the wall-mount step capacity “quiet climate” heat pumps ... · form no. s3447-516...

16
Form No. S3447-516 Supersedes S3447-715 Page 1 of 16 Copper Tube / Aluminum Fin Coils: Grooved copper tubing and enhanced aluminum fins provide maximum heat transfer and high energy efficiency. Evaporator coil constructed with hydrophilic fin stock that seals fin surface against aluminum oxide formation, is resistant to mold and mildew growth (tested to ASTM D3273, no growth) and reduces beading of condensate on the fin surface. Optional phenolic-coated coils are also available. Twin Blowers: Move air quietly. All models feature variable speed blower motors providing airflow adjustment for high and low static operation. Motor overload protection is standard on all models. ECM Indoor Blower Motor: Features a variable speed motor providing super-high efficiency, low sound levels and soft-start capabilities. The motor is self- adjusting to provide the proper airflow rate for the staged capacity, and for higher static pressure in ducted installations without user adjustment or wiring changes. Heat Pump Compressor: Scroll 2-Stage Compressors are standard on all 2½ to 5 ton models. Eliminates need for crankcase heater. Double isolated floating compressor mounting system, compressor sound blanket, and discharge muffler for reduced outdoor sound level. Phase Rotation Monitor: Standard on all 3 phase scroll compressors. Protects against reverse rotation if power supply is not properly connected. R-410A Refrigerant: Designed with R-410A (HFC) non-ozone depleting refrigerant in compliance with the Montreal protocol and 2010 EPA requirements. Liquid Line Filter Drier: Standard on all units. Protects system against moisture. Galvanized 20 Gauge Zinc Coated Steel Cabinet: Cleaned, rinsed, sealed and dried before the polyurethane primer is applied. The cabinet is handsomely finished with a baked on, beige textured enamel, which allows it to withstand 1000 hours of salt spray tests per ASTM B117-03. Stainless Steel cabinets available. Foil Faced Insulation: Standard on all units. Electrical Components: Are easily accessible for routine inspection and maintenance through a right side, service panel opening. Features a lockable, hinged access cover to the circuit breaker or rotary disconnect switch. Electric Heat Strips: Features an automatic limit and thermal cut-off safety control. Heater packages are factory or field installed for all 2 through 5 ton models. Features easy slide-in field assembly with various BTUH outputs. Condenser Fan and Motor Shroud Assembly: Slide out for easy access. Filter Service Door: Separate service door provides easy access for filter change. One Inch, Disposable Air Filters: Are standard equipment. Optional one inch washable filters available and filter racks permit the addition of 2" pleated filter. Factory or field installed. Solid State Electronic Heat Pump Control: Provides efficient 30, 60 or 90 minute defrost cycle. A thermistor sensor, speed up terminal for service and 10 minute defrost override are standard on the electronic heat pump control. High & Low Pressure Switches are Auto-Reset: Standard on all units. Built-in lockout circuit resets from the room thermostat. Provides commercial quality protection to the compressor. Five Minute Compressor Time Delay: Short cycle protection is standard. Built into the heat pump control. Emergency Heat Circuit: Permits continuous operation of the system. Barometric Fresh Air Damper: Standard on all units. Allows up to 25% outside fresh air. Not installed if other optional vent packages selected. The Bard Wall-Mount Heat Pump is a self-contained energy efficient heating and cooling system, which is designed to offer maximum indoor comfort at a minimal cost without using valuable indoor floor space or outside ground space. This unit is the ideal product for versatile applications such as: new construction, modular offices, school modernization, telecommunication structures, portable structures or correctional facilities. Factory or field installed accessories are available to meet specific job requirements. Six ventilation options are available. See Page 3 for details on these options. Built-in Circuit Breakers: Standard on all electric heat versions of single and three phase (230/208 volt) equipment. Rotary disconnects are standard on all electric heat versions of three phase (460 volt) equipment. Slope Top: Standard feature for water run-off. Full Length Mounting Brackets: Built into cabinet for improved appearance and easy installation. NOTE: Bottom mounting bracket included to assist in installation. Top Rain Flashing: Standard feature on all models. Ventilation System Packages THE WALL-MOUNT STEP CAPACITY “QUIET CLIMATE” HEAT PUMPS Integrated Part Load Value (IPLV) Efficiency Up To 15.0 BTU/WATT Complies with efficiency requirements of ANSI/ASHRAE/IESNA 90.1-2013. Certified to ANSI/ARI Standard 390-2003 for SPVU (Single Package Vertical Units). Intertek ETL Listed to Standard for Safety Heating and Cooling Equipment ANSI/UL 1995/CSA 22.2 No. 236-05, Fourth Edition. Commercial Product - Not intended for Residential application. Engineered Features Models: T30S to T60S Up to 11.0 EER Heating Capacities: 19,000 to 52,000 BTUH Cooling Capacities: 22,400 to 56,000 BTUH GREEN REFRIGERANT R-410A

Upload: hahanh

Post on 20-Jul-2018

216 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: THE WALL-MOUNT STEP CAPACITY “QUIET CLIMATE” HEAT PUMPS ... · Form No. S3447-516 SupersedesS3447-715 Page 1 of 16 Copper Tube / Aluminum Fin Coils: Grooved copper tubing and

Form No. S3447-516Supersedes S3447-715Page 1 of 16

Copper Tube / Aluminum Fin Coils: Grooved copper tubing and enhanced aluminum fins provide maximum heat transfer and high energy efficiency. Evaporator coil constructed with hydrophilic fin stock that seals fin surface against aluminum oxide formation, is resistant to mold and mildew growth (tested to ASTM D3273, no growth) and reduces beading of condensate on the fin surface. Optional phenolic-coated coils are also available.

Twin Blowers: Move air quietly. All models feature variable speed blower motors providing airflow adjustment for high and low static operation. Motor overload protection is standard on all models.

ECM Indoor Blower Motor: Features a variable speed motor providing super-high efficiency, low sound levels and soft-start capabilities. The motor is self-adjusting to provide the proper airflow rate for the staged capacity, and for higher static pressure in ducted installations without user adjustment or wiring changes.

Heat Pump Compressor: Scroll 2-Stage Compressors are standard on all 2½ to 5 ton models. Eliminates need for crankcase heater.Double isolated floating compressor mounting system, compressor sound blanket, and discharge muffler for reduced outdoor sound level.

Phase Rotation Monitor: Standard on all 3 phase scroll compressors. Protects against reverse rotation if power supply is not properly connected.

R-410A Refrigerant: Designed with R-410A (HFC) non-ozone depleting refrigerant in compliance with the Montreal protocol and 2010 EPA requirements.

Liquid Line Filter Drier: Standard on all units. Protects system against moisture.

Galvanized 20 Gauge Zinc Coated Steel Cabinet: Cleaned, rinsed, sealed and dried before the polyurethane primer is applied. The cabinet is handsomely finished with a baked on, beige textured enamel, which allows it to withstand 1000 hours of salt spray tests per ASTM B117-03.Stainless Steel cabinets available.

Foil Faced Insulation: Standard on all units.

Electrical Components: Are easily accessible for routine inspection and maintenance through a right side, service panel opening. Features a lockable, hinged access cover to the circuit breaker or rotary disconnect switch.

Electric Heat Strips: Features an automatic limit and thermal cut-off safety control. Heater packages are factory or field installed for all 2 through 5 ton models. Features easy slide-in field assembly with various BTUH outputs.

Condenser Fan and Motor Shroud Assembly: Slide out for easy access.

Filter Service Door: Separate service door provides easy access for filter change.

One Inch, Disposable Air Filters: Are standard equipment. Optional one inch washable filters available and filter racks permit the addition of 2" pleated filter. Factory or field installed.

Solid State Electronic Heat Pump Control: Provides efficient 30, 60 or 90 minute defrost cycle. A thermistor sensor, speed up terminal for service and 10 minute defrost override are standard on the electronic heat pump control.

High & Low Pressure Switches are Auto-Reset: Standard on all units. Built-in lockout circuit resets from the room thermostat. Provides commercial quality protection to the compressor.

Five Minute Compressor Time Delay: Short cycle protection is standard. Built into the heat pump control.

Emergency Heat Circuit: Permits continuous operation of the system.

Barometric Fresh Air Damper: Standard on all units. Allows up to 25% outside fresh air. Not installed if other optional vent packages selected.

The Bard Wall-Mount Heat Pump is a self-contained energy efficient heating and cooling system, which is designed to offer maximum indoor comfort at a minimal cost without using valuable indoor floor space or outside ground space. This unit is the ideal product for versatile applications such as: new construction, modular offices, school modernization, telecommunication structures, portable structures or correctional facilities. Factory or field installed accessories are available to meet specific job requirements.

Six ventilation options are available.See Page 3 for details on these options.

Built-in Circuit Breakers: Standard on all electric heat versions of single and three phase (230/208 volt) equipment. Rotary disconnects are standard on all electric heat versions of three phase (460 volt) equipment.

Slope Top: Standard feature for water run-off.

Full Length Mounting Brackets: Built into cabinet for improved appearance and easy installation. NOTE: Bottom mounting bracket included to assist in installation.

Top Rain Flashing: Standard feature on all models.

Ventilation System Packages

THE WALL-MOUNT™ STEP CAPACITY “QUIET CLIMATE” HEAT PUMPSIntegrated Part Load Value (IPLV) Efficiency Up To 15.0 BTU/WATT

• Complies with efficiency requirements of ANSI/ASHRAE/IESNA 90.1-2013.• Certified to ANSI/ARI Standard 390-2003 for SPVU (Single Package Vertical Units).• Intertek ETL Listed to Standard for Safety Heating and Cooling Equipment ANSI/UL 1995/CSA 22.2 No. 236-05, Fourth Edition.• Commercial Product - Not intended for Residential application.

Engineered Features

Models: T30S to T60S Up to 11.0 EERHeating Capacities: 19,000 to 52,000 BTUH Cooling Capacities: 22,400 to 56,000 BTUH

Green refriGerant

r-410a

Page 2: THE WALL-MOUNT STEP CAPACITY “QUIET CLIMATE” HEAT PUMPS ... · Form No. S3447-516 SupersedesS3447-715 Page 1 of 16 Copper Tube / Aluminum Fin Coils: Grooved copper tubing and

Form No. S3447-516Supersedes S3447-715Page 2 of 16

MODELS T30S1-A T30S1-B T30S1-C T36S1-A T36S1-B T36S1-CElectrical Rating – 60 Hz 230/208 - 1 230/208 - 3 460 - 3 230/208 - 1 230/208 - 3 460 - 3

Operating Voltage Range 197-253 197-253 414-506 197-253 197-253 414-506Compressor--Circuit A

Voltage 230/208 230/208 460 230/208 230/208 460Rated Load Amps 9.6 / 10.8 7.1 / 8.0 4.0 11.5 / 12.9 8.8 / 9.8 4.9Branch Circuit Selection Current 13.1 8.7 4.3 15.3 11.7 5.8Lock Rotor Amps 73 / 73 58 / 58 28 83 / 83 73 / 73 38Compressor Type Scroll Scroll Scroll Scroll Scroll Scroll

Fan Motor & CondenserFan Motor--HP--RPM--SPD 1/5 - 1050 - 1 1/5 - 1050 - 1 1/5 - 1050 - 1 1/3 - 825 - 2 1/3 - 825 - 2 1/3 - 825 - 2Fan Motor--Amps 1.5 1.5 .8 2.5 2.5 1.1Fan--DIA/CFM 20"-1900 20"-1900 20"-1900 24"-2900 24"-2900 24"-2900

Blower Motor & Evap.Blower Motor--HP-RPM-SPD 1/3 Var. 1/3 Var. 1/3 Var. 1/2 Var. 1/2 Var. 1/2 Var.Blower Motor--Amps 2.8 2.8 2.8 3.2 3.2 3.2CFM Cooling & E.S.P. w/Filter (Rated-Wet Coil)

900 - .10 900 - .10 900 - .10 1100 - .15 1100 - .15 1100 - .15

Filter Sizes (inches) STD. 16 x 30 x 1 16 x 30 x 1 16 x 30 x 1 20 x 30 x 1 20 x 30 x 1 20 x 30 x 1Basic Unit Weight --LBS. 400 400 400 490 490 530 Barometric Fresh Air Damper 4 4 4 4.5 4.5 4.5 Blank-Off Plate 1 1 1 1 1 1 Motorized Fresh Air Damper 11 11 11 11.5 11.5 11.5 Commercial Room Ventilator 35 35 35 42 42 42 Economizer 64 64 64 50 50 50 Energy Recovery Ventilator 52 52 52 81 81 81

MODELS T30S1 T36S1 T42S1 T48S1 T60S1Cooling BTUH, Stage 1 (Partial Capacity) 80/67-80EER @ Part Load (80/67-80) Stage 1 CoolingOperating CFM

22,40014.0650

27,00015.0800

31,00014.9900

37,00015.61000

45,00015.21300

High Temp. Heating 47°BTUH, Stage 1 (Partial Capacity)Operating CFM

19,000650

22,600800

26,000900

30,8001000

38,0001300

MODELS T42S1-A T42S1-B T42S1-C T48S1-A T48S1-B T48S1-C T60S1-A T60S1-B T60S1-CElectrical Rating – 60 Hz 230/208 - 1 230/208 - 3 460 - 3 230/208 - 1 230/208 - 3 460 - 3 230/208 - 1 230/208 - 3 460 - 3

Operating Voltage Range 197-253 197-253 414-506 197-253 197-253 414-506 197-253 197-253 414-506Compressor--Circuit A

Voltage 230/208 230/208 460 230/208 230/208 460 230/208 230/208 460Rated Load Amps 14.1 / 16 11.2 / 12.7 5.6 16.8 / 19.2 11.1 / 12.7 5.8 21.4 / 23.3 13.1 / 14.2 6.2Branch Circuit Selection

Current18.0 14.2 6.3 21.2 14.1 6.5 27.2 16.6 7.3

Lock Rotor Amps 96 / 96 88 / 88 44 104 83 / 83 41 153 / 153 110 / 110 52Compressor Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll

Fan Motor & CondenserFan Motor--HP--RPM--SPD 1/3-825-2 1/3-825-2 1/3-825-1 1/3-825-2 1/3-825-2 1/3-825-1 1/2-1025-1 1/2-1025-1 1/2-1025-1Fan Motor--Amps 2.5 2.5 1.2 2.5 2.5 1.2 3.8 3.8 3.8Fan--DIA/CFM 24"-2900 24"-2900 24"-2900 24"-2900 24"-2900 24"-2900 24"-3700 24"-3700 24"-3700

Blower Motor & Evap.Blower Motor--HP-RPM-SPD 3/4 Var. 3/4 Var. 3/4 Var. 3/4 Var. 3/4 Var. 3/4 Var. 3/4 Var. 3/4 Var. 3/4 Var.Blower Motor--Amps 4.0 4.0 4.0 4.9 4.9 4.9 4.9 4.9 4.9CFM Cooling & E.S.P. w/Filter (Rated-Wet Coil)

1250 - .15 1250 - .15 1250 - .15 1550 - .2 1550 - .2 1550 - .2 1650 - .2 1650 - .2 1650 - .2

Filter Sizes (inches) STD. 20 x 30 x 1 20 x 30 x 1 20 x 30 x 1 20 x 30 x 1 20 x 30 x 1 20 x 30 x 1 20 x 30 x 1 20 x 30 x 1 20 x 30 x 1Shipping Weight --LBS. 500 500 540 560 560 605 565 565 610 Barometric Fresh Air Damper 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 Blank-Off Plate 1 1 1 1 1 1 1 1 1 Motorized Fresh Air Damper 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 Commercial Room Ventilator 42 42 42 42 42 42 42 42 42 Economizer 50 50 50 50 50 50 50 50 50 Energy Recovery Ventilator 81 81 81 81 81 81 81 81 81

MODELS T30S1 T36S1 T42S1 T48S1 T60S1Cooling BTUH, Stage 2 (Full Capacity) j 80/67-95EER jRated CFM

28,00010.8900

33,80011.01100

39,50011.01250

46,50011.01550

56,00010.71650

IPLV (Integrated Stage 1 and Stage 2) jl 80/67-80 13.7 14.7 14.6 15.0 14.9High Temp Heating (47F) BTUH, Stage 2 (Full Capacity)COP jmRated CFM

27,8003.30900

33,0003.401100

39,0003.301250

43,0003.501550

52,0003.301650

Low Temp Heating (17F) BTUH, Stage 2 (Full Capacity)COP mRated CFM

16,6002.20900

20,0002.401100

23,0002.201250

27,0002.301550

34,6002.401650

j Certified in accordance with ARI Standard 390-2003 for single package vertical units EER = Energy Efficiency Ratio - BTU/WATT efficiencyl Integrated Part Load Value - BTU/WATT efficiency (combines Stage 1 & 2 performance)m COP = Coefficient of Performance - BTU/WATT efficiency

Capacity and Efficiency Ratings at Partial Capacity

Specifications 2-1/2 through 3-Ton

Specifications 3-1/2 through 5 Ton

Certified Capacity and Efficiency Ratings at Full Capacity

Page 3: THE WALL-MOUNT STEP CAPACITY “QUIET CLIMATE” HEAT PUMPS ... · Form No. S3447-516 SupersedesS3447-715 Page 1 of 16 Copper Tube / Aluminum Fin Coils: Grooved copper tubing and

Form No. S3447-516Supersedes S3447-715Page 3 of 16

Bard Wall-Mounts are designed to provide optional ventilation packages to meet all of your ventilation and indoor air quality requirements. All units are equipped with a barometric fresh air damper as the standard ventilation package. All ventilation packages can be built-in at the factory, or field-installed at a later date.

BAROMETRIC FRESH AIR DAMPER - BFAD STANDARD The barometric fresh air damper is a standard feature on all models. It is installed on the inside of the service door and allows outside ventilation air, up to 25% of the total airflow rating of the unit, to be introduced through the air inlet openings and to be mixed with the conditioned air. The damper opens during blower operation and closes when the blower is off. Adjustable blade stops allow different amounts of outside air to be introduced into the building and can be easily locked closed if required.

BLANK OFF PLATE - BOP OPTIONAL A blank off plate is installed on the inside of the service door. It covers the air inlet openings which restricts any outside air from entering into the unit. The blank off plate should be utilized in applications where outside air is not required to be mixed with the conditioned air.

MOTORIZED FRESH AIR DAMPER - MFAD OPTIONAL The motorized fresh air damper is internally mounted behind the service door and allows outside ventilation air, up to 25% of the total airflow rating of the unit, to be introduced through the air inlet openings and to be mixed with the conditioned air. The two position damper can be fully open or closed. The damper blade is powered open by a 24VAC motor with spring return on power loss. The damper can be controlled by indoor blower operation or can be field connected to be managed based on building occupancy.

COMMERCIAL ROOM VENTILATOR - CRV OPTIONALThe built-in commercial room ventilator is internally mounted behind the service door and allows outside ventilation air, up to 50% of the total airflow rating of the unit, to be introduced through the air inlet openings. It includes a built-in exhaust air damper. The commercial room ventilator (CRV) is a simple and innovative approach to improving the indoor air quality by providing fresh air intake and exhaust capability through the CRV. The damper can be easily adjusted to control the amount of fresh air supplied into the building. The CRV can be controlled by indoor blower operation or field controlled based on room occupancy. The CRV is power open - spring return on power loss. Complies with ANSI/ASHRAE Standard 62.1 “Ventilation for Acceptable Indoor Air Quality.”

Four Models Available: CRVS - spring return on power loss or deactivation CRVP - power return (will not close on power loss) CHCRV - modulating actuator with spring return on power loss or deactivation CRVMWH - modulating spring return on power loss or deactivation

ECONOMIZER - ECONWM-Series OPTIONAL The built-in economizer system is internally mounted behind the service door and allows outdoor air to be introduced through the air inlet openings. The amount of outdoor air varies in response to the system controls and settings defined by the end user. It includes a built-in exhaust air damper. The economizer is designed to provide “free cooling” when outside air conditions are cool and dry enough to satisfy cooling requirements without running the compressor. This in turn provides lower operating costs, while extending the life of the compressor.

• ECONWMT Equipment Building versions have extended 11" air intake hood to deliver up to 100% of cooling rated airflow.• ECONWMS Standard versions have 3" air intake hood to deliver up to 75% of cooling rated airflow.

Standard Features:• Fully modulating• Honeywell Direct Drive Hi-Torque Actuator• No linkage required• Simple single blade design• Positive shut-off with non-stick gaskets• Electronic DB and/or Enthalpy sensors depending upon version• Honeywell JADE™ electronic economizer module with precision settings and diagnostics• DB or Enthalpy economizer versions available WALL-MOUNT ENERGY RECOVERY VENTILATOR - ERV OPTIONAL The wall-mount energy recovery ventilator (ERV) is a highly innovative approach to meeting indoor air quality ventilation requirements as established by ANSI/ASHRAE Standard 62.1. The ERV allows from 200 to 450 CFM (depending upon model) of fresh air and exhaust through the unit while maintaining superior indoor comfort and humidity levels. In most cases this can be accomplished without increasing equipment sizing or operating costs. Heat transfer efficiency is up to 67% during summer and 75% during winter conditions. The ERV consists of a unique “rotary energy recovery cassette” that provides effective sensible and latent heat transfer capabilities during summer and winter conditions. Various control schemes are addressed including limiting ventilation during building occupancy only. The ERV is designed to be internally mounted behind the service door in the WA, WH or WL model wall-mount units. It can be built-in at the factory or field installed as an option. ERV-*3 and ERV-*5 can be independently adjusted for intake and exhaust rates. 3" air intake hood is standard.

NOTE: The above vent systems are intake only without built-in exhaust capability. Building will likely require separate field installed barometric relief or mechanical exhaust elsewhere within the conditioned space. Balancing dampers in the return air grille may be required to achieve specified amount of outdoor air intake.

Ventilation System Packages

Barometric Fresh Air Damper

Motorized Fresh Air Damper

Commercial Room Ventilator

Economizer

Energy Recovery Ventilator

Page 4: THE WALL-MOUNT STEP CAPACITY “QUIET CLIMATE” HEAT PUMPS ... · Form No. S3447-516 SupersedesS3447-715 Page 1 of 16 Copper Tube / Aluminum Fin Coils: Grooved copper tubing and

Form No. S3447-516Supersedes S3447-715Page 4 of 16

Commercial Room Ventilator Performance Data : CRVS-3, CRVP-3 & CRVMWH

0

100

200

300

400

500

600

700

800

900

1000

1100

1200

1300

A B C D E F

Airf

low

(cfm

)

Vent Position

T30*1 High Speed Total and Ventilation Airflow

Total Air 0 ESP

Total Air .2 ESP

Total Air .4 ESP

Vent Air 0 ESP

Vent Air .2 ESP

Vent Air .4 ESP

0

100

200

300

400

500

600

700

800

900

0 A B C D E F

Airf

low

(cfm

)

Vent Position

T24H High Speed Total and Ventilation AirflowT30* Low Speed Total And Ventilation Airflow

Total Air 0 ESP

Total Air .2 ESP

Total Air .4 ESP

Vent Air 0 ESP

Vent Air .2 ESP

Vent Air .4 ESP

Airfl

ow (c

fm)

T30*1 High Speed Total and Ventilation Airflow

T24* High Speed Total and Ventilation AirflowT30* Low Speed Total And Ventilation Airflow

Airfl

ow (c

fm)

Page 5: THE WALL-MOUNT STEP CAPACITY “QUIET CLIMATE” HEAT PUMPS ... · Form No. S3447-516 SupersedesS3447-715 Page 1 of 16 Copper Tube / Aluminum Fin Coils: Grooved copper tubing and

Form No. S3447-516Supersedes S3447-715Page 5 of 16

Commercial Room Ventilator Performance Data : CRVS-5, CRVP-5 & CHCRV-5

0200400600800

10001200

A B C D E F

Airf

low

(CFM

)

Blade Position

T36S1 with CRVS-5,CRVP-5 & CHCRV-5

Vent Air, Cooling/Heating Mode Total Air, Cooling/Heating Mode

0

200

400

600

800

1000

1200

1400

A B C D E F

Airf

low

(CFM

)

Blade Position

T42S1 with CRVS-5,CRVP-5 & CHCRV-5

Vent Air, Cooling/Heating Mode Total Air, Cooling/Heating Mode

Page 6: THE WALL-MOUNT STEP CAPACITY “QUIET CLIMATE” HEAT PUMPS ... · Form No. S3447-516 SupersedesS3447-715 Page 1 of 16 Copper Tube / Aluminum Fin Coils: Grooved copper tubing and

Form No. S3447-516Supersedes S3447-715Page 6 of 16

Commercial Room Ventilator Performance Data : CRVS-5, CRVP-5 & CHCRV-5

Commercial Room Ventilator Performance Data : CRVS-5, CRVP-5 & CHCRV-5

0

100

200

300

400

500

600

0 2 4 6 8 10 12 14 16 18

Air f

low

(CFM

)

Vent Position

T48S1 Vent Airflow

Blower Only Vent Airflow 0.2 ESP

High Speed Comp Vent Airflow 0.2 ESP

A B C D E F

0

100

200

300

400

500

600

700

0 2 4 6 8 10 12 14 16 18

Air f

low

(CFM

Vent Position

T60S1 Vent Airflow

High Speed Comp Vent Airflow 0.2 ESP

Blower Only Vent Airflow 0.2 ESP

A B C D E F

Page 7: THE WALL-MOUNT STEP CAPACITY “QUIET CLIMATE” HEAT PUMPS ... · Form No. S3447-516 SupersedesS3447-715 Page 1 of 16 Copper Tube / Aluminum Fin Coils: Grooved copper tubing and

Form No. S3447-516Supersedes S3447-715Page 7 of 16

This Page Intentionally Left Blank

Page 8: THE WALL-MOUNT STEP CAPACITY “QUIET CLIMATE” HEAT PUMPS ... · Form No. S3447-516 SupersedesS3447-715 Page 1 of 16 Copper Tube / Aluminum Fin Coils: Grooved copper tubing and

Form No. S3447-516Supersedes S3447-715Page 8 of 16

Performance and Application Data - ERVF-*3 (T30S1)

LEGEND:

VLT = Ventilation Load - TotalVLS = Ventilation Load - SensibleVLL = Ventilation Load - LatentHRT = Heat Recovery - TotalHRS = Heat Recovery - SensibleHRL = Heat Recovery - LatentWVL = Ventilation Load - LatentWHR = Heat Recovery - Total

ERVF-*3 WINTER HEATING PERFORMANCE(INDOOR DESIGN CONDITIONS 70°F DB)

AmbientO.D.

VENTILATION RATE

400 CFM75% EFF.

325 CFM76% EFF.

250 CFM77% EFF.

DB/°F WVL WHR WVL WHR WVL WHR

65 2160 1620 1755 1333 1350 1039

60 4320 3240 3510 2667 2700 2079

55 6480 4860 5265 4001 4050 3118

50 8640 6480 7020 5335 5400 4158

45 10800 8100 8775 6669 6750 5197

40 12960 9720 10530 8002 8100 6237

35 15120 11340 12285 9336 9450 7276

30 17280 12960 14040 10670 10800 8316

25 19440 14580 15795 12004 12150 9355

20 21600 16200 17550 13338 13500 10395

15 23760 17820 19305 14671 14850 11434

SUMMER COOLING PERFORMANCE(INDOOR DESIGN CONDITIONS 75°DB/62°WB)

AmbientO.D.

VENTILATION RATE -- 400 CFM63% EFFICIENCY

VENTILATION RATE -- 325 CFM64% EFFICIENCY

VENTILATION RATE -- 250 CFM65% EFFICIENCY

DB/WB F VLT VLS VLL HRT HRS HRL VLT VLS VLL HRT HRS HRL VLT VLS VLL HRT HRS HRL

105757065

190801296012960

129601296012960

612000

1202081648164

816481648164

385500

155021053010530

105301053010530

497200

992167396739

673967396739

318200

1192581008100

810081008100

382500

775152655265

526552655265

248600

100

8075706560

2808019080109801080010800

1080010800108001080010800

172808280180

00

1769012020671768046804

68046804680468046804

108865216113

00

2281515502892187758775

87758775877587758775

140406727146

00

146019921570956165616

56165616561656165616

89854305

9300

1755011925686267506750

67506750675067506750

108005175112

00

114077751446043874387

43874387438743874387

70193363

7300

95

8075706560

28080190801098086408640

86408640864086408640

19440104402340

00

1769012020691754435443

54435443544354435443

1224765771474

00

2281515502892170207020

70207020702070207020

1579584821901

00

146019921570944924492

44924492449244924492

1010854281216

00

1755011925686254005400

54005400540054005400

1215065251462

00

114077751446035103510

35103510351035103510

78974241950

00

90

8075706560

28080190801098064806480

64806480648064806480

21600126004500

00

1769012020691740824082

40824082408240824082

1360879382835

00

2281515502892152655265

52655265526552655265

17550102373656

00

146019921570933693369

33693369336933693369

1123265522340

00

1755011925686240504050

40504050405040504050

1350078752812

00

114077751446026322632

26322632263226322632

877451181828

00

85

8075706560

28080190801098043204320

43204320432043204320

23760147606660

00

1769012020691727212721

27212721272127212721

1496892984195

00

2281515502892135103510

35103510351035103510

19305119925411

00

146019921570922462246

22462246224622462246

1235576753463

00

1755011925686227002700

27002700270027002700

1485092254162

00

114077751446017551755

17551755175517551755

965259962705

00

80

75706560

190801098037802160

2160216021602160

1692088201620

0

12020691723811360

1360136013601360

1065955561020

0

15502892130711755

1755175517551755

1374771661316

0

9921570919651123

1123112311231123

87984586842

0

11925686223621350

1350135013501350

1057555121012

0

775144601535877

877877877877

68733583658

0

75706560

109803780

0

000

109803780

0

69172381

0

000

69172380

0

89213071

0

000

89213071

0

57091965

0

000

57091965

0

68622362

0

000

68622362

0

44601535

0

000

44601535

0

NOTE: Sensible performance only is shown for winter application.

Page 9: THE WALL-MOUNT STEP CAPACITY “QUIET CLIMATE” HEAT PUMPS ... · Form No. S3447-516 SupersedesS3447-715 Page 1 of 16 Copper Tube / Aluminum Fin Coils: Grooved copper tubing and

Form No. S3447-516Supersedes S3447-715Page 9 of 16

Performance and Application Data - ERVF-*5 (T36S1, T42S1, T48S1 & T60S1)

ERVF-*5 WINTER HEATING PERFORMANCE(INDOOR DESIGN CONDITIONS 70°F DB)

AmbientO.D.

VENTILATION RATE

450 CFM 375 CFM 300 CFM

DB/°F WVL WHR WVL WHR WVL WHR

65 2430 1944 2025 1640 1620 1328

60 4860 3888 4050 3280 3240 2656

55 7290 5832 6075 4920 4860 3985

50 9720 7776 8100 6561 6480 5313

45 12150 9720 10125 8201 8100 6642

40 14580 11664 12150 9841 9720 7970

35 17010 13608 14175 11481 11340 9298

30 19440 15552 16200 13122 12960 10627

25 21870 17496 18225 14762 14580 11955

20 24300 19440 20250 16402 16200 13284

15 26730 21384 22275 18042 17820 14612

SUMMER COOLING PERFORMANCE(INDOOR DESIGN CONDITIONS 75°DB/62°WB)

AmbientO.D. VENTILATION RATE -- 450 CFM VENTILATION RATE -- 375 CFM VENTILATION RATE -- 300 CFM

DB/WB F VLT VLS VLL HRT HRS HRL VLT VLS VLL HRT HRS HRL VLT VLS VLL HRT HRS HRL

105757065

214651458014580

145801458014580

688400

1395294779477

947794779477

447500

178871215012150

121501215012150

573700

1180580188018

801880188018

378600

1431097209720

972097209720

459000

958765126512

651265126512

307500

100

8075706560

3159021465123521215012150

1215012150121501215012150

194409314202

00

2053313952802978977897

78977897789778977897

126356054131

00

2632517887102931012510125

1012510125101251012510125

162007762168

00

1737411805679366826682

66826682668266826682

106925123111

00

2106014310823581008100

81008100810081008100

129606210135

00

141109587551754275427

54275427542754275427

86834160

9000

95

8075706560

31590214651235297209720

97209720972097209720

21870117442632

00

2053313952802963186318

63186318631863186318

1421576341711

00

26325178871029381008100

81008100810081008100

1822597872193

00

1737411805679353455345

53455345534553455345

1202864591447

00

2106014310823564806480

64806480648064806480

1458078301755

00

141109587551743414341

43414341434143414341

976852461175

00

90

8075706560

31590214651235272907290

72907290729072907290

24300141755062

00

2053313952802947384738

47384738473847384738

1579492133290

00

26325178871029360756075

60756075607560756075

20250118124218

00

1737411805679340094009

40094009400940094009

1336577962784

00

2106014310823548604860

48604860486048604860

1620094503375

00

141109587551732563256

32563256325632563256

1085463312261

00

85

8075706560

31590214651235248604860

48604860486048604860

26730166057492

00

2053313952802931593159

31593159315931593159

17374107934870

00

26325178871029340504050

40504050405040504050

22275138376243

00

1737411805679326722672

26722672267226722672

1470191324120

00

2106014310823532403240

32403240324032403240

17820110704995

00

141109587551721702170

21702170217021702170

1193974163346

00

80

75706560

214651235242522430

2430243024302430

1903599221822

0

13952802927641579

13952802927641579

1237264491184

0

178871029335432025

2025202520252025

1586282681518

0

11805679323381336

1336133613361336

1046954571002

0

14310823528351620

1620162016201620

1269066151215

0

9587551718991085

1085108510851085

85024432814

0

75706560

123524252

0

000

123524252

0

80292764

0

000

80292764

0

102933543

0

000

102933543

0

67932338

0

000

67932338

0

82352835

0

000

82352835

0

55171899

0

000

55171899

0

LEGEND:

VLT = Ventilation Load - TotalVLS = Ventilation Load - SensibleVLL = Ventilation Load - LatentHRT = Heat Recovery - TotalHRS = Heat Recovery - SensibleHRL = Heat Recovery - LatentWVL = Ventilation Load - LatentWHR = Heat Recovery - Total

NOTE: Sensible performance only is shown for winter application.

Page 10: THE WALL-MOUNT STEP CAPACITY “QUIET CLIMATE” HEAT PUMPS ... · Form No. S3447-516 SupersedesS3447-715 Page 1 of 16 Copper Tube / Aluminum Fin Coils: Grooved copper tubing and

Form No. S3447-516Supersedes S3447-715Page 10 of 16

MODELRated Volts & Phase

No. Field Power

Circuits

Single Circuit Multiple Circuit

jMinimum

Circuit Ampacity

Maximum External Fuse or

Ckt. Brkr.

lField Power Wire Size

lGround

Wire

j Minimum Circuit

Ampacity

MaximumExternal Fuse or Ckt.

Breaker

lField Power Wire

Size

lGround

Wire Size

Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C

T30S1-A00, A0Z-A04

m -AS8p -AF8

230/208-1

111

1 or 2

23444665

35505070

8886

1010108 24 42 35 45 8 8 10 10

T30S1-B00, B0Z-B06-B09

230/208-3111

183645

254045

1088

101010

T30S1-C0Z-C06-C09

460-3111

101924

152025

141210

141210

T36S1-A00, A0Z-A05-A08-A10

n -A15

230/208-1

11

1 or 21 or 21 or 2

2753697985

4060708090

86444

1010888

272733

425252

404040

456060

888

866

101010

101010

T36S1-B00, B0Z-B06-B09

o -B15

230/208-3

1111

23415052

30455060

10866

10101010

T36S1-C0Z -C06-C09

o -C15

460-3

1111

12212627

15253030

14101010

14101010

T42S1-A00, A0Z-A05-A08-A10

n -A15

230/208-1

11

1 or 21 or 21 or 2

3157738386

4060809090

86443

1010888

313134

425252

404040

456060

888

866

101010

101010

T42S1-B00, B0Z-B06-B09

o -B15

230/208-3

1111

26445353

35506060

8866

10101010

T42S1-C0Z-C06-C09

o -C15

460-3

1111

13222727

15253030

14101010

14101010

T48S1-A00, A0Z-A04-A05-A08-A10

n -A15

230/208-1

11

1 or 21 or 21 or 21 or 2

375763788989

50607090

100100

866433

10108888

37373737

26425252

50505050

30506060

8888

10866

10101010

10101010

T48S1-B00, B0Z-B06-B09

o -B15

230/208-3

1111

28465555

40506060

8866

10101010

T48S1-C0Z-C06-C09

o -C15

460-3

1111

14232829

20253030

12101010

12101010

T60S1-A00, A0Z-A05-A10

n -A15n -A20

230/208-1

11 or 21 or 21 or 21 or 3

45719797

113

6080

100100125

84332

108886

45454545

26525252 26

50505050

30606060 30

8888

10666 10

10101010

10101010 10

T60S1-B00, B0Z-B09

o -B15o -B18

230/208-3

1112

325959N/A

456060N/A

866

N/A

101010N/A 59 28 60 30 6 10 10 10

T60S1-C0Z-C09

o -C15o -C18

460-3

1111

15293034

20303035

1210108

12101010

j These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical Code (latest version), Article 310 for power conductor sizing.Caution: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three (3) conductors are in a raceway. Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.l Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.m Maximum KW that can operate with the heat pump on is 4KW. Full heat available during Emergency Heat Mode.n Maximum KW that can operate with the heat pump on is 10KW. Full heat available during Emergency Heat Mode.o Maximum KW that can operate with the heat pump on is 9KW. Full heat available during Emergency Heat Mode.p Maximum KW that can operate with the heat pump on is 8KW. Full heat available during Emergency Heat Mode.IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses & conductor wires in accordance with the National Electrical Code & all local codes.

Electrical Specifications — Standard Heat Pumps

Page 11: THE WALL-MOUNT STEP CAPACITY “QUIET CLIMATE” HEAT PUMPS ... · Form No. S3447-516 SupersedesS3447-715 Page 1 of 16 Copper Tube / Aluminum Fin Coils: Grooved copper tubing and

Form No. S3447-516Supersedes S3447-715Page 11 of 16

MODELRated Volts & Phase

No. Field Power

Circuits

Single Circuit Multiple Circuit

jMinimum

Circuit Ampacity

Maximum External Fuse or

Ckt. Brkr.

lField Power Wire Size

lGround

Wire

j Minimum Circuit

Ampacity

MaximumExternal Fuse or Ckt.

Breaker

lField Power Wire

Size

lGround

Wire Size

Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C

T30S1DA00, A0ZDA04

m DAS8p DAF8

230/208-1

111

1 or 2

23444665

35505070

8886

1010108 24 42 35 45 8 8 10 10

T30S1DB00, B0ZDB06DB09

230/208-3111

183645

254045

1088

101010

T30S1DC0ZDC06DC09

460-3111

101924

152025

141210

141210

T36S1DA00, A0ZDA05DA08DA10

n DA15

230/208-1

11

1 or 21 or 21 or 2

2955708085

4060708090

86444

1010888

272733

425252

404040

456060

888

866

101010

101010

T36S1DB00, B0ZDB06DB09

o DB15

230/208-3

1111

24425052

30455060

10866

10101010

T36S1DC0Z DC06DC09

o DC15

460-3

1111

14232829

15253030

14101010

14101010

T42S1DA00, A0ZDA05DA08DA10

n DA15

230/208-1

11

1 or 21 or 21 or 2

3157738386

4060809090

86443

1010888

313134

425252

404040

456060

888

866

101010

101010

T42S1DB00, B0ZDB06DB09

o DB15

230/208-3

1111

26445353

35506060

8866

10101010

T42S1DC0ZDC06DC09

o DC15

460-3

1111

13222727

15253030

14101010

14101010

T48S1DA00, A0ZDA04DA05DA08DA10

n DA15

230/208-1

11

1 or 21 or 21 or 21 or 2

375763788989

50607090

100100

866433

10108888

37373737

26425252

50505050

30506060

8888

10866

10101010

10101010

T48S1DB00, B0ZDB06DB09

o DB15

230/208-3

1111

28465555

40506060

8866

10101010

T48S1DC0ZDC06DC09

o DC15

460-3

1111

14232829

20253030

12101010

12101010

T60S1DA00, A0ZDA05DA10

n DA15n DA20

230/208-1

11 or 21 or 21 or 21 or 3

45719797

113

6080

100100125

84332

108886

45454545

26525252 26

50505050

30606060 30

8888

10666 10

10101010

10101010 10

T60S1DB00, B0ZDB09

o DB15o DB18

230/208-3

1112

325959N/A

456060N/A

866

N/A

101010N/A 59 28 60 30 6 10 10 10

T60S1DC0ZDC09

o DC15o DC18

460-3

1111

15293034

20303035

1210108

12101010

Electrical Specifications — Dehumidification Models

j These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical Code (latest version), Article 310 for power conductor sizing.Caution: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three (3) conductors are in a raceway. Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.l Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.m Maximum KW that can operate with the heat pump on is 4KW. Full heat available during Emergency Heat Mode.n Maximum KW that can operate with the heat pump on is 10KW. Full heat available during Emergency Heat Mode.o Maximum KW that can operate with the heat pump on is 9KW. Full heat available during Emergency Heat Mode.p Maximum KW that can operate with the heat pump on is 8KW. Full heat available during Emergency Heat Mode.IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses & conductor wires in accordance with the National Electrical Code & all local codes.

Page 12: THE WALL-MOUNT STEP CAPACITY “QUIET CLIMATE” HEAT PUMPS ... · Form No. S3447-516 SupersedesS3447-715 Page 1 of 16 Copper Tube / Aluminum Fin Coils: Grooved copper tubing and

Form No. S3447-516Supersedes S3447-715Page 12 of 16

ModelReturn Air(DB/WB)

Cooling Capacity 75°F 80°F 85°F 90°F 95°F 100°F 105°F 110°F 115°F 120°F

T30S1

75/62Total Cooling

Sensible Cooling31,70024,600

29,40023,500

27,40022,500

25,80021,700

24,40021,000

23,40020,500

22,70020,100

22,20019,900

22,00019,700

22,00019,800

80/67Total Cooling

Sensible Cooling33,80023,800

32,00023,000

30,40022,300

29,10021,700

28,00021,200

27,20020,800

26,70020,600

26,40020,500

26,40020,500

26,60020,700

85/72Total Cooling

Sensible Cooling40,30024,400

37,40023,400

34,90022,400

32,90021,600

31,10020,800

29,80020,200

28,80019,700

28,10019,200

27,80018,900

27,70018,700

T36S1

75/62Total Cooling

Sensible Cooling36,70028,700

34,60028,100

32,70027,400

30,90026,600

29,30026,000

27,80025,300

26,60024,500

25,30023,700

24,20023,000

23,30022,200

80/67Total Cooling

Sensible Cooling39,20027,800

37,70027,500

36,30027,100

34,90026,600

33,80026,200

32,40025,700

31,30025,100

30,20024,500

29,10023,900

28,20023,200

85/72Total Cooling

Sensible Cooling46,70028,500

44,10027,900

41,70027,300

39,40026,400

37,30025,700

35,50024,900

33,80023,900

32,20023,000

30,60022,000

29,30021,000

T42S1

75/62Total Cooling

Sensible Cooling42,10033,400

40,10032,400

38,30031,300

36,50030,400

34,70029,500

33,00028,600

31,30027,800

29,70027,100

28,10026,400

26,50025,700

80/67Total Cooling

Sensible Cooling44,90032,400

43,70031,700

42,50031,000

41,20030,400

39,50029,700

38,40029,100

36,90028,500

35,40028,000

33,80027,400

32,10026,900

85/72Total Cooling

Sensible Cooling53,50033,200

51,10032,200

48,80031,200

46,50030,200

44,20029,200

42,00028,200

39,80027,200

37,70026,300

35,50025,300

33,40024,300

T48S1

75/62Total Cooling

Sensible Cooling48,80039,400

46,60038,500

44,60037,600

42,50036,700

40,50035,700

38,60034,800

36,80033,800

35,00032,800

33,20031,800

31,40030,800

80/67Total Cooling

Sensible Cooling52,10038,200

50,80037,700

49,50037,200

48,00036,700

46,50036,000

45,00035,400

43,40034,700

41,70033,900

39,90033,100

38,00032,200

85/72Total Cooling

Sensible Cooling62,10039,100

59,40038,300

56,90037,400

54,20036,500

51,70035,300

49,20034,300

46,80033,100

44,40031,800

41,90030,500

39,50029,100

T60S1

75/62Total Cooling

Sensible Cooling58,10045,200

55,60043,700

53,20042,400

51,00041,100

48,80039,900

46,70038,800

44,70037,800

42,70036,900

40,80036,000

38,90035,200

80/67Total Cooling

Sensible Cooling62,00043,800

60,60042,800

59,10042,000

57,60041,100

56,00040,300

54,40039,500

52,70038,800

50,90038,100

49,10037,400

47,20036,800

85/72Total Cooling

Sensible Cooling73,90044,900

70,90043,400

67,90042,200

65,00040,800

62,20039,500

59,50038,200

56,80037,000

54,20035,700

51,60034,500

49,10033,300

Capacity Multiplier Factors% of Rated Airflow -10 Rated +10

Total BTUHSensible BTUH

0.9750.950

1.01.0

1.021.05

MODEL 0° 5° 10° 15° 20° 25° 30° 35° 40° 45° 50° 55° 60°F

T30S1BTUH

WATTSCOP

10,30020901.45

12,20021201.69

14,00021601.90

15,90022002.12

17,30022102.30

18,30022202.42

19,40022202.57

20,50022302.70

23,50023102.99

26,60024003.25

29,00024603.46

30,80024903.63

32,70025303.79

T36S1BTUH

WATTSCOP

14,20023001.81

16,20023402.03

18,20023902.24

20,20024302.44

21,60024602.58

22,40024802.65

23,20025002.72

24,10025202.81

27,80026003.14

31,60026703.47

34,20027303.68

36,20027803.82

38,20028203.97

T42S1BTUH

WATTSCOP

14,00027501.50

16,60028101.74

19,30028701.98

22,00029302.20

23,90029602.37

25,40029702.51

26,90029802.65

28,40029902.79

32,80031303.08

37,30032703.35

40,60033703.53

43,30034303.70

46,00034903.87

T48S1BTUH

WATTSCOP

18,00030101.76

20,60030701.97

23,30031302.19

26,00031902.39

28,00032402.54

29,50032802.64

31,10033202.75

32,70033602.86

37,00034503.15

41,30035403.42

44,60036103.62

47,30036703.78

50,00037303.93

T60S1BTUH

WATTSCOP

24,80037701.93

27,70038502.11

30,60039302.29

33,50040102.45

35,80040802.58

37,60041402.67

39,40042002.75

41,30042602.85

45,80043703.08

50,30044703.30

53,80045603.46

56,70046403.59

59,60047203.70

* 70°F DB indoor return air at rated CFM includes defrost operation below 45°.

j Below 65°F, unit requires a factory or field installed low ambient control. Return air temperature °F.

Full Load Cooling Application Data - Outdoor Temperature °F j

Full Load Heating Application Rating & Outdoor Temperature °F*

Page 13: THE WALL-MOUNT STEP CAPACITY “QUIET CLIMATE” HEAT PUMPS ... · Form No. S3447-516 SupersedesS3447-715 Page 1 of 16 Copper Tube / Aluminum Fin Coils: Grooved copper tubing and

Form No. S3447-516Supersedes S3447-715Page 13 of 16

ModelReturn Air(DB/WB)

Cooling Capacity 75°F 80°F 85°F 90°F 95°F 100°F 105°F 110°F 115°F 120°F

T30S1

75/62Total Cooling

Sensible Cooling23,80018,700

22,40017,700

20,70016,800

19,50016,100

18,30015,600

17,40015,200

16,60014,900

15,90014,600

15,40014,600

15,00014,700

80/67Total Cooling

Sensible Cooling25,40018,100

24,10017,300

23,00016,600

22,00016,100

21,00015,700

20,20015,400

19,50015,200

18,90015,100

18,50015,200

18,10015,400

85/72Total Cooling

Sensible Cooling30,30018,600

28,20017,600

26,40016,700

24,90016,000

23,40015,400

22,10014,900

21,10014,500

20,10014,200

19,50014,000

18,80013,900

T36S1

75/62Total Cooling

Sensible Cooling26,40021,300

24,80020,800

23,40020,300

22,10019,800

20,80019,400

19,60018,700

18,30018,200

17,20017,400

16,20016,800

15,00016,100

80/67Total Cooling

Sensible Cooling28,10020,600

27,00020,400

26,00020,100

24,90019,800

23,80019,500

22,80019,000

21,60018,600

20,50018,000

19,40017,400

18,20016,800

85/72Total Cooling

Sensible Cooling33,50021,100

31,60020,700

29,90020,200

28,10019,700

26,50019,200

25,00018,400

23,30017,800

21,80016,900

20,40016,100

18,90015,200

T42S1

75/62Total Cooling

Sensible Cooling30,70023,200

28,50023,000

26,60022,600

24,90022,100

23,40021,500

22,10020,900

21,00020,100

20,20019,200

19,40018,100

18,80017,000

80/67Total Cooling

Sensible Cooling32,70022,500

31,00022,500

29,50022,400

28,10022,100

26,80021,700

25,70021,200

24,80020,600

24,00019,800

23,30018,800

22,80017,800

85/72Total Cooling

Sensible Cooling39,00023,100

36,30022,900

33,90022,500

31,80022,000

29,80021,300

28,10020,500

26,80019,700

25,60018,600

24,50017,300

23,70016,100

T48S1

75/62Total Cooling

Sensible Cooling35,30027,500

34,00027,200

32,60026,800

31,20026,300

29,60025,700

28,10025,100

26,50024,300

24,80023,300

23,00022,400

21,20021,300

80/67Total Cooling

Sensible Cooling37,70026,600

37,00026,600

36,20026,500

35,20026,300

34,00025,900

32,70025,500

31,20024,900

29,50024,100

27,70023,300

25,70022,300

85/72Total Cooling

Sensible Cooling43,30033,900

41,30033,100

39,50032,300

37,50031,400

35,50030,500

33,70029,600

31,80028,700

30,00027,700

28,10026,700

26,30025,700

T60S1

75/62Total Cooling

Sensible Cooling43,30033,900

41,30033,100

39,50032,300

37,50031,400

35,50030,500

33,70029,600

31,80028,700

30,00027,700

28,10026,700

26,30025,700

80/67Total Cooling

Sensible Cooling46,20032,900

45,00032,400

43,80032,000

42,40031,400

40,80030,800

39,20030,100

37,50029,400

35,70028,600

33,80027,800

31,80026,900

85/72Total Cooling

Sensible Cooling55,10033,700

52,60032,900

50,30032,200

47,90031,200

45,30030,200

42,90029,100

40,50028,000

38,00026,800

35,50025,600

33,10024,300

Capacity Multiplier Factors% of Rated Airflow -10 Rated +10

Total BTUHSensible BTUH

0.9750.950

1.01.0

1.021.05

MODEL 0° 5° 10° 15° 20° 25° 30° 35° 40° 45° 50° 55° 60°F

T30S1BTUH

WATTSCOP

6,50017501.09

7,80017701.30

9,20017901.51

10,50018001.71

11,70018101.90

12,80018102.08

13,90018102.26

15,10018102.45

16,70018502.65

18,40018902.86

19,80019203.03

21,20019403.21

22,50019503.39

T36S1BTUH

WATTSCOP

6,70019601.01

8,40019701.25

10,10019801.50

11,80019901.74

13,40020101.96

14,90020402.15

16,50020602.35

18,00020902.53

20,00020802.82

21,90020803.09

23,70020803.34

25,40021003.55

27,10021103.77

T42S1BTUH

WATTSCOP

8,80023401.11

10,60023601.32

12,50023901.54

14,30024101.74

16,20024101.97

18,10024002.21

20,00023802.47

21,90023702.71

23,60024502.83

25,40025402.93

27,10025903.07

29,00026103.26

30,80026403.42

T48S1BTUH

WATTSCOP

10,80024901.28

12,90025201.50

15,10025501.74

17,20025801.96

18,90025902.14

20,30026002.29

21,60026002.44

23,00026002.60

26,30026702.89

29,50027403.16

32,10027903.38

34,30028203.57

36,40028503.75

T60S1BTUH

WATTSCOP

11,40028601.17

14,20029001.44

17,10029501.70

19,90029901.96

22,70030402.19

25,50031102.41

28,30031702.62

31,00032302.82

33,90032503.06

36,90032603.32

39,70032903.54

42,60033403.74

45,40033803.94

* 70°F DB indoor return air at rated CFM includes defrost operation below 45°.

j Below 65°F, unit requires a factory or field installed low ambient control. Return air temperature °F.

Part Load Cooling Application Data - Outdoor Temperature °F j

Part Load Heating Application Rating & Outdoor Temperature °F*

Page 14: THE WALL-MOUNT STEP CAPACITY “QUIET CLIMATE” HEAT PUMPS ... · Form No. S3447-516 SupersedesS3447-715 Page 1 of 16 Copper Tube / Aluminum Fin Coils: Grooved copper tubing and

Form No. S3447-516Supersedes S3447-715Page 14 of 16

Model Rated ESP jMax ESP

Blower Only

lCooling

& Heat PumpStage 1

mCooling

& Heat PumpStage 2

mElectric Heat

T30S .10 .50 650 650 900 900

T36S .15 .50 800 800 1100 1100

T42S .15 .50 800 900 1250 1250

T48S .20 .50 825 1000 1550 1550

T60S .20 .50 850 1300 1650 1650

NominalKW

At 240V j At 208V j At 480V At 460V

KW1-Ph Amps

3-Ph Amps

Btuh KW1-Ph Amps

3-Ph Amps

Btuh KW3-Ph Amps

Btuh KW3-Ph Amps

Btuh

4.0 4.0 16.7 13,652 3.00 14.4 10,239

5.0 5.0 20.8 17,065 3.75 18.0 12,799

6.0 6.0 14.4 20,478 4.50 12.5 15,359 6.0 7.2 20,478 5.52 6.9 18,840

8.0 8.0 33.3 27,304 6.00 28.8 20,478

9.0 9.0 21.7 30,717 6.75 18.7 23,038 9.0 10.8 30,717 8.28 10.4 28,260

10.0 10.0 41.7 34,130 7.50 36.1 25,598

15.0 15.0 62.5 36.1 51,195 11.25 54.1 31.2 38,396 15.0 18.0 51,195 13.80 17.3 47,099

20.0 20.0 83.3 68,260 15.00 72.1 51,195

j These electric heaters are available in 230/208V units only. These electric heaters are available in 480V units only.

• Designed for adding Electric Heat to 0 KW Units • ETL US & Canada Listed• Circuit Breaker Standard on 230/208V Models • Toggle Disconnect Standard on 460V Models

Heat Pump Models

-A00 Models230/208-1

-B00 Models230/208-3

-C00 Models460-3

Heater Model # KW Heater Model # KW Heater Model # KW

T30S1EHT03H-A04BEHT03H-AF8BEHT03H-AS8B

4F8S8

EHT03H-B06BEHT03H-B09B

69

EHT03H-C06EHT03H-C09

69

T36S1

EHS03H-A05BEHT05H-A08BEHT05H-A10BEHT05H-A15B

58

1015

EHT05H-B06BEHT05H-B09BEHS05H-B15B

69

15

EHS05H-C06EHS03H-C09EHS03H-C15

69

15

T42S1

EHS03H-A05BEHT05H-A08BEHT05H-A10BEHT05H-A15B

58

1015

EHS05H-B06BEHS05H-B09BEHS05H-B15B

69

15

EHS05H-C06EHS05H-C09EHS05H-C15

69

15

T48S1

EHT06H-A05BEHT06H-A08BEHT06H-A10BEHT06H-A15B

58

1015

EHT06H-B06BEHT06H-B09BEHT06H-B15B

69

15

EHT06H-C06EHT06H-C09EHT06H-C15

69

15

T60S1

EHT06H-A05BEHT06H-A10BEHT06H-A15BEHT06H-A20B

5101520

EHT06H-B09BEHT06H-B15BEHT06H-B18B

91518

EHT06H-C09EHT06H-C15EHT06H-C18

91518

Heater Packages - Field Installed for Standard & Dehumidification Models

Electric Heat Table - Refer to Electrical Specifications for Availability by Unit Model

NOTE: These units are equipped with a variable speed (ECM) indoor motor that automatically adjusts itself to maintain approximately the same rate of indoor airflow in both heating & cooling, dry & wet coil conditions and at both 230/208 or 460 volts.j Maximum ESP (inches WC) shown is with 2" thick disposable filter. Blower only CFM is the total air being circulated during continuous fan mode. Airflow remains constant.l Blower only CFM reduces during continuous fan mode. Requires wiring modification; consult Installation Instructions and Wiring Diagram.m CFM output on Cooling or Electric Heat.

Indoor Blower Performance - CFM (0.00" — 0.50" H20) j

Page 15: THE WALL-MOUNT STEP CAPACITY “QUIET CLIMATE” HEAT PUMPS ... · Form No. S3447-516 SupersedesS3447-715 Page 1 of 16 Copper Tube / Aluminum Fin Coils: Grooved copper tubing and

Form No. S3447-516Supersedes S3447-715Page 15 of 16

Dimensions of Basic Unit for Architectural & Installation Requirements (Nominal)

MODEL WIDTH(W)

DEPTH(D)

HEIGHT(H)

SUPPLY RETURN

A B C B E F G I J K L M N O P Q R S T

T30S1 38.200 17.125 70.563 7.88 27.88 13.88 27.88 40.00 10.88 25.75 17.93 26.75 28.75 29.25 27.00 2.63 39.13 22.75 9.14 5.00 12.00 5.00

T36S1T42S1

42.075 22.432 84.875 9.88 29.88 15.88 29.88 43.88 13.56 31.66 30.00 32.68 26.94 34.69 32.43 3.37 43.00 23.88 10.00 1.44 16.00 1.88

T48S1T60S1

42.075 22.432 93.000 9.88 29.88 15.88 29.88 43.88 13.56 37.00 30.00 40.81 35.06 42.81 40.56 3.37 43.00 31.00 10.00 1.44 16.00 10.00

Clearances Required for Service Accessand Adequate Condenser AirflowMODELS LEFT SIDE RIGHT SIDE

All Models 20" 20"

Minimum Clearances Required to Combustible Materials

MODELS j SUPPLY AIR DUCT FIRST THREE FEET CABINET

All Models 1/4" 0"

j Refer to the Installation Manual for more detailed information.

All dimensions are in inches. Dimensional drawings are not to scale.

3"

7.881.00

11"

31.88

Filter Access Panel

Air Outlet

Front View

Condenser

Standardflush ventdoor fornon-ERV/Econ.models

Ventilation Air

W

5.88

F

G

1

1

Heat

models.

1

Electric

Hood forECONWMT

MIS-2487 H

(Lockable)

Built InRain Hood

4° Pitch

Entrance

High VoltageEntrance

Access Panel

Low Voltage

Disconnect

Heater

PanelAccess

AirInlet

Drain

Cond.

Electrical

Side View

Electrical

C. Breaker/

Hood for ERV andECONWMS modelsonly

1.250

H

A

I

D

J

2.13

C

K

Electrical

Side Wall

Entrances

Mounting

Optional

Supply Air Opening

(Built In)

ShippingLocation

Brackets

Return Air Opening

Top RainFlashing

Bottom InstallationBracketBack View

T

B

M

OE

R

S

S

S

S

S P

.44

NQ

L

Unit Charge Rates

UNIT Std. Unit - Lbs.

Dehum. Units - Lbs.

T30S1 - High Efficiency Step Capacity Quiet Climate HP

7.0625 6.625

T36S1 - High Efficiency Step Capacity Quiet Climate HP

10.75 11.5625

T42S1 - High Efficiency Step Capacity Quiet Climate HP

11.625 12.125

T48S1 - High Efficiency Step Capacity Quiet Climate HP

12.00 12.00

T60S1 - High Efficiency Step Capacity Quiet Climate HP

12.4375 12.4375

Page 16: THE WALL-MOUNT STEP CAPACITY “QUIET CLIMATE” HEAT PUMPS ... · Form No. S3447-516 SupersedesS3447-715 Page 1 of 16 Copper Tube / Aluminum Fin Coils: Grooved copper tubing and

Form No. S3447-516Supersedes S3447-715Page 16 of 16

Heat Pump Wall-Mount Model Nomenclature

REVISION

j For 0 KW and circuit breakers (230/208 volt) or toggle disconnect (460V) applications, insert 0Z in the KW field of the model number. See Pages 10 & 11. Insert “D” for dehumidification with hot gas reheat. Reference Form 7960-640 for complete details.

T 36 S 1 A 05 X X X X X XMODELNUMBER |

SUPPLY AIROUTLETX - Front (Standard)

COIL OPTIONSX - Standard Hydrophilic Fin Indoor Coil & Uncoated Aluminum Outdoor Coil1 - Phenolic Coated Indoor Coil2 - Phenolic Coated Outdoor Coil3 - Phenolic Coated ID & OD Coil

COLOR OPTIONSX - Beige1 - White4 - Buckeye Gray5 - Desert Brown8 - Dark BronzeS - Stainless Steel

FILTER OPTIONS X - 1-Inch Fiberglass (MERV 2)M - 2-Inch Pleated (MERV 11) P - 2-Inch Pleated (MERV 8)

CAPACITY | 30 - 2½ Ton 36 - 3 Ton 42 - 3½ Ton 48 - 4 Ton60 - 5 Ton

CONTROL MODULES (See Control Module Options)

VOLTS & PHASE | A - 230/208/60/1 B - 230/208/60/3 C - 460/60/3

KW j 0Z - 0KW04 - 4KW05 - 5KW 06 - 6KWF8 - 8KWS8 - 8KW 09 - 9KW 10 -10KW15 -15KW18 -18KW20 -20KW

VENTILATION OPTIONS(See Vent Options Table Below)

STEP CAPACITY HEAT PUMP

SPECIALTY PRODUCTS (Non-Standard)

Form No. S3447

May, 2016

Supersedes: S3447-715

Ventilation OptionsModels T30S1 T36S1, T42S1, T48S1, T60S1

Description Factory InstalledCode No.

Field InstalledPart No.

Factory InstalledCode No.

Field InstalledPart No.

Barometric Fresh Air Damper - Standard X BFAD-3 X BFAD-5

Blank-Off Plate B BOP-3 B BOP-5

Motorized Fresh Air Damper - No Exhaust j M MFAD-3 M MFAD-5

Commercial Ventilator - Modulating Spring Return w/Exhaust C CRVMWH-3 C CHCRV-5

Commercial Ventilator - Spring Return w/Exhaust V CRVS-3 V CRVS-5

Commercial Ventilator - Power Return w/Exhaust P CRVP-3 P CRVP-5

Economizer - Standard - Enthalpy m S ECONWMS-E3B S ECONWMS-E5B

Economizer - Equipment Bldg., Enthalpy n W ECONWMT-E3B W ECONWMT-E5B

Economizer - Equipment Bldg., DB Temp n T ECONWMT-T3B T ECONWMT-T5B

Energy Recovery Ventilator - 230 Volt l R ERVF-A3 j R ERVF-A5 j

Energy Recovery Ventilator - 460 Volt l R ERVF-C3 j R ERVF-C5 j Door Kit for ERVF (Required) N/A WMDK3- l N/A WMDK5- l

Heat Pump Control ModulesLow Pressure

Control j High Pressure

Control jLow Ambient Control

and Relay Start Kit

lStart Kit

mOutdoor

ThermostatFactory Installed Code Field Installed Part

STD STD X X

STD STD T30-48 l 230V n E CMH-20

STD STD T30-48 l 460V n E CMH-21

STD STD T60 l All n E CMH-19

STD STD l Field Installed Only CMC-15 l

STD STD l Field Installed Only SK111 m

STD STD l Field Installed Only CMC-29

STD = Standard Equipmentj The high & low pressure controls are auto reset. Operating circuit includes a lockout feature and is resettable from the wall thermostat. All low pressure controls use a timed bypass circuit to prevent nuisance tripping during low temperature start-up. The low ambient control includes an 8201-008 (fan relay) and permits cooling operation down to 0°F.l PTCR start kit can be used with all -A single phase models. Increases starting torque 2-3x. Not used for -B or -C three phase models. Do not use if SK111 is used.m Start capacitor and potential relay start kit can be used with all -A single phase models. Increases starting torque 9x. Not used for -B or -C three phase models. Do not use if CMC-15 is used.n ODT. Outdoor thermostat. Field-installed only. Bard Part #8403-061. Comes with weatherproof enclosure. Works in conjunction with multi-stage thermostats offered by Bard and can be configured for any or all of compressor cut-off in heat pump mode, minimum cooling mode and maximum electric heat operation based on outdoor temperature.o Freezestat is standard on dehumidification models. Field installed option for standard units. NOTE: Standard heat pump control board has a 5-minute compressor anti-short cycle timer.

j Intake and exhaust can be independently adjusted. Insert color to match unit ("X" = Beige; "4" = Buckeye Gray; etc.)l WMDK Door Kit must be ordered in addition to ERVF Assembly and color matched to unit ("X" = Beige; "4" = Buckeye Gray; etc.)m Units controlled by thermostats other than Bard 8403-060 or Bard CompleteStat™ may require Bard “8620-220 2-Stage Heat Pump with Economizer” Relay Kit for proper operation.n Partial Full Flow (75% of Rated Cooling Airflow). All ECONWMS versions have 3" deep air intake hood.

Bard Manufacturing Company, Inc. Bryan, Ohio 43506 www.bardhvac.com