sdmo kerys control panel manual

65
User's guide S S D D M M O O C C o o n n t t r r o o l l u u n n i i t t K K E E R R Y Y S S T T A A C C T T I I L L - - S S 9 9 0 0 0 0 0 0 V 1.05 (29/06/06) 33502015901_2_1

Upload: zekai-yurtman

Post on 15-Oct-2014

1.764 views

Category:

Documents


230 download

TRANSCRIPT

Page 1: Sdmo Kerys Control Panel Manual

User's guide

SSDDMMOO

CCoonnttrrooll uunniitt

KKEERRYYSS TTAACCTTIILL -- SS 99000000

V 1.05 (29/06/06) 33502015901_2_1

Page 2: Sdmo Kerys Control Panel Manual
Page 3: Sdmo Kerys Control Panel Manual

1/62 33502015901_2_1

1. MICS Kerys .......................................................................................................................................................................................... 2

1.1. Aim and structure .................................................................................................................................................................... 2 2. Using the interface ................................................................................................................................................................................ 2

2.1. Presentation of the keypad....................................................................................................................................................... 2 2.1.1 The display .............................................................................................................................................................................. 3 2.1.2 The alphanumeric keys............................................................................................................................................................ 3 2.1.3 The generating set operational keys ........................................................................................................................................ 4 2.1.4 The navigation keys ................................................................................................................................................................ 5 2.1.5 The signalling control keys ..................................................................................................................................................... 5

2.2. Interface ergonomics ............................................................................................................................................................... 5 2.2.1 Description of the screens ....................................................................................................................................................... 6 2.2.2 The home screen ..................................................................................................................................................................... 6 2.2.3 Navigation screens .................................................................................................................................................................. 7 2.2.4 Operating and configuration screens ....................................................................................................................................... 8

2.2.4.1. Upper band indicators ................................................................................................................................................ 8 2.2.4.2. Upper band commands............................................................................................................................................... 9 2.2.4.3. Lower band functions................................................................................................................................................. 9

2.2.5 The dialogue boxes.................................................................................................................................................................. 9 2.2.5.1. Confirming an entry in a main screen ........................................................................................................................ 9 2.2.5.2. Entering text ............................................................................................................................................................. 10 2.2.5.3. Entering numerical values ........................................................................................................................................ 10 2.2.5.4. Selecting from a list.................................................................................................................................................. 11

2.2.6 Saving modifications............................................................................................................................................................. 11 3. Using menus ....................................................................................................................................................................................... 12

3.1. Layout of the menus .............................................................................................................................................................. 12 3.1.1 Generating set operating modes ............................................................................................................................................ 13 3.1.2 Menu layout according to operating mode............................................................................................................................ 18

3.2. Operating menus.................................................................................................................................................................... 19 3.2.1 Driving .................................................................................................................................................................................. 19 3.2.2 Function keys ........................................................................................................................................................................ 19 3.2.3 Synchronisation column........................................................................................................................................................ 19 3.2.4 Power plant measurements summary .................................................................................................................................... 19 3.2.5 Measurements ....................................................................................................................................................................... 19

3.2.5.1. Generating set electrical measurements ................................................................................................................... 19 3.2.5.2. BUSBAR/grid(s) electrical measurements ............................................................................................................... 19 3.2.5.3. Mechanical measurements ....................................................................................................................................... 19 3.2.5.4. Generating set harmonic measurements ................................................................................................................... 19 3.2.5.5. BUSBAR/grid(S) harmonic measurements.............................................................................................................. 19 3.2.5.6. Rotating field measurements .................................................................................................................................... 19 3.2.5.7. Customised display of analogue values.................................................................................................................... 19

3.2.6 Alarms and faults .................................................................................................................................................................. 19 3.2.6.1. Help .......................................................................................................................................................................... 19

3.2.7 User settings .......................................................................................................................................................................... 19 3.2.7.1. Set points .................................................................................................................................................................. 19 3.2.7.2. Power thresholds ...................................................................................................................................................... 19 3.2.7.3. Wattmetric control / General parameters.................................................................................................................. 19 3.2.7.4. Wattmetric control / Thresholds............................................................................................................................... 19 3.2.7.5. Generating set priorities ........................................................................................................................................... 19 3.2.7.6. User parameters (1/2) ............................................................................................................................................... 19 3.2.7.7. User parameters (2/2) ............................................................................................................................................... 19

3.3. Regional parameters .............................................................................................................................................................. 19 4. Generating set starting modes ............................................................................................................................................................. 19

4.1. General information............................................................................................................................................................... 19 4.2. Prerequisites .......................................................................................................................................................................... 19 4.3. Manual starting...................................................................................................................................................................... 19 4.4. Starting using the no load test function ................................................................................................................................. 19 4.5. Starting using the load test function ...................................................................................................................................... 19 4.6. Starting in automatic mode.................................................................................................................................................... 19

5. Definitions .......................................................................................................................................................................................... 19 5.1. Glossary................................................................................................................................................................................. 19

Page 4: Sdmo Kerys Control Panel Manual

2/62 33502015901_2_1

1. MICS Kerys 1.1. Aim and structure The MICS KERYS system comprises a range of electronic modules which are to be used for control and command operations, setting and protecting generating sets which stand alone or feature as part of a power plant. The system includes the following modules:

industrial programmable automatic control module (A.P.I.) All or nothing logical inputs and outputs module Analogue inputs and outputs module temperature acquisition module electrical safety module Man-Machine Interface Module adjustment module

An industrial programmable automatic control module and a Man-Machine Interface module form the basic configuration of the system. 2. Using the interface 2.1. Presentation of the keypad

Back-lit display with touch panel

Alphanumeric keypad. Navigation keys

Man Machine Interface operation indicator LED (flashing)

Generating set control keys

Signalling control keys

Page 5: Sdmo Kerys Control Panel Manual

3/62 33502015901_2_1

2.1.1 The display The display has the following specifications:

7-inch colour TFT display, 16/9, 65536 colours dimensions: 154 mm x 86 mm neon backlighting 480 x 234 resolution touch panel (8 columns x 8 rows)

2.1.2 The alphanumeric keys Pressing these keys successively allows the facial values to be entered. The characters entered appear in the order they were typed on the keypad.

Page 6: Sdmo Kerys Control Panel Manual

4/62 33502015901_2_1

2.1.3 The generating set operational keys

1 Manual mode selection. The illuminated led indicates that the mode is active 2 Selecting stop mode. The illuminated led indicates that the mode is active 3 Automatic mode selection The illuminated led indicates that the mode is active 4 Test in progress 5 In automatic mode: test sequence control

In manual mode: starting and stopping the motor 6 Generating set circuit breaker opening control 7 Open generating set circuit breaker 8 Grid circuit breaker opening control 9 Open grid circuit breaker

10 Grid circuit breaker closing control 11 Closed grid circuit breaker 12 Grid voltage status 13 Grid circuit breaker closing control 14 Closed generating set circuit breaker 15 Generating set voltage status

If test is requested a screen is brought up with the choice of a test under load or test off load.

1

2

3

5 14 15

12

13 7

6

9

8

4

11

10

Page 7: Sdmo Kerys Control Panel Manual

5/62 33502015901_2_1

2.1.4 The navigation keys These keys are described in the section on "Interface Ergonomics". 2.1.5 The signalling control keys The key is used to clear any faults

The keys stops the buzzer

The key controls the keypad indicator test.

2.2. Interface ergonomics The KERYS interface screen has a touch panel enabling various menus and commands to be accessed. The active zones on the screen are indicated by rectangles. The extended zones indicate the control keys, the recessed zones indicate the indicators. However, in some cases, the indicators allow access to menus listing general information; for example, pressing the fault indicator displays the list of alarms and faults.

15/10/02 19:10 :00 GS 1 Event archives Auto Faults Alarms

- 1 - Electrical archives

- 2 - Mechanical archives

-3 – Event metering

Warning

These keys only need to be touched briefly. If they are pressed for too long and there is a key in the same position on the new screen, the corresponding command will be performed.

Control key Key selected.

When an indicator is active, pressing one of these indicators displays the list of faults and alarms

Page 8: Sdmo Kerys Control Panel Manual

6/62 33502015901_2_1

It is also possible to navigate through the menus using the keypad.

Lastly, it is possible to access a menu directly by pressing the corresponding number key. 2.2.1 Description of the screens There are three types:

the home screen the navigation screens the operation and configuration screens

2.2.2 The home screen This screen is the entry point to the system. It enables the main functions of the navigation to be accessed.

15/10/03 19:10 :00 GS 1 Home Auto Faults Alarms

- 1 - Operation - 6 -

System

- 2 - Fault finding - 5 -

Configuration

- 3 - Archiving/Metering

- 4 - Maintenance

Scroll right

Scroll up

Scroll down Confirms the function ofthe selected key

Move up one level or quit if in dialogue box

Scroll left

Page 9: Sdmo Kerys Control Panel Manual

7/62 33502015901_2_1

2.2.3 Navigation screens These screens enable the various sub-menus to be accessed.

15/10/03 19:10 :00 GS 1 Operation Auto Faults Alarms

- 0 - Welcome

- 1 -

Operation

- 2 - Function keys

- 7 - User adjustments

- 6 - Alarms & Faults

- 4 - Central measurements

summary

- 5 - Measurements

When a key is selected the lower level sub-menu appears if available or the allocated operation screen. A sub-menu can also be accessed by pressing the corresponding numbered key.

Active menu title Upper level Lower levels

Page 10: Sdmo Kerys Control Panel Manual

8/62 33502015901_2_1

2.2.4 Operating and configuration screens These screens bring up the information and commands relating to the active menu. They are divided into three zones:

an upper band present on all types of screens the centre section in which the specific information relating to the selected menu appears a lower band

15/10/03 19:10 :00 GS 1 Event archives Auto Faults Alarms

- 1 - Electrical archives

-3 – Central measurements

summary

2.2.4.1. Upper band indicators

15/10/02 19:10 :00 GS 1 Welcome Auto Faults Alarms

Centre section Upper band

Lower band

System date

System time Number of generating set with which the man machine interface is in dialogue with

Indication of fault on the generating set concerned (flashing)

Indication of alarm on the generating set concerned (flashing)

Indication of the operating mode of the generating set concerned

Name of the active screen

Page 11: Sdmo Kerys Control Panel Manual

9/62 33502015901_2_1

2.2.4.2. Upper band commands

15/10/03 19:10:00

GS 1 Welcome

Auto Faults Alarms

2.2.4.3. Lower band functions

- 1 - Function keys

-3 – Central measurements

summary

2.2.5 The dialogue boxes To make it easier to enter information, there are special screens called "dialogue boxes" which appear if required.

2.2.5.1. Confirming an entry in a main screen When a value in the main menu has been modified the following dialogue box appears:

Validation

Validation of data entered

Confirm Esc.

The "Confirm" key saves the change, the "Esc." escape key cancels the change.

Access to the regional parameters screen Access to the regional parameters screen

Access to the operation screen

Access to the Alarms & Faults screen Access to the Alarms & Faults screen

1st action: access to the home screen 2nd action: return to previously selected

menu

If in power plant configuration, open a dialogue box enabling the generating set which you want to connect to be selected

Return to previous active operation screen

Return to the navigation menu Pressing one or more of the short cut keys directs you to the functions linked to the active screen

Page 12: Sdmo Kerys Control Panel Manual

10/62 33502015901_2_1

2.2.5.2. Entering text

Title configuration

CDE AERO

Insert Copy Paste

Confirm Delete title Delete a character Esc.

Left or right arrows on the keypad are used to move within the text. Characters are entered via alphanumeric keys on the keypad.

2.2.5.3. Entering numerical values The dialogue box heading displays the type of value entered,its unit of measurement and the variable concerned. These indications are linked to the type of modified parameter.

Time in 1/10 second (6000)

0<= 0000 <=9999

Confirm Esc.

Saves the modifications and closes the dialogue box Deletes all the text

Deletes the letter highlighted by the cursor

Closes the menu without saving the modifications.

Name of the function modified Text to be modified or created.

Inserts a space to the left of the cursor

Saves the modifications and closes the dialogue box

Closes the dialogue box without saving the modifications

When present, displays the minimum possible value

When present, displays the maximum possible value

Page 13: Sdmo Kerys Control Panel Manual

11/62 33502015901_2_1

2.2.5.4. Selecting from a list The box heading indicates the parameter which will be assigned from your selection.

Type of fault (6000)

Without General Alarm

Confirm

Esc.

2.2.6 Saving modifications After modifying a parameter, the new data is stored in volatile memory, which means that if the power supply is lost any changes will be lost. It is also necessary to transfer these values to permanent memory. This is a "Flash save" operation Following a modification, a red "Perform back-up" indicator light flashes at the top left-hand side of the screen. Pressing this indicator makes one of the following dialogue boxes appear.

Save in flash

Confirm. Esc.

Save in flash

Customer

Factory

Confirm. Esc.

Pressing "Confirm.", confirms the operation, pressing "Esc.", cancels it. While the data is being saved, a screen indicates that the operation is in progress.

List showing possible selections Arrows enabling the cursor to be moved

Active selection

Arrows visible only if the selection numbers do not remain on the screen

Page 14: Sdmo Kerys Control Panel Manual

12/62 33502015901_2_1

3. Using menus 3.1. Layout of the menus The diagram below shows the layout of the main menus.

- 1 -

Operation

- 2 -

Fault finding

- 3 -Archiving

& Metering

- 4 -

Maintenance

- 5 -

Configurations

- 6 -

System

- 0 -

Welcome

- 1.2 -Function keys

- 1.3 -

Synchro. column

- 1.4 -Central unit

measure, summary

- 1.5 -

Measurements

- 1.6 -Alarms

& faults

- 1.7 -

User adjustments

- 2.1 -

Digital I/O

- 2.2 -

Analog variables

- 2.3 -REG & PRO

variables

- 2.4 -Curves (Kerys

Tactil)

- 3.1 -

Events archives

- 3.2 -Electrical archives

- 3.3 -

Mechanical archives

- 3.4 -

Events metering

- 3.5 -Mechanical

metering

- 3.6 -Electrical metering

- 1.1 -

Operation

- 4.1 -

Provider

- 4.2 -

E-mail

- 4.3 -Serviceintervals

- 4.4 -

Consumables

- 4.5 -Progressreports

- 5.1 -

Equipment

- 5.2 -

Applications

- 5.3 -Regulations

- 5.4 -

Safety features

- 6.1 -

Regional parameters

- 6.2 -

Identification application

- 6.3 -

Software versions

- 6.4 -

Printing

- 6.5 -

Access management

- 6.6 -

Management of Web access

- 6.7 -

Factory

- 2.5 --Electrical faults

- 2.6 -

Help

- 4.6 -

Reports

- 2.7 -All or nothing personalised

display

Warning

Only the menu functions on the white background are described in this manual.

Page 15: Sdmo Kerys Control Panel Manual

13/62 33502015901_2_1

3.1.1 Generating set operating modes The operational modes are as follows:

generating set operating alone / without normal / emergency inversion (configurations A612)

generating set operating alone / with normal / emergency inversion and alternator circuit breaker (configurations A622)

generating set operating alone / generating set coupled to the network (configurations A641 / A642 / A651 / A661)

generating set operating as part of power plant / operating without shared normal/emergency switching unit. (configurations A633)

generating set operating as part of power plant / operating with shared normal/emergency switching unit. (configurations A634)

generating set operating as part of a power plant / operating with shared switching unit (configuration A635) Configuration A612

Configuration A622

Standard module

Protection card

TC: X/5A 5P5 10VA

ETHERNET Network

3Ph+N 5VA Power voltage

detection

CAN 3 bus

m m

Standard module

Protection card

TC: X/5A 5P5 10VA

ETHERNET Network

3Ph+N 5VABus CAN no. 3

m

Page 16: Sdmo Kerys Control Panel Manual

14/62 33502015901_2_1

Configuration A641

Configuration A642

Standard module

Control card

TC: X/5A 0.5 10VA

ETHERNET Network

3Ph+N 5VA

TC: X/5A 0.5 10VA

3Ph 5VA

CAN 3 bus

m

m

Standard module

Control card

ETHERNET Network

3Ph+N 5VA

3Ph 5VA

TC: X/5A 0.5 10VA

CAN 3 bus

m

m

Page 17: Sdmo Kerys Control Panel Manual

15/62 33502015901_2_1

Configuration A651

Configuration A661

Standard module

Control card

TC: X/5A 0.5 10VA

ETHERNET Network

3Ph+N 5VA

TC: X/5A 0.5 10VA

3Ph 5VA

CAN 3 bus

Circuit breaker Alternator OPTIONAL MANUAL

OR Auto

mm

Standard module

Control card

TC: X/5A 0.5 10VA

ETHERNET Network

3Ph+N 5VA

TC: X/5A 0.5 10VA

3Ph 5VA

CAN 3 bus

Circuit breaker ALTERNATOR

OPTIONAL MANUAL

OR AUTOMATIC

mm

Page 18: Sdmo Kerys Control Panel Manual

16/62 33502015901_2_1

Configuration A633

Configuration A634

Power voltage detection

Standard module

TC: X/5A 0.5 10VA

ETHERNET Network

3Ph+N 5VA

M

Control card

3Ph 5VA

Bus CAN REG

CAN 4 busCAN 3 bus

Standard module

TC: X/5A 0.5 10VA

ETHERNET Network

3Ph+N 5VA

M

Control card

3Ph 5VA

CAN 3 bus

Normal/emergency control via each base

m m

mm

Standard module

TC: X/5A 0.5 10VA

ETHERNET Network

3Ph+N 5VA

M

Control card

Standard module

TC: X/5A 0.5 10VA

ETHERNET Network

3Ph+N 5VA

M

Control card

3Ph 5VA 3Ph 5VA

Bus CAN REG

CAN 4 bus

CAN 3 bus CAN 3 bus

mm

Page 19: Sdmo Kerys Control Panel Manual

17/62 33502015901_2_1

Configuration A635

Standard module

TC: X/5A 0.5 10VA

ETHERNET Network

3Ph+N 5VA

M

Control card

3Ph 5VA

Bus CAN REG

CAN 4 busCAN 3 bus

Standard module

TC: X/5A 0.5 10VA

ETHERNET Network

3Ph+N 5VA

M

Control card

3Ph 5VA

CAN 3 bus

Standard module

Control card

3Ph 5VA

CAN 3 bus

Central measurements are required if there are several grids

ETHERNET Network

m m

mm

Page 20: Sdmo Kerys Control Panel Manual

18/62 33502015901_2_1

3.1.2 Menu layout according to operating mode The layout of the menus according to operation mode is as follows: Modes:

A612 - A622 Modes:

A633 - A634 - A635 - A641 - A642 - A651 - A661 - 0 -

Home - 0 -

Home

- 1 - Operation

- 6 - System

- 1 - Operation

- 6 - System

- 1.1 - Operation

- 6.1 - Regional

parameters

- 1.1 - Operation

- 6.1 - Regional

parameters

- 1.2 - Function keys

- 1.2 - Function keys

- 1.3 - Synchronisation

Column

- 1.4 - Central

measurements summary

- 1.4 - Central

measurements summary

- 1.5 -

Measurements - 1.5 -

Measurements

- 1.6 -

Alarms & Faults

- 1.6 - Alarms &

Faults

- 1.7 -

User settings - 1.7 -

User settings

Warning

The description of menus and associated screens refers to the above-mentioned operating modes. If there is no particular information, the menus are considered as being general and applicable to all operating modes defined above.

Page 21: Sdmo Kerys Control Panel Manual

19/62 33502015901_2_1

3.2. Operating menus The operating menus combine all the menus required for operating the generating set. Operating modes:

A633 - A634 - A635

15/10/03 19:10 :00 GS 1 Operation Auto Faults Alarms

- 0 - Welcome

- 1 -

Operation

-2-

Function keys - 7 -

User adjustments

-3-

Synchronisation column - 6 -

Alarms & Faults

-4- Central measurements

summary - 5 -

Measurements

Operating mode:

A612 - A622 - A642

15/10/03 19:10 :00 GS 1 Operation Auto Faults Alarms

- 0 - Welcome

- 1 -

Operation

-2-

Function keys - 7 -

User adjustments

- 6 -

Alarms & Faults

- 5 -

Measurements

Page 22: Sdmo Kerys Control Panel Manual

20/62 33502015901_2_1

Operating mode:

A641 - A651 - A661

15/10/03 19:10 :00 GS 1 Operation Auto Faults Alarms

- 0 - Welcome

- 1 -

Operation

-2-

Function keys - 7 -

User adjustments

-3-

Synchronisation column - 6 -

Alarms & Faults

- 5 -

Measurements

15/10/2003 00 : 00 :00 GS 1 Operation Stop Faults Alarm

Page 23: Sdmo Kerys Control Panel Manual

21/62 33502015901_2_1

3.2.1 Driving This general screen displays all the main electrical parameters of the generating set. It is the general operating and monitoring screen for the generating set. This screen can also be displayed by pressing indicator displaying the operation mode of the generating set. The frequency, U23 voltage, active and reactive power indicators, can be displayed in analog or digital form. Switching from one mode to another is performed by pressing the desired indicator.

15/10/2003 00 : 00 :00 GS 1 Operation Manu Faults Alarms

I1(A) 2701 P.F 0.9 L

Q(kVAr)

Speed (rpm) 1505 Operating time: 10:05

+Speed -Speed +U -U 765

- 1 - Function keys

- 2 - Synchronisation column

- 3 - Power plant

measurements summary

Warning

The speed and voltage adjustment buttons are only present on coupled applications in manual mode.

Generating set output position indicator

Motor rotation speed control Alternator voltage control

Page 24: Sdmo Kerys Control Panel Manual

22/62 33502015901_2_1

3.2.2 Function keys Pressing one of these keys, activates a particular function programmed in production, according to the generating set user configuration selected by the user. This menu has the additional commands required for operating the generating set. The most frequently used commands are:

Restore mains in EJP Confirm mains return Normal maintenance Forced global operation Inhibit safety features Open emergency circuit breaker Close emergency circuit breaker Open emergency circuit breaker Close normal emergency circuit breaker

It is possible to change the text describing the function of the key. The procedure is as follows: press the"title configuration " key, select the key concerned and the text box will appear. Operating modes:

A641 - A642 - A651 - A661

15/10/2003 00 :00 :00 GS 1 Function keys Stop Faults Alarms

U23(V) 0 I 1(A) 0 P.F. 0L F (Hz) 0

TCH FCT 1 (3710) TCH FCT 5 (3714) Status messages

RESTORE MAINS POWER TCH FCT 6 (3715)

TCH FCT 3 (3712) TCH FCT 7 (3716)

TCH FCT 4 (3713) Operating time 0: 00 TCH FCT 8 (3717)

Title configuration

-1- Synchronisation column

-3- Measurements

Active key Key active and selected

Page 25: Sdmo Kerys Control Panel Manual

23/62 33502015901_2_1

Operating modes:

A633 - A634 - A635

15/10/2003 00 :00 :00 GS 1 Function keys Stop Faults Alarms

U23(V) 0 I 1(A) 0 P.F. 0L F (Hz) 0

TCH FCT 1 (3710) TCH FCT 5 (3714) Status messages

TCH FCT 2 (3711) TCH FCT 6 (3715)

TCH FCT 3 (3712) TCH FCT 7 (3716)

TCH FCT 4 (3713) Operating time 0: 00 TCH FCT 8 (3717)

Title configuration

-1- Synchronisation column

-2- Central measurements

summary -3-

Measurements

Active key Key active and selected

Page 26: Sdmo Kerys Control Panel Manual

24/62 33502015901_2_1

Operating modes:

A612 - A622

15/10/2003 00 :00 :00 GS 1 Function keys Stop Faults Alarms

U23(V) 0 I 1(A) 0 P.F. 0L F (Hz) 0

TCH FCT 1 (3710) TCH FCT 5 (3714) Status messages

TCH FCT 2 (3711) TCH FCT 6 (3715)

TCH FCT 3 (3712) TCH FCT 7 (3716)

TCH FCT 4 (3713) Operating time 0: 00 TCH FCT 8 (3717)

Title configuration

-3- Measurements

Active key Key active and selected

Page 27: Sdmo Kerys Control Panel Manual

25/62 33502015901_2_1

3.2.3 Synchronisation column This screen allows the user to view the synchronisation in progress of two sources (frequency, voltage and phase deviations). Operating modes:

A633 - A634 - A635

15/10/2003 00: 00: 00 GS 1 Synchronisation column Manu Faults Alarms

Delta F Delta V

- + - +

0.00Hz 0%

+ Speed - Speed +V -V

20° 20°

+ -

TOP COUPLAGE

Synchro in progress

-1- Function keys

-2- Central unit measure.

summary -3-

Measurements

Warning

The TOP COUPLING button, the + Speed and – Speed controls, and +V –V only appear in Manual mode

Indication of frequency deviation Indication of voltage deviation

Graph showing frequency deviation Graph showing voltage deviation

Page 28: Sdmo Kerys Control Panel Manual

26/62 33502015901_2_1

Operating modes:

A641 - A 642 - A651 - A661

15/10/2003 00: 00: 00 GS 1 Synchronisation column Manu Faults Alarms

Delta F Delta V

- + - +

0.00Hz 0%

+ Speed - Speed +V -V

20° 20°

+ -

TOP COUPLAGE

Synchro in progress

-1- Function keys

-3- Measurements

Warning

The TOP COUPLING button, the + Speed and – Speed controls, and +V –V only appear in Manual mode

Indication of frequency deviation Indication of voltage deviation

Graph showing frequency deviation Graph showing voltage deviation

Page 29: Sdmo Kerys Control Panel Manual

27/62 33502015901_2_1

3.2.4 Power plant measurements summary This screen can only be accessed in "power plant" operation. It displays electrical measurement values for each generating set in the power plant as well as power plant outputs. Operating modes:

A633 - A634 - A635

15/10/2003 00 : 00: 00 GS 1Central unit

measure. summary Stop Faults Alarm

Choice of sets to display P(kW) Q(kVAR) S(kVA) I1(A) P.F.

Gen set no. 01 0 0 0 0 0L

Gen set no. 02 0 0 0 0 0L

Gen set no. 03 0 0 0 0 0L

Control unit 0 0 0

F(Hz) 0 U23(V) 0

-1-Function keys

-2-Synchro. column

-3-Measurements

14Kerys Tactyl

14Kerys

Page 30: Sdmo Kerys Control Panel Manual

28/62 33502015901_2_1

3.2.5 Measurements This command brings up a sub-menu from which the following measurements can be taken: Operating modes:

A633 - A634 - A635 - A641 - A642 - A651 - A661 Operating modes:

A612 - A622

15/10/03 19:10:00 Genset Measurements Auto Faults Alarms

- 0 - Operation

-1-

Electrical measurements

-2-

BUSBAR/Grid(s) elect. measurements

- 7 - Customised analogue

display

- 3 - Mechanical

measurements. - 6 -

Rotating fields

- 4 -

Harmonics - 5 -

Grid(s) harmonics

15/10/03 19:10:00 GS 1 Measurements Auto Faults Alarms

- 0 - Operation

-1-

Electrical measurements

-2-

BUSBAR/Grid(s) elect. measurements

- 3 - Mechanical

measurements.

Page 31: Sdmo Kerys Control Panel Manual

29/62 33502015901_2_1

3.2.5.1. Generating set electrical measurements This screen displays all the electrical measurements of the generating set:

starter battery voltage (Vbat) voltages between phases expressed in Volts (V12, V23 and V31) phase currents expressed in Amps (I12, I23 and I31) power factor (PF) frequency F expressed in Hertz active power per phase (P1, P2 and P3) expressed in kW total active power (PT1) expressed in kW reactive power per phase (Q1, Q2 and Q3) expressed in kvar total reactive power (QT) expressed in kvar active energy (AE) supplied, expressed in MWh reactive energy (RE) supplied, expressed in Mvar

Operating modes: A633 - A634 - A635 - A641 - A642 - A651 - A661

Page 32: Sdmo Kerys Control Panel Manual

30/62 33502015901_2_1

Operating modes:

A612 - A622

Page 33: Sdmo Kerys Control Panel Manual

31/62 33502015901_2_1

3.2.5.2. BUSBAR/grid(s) electrical measurements This screen enables all the grid electrical measurements to be displayed:

the starter battery voltage (Ubat) the voltages between phases expressed in (U12, U23 and U31) the phase currents expressed in Amps (I12, I23 and I31) the power factor (P.F.) the frequency expressed in Hertz the active power by phase (P1, P2 and P3) expressed in kW the total active power (PT1) expressed in kW the reactive power by phase (Q1, Q2 and Q3) expressed in kvar the total reactive power (QT) expressed in kvar

Operating modes:

A633 - A634 - A635 - A641 - A642 - A651 - A661

15/10/2003 00 : 00 :00 GS 1 BUSBAR/Grids electrical measurements Stop Faults Alarms

01

U12(V) 0 I1(A) 0 P1(kW) 0 Q1(kVAR) 0

U23(V) 0 I2(A) 0 P2(kW) 0 Q2(kVAR) 0

U31(V) 0 I3(A) 0 P3(kW) 0 Q3(kVAR) 0

P.F. 0L F (Hz) 0 PT(kW) 0 QT(kVAR) 0

-1- Electrical measurements

- 2 - Mechanical

measurements

- 3 - Grid(s) harmonics

Warning

The grid selection dialogue box is only present if the installation is managing several power supplies.

Page 34: Sdmo Kerys Control Panel Manual

32/62 33502015901_2_1

Operating mode:

A612 - A622

15/10/2003 00 : 00 :00 GS 1 BUSBAR/Grids electrical measurements Stop Faults Alarms

01

U12(V) 0 I1(A) 0 P1(kW) 0 Q1(kVAR) 0

U23(V 0 I2(A) 0 P2(kW) 0 Q2(kVAR) 0

U31(V 0 I3(A) 0 P3(kW) 0 Q3(kVAR) 0

P.F. 0L F (Hz) 0 PT1(kW) 0 QT(kVAR) 0

-1- Electrical measurements

- 2 - Mechanical

measurements

Warning

The grid selection dialogue box is only present if the installation is managing several power supplies.

Page 35: Sdmo Kerys Control Panel Manual

33/62 33502015901_2_1

3.2.5.3. Mechanical measurements This screen enables the main motor parameter values to be displayed. Operating modes:

A633 - A634 - A635 - A641 - A642 - A651 - A661

15/10/2003 00 : 00 :00 GS 1 Mechanical measurements Stop Faults Alarms

Temp. LT coolant(°C) 0.00 Oil pres. (bar) 0.00

Temp. HT Coolant(°C) 0.00 Air intake pres. (bar) 0.00

Air intake Temp.(°C) 0.00 Common rail pres. (bar) 0.00

Fuel temp. (°C) 0.00 Fuel pres. (bar) 0.00

Oil temp. (°C) 0.00

°F display Display in PSI

-1- Electrical measurements

-2- BUSBAR/grid (s)

electrical measurements - 3 -

Harmonics

In this zone, when supplied by the motor regulation system, operational information is supplied

Page 36: Sdmo Kerys Control Panel Manual

34/62 33502015901_2_1

Operating modes: A612 - A622

Warning

The type of values displayed varies according to the type of motor selected.

The “Display in …" keys enables the temperature measurements to be read in degrees Celsius or degrees Fahrenheit and the pressure measurements in bar or in PSI.

15/10/2003 00 : 00 :00 GS 1 Mechanical measurements Stop Faults Alarms

Temp. LT coolant(°C) 0.00 Oil pres. (bar) 0.00

Temp. HT Coolant(°C) 0.00 Air intake pres. (bar) 0.00

Air intake Temp.(°C) 0.00 Common rail pres. (bar) 0.00

Fuel temp. (°C) 0.00 Fuel pres. (bar) 0.00

Oil temp. (°C) 0.00

°F display Display in PSI

-1- Electrical measurements

-2- BUSBAR/grid (s)

electrical measurements

In this zone, when supplied by the motor regulation system, operational information is supplied

Page 37: Sdmo Kerys Control Panel Manual

35/62 33502015901_2_1

3.2.5.4. Generating set harmonic measurements This screen lets the user find out level 3, 5 and 7 harmonic rates on generating set currents and voltages. Operating modes:

A633 - A634 - A635 - A641 - A642 - A651 - A661

15/10/2003 00:00:00 GS 1 Genset harmonics Stop Faults Alarms

Voltages Currents

0% 0% 0% 0% 0% 0%

L1

0% 0% 0% 0% 0% 0%

L2

0% 0% 0% 0% 0% 0%

L3

3 5 7 3 5 7

- 1 Electrical measurements

- 2 - Mechanical

measurements

- 3 - Grid(s) harmonics

3.2.5.5. BUSBAR/grid(S) harmonic measurements This screen displays the emergency Bus bars or grid harmonics. Operating modes:

A633 - A634 - A635 - A641 - A642 - A651 - A661

15/10/2003 00 : 00 :00 GS 1 Grid(s) harmonics Stop Faults Alarms

Voltages Currents

0% 0% 0% 0% 0% 0%

L1

0% 0% 0% 0% 0% 0% 01

L2

0% 0% 0% 0% 0% 0%

L3

3 5 7 3 5 7

-1- BUSBAR/Grids electrical

measurements

- 2 - Mechanical

measurements

- 3 - Harmonics

Page 38: Sdmo Kerys Control Panel Manual

36/62 33502015901_2_1

3.2.5.6. Rotating field measurements This screen enables the direction of rotation for each power supply field to be compared. Operating modes:

A633 - A634 - A635 - A641 - A642 - A651 - A661

15/10/2003 00 : 00 :00 GS 1 Rotating fields Stop Faults Alarm

Grid(s) Generating set(s)

R S T R S T

01 A B C A B C

Phase sequence

Phase sequence

Inverse normal Inverse normal

-1- BUSBAR/grid (s)

electrical measurements

- 2 - Mechanical

measurements

- 3 - Harmonics

Warning

The data supplied is directly linked to the correct voltage connections on the I.A.S. inputs The user must always check that the indication is correct.

Page 39: Sdmo Kerys Control Panel Manual

37/62 33502015901_2_1

3.2.5.7. Customised display of analogue values This screen lets the user view the specific analogue values.

15/10/2003 00 : 00: 00 GS 1 Personalised analog display Stop Faults Alarm

FREE +000000 FREE +000000

FREE +000.00 FREE +000000

FREE +00.000 FREE +000000

FREE +0000.0 FREE +000000

FREE +000000 FREE +000000

FREE +000000 FREE +000000- 1

Electrical measurements-2-

Electrical measurementsJDB/Grid(s)

- 3 -Harmonics

157Kerys Tactyl

157Kerys

Warning

Each set of analogue values only appears when an associated variable has been configured

Page 40: Sdmo Kerys Control Panel Manual

38/62 33502015901_2_1

3.2.6 Alarms and faults This menu can be brought onto screen by pressing the Alarms and Faults buttons on the upper bar. This screen allows the user to view the list of faults present on the installation. The first two columns give details of the date and time that the fault appeared. The Status column shows whether or not the fault is still present: 1 = yes or 0 = no. The @ column gives the location of the variable associated with the fault. The Title column gives details of the fault. A line on a red background shows a fault, and a line on an orange background shows an alarm.

15/10/2003 00: 00: 00 GS 1 Alarms & faults Stop Faults Alarms

Date Time Status @ Title

26/11/03 11:11:12’55 1 6131 HT LOW COOLANT LEVEL FAULT

26/11/03 10:35:16’28 0 6017 INSULATION 1 ALARM

26/11/03 10:10:10’10 0 60C3 CIRCUIT BREAKER FAULT ON GENERATING SET OUTPUT

-1- Function keys

-2- Synchronisation column

-3- Central unit measure.

summary

To clear a fault, it is necessary to:

check that the fault has disappeared (status 0) and, if necessary, remove the causes of the fault select the line in question; the text on the line is displayed in white press the Reset button on the keypad, and the line is cleared

Warning

When a fault is displayed, its effect on operation remains active even if the cause has disappeared. When in Manu or Auto mode, if the user wants to clear a fault with an "In stopped" clearance mode, a screen will inform the user to switch to Stop mode.

Active line Scroll down buttons for when the list is longer than the number of lines on the

Page 41: Sdmo Kerys Control Panel Manual

39/62 33502015901_2_1

3.2.6.1. Help This screen displays possible causes of a problem and what to check.

15/10/2003 00:00:00 GS 1 Help Stop Faults Alarm

Fault number 60D6 Keywords THEN

Title ACTIVE OUTPUT MAXIMUM ALARM (32)

Possible causes

Genset overload in active power.

Check

Previous fault Search Next fault

-1- Digital I/O

-2- Curves

-3- Electrical faults

Searches can be done in two ways:

enter a keyword enter the fault number

Pressing in the "Checks" area displays a description of the checks.

15/10/2003 00:00:00 GS 1 Help Stop Faults Alarm

Fault number 60D6 Keywords THEN

Title ACTIVE OUTPUT MAXIMUM ALARM (32)

Check

Adjust output to genset capacity. Drop part of the load.

Possible causes

Previous fault Search Next fault

-1- Digital I/O

-2- Curves

-3- Electrical faults

Pressing in the "Possible causes" area displays a description of the cause. The "Search" key launches a search.

Page 42: Sdmo Kerys Control Panel Manual

40/62 33502015901_2_1

How to search: 1. Enter a keyword or fault number.

2. Launch the search by pressing on "Search".

3. When the search is over, the user can display the possible cause or what to check by pressing the appropriate icon (right of

screen).

4. The user can display the previous or next fault found by the search by using the appropriate keys. 3.2.7 User settings This command has the following options: Operating modes:

A612 - A622 - A641 - A642 - A651 - A661

15/10/2003 19:10:00 GS 1 User adjustments Auto Faults Alarms

- 0 - Operation

- 1 -

Set point

- 2 -

Power threshold

- 4 -

User parameters 1/2 - 5 -

User parameters 2/2

Page 43: Sdmo Kerys Control Panel Manual

41/62 33502015901_2_1

Operating modes:

A633 - A634

15/10/2003 00:00:00 GS 1 User adjustments Stop Faults Alarms

- 0 - Operation

- 1 -

Set point

- 2 -

Power threshold

- 3 -

Wattmeter control

- 4 -

User parameters 1/2 - 5 -

User parameters 2/2

Operating mode:

A635

15/10/2003 00:00:00 GS 1 User adjustments Stop Faults Alarms

- 0 - Operation

- 2 -

Power threshold

- 3 -

Wattmeter control

- 4 - User parameters 1/2

- 5 - User parameters 2/2

Page 44: Sdmo Kerys Control Panel Manual

42/62 33502015901_2_1

3.2.7.1. Set points This menu is used for defining set point values for adjusting the generating set. Designed for multi-voltage applications, this menu enables the required value for each set point to be defined. These values relate to the following parameters:

Generating set Grid Voltage Active power Active power Power factor Power factor Reactive power Reactive power

A green background indicates the active set point Operating modes:

A612 - A622 - A641 - A642 - A651 - A661 Voltage setting Designed for multi-voltage applications, enabling the required value for each set point to be defined. Power setting Enables the power and power factor values to be assigned for periods of operation coupled to the grid.

Grid set point: the grid supplies a fixed output and the generating set control unit provides any additional power Genset set point: the generating set supplies a fixed output and the grid provides any additional power

Page 45: Sdmo Kerys Control Panel Manual

43/62 33502015901_2_1

Operating modes:

A633 - A634 Voltage setting Designed for multi-voltage applications, enabling the required value for each set point to be defined. Power setting Enables the power and power factor values to be assigned for periods of operation coupled to the grid.

Grid set point: the grid supplies a fixed output and the generating set control unit provides any additional power Genset set point: the generating set supplies a fixed output and the grid provides any additional power

Page 46: Sdmo Kerys Control Panel Manual

44/62 33502015901_2_1

3.2.7.2. Power thresholds In this menu the threshold values are defined, which, with the digital variables, authorise the creation of additional functions linked to the generating set or grid power. The green background indicates that the threshold value has been reached or exceeded. Operating modes:

A612 - A622 - A641 - A642 - A651 - A661

05/10/2003 00 : 00 :00 GS 1 Power threshold Stop Faults Alarm

Gen set P thresholds as % of gen set Pn

4780 4781 4782 4783 4784 4785 4786 4787

10 15 20 30 40 50 75 100

Power plant P threshold as % of Power plant Pn

4788 4799 478A 478B 478C 478D 478E 478F

0 0 0 0 0 0 0 0

-1 Set points

-2- User parameters

Operating modes:

A633 - A634

05/10/2003 00 : 00 :00 GS 1 Power thresholds Stop Faults Alarm

Gen set P thresholds as % of gen set Pn

4780 4781 4782 4783 4784 4785 4786 4787

10 15 20 30 40 50 75 100

Power plant P threshold as % of Power plant Pn

4788 4799 478A 478B 478C 478D 478E 478F

10 30 45 60 75 90 105 120

-1 Set points

-2- User parameters

-3 Wattmetric control

Page 47: Sdmo Kerys Control Panel Manual

45/62 33502015901_2_1

Operating mode:

A635

05/10/2003 00 : 00 :00 GS 1 Power thresholds Stop Faults Alarm

Gen set P thresholds as % of gen set Pn

4780 4781 4782 4783 4784 4785 4786 4787

10 15 20 30 40 50 75 100

Power plant P threshold as % of Power plant Pn

4788 4799 478A 478B 478C 478D 478E 478F

10 30 45 60 75 90 105 120

-2- User parameters

-3 Wattmetric control

Page 48: Sdmo Kerys Control Panel Manual

46/62 33502015901_2_1

3.2.7.3. Wattmetric control / General parameters Operating mode:

A633 - A634 - A635 This section allows you to define the icommissioning criteria of generating sets in a power plant according to the power requirements of the installation. The setting entry fields only appear if the With Wattmeter control selection is confirmed.

15/10/2003 00:00:00 GS 1 General parameters Stop Faults Alarms

Wattmeter control Avec

Global operation time delay (sec): 70

Power on time delay (seconds) 10 Power off time delay (seconds) 10

Minimum number of GS 01 Maximum number of GS 05

Number of additional generating sets 0

-1- Generating set priority

-2- Thresholds

Global operation time delay: Time taken for all generating sets to be started and for generating sets to power the installation. Power on time delay: Time taken for the generating set to perform the power on keyway needed to power the installation. Power off time delay: Time taken for the generating set to perform the power off keyway needed to remove power from the installation. Minimum number of generating sets: Determines the minimum number of generating sets needed to start in order that the power plant can authorise the switching on of the installation. Maximum number of generating sets: All generating sets start when there is a request for emergency operation; the Wattmeter control only intervenes after an operation period allowing load stabilisation after the restart. This adjustment enables the number of generating sets starting during this sequence to be limited. Number of additional generating sets: Corresponds to the number of generating sets which have started in addition to the minimum number of generating sets needed to power the installation.

Page 49: Sdmo Kerys Control Panel Manual

47/62 33502015901_2_1

3.2.7.4. Wattmetric control / Thresholds Operating mode:

A633 - A634 - A635 Power-on thresholds These parameters are located in the left half of the on-screen configuration field. They define the active power threshold leading to an additional generating set start request. The power-on request is delayed for the duration of the time delay period to prevent the installation being started with a temporary overload, i.e. a motor starting, Power-off thresholds These parameters are located in the right half of the on-screen configuration zone. They define the active power threshold leading to the power-off request when the power consumption of an installation is reduced. If the threshold appears,the request to switch off the generating set is delayed for the duration of the time delay period.

15/10/2003 00: 00:00 GS 1 Thresholds Stop Faults Alarms

1 GS => 2 GS 0% 0 kW 2 GS => 1 GS 0% 0 kW

2 GS => 3 GS 0% 0 kW 3 GS => 2 GS 0% 0 kW

3 GS => 4 GS 0% 0 kW 4 GS => 3 GS 0% 0 kW

4 GS => 5 GS 0% 0 kW 5 GS => 4 GS 0% 0 kW

5 GS => 6 GS 0% 0 kW 6 GS => 5 GS 0% 0 kW

6 GS => 7 GS 0% 0 kW 7 GS => 6 GS 0% 0 kW

-1- General parameters

-2 Generating set priority

-3- Thresholds 2

This only appears if there are more than 7 generating sets

Page 50: Sdmo Kerys Control Panel Manual

48/62 33502015901_2_1

15/10/2003 00: 00:00 GS 1 Thresholds 2 Stop Faults Alarms

7 GS => 8 GS 0% 0 kW 8 GS => 7 GS 0% 0 kW

8 GS => 9 GS 0% 0 kW 9 GS => 8 GS 0% 0 kW

9 GS => 10 GS 0% 0 kW 10 GS => 9 GS 0% 0 kW

10 GS => 11 GS 0% 0 kW 11 GS => 10 GS 0% 0 kW

11 GS => 12 GS 0% 0 kW 12 GS => 11 GS 0% 0 kW

12 GS => 13 GS 0% 0 kW 13 GS => 12 GS 0% 0 kW

-1- Thresholds

-2- Thresholds 3

15/10/2003 00: 00:00 GS 1 Thresholds 3 Stop Faults Alarms

13 GS => 14 GS 0% 0 kW 14 GS => 13 GS 0% 0 kW

14 GS => 15 GS 0% 0 kW 15 GS => 14 GS 0% 0 kW

-1- Thresholds

-2- Thresholds 2

On each threshold screen, only generating sets which do not exceed the maximum number of generating sets are monitored on screen.

This only appears if there are more than 13 generating sets

Page 51: Sdmo Kerys Control Panel Manual

49/62 33502015901_2_1

3.2.7.5. Generating set priorities Operating mode:

A633 - A634 - A635

This function is used to select the order in which the generating sets are controlled by the Wattmetric control.

15/10/2003 00: 00:00 GS 1 Generating set priority Stop Faults Alarms

Modification

Genset selection 01

Priority selection 04

Valid Cancelling modifications

Display

Gen set 1 2 3 4 5 6 7

Priority 04 02 03 01 05 06 07

-1- General parameters

-2- Thresholds

To modify the priority level assigned to a generating set:

select the generating set (number) select the new priority confirm

The previous priority of the modified generating set is assigned to the generating set affected by this change.

Gen set 1 2 3 4 5 6 7 Before

Priority 01 02 03 04 05 06 07 After

Modified priority

04 02 03 01 05 06 07

The "Return to previous parameters" key allows the initial setting to be restored. This command is confirmed until it is saved in flash

Select the generating set of which you want to modify the priority level

New level of priority selection

The number of generating set displayed depends on the number of the generating set declared in the power plant

Displays the priority attributed to each generating set again

Page 52: Sdmo Kerys Control Panel Manual

50/62 33502015901_2_1

3.2.7.6. User parameters (1/2) This menu enables the user to modify certain settings in order to adapt operation to his requirements.

15/10/2003 00 : 00 :00 GS 1 User parameters Stop Faults Alarm

Power return confirmation request

No load test time delay (sec): 600

Power 1 Power 2

Power loss time delay (sec): 3 3

Power return time delay (sec): 30 30

Inversion in non- coupling in emergency

mode

Inversion in non-coupling in normal

mode

-1 Set points

Mains return confirmation request If the choice is "With ", when the grid voltage reappears, the mains return sequence is conditioned by additional signal.

Warning

Before confirming this selection, ensure that the equipment has been designed for this and that the command is present.

Power cut time delay Defines the time between the actual loss of the grid voltage and the beginning of the starting sequence. Mains return time delay Defines the time between the actual loss of the grid voltage and the start of the switching off sequence. If the "with mains return" selection is operational, this triggers the switching off sequence. Inversion in non-coupling in normal Enables a programme to be selected in the event of the grid synchronisation failing. If the "Without" selection is active, the installation remains supplied by the replacement power supply, if not, the installation cuts-off the supply. Inversion on non-connection in emergency Enables a program to be selected in the event of the grid synchronisation failing. If the "Without" selection is active, the installation remains supplied by the grid, if not, the installation cuts-off the replacement power supply.

WithoutWithout

Without

Without

Without

According to the number of grids managed by the system

Page 53: Sdmo Kerys Control Panel Manual

51/62 33502015901_2_1

3.2.7.7. User parameters (2/2) Access to this screen depends on the configuration.

Function (CRF/CRP): Choice of the type of coupling. This choice appears if the user has selected Long term synch (CRP) on the Configuration/Parameters/General screen. Power surge keyway (sec): Definition of the time delay associated with the power surge keyway (Range of values: 0 to 32767). Power off keyway (sec): Definition of the time delay associated with the power off keyway (Range of values: 0 to 32767). Starting mode: Choice of Starting mode. This choice is possible if the user has programmed 2 starters:

non alternating alternating

Starter priority: Choice of starter priority. This choice is possible when two starters have been configured. Pump priority: Choice of pump priority. This choice is possible when two pumps have been configured.

Page 54: Sdmo Kerys Control Panel Manual

52/62 33502015901_2_1

3.3. Regional parameters The various display parameters can be selected from this menu:

language selection for display setting the date and time setting the module synchronisation time

15/10/2003 00 : 00 :00 GS 1 Regional parameters Stop Faults Alarm

Français English Spanish Deutsch Portuguese Language option

Day Month Year Hours Minutes Seconds

26 11 03 16 20 00

Synchronisation time: 00 00

Inhibit the keys

-1- Application identification

-2- Software versions

-3- Printing

The top on the bus enables the resetting of various time settings in real time defined by the synchronisation time. To authorise cleaning the touch panel, the key inhibition function locks for approximately twenty seconds and does not register any presses on the screen. A special screen shows the time elapsing. 4. Generating set starting modes 4.1. General information The aim of this section is to describe the actions to be carried out for starting a generating set in the various possible modes:

starting in manual mode starting using the no load test function starting using the load test function starting in automatic mode

4.2. Prerequisites Make sure that you use an operational installation which includes a standard module and a KERYS IHM.

Page 55: Sdmo Kerys Control Panel Manual

53/62 33502015901_2_1

4.3. Manual starting

If faults are present, the fault management screen can be accessed by pressing the reset button.

If no faults are present, manual mode can be activated by pressing the Manu button.

Check there are no faults :

grey: no fault. red: fault present.

grey: no alarm. red: alarm present.

Page 56: Sdmo Kerys Control Panel Manual

54/62 33502015901_2_1

The manual starting phase will begin once button 1 in the test unit is pressed. The starting request is maintained until the generating set group starts. This method may not under any circumstances be used to turn the motor over.

During the starting phase and until the alternator voltage stabilises, the green LED underneath the generating set symbol flashes, and then lights up permanently once the phase is complete.

The generating set may be stopped at any time by pressing the stop button or the 0 button in the test unit. The green LED underneath the generating set symbol goes out to indicate that the generating set has stopped.

Page 57: Sdmo Kerys Control Panel Manual

55/62 33502015901_2_1

4.4. Starting using the no load test function

If faults are present, the fault management screen can be accessed by pressing the reset button.

If no faults are present, automatic mode can be activated by pressing the Auto button.

Check there are no faults:

grey: no fault. red: fault present.

grey: alarm not present. red: alarm present.

Page 58: Sdmo Kerys Control Panel Manual

56/62 33502015901_2_1

The test starting phase will then begin once button 1 of the test unit is pressed.

If you press button 1 on the test unit, the following window will appear in which the type of test can be selected.

15/10/2003 00: 00:00 GS 1 Operation Manu Faults Alarms

I1(A) 2701 P.F 0.9 L

Q(kVAr)

Speed (rpm) 1505 Operating time: 10:05

+ Speed - Speed +U -U 765

- 1 - Function keys

- 2 - Synchronisation column

- 3 - Power plant

measurements summary Using the KERYS touch-sensitive Man-Machine Interface, the no load test is started by pressing the corresponding touch key. The orange LED in the test unit lights up permanently once the test is confirmed During the starting phase and until the alternator voltage stabilises, the green LED underneath the generating set symbol flashes, and then lights up permanently once the phase is complete.

Test selected

Select the test to be carried out

Under load test Esc No load

test

Page 59: Sdmo Kerys Control Panel Manual

57/62 33502015901_2_1

The generating set may be stopped at any time by pressing the stop button or the 0 button in the test unit. The generating set will stop automatically once the no load test is complete (600 seconds by default).

The green LED underneath the generating set symbol goes out to indicate that the generating set has stopped.

Page 60: Sdmo Kerys Control Panel Manual

58/62 33502015901_2_1

4.5. Starting using the load test function

If faults are present, the fault management screen can be accessed by pressing the reset button.

If no faults are present, automatic mode can be activated by pressing the Auto button.

Check there are no faults:

grey: no fault. red: fault present.

grey: alarm not present. red: alarm present.

Page 61: Sdmo Kerys Control Panel Manual

59/62 33502015901_2_1

The test starting phase will then begin once button 1 of the test unit is pressed.

If you press button 1 in the test unit, the following window will appear in which the type of test can be selected.

15/10/2003 00: 00:00 GS 1 Operation Manu Faults Alarms

I1(A) 2701 P.F 0.9 L

Q(kVAr)

Speed (rpm) 1505 Operating time: 10:05

+ Speed - Speed +U -U 765

- 1 - Function keys

- 2 - Synchronisation column

- 3 - Power plant

measurements summary Using the KERYS touch-sensitive Man-Machine Interface, the no load test is started by pressing the corresponding touch key. The orange LED in the test unit lights up permanently once the test is confirmed During the starting phase and until the alternator voltage stabilises, the green LED underneath the generating set symbol flashes, and then lights up permanently once the phase is complete.

The installation is then controlled via the automatic systems in accordance with the configuration of the application:

inversion of normal/emergency supply grid coupling etc

Test selected

Select the test to be carried out

Under load test Esc No load

test

Page 62: Sdmo Kerys Control Panel Manual

60/62 33502015901_2_1

The generating set may be stopped at any time by pressing the stop button or the 0 button in the test unit.

Important: Pressing the stop button may cause an interruption in the power supply depending on its status when the button is pressed (e.g. isolated grid operation) The generating set will stop after a cooling delay (180 seconds by default). The green LED underneath the generating set symbol goes out to indicate that the generating set has stopped.

Page 63: Sdmo Kerys Control Panel Manual

61/62 33502015901_2_1

4.6. Starting in automatic mode In AUTO mode, except for during the test functions, the generating set starts as a result of an external command which may be triggered by various sources:

power loss EJP command (France only) customer command

The installation is then controlled via the automatic systems in accordance with the configuration of the application:

inversion of normal/emergency source grid coupling etc

The generating set may be stopped at any time by pressing the 0 button in the test unit.

Important: Pressing the stop button may cause an interruption in the power supply depending on its status when the button is pressed (e.g. isolated grid operation) The generating set will stop after a cooling delay (180 seconds by default). The green LED underneath the generating set symbol goes out to indicate that the generating set has stopped.

Page 64: Sdmo Kerys Control Panel Manual

62/62 33502015901_2_1

5. Definitions 5.1. Glossary

I.A.S. Industrial Automated System Coupling Grouping together of more than one power supply on the same distribution grid

I.H.M. Man Machine Interface. Tool enabling data to be exchanged between the user and the machine

I.N.S.

Emergency/Normal Switching Describes the device (switch) which enables the installation to be supplied by the grid (normal) or by the replacement power supply (emergency) or the operation (switching) from one power-supply to the other with a cut-off in supply to the installation

Led Light-emitting diode

Synchronisation Continuous operation to equalise the voltage and frequency of several electrical supplies before linking them to the same Bus bars

Page 65: Sdmo Kerys Control Panel Manual