2-473
CoilVolts24V
120V208/240V
24V120V
208/240V
InductFLA
75 Amp75 Amp75 Amp90 Amp90 Amp90 Amp
ResistivePer Pole90 Amp90 Amp90 Amp
120 Amp120 Amp120 Amp
LockedRotor
@ LineVoltage
450Amp375 Amp300 Amp450 Amp450 Amp360 Amp
240V480V600V240V480V600V
3P/50,60A
3P/75,90A
AC CONTACTOR
CPLC2-50/3
CPLC2-75/3
B A-32
FUSE
E
People Electric Appliance serves for people.
• ISO14001 OHSAS18001ISO9001
NT H.R.C LOW VOLTAGE FUSE
TECHNICAL SPECIFICAITONS
6
10
16
20
25
32
35
40
50
63
80
100
125
160
80
100
125
160
200
224
250
125
160
200
224
250
300
315
355
400
315
355
400
425
500
630
800
1000
1.03
1.42
2.45
2.36
2.7
3.74
4.3
4.7
5.5
6.9
7.6
8.9
10.1
15.2
6.2
7.5
10.2
13
15.2
16.8
18.3
9
11.5
15
16.6
18.4
21
19.2
24.5
26
21.7
22.7
26.8
28.9
32
40.3
62
75
500,600
500,600
500,600
500,600
500,600
500,600
500,600
500,600
500,600
500,600
500,600
500,600
500
500
500,600
500,600
500,600
500,600
500,600
500
500
500,600
500,600
500,600
500,600
500,600
500,600
500,600
500,600
500,600
500,600
500,600
500,600
500,600
500
500
380
380
Fuse link Fuse base
Type Ratedcurrent
(A)
Ratedvoltage
(V)
Ratedpower loss
(W)
Weight(kg)
Weight(kg)
Ratedcurrent
(A)Type
NT0
NT1
NT2
NT3
NT4
0.2 Sist 100 160 0.32
0.36 Sist 201 250 0.8
0.65 Sist 401 400 1.2
0.85 Sist 601 630 1.5
1.95 Sist 1001 1000 3.45
FUSE
Puller
B E-01
NT00C
NT00C
H. R. C. FUSE
RT18-63X 1P
RT18-32 3PRT18-32X 1P
FUSE
RT18-63X 2P RT18-63X 3P
B E-02
RT18-32X 2P
PRT18-32 1P PRT18-32 2P PRT18-32 3P
PSF 1P PSF 2P PSF 3P
FUSE
50KAcos 0.1-0.2kg=
50kAcos 0.1-0.2=
50kAcos 0.1~0.2=
Dimensionmm Rated current(A) L Hamx C
(MM)
8.2
10.5
13.8
16.2
16.2
8.5 0.1
10.3 0.1
14.3 0.1
22.2 0.1
30 0.1
8.5 31.5
10 38
14 51
22 58
30 58
2,4,6,10,16,20,25,32
2,4,6,10,16
2,4,6,10,16,20,25,3240,50,63
63,80,100,125
10,16,20,25,32 ,40,50,63,80,100
31.5
31.5
51
58
58
00.6
0.60610
0120
0120
APPLICATIONS
FUSE LIND
RL6 FUSE
CYLINDRICAL FUSE
The fuses with fuse links hav ing cylindrical contact caps are designed for protecting
electrical distributing installations of rated voltage of 380V AC,with rated current up to 125A
against damage due to overload and short circuit current.
Fuse links with the stricker are su ppli ed for pu rpos e of pro tecti ng motors against motor single
phasing operation when fitted in fuse isolators.
TECHNICAL SPECIFICATIONS
RL6-63RL6-25RL6-16ND
RL-16ND
500V
25A
1,2,4,6,10A
35X35X70mm
0.15kg
RL6-25
500V
25A
2,4,6,10,16,20,25A
66X43X80mm
0.20kg
RL6-63
500V
63A
35,50,63A
89X54X82mm
0.35kg
Model
Rated voltage
Rated current of fuse
Rated current offusant
Rated breakingcurrent
Overalldimensions
Weight
SPECIFICATION
E33 63A 3PE27 25A 3P
B E-03
KR-2P-30A KR-4P-30A
RT10 RT32 RT16 RT32-1
FUSE
KR-4P-63A
HRC-100-B HRC-63 HRC-100
BS 60N FUSE BS 100N FUSE BS 100N-1P+N FUSE
HRC-100/C
FUSE
B E-04
DIMENSION
Switch RatingHeat Current(A)
Number ofPoles
AssortedFuse
2,3,4
160250400630
NT00NT1NT2NT3
Rated Current(A)
4,6,10,16,20,25,32,35,40,50,63,80,100,125,16080,100,125,160,200,224,250
125,160,200,224,250,300,315,355,400315,335,400,425,500,630
ModelHR17-160/20HR17-250/20HR17-400/20HR17-630/20HR17-160/30HR17-250/30HR17-400/30HR17-630/30
Assorted FuseNT00NT1NT2NT3
NT00NT1NT2NT3
A106184210256106184210256
B73
128145175200243288300
C82.5111.5128
142.582.5111.5128
142.5
D456680
94.5456682
94.5
E151
214.5255267151
214.5255267
HR17 FUSE DISCONNECTOR
a
HR17-250A~630A
b
c
d
e
a
c
bf
d
HR17-160A
214 128
HR17BModel
HR17B-160/10HR17B-250/10HR17B-400/10HR17B-630/10
HR17B-1250/10
FuseNT00NT1NT2NT3NT4
A200290290290345
B50
100100115127
C128214214214235
D192280280280410
E3035353550
F30303035
232150
HR17
HR17B
204
142178
28095
192
290
250
35 25 140
30
40AB
200
120
30
310 27
016
05031
0
203050
185
HR17B-160~630/10 HR17B-1250/10
HG2B
SPECIFICATIONS
HR17
FUSE
B E-05
MINI CIRCUITBREAKER
A
People Electric Appliance serves for people.
• ISO14001 OHSAS18001ISO9001
APPLICATION
DZ47-63 MINI CIRCUIT BREAKER
DZ47-63 series circuit breaker is used in lighting distribution system or motor distribution systemfor protecting overload and short-circuit in the system. The product novel in structure, light in weight, reliable and excellent in performance. It has high breaking capacity, can trip quickly andits instal lation uses with guide, its case and items are adopted with high fire-resistant and shockproof plastic. The product, with long life, is mainly used in AC 50/60Hz single-pole 240V or two, three, four-pole 415V circuit for overload and short-circuit protection as well as for unfrequent on-and-offswitching electric equipment and lighting circuit in normal case. This product conform with GB10963,IEC60898, BS3871.
MINI CIRCUIT BREAKER
• A-01
SPECIFICATIONS
Rated temperature 40
Rated voltage 240V/415V AC
Rated current (C): 1, 2, 3, 4, 5, 6, 10, 15, 16, 20, 25, 32, 40, 50, 60, 63A (D): 6,10, 15, 16, 20, 25, 32, 40A
Mechanical endurance lower than 20000 times
Tropical test: 2 kinds
Weight (g)1P
102
2P
208
3P
308
4P
408
Standard
BS3871-1IEC60898
Rated current (A)
1 to 40
Pole
1
2, 3, 4
Voltage (V)
240
415
220/2401
Breaking capacity (A)
6000
6000
4000
400/4152, 3, 4 4000
DZ47-63
DIMENSIONS
DZ47-63 4P
DZ47-63 3P
DZ47-63 2P
DZ47-63 1P
60003
60003
60003
60003
50 to 63
APPLICATION
RDX65-63 MINI CIRCUIT BREAKERMINI CIRCUIT BREAKER
RDX65-63 1P
RDX65-63 2P
RDX65-63 3P
RDX65-63 4P
TECHNICAL SPECIFICATIONS
DIMENSIONS
The RDX65-63 is an all new high performance current limiting device with the ability to disconnect short circuits of up to 6KA. They have protective function as shortage as overload, and are used in lighting distribution system in industy, commerce and dwelling, and protecting frac-tional electric motors. And they also have many merits of high protective grade (up to IP20), high breaking capacity, reliable sensitive action, convenient, multipole assembing, long life etc. They are mainly adapted to the circuit of AC 50Hz, 230V in single pole, 400V in double, three, four poles for protecting overload and short-circuit. Meanwhile, they are also used in turning on oroff the electric apparatus and lighting circuit under the normal condition.
1P, 2P, 3P, 4P
230/400V
(0-C) not less than 6000 times
1, 2, 4, 6, 10, 16, 20, 25, 32, 40, 50, 63A
IP20
(IEC60898): 6KA
Pole
Rated voltage
Mechanical and electrical life
Rated current
Protective grade
Breaking capacity
60003
60003
60003
••••••••
••••••••
• A-02
APPLICATION
RDX2-100 MINI CIRCUIT BREAKER
The product used to protect line-conductor and overload, and short-circuit of small sealedmotors, is mainly for protection of circuits with AC 220V and 50/60Hz, and for unfrequent conversion under normal conditions as well. Its action can be as up to 22-pole with it s only one pole volume and it can be used as a leakage breaker by assembling with leakage.
MINI CIRCUIT BREAKER
SPECITICATIONS
RDX2-100 1P
RDX2-100 3P
RDX2-100 4P
RDX2-100 2P
DIMENSIONS
220~415V
40, 50, 63, 80, 100A
10KA (IEC60947)
6000 times
27mm
IEC60898, GB10963-89 BS 3871
Rated voltage
Rated current
Breaking capacity
Mechanical and electrical life
Width pole
According to standands
Rated voltage (V)Rated current (A) Breaking capacity (A)
40
50
63
80
100
Pole numher (P)
1
2, 3, 4
120
230/240
400/415
230/240
400/415
440
20000
10000
4000
20000
10000
6000
• A-03
240415240415
220/240220/240380/415220/240220/240380/415220/240220/240380/410220/240220/240380/410220/240220/240380/410
Standard Rated current(A)
BS3871-1IEC60898
1 to 4050 to 63
50 to 63
1
3
10 to 40
50
63
1 to 40
1 to 40
Pole Voltage(V) Breaking capacity(A)
Standard Rated current(A) Pole Voltage(V) Breaking capacity(A)
IEC157-1
BS3871-1IEC60898
IEC157-1
12,3,4
12,3,4
12,3,42,3,4
12,3,42,3,4
12,3,42,3,4
12,3,42,3,4
12,3,42,3,4
12,3,4
12,3,42,3,4
6000600040004000
1000020000100008000
2000080007000
1600080006000
1000060005000
100005000
APPLICATION
PC1-63 MINI CIRCUIT BREAKER
PC1-63 series circuit breaker is used in lighting distribution system or motor distribution system for protection overload and short-circuit in the system. The product is neoteric in structure,ligth weight, reliable and excellent in performance. It has high breaking capacity, can trip quickly,and its case and items are adopted by high fire-resis tant and s hockproof plastic. The product, withlong life, is mainly used in AC 50Hz/60Hz single-pole 240 or two, three , f our -po le 415V c ircuitfor overload and short-circuit protection as well as un freq ue nt o n- an d- off sw itch ing e lectricequipment and lighting circuit in normal case. The products comply with IEC 60898 & BS 3871.
SPECIFICATIONS
Setting temperature of protective characteristics at 40 Rated Voltage:240V/415V Rated current:1,3,5,6,10,16,20,25,32,40,50,63A Electrical life: no less than 6000 operations Mechanical life:(O-C) no less than 20000 operations
CHARACTERISTIC CURVE & DIMENSIONS
1000050002000
500200100
502010
521
0.50.20.1
0.050.020.01
0.0050.0020.001
0.5 1 2 3 4 5 710 20305070100200i/in
Therma tripping
Electromagnetic tripping
1000
t(s) TYPE C
1000050002000
500200100
502010
521
0.50.20.1
0.050.020.01
0.0050.0020.001
0.5 1 2 3 4 5 710 20305070100200i/in
Therma tripping
Electromagnetic tripping
1000
t(s)TYPE D
short circuit prospective short-circuitcurrent peak value
prospectiveshort-circuit encrgy
Current-limiting peak valueCurrent-limiting
0 2ms 10msShort-circuit energy times
4p3p2p1p
7254
3618
7.5
35 27
L
7040
77 45
240415
220/240220/240380/415
400040006000
120006000
PC1-63
PC1-63
PC1-63
MINI CIRCUIT BREAKER
PC1-63 1P
PC1-63 2P
PC1-63 3P
• A-04
PBKN MINI CIRCUIT BREAKER
APPLICATION
SPECIFICATIONS
PBKN series circuit breaker is used in lighting distribution system or m otor distr ibutionsystem for protection overload and short-citcuit in the system. The product is neoteric in struc ture,light in weight, reliable and excellent in performance. It has high breaking capacity,can trip quickly,and its case and items are adopted by high fire-resistant and shockproof plastics. The product, withlong life, is mainly used in AC 50Hz/60Hz single-pole 230V or two, three, four-p ole 400V ci rcuitfor overload and short-circuit protection as well as unfreque nt o n-an d-of f sw itch ing el ect ricequipment and lighting circuit in normal case. The products comply with IEC 60898.
Number of PolesRated Current (A)Breaking Capacity (A)Rated Voltage (A)Rated Frequency (Hz)EnduranceCircumstance TemperatureElectrical LifeMechanical LifeProtection Degree
1P,2P,3P,4P1,2,34,6,10,16,20,25,32,40,50,63
6000230/400
50/604000
-5 to +40no less than 6000 operations
(O-C) no less than 20000 operationsIP20
CHARACTERISTIC CURVE
Short circuit prospective short-circuitcurrent peak value
prospectiveshort-circuit energy
Current-limiting peak valueCurrent-limitingShort-circuit energy times
0 2ms 10ms
18 0.9 36 1.25 54 1.5 72 1.5 72.5
35.5
100005000
1H20001000
500200100
502010
521
0.50.20.1
0.050.020.01
0.0050.0020.001 0.5 1 2 3 4 5 7 102030 50 70100200 I/IR
B type 3-5InC type 5-10InD type 10-14In
t(s)
PBKN
PBKN
PBKN
MINI CIRCUIT BREAKER
PBKN 1P
PBKN 2P
PBKN 3P
• A-05
APPLICATION
DXM3 (DPN) MINI CIRCUIT BREAKERMINI CIRCUIT BREAKER
SPECIFICATIONS
DXM3 (DPN)
The product used to protect line conductor and overload, and short-circuit of small size motors,
is mainly for protection of circuits with AC 220V and 50/60Hz, and for unfrequent conversion
under normal conditions as well. Its action can be up to 2 poles with its only one pole volume and
can be used as a leakage breaker by assembling with leakage.
220/240V
2, 4, 6, 10, 16, 20, 25,32A
4500A
6000 times
P+N=18mm
IEC60898, GB10963-89 BS 3871
Rated voltage
Rated current
Breaking capacity
Mechanical and electrical life
Width pole
According to standands
TECHNICAL DATA
Pole NO: 1, 2, 3, 4
Rated current (A): 16, 25, 40, 63, 80, 100, 125
Rated voltage: 230/400V AC
Rated frequency: 50/60Hz
Usage category: AC22
Rated withstand current: 1800A within 1 secretary
Electro-mechanical endurance: 10,000 cycles2 Connection capacity: rigid conductor 35mm
Connection terminal: pillar terminal with clamp
Installation: on symmetrical din rail 35mm
panel mounting
HL32-100 2P
HL32-100 ISOLATING SWITCH
APPLICATION
Having superior dynamic-heating ability, it is mainly used as a main switch for both terminal
assembly electric equi pment case , and illu mination assembly case, and to control various motors
and small power electric equipment as well, it has no function of protection of over loas short-circuit.
••••
• A-06
TECHNICAL SPECIFICATIONS
RDX6-63 MINI CIRCUIT BREAKERMINI CIRCUIT BREAKER
ACCESSORIES
TECHNICAL SPECIFICATIONS
RDX6-63 1P
RDX6-63 2P
RDX6-63 3P
RDX6-63 4P
Pole: one pole, two poles, three poles, four poles
Rated voltage: 110/230/400V
Rated frequency: 50/60Hz
Rated short-circuit lnterrupting capacity: 10KA
Electric endurance: In the case of Un, In and COS=0.90 and the 63A and below, it is eight-
thousand times of cycles; in the case of 80A to 100A, it is 1500 times of cycles (Each times of
cycle includes one time of making operation and one minute of breaking operation).
Voltage endurance: Power frequency voltage endurance 2000V (1 min), pulse voltage endurance
(1.2/50 s).
Impact resistance performance: Withstand the impact of 10ms and 20g at least 18 times, and
withstand the impact of 5ms and 40g at least 18 times, and withstand the shake of 10~55Hz at
least half an hour.
Storage temperature : According to chapter one section two IEC60898 (for a duration of 96 hours)
-55 ~+55
Working environment temperature:-5 ~+452 2 Wiring capabillty: 63A and below: 25mm and below for soft wire and 35mm and below for
hard wire.2 2 80A~100A: 35mm and below for soft wire and 50mm and below for hard wire.
DC application: 1A~63A: rated breaking breaking capability: 6KA; maximum voltage: single
pole 60V; dual-pole series 110V; 80A~125A; rated short-circuit breaking capability: 10KA;
maximum.
Voltage: dual-pole series 125V; four-pole series 250V; transient tripping current is high about
40% compared with the case of 50/60Hz.
Shunt trip
Auxilliary contact
Contact with alarm indication
Under voltage trip
According to standard: 63A less than: IEC60898 GB10963 80~100A: IEC947-2 GB14048.2
Modular design: width of 18mm or 27mm (125A case grade) at different environment condition.
Selection of rated current according to the temperature adjustment curve.
Free tripping mechanism: In the case of short circuit and overload, the circuit breaker would
automatically trip. Before the failure eliminates, the circuit would refuse to switch againg
even the hand handle at the close position to avoid the intentional switching of the failure circuit
mistakenly.
Transient tripping performance: B-type performance: 3~5In;
C-type performance: 5~10In
D-type performance:10~20In
• A-07
MINI CIRCUIT BREAKERMINI CIRCUIT BREAKER
PL71 1P PL71 2P PL71 3P
PH7 3PPH7 2PPH7 1P
ISOLATING SWITCH
PDB6 PDB7-FL
••• ••• •••
••• ••••••
• A-08
7.5
35 27
L
100005000
1H2000
500200100
502010
521
0.50.20.1
0.050.020.01
0.0050.0020.001
0.5 1 2 3 4 5 7 10 20 305070100 200I/IR
B typeC typeD type
APPLICATION
PMT PMY PMC MINI CIRCUIT BREAKER
PMT PMY PMC mini circuit breaker is mainly suitable for overload and short circuitprotection. It is especially used for illumination and distribution in industry and commerce. It is of pleasing outlook & high breaking capacity etc. Its frame and parts adopted plastics of light weight, reliable performance, high inflammable resistance and shock resistance for long serv ice l ife, I t is mainly used for overload and short-circuit protection within the circuit of AC 50/60Hz, rated voltage of single pole up to 240V, two, three or four poles u p to 415V. It can al so be u sed for an unfrequent switchover of the circuit and illumination under normal conditions.
SPECIFICATIONS
MCB typeCurrent rating
CHARACTERISTIC CURVE & DIMENSIONS
MINI CIRCUIT BREAKER
1P
2P
3P
PMT PMY PMC
6-40A 6-63A 2-63A
Tripping curveB: 3-5InC: 5-10InD: 10-20In
Breaking capacityEN 60898 & IEC 60898IEC 947-2NEMA AB-1
Rated voltage - 50/60Hz
Isolating voltage
Electrical endurance
C
4.5KA6KA10KAIC
230/400V
500V0.5 or 32A 20,000 operations 40 to 63A 10,000 operations
B C
6KA10KA22KAIC
6KA10KA22KAIC
PM14 1P PM14 2P PM14 3P
• A-09
PE90/91 MINI CIRCUIT BREAKER
APPLICATION
Safety terminal: - easy wiring - no wrong fixing - protection degree Ip20.
Slot screw head. Torque up to 4.5 N.m.
Incoming/outgoing terminal capacity up to 35mm2.Terminal side for fork busbar is isolated between the poles.MCB s and RCCB s can be connected with PIN type busbar at the top
terminals.MCB s and RCCB s can be connected with PIN type busbar at the
bottom of terminals, with easy DIN-rail extraction.MCB s and RCCB s can be connected with FORK type busbar at the
bottom of terminals, with easy DIN-rail extraction.Auxiliary contacts can be added on the left side of the MCB.
PERFORMANCES
Thermal setting InRated voltage AC UnMinimum operating voltage UB minTripping characteristicsSelectivity classMechanical/electrical enduranceTropicalisation acc.to IEC 60068-2Terminal capacity flexible/rigid cablePolesWeightThermal operating limit
(A)(V)(V)
(mm2)
(g/pole)
2-40240/41512B-C320000/1000095%RH at 5525-351, 2, 3, 4120(1.13-1.45) InB: (3-5) InC: (5-10) In
Magnetic operating
MINI CIRCUIT BREAKER
PE91 1P
PE91 2P
PE91 3P PE90 1P PE90 2P PE90 3P
• A-10
PSX MINI CIRCUIT BREAKER
PSX mini circuit breaker is mainly suitable for overl oad a nd sh ort-c ircui t protection. It is especially used for illumination and distributi on in i ndust ry and commerce, e tc. It has pl easingoutlook & high breaking capacity, reliable performance, high inflamable re sistance and shock resistance for long service life. It is within the circuit of AC 50/60Hz, rat ed volt age o f sin gle pole up to 240V, two ,three or four-poles up to 415V. It can also be used for an unfrequent changeoverof the circuit and illumination under normal conditions.
SPECIFICATIONS
Ratedcurrent
(A)Pole
Ratedvoltage
(V)
Breakingcapacity
(A)
Electricallife
(times)
Mechanicallife
(times)
1,2,3,4,6,10,16,
20,25,32,40
1
2,3,4
1
2,3,450,63
6000
6000
6000
6000
240
415
240
415
8000 6000
CHARACTERISTIC CURVE
100005000
1H20001000
500200100
502010
521
0.50.20.1
0.050.020.01
0.0050.0020.001
0.5 1 2 3 4 5 7 10 20 30 50 70 100 200 1/1R
typeB3-5InC5-10InD10-14In
type
type
DIMENSIONS
18 0.9 36 1.25 54 1.5 72 1.5
APPLICATION
MINI CIRCUIT BREAKER
PSX 1P
PSX 2P
PSX 3P
• A-11
1P M5
18
44 6
4587
4461
2P
87 87 8787
3P 3P+N
1P+N
3654
36 72
1836
N
StardandRated voltageRated current InAmbient tempertureTripping curveRated short-circuit interrupting capacityRated running short-circuit interrupting capacityMechanical lifeElectrical lifeFixTerminal (the side of ON)Terminal (the side of OFF)Bus.tApplied wireReleasing method of overloadAccessories
GB10963, IEC60898230/400VAC, 50/60Hz6,10,13,16,20,25,32,40,50,63A-10~40B,C,D6kA6kA80008000Track of 35mm of IECNon-weld tin terminalNon-weld tin terminal/terminal with mouth0.7-1.5mm
21-.2.5mmThermal-coil magneticInsulation-board
APPLICATION
PBH-D6 MINI CIRCUIT BREAKER
PBH-D6 products of domestic power distribution box have come out. The high-quality and high-function circuit breaker used in domestic power distribution box is looking forward to your selectionand application.
FUNCTION
All the machines meet the standards of IEC and GB. They can be installed in the track or 35mm of IEC. They have the function of high current limit. Protective grade:IP2x
SPECIFICATIONS
DIMENSIONS
MINI CIRCUIT BREAKER
PBH-D6 1P
PBH-D6 2P
PBH-D6 3P
• A-12
PP11 HIGH BREAKING CAPACITY MINI CIRCUIT BREAKER
SPECIFICATIONS
PP11 1P
PP11 2P
PP11 3P
Conform to standard of electrical
Rated voltage(V)
Rated breaking capacity
Short circuit breaking capacity of DC
Performance
Max.fuse that can be connected to
Selective grade
Working ambient temperature
Enclosed protective class
Electrical Life
Mechnical Life
EN60898(IEC60898)GB10963-99
230V/400V; 50/60Hz
10KA IEC60898(0.5~63A)15KA IEC60947-2(0.5~63A)
Max.48v(XYDB7...,10KA)single poleMax.250V(XYDB7-DC,6KA)single pole
C,D charactisistic curve
100AgL(>10KA)
3
-5 to +40
P40(Under mounting)
No less of 8000 times switching operation
No less of 20000 times switching operation
The length of exposed plane
Enclosure height
Enclosure width
Mounting manner
Terminal manner
Terminal block capacity
45mm
80mm
17.5mm per pole(single pole)35mm:1P+N(two pole)
Used for track of 35mm of IEC standard
Two-function terminal can connect with rubber and conducting wire
Wire 1-25mm2 Conducting wire 0.8-2mm
MINI CIRCUIT BREAKER
• A-13
PET1-68 MINI CIRCUIT BREAKER
APPLICATION
PET1-68 Mini circuit Breaker is used in lighting distribution system or motor distribution system for protection overload and short-circuit in the system. This product is neoteric in structure, light weight, reliable and excellent in performance. They are applicable to circuit with rated voltage not exceeding 400V, rated current not exceeding 63A.
SPECIFICATIONS
Type No:
Number of poles:
Rated Voltage
Rated Current In
Frequency(F):
Tripping Characteristics:
Conform to standard of electrical:
Electrical life:
Mechanical life:
PET1-68
1P,2P,3P,4P
230/400VAC
6,10,16,20,25,32,40,50,63A
50/60Hz
B,C curve
EN60898, IEC60898
No less than 6000 operations
No less than 20000 operations
PET1-68 1P
PET1-68 2P
PET1-68 3P
100005000
1H20001000
500200100
502010
521
0.50.20.1
0.050.020.01
0.0050.0020.001 0.5 1 2 3 4 5 7 102030 50 70100200 I/IR
B type 3-5InC type 5-10InD type 10-14In
t(s)
CHARACTERISTIC CURVE
MINI CIRCUIT BREAKER
• A-14
APPLICATION
PBKM MINI CIRCUIT BREAKER
The design on the base of the current-limiting device increases the capability of cir-cuit breaking, with a max.of 7.5KA(AC 220V standard) The super-miniature and light product leaves the installation area minimum. The overcurrent protection of bimetal sheet and the instantaneous and short-circuit protection featuring solenoid trip produce a perfect protection to current fault. The assembly mode of DIN-Rail makes the installation easier. Delicate appearance of Europe-style Available to fit such accessories as auxiliary switch(AX) and alarm switch, etc.
SPECIFICATIONS
Series
Type
Poles
Rated voltage (V)
Rated current (A)
Breaking capacity(KA)
Tripping device
PBKM
B
1 2 3
6,10,16,20,25
10
C
1 2 3 4
230/400
2,4,6,10,20,25,32,40,50
6
G
1 2 3
6,10,15,20,30,40,50
6
Thermal-coil magnetic
Auxiliary switch & alarm switch
Rated operational current
AC 11 duty
Mechanical life
Thermal capacity
Weight
220V 3.5A
400V 2A
No less than 2000 operations
0.75, 2.5mm
0.04kg/EA
DIMENSIONS CHARACTERISTICS OFTIME-CURRENT CURRENT CURVES
According to standard track of 35mm of IEC 715
45
3580
6843
24.4
7.3
5.3
59.5
65
B
2N100
40
10
4
1402010
521
200
50
20
52
1.5 2 3 5 10 30
IEO 898
BS 3871-P1
Mim
utes
Seco
nds
Mill
isec
onds
PBKM
PBKM
PBKM
MINI CIRCUIT BREAKER
PBKM 1P
PBKM 2P
PBKM 3P
• A-15
List NoFP
PMCH401PMCH402PMCH404PMCH406PMCH408PMCH410PMCH413PMCH416PMCH420PMCH425PMCH432PMCH440PMCH450PMCH463
APPLICATION
PMB MINI CIRCUIT BREAKER
SP MCB s can be used in type A distribution boards. SP,DP and TP MCBs can be used in type B distribution boards. SPSN and DP MCBs can be used in DP distribution boards. TPSN and FP MCBs are for specialist OEM applications.
PMB MCB-TYPE B TO BSEN60898(IEC60898),3 TO 5 X IN
RatingA
List NoSP
List NoSPEN
List NoTP
List NoDP
List NoTPSN
List NoFP
12468101316202532405063
PMBH101PMBH102PMBH104PMBH106PMBH108PMBH110PMBH113PMBH116PMBH120PMBH125PMBH132PMBH140PMBH150PMBH163
PMBH101NPMBH102NPMBH104NPMBH106NPMBH108NPMBH110NPMBH113NPMBH116NPMBH120NPMBH125NPMBH132NPMBH140NPMBH150NPMBH163N
PMBH201PMBH202PMBH204PMBH206PMBH208PMBH210PMBH213PMBH216PMBH220PMBH225PMBH232PMBH240PMBH250PMBH263
PMBH301PMBH302PMBH304PMBH306PMBH308PMBH310PMBH313PMBH316PMBH320PMBH325PMBH332PMBH340PMBH350PMBH363
PMBH301NPMBH302NPMBH304NPMBH306NPMBH308NPMBH310NPMBH313NPMBH316NPMBH320NPMBH325NPMBH332NPMBH340NPMBH350NPMBH363N
PMBH401PMBH402PMBH404PMBH406PMBH408PMBH410PMBH413PMBH416PMBH420PMBH425PMBH432PMBH440PMBH450PMBH463
PMC MCB-TYPE C TO BSEN60898(IEC60898), 5 TO 10 X IN
12468101316202532405063
PMCH301NPMCH302NPMCH304NPMCH306NPMCH308NPMCH310NPMCH313NPMCH316NPMCH320NPMCH325NPMCH332NPMCH340NPMCH350NPMCH363N
PMCH301PMCH302PMCH304PMCH306PMCH308PMCH310PMCH313PMCH316PMCH320PMCH325PMCH332PMCH340PMCH350PMCH363
PMCH201PMCH202PMCH204PMCH206PMCH208PMCH210PMCH213PMCH216PMCH220PMCH225PMCH232PMCH240PMCH250PMCH263
PMCH101NPMCH102NPMCH104NPMCH106NPMCH108NPMCH110NPMCH113NPMCH116NPMCH120NPMCH125NPMCH132NPMCH140NPMCH150NPMCH163N
PMCH101PMCH102PMCH104PMCH106PMCH108PMCH110PMCH113PMCH116PMCH120PMCH125PMCH132PMCH140PMCH150PMCH163
List NoTPSN
List NoTP
List NoDP
List NoSPEN
List NoSP
RatingA
FEATURES
PMB MCBs are available with a breaking capacity of 10KA to BSEN60898.The MCBs are calibrated to 40 .MCBs can be supplied with 50 ambient calibration. To order insert X at the endof the MCB list number eg:-MCH 116X.Please contact our Technical Services department for details of PMB MCBs suitablefor other reference calibration temperatures.
PMB 1P
PMB 2P
PMB 3P
• A-16
MINI CIRCUIT BREAKER
MINI CIRCUIT BREAKER
APPLICATION
PH6 mini circuit breaker applies to electromagnet ic de sign which possesses the functions of overload and short-circuit protection. It is widely used for illumination and distribution in industry and commerce. Because of its characters of pleasing outlook, light weight, reliable performance, high breaking capacity for rated current under 63A(6KA)and for rated current from80A to 125A, the capacity is 10KA, easy and clearly for operation etc. It complies with the standardof IEC60898.
SPECIFICATIONS
Character I/In Standard Ratedcurrent(A) Poles(P) Rated
voltage(V)Breaking
capacity(A)
BCD
BCD
3~5In5~10In10~20In
3~5In5~10In10~20In
IEC60898GB10963
IEC60898GB10963
2,4,6,1016,20,2532,40,50,63
80A100A125A
1
234
1
234
230/240
400/415V
230/240
400/415V
6000
6000
10000
PE4CB 1P PE4CB 2P PE4CB 3P
PH6 1P
PH6 2P
PH6 3P
• A-17
MINI CIRCUIT BREAKER
MINI CIRCUIT BREAKER
PC2-63 1P PC2-63 2P PC2-63 3P
MINI CIRCUIT BREAKER
PC30N 1P PC30N 2P PC30N 3P
PS230 1P PS230 2P PS230 3P
PK5SXPK5SX
PK5SX
PK5SX 1P PK5SX 2P PK5SX 3P
• A-18
DIN RAIL ACCESSORIES
MN1
SB-140 SB-240 SB-340
SF-119G SF-219G SF-319G
E8PT1-10D S101 S101-N
DIN RAIL ACCESSORIES
PS-KEP510
• A-19
MODULAR SIGNAL LAMP
P-D LED Singal Lamp
PZ47D Neon Signal Lamp
APPLICATION
The Modular Signal Lamp is applicable to circuit with rated voltage 230V~ and frequency 50/60Hz for visual indication and signaling.
Low service duration, minimum power consumption Compact design in modular size Easy installation
Rated voltage: 230V AC Rated frequency: 50/60Hz Colour: red, green, yellow Connection terminal: pillar terminal with clamp Connection capacity: rigid conductor 10mm2 Installation: On symmetrical DIN rail Panel mounting
Max power: 0.6W Illumination: LED Service duration: 30,000 hours
Max power: 1.2W Illumination: Neon bulb Service duration: 15,000 hours
OVERALL & INSTALLATION DIMENSIONS
36
MODULAR SIGNAL LAMP
SV1-Y SV1-G SV1-R SV1-B
SV2-G SV3 SV4-NSV2-R
• A-20
DIN RAIL ACCESSORIES
PLP-10 PLP-11
G2PT F2PT
AC10-1P AC10-2P AC16-2P AC25-3P
OF SD MX+OF
TMS-5
MX+OF+A
T68
DIN RAIL ACCESSORIES
SU213
• A-21
APPLICATION
HYDRAULIC MAGNETICMINI CIRCUIT BREAKER
Hydraulic magnetic mini circuit breakers are mainly suitable for overload and short circuitprotection . It adopted hydraulic magnetic trip instead of bimetal. So it has a high sensitivity and it is also not effected by the ambient temperature. It is especially used for illumination and distribution in industry and commerce. They are mainly used for overload and short circuit protection within thecircuit of AC 50Hz/60Hz, rated voltage of single pole or doub le poles up to 240V, three poles up to 415V. They can also be used for an unfrequent switch-over of the circuit and illumination undernormal conditions. They comply with IEC 157-1973 BC 4752-1977 and BS 3871.
CHARACTERISTIC CURVE
Maximum
Maximum
1000
100
10
1
10
1
0.1
0.01
0.00
MIN
1 1.5 2 3 4 5 10 20 30 40 50
Maximum
Maximum
1000
100
10
1
10
1
0.1
0.01
0.00
MIN
1 1.5 2 3 4 5 10 20 30 40 50
SF3-G3SF2-G3SA3-G3
SA2-G3
SA1-G3
MINI CIRCUIT BREAKER
SF2-G310A
• A-22
HYDRAULIC MAGNETIC MINI CIRCUIT BREAKER
SPECIFICATION
CHARACTERISTIC CURVE
Maximum
Maximum
1000
100
10
1
10
1
0.1
0.01
0.00
MIN
1 1.5 2 3 4 5 10 20 30 40 50
Maximum
Maximum
1000
100
10
1
10
1
0.1
0.01
0.00
MIN
1 1.5 2 3 4 5 10 20 30 40 50
Standard
IEC157-1973
BC4752-1977
BS3871
Rated current(A)
3,5,6,10,16,
20,25,32,40,
50,63
Poles(P)
1
2,3
Ratedvoltage(V)
230/240
400/415
6000
6000
3000
3000
Breaking capacity(A)
SX1-G3SF-G3SA-G3
TQA-3P
TQA-2P
SX2N-3P
SX2N-1P
SX3SX2SX1
MINI CIRCUIT BREAKER
• A-23
MINI CIRCUIT BREAKERMINI CIRCUIT BREAKER
PME-1P PME-2P PME-3P
BH-1P BH-2P BH-3P
BH-P 1P BH-P 2P BH-P 3P
BH-S 1P BH-S 2P BH-S 3P
• A-24
MINI CIRCUIT BREAKERMINI CIRCUIT BREAKER
PTHQC 1P PTHQC 2P PTHQC 3P
PTHQL1 -1P PTHQL1 -2P PTHQL1 -3P
M3 AM6 AM6 1P
F1
HQP -1P
X5 P05 P06
PTHQL 1/2
••
• A-25
PolesRated voltage Ui(V)
Rated current(A)
Rated leakage operating current
Rated leakage dead current
Leakage operating time
Mechanical and electrical endurance
2P
AC 240V
30A
15mA 30mA
7.5mA 15mAST<0.1
>4000 times
APPLICATION
NT-50 SAFETY BREAKER
NT-50B
NT-50Z
NT-50 series safety type mini circuit breakers features lively machine, excellent quality, beautifulapperance, small volume. The product is suitable for AC 50Hz, rated vol tage up to 240V, ratedcurrent up to 32A, it is used for protection of the overload and short circuit of all kinds of modernfamily applicable apparatus. It can also be used for unfrequently operating and controlling.
Rated Voltage(V)
Rated Current(A)
Rated capacity of short-circuitBreaking(KA)
No.of pole(P)
220
6,10,16,20,25,32
1.5
2
CONFIGURATION AND MOUNTING DIMENSIONS
103 EARTH LEAKAGE CIRCUIT BREAKER
APPLICATION
103 Series earth leakage circuit breaker is suitable for the circuit of AC 50/60Hz, rated voltage250V, and rated current up to 30A, It can cut off the circuit immediately on the occasion of shockhazard and fire caused by earth leakage. And it is especially used in household and pubic building.And this product conform with GB16916. 1/IEC1008.1.
SPECIFICATIONS
32
71 62
35.5
26.5
38
54
2- 4
CIRCUIT BREAKER
NT-50W
103
• A-26
7.5A
10A
15A
20A
25A
30A
0 5 10 15 20 255
7.5
10
15
20
25
30
4.75
7.13
9.5
14.25
19
23.75
28.5
4.5
6.75
9
13.5
18
22.5
27
4.25
6.28
8.5
12.75
17
21.25
25.5
4
6
8
12
16
20
24
3.75
5.63
7.5
11.25
15
18.75
22.5
VOLTFREQUEUCYAMP. RANGEI.C. at 380V~
380V~60 Hz3.75 30A2KA
CHARACTERISTICS GENERAL CHARACTERISTICS
NUMBER OF PHASES
16011601N-1601NI-1611N-1611NI16021602N16031603NTEMPERATURETERMINAL SIZE
1P
1P+N2P2P+N3P3P+N0-40
26MM
thermomagnetic tripping characteristicreferred to a 20 C ambietn ermperature(starting from cold)
410
310
210
110
010
-110
-210
-3100,8 2 3 4 5 7 10 20 30 40 60 100 200
multiple of rated current
timei
nse
cond
s
MAIN SWITCH
601 602 603
1601
1602
1603
MAIN SWITCH
• A-27
DESCRIPTION:
CONNECTION:
Designation Rating (Amps) Pack Qty. Cat. No.
Acting as weather-protect isolating switches for outdoor and wet/ dusty envi ronment, Available with switched control
2 2 A Max 10 mm incoming cable, internal cable 1.5 mm Conduit entry through 1xM25 threaded entry on top and bottom 2xM25. M20 is possible throughreducers provided.
Conform to IEC 60947-3, BS 1363: Pt2Suitable for 13A 3-pin plug complying to BS 1363: Pt1Rated 13A, 250V AC 50Hz Switches pad lockable in 'OFF' positionHigh impact, UV Resistant polycarbonate material degree of protection: IP55 / IP66
Approval: CE, pantented design
TECHNICAL PARAMETER:
Double pole withsocket outlet IP55
20A with 13A socket oulet 1 66CV313N
Double pole withsocket outlet IP66
20A with 13A socket oulet 1 66CV313
20A with 15A socket oulet 1 66CV315Double pole withsocket outlet IP66
WEATHER-PROTECT ISOLATING SWITCHWEATHER-PROTECT ISOLATING SWITCH
• A-28
DESCRIPTION:
CONNECTION:
Designation Pack Qty. Cat. No. Rating (Amps)
Acting as weather-protect isolating switches for outdoor and wet/ dusty environment.
Conform to BS 1363: Pt2 Suitable for 13A 3-pin plug Complying to BS 1363: Pt1 Rated 13A, 250V AC 50HzHigh impact, UV Resistant polycarbonate material degree of protection: IP55 / IP66
Approval: CE, pantented design
TECHNICAL PARAMETER:
Max 2.5 sq. mm 3C flexible cable or rigid cable. Conduit entrythrough 1xM25 threaded entry on top and bottom 2xM25. M20 is possible through reducers provided.
Unswitched socket outlet IP55
13A socket outlet 1 66SO313N
Unswitched socketOutlet IP66
13A socket outlet 1 66SO313
Unswitched socketOutlet IP66
15A socket outlet 1 66SO315
Isolating SwitchIP66
2 pole 20A
3 pole 20A
2 pole 32A
3 pole 32A
1
1
1
1
66SW220
66SW320
66SW232
66SW332
WEATHER-PROTECT ISOLATING SWITCHWEATHER-PROTECT ISOLATING SWITCH
• A-29
20A35A45A63A20A32A45A63A20A35A45A63A20A32A45A63A20A35A45A63A20A32A45A63A
TECHNICAL PARAMETER:
DESCRIPTION:
CONNECTION:
Designation Rating (Amps) Pack Qty. Cat. No.
Acting as an weather-protect isolating Switch in all types of circuit as defined in the IEE regulation. Using high impact strength, UV, resistast polycarbonate.
Conform to IEC 60947-3 Rated Voltage: 240/415VAC Rated Frequency: 50 Hz/60HzNumber of Pole : 2 poles, 3 poles & neutral, 4 polesDegree of protection: IP56 / IP66Utilization category: AC 22A/ AC 23A High impact, UV Resistant polycarbonate
Approval: CE, pantented design
2Max: 25mm connection capacity.Conduit entry through 2XM25 threaded entries or 2XPG16/2XM25 threaded entries on top and bottom. Pg21 entries available upon request
HPS
HPM
1
1111111
HPS220HPS235HPS245HPS263HPM220HPM232HPM245HPM263
Double Pole
Triple Pole& neutral
Four Pole
HPS320
HPS420
HPS335
HPS435
HPS345
HPS445
HPS363
HPS463
HPM320
HPM420
HPM332
HPM432
HPM345
HPM445
HPM363
HPM463
1
1111111
1
1111111
WEATHER-PROTECT ISOLATING SWITCHESWEATHER-PROTECT ISOLATING SWITCHES
• A-30
Category
Rated voltage :
Max. continuous operating voltage Uc(V)
Voltage protection level Up(Kv)
Norminal discharge current In(kA)
Rated varistor voltage(V)
Max. discharge current Imax (kA)(8/20uS)
Response time (ms)
Power withstand (J) (2ms)
Ambient temperature
Function unit colour2Min. terminal connection (mm ):
Un
PS1-A
220
320
1
5
510 10%
10
300
PS1-B
220
320
1.2
10
510 10%
20
390
PS1-C
220
320
1.5
20
510 10%
40
640
PS1-D
380
420
2.0
30
680 10%
60
1500
PS1-E
380
460
2.3
40
680 10%
70
1580
<25
deep yellow light yellow light grey brown red
phase, neutral 2.5, earth 4
-40~+80
PS1 SURGE PROTECTIVE DEVICE
DESCRIPTION
PS1 Surge Protec tive Device (referred as SPD) provides protection against surge current resulted from direct or indirect lightning strike or similar surge voltage. SPD is applicable to circuit with rated voltage up to 400V~, rated frequency 50/60Hz.The product, using metal oxide varistor, designed to protect both phase and neutral line, is of high electricity resistance under normal operations. In case of surge curre nt or vol tage caused by lightning strike or similar, SPD functions quickly to conduct the surge voltage/current to earth and thus effectively prevent the downstream equipments of its protected lin e from destr uction. SPD resumes its high electricity resi stance to secure normal operation of the protec ted power networkwithout presence of the surge voltage.
TECHNICAL DATA
CONSTRUCTION AND FEATURE
Pole No. : 1 2 3 4 Frequency: 50/60Hz Connection terminal: Pillar terminal with clamp
On-Off indicating window:Green: normal function Red: functionless, immediate replacement required
2Connection capacity: rigid conductor 25mm
Plug-in type function unit makes easy replacement On-off indicating window Quick response less than 25ms
OVERALL & INSTALLATION DIMENSIONS
SURGE PROTECTIVE DEVICE
• A-31
PS1-B SURGE PROTECTIVE DEVICE
Type
Rating Voltage Un(V~)DC Voltage U1 mA(V~)
Max.Working
Max.available
Clamping currentlsn(8/
Max.Clamping currentlsnResponse time t(ns)Energy(2000 s)(A)Temperature
ColorModule
BaseMaterial of case
5
10
25200A
-40 ~+80GreyGrey
Nylon
Uc~Uc~
Is=1KAIs=5KA
Is=10KA
PS1-B/1 PS1-B/1 PS1-B/1 PS1-B/2 PS1-B/3 PS1-B/4
7512075
1000.240.3
0.35
1102001301700.390.450.5
2205103204150.91.01.0
2205103204150.91.01.0
3806304205601.21.51.7
3806304205601.21.51.7
DESCRIPTION
PS1-B Surge Protective Device can be used in the entrance of the low tension power supply net of220V,380V to protect the electrical appliance against damage from the pulse voltage.
TECHNICAL DATA:PS1-B/4-385-30
PS1-B/4-385-40
PS4-60/4-385
PS4-80/4-385 PS4-100/4-385 PS1-C/2QB
SURGE PROTECTIVE DEVICE
• A-32
PS1-C SURGE PROTECTIVE DEVICE
SPECIFICATIONS
Type
Rating Voltage Un(V~)
DC Voltage U1 mA(V~)
Max.Working
Max.available
Uc~
Uc~
Is=1KA
Is=5KA
Is=10KA
Is=15KA
Is=20KA
Is=30KA
Is=40KA
Is=60KA
Clamping current lsn(8/20
Max.Clamping currentIsn(8/
Response time t(ns)
Energy(2000 s)(A)
Temperature
ColorModule
Base
Material of case
PS1-C/1 PS1-C/2 PS1-C/3 PS1-C/4 PS1-B/4
220
510
320
415
0.9
1.0
1.2
1.3
1.4
1.9
220
510
320
415
0.9
1.0
1.2
1.3
1.4
1.9
380
680
420
560
1.2
1.5
1.7
1.8
1.9
2.6
380
680
420
560
1.2
1.5
1.7
1.8
1.9
2.6
380
510
320
415
1.0
1.1
1.3
1.4
1.9
2.6
20 30
40 60
25
200
-40 ~+80
Grey Orange
Nylon
Grey
PS1-C/2-320-20
PS1-C/4-420-20
PS1-C/2+1-320-20
PS1-C/3+1-320-20X PS1-D/2-320-5 PS1-D/4-320-5
SURGE PROTECTIVE DEVICE
• A-33
Type
Rating Voltage Un(V~)DC Voltage U1 mA(V~)
Max.Working
Max.available
Clamping currentlsn(8/
Max.Clamping currentlsnResponse time t(ns)Energy(2000 s)(A)Temperature
ColorModule
BaseMaterial of case
5
10
25200A
-40 ~+80GreyGrey
Nylon
Uc~Uc~
Is=1KAIs=5KA
Is=10KA
PLY1-D/1
7512075
1000.240.3
0.35
1102001301700.390.450.5
2205103204150.91.01.0
2205103204150.91.01.0
3806304205601.21.51.7
3806304205601.21.51.7
Type
Rating Voltage Un(V~)DC Voltage U1 mA(V~)
Max.Working
PLY1-C/2
Max.available
Uc~Uc~
Is=1KAIs=5KA
Is=10KAIs=15KAIs=20KAIs=30KAIs=40KAIs=60KA
2205103204150.91.01.21.31.4
1.9
2205103204150.91.01.21.31.4
1.9
3806804205601.21.51.71.81.9
2.6
3806804205601.21.51.71.81.9
2.6
3805103204151.01.11.31.4
1.9
2.6Clamping current lsn(8/20
Max.Clamping currentIsn(8/Response time t(ns)Energy(2000 s)(A)Temperature
ColorModule
BaseMaterial of case
20 30
40 60
25200
-40 ~+80Grey Orange
NylonGrey
PLY1 SURGE PROTECTIVE DEVICE
APPLICATION
PLY1 Surge protective Device can be used in the entrance of the low tension power supply net of220V,380V to protect the electrical appliance against damage from the pulse voltage.
TECHNICAL DATA:
SPECIFICATIONS
PLY1-D/1 PLY1-D/1 PLY1-D/2 PLY1-D/3 PLY1-D/4
PLY1-C/2 PLY1-C/3 PLY1-C/4 PLY1-C/4
PLY1-D/1
PLY1-D/2
PLY1-D/3
PLY1-D/4
SURGE PROTECTIVE DEVICE
• A-34
PL15OVER-VOLTAGE/UNDER-VOLTAGE DELAY PROTECTOR
MAIN TECHNICAL INDEX
Full-automatic under-voltage protection Input power delay output Whole normally automatic recovery Electrical net high voltage protector
works normally Reliable work and long service life
DESCRIPTION
PL15 household full-automatic under-voltage delay protector is a new generation of
household electrical equipment protector, made by our company according to current city power
condition. The control circuit is made up of imported element s. The product is made according to
modularization standard. It is of excellent and reliable performances and can work normally under
abnormal voltage. When the city power voltage exceeds protector action voltage. The protector will
cut off the power quickly and reliably so as to protect electrical equipmen t and body safety. When
the city power voltage recovers normal value, the protector will cut off the power automatically and
recover to supply the power. All the functions will be conducted full automatically without manual
operation. Double color LED on the panel can indicate the working status o f protecto r. The power
is supplied normally when the indicator light is green. The protection function starts and cuts off the
power when the indicator is red.
This series of product is of compac t str uctur e and b eautiful appearance. The installation
can be conducted with DZ47(C45N) ge neral guide . This product is in great demand in market.
The demander can contact with us through telegram or correspondence.
1.Rated AC voltage 220V and frequency 50Hz
2.Passing Max Current:20A 32A 40A(resistance)
3.Max.Loading power:4.4KVA 6.6KVA 8.8KVA
4.Over-voltage action cut-off value:260-270VAC
5.Over-voltage recover value:248 5VAC
6.Under-voltage action cur-off value:180 5VAC
7.Under-voltage recovery value: :170 5VAC
8.Electricity transmitting delay after cur-off:2~3minutes
9.Action delayed time:1~6 seconds
10.Self power consumption 2W
11.Electric machinery life 10
12.Dimension:80 50 66.5mm(Length Width Height)
DELAY PROTECTOR
• A-35
MOULDED CASECIRCUIT BREAKER
C
People Electric Appliance serves for people.
• ISO14001 OHSAS18001ISO9001
RDM1 MOULDED CASE CIRCUIT BREAKER
APPLICATION
RDM1 series of moulded case circuit breaker is a new type product developed and manufacturedby adopting international advanced technology. It is supplied with rated insu lation voltage 800V and used for circuit of AC50Hz, rated operating voltage AC 400V or below rated operation currentup to 800A for infrequent changing over and starting of the motors. Equipped w ith t he protectiondevices for over-current, short circuit and undervoltage, the product is capable of preventingdamage of circuits and supplying units The product conforms to IEC60947-2.
SPECIFICATION
TypeRated
current(A)
Num-ber ofPoles
Ratedinsula-
tionvoltage
(V)
Ratedoperat-
ingvoltage
(V)
Arcing-over
distance(mm)
Ultimateshort
circuitbreakingcapacity
(KA)
Serviceshort
circuitbreakingcapacity
(KA)
Operationperfor-mance
ON OFF
RDM1-63LRDM1-63MRDM1-100CRDM1-100LRDM1-100MRDM1-100HRDM1-225CRDM1-225LRDM1-225MRDM1-225HRDM1-400CRDM1-400LRDM1-400MRDM1-630CRDM1-630LRDM1-630MRDM1-630HRDM1-800MRDM1-800H
6,10,16,20,25,32,40,
50,63
10,16,20,25,32,40,50,63,80,
100
100,125160,180
200,
225,250315,350
400
400500630
630,700800
3P,4P 660V 380V
000
0( 50)0( 50)0( 50)
50505050505050
100100100100100100
25502535508525355085355065355065
10065
100
18351822355018223550253542253542654265
1500 8500
1000 7000
1000 4000
RDM1-63L 3P
RDM1-225L 3P
RDM1-400 3P
ACCESSORIES FOR MCCB
Alarm contact Under voltage release
Manual operation Auxiliary contact Shunt release
MOULDED CASE CIRCUIT BREAKER
A C-01
APPLICATION
RDM11 MOULDED CASE CIRCUIT BREAKER
RDM11 moulded case circuit breake r is one o f the most advanced type breakers i n the world, which adopts international advanced design and manufacture technology. They are suitable for shortcircuit and overload protection for circuit of AC 690V 50/60Hz, rated current from 12.5A to 630A.It takes protective effect when mouse cage motors non-fre quent star t, breakin g off working and protecting overload, short circuit and lacking voltage.
TRIPPING CHARACTERISTICS OF MCCB
Rated current of
release(A)
In 63
63 In 100
100 In 630
Thermodynamic release (ambient temp+40 )
1.05In(cold state)operative time (h)
1.30In(heat state)operative time (h)
1
2
2
1
2
2
Operational currentof magneticrelease(A)
10In 20%
10In 20%
5-10In 20%
Rated current of
release(A)
12.5 In 400
Thermodynamic release (ambient temp+40 )
2
1.0In(cold state)operativetime (h)
1.20In(heat state)operativetime (h)
1.50In(heat state)operativetime (h)
2 4min
7.20In(coldstate)
operativetime (h)
2S Tp 10S
Operational currentof magneticrelease(A)
12In 20%
SPECIFICATION
RDM11-100N 3P
RDM11-250N 4P
RDM11-630N 3P
Ratedcurrent
(A)Type Poles
Ratedinsulatingvoltage
(V)
Ratedoperatingvoltage
(V)
Arcingover
distance(mm)
Serviesshort
circuitbreakercapacity
Ultimateshort
circuitbreakercapacit
Operatingperfor-mance(times)
RDM11-100DRDM11-100NRDM11-100HRDM11-100LRDM11-160DRDM11-160NRDM11-160HRDM11-160LRDM11-250DRDM11-250NRDM11-250HRDM11-250LRDM11-400DRDM11-400NRDM11-400HRDM11-400LRDM11-630DRDM11-630NRDM11-630HRDM11-630LRDM11-1250DRDM11-1250NRDM11-1250HRDM11-1250LRDM11-1600DRDM11-1600NRDM11-1600HRDM11-1600L
12.5,16,20,25,32,40,50,63,
80,100
16,20,25,32,40,50,
63,80,100,125,160
160,180,200,225,
250
200,225,250,300,315,400
315,350,400,500,600,630
3,4 950 690 0
182570150253670150253670150354570150354570150506585160506585160
182570150253670150253670150354570150354570150506585160506585160
1500 8500
1500 7000
1000 7000
1000 4000
1000 4000
630,700800,1000,
1250
800,1000,1250,1600
500,2500
500,2500
MOULDED CASE CIRCUIT BREAKER
RDM11-250N
RDM11-100N
A C-02
PNE-100 2P
PNE-100 3P
PNE-250 3P
Type
Number of Poles
Rated Current In(A)
Rated Operating Voltage Ue(V) AC50/60Hz
Rated Insulation Voltage Ui(V)
Rated (kV)Uimp
Breaking Capacity
(kA ms)
IEC60947-2
Icu AC
220/240V
380V
400
220/240V
380V
400V
240V
480V
Ics%Icu
ACBreaking Capacity(kA)(NEMA-ABI)(HIC)
Mechanical Life
Electrical Life
OverloadCurrentProtection(A)
Hot protection
Magnetism protection
Dimensions(mm)
L H D
PNE 60E PNE 100F PNE 100H PNE 250
3 3 3 3
15,20,25,30,40,50,
60
15,20,25,30,40,50,60,75,80,
100
15,20,25,30,40,50,60,75,80,
100
125,160225,250
500
500
6
10
7.5
7.5
25%
25%
25%
-
-
8.500
4.000
Fixed
Fixed
500
500
6
25
10
7.5
25%
25%
25%
-
-
8.500
4.000
Fixed
Fixed
500
500
6
50
30
20
25%
25%
25%
25
10
8.500
4.000
Fixed
Fixed
500
500
6
85
18
15
50%
50%
50%
25
10
8.500
4.000
Fixed
Fixed
75 13060
75 13060
75 13060
105 16565
PNE MOULDED CASE CIRCUIT BREAKER
APPLICATION
PNE moulded case circuit break er is one of the most advanced type breakers in the world, which ado pts international advanced design and manufactur technology. They aresuitable for short circuit and overload protection for circuit of AC 690V 50 / 60Hz, rated currentfrom 15A to 160A. Its rated insulation voltage is 690V. It can make and break the non-frequen t c ircui t in the normal cond itio ns. It takes protective effect when mouse cagemotors no n-fr equent st arting or breaking off working and protecting overload, shortcircuit and lacking voltage. It complies with IEC60947-2.
MAIN TECHNICAL SPECIFICATION
MOULDED CASE CIRCUIT BREAKER
PNE-100
PNE-250
A C-03
RDM6-125 3P
RDM6-250 3P
RDM6-600 3P
RDM6 MOULDED CASE CIRCUIT BREAKER
APPLICATION
RDM6 Moulded case circuit breaker is suitable for circuit AC 50Hz/60Hz, rated voltage up to AC 660V,rated operating current to 630A. It features normal stru ct ur e, rel iab le per for man ce, com pleteaccessories & high breaking capacity, used for power distributi on an d pro tecti ng the c ircui t and electrical equipment against overload and short circuit. It complies with standard of IEC60947-2.
TRIPPING CHARACTERISTICS OF MCCB
Rated current of
release(A)
In 63
63 In 250
25 In 800
Thermodynamic release (ambient temp+40 )
1.05In(cold state)inoperative time (h)
1.30In(heat state)inoperative time (h)
1
2
2
1
2
2
Operational currentof magneticrelease(A)
10-50In 20%
10In 20%
5-10In 20%
SPECIFICATION
Ratedcurrent
(A)
Type
Ultimate short circuitbreaking capacity lcu
KARated
insulatingvoltage
Polenumber
Ratedoperatingvoltage
Service shortcircuit breakingcapacity lcu KA
AC380V(400)
AC660V(690) DC250V
AC380V(400)
AC660V(690)
RDM6-125E
RDM6-125S
RDM6-160S
RDM6-160H
RDM6-250S
RDM6-250M
RDM6-250H
RDM6-400S
RDM6-400M
RDM6-400H
RDM6-630S
RDM6-630M
RDM6-630H
RDM6-800S
RDM6-800M
RDM6-800H
1250S
1250M
1250H
1600S
1600M
1600H
12.5,16,20,25,32,40,50,63,80,100,
12516,20,32,40,50,63,80,100,125,160
100,125,160,180,200,225,
250
200,225,250,315,350,400
400,500,630
500,630,700,800
660Vtwo
threefour
380V660V
15
25
35
50
35
50
65
35
50
65
50
65
80
50
65
80
55
70
95
55
70
95
-
-
8
10
10
16
18
16
20
25
20
25
30
20
25
30
25
28
35
25
28
35
-
20
20
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
7.5
16
18
25
18
30
48
18
30
48
30
48
60
30
48
60
35
50
75
35
50
75
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
630,700,800,1000,
1250
800,1000,1250,1600,
RDM6-600
RDM6-600
MOULDED CASE CIRCUIT BREAKER
RDM6-125
RDM6-125
RDM6-250
A C-04
Type
RDM8(CW)-100
Rated current (A)
15,20,30,40,50,60,75,100,125
Pole number
3 pole
Rated operating voltage (V)
Rated operating voltage (V)
PT-125
PT-250
RDM8 125-CW
RDM8 250-CW
PT MOULDED CASE CIRCUIT BREAKER
APPLICATION
PT Moulded case circuit breaker is suitable for circuit AC 50Hz/60Hz, rated voltage up toAC 660V,rated operating current to 630A. It features normal structure, reliable performance, complete accessories & high breaking capacity, used for power dis tribut ion and protecting t he circu it and electrical equipment against overload and short-circuit. It complies with standard of IEC947-2.
TRIPPING CHARACTERISTICS OF MCCB
Rated current of
release (A)
In 63
63 In 250
25 In 800
Thermodynamic release(ambient temp+40 )
1.05In (cold state)operative time (h)
1.30In (heat state)operative time (h)
Operational currentof magneticrelease(A)
1
2
2
1
2
2
10-50In 20%
10In 20%
5-10In 20%
RDM8-CW MOULDED CASE CIRCUIT BREAKER
RDM8-CW moulded case circuit breaker is available in three ranges, standard, high-breaking capacity. The performance of the RDM8-CW MCCB range is the result of ex tens ive design& development utilising AAD accredited test station. The current limiting action fo RDM8-CWMCCB provi des low va lues of let-through energy. Full information for this and time/currentcharacteristic curves are both available on request to provide more information.
MOULDED CASE CIRCUIT BREAKER
660V 380V, 660VRDM8(CW)-250 125,150,175,200,225,250 3 pole 660V 380V, 660V
TRIPPING CHARACTERISTICS OF MCCB
Rated current of
release (A)
In 63
63 In 250
25 In 800
Thermodynamic release(ambient temp+40 )
1.05In (cold state)operative time (h)
1.30In (heat state)operative time (h)
Operational currentof magneticrelease(A)
1
2
2
1
2
2
10-50In 20%
10In 20%
5-10In 20%
RDM8 125-CW
RDM8 125-CW
A C-05
TypePole
Number(P)
Rated current(A)Rated
current offrame(A)
Rated ultimatebreaking capacity
(KA)
RDM8 30-CSRDM8 50-CSRDM8 60-CSRDM8 100-CSRDM8 250-CSRDM8 400-CSRDM8 630-CSRDM8 800-CSRDM8 1250-CS
32,33
2,333333
3,5,10,15,20,3010,15,20,30,40,50
6060,70,100
125,150,175,200,225,250250,300,350,400
500,600,630600,700,800
800,1000,1200,1250
305060
100250400630800
1250
1.55/105/10
18/2518/3525/50
353585
RDM8-CS MOULDED CASE CIRCUIT BREAKER
APPLICATION
RDM8-CS series Moulded Case Circuit Breaker is a kind of economic breaker, has the features as following, such as steady and reliable property, reasonable structure, beautiful style, small volume,etc. This breaker applies to the circuit with AC 50/60 Hz, r ated insulation voltage 660V, max.rated current 1250A as on-off operation, and take effect, it also can be used as unfrequent conversion of line and unfrequency.
SPECIFICATION
RDM8-SS MOULDED CASE CIRCUIT BREAKERAPPLICATION
SPECIFICATION
RDM8-SS series Moulded Case Circuit Breaker is a kind of economic breaker, has the features asfollowing, such as steady and reliable property, reasonable structure, beautiful style, small volume,etc. This breaker applies to the circuit with AC50/60Hz, rated insulation voltoge 660V, max .ratedcurrent 1250A as on-off operation, and take effect, it also can be used as unfrequent conversion ofline and unfrequency.
Type Polenumber
Rated current(A)
Breaking capacity(KA)
AC(P1/P2)
RDM8 30-SS
RDM8 50-SSRDM8 60-SS
RDM8 100-SS
RDM8 250-SS
RDM8 400-SS
RDM8 630-SS
RDM8 800-SS
23333434343434
3,5,10,15,20,30
10,20,30,40,5010,20,30,40,50,60
60,75,100
125,150,175,200,225,255
250,300,350,400
500,600,630
600,700,800
240 380 415 500 600 660
5/5 5/2.5 2.5/1.5 2.5/1.0
5/105/10
10/7.510/7.5
7.5/57.5/5
7.5/57.5/5
2.5/1.52.5/1.5
- -
--
50/42
50/42
85/60
85/60
85/60
30/20
30/22
50/35
50/35
50/35
7.5/8
25/15
25/20
50/30
50/30
15/10
18/15
35/25
35/25
35/25
10/5
15/10
25/18
25/18
25/18
5/2.5
5/2.5
15/10
15/10
15/10
RDM8 30-CS 3P
RDM8 100-CS 3P
RDM8 50-SS 3P
RDM8 250-SS 3P
MOULDED CASE CIRCUIT BREAKER
RDM8 30-CS
RDM8 100-CS
RDM8 50-SS
RDM8 250-SS
A C-06
Type Pole Rated current(A)Breakingcapacity
(KA)Rated voltage(V)
RDM7 32
RDM7 33
RDM7 52
RDM7 53
RDM7 62
RDM7 63
RDM7 102
RDM7 103
RDM7 202
RDM7 203
RDM7 403
2
3
2
3
2
3
2
3
2
3
3
3,5,10,15,20,30
3,5,10,15,20,30
15,20,30,40,50
15,20,30,40,50
60
60
60,75,100
60,75,100
125,150,175,200,225
125,150,175,200,225
250,300,350,400
1.5
1.5
2.5
2.5
2.5
2.5
7.5
7.5
10
10
18
415
415
600
600
600
600
600
600
600
600
600
Type Pole Rated current(A)Breakingcapacity
(KA)Rated voltage(V)
RDM7 32
RDM7 33
RDM7 52
RDM7 53
RDM7 62
RDM7 63
RDM7 103
RDM7 202
RDM7 203
RDM7 403
2
3
2
3
2
3
3
2
3
3
3,5,10,15,20,30
3,5,10,15,20,30
15,20,30,40,50
15,20,30,40,50
60
60
15,20,30,40,50,60,75,100
125,150,175,200,225
125,150,175,200,225
250,300,350,400
1.5
1.5
5
5
5
5
15
18
18
22
660
660
660
660
660
660
660
660
660
660
RDM7(EA\SA) MOULDED CASE CIRCUIT BREAKER
APPLICATION
The circuit breaker is suitable for industrial or commercial power and lighting circuit. Its ratedworking voltage is from 240V to 415V(AC 50Hz). It can be used to protect the ci rcuit that overload or short circuit may take place and also for protecting the circuit which is not frequent in makingbreak operation under normal conditions.
SPECIFICATION
RDM7 52B(SA52B)
RDM7 33B(SA33B)
RDM7 103B(EA103B)
MOULDED CASE CIRCUIT BREAKER
RDM7 103B
RDM7 33B
RDM7 52B
A C-07
PABS-D MOULDED CASE CIRCUIT BREAKER
APPLICATION
PABS-D series moulded case circuit breaker is suitable for industrial or commercial power andlighting with AC 50/60Hz, rated working volt age up to AC600V/DC 250V, rate d cu rrent up to 1200A. It s a kind of economical breakers with the ch aract ers of s table an d r eli abl e f unctio n,beautiful appearance, small size and line and infrequent starting motor. It can also be a ttachedto ins tall the accessor ies which have protection function for avoiding loss-voltage, under-vo ltage.The prod uct can inst all conn ection line with front board and back board, it also can be equipped hand-operating appar atus or mo tor-op erating apparatus to control in a remote distance.
SPECIFICATION
Number of poles
Max rated servicevoltage Ui (V)
Dim
ensionsandm
ountingdetails aa
ac
MOULDED CASE CIRCUIT BREAKER
PABS-103b
PABS-103b
PABS-203b
PABS-203b
PABS-403b
PABS-403b
A C-08
10,15,20,30,40,50,60,75,100
500V 600V
440V 480V
380V
220V 240V
3
600
250
90
155
56
82
132
30
10
14
25
50
10
14
14
25
50
20
14
-
-
-
-
-
-
-
-
Rated current in (A) 40 reference ambient temperature
3
600
250
105
165
56
84
126
30
10
14
25
50
10
14
25
25
50
20
14
3
600
250
140
257
95
145
215
44
22
25
35
50
22
25
35
35
50
20
14
125,150,175,200,225
250,300,350,400
Dim
ensionsandm
ountingdetails
GB14048-2 AC (No symmetry value/symmetry value)
IEC60947-2 Icu AC
DC
Connection way
Alarming switch (AL)Auxiliary switch (AUX)
Voltage release mounting (SHT)
Low voltage release mounting (UVT)Accessory lead wire terminal platform (LT)
Outer operate handle
Terminal isolation cover
Automatic tripping device
Trip button
AC
DC
a
b
c
ca
bb
aa
500V
440V
415V
380V
240V
250V
125V
Shoppingfitting
Press terminal
-
- Thermal electro-magnetism type
Have
b bb
ca
MCCB Description Standard rangeCurrent rating(A)
Standard range
16A20A32A40A50A63A80A
100A125A160A200A
1 poleList number
3 polesList number
PME161PME201PME321PME401PME501PME630PME801
PME1001PME1251PME1604
-
PME163PME203PME323PME403PME503PME633PME803
PME1003PME1253PME1603PME2003
Impulse withstand V.Utilisation categoryAdjustment thermal
Adjustment magneticTerminal capacity(Max)
8KVA
FixedFixed
120mm2
8KVA
FixedFixed
120mm2
Breaking capacity IEC60947 2/BS EN60947-2(AC 50/60Hz)
690V AC
480V AC
400V AC/440V AC
380V AC
220V AC/240V AC
250V DC
Icu (KA)Ics (KA)Icu (KA)Ics (KA)Icu (KA)Ics (KA)Icu (KA)Ics (KA)Icu (KA)Ics (KA)Icu (KA)Ics (KA)
--------
2519--
121220202525303040403719
PME-125 3P
PME-250 3P
PME MOULDED CASE CIRCUIT BREAKER
SPECIFICATION
PME moulded case circuit breaker is highly specified. Positive contact indication is standard,with three positions ON OFF and centre TRIPPED preventing the MCCB contactsfrom being held closed in the event of over current.
PME moulded case circuit breaker 3 & 1 pole units have a trip to test button provided a s st andard.All main contacts are of quality. Silve alloy construction for durability. Comply ing with IEC60947-2is covered by type test and marine approval certification.1. Moulded case circuit breakers 16 to 200A.2. Available in three ranges: standard, standard adjustable, Hi-break adjustable.3. Complies with IEC60947-2.4. Current limiting action provides low values of lot-through energy.
PME STANDARD RANGE
MOULDED CASE CIRCUIT BREAKER
A C-09
PAA MOULDED CASE CIRCUIT BREAKER
DESCRIPTION
PAA MCCB is Available in two frame sizes from 25 to 800 A. Loadline series of mouldedcase circuit breakers provide overload and short-circuit protection for the full range o f transf-orme r sizes encountered in normal service. The over load and i nstantaneo us trippin g elements,adjustable over a wide band, make these MCCBs ideal for many distribution applications. PAA MCCBs are available in single pole, three poles, three pol es with sw itched neu tral and switch-disconnector versions. Loadline triple poles PAA Frame circuit breaker and switch-disconnectorare physically interchangeable with PAA breakers for Motor Duty requirments. PAA Frame have front adjustable overload and fixed instantaneous tripping elements.
SPECIFICATION
TRIPPING ELEMENT
Insulation voltage(Ui)-660V acOperating voltage(Ue)-415 acRated frequency-~50/60HzReference Calibration-40 (50 on request)
Overload front adjustable 0.7-1.0 times rated currentInstantaneous-non-adjustable
PAA 25-63A=400A PAA 80-125A=800A PAA 160-250A=1600A
Description
25
32
40
50
63
80
100
125
160
200
225
250
315
400
500
630
800
In/A Lowest Setting Current amps
17.5
22.5
28
35
44
56
70
88
112
140
157.5
175
221
280
350
441
560
PAA-100
single pole MCCB
triple poles MCCB
PAA-250
PAA Frame
PAA-400
PAA-630
PAA-800
PAA 100 1P
PAA 250 3P
PAA 400 3P
MOULDED CASE CIRCUIT BREAKER
A C-10
PDPX-125N 3P
PDPX-250N 3P
PDPX MOULDED CASE CIRCUIT BREAKER
Pole numberRated current In(A)
Type
The electrical characteristic satisfiesEn60947 - 2Rated working voltageUe(50-60Hz)
Rated working voltage Ue=(V)Rated insulation voltage Ui~(V)Rated impulse voltage Uimp(KV)Usage groupMoulded case switch typeLimited breaking capacity(KA) 230/240V~
400/415V~440V~480/500V~600V~690V~250V
Used breaking capacity lcos(%Icu)Short-circuit closed capacity(400V~)Short-time withstand current Icw(KA)Life (open,close for a time) mechanical
ElectricalInsulation capacity
Protection groupHot-magnetic tripElectronic tripTake to connect the ground to breakDown to probe into the function s theHigh choice electronic-tripResidual currentprotected modules installation
Bottom
On the sideinstallation
Outer accessoriesControl from a distanceFix typeInsert typeDrawer typeScrew hand handlePower conversion systemDimension and weightDimension (L W H) (mm)
Weight(kg)
3 pole4 pole3 pole4 pole
PDPX 125 PDPX 250
PDPX-E PDPX PDPX PDPX PDPXPDPX-E
3-416-125
3-425-250
500
250500
6A
690
250690
8A
E2216108--
1610032
35251812--
2550
52.5
50362014--
3050
75.6
60363025201636
10075.6
L170100704025204050
220
H10070604025204075
154
7000
1000
7000
1000
75.6 120 74101 120 74
11.2
105 200 105140 200 105
2.53.7
MOULDED CASE CIRCUIT BREAKER
A C-11
DESCRIPTION
PVL-160X 3P
PVL-250X 3P
PVL MOULDED CASE CIRCUIT BREAKER
DESCRIPTION
TypeRated
currentIn(A)
Setting current ofinverse-time
delayed overloadrelease L I (A)R
Operating current ofinstantaneous short-circuit release I Ii
(A)
Standard switchingcapacity N 40/45/50kA
at 380/415V AC
PVL 160X
PVL250
20
32
40
50
63
80
100
125
160
200
255
16-20
25-32
32-40
40-50
50-63
63-80
80-100
100-125
125-160
160-200
200-250
300
300
600
600
600
1000
1000
1000
1600
1000-2000
200-2500
PVL1702-1DD33-...
PVL1703-1DD33-...
PVL1704-1DD33-...
PVL1705-1DD33-...
PVL1706-1DD33-...
PVL1708-1DD33-...
PVL1710-1DD36-...
PVL1712-1DD36-...
PVL1716-1DD36-...
PVL3720-1DD36-...
PVL3725-1DD36-...
Type
PVL 160X
High switching capacity H 70 kA
at 380/415V AC
Very high switching capacity L
100kA at 380/415V AC
PVL 250
PVL1702-2DD36-...
PVL1703-2DD36-...
PVL1704-2DD36-...
PVL1705-2DD36-...
PVL1706-2DD33-...
PVL1708-2DD36-...
PVL1710-2DD36-...
PVL1712-2DD36-...
PVL1716-2DD36-...
PVL3720-2DD36-...
PVL3725-2DD36-...
PVL3720-3DC36-...
PVL3725-3DC36-...
XXX
X
Z
Y Y
PVL 160 circuit-breaker
419
2411
106.590.58781.5
120.5 63.5
5831
.5
4-(250)d2.5-(160)
88.5
15.5 Y Y
35 35 35
PVL 160 and PVL 250circuit-breakers mounting detailPVL 250 circuit-breaker
17.56 5.2
75.5
140 174.5
115.5 Y
88.5
1224.5
104.5139.5
52.5
1632
1632
NSK
-884
0
NSK
-884
1
8
35 35 35 17.56 8.4
17.535
(3P)
7 13 5.5
75.5
174.5
185.514
913
11.5
24.5104.5
139.552.5
18(8) 70(4P)
19.5
6513
1.5
2 5.2(3P)4 5.2(4P)
MOULDED CASE CIRCUIT BREAKER
A C-12
A C-13
105 86
152
100
DESCRIPTION
PHFD MOULDED CASE CIRCUIT BREAKER
PHFD moulded case circuit breakers are the choice of designer for coordinate protection of all types of low voltage power distribution systems.
Description
Single pole MCCB
Triple poles MCCB
In/ARated isolating
voltage(V)
Rated capacity
(KA)
15
20
25
30
35
40
50
70
90
100
125
150
15
20
25
30
35
40
50
70
90
100
125
150
175
200
225
250
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
PHFD-250N 3P
PHFD-125N 3P
MOULDED CASE CIRCUIT BREAKER
A C-14
SPECIFICATION
PHB MOULDED CASE CIRCUIT BREAKER
Manufacture stardand:IEC60947-2Fixing type thermal tripFixing type magnetic trip
MAX. RATED SHORT-CIRCUIT BREAKING CAPACITY
PHB126HPHB226HPHB226NPHB226E
Hull
65kA35kA40kA
100kA
220/240VAC
25kA25kA40kA70kA
380/415VAC 660/690VAC
--
12kA14kA
250VDC*
10kA-
10kA20kA
Description Rated current(A)
MCCBMCCBMCCBMCCBMCCBMCCBMCCBMCCBMCCB
PHB226H-25kAMCCBMCCBMCCBMCCBMCCBMCCBMCCB
PHB126H-25kA1620253240506380
100
6380
100125160200225
PHB226N-40kA
Description
MCCBMCCBMCCBMCCBMCCBMCCBMCCB
PHB226E-70kAMCCBMCCBMCCBMCCBMCCBMCCBMCCB
6380
100125160200225
6380
100125160200225
Rated current(A)
ACCESSORY AND AUXILIARY EQUIPMENT
Revolve the hand handle the organizationLocks-AA auxiliary switch,2NO+2NC-UV Owe-voltage trip,415V~-SR Cent trip,240V~-UV2 Owe-voltage trip,240V~
80
72
80
126
101.
7
104.785.8
81
226
PHB-126 3P
PHB-226 3P
MOULDED CASE CIRCUIT BREAKER
PHB-126
PHB-226
A C-15
MOULDED CASE CIRCUIT BREAKER
PTCD\PEB\PQD Series moulded case c ircuit breaker is one of our new type productsdeveloped and manufactured by adopting international adv anced technology. It is supplied withrated insulating voltage 660V and used for circuit of A.C.50Hz, rated operati ng voltage AC 380V.(Or below), rated operati ng current up to 22 5A for infre que nt cha ngi ng ove r and starting of the motors. Equipped with the protection devices for over-cur rent, shor t-circ uit a nd under-voltage, the products are capable of preventing damage of circuits and supply units.
DIMENSIONS OF OUTLINE AND INSTALLATION (PQD)
SPECIFICATION
Model Pole Rated Current (A) Rated Insulation voltage
Rated operating voltage
PTCD
PEB
PQD
3 30,40,50,60,70,100
125,150,175,200,225
3
3
30,40,50,60,70,100 600V240V380V660V
PTCD-100 3P
PEB-100 3P
PQD-250 3P
243
183
6169
35
8
487
321 32
27 14
223 32
1116 1 8
3
11 3219 32
123 64
3 81 4
34
2532
5 329 16 23
1
1116
138
1116
138
9 323
4 81
2 141 1 1
142332 7 32
19 32
13
4
1 32
122 15
16
2 582 16
143 14
7
116
14 1
5 32
132
MOULDED CASE CIRCUIT BREAKER
PTCD-100
DESCRIPTION
Type
RDW1-2000
RDW1-32004000
RDW1-63004000/5000
RDW1-6300
Pole
3P
4P
3P
3P
4P
3P
4P
3P
L1
375
470
435
550
550
813
928
928
L2
335
430
395
510
510
773
888
888
L3
292
292
352
352
352
352
352
352
L4
356
360
325
440
440
703
818
818
L5
247
247
307
307
307
307
307
307
W1
421
494
W2
467
540
b
139
212
In A
10
15
20
30
20
30
RDW1-3200 could increase to 4000A,its installation dimension is same with RDW1-3200,4P
RDW1-2000 cable dimensionfor with drawable type
RDW1-3200 cable dimensionfor with drawable type
RDW1-3200 In=4000A RDW1-6300, In=4000A, 5000Acable dimension for with drawable type
RDW1-6300, In=6300Acable dimension for with drawable type
RDW1-2000
RDW1-3200
RDW1 AIR CASE CIRCUIT BREAKER
SCOPE OF APPLICATION
400~630
800~1600
2000~2500
3200~4000
4000
5000~6300
a
AIR CASE CIRCUIT BREAKER
A C-16
RDW1 AIR CASE CIRCUIT BREAKER
50kA/400V40kA/690V
50kA/400V40kA/690V
100kA/400V80kA/690V
80kA/400V60kA/690V
80kA/400V65kA/690V
100kA/400V80kA/690V
80kA/400V65kA/690V
80kA/400V65kA/690V
120kA/400V80kA/690V
100kA/400V70kA/690V
100kA/400V70kA/690V
It can be used as controlling and protecting Electric Power Distribution line & Net. It is normally installed in Low-Volt age Sw itc hge ar as main Switch for total protection. The technical performance of our goods have reached advanced level of same item in the world.
MAIN TECHNICAL PARAMETER
Frame classing rated current
Rated insulation voltage
Rated voltage
Rated current
Rated ultimate short-circuit breaking capacity(lcu)
Rated service short-circuit breaking capacity(lcs)
Rated withshand current for short-time(lcw)
Number of poles
Arcing distance
2000A 3200A 4000A 6300A
690V
400V
630A,800A,1000A,1250A,1600A,2000A,2500A,3200A,4000A
80kA/400V50kA/690V
3P, 4P
0
Fault deviate indication/reposit pbutton
Shut button
Manua/Power store handle
Dispart button
Power store & releaseindication
Shut & Dispart indication
Panel
In-Out devicePosition indication
Shakable handle &its depositary
Two times loop terminal connector(moving)
Two times loop terminal connector(moving)
Under-Uoltage reloaseDraw-out seatingShunt releaseAwciliary contactClose electromagnetIntelligent controller
Electric operation frameworkOperation framework
AC Rated Current:630A-3200ABreaking Capacity:80kA-100KA(virtual value)Rated working voltage: AC960VType:Draw-Out type and Fixed Mounted typeStandards: IEC60947-2, GB14048.2
AIR CASE CIRCUIT BREAKER
A C-17
CURRENTTRANSFORMER
E
People Electric Appliance serves for people.
• ISO14001 OHSAS18001ISO9001
WITH BUSBAR
Type Rated Current(A)
Class:0.5 Class:1
Weight(kg)
MSQ-30B
5/510/515/520/525/530/540/550/560/575/580/5
100/5120/5125/5150/5200/5250/
5-105-105-105-105-105-105-105-105-105-105-105-105-105-105-105-105-10
5-105-105-105-105-105-105-105-105-105-105-105-105-105-105-105-105-10
0.600.600.600.600.600.600.600.600.600.600.600.600.600.600.600.600.60
WINDOWS TYPE Bar:30 10mm.Conductor: 20mm.
Type Rated Current(A)
Rated Power(VA)
Class:0.5 Class:1
Weight(kg)
MSQ-30T
100/5125/5150/5160/5200/5250/5
2.5-53-5
5-105-105-105-10
55-105-105-105-105-10
0.620.620.620.620.620.62
MSQ CURRENT TRANSFORMERS
This series of CT can be applied to test, control, display and record the running of the electricalequipment, and to protect the equipment against the damage. In the AC circuit with the rated voltage value below 720V and the frequency of 50-60Hz. The product can be also applied to form a complete set of mine transformer.The products comply with VDE 0414,BS7626 and IEC 44-1 standard.
TECHNICAL CHARACTERISTICS OF CURRENT TRANSFORMERS:
MSQ-30T
Rated Power(VA)
MSQ-30B
CURRENT TRANSFORMER
• ••••
MSQ CURRENT TRANSFORMERS
MSQ-30
MSQ-40
MSQ-60
MSQ-100
TypeClass:0.5 Class:1
Weight(kg)
MSQ-100
1500/51600/52000/52250/52500/53000/5
151515151515
151515151515
0.800.800.940.981.101.16
Type Rated Current(A)
Class:0.5 Class:1
Weight(kg)
WINDOWS TYPEBar:30 10mm.Conductor: 20mm.
MSQ-30
30/540/550/560/575/580/5
100/5150/5200/5250/5300/5
----1
1.52.5
5-105-105-105-10
1111
1.52.55
5-105-105-105-10
0.40.40.40.40.40.40.40.40.40.40.4
WINDOWS TYPEBar:40 10mm.Conductor: 30mm.
MSQ-40
100/5150/5200/5250/5300/5400/5500/
2.535
5-105-105-105-10
2.55
5-105-105-105-105-10
0.380.380.380.380.380.380.38
Type
Class:0.5 Class:1
Weight(kg)
WINDOWS TYPEBar:60 20mm.Conductor: 40mm.
MSQ-60
250/5300/5400/5500/5600/5750/5800/5
1000/5
55
5-105-10
10-1510-1510-15
15
55
5-105-15
10-1510-1510-15
15
0.600.600.600.600.600.600.60
WINDOWS TYPEBar:80 30mm.or 100 10mm.conductor: 60mm.
TECHNICAL CHARACTERISTICS OF CURRENT TRANSFORMERS:
Rated Power(VA)
Type Rated Current(A)
Rated Power(VA)
Class:0.5 Class:1
Weight(kg)
Rated Power(VA)Rated Current(A)
Rated Current(A)
Rated Power(VA)
CURRENT TRANSFORMER
• E-02
MSQ CURRENT TRANSFORMERS
MSQ-125
PX-125
MSQ-85
TECHNICAL CHARACTERISTICS OF CURRENT TRANSFORMERS:
WINDOWS TYPEBar:82 30mm.Conductor: 80mm.
Model Rated Current(A)
Rated Power(VA)
Class:0.5 Class:1
Weight(kg)
MSQ-85
750/5800/5
1000/51200/51500/5
1515151515
1515151515
0.750.820.890.991.02
TypeRated Power(VA)
Class:0.5 Class:1
Weight(kg)
WINDOWS TYPEBar:125 57mm.125 10mm.Conductor: 60mm.
MSQ-125
1500/52000/52500/53000/54000/55000/5
151515151515
151515151515
1.01.151.451.601.902.20
WINDOWS TYPEBar:125 38mm.Conductor: 60mm.
TypeRated Power(VA)
Class:0.5 Class:1
Weight(kg)
PX-125
800/51000/51200/51250/51500/51600/52000/52250/52500/53000/54000/55000/5
7.51010
12.51515151515151515
152020253030303030303030
1.01.01.01.01.0
1.051.151.201.451.601.902.20
Rated Current(A)
Rated Current(A)
CURRENT TRANSFORMER
• E-03
The MES series of current transformer are convenient for mounting in many ways.The most currenttransformer need the special mounting and the MES series used the mounting of DIN typing without a lot of times.The protectivecover for the terminal block used the switching device with safety and quick.
MES GUIDE RAIL TYPE CT:
Primary current: 5A-3000ASecondary current: 5A,1AStandard approval:VDE0414,BS7626,IEC44-1Maximum voltage: 0.72/3KVFrequency: 50-60HzRated load:2.5VA,5VA,10VA,15VAClass:0.5,1.0Short-time thermal current: lth=60 lhRated security efficient: FS 5
MES CURRENT TRANSFORMERS
MES-145/100MES-100/60MES-80/40MES-80/30
MES-62/20B MES-62/20 MES-62/30 MES-62/40
CURRENT TRANSFORMER
• E-04
TypeRated
Current(A)
Rated Power(AV)
Class:0.5 Class:1.0
DIMENSION OF CASE[MM]:
OUTLINE DRAWING:
A
B
D
EFG
C
C
MES CURRENT TRANSFORMERS
MES-100/60
MES-145/100
600/5800/5
1000/51200/5
15151515
20202020
1000/51200/51500/51600/52000/52500/53000/5
15151515151515
30303030303030
MES-62/30
MES-62/40
MES-80/30
MES-80/40
30/540/550/560/575/5
100/5150/5200/5
-----
1.52
2.5
111
1.51.52.535
60/575/5
100/5150/5200/5250/5300/5
--1
1.52.535
112
2.555
7.5
30/550/560/575/5
100/5150/5200/5
----
1.52.55
112
2.555
7.5
100/5150/5200/5250/5300/5400/5500/5
1.52.555
101010
2.5555
151515
MES-62/20
MES-62/20B
5/510/515/520/525/530/540/550/560/575/5
100/5150/5
2.52.52.52.52.52.52.52.52.52.52.52.5
555555555555
30/540/550/560/575/580/5
100/5150/5200/5
--11
1.51.52
2.53
112233
3.7555
Model
MES-62/20B
MES-30/20
MES-62/30
MES-62/40
MES-89/30
MES-89/40
MES-100/60
MES-145/100
A
81
81
81
81
88
88
117
115
B
47
47
47
47
52
52
57
53
C
20B
20
30
30
30
30
50
86
D
35
35
35
35
41
41
184
38
E
71
71
71
71
77
77
77
74
F
20B
20
31
41
31
41
61
101
G
62
62
62
62
80
80
101
145
CURRENT TRANSFORMER
• E-05
MBO CURRENT TRANSFORMER SERIES
TypeRated
Current(A)
Rated Power(AV)
Class:0.5 Class:1.0
MBO-62/30
MBO-62/40
30/540/550/560/575/5
100/5150/5200/5
-----
1.52
2.5
111
1.51.52.535
60/575/5
100/5150/5200/5250/5300/5
--1
1.52.535
112
2.555
7.5
MBO-62/20
MBO-62/B
5/510/515/520/525/530/540/550/560/575/5
100/5150/5
2.52.52.52.52.52.52.52.52.52.52.52.5
555555555555
30/540/550/560/575/580/5
100/5150/5200/5
--11
1.51.52
2.53
112233
3.7555
MBO-62/B
MBO-62/20
MBO-62/30
MBO-62/40
76.5
60
75
30
38 0.5
2S S1
P 2
54.5
75
50 0.5
66
2.5
40
18
- L
76.5
1113212631
60
75
30
2S S1
P 2 - L
38 0.5
50 0.566
40
- L2P
1SS2
38 0.5
30
75
60
76.5
66
50 0.533
40.5
40
13 19 26.5
L - 2P
1SS2
75
60
\U+220522
38 0.538 0.5
30
76.5
66
50 0.5
40
CURRENT TRANSFORMER
• E-06
MBO CURRENT TRANSFORMER SERIES
MBO-100
TypeRated
Current(A)
Rated Power(AV)
Class:0.5 Class:1.0
MBO-100
750/5800/5
1000/51200/51500/51600/52000/52250/52500/53000/5
15151515152020202020
20202020202040405050
MBO-70
MBO-60
300/5400/5500/5600/5750/5800/5
1000/51200/5
1010101515151520
1515152020202530
400/5500/5600/5750/5800/5
1000/51200/51500/51600/52000/5
10101015151520303040
15151520202530404050
105
95
L - 2P
1SS2
106.
5
40
48 0.5
7660 0.5
10.5
30.5
50.5
64
44.2
60
S2 1S
P 2L -
101.5
60
56166.
5
94.5
6080 0.5
96
68 0.546
95.5
129
48 0.5
40
106.
5
2S S1
P 2L -
95
105
51
61.5
31 410
R19
60 0.576
60
MBO-60
MBO-70
CURRENT TRANSFORMER
• E-07
NSQ CURRENT TRANSFORMERS
NSQ SERIESPrimary current: 30A-3000ASecondary current: 5A,10AStandard approval: BS7626,IEC44-1Maximum voltage: 0.66KVFrequency: 50-60HzRated load: 2.5VA, 15VAClass:0.5,1.0,3.0Short-time thermal current: lth=60 lhRated security efficient: Fs 5
Model Primary/Secondary
Busbar Hole Dimension
RatedBurden
(VA)Class Rated
VoltageRated
Frequency
NSQ-30
NSQ-35
NSQ-40
NSQ-60
NSQ-100
30/5A-300/5A
50/5A-400/5A
100/5A-600/5A
600/5A-1600/5A
800/5A-3000/5A
30 10mm
35 10mm
40 10mm
60 10mm
100 10mm
2.5-5
5
10
15
15
0.5/1.0
0.5/1.0
0.5/1.0
0.5/1.0
0.5/1.0
0.72
0.72
0.72
0.72
0.72
50/60Hz
50/60Hz
50/60Hz
50/60Hz
50/60Hz
DIMENSION OF CASE[MM]:
Model
NSQ-30
NSQ-35
NSQ-40
NSQ-60
NSQ-100
A
30
40
45
60
100
B
78
70
80
110
155
C
46
46
46
53
53
D
95
84
87
130
174
E
112
100
104
148
191
F
70
70
70
80
80
C
D E
F
A
B
E
OUTLINE DRAWING:
TECHNICAL DATA:NSQ-30
NSQ-35
NSQ-40
NSQ-60
NSQ-100
CURRENT TRANSFORMER
• E-08
Model Primary/Secondary
Busbar Hole Dimension
(MM)
RatedBurden
(VA)Class Rated
Voltage
PX1-20
PX1-30
PX1-40
PX1-20L
PX1-30L
50/5A-150/5A
100/5A-500/5A
150/5A-1000/5A
50/5A-150/5A
100/5A-500/5A
=20mm
30 10mm
40 10mm
=20mm
30 10mm
1.5-2.5
1.5-2.5
3-10
1.5-2.5
1.5-.5
1.0
1.0
1.0
1.0
1.0
660V
660V
660V
660V
660
PX1-20
PX1-30
PX1-40
PX1-20L
PX1-30L
Model A
53
53
71
53
53
B
28
28
45
28
28
C
57
57
73
57
57
D
66
66
81
66
66
E
54
54
65
54
54
A
B
CD
E
Model PX1-20,PX1-30,PX1-40 are available for connecting with cable,and alsoavailable for connecting with bus bar.
PX1 CURRENT TRANSFORMERS
PX1 SERIES
Maximum voltage: 0.66KVFrequency: 50-60HzClass: 1.0Short-time thermal current: lth=60 lhMounting methods: either by din rail(35mm)or by screwsWindow dimensions: diameter 22mm(PX1-20,PX1-20L) 31 10mm(PX1-30,PX130L) 41 10mm(PX1-40)
TECHNICAL DATA & SPECIFICATION:
DIMENSION OF CASE[MM]:
OUTLINE DRAWING:
PX1-20
PX1-30
PX1-40
PX1-20L
PX1-30L
CURRENT TRANSFORMER
• E-09
PS CURRENT TRANSFORMERS
TECHNICAL DATA&SPECIFICATION:
ModelRated Current(A)Primary/Second-
ary
BusbarHole
Dimension
RatedBurden
(VA)Accuracy
ClassRated
VoltageRated
Frequency
PSM-20B
PSM-20
PSM-30
PS-30
PS-40
PS-60
PS-100
50/5A-200/5A
50/5A-200/5A
50/5A-200/5A
50/5A-300/5A
150/5A-800/5A
400/5A-1000/5A
800/5A-3000/5A
20 10mm
20 10mm
30 10mm
40 10mm
60 10mm
100 10mm
1.5-3
1.5-3
1.5-3
2.5-5
5-10
10
15
1.0
1.0
1.0
1.0
1.0
1.0
1.0
660V
660V
660V
660V
660V
660V
660V
50/60Hz
50/60Hz
50/60Hz
50/60Hz
50/60Hz
50/60Hz
50/60Hz
DIMENSION OF CASE[MM]:
Model
PS-20A
PS-20
PS-30
PS-30
PS-40
PS-60
PS-100
A
56
56
56
79
79
103
151
B
30
30
30
42
42
42
42
C
63
63
63
87
87
113
166
D
80
50
50
66
66
66
69
S1 S2
P2
A B
C
D
OUTLINE DRAWING:
PSM-20B PSM-20 PSM-30
PS-30
PS-40
PS-60
PS-100
CURRENT TRANSFORMER
• E-10
CPS CURRENT TRANSFORMERS
CPS SERIES:Primary current: 100A-5000ASecondary approval: 5A,1AStandard current: BS7626,IEC44-1Maximum voltage: 0.72KVFrequency: 50-60HzRated load: 2.5VA-60VAClass: 0.5,1.0,3.0Short-time thermal current: lth=100 lhRated security coefficient: Fs 5-High fire retardancy and security-Wide range of sizes to accommodate all the existing installations
SPECIFICATION:
Model
CPS-40
CPS-60
CPS-80
CPS-100
CPS-120
Primary/secondary(A)
100/5,150/5,200/5,250/5,300/5,400/5,500/5,600/5A
300/5,400/5,500/5,600/5,750/5,800/5,1000/5,1200/5A
500/5,600/5,750/5,800/5,1000/5,1200/5,1500/5,1600/5A
600/5,750/5,800/5,1000/5,1200/5,1500/5,1600/5,2000/5A,2500/5,3000/5A
1000/5,1200/5,1500/5,1600/5,2000/5,2500/5,3000/5,4000/5A,5000/5
DIMENSION OF CASE[MM]:
Dimensions
CPS40
Dimensions Busbar hole dimension Installation dimension
CPS-40
CPS-60
CPS-80
CPS-100
CPS-120
W
75
98
118
140
165
H
105
116
120
130
152
D
45
45
45
49
49
A
42
62
82
102
102
M
45
42
60
80
80
D
H
A
E
M
W
P1
People
OUTLINE DRAWING:
CPS-60
CPS-80
CPS-100
CPS-120
CPS-40
E
32
32
32
32
53
CURRENT TRANSFORMER
• E-11
RCT CURRENT TRANSFORMERS
RCT SERIES:Primary current: 30A-3000ASecondary current: 5A,1AStandard approval: IEC44-1Maximum voltage: 0.66KVFrequency: 50-60HzRated load: 15VAClass: 1.0Short-time thermal current: lth=60 lhRated security efficient: Fs 5
SPECIFICATION:
Model
RCT-25
RCT-35
RCT-60
RCT-90
RCT-110
Primary/secondary(A)
15/5,200/5,30/5,40/5,50/5,60/5,75/5,100/5A
30/5,50/5,60/5,80/5,100/5,120/5,150/5,200/5A,250/5,300/5
300/5,400/5,500/5,600/5,800/5,1000/5,1200/5
800/5,1000/5,1200/5,1500/5,1600/5
1000/5,1200/5,1500/5,1600/5,2000/5,2500/5,3000/5
DIMENSIONS[MM]:
Model
A
B
C
D
E
F
G
RCT-25 RCT-35 RCT-60 RCT-90 RCT-110
93
78
25
78
2
55
9
93
78
25
78
2
55
9
93
78
60
104
2
41
9
93
78
90
136
2
41
9
102
86
111
157
2
52
9
A
B
C
D
E
F
G
OUTLINE DRAWING
RCT-25
RCT-35
RCT-60
RCT-90
RCT-110
CURRENT TRANSFORMER
• E-12
MR CURRENT TRANSFORMERS
MR SERIES:Primary current: 30A-5000ASecondary current: 5A,1AStandard approval: BS7626,IEC185Maximum voltage: 0.72KVFrequency: 50-60HzRated load: 5VA-15VAClass: 1.0,3.0Short-time thermal current: lth=60 lhRated security efficient: Fs 5
SPECIFICATION&DIMENSIONS[MM]
Model
MR-28
MR-42
MR-45
MR-60
MR-60
MR-85
MR-125
Specification
30/5A-60/5A
100/5A-250/5A
300/5A
400/5A
500/5A 600/5A
800/5A-1600/5A
2000/A-5000/5
ID
28
42
45
60
60
85
125
CD
70
80
80
100
100
120
165
HT
40
30
30
30
30
20
20
Noted: For measuring current transformers,the accuracy class is designated by the highest permissible percentage current(ratio)error at the rated current prescribed for the accuracy class concerned.
OUTLINE DRAWING:
M6 SCREWS
ID
OD HT
CURRENT TRANSFORMER
• E-13
PR CURRENT TRANSFORMERS
Protective current transformers are required to operate over a range of current manytimes the circuit rating and is frequently subjected to conditions greatly exceedingthose which it would be subjected to as a measuring current transformer. When a current transformer is used to energise a protective relay, it must maintain itscharacteristic ratio up to some multiple of its rated current. This multiple, may be 5,10,20 or some even higher value and is know as Accuracy Limit Factor (ALF).Therefore,the selection of Protective Current Transformers in relation to accuracyclass and ALF require a close examination of relay characteristic and circuit condi-tions which includes the relay burden and the pilot wire lead burden.
DIMENSIONS[MM]:
Spec.
OD
ID
HT
60/5A
100
34
148
100/5A
100
34
98
150/5A
100
34
68
200/5A
100
34
58
250/5A
96
34
68
300/5A
96
34
68
400/5A
100
60
68
500/5A
100
60
48
600/5A
100
65
58
CI:10P5 15VA
CI:5P10 15VA
Spec.
OD
ID
HT
100/5A
150/5A
200/5A
250/5A
300/5A
400/5A
500/5A
600/5A
800/5A
1000/5A
1200/5A
1600/5A
2000/5A
2500/5A
3000/5A
3500/5A
4000/5A
5000/5A
100
34
180
100
34
130
100
34
110
96
45
110
96
45
110
96
45
90
102
62
110
110
68
88
120
85
88
120
85
68
123
82
68
123
82
60
123
125
40
178
125
40
178
125
40
182
120
35
182
120
35
184
118
38
Spec.
OD
ID
HT
100/5A
150/5A
200/5A
300/5A
400/5A
500/5A
600/5A
800/5A
1000/5A
1200/5A
1600/5A
2000/5A
2500/5A
3000/5A
100
34
168
100
34
108
100
34
88
96
45
108
96
60
108
102
60
88
110
70
68
120
85
68
120
85
58
123
82
60
123
82
50
178
125
38
178
125
38
178
125
38
CI:10P10 15VA
ID
OD HT
M6 SCREWS
OUTLINE DRAWING:
CURRENT TRANSFORMER
• E-14
MR CURRENT TRANSFORMERS
ID
OD HT
SPECIFICATION&DIMENSIONS[MM]
Model
MR-28L
MR-42L
MR-45L
MR-60L
MR-60L
MR-85L
MR-125L
Specification
30/5A-60/5A
100/5A-250/5A
300/5A
400/5A
500/5A 600/5A
800/5A-1600/5
2000/A-5000/5
ID
28
42
45
60
60
85
125
CD
70
80
80
100
100
120
165
HT
40
30
30
30
30
20
20
Noted:For measuring current transformers,the accuracy class in designated by the highest permissible percentage current(ratio)error at the rated current perscribed for the accuracy class concerned.
OUTLINE DRAWING:
CURRENT TRANSFORMER
• E-15
BSMJ SERIES CAPACITORS
GENERAL DESCRIPTION
MAIN CHARACTERISTICS
Self-healing type low voltage shunt capacitor, made of advanced metallized film, is prod-uced strictly in accordance with the National Standard and IEC Standard by the introduced adva-nced foreign techniques and equipment. The device is mainly suitable for low voltage electric network to improve power factor, reduce reactive loss, and better the voltage quality.
1.Small volume and light weightIt is only 1/4 and 1/5 of the weight and the volume of the outdated products respectively.2.Low lossWith the actual less than 0.1%,the capacitor, itself,has low consumption of energy, little radiation, low temperature rise, long service life, and good energy conservation effect.3.Excellent self-healing performanceWhen a part of the isolation is fed through due to overvoltage, it is capable of self-healing so as to continue the normal operation, therefore the reliability is improved greatly.4.SafetyEquipped with self-discharging resistant and safety devices inside, it is safe and reliable.5.Without oil leakageIn order to avoid oil leakage during operation s o as to prot ect the e nviro nment , it emplo ys t hemicrocrystalline wax as the inpregnant, which remains solid at ordingary t emp era tur e and has a drip melting point higher than 70 .
CBB SERIES CAPACITORS
MIN SPECIFICATIONS
GENERAL DESCRIPTION
Brand of CBB60 and CBB65 self-healing type AC capacitors, Which made of the advanced meta-llized film, are widely applied to household electric appliaces such as fan, washing machine, refrig-erator, airconditioner,oil vapor exhausting machine, etc. Each technic target of the device complies with GB/T3667-93 Standard.
Dimension
230~300
VAC
350~500
VAC
D
H
A
D
H
A
30 34 42 50 60
60 80 100 120
11 12 15 18
42 50 60
80 100 150
12(15) 15(18) 18
4.7 5 6 8 8.5 9 10 12 15 16 20 2 5 30 40 50 60
Voltage/ Capacitance( f)
• E-16
CAPACITOR
CAPACITORS
APPLICATION
SPECIFICATIONS
Motor run capacitor has features of small size, light weight and small tangent in waste angle.Applicable to start and operate with 50/60Hz A.C single motor, the items are specially suitable for micro pump, baric pump, micro motor and all kinds of domestic electric appliance.
Rated voltage Ambient TemperatureRated VoltageTest Voltage
Capacitance ToleranceInsulation Resistance
Dissipation FactorStandard
-40~+70250V AC 400V AC
T-T:1.5Un T: 10S T-C:2000V AC T:105% 10%
T-T 3000M F T-C 100Mtg 0.004(50Hz)
SJ2600.1-85
AC250V
AC450V
Nominal Capacity F
4,5,6,8,10,12,14,16,18,20,22,25,30,31.5,35,40,45,50,60,70,80,85,
90,95,100
4,5,6,8,10,12,14,16,18,20,22,25,30,31.5,35,40,45,50,60,70,80,
85,90,95,100
MOTOR RUN CAPACITOR
P-1 P-2
P-3 P-5 P-111 P-29 P-28
P-111-A P-111-B P-111-C P-75 P-76
• E-17
A
People Electric Appliance serves for people.
PANEL METER
• ISO14001 OHSAS18001ISO9001
PE-L96, 72, 48
PE-T80, 780, 670, 60
AC Ammeter
~
AC Voltmeter
1 2
3
1 2
3
1 2
3
1 2
3
AC Ammeter AC Voltmeter
PE-C96, 72, 48
PE-T80, 780, 670, 60
PE-C96, 72, 48
PE-C80, 780, 670, 60
PE-C96, 72, 48
PE-C80, 780, 670, 60
PE-F96, 80,72, 48
PE-E80,780,670,60
Hz meter
PE-R96,72
two rows of reeds type
frequency meter
PE-S96,72
Three phase
Synchroscope
PANEL METER
IEC51, IEC61010-1, VDE410, BS89, UL94, NE60051, IEN43780
The insulation test is carried out at a voltage of 2KV, 50Hz 1min and applies for instruments with the full scale deflection up to650V. Other standards comply with IEC61010-1.
CASES:All cases at least dust and splash water-proof.All cases are made of strengthened self-extinguishing PPOWith a high hit-resistance and a maximum electric isolation
ACCURACY CLASS:AC, DC Voltmeters and Ammeters comply with the accuracyclass 1.5.The power meters comply with accuracy class 1.5.The frequency meters comply with accuracy class 1.0.The maximum-demand meters comply with accuracy class 3.0.The power factor meters and synchroscope meter complywith accuracy class 2.5.
INSULATION TEST:
All instruments operate trouble-free at room temperature rang-ing from -25 to + 40 .The Max. Voltage to earth Voltmeter-The upper range voltage(full scale deflection)Ammeter-The Voltage of the main power supply.The meter use d shall be keep cleaning.The user shall be made aware of that, if the me ter is used in a manner not specified by the manufacturer,the protection provided by the meter may be impaired.
TEMPERATURE INFLUENCE:
MOUNTING ANGLE:The instruments are calibrated for vertical mounting, unless otherpositions such as horizontal or inclined at any specified angle to thehorizon. Can be provided upon request(in this case, specify angle ofinclination, please) The accuracy class refers to the specified mounting angle only.
STANDARDS:
1 2
3
~ A B C
L1L2L3
A B C
AO BO
• A-01
~
L1
L2
L3
2 5
1 3
L1
L2
L3
1 3
2 4
5 6 7
PE-M96, 80,72, 48
Maximum demand meter
PE-PF96, 80,72, 48
PE-PF80, 780, 670, 60
3 Phase Power factor meter
PE-W(Var)96, 80,72, 48
PE-W80, 780, 670, 60
Three phase three wire active
power and reactive Power meter
without voltage transformers
1 2
3 4
5 6 7
L
N
~L
N
~
1
2
3
4
5 6 7
L1
L2
L3
PE-W(Var)96, 72, 48PE-W(Var)80, 780, 670, 60Single~phase Power meterwith Current transformers
PE-W(Var)96, 72, 48PE-W(Var)80, 780, 670, 60Single~phasePower meter with Current and Voltage transformers
PE-W(Var)96, 72, 48PE-W(Var)80, 780, 670, 60Three phase three wire ActivePower and Reactive Power meter withcurrent and voltage transformers
2 5L N
~L N
A B C
A B
PE-S96, 72
Single phase
Synchroscope
PE-PF96, 80, 72, 48
PE-PF80, 780, 670, 60
Single phase power factor meter
PANEL METER
• A-02
Model: PE-T96, PE-T72, PE-T48, PE-C96, PE-C72, PE-C48Accuracy: Class 1.5Specs: 0.1A,0.5A,1A,1.5A,3A,5A,7.5A,10A,20A,25A,30A,50A,75,100A(use Ext. CT 5A)Note: For 60/75/100A direct meter, the class in 2.5.Advantage: The scale can be easily changed without opening the front frame so that the class will not be influenced.
MOVING IRON & MOVING COIL INSTRUMENTS AC AMMETER
Model:PE-T96, PE-T72, PE-T48, PE-C96, PE-C72, PE-C48Accuracy: Class 1.5Specification:30V, 50V,75V, 100V, 120V, 150V, 250V, 300V, 450V, 600V(For 450-380KV, should be used with potential transformer whose secondaryvoltage 100V).
MOVING IRON & MOVING COIL INSTRUMENTS AC VOLTMETERS
Model: PE-C96, PE-C72, PE-C48Accuracy: Class 1.5Specification:25uA, 30uA, 50uA, 1mA, 2mA, 5mA, 10mA, 20mA, 30mA, 50mA, 75mA, 100mA, 150mA, 200mA, 250mA, 300mA, 500mA, 1A, 3A, 5A, 7.5A, 10A, 20A,30A, 50A, 75,100A(used with Shunt)Note: For 60/75/100A direct meters, the class in 2.5.Advantage: The scale can be easily changed without opening the front frameso that the class will not be influenced.
MOVING COIL INSTRUMENTS DC AMMETER
Model: PE-C96, PE-C72, PE-C48Accuracy: Class 1.5Specification: 3V, 5V, 7.5V, 10V, 15V, 20V, 30V, 50V, 75V, 100V, 120V, 150V,200V, 250V, 300V, 400V, 450V, 600V,Note: Over 6000V should be used with Ext. Resistor. (Rated current 5mA).
MOVING COIL INSTRUMENTS DC VOLTMETERS
PANEL METER
PE-96
PE-96
PE-96
PE-96
• A-03
Model: PE-F96, PE-F72, PE-F48Accuracy: Class 1.0Volt: 50V,100V, 220V, 380VFreq:44-55Hz, 45-65Hz, 55-65Hz, 47-53Hz, 57-63Hz, 44-56Hz, 54-66Hz, 450-550Hz, 550-650Hz
MOVING COIL INSTRUMENTS FREQUENCY METER POINTER TYPE
Model: PE-F96, PE-F72, PE-F48these meters can measure the other non-electric values: temperature, speed,and so on. Heat resistance: Case of non-combustible plastic material accord-ing to UL-94 V0.Fastening: By means of nuts, absolutely safe, fast, robust, side-by-side
MOVING COIL INSTRUMENTS FOR NON-ELECTRIC VALUES
One row of reeds Model: PE-R96-1, PE-R72-1Two rows of reeds Model: PE-R96-2, PE-R72-2Accuracy: Class 0.5Specification:Voltage: 50V 100V 220V 380V 440V 415VFrequency: 45~55Hz, 45~65Hz, 55~65Hz, 47~53Hz, 57~63Hz, 44~56Hz, 54~66Hz, 450~550Hz, 450~650Hz, 550~650HzThis vibrating reed frequency meter with one row of horizontal reeds or with two rowsof horizontally arranged reeds for connection to one main voltage. Vertical arrangementson requestHeat resistance: Case of non-combustible plastic material.Changeable scale: All scales with printing technique.The dial plate with different scale, which is at the same internal value, can be changeable.But the accuracy is unchangeable.Fastening: By means of nuts, absolutely safe,fast,robust,sibe-by-side.Mounting depth: Max.43mm.
FREQUENCY METER WITH REEDS TYPES
PANEL METER
PE-96
PE-96
PE-96
• A-04
For 3 phases circuits, balanced load 45-65Hz and for 1 phase AC 50Hz.Model: PE-PE96,PE-PF72Accuracy: Class 2.5Voltage:100V,380V,440VFrequency:50Hz,60HzScale graduation:0.5cap-1-0.5ind,0.3cap-1-0.7ind,0.4cap-1-0.4ind, 0.7cap-1-0.3indOrders to be noted:Type of Current: 1P,3P 3W circuits, balanced load.Rated Volt: The voltage is line voltage (between two wire).Operating Current: If used with CT, the secondary current 5A or 1A is standard.
POWER FACTOR METER
Wattmeters or Varmeters with build-in converter for 1 phase 3P 3W, 3P 4W.Model: PE-W96, PE-W72Accuracy: Class 1.5Voltage:50V,100V,220V,240V,220/380V,240/415VCurrent:5AThese meters are used with potential secondary voltage 100V voltage transformer orsecondary current 5A CT. Wattmeters with built-in converter for 3P 3W, 3P 4W andsingle phase.
POWER METER
Synchrony scope for phase comparison for three phase AC circuits, 50Hz or 60Hz.Model:PE-S96 PE-S72Specification:Voltage:100V 220V 380V 440VWorking time:15min max.
SYNCHROSCOPE METERS
This indicator is designed for easy testing of phase sequence in three-phase systemswith a permissible operating voltage up to 500V. For short connections, no longer than5 minutes for one test, a push-button switch is placed on the front plate. A disc with anindicating arrow rotates in the direction of the arrow, if the three phases are properlyconnected, otherwise the disc rotates in the other direction. By changing of two wires,the phase sequence will be corrected to corresponding designation of the terminals.Model:PE-SI 96 PE-SI72Specification:Voltage:110-550VWorking time:no longer than 5 minutes.
SEQUENCE INDICATOR
PANEL METER
PE-96
PE-96
PE-96
• A-05
Model: PE-L96V, PE-L80V, PE-L72V, PE-L48VSpecification: 0/90-110V, 0/100-120V, 0/200-240V, 0/340-420VHeat resistance: Case of non-combustible plastic material according to UL-94 V0.Fastening: By means of nuts, absolutely safe,fast,robust,sibe-by-side.Mounting depth: Max.43mm.
Model:PE-AM96 PE-AM72Features: For the cont rol of Maximum Demand and the monitoring and control of overload on distribution systems. Constructed with an electronic circuit and 5A relay. The alarm was set by the blue slim pointer, the red light is the alarm one, which can be used with buzzer.Accuracy: Class 3.0Rating: 1A,5A for use with separate CT.Burden: MDI2.2VA Frequency:50/60HzOverload: x1.2 continuous, 10 1 second, 20 1 second via5/5 CT.Relay CircuitAuxiliary: AC 220V 10%, 50/60Hz Burden:2.6VA Bestrews: 1%Time delay: 1 second approximately fixed. Alarm and Trip pointWorking Range:20-100% 1%added to the MDI AccuracyRelay: Single Pole ChangeoverRelay Rating: AC 250V 5A non inductive, DC 24V 2A ResistiveTemperature: -10 to+50
For measuring mean maximum current value, when it is 8min or 15min or 30min.Model: PE-M96 PE-M72Accuracy: Class3.0Specificat ion: 8min 5A, 15min 5A, 30min 5A, 8min 1A, 15min 1A(No specification for 30 min 5A for PE-M48)With bimetal movement and thermal delayed indicator for measuring the maximum mean load during a period of 8 or 15 minutes, eats red maximum pointer. Lead seal can protect resettingknob of maximum pointer. Response time 8 or 15,30 minutes(to be specified when ordering).Heat resistance: Case of non-combustible plastic material.Changeable sca le: All scales with printing technique. The dial plate with different scale which is at the same internal value can be changeable. But the accuracy is unchangeable.Fastening: By means of nuts, absolutely safe, fast, robust, side-by-side.Mounting depth: Max 43mm.
MAXIMUM DEMAND AMMETER
For measuring mean maximum content value and instantaneous values for combinedwith moving iron movement movement meters.Model:PE-2M96, PE-2M72Accuracy: Class3.0(instantaneous values)Class 1.5Specification:8min 5A,15min5A, 8min 1A,15min1AWith bimetal movement and thermal delayed indicator for measuring the maximum mean load during a period of 8 or 15 minutes, eats red maximum pointer. Lead seal can protect resettingknob of maximum pointer. Scale compressed at the beginning, convenient reading from 25% of full-scale deflection. Accuracy of maximum load indication3%. Referred to the maximum pointer. Response time 8 or 15,30 minutes(to be specified when ordering).Heat resistance: Case of non-combustible plastic material.Changeable scale: All scales with printing technique. The dial plate with different scale, whichis at the same internal value, can be changeable. But the accuracy is unchangeable.Fastening: By means of nuts, absolutely safe, fast, robust, side-by-side.Mounting depth: Max 43mm
COMBINED WITH MOVING IRON AMMETERS
MAXIMUM DEMAND INDICATOR WITH RELAY
MOVING COIL INSTRUMENTS FOR RATED VOLTMETERS
PANEL METER
PE-96
PE-96
• A-06
Model: PE-H96 PE-H72 PE-H48Display:99999.99Voltage:AC 100~125V,AC200~250V,AC380~440V,AC24VBurden:2.5VAFrequency:50/60HzFeatures: Elapsed Time Meters or Hours Run meters or Hours Run Meters monitor ON/RUN time of plant and equipment allowin g the user to perform functions such as Production Effici-ency Cost Estimating and Service Period monitor-ink for preventatives maintenance etc. Thetime is measured in instrument of 0.01h up to 99999.99 hours after which time the meterresets to zero. Non-reset table to prevent accidental resetting.
The instruments are suitable for measuring AC Ampere in 4 or 3 wire networks by using a change over switch on the front side of the instrument.Model: PE-T96A-S, PE-T72A-STechnical data:Movement: Moving-iron movement with oil filled bearings, practically vibration-free oildamping.Accuracy: Class 1.5Frequency range: 50Hz.Heat resistance: Case of non-combustible plastic material according to UL-94 V0.Measuring range: 0.1/1A, 0.2A/2A, 0.3A/3A, 0.4A/4A, 1A/10APosition: L1-L2,L1-L3,L2-L3.
The instrument are suitable for measuring AC Voltages in three phase 4 or 3 wire networks by using a change over switch on the front side of the instrument.Model: PE-T96V-S PE-T72V-STechnical data:Movement: Moving-iron movement with oil filled bearings, practically vibration-free oildamping.Class of accuracy: 1.5%Frequency range: 50Hz.3 phase 4 wire Measuring range: 60V/100V,80/150V 100/200V 150/250V, 250/400V 300/500V.Position:L1-L2,L1-L3,L2-L3,L1-N,L2-N,L3-NHeat resistance: Case of non-combustible plastic material according to UL-94 V0.3 phase 3 wire Measuring range: 100V,150V 200V 250V 400V 500VPosition: L1-L2,L1-L3,L2-L3.
Model: PE-C96, PE-C72, PE-C48these meters can measure the other non-electric values: temperature, speed, and so on.Heat resistance: Case of non-combustible plastic material according to UL-94 V0.Fastening: By means of nuts, absolutely safe, fast, robust, side-by-side
MOVING COIL AMMETERS WITH CHANGE OVER SWITCH FOR AC AMMETERS
MOVING IRON VOLTMETER WITH CHANGE OVER SWITCH FOR AC VOLTMETERS
MOVING COIL INSTRUMENTS FOR NON-ELECTRIC VALUES
ELAPSED TIME METER OR HOURS RUN METERS
PANEL METER
PE-96
PE-96
PE-96
• A-07
Model: PE-C96A PE-C72AAccuracy: Class 1.5Specification: 3V, 5V, 7.5V, 10V, 15V, 20V, 30V, 50V, 75V, 100V, 120V, 150V, 200V, 250V, 300V, 400VMeasuring ranges over 450V with external resistor(rated current 5mA)Heat resistance: Case of non-combustible plastic material according to UL-94 V0.Fastening: By means of nuts, absolutely safe, fast, robust, sibe-by-side.Mounting depth: Max.43mm.
Model: PE-C96A. PE-C72AAccuracy: Class 1.5Specification: 100uA 500uA 1mA 2mA 5mA 10mA 20mA 30mA 50mA 75mA 150mA200mA 250mA 300mA 500mA 1A 3A 7.5A 10A 20A 30A 50A 60A 100A. For 10A-10KA,useexternal 75mV, 65mV or 45mV shunt.Notes: For 50A 60A 75A 100A meters, when these meters directly connections circuit, their accuracy is class 2.5Heat resistance: Case of non-combustible plastic material according to UL V0.Changeable sca le: All scales with printing technique. The dial plate with different scale, which is at the same internal value, can be changeable. But the AC is unchangeable.Fastening: By means of nuts, absolutely safe, fast, robust, side-by-side.Mounting depth: Max.43mm.
MOVING COIL INSTRUMENTS(240DEG) DC AMMETERS
MOVING COIL INSTRUMENTS(240 DEG) DC VOLTMERS
Model: PE-L96A, PE-L72AAccuracy: Class 1.5Specification: 0.5A, 1A, 1.5A, 3A, 5A, 7.5A, 10A, 15A, 20AFor 10A-10KA, Use external current transformer, which secondary current is 5A.Notes: These meters measure r.m.s values and are scaled in r. m. s values.Heat resistance: Case of non-combustible plastic material according to UL-94 V0.Changeable scale: All scales with printing the technique. The dial plate with different scale,which is at the same internal value, can be changeable, But the accuracy is unchangeable.Fastening: By means of nuts, absolutely safe, fast, robust, side-by-side.Mounting depth: Max.43mm.
Model: PE-L96A, PE-L72AAccuracy: Class 1.5Specification: 3V, 5V, 7.5V, 10V, 15V, 20V, 30V, 50V, 100V, 150V, 200V, 250V, 300V,400V, 450V, Rated voltage over 450V use external resistance(rated current 5mA).Heat resistance: Case of non-combustible plastic material according to UL-94 V0.Fastening: By means of must, absolutely safe, fast, robust, side-by-side.Mounting depth: Max43mm.
MOVING COIL INSTRUMENTS WITH RECTIFIER(240 DEG) AC AMMETERS
MOVING COIL WITH RECTIFIER INSTRUMENTS(240DEG) AC VOLTMETERS
PANEL METER
PE-96
PE-96
PE-96
• A-08
Model: PE-W96, PE-W72Accuracy: Class 1.5Specification:Voltage: 50V 100V 380V 240V 415V 400V 380V 220/380V 240/415VCurrent: 1A, 5AThe voltage circuits of the meter connected with voltage transformers. Which secondary voltage is 100V, if the secondary voltage is lower than 450V, it also can be connected directly. The current circuits connected with current transformers, which se condary current is 5A. Wattmeters and varmeters with converter for three-phase three wires or four wire and single phase.Heat resistance: Case of non-combustible plastic material according to UL-94 V0.Fastening: By means of must, absolutely safe, fast, robust, side-by-sideMounting depth: Max 43mmExternal converter with size.
Accuracy:Class 1.0Model: PE-F96,PE-F72Specification:Voltage: 50V 100V 220V 380V 440VFrequency: 45~55Hz, 45~65Hz, 45~53Hz, 57~63Hz, 44~56Hz,54~66Hz, 450~550Hz, 450~650Hz, 550~650HzHeat resistance: Case of non-combustible plastic material according to UL-94 V0.Fastening: By means of nuts, absolutely safe, robust, sibe-by-side.Mounting depth: Max. 43mm.
Model: PE-PF96, PE-PF72AAccuracy: Class 2.5Voltage: 100V 220V 380V 415V 440 current: 5ASpecification: 0.5cap-1-0.5ind, 0.3cap-1-0.1ind, 0.4cap-1-0.4ind, 0.7cap-1-0.2indHeat resistance: Case of non-combustible plastic material according to UL-94 V0.Fastening: By means of must, absolutely safe, fast, robust, side-by-side.Mounting depth: Max 43mm.
MOVING COIL INSTRUMENTS FREQUENCY METERS [240 DEG]
MOVING COIL INSTRUMENTS POWER FACTOR METERS [240 DEG]
MOVING COIL INSTRUMENTS(240DEG) DC AMMETERS [240 DEG]
SIZE OF RECTANGULAR TYPE METER
Model
PE-96
PE-72
PE-48
Unit
mm
mm
mm
A
96
72
48
B
92
68
44
C
90
66
42
D
5.5
5.5
5.5
E
65
65
65
F
43
43
43
F43E65
D5.5
ABC
PANEL METER
PE-96
PE-96
PE-96
• A-09
A
BH
M
G
CE F
D
H
Model
PE-50
PE-60
PE-670
PE-80
A
50
60
60
81
B
52
60
70
81
C
23.5
24
23
22
D
13.5
11
10
12
E
4.4
9.5
11
18.5
F
12.5
11
12
13.5
G
45
52
52
63.5
H
19
24
24
32.5
M
3
3
3
3
For Hole
46
53
53
65
Name
DC Ammeter
DC Voltmeter
AC Ammeter
AC Voltmeter
Frequency Meter
Specifications
Direct connection withExt.SHUNT
Direct connection withExt.Resistor
Direct connection withExt.CT
Direct connection withExt.CT
30-1000uA 1-1000mA 1-50A1K-10KA
40-1000mV 1-1000V1K-10KA
1-1000mA 1-50A5-1000A 1K-10KA
40-1000mA 1-1000V1K-380KV50-380V
44-55Hz 45-65Hz 55-65Hz
Remarks
DIMENSIONS(MM)
Struction: Moving Coil, Moving Iron and Rectifier.Class: 2.0,2.5
TECHNICAL DATA
OUTLINE DRAWING
PE-50
PE-60
PE-70
PE-80
PANEL METER
PE-50
PE-60
PE-70
PE-80
• A-10
ROUND TYPE SERIES PANEL METER
PE-52
PE-65
PE-62T2
PANEL METER
PE-52
PE-62T2
Name
DC Ammeter
DC Voltmeter
AC Ammeter
AC Voltmeter
Specifications
Direct connection withExt.SHUNT
Direct connection withExt.Resistor
Direct connection withExt.CT
Direct connection withExt.CT
30-1000uA 1-1000mA 1-50A1K-10KA
40-1000mV 1-1000V1K-10KA
1-1000mA 1-50A5-1000A 1K-10KA
40-1000mA 1-1000V1K-380KV
Remarks
TECHNICAL DATA:
Model
PE-52
PE-65
PE-62T2
Unit
mm
mm
mm
A
58
73.5
75
G
39
39
35
F
52
65
70
E
40.5
42
65
D
26
31
45
C
4.5
4.5
8
B
66.5
83.5
90
DIMENSIONS(MM):
A
B
F
DE
C
G
OUTLINE DRAWING
• A-11
NEW TYPE PET SERIES PANEL METER
AC AMMETRS
Model: PET-80 PET-60 PET-50 PET-680 PET-780 PET-100 PET-560 PET-670Accuracy: Class 1.5Specification: 30V 50V 75V 100V 120V150V 250V 400V 450V 500V 600VFor 450V-450KV, meters can potentialtransformer with secondary voltage 100V.Heat resistance: case of non-combustibleplastic material.
AC VOLTMETRS
Model: PET-80 PET-60 PET-50 PET-680 PET-780 PET-100 PET-560 PET-670Accuracy: Class 1.5Specification: 0.1A 0.5A 1A 3A 5A 7.5A 10A 15A20A 25A 30A 40A 50A 60A.For 10A-10KA, use external current transformer withsecondary current 5A connected directly with cur-rent from 20A to 60A, the class is 2.5 .Changeable scale: The dial plate with different scale,which is at the same division and internal value, canbe changeable.
DC VOLTMETRS
Model: PET-80 PET-60 PET-50 PET-680 PET-780 PET-100 PET-560 PET-670Accuracy: Class 1.5Specif ication: 20V 30V 50V 100V 150V 200V 250V300V 450V 500V 600V can be connected directly.Measuring ranges over 450V with external resistor(rated current 5mA).Heat resistance: case of non-combustible plasticmaterial.
DC AMMETRS
Model: PET-80 PET-60 PET-50 PET-680 PET-780 PET-100 PET-560 PET-670Accuracy: Class 1.5Specification: 100 A 1mA 3mA 5mA10mA 20mA 30mA 50mA 100mA 150mA200mA 250mA 300mA 500mA 1A 3A 5A7.5A 10A 20A 30A 40A 60AFor 10A-10KA, use external 75mV 60mV45mV shunt.The accuracy of the direct reading meterfrom 20A to 60A is class 2.5 .Changeable scale: The dial plate with differentscale, which is at the same division and internalvalue, can be changeable.
FREQUENCY METERS
Model: PET-80 PET-60 PET-50 PET-680 PET-780 PET-100 PET-560 PET-670Accuracy: Class 1.0Specification:Voltmeter: 100V 220V 380V 440VFrequency: 45-55Hz 45-65Hz 54-66Hz 350-450Hz 450-550Hz 550-650HzHeat resistance: case of non-combustibleplastic material.
POWER FACTOR METER COS
Model: PET-80 PET-60 PET-50 PET-680 PET-780 PET-100 PET-560 PET-670Accuracy: Class 2.5Specification: 100V 220V 380V 440V current: 5AThree phase: 100V 220V 380V 440V current: 5ASpecification: 0.5cap-1-0.5ind 0.3cap-1-0.7ind 0.4cap-1-0.4ind 0.7cap-1-0.2indFrequency: 50Hz or 60HzHeat resistance: case of non-combustible plasticmaterial.With external converter, which size is48mm 48mm
PET-60 PET-60
METERS & CURRENT TRANSFORMERS
PET-60
PET-60 PET-60 PET-60
PANEL METER
• A-12
6145.5
26M3
B114(81)A1
A2
L
B2
Dm
ax
NEW TYPE PET SERIES PANEL METER
OUTLINE DRAWING OF SFT SERIES PANEL METER
SIZE OF SQUARE OR RECTANGULAR WITH ROUND PANEL CUT-OUT METER
Model
PET-120
PET-80
PET-780
PET-670
PET-560
PET-60
PET-50
Unit
mm
mm
mm
mm
mm
mm
mm
A1
120
80
80
70
60
60
50
A2
100
80
70
60
50
60
50
B1
84
64
54
48
34
36
34
B2
84
64
54
48
34
36
34
L
31.2
39.2
27.2
27.2
23.2
30.2
23.2
D1
47.5
47.5
47.5
47.5
47.5
47.5
44
The items of B1 and B2 for the distance of the mounting screwsThe item D1 for the size of panel cut-out of switchboard
MOVING COIL INSTRUMENT POWER METERS WATTMETER
Model: PET-W80 PET-60 PET-670 AmmetrsAccuracy: Class 1.5Specification:Voltage: Single phase:100V 220V 380VThree phase three wire: 100V 220V 380V 415VThree phase three wire: 100V 220V(380)V240( 415)VAbove-mentioned can be connected directly. The following should be connected with voltagetransformers: 380/100V 500/100V 3K/100V 6K/100 10K/100V 15K/100V 35K/100Current: 1A, 5AThe voltage circuits of the meter connected with voltage transformers. Which secondary voltage is100V. The current circuits connected with current transformers, which secondary current is 5A or 1A.Wattmeters and Varmeters with converter for three-phase three wires or four wire and single phase,which can be used for the balance and unbalance burden circuit.Heat resistance: Case of non-combustible plastic material.Fastening: By means of nuts, absolutely safe, fast, robust, side-by-sideExternal converter with size: 72mm 87.2mm 65mm
PET-60
PET-60
PANEL METER
• A-13
DIGITAL PANEL METER
D
PE-96
PE-96
PE-96
PE-96
Function: Measure AC currentModel: PE-D96A-AC, PE-D72A-AC, PE-D48A-ACFeature:1.Display: 3 1/ 2 digital.LED display(red or green)2.Accuracy: 0.5% 1 digit3.Auxiliary power: AC 110V 10% 50/60Hz AC 220V 10% 50/60Hz4.Input signal: AC current5.Measuring range: 0-20A AC, For the current over 20A can use the AC current transformer.6.Consumption:<3.2VA7.Max Signal Consumption:<0.3VA8.Operating Environment: temperature-10 ~+50 humidity: 85%9.Storage Environment: temperature-30 ~+60 humidity: 70%10.Heat resistance: case of non-combustible plastic material11.Voltage Testing: over 2000V12.Fastening: By means of nuts, absolutely safe, fast, robust, side-by-side.
DIGITAL AC AMMETER
Function:Measure AC VoltageModel: PE-D96V-AC, PE-D72V-AC, PE-D48V-ACFeature:1.Display: 3 1/ 2 digital. LED display(red or green)2.Accuracy: 0.5% 1 digit3.Auxiliary power: AC 110V 10% 50/60Hz AC 220V 10% 50/60Hz4.Input signal: AC Voltage5.Measuring range:0-600V AC, For the Voltage over 600V can use the potential transformer.6.Consumption: <3.2VA7.Max Signal Consumption:<0.3VA8.Operating Environment: temperature -10 ~+50 humidity: 85%9.Storage Environment: temperature -30 ~+60 humidity: 70%10.Heat resistance: case of non-combustible plastic material11.Voltage Testing: over 2000V12.Fastening: By means of nuts, absolutely safe, fast, robust, side-by-side.
DIGITAL AC VOLTMETER
Model: PE-D96A-DC, PE-D72A-DC, PE-D48A-DCFeature:1.Display: 3 1/ 2 digital. LED display(red or green)2.Accuracy:0.5% 1 digit3.Auxiliary power: AC 110V 10% 50/60Hz AC 220V 10% 50/60Hz4.Input signal: DC current5.Measuring range:0-20A DC, For the current over 20V can use the external shunt.6.Consumption: <3.2VA7.Max Signal Consumption:<0.3VA8.Operating Environment: temperature-10 ~+50 humidity: 85%9.Storage Environment: temperature-30 ~+60 humidity: 70%10.Heat resistance: case of non-combustible plastic material11.Voltage Testing: over 2000V12.Fastening: By means of nuts, absolutely safe, fast, robust, side-by-side.
DIGITAL DC AMMETER
Model: PE-D96V-DC, PE-D72V-DC, PE-D48V-DCFeature:1.Display: 3 1/ 2 digital. LED display(red or green)2.Accuracy:0.5% 1 digit3.Auxiliary power: AC 110V 10% 50/60Hz AC 220V 10% 50/60Hz4.Input signal: AC Voltage5.Measuring range:0-600V DC or according to your own requirement.6.Consumption: <3.2VA7.Max Signal Consumption:<0.3VA8.Operating Environment: temperature-10 ~+50 humidity: 85%9.Storage Environment: temperature-30 ~+60 humidity: 70%10.Heat resistance: case of non-combustible plastic material11.Voltage Testing: over 2000V12.Fastening: By means of nuts, absolutely safe, fast, robust, side-by-side.
DIGITAL DC VOLTMETER
• A-14
Unit
mm
mm
mm
mm
mm
mm
A
96
3.74
72
2.83
48
1.89
Model
PE-96
PE-72
PE-48
B
92
3.62
58
2.68
44
1.73
C
75
2.95
75
2.95
110
4.33
D
10
0.39
9
0.35
8
0.31
The ltem B for the size of panel cut-out of swithboard
SIZE OF RECTANGULAR TYPE METER
DIGITAL PANEL METER
PE-96
PE-96
PE-96
Model: PE-D96F, PE-D72FFeature:1.Display:4 digital.LED display(red or green)2.Accuracy:0.2% 1 digit3.Auxiliary power: AC 110V 10% 50/60Hz AC 220V 10% 50/60Hz4.Input signal: AC Voltage, rated signal value: 0-600V(admissible input Voltage error 80%,+100%)5.Measuring range: 0-1M Hz6.Consumption:<3.2VA7.Max Signal Consumption:<0.3VA8.Operating Environment: temperature -10 ~+50 humidity: 85%9.Storage Environment: temperature -30 ~+60 humidity: 70%10.Heat resistance: case of non-combustible plastic material11.Voltage Testing: over 2000V12.Fastening: By means of nuts, absolutely safe, fast, robust, side-by-side.
DIGITAL FREQUENCY METER
Single Phase Model: PE-D96PF1, PE-D72PF1Three Phase Model: PE-D96PF3, PE-D72PF3Feature:1.Display:4 digital. LED display(red or green)2.Accuracy:0.5% 3 digit3.Auxiliary power: AC 110V 10% 50/60Hz AC 220V 10% 50/60Hz4.Input signal: Voltage 100V 200V 380V or according to the requirement current:0-1A or0-5A5.Measuring range: 0-1.00(C or L)6.Consumption:<3.2VA7.Max Signal Consumption:<0.3VA8.Operating Environment: temperature -10 ~+50 humidity: 85%9.Storage Environment: temperature -30 ~+60 humidity: 70%10.Heat resistance: case of non-combustible plastic material11.Voltage Testing: over 2000V12.Fastening: By means of nuts, absolutely safe, fast, robust, side-by-side.
DIGITAL POWER FACTOR METER COS
Model: PE-D96W(Var), PE-D72W(Var)Function:measure the single phase Wattmeter, single phase Varmeter, 3P3Wwattmeter, 3P3W Varmeter, 3P4W Wattmeter or 3P4W Varmeter.Feature:1.Display:4 1/ 2 digital. LED display(red or green)2.Accuracy:1.0% 3 digit3.Auxiliary power: AC 110V 10% 50/60Hz AC 220V 10% 50/60Hz4.Input signal: Voltage 100V 200V 380V or according to the requirement current:0-5A5.Measuring range: all ranges6.Consumption:<3.2VA7.Max Signal Consumption:<0.3VA8.Operating Environment: temperature-10 ~+50 humidity: 85%9.Storage Environment: temperature-30 ~+60 humidity: 70%10.Heat resistance: case of non-combustible plastic material11.Voltage Testing: over 2000V12.Fastening: By means of nuts, absolutely safe, fast, robust, side-by-side.
DIGITAL POWER METER
OUTLINE DAWING:
C AD B
PE-96AC AMMETER
KA~
• A-15
• A-16
DIGITAL PANEL METER
PE-48
PE-48
PE-48
PE-48
Model: PE-D3A ACSize:96 48Feature:1.Display: 3 1/ 2 digital. LED display(red or green)2.Accuracy:0.5% 1 DIFIT3.Auxiliary power: AC 110V 10% 50/60Hz AC 220V 10% 50/60Hz4.Input signal: AC current5.Measuring range: 0-10A AC, For the current over 10A can use the AC current transformer.6.Consumption:<1.8VA7.Max Signal Consumption:<0.3VA8.Operating Environment: temperature -10 ~+50 humidity: 85%9.Storage Environment: temperature -30 ~+60 humidity: 70%10.Heat resistance: case of non-combustible plastic material according to UL94-V0.11.Voltage Testing: over 2000V
DIGITAL AC AMMETER
Model:PE-D3V ACSize:96 48Feature:1.Display: 3 1/ 2 digital. LED display(red or green)2.Accuracy:0.5% 1 DIFIT3.Auxiliary power: AC 110V 10% 50/60Hz AC 220V 10% 50/60Hz4.Input signal: AC Voltage5.Measuring range: 0-600A AC, For the Voltage over 600A can use the AC potential transformer.6.Consumption:<1.8VA7.Max Signal Consumption:<0.3VA8.Operating Environment: temperature -10 ~+50 humidity: 85%9.Storage Environment: temperature -30 ~+60 humidity: 70%10.Heat resistance: case of non-combustible plastic material according to UL94-V0.11.Voltage Testing: over 2000V
DIGITAL AC AMMETER
Model:PE-D3A DCSize:96 48Feature:1.Display: 3 1/ 2 digital. LED display(red or green)2.Accuracy:0.5% 1 DIFIT3.Auxiliary power: AC 110V 10% 50/60Hz AC 220V 10% 50/60Hz4.Input signal: DC current5.Measuring range: 0-20A DC6.Consumption:<1.8VA7.Max Signal Consumption:<0.3VA8.Operating Environment: temperature -10 ~+50 humidity: 85%9.Storage Environment: temperature -30 ~+60 humidity: 70%10.Heat resistance: case of non-combustible plastic material according to UL94-V0.11.Voltage Testing: over 2000V
DIGITAL DC AMMETER
Model:PE-D3V DCSize:96 48Feature:1.Display: 3 1/ 2 digital. LED display(red or green)2.Accuracy:0.5% 1 DIFIT3.Auxiliary power: AC 110V 10% 50/60Hz AC 220V 10% 50/60Hz4.Input signal: AC voltage5.Measuring range: 0-600V DC6.Consumption:<1.8VA7.Max Signal Consumption:<0.3VA8.Operating Environment: temperature -10 ~+50 humidity: 85%9.Storage Environment: temperature -30 ~+60 humidity: 70%10.Heat resistance: case of non-combustible plastic material according to UL94-V0.11.Voltage Testing: over 2000V
DIGITAL DC VOLTMETER
• A-17
Model: PE-D3W,PE-D3VarSize:96 48Funtion:measure the single phase Wattmeter, Varmeter, 3P3W wattmeter, 3P3WVarmeter, 3P4W Wattmeter or 3P4W Varmeter.Feature:1.Display: 3 1/ 2 digital. LED display(red or green)2.Accuracy:1.0% 1 DIFIT3.Auxiliary power: AC 110V 10% 50/60Hz AC 220V 10% 50/60Hz4.Input signal: Voltage 100V, 220V, 380V or the requirement current:0-5A5.Measuring range: all ranges6.Consumption:<1.8VA7.Max Signal Consumption:<0.3VA8.Operating Environment: temperature-10 ~+50 humidity: 85%9.Storage Environment: temperature-30 ~+60 humidity: 70%10.Heat resistance: case of non-combustible plastic material according to UL94-V0.11.Voltage Testing: over 2000V
Model: PE-D3FSize:96 48Feature:1.Display: 4 digital. LED display(red or green)2.Accuracy:0.2% 1 DIFIT3.Auxiliary power: AC 110V 10% 50/60Hz AC 220V 10% 50/60Hz4.Input signal: AC Voltage, rated signal value:0-600V(admissible input Voltage error 80%, +100%)5.Measuring range: 0-1MHz6.Consumption:<1.8VA7.Max Signal Consumption:<0.3VA8.Operating Environment: temperature-10 ~+50 humidity: 85%9.Storage Environment: temperature-30 ~+60 humidity: 70%10.Heat resistance: case of non-combustible plastic material according to UL94-V0.11.Voltage Testing: over 2000V
Model: Single phase: PE-D3PF1 Three phase: PE-D3PF3Size:96 48Feature:1.Display: 4 digital. LED display(red or green)2.Accuracy:0.5% 1 DIFIT3.Auxiliary power: AC 110V 10% 50/60Hz AC 220V 10% 50/60Hz4.Input signal: Voltage 100V, 220V, 380V, or according to the requirment current:0-5A5.Measuring range: all ranges6.Consumption:<1.8VA7.Max Signal Consumption:<0.3VA8.Operating Environment: temperature-10 ~+50 humidity: 85%9.Storage Environment: temperature-30 ~+60 humidity: 70%10.Heat resistance: case of non-combustible plastic material according to UL94-V0.11.Voltage Testing: over 2000V
DIGITAL FREQUENCY METER(Hz)
DIGITAL POWER FACTOR METER COS
DIGITAL POWER METER(KW)
Model
PE-96 48mm
mm
44 92
1.73 3.62
Number of Terminal
16
A1 A2 Panel cut-out sizeUnit
96108
A1
A2
8
29.8A~ 48
64
OUTLINE DAWING: SIZE OF RECTANGULAR TYPE METER
DIGITAL PANEL METER
PE-48
PE-48
PE-48
1.for correctly use of this instrument, please read carefully this specification before operation.2.keep properly this specification after reading.Technical date
Power supply:
Display range:
Precision:
Sampling speed:
A/D convert:
Operation temperature:
Power consumption:
AC 220V AC,DC 90-270V OR AC, DC 36-72V
MAX.DISPLAY 1999 LED 12.2mm H
0.5%fs 1 digit
About 2.5 TIMES/S
Dual scope
0~50
<3W
Weight:
Size:
Hole:
About300g
96mm(w) 48mm(h) 112mm(d)
93mm 45mm
AC 1500V 1MIN
DC 500V>100M
AC voltage range change
MAX.INPUT: AC600V
NO
7
6
5
4
600
3
199.9
2
19.99
1
First: AC600VModel: PE 35-AVModel: PE-96-AC
ON
1 2 3 4 5 6 7
AC current range change
MAX.INPUT:AC5A
NO
7
6
5
4
1999
199.9
19.99
1.999
3
1500
150.0
15.00
1.500
2
1000
100.0
10.00
1.000
1
500
50.0
5.00
.500
First: AC 1999/5VModel: PE 35-AAModel: PE-96-AA
ON
1 2 3 4 5 6 7
DC voltage range change
MAX.INPUT: AC600V
NO
7
6
5
4
600
3
199.9
2
19.99
1
1.999
First: DC600VModel: PE 35-DVModel: PE-96-DV
ON
1 2 3 4 5 6 7
DC current range change
MAX.INPUT:DC75mV
NO
7
6
5
4
1999
199.9
19.99
1.999
3
1500
150.0
15.00
1.500
2
100
100.0
10.00
1.000
1
500
50.0
5.00
.500
First: DC 199/75mvModel: PE 35-DAModel: PE-96-DA
ON
1 2 3 4 5 6 7
OPERATION RANGE
DESCRIPTION OF WIRING TERMINAL
(1).For best performance, the meter should be pre-heated 15minutes before operation if it is not use for a long time.(2).The meter should be used under condition of:Ambient temperature: 0-50 , Relative humidity: 85%(3). The calibration interval should be one year; the precision ofcalibrator should be superior to 0.1 Grade.(4). The meter should prevent from shocking and im pulsing, and should not use under condition of heavy dust or high concentration chemical drug or gas. Plea se apply power supply filter or other anti-interference circuit when use the meter in environment of high mag-netic field, high frequency or high voltage spark.(5). The calibrating rheostat is use for calibrating the meter, non-professional should not calibrate or disassembly the meter, as wellas no calibrator available.
18 10
12379
Input
H L
NC.
AC 220Vpower supply
AC 110V
1 2 3 4
5 6 7 8
H LINPUT
AC 220V
Power supply
AC 110V
PE35 wiring terminalSIZE:96 48 112mmHOLE:92 44mm
PE-96 wiring terminalSIZE:96 96 65mmHOLE:90 90mm
MAX.INPUT
Insulationstrength:Insulation
impedance:
VOLTAGE METER 600VCURRENT 5A AC>5A CT/5A DC/75mV
DIGITAL PANEL METER
TECHNICAL DATA
NOTE
PE-96A-S
DIGITAL PANEL METER
PE-96
• A-18
DIGITAL PANEL METER
For correctly of this instrument, please read carefully this specification before operation.Check the ratio CT value if match with ratio meter.Keep properly this specification after reading.1.Digit panel-type meter is a digital measurement instrument, which applying dual-integral method, consists of LSI and high-reliable components, high-accuracy A/D conver circuit and high-brightness LED display, with feature such as advanced design,reasonable distribution of components, nice appearance and easy to install. It is mainly use as displaying meter for every kindof instuments.2.Corretly connect the meter to power supply(AC220V) before using, clients also can select the meter with power supply otherthan AC220V(when supply by DC power, polarity must be correctly connected, otherwise, the meter will be destroyed).3.AC or DC imput voltage within measuring range(0-600V) could be measure and display directly. When the input voltage is morethan 600V, the meter must match with constant mutual-inductor.4.AC or DC input current within measuring range(0-10A) can be measure and display directly. When the AC input current ismore than 10A, the meter must match with constant mutual-inductor, when the DC input current is more than 10A, themeter must match with constant current-divide mutual-inductor, the display value will be error if the ratio of current-divider is notmatch with the meter.5.Commercial frequency meter sample the AC voltage signal, the merer can display directly the frequency value when inputvoltage signal is between 30V-600V, and the frequency measuring range is from 10.0Hz to 2000Hz.6.Single-phase or three-phase wattmeter and power-factor meter, please connect correctly according to the wiring diagram onthe meter, check carefully the high(H) and low(L) label beside the voltage or current input terminal. The display value will be errorif connect wrongly. The input voltage can be selectable with 100V, 220V or 380V, the input current should be between 0 to 5A, ifthe input current is more than 5A, the meter must match with constant current mutual-inductor, otherwise the display valueshould be error.7.As for input sensor signal is between 4 to 20 mA or 0 to 10V, the meter can be made to order by clients for measuing and display temperature, rotate speed or pressure, the specification is cover by other copy.8.Note:(1).For best performance, the meter should be pre-heated 15 minutes before operation if it is not use for a long time.(2).The meter should be used under condititon of:Ambient temperature: 0-50 , Relative humidity: 85%(3).The calibration interval should be one year; the precision of calibrator should be superior to 0.1 Grade.(4).The meter should prevent from shocking and impulsing, and should not use under conditon of heavy dust or high concentrationchemical drug or gas. Please apply power supply filter or other anti-interference circuit when use the meter in environment ofhigh magnetic field, high frequency or high voltage spark.(5). The calibrating rheostat is use for calibrating the meter, non-professional should not calibrate or disassemblythe meter, as well as no calibrator available.
DIGITAL PANEL METER
PE-96PE-96
• A-19
MODULAR TYPE PANEL METER
DC VOLTMETRS
Model: PE-C45VAccuracy: Class 1.5Specification:20V 30V 50V 100V 150V 200V 250V 300V 450V 600V 1000VMeasuring ranges over 450V with external re-sistor (rated current 5mA)Heat resistance: case of non-combustible plasticmaterial.Mounting type: DIN rail
FREQUENCY METERS AC VOLTMETRS
Model: PE-F45VAccuracy: Class 1.0Specification:Voltmeter: 100V 220V 380V 440VFrequency: 45-55Hz 45-65Hz 47-63Hz 57-63Hz 44-56Hz 54-66Hz 350-450Hz 450-550Hz 550-650HzHeat resistance: case of non-combustible plasticmaterial.Mounting type: DIN rail
Model: PE-F45VAccuracy: Class 1.0Specification:30V 50V 75V 120V 120V 150V 250V 400V 450V 500V 600VFor450V-450KV, meters can use potential trans-former with secondary voltage 100V.Heat resistance: case of non-combustible plasticmaterial.Mounting type: DIN rail
DC AMMETRS POWER FACTOR METER COS AC VOLTMETRS
Model: PE-T45AAccuracy: Class 1.5Specification: 100 A 500 A lmA 3mA5mA 10mA 20mA 30mA 50mA 100mA 150mA200mA 250mA 300mA 500mA 1A 3A 7.5A10A 15A 20AFor 10A-10KA, use external 75mV 60mV or45mV shunt. For the direct reading from 20A to60A meter the class is 2.5A.Heat resistance: case of non-combustible plasticmaterial.Changeable scale: The dial plate with the samescale division, which is at the same internal value,can be changeable.
Model: PE-PF45Accuracy: Class 2.5Single phase: 100V 220V 380V 440V current: 5AThree phase: 100V 220V 380V 440V current: 5ASpecification: 0.5cap-1-0.5ind 0.3cap-1-0.7ind 0.4cap-1-0.4ind 0.7-1-0.2indHeat resistance: case of non-combustible plasticmaterial.Frequency: 50Hz or 60HzMounting type: DIN rail
Model: PE-T45AAccuracy: Class 1.5 2.5Specification: 0.1A 0.5A 1A 7.5A 10A 15A 20A 30A 40A 60AFor 10-10KA, use external current transformerwith secondary current 5A. For the direct readingfrom 20A to 60A meter, the class is 2.5 .Heat resitance: case of non-combustible plasticmaterial.Changeable scale: All scales with printingtechnique. The dial plate with the same scaledivision, which is at the same division and inter-nal value, can be changeable.
PE-C45V PE-C45VPE-C45V
PE-C45VPE-C45V
PE-C45V
MODULAR TYPE PANEL METER
• A-20
45.3
30.6
8.5
K
45.3
62.7
6435
51.7
19.7
D
87.2
65
32
1 2 3 4220V
MOVING COIL INSTRUMENT POWER METERS
Wattmeter Model: PE-W45Varmeter Model: PE-VAR45Accuracy: Class 1.5Specification:Voltage: Single phase: 100A 200V 380VThree phase three wire: 100A 220V 380V 415VThree phase four wire: 100A 220V(380)V 240V( 415)VAbove-mentioned can be connected directly. The following should be connected with voltagetransformers: 380/100V 500/100V 3K/100V 6K/100V 10K/100 15K/100V 35K/100V...Current: 1A, 5AThe voltage circuits of the meter connected with voltage transformers. Which secondary voltage is100V, if the secondary voltage is lower than 450V, it also can be connected directly. The currentcircuits connected with current transformers, which secondary current is 5A or 1A. Wattmeters andVarmeters with converter for three-phase three wires or four wire and single phase, which can beused for balance and unbalance burden circuit.Heat resistance: Case of non-combustible plastic material.Frequency: 50Hz or 60HzFastening: By means of nust, absolutely safe, fast, robust, side-by-sideMounting: DIN rail: 72mm 87.2mm 65mm
MODULAR (EXPLOSION-PROOF)OUTLINE DRAWING
PE-36
PE-100
SIZE OF DIN RAIL TYPE SERIES METER
Model
PE-36
PE-45
PE-100
Unit
mm
mm
mm
D
36
45
100
Number of Terminal
4
4
10
Measurement of Din Rail
35
35
35
PE-VAR45
PE-W45
PE-Var45
PE-W45
MODULAR TYPE PANEL METER
• A-21
DIGITAL MODULAR AC & DC AMMETER AND VOLTMETERModel: PE-D365 AC PE-D365 DCFeature:1. Display: 3 1/2digits. LED display (red or green)2. Accuracy: 0.5% 2 digits3. Auxiliary power: AC 110V 10% 50/60Hz or AC 110V 10% 50/60Hz4. Input signal: AC current8.5. Measuring range: 0-10A Acm if the current morethan 1A, the meter should be used with current trans- former.0-10A DC, if the current more than 10A, the meter should be used with shunt.6. Consumption: <1.8VA7. Max Signal Consumption: <0.3VA8. Operating Environment: temperature0 ~-40 humidity: 85%9. Storage Environment: temperature-40 ~+60 humidity: 70%10. Heat resistance: case of non-combustible plastic material11. Hi-pot testing: more than 2000V
POWER FACTOR METER COSORDCRING MODEL (SINGLE PHASE): PLY-D725PF(1P)(3 PHASE): PLY-D725PF(3P)
Feature:1. Display: 4digits. LED display (with red and green options)2. Accuracy: (0.5% reading +3 digits)3. Auxiliary power: AC 110V 10% 50/60Hz or AC 110V 10% 50/60Hz4. Input Signal: 100V,220V,380V Current 0-1A or 0-5A is at users option.5. Measuring range: 0o -360o phase angle.6. Power Consumption: <3.2VA7. Maximum Voltage Consumption: <0.5VA Maximum Current Consumption: <0.5VA8. Operating Environment: 0 ~-40 Relative Humidity: 85%9. Shelf Environment: -40 ~+60 Relative Humidity: 70%10. Hi-pot Testing: AC 2000V/1min11. External Case: Made of non-flammable plastic material.12. Fixing Mode: Sliding in (PLY-D120); Din rail mode (PLY-D725)13. Imbedding Depth: 53mm (PLY-120); 65mm (PLY-D725)
DIGITAL POWER METER
Ordering Model: PLY-D725W (Var)Function: For measuring single phase withpower, single phase without power.Feature:1. Display: 4 1/2digital LED display(with red and green options)2. Accuracy: (0.5% reading +3 digits)3. Auxiliary power: AC 110V 10% 50/60Hz and AC 220V 10% 50/60Hz4. Input Signal: Voltage 100V, 220V, 380V. Current 0-1A or 0-5A is atusers option.5. Measuring Range: At users option.6. Power Consumption: <3.2VA7. Maximum Voltage Consumption: <0.5VA Maximum Current Consumption: <0.5VA8. Operating Environment: 0 ~40 . Relative Humidity: 85%9. Shelf Environment: -40 ~+60 Relative Humidity: 70%10. Hi-pot Testing: AC 2000V/1 min11. External Case: Made of non-flammable white plastic material.12. Fixing Mode: Sliding in (PLY-D120); Din rail mode (PLY-D725)13. Imbedding Depth: 53mm (PLY-120); 65mm (PLY-D725)
PLY-D725
PE-D36A
PE-D36V
MODULAR TYPE PANEL METER
• A-22
Function: For measuring the DC/AC current andvoltage.Ordering Model: PLY-D725A/V or DCFeature:1. Display: 3 1/2digital LED display (with red and green options)2. Accuracy: (0.5% reading +2 digits)3. Auxiliary Power: AC 110V 10% 50/60Hz or AC 220V 10% 50/60Hz4. Input Signal: AC/DC current and voltage.5. Measuring Range: 0-20A AC, for those above20A, match with current transformer;0-20A DC for those above 20A, match with shunt;0-600V-AC for those above 600V, match with voltage transformer.0-600V-DC6. Power Consumption: <3.2VA7. Maximum Signal Consumption: <0.5VA8. Operating Environment: 0 ~40 . Relative Humidity: 85%9. Shelf Environment: -40 ~+60 Relative Humidity: 70%10. Hi-pot Testing: AC 2000V/1 min11. External Case: Made of non-flammable plastic material.12. Fixing Mode: Flush fixing with nuts.13. Imbedding Depth: 43mm
DIGITAL AC/DC AMMETER & VOLTMETER
Ordering Model: PLY-D725FFeature:1. Display: 4digital LED display (with red and green options)2. Accuracy: (0.1% reading +1 digits)3. Auxiliary Power: AC 110V 10% 50/60Hz or AC 220V 10% 50/60Hz4. Input Signal: VC voltage, rated signal amplitude value 0-600V optional (Input voltage error allowance: -80%, +100%)5. Measuring Range: 1.000-9999Hz6. Power Consumption: <3.2VA7. Maximum Signal Consumption: <0.5VA8. Operating Environment: 0 ~40 Relative Humidity: 85%9. Shelf Environment: -40 ~+60 Relative Humidity: 70%10. Hi-pot Testing: AC 2000V/1 min11. External Case: Made of non-flammable plastic material.12. Fixing Mode: Sliding in (PLY-D120); Din rail mode(PLY-D725)13. Imbedding Depth: 53mm(PLY-120);65mm (PLY-D725)
DIGITAL FREQUENCY METER
PLY-D725
PLY-D725
ELECTRIC CABLE FITTING
• A-23
APPLICATIONS
This series of thermal relay can be used in the circuit of 50Hz or 60Hz,rated ins ulation voltage 660V,rated current 0.1-96A for protecting the phase b reak when the electric motor is overload.The relay has different mechanism and temperature compensation & can be plugged in PLC1-D series AC contactor.It is the most advanced thermal relay in the nineties in the world.
SPECITFICATION
TypeRated working current
of thermal relay
Thermal component
Rated current (A)
Rated or scale of rated current(A)
0.10-0.160.16-0.250.25-0.400.40-6.30.63-1.01.0-1.6
1.25-2.01.6-2.52.5-4.04.0-6.05.5-8.0
7.0-10.09.0-13.0
12.0-18.017.0-25.023.0-32.028.0-36.023.0-32.030.0-40.037.0-50.048.0-65.055.0-70.063.0-80.080.0-93.0
0.160.250.400.631.01.62.02.54.06.08.0
10.013.018.025.0323632405065709093
PLR2-D 13011302130313041305130613x613071308131013121314131613211322
PLR2-D 23532355
PLR2-D 3353335533573359336133633365
PLR2-D13
PLR2-D23
PLR2-D33
25
36
93
PLR2-D THERMAL RELAY
CHARACTERISTIC
A.Fundamental parameter of the main circuit(a).Rated insulation voltage 660V.(b).Rated working current 25,36,93A separately.(c).The regulator seal of rated setting current and setting.(d).Current of the thermal component(see list 1)B.Auxiliary Circuit(a).There is one pair of NO/ and N/C contact with electric insulation.(b).Rated insulation voltage 500V.(c).Rated frequency 50-60Hz.(d).Use group, rated working voltage ,appoint thermal current and rated current.
PLR2-D13
PLR2-D23
PLR2-D33
THERMAL RELAY
B B-01
Type
Adjustingrange of current
(A)
Control power(AC)(KW) Plug-in
contactor220V 380V 415V 440V 660V
PLR1-D 09301
PLR1-D 09302
PLR1-D 09303
PLR1-D 09304
PLR1-D 09305
PLR1-D 09306
PLR1-D 09307
PLR1-D 09308
PLR1-D 09310
PLR1-D 09312
PLR1-D 09314
PLR1-D 09316
PLR1-D 16321
PLR1-D 25322
PLR1-D 40353
PLR1-D 40355
PLR1-D 63357
PLR1-D 63359
PLR1-D 63361
PLR1-D 80363
PLC1-D09-25PLC1-D09-25PLC1-D09-25PLC1-D09-25PLC1-D09-25PLC1-D09-25PLC1-D09-25PLC1-D09-25PLC1-D09-25PLC1-D09-25PLC1-D09-25PLC1-D09-25PLC1-D09-25PLC1-D09-25PLC1-
D40 50 60PLC1-
D40 50 60PLC1-
D40 50 60PLC1-
D40 50 60PLC1-
D40 50 60PLC1-
D40 50 60
0.37
0.55-0.75
1.1
1.5
2.2
3
4
5.5
7.5
10
11
15
18.5
22
0.1-0.16
0.16-0.25
0.25-0.40
0.40-0.63
0.63-1
1-1.6
1.6-2.5
2.5-4
4-6
5.5-8
7-10
10-13
13-18
19-25
23-32
30-40
38-50
48-57
57-66
63-80
0.37
0.55-0.75
1.1-1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
25
30
33-37
0.55
0.55-0.75
1.5
2.2
3
4
5.5
9
1
15
2
25
30
37
33-37
1.1
1.5
2.2
3
4
5.5
9
1
15
2
25
30
37
33-37
0.37
0.55
0.7-1.1
1.5
2.2-3
4
5.5
7.5
10
15
18.5
22
30
37
45
55
59-63
APPLICATIONS
PLR1-09301
PLR1-25322
PLR1-09305
PLR1-D THERMAL RELAY
PLR1-D series thermal relay is suit able for ther mal p rotect ion in the circuit with AC 50 or 60Hz,voltage up to 660V,motor power up to 45KW or less. It has diffe rent attachment and temperature compensating function. It can be fixed onto contactor an d can a lso be fixed independently. The product is made in ac cor dan ce w ith IEC 292 -1 P LR1-D series thermal relay and has kinds of species,9A,12A 16A,25A,40A,63A,80A.
SPECIFICATION
THERMAL RELAY
B B-02
PLRD THERMAL RELAYDifferential thermal overload relays for using with fuseCompensated relays with manual or automatic reset,with relay trip indicator,for AC.or DC.
Relay setting rangeFor using with
contactor PLC11-Reference Weight
Class 10A(1)with connection by screw clamp teminals
aM gG BS88A A A
0.10..0.160.16...0.250.25...0.400.40...0.630.63...11...1.71.6...2.52.5...44...65.5...87...109...1312...1816...2423...3230...3817...2523...3230...4037...5048...6555...7063...8080...10480...10495...120110...14080...10495...120110...140
0.250.51122468
12121620254050254040638080
100125125160100125160
2222446
1016202025
2355063805063
100100100125125160200200250160200250
-----6
101616202025325063805063
08010010012515
160160200200160200200
D09...D38D09...D38D09...D38D09...D38D09...D38D09...D38D09...D38D09...D38D09...D38D09...D38D09...D38D12...D38D18...D38D25...D38D25...D38
D32 and D38D40...D90D40...D90D40...D90D40...D90D50...D90D50...D90
D65 and D96D80 and D96
D115 and D150D115 and D150
D150(2)(2)(2)
0.1240.1240.1240.1240.1240.1240.1240.1240.1240.1240.1240.1240.1240.1240.1240.1240.5100.5100.5100.5100.5100.5100.5100.5100.9000.9000.9001.0001.0001.000
PLRD-01PLRD-02PLRD-03PLRD-04PLRD-05PLRD-06PLRD-07PLRD-08PLRD-10PLRD-12PLRD-14PLRD-16PLRD-21PLRD-22PLRD-32PLRD-35
PLRD-322PLRD-3353PLRD-3355PLRD-3357PLRD-3359PLRD-3362PLRD-3363PLRD-3365PLRD-4365PLRD-4367PLRD-4369
PLRD-33656PLRD-33676PLRD-33696
Class 10A(1)with spring terminal connections(for direct mounting on the contactor only)
0.10..0.160.16...0.250.25...0.400.40...0.630.63...11...1.71.6...2.52.5...44...65.5...87...109...1312...1816...24
0.250.51122468
1212162025
2222446
1016202025
23550
-----6
1016162020253250
D09...D38D09...D38D09...D38D09...D38D09...D38D09...D38D09...D38D09...D38D09...D38D09...D38D09...D38D12...D38D18...D38D25...D38
0.1400.1400.1400.1400.1400.1400.1400.1400.1400.1400.1400.1400.1400.140
PLRD-013PLRD-023PLRD-033PLRD-043PLRD-053PLRD-063PLRD-073PLRD-083PLRD-103PLRD-123PLRD-143PLRD-163PLRD-213PLRD-223
Thermal overload relays for using with unbalanced loadsClass 10A(1) with connection by screw clamp terminalsChange the prefix in the referenes above from PRD(except PRD-4...) to PLRD-D.Example:PRD-01 becomes PR3-D01.Thermal overload relays for using on 1000V suppliesClass 10A(1) with connection by screw clamp terminals(1)Standard IEC947-1 specifies a tripping time for 7.2 times the setting current I :R
class 10A:between 2 and 10 seconds.(2)Independent mounting.
A
PLRD-13
PLRD-23
PLRD-33
THERMAL RELAY
B B-03
P3UA-50
P3UA-52
P3UA-58
P3UA series thermal relay is suitable for using is power system with AC 50Hz,ra ted opertaionvoltage up to 660V and 1000V, in main circuit,current form 0.1A to 630A, It is used to protect ACthree-phase asynchronous motor against overload and open-phase. The rel ays ha ve the rest push-button for breaking NC contacts and the opertaing indication and free trip characteristics. The products also can be supplied with protecting case to ensure safety.The products can be plugged inthe contactor and installed independently or mounted by rail.
P3UA SERIES THERMAL RELAY
0.16~0.250.32~0.630.8~1.251.25~22~3.23.2~55~8
8~12.50.16~0.250.4~0.630.8~1.251.25~22~3.23.2~5
5.88~12.5
12.5~20
6.3~1012.5~2020~3220~3232~5050~6363~80
0.16~0.250.4~0.630.8~1.251.25~22~3.23.2~55~8
8~12.512.5~2020~3232~4550~6363~90
90~120120~150150~180125~200200~320
400~630
0.1~0.160.25~0.40.63~0.1
1~1.61.6~2.52.5~44~6.3
6.3~100.1~0.160.25~0.40.63~11~1.6
1.6~2.52.5~44~6.3
6.3~1010~1616~254~6.310~1616~2516~2525~4040~5757~70
0.1~0.160.25~0.40.63~11~1.6
1.6~2.52.5~44~6.3
6.3~1010~1616~2525~4040~5755~80
80~110110~135135~16080~125
180~250250~400320~500
P3UA50
P3UA52
12.5
25
660
660
P3UA54
P3UA58
P3UA59
P3UA62
P3UA66
P3UA68
32 660
80
63
180
400
630
1000
1000
1000
660
Type Rated opertaing current(A)
Rated insulation voltage(V) Current setting range(A)
SPECIFICATION
THERMAL RELAY
B B-04
APPLICATIONS
660
APPLICATIONS
PTH-K/N THERMAL RELAY
The thermal overload relays are suitable for overload protection of AC motor operated on 8-hour duty or uninterrupted duty. The overload protected AC motor with frequency 50Hz,voltage upto 660V, current up to 40A. Several functions provided by these relays are phase-failure protection,temperature compensation,ON/OFF indicat ion a nd manual/automatic reset.The relays comply withIEC292-1 standard.
SPEIFICATION
TypePlug in AC
contactRtaed current of
Thermal element(A) Setting current range(A)
PTH-K12
PTH-K20
PTH-K60
S-K10 S-K11
S-K12 S-K18
S-K20 S-K21
S-K23 S-K35
S-K50 S-K65
S-K80 S-K95
0.1-0.28 0.28-0.42 0.4-0.6 0.55-0.85 0.7-1.1 1-1.6
1.4-2 1.7-2.1 2-3 28-4.4 4-6 5.2-8 7-11 9-13
34-50 43-6542,54
1.7-2.1 2-3 2.8-4.4 4-6 5.2-8 7-11 9-13
12-18 16-22 18-26 24-34 30-40
0.15,0.35,0.5,0.7,0.9,1.3,
1.7,2.1,2.5,3.6,5,6.6,9,11
2.1,2.5,3.6,5,6.6,9,11,
15,19,22,29,35
30-50
48-80
60-100
90-150
132-220
200-330
300-500
380-630
F115-F185
F115-F185
F115-F185
F115-F185
F225-F265
F330-F500
F330-F500
F400-F630
Type
PLR9-200
Setting range For contactor
PLR9-630
PLR9 SERIES ELECTRONIC THERMAL RELAY
132 d
174
120
255
136
PTH-K12
PTH-K20
PTH-K60
PLR9-200
PLR9-630
THERMAL RELAY
B B-05
PTH-K20KP
PTH-K60KP
THERMAL RELAY
Element No.
Type
Ratings Nominal current
PTH-22 PTH-40 PTH-85Ranges Ranges Ranges
Min. Mid. Max. Min. Mid. Max. Min. Mid. Max.
Rated current(A)
0.140.210.330.520.821.32.13.35
6.57.58.511151922303442556574
0.10.160.250.4
0.631
1.62.545679
1216
0.140.210.330.520.821.32.13.35
6.57.58.5111519
0.160.250.4
0.631
1.62.54689
10131822
45679
1216182428
56.57.58.5111519223034
689
10131822263640
79
121618242834455463
8.511151922303442556574
1013182226364050657585
Aux.contactReset typePower consumptionDimension(mm) (W H D) Separate mounting unit
2heaters3heaters
Standardoption
Standardoption
Standardoption
Other model
Applied contactorsApplied switches
3heatersDifferentialDelay open
1NO1NCAuto/Manual1.8VA/heater44 63 90
AZ-22HPTH-22/3PTK-22
PTH-22/LPMC-9,12,18,22PMS-9,12,18,22
1NO1NCAuto/Manual2.0VA/heater53 67 90
AZ-40HPTH-40/3PTK-40
PTH-40/LPMC-32,40PMS-32,40
1NO1NCAuto/Manual3.5VA/heater70 73 103
AZ-85HPTH-85/3PTK-85
PTH-85/LPMC-50,65,75,85PMS-50,65,75,85
PTH SERIES THERMAL OVERLOAD RELAY
APPLICATION
The TOR Protect the motors, Locking, Open phase(differential)
CHARACTERISTICSDirect mounting structure
The TOR is mounting directly to the Magnetic Contactors without addtional brackets.(Applied model: PTH-22, 40, 85)
Safety coverThe finger proof safety cover prevent careless touch of electric conductor(Applied model:PTH-22, 40, 85)
Separation of power part and operation partThe main circuit and the operation part are separately designed and the operation part iscommonly used in PTH-22, 40, 85
Easy operation
TYPES AND RATINGS
PTH-22
PTH-40
PTH-85
B B-06
SOLID STATE RELAY
45
59
11.5 2- 4
Size(mm):59 45 25On-off time:Below 0.5 period of 1ms+load currentLoad Voltage:25V-250VAC, H:150V-450VACOutput Voltage Drop:1.8VmaxOff Leakage Current:Type zero-crossing:10mA max.(at 220VAC)15mA max.(at 380VAC)Type random 5mA max(at 220VAC) 10mA max.(at 380VAC)Insulation Resistance: 100M min. (at 500VDC)Dielectric Strength: 2000VAC 50Hz/1minOperating Temperature: -20 ~80
48m
m
2- 4.5
LED
Size(mm) 62.5 45 23.5Controlmethod:DA:DC control of AC AA:AC control of ACControl Voltage:3-32VDC 80-250VACLoad Voltage:24V-380VAC,H:90V-480VACOutput Voltage Drop:1.5Vmax.Off Leakage Current: 5mA No build-in RC absorption ringInsulation Resistance: 1000M 500VDC Voltage testingDielectric Strength: 4000Vrms lnput terminal output terminal 2500Vrms lnput terminal, output terminal radiatorOperating Temperature: -20 ~80
48m
m
2- 4.5
LED
Size(mm): 62.5 45 23.5Control method:VA:Solid voltage regulatorControl Voltage:Outside-controlled adjustsble potentiometer 470K -560K /2WLoad Voltage:24V-380VAC,H:90V-480VACOutput Voltage Drop:1.5Vmax.Off Leakage Current: 5mA No build-in RC absorption ringInsulation Resistance: 1000M 500VDC Voltage testingDielectric Strength: 4000Vrms lnput terminal output terminal
2500Vrms lnput terminal, output terminal radiatorOperating Temperature: -20 ~80
48m
m
2- 4.5
LED
Size(mm): 57.4 44.8 28Control method:DC control of AC,AC control of AC, Solid voltage regulatorLoad Voltage:24V-380VAC,H:90V-480VACOutput Voltage Drop:1.5Vmax.Off Leakage Current: 5mA No build-in RC absorption ringInsulation Resistance: 1000M 500VDC Voltage testingDielectric Strength: 4000Vrms lnput terminal output terminal 2500Vrms lnput terminal, output terminal radiatorOperating Temperature: -20 ~80
Size(mm):59 45 25On-off time:Below 0.5 period of 1ms+load currentLoad Voltage:25V-250VAC, H:150V-450VACOutput Voltage Drop:1.8VmaxOff Leakage Current:Type zero-crossing:10mA max.(at 220VAC)15mA max.(at 380VAC)Type random 5mA max(at 220VAC) 10mA max.(at 380VAC)Insulation Resistance: 100M min. (at 500VDC)Dielectric Strength: 2000VAC 50Hz/1minOperating Temperature: -20 ~80
45
59
11.5 2- 4
Size(mm) 59 45 25On-off time Below 0.5 period of 1ms+load currentLoad Voltage 25V-250VAC, H:150V-450VACOutput Voltage Drop:1.8VmaxOff Leakage Current:10mA max.(at 200VAC) 20mA max.(at 380VAC)Insulation Resistance: 100M min. (at 500VDC)Dielectric Strength: 2000VAC 50Hz/1minOperating Temperature: -20 ~80
45
59
11.5 2- 4
SOLID STATE RELAY
JGX-25F
JGX-40F
JGX-60F
SSR-10 DA
SSR-10 VA
P/N 4B3991
B B-07
GENERAL RELAY
Type WeightContact
capacity
Coil nominal
voltageCoil nominal power
Insulation
resistance
Contact
resistance
Dielectric
strength
Expectancy(ops)Electrical
Mechanical
Operating
temperature
55.02
57.04
70.2
70.3
35g
35g
85g
85g
10A 250VAC
10A 30VDC100M
100M
100M
100M
50m
50m
50m
50m
-40 to 60
-40 to 60
-40 to 60
-40 to 60
BOC 1000VAC
BCC 1500VACBOC 1000VAC
BCC 1500VAC
BOC 1000VAC
BCC 1500VAC
Ele 100,000
Me 10,000,000
Ele 100,000
Me 10,000,000Ele 100,000
Me 10,000,000
DC 6V to 110V
AC 6V to 240V
DC 6V to 110V
AC 6V to 240V
DC 6V to 220V
AC 6V to 380V
DC 1.5W
AC 2.0VA to 2.8VA
DC 6V to 220V
AC 6V to 380V
DC 1.5W
AC 2.0VA to 2.8VA
BOC 1000VAC
BCC 1500VAC
Ele 100,000
Me 10,000,000
5A 250VAC
5A 30VDC
10A 250VAC
10A 30VDC
10A 250VAC
10A 30VDC
DC 0.9W
AC 0.9VA to 1.2VADC 0.9W
AC 0.9VA to 1.2VA
APPLICATIONS
The following general relay is widely suitable for DC or AC circuit switching in various auto mation devices, p rocess control and communication equipments etc.It is characteristic of stable perfomance, high reliability, capable of making and breaking relatively large load current, easy in maintenance and inspection as well as long service life.The plug-in base of the relay is suitable for using with standard 8 and 11 pins socket.
GENERAL RELAY
57.02 57.04 70.2 70.3
Model
HH53P
HH54P
JQX-14FC-1Z(16A)
JQX-14FC-1Z
Coil nominal voltage Coil nominal power Electrical life Mechanical life Operating temperature Weight Mounting methods
DC 6 to 110VAC 6 to 220V
DC 6 to 110VAC 6 to 240V
DC 6 to 110VAC 6 to 220VDC 6 to 110VAC 6 to 220V
DC 0.9WAC 1.2VA
DC 0.9WAC 0.9 to 1.2VA
DC 0.55WAC 0.9 VAto2.5VA
DC 0.55WAC 1.2 to 2.5 VA
510 OPS
510 OPS
510 OPS
510 OPS
510 OPS
710 OPS
710 OPS
710 OPS
710 OPS
710 OPS
-40 ~70
-40 ~70
-40 ~70
-40 ~70
-40 ~70
32g
32g
32g
16g
16g
Flange,Outlet
Flange,Outlet
Printed-circuti board
Printed-circuti board
HH53P HH54P JQX-14FC-1Z(16A) JQX-14FC-1ZHH52P
HH52P DC 6 to 110VAC 6 to 220V
DC 0.9WAC 1.2VA
Flange,Outlet
B B-08
GENERAL RELAY
Type WeightContact
capacity
Coil nominal
voltageCoil nominal power
Insulation
resistance
Contact
resistance
Dielectric
strength
Expectancy(ops)Electrical
Mechanical
Operating
termperature
55.02
55.02
60.2
60.3
35g
35g
80g
80g
10A 250VAC
10A 30VDC100M
100M
100M
100M
50m
50m
50m
50m
-40 to 60
-40 to 60
-40 to 60
-40 to 60
BOC 1000VAC
BCC 1500VACBOC 1000VAC
BCC 1500VAC
BOC 1000VAC
BCC 1500VAC
Ele 100,000
Me 10,000,000
Ele 100,000
Me 10,000,000Ele 100,000
Me 10,000,000
DC 6V to 110V
AC 6V to 240V
DC 6V to 110V
AC 6V to 240V
DC 6V to 110V
AC 6V to 240V
DC 1.5W
AC 2.0VA to 2.8VA
DC 6V to 110V
AC 6V to 240V
DC 1.5W
AC 2.0VA to 2.8VA
BOC 1000VAC
BCC 1500VAC
Ele 100,000
Me 10,000,000
5A 250VAC
5A 30VDC
10A 250VAC
10A 30VDC
10A 250VAC
10A 30VDC
DC 0.9W
AC 0.9VA to 1.2VADC 0.9W
AC 0.9VA to 1.2VA
Type WeightContace
capacity
Coil nominal
voltageCoil nominal power
Insulation
resistance
Contact
resistance
Dielectric
strength
Expectancy(ops)Electrical
Mechanical
Operating
termperature
58.02
56.02
56.04
35g
35g
70g
100M
100M
100M
50m
50m
50m
-40 to 70
-40 to 70
-40 to 70
BOC 1000VAC
BCC 1500VAC
Ele 100,000
Me 10,000,000DC 6V to 110V
AC 6V to 240V
DC 0.9W
AC 0.9VA to 1.2VA
DC 6V to 110V
AC 6V to 240V
DC 6V to 110V
AC 6V to 240V
DC 0.9W
AC 0.9VA to 1.2VA
BOC 1000VAC
BCC 1500VAC
BOC 1000VAC
BCC 1500VAC
Ele 100,000
Me 10,000,000
Ele 100,000
Me 10,000,000
10A 250VAC
10A 28VDC
10A 250VAC
10A 28VDC
10A 250VAC
10A 28VDC
DC 1.6W
AC 2.5VA
APPLICATIONS
The following general re lay is widely suitable for DC or AC circuit switching in various automation devices, process control and commmunicationequipments etc.It is characteristic of stable perfomance. High reli abil ity, c apab le of maki ng an d brc akin g rela tivcly large load cu rren t, ea sy in maintenance and inspection as well as long service life.The plug-in base of the relay is suitable for using with standard 8 and 11 pins socket.
GENERAL RELAY
58.02 56.02 56.04
60.360.255.0455.02
B B-09
GENERAL RELAY
Coil nominal voltage Coil nominal power Electrical life Mechanical life Operating temperature Weight Mounting methods
55.12
55.14
56.12
56.14
DC 6V to 110VAC 6V to 240V
DC 0.9WAC 0.9VA to 1.2VA
510 OPS
510 OPS
510 OPS
510 OPS
710 OPS
710 OPS
710 OPS
710 OPS
-25 ~55
-25 ~55
-25 ~55
-25 ~55
35g
35g
35g
70g
Printed-circuit board,Flange,Outlet
Printed-circuit board,Flange,Outlet
Printed-circuit board,Flange,Outlet
Printed-circuit board,Flange,Outlet
Model
DC 6V to 110VAC 6V to 240V
DC 6V to 110VAC 6V to 240V
DC 6V to 110VAC 6V to 240V
DC 0.9WAC 0.9VA to 1.2VA
DC 0.9WAC 0.9VA to 1.2VA
DC 0.9WAC 2.5VA
GENERAL RELAY
346.
5
2
6 7
13 14
1 3
59 10 11
8
4
1227.5
6.5
6.3
4.2
20.52.8 1.8
(-) (+)
55.14
Size(mm) 20.5 27.5 34Terminal layout 4ZContact capacity 3A 250VAC 3A 30VDCContact resistance 50mInsulation resistance 100MDielectric strength BOC 1000VAC
BCC 1500VAC
35.3
6.5
2
6
7
1
3
5
(-)8
4
13.2
20.52.8 1.8
27.5
6.5
6.3
4.2
(+)
55.12
Size(mm) 20.5 27.5 35.3Terminal layout 2ZContact capacity 5A 250VAC 5A 30VDCContact resistance 50mInsulation resistance 100MDielectric strength BOC 1000VAC
BCC 1500VAC
2
6
7
1
35(-)
8
435.3
6.5 14.2
1020.8
4.6
67.1
5 27
4.9 0.5
(+)
56.12
Size(mm) 20.8 27 35.3Terminal layout 2ZContact capacity 10A 250VAC 10A 28VDCContact resistance 50mInsulation resistance 100MDielectric strength BOC 1000VAC
BCC 1500VAC
2
6 7
13 14
1 3
5
(-) (+)
9 10 118
4
12
356.
5
4.90.5
4.6
67.
228
103041
56.14
Size(mm) 41 28 35Terminal layout 4ZContact capacity 10A 250VAC 10A 28VDCContact resistance 50mInsulation resistance 100MDielectric strength BOC 1000VAC
BCC 1500VAC
55.12
55.14
56.12
56.14
B B-10
GENERAL RELAYGENERAL RELAY
Model Coil nominal voltage Coil nominal power Electrical life Mechanical life Operating temperature Weight Mounting methods
MK-2P
FMK-2P
DC 6 to 110VAC 6 to 220V
DC 6 to 110VAC 6 to 220V
DC 2WAC 3.5 VA
DC 2WAC 3.5 VA
DC 2WAC 3.5 VA
710 OPS
710 OPS
710 OPS
-40 ~65
-40 ~55
-40 ~70
78g
78g
76g
510 OPS
510 OPS
510 OPS
MK-3P DC 6 to 110VAC 6 to 220V
FMK-2P
Size(mm) 32.6 36.5 52Terminal layout 2PContact capacity 10A 220VAC 10A 28VDCContact resistance 50mInsulation resistance 500MDielectric strength BOC 1000VAC
BCC 1500VAC
FMK-2P
50
2.4
9.2
12
345
6
78 1
2
345
6
78
5 4
6 3
7 2
8 1
32.5
36.5
60.2-1 60.2-2
Size(mm) 34 34 50.5Terminal layout 3PContact capacity 10A 220VAC 10A 28VDCContact resistance 50mInsulation resistance 500MDielectric strength BOC 1000VAC
BCC 1500VAC
MK-3P
1 23
4
567
8
9
1011
50.5
2.4
34
34
12
11
34
5678910
12
11
34
5678910
111
678910 2
34
5
MK-3P
MK-2P
Size(mm) 34 34 50.5Terminal layout 2PContact capacity 10A 220VAC 10A 28VDCContact resistance 50mInsulation resistance 500MDielectric strength BOC 1000VAC
BCC 1500VAC
50.5
2.4
5 46 37 28 1
34
34
12
345
6
78
12
345
6
78
MK-2P
Size(mm) 32.6 36.5 52Terminal layout 3PContact capacity 10A 220VAC 10A 28VDCContact resistance 50mInsulation resistance 500MDielectric strength BOC 1000VAC
BCC 1500VAC
FMK-3P
1 23
4
567
8
9
1011
32.6
36.5
12
34
56789
1011 1
234
56789
1011
60.3-1 60.3-2
FMK-3P
Outlet80g-40 ~70510 OPS 710 OPSDC 2.0WAC 3.5VA
DC 6 to 110VAC 6 to 220VFMK-3P
B B-11
FMK-2P-
GENERAL RELAY
MY2
GENERAL RELAY
Operating temperature WeightModel
MY2
MY3
MY4
Coil nominal voltage Coil nominal power Electrical life Mechanical life Mounting methods
DC 6 to 110VAC 6 to 220V
DC 6 to 110VAC 6 to 220V
DC 6 to 110VAC 6 to 220V
DC 0.9WAC 1.2VA
DC 0.9WAC 1.2VA
DC 0.9WAC 1.2VA
510 OPS
510 OPS
510 OPS
710 OPS
710 OPS
710 OPS
-40 ~70
-40 ~70
-40 ~70
32g
32g
32g
Printed-circuit board,Flange,Outlet
Printed-circuit board,Flange,Outlet
Printed-circuit board,Flange,Outlet
33.4
7 14.2
20.5
27.5
6.5
6.3
4.2
Out let
PCB
1 4
5 89 12
13 14(-)0.
5
2.6
(+)
MY2
Size(mm) 20.5 27 33.4Terminal layout 2ZContact capacity 5A 220VAC 5A 28VDCContact resistance 50mInsulation resistance 100MDielectric strength BOC 1000VAC
BCC 1500VAC
33.4
7
14.2
20.5
276.
56.
34.
2 Out let1 2 3
674 5
8 9
10 11(-)0.
5
2.6
PCB
3.9
(+)
MY3
Size(mm) 20.5 27 33.4Terminal layout 3ZContact capacity 5A 220VAC 5A 28VDCContact resistance 50mInsulation resistance 100MDielectric strength BOC 1000VAC
BCC 1500VAC
33.4
7
Out let1 2 3
6 75 89
13(-)
PCB
14.2
20.5
276.
56.
34.
2
0.5
2.6 1.9
14
4
10 11 12
(+)
MY4
Size(mm) 20.5 27 33.4Terminal layout 4ZContact capacity 3A 220VAC 3A 28VDCContact resistance 50mInsulation resistance 100MDielectric strength BOC 1000VAC
BCC 1500VAC
MY3
MY4
B B-12
GENERAL RELAYGENERAL RELAY
Out let
PCB
1 2
3 4
5 6
7 8
33.4
277.1
56
4.6
7
20.55
14.2
0.5 5
5
LY1
Size(mm) 20.5 27 33 4Terminal layout 1Z 1HContact capacity 16A 220VAC 16A 28VDCContact resistance 50mInsulation resistance 100MDielectric strength BOC 1000VAC
BCC 1500VACLY2
Size(mm) 20.5 27 33.4Terminal layout 2Z 2HContact capacity 10A 220VAC 10A 28VDCContact resistance 50mInsulation resistance 100MDielectric strength BOC 1000VAC BCC 1500VAC
Out let
PCB
1 2
3 4
5 6
33.4
70.5 5
277.1
56
4.6
20.55
14.2
5
7 8(-) (+)
Size(mm) 31 27 2 35.4Terminal layout 3ZContact capacity 10A 220VAC 10A 28VDCContact resistance 50mInsulation resistance 100mDielectric strength BOC 1000VAC BCC 1500VAC
LY3
33.4
7
0.5 5
27.2
7.15
64.6
31
20
Out let
PCB
2
6 7
13 14
1 3
5
(-)
9 10 11
(+)
LY4
Size(mm) 41 27.4 34.9Terminal layout 4ZContact capacity 10A 220VAC 10A 28VDCContact resistance 50mInsulation resistance 100MDielectric strength BOC 1000VAC
34.9
6.5
0.5 5
27.4
7.15
64.6
41
Out let2
6 7
13 14
1 3
59 10 11
27.5
1030
8
4
12PCB(-) (+)
Model Coil nominal voltage Coil nominal power Electrical life Mechanical life Operating temperature Weight Mounting methods
LY1
LY2
LY3
LY4
DC 6 to 220VAC 6 to 380V
DC 6 to 220VAC 6 to 380V
DC 6 to 220VAC 6 to 380V
DC 6 to 220VAC 6 to 380V
DC 0.9WAC 1.2VA
DC 0.9WAC 1.2VA
DC 1.4WAC 2.0VA
DC 1.5WAC 2.5VA
510 OPS
510 OPS
510 OPS
510 OPS
710 OPS
710 OPS
710 OPS
710 OPS
-25 ~55
-25 ~55
-25 ~55
-25 ~55
32g
34g
49g
69g
Printed-circuit board,Flange,Outlet
Printed-circuit board,Flange,Outlet
Printed-circuit board,Flange,Outlet
Printed-circuit board,Flange,Outlet
LY1
LY2
LY3
LY4
B B-13
GENERAL RELAYGENERAL RELAY
JQX-53F-2Z
Size(mm) 35.8 36 47Terminal layout 2ZContact capacity 10A 220VAC 10A 28VDCContact resistance 50mInsulation resistance 500MDielectric strength BOC 1000VAC
BCC 1500VAC
478
4.6
(-) (+)A B
1 3
4 6
97
2235.8
0.5
8.5
6
16 36
JQX-53F-3Z
Size(mm) 35.8 36 47Terminal layout 3ZContact capacity 10A 220VAC 10A 28VDCContact resistance 50mInsulation resistance 500MDielectric strength BOC 1000VAC
BCC 1500VAC
(-) (+)A B
1 2 3
4 5 67 8 9
478
4.6
2235.8
0.5
8.5
6
16 36
RR2P
Size(mm) 28.9 36 55Terminal layout 2PContact capacity 10A 220VAC 10A 28VDCContact resistance 50mInsulation resistance 500MDielectric strength BOC 1000VAC
BCC 1500VAC
12
345
6
78 1
2
345
6
78
5510
2.4
28.936
RR3P
Size(mm) 36 36 55Terminal layout 3PContact capacity 10A 220VAC 10A 28VDCContact resistance 50mInsulation resistance 500MDielectric strength BOC 1000VAC
BCC 1500VAC
12
34
56789
1011 1
234
56789
1011 1
234
56789
1011
5510
2.4
36
36
Operating temperature WeightModel Coil nominal voltage Coil nominal power Electrical life Mechanical life Mounting methods
Printed-circuit board,Flange,Outlet
Printed-circuit board,Flange,Outlet
Outlet
Outlet
70g
72g
74g
80g
-40 ~55
-40 ~55
-40 ~55
-40 ~55
510 OPS
510 OPS
510 OPS
510 OPS
710 OPS
710 OPS
710 OPS
710 OPS
JQX-53F-2Z
JQX-53F-3Z
RR2P
RR3P
DC 6 to 110VAC 6 to 220V
DC 2WAC 3.5VA
DC 6 to 110VAC 6 to 220V
DC 6 to 110VAC 6 to 240V
DC 6 to 110VAC 6 to 220V
DC 2WAC 3.5VA
DC 2WAC 3.5VA
DC 2WAC 3.5VA
JQX-53F-2Z
JQX-53F-3Z
RR2P
RR3P
B B-14
GENERAL RELAYGENERAL RELAY
Operating temperature WeightCoil nominal voltage Coil nominal power Electrical life Mechanical life Mounting methods
510 OPS
510 OPS
510 OPS
510 OPS
DC 0.9WAC 1.2VA
Model
RH1B-U
RY2S-U
PRM2-U
RPM4-U
DC 6 to 110VAC 6 to 220V
DC 6 to 110VAC 6 to 220V
DC 6 to 110VAC 6 to 220V
DC 6 to 110VAC 6 to 220V
DC 0.9WAC 1.2VA
DC 0.9WAC 1.2VA
DC 0.9WAC 1.2VA
710 OPS
710 OPS
710 OPS
710 OPS
510 OPS
510 OPS
510 OPS
510 OPS
22g
22g
34g
34g
Outlet
Outlet
Flange,Outlet
Flange,Outlet
RH1B-U
Size(mm) 27.8 14 42Terminal layout 1ZContact capacity 10A 240VAC 10A 30VDCContact resistance 50mInsulation resistance 500MDielectric strength BOC 1000VAC
BCC 1500VAC
27.8 14
0.5
4.8
2.6
4.4
35.5
6.5
6.4
4.6
6
0.5
PRM2-U
Size(mm) 20.5 27 33.4Terminal layout 2ZContact capacity 5A 220VAC 5A 28VDCContact resistance 50mInsulation resistance 500MDielectric strength BOC 1000VAC
BCC 1500VAC
33.4
7
Out let
1 2
3 4
5 6
7 8(-)
14.2
20.5
276.
56.
34.
2
0.5
2.6
(+)
RY2S-U
Size(mm) 27.8 14 42Terminal layout 2ZContact capacity 3A 240VAC 3A 30VDCContact resistance 50mInsulation resistance 500MDielectric strength BOC 1000VAC
BCC 1500VAC
27.8 14
0.5
2.6
4.4
35.5
6.5
6.4
4.66
0.5
PRM4-U
Size(mm) 20.5 27 33.4Terminal layout 4ZContact capacity 3A 220VAC 3A 28VDCContact resistance 50mInsulation resistance 500MDielectric strength BOC 1000VAC
BCC 1500VAC
33.4
7
Out let
1 2 3 4
5 6 7 89 10 11 12
13 14(-)
14.2
20.5
276.
56.
34.
2
0.5
2.8 1.5
(+)
RH1B-U
PRM2-U
RY2S-U
PRM4-U
B B-15
GENERAL RELAY
JQX-10F-2C(JTX)
Size(mm) 34.7 34.7 50Terminal layout 2Z/2CContact capacity 10A 220VAC 10A 28VDCContact resistance 50mInsulation resistance 500MDielectric strength BOC 1000VAC
BCC 1500VAC
50
2.4
12
345
6
78 1
2
345
6
78
5 4
6 3
7 2
8 1
34.7
34.7
Size(mm) 34.7 34.7 50Terminal layout 3Z/3CContact capacity 10A 220VAC 10A 28VDCContact resistance 50mInsulation resistance 500MDielectric strength BOC 1000VAC
BCC 1500VAC
JQX-10F-3C(JTX)
50
2.4
12
34
5678
1 23
4
567
8
34.7
34.7 9
1011
910
11 12
34
56789
1011
Operating temperature WeightModel Coil nominal voltage Coil nominal power Electrical life Mechanical life Mounting methods
DC 3 to 110VAC 6 to 220V
510 OPS
510 OPS
510 OPS
510 OPS
710 OPS
710 OPS
710 OPS
710 OPS
-40 ~65
-40 ~65
-40 ~65
-40 ~65
13g
13g Printed-circuit board
Printed-circuit boardJQX-14FF-1Z
JQX-14FF-2Z
DC 3 to 110VAC 6 to 220V
DC 3 to 110VAC 6 to 220V
DC 6 to 110VAC 6 to 220V
DC 0.55WAC 1.2VA to 2.5VA
DC 0.55WAC 1.2VA to 2.5VA
GENERAL RELAY
JQX-14FF-2Z
Size(mm) 29 13 20.5Terminal layout 2Z 2H 2DContact capacity 5A 250VAC 5A 30VDCContact resistance 50mInsulation resistance 1000MDielectric strength BOC 1000VAC
BCC 1500VAC
13 1
7.5
20
A-3 5/5
AA
20.5
29
5
JQX-14FF-1Z
Size(mm) 29 13 20.5Terminal layout 1Z 1H 1DContact capacity 10A 250VAC 10A 30VDCContact resistance 50mInsulation resistance 1000MDielectric strength BOC 1000VAC
BCC 1500VAC
20.5
29
5
131.3
7.520
JQX-14FF-2Z
JQX-14FF-1Z
JQX-10F-2C(JTX)
DC 2WAC 3.5 VA
DC 2WAC 3.5 VA
68g Outlet
Outlet
JQX-10F-2C(JTX)
JQX-10F-3C(JTX)
B B-16
JQX-10F-3C(JTX) 68g
GENERAL RELAY
JQX-53FF-2Z
Size(mm) 37 34 47.3Terminal layout 2ZContact capacity 10A 240VAC 10A 28VDCContact resistance 50mInsulation resistance 500MDielectric strength BOC 1000VAC
BCC 1500VAC
(-) (+)A B
1 3
4 6
97
2237
0.5
8.5
6
16 34
47.3
8
4.6
JQX-53FF-2Z
GENERAL RELAY
Operating temperature WeightModel Coil nominal voltage Coil nominal power Electrical life Mechanical life Mounting methods
Printed-circuit board,Flange,Outlet
Printed-circuit board,Flange,Outlet
Printed-circuit board,Flange,Outlet
72g
76g
75g
-40 ~70
-40 ~70
-40 ~70
510 OPS
510 OPS
510 OPS
710 OPS
710 OPS
710 OPS
DC 2.0WAC 3.5VA
DC 2.0WAC 3.5VA
DC 2.0WAC 3.5VA
DC 6 to 110VAC 6 to 220V
DC 6 to 110VAC 6 to 220V
DC 6 to 110VAC 6 to 220V
JQX-53FF-2Z
JQX-53FF-3Z
737
JQX-53FF-3Z
Size(mm) 37 34 47.3Terminal layout 3ZContact capacity 10A 240VAC 10A 28VDCContact resistance 50mInsulation resistance 500MDielectric strength BOC 1000VAC
BCC 1500VAC
(-) (+)A B
1 2 3
4 5 67 8 9
2237
0.5
8.5
6
16 3447.3
8
4.6JQX-53FF-3Z
737
Size(mm) 37 34 47.3Terminal layout 1ZContact capacity 30A 300VAC 30A 28VDCContact resistance 50mInsulation resistance 500MDielectric strength BOC 1600VAC
BCC 1500VAC
47.3
8
4.6
2237
0.5
8.5
6
16 34
737
B B-17
POWER RELAYPOWER RELAY
JQX-40F-2Z
Size(mm) 68 48 51Terminal layout 2Z 2HContact capacity 40A 220VAC 40A 28VDCContact resistance 50mInsulation resistance 1000MDielectric strength BOC 1500VAC
BCC 1500VAC
47.625.5
517.3 7.7 10.5
65
8
37.7
35.5
37.6
JQX-52F-1Z
Size(mm) 59 34.6 46Terminal layout 1Z 1HContact capacity 40A 125VACContact resistance 50mInsulation resistance 1000MDielectric strength BOC 1500VAC
BCC 2500VAC
46.6
38.8
76.2
38
10 9 9
46
Size(mm) 65 38.5 46Terminal layout 1Z 1H 1DContact capacity 60A 250VACContact resistance 50mInsulation resistance 1000MDielectric strength BOC 1500VAC
BCC 2500VAC
JQX-58F-1Z
31
79.7
38
38.8 46.5
9.8 9.5 10.5
Operating temperature WeightModel Coil nominal voltage Coil nominal power Electrical life Mechanical life Mounting methods
JQX-40F-2Z
JQX-52F-1Z
JQX-58F-1Z
JQX-59F-1Z
DC 6 to 220VAC 6 to 220V
DC 6 to 220VAC 6 to 380V
DC 6 to 220VAC 6 to 380V
DC 6 to 220VAC 6 to 380V
DC 3WAC 4.5VA
DC 2.8WAC 4.2VA
DC 3WAC 4.5VA
DC 3.5WAC 6VA
510 OPS
510 OPS
510 OPS
510 OPS
610 OPS
610 OPS
610 OPS
610 OPS
-40 ~55
-45 ~55
-40 ~55
-40 ~55
180g
150g
191g
233g
Outlet,Guide Rail
Screw Mounting
Screw Mounting
Screw Mounting
JQX-59F-1Z
Size(mm) 46 51 66.3Terminal layout 1Z 1H 1DContact capacity 80A 250VACContact resistance 50mInsulation resistance 1000MDielectric strength BOC 1500VAC
BCC 2500VAC
32
46.2
79.5
13.2
11.8
8.651
.2
71.2
JQX-40F-2Z
JQX-52F-1Z
JQX-58F-1Z
JQX-59F-1Z
B B-18
POWER RELAYPOWER RELAY
Operating temperature WeightModel Coil nominal voltage Coil nominal power Electrical life Mechanical life Mounting methods
JQX-55F
JQX-30F-2C
JQX-38F-3C(B TYPE)
JQX-40F-1Z
DC 6 to 48V DC 0.9W
DC 6 to 110VAC 6 to 220VDC 6 to 220VAC 6 to 380VDC 6 to 220VAC 6 to 380V
DC 0.9WAC 1.2VADC 2.5WAC 4.5VADC 2.8WAC 4.2VA
510 OPS
510 OPS
510 OPS
510 OPS
610 OPS
610 OPS
610 OPS
610 OPS
-25 ~55
-40 ~55
-40 ~70
-40 ~55
22g
71g
115g
150g
Printed-circuit board
Printed-Outlet
Outlet
Screw Mounting
JQX-55F
Size(mm) 29.6 21.7 17.1Terminal layout 1Z 1HContact capacity 30A 125VAC 30A 250VACContact resistance 50mInsulation resistance 100MDielectric strength BOC 1000VAC
BCC 1500VAC
17.5
29.6N H
5
16.3
21.7 17
.1
JQX-30F-2C
Size(mm) 52 35 47.9Terminal layout 1C 2CContact capacity 30A 250VAC 30A 28VACContact resistance 50mInsulation resistance 500MDielectric strength BOC 1000VAC
BCC 1500VAC
35
6.238
.99
5233.4
14.8
2233.4
6.2
JQX-38F-3C(B TYPE)
Size(mm) 42.2 37.6 55.3Terminal layout 2C 2H 3C 3HContact capacity 30A 28VDC 30A 250VDCContact resistance 50mInsulation resistance 100MDielectric strength BOC 1000VAC
BCC 1500VAC
37.6 42.230
6.4
279.3
55.3
50.5
0.8
JQX-40F-1Z
Size(mm) 59 34.6 46Terminal layout 2Z 1H 1DContact capacity 40A 250VACContact resistance 50mInsulation resistance 1000MDielectric strength BOC 1000VAC
BCC 2500VAC
46.6
38.8
76.2
38
10 9 9
46
JQX-55F
JQX-30F-2C
JQX-38F-3C(B TYPE)
JQX-40F-1Z
B B-19
POWER RELAY
JQX-60F-1Z
Size(mm) 65 38.5 46Terminal layout 1Z 1H 1DContact capacity 60A 250VACContact resistance 50mInsulation resistance 1000MDielectric strength BOC 1500VAC
BCC 2500VAC
79.7
38
31
38.8
9.8 9.5 10.5
46.5
JQX-62F-1Z
Size(mm) 61.7 63.5 56.5Terminal layout 1ZContact capacity 80A 250VAC 80A 30VDCContact resistance 50mInsulation resistance 1000MDielectric strength BOC 1500VAC
BCC 2500VAC
63.547.5
41.1
61.7
Operating temperature WeightModel Coil nominal voltage Coil nominal power Electrical life Mechanical life Mounting methods
JQX-60F-1Z
JQX-62F-1Z
JQX-62F-2Z
G7L-2P-TUBJ
DC 6 to 220VAC 6 to 380V
DC 3WAC 4.5VA
510 OPS
510 OPS
510 OPS
510 OPS
610 OPS
610 OPS
610 OPS
610 OPS
-40 ~55
-45 ~40
-40 ~40
-40 ~70
187g
210g
340g
100g
Screw Mounting
Screw Mounting
Screw Mounting
Outlet
DC 6 to 220VAC 6 to 380VDC 6 to 220VAC 6 to 380VDC 6 to 240VAC 6 to 220V
DC 3.3WAC 5VADC 4WAC 6VA
DC 2W
JQX-62F-2Z
Size(mm) 84 68.2 65.5Terminal layout 2ZContact capacity 60A 250VAC 60A 30VDCContact resistance 50mInsulation resistance 1000MDielectric strength BOC 2200VAC
BCC 2200VAC
65.5 68.2
84 30
G7L-2P-TUBJ
Size(mm) 68.5 33.5 47Terminal layout 1H 2HContact capacity 20A 220VACContact resistance 50mInsulation resistance 1000MDielectric strength BOC 1500VAC
BCC 2500VAC
11
53
52.550.5
6.333.50.8
0 1
2
2 4 6 8
JQX-60F-1Z
JQX-62F-1Z
JQX-62F-2Z
G7L-2P-TUBJ
POWER RELAY
B B-20
1
Chương 1: KHÁI NIỆM VỀ QUÁ TRÌNH QUÁ ĐỘ ĐIỆN TỪ
I. KHÁI NIỆM CHUNG Chế độ của hệ thống điện thay đổi đột ngột sẽ làm phát sinh quá trình quá độ điện từ, trong đó quá trình phát sinh do ngắn mạch là nguy hiểm nhất. Để tính chọn các thiết bị điện và bảo vệ rơle cần phải xét đến quá trình quá độ khi: - ngắn mạch. - ngắn mạch kèm theo đứt dây. - cắt ngắn mạch bằng máy cắt điện. Khi xảy ra ngắn mạch, tổng trở của hệ thống điện giảm, làm dòng điện tăng lên, điện áp giảm xuống. Nếu không nhanh chóng cô lập điểm ngắn mạch thì hệ thống sẽ chuyển sang chế độ ngắn mạch duy trì (xác lập). Từ lúc xảy ra ngắn mạch cho đến khi cắt nó ra, trong hệ thống điện xảy ra quá trình quá độ làm thay đổi dòng và áp. Dòng trong quá trình quá độ thường gồm 2 thành phần: chu kỳ và không chu kỳ. Trường hợp hệ thống có đường dây truyền tải điện áp từ 330 KV trở lên thì trong dòng ngắn mạch ngoài thành phần tần số cơ bản còn các thành phần sóng hài bậc cao. Nếu đường dây có tụ bù dọc sẽ có thêm thành phần sóng hài bậc thấp. Nhiệm vụ của môn học ngắn mạch là nghiên cứu diễn tiến của quá trình ngắn mạch trong hệ thống điện, đồng thời xét đến các phương pháp thực dụng tính toán ngắn mạch.
II. CÁC ĐỊNH NGHĨA CƠ BẢN Ngắn mạch: là một loại sự cố xảy ra trong hệ thống điện do hiện tượng chạm
chập giữa các pha không thuộc chế độ làm việc bình thường. - Trong hệ thống có trung tính nối đất (hay 4 dây) chạm chập một pha hay nhiều
pha với đất (hay với dây trung tính) cũng được gọi là ngắn mạch. - Trong hệ thống có trung tính cách điện hay nối đất qua thiết bị bù, hiện tượng
chạm chập một pha với đất được gọi là chạm đất. Dòng chạm đất chủ yếu là do điện dung các pha với đất.
Ngắn mạch gián tiếp: là ngắn mạch qua một điện trở trung gian, gồm điện trở do hồ quang điện và điện trở của các phần tử khác trên đường đi của dòng điện từ pha này đến pha khác hoặc từ pha đến đất.
Điện trở hồ quang điện thay đổi theo thời gian, thường rất phức tạp và khó xác định chính xác. Theo thực nghiệm:
R lI
=1000. [ ]Ω
trong đó: I - dòng ngắn mạch [A] l - chiều dài hồ quang điện [m]
Ngắn mạch trực tiếp: là ngắn mạch qua một điện trở trung gian rất bé, có thể bỏ qua (còn được gọi là ngắn mạch kim loại).
2
Ngắn mạch đối xứng: là dạng ngắn mạch vẫn duy trì được hệ thống dòng, áp 3 pha ở tình trạng đối xứng.
Ngắn mạch không đối xứng: là dạng ngắn mạch làm cho hệ thống dòng, áp 3 pha mất đối xứng.
- Không đối xứng ngang: khi sự cố xảy ra tại một điểm, mà tổng trở các pha tại điểm đó như nhau.
- Không đối xứng dọc: khi sự cố xảy ra mà tổng trở các pha tại một điểm không như nhau.
Sự cố phức tạp: là hiện tượng xuất hiện nhiều dạng ngắn mạch không đối xứng ngang, dọc trong hệ thống điện.
Ví dụ: đứt dây kèm theo chạm đất, chạm đất hai pha tại hai điểm khác nhau trong hệ thống có trung tính cách đất.
Bảng 1.1: Ký hiệu và xác xuất xảy ra các dạng ngắn mạch DạNG
NGắN MạCH HÌNH Vẽ QUY ƯớC KÍ HIệU
XÁC SUấT XảY RA %
3 pha
N(3) 5
2 pha
N(2) 10
2 pha-đất N(1,1) 20
1 pha N(1) 65
III. NGUYÊN NHÂN VÀ HẬU QUẢ CỦA NGẮN MẠCH
III.1. Nguyên nhân: - Cách điện của các thiết bị già cỗi, hư hỏng. - Quá điện áp. - Các ngẫu nhiên khác, thao tác nhầm hoặc do được dự tính trước...
III.2. Hậu quả: - Phát nóng: dòng ngắn mạch rất lớn so với dòng định mức làm cho các phần tử có
dòng ngắn mạch đi qua nóng quá mức cho phép dù với một thời gian rất ngắn. - Tăng lực điện động: ứng lực điện từ giữa các dây dẫn có giá trị lớn ở thời gian đầu
của ngắn mạch có thể phá hỏng thiết bị. - Điện áp giảm và mất đối xứng: làm ảnh hưởng đến phụ tải, điện áp giảm 30 đến
40% trong vòng một giây làm động cơ điện có thể ngừng quay, sản xuất đình trệ, có thể làm hỏng sản phẩm.
3
- Gây nhiễu đối với đường dây thông tin ở gần do dòng thứ tự không sinh ra khi ngắn mạch chạm đất.
- Gây mất ổn định: khi không cách ly kịp thời phần tử bị ngắn mạch, hệ thống có thể mất ổn định và tan rã, đây là hậu quả trầm trọng nhất.
IV. MỤC ĐÍCH TÍNH TOÁN NGẮN MẠCH VÀ YÊU CẦU ĐỐI VỚI CHÚNG:
Khi thiết kế và vận hành các hệ thống điện, nhằm giải quyết nhiều vấn đề kỹ thuật yêu cầu tiến hành hàng loạt các tính toán sơ bộ, trong đó có tính toán ngắn mạch.
Tính toán ngắn mạch thường là những tính toán dòng, áp lúc xảy ra ngắn mạch tại một số điểm hay một số nhánh của sơ đồ đang xét. Tùy thuộc mục đích tính toán mà các đại lượng trên có thể được tính ở một thời điểm nào đó hay diễn biến của chúng trong suốt cả quá trình quá độ. Những tính toán như vậy cần thiết để giải quyết các vấn đề sau:
- So sánh, đánh giá, chọn lựa sơ đồ nối điện. - Chọn các khí cụ, dây dẫn, thiết bị điện. - Thiết kế và chỉnh định các loại bảo vệ. - Nghiên cứu phụ tải, phân tích sự cố, xác định phân bố dòng... Trong hệ thống điện phức tạp, việc tính toán ngắn mạch một cách chính xác rất khó
khăn. Do vậy tùy thuộc yêu cầu tính toán mà trong thực tế thường dùng các phương pháp thực nghiệm, gần đúng với các điều kiện đầu khác nhau để tính toán ngắn mạch.
Chẳng hạn để tính chọn máy cắt điện, theo điều kiện làm việc của nó khi ngắn mạch cần phải xác định dòng ngắn mạch lớn nhất có thể có. Muốn vậy, người ta giả thiết rằng ngắn mạch xảy ra lúc hệ thống điện có số lượng máy phát làm việc nhiều nhất, dạng ngắn mạch gây nên dòng lớn nhất, ngắn mạch là trực tiếp, ngắn mạch xảy ra ngay tại đầu cực máy cắt ...
Đê giải quyết các vấn đề liên quan đến việc chọn lựa và chỉnh định thiết bị bảo vệ rơle thường phải tìm dòng ngắn mạch nhỏ nhất. Lúc ấy tất nhiên cần phải sử dụng những điều kiện tính toán hoàn toàn khác với những điều kiện nêu trên.
1
CHƯƠNG 2:CÁC CHỈ DẪN KHI TÍNH TOÁN NGẮN MẠCH
I. Những giả thiết cơ bản: Khi xảy ra ngắn mạch sự cân bằng công suất từ điện, cơ điện bị phá hoại, trong hệ
thống điện đồng thời xảy ra nhiều yếu tố làm các thông số biến thiên mạnh và ảnh hưởng tương hổ nhau. Nếu kể đến tất cả những yếu tố ảnh hưởng, thì việc tính toán ngắn mạch sẽ rất khó khăn. Do đó, trong thực tế người ta đưa ra những giả thiết nhằm đơn giản hóa vấn đề để có thể tính toán.
Mỗi phương pháp tính toán ngắn mạch đều có những giả thiết riêng của nó. Ở đây ta chỉ nêu ra các giả thiết cơ bản chung cho việc tính toán ngắn mạch.
1. Mạch từ không bão hòa: giả thiết này sẽ làm cho phương pháp phân tích và tính toán ngắn mạch đơn giản rất nhiều, vì mạch điện trở thành tuyến tính và có thể dùng nguyên lý xếp chồng để phân tích quá trình.
2. Bỏ qua dòng điện từ hóa của máy biến áp: ngoại trừ trường hợp máy biến áp 3 pha 3 trụ nối Yo/Yo.
3. Hệ thống điện 3 pha là đối xứng: sự mất đối xứng chỉ xảy ra đối với từng phần tử riêng biệt khi nó bị hư hỏng hoặc do cố ý có dự tính.
4. Bỏ qua dung dẫn của đường dây: giả thiết này không gây sai số lớn, ngoại trừ trường hợp tính toán đường dây cao áp tải điện đi cực xa thì mới xét đến dung dẫn của đường dây.
5. Bỏ qua điện trở tác dụng: nghĩa là sơ đồ tính toán có tính chất thuần kháng. Giả thiết này dùng được khi ngắn mạch xảy ra ở các bộ phận điện áp cao, ngoại trừ khi bắt buộc phải xét đến điện trở của hồ quang điện tại chỗ ngắn mạch hoặc khi tính toán ngắn mạch trên đường dây cáp dài hay đường dây trên không tiết diện bé. Ngoài ra lúc tính hằng số thời gian tắt dần của dòng điện không chu kỳ cũng cần phải tính đến điện trở tác dụng.
6. Xét đến phụ tải một cách gần đúng: tùy thuộc giai đoạn cần xét trong quá trình quá độ có thể xem gần đúng tất cả phụ tải như là một tổng trở không đổi tập trung tại một nút chung.
7. Các máy phát điện đồng bộ không có dao động công suất: nghĩa là góc lệch pha giữa sức điện động của các máy phát điện giữ nguyên không đổi trong quá trình ngắn mạch. Nếu góc lệch pha giữa sức điện động của các máy phát điện tăng lên thì dòng trong nhánh sự cố giảm xuống, sử dụng giả thiết này sẽ làm cho việc tính toán đơn giản hơn và trị số dòng điện tại chỗ ngắn mạch là lớn nhất. Giả thiết này không gây sai số lớn, nhất là khi tính toán trong giai đoạn đầu của quá trình quá độ (0,1 ÷ 0,2 sec).
II. Hệ đơn vị tương đối: Bất kỳ một đại lượng vật lý nào cũng có thể biểu diễn trong hệ đơn vị có tên hoặc
trong hệ đơn vị tương đối. Trị số trong đơn vị tương đối của một đại lượng vật lý nào đó là tỷ số giữa nó với một đại lượng vật lý khác cùng thứ nguyên được chọn làm đơn vị đo lường. Đại lượng vật lý chọn làm đơn vị đo lường được gọi đại lượng cơ bản.
2
Như vậy, muốn biểu diễn các đại lượng trong đơn vị tương đối trước hết cần chọn các đại lượng cơ bản. Khi tính toán đối với hệ thống điện 3 pha người ta dùng các đại lượng cơ bản sau:
S : công suất cơ bản 3 pha. cb : điện áp dây cơ bản. Ucb
Icb : dòng điện cơ bản. Z : tổng trở pha cơ bản. cbtcb : thời gian cơ bản. ωcb : tốc độ góc cơ bản.
Xét về ý nghĩa vật lý, các đại lượng cơ bản này có liên hệ với nhau qua các biểu thức sau:
3S = U . I (2.1) cb cb cb
ZU
Icbcb
cb=
3. (2.2)
t cbcb
=1ω
(2.3)
Do đó ta chỉ có thể chọn tùy ý một số đại lượng cơ bản, các đại lượng cơ bản còn lại được tính từ các biểu thức trên. Thông thường chọn trước S , U và ω . cb cb cb
Khi đã chọn các đại lượng cơ bản thì các đại lượng trong đơn vị tương đối được tính từ các đại lượng thực như sau:
E EU
UU
S SS
II
Z ZZ
IU
SU
cbcb
cbcb
cbcb
cbcb
cbcb
cb
cb
cb
cb
*( ) * ( )
* ( ) * ( )
* ( ).
= =
= =
=
; U
; I
= Z.3
= Z. 2
E*(cb) đọc là E tương đối cơ bản (tức là sức điện động E trong hệ đơn vị tương đối với lượng cơ bản là Ucb). Sau này khi ý nghĩa đã rõ ràng và sử dụng quen thuộc thì có thể bỏ dấu (*) và (cb).
MộT Số TÍNH CHấT CủA Hệ ĐƠN Vị TƯƠNG ĐốI: 1) Các đại lượng cơ bản dùng làm đơn vị đo lường cho các đại lượng toàn phần
cũng đồng thời dùng cho các thành phần của chúng. Ví dụ: S dùng làm đơn vị đo lường chung cho S, P, Q; Z - cho Z, R, X. cb cb
2) Trong đơn vị tương đối điện áp pha và điện áp dây bằng nhau, công suất 3 pha và công suất 1 pha cũng bằng nhau.
3) Một đại lượng thực có thể có giá trị trong đơn vị tương đối khác nhau tùy thuộc vào lượng cơ bản và ngược lại cùng một giá trị trong đơn vị tương đối có thể tương ứng với nhiều đại lượng thực khác nhau.
4) Thường tham số của các thiết bị được cho trong đơn vị tương đối với lượng cơ bản là định mức của chúng (Sđm, Uđm, Iđm). Lúc đó:
Z ZZ
IU
SUâm
âm
âm
âm
âm
âm*( )
. = Z.
3 = Z.= 2
3
5) Đại lượng trong đơn vị tương đối có thể được biểu diễn theo phần trăm, ví dụ như ở kháng điện, máy biến áp...
XI
U
XI
U
K âmâm
âm
Bâm
âmN
% 100.X = X .3
.100
% = X .3
.100 = U %
K
B
= * ( ).
.
TÍNH ĐổI ĐạI LƯợNG TRONG Hệ ĐƠN Vị TƯƠNG ĐốI: Một đại lượng trong đơn vị tương đối là A*(cb1) với lượng cơ bản là Acb1 có thể tính
đổi thành A*(cb2) tương ứng với lượng cơ bản là A theo biểu thức sau: cb2A = At *(cb1) * Acb1 = A*(cb2) * Acb2
Ví dụ, đã cho E*(cb1) , Z*(cb1) ứng với các lượng cơ bản (Scb1, U , Icb1 cb1) cần tính đổi sang hệ đơn vị tương đối ứng với các lượng cơ bản (Scb2, U , Icb2 cb2):
EUU
ZII
UU
SS
UU
cb cbcb
cb
cb cbcb
cb
cb
cbcb
cb
cb
cb
cb
*( ) * ( )
* ( ) * ( ) * ( ). .
2 11
2
2 12
1
1
21
2
1
12
22
E .
Z . = Z .
=
=
Nếu tính đổi các tham số ứng với lượng định mức (Sđm, Uđm, Iđm) thành giá trị ứng với lượng cơ bản (S , U , I ) thì: cb cb cb
EUU
ZII
UU
SS
UU
cb âmâm
cb
cb âmcb
âm
âm
cbâm
cb
âm
âm
cb
*( ) * ( )
* ( ) * ( ) * ( ). .
E .
Z . = Z .
=
=2
2
Khi chọn U = Ucb đm ta có các biểu thức đơn giản sau:
E
ZII
SS
cb âm
cb âmcb
âmâm
cb
âm
*( ) * ( )
* ( ) * ( ) * ( )
E
Z . = Z .
=
=
CHọN CÁC ĐạI LƯợNG CƠ BảN: Thực tế trị số định mức của các thiết bị ở cùng một cấp điện áp cũng không giống
nhau. Tuy nhiên, sự khác nhau đó không nhiều (trong khoảng ± 10%), ví dụ điện áp định mức của máy phát điện là 11KV, máy biến áp - 10,5KV, kháng điện - 10KV. Do đó trong tính toán gần đúng ta có thể xem điện áp định mức Uđm của các thiết bị ở cùng một cấp điện áp là như nhau và bằng giá trị trung bình Utb của cấp điện áp đó. Theo qui ước có các Utb sau [KV]:
500; 330; 230; 154; 115; 37; 20; 15,75; 13,8; 10,5; 6,3; 3,15; 0,525 Khi tính toán gần đúng người ta chọn U = Ucb đm = Utb, riêng đối với kháng điện nên
tính chính xác với lượng định mức của nó vì giá trị điện kháng của kháng điện chiếm phần lớn trong điện kháng tổng của sơ đồ, nhất là đối với những trường hợp kháng điện làm việc ở điện áp khác với cấp điện áp định mức của nó (ví dụ, kháng điện 10KV làm việc ở cấp 6KV).
Nói chung các đại lượng cơ bản nên chọn sao cho việc tính toán trở nên đơn giản, tiện lợi. Đối với Scb nên chọn những số tròn (chẳng hạn như 100, 200, 1000MVA,...) hoặc đôi khi chọn bằng tổng công suất định mức của sơ đồ.
4
Trong hệ đơn vị tương đối, một đại lượng vật lý này cũng có thể biểu diễn bằng một đại lượng vật lý khác có cùng trị số tương đối. Ví dụ nếu chọn ωđb làm lượng cơ bản thì khi ω*(đb) = 1 ta có:
X L
X M
L X
E
cb cb cb
cb cb cb
cb cb cb cb
cb cb cb
*( ) * ( ) * ( )
* ( ) * ( ) * ( )
* ( ) * ( ) * ( ) * ( )
* ( ) * ( ) * ( )
.
.
. .
.
= L
= M
I = L
=
*(âb)
* (âb)
* (cb)
* (âb)
=
=
=
=
ω
ω
ψ
ω ψ ψ
III. Cách thành lập sơ đồ thay thế: Sơ đồ thay thế là sơ đồ cho phép thế các mạch liên hệ nhau bởi từ trường bằng một
mạch điện tương đương bằng cách qui đổi tham số của các phần tử ở các cấp điện áp khác nhau về một cấp được chọn làm cơ sở. Các tham số của sơ đồ thay thế có thể xác định trong hệ đơn vị có tên hoặc hệ đơn vị tương đối, đồng thời có thể tính gần đúng hoặc tính chính xác.
III.1. Qui đổi chính xác trong hệ đơn vị có tên:
Hình 2.1 : Sơ đồ mạng điện có nhiều cấp điện áp
Xét mạng điện có nhiều cấp điện áp khác nhau (hình 2.1) được nối với nhau bằng n
máy biến áp có tỷ số biến áp k , k , ...... k1 2 n. Chọn một đoạn tùy ý làm đoạn cơ sở, ví dụ đoạn đầu tiên. Tham số của tất cả các đoạn còn lại sẽ được tính qui đổi về đoạn cơ sở.
Sức điện động, điện áp, dòng điện và tổng trở của đoạn thứ n được qui đổi về đoạn cơ sở theo các biểu thức sau:
E E
U U
I I
Z Z
n qâ n
n qâ n
n qâ n
n qâ n
(k k k
(k k k
1k k k
(k k k
1 2 n
1 2 n
1 2 n
1 2 n
=
=
=
=
. ............... )
. ............... )
. ................ ............... ) 2
Các tỷ số biến áp k trong những biểu thức trên lấy bằng tỷ số biến áp lúc không tải. Các thành phần trong tích các tỷ số biến áp k chỉ lấy của những máy biến áp nằm giữa đoạn xét và đoạn cơ sở, “chiều” của tỷ số biến áp k lấy từ đoạn cơ sở đến đoạn cần xét.
kUU
UU
UU
csn
n
n1
12
1
2
1 ; k ; .................. ; k = = = −' '
Trong những biểu thức qui đổi trên, nếu các đại lượng cho trước trong đơn vị tương đối thì phải tính đổi về đơn vị có tên. Ví dụ, đã cho Z thì: *(đm)
5
Z U
IUSâm
âm
âmâm
âm
âm= Z . = Z .*( ) * ( ).3
2 (2.4)
III.2. Qui đổi gần đúng trong hệ đơn vị có tên: Việc qui đổi gần đúng được thực hiện dựa trên giả thiết là xem điện áp định mức
của các phần tử trên cùng một cấp điện áp là như nhau và bằng trị số điện áp trung bình của cấp đó. Tức là:
U1 2 U = U ; U U = U ; .................1'
tb1 2'
tb2= = Như vậy:
kUU
UU
UU
tbcs
tb
tb
tbn
tbn
tbn1
12
1
2
1 ; k ; .................. ; k = = = −
Do đó ta sẽ có các biểu thức qui đổi đơn giản hơn:
E En qâ n n UU
.UU
.......UU
= UU
tbcs
tb1
tb1
tb2
tbn-1
tbn
tbcs
tbn= ... . .E
I I
Z Z
n qâ n
n qâ n
UU
UU
tbn
tbcs
tbcs
tbn
=
=⎛
⎝⎜
⎞
⎠⎟
.
.2Tương tự:
Nếu các phần tử có tổng trở cho trước trong đơn vị tương đối, thì tính đổi gần đúng về đơn vị có tên theo biểu thức (2.4) trong đó thay U = U . đm tb
III.3. Qui đổi chính xác trong hệ đơn vị tương đối: Tương ứng với phép qui đổi chính xác trong hệ đơn vị có tên ta cũng có thể dùng
trong hệ đơn vị tương đối bằng cách sau khi đã qui đổi về đoạn cơ sở trong đơn vị có tên, chọn các lượng cơ bản của đoạn cơ sở và tính đổi về đơn vị tương đối. Tuy nhiên phương pháp này ít được sử dụng, người ta thực hiện phổ biến hơn trình tự qui đổi như sau:
Chọn đoạn cơ sở và các lượng cơ bản S , U của đoạn cơ sở. cb cbcs Tính lượng cơ bản của các đoạn khác thông qua các tỷ số biến áp k , k1 2, ......
k . Công suất cơ bản Sn cb đã chọn là không đổi đối với tất cả các đoạn. Các lượng cơ bản U và I của đoạn thứ n được tính như sau: cbn cbn
U U
I IU
cbn cbcs
cbn cbcscbn
cbn cbcs cb
1k k k
(k k k = S
3 S = S
1 2 n
1 2 ncb
=
=
=
. ...............
. ............... ).
(S )
Tính đổi tham số của các phần tử ở mỗi đoạn sang đơn vị tương đối với lượng cơ bản của đoạn đó:
Nếu tham số cho trong đơn vị có tên thì dùng các biểu thức tính đổi từ hệ đơn vị có tên sang hệ đơn vị tương đối. Ví dụ:
6
U ; Z Z.*( ) * ( )cbcb
cbcb
cb
UU
SU
= = 2
Nếu tham số cho trong đơn vị tương đối với lượng cơ bản là định mức hay một lượng cơ bản nào đó thì dùng các biểu thức tính đổi hệ đơn vị tương đối. Ví dụ:
ZSS
UUcb âm
cb
âm
âm
cb*( ) * ( ) Z . .=
2
2
III.4. Qui đổi gần đúng trong hệ đơn vị tương đối: Tương tự như qui đổi gần đúng trong hệ đơn vị có tên, ta xem k là tỷ số biến áp
trung bình, do vậy việc tính toán sẽ đơn giản hơn. Trình tự qui đổi như sau: Chọn công suất cơ bản S chung cho tất cả các đoạn. cb Trên mỗi đoạn lấy U = U của cấp điện áp tương ứng. đm tb Tính đổi tham số của các phần tử ở mỗi đoạn sang đơn vị tương đối theo các
biểu thức gần đúng.
III.5. Một số điểm cần lưu ý: - Độ chính xác của kết quả tính toán không phụ thuộc vào hệ đơn vị sử dụng mà chỉ
phụ thuộc vào phương pháp tính chính xác hay gần đúng. - Khi tính toán trong hệ đơn vị có tên thì kết quả tính được là giá trị ứng với đoạn
cơ sở đã chọn. Muốn tìm giá trị thực ở đoạn cần xét phải qui đổi ngược lại. Ví dụ: Dòng tìm được ở đoạn cơ sở là Ics = In qđ. Dòng thực ở đoạn thứ n là:
In = (k1. k ...... k ) I2 n n qđ - Khi tính toán trong hệ đơn vị tương đối thì kết quả tính được là ở trong đơn vị
tương đối, muốn tìm giá trị thực ở một đoạn nào đó chỉ cần nhân kết quả tính được với lượng cơ bản của đoạn đó.
Ví dụ: Dòng tính được là I*n. Dòng thực ở đoạn thứ n là:
I IUn n cbn n
cbn I . = I .
S3
cb= * * .
Bảng 2.1: Tóm tắt một số biểu thức tính toán tham số của các phần tử THIẾT BỊ SƠ ĐỒ THAM
SỐ TRA ĐƯỢC
TÍNH TRONG ĐƠN VỊ CÓ TÊN
TÍNH TÍNH THAY THẾ CHÍNH XÁC
TRONG ĐVTĐ GẦN ĐÚNG
TRONG ĐVTĐ
x .d" S
Scb
âm
x”Máy phát
d, S x . .d
" SS
UU
cb
âm
âm
cb
2
2x .d" U
Sâm
âm
2 đm,Uđm
Máy biến áp (2 cuộn
dây)
uN%, k, S
u SS
N c
âm
%100
.đm
u US
N â
âm
%100
2. m u S
SU
UN cb
âm
âm
cb
%100
2
2. . b
X UIâm
âm
%.100 3
.X%,
IX I
IUU
cb
âm
âm
cb
%100
. .X I
Icb
âm
%100
. Kháng điện đm, Uđm
X X .l.1
SU
cb
cb2 X .l.1
SU
cb
tb2
1 Đường dây X .l 1[Ω/Km]
7
Chú ý: Đối với máy biến áp 3 cuộn dây thì các tham số tra được là điện áp ngắn mạch giữa
các cuộn dây: uN I-II% , uN I-III% , uN II-III% , ta phải tính uN% của từng cuộn dây và sau đó tính điện kháng của từng cuộn dây theo các biểu thức trong bảng 2.1 đối với máy biến áp 2 cuộn dây. Điện áp ngắn mạch uN% của từng cuộn dây được tính như sau:
uN I% = 0,5 (uN I-II% + uN I-III% - uN II-III%) uN II% = u % - u % N I-II N IuN III% = uN I-III% - uN I%
IV. Biến đổi sơ đồ thay thế Các phép biến đổi sơ đồ thay thế được sử dụng trong tính toán ngắn mạch nhằm
mục đích biến đổi những sơ đồ thay thế phức tạp của hệ thống điện thành một sơ đồ đơn giản nhất tiện lợi cho việc tính toán, còn gọi là sơ đồ tối giản. Sơ đồ tối giản có thể bao gồm một hoặc một số nhánh nối trực tiếp từ nguồn sức điện động đẳng trị E∑ đến điểm ngắn mạch thông qua một điện kháng đẳng trị X∑.
IV.1. Nhánh đẳng trị: Phép biến đổi này được dùng để ghép song song các nhánh có nguồn hoặc không
nguồn thành một nhánh tương đương. Xét sơ đồ thay thế (hình 2.2a) gồm có n nhánh nối chung vào một điểm M, mỗi nhánh gồm có 1 nguồn sức điện động Ek nối với 1 điện kháng X , ta có thể biến đổi nó thành sơ đồ tối giản (hình 2.2b) bằng các biểu thức sau: k
EE Y
Y Yât
k kk
n
kk
n ât
kk
n ; X = ==
= =
∑
∑ ∑
.1
1 1
1
trong đó : Y = 1/ X là điện dẫn của nhánh thứ k. k kKhi sơ đồ chỉ có 2 nhánh thì:
EE X X
XX
Xât ât + E + X
; X . X
+ X= =1 2 2 1
1 2
1 2
1 2
. .
Khi E = E1 2 = .............. = E = E thì En đt = E.
Hình 2.2 : Phép biến đổi dùng nhánh đẳng trị
8
IV.2. Biến đổi Y - Δ: Biến đổi sơ đồ thay thế có dạng hình sao gồm 3 nhánh (hình 2.3a) thành tam giác
(hình 2.3b) theo các biểu thức sau:
XX X
X
XX X
X
XX X
X
12 1 21 2
3
13 1 31 3
2
23 2 32 3
1
X + X +
X + X +
X + X +
=
=
=
.
.
.
Ngược lại, biến đổi sơ đồ có dạng hình tam giác sao thành hình sao dùng các biểu thức sau:
XX X
X X XX X
X X XX X
X X X112 13
12 13 232
12 23
12 13 233
23 13
12 13 23= ; X ; X
. .+ +
=+ +
=+ +
.
Hình 2.3 : Biến đổi Y - Δ
Biến đổi Y - Δ cũng có thể áp dụng được khi ở các nút có nguồn, lúc đó có thể ứng
dụng tính chất đẳng thế để tách ra hay nhập chung các nút có nguồn (ví dụ như trên hình 2.4).
Hình 2.4 : Tách / nhập các nút có nguồn
9
IV.3. Biến đổi sao - lưới: Sơ đồ thay thế hình sao (hình 2.5a) có thể biến đổi thành lưới (hình 2.5b). Điện
kháng giữa 2 đỉnh m và n của lưới được tính như sau: X = Xmn m . X .ΣY ntrong đó: Xm , X là điện kháng của nhánh thứ m và n trong hình sao. n
ΣY là tổng điện dẫn của tất cả các nhánh hình sao.
Hình 2.5 : Biến đổi sao - lưới
Phép biến đổi này sử dụng tiện lợi
trong tính toán ngắn mạch khi có một nút là điểm ngắn mạch và tất cả các nút còn lại là các nút nguồn. Nếu các nguồn là đẳng thế thì điện kháng tương hổ giữa các nguồn có thể bỏ qua, lúc đó sơ đồ sẽ trở nên rất đơn giản. Ví dụ, từ sơ đồ lưới ở hình 2.5b khi các nút 1, 2, 3, 4 có nguồn đẳng thế và nút 5 là điểm ngắn mạch ta có thể đơn giản thành sơ đồ trên hình 2.6.
Hình 2.6 : Ap dụng biến đổi sao-lưới
IV.4. Tách riêng các nhánh tại điểm ngắn mạch: Nếu ngắn mạch trực tiếp 3 pha tại điểm nút có nối một số nhánh (ví dụ, hình 2.7) ,
thì có thể tách riêng các nhánh này ra khi vẫn giữ ở đầu mỗi nhánh cũng ngắn mạch như vậy. Sơ đồ nhận được lúc này không có mạch vòng sẽ dễ dàng biến đổi. Tính dòng trong mỗi nhánh khi cho ngắn mạch chỉ trên một nhánh, các nhánh ngắn mạch khác xem như phụ tải có sức điện động bằng không. Dòng qua điểm ngắn mạch là tổng các dòng đã tính ở các nhánh ngắn mạch riêng rẽ.
Phương pháp này thường dùng khi cần tính dòng trong một nhánh ngắn mạch nào đó.
10
Hình 2.7 : Tách riêng các nhánh tại điểm ngắn mạch
IV.5. Lợi dụng tính chất đối xứng của sơ đồ: Lợi dụng tính chất đối xứng của sơ đồ ta có thể ghép chung các nhánh một cách đơn
giản hơn hoặc có thể bỏ bớt một số nhánh mà dòng ngắn mạch không đi qua (hình 2.8).
Hình 2.8 : Lợi dụng tính chất đối xứng của sơ đồ
11
IV.6. Sử dụng hệ số phân bố dòng: Hệ số phân bố dòng là hệ số đặc trưng cho phần tham gia của mỗi nguồn vào dòng
ngắn mạch với giả thiết là các nguồn có sức điện động bằng nhau và không có phụ tải. Dùng hệ số phân bố dòng để tính tổng trở tương hổ giữa các nguồn và điểm ngắn
mạch, đưa sơ đồ về dạng rất đơn giản gồm các nguồn nối với điểm ngắn mạch qua tổng trở tương hổ:
ZZCkN
k = Σ
trong đó: Z - tổng trở đẳng trị của toàn sơ đồ đối với điểm ngắn mạch. Σ
Ck - hệ số phân bố dòng của nhánh thứ k. Hệ số phân bố dòng có thể tìm được bằng mô hình, thực nghiệm hoặc giải tích.
Phương pháp giải tích được thực hiện bằng cách cho dòng qua điểm ngắn mạch bằng đơn vị và coi rằng các sức điện động bằng nhau. Dòng tìm được trong các nhánh sẽ là trị số của các hệ số phân bố dòng C , C , ..... , C tương ứng với các nhánh đó. 1 2 k
Hình 2.9 : Sơ đồ để xác định hệ số phân bố dòng
Ví dụ, cho sơ đồ trên hình 2.9a trong đó các sức điện động bằng nhau, không có phụ tải và cho dòng ngắn mạch IN = 1. Sau khi biến đổi sơ đồ và từ điều kiện cân bằng thế ta có:
IN . X = C . X = C . X = C . Xđt 1 1 2 2 3 3
CXX
XX
XX
ât ât ât1
12
23
3 ; C ; C = = =⇒
và: IN . X = C . XΣ 1 1N = C . X2 2N = C . X3 3N
XXC
XC
XCN N N1
12
23
3 ; X ; X = =Σ Σ = Σ⇒
12
V. Công suất ngắn mạch Công suất ngắn mạch SNt vào thời điểm t là đại lượng qui ước được tính theo dòng
ngắn mạch I vào thời điểm t trong quá trình quá độ và điện áp trung bình UNt tb của đoạn tính dòng ngắn mạch:
3S = I . UNt Nt tbCông suất ngắn mạch dùng để chọn hay kiểm tra máy cắt, lúc đó t là thời điểm mà
các tiếp điểm chính của máy cắt mở ra. Công suất này phải bé hơn công suất đặc trưng cho khả năng cắt của máy cắt hay còn gọi là công suất cắt định mức của máy cắt:
3S < SNt Cđm = ICđm. UđmNgoài ra, khi đã biết công suất ngắn mạch SNH (hoặc dòng ngắn mạch INH) do hệ
thống cung cấp cho điểm ngắn mạch có thể tính được điện kháng của hệ thống đối với điểm ngắn mạch:
XU
IUSH
tb
NH
tb
NH = =
3
2
.
khi tính toán trong hệ đơn vị tương đối với các lượng cơ bản S và U = U thì: cb cb tb
XII
SSH
cb
NH
cb
NH* = =
1
Chương 3:QUÁ TRÌNH QUÁ ĐỘTRONG MẠCH ĐIỆN ĐƠN GIẢN
I. NGẮN MẠCH 3 PHA TRONG MẠCH ĐIỆN ĐƠN GIẢN:
Xét mạch điện 3 pha đối xứng đơn giản (hình 3.1) bao gồm điện trở, điện cảm tập trung và không có máy biến áp.
Qui ước mạch điên được cung cấp từ nguồn công suất vô cùng lớn (nghĩa là điện áp ở đầu cực nguồn điện không đổi về biên độ và tần số).
Hình 3.1 : Sơ đồ mạch điện 3 pha đơn giản
Lúc xảy ra ngắn mạch 3 pha, mạch điện tách thành 2 phần độc lập: mạch phía
không nguồn và mạch phía có nguồn.
I.1. Mạch phía không nguồn: Vì mạch đối xứng, ta có thể tách ra một pha để khảo sát. Phương trình vi phân viết
cho một pha là:
u = i.r + L .didt
= 0' '
Giải ra ta được: i t
= C.e- rL
'
' Từ điều kiện đầu (t=0): i0 = i0+ , ta có: C = i0
Như vậy: i t
= i .e0- rL
'
' Dòng điện trong mạch phía không nguồn sẽ tắt dần cho đến lúc năng lượng tích lũy
trong điện cảm L’ tiêu tán hết trên r’.
2
I.2. Mạch phía có nguồn: Giả thiết điện áp pha A của nguồn là:
u = uA = Umsin(ωt+α) Dòng trong mạch điện trước ngắn mạch là:
i = UZ
sin( t + - ) = I sin( t + - )mmω α ϕ ω α ϕ
Lúc xảy ra ngắn mạch 3 pha, ta có phương trình vi phân viết cho một pha:
u = i.r + L.didt
Giải phương trình đối với pha A ta được:
i Nt=
UZ
sin( t + - ) + C.em
N
- rLω α ϕ
Dòng ngắn mạch gồm 2 thành phần: thành phần thứ 1 là dòng chu kỳ cưỡng bức có biên độ không đổi:
i ck N N = UZ
sin( t + - ) = I sin( t + - ) m
Nckmω α ϕ ω α ϕ
Thành phần thứ 2 là dòng tự do phi chu kỳ tắt dần với hằng số thời gian:
Ta = Lr
= xrω
i tdt t = C.e = i .e- r
L td0+- rL
Từ điều kiện đầu: i0 = i0+ = ick0+ + itd0+ , ta có: C = itd0+ = i0 - ick0+ = Imsin(α - ϕ) - Ickmsin(α - ϕN)
Hình 3.2 : Đồ thị véctơ dòng và áp vào thời điểm đầu ngắn mạch
3
Trên hình 3.2 là đồ thị véctơ dòng và áp vào thời điểm đầu ngắn mạch trong đó UA, UB, UC, IA, IB, IC là áp và dòng trước khi xảy ra ngắn mạch, còn IckA, IckB, IckC là dòng chu kỳ cưỡng bức sau khi xảy ra ngắn mạch. Từ đồ thị, ta có những nhận xét sau:
itd0+ bằng hình chiếu của véctơ lên trục thời gian t. (. .I Im ckm - )
tùy thuộc vào α mà itd0+ có thể cực đại hoặc bằng 0. itd0+ phụ thuộc vào tình trạng mạch điện trước ngắn mạch; itd0+ đạt giá trị lớn
nhất lúc mạch điện trước ngắn mạch có tính điện dung, rồi đến mạch điện trước ngắn mạch là không tải và itd0+ bé nhất lúc mạch điện trước ngắn mạch có tính điện cảm.
Thực tế hiếm khi mạch điện trước ngắn mạch có tính điện dung và đồng thời thường có ϕN ≈ 90o , do vậy trong tính toán điều kiện để có tình trạng ngắn mạch nguy hiểm nhất là:
a) mạch điện trước ngắn mạch là không tải. b) áp tức thời lúc ngắn mạch bằng 0 (α = 0 hoặc 180o).
II. Trị hiệu dụng của dòng ngắn mạch toàn phầnvà các thành phần của nó:
II.1. Thành phần chu kỳ của dòng ngắn mạch: i ck N = I sin( t + - ) ckm ω α ϕ
- Nếu nguồn có công suất vô cùng lớn hoặc ngắn mạch ở xa máy phát (Um = const.), thì:
I ckm = UZ
= const. m
N
Trong trường hợp này, biên độ dòng chu kỳ không thay đổi theo thời gian và bằng dòng ngắn mạch duy trì (xác lập).
- Nếu ngắn mạch gần, trong máy phát cũng xảy ra quá trình quá độ điện từ, sức điện động và cả điện kháng của máy phát cũng thay đổi, do đó biên độ của dòng chu kỳ thay đổi giảm dần theo thời gian đến trị số xác lập (hình 3.3).
Trị hiệu dụng của dòng chu kỳ ở thời điểm t là:
IZckt
N =
I2
= E
3ckmt t
. Σ
trong đó: Et - sức điện động hiệu dụng của máy phát ở thời điểm t ZNΣ - tổng trở ngắn mạch (trong mạng điện áp cao có thể coi ZNΣ ≈ xNΣ)
4
Hình 3.3 : Đồ thị biến thiên dòng điện trong quá trình quá độ
Trị hiệu dụng của dòng chu kỳ trong chu kỳ đầu tiên sau khi xảy ra ngắn mạch gọi
là dòng siêu quá độ ban đầu:
Ix xd ng
0"
".( ) =
I2
= E3
ckm0+ "
+
trong đó: E” - sức điện động siêu quá độ ban đầu của máy phát.
x”d - điện kháng siêu quá độ của máy phát.
xng - điện kháng bên ngoài từ đầu cực máy phát đến điểm ngắn mạch.
II.2. Thành phần tự do của dòng ngắn mạch: Thành phần tự do của dòng ngắn mạch còn gọi là thành phần phi chu kỳ, tắt dần
theo hằng số thời gian Ta của mạch:
i td = i .etd0+
tTa
−
với: i td N0+ = I sin( - ) - I sin( - )m ckm0+α ϕ α ϕ Khi tính toán với điều kiện nguy hiểm nhất, ta có:
a) mạch điện trước ngắn mạch là không tải: Im sin(α - ϕ) = 0 b) áp tức thời lúc ngắn mạch bằng 0 (α = 0) và ϕN ≈ 90o .
thì: i td0+ = - I sin(-90 ) = Ickm0+o
ckm0+Trị hiệu dụng của dòng tự do ở thời điểm t được lấy bằng trị số tức thời của nó tại
thời điểm đó: Itdt = itdt
5
II.3. Dòng ngắn mạch xung kích: Dòng ngắn mạch xung kích ixk là trị số tức thời của dòng ngắn mạch trong quá trình
quá độ. Ứng với điều kiện nguy hiểm nhất, dòng ngắn mạch xung kích xuất hiện vào khoảng 1/2 chu kỳ sau khi ngắn mạch, tức là vào thời điểm t = T/2 = 0,01sec (đối với mạng điện có tần số f = 50Hz).
ixk = ick0,01 + itd0,01
trong đó: ick0,01 ≈ Ickm0+
i td0 01, = i .e = I .etd0+
0,01T
ckm0+
0,01Ta a
− −
Vậy: i xk = I .(1+ e ) = k .I
= 2.k I ckm0+
0,01T
xk ckm0+
xk 0"
a−
với kxk : hệ số xung kích của dòng ngắn mạch, tùy thuộc vào Ta mà kxk có giá trị khác nhau trong khoảng 1 ≤ kxk ≤ 2.
Trị hiệu dụng của dòng ngắn mạch toàn phần ở thời điểm t được tính như sau:
I INt ckt = 1T
= + I tdt2i .dtN
2
t T2
t T2
−
+
∫ 2
Tương ứng, trị hiệu dụng của dòng ngắn mạch xung kích là:
I Ixk ck = + I td0,012
0 012
,
với: I ck0 01, = I 0"
I td td xk ck xk0 01 0 01 0 01, , , = i = i - i = i - I
= (k -1)I = 2(k -1)I ckm0+
xk ckm0+ xk 0"
Vậy: I I Ixk = + 2 (k -1) 2 2xk
20 0" "
hay : I xk = I + 2(k -1) xk2
0 1"
6
III. NGẮN MẠCH 3 PHA TRONG MẠCH có máy biến áp:
Hình 3.4 : Sơ đồ mạch điện có máy biến áp
Giả thiết điện áp nguồn không đổi phát (Um = const.) và mạch từ của máy biến áp
không bảo hòa. Khi xảy ra ngắn mạch 3 pha, ta lập phương trình vi phân cho một pha như sau (tất cả các tham số của máy biến áp được qui đổi về cùng một phía):
Phía sơ cấp: u = R .i + L .didt
- M.didt1 1 1
1 2
Phía thứ cấp: 0 = R .i + L .didt
- M.didt2 2 2
2 1
Khi bỏ qua dòng từ hóa của máy biến áp (iµ = 0) thì i1 = i2. Cộng 2 phương trình trên ta có:
u = (R + R )i + (L + L - 2M)didt
= R .i + Ldidt
1 2 1 1 21
B 1 B1
trong đó: RB = R1 + R2 : là điện trở của máy biến áp. LB = L1 + L2 - 2M = (L1 - M) + (L2 - M) : là điện cảm của máy biến áp.
Phương trình trên giống như phương trình của mạch điện đơn giản đã khảo sát ở mục I trước đây. Do vậy trong quá trình quá độ khi bỏ qua dòng từ hóa, máy biến áp có thể được thay thế bằng điện trở và điện cảm để tính toán như mạch điện thông thường.
1
Chương 4:TÌNH TRẠNG NGẮN MẠCH DUY TRÌ
Tình trạng ngắn mạch duy trì là một giai đoạn của quá trình ngắn mạch khi tất cả
các thành phần dòng tự do phát sinh ra tại thời điểm ban đầu của ngắn mạch đã tắt hết và khi đã hoàn toàn kết thúc việc tăng dòng kích từ do tác dụng của các thiết bị TĐK.
I. Thông số tính toán của nguồn và phụ tải: Các thông số cơ bản của máy điện đồng bộ trong tình trạng ngắn mạch đối xứng
duy trì là điện kháng không bảo hòa đồng bộ dọc trục xd và ngang trục xq. Thay cho xd người ta có thể dùng một đại lượng là tỷ số ngắn mạch TN, đó chính là
dòng duy trì tính trong đơn vị tương đối khi ngắn mạch 3 pha ở đầu cực máy điện với dòng kích từ tương đối If = 1:
TNIIIf
âm= =( )1
Xuất phát từ điều kiện ngắn mạch ở đầu cực máy điện ta có:
x CTNd =
trong đó: C - sức điện động bảo hòa tương đối của máy điện khi If = 1. Trung bình có thể lấy các trị số như sau:
- Đối với máy phát turbine hơi: C = 1,2 và TN = 0,7 - Đối với máy phát turbine nước: C = 1,06 và TN = 1,1
Đối với máy điện cực lồi, điện kháng đồng bộ ngang trục xq rất ít phụ thuộc vào sự bảo hòa, thực tế có thể coi nó là không đổi và bằng:
xq ≈ 0.6xdTrong tính toán gần đúng coi: xd =1/TN Đối với máy điện có TĐK, thông số đặc trưng là dòng kích từ giới hạn Ifgh, khi dùng
kích từ kiểu máy điện thì trị số tương đối của Ifgh = (3÷5).
II. Ảnh hưởng của phụ tải và TĐK:
II.1. Anh hưởng của phụ tải: Phụ tải một mặt làm cho máy phát mang tải trước ngắn mạch, nên trong tình trạng
ngắn mạch duy trì máy phát có dòng kích từ lớn hơn so với máy phát làm việc ở chế độ không tải. Mặt khác, khi có phụ tải nối vào mạng, nó có thể làm thay đổi đáng kể trị số và sự phân bố dòng trong sơ đồ mạng.
2
Ví dụ trên sơ đồ hình 4.1, ta thấy phụ tải nối song song với nhánh ngắn mạch nên nó làm giảm điện kháng ngoài của máy phát, do vậy làm tăng dòng trong máy phát, làm giảm điện áp đầu cực máy phát và giảm dòng điện tại chỗ ngắn mạch. Ngắn mạch càng xa thì ảnh hưởng của phụ tải càng lớn, ngược lại khi ngắn mạch ngay tại đầu cực máy phát thì phụ tải không có tác dụng trong tình trạng ngắn mạch duy trì.
Hình 4.1
Nếu phụ tải bao gồm các hộ tiêu thụ tĩnh có tổng trở không đổi thì việc tính toán tổng trở của phụ tải không khó khăn gì. Tuy nhiên các phụ tải công nghiệp đa số là các động cơ không đồng bộ có tổng trở phụ thuộc rất nhiều vào độ trượt. Độ trượt lại phụ thuộc điện áp đặt vào động cơ, mà trong tình trạng sự cố thì điện áp lại là một hàm của dòng điện phải tìm. Bởi vì các quan hệ tương hổ này là không tuyến tính nên việc giải một bài toán như vậy gặp nhiều khó khăn.
Trong một hệ thống điện phức tạp, thực tế là không thể tính toán phụ tải một cách chính xác. Để đơn giản ta thay phụ tải bằng một tổng trở không đổi:
xPT = 1,2
II.1. Anh hưởng của TĐK: Khi ngắn mạch, TĐK làm tăng dòng kích từ của máy phát và trị số dòng, áp của
máy phát sẽ luôn luôn lớn hơn so với khi không có TĐK. Mức độ tăng phụ thuộc vào vị trí điểm ngắn mạch và các thông số chính của máy phát.
Thực vậy, khi ngắn mạch xa, để khôi phục điện áp đến trị số định mức chỉ cần tăng dòng kích từ lên một ít, nhưng khi ngắn mạch càng gần thì cần phải tăng dòng kích từ lên càng hơn.
Nhưng dòng kích từ chỉ có thể tăng đến một trị số giới hạn Ifgh nào đó tương ứng với khi ngắn mạch sau một điện kháng tới hạn Xth.
Khi xN ≤ Xth thì máy phát làm việc ở trạng thái kích từ giới hạn và dòng ngắn mạch là:
IE
x xqgh
d N=
+
trong đó: Eqgh - sức điện động tương ứng với dòng kích từ giới hạn Ifgh. Trong đơn vị tương đối thì: Eqgh* = Ifgh*
Khi xN ≥ Xth thì máy phát làm việc ở trạng thái điện áp định mức và:
I Ux
âm
N=
Khi xN = Xth thì: UX
Ex X
x UE U
âm
th
qgh
d thd
âm
qgh âm=
+⇒ =
− X th
3
Trong đơn vị tương đối, chọn Ucb = Uđm thì: X th* = −x
Edqgh
**
11
và dòng ngắn mạch là: I I UXth
âm
th= =
Bảng 4.1: CÁC QUAN HỆ ĐẶC TRƯNG CHO TRẠNG THÁI CỦA MÁY PHÁT CÓ TĐK
Trạng thái kích từ giới hạn Trạng thái điện áp định mức xN ≤ Xth xN ≥ Xth
If = Ifgh ; Eq = Eqgh If ≤ Ifgh ; Eq ≤ Eqgh
U ≤ Uđm U = Uđm
IE
x xIqgh
d Nth=
+≥ I U
xIâm
Nth= ≤
1
Chương 5: QUÁ TRÌNH QUÁ ĐỘ TRONG MÁY ĐIỆN
I. Khái niệm chung: Quá trình quá độ trong máy điện xảy ra phức tạp hơn trong máy biến áp hay các
thiết bị tĩnh khác do tính chất chuyển động của nó. Do vậy nếu kể đến tất cả các yếu tố ảnh hưởng thì việc nghiên cứu sẽ vô cùng khó khăn và phức tạp. Để đơn giản người ta đưa ra nhiều giả thiết gán cho máy điện một số tính chất “lý tưởng hóa”. Dĩ nhiên kết quả sẽ có sai số, nhưng so sánh với các số liệu thực nghiệm thường sai số nằm trong phạm vi cho phép.
Việc nghiên cứu vào thời điểm đầu của quá trình quá độ dựa trên nguyên lý từ thông móc vòng không đổi và để đơn giản chỉ xét trên một pha của máy điện, các cuộn dây stato và rôto xem như chỉ có một vòng dây, lúc đó từ thông Φ trong mạch từ cũng chính là từ thông móc vòng Ψ.
Qui ước chọn hệ trục tọa độ trong máy điện như sau (hình 5.1):
Hình 5.1
• Các trục tọa độ d, q giá theo dọc trục và ngang trục của rôto. • Thành phần dọc trục của dòng stato dương khi sức từ động do nó tạo nên cùng
chiều với sức từ động của cuộn kích từ. • Thành phần ngang trục của dòng stato dương khi sức từ động do nó tạo nên chậm
90o so với sức từ động của cuộn kích từ.
II. Các loại từ thông trong máy điện:
• Từ thông toàn phần của cuộn kích từ: Ψ. .
.f f fI X=trong đó: Xf - điện kháng của cuộn kích từ.
- Từ thông hữu ích: Ψ. .
.d f adI X=trong đó: Xad - điện kháng hổ cãm giữa các cuộn dây stato và rôto, được gọi là điện kháng phản ứng phần ứng dọc trục.
- Từ thông tản: Ψ. .
.σ σf f fI X=trong đó: Xσf - điện kháng tản của cuộn kích từ.
Như vậy: Ψ Ψ Ψ. . .
f d f f adX X= + = +σ σ vaì X f
2
Hệ số tản của cuộn kích từ: σ σ σf
f
f
f
f
XX
= =Ψ
Ψ
.
.
• Từ thông phần ứng: - Từ thông phản ứng phần ứng:
dọctrục: Ψ . .
.ad d adI X=
ngang trục: Ψ. .
.aq q aqI X=- Từ thông tản:
dọc trục: Ψ . .
.d dI X= σ
ngang trục: Ψ . .
.q qI X= σ
toàn phần: Ψ . .
.σ σ= I X
trong đó: I I Id q= +2 2
Hình 5.2
• Từ thông tổng hợp móc vòng với cuộn kích từ: (chỉ có theo trục dọc)
Ψ Ψ ΨΣ
. . . . .. .f f ad f f d adI X I X= + = +
• Từ thông tổng hợp móc vòng với cuộn stato: - dọc trục:
Ψ Ψ Ψ Ψ. . . . . . .
. ( ) . .sd d ad d f ad ad f ad d dI X X X I X I X= + + = + + = +σ σ - ngang trục:
Ψ Ψ Ψ. . . . .
.( ) .sq aq q q aq q qI X X I X= + + = + =0 σ σ • Từ thông kẻ hở không khí dọc trục:
Ψ Ψ Ψ. . . . . . .
. . ( )δd d ad f ad d ad f d adI X I X I I X= + = + = + • Từ thông cuộn cản:
- Cuộn cản dọc:
từ thông chính: Ψ. .
.1 1d d adI X=
từ thông tản: Ψ. .
.σ σ1 1 1d d dI X=- Cuộn cản ngang:
từ thông chính: Ψ. .
.1 1q qI X= aq
từ thông tản: Ψ. .
.σ σ1 1 1q q qI X=
III. Sức điện động và điện kháng quá độ: Sức điện động và điện kháng quá độ là những tham số đặc trưng cho máy phát điện
không có cuộn cản vào thời điểm đầu của quá trình ngắn mạch. Khi ngắn mạch, từ thông Φad tăng đột ngột một lượng ∆Φado+ (hình 5.3). Theo định
luật Lenx, độ tăng ∆Φado+ sẽ làm cho Φf tăng lên một lượng ∆Φfo+ sao cho tổng từ thông móc vòng là không đổi.
3
∆Ψ ∆Ψ ∆ΨΣ
. . .f fo ado= ++ + 0=
Do Φf tăng nên Φσf cũng tăng một lượng tỷ lệ vì:
Ψ Ψ. .
.σ σf f f= và từ thông kẻ hở không khí cũng giảm xuống vì:
Φ Φ ΦΣδ σd f f= − Điều này chứng tỏ Φd, Φδd và sức điện động Eq, Eδ tương ứng của máy phát thay
đổi đột biến vào thời điểm đầu của ngắn mạch nên không thể sử dụng các tham số này để thay thế cho máy phát vào thời điểm đầu của ngắn mạch.
Hình 5.3
Để đặc trưng cho máy phát trong tính toán ta sử dụng từ thông không đột biến lúc
ngắn mạch là ΦfΣ, trong đó phần xem như móc vòng với cuộn dây stato là:
Ψ Ψ Σ. ' .
( )d f= −1 σ f Ψd’ được gọi là từ thông quá độ dọc trục.
Ψ Ψ Ψ. ' . . . .
. .
( )( ) ( )df
f adf ad
ad
f adf f ad d ad
f ad dad
f ad
XX X
XX X
I X X I X
I X I XX X
= −+
+ =+
+ +⎡⎣⎢
⎤⎦⎥
++
1
2
σ
σ σσ
σ =
Từ thông móc vòng này ứng với sức điện động Eq’ được gọi là sức điện động quá độ:
E E j I XX X
U j I x XX X
U j I xq q dad
f adq d d
ad
f adq d d' (
. . . . . . . '= −+
= + −+
+2 2
σ σ=) .
xd’ được gọi là điện kháng quá độ dọc trục.
x x XX X
XX X
X Xd dad
f ad
f ad
f a
' .= −
+= +
+
2
σσ
σ
σ d
4
Đối với máy phát không có cuộn cản ngang trục, từ thông phản ứng phần ứng ngang trục Φaq trong quá trình quá độ có thể đột biến. Sự đột biến của từ thông này có thể xem như là điện áp rơi do dòng Iq trên điện kháng xq, nghĩa là:
Ed’ = 0 ; xq’ = xqTóm lại, nếu máy điện không có cuộn cản thì
ở thời điểm đầu ngắn mạch có thể thay thế bằng Eq’ và xd’.
Dòng quá độ ở thời điểm đầu ngắn mạch chỉ có thành phần dọc trục:
Hình 5.4
I IE
x xo doq
d n
' ''
'= =+ g
=
σ
I.
trong đó: xng - điện kháng từ đầu cực máy điện đến điểm ngắn mạch.
IV. Sức điện động và điện kháng siêu quá độ: Sức điện động và điện kháng siêu quá độ là những tham số đặc trưng cho máy phát
điện có cuộn cản vào thời điểm đầu của quá trình ngắn mạch. Xét một máy điện có các cuộn cản dọc trục và ngang trục, giả thiết cuộn kích từ và
cuộn cản dọc trục là như nhau nên cả 2 đều liên hệ với cuộn dây stato bởi từ thông hỗ cảm chung Φad được xác định bởi Xad.
Khi có một lượng tăng đột ngột từ thông ∆Φad, ở rôto sẽ có thay đổi tương ứng từ thông của cuộn kích từ ∆Φf và của cuộn cản dọc trục ∆Φ1d sao cho tổng từ thông móc vòng không đổi, do vậy:
- Đối với cuộn kích từ: ∆Ψ ∆Ψ ∆Ψ. . .
f d ad+ + =1 0
∆ ∆ ∆I X X I X I Xf f ad d ad d ad. . .
( )σ + + +1 = 0 (5.1)
- Đối với cuộn cản dọc: ∆Ψ ∆Ψ ∆Ψ ∆Ψ. . . .
1 1 0d d d ad+ + +σ
∆ ∆ ∆I X X I X I Xd d ad f ad d ad. . .
( )1 1σ + + + = 0 (5.2)
Từ (5.1) và (5.2) ta có: (5.3) ∆ ∆I X I Xf f d d. .
σ = 1 1 Từ (5.3) thấy rằng lượng tăng ∆Id tạo ra ở 2 cuộn kích từ và cuộn cản dọc các dòng
điện tăng cùng chiều nhưng độ lớn tỷ lệ nghịch điện kháng tản của chúng. Thay thế phản ứng của 2 cuộn dây ở rôto tại thời điểm đầu của ngắn mạch bằng
phản ứng của một cuộn dây tương đương dọc trục có dòng bằng:
∆ ∆ ∆I Ird f d. .
= + 1 và điện kháng tản Xσrd với điều kiện vẫn thỏa mãn nguyên lý từ thông móc vòng không đổi, tức là:
5
∆Ψ ∆Ψ ∆Ψ. . .
rd rd ad+ +σ 0=
⇒ + +
⇒ + + +
= 0
= 0 (5.4)
∆ ∆
∆ ∆ ∆
I X X I X
I I X X I X
rd rd ad d ad
f d rd ad d ad
. .
. . .
( )
( )( )
σ
σ1
Giải các phương trình (5.2), (5.3) và (5.4) ta được:
XX X
X Xrdf d
f dσ
σ σ
σ σ=
+. 1
1
Như vậy điện kháng tản của cuộn dây tương đương với cuộn kích từ và cuộn cản dọc bằng điện kháng tản của 2 cuộn dây này ghép song song.
Để tìm điện kháng đặc trưng cho máy điện theo trục dọc ở thời điểm đầu của ngắn mạch, ta thực hiện tính toán tương tự như mục III (đối với máy điện không có cuộn cản) trong đó thay cuộn kích từ có Xσf bằng cuộn dây tương đương có Xσrd và ta cũng tìm được:
x x XX X
X
X X X
d dad
rd ad
f d
'' = −+
= ++ +
2
1
11 1 1σ
σ
σ σ ad
xd’’ được gọi là điện kháng siêu quá độ dọc trục. Tương tự cho trục ngang, ta cũng có điện kháng siêu quá độ ngang trục:
x xX
X XX
X XX Xq q
aq
q aq
q aq
q a
'' .= −
+= +
+
2
1
1
1σσ
σ
σ q
Các sức điện động tương ứng với các điện kháng trên được gọi là sức điện động siêu quá độ ngang trục Eq’’ và dọc trục Ed’’, chúng có giá trị không đột biến vào thời điểm đầu ngắn mạch.
E U j I x
E U j I x
q qo do d
d do qo q
. . . ''
. . . ''
' ' .
' ' .
= +
= +
trong đó: Uqo, Udo, Iqo, Ido - áp và dòng trước
ngắn mạch.
E E Eo q'' '' ''= +2
d2 - sức điện động siêu
quá độ toàn phần. Hình 5.5
Vậy máy phát ở thời điểm đầu ngắn mạch có thể đặc trưng bằng sức điện động siêu quá độ và điện kháng siêu quá độ.
Giá trị dòng siêu quá độ dọc trục và ngang trục tương ứng là:
IE
x x
I Ex x
dq
d n
qd
q n
''''
''
''''
''
=+
=+
g
g
6
Và dòng siêu quá độ toàn phần là: I I Io d'' '' ''= +2 2
q Trong tính toán thực dụng gần đúng xem xd’’ = xq’’ ta có:
E
E
o d
o d d
U U I x
hay U I x I x
'' ''
'' '' ''
( cos ) ( sin . )
: ( . sin ) ( . cos )
= + +
= + +
ϕ ϕ
ϕ ϕ
2 2
2 2
V. Ý nghĩa vật lý của các điện kháng: Từ các biểu thức tính toán điện kháng ta thấy: xd’’ < xd’ < xdVề mặt vật lý điều đó được giải thích như sau: Trong chế độ bình thường từ thông
tạo bởi dòng stato gồm một phần móc vòng theo đường tản từ, còn phần chính đi ngang kẻ hở không khí khép vòng qua các cực và thân rôto. Vì từ trở chủ yếu là ở kẻ hở không khí có từ dẫn λad nhỏ (hình 5.6a), từ cảm lớn; do vậy tương ứng với điện kháng xd.
Khi từ thông stato thay đổi đột ngột, trong cuộn kích từ sẽ có dòng cảm ứng tạo nên từ thông ngược hướng với từ thông stato, vì vậy có thể xem như một phần từ thông stato bị đẩy ra ngoài đi theo đường tản từ của cuộn kích từ có từ dẫn λσf (hình 5.6b). Như vậy từ thông stato phải đi qua một tổng từ dẫn lớn, từ cảm sẽ nhỏ hơn và sẽ có: xd’ < xd
Hình 5.6
Rôto càng có nhiều mạch vòng kín, từ thông stato càng khó xâm nhập vào rôto.
Trường hợp giới hạn, khi từ thông hoàn toàn không thể đi vào rôto, nghĩa là chỉ đi theo đường tản từ của cuộn dây stato có từ dẫn λσ, điện kháng của stato lúc đó chính là điện kháng tản Xσ, tương ứng với trường hợp xd’’ nhỏ nhất có thể có.
Đối với các máy điện không có cuộn cản, bản thân rôto cũng có tác dụng như cuộn cản nên có thể xem: xd’’ = (0,75÷0,9) xd’
VI. Qua trình quá độ trong máy điện không cuộn cản: Để đơn giản trước tiên ta khảo sát các máy điện không có thiết bị TĐK. Giả thiết
ngắn mạch tại đầu cực của máy điện, mạch điện xem như thuần kháng, dòng ngắn mạch chỉ có theo trục dọc.
Khi xảy ra ngắn mạch, thành phần chu kỳ của dòng ngắn mạch sẽ thay đổi đột biến. Độ tăng là:
7
∆I I IEx
Id do doqo
ddo= − = −+
+''
'
trong đó: Ido - dòng làm việc trước ngắn mạch. I‘do+ - dòng quá độ tại thời điểm đầu ngắn mạch.
Để từ thông móc vòng không đổi, dòng kích từ If cần phải tăng một lượng:
∆ ∆I I XX Xf d
ad
ad f=
+ σ
Do cuộn kích từ có điện trở rf nên trị số này sẽ suy giảm theo hằng số thời gian Td’ của cuộn kích từ và ∆If chính là trị số ban đầu của thành phần tự do không chu kỳ iftd của dòng kích từ (hình 5.7):
i i e I eftd ftdo
tTd
f
tTd= =+
− −. .' '∆
Dòng iftd tạo nên sức điện động ∆Eq trong cuộn dây stato và làm xuất hiện thành phần tự do chu kỳ ∆i’ck trong dòng stato với trị hiệu dụng ban đầu là:
∆ ∆I I I Ick d do d' ' '= = −+ ∞
Id∞ = IN∞ : dòng ngắn mạch xác lập ứng với sức điện động đồng bộ ngang trục Eq∞ do dòng kích từ cưỡng bức Ifo = If∞ tạo ra.
Như vậy, thành phần chu kỳ cơ bản của dòng ngắn mạch gồm 2 thành phần: tự do chu kỳ ∆i’ck do dòng tự do của cuộn kích từ iftd sinh ra và do đó cũng tắt
dần theo hằng số thời gian Td’. chu kỳ cưỡng bức ick do dòng kích từ cưỡng bức Ifo = If∞ tạo ra.
i’ck = ick + ∆i’ck gọi là dòng ngắn mạch quá độ và có trị hiệu dụng ban đầu là I‘do+. Do dòng chu kỳ tăng so với trước khi ngắn mạch nên trong cuộn dây stato xuất hiện
thành phần tự do không chu kỳ itd sao cho dòng ngắn mạch toàn phần ở thời điểm đầu ngắn mạch là không đột biến. Dòng này tắt dần theo hằng số thời gian Ta của mạch stato:
i i e I etd tdo
tTa
d
tTa= = −+
− −. .∆
Dòng itd tạo từ thông đứng yên đối với stato, do đó sẽ cảm ứng sang rôto thành phần tự do chu kỳ ifck trong dòng kích từ. Vì dòng kích từ if ở thời điểm đầu ngắn mạch không đột biến nên trị số ban đầu của các thành phần trong dòng kích từ phải thỏa mãn: ifcko+ = -iftdo+ = -∆If
Dòng ifck tắt dần theo hằng số thời gian Ta vì dòng itd ở stato sinh ra nó tắt dần theo hằng số thời gian Ta.
Hình 5.7
8
Dòng ifck sinh ra từ trường đập mạch ở rôto nên có thể phân ra thành 2 từ trường quay ngược chiều nhau:
- Từ trường quay ngược chiều với rôto (-ω) sẽ đứng yên so với stato nên không cảm ứng sang stato.
- Từ trường quay cùng chiều với rôto (+ω) sẽ quay với tốc độ 2ω so với stato và cảm ứng sang stato tạo nên dòng tự do chu kỳ ick(2ω) có tần số 2ω. Dòng này tắt dần theo hằng số thời gian Ta.
Tóm lại: Dòng trong cuộn dây stato là:
iN = ick + ∆i’ck - itd - ick(2ω) = i’ck - itd - ick(2ω)Dòng trong cuộn dây kích từ là:
if = Ifo + iftd - ifck
VII. Quá trình quá độ trong máy điện có cuộn cản: Khi từ thông phản ứng phần ứng thay đổi, trong cuộn cản cũng cảm ứng nên một
dòng tự do không chu kỳ tương tự như trong cuộn kích từ. Dòng này lại tác dụng lên cuộn dây stato và cuộn cản trong quá trình quá độ.
VII.1. Dòng trong cuộn dây stato: Ngoài các thành phần dòng điện giống như ở máy điện không cuộn cản, trong cuộn
dây stato của máy điện có cuộn cản còn bao gồm: Thành phần siêu quá độ tự do dọc trục ∆ i’’ck do dòng tự do trong cuộn cản dọc
trục sinh ra, do đó nó tắt dần theo hằng số thời gian T’’d của cuộn cản dọc trục. Như vậy thành phần chu kỳ dọc trục gồm:
i’’ck = ick + ∆ i’ck + ∆ i’’ck = i’ck + ∆ i’’cki’’ck gọi là dòng ngắn mạch siêu quá độ dọc trục, có trị hiệu dụng ban đầu là:
IExdo
q
d+ =
""
"
Do T’’d bé nên dòng trong cuộn cản và dòng ∆ i’’ck tắt nhanh hơn dòng ∆ i’ck do cuộn kích từ sinh ra.
Thành phần siêu quá độ tự do ngang trục i’’q do dòng tự do trong cuộn cản ngang trục sinh ra, do đó nó tắt dần theo hằng số thời gian T’’q của cuộn cản ngang trục và có trị hiệu dụng ban đầu là:
I Exqo
d
q+ =
""
"
Vậy dòng ngắn mạch toàn phần của máy điện có cuộn cản: iN = ick + ∆ i’ck + ∆ i’’ck + i’’q - itd - ick(2ω)
Trị hiệu dụng của dòng siêu quá độ ban đầu là:
I I Io do qo" " "= ++ +
2 2
Trong tính toán gần đúng, khi coi x”d = x”q thì: I Exo
o
d
""
"=
9
VII.2. Dòng trong cuộn kích từ: Vẫn gồm các thành phần như ở máy điện không cuộn cản nhưng thành phần tự do
không chu kỳ có khác do ảnh hưởng của cuộn cản. iftd = iftd(KCC) - i’’f
iftd(KCC): thành phần tự do không chu kỳ xuất hiện trong máy điện không cuộn cản. i”f : thành phần tự do không chu kỳ do ảnh hưởng của cuộn cản, tắt theo hằng số thời
gian T”d.
VII.3. Dòng trong cuộn cản: Trong chế độ làm việc bình thường hoặc khi ngắn mạch duy trì, qua cuộn cản
không có dòng điện. Trong quá trình quá độ, ở cuộn cản dọc trục xuất hiện dòng tự do không chu kỳ tắt dần theo 2 hằng số thời gian T”d và T’d. Đồng thời dưới tác dụng của dòng tự do trong cuộn dây stato, ở cuộn cản sẽ có thành phần chu kỳ i1dck tắt dần theo hằng số thời gian Ta sao cho dòng trong cuộn cản không đột biến.
i1d = i1dtd + i1dckTrong cuộn cản ngang trục cũng xuất hiện các thành phần dòng tương tự. Đối với máy phát turbine hơi không có cuộn cản, lõi thép cũng được xem như có
tác dụng tương tự cuộn cản. Do vậy trong qúa trình quá độ, diễn biến dòng trong cuộn dây stato và rôto có dạng giống như đối với các máy điện có cuộn cản. Và trong tính toán vẫn dùng những tham số siêu quá độ để thay thế tại thời điểm đầu ngắn mạch.
VIII. Các hằng số thời gian tắt dần: Do trong mạch có điện trở tác dụng nên các thành phần dòng tự do sẽ tắt dần với
hằng số thời gian T = L/r. Trong hệ đơn vị tương đối thì:
T Lr
Xr
Xr*
*
*
*
*= = =
VIII.1. Hằng số thời gian của cuộn dây stato:
T Xrast
= 2 trong đó: X2 - điện kháng thứ tự nghịch của máy điện
Nếu ngắn mạch cách máy điện một đoạn có tổng trở Z = r + jx thì:
T X xr rast
=++
2
VIII.2. Hằng số thời gian của cuộn kích từ:
Khi máy phát không tải: T Xr
X Xrfo
f
f
ad f
f= =
+ σ
Khi ngắn mạch ngay tại đầu cực máy phát:
T TX
X XX Xr
Xrf d
fad
ad
f
f
f
' ''
.
= =+
+=
σσ
σ
10
Có thể chứng minh được rằng: T T XX
T xxd fo
f
ffo
d
d
'' '
= =
trong đó: Xf’ - điện kháng của cuộn kích từ khi nối tắt cuộn dây stato. Nếu ngắn mạch cách máy phát một đoạn có điện kháng bằng x thì:
T T x xx xd fo
d
d
''
=++
VIII.3. Hằng số thời gian của cuộn cản: Hằng số thời gian của cuộn cản dọc Td’’ và cuộn cản ngang Tq’’ cũng phụ thuộc
vào khoảng cách đến điểm ngắn mạch. Có thể lấy các trị số trung bình như sau: - Máy phát turbine hơi: Td’’ ≈ Tq’’ ≈ 0,1 sec.
- Máy phát turbine nước: Td’’ ≈ Tq’’ ≈ 0,05 sec.
IX. Ảnh hưởng của TĐK và phụ tải đến quá trình ngắn mạch:
IX.1. Anh hưởng của TĐK: Tại thời điểm đầu của ngắn mạch, vì từ thông móc vòng với các cuộn dây là không
đổi nên thiết bị TĐK không có ảnh hưởng. Điều đó cho phép tính toán các tham số ở thời điểm đầu của ngắn mạch (chẳng hạn như Io’’, Eo’’, ixk) giống như đối với các máy điện không có TĐK.
Trong khoảng thời gian tiếp theo của quá trình quá độ, TĐK làm tăng dòng kích từ và do đó làm tăng các thành phần dòng trong cuộn dây stato và cuộn cản dọc. Quá trình này diễn ra chậm, do vậy thực tế nó chỉ làm thay đổi sức điện động quay của stato và thành phần chu kỳ của dòng stato. Thành phần không chu kỳ và sóng điều hòa bậc 2 ở stato vẫn giống như khi không có TĐK.
Đối với cuộn cản dọc, dòng sinh ra trong nó là do sức điện động biến áp, sức điện động này nhỏ vì dòng kích từ if thay đổi chậm. Do vậy dòng tự do có bị giảm xuống nhưng không đáng kể.
IX.2. Anh hưởng của phụ tải: Anh hưởng của phụ tải ở thời điểm đầu của ngắn mạch phụ thuộc vào điện áp dư tại
điểm nối phụ tải, tức phụ thuộc vào điện kháng xN từ phụ tải cho đến điểm ngắn mạch. Khi xN < 0,4: phụ tải xem như nguồn cung cấp làm tăng dòng ngắn mạch. Khi xN > 0,4: phụ tải tiêu thụ dòng điện làm giảm dòng ngắn mạch. Khi xN = 0 thì dòng phụ tải chiếm khoảng 25% dòng ngắn mạch.
Trong tính toán thực tế, các phụ tải được gộp chung thành phụ tải tổng hợp ở một điểm của hệ thống điện và được thay thế gần đúng bằng: X’’PT = 0,35 và E’’PT = 0,8
Chỉ kể đến một cách riêng rẽ các động cơ cỡ lớn và được thay thế như sau: - Các động cơ đồng bộ có cấu tạo giống như máy phát. Ở thời điểm đầu của ngắn
mạch, động cơ đang quay theo quán tính xem như vẫn còn tốc độ đồng bộ nên có thể thay thế bằng các tham số giống như đối với máy phát là Eo’’ và xd’’.
11
- Các động cơ không đồng bộ với hệ số trượt bé xem như là động cơ đồng bộ không có cuộn kích từ, cũng được thay thế bằng sức điện động và điện kháng siêu quá độ:
Eo o o o
Nmm
U I X
X xI
'' ''
*"
*"
*
. .sin
( , , )
≈ −
= = = ÷
ϕ1 0 25 0 35
trong đó: I*mm - dòng mở máy của động cơ. Uo, Io, ϕo - tham số của động cơ trước khi xảy ra ngắn mạch.
1
Chương 6: CÁC PHƯƠNG PHÁP TÍNH TOÁN NGẮN MẠCH
I. Khái niệm chung: Phương pháp tính dòng ngắn mạch bằng cách giải hệ phương trình vi phân đòi hỏi
nhiều công sức, mặc dù chính xác nhưng ngay cả để tính một sơ đồ đơn giản khối lượng tính toán cũng khá cồng kềnh, bậc phương trình tăng nhanh theo số máy điện có trong sơ đồ. Ngoài ra còn có những vấn đề làm phức tạp thêm quá trình tính toán như: dao động công suất, dòng tự do trong các máy điện ảnh hưởng nhau, tác dụng của thiết bị tự động điều chỉnh kích từ (TĐK), tham số dọ trục và ngang trục khác nhau.... Do đó, trong thực tế thường dùng các phương pháp thực dụng cho phép tính toán đơn giản hơn.
Ngoài các giả thiết cơ bản đã nêu trước đây, còn có thêm những giả thiết sau: Qui luật biến thiên thành phần chu kỳ của dòng ngắn mạch trong sơ đồ có một
máy phát tương tự như trong sơ đồ có nhiều máy phát. Việc xét đến thành phần không chu kỳ của dòng ngắn mạch trong tất cả các
trường hợp có thể tiến hành một cách gần đúng. Rôto của các máy điện đồng bộ là đối xứng do đó không cần phân biệt sức điện
động, điện áp, dòng điện theo các trục và có thể bỏ qua thành phần chu kỳ 2ω. Tùy mục đích tính toán có thể sử dụng các phương pháp khác nhau với sai số không
được vượt quá phạm vi cho phép ±5% đối với trị số ban đầu và ±10÷15% ở các thời điểm khác.
II. Phương pháp giảI tích:
II.1. Tính dòng siêu quá độ ban đầu: Trình tự tính toán như sau:
a) Lập sơ đồ thay thế, tính toán qui đổi tham số của các phần tử trong hệ đơn vị có tên hay đơn vị tương đối:
- Máy phát: thay thế bằng E”o và X’’ = x”d = x”q, đối với máy phát không có cuộn cản xem rôto như cuộn cản tự nhiên, tức là cũng dùng các thông số siêu qúa độ để tính toán với x”d = (0,75÷0,9) x’d.
Sức điện động E”o được tính theo công thức gần đúng với giả thiết máy phát làm việc ở chế độ định mức trước khi ngắn mạch:
E U I x Uo F F d F" "( sin ) ( cos )= + +ϕ ϕ2 2
Nếu máy phát làm việc ở chế độ không tải trước khi ngắn mạch thì E”o = UF. - Động cơ và máy bù đồng bộ được tính như máy phát. - Động cơ không đồng bộ và phụ tải tổng hợp thay thế bằng:
X XIN
mm*"
**
= =1
2
và: E”o ≈ Uo - IoX”sinϕotrong đó: X*N - điện kháng ngắn mạch (lúc động cơ bị hãm).
I*mm - dòng mở máy của động cơ. Uo, Io, sinϕo - được lấy ở tình trạng trước ngắn mạch.
Khi không có đủ số liệu cần thiết có thể tra bảng sau: THIẾT BỊ X” E”o
Máy phát turbine hơi 0,125 1,08 Máy phát turbine nước có cuộn cản 0,2 1,13 Máy phát turbine nước không cuộn cản 0,27 1,18 Động cơ đồng bộ 0,2 1,1 Máy bù đồng bộ 0,2 1,2 Động cơ không đồng bộ 0,2 0,9 Phụ tải tổng hợp 0,35 0,8
b) Tính toán: Biến đổi sơ đồ thành dạng đơn giản gồm một hay nhiều nhánh nối trực tiếp từ nguồn đến điểm ngắn mạch (hình 6.1), từ đó tính được dòng siêu quá độ ban đầu theo biểu thức sau:
I EXo
i
ii
n"
"
"==∑
1
c) Chú ý: Trong thực tế, việc tính toán dòng siêu quá độ ban đầu thường chỉ xét đến những phụ tải nối trực tiếp vào điểm ngắn mạch.
Hình 6.1
II.2. Tính dòng ngắn mạch đối với nguồn công suất vô cùng lớn: Trong tính toán đơn giản sơ bộ hay trong mạng có nguồn công suất vô cùng lớn thì
thành phần chu kỳ của dòng ngắn mạch là không đổi và được tính như sau:
I UX
I Icktb
o= = = ∞3 Σ
"
trong đó: Utb - điện áp trung bình của đoạn có điểm ngắn mạch. XΣ - điện kháng giữa nguồn và điểm ngắn mạch qui về đoạn có điểm ngắn
mạch. Trong hệ đơn vị tương đối với lượng cơ bản là Scb và Ucb = Utb thì:
S IXN ck* *
*= =
1Σ
với: S UN tb= 3 I ck Trong tính toán thực dụng, việc xét đến các hệ thống thường là gần đúng. Nếu đã biết trị số dòng siêu qúa độ ban đầu I”o hoặc công suất S”N khi ngắn
mạch 3 pha tại một nút bất kỳ trong hệ thống (hình 6.2), thì có thể xác định điện kháng XH của hệ thống đối với điểm nút này:
X UI
USH
tb
o
tb
N= =
3
2
. " " hay X II
SSH
cb
o
cb
N* " "= = (6.1)
3
Nếu không biết dòng hay công suất ngắn mạch, có thể xác định điện kháng XH gần đúng từ công suất cắt định mức của máy cắt dùng để cắt công suất ngắn mạch đó (hình 6.3), tức là trong các biểu thức (6.1) ở trên dùng ICđm và SCđm thay cho I”o và S”N.
Hình 6.2
Hình 6.3 Nếu tại nút đang xét còn có nhà máy điện địa phương (hình 6.3) thì phải giảm bớt
lượng I”F, S”F do nhà máy điện này cung cấp, tức là trong các biểu thức (6.1) ở trên dùng (ICđm- I”F) và (SCđm- S”F) thay cho I”o và S”N.
Trường hợp có một số hệ thống liên lạc với nhau qua một số điểm nút, nếu đã biết dòng hay công suất ngắn mạch ở mỗi điểm nút, cũng có thể xác định được điện kháng XH của hệ thống. Ví dụ, trên hình 6.4 ta có:
X UI
UIM
tb
MN
tb
NΣ Σ= =
3 3. ." " vaì X
X X X XX X X
X X X XX X X
MH H MN
H H M
NH MN H
H H M
Σ
Σ
=N
N
++ +
=++ +
1 2
1 2
1 2
1 2
( )
( )
từ đó, khi đã biết I”M, I”N và XMN có thể tính được XH1 và XH2.
Hình 6.4
II.3. Tính dòng xung kích: a) Đối với mạng có công suất vô cùng lớn:
I”o = Ick = I∞
lúc đó: i k I k I
I I kxk xk ckm xk ck
xk ck xk
= =
= + −
2
1 2 1 2( )
4
b) Đối với mạng có công suất hữu hạn:
i k I
I I kxk xk o
xk o xk
=
= + −
2
1 2 1 2
"
" ( )
trong các biểu thức trên, kxk là hệ số xung kích, phụ thuộc vào hằng số thời gian Ta=L/r. Khi xét riêng ảnh hưởng của các động cơ và phụ tải tổng hợp thì:
i k I kxk xk o xk Â= +2 2" "I với: I”Đ - dòng siêu quá độ ban đầu do động cơ hay phụ tải cung cấp.
kxkĐ - hệ số xung kích của động cơ hay phụ tải tổng hợp. Trung bình có thể lấy giá trị như sau:
Ngắn mạch tại thanh góp điện áp máy phát hoặc đầu cao áp của máy biến áp tăng: kxk = 1,9
Ngắn mạch ở các thiết bị cao áp xa máy phát: kxk = 1,8 Ngắn mạch phía thứ cấp của các trạm hạ áp (S<1000KVA): kxk = 1,3 Đối với động cơ không đồng bộ, độ suy giảm của các thành phần dòng chu
kỳ và tự do do nó cung cấp cho điểm ngắn mạch là gần như nhau, có thể lấy: - động cơ cở lớn : kxkĐ = 1,8
- động cơ cở 100÷200KW: kxkĐ = 1,5÷1,6 - động cơ cở bé và phụ tải tổng hợp: kxkĐ = 1
II.4. Tính dòng ngắn mạch duy trì: Các phần tử được thay thế bởi các tham số giống như ở chế độ làm việc bình
thường của hệ thống điện.
a) Đối với hệ thống điện bao gồm các máy phát không có TĐK: - Máy phát được thay bằng Eq và xd với Eq* = If*. Nếu chưa biết dòng kích từ If
thì có thể tính Eq từ chế độ làm việc của máy phát trước khi xảy ra ngắn mạch:
E U I x Uq F F d F" ( sin ) ( cos )= + +ϕ ϕ2 2
- Phụ tải tập trung tại các nút được thay bằng: xPT = 1,2 và EPT = 0 - Lập sơ đồ thay thế và biến đổi để tìm dòng ngắn mạch:
I I EXN ck= = Σ
Σ
b) Đối với hệ thống điện bao gồm các máy phát có TĐK: Trường hợp mạch đơn giản chỉ có một máy phát thì tình trạng làm việc của máy
phát khi ngắn mạch duy trì có thể được xác định bằng cách so sánh điện kháng ngắn mạch XN với Xth:
X x UE Uth d
âm
qgh âm=
−
hay khi Ucb = Uđm thì: X xEth d
qgh* *
*=
−1
1
Nếu XN > Xth thì máy phát làm việc ở trạng thái định mức và được thay bằng Eqgh và xd với: Eqgh* = Ifgh*
5
Nếu XN < Xth thì máy phát làm việc ở trạng thái kích từ giới hạn và được thay bằng Uđm và XF = 0.
Trường hợp mạch phức tạp có nhiều nguồn liên kết ảnh hưởng nhau thường không thể sử dụng chỉ tiêu nêu trên để xác định tình trạng làm việc của các máy phát. Do đó phải dùng phương pháp gần đúng như sau:
- Tùy thuộc vào vị trí của máy phát đối với điểm ngắn mạch, giả thiết trước tình trạng làm việc của máy phát.
- Lập sơ đồ thay thế và tiến hành tính toán dòng ngắn mạch IN. - Kiểm tra lại giả thiết bằng cách tính ngược lại để tìm dòng IF do mỗi máy phát
cung cấp cho điểm ngắn mạch và so sánh với Ith của từng máy phát.
IX
Exth
th
qgh
d*
*
*
*= =
−1 1
Nếu IF > Ith thì máy phát làm việc ở trạng thái kích từ giới hạn. Nếu IF < Ith thì máy phát làm việc ở trạng thái định mức.
Đối với những máy phát đã giả thiết làm việc ở trạng thái kích từ giới hạn cũng có thể kiểm tra theo điện áp đầu cực máy phát (UF < Uđm)
Nếu giả thiết đúng xem như bài toán đã giải xong. Nếu giả thiết sai ở một máy phát nào đó cần phải thay đổi trạng thái của nó và tính toán lại.
- Những điểm cần lưu ý: Phụ tải làm tăng tổng dẫn so với điểm ngắn mạch, vì vậy nếu bỏ qua ảnh
hưởng của phụ tải thì kết quả tính toán có thể có sai số lớn, chỉ bỏ qua ảnh hưởng của phụ tải khi xét đến ngắn mạch ở ngay đầu cực máy phát.
Phụ tải cũng có thể ảnh hưởng đến tình trạng làm việc của máy phát trong điều kiện ngắn mạch, do vậy cần phải xét đến chúng khi giả thiết.
Nếu trong hệ thống có máy phát không có TĐK thì thay thế nó bằng Eq và xd.
II.5. Tính dòng ngắn mạch toàn phần: Để máy cắt làm việc đảm bảo cần chọn SCđm và ICđm của nó sao cho vào thời điểm
cắt t ta có: SCđm > SNt và ICđm > INtDo đó cần xác định trị hiệu dụng của dòng ngắn mạch toàn phần vào thời điểm t:
I I INt ckt tdt= +2 2 trong đó, Ickt tính toán bằng giải tích rất phức tạp, thường tra theo đường cong tính toán, còn Itdt được tính bằng biểu thức sau:
I I e I etdt tdo
tTa
o
tTa= =+
− −. ."2
Thực tế để đơn giản dùng công thức gần đúng sau: INt = αt.I”o
αt : hệ số tính toán, giá trị trung bình của nó có thể lấy như sau: khi t = 0,05sec: αt = 1,1 khi t = 0,1 sec: αt = 1 khi t ≥ 0,2 sec: có thể xem INt ≈ Ickt vì hầu như thành phần tự do đã tắt hết.
6
III. Phương pháp đường cong tính toán: III.1. Đường cong tính toán: Đường cong tính toán là đường cong biểu diễn trị số tương đối của thành phần chu
kỳ trong dòng ngắn mạch tại những thời điểm tùy ý của quá trình quá độ phụ thuộc vào một điện kháng - điện kháng tính toán x*tt = x”d + xN.
I*ckt = f(x*tt , t)
Hình 6.5
Đường cong được xây dựng theo sơ đồ đơn giản như hình 6.5, trong đó coi rằng trước ngắn mạch máy phát làm việc với phụ tải định mức và phụ tải đó không đổi trong suốt quá trình ngắn mạch, nhánh bị ngắn mạch 3 pha tại điểm N có điện kháng xN không mang tải trước khi xảy ra ngắn mạch.
Cho xN các giá trị khác nhau, theo các biểu thức đã biết hoặc bằng mô hình tính Ick tại điểm ngắn mạch ở các thời điểm khác nhau. Từ kết quả tính được, xây dựng họ đường cong I*ckt = f(x*tt , t). Các tham số đều tính trong đơn vị tương đối với lượng cơ bản là định mức của máy phát: Ucb = Utb và Scb = SđmF.
đường cong tính toán
Hình 6.6 Thực tế có 2 loại đường cong tính toán khác nhau cho 2 loại máy phát: turbine hơi
và turbine nước (hình 6.6). Các đặc điểm của đường cong tính toán như sau:
Khi xtt càng lớn (ngắn mạch càng xa) thì sự biến thiên của biên độ dòng điện chu kỳ theo thời gian càng ít. Khi xtt > 3 có thể xem Ickt = I”o.
Khi xtt càng tăng lên thì sự khác biệt về dòng giữa 2 loại máy phát càng nhỏ và khi xtt > 1 thì đường cong tính toán của 2 loại máy phát hầu như trùng nhau.
Đường cong tính toán tương ứng với các thời điểm khác nhau có thể cắt nhau. Điều này là do tác dụng của thiết bị TĐK làm tăng dòng ngắn mạch sau khi qua một trị số cực tiểu nào đó. Các đường cong tính toán bị giới hạn bởi đường cong I*ck = 1/x*N do phải thỏa mãn điều kiện Ickt ≤ Uđm/xN.
Nếu hằng số thời gian Tfo của máy phát khác với Tfotc của máy phát tiêu chuẩn thì cần hiệu chỉnh thời gian t ở đường cong tính toán thành:
7
t t TTfotc
fo
' .=
Đối với máy phát turbine hơi: Tfotc= 7sec, máy phát turbine nước: Tfotc= 5sec. Đường cong tính toán được vẽ với máy phát có phụ tải định mức, do đó trường
hợp máy phát không có phụ tải ở đầu cực thì trị số dòng điện tìm được I*ck phải hiệu chỉnh thành:
I x x Icktt d
ck*'
"
*(,
)= +−1
1 2
III.2. Phương pháp tính toán: III.2.1. Tính toán theo một biến đổi: Tính toán theo một biến đổi còn gọi là tính toán theo biến đổi chung. Phương pháp
này sử dụng khi khoảng cách giữa các máy phát đến điểm ngắn mạch gần như nhau, lúc đó sự tắt dần của thành phần chu kỳ trong dòng ngắn mạch của các máy phát là gần như nhau, cho nên có thể nhập chung tất cả các máy phát thành một máy phát đẳng trị có công suất tổng để tính toán. Trình tự tính toán như sau:
Lập sơ đồ thay thế trong đơn vị tương đối theo phép qui đổi gần đúng (với các lượng cơ bản Scb, Ucb = Utb):
- điện kháng của máy phát lấy bằng x”d. - không cần đặt bất kỳ sức điện động nào trong sơ đồ. - phụ tải có thể bỏ đi, trừ trường hợp những động cơ cỡ lớn nối trực tiếp vào
điểm ngắn mạch thì tính toán như máy phát có cùng công suất. Biến đổi sơ đồ thay thế, đưa nó về dạng đơn giản nhất để tính điện kháng đẳng trị
x*Σ của sơ đồ đối với điểm ngắn mạch. Tính đổi về điện kháng tính toán:
x x SSttâm
cb* * .= Σ
Σ
trong đó: SđmΣ - tổng công suất định mức của các máy phát. Từ điện kháng tính toán x*tt và thời điểm t cần xét, tra đường cong tính toán (hình
6.6) sẽ tìm được I*ckt. Tính đổi về đơn vị có tên (nếu cần) với lượng cơ bản lúc này là SđmΣ và Utb:
I I I I SUckt ckt âm ckt
âm
tb= =* *. .
.ΣΣ
3
Một số điểm cần lưu ý:
- Khi x*tt > 3 thì dòng chu kỳ không thay đổi và bằng: I*ck = 1/x*tt. - Nếu các máy phát khác loại thì dùng đường cong tính toán của máy phát có
công suất lớn, gần điểm ngắn mạch. - Nếu rΣ < xΣ/3 thì không thể bỏ qua điện trở tác dụng và phải tính toán ZΣ, sau
đó dùng Ztt thay vì xtt.
III.2.2. Tính toán theo nhiều biến đổi: Tính toán theo nhiều biến đổi còn gọi là tính toán theo những biến đổi riêng biệt.
Phương pháp này sử dụng khi trong sơ đồ khoảng cách từ các máy phát đến điểm ngắn mạch khác nhau nhiều, nhất là khi có nguồn công suất vô cùng lớn, lúc đó phải kể đến sự
8
thay đổi dòng điện riêng rẽ của từng máy phát hay từng nhóm máy phát. Trình tự tính toán như sau:
Lập sơ đồ thay thế, tham số của các phần tử được tính toán gần đúng trong hệ đơn vị tương đối (với các lượng cơ bản Scb, Ucb = Utb).
Dựa vào sơ đồ xác định nhóm các máy phát có thể nhập chung, hệ thống công suất vô cùng lớn phải tách riêng ra.
Dùng các phép biến đổi đưa sơ đồ về dạng từng nhánh độc lập nối với điểm ngắn mạch.
Tính toán với từng nhánh riêng rẽ theo phương pháp biến đổi chung. Công suất cơ bản để tính x*tt là tổng công suất các máy phát trên mỗi nhánh.
x x SStti iâm i
cb* * .= Σ
Σ
Tra theo đường cong tính toán tại thời điểm đang xét tìm ra dòng I*ckti trên mỗi nhánh riêng biệt.
Tính dòng tổng trong hệ đơn vị có tên: Ickt = ΣI*ckti.IđmΣi
Nhánh có hệ thống công suất vô cùng tách riêng ra và tính trực tiếp dòng ngắn mạch do nó cung cấp:
I Ix xNH
cb
NH cbNH
NH cb= =
* ( )*
* ( ) hay I 1
trong đó: x*NH(cb) - điện kháng tương hổ giữa hệ thống và điểm ngắn mạch tính trong hệ đơn vị tương đối với các lượng cơ bản Scb, Ucb = Utb.
Thông thường trong tính toán sử dụng 2 đến 3 nhánh biến đổi độc lập.
1
Chương 7:NGẮN MẠCH KHÔNG ĐỐI XỨNG
I. Khái niệm chung: Ngoài ngắn mạch 3 pha đối xứng, trong hệ thống điện còn có thể xảy ra ngắn mạch
không đối xứng bao gồm các dạng ngắn mạch 1 pha, ngắn mạch 2 pha, ngắn mạch 2 pha chạm đất. Khi đó hệ thống véctơ dòng, áp 3 pha không còn đối xứng nữa.
Đối với máy phát, khi trong cuộn dây stato có dòng không đối xứng sẽ xuất hiện từ trường đập mạch, từ đó sinh ra một loạt sóng hài bậc cao cảm ứng giữa rôto và stato: sóng bậc lẽ ở stato sẽ cảm ứng sang rôto sóng bậc chẵn và ngược lại. Biên độ các sóng này phụ thuộc vào sự đối xứng của rôto, rôto càng đối xứng thì biên độ các sóng càng bé. Do đó thực tế đối với máy phát turbine hơi và turbine nước có các cuộn cản dọc trục và ngang trục, các sóng hài bậc cao có biên độ rất nhỏ, có thể bỏ qua và trong tính toán ngắn mạch ta chỉ xét đến sóng tần số cơ bản.
Tính toán ngắn mạch không đối xứng một cách trực tiếp bằng các hệ phương trình vi phân dựa trên những định luật Kirchoff và Ohm rất phức tạp, do đó người ta thường dùng phương pháp thành phần đối xứng. Nội dung của phương pháp này là chuyển một ngắn mạch không đối xứng thành ngắn mạch 3 pha đối xứng giả tưởng rồi dùng các phương pháp đã biết để giải nó.
II. Phương pháp thành phần đối xứng: Phương pháp này dựa trên nguyên tắc Fortesene - Stokvis. Một hệ thống 3 véctơ
không đối xứng bất kỳ (hình 7.1) có thể phân tích thành 3 hệ thống véctơ đối xứng: F F Fa b. . .
, , c
1
2
0
0
0
0
- Hệ thống véctơ thứ tự thuận : F F Fa b c. . .
, ,1 1
- Hệ thống véctơ thứ tự nghịch: F F Fa b c. . .
, ,2 2
- Hệ thống véctơ thứ tự không : F F Fa b c. . .
, ,0 0 Theo điều kiện phân tích ta có:
F F F FF F F FF F F F
a a a a
b b b b
c c c c
. . . .
. . . .
. . . .
= +
= +
= +
1 2
1 2
1 2
+++
2
Hình 7.1
Dùng toán tử pha ta có: a ej o= 120
FFF
a aa a
FFF
a
b
c
a
a
.
.
.
.
.
.
⎡
⎣
⎢⎢⎢⎢
⎤
⎦
⎥⎥⎥⎥
=
⎡
⎣
⎢⎢⎢⎢
⎤
⎦
⎥⎥⎥⎥
⎡
⎣
⎢⎢⎢⎢
⎤
⎦
⎥⎥⎥⎥
1 1 111
2
2
0
1
2
và ngược lại:
FFF
a aa a
FFF
a
a
a
b
c
.
.
.
.
.
.
0
1
2
2
2
13
1 1 111
⎡
⎣
⎢⎢⎢⎢
⎤
⎦
⎥⎥⎥⎥
=
⎡
⎣
⎢⎢⎢⎢
⎤
⎦
⎥⎥⎥⎥
⎡
⎣
⎢⎢⎢⎢
⎤
⎦
⎥⎥⎥⎥
Khi thì hệ thống 3 véctơ là cân bằng. F F F Fa b c. . . .+ + = =3 0 0
Hệ số không cân bằng: b0 = F0/F1 Hệ số không đối xứng: b2 = F2/F1
Hệ thống véctơ thứ tự thuận và thứ thự nghịch là đối xứng và cân bằng, hệ thống véctơ thứ tự không là đối xứng và không cân bằng.
Một vài tính chất của các thành phần đối xứng trong hệ thống điện 3 pha:
Trong mạch 3 pha - 3 dây, hệ thống dòng điện dây là cân bằng. Dòng đi trong đất (hay trong dây trung tính) bằng tổng hình học dòng các pha, do
đó băng 3 lần dòng thứ tự không. Hệ thống điện áp dây không có thành phần thứ tự không. Giữa điện áp dây và điện áp pha của các thành phần thứ tự thuận và thứ thự
nghịch cũng có quan hệ 3 3 1 2: U ; Ud1 d2= =U Uf f3 Có thể lọc được các thành phần thứ tự.
3
III. Các phương trình cơ bản của thành phần đối xứng: Quan hệ giữa các đại lượng dòng, áp, tổng trở của các thành phần đối xứng cũng
tuân theo định luật Ohm:
U j I X
U j I X
U j I X
. .
. ..
. ..
.
.
.
1 1 1
2 2 2
0 0 0
=
=
=
trong đó: X1, X2, X0 - điện kháng thứ tự thuận, nghịch và không của mạch. Khi ngắn mạch không đối xứng ta xem tình trạng mạch như là xếp chồng của các
mạch tương ứng với các thành phần đối xứng tuân theo những phương trình cơ bản sau:
U E jI X
U j I
U j I
N N
N N
N N
. . .
. ..
. ..
.
.
.
1 1 1
2 2 2
0 0 0
0
0
= −
= −
= −
Σ Σ
Σ
Σ
X
X
trong đó: UN1, UN2, UN0, IN1, IN2, IN0 - các thành phần thứ tự của dòng và áp tại điểm ngắn mạch.
Nhiệm vụ tính toán ngắn mạch không đối xứng là tính được các thành phần đối xứng từ các phương trình cơ bản và điều kiện ngắn mạch, từ đó tìm ra các đại lượng toàn phần.
IV. Các tham số thành phần thứ tự của các phần tử: Tham số của các phần tử là đặc trưng cho phản ứng khi có dòng, áp qua chúng. Do
đó tham số thành phần thứ tự của các phần tử là phản ứng khi có hệ thống dòng, áp thứ tự thuận, nghịch và không tác dụng lên chúng.
- Tham số thứ tự thuận của các phần tử là các tham số trong chế độ đối xứng bình thường đã biết.
- Đối với những phần tử có ngẫu hợp từ đứng yên như máy biến áp, đường dây ... thì điện kháng không phụ thuộc vào thứ tự pha, tức là điện kháng thứ tự thuận và thứ tự nghịch giống nhau (X2 = X1). Đối với những phần tử có ngẫu hợp từ quay thì X2 ≠ X1. Điện kháng thứ tự không thì nói chung là X0 ≠ X2, X1, trừ trường hợp mạch không có ngẫu hợp từ thì X0 = X2 = X1.
IV.1. Máy điện đồng bộ: - Điện kháng thứ tự nghịch X2 là phản ứng của máy điện do dòng thứ tự nghịch tạo
từ trường quay ngược với vận tốc 2ω so với rôto. Trị số của X2 tùy thuộc độ đối xứng của máy điện, thường ghi trong lý lịch máy. Trong tính toán gần đúng có thể lấy:
• Máy điện không cuộn cản: X2 = 1,45x’d• Máy điện có cuộn cản: X2 = 1,22x”d
- Điện kháng thứ tự không Xo đặc trưng cho từ thông tản của dòng thứ tự không: Xo = (0,15 ÷ 0,6)x”d
X1 thay đổi trong quá trình ngắn mạch nhưng X2 và Xo nếu không xét đến bảo hòa thì có thể xem là không đổi. Tính toán gần đúng có thể lấy giá trị trung bình trong bảng 7.1.
4
Bảng 7.1:
LOạI MÁY ĐIệN X2 XO
Máy phát turbine hơi < 200MW 0,15 0,05 Máy phát turbine hơi ≥ 200MW 0,22 0,05 Máy phát turbine nước có cuộn cản 0,25 0,07 Máy phát turbine nước không cuộn cản 0,45 0,07 Máy bù và động cơ đồng bộ cỡ lớn 0,24 0,08
IV.2. Phụ tải tổng hợp: Phụ tải tổng hợp chủ yếu là động cơ không đồng bộ nên có thể lấy một động cơ
không đồng bộ đẳng trị thay thế cho toàn bộ phụ tải để tính toán. - Điện kháng thứ tự nghịch X2 ứng với từ thông thứ tự nghịch có độ trượt (2-s), lúc
s=1 (tức động cơ bị hãm) thì X2 bé nhất, đó là trường hợp nguy hiểm nhất được tính toán trong thực tế:
X2 = X2(s=1) = XNtrong đó: XN - điện kháng ngắn mạch của động cơ với X*N = 1/I*mm
Tính toán gần đúng lấy: X2 = X” = 0,35 - Hầu hết các động cơ có trung tính cách điện với đất nên không có dòng thứ tự
không đi qua chúng. Do vậy không cần tìm Xo của các động cơ (tức Xo ≈ ∞).
IV.3. Kháng điện: Kháng điện là phần tử đứng yên, liên lạc về từ yếu nên:
Xo ≈ X1 = X2
IV.4. Máy biến áp: Máy biến áp có X1 = X2, còn Xo phụ thuộc vào tổ nối dây. Tổ nối dây ∆ chỉ có thể
cho dòng thứ thự không chạy quẩn trong cuộn dây mà không ra ngoài lưới điện. Tổ nối dây Y cho dòng thứ thự không đi qua cuộn dây chỉ khi trung tính nối đất.
Nối Yo /∆ :(hình 7.2) xµo >> xII
Xo = xI + xII =X1
Hình 7.2
Nối Yo / Yo :(hình 7.3) Xo tùy thuộc vào chế độ làm việc của điểm trung tính lưới điện.
5
Hình 7.3
Nối Yo / Y :(hình 7.4)
Xo = xI + xµo
Hình 7.4
Đối với máy biến áp 2 cuộn dây gồm 3 máy biến áp 1 pha hoặc đối với máy biến áp
3 pha 4 trụ hay 5 trụ thì xµo = ∞, đối với máy biến áp 3 pha 3 trụ thì xµo = 0,3 ÷ 1. Đối với máy biến áp 3 cuộn dây thường có 1 cuộn dây nối ∆ vì vậy có thể bỏ qua
xµo
Nối Yo /∆ /Y :(hình 7.5) Xo = xI + xII
Hình 7.5
Nối Yo /∆ /Yo :(hình 7.6)
Xo tùy thuộc vào chế độ làm việc của điểm trung tính lưới điện.
Hình 7.6
Nối Yo /∆ /∆ :(hình 7.7) Xo = xI + (xII // xIII)
6
Hình 7.7
IV.5. Đường dây: IV.5.1. Đường dây trên không:
X2 = X1 Xo phụ thuộc đường đi của dòng thứ thự không, nghĩa là phụ thuộc vào sự phân
bố của chúng trong đất, trong dây trung tính, trong những mạch nối đất song song (dây chống sét). Hỗ cảm giữa các pha làm giảm X1, X2 nhưng làm tăng Xo.
- Đối với đường dây đơn 3 pha (1 lộ): Xo > X1- Đối với đường dây kép 3 pha (2 lộ), X’o của một lộ lớn hơn điện kháng thứ
tự không Xo của đường dây đơn 3 pha do có hỗ cảm giữa 2 mạch song song: X’o = Xo + XI-IIo
trong đó: XI-IIo - điện kháng thứ tự không hỗ cảm giữa 2 lộ. Điện kháng tương đương của 1 pha đường dây kép là:
X’’o = X’o/2 = (Xo + XI-IIo)/2 - Anh hưởng của dây chống sét:
Dây chống sét thường được nối đất ở mỗi cột tạo thành những mạch vòng kín cho dòng cảm ứng đi qua khi có dòng thứ tự không trong các pha (đối với dòng thứ tự thuận và dòng thứ tự nghịch không có cảm ứng vì tổng từ thông móc vòng do chúng tạo nên bằng không).
Chính hỗ cảm giữa dây chống sét và các pha làm giảm Xo của đường dây, hỗ cảm này phụ thuộc vào vật liệu, số lượng và sự bố trí của dây chống sét. Trong tính toán gần đúng có thể lấy trị số trung bình trong bảng 7.2.
Bảng 7.2:
TÍNH CHấT ĐƯờNG DÂY Tỷ Số Xo/X1
Đường dây đơn không có dây chống sét 3,5 Đường dây đơn có dây chống sét bằng thép 3 Đường dây đơn có dây chống sét dẫn điện tốt 2 Đường dây kép không có dây chống sét 5,5 Đường dây kép có dây chống sét bằng thép 4,7 Đường dây kép có dây chống sét dẫn điện tốt 3
7
IV.5.1. Đường dây cáp: Võ cáp thường được nối đất ở 2 đầu và nhiều điểm trung gian (hộp nối cáp), do đó
tạo thành đường đi đối với dòng thứ tự không, võ cáp có ảnh hưởng tương tự như dây chống sét của đường dây trên không. Giá trị ro, Xo của dây cáp thay đổi trong phạm vi rộng. Trong tính toán gần đúng, với cáp 3 lõi có thể xem:
ro ≈ 10r1
Xo ≈ (3,5 ÷ 4,6)X1
V. Sơ đồ Các thành phần thứ tự: V.1. Sơ đồ thứ tự thuận và thứ tự nghịch:
Sơ đồ thứ tự thuận là sơ đồ dùng để tính toán ở chế độ đối xứng. Tùy thuộc vào phương pháp và thời điểm tính toán, các máy phát và các phần tử khác được thay thế bằng sức điện động và điện kháng tương ứng.
Sơ đồ thứ tự nghịch và sơ đồ thứ tự thuận có cấu trúc tương tự nhau vì đường đi của dòng thứ tự nghịch và dòng thứ tự thuận là như nhau. Điểm khác biệt của sơ đồ thứ tự nghịch so với sơ đồ thứ tự thuận là:
- các nguồn sức điện động bằng không. - các điện kháng thứ tự nghịch không thay đổi, không phụ thuộc vào dạng ngắn
mạch và thời điểm tính toán. Ta gọi: Điểm đầu của sơ đồ thứ tự thuận và thứ tự nghịch là điểm nối tất cả các trung tính
máy phát và phụ tải, đó là điểm có thế điện bằng không. Điểm cuối của sơ đồ thứ tự thuận và thứ tự nghịch là điểm sự cố. Điện áp giữa điểm cuối và điểm đầu của sơ đồ thứ tự thuận và thứ tự nghịch tương
ứng là điện áp ngắn mạch thứ tự thuận và thứ tự nghịch.
V.2. Sơ đồ thứ tự không: Đường đi của dòng thứ tự không rất khác với dòng thứ tự thuận và thứ tự nghịch.
Sơ đồ thứ tự không phụ thuộc rất nhiều vào cách nối dây của máy biến áp và chế độ nối đất điểm trung tính của hệ thống điện.
Muốn thành lập sơ đồ thứ tự không cần bắt đầu từ điểm ngắn mạch, coi rằng cả 3 pha tại điểm đó nhập chung và có điện áp là UNo. Sơ đồ thứ tự không chỉ bao gồm các phần tử mà dòng thứ tự không có thể đi qua. Tổng trở nối đất các điểm trung tính cần nhân 3, vì sơ đồ thứ tự không được lập cho 1 pha trong khi qua tổng trở nối đất có dòng thứ tự không của cả 3 pha.
VI. Tính toán các dạng ngắn mạch cơ bản: Qui ước: - Coi pha A là pha đặc biệt (ở trong điều kiện khác 2 pha còn lại). - Xét ngắn mạch ngay tại đầu nhánh rẽ của phần tử và chiều dương của dòng điện là
từ các pha đến điểm ngắn mạch. Theo điều kiện phân tích hệ thống véctơ không đối xứng, ta đã có:
8
III
a aa a
III
NA
NB
NC
N
NA
NA
.
.
.
.
.
.
⎡
⎣
⎢⎢⎢⎢
⎤
⎦
⎥⎥⎥⎥
=
⎡
⎣
⎢⎢⎢⎢
⎤
⎦
⎥⎥⎥⎥
⎡
⎣
⎢⎢⎢⎢
⎤
⎦
⎥⎥⎥⎥
1 1 111
2
2
0
1
2
và
III
a aa a
III
N
NA
NA
NA
NB
NC
.
.
.
.
.
.
0
1
2
2
2
13
1 1 111
⎡
⎣
⎢⎢⎢⎢
⎤
⎦
⎥⎥⎥⎥
=
⎡
⎣
⎢⎢⎢⎢
⎤
⎦
⎥⎥⎥⎥
⎡
⎣
⎢⎢⎢⎢
⎤
⎦
⎥⎥⎥⎥
và các phương trình cơ bản:
U E j I X
U j I
U j I
NA A NA
NA NA
N N
. . .
. .
. .
.
.
.
1 1 1
2 2 2
0 0 0
0
0
= −
= −
= −
Σ Σ
Σ
Σ
X
X
(7.1)
(7.2)
(7.3)
VI.1. Ngắn mạch 2 pha: Xét ngắn mạch giữa 2 pha B,
C (hình 7.8). Điều kiện ngắn mạch là:
II IU U
NA
NB NC
NB NC
.
. .
. .
(7.4) (7.5) (7.6)
=
= −
=
0
Thay vào các phương trình thứ tự:
Hình 7.8
UUU
a aa a
UUU
U UN
NA
NA
NA
NB
NB
NA NA
.
.
.
.
.
.
. .0
1
2
2
21 2
13
1 1 111
⎡
⎣
⎢⎢⎢⎢
⎤
⎦
⎥⎥⎥⎥
=
⎡
⎣
⎢⎢⎢⎢
⎤
⎦
⎥⎥⎥⎥
⎡
⎣
⎢⎢⎢⎢
⎤
⎦
⎥⎥⎥⎥
⇒
= (7.7)
III
a aa a
II
I
I I
N
NA
NA
NB
NB
N
NA NA
.
.
.
.
.
.
. .
0
1
2
2
2
0
1 2
13
1 1 111
00
⎡
⎣
⎢⎢⎢⎢
⎤
⎦
⎥⎥⎥⎥
=
⎡
⎣
⎢⎢⎢⎢
⎤
⎦
⎥⎥⎥⎥ −
⎡
⎣
⎢⎢⎢⎢
⎤
⎦
⎥⎥⎥⎥
⇒ =
= −
(7.8)
(7.9)
Giải các phương trình từ (7.1) đến (7.9) ta có:
E j I X j I X j I XA NA NA NA. . . .
.Σ Σ Σ− = − +1 1 2 2 1 20 0. = . Σ Như vậy:
I Ej X X
NAA.
.
( )1
1 2=
+Σ
Σ Σ
9
;
;
I I j IU U j I X UU U U U U
NB NC NA
NA NA NA N
NA NA NB NC NA
. . .
. . . .
. . . . ..
= − = −
= =
= =
30
2
1
1 2 1 2 0
1 1
Σ =
= −
Hình 7.9
VI.2. Ngắn mạch 1 pha: Xét ngắn mạch 1 pha ở pha
A (hình 7.10). Điều kiện ngắn mạch là:
IIU
NB
NC
NA
.
.
.
(7.10) (7.11) (7.12)
=
=
=
000
Thay vào phương trình thứ tự dòng:
Hình 7.10
III
a aa a
II I I I
N
NA
NA
NA
N NA NA NA
.
.
.
.
. . . .0
1
2
2
20 1 2
13
1 1 111
00
13
⎡
⎣
⎢⎢⎢⎢
⎤
⎦
⎥⎥⎥⎥
=
⎡
⎣
⎢⎢⎢⎢
⎤
⎦
⎥⎥⎥⎥
⎡
⎣
⎢⎢⎢⎢
⎤
⎦
⎥⎥⎥⎥
⇒ = = =
(7.13)
Từ phương trình thứ tự áp ta có:
U U U UNA NA NA N. . . .
= + + =1 2 0 0 Và từ các phương trình cơ bản (7.1) ÷ (7.3) ta có:
E j I X X XA NA. .
( )Σ Σ Σ Σ− +1 1 2 0 0+ =
Như vậy: I Ej X X X
NAA.
.
( )1
1 2 0=
+ +Σ
Σ Σ Σ
10
U jX I jX I U jX I IU U U j I X X
N N NA NA NA NA
NA N NA NA
. . . . .
. . . .( ) (
0 0 0 0 1 2 2 2 2 1
1 0 2 1 0 2
= − = − = −
= − + = +Σ Σ Σ Σ
Σ Σ
; = -jX )
.
Dòng tại chỗ ngắn mạch, cũng là dòng đi qua đất IĐ:
I I INA Â NA. . .
= = 3 1 Ap tại chỗ ngắn mạch:
U U a U aU j a a X a X II X aX I X a X
X
NB N NA NA NA
NA NA
. . . . .
. .[( ) ( ) ]
( (= + + = − + −
= − = −
02
1 22
22
0 1
1 2 0 1 20
2
13 3 1
)
Σ Σ
Σ Σ ΣΣ
Σ)
U U aU a U j a a X a X II X a X I X a X
X
NC N NA NA NA
NA NA
. . . . .
. .[( ) ( ) ]
( (= + + = − + −
= − − = − −
0 12
22
2 0 1
1 22
0 1 22 0
2
13 3 1
)
Σ Σ
Σ Σ ΣΣ
Σ)
Hình 7.11
VI.3. Ngắn mạch 2 pha chạm đất: Xét ngắn mạch 2 pha B, C
chạm đất (hình 7.12). Điều kiện ngắn mạch là:
IUU
NA
NB
NC
.
.
.
(7.14) (7.15) (7.16)
=
=
=
000
Thay vào phương trình thứ tự áp:
Hình 7.12
UUU
a aa a
UU U U U
N
NA
NA
NA
N NA NA NA
.
.
.
.
. . . .0
1
2
2
20 1 2
13
1 1 111
00
13
⎡
⎣
⎢⎢⎢⎢
⎤
⎦
⎥⎥⎥⎥
=
⎡
⎣
⎢⎢⎢⎢
⎤
⎦
⎥⎥⎥⎥
⎡
⎣
⎢⎢⎢⎢
⎤
⎦
⎥⎥⎥⎥
⇒ = =
= (7.17)
Từ (7.14) ta có: I I I INA NA NA N. . . .
= + + =1 2 0 0Và từ các phương trình cơ bản (7.1) ÷ (7.3) ta có:
jX I jX INA N2 2 0 0Σ Σ
. .=
11
Như vậy: I I XX X
I I XX X
N NA NA NA. . . .
( ) ( )0 12
0 22 1
0
0 2= −
+= −
+Σ
Σ Σ
Σ
Σ Σ ;
Từ các phương trình cơ bản và (7.17) ta có:
U E j I X U j I X j I XX X
XNA A NA N N NA. . . . . .
( )1 1 1 0 0 0 12
0 20= − = = − =
+Σ Σ Σ
Σ
Σ ΣΣ
Do đó: I E
j X X XX X
NAA.
.
( )1
12 0
2 0
=+
+
Σ
ΣΣ Σ
Σ Σ
Dòng tại chỗ ngắn mạch:
I a X aXX X
I I a X a XX X
INB NA NC NA. . .
( ) ( )= −++
= −++
2 2 0
2 01
22
0
2 01
Σ Σ
Σ Σ
Σ Σ
Σ Σ ;
.
Dòng đi qua đất IĐ là: I I I XX X
 N NA. . .
= = −+
3 30 12
0 2
Σ
Σ Σ
Áp tại điểm ngắn mạch: U U j I X XX X
NA NA NA. . .
= =+
3 31 12 0
0 2
Σ Σ
Σ Σ
Hình 7.13
Bảng 7.3: TÓM TẮT BIỂU THỨC ĐỐI VỚI CÁC DẠNG NGẮN MẠCH
Dạng NM Dòng Áp
N(2) I E
j X XI I I
NAA
NA NA N
..
. . .( )
11 2
2 1 0 0
=+
= − =
Σ
Σ Σ
;
U jX IU U U
NA NA
NA NA N
. .
. . .1 2 1
2 1 0 0=
= =Σ
;
N(1) I E
j X X XI I I
NAA
NA N NA
..
. . .( )
11 2 0
2 0 1
=+ +
= =
Σ
Σ Σ Σ
U j X X IU U U
NA NA
NA NA N
. .
. . .( )1 2 0 1
1 2 0 0= +
+ =Σ Σ
+
12
N(1,1) I E
j X X XX X
I I I
NAA
NA NA N
..
. . .
( )1
12 0
2 0
1 2 0 0
=+
+
+ + =
Σ
ΣΣ Σ
Σ Σ
U j I X XX X
U U U
NA NA
NA N NA
. .
. . .
( )1 12 0
0 2
2 0 1
=+
= =
Σ Σ
Σ Σ
VII. Qui tắc đăng trị thứ tự thuận: Qua bảng 7.3 thấy rằng các thành phần đối xứng của dòng và áp tỷ lệ với dòng thứ
tự thuận ở chỗ ngắn mạch, do vậy nhiệm vụ tính toán một dạng ngắn mạch không đối xứng bất kỳ trước hết là tìm dòng thứ tự thuận ở chỗ ngắn mạch. Để tính toán người ta đưa ra qui tắc đẳng trị thứ tự thuận như sau:
“ Dòng thứ tự thuận của một dạng ngắn mạch không đối xứng bất kỳ được tính như là dòng ngắn mạch 3 pha ở một điểm xa hơn điểm ngắn mạch thực sự một điện kháng phụ X∆
(n). Trị số của X∆(n) không phụ thuộc vào tham số của sơ đồ thứ tự thuận mà chỉ
phụ thuộc vào X2Σ và XoΣ.”
I Ej X X
U jX I
I m I
NAn
An
NAn n
NAn
Nn n
NAn
. ( ) .
( )
. ( ) ( ) . ( )
. ( ) ( ) . ( )
( )
.
.
11
1 1
1
=+
=
=
Σ
Σ ∆
∆
trong đó, m(n), X∆(n) tùy thuộc vào dạng ngắn mạch được tính theo bảng 7.4.
Bảng 7.4:
Dạng NM (n) X∆
(n) m(n)
3 pha (3) 0 1 2 pha (2) X2Σ 3 1 pha (1) X2Σ + XoΣ 3 2 pha - đất (1,1) X X
X X2 0
2 0
Σ Σ
Σ Σ+ 3 1 2 0
2 02−
+X X
X XΣ Σ
Σ Σ( )
Như vậy các phương pháp tính toán, công thức sử dụng cho ngắn mạch 3 pha đối
xứng đều có thể dùng để tính toán thành phần thứ tự thuận của một dạng ngắn mạch không đối xứng bất kỳ.
VIII. Sơ đồ thay thế phức hợp: Sơ đồ thay thế phức hợp là sơ đồ trong đó bao gồm các sơ đồ thứ tự nối với nhau
thỏa mãn điều kiện quan hệ giữa các thành phần dòng điện và điện áp tại điểm ngắn mạch.
Dòng thứ tự tại điểm ngắn mạch hay trong một phần tử nào đó là dòng trong sơ đồ thứ tự tương ứng. Ap thứ tự là hiệu thế giữa điểm đang xét và điểm đầu của sơ đồ thứ tự tương ứng.
13
Ngắn mạch 2 pha:
U U
I I Ej X X
NA NA
NA NAA
. .
. ..
( )
1 2
1 21 2
=
= − =+Σ
Σ Σ
Hình 7.14
Hình 7.15
Ngắn mạch 1 pha:
U U UI I I
Ej X X X
NA NA N
NA NA N
A
. . .
. . .
.
( )
1 2 0
1 2 0
1 2 0
0+ + =
= =
=+ +
Σ
Σ Σ Σ
Hình 7.16
Ngắn mạch 2 pha - đất:
U U UI I I
E
j X X XX X
NA NA N
NA NA N
A
. . .
. . .
.( )
( )
1 2 0
1 2 0
12 0
2 0
= =
= − +
++
= Σ
ΣΣ Σ
Σ Σ
Sơ đồ phức hợp rất thuận tiện khi cần nghiên cứu các thành phần dòng và áp tại một phần tử hoặc một nhánh nào đó, nhất là khi dùng mô hình tính toán, vì nó cho phép đo trực tiếp kết quả ngay trên mô hình.
14
IX. Sử dụng phương pháp đường cong tính toán: Bằng qui tắc đẳng trị thứ tự thuận ta có thể sử dụng đường cong tính toán để tìm
dòng thứ tự thuận của một dạng ngắn mạch bất kỳ và từ đó tính được dòng ngắn mạch.
IX.1. Dùng một biến đổi: Lập các sơ đồ thứ tự thuận, thứ tự nghịch, thứ tự không; tính X1Σ, X2Σ, XoΣ của sơ
đồ đối với điểm ngắn mạch tính toán trong đơn vị tương đối với các lượng cơ bản Scb, Ucb = Utb.
Tính điện kháng phụ X∆(n) tùy theo dạng ngắn mạch và từ đó tìm được điện kháng
tính toán X*tt:
X X X SStt
n âm
cb*
( )( )= +1Σ ∆Σ
trong đó: SđmΣ - tổng công suất định mức của tất cả các máy phát có trong sơ đồ. Tra đường cong tính toán tại thời điểm t cần xét tương ứng với điện kháng tính
toán X*tt để có dòng thứ tự thuận I(n)*N1t.
Tính dòng ngắn mạch toàn phần trong đơn vị có tên: I m I INt
n nN tn
âm( ) ( )
*( ). .= 1 Σ
trong đó: IđmΣ - dòng định mức tổng tương ứng với cấp điện áp cần tính dòng ngắn mạch.
IX.2. Dùng nhiều biến đổi: Lập các sơ đồ thứ tự nghịch, thứ tự không để tính X2Σ, XoΣ của sơ đồ đối với điểm
ngắn mạch trong đơn vị tương đối với các lượng cơ bản Scb, Ucb = Utb. Tính điện kháng phụ X∆
(n) tùy theo dạng ngắn mạch.
Lập sơ đồ thứ tự thuận và đặt thêm điện kháng phụ X∆(n) vào điểm ngắn mạch,
xem như ngắn mạch 3 pha sau điện kháng này. Dùng các phép biến đổi, tách riêng từng nhánh đối với điểm ngắn mạch giả tưởng
để tính điện kháng XΣi của từng nhánh. Tính điện kháng tính toán của từng nhánh:
X X SStti iâm i
cb* = Σ
Σ
trong đó: SđmΣi - tổng công suất định mức của các máy phát ghép chung trong nhánh thứ i.
Tra đường cong tính toán tại thời điểm t cần xét tương ứng với điện kháng tính toán X*tti để có dòng thứ tự thuận I(n)
*N1ti của nhánh thứ i. Tính dòng ngắn mạch toàn phần trong đơn vị có tên:
I m I INtn n
N tin
âm ii
k( ) ( )
*( ) .=
=∑ 1
1Σ
trong đó: k - số nhánh tách riêng của sơ đồ thay thế. IđmΣi - dòng định mức tổng của nhánh thứ i tương ứng với cấp điện áp cần tính
dòng ngắn mạch.
15
MỘT SỐ ĐIỂM LƯU Ý: - Nếu có hệ thống công suất vô cùng lớn thì phải tách nó thành một nhánh riêng,
sau khi thêm X∆(n) dùng các phép biến đổi để tính điện kháng tương hổ giữa hệ thống và
điểm ngắn mạch X*HN và tính riêng dòng do hệ thống cung cấp:
I IX
I m I
N Hn cb
HN
NHn n
N Hn
1
1
( )
*( ) ( ) ( )
=
=
- Vì phương pháp đường cong tính toán sử dụng cách tính gần đúng nên có thể xem X2Σ ≈ X1Σ mà không cần lập sơ đồ thứ tự nghịch.
- Do cách điểm ngắn mạch giả tưởng thêm một điện kháng phụ X∆(n) nên sự khác
biệt giữa các nguồn ít hơn. Vì vậy thường dùng 1 hoặc 2 biến đổi chung là đảm bảo đủ độ chính xác yêu cầu, chỉ tách riêng những nhánh cần thiết.
X. Sự biến đổi của dòng và áp qua máy biến áp: Qua máy biến áp, dòng và áp thay đổi cả về trị số lẫn góc pha. Thường tổ nối dây
của máy biến áp được gọi theo chỉ số của kim đồng hồ:
( , ) .. .U U Na A
o= =γ 30 trong đó: N - chỉ số của kim đồng hồ.
Như vậy có thể sử dụng hệ số biến đổi phức:
k U
Uk e k eA
a
j j o..
... .1
30= = =γ N
với k UU
UU
A
a
âmI
âmII= = là tỷ số biến áp không tải.
k1 chính là hệ số biến đổi của điện áp thứ tự thuận vì nó được xác định trong chế độ bình thường, đối xứng.
k U
UU
kU
kU eA
a
a A Aj No.
.
.
.
.
. . ..11
1
1
1
1 1301 1
= ⇒ − = =
Từ đó ta có biểu thức biến đổi dòng thứ tự thuận dựa vào quan hệ:
=
hay: = = k.
U I U I I U
UI k I
I k I I e
A A a a aA
a
A A
a A Aj No
. . . . ..
.
. . .
. . . . .. .
1 1 1 1 11
1
1 1
1 1 1 130
1
∧=
∧⇒
∧=
∧ ∧
∧−
Dòng và áp thứ tự thuận biến đổi qua máy biến áp với cùng một góc pha như nhau (hình 7.17).
16
Hình 7.17
Hình 7.18
Tương tự, dòng và áp thứ tự nghịch biến đổi qua máy biến áp cũng với cùng một góc pha (hình 7.18) của hệ số biến đổi phức k2 liên hiệp với k1.
= = k.
k k k e
Uk
Uk
U e
I k I I e
j N
a A Aj N
a A Aj N
o
o
o
. . .
.
.
. . .
. . . . .
.
.
. .
2 130
2
2
2 230
2 2 2 230
1 1=∧=
= =
∧
−
Dòng và áp thứ tự không biến đổi qua máy biến áp (nếu có thể được) hoặc cùng pha hoặc lệch pha nhau 180o.
Xét một số trường hợp sau: - Trường hợp máy biến áp nối Y/Y-12 hay∆ /∆-12 (tức N=12), các véctơ dòng
và áp ở 2 phía trùng pha nhau, nghĩa là hệ thống véctơ xem như không lệch pha khi biến đổi qua máy biến áp.
Khi N=6, hệ thống véctơ ở 2 phía của máy biến áp sẽ lệch nhau 180o. Đối với máy biến áp nối Yo/Yo cần tính đến sự biến đổi của thành phần dòng và áp
thứ tự không. - Trường hợp thông dụng nhất máy biến áp nối Y/∆-11, khi biến đổi từ phía Y
qua phía ∆ thì hệ thống véctơ thứ tự thuận sẽ quay một góc 30o ngược chiều kim đồng hồ. Một số lưu ý:
- Dòng trong cuộn dây nối ∆ của máy biến áp có thể có thành phần thứ tự không, nhưng dòng dây và áp dây không có thành phần này.
- Trong hệ đơn vị tương đối thì tỷ số biến áp k = 1, do đó hệ thống véctơ ở 2 phía của máy biến áp có độ lớn bằng nhau, chỉ khác nhau về góc pha.
PDF Merger