Freeboard
GEH® – Granular Ferric Hydroxide
Supporting gravelFilter fl oor
1. Basic Design of GEH® Adsorber Units
Conventional pressure fi lter with fi lter nozzles (fi lter fl oor or star-shaped hub collector), used as stand-alone unit or in combined systems arranged in parallel or series
Air relieve valve and mechanism to prevent drainage of fi lter
Additional connections for fi lling/removal of GEH® and for disinfection
Diff erential pressure gauge and sampling valves at inlet and outlet
Suitable materials for adsorber vessles: plastic (e.g. GRP), steel with inner surface coat or stainless steel
Filling of bed:
Supporting layer of quartz gravel (particle size 2.00 - 3.15 mm) to cover the fi lter nozzles
GEH® adsorbent (bed depth between 0.8 - 1.6 m)
Freebord, approx. 50 % of GEH® bed depth, for backwashing
Adsorber Units for Water Treatment 105
R
fi g.1 Basic Design of GEH® Adsorber Units
Adsorber bed depth
Freeboard height
Filtration velocity
Empty bed contact time (EBCT)
Permissible pressure drop
Backwash velocity
Duration of backwashing
0.8 - 1.6 m
50 % of bed depth
≤ 20 m/h
≥ 3 minutes
Max. 0.5 bar (7 psi)
26 m/h (with water only)
until outlet water is clear
Recommended Operating Conditions
Source of solutions.
3. Installation backwash
Backwash after installation to remove fines from the adsorber bed.
Backwash speed: 26 m/h
Backwash, until effluent is free of turbidity (approx. 15 minutes)
Backwash with water only. Do not backwash with air or air/water mixture.
4. Disinfection
Use chlorine bleach or hydrogen peroxide as disinfectant.
After disinfection, backwash adsorber bed (in the same manner as installation backwash)
Confirm successful disinfection by checking microbial parameters, i.e. confor-mance of treated water to applicable drinking water specification.
When carrying out disinfection, observe data and instructions given in the technical datasheet “Disinfection” from GEH Wasserchemie.
Disinfectant solution
Backwash effluent
Fresh water
2. Filling
Partial filling with water to protect the filter nozzles while filling of gravel
Transfer quartz gravel (DIN EN 12904 grade) supporting layer into unit in accordance with suppliers instructions, level and rinse the layer
Inject GEH® hydraulically using water-driven injector system or place manually through manhole or filling port
Check to ensure proper functioning of the filter nozzles before placing gravel and GEH®. Take care not to crush or otherwise damage the GEH® when placing. Do not allow GEH® to get into filter nozzles.
fig. 2 Filling
fig. 3 Installation backwash
fig. 4 Disinfection
0
1
2
3
4
5
0,0
0,1
0,2
0,3
0,4
0,5
0 5 10 15 20 25 30 35
Dru
ckve
rlust
[m
WS/
m F
ilter
bett-
Schü
tthöh
e]
Dru
ckve
rlust
[b
ar/m
Filt
erbe
tt-Sc
hütth
öhe]
Filtergeschwindigkeit [m/h]
Temperatur: 15°C
0
1
2
3
4
5
6
7
0,0
0,1
0,2
0,3
0,4
0,5
0 5 10 15 20 25 30 35
Pres
sure
dro
p [p
si/m
bed
dep
th]
Pres
sure
dro
p
[bar
/m b
ed d
epth
]
Filtration speed [m/h]
Temperature: 15°C
0
20
40
60
80
0 5 10 15 20 25 30 35
Bet
taus
dehn
ung
[%]
Spülwassergeschwindigkeit [m/h]
Temperatur: 15°C
0
20
40
60
80
0 5 10 15 20 25 30 35
Bed
exp
ansi
on [
%]
Backwash flow speed [m/h]
Temperature: 15°C
Bed
expa
nsio
n [%
]
Backwash flow speed [m/h]
80
60
40
20
00 5 10 15 20 25 30 35
Adsorber Bed Expansion vs. Backwash Speed
Source of solutions.
5. Adsorber operation
Uniform flow through the adsorber bed must be ensured
Flow speed through adsorber bed: ≤ 20 m/h
Empty bed contact time (EBCT): ≥ 3 min
Maximum permissible pressure drop: 0.5 bar (7 psi)
Prevent draining of adsorber unit during operation (e.g. pressure retention valve)
Monitor treated water for compliance with applicable water specification.
Discontinuous or intermittent operation does not impair functioning.
6. Operational Backwash
Operational backwash to remove particulate matter retained in bed is necessary when pressure drop exceeds the maximum permissible value of 0.5 bar (7 psi).
Backwash process (upflow configuration):
Backwash speed: 26 m/h
Duration: until effluent is free of turbidity (approx. 10 minutes).
Treatment of backwash water to meet local discharge requirements, if necessary
7. Replacement of GEH®
When treated water quality drops below specification, the GEH® bed must be replaced. Removal is normally carried out by vacuum transfer or flushing out through the lower removal channel.
Disposal or use of exhausted GEH® must be in compliance with applicable waste regulations.
fig.5 Adsorber operation
fig. 6 Operational Backwash
fig. 7 Replacement of GEH®
0
1
2
3
4
5
0,0
0,1
0,2
0,3
0,4
0,5
0 5 10 15 20 25 30 35
Dru
ckve
rlust
[m
WS/
m F
ilter
bett-
Schü
tthöh
e]
Dru
ckve
rlust
[b
ar/m
Filt
erbe
tt-Sc
hütth
öhe]
Filtergeschwindigkeit [m/h]
Temperatur: 15°C
0
1
2
3
4
5
6
7
0,0
0,1
0,2
0,3
0,4
0,5
0 5 10 15 20 25 30 35
Pres
sure
dro
p [p
si/m
bed
dep
th]
Pres
sure
dro
p
[bar
/m b
ed d
epth
]
Filtration speed [m/h]
Temperature: 15°C
0
20
40
60
80
0 5 10 15 20 25 30 35
Bet
taus
dehn
ung
[%]
Spülwassergeschwindigkeit [m/h]
Temperatur: 15°C
0
20
40
60
80
0 5 10 15 20 25 30 35
Bed
exp
ansi
on [
%]
Backwash flow speed [m/h]
Temperature: 15°C
Pres
sure
dro
p [b
ar/m
bed
dep
th]
Filtration speed [m/h]
Pres
sure
dro
p [p
si/m
bed
dep
th]
0,5
0,4
0,3
0,2
0,1
0,00 5 10 15 20 25 30 35
5
4
3
2
1
0
Pressure Drop vs. Flow Speed through Bed
Raw water
Backwash effluent
Treated water
Fresh water
Source of solutions.
Tel. +49 (0) 541 12 20 09Fax +49 (0) 541 18 11 [email protected] www.geh-wasserchemie.de
GEH Wasserchemie GmbH & Co. KGAdolf-Köhne-Straße 449090 Osnabrück, Germany Is
sue:
Oct
ober
201
8
All work described above is to be done by qualifi ed technical personnel only and in accordance with all applicable safety regulations.
Every application in water treatment is unique. The application must be studied in detail including all peripheral factors before the operating conditions of the GEH® system can be determined. Accordingly, the recommendations given above are general in nature and not legally binding.
We will gladly provide application advice regarding dimensioning and operation of your GEH® adsorption unit.
Please observe all instructions and information given in our product data sheets and safety data sheets.
Important Information
Quality management system certi edin accordance with ISO 9001:2015
Free of turbidity
Positive redox potential
No calcium precipitation
For every application, a raw water analysis should be provided to assess the adsorption performance.
Requirements for Raw Water