the verification of shunting method for limitation of earth fault current in mv compensated networks...

18
THE VERIFICATION OF SHUNTING METHOD FOR LIMITATION OF EARTH FAULT CURRENT IN MV COMPENSATED NETWORKS Petr TOMAN Jaroslava ORSÁGOVÁ David TOPOLÁNEK Vladimír BLAŽEK Brno University of Technology Jaromír DVOŘÁK E.ON Czech Republic

Upload: barnaby-page

Post on 22-Dec-2015

220 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: THE VERIFICATION OF SHUNTING METHOD FOR LIMITATION OF EARTH FAULT CURRENT IN MV COMPENSATED NETWORKS Petr TOMAN Jaroslava ORSÁGOVÁ David TOPOLÁNEK Vladimír

THE VERIFICATIONOF SHUNTING METHOD

FOR LIMITATION OF EARTH FAULT CURRENT IN MV

COMPENSATED NETWORKS

Petr TOMANJaroslava ORSÁGOVÁDavid TOPOLÁNEKVladimír BLAŽEK

Brno University of Technology

Jaromír DVOŘÁK

E.ON Czech Republic

Page 2: THE VERIFICATION OF SHUNTING METHOD FOR LIMITATION OF EARTH FAULT CURRENT IN MV COMPENSATED NETWORKS Petr TOMAN Jaroslava ORSÁGOVÁ David TOPOLÁNEK Vladimír

Objectives• Try to find out the reason of damaged concrete

towers in the distribution network

Page 3: THE VERIFICATION OF SHUNTING METHOD FOR LIMITATION OF EARTH FAULT CURRENT IN MV COMPENSATED NETWORKS Petr TOMAN Jaroslava ORSÁGOVÁ David TOPOLÁNEK Vladimír
Page 4: THE VERIFICATION OF SHUNTING METHOD FOR LIMITATION OF EARTH FAULT CURRENT IN MV COMPENSATED NETWORKS Petr TOMAN Jaroslava ORSÁGOVÁ David TOPOLÁNEK Vladimír

Objectives• Try to find out the reason of damaged concrete

towers in the distribution network• To measure the voltage and currents during the

earth fault for fault on unearthed console of concrete tower and for other types of fault

• The method of shunting (connecting affected phase to earth system in substation) should be tested

• The conditions during the fault state should be the same as in normal operation

Page 5: THE VERIFICATION OF SHUNTING METHOD FOR LIMITATION OF EARTH FAULT CURRENT IN MV COMPENSATED NETWORKS Petr TOMAN Jaroslava ORSÁGOVÁ David TOPOLÁNEK Vladimír

The network

• The distribution grids (22 and 35 kV) in the Czech Republic are operated as compensated via Petersen coil or as earthed via resistor (urban predominantly cable grids)

• When the earth fault comes the automatic of coil tuning stops and the dispatcher tries to find out the point of fault. During this process the mistuning caused by switching operation could rise

Page 6: THE VERIFICATION OF SHUNTING METHOD FOR LIMITATION OF EARTH FAULT CURRENT IN MV COMPENSATED NETWORKS Petr TOMAN Jaroslava ORSÁGOVÁ David TOPOLÁNEK Vladimír

The measuring

Six types of fault were realized– Low impednace – conductor lying on the earth– Arc - spark gap– Arc - damaged MV cable– 400 – 1600 – Unearthed console of concrete tower

Page 7: THE VERIFICATION OF SHUNTING METHOD FOR LIMITATION OF EARTH FAULT CURRENT IN MV COMPENSATED NETWORKS Petr TOMAN Jaroslava ORSÁGOVÁ David TOPOLÁNEK Vladimír

The measuring

The size of the network was 140 A:– Tuned Petersen coil– Mistuned Petersen coil about 40 A low

All experiments was made in three places of fault:

– Close to substation (busbar)– The long distance (about 25 km) from busbar– The middle distance (about 12 km) from busbar

Page 8: THE VERIFICATION OF SHUNTING METHOD FOR LIMITATION OF EARTH FAULT CURRENT IN MV COMPENSATED NETWORKS Petr TOMAN Jaroslava ORSÁGOVÁ David TOPOLÁNEK Vladimír

L2L1 L3

110kV/22kV

Petersencoil

Line 1

Line 2

Transformer

busbar

Shuntingcircuit breaker

Fault

Page 9: THE VERIFICATION OF SHUNTING METHOD FOR LIMITATION OF EARTH FAULT CURRENT IN MV COMPENSATED NETWORKS Petr TOMAN Jaroslava ORSÁGOVÁ David TOPOLÁNEK Vladimír

The time sequence of fault

1. Switch on the fault

2. Switch on the shunting circuit breaker

3. Switch off the fault

4. Switch off the shunting circuit breaker

Page 10: THE VERIFICATION OF SHUNTING METHOD FOR LIMITATION OF EARTH FAULT CURRENT IN MV COMPENSATED NETWORKS Petr TOMAN Jaroslava ORSÁGOVÁ David TOPOLÁNEK Vladimír

Tuned coil

Page 11: THE VERIFICATION OF SHUNTING METHOD FOR LIMITATION OF EARTH FAULT CURRENT IN MV COMPENSATED NETWORKS Petr TOMAN Jaroslava ORSÁGOVÁ David TOPOLÁNEK Vladimír

Mistuned coil

Page 12: THE VERIFICATION OF SHUNTING METHOD FOR LIMITATION OF EARTH FAULT CURRENT IN MV COMPENSATED NETWORKS Petr TOMAN Jaroslava ORSÁGOVÁ David TOPOLÁNEK Vladimír

Earth fault on unearthed console of concrete tower-tuned coil

Page 13: THE VERIFICATION OF SHUNTING METHOD FOR LIMITATION OF EARTH FAULT CURRENT IN MV COMPENSATED NETWORKS Petr TOMAN Jaroslava ORSÁGOVÁ David TOPOLÁNEK Vladimír

Earth fault on unearthed console of concrete tower- mistuned coil

Page 14: THE VERIFICATION OF SHUNTING METHOD FOR LIMITATION OF EARTH FAULT CURRENT IN MV COMPENSATED NETWORKS Petr TOMAN Jaroslava ORSÁGOVÁ David TOPOLÁNEK Vladimír

Earth fault on unearthed console

Page 15: THE VERIFICATION OF SHUNTING METHOD FOR LIMITATION OF EARTH FAULT CURRENT IN MV COMPENSATED NETWORKS Petr TOMAN Jaroslava ORSÁGOVÁ David TOPOLÁNEK Vladimír

Conclusion

• The longer operation of earth faulton unearthed console of concrete towercould be very dangerous for the lifecycle of towers

• Fault currents after closing shunting circuit breaker decreased practically to zero during all experiments

Page 16: THE VERIFICATION OF SHUNTING METHOD FOR LIMITATION OF EARTH FAULT CURRENT IN MV COMPENSATED NETWORKS Petr TOMAN Jaroslava ORSÁGOVÁ David TOPOLÁNEK Vladimír

Conclusion

• DSO on the base of series of experiments decided about the pilot project of shunting in substation Medlanky in the periphery of Brno city.

• The equipment could shortly make the second earth fault in substation in the other phase.

Page 17: THE VERIFICATION OF SHUNTING METHOD FOR LIMITATION OF EARTH FAULT CURRENT IN MV COMPENSATED NETWORKS Petr TOMAN Jaroslava ORSÁGOVÁ David TOPOLÁNEK Vladimír

Conclusion

• The next series of experiments are prepared. The main aim is to verify touch voltage for specified cases and evaluate the possibilities of fault location by distance principle (during double earth fault)

Page 18: THE VERIFICATION OF SHUNTING METHOD FOR LIMITATION OF EARTH FAULT CURRENT IN MV COMPENSATED NETWORKS Petr TOMAN Jaroslava ORSÁGOVÁ David TOPOLÁNEK Vladimír

Thank you for your attention!