schneider-electric.com | erie vt/vs poptop erie™ vt/vs

4
© 2019 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. May, 2019 tc Document Number: F-27204-8 www.schneider-electric.com schneider-electric.com | 1 Selection Guide Erie™ VT/VS PopTop™ Series Two-Position Spring Return Valves General & High Close-Off PopTop Zone Valves VT/VS Series with General Close-Off Actuator VT/VS Series with High Close-Off Actuator Specifications Valve Service Hot and chilled water models, up to 50% glycol. Steam models up to 15 psi (both valve body and valve actuator must be rated for high temperature) System Static Pressure Limits 400 psi (2758 kPa) Close-off Refer to Table 2 Fluid/Ambient Temperature Limits Refer to Table 1 Seat Leakage ANSI class IV (0.01%) with pressure at inlet (B-port/A-port, if 3-way) Body Forged brass Stem Nickel-plated Seat Brass Paddle (VT series) Buna N Paddle (VS series) Highly saturated nitrile Actuator Voltage 24 Vac @ 50/60 Hz, 110 Vac @ 50 Hz and 120 Vac @ 60 Hz, 230 Vac @ 50 Hz, 240 Vac @ 60 Hz, 208 Vac @ 50/60 Hz., 277 Vac @50/60 Hz. Power Requirements 6.5 watts, 7.5 Va End Switch, 24 -240 Vac Models 24 to 250 Vac/101 mA min. to 5 A max. and 9…30 Vdc @ 100 mA max. 277 Vac Models 277 Vac/101mA min. to 5A max. Control Signal On/off, 2 position, spring return Timing Full Open to Full Close 25 Sec max for 60 Hz; 30 Sec max for 50 Hz; and 9 Sec max spring return Materials Base Plate Stainless steel Cover aluminum Ambient Temperature Limits Shipping & Storage -40…160 °F (-40…71 °C) Operating Refer to Table-1 Humidity 5 to 95% relative humidity non-condensing Agency Listings Refer to product label Shipping Weight (Actuator/Valve Assembly) 2.25 lbs (1020 g). Table 1 Valve Body and Actuators Model Chart Model Temperature Range VTXXXX 32 to 200 ×F (fluid) @ 104 ×F (Ambient) (0 to 93 ×C @ 40 ×C) VSXXXX 32 to 250 ×F (fluid) @ 169 ×F (Ambient) (0 to 121 ×C @ 76 ×C), and/or 15 PSI (103 kPa) Steam a AXX3XXX 32 to 200 ×F (fluid) @ 104 ×F (Ambient) (0 to 93 ×C @ 40 ×C) AXX4XXX 32 to 250 ×F (fluid) @ 169 ×F (Ambient) (0 to 121 ×C @ 76 ×C), and/or 15 PSI (103 kPa) Steam a a - For steam applications both valve body and valve actuator must be rated for high temperature. Example: VS2213G14A020 = Assembly. VS2213 = Valve body. G14A020 = Actuator Table 2 Flow Coefficients and Maximum Close-Off Pressure Differential Valve 2-way 3-way (G) a Close-Off (H) b PSI Close-off Size Cv (kv) Cv (kv) DP PSI (kPa) DP (kPa) 1/2” 1.0 (0.9) 1.5 (30) 60 (414) 75 (517) 3/4” 1.0 (0.9) 1.5 (30) 60 (414) 75 (517) 1/2” 2.5 (2.2) 3.0 (2.6) 40 (276) 50 (344) 3/4” 2.5 (2.2) 3.0 (2.6) 40 (276) 50 (344) 1/2” 3.5 (3.0) 4.0 (3.4) 25 (172) 30 (208) 3/4” 3.5 (3.0) 4.0 (3.4) 25 (172) 30 (208) 1” 3.5 (3.0) 4.0 (3.4) 25 (172) 30 (208) 3/4” 5.0 (4.3) 5.0 (4.3) 20 (137) 25 (172) 1” 5.0 (4.3) 5.0 (4.3) 20 (137) 25 (172) 3/4” 7.5 (6.5) 7.5 (6.5) 17 (117) 20 (137) 1” 8.0 (6.9) 8.0 (6.9) 17 (117) 20 (137) 1-1/4” 8.0 (6.9) 8.0 (6.9) 17 (117) 20 (137) Accessories for Inverted Flare Connection Valves 3/4” inverted flare bodies accept the following adapters to copper pipe: 436-214-1 Union nut & elbow assembly, female for 1/2” (5/8” O.D. copper, 15/16” long 436-220 Union nut & coupling assembly, female for 1/2” (5/8” O.D.) copper, 1-1/16” long 436-252 Union nut & coupling assembly, female for 3/4” (7/8” O.D.) copper, 1-27/32” long 436-229-3 Union nut & nipple assembly, male for 1/2” (5/8” O.D.) copper, 3” long 436-214-4 Union nut & elbow assembly, male for 1/2” (5/8” O.D.) copper, 1-15/16” long 436-256 Union nut & coupling assembly, female for 1” (1-1/8” O.D.) copper, 1-3/8” long

Upload: others

Post on 14-May-2022

7 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: schneider-electric.com | Erie VT/VS PopTop Erie™ VT/VS

© 2019 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. May, 2019 tcDocument Number: F-27204-8

www.schneider-electric.com

schneider-electric.com | 1Selection Guide

Erie™ VT/VS PopTop™ Series Two-Position Spring Return Valves General & High Close-Off PopTop Zone Valves

Printed in U.S.A. 6-16 © Copyright 2016 Schneider Electric All Rights Reserved. F-27204-7

SPECIFICATIONS Valve

Service Hot and chilled water models, up to 50% glycol. Steam models up to 15 psi (both valve body and valve actuator must be rated for high temperature).System Static Pressure Limits 400 psi (2758 kPa).Close-off Refer to Table-2.Fluid/Ambient Temperature Limits Refer to Table-1.Seat Leakage ANSI class IV (0.01%) with pressure at inlet (B-port/A-port, if 3-way).

Body Forged brass.Stem Nickel-plated.Seat Brass.Paddle (VT series) Buna N.Paddle (VS series) Highly saturated nitrile.

ActuatorVoltage 24 Vac @ 50/60 Hz, 110 Vac @ 50 Hz and 120 Vac @ 60 Hz, 230 Vac @ 50 Hz, 240 Vac @ 60 Hz, 208 Vac @ 50/60 Hz., 277 Vac @50/60 Hz.Power Requirements 6.5 watts, 7.5 Va.End Switch, 24 -240 Vac Models: 24 to 250 Vac/101 mA min. to 5 A max. and 9 to 30 Vdc @ 100 mA max. 277 Vac Models: 277 Vac/101mA min. to 5A max.Control Signal On/off, 2 position, spring return.Timing, Full Open to Full Close 25 Sec max for 60 Hz; 30 Sec max for 50 Hz; and 9 Sec max spring return.Materials Stainless steel base plate, aluminum cover.Ambient Temperature Limits:

Shipping & Storage -40 to 160 °F (-40 to 71 °C).Operating Refer to Table-1.

Humidity 5 to 95% relative humidity, non-condensing.Agency Listings Refer to your individual product label.Shipping Weight (Actuator/Valve Assembly) 2.25 lbs (1020 g).

Table-1 Valve Body and Actuators Model Chart

a: For steam applications both valve body and valve actuator must be rated for high temperature.Example: VS2213G14A020 = Assembly. VS2213 = Valve body. AG14A020 = Actuator.

Model Temperature Range

VTXXXX 32 to 200 ×F (fluid) @ 104 ×F (Ambient)(0 to 93 ×C @ 40 ×C)

VSXXXX32 to 250 ×F (fluid) @ 169 ×F (Ambient)

(0 to 121 ×C @ 76 ×C), and/or 15 PSI (103 kPa) Steama

AXX3XXX 32 to 200 ×F (fluid) @ 104 ×F (Ambient)(0 to 93 ×C @ 40 ×C)

AXX4XXX32 to 250 ×F (fluid) @ 169 ×F (Ambient)

(0 to 121 ×C @ 76 ×C), and/or 15 PSI (103 kPa) Steama

Table-2 Flow Coefficients and Maximum Close-Off Pressure Differential

Accessories for Inverted Flare Connection Valves3/4" inverted flare bodies accept the following adapters to copper pipe:

436-214-1 Union nut & elbow assembly, female for 1/2"(5/8" O.D.) copper, 15/16" long436-220 Union nut & coupling assembly, female for 1/2"(5/8" O.D.) copper, 1-1/16" long436-252 Union nut & coupling assembly, female for 3/4"(7/8" O.D.) copper, 1-27/32" long436-229-3 Union nut & nipple assembly, male for 1/2"(5/8" O.D.) copper, 3" long436-214-4 Union nut & elbow assembly, male for 1/2"(5/8" O.D.) copper, 1-15/16" long436-256 Union nut & coupling assembly, female for 1"(1-1/8" O.D.) copper, 1-3/8" long

Valve Size

2-way Cv (kv)

3-way Cv(kv)

(G)a Close-Off DPPSI (kPa)

a G = General close off actuator

(H)b PSI Close-Off DP (kPa)

b H = High close off actuator

1/2"1.0 (0.9) 1.5 (30) 60 (414) 75 (517)

3/4"1/2"

2.5 (2.2) 3.0 (2.6) 40 (276) 50 (344)3/4"1/2"

3.5 (3.0) 4.0 (3.4) 25 (172) 30 (208)3/4"1"

3/4"5.0 (4.3) 5.0 (4.3) 20 (137) 25 (172)

1"3/4" 7.5 (6.5) 7.5 (6.5) 17 (117) 20 (137)1"

8.0 (6.9) 8.0 (6.9) 17 (117) 20 (137)1-1/4"

Erie™ VT/VS PopTop™ SeriesTwo Position Spring Return Valves

General & High Close-Off PopTop Zone ValvesInstallation Instructions

VT/VS Series with General Close-Off Actuator

VT/VS Series with High Close-Off Actuator

Specifications

ValveService Hot and chilled water models, up to 50% glycol. Steam models up to 15 psi (both valve body and valve actuator must be rated for high temperature)System Static Pressure Limits 400 psi (2758 kPa)Close-off Refer to Table 2Fluid/Ambient Temperature Limits Refer to Table 1Seat Leakage ANSI class IV (0.01%) with pressure at inlet (B-port/A-port, if 3-way)Body Forged brass Stem Nickel-plated Seat Brass Paddle (VT series) Buna N Paddle (VS series) Highly saturated nitrile

ActuatorVoltage 24 Vac @ 50/60 Hz, 110 Vac @ 50 Hz and 120 Vac @ 60 Hz, 230 Vac @ 50 Hz, 240 Vac @ 60 Hz, 208 Vac @ 50/60 Hz., 277 Vac @50/60 Hz.Power Requirements 6.5 watts, 7.5 Va End Switch, 24 -240 Vac Models 24 to 250 Vac/101 mA min. to 5 A max. and 9…30 Vdc @ 100 mA max. 277 Vac Models 277 Vac/101mA min. to 5A max.Control Signal On/off, 2 position, spring returnTiming Full Open to Full Close 25 Sec max for 60 Hz; 30 Sec max for 50 Hz; and 9 Sec max spring returnMaterials Base Plate Stainless steel Cover aluminumAmbient Temperature Limits Shipping & Storage -40…160 °F (-40…71 °C) Operating Refer to Table-1 Humidity 5 to 95% relative humidity non-condensingAgency Listings Refer to product labelShipping Weight (Actuator/Valve Assembly) 2.25 lbs (1020 g).

Table 1 Valve Body and Actuators Model Chart Model Temperature Range VTXXXX 32 to 200 ×F (fluid) @ 104 ×F (Ambient) (0 to 93 ×C @ 40 ×C) VSXXXX 32 to 250 ×F (fluid) @ 169 ×F (Ambient) (0 to 121 ×C @ 76 ×C), and/or 15 PSI (103 kPa) Steama AXX3XXX 32 to 200 ×F (fluid) @ 104 ×F (Ambient) (0 to 93 ×C @ 40 ×C) AXX4XXX 32 to 250 ×F (fluid) @ 169 ×F (Ambient) (0 to 121 ×C @ 76 ×C), and/or 15 PSI (103 kPa) Steama

a - For steam applications both valve body and valve actuator must be rated for high temperature. Example:

VS2213G14A020 = Assembly. VS2213 = Valve body. G14A020 = Actuator

Table 2 Flow Coefficients and Maximum Close-Off Pressure Differential Valve 2-way 3-way (G)a Close-Off (H)b PSI Close-off Size Cv (kv) Cv (kv) DP PSI (kPa) DP (kPa) 1/2” 1.0 (0.9) 1.5 (30) 60 (414) 75 (517) 3/4” 1.0 (0.9) 1.5 (30) 60 (414) 75 (517) 1/2” 2.5 (2.2) 3.0 (2.6) 40 (276) 50 (344) 3/4” 2.5 (2.2) 3.0 (2.6) 40 (276) 50 (344) 1/2” 3.5 (3.0) 4.0 (3.4) 25 (172) 30 (208) 3/4” 3.5 (3.0) 4.0 (3.4) 25 (172) 30 (208) 1” 3.5 (3.0) 4.0 (3.4) 25 (172) 30 (208) 3/4” 5.0 (4.3) 5.0 (4.3) 20 (137) 25 (172) 1” 5.0 (4.3) 5.0 (4.3) 20 (137) 25 (172) 3/4” 7.5 (6.5) 7.5 (6.5) 17 (117) 20 (137) 1” 8.0 (6.9) 8.0 (6.9) 17 (117) 20 (137) 1-1/4” 8.0 (6.9) 8.0 (6.9) 17 (117) 20 (137)

Accessories for Inverted Flare Connection Valves3/4” inverted flare bodies accept the following adapters to copper pipe:436-214-1 Union nut & elbow assembly, female for 1/2” (5/8” O.D.

copper, 15/16” long436-220 Union nut & coupling assembly, female for 1/2” (5/8”

O.D.) copper, 1-1/16” long436-252 Union nut & coupling assembly, female for 3/4” (7/8”

O.D.) copper, 1-27/32” long436-229-3 Union nut & nipple assembly, male for 1/2” (5/8” O.D.)

copper, 3” long436-214-4 Union nut & elbow assembly, male for 1/2” (5/8” O.D.)

copper, 1-15/16” long436-256 Union nut & coupling assembly, female for 1” (1-1/8” O.D.)

copper, 1-3/8” long

Page 2: schneider-electric.com | Erie VT/VS PopTop Erie™ VT/VS

2 | schneider-electric.com

May, 2019 tc © 2019 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. Document Number: F-27204-8

Typical Application (Wiring Diagram)

2 © Copyright 2016 Schneider Electric All Rights Reserved. F-27204-7

TYPICAL APPLICATION (wiring diagram)

To Aux. Circuit

Motor

End SwitchRed

To Aux. Circuit

RedBlack

BlackL1(HOT)

L2

Erie Wire Leads

Motor

THERMOSTAT

THERMOSTAT

THL1

(HOT)

L2

Honeywell - Terminal Block

Erie Terminal Block

ES ES

To Aux. Circuit24 V 5A max

THERMOSTAT

TH

L1(HOT)

L2 MotorTH

TR

ESES

TH

TRTH

TR

TR

End

Switc

h

End Switch

Motor

End SwitchRed

To Aux. Circuit

RedBlack

BlackL1(HOT)

L2

Honeywell - Wire LeadsTHERMOSTAT

Figure-1 Typical Wiring of a PopTop to Replace a Honeywell Valve.

Erie Terminal Block

Erie Wire Leads

564

White - Rodgers (1311 or 1321)

L1(Hot)

L2

MotorEnd Switch To Aux. Circuit

6 54

321

546

To Aux. Circuit24 V 5A max

THERMOSTAT

THERMOSTAT

Motor

End SwitchRed

RedBlack

BlackL1(Hot)

L2

564

THERMOSTAT

TH

L1(HOT)

L2 Motor

TR

ESES

TH

End Switch

THTR

To Aux. Circuit

Figure-2 Typical Wiring of a PopTop to Replace a Flair or White-Rodgers 3-Wire Valve.

To Aux. Circuit

Motor

THERMOSTAT

THERMOSTAT

L1(HOT)

L2

Flair - Terminal Block

1 4 5

2

3To Aux. Circuit

Motor

THERMOSTAT

THERMOSTAT

L1(HOT)

L2

Taco - Terminal Block

1

2

3

Erie Wire LeadsErie Wire Leads

Erie Terminal Block

Motor

End SwitchRed

To Aux. Circuit

Red

Black

BlackL1(HOT)

L2Motor

End SwitchRed

To Aux. Circuit

RedBlack

BlackL1(HOT)

L2

To Aux. Circuit24 V 5A max

THERMOSTAT

L1(HOT)

L2 Motor

TR

ESES

TH

End Switch

TRTH

Figure-3 Typical Wiring of a PopTop to Replace a Flair or Taco 3-Wire Valve.

Thermostat

T1

T2

Valve #1

Valve #2

BURNER

CONTROL

TH

TR ES

ESTH/TR

T

T

L1

L2

TH

TR ES

ESTH/TR

Figure-4 Typical Multiple Valve Wiring.

Page 3: schneider-electric.com | Erie VT/VS PopTop Erie™ VT/VS

schneider-electric.com | 3

© 2019 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. May, 2019 tcDocument Number: F-27204-8

Installation

InspectionInspect the package for damage. If package is damaged, notify the appropriate carrier immediately. If undamaged, open the package and inspect the device for obvious damage. Return damaged products.

RequirementsTools (not provided)• Wrench 1 to 1-5/8” (if threaded valve)• Soldering equipment (if sweat fit) or flare• Training: Installer must be a qualified, experienced

technician• Other accessories as appropriate

PrecautionsNotice: Electrical shock hazard. Disconnect power before installation to prevent electrical shock or equipment damage. • Make all connections in accordance with the electrical

wiring diagram and in accordance with national and local electrical codes. Use copper conductors only.

• All conductors shall be provided with insulation rated for the highest voltage motor and end switch circuits.

• Avoid locations where excessive moisture, corrosive fumes, explosive vapors, or vibration are present.

• Avoid electrical noise interference. Do not install near large conductors, electrical machinery, or welding equipment.

• When making lead connections within the actuator, use caution not to put leads or connectors below the motor.

MountingThe valves can be mounted in horizontal or vertical piping. When installed in horizontal piping, the actuator must be above the valve body. Refer to Figure-5. When installed in horizontal piping the actuator can be tilted left or right but it must not be tilted below 85° from vertical.

F-27204-7 © Copyright 2016 Schneider Electric All Rights Reserved. 3

INSTALLATION

InspectionInspect the package for damage. If package is damaged, notify the appropriate carrier immediately. If undamaged, open the package and inspect the device for obvious damage. Return damaged products.

Requirements• Tools (not provided)

— Wrench 1 to 1-5/8" (if threaded valve)— Soldering equipment (if sweat fit) or flare

• Training: Installer must be a qualified, experienced technician• Other accessories as appropriate

Precautions

General W A R N I N G

• Electrical shock hazard! Disconnect power before installation to prevent electrical shock or equipment damage.

• Make all connections in accordance with the electrical wiring diagramand in accordance with national and local electrical codes. Use copperconductors only.

• All conductors shall be provided with insulation rated for the highestvoltage motor and end switch circuits.

C A U T I O N• Avoid locations where excessive moisture, corrosive fumes, explosive

vapors, or vibration are present.

• Avoid electrical noise interference. Do not install near large conductors, electrical machinery, or welding equipment.

• When making lead connections within the actuator, use caution not toput leads or connectors below the motor.

Mounting

The valves can be mounted in horizontal or vertical piping. When installed in horizontal piping, the actuator must be above the valve body. Refer toFigure-5. When installed in horizontal piping the actuator can be tilted leftor right but it must not be tilted below 85° from vertical.

N O T E• Make certain there is no overhead water source that may drip onto valve

actuator.

• In normal service, some condensation may occur on or around thevalve. A drip pan may be necessary or the valve body may be insulated.

PipingThese valves must be piped so the paddle closes against the direction of flow. Flow is from B to A. Refer to Figure-6a toFigure-6f. When installing the actuator to a normally closed valve, the actuator must be placed in the manually open position by using the manual operating lever. The first time the valve is operated electrically, the manual operating lever of the actuator will transfer to the automatic position. The manual operating lever can be used to allow flushing of the system after installation. The valves are designed for application in closed hydronic heating and cooling systems. High levels of dissolved oxygen and chlorine found in open systems may attack the valve materials and result in premature failure. Install over a drip pan if condensation in chilled water applications occurs.

C A U T I O NUse in systems which have substantial make-up water (open systems) is not recommended. Follow proper water treatment practices and system procedures. Refer to document F-26080-1 for Water and Steam EN205 Guidelines.

N O T E• Three-way valves always require a normally closed actuator.• Three-way valves are always closed at the B port when no power is

applied to the motor.• On power-up the valve closes to A port on three-way valves.• Orient the three-way valve body as needed for normally open or

normally closed flow through coil.

85

360

Figure-5 Mounting Position.

POWEROFF

A BCoil

POWEROFF

ABCoil

POWEROFF

ABCoil

POWEROFF

ABCoil

Figure-6b 2-Way Valve With Normally Open

Actuator.

Figure-6a 2-Way Valve With Normally Closed

Actuator.

Figure-6c 3-Way Valve in Mixing Configuration

Normally Closed to the Coil.

Figure-6d 3-Way Valve in Mixing Configuration

Normally Open to the Coil.

POWEROFF

ABCoil

A B

POWEROFF

Coil

Figure-6e 3-Way Valve in Diverting Configuration Normally Closed to the

Coil.

Figure-6f 3-Way Valve in Diverting Configuration Normally Open to the

Coil.

Make certain there is no overhead water source that may drip onto valve actuator.

In normal service, some condensation may occur on or around the valve. A drip pan may be necessary or the valve body may be insulated.

PipingThese valves must be piped so the paddle closes against the direction of flow. Flow is from B to A. Refer to Figure-6a to

Figure-6f.

F-27204-7 © Copyright 2016 Schneider Electric All Rights Reserved. 3

INSTALLATION

InspectionInspect the package for damage. If package is damaged, notify the appropriate carrier immediately. If undamaged, open the package and inspect the device for obvious damage. Return damaged products.

Requirements• Tools (not provided)

— Wrench 1 to 1-5/8" (if threaded valve)— Soldering equipment (if sweat fit) or flare

• Training: Installer must be a qualified, experienced technician• Other accessories as appropriate

Precautions

General W A R N I N G

• Electrical shock hazard! Disconnect power before installation to prevent electrical shock or equipment damage.

• Make all connections in accordance with the electrical wiring diagramand in accordance with national and local electrical codes. Use copperconductors only.

• All conductors shall be provided with insulation rated for the highestvoltage motor and end switch circuits.

C A U T I O N• Avoid locations where excessive moisture, corrosive fumes, explosive

vapors, or vibration are present.

• Avoid electrical noise interference. Do not install near large conductors, electrical machinery, or welding equipment.

• When making lead connections within the actuator, use caution not toput leads or connectors below the motor.

Mounting

The valves can be mounted in horizontal or vertical piping. When installed in horizontal piping, the actuator must be above the valve body. Refer toFigure-5. When installed in horizontal piping the actuator can be tilted leftor right but it must not be tilted below 85° from vertical.

N O T E• Make certain there is no overhead water source that may drip onto valve

actuator.

• In normal service, some condensation may occur on or around thevalve. A drip pan may be necessary or the valve body may be insulated.

PipingThese valves must be piped so the paddle closes against the direction of flow. Flow is from B to A. Refer to Figure-6a toFigure-6f. When installing the actuator to a normally closed valve, the actuator must be placed in the manually open position by using the manual operating lever. The first time the valve is operated electrically, the manual operating lever of the actuator will transfer to the automatic position. The manual operating lever can be used to allow flushing of the system after installation. The valves are designed for application in closed hydronic heating and cooling systems. High levels of dissolved oxygen and chlorine found in open systems may attack the valve materials and result in premature failure. Install over a drip pan if condensation in chilled water applications occurs.

C A U T I O NUse in systems which have substantial make-up water (open systems) is not recommended. Follow proper water treatment practices and system procedures. Refer to document F-26080-1 for Water and Steam EN205 Guidelines.

N O T E• Three-way valves always require a normally closed actuator.• Three-way valves are always closed at the B port when no power is

applied to the motor.• On power-up the valve closes to A port on three-way valves.• Orient the three-way valve body as needed for normally open or

normally closed flow through coil.

85

360

Figure-5 Mounting Position.

POWEROFF

A BCoil

POWEROFF

ABCoil

POWEROFF

ABCoil

POWEROFF

ABCoil

Figure-6b 2-Way Valve With Normally Open

Actuator.

Figure-6a 2-Way Valve With Normally Closed

Actuator.

Figure-6c 3-Way Valve in Mixing Configuration

Normally Closed to the Coil.

Figure-6d 3-Way Valve in Mixing Configuration

Normally Open to the Coil.

POWEROFF

ABCoil

A B

POWEROFF

Coil

Figure-6e 3-Way Valve in Diverting Configuration Normally Closed to the

Coil.

Figure-6f 3-Way Valve in Diverting Configuration Normally Open to the

Coil.

When installing the actuator to a normally closed valve, the ac-tuator must be placed in the manually open position by using the manual operating lever. The first time the valve is operated electrically, the manual operating lever of the actuator will transfer to the automatic position. The manual operating lever can be used to allow flushing of the system after installation. The valves are designed for application in closed hydronic heating and cooling systems. High levels of dissolved oxygen and chlorine found in open systems may attack the valve ma-terials and result in premature failure. Install over a drip pan if condensation in chilled water applications occurs.

Use in systems which have substantial make-up water (open systems) is not recommended. Follow proper water treat-ment practices and system procedures. Refer to document F-26080-1 for Water and Steam EN205 Guidelines.

Three-way valves always require a normally closed actuator.

Three-way valves are always closed at the B port when no power is applied to the motor.

On power-up the valve closes to A port on three-way valves.

Orient the three-way valve body as needed for normally open or normally closed flow through coil.

Sweat ConnectionsNotice: Do not solder with actuator in place, or with paddle against seat, as the heat can damage the unit. Before sol-dering, move the manual open lever into Open position then remove the actuator from the body. Orient paddle so it is not

Page 4: schneider-electric.com | Erie VT/VS PopTop Erie™ VT/VS

4 | schneider-electric.com

May, 2019 tc © 2019 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. Document Number: F-27204-8

© Copyright 2016, Schneider Electric All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.

F-27204-7

North America (USA): +1 888 444 1311Europe, Middle East & Africa (Sweden): +46 10 478 2000 Asia Pacific (Singapore): +65 6484 7877product.support@schneider-electric.comwww.schneider-electric.com

Sweat Connections C A U T I O N

Do not solder with actuator in place, or with paddle against seat, as the heat can damage the unit. Before soldering, move the manual open lever into Open position then remove the actuator from the body. Orient paddle so it is not against a seat.

Use lead or tin based solder with melting point below 600 °F. Do not overheat. Direct flame tip away from valve. Cool valve quickly with a wet cloth.Body assembly can be submerged for leak testing prior to attaching the actuator.

Threaded ConnectionApply Teflon tape to all but the last two threads of male pipe thread. Hand screw the pipe into the valve, turning it as far as it will go. Use a wrench to fully tighten the valve to the pipe. Do not over tighten or strip the threads.

Inverted Flare Union ConnectionSolder fittings onto pipe. Use solder with melting point below 600°F. Mount valve to union nuts.

Installing Actuator on Valve BodySlowly latch the manual operating lever in the open, engaged position (AG1 or AH1 only). Depress the release button (see Figure-7). Align the body

with the actuator to ensure the stem is inserted into the large mating hole on the bottom side of the actuator. Engage the actuator on the body and release the button.

C A U T I O NDo not use the valve body to manually open the actuator as damage to the valve actuator will result.

CHECKOUT1. Make sure the valve stem rotates freely before and after installing the

actuator.2. If the stem does not operate freely it may indicate that the stem was

damaged and may require that the valve be repaired or replaced.3. After the piping is under pressure, check the valve body and the

connections for leaks.4. After the valve and actuator are installed, power the actuator and check

the operation.

THEORY OF OPERATIONPopTop Series are two position spring return valves. When powered, the actuator moves to the desired position, tensing the spring return system. When power is removed the actuator returns to the normal position.

PopTop Series two position spring return valves can be purchased with an optional built-in auxiliary SPDT end switch for interfacing or signaling; for example, zone pump burner control.

MAINTENANCEPopTop Series two position spring return valves are maintenance free. Replace defective modules. Actuator may be replaced without removing the valve.

Regular maintenance of the total system is recomended to assuresustained, optimum performance.

FIELD REPAIRReplace any damaged or failed components with complete replacement unit.

ReleaseButton

ManualOperatingLever

MatingHole

High Close-Off (H)General Close-Off (G)

MatingHole

ReleaseButton

ManualOperatingLever

Stem

Figure-7 PopTop Installation.

Commercial Reference

Part Name (Pb) (Hg) (Cd) (Cr (VI)) (PBB) (PBDE)

Metal PartsX O O O O O

Plastic PartsO O O O O O

ElectronicO O O O O O

Cables & cabling accessoriesO O O O O O

This table is made according to SJ/T 11364.O: indicates that the concentration of hazardous substance in all of the homogeneous materials for this part is below the limit as stipulated in GB/T 26572.X: indicates that concentration of hazardous substance in at least one of the homogeneous materials used for this part is above the limit as stipulated in GB/T 26572

Range Brand Product Description

AGXXXXXXAHXXXXXX

ERIE ACTUATORSAG GENERAL CLOSEOFF NO/NC CLASS-A/F SR/NSR

AH HIGH CLOSEOFF NO/NC CLASS-A/F SR/NSR

- Hazardous Substances

against a seat. Use lead or tin based solder with melting point below 600 °F. Do not overheat. Direct flame tip away from valve. Cool valve quickly with a wet cloth. Body assembly can be submerged for leak testing prior to attaching the actuator.

Threaded ConnectionApply Teflon tape to all but the last two threads of male pipe thread. Hand screw the pipe into the valve, turning it as far as it will go. Use a wrench to fully tighten the valve to the pipe. Do not over tighten or strip the threads.

Inverted Flare Union ConnectionSolder fittings onto pipe. Use solder with melting point below 600°F. Mount valve to union nuts.

Installing Actuator on Valve BodySlowly latch the manual operating lever in the open, engaged position (AG1 or AH1 only). Depress the release button (see Figure-7). Align the body with the actuator to ensure the stem is inserted into the large mating hole on the bottom side of the actuator. Engage the actuator on the body and release the button.

© Copyright 2016, Schneider Electric All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.

F-27204-7

North America (USA): +1 888 444 1311Europe, Middle East & Africa (Sweden): +46 10 478 2000 Asia Pacific (Singapore): +65 6484 7877product.support@schneider-electric.comwww.schneider-electric.com

Sweat Connections C A U T I O N

Do not solder with actuator in place, or with paddle against seat, as the heat can damage the unit. Before soldering, move the manual open lever into Open position then remove the actuator from the body. Orient paddle so it is not against a seat.

Use lead or tin based solder with melting point below 600 °F. Do not overheat. Direct flame tip away from valve. Cool valve quickly with a wet cloth.Body assembly can be submerged for leak testing prior to attaching the actuator.

Threaded ConnectionApply Teflon tape to all but the last two threads of male pipe thread. Hand screw the pipe into the valve, turning it as far as it will go. Use a wrench to fully tighten the valve to the pipe. Do not over tighten or strip the threads.

Inverted Flare Union ConnectionSolder fittings onto pipe. Use solder with melting point below 600°F. Mount valve to union nuts.

Installing Actuator on Valve BodySlowly latch the manual operating lever in the open, engaged position (AG1 or AH1 only). Depress the release button (see Figure-7). Align the body

with the actuator to ensure the stem is inserted into the large mating hole on the bottom side of the actuator. Engage the actuator on the body and release the button.

C A U T I O NDo not use the valve body to manually open the actuator as damage to the valve actuator will result.

CHECKOUT1. Make sure the valve stem rotates freely before and after installing the

actuator.2. If the stem does not operate freely it may indicate that the stem was

damaged and may require that the valve be repaired or replaced.3. After the piping is under pressure, check the valve body and the

connections for leaks.4. After the valve and actuator are installed, power the actuator and check

the operation.

THEORY OF OPERATIONPopTop Series are two position spring return valves. When powered, the actuator moves to the desired position, tensing the spring return system. When power is removed the actuator returns to the normal position.

PopTop Series two position spring return valves can be purchased with an optional built-in auxiliary SPDT end switch for interfacing or signaling; for example, zone pump burner control.

MAINTENANCEPopTop Series two position spring return valves are maintenance free. Replace defective modules. Actuator may be replaced without removing the valve.

Regular maintenance of the total system is recomended to assuresustained, optimum performance.

FIELD REPAIRReplace any damaged or failed components with complete replacement unit.

ReleaseButton

ManualOperatingLever

MatingHole

High Close-Off (H)General Close-Off (G)

MatingHole

ReleaseButton

ManualOperatingLever

Stem

Figure-7 PopTop Installation.

Commercial Reference

Part Name (Pb) (Hg) (Cd) (Cr (VI)) (PBB) (PBDE)

Metal PartsX O O O O O

Plastic PartsO O O O O O

ElectronicO O O O O O

Cables & cabling accessoriesO O O O O O

This table is made according to SJ/T 11364.O: indicates that the concentration of hazardous substance in all of the homogeneous materials for this part is below the limit as stipulated in GB/T 26572.X: indicates that concentration of hazardous substance in at least one of the homogeneous materials used for this part is above the limit as stipulated in GB/T 26572

Range Brand Product Description

AGXXXXXXAHXXXXXX

ERIE ACTUATORS AG GENERAL CLOSEOFF NO/NC CLASS-A/F SR/NSRAH HIGH CLOSEOFF NO/NC CLASS-A/F SR/NSR

- Hazardous Substances

Do not use the valve body to manually open the actuator as damage to the valve actuator will result.

Checkout1. Make sure the valve stem rotates freely before and after

installing the actuator.2. If the stem does not operate freely it may indicate that

the stem was damaged and may require that the valve be repaired or replaced.

3. After the piping is under pressure, check the valve body and the connections for leaks.

4. After the valve and actuator are installed, power the actua-tor and check the operation.

Theory Of OperationPopTop Series are two position spring return valves. When powered, the actuator moves to the desired position, tensing the spring return system. When power is removed the actuator returns to the normal position.

PopTop Series two position spring return valves can be purchased with an optional built-in auxiliary SPDT end switch for interfacing or signaling; for example, zone pump burner control.

MaintenancePopTop Series two position spring return valves are mainte-nance free. Replace defective modules. Actuator may be replaced without removing the valve.

Regular maintenance of the total system is recomended to assure sustained, optimum performance.

Field RepairReplace any damaged or failed components with complete replacement unit.