Page 1: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

September 24, 2014 UL and the UL logo are Trademarks of UL © 2014

Rich Walke UL Codes and Advisory Services

Fire-Resistance-Rated Construction

Page 2: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

2

Rich Walke

• 29 years conducting and supervising investigations on surface flammability, factory built air duct products, fire-resistance-rated construction, firestop systems, joint systems and perimeter fire containment systems

• Developed test method and test equipment for testing joint systems and perimeter fire containment systems

• Established an Architectural Services Group at UL • 9 years in Codes and Advisory Services Department • Spearheading effort to revamp UL’s Fire-Resistance

certification information

Page 3: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

3

Agenda

• UL’s Codes and Advisory Services Department

• Fire Resistance-Rated Construction • Definitions • Code Requirements • Establishing Fire-Resistance Ratings • Methods of Showing Code Compliance • Navigating the UL Directories

Page 4: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

4

Agenda Cont.

• UL’s Online Resources • Permitted Changes to Designs • Engineering Judgments • Plan Review / Inspection Process

• Openings in Fire-Resistance-Rated Construction

• Summary and Closing

Page 5: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

5 5

UL’s Codes and Advisory Services Department

Page 6: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

6

Support for Regulatory Community

•  Product Directories • Newsletters

• The Code Authority • Fire & Security Authority • TCA – Electrical Connections • EPH RegULator

• ULtimate Email •  Training Seminars • Code Development •  Technical Assistance

Page 7: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

7

For Technical Assistance, Call

(800) 595 – 9844 or

[email protected]

Technical Support

Page 8: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

8 8

Fire Resistive Construction

Page 9: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

9

Fire Resistive Construction

Which Code applies? It depends!!!

Page 10: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

10

Code Requirements for Fire-Resistance-Rated Construction

• IBC Section 703.2 – Fire-resistance ratings shall be determined in accordance with ANSI/UL 263 or ASTM E 119

• LSC 8.2.3.1 – The fire resistance of structural elements and building assemblies shall be determined in accordance with test procedures set forth in NFPA 251 (i.e. ANSI/UL 263 or ASTM E 119)

Page 11: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

11

Fire Resistance

• Expressed as an Hourly Time Period • Ratings range from 1/2 to 4 hours • Containment of Fire to Room or Floor of

Origin

Page 12: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

12

Fire Resistive Construction

Establishing Fire-Resistance

Ratings

Page 13: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

13

Standards

• ANSI / UL 263 • ASTM E 119 • NFPA 251

Page 14: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

14

Building Components

• Columns • Beams • Floor/Ceilings or Roof/Ceilings • Walls

Page 15: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

15

Temp

(ºF)

Time (Hr)

Time - Temperature Curve

Page 16: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

16

Walls

• Sample size - 100 sq ft / 9 ft • Load applied - Per design

Page 17: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

17

Page 18: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

18

Page 19: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

19

Page 20: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

20

Page 21: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

21

Page 22: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

22

Page 23: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

23

Conditions of Acceptance – Walls

• Flame passage • 250ºF / 325ºF • Support load • Hose stream

Page 24: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

24

Fire Resistive Construction

Methods of Showing Code Compliance

Page 25: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

25

• 703.2 – Fire-resistance ratings shall be determined in accordance with ASTM E 119 or UL 263

• 703.3 – Methods for determining fire resistance shall be based on fire exposure and acceptance criteria of ASTM E 119 or UL 263

Methods of Showing Compliance with the Fire Resistance Requirements of the FBC

Page 26: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

26

Methods of Showing Compliance with the Fire Resistance Requirements of the FBC • 703.3 Cont. – Required fire resistance

permitted to be established based on any of the following: • Designs documented from approved sources • Prescriptive requirements from Section 720 • Calculations in accordance with Section 721 • Engineering analysis based on ASTM E 119 or UL 263

• Alternative protection methods as allowed in Section 104.11

Page 27: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

27

Designs Documented From Approved Sources

• Product Directories of Nationally Recognized Testing Laboratories • UL – Fire Resistance Directory, Fire Resistance Directory on CD-ROM and Online Certifications Directory

• FM Global – Factory Mutual Approval Guide • Intertek – Intertek Directories of Certified Products

• Southwest Research Institute – Directory of Tested Products

• 27

Page 28: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

28

Designs Documented From Approved Sources Cont.

• Gypsum Association - Fire Resistance Design Manual

• American Insurance Services Group, Inc. (210) 469 – 3922 - Fire Resistance Ratings

• BOCA - Guidelines for Determining Fire Resistance Ratings of Building Elements

Page 29: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

29

Designs Documented From Approved Sources Cont.

• ASCE / SFPE 29 – Standard Calculation Methods for Structural Fireproofing

• ACI 261.1 / TMS 0216.1 – Standard Method for Determining Fire Resistance of Concrete and Masonry Construction Assemblies

Page 30: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

30

Prescriptive Fire Resistance Section 720 of the FBC

Page 31: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

31

Calculated Fire Resistance Section 721 of the FBC

Page 32: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

32

Engineering Analysis Based on ASTM E 119 or UL 263

• Engineering judgments • Product manufacturer • Testing laboratory • Fire protection engineer • Professional engineer

Page 33: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

33

Alternate Materials, Design and Methods of Construction and Equipment • Allows authority having jurisdiction to

accept other information to show compliance • Evaluation Services Reports

• IAPMO Evaluation Services • ICC Evaluation Services • UL Evaluation Services

Page 34: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

34

Fire Resistive Construction

Navigating the UL Directories

Page 35: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

35

Navigating the UL Directories

Hard Copy

CD-ROM

Online

Page 36: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

36

Fire Resistance Directory

Page 37: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

37

Fire Resistance Directory

• Volume 1 – Columns, Beams, Floor/Ceilings, Roof/Ceilings and Walls

• Volumes 2A & 2B – Joint Systems, Perimeter Fire Containment Systems, and Through-Penetration Firestop Systems

• Volume 3 – Dampers, Fire Doors, Door Frames and Glazing

Page 38: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

38

Organization Under Each Product Area

• Guide Information • Designs, Systems or Assemblies • Product Categories (indexed by

manufacturer’s names)

Page 39: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

39

Guide Information

• Equipment, materials or systems included in the Category

• Intended use, restrictions or supplemental information that apply

• Standard(s) used to evaluate products under the Category

• Listing or Classification Mark information for the Category

Page 40: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

40

Page 41: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

41

Designs

• Each design contains specific construction features

• Many designs contain various options and various ratings

• Must be followed exactly for rating to apply

Page 42: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

42

Product Categories

• Located near end of Volume 1 of Fire Resistance Directory

• Each Product Category describes some generic family of products (e.g. Acoustical Materials)

• Each Product Category contains the manufacturers and designations of products tested and specified in the designs

Page 43: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

43

Product Categories Cont.

• Manufacturers arranged alphabetically within Product Category

Page 44: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

44

UL’s Online Search Tools

• Online Certifications Directory

• ULtimate Fire Wizard • Code Correlation Database

on UL PRODUCT SPEC™

Page 45: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

45

Online Certifications Directory

• Helps you achieve code compliance • Is continuously updated • Needs no password • Is free – no charge for use • www.ul.com/database

Page 46: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

46

ULtimate Fire Wizard

• Helps identify designs meeting project parameters

• Needs no password • Is free – no charge for use • Saves search results in Design Lists • www.ul.com/firewizard

Page 47: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

47

Code Correlation Database

• Correlates model code sections to UL product categories

• Covers many model codes and editions (IBC, IFC, NEC, etc.)

• Flexible search capabilities • Powerful tool to locate appropriate Listings • www.ul.com/codelink

Page 48: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

48

Fire Resistive Construction

Permitted Changes to

Designs – Wood Frame and Light

Gauge Steel Construction

Page 49: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

49

Walls and Partitions

• Rating applies when either face exposed to fire, unless otherwise noted

• Unsymmetrical walls tested from both sides • Exterior walls may only require rating from

inside face • Load bearing rating applies to non load

bearing applications

Page 50: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

50

Walls and Partitions Cont.

• Walls are intended for interior applications unless otherwise specified (e.g. exterior use is obvious or design states “Investigated for Exterior Use”)

Page 51: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

51

Studs

• Size of studs specified is minimum • Gauge of steel studs specified is minimum • Stud spacing specified is maximum • Fire-retardant-treated wood studs may

used in lieu of specified non-treated wood studs

Page 52: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

52

Recessed (Can) Lighting

• Generic recessed luminaires not permitted unless covered in design

• Luminaires specifically tested and Listed for use in fire resistive construction covered in “Luminaires and Luminaire Assemblies Classified for Fire Resistance Category” (CDHW)

Page 53: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

53

Gypsum Board General Requirements

• Thickness may be increased providing fastener length is also increased

• Additional layers may be added • For designs reading “See Gypsum Board

(CKNX) Category for names of Classified Companies” any gypsum board Classified for fire resistance and meeting the description contained in the design may be used

Page 54: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

54

Gypsum Board on Walls

• Vertically applied board is board installed with the long edge parallel to the framing

• Horizontally applied board is board installed with the long edge perpendicular to the framing

• Board orientation shall be as specified in design

Page 55: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

55

Gypsum Board on Walls Cont.

• Except where board orientation is permitted to be horizontal, butt joints of vertically applied gypsum shall be backed.

• Horizontal butt joint on opposite sides of wall shall be staggered min 12 in. unless otherwise indicated

• Horizontal butt joint in adjacent layers on the same sides of wall shall be staggered min 12 in. unless otherwise indicated

Page 56: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

56

Gypsum Ceiling Control Joints

• Ceiling suspended below floor assembly • Guide describes control joints when

gypsum board is parallel to wood joists • Guide describes control joints when

gypsum board is perpendicular to wood joists

Page 57: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

57

Joint Treatment in Gypsum Construction

• Joints between adjacent sheets of gypsum board shall be treated with tape and one layer of compound unless otherwise indicated

• Base layer(s) in multi-layered designs need not be treated

• Joints in walls above ceiling which is part of a FRR floor-ceiling or roof-ceiling need not be treated

Page 58: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

58

Insulation

• Use of insulation shall be as specified in design

Page 59: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

59

Blanket Insulation in Horizontal Assemblies

• May cause premature disruption of ceiling membrane

• For certain assemblies, fiberglass insulation can be used with additional layer of gypsum board

• Otherwise, only permitted as specified

Page 60: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

60

Fasteners

• Cement coated box or cooler nails shall be used for securing gypsum board, unless otherwise specified in design

• Screws meeting ASTM C 1002 or C 954 may be substituted for nails providing head diameter and length are equal or larger than specified nail

Page 61: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

61

Outlet Boxes in Walls

• Metallic boxes may be installed in wall assemblies incorporating gypsum board protection providing: • Max 2 hr rated assemblies • Clearance not to exceed 1/8 in. • Area of each box not to exceed 16 sq in.

Page 62: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

62

Outlet Boxes in Walls Cont.

• Total area of boxes not to exceed 100 sq in. per 100 sq ft of wall surface

• Boxes on opposite sides of wall separated by min 24 in. or provided with heat barrier [generic non-listed product or listed protection (CLIV)]

• Nonmetallic boxes tested and listed (CEYY)

Page 63: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

63

Outlet Boxes in Ceilings

• Metallic boxes may be installed in F/C and R/C assemblies incorporating gypsum board protection providing: • Clearance not to exceed 1/8 in. • Area of each box not to exceed 16 sq in. • Total area of boxes not to exceed 100 sq in. per 100 sq ft of ceiling area

• Nonmetallic boxes tested and listed (CEYY)

Page 64: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

64

Upgrading Wall Ratings from 1 to 2 Hrs

• Five steel stud / gypsum board designs intended to permit upgrading from 1 to 2 hrs working from one side: • U408, U421, U453, U477, V449 • Use of these designs is predicated on the specified board being present on existing wall

Page 65: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

65

Upgrading Wall Ratings from 1 to 2 Hrs Cont.

• Tested shaft wall can always be built adjacent to existing 1 hr wall

Page 66: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

66

HVAC Openings in Gypsum Ceilings

•  Some assemblies with gypsum board ceilings have been tested with specific UL Classified Ceiling Radiation Dampers

•  In assemblies with gypsum board ceilings, damper may not be utilized if not specified in design

• Only those dampers specified in design may be used

Page 67: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

67

Fire Resistive Construction

Permitted Changes to Designs –

Concrete and Steel

Construction

Page 68: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

68

HVAC Openings in Acoustical Ceilings

• Most acoustical ceilings are tested with generic hinged blade damper

• UL Classified Ceiling Damper, Ceiling Air Diffuser or Air Terminal Unit may be substituted for generic hinged blade damper

• Duct Protection Systems A and B may also be substituted per Guide Info

Page 69: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

69

Concrete Masonry Unit Walls

• Code requires CMU walls to be tested in accordance with UL 263 / ASTM E 119

• UL U900 series designs describe CMU walls

• Each designs describes use of listed block in conjunction with a specific mortar

• CMU shipment supplied with Certificate label covering a specific shipment to a specific job site

Page 70: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

70

Concrete Masonry Unit Walls Cont.

• D-2 Certificate equals “2 hr” block • C-3 Certificate equals “3 hr” block • B-4 Certificate equals “4 hr” block

• Some designs describe use of some other component to extend rating

• UL 618, FBC Prescriptive Section and industry trade associations provide prescriptive information on how to produce a rated block

Page 71: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

71

Concrete Masonry Unit Walls Cont.

• Many manufacturers self-certify to UL 618 • When block is self-certified, who confirms

block was produced in accordance with UL 618?

• When block is self-certified, what mortar is to be used?

• Can rating be extended through use of another component?

Page 72: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

72

Steel Joists

• Specified joist is minimum depth • Specified joist is minimum weight/foot • K-Series Joist may often substitute • Spacing between joists may be increased

to 4 ft OC providing: • Structural integrity of floor is maintained • Hanger wire spacing is not increased

• Bridging bar size is minimum

Page 73: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

73

Beam Size

• Larger beams may be substituted without restriction

• Larger is based on W/D ratio • Larger W/D yields greater fire resistance

Page 74: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

74

Column Size

• Larger columns may be substituted without restriction

• Based on W/D ratio • Larger W/D yields greater fire resistance

Page 75: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

75

Types of Direct Applied Protection Materials

• Spray-Applied Fire-Resistive Material (SFRM) • Cementitious mixture • Sprayed fiber

• Mastic Coating • Thin-Film Intumescent Material

Page 76: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

76

Application of Direct Applied Protection Materials

• Surface must be free of dirt, oil and loose scale

• Thickness and Density of SFRM determined per ASTM E 605

• Bond Strength of SFRM Determined per ASTM E 736

• Thickness of Thin-Film Intumescent Materials determined per AWCI Technical Manual 12-B

Page 77: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

77

Application of Direct Applied Protection Materials Cont.

• Any material removed by trades after application must be repaired

• If wall terminates at SFRM, the resulting Head-of-Wall Joint System dictates how to attach wall to SFRM protected element

Generally not acceptable

Page 78: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

78

Adjustment of Thickness of SFRM - Beams

• Not applicable to mastic and intumescent materials

• Coating material thickness on beams with lesser W/D requires adjustment and thickness on beams with greater W/D may be adjusted as follows:

Page 79: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

79

Adjustment of Thickness of SFRM - Columns

• Not applicable to mastic and intumescent materials

• Coating material thickness on columns with lesser W/D requires adjustment as follows:

Page 80: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

80

Fire Resistive Construction

Engineering Judgments

Page 81: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

81

Engineering Judgments

• An Engineering Judgment is a letter or report issued by some knowledgeable party which evaluates the construction of some site-specific application which deviates from a tested design, system or assembly and concludes with a judgment of the applicable rating of that assembly

Page 82: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

82

Engineering Judgments Cont.

• Typically, an Engineering Judgment is used when a tested design, systems or assembly is unavailable

• Most often applied to fire resistive construction

• Must be acceptable to the Building Official or AHJ

Page 83: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

83

Who Issues Engineering Judgments?

• Who issues Engineering Judgments? • Professional engineer • Fire protection engineer • Manufacturer • Testing laboratory

• Individual issuing judgment must be acceptable to the Building Official or the AHJ

Page 84: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

84

IFC Guidelines

• Four Documents • Recommended IFC Guidelines for Evaluating Firestop Systems in Engineering Judgments (EJs) • Covers firestops, joint systems and grease/air duct assemblies

• Perimeter fire barrier systems • Fire resistant duct enclosure systems for commercial kitchen exhaust ducts

• Fire resistant duct enclosure systems for ventilation ducts

Page 85: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

85

Summary of Engineering Judgments

• Emphasizes importance of tested designs • Not a substitute for existing designs • Should be issued only by those who know

the components • Based on sound engineering practices and

knowledge of performance of the designs • Based on interpolation of previous testing • Issued only for a specific jobsite • Presented in clear detail

Page 86: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

86

Fire Resistive Construction

Plan Review / Inspection

Page 87: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

87

For the Contractor

2)    A  set  of  build-­‐instruc3ons  

1)  Evidence  of  compliance  

UL  Designs  serve  two  roles:  

Page 88: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

88

For the Building or Fire Official

1)  Evidence  of  compliance  

UL  Designs  serve  two  roles:  

2)    Document  by  which  to  inspect  

Page 89: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

89

Plan Review

• 107.2.1 - Construction documents shall be of sufficient clarity to indicate the location, nature and extent of the work proposed and show in detail that it will conform to the provisions of this code …

Page 90: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

90

Plan Review Cont.

• Details showing compliance with the fire-resistive requirements of the IBC should be included on the plans and in the specifications

• Recommended that the UL designs (or others) be imported into the plans

• Importing designs into plans does NOT violate UL copyright requirements

Page 91: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

91

Available Resources

• Association of Wall and Ceilings Industry (AWCI) – www.awci.org

• Firestop Contractors International Association (FCIA) – www.fcia.org

• Fire Safe North America (FSNA) – www.firesafenorthamerica.org

• Gypsum Association (GA) – www.gypsum.org

Page 92: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

92

Available Resources Cont.

• International Firestop Council (IFC) – www.firestop.org

Page 93: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

93 93

Openings in Fire-Resistance-Rated Construction

• Penetrations (Section 713) • Fire-Resistant Joint Systems (Section 714) • Opening Protectives (Section 715) • Ducts and Air Transfer Openings (Section

716)

Page 94: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

94

Openings in Fire-Resistance-Rated Construction Cont.

Do openings really impact the performance of a fire-resistance-rated assembly?

Absolutely!!!

Page 95: Fire-Resistance- Rated Construction - AHCA Seminar Safety Wed/Fire... · fire-resistance-rated construction, ... Fire Resistance Directory, ... • UL U900 series designs describe

95

Openings in Fire-Resistance-Rated Construction Cont.

•  Unsealed or improperly sealed openings cost lives and property! • MGM Grand, Las Vegas, NV – Fire confined to 1st floor.

Eighty-four fatalities, most on upper floors. • Hilton Hotel, Las Vegas, NV – Fire spread from 8th to 23rd

floor in 25 minutes at exterior of building. Eight fatalities. • First Interstate Bank, Los Angeles, CA – Fire spread from

12th to 16th floor through improperly protected penetrations and through unprotected perimeter joint. One fatality.

• One Meridian Plaza, Philadelphia, PA – Fire spread from 22nd to 30th floor through improperly protected penetrations and through perimeter joint. Three fatalities.