Page 1: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

May 12, 2014 UL and the UL logo are Trademarks of UL © 2014

Rich Walke UL Regulatory Services

Testing of Fire Resistance and

Smoke Resistant Assemblies

Page 2: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

2 2

Fire-Resistance-Rated Construction

Page 3: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

3

Fire-Resistance-Rated Construction

Code Requirements

for Fire-Resistance-

Rated Construction

Page 4: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

4

Code Requirements

• IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM E 119

• LSC 8.2.3.1 – The fire resistance of structural elements and building assemblies shall be determined in accordance with test procedures set forth in NFPA 251 (i.e. ANSI/UL 263 or ASTM E 119)

Page 5: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

5

Fire Resistance

• Expressed as an Hourly Time Period • Ratings range from 1/2 to 4 hours • Containment of Fire to Room or Floor of

Origin

Page 6: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

6

Fire-Resistance-Rated Construction

Establishing

Fire-Resistance Ratings

Page 7: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

7

Standards

• ANSI/UL 263 • ASTM E 119 • NFPA 251

Page 8: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

8

Building Components

• Columns • Beams • Floor/Ceilings or Roof/Ceilings • Walls

Page 9: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

9

Temp

(ºF)

Time (Hr)

Time - Temperature Curve

Page 10: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

10

Floor/Ceiling or Roof/Ceilings

• Sample size – 180 sq ft / 12 ft • Load applied – Per design

Page 11: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

11

Page 12: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

12

Page 13: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

13

Page 14: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

14

Page 15: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

15

Page 16: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

16

Page 17: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

17

Page 18: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

18

Page 19: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

19

Page 20: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

20

Page 21: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

21

Page 22: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

22

Conditions of Acceptance Floor/Ceilings or Roof/Ceilings

• Support load • Flame passage • 250ºF / 325ºF • Support temperatures

Page 23: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

23

Page 24: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

24

Walls

• Sample size - 100 sq ft / 9 ft • Load applied - Per design

Page 25: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

25

Page 26: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

26

Page 27: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

27

Page 28: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

28

Page 29: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

29

Page 30: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

30

Page 31: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

31

Conditions of Acceptance – Walls

• Flame passage • 250ºF / 325ºF • Support load • Hose stream

Page 32: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

32

Where Are Listings Found?

Hard Copy

CD-ROM

Online

Page 33: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

33

Questions / Comments

Page 34: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

34 34

Breaches in Fire-Resistance-Rated Construction

• Penetrations • Joint Systems • Opening Protectives • Ducts and Air Transfer Openings

Page 35: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

35

Breaches in Fire-Resistance-Rated Construction Cont.

Do breaches really impact the performance of a fire-resistance-rated assembly?

Absolutely!!!

Page 36: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

36

Breaches in Fire-Resistance-Rated Construction Cont.

• Unsealed or improperly sealed breaches cost lives and property! • MGM Grand, Las Vegas, NV – Fire confined to 1st floor.

Eighty-four fatalities, most on upper floors. • Hilton Hotel, Las Vegas, NV – Fire spread from 8th to 23rd

floor in 25 minutes at exterior of building. Eight fatalities. • First Interstate Bank, Los Angeles, CA – Fire spread from

12th to 16th floor through improperly protected penetrations and through unprotected perimeter joint. One fatality.

• One Meridian Plaza, Philadelphia, PA – Fire spread from 22nd to 30th floor through improperly protected penetrations and through perimeter joint. Three fatalities.

Page 37: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

37

Code Requirements

• IBC – Breaches shall be protected • Section 713 – Penetrations • Section 714 – Fire-Resistant Joint Systems • Section 715 – Opening Protectives • Section 716 – Ducts and Air Transfer Openings

• Each type of breach has a unique fire test standard associated with it which compliments ANSI/UL 263 and ASTM E 119

Page 38: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

38

Code Requirements Cont.

• LSC – Breaches shall be protected • Penetrations • Joint Systems • Opening Protectives • Ducts and Air Transfer Openings

• Each type of breach has a unique fire test standard associated with it which compliments NFPA 251

Page 39: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

39

Questions / Comments

Page 40: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

40 40

Through- and Membrane-Penetration Firestop Systems

Page 41: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

41

Three Elements of a Firestop System

• Floor or Wall Assembly

• Penetrating Item • Firestopping

Products

Page 42: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

42

Penetrations

Code Requirements

for Penetrations

Page 43: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

43

Code Requirements

• IBC Section 713 – Firestop systems shall be protected by an approved penetration firestop system installed as tested in accordance with ASTM E 814 or UL 1479

• LSC – Firestop systems or devices shall be tested in accordance with ASTM E 814 or UL 1479

Page 44: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

44

Ratings

• F - Flame Occurrence • T - Heat Transmission • L - Leakage (Optional) • W - Water Leakage (Optional)

Page 45: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

45

Fire-Resistance-Rated Construction

Establishing

F and T Ratings

Page 46: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

46

Standards

• ANSI / UL 1479 • ASTM E 814

Page 47: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

47

Full-Scale Wall Assembly

Page 48: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

48

Small-Scale Wood Floor Assembly

Page 49: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

49

Cables Through Wood Floor

Page 50: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

50

Conduit Through Wood Floor

Page 51: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

51

Temp

(ºF)

Time (Hr)

Time - Temperature Curve

Page 52: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

52

Hose Stream Test

Page 53: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

53

Conditions of Acceptance F Rating

• Passage of Flame • Hose Stream

Page 54: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

54

Conditions of Acceptance T Rating

• Passage of Flame • 325ºF Temperature Rise • Hose Stream

Page 55: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

55

L (Air Leakage) Ratings

• L Rating methodology added to ANSI/UL 1479 in 1993

• Leakage determined at 0.3 in. WC • Tested at Ambient and 400°F • Results published in either CFM or CFM per

sq ft

Page 56: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

56

L (Air Leakage) Ratings

Page 57: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

57

L (Air Leakage) Ratings

Page 58: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

58

L (Air Leakage) Ratings

Page 59: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

59

L (Air Leakage) Ratings

Page 60: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

60

Test Procedure

• Incidental chamber leakage determined using blank slab

• Air leakage of test sample determined at ambient temperature

• Air leakage of test sample determine at 400ºF

• Incidental chamber leakage rechecked after cooling

Page 61: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

61

Test Procedure Cont.

• Firestop system assigned L Rating at ambient and 400ºF, by subtracting incidental chamber leakage from test sample leakage

• L Ratings of firestop systems published in UL Fire Resistance Directory along with F and T Ratings

Page 62: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

62

Where Are Listings Found?

Hard Copy

CD-ROM

Online

Page 63: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

63

Questions / Comments

Page 64: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

64 64

Opening Protectives

• Fire Door

Assemblies • Fire Window

Assemblies

Page 65: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

65

Opening Protective

Code Requirements for Fire Door Assemblies

Page 66: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

66

Code Requirements

• Section 715 of the IBC •715.4.1 – Side-hinged or pivoted swinging doors shall be tested to ANSI/UL 10C or NFPA 252

•715.4.2 – Other types of doors shall be tested to ANSI/UL 10B or NFPA 252

Page 67: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

67

Code Requirements Cont.

•715.4.3.1 – Doors in corridors and smoke barriers required to have leakage rating of 3 cfm per sq ft of door opening when tested to UL 1784

•715.4.4 – Doors in exit enclosures and exit passageways shall have maximum transmitted temperature end point of not more than 450ºF for 30 minutes

Page 68: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

68

Code Requirements Cont.

• LSC •Fire protection ratings shall be determined in accordance with NFPA 252, UL 10B or UL 10C

Page 69: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

69

Opening Protectives

Establishing

Fire-Protection Rating

Page 70: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

70

Standards

• ANSI / UL 10B • ANSI / UL 10C • NFPA 252

Page 71: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

71

Temp

(ºF)

Time (Hr)

Time - Temperature Curve

Page 72: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

72

Page 73: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

73

Page 74: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

74

Page 75: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

75

Conditions of Acceptance Fire Door Assemblies

• Flame Passage • Hose Stream After Full Duration Fire

Exposure

Page 76: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

76

Where Are Listings Found?

Hard Copy

CD-ROM

Online

Page 77: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

77

Questions / Comments

Page 78: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

78 78

Fire Resistive Construction

UL’s Online

Search Tools

Page 79: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

79

UL’s Online Search Tools

• Online Certifications Directory • ULtimate Fire Wizard • Code Correlation Database

Page 80: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

80

Online Certifications Directory

• Helps you achieve code compliance • Is continuously updated • Needs no password • Is free – no charge for use • www.ul.com/database

Page 81: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

81

• Helps identify designs meeting project parameters

• Needs no password • Is free – no charge for use • Saves search results in Design Lists • www.ul.com/firewizard

ULtimate Fire Wizard

Page 82: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

82

Code Correlation Database

• Correlates model code sections to UL product categories

• Covers many model codes and editions (IBC, IFC, NEC, etc.)

• Flexible search capabilities • Powerful tool to locate appropriate Listings • www.ul.com/codelink

Page 83: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

83

Questions / Comments

Page 84: Testing of Fire Resistance and Smoke Resistant … . Code Requirements • IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM

84 84

Thank You for Attending!!!

Rich Walke Regulatory Services Department

Underwriters Laboratories 333 Pfingsten Road

Northbrook, IL 60062 [email protected]

(847) 664-3084