The Building Regulations (Northern Ireland) 2000
Part R
‘Access to and use of Buildings’Presentation for RSUA & CIATFacilitators
Laura Hillis – Belfast Building Control
Patrick Hobson – SE Group
Billy Gillespie – NE Group
![Page 2: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/2.jpg)
Part RProgramme
Introduction Part R and dwellings Part R and buildings which are not dwellings
Access to and within buildings Facilities and Services in buildings
Some Examples
![Page 3: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/3.jpg)
3
Disabling Conditions
* Physical
* Sensory
* Cognitive
* Aging
* Hidden
* Temporary
* Encumbered
![Page 4: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/4.jpg)
4
Some Numbers
* 19.4% (200,000) Registered Disabled
* 70% find Built Environment Aggressive
* 1/3 European population elderly
* 24,000 in NI with serious sight loss
* 201,000 in NI with hearing impairment
![Page 5: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/5.jpg)
Evolution of Design
![Page 6: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/6.jpg)
Evolution of Design
The Average Person
Access for Disabled
Universal Accessibility
![Page 7: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/7.jpg)
Evolution of Design
![Page 8: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/8.jpg)
What has brought aboutthis change?
![Page 9: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/9.jpg)
Change agents
![Page 10: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/10.jpg)
![Page 11: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/11.jpg)
LEGISLATION
• Chronically Sick and Disabled Persons Act 1978
• Disabled Persons Act 1982
• Building Regulations 1994/2000
• Disability Discrimination Act
Equality Commission for N. Ireland
![Page 12: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/12.jpg)
The need for Regulation
• “The provision of advice, guidance and persuasion over a number of years have not raised awareness of designers and house builders to substantially improve access to dwellings for disabled people. There does not therefore appear to be an effective alternative to Regulations” Department of the Environment
![Page 13: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/13.jpg)
Positive Enforcement
• Regulation is probably the most potent weapon in the drive towards an accessible environment for all.
![Page 14: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/14.jpg)
14
Part R of theBuilding Regulations
Access to and use of buildings
![Page 15: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/15.jpg)
Principles of Part R
Part R - Access to and use of buildings
PEOPLE, including parents with children, elderly people and people with disabilities, should be able to:
• visit new dwellings and use principal storey…cope better…’stay put’ longer in own homes...
Secretary of State
![Page 16: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/16.jpg)
16
WHAT MUST BE PROVIDED
R2 - Reasonable Access - to/into/within and to use the building & facilities
R3 - Reasonable Access to extensions
R4 - Sanitary accommodation in extensions (not dwellings)
R5 - Sanitary conveniences in dwellings
R6 - Deemed-to-satisfy – R2,R3,R4 & R5
Technical Booklet R 2006
Dept. Ed. & Emp. Bld. Bulletin 91
![Page 17: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/17.jpg)
GUIDING PRINCIPLE
Make as many new buildings as possible accessible to everyone
![Page 18: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/18.jpg)
Definitions of disability
• Building Regulations Now no reference to disability
Previously defined as :-• Physical impairment that affects mobility• Impairment of hearing or sight
• Disability Discrimination Act• Different definition
![Page 19: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/19.jpg)
Goals of the regulationsfor Dwellings
To make reasonable provision for people to :-– reach the principal entrance from the
point of entry– have access into and within the entrance
storey or principal storey– have access to a sanitary convenience
![Page 20: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/20.jpg)
Stage 1 - The Approach
Technical Booklet R 2006 Section 7
![Page 21: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/21.jpg)
Point of entry
Principal entrance
Point of entry
Approach to principal entrance or common entrance
![Page 22: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/22.jpg)
Approach to Dwellings
• The approach from point of entry to principal entrance– Level
• Firm and even surface• Maximum gradient 1:20• Minimum width 900mm
– Ramped • Maximum gradient 1:12 for length < 5m• Maximum gradient 1:15 for length < 10m• 1200mm long landings
– or a combination
![Page 23: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/23.jpg)
![Page 24: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/24.jpg)
Steep sites
• “Steep” plot gradient to Principal Entrance (greater than 1:15 or 1:12 < 5m travel distance)
– an “alternative entrance” can be used
• Plot gradient to Alternative Entrance (greater than 1:15 or 1:12 < 5m travel distance)
– a “stepped approach” can be used
![Page 25: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/25.jpg)
Point of entry
Route of travel
Alternative entrance
Principal entrance
Approach to alternative entrance
![Page 26: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/26.jpg)
Stepped Approach
In addition to Part H requirements
— Width = 900mm min.— Rise = 150mm max. (75mm min)
— Going = 280mm min.— Flight = 1800mm max.
(16 steps max)
— Landing = 900mm min. length— Closed tread profile— Suitable handrail when >2 risers
![Page 27: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/27.jpg)
Stage 2 - The Entrance
Technical Booklet R 2006 Section 7
![Page 28: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/28.jpg)
Principal Entrance
• Landing– level for 900mm
• Entrance door– 775mm clear width
( i.e. 2’9” door)
• Level threshold– proprietary details
![Page 29: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/29.jpg)
PVC door threshold
![Page 30: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/30.jpg)
![Page 31: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/31.jpg)
Stage 3 - Horizontal circulation within the
dwelling
Technical Booklet R 2006 Section 8
![Page 32: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/32.jpg)
Circulation within dwelling
• In most cases
– Access to all habitable rooms and a toilet on the entrance storey
• No habitable rooms on the entrance storey?
– Access to all habitable rooms and a toilet on the principal storey
![Page 33: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/33.jpg)
Width of circulation routes
![Page 34: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/34.jpg)
![Page 35: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/35.jpg)
Stage 4 - Vertical circulation within the dwelling
Technical Booklet R 2006 Section 8
![Page 36: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/36.jpg)
Internal stairs
• Changes in level within an entrance storey
• Between an entrance storey and a principal storey
• Requirements– 900mm clear width
– Suitable handrail to both sides including landings
![Page 37: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/37.jpg)
Internal stairs
![Page 38: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/38.jpg)
Stage 5 - Common Stairs and Lifts in Apartments
Technical Booklet R 2006 Section 9
![Page 39: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/39.jpg)
Apartments - what else is needed?
• Approach, entrance door, threshold– as per dwellings, to the common entrance
• Common circulation routes– 1200mm minimum width
– level or ramped
![Page 40: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/40.jpg)
Apartments - common ramps
• Ramps– 1200mm width (1000mm between handrails)
– max 10m length at 1:15
– max 5m length at 1:12
– 1200mm landings
– handrails both sides over 2m
![Page 41: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/41.jpg)
Apartments - common stairs
• Common stairs– contrasting nosings– 1000mm clear width– 170mm maximum risers– 250mm minimum goings– closed profile– 1200mm landings– suitable handrails to each side
![Page 42: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/42.jpg)
Apartments - is a lift needed?
• No - but if provided, then– 800mm doors– 900mm x 1250mm car size– controls (900-1200+400)– Visual/audible indication over 3
stories– Call signalling and 5s dwell– 1500mm x 1500mm landing– 400kg loading
![Page 43: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/43.jpg)
Stage 6 - Access to Toilets
Technical Booklet R 2006 Section 10
![Page 44: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/44.jpg)
Toilet Access
• Access should be provided to a toilet on the Entrance Storey or the Principal Storey as appropriate
![Page 45: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/45.jpg)
Toilets
• WHB can project into the clear space
• Door swing must not obstruct clear space
• Door width is already determined by circulation route width
450 mm450 mm
75
0 m
m 40
0 m
m
Frontal access
![Page 46: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/46.jpg)
Toilets
• “The doorway shall be located so that its edge is not in front of , or >250mm behind, the WC……”
25
0 m
m
500 mm
400 mm
75
0 m
m
Oblique access
![Page 47: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/47.jpg)
Stage 7 - Heights of switches
Technical Booklet R 2006 Section 11
![Page 48: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/48.jpg)
Switch positions• “Switches, socket outlets etc.”
– zone between 450 to 1200mm above floor level
![Page 49: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/49.jpg)
![Page 50: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/50.jpg)
Case 1
![Page 51: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/51.jpg)
![Page 52: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/52.jpg)
![Page 53: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/53.jpg)
Case 2
![Page 54: The Building Regulations (Northern Ireland) 2000 Part R Access to and use of Buildings Presentation for RSUA & CIAT Facilitators Laura Hillis – Belfast](https://reader033.vdocuments.site/reader033/viewer/2022061305/5513f2c355034646298b611a/html5/thumbnails/54.jpg)