Reference Codes Controls
Motors | Automation | Energy | Transmission & Distribution | Coatings
www.weg.net
Reference Codes - Switchgear2
Power Contactors
C W M 1 2 - 1 0 - 3 0 - V 4 0
Model
CWMC
CWC0
CWCI0
CWCH0
CWM
CWB
Terminal type Code
Screw Blank
For printedcircuit board
I
Spring S
Main contacts Code
2NO 20
3NO 30
4NO 40
2NC 02
2NO+2NC 22
Coil voltage Code
24 V 50/60 Hz D02
220 V 50/60 Hz D23
24 V dc C03
220 V dc C15
Complete table at pages 21 and 22
Auxiliary contacts Code
1NO 10
1NC 01
1NO+1NC 11
1NO+3NC 13
2NO+2NC 22
3NO+1NC 31
4NO 40
4NC 04
4NO+4NC 44
None 00
Rated currentIn (AC-3)
Code
7 A 7
9 A 9
12 A 12
16 A 16
18 A 18
25 A 25
32 A 32
38 A 38
40 A 40
50 A 50
65 A 65
80 A 80
95 A 95
105 A 105
112 A 112
150 A 150
180 A 180
250 A 250
300 A 300
400 A 400
500 A 500
630 A 630
800 A 800
www.weg.net
Reference Codes - Switchgear 3
Control Relays
Model
CWCA0
C W C A 0 - 2 2 - 0 0 - V 4 0
Terminal type Code
Screw Blank
For printedcircuit board
I
Spring S
Auxiliary contacts1) Code
1NO+1NC 11
1NO+3NC 13
2NO+2NC 22
3NO+1NC 31
4NO 40
4NC 04
4NO+4NC 44
5NO+3NC 53
6NO+2NC 62
7NO+1NC 71
8NO 80
8NC 08
Coil voltage Code
24 V 50/60 Hz D02
220 V 50/60 Hz D23
24 V dc C03
220 V dc C15
Complete table at pages 21 and 22
Note: 1) Configurations with more than 4 auxiliary contacts can be achieved only by adding auxiliary contact blocks.
www.weg.net
Reference Codes - Switchgear4
Overload Relays
Solid-State Relays
Model
RW17
RW27
RW67
RW117
RW317
RW407
R W 1 1 7 - 2 D 3 - U 0 8 0
Connector links
1 D
2 D
Poles
2
3
Rated current (A) Code
0.28-0.4 D004
0.4-0.63 C063
0.56-0.8 D008
0.8-1.2 D012
1.2-1.8 D018
1.8-2.8 D028
2.8-4 U004
4-6.3 D063
5.6-8 U008
7-10 U010
8-12.5 D125
10-15 U015
11-17 U017
15-23 U023
22-32 U032
Rated current (A) Code
32-40 U040
25-40 U040
32-50 U050
40-57 U057
50-63 U063
57-70 U070
63-80 U080
75-97 U097
90-112 U112
100-150 U150
140-215 U215
200-310 U310
275-420 U420
400-600 U600
560-840 U840
Model
RWB40
RWM40
RWM112
RWM420
RWM840
R W B 4 0 - 3 - A 4 U 0 4 0
Rated current (A) Code
0.4-2 U002
1.6-8 U008
5-25 U025
8-40 U040
14-56 U056
28-112 U112
50-250 U250
85-420 U420
170-840 U840
Bimetallic Relays
www.weg.net
Reference Codes - Switchgear 5
Smart Relay - Control Unit
Motor Protective Circuit Breaker
Model
MPW12
MPW18
MPW40
MPW80
MPW100
M P W 4 0 i - 3 - D 0 6 3
S R W 0 1 - U C P T 1 E 4 7
Terminal type Code
Screw Blank
Spring1) S
Communication protocol
Code
No communication B
DeviceNet D
Modbus-RTU M
Profibus-DP P
Protection Code
PTC T
Earth leakage E
Digital input operating voltage
Code
24 V dc 1
110 V ac 2
Supply voltage Code
24 V ac (50-60 Hz) / V dc E26
110-240 V ac (50-60 Hz) / V dc E47
Type of protection Code
Thermomagnetic (Imx13) Blank
Magnetic only (Imx13) i
Thermomagnetic (Imx19) t
Rated current (A) Current (A) Code
0.1-0.16 0.16 C016
0.16-0.25 0.25 C025
0.25-0.4 0.4 D004
0.4-0.63 0.63 C063
0.63-1 1 U001
1-1.6 1.6 D016
1.6-2.5 2.5 D025
2.5-4 4 U004
4-6.3 6.3 D063
6.3-10 10 U010
8-12 12 U012
10-16 16 U016
16-20 20 U020
20-25 25 U025
25-32 32 U032
32-40 40 U040
40-50 50 U050
50-65 65 U065
55-75 75 U075
65-80 80 U080
70-90 90 U090
80-100 100 U100
Note: 1) Spring terminal available only for MPW12 (up to 12 A).
www.weg.net
Reference Codes - Switchgear6
Pushbuttons - CSW Pushbuttons and Pilot Lights
Line Code
Standard CSW
New line CSW2
C S W - B F 2
Color Code
White/translucid 0
Red 1
Green 2
Yellow 3
Blue 4
Black 5
Orange 6
N/A (CSW-BES) Blank
Type Code
Pushbutton B
Flange Code
No flange WH
Flange AF3 (old version) Blank
Front typeAvailable for line
Code
Mushroom
CSW
C
Illuminated mushroom CI
Illuminated extended SI
Double (CSW) D
Emergency with key EY
Emergency (CSW) EG
Illuminated flush FI
Extended S
Flush (CSW) F
Guarded GA
Emergency stop - pull to release ESP
Emergency stop - turn to release ESG
Emergency stop - key to release ESY
Emergency stop with green position indicator - pull to release
ESPS
Emergency stop with green position indicator - turn to release
ESGS
Emergency stop with green position indicator - key to release
ESYS
Mushroom with latch - turn to release CT
Mushroom with latch - key to release CY
Flush double
CSW2
DF
Extended double DS
Illuminated flush double1) DFI
Illuminated extended double1) DSI
Flush triple1) TF
Extended triple TS
www.weg.net
Reference Codes - Switchgear 7
Selector Switches - CSW Pushbuttons and Pilot Lights
Line Code
Default CSW
C S W - C K 3 F 4 5 W H
Type Code
Selector switch C
Front type Code
Lever A
With key Y
Illuminated knob KI
Knob K
Release Code
Return R
Return right RD
Return left RE
Fixed F
Voltage Code
White/translucid 0
Red 1
Green 2
Yellow 3
Blue 4
Black (default CSW-CK) Blank
N/A (Key) Blank
Angle Code
45° 45
90° 90
Pilot Lights - CSW Pushbuttons and Pilot Lights
Line Code
Default CSW
C S W - S D 1 F 3 F V
Color Code
White/translucid 0
Red 1
Green 2
Yellow 3
Blue 4
Black 5
Orange 6
Frontal Code
CSW SD
Line Voltage Code
CSW
12 V ac/dc E25
24 V ac/dc E26
48 V ac/dc E27
110-130 V 50/60 Hz D61
220-240 V 50/60 Hz D66
125 V dc C13
Flange Code
New flange 3VF
Old version Blank
Flange Code
New flange F
Old version Blank
Positions
3
2
Flange Code
No flange WH
Flange AF3 (old version) Blank
www.weg.net
Reference Codes - Switchgear8
Common Sets - CSW Pushbuttons and Pilot Lights
Line Code
Default CSW
New line CSW2
Tipo Code
Pushbutton B
Selector switch C
Signalling light S
Position Code
Return R
Return right RD
Return left RE
Fixed F
N/A Blank
Positions Code
3 3
2 2
N/A Blank
Only for selector switches Only for selector switches
Only for selector switches
Angle Code
45° 45
90° 90
Available for type
Front typeAvailable for line
Code
Signalling light
Diffused
CSW
D
Selector switch
Lever A
With key Y
Illuminated knob KI
Knob K
Pushbutton
Mushroom C
Illuminated mushroom CI
Illuminated extended SI
Double D
Emergency stop key to release
ESY
Emergency stop turn to reset (CSW)
ESG
Emergency stop pull to release (CSW)
ESP
Emergency stop with green position indicator - pull to release
ESPS
Emergency stop with green position indicator - turn to release
ESGS
Emergency stop with green position indicator - key to release
ESYS
Illuminated flush FI
Extended S
Flush F
Guarded GA
Flush double
CSW2
DF
Extended double DS
Illuminated flush double1) DFI
Illuminated extended double1) DSI
Flush triple1) TF
Extended triple TS
C S W - B F I 2 - 0 0 2 0 0 0 0 0 F D 6 6 3 F V
www.weg.net
Reference Codes - Switchgear 9
C S W - B F I 2 - 0 0 2 0 0 0 0 0 F D 6 6 3 F V
Qty of blocks2NO (BC20)
1
2
3
4
5
0
Qty of blocks1NC late break (BCR01)
1
2
3
4
5
0
Qty of blocks1NO (BC10)
1
2
3
4
5
0
Qty of blocks2NC (BC02)
1
2
3
4
5
0
Qty of blocks1NO+1NC (BC11)
1
2
3
4
5
0
Qty of blocks1NC (BC01)
1
2
3
4
5
0
Qty of blocks1NO early make (BCA10)
1
2
3
4
5
0
Color Code
White/translucid 0
Red 1
Green 2
Yellow 3
Blue 4
Black 5
Orange 6
Qty of blocks1NC (BCM01)
1
2
3
0
Voltage Code
12 V dc 50/60 Hz E25
24 V dc 50/60 Hz E26
48 V dc 50/60 Hz E27
110-130 V dc 50/60 Hz D61
110-130 V dc C40
110 V 50/60 Hz D13
125 V dc C13
220 V 50/60 Hz D23
220-240 V 50/60 Hz D66
Flange Code
New flange F
Old version Blank
Flange Code
New flange 3VF
Old version Blank
www.weg.net
Reference Codes - Switchgear10
Coil voltage Code
230 V 50/60 Hz D24
400 V 50/60 Hz D34
Complete table at pages 21 and 22
Enclosed Direct On Line Starter
Model
DLW
DLWM
ESW
ESWS
D L W - 0 7 D 2 4 P 6 5 - R 2 3
ContactorAC-3 current
Contactor model Code
7 ACW07 7
CWC07 07
9 ACWM9 9
CWC09 09
12 ACWM12 12
CWC012 012
16 A CWC016 016
18 A CWM18 18
25 A CWM25 25
32 A CWM32 32
40 A CWM40 40
50 A CWM50 50
65 A CWM65 65
Overload relay Code
RW17-1D3-C063 R02
RW17-1D3-D008 R03
Complete table at page 23
Pilot device type CodeAvailable for model
Manual-Off-Auto Switch B
DLW / DLWM
Reset I
Start + Stop/Reset P
Stop/Reset D
No pushbutton E ESW / ESWSStart-Stop pushbutton A
Protection degree Code
IP65 (DLW) 65
IP52 (DLW) None
Type 4X (ESW/ESWS) X
www.weg.net
Reference Codes - Switchgear 11
Electronic Timing Relays
Type Code
Single function RTW
Multifunction ERWT
Auxiliary contacts
Type Code
1 NOC4) 01
2 NOC 02
Timing selection
Time range Code
0.1 - 1s5) U001S
0.3 - 3s U003S
1 - 10s U010S
3 - 30s U030S
6 - 60s U060S
10 - 100s U100S
30 - 300s U300S
1 - 10min6) U010M
3 - 30min6) U030M
0.1s - 10min7) MAT
0.2s - 150h7) MBT
0.1s - 10 days8) MT1
Function Code
ON delay RE
Pulse ON PE
Pulse flasher - start ON1) CI
Pulse flasher - start OFF1) CIR
Symmetric flasher - start ON CIL
Symmetric flasher - start OFF CID
OFF-delay RD
OFF-delay no control1) RDI
Star-delta2) ET
8 selectable functions3) MF1
ON-delay (A)
OFF-delay with control signal (Ba)
ON- and OFF-delay with control signal (Ca)
Symmetrical flasher, starts with pulse on (Da)
Symmetrical flasher, starts with pulse off (Db)
Interval (E)
Retriggerable interval with control signal off (Fa)
Star-Delta (G)
8 selectable functions3) MF2
ON and OFF delay with control signal (Cb)
Asymetrical flasher, starts with pulse OFF (Dd)
Percentage flasher, starts with pulse OFF (Df)
Delayed adjustable-length pulse (Ia)
Asymmetrical flasher, starts with pulse ON (Dc)
Percentage flasher, starts with pulse ON (De)
Flasher to reversing motor (Dg)
Bistable (J)
Supply voltage
Alternating current (50/60 Hz) / Direct current
DescriptionApplicable to the following
RTW modelsCode
24 V ac / 24 V dc RE, PE, CI, CIR, CIL, CID, ET E26
48 V ac / 24 V dc RE, PE, CI, CIR, CIL, CID, ET E33
110-130 V ac / 24 V dc RE, PE, CI, CIR, CIL, CID, ET E37
220-240 V ac / 24 V dc RE, PE, CI, CIR, CIL, CID, ET E40
24-240 V ac / 24-240 V dc RE, PE, CI, CIR, CIL, CID, ET, RD, RDI E059)
Alternating current (50/60 Hz)
DescriptionApplicable to the following
RTW models10) Code
24 V ac RD D02
48 V ac RD D07
110-130 V ac RD D61
220-240 V ac RD D66
380-440 V ac RE, PE, ET D71
Direct current
DescriptionApplicable to the following
RTW modelsCode
24 V dc RD C03
Notas:1) Not available for multi-timing models (RTW-M);2) RTW-ET is available only with two timing options: 3 - 30s (code U030S) and 0.1s - 10min (code MAT);3) MF1 and MF2 functions available only on multifunction models ERWT;4) Not available for star-delta models (RTW-ET) and multifunction models (ERWT-MF1, MF2);5) Timing range 0.1 - 1s (code U001S) is not available for Models RTW-CI, CIR, RD and RDI;6) Timing ranges 60 - 600s (code U010M) and 3 - 30min (code U030M) are available only for model RTW-RDI;7) Timing ranges 0.1s - 10min (code MAT) and 0.2s - 150h (code MBT) are available only for models RTW-RE, PE, RD, CIL, CID and ET;8) Timing range 0.1s - 10 days (code MT1) is available only for multi function models ERWT-MF1 and MF2;9) E05 supply voltage available for:
Single timing models: RTW-CI, CIR e RDI Multi timing models (MAT / MBT): RE, PE, CI, CIL, CIR, CID, RD e ET Multi function models: MF1 and MF2;
10) Available only for single-timing models.
E R W T - M F 1 - 0 2 - M T 1 - E 0 5
www.weg.net
Reference Codes - Switchgear12
Electronic Monitoring Relays
Phase Loss Protector
Supply voltage Code
220-240 V 50/60 Hz D66
380-415 V 50/60 Hz D70
440-480 V 50/60 Hz D74
Phase loss
Phase Loss and Phase Sequence Protector
Supply voltage Code
220-240 V 50/60 Hz D66
380-415 V 50/60 Hz D70
440-480 V 50/60 Hz D74
Phase loss and phase sequence
Undervoltage and Overvoltage Protector
Supply voltage Code
208 V 50/60 Hz D77
220 V 50/60 Hz D23
230 V 50/60 Hz D24
240 V 50/60 Hz D25
380 V 50/60 Hz D33
Supply voltage Code
400 V 50/60 Hz D34
415 V 50/60 Hz D35
440 V 50/60 Hz D36
460 V 50/60 Hz D38
480 V 50/60 Hz D39
Undervoltage and overvoltage
Power supply system
Blank Three phase
M Single phase
Supply voltage Code
220-240 V 50/60 Hz D66
380-415 V 50/60 Hz D70
440-480 V 50/60 Hz D74
Phase sequence
Phase Sequence Protector
R P W - F F - D 7 0
R P W - S F - D 7 0
R P W - F S F - D 7 0
R P W - S S M D 2 3
www.weg.net
Reference Codes - Switchgear 13
Temperature Monitoring with PTC
Supply voltage Code
24-240 V ac / V dc E05
Supply voltage Code
220-440 V ac D90
Type of monitoring and protection Code
Phase loss (PF)Overvoltage (>Un)
Phase unbalance (Asy)Phase sequence (PS)Undervoltage (<Un)
Neutral detection (ND)
VM1
Phase loss (PF)Overvoltage (>Un)
Phase unbalance (Asy)Undervoltage (<Un)
Neutral detection (ND)
VM2
PTC protection
Multifunction Three-Phase Monitoring Relays
Electronic Level Control Relay
Supply voltage Code
100-240 V ac / V dc E09
Type of control Code
Filling EN
Draining ES
Electronic Monitoring Relays
R P W - P T C - E 0 5
R N W - E N - E 0 9
E R W M - V M 1 - 0 1 - D 9 0
www.weg.net
Reference Codes - Switchgear14
Miniature Circuit Breakers
MDW / MDWH
Rated current (in) Code
6 A 6
10 A 10
16 A 16
20 A 20
25 A 25
32 A 32
40 A 40
50 A 50
63 A 63
MDW
Rated current (in) Code
70 A 70
80 A 80
100 A 100
125 A 125
Tripping curve Code
B B
C C
M D W H 3 - 1 0 0 - 2
Model
MDW
MDWH
Poles
1
2
3
4
Miniature Switch Disconnectors
Rated current (in) Code
40 A 40
63 A 63
80 A 80
100 A 100
S I W - 1 0 0 - 2
Poles
2
3
4
Residual Current Circuit Breakers (Earth Leakage Switches)
Sensibility Code
30 mA 30
300 mA 300
Rated current (in) Code
25 A 25
40 A 40
63 A 63
80 A 80
100 A 100
R D W 3 0 0 - 1 0 0 - 2
Referência
RDW
Poles
2
4
www.weg.net
Reference Codes - Switchgear 15
D W A 8 0 0 H - E 3 2 0 - 3 - 1 6 6 - 2 1 - E 15 - D 6 6
D W B 1 6 0 N 2 5 - 3 D F
DWB Line
Molded Case Circuit Breakers
DWA Line
Type of protection
Code
Distribution DWA
Motor protection DWM
Generator protection
DWG
Without prot.(switch)
IWATrip unit Code
Electronic LSI (default for DWA1600)
E
Thermomagnetic (default for DWA800) Blank
Breaking capacity at 380-415 V ac Code
30/35 kA N
50 kA S
65 kA H
Poles
22)
3
42)
Auxiliary contacts BC/AL Code
AL 01
BC1 10
BC1+AL 11
BC2 20
BC2+AL 21
BC3 30
None 0
Operating handle Code
MR (short) DWA800-1600 166
MR (long) DWA800-1600 465
MRI MRI
None 0
Shunt release Code
24 V ac / V dc E26
48 V ac / V dc E27
60 V ac / V dc E28
110-130 V ac / V dc E10
220-250 V ac / V dc E15
None 0
Undervoltage release Code
24 V dc C03
48 V dc C07
125 V dc C13
110-127 V ac D60
200-250 V ac D66
380-415 V ac D70
None 0
Frame
800
1,600
Rated current
320
400
420
500
630
700
800
1,250
1,600
Notes: 1) For IWB switches, please disconsider “Breaking capacity” and “Type of protection”. 2) 2 and 4-pole versions under request. 3) DWB400 only.
Model
DWB160
DWB250
DWB400
IWB1601)
IWB2501)
IWB4001)
Rated current (A)
16 90
20 95
25 100
32 105
40 110
50 125
55 140
Ratedcurrent (A)
63 150
65 160
70 185
75 200
80 250
85 320
400
Breaking capacity at 380-415 V ac Code
16 kA B
30/35 kA N
65 kA H3)
80 kA L
Poles
22)
3
4
Type of protection
Trip settings Code
Distribution
Fixed thermal and magnetic release DX
Adjustable thermal and fixed magnetic release DF
Adjustable thermal and magnetic release DA
Motor protectionFixed magnetic release MF
Adjustable magnetic release MA
Generator protection
Fixed thermal and magnetic release GX
Adjustable thermal and fixed magnetic release GF
TAdjustable thermal and magnetic releases GA
www.weg.net
Reference Codes - Switchgear16
A C W 1 0 0 H - F M U 2 0 - 3
Type of protection Code
Adjustable thermal and fixed magnetic release FMU
Adjustable thermal and magnetic releases ATU
Electronic LSI ETS
Magnetic only - motor protection MTU
Breaking capacity Code
High capacityH
U (ACW800)
Very high capacity2) V
Rated current (A)
20
25
32
40
50
63
80
Rated current (A)
100
125
160
200
400
630
800
Model
ACW100
ACW1011)
ACW160
ACW1611)
ACW250
ACW400
ACW630
ACW800
Poles
3
ACW Line
Molded Case Circuit Breakers
Notes: 1) MTU protection only. 2) Up to ACW630.
www.weg.net
Reference Codes - Switchgear 17
Switch-Disconnectors
Compact Switch-Disconnectors with Red-Yellow Handle1)
Fuse Switch-Disconnectors
M S W 1 0 0 P - 3 H
F S W 1 0 0 - 3 H
Rated current (A)
12
16
20
25
40
63
80
100
125
160
Rated current (A)
100
160
250
400
630
1,250
Poles
3
2
Mounting Code
Base B
Door P
Handle Code
With handle H
Without handle Blank
Model Code
Fuse-switch-disconnectors FSW
Handle Code
With handle H
Note: 1) Black-gray handle available upon request.
www.weg.net
Reference Codes - Switchgear18
Fuses
gL/gG Fuses - D and NH (Blade Contact) Types
Fuse type Code
D type FDW
NH type FNH
Breaking capacity Fuse type Code
120 kA NH type U
50 kA D type S
Rated current (A)
2
4
6
10
16
20
25
35
50
63
80
100
Rated current (A)
125
160
200
224
250
300
315
355
400
425
500
630
F N H 2 - 6 3 0 U
Size for NH fuses1)
000
00
1
2
3
Size Code
00 00
1 1
2 2
3 3
2X3 (FEA) 23
Type Code
aR A
Breaking capacity
Code
200 kA Y
100 kA K
Constructive characteristics Code
Metric flush end(terminal with metric thread)
FEM
Metric flush end2X3 with busbar in one side
FEA
Blade contact Blank
High Speed - aR Type - Fuses NH
F N H 3 F E M - 1 0 0 0 Y - A
Rated current (A)
20
25
35
40
50
63
80
100
125
160
200
250
315
350
400
Rated current (A)
450
500
550
630
700
710
800
900
1,000
1,100
1,250
1,400
1,600
1,800
2,000
Note: 1) For D type fuses keep it blank.
www.weg.net
Reference Codes - Switchgear 19
Capacitors for Power Factor Correction
U C W 2.5 V25 L10
Valid only for models UCW and UCWT
Capacitor type Code
Single-phase unit UCW
3-phase unit UCWT
3-phase module MCW
DimensionsØ x H (mm)
Code
53x68 J2
53x85 J4
53x105 J6
53x141 J8
60x105 L6
60x156 L10
60x211 L16
DimensionsØ x H (mm)
Code
70x156 M10
75x205 N12
75x225 N20
75x285 N22
100x230 Q26
116x230 S26
116x290 S28
Rated voltage Code
220 V 60 Hz V25
380 V 60 Hz V40
440 V 60 Hz V49
480 V 60 Hz V53
535 V 60 Hz V57
Reactive power (kvar)1)
2.5
5
7.5
10
12.5
15
17.5
Reactive power (kvar)1)
20
22.5
25
27.5
30
35
Note: 1) When selecting the reactive power (kvar) it is important to keep in mind the network frequency and voltage. For further information check the Power Factor Correction catalogue at www.weg.net.
www.weg.net
Reference Codes - Switchgear20
Air Circuit Breakers
Maximum rated
currentCode
800 A 08
1,600 A 16
2,000 A 20
2,500 A 25
3,200 A 32
4,000 A 40
5,000 A 50
6,300 A 63
Rated current
Code
800 A 08
1,600 A 16
2,000 A 20
2,500 A 25
3,200 A 32
4,000 A 40
5,000 A 50
6,300 A 63
Motorized operator
Code
None (default) 0
100~130 V ac/dc 1
200~250 V ac/dc 2
24~30 V dc 3
48~60 V dc 4
380 V ac 5
480 V ac 6
Accessories CodeNone (default) Blank
ON/OFF button lock B Key lock for 1 ACB K
Key interlock for 3 ACBs K2 Mechanial interlock (2 breakers) M Mechanical interlock (3 breakers) M3
Door interlock D
B+K BK
B+K2 B2 B+M BM B+D BD K+M KM K+D KD
Profibus communication1) CP Modbus communication1) CM
Undervoltage release CodeNone (default) 0
100~130 V ac/dc 1200~250 V ac/dc 2
24~30 V dc 348~60 V dc 4
380~480 V ac 5200~250 V ac/dc with delay 6100~130 V ac/dc with delay 7
48~60 V dc with delay 8380~480 V ac with delay 9
Opening coil Code200~250 V ac/dc (default) 2
No coil 0100~130 V ac/dc 1
24~30 V dc 348~60 V dc 4
380~480 V ac 5
Closing coil Code200~250 V ac/dc (default) 2
No coil 0100~130 V ac/dc 1
24~30 V dc 348~60 V dc 4
380~480 V dc 5
Version Code
Fixed F
Withdrawable E
Frame size Code
For 1,600 A DN
For 2,000~3,200 A ES
For 4,000~5,000 A FS
For 6,300 A GS
Poles
3
4
Auxiliary contacts Code
5NO+5NC (default) A
Position auxiliary contacts(for withdrawable version)
B
Protection and measurement unit2) Code
LSIG + A3) (100~250 V ac/dc, 60 Hz) - default AZ1
No protection unit 000
LSI + A3) (100~250 V ac/dc, 60 Hz) + Earth leakage5) AF1
LSI + A3) (100~250 V ac/dc, 50 Hz) + Earth leakage5) AF6
LSIG + A3) + Communication (100~250 V ac/dc, 60 Hz) AC1
LSIG + A3) + Communication (100~250 V ac/dc, 50 Hz) AC6
LSIG + A3) + Communication 24~60 V dc AC2
LSIG + M4) + Communication (100~250 V ac/dc, 60 Hz) PC1
LSIG + M4) + Communication (100~250 V ac/dc, 50 Hz) PC6
LSIG + V + A3) + Communication 24~60 V dc PC2
LSIG + A3) 24~60 V dc AZ2
LSIG + A3) (100~250 V ac/dc, 50 Hz) AZ6
Accessories supplied as standard for the entire range
Auxiliary contacts (5NO+5NC)
Alarm contacts
Opening coil 200-250 V ac/dc
Closing coil 200-250 V ac/dc
Operation counter
Position locking with padlock (padlock not included) - withdrawable version only
Position indicator (inserted /test/ withdrawn) - withdrawable version only
A B W 1 6 D N 3 - 1 6 A Z 1 F - A 0 2 2 0
Notes: 1) To be used with circuit breakers that have protection units type AC or PC. 2) For further information about protection units, check the catalogue at WEG website. 3) A - Current measurement. 4) M - Current, voltage, power and frequency measurements. 5) The current transformer ABW-ZCT must be used for earth leakage protection (supplied as accessory).
www.weg.net
Reference Codes - Switchgear 21
Supply voltage Code
10 V 50 Hz / 12 V 60 Hz V01
12 V 50 Hz / 14 V 60 Hz V02
16 V 50 Hz / 20 V 60 Hz V03
20 V 50 Hz / 24 V 60 Hz V04
24 V 60 Hz V05
24 V 50 Hz / 28 V 60 Hz V06
28 V 50 Hz / 32 V 60 Hz V07
32 V 50 Hz / 36 V 60 Hz V08
36 V 50 Hz / 42 V 60 Hz V09
42 V 50 Hz / 48 V 60 Hz V10
48 V 50 Hz / 56 V 60 Hz V11
52 V 50 Hz / 60 V 60 Hz V12
75 V 60 Hz V13
70 V 50 Hz / 80 V 60 Hz V14
95 V 50 Hz / 110 V 60 Hz V15
110 V 60 Hz V16
100 V 50 Hz / 115 V 60 Hz V17
110 V 50 Hz / 120 V 60 Hz V18
110-115 V 50 Hz / 127 V 60 Hz V19
120 V 50 Hz / 140 V 60 Hz V20
127 V 50 Hz / 150 V 60 Hz V21
139 V 50 Hz /160 V 60 Hz V22
180 V 50 Hz / 208 V 60 Hz V23
180-208 V 50 Hz / 208-240 V 60 Hz V24
220 V 60 Hz V25
190 V 50 Hz / 220 V 60 Hz V26
230 V 60 Hz V27
200 V 50 Hz / 230 V 60 Hz V28
240 V 60 Hz V29
208 V 50 Hz / 240 V 60 Hz V30
220 V 50 Hz V31
220 V 50 Hz / 255 V 60 Hz V32
220-230 V 50 Hz / 240-260 V 60 Hz V33
230 V 50 Hz V34
250 V 50 Hz V35
230 V 50 Hz / 266 V 60 Hz V36
Supply voltage Code
12 V 50/60 Hz D01
24 V 50/60 Hz D02
28 V 50/60 Hz D03
32 V 50/60 Hz D04
36 V 50/60 Hz D05
42 V 50/60 Hz D06
48 V 50/60 Hz D07
56 V 50/60 Hz D08
60 V 50/60 Hz D09
72 V 50/60 Hz D10
80 V 50/60 Hz D11
100 V 50/60 Hz D12
110 V 50/60 Hz D13
115 V 50/60 Hz D14
120 V 50/60 Hz D15
125 V 50/60 Hz D16
127 V 50/60 Hz D17
130 V 50/60 Hz D18
140 V 50/60 Hz D19
150 V 50/60 Hz D20
190 V 50/60 Hz D21
200 V 50/60 Hz D22
220 V 50/60 Hz D23
230 V 50/60 Hz D24
240 V 50/60 Hz D25
250 V 50/60 Hz D26
255 V 50/60 Hz D27
265 V 50/60 Hz D28
270 V 50/60 Hz D29
330 V 50/60 Hz D30
350 V 50/60 Hz D31
370 V 50/60 Hz D32
380 V 50/60 Hz D33
400 V 50/60 Hz D34
415 V 50/60 Hz D35
440 V 50/60 Hz D36
450 V 50/60 Hz D37
460 V 50/60 Hz D38
480 V 50/60 Hz D39
Supply voltage Code
230-240 V 50 Hz / 277 V 60 Hz V37
250 V 60 Hz V38
310 V 60 Hz V39
380 V 60 Hz V40
325 V 50 Hz / 380 V 60 Hz V41
380 V 50 Hz / 440 V 60 Hz V42
380-400 V 50 Hz / 440-460 V 60 Hz V43
400 V 50 Hz V44
400 V 60 Hz V45
400 V 50 Hz / 460 V 60 Hz V46
400-415 V 50 Hz / 480 V 60 Hz V47
440 V 50 Hz V48
440 V 60 Hz V49
440 V 50 Hz / 510 V 60 Hz V50
460 V 50 Hz V51
480 V 50 Hz V52
480 V 60 Hz V53
500 V 50 Hz V54
500 V 60 Hz V55
500 V 50 Hz / 600 V 60 Hz V56
535 V 60 Hz V57
550 V 50 Hz V58
550 V 60 Hz V59
550 V 50 Hz / 660 V 60 Hz V60
575 V 60 Hz V61
660 V 60 Hz V62
600 V 50 Hz / 690 V 60 Hz V63
Voltage Codes - Controls
Alternating Current
www.weg.net
Reference Codes - Switchgear22
Supply voltage Code
500 V 50/60 Hz D40
510 V 50/60 Hz D41
525 V 50/60 Hz D42
550 V 50/60 Hz D43
575 V 50/60 Hz D44
600 V 50/60 Hz D45
630 V 50/60 Hz D46
660 V 50/60 Hz D47
690 V 50/60 Hz D48
12-24 V 50/60 Hz D49
12-60 V 50/60 Hz D50
20-24 V 50/60 Hz D51
24-28 V 50/60 Hz D52
24-48 V 50/60 Hz D53
40-48 V 50/60 Hz D54
48-127 V 50/60 Hz D55
50-250 V 50/60 Hz D56
72-250 V 50/60 Hz D57
100-110 V 50/60 Hz D58
100-127 V 50/60 Hz D59
110-127 V 50/60 Hz D60
110-130 V 50/60 Hz D61
110-220 V 50/60 Hz D62
127-250 V 50/60 Hz D63
200-220 V 50/60 Hz D64
200-240 V 50/60 Hz D65
220-240 V 50/60 Hz D66
250-380 V 50/60 Hz D67
270-380 V 50/60 Hz D68
365-440 V 50/60 Hz D69
380-415 V 50/60 Hz D70
380-440 V 50/60 Hz D71
380-510 V 50/60 Hz D72
400-510 V 50/60 Hz D73
440-480 V 50/60 Hz D74
500-510 V 50/60 Hz D75
660-690 V 50/60 Hz D76
208 V 50/60 Hz D77
Supply voltage Code
5 V dc C01
12 V dc C02
24 V dc C03
28 V dc C04
36 V dc C05
42 V dc C06
48 V dc C07
55 V dc C08
60 V dc C09
72 V dc C10
80 V dc C11
110 V dc C12
125 V dc C13
130 V dc C14
220 V dc C15
230 V dc C16
250 V dc C17
400 V dc C18
415 V dc C19
440 V dc C20
500 V dc C21
600 V dc C22
1,000 V dc C23
1,200 V dc C24
6-240 V dc C31
6-250 V dc C32
12-600 V dc C33
24-28 V dc C34
24-48 V dc C35
24-240 V dc C36
42-50 V dc C37
48-260 V dc C38
100-125 V dc C39
110-130 V dc C40
120-127 V dc C41
130-250 V dc C42
200-240 V dc C43
208-240 V dc C44
208-250 V dc C45
230-240 V dc C46
150 V dc C47
42-48 V dc C97
110-125 V dc C98
220-250 V dc C99
Supply voltage Code
12-48 V dc 50/60 Hz E01
24-28 V dc 50/60 Hz E02
24-48 V dc 50/60 Hz E03
24-60 V dc 50/60 Hz E04
24-240 V dc 50/60 Hz E05
42-50 V dc 50/60 Hz E06
60-72 V dc 50/60 Hz E07
100-125 V dc 50/60 Hz E08
100-240 V dc 50/60 Hz E09
110-130 V dc 50/60 Hz E10
110-220 V dc 50/60 Hz E11
200-240 V dc 50/60 Hz E12
208-250 V dc 50/60 Hz E13
220-240 V dc 50/60 Hz E14
220-250 V dc 50/60 Hz E15
360-415 V dc 50/60 Hz E16
265-347 V dc 50/60 Hz E17
380-415 V dc 50/60 Hz E18
380-450 V dc 50/60 Hz E19
400-500 V dc 50/60 Hz E20
430-500 V dc 50/60 Hz E21
440-500 V dc 50/60 Hz E22
440-575 V dc 50/60 Hz E23
575-690 V dc 50/60 Hz E24
12 V dc 50/60 Hz E25
24 V dc 50/60 Hz E26
48 V dc 50/60 Hz E27
60 V dc 50/60 Hz E28
110 V dc 50/60 Hz E29
130 V dc 50/60 Hz E30
220 V dc 50/60 Hz E31
380 V dc 50/60 Hz E32
48 V 50/60 Hz /24Vdc E33
50-127 V 50/60 Hz / 60-180 V dc E34
100-127 V 50/60 Hz / 100-110 V dc E35
100-240 V 50/60 Hz / 100-220 V dc E36
110-130 V 50/60 Hz / 24 V dc E37
130-275 V 50/60 Hz / 180-300 V dc E38
200-240 V 50/60 Hz / 200-220 V dc E39
220-240 V 50/60 Hz / 24 V dc E40
277-380 V 50/60 Hz / 300-510 V dc E41
430-525 V dc 50/60 Hz E42
208-240 V dc 50/60 Hz E43
220-240 V 50/60 Hz / 250 V dc E44
100-110 V 50/60 Hz /110 V dc E45
230 V 50/60 Hz /220 V dc E46
Voltage Codes - Controls
Alternating Current (50/60 Hz) Direct Current Alternating Current / Direct Current
www.weg.net
Reference Codes - Switchgear 23
Description Code Setting range
RW17-1D3-D004 R01 0.28 - 0.4
RW17-1D3-C063 R02 0.4 - 0.63
RW17-1D3-D008 R03 0.56 - 0.8
RW17-1D3-D012 R04 0.8 - 1.2
RW17-1D3-D018 R05 1.2 - 1.8
RW17-1D3-D028 R06 1.8 - 2.8
RW17-1D3-U004 R07 2.8 - 4
RW17-1D3-D063 R08 4.0 - 6.3
RW17-1D3-U008 R09 5.6 - 8
RW17-1D3-U010 R10 7 - 10
RW17-1D3-D125 R11 8 - 12.5
RW17-1D3-U015 R12 10 - 15
RW17-1D3-U017 R13 11 - 17
RW27-1D3-C063 R21 0.4 - 0.63
RW27-1D3-D008 R22 0.56 - 0.8
RW27-1D3-D012 R23 0.8 - 1.2
RW27-1D3-D018 R24 1.2 - 1.8
RW27-1D3-D028 R25 1.8 - 2.8
RW27-1D3-U004 R26 2.8 - 4
RW27-1D3-D063 R27 4.0 - 6.3
RW27-1D3-U008 R28 5.6 - 8
RW27-1D3-U010 R29 7 - 10
RW27-1D3-D125 R30 8 - 12.5
RW27-1D3-U015 R31 10 - 15
RW27-1D3-U017 R32 11 - 17
RW27-1D3-U023 R33 15 - 23
RW27-1D3-U032 R34 22 - 32
RW67-1D3-U040 R35 25 - 40
RW67-1D3-U050 R37 40 - 57
RW67-2D3-U050 R38 40 - 57
RW67-2D3-U057 R39 50 - 63
RW67-2D3-U063 R40 57 - 70
RW67-2D3-U070 R41 63 - 80
RW67-2D3-U080 R42 63 - 80
RW117-1D3-U097 R44 75 - 97
RW117-1D3-U112 R45 90 - 112
Description Code Setting range
RW17-1D2-D018 RM05 1.2 - 1.8
RW17-1D2-D028 RM06 1.8 - 2.8
RW17-1D2-U004 RM07 2.8 - 4
RW17-1D2-D063 RM08 4 - 6.3
RW27-1D2-D008 RM22 0.56 - 0.8
RW27-1D2-D012 RM23 0.8 - 1.2
RW27-1D2-D018 RM24 1.2 - 1.8
RW27-1D2-D028 RM25 1.8 - 2.8
RW27-1D2-U004 RM26 2.8 - 4
RW27-1D2-D063 RM27 4 - 6.3
RW27-1D2-U008 RM28 5.6 - 8
RW27-1D2-U010 RM29 7 - 10
RW27-1D2-D125 RM30 8 - 12.5
RW27-1D2-U015 RM31 10 - 15
RW27-1D2-U017 RM32 11 - 17
RW27-1D2-U023 RM33 15 - 23
RW27-1D2-U032 RM34 22 - 32
RW67-1D2-U040 RM35 25 - 40
RW67-2D2-U050 RM38 32 - 50
RW67-2D2-U057 RM39 40 - 57
RW67-2D2-U063 RM40 50 - 63
RW67-2D2-U070 RM41 57 - 70
Short Codes for Overload Relays to be Used on Enclosed Direct On Line Starters
WEG Worldwide Operations
WEG Group - Automation Business Unit Jaraguá do Sul - SC - Brazil Phone: +55 47 3276 4000 [email protected] www.weg.net C
od: 5
005
8173
| R
ev: 0
3 | D
ate
(m/y
): 06
/201
5Th
e va
lues
sho
wn
are
sub
ject
to c
hang
e w
ithou
t prio
r no
tice.
For those countries where there is not a WEG own operation, find our local distributor at www.weg.net.
ARGENTINASan Francisco - CordobaPhone: +54 3564 [email protected]
Cordoba - CordobaPhone: +54 351 [email protected]
Buenos AiresPhone: +54 11 [email protected]
AUSTRALIAScoresby - Victoria Phone: +61 3 [email protected]
AUSTRIAMarkt Piesting - Wiener Neustadt-LandPhone: +43 2633 [email protected]
BELGIUMNivelles - BelgiumPhone: +32 67 [email protected]
BRAZILJaraguá do Sul - Santa CatarinaPhone: +55 47 [email protected]
CHILELa Reina - SantiagoPhone: +56 2 [email protected]
CHINANantong - JiangsuPhone: +86 513 [email protected]
Changzhou – Jiangsu Phone: +86 519 [email protected]
COLOMBIASan Cayetano - BogotaPhone: +57 1 [email protected]
ECUADOREl Batan - QuitoPhone: +593 2 [email protected]
FRANCESaint-Quentin-Fallavier - IsèrePhone: +33 4 [email protected]
GERMANYTürnich - Kerpen Phone: +49 2237 [email protected]
Balingen - Baden-WürttembergPhone: +49 7433 [email protected]
Homberg (Efze) - HessePhone: +49 5681 [email protected]
GHANAAccraPhone: +233 30 [email protected]
INDIABangalore - KarnatakaPhone: +91 80 [email protected]
Hosur - Tamil NaduPhone: +91 4344 [email protected]
ITALYCinisello Balsamo - MilanoPhone: +39 2 [email protected]
JAPANYokohama - KanagawaPhone: +81 45 [email protected]
MALAYSIAShah Alam - SelangorPhone: +60 3 [email protected]
MEXICOHuehuetoca - MexicoPhone: +52 55 [email protected]
Tizayuca - HidalgoPhone: +52 77 97963790
NETHERLANDSOldenzaal - OverijsselPhone: +31 541 [email protected]
PERULa Victoria - LimaPhone: +51 1 [email protected]
PORTUGALMaia - PortoPhone: +351 22 [email protected]
RUSSIA and CISSaint PetersburgPhone: +7 812 363 [email protected]
SOUTH AFRICAJohannesburgPhone: +27 11 [email protected]
SPAINCoslada - MadridPhone: +34 91 [email protected]
SINGAPORESingaporePhone: +65 [email protected]
SingaporePhone: +65 [email protected]
SCANDINAVIAMölnlycke - SwedenPhone: +46 31 [email protected]
UKRedditch - WorcestershirePhone: +44 1527 [email protected]
UNITED ARAB EMIRATESJebel Ali - DubaiPhone: +971 4 [email protected]
USADuluth - GeorgiaPhone: +1 678 [email protected]
Minneapolis - MinnesotaPhone: +1 612 3788000
VENEZUELAValencia - CaraboboPhone: +58 241 [email protected]