sttpgaaa31e - tp presentation for bdam - copy

46
During a transformer short circuit, the TRANSFORMER PROTECTOR is activated within milliseconds by the first dynamic pressure of the shock wave, avoiding transformer explosions before static pressure increase TRANSFORMER PROTECTOR The Only Solution Against Transformer Explosion www.transproco.com TRANSFORMER PROTECTOR Presentation

Upload: md-farhad-hossain

Post on 13-Apr-2017

209 views

Category:

Documents


16 download

TRANSCRIPT

Page 1: StTPgaaa31e - TP Presentation for BDAM - Copy

During a transformer short circuit, the TRANSFORMER PROTECTOR is activated within milliseconds by the firstdynamic pressure of the shock wave, avoiding transformer explosions before static pressure increase

TRANSFORMER PROTECTOR

The Only Solution Against Transformer Explosion

www.transproco.com

TRANSFORMER PROTECTOR Presentation

Page 2: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e 2

NFPAThe TRANSFORMER PROTECTOR is now recommended for all Power Plants and Substations in the National Fire Protection Association 2010 edition of:• NFPA 850 (Recommended Practice for Fire Protection for Electric Generating Plants and High Voltage Direct Current Converter Stations),• NFPA 851 (Recommended Practice for Fire Protection for Hydroelectric Generating Plants).

The introduction of the 2010 edition of NFPA 850 & NFPA 851 stands : “Fast depressurization systems have been recognized, and recommendations for the use of these systems are now included”

“Fast depressurization system: a passive mechanical system designed to depressurize the transformer a few milliseconds after the occurrence of an electrical fault”

More details later in the presentation or

Just click here

2

Page 3: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e 3

1. Transformers are very dangerous

• Examples of explosions

• Conventional protections

• The answer

1. Transformers are very dangerous

Page 4: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e 4

Danger :

• The whole power plant (1,350MW) was out of service for 4 months.

• The damaged section (450 MW) was out of service for 13 months.

• 2 people were badly burned.• Fire extinguishing systems did not

work.• Security fire doors were too slow.

Transformer explosion in substation :

Power transformers are very dangerous

Transformer explosion in substation

•Large quantity of oil in contact with high voltage elements•No international security norm for transformers

1. Transformers are very dangerous Examples of explosions

Click on picture to watch video

Page 5: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e 5

Other explosion examples

Krümmel Nuclear Power Plant, GermanyJune 2007, still not restarted !

Cost: 1 Million USD / day !

3Transformer explosions lead to:

• Huge fire

• Plant outage

• Huge costs : hundreds millions USD

• Ruin company reputation

• Environmental pollution

• Human life risks

1. Transformers are very dangerous Examples of explosions

5

Page 6: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e 6

1. Transformers are very dangerous Conventional protections

a) South Bend, Indiana , USA, 1999

Efficiency ?Corrective Means

• Firewalls • Fire extinguishing systems

Limit fire propagation induced by the explosion Fire propagated from one transformer

to the other

1

6

Page 7: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e 7

1. Transformers are very dangerous Conventional protections

b) Venice Plant, Illinois , USA, 2000

Efficiency ?Corrective Means

Solution : Preventing transformer explosion to avoid fire

• Firewalls • Fire extinguishing systems

Limit fire propagation induced by the explosion

Fire propagated to the whole plant: All 9 transformers caught fire despite fire

walls and fire extinguishing systems (cost: USD 230 millions)

1

7

Page 8: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e 8

1. Transformers are very dangerous Conventional protections

All exploded transformers

were equipped with these

devices

Efficiency ?Preventive Means

• Circuit breakers

• Buchholz Relay

• Sudden Pressure Relay

• Gas Monitoring

• Pressure Relieve Valve

Solution : The protection must act faster !

2

8

Page 9: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e 9

1. Transformers are very dangerous The answer

During a short circuit, the TP is activated within milliseconds by the first dynamic pressure peak of the shock wave, avoiding explosions by preventing static pressure increase.

The TP key of success

The TRANSFORMER PROTECTOR (TP)The TP depressurizes transformers within milliseconds

avoiding explosion and subsequent fire.

9

Page 10: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e 10

2. Preventing transformer explosion: the TP principle

• Transformer explosion process

• TP strategy to prevent explosion

• TP operation

• TP standard configuration

• TP operation movie

2. Preventing Transformer Explosion: The TP Principle

10

Page 11: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e 11

Why do transformers explode ?

Dielectric oil insulation rupture

Electrical arc

Oil vaporization

Local dynamic pressure increase

First dynamic pressure peak propagates

Dynamic pressure peak reflects off walls

Static pressure increases

Tank rupture & Fire

2. Preventing transformer explosion: the TP principle Transformer explosion process

Page 12: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e 12

How to break that sequence?

Dielectric oil insulation rupture

Electrical arc

Oil vaporisation

Local dynamic pressure increase

First dynamic pressure peak propagates

Dynamic pressure peak reflects off walls

Static pressure increases

Tank rupture & Fire

2. Preventing transformer explosion: the TP principle Prevention strategy

12

Page 13: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e 13

Activation within milliseconds by the first dynamic pressure peak

Quick Oil Evacuation

Tank depressurization

Prevents the explosion

How to break that sequence?

Dielectric oil insulation rupture

Electrical arc

Oil vaporisation

Local dynamic pressure increase

First dynamic pressure peak propagates

Dynamic pressure peak reflects off walls

2. Preventing transformer explosion: the TP principle Prevention strategy

Page 14: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e 14

2. Preventing transformer explosion: the TP principle TP operation

14

Page 15: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e 15

2. Preventing transformer explosion: the TP principle TP operation

• Electrical arc• Pressurized gas bubble• Dynamic pressure peak propagation

15

Page 16: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e 16

2. Preventing transformer explosion: the TP principle TP operation

Quick oil evacuation generating fast depressurization of the tank (within milliseconds)

TP Activation1

• Electrical arc• Pressurized gas bubble• Dynamic pressure peak propagation

16

Page 17: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e 17

2. Preventing transformer explosion: the TP principle TP operation

• Explosive gases remain• Melting parts of the windings are still emitting gases

Quick oil evacuation generating fast depressurization of the tank (within milliseconds)

TP Activation1

• Electrical arc• Pressurized gas bubble• Dynamic pressure peak propagation

17

Page 18: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e 18

2. Preventing transformer explosion: the TP principle TP operation

Evacuation of the explosive gases until the melted parts are cooled down (~ 45 mn)

Injection of Inert Gas2

Quick oil evacuation generating fast depressurization of the tank (within milliseconds)

TP Activation1

• Explosive gases remain• Melting parts of the windings are still emitting gases

• Electrical arc• Pressurized gas bubble• Dynamic pressure peak propagation

18

Page 19: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e 19

2. Preventing transformer explosion: the TP principle TP operation

Transformer safe and ready for repair

Quick oil evacuation generating fast depressurization of the tank (within milliseconds)

TP Activation1

Evacuation of the explosive gases until the melted parts are cooled down (~ 45 mn)

Injection of Inert Gas2

• Explosive gases remain• Melting parts of the windings are still emitting gases

• Electrical arc• Pressurized gas bubble• Dynamic pressure peak propagation

19

Page 20: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e 20

2. Preventing transformer explosion: the TP principle TP standard configuration

Standard TRANSFORMER PROTECTOR (TP)

6

2

1 4

1. Vertical Depressurization Set (VDS)

2. OLTC Depressurization Set (OLTC DS)

3. Slice Oil-Gas Separation Tank (SOGST)

4. Explosive Gases Evacuation Pipe (EGEP)

5. Air Isolation Shutter

6. TP Cabinet

7. Inert Gas Injection Pipe (IGIP)

The ComponentsTP Components

7

3

5

20

Page 21: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e 21

2. Preventing transformer explosion: the TP principle TP operation movie

TP Operation Movie

Click on picture to watch video

21

Page 22: StTPgaaa31e - TP Presentation for BDAM - Copy

Ref: StTPgaaa31eTRANSFORMER PROTECTOR

The Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

22

3. Physical Explanations and Testing of the TP Experimental tests: general overview

Two main test campaigns

ConclusionDuring the 62 tests, the TP always saved transformers from explosion without permanent tank deformation

• 2002: 28 tests by EDF (Electricité de France) on small transformers

• 2004: 34 tests by CEPEL (HV independent lab.) on large transformers (8.4m – 26ft long)

• Principle: electrical arcs were ignited inside transformers tanks equipped with a TP

Click on pictures to watch videos

22

Page 23: StTPgaaa31e - TP Presentation for BDAM - Copy

Ref: StTPgaaa31eTRANSFORMER PROTECTOR

The Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

23

3. Physical Explanations and Testing of the TP Vaporization saturation process

SKIP

1st key phenomena: oil vaporization & arc creation – video1

Arc movie during the EDF testsHigh speed camera 3000 fps

Chronology

0 ms : Start of applied current

3.66 ms : Bubble generation

4 ms : Bubble volume = 9 cm3, 0.5 in.3

4.33 ms : Bubble volume = 60 cm3, 3.7 in.3

4.66 ms : Bubble volume = 97 cm3, 5.9 in.3

5 ms : Bubble volume = 190 cm3, 11.6 in.3

5.33 ms : Bubble volume = 299 cm3, 18.2 in.3

5.66 ms : Bubble volume = 399 cm3, 24.3 in.3

6 ms : Bubble volume = 568 cm3, 34.7 in.3

6.33 ms : Electrical arc fully developed - plasma

23

Page 24: StTPgaaa31e - TP Presentation for BDAM - Copy

Ref: StTPgaaa31eTRANSFORMER PROTECTOR

The Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

24

3. Physical Explanations and Testing of the TP Dynamic / static pressure

• Spatially uniform all over the tank• Progressive, slow increase • Oil behaves as an incompressible

media• Max withstand ~1 bar – 15 psi (gauge)

• Very localized and moving in the tank• Propagates quickly within the tank• Oil behaves as a compressible media• Tank can resist 13 bar – 190 psi

(gauge)

The tank does not explode The tank explodes

Dynamic PressurePressure gradients over 25 bar/s – 360 psi/s

Static PressurePressure gradients under 25 bar/s – 360 psi/s

How does the PRV react to dynamic

pressure ?

Click here

Pressure gradients up to 5000 bar/s – 72000 psi/s

Propagation speed: 1200 m/s – 4000 ft/s

24

Page 25: StTPgaaa31e - TP Presentation for BDAM - Copy

Ref: StTPgaaa31eTRANSFORMER PROTECTOR

The Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

25

3. Physical Explanations and Testing of the TP Influence of the TP

a) No static pressure The quick oil evacuation generates rarefaction waves that depressurizes the tank before static pressure builds up.

0 ~10 ms

Arc occurrence

TP is activated

Tank is depressurized

~80 ms

Dyn. pressure travelling

Oil evacuation

Click on picture to watch videoThe DS is activated within milliseconds by the first dynamic pressure peak and evacuates pressure while tank structure inertia to rupture is much higher.

The breaking section to open the precut Rupture Disk at the dome is more than 50 times less than the section of tank bolts.

Very small section to break to activate TP

6th key phenomena: the TP depressurizes tanks preventing explosion6

25

Page 26: StTPgaaa31e - TP Presentation for BDAM - Copy

Ref: StTPgaaa31eTRANSFORMER PROTECTOR

The Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

50 ms

30 ms

10 ms

4 ms

1 ms

100 ms

26

50 ms60 ms70 ms80 mst =

Static pressure builds up

Dynamic pressure reach more than 9 bar – 130 psi (gauge) in a bushing

Reflects off the walls and creates complex pressure waves

Gas bubble under pressure

The first dynamic pressure peak propagates

Static pressure stabilizes at 5.5 bar – 80 psi (gauge)

100 ms

Transformer explodes

3. Physical Explanations and Testing of the TP Simulation tool – 200 MVA transformer – no protection

11 MJ electrical arc

Max. static withstand limit pressure of transformer tanks :

1.2 bar – 17 psi (gauge)

Pressure (gauge) (psi) (bar)

without TP

Page 27: StTPgaaa31e - TP Presentation for BDAM - Copy

Ref: StTPgaaa31eTRANSFORMER PROTECTOR

The Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

1 ms

27

70 ms80 ms100 mst =

After 60 ms

11 MJ electrical arc

Gas bubble under pressure

150 ms

3. Physical Explanations and Testing of the TP Simulation tool – 200 MVA transformer – with TP

4 ms

10 ms The dynamic pressure peak activates the TP

The first dynamic pressure peak propagates

15 ms

30 ms

60 ms

The tank depressurizes

Rarefaction waves are spread in the tank

The tank is fully depressurized

without TP

with TP

• without TP, static press. = 5.5 bar – 80 psi

Pressure (gauge) (psi) (bar)

• with TP, static pressure = atm. pressure

without TP

with TP

Page 28: StTPgaaa31e - TP Presentation for BDAM - Copy

Ref: StTPgaaa31eTRANSFORMER PROTECTOR

The Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

after 120 ms

28

3. Physical Explanations and Testing of the TP Simulation tool – Real case study – 400 MVA transformer

• Without TP, the max. pressure is 14 bar – 200 psi and the static pressure builds up at around 7 bar – 100 psi.

the tank explodes

• With TP, the first dynamic pressure peak activated the TP within milliseconds before static pressure is built up.

the tank is safe

with TPwithout TP

Pressure (gauge) (psi) (bar)

after 120 ms after 120 ms

28

Page 29: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e 29

4. TP Technical Description Retrofitting on existing transformers

The TRANSFORMER PROTECTOR is easily retrofitted without tank machining by using the existing interfaces

1. Depressurization Set: Cover and Side Manholes, Pressure Relief Valves and Existing Valves can be used for the adaptation

SKIP

Retrofitting on existing transformers

29

Page 30: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e

Retrofitting on existing transformers

30

4. TP Technical Description Retrofitting on existing transformers

The TRANSFORMER PROTECTOR is easily retrofitted without tank machining by using the existing interfaces

1. Depressurization Set: Cover and Side Manholes, Pressure Relief Valves and Existing Valves can be used for the adaptation

2. Inert Gas Injection: Existing Valves for oil sampling and draining can be used to retrofit the inert gas injection

30

Page 31: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e 31

5. References Financial benefit

The TP Financial Benefit is very high

The Protection Financial Benefit (PFB) is calculated as :PFB = CTC / (MLEB – LEA)

For corporate risk managers and insurance, if:• PFB < 1 %, the protective technology is highly recommended• 1% < PFB < 4%, insurance companies adjust their rates and premiums

Analyses showed that the TP Financial Benefit varies from 0.015 % to 0.06 % !

When an incident occurs, the TP compensates several thousand times the investment

• CTC (Cost To Complete) : complete price of the protection (including erection and tests)• MLEB (Maximum Loss Expectancy Before): cost of the worst recorded incident before

installing a protection• LEA (Loss Expectancy After): evaluation of the damage cost of the worst recorded incident

with the chose protection after installation

Extract from “Transformer Explosion and Fire Incidents, Guideline for

Damage Cost Evaluation, Transformer Protector Financial Benefit”

Available on request

31

Page 32: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e

Generation Transmission Distribution

32

5. References Sold TP

More than 1.400 TP sold since 2000

Every kind of oil-filled transformers (above 1 MVA)

32

Page 33: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e 33

5. References End users

More than 106 companies in 53 countries:

• Australia: Delta Electricity• Brazil: Abengoa, Tractabel,• France: EDF• Germany: Vattenfall

•Jordan: JEPCO, NEPCO•Mexico: CFE•Namibia: NamPower•Russia: Rusgidro, FNK

•Qatar: Kahramaa, Qatar Petroleum•South Africa: Eskom, City Power•Spain: Metro de Madrid•USA: PG&E, Sunflower Electric

33

Page 34: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e 34

5. References NFPA

• Standard NFPA 850 (Recommended Practice for Fire Protection for Electric Generating Plants and High Voltage Direct Current Converter Stations)

• Standard NFPA 851 (Recommended Practice for Fire Protection for Hydroelectric Generating Plants)

The NFPA recommends the TP

In the introduction of NFPA 850 and 851:

34

Page 35: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e 35

5. References NFPA

Definition of “fast depressurization system” by the NFPA:

• Standard NFPA 850 (Recommended Practice for Fire Protection for Electric Generating Plants and High Voltage Direct Current Converter Stations)

• Standard NFPA 851 (Recommended Practice for Fire Protection for Hydroelectric Generating Plants)

The NFPA recommends the TP

35

Page 36: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e 36

5. References NFPA

Explanation of the operation by the NFPA:

• Standard NFPA 850 (Recommended Practice for Fire Protection for Electric Generating Plants and High Voltage Direct Current Converter Stations)

• Standard NFPA 851 (Recommended Practice for Fire Protection for Hydroelectric Generating Plants)

The NFPA recommends the TP

Documents available on

request

36

Page 37: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e 37

FM Global : Certification under progress

NFPA : TP is recommended in the standards 850 & 851 and in the NFPA Fire Handbook 2002 & 2008

EDF (Electricité de France) and CEPEL (Brazil) laboratories TP tests validation

Active participation in the Power Transformer Subcommittee (tank rupture mitigation taskforce)

Various IEEE Conferences

Active participation in the A2 Study Committee – Transformers (transformer fire safety practices WG)

Various Cigré Conferences

5. References Valorization or certification organisms

37

Page 38: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e 38

5. References Successful activations

• Romania (TransElectrica), • Philippines (Transco), • Botswana (Botswana Power Corporation),• Activation in Pakistan, Mexico (3) and Romania under

process

The TP saved transformers, successful activation certificates from:

38

Page 39: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e

with TP without TP

after 100 ms

Pressure (gauge) (psi) (bar)

39

Conclusion

Brazil Germany France

• The NFPA Fire Handbook emphasizes the TP technology• Several successful activations• More than thousand TP sold all over the world (USA, Europe, Middle East…)

3. The TP is a recommended solution

• Principle: No Actuator !The TP is activated by the first dynamic pressure peak generated by the arc, avoiding the explosion by preventing static pressure increase

• Efficiency demonstrated by experimental tests & numerical simulations

2. The TRANSFORMER PROTECTOR prevents the explosion

• Explosions are more and more frequent• Dangerous, expensive, polluting, hurt reputation…• Conventional corrective means do not prevent explosion (fire extinguishing systems,

firewalls)• Conventional preventive means are not efficient (circuit breakers, buchholtz, PRV...)

1. Power transformers are very dangerous

39

Page 40: StTPgaaa31e - TP Presentation for BDAM - Copy

During a transformer short circuit, the TRANSFORMER PROTECTOR is activated within milliseconds by the firstdynamic pressure of the shock wave, avoiding transformer explosions before static pressure increase

TRANSFORMER PROTECTOR

The Only Solution Against Transformer Explosion

www.transproco.com

Page 41: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e 41

5. References CEPEL (Brazilian independent laboratory)

Back to the presentation

Click here

41

Page 42: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e 42

3. Physical Explanations and Testing of the TP TP – PRV reaction to dynamic pressure

TRANSFORMER PROTECTOR Pressure Relieve Valve (PRV)

How does the PRV react to dynamic pressure ?

42

Page 43: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e 43

• Spring inertia to open: 5 ms• PRV reacts to dynamic pressure for

0.1ms PRV diameter: 15 cm - 6 in. Dyn. press. speed: 1200 m/s – 4000 ft/s

• activated by dynamic pressure peak • depressurizes the tank within

milliseconds• prevents static pressure increase

The tank does not explode Dynamic pressure peak too

fast to activate the PRV

TRANSFORMER PROTECTOR Pressure Relieve Valve (PRV)

0.1 ms

3. Physical Explanations and Testing of the TP TP – PRV reaction to dynamic pressure

43

Page 44: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e

3. Physical Explanations and Testing of the TP PRV reaction for lower pressure gradient

Even for lower pressure gradients, the PRV is not adapted• 1st step : spring inertia is 5 ms• 2nd step: when the PRV is 50% open, only 15% of the section is used to

evacuate the oil

Evacuation Section only 15% when half open

0%

50% Spring inertia 5 ms

44

Page 45: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e

3. Physical Explanations and Testing of the TP PRV reaction for lower pressure gradient

Even for lower pressure gradients, the PRV is not adapted• 1st step : spring inertia is 5 ms• 2nd step: when the PRV is 50% open, only 15% of the section is used to

evacuate the oil• 3rd step: oil has to make a “U turn” to escape, the evacuation is slowed

down• 4th step: even when the PRV is fully opened, only 80% of the section is used

Evacuation SectionOnly 80% of 6’’ when

fully open

0%

50%

100%

U turn for the oil evacuation

45

Page 46: StTPgaaa31e - TP Presentation for BDAM - Copy

TRANSFORMER PROTECTORThe Only Solution Against Transformer Explosion

1/ Transformers explosions2/ TP principle3/ Physical explanations4/ Technical description5/ TP References

Ref: StTPgaaa31e

3. Physical Explanations and Testing of the TP PRV reaction for lower pressure gradient

What is the use of the PRV ?

• PRV is not adapted for low impedance fault (arcing)• PRV is designed for slow pressure increase to relieve low static

overpressure High impedance fault Low temperature increase Very slow gas creation …

Back to the presentation

Click here

4646