power station electrical protection -...

64
Power Station Electrical Protection } M M M L L L M L E A 2 B 2 C 2 Neutral C.T a 2 b 2 c 2 TO TRIP CIRCUIT Restricted E/F Relay CT

Upload: dangliem

Post on 19-Apr-2019

225 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

mPower Station Electrical Protection

}

M

M

M

L

L

LM

L

E

A2

B2

C2

Neutral C.T

a2

b2

c2

TO TRIP CIRCUIT

Restricted E/F Relay

CT

Page 2: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

mContents

1 The Need for Protection 21.1 Types of Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

1.1.1 Overcurrent . . . . . . . . . . . . . . . . . . . . . . . . . . 21.1.2 Earth Fault . . . . . . . . . . . . . . . . . . . . . . . . . . 2

1.2 Fault Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21.3 Isolation of Faulty Equipment . . . . . . . . . . . . . . . . . . . . 21.4 Protective Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . 31.5 Classes of Protection . . . . . . . . . . . . . . . . . . . . . . . . . 41.6 Characteristics of a Good Protection Scheme . . . . . . . . . . . 4

2 Common Terms Related to Protection 5

3 Unit protection schemes 73.1 Transformer protection . . . . . . . . . . . . . . . . . . . . . . . . 7

3.1.1 The Buchholz relay . . . . . . . . . . . . . . . . . . . . . . 73.1.2 Explosion Vent . . . . . . . . . . . . . . . . . . . . . . . . 83.1.3 Qualitrol Pressure Relief . . . . . . . . . . . . . . . . . . . 83.1.4 Continuous Gas Analyser . . . . . . . . . . . . . . . . . . 83.1.5 Earth Fault Protection of High Voltage Delta Windings . 103.1.6 Differential protection . . . . . . . . . . . . . . . . . . . . 123.1.7 Differential Protection of a Three Phase Transformer . . . 153.1.8 Differential Earth Fault Protection of Star Windings . . . 17

3.2 Busbar protection . . . . . . . . . . . . . . . . . . . . . . . . . . 193.2.1 Check Zones . . . . . . . . . . . . . . . . . . . . . . . . . 193.2.2 Blind Spots and Blind Spot Protection . . . . . . . . . . . 223.2.3 AC Wiring Supervision . . . . . . . . . . . . . . . . . . . 233.2.4 DC Supply Failure . . . . . . . . . . . . . . . . . . . . . . 243.2.5 Protection Inoperative Alarm . . . . . . . . . . . . . . . . 243.2.6 Circuit Breaker failure (CB fail) Protection . . . . . . . . 24

3.3 Circuit Protection . . . . . . . . . . . . . . . . . . . . . . . . . . 253.3.1 Distance-time and definite distance protection . . . . . . 253.3.2 Auto Reclose . . . . . . . . . . . . . . . . . . . . . . . . . 333.3.3 Pilot Wire Protection . . . . . . . . . . . . . . . . . . . . 333.3.4 220kV Oil-filled Cable Protection . . . . . . . . . . . . . . 35

3.4 Generator Protection . . . . . . . . . . . . . . . . . . . . . . . . . 363.4.1 Generator Earth Faults . . . . . . . . . . . . . . . . . . . 363.4.2 Stator Differential Protection . . . . . . . . . . . . . . . . 383.4.3 Generator Stator Over-Currents . . . . . . . . . . . . . . 393.4.4 Negative Phase Sequence Protection . . . . . . . . . . . . 403.4.5 Reverse Power Protection . . . . . . . . . . . . . . . . . . 44

4 Non-Unit protection 454.1 Overcurrent Relays . . . . . . . . . . . . . . . . . . . . . . . . . . 454.2 Earth Fault Relays . . . . . . . . . . . . . . . . . . . . . . . . . . 464.3 Earth Fault Protection of Transformers . . . . . . . . . . . . . . 464.4 Earth Fault Protection on Circuits . . . . . . . . . . . . . . . . . 474.5 Earth Fault on Interconnecting and Generator Transformers . . . 484.6 Time Graded (Non-Unit) Protection . . . . . . . . . . . . . . . . 49

Page 3: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

m4.7 Directional Relays . . . . . . . . . . . . . . . . . . . . . . . . . . 51

5 Backup Protection 53

6 Measuring Voltage and Current 556.1 Voltage Transformers . . . . . . . . . . . . . . . . . . . . . . . . . 556.2 Current Transformers . . . . . . . . . . . . . . . . . . . . . . . . 55

A Pre 1985 relay codes 57

B Post 1985 relay codes 58

Page 4: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

mList of Figures

1 Photo of Transformer explosive vent . . . . . . . . . . . . . . . . 92 Photo of Transformer Qualitrol . . . . . . . . . . . . . . . . . . . 93 Photo of Transformer Gas Analyser . . . . . . . . . . . . . . . . . 104 Delta-Star transformer Protection . . . . . . . . . . . . . . . . . 115 Fault is outside area covered by CT’s therefore relay does not

operate (i.e. current from CT – A is cancelled by current fromCT – B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

6 Relay operates as fault is between CT’s (i.e. current from CT –A is NOT cancelled by current from CT – B) . . . . . . . . . . . 13

7 Instantaneous relay . . . . . . . . . . . . . . . . . . . . . . . . . . 138 Biased relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139 Biased type relay . . . . . . . . . . . . . . . . . . . . . . . . . . . 1410 Protection of single phase of a Transformer . . . . . . . . . . . . 1511 Transformer Differential Protection . . . . . . . . . . . . . . . . . 1612 Differential (Restricted) Earth Fault Protection of Transformer -

Operation on Fault inside Zone . . . . . . . . . . . . . . . . . . . 1813 Differential (Restricted) Earth Fault Protection of Transformer –

Operation on Fault outside Zone . . . . . . . . . . . . . . . . . . 1814 Busbar protection scheme for a single busbar . . . . . . . . . . . 2015 Bus zone protection scheme for a single bus with bus section

circuit breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2016 Bus zone protection for circuit breakers and a half without check

zone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2117 Busbar protection scheme for a single bus with a bus section

circuit breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2218 measurement of distance to fault . . . . . . . . . . . . . . . . . . 2519 distance protection zones . . . . . . . . . . . . . . . . . . . . . . 2720 Acceleration of Distance measurement . . . . . . . . . . . . . . . 3121 Differential comparison Earth fault protection . . . . . . . . . . . 3222 Summation Transformer . . . . . . . . . . . . . . . . . . . . . . . 3423 Generator stator earth fault protection . . . . . . . . . . . . . . . 3724 Location of differential protection CT’s . . . . . . . . . . . . . . . 3825 Basic generator differential scheme . . . . . . . . . . . . . . . . . 3926 Positive phase sequence . . . . . . . . . . . . . . . . . . . . . . . 4127 Negative sequence rotation . . . . . . . . . . . . . . . . . . . . . 4228 Zero phase sequence . . . . . . . . . . . . . . . . . . . . . . . . . 4229 Effects of PPS and NPS on turbo-alternator (top - Positive phase

sequence; bottom - Negative phase sequence) . . . . . . . . . . . 4330 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4631 Earth fault protection on the Delta side of a transformer . . . . . 4732 Overcurrent and Earth Leakage Relays Connections . . . . . . . 4833 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4834 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4935 Instantaneous relays with Definite Time . . . . . . . . . . . . . . 4936 Inverse Time relays . . . . . . . . . . . . . . . . . . . . . . . . . . 5037 Directional relay . . . . . . . . . . . . . . . . . . . . . . . . . . . 5138 Non-Directional relays applied to parallel feeders . . . . . . . . . 5239 Directional relays applied to parallel feeders . . . . . . . . . . . . 52

Page 5: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

m40 Illustration of gross errors in distance measurement with feed in

between relay and fault . . . . . . . . . . . . . . . . . . . . . . . 53

Page 6: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

m19481 – Demonstrate knowledge of electricity supply protection equipmentProtection 19481Author - Richard J Smith Creation date - 7 November 2006 Last Updated - 3May 2007Description This course provides the student with an understanding of elec-tricity supply protection equipment with emphasis on the equipment providedat Huntly Power Station. Successful completion of this course will enable thestudent to achieve NZQA unit standard 19481 – Demonstrate knowledge ofelectrical supply protection equipment.Pre-Requisites The student have achieved EnChem level 2 and completed his/herelectrical component of their plant training at Huntly or equivalent work expe-rience.Completing and Passing the Course The following modules need to be success-fully completed to pass the course: 1. the 19481 Protection workbook to asatisfactory level 2. the course evaluation surveyWho should do this Course Genesis staff wishing to complete NZQA NationalCert Electricity Supply (Level 4) will be required to undertake this course.Student Objectives On completing this course, the student will be able to; 1.Define common terms and abbreviations used in discussing electrical protection.2. Describe the purpose and classes of protection (range: purpose of protection,typical causes of faults) 3. Identify the methods of discrimination used to findfaults (range: time, current, direction of power flow, distance measurement,differential relays) 4. State the purpose of voltage and current transformers5. Identify and describe the types of transformer protection (range: buchholz,overcurrent, earth fault, differential) 6. Describe the principles of circuit andbusbar protection (range: distance measurement, earth faults, bus zone, CBfail, and backup protection) 7. Describe relay numbering systems, both pre1985 and ANSI C37.2

1

Page 7: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

m1 The Need for Protection

If a fault or other abnormal condition occurs in a power system, the faultyapparatus must be isolated from the rest of the system as quickly as possible toreduce damage both to the faulty equipment and to those parts of the systemcarrying the fault current. Protective devices are therefore installed in thesystem to detect the presence of a fault and initiate the required action. Isolationof the affected equipment will then allow continued operation of the remainderof the system as normal.

1.1 Types of Faults

1.1.1 Overcurrent

When a circuit or piece of equipment is carrying a greater current than it wasdesigned for, it is said to be overloaded. Most equipment can tolerate somedegree of overloading for a limited time, but protection needs to be provided tolimit the overloading to a value that doesn’t damage the equipment. Overcurrentcan be caused by lighting strikes on overhead lines or just attempting to supplymore load than the circuit design load.

1.1.2 Earth Fault

A common cause of faults on buried cables and overhead lines is an earth fault.This can be caused by breakdown of insulation or digging up of buried cables,or by operating cranes, etc near overhead lines. When a live circuit is connectedto earth a large current will flow (which can cause overloading on the circuit),the earth voltage near the point of the earth fault can increase to a dangerouslevel, and supply to the intended recipient can be interrupted.

1.2 Fault Detection

Faults and other abnormal conditions may cause changes in the magnitude, di-rection, phase angle and frequency of circuit currents and voltages. The natureof these changes depends upon the fault and the position of the fault relativeto the point in the system from which the fault is being observed.

A protective system uses current transformers and voltage transformers (to mea-sure magnitudes of current and voltage and transform them to values which canbe handled by the relays), relays (to monitor these values and detect an abnor-mal condition) and a tripping circuit to the circuit breaker.

A fault detection system must provide protection of the system.

1.3 Isolation of Faulty Equipment

Protection of the system is the ability of a fault on equipment to be isolatedfrom the system quickly and with as little interruption to other supplies as pos-sible. By the operation of many types of relays which measure the electricityin the system, an appropriate operation of a particular relay will trip circuitbreakers to isolate the fault.

2

Page 8: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

mThe protective equipment should be simple as possible, but it should also pro-cess ’discrimination’ in order that it should isolate only the faulty circuit orapparatus and not operate for other faults outside its zone.

1.4 Protective Relays

A relay used for automatic protection may be defined as a mechanical or elec-trical apparatus triggered by current, voltage, or power which opens or closesa local circuit when the current has a specified magnitude, or bears a specifiedrelation to the voltage of the main circuit with which the relay is associated.The function the relay provides may be classified as follows:

• UNDER VOLTAGE, and UNDER CURRENT in which operation takesplace when the voltage or current falls below a specified value.

• OVER VOLTAGE, and OVER CURRENT, in which operation takes placewhen the voltage or current rises above a specified value.

• DIRECTIONAL, in which operation takes place when the component ofthe current in phase with the voltage, assumes a specified magnitude anda specified direction in relation to the voltage.

• DISTANCE, in which the operation is governed by the ratio of the voltageto the current, i.e. impedance, or to the component of the current havingsome specified phase relation to the voltage.

Relays can be classified, with regard to their timing characteristics, under thefollowing headings;

• INSTANTANEOUS, in which complete operation takes place with no in-tentional time delay from the incidence of the operating current reachingthe minimum pick up value.

• DEFINITE TIME, in which the time delay between incidence of the oper-ating current and the completion of the relay operation is independent ofthe magnitude of the current. That is a definite time must elapse after theminimum pick up value of current is reached, before tripping is initiated.

• INVERSE TIME, in which the time lag decreases as the value of theoperating current or power increases.

The function of a protective relay is to remove the faulty line or equipmentfrom service with as little disturbance and as little damage to the equipment aspossible. Both these considerations require that the time of operation must beas fast as possible but the first also requires that only the faulty section mustbe removed.

Protective relays must therefore be speedy and selective and this is achievedby the use of both time and current graded relays and special relays for specialtypes of fault.

Remember

3

Page 9: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

m• Relays may require current and/or voltage supplies from CTs and/or VT’s.

• Relays operate on current, voltage, power, or impedance.

• Some relays have a built in, time delay, either definite time or inverse time.

1.5 Classes of Protection

Protection systems can be divided into two basic classes:

Unit Protection Unit protection protects a precisely defined area of the pri-mary system and will respond only to faults within that area.

• Typical examples are differential protection, differential earth faultprotection, busbar protection, Buchholz relay, pilot wire, directioncomparison earth fault.

Non-Unit Protection will respond to a fault within an area that is not pre-cisely defined.

• Typical examples are overcurrent protection, unrestricted earth faultprotection.

1.6 Characteristics of a Good Protection Scheme

• Reliability

• Discrimination

• Stability

• Speed of operation

4

Page 10: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

m2 Common Terms Related to Protection

Back up Protection This is a second, often slower and cheaper protectivesystem, that supplements the primary protection should the latter fail tooperate for any reason.

CT Current Transformer

Definite Time Relay A relay which operates in a pre-determined time, whichis not affected by fault values. Usually it is operated by the closure ofa contact on another relay, such as an instantaneous over-current relay,instantaneous earth fault relay, etc.

Discrimination The ability of protection to select and disconnect only thefaulty equipment, leaving as much other equipment as possible live. Alsocalled “selectivity”

Instantaneous Relay These are relays whose operation is not intentionallydelayed. Typical operating times are from about 0.05 to 0.1 second.

Inverse Time (e.g. Overcurrent Relay) These have a time of operationthat decreases as the magnitude of the operating current (or other op-erating quantity) increases.

Non-Unit Protection Protection that will respond to a fault over a wide areaof the system. In general the area will not be precisely defined.

High Speed Tripping This is a relative term but generally implies operationin less than 2 or 3 cycles (0.04 or 0.06 seconds).

HV High Voltage

LV Low Voltage

Primary Protection This is the main protective system that is intended tooperate on an internal fault.

Relay Drop off Value When the current is lowered, the value at which therelay returns to the de-energised position.

Relay Pick up Current The value of current at which the relay just operatesand closes its contacts (or voltage for voltage operated relays).

Reliability In the event of a fault in a zone, the protection of that zone mustoperate and trip the correct circuit breakers to isolate that zone, andonly that zone, from all live supplies. If it fails to operate, or operatesunnecessarily, the protection system is said to mal-operate. Achievingreliability requires correct design and installation and regular maintenanceof the protective equipment.

Residual Current The current that results from combining the three currentsin the phases. Paralleling the three secondaries of CT’s on R, Y and Bphases gives an output of the vector sum of the currents in the three phases- the residual current. This is commonly connected to an earth fault relay.

5

Page 11: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

mResidual Voltage The vector sum of the voltages to earth of the three phase

conductors. The secondary equivalent is obtained by connecting the threeVT secondaries in series.

Restraint A relay may be hindered from operating by some quantity, such asvoltage. it is then said to be given (voltage) restraint. An impedancerelay is restrained by voltage, operated by current. The current tendingto close the contacts, the voltage to open them.

Sensitivity A protective scheme is sensitive when it will respond to very smallinternal faults, but note that extreme sensitivity is usually accompaniedby poor stability.item[Selectivity or discrimination] The protection in any zone is said todiscriminate or be selective, when it can distinguish between an internalfault within the zone and an external (through) fault in another zone. Theprotection should trip on an internal fault but ignore all external faultsand normal load current. A scheme that lacks discrimination will causeunnecessary disconnection of healthy plant and circuits.

Signal Link A communication link between two substations used for protec-tion purposes, usually to close (or open) a contact at the remote station.The link may be by metallic wires (pilots), carrier over pilot wires, powerline carrier, radio, etc.

Speed of Operation The longer a fault is allowed to persist, the greater thedamage that may be caused. In the case of a high current fault close toa generator, synchronisation to the system may be lost. Fast operationshould not, however, be sought at the expense of selectivity or reliability.

Stability Protection is stable if it does not respond to faults outside the pro-tected zone, i.e. it operates only for those faults it is designed to operatefor.

Unit Protection Protection which protects a precisely defined area of thepower system. It responds only to faults within that defined area. Typicalexamples are differential protection, busbar protection, Buchholz relay.

VT Voltage Transformer

6

Page 12: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

m3 Unit protection schemes

Unit protection responds only to faults within clearly defined boundaries andtherefore no time delay is necessary for discrimination. This allows fast clearancetimes which are important for protection of main equipment such as generatorsand transformers. Usually the protective scheme consists of two CT’s per phase,one set at each end of the protective zone. The relay measures the differencebetween the secondary currents. If the zone is healthy, there is no differencebetween the currents and the relay remains inoperative. If a fault occurs withinthe zone (i.e. between the ends), currents from the CTs no longer balance andthe relay operates.

Examples of unit protection:

• Differential protection of generators

• Differential protection of transformers

• Overall differential protection of generator transformers

• Differential earth fault protection of the star winding of transformers,including cables

• Earth fault protection of transformer delta windings

• Busbar protection

• Pilot wire protection

• Some directional comparison schemes (or distance carrier)

• Buchholz protection

3.1 Transformer protection

3.1.1 The Buchholz relay

The Buchholz relay is mounted on transformers in the oil pipe between themain transformer tank and the conservator tank. Its purpose is to collect anygas from the transformer. Gas given off can be an early warning of damageto the transformer and early detection can greatly reduce the cost of repair.The Buchholz relay has two switches, ”alarm” and ”trip”. The alarm switch isconnected to a float in the top of the relay.

This will operate when a certain amount of gas has accumulated in the re-lay. The trip switch is connected to a flap in line with the oil pipe, and mayhave a float in addition. In the event of major trouble the switch will be ac-tivated by a sudden rush of gas or oil. Some transformer tap changers have aBuchholz relay with trip contacts only.

Early Buchholz relays used mercury switches; these caused spurious alarmsor trippings in times of earth tremors due to slopping of the mercury. Thesealarms or trippings can be prevented by the use of a seismic blocking relay which

7

Page 13: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

mswitches the Buchholz relay out of service when earth tremors are detected. Aseismic blocking relay uses the pendulum principle. When the pendulum moves,contacts close and the Buchholz trip circuit is temporarily made inoperable.This relay must he firmly mounted so that movement caused by vehicles etc isnot detected. The disadvantage is that at the time of earth tremors this pro-tection is out of service.

An improved method is the use of a Buchholz relay using reed switches. Theseare not affected by movement, as reed switches are closed magnetically. Toprevent the possibility of reed switches closing due to the magnetic field causedby inrush currents special ”biased reed switches” are used. These have a smallmagnet holding the contacts open. This prevents the switch from being closedby stray magnetic fields. When the switch is moved to its operating magnet,the switch closes as usual.

The Buchholz alarm which is float operated can be activated by low oil levelallowing air into the relay or by air from the oil in the transformer after filteringhas been carried out.

The Buchholz relays primary purpose is to provide early warning of conditionsinside the transformer that indicate the probability of a developing fault. If alarge internal fault in the transformer does develop, the fault would be clearedby a differential relay.

3.1.2 Explosion Vent

Explosion vents are fitted to all large transformers. This vent is a large diameterpipe welded to the top of the transformer tank with a down turned burstingdisk or diaphragm. The pipe is usually higher than the conservator tank toprevent excessive loss of oil, should the disk burst. The explosion vent protectsthe transformer case from building up pressure in the case of an internal fault.When a serious internal fault occurs gas is produced. This quickly builds uppressure which will operate the Buchbolz trip. Should the pressure not besufficiently relieved the bursting disk will shatter and relieve the pressure frominside the tank case. This is usually obvious by the spillage of oil down thetransformer and over the ground below the vent.

3.1.3 Qualitrol Pressure Relief

A more modern form of explosive vents for transformer is called a Qualitrol.When a fault or short circuit occurs in a transformer, the arc instantaneouslyvaporises the liquid causing extremely rapid build-up of gaseous pressure. Ifthis pressure is not relieved adequately within several thousandths of a second,the transformer tank will rupture spraying flaming oil over a wide area. TheQualitrol pressure relief valve opens fully under such pressure within 2 millisec-onds.

3.1.4 Continuous Gas Analyser

Most modern large transformers are fitted with a dissolved gas analyser whichcan provide continuous on-line reading of dissolved gas in oil and also moisture

8

Page 14: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

m

Figure 1: Photo of Transformer explosive vent

Figure 2: Photo of Transformer Qualitrol

9

Page 15: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

mlevel in oil.

The gas detection component is based on combustible gases dissolved in oilpassing through a selectively gas-permeable membrane into an electrochemicalgas detector. Within the gas detector, the gases combine with oxygen from theambient air to produce an electrical signal that is measured by an electroniccircuit and converted to ppm. The gas detector is sensitive to the gases thatare the primary indicators of incipient faults in oil-filled transformers (i.e. Hy-drogen, Carbon monoxide, Ethylene, and Acetylene).

Moisture detection is performed by a thin-film capacitive moisture sensor. Thecapacitive value of this sensor varies according to the moisture level and thisvalue is converted to an electrical signal.

Both the gas detection and moisture level reading are configured to generatealarms but are not usually connected to transformer trip circuits.

Figure 3: Photo of Transformer Gas Analyser

3.1.5 Earth Fault Protection of High Voltage Delta Windings

This protection is provided by an earth fault relay operated from CT’s in theleads to the transformer HV delta winding. See Figure 4.

The delta winding, being insulated from earth, cannot provide an earth re-turn path for faults anywhere on the system between the generation source andthe HV CT’s.

The earth fault relay can only operate for earth faults on the transformer delta

10

Page 16: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

m(primary) winding or leads from the transformer to the CT’s.

The protection is therefore a form of unit protection and trips without timedelay.

Earth Fault Relay

R

Y

B

a2

b2

c2

A2

B2

C2

CT’s

Figure 4: Delta-Star transformer Protection

Consider the case of a delta star transformer as shown in Figure 4 supplied fromgeneration source on the left hand side of RYB, and connected to load a2 b2 c2.

When the transformer is un-faulted, the currents in each of the leads R,Y,Bat any instant of time return through the other two. The secondary currentsfrom the CTs circulate round the CT secondaries, but do not pass through theearth fault relay.

Faults to earth in the secondary side of the transformer (e.g. feeder faults)do not operate the HV earth fault relay. An earth fault on secondary terminala2 will be balanced on the supply side by primary current in R phase returningto the source via B phase.

Even with the transformer back livened from the secondary, the earth faultrelay could not pick up for a primary earth fault to the left of the CTs.

Now if there is an earth fault on say the HV A2 terminal, earth fault cur-rent will flow through Red phase CT and operate the HV earth fault relay.Thus operation of the relay only occurs for HV faults on the transformer andconnections up to the CT.

Advantages

• Unit protection given for earth faults on HV winding.

• Location of the fault is more easily found than for full differential protec-tion where LV faults also actuate the relay.

11

Page 17: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

m• Fast operating, and cheap.

Disadvantages

• Only operates for HV earth faults.

• Does not cover HV phase to phase faults, short circuited turns, or LVfaults. (However if the fault is inside the transformer, it is cleared by thebuchholz relay.)

Remember

• Differential earth fault protection of transformer LV star windings alsoprotects the LV cables if the CT position includes them in the protectedzone.

• Earth fault protection of the delta winding may operate for flashover ofthe transformer rod gaps or surge diverters.

3.1.6 Differential protection

Circulating Current Differential Protection Figure 5 shows two CT’s, Aand B, protecting the conductor AB with differential protection. An externalload or an external fault is represented at F. Secondary currents flow as shown,and if the CTs have the same ratios and maintain their accuracy, the currentscancel out to zero and no current flows in the relay.

R

CT - A CT - B

Fault to earth(F)

A B

Fault Current

Figure 5: Fault is outside area covered by CT’s therefore relay does not operate(i.e. current from CT – A is cancelled by current from CT – B)

If an internal fault occurs between the CT’s as shown in Figure 6, secondarycurrent flows in the relay. If current is fed to the fault from side A only, theequivalent secondary current flows into the relay. If current is also fed in fromside B, the secondary current is added to that from CT A. Hence the relayoperates for internal faults (i.e. faults between the two CTs).

Differential relays fall into two basic types:

• Simple instantaneous relays.

• Biased relays (relays with current restraint).

12

Page 18: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

mR

CT - A CT - B

A B

Fault

Fault to earth(F)

Figure 6: Relay operates as fault is between CT’s (i.e. current from CT – A isNOT cancelled by current from CT – B)

Relay Operates

Relay does not operate

Relayoperating coilcurrent

Current through CTs A and B

Figure 7: Instantaneous relay

Relay Operates

Relay does not operate

Relayoperating coilcurrent

Current through CTs A and B

Figure 8: Biased relay

13

Page 19: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

mSimple Instantaneous Relays Attracted armature type relays can be verystable in differential circuits where the currents entering and leaving the equip-ment are identical, i.e. differential protection of busbars and generators, butnot transformers. Simply by connecting a resistance in series with the relay, ofa value chosen to simple established rules, it can be assured that the relay willnot operate for faults external to the protected zone.

The CT’s must have the same turn’s ratio, and reasonably similar magneti-sation characteristics.

Biased Differential Relays These relays are given a restraint against op-erating which increases with the through current. A common construction isthe induction disc pattern, similar to the inverse over-current relay, with anoperating coil on one electromagnet causing the disc to rotate to close the relaycontacts. Another coil carrying the secondary equivalent of through currentproduces a torque on the disc in the opposite direction, tending to prevent(restrain) relay operation (see Figure 9).

CT CT

Restraint

Operating

Figure 9: Biased type relay

Neglecting initial spring tension then, a 1 amp relay with 20% bias would op-erate at 0.2 amp with 1 amp through current, and operate at 2 amps with 10amp through current.

This assists the relay to remain inoperative when the two CTs do not matchcorrectly in ratio. In particular this occurs with transformer differential pro-tection, where there are taps on the main transformer. The CT ratios may besatisfactory for one transformer tap ratio, but not for other taps.

Transformer Differential Protection In the differential protections de-scribed above the currents entering and leaving the equipment are identicalin value if the equipment is healthy. In transformer differential protection, theinput and output currents (primary and secondary) which are compared, havea known ratio to one another unless there is a short circuit in the transformer.Figure 10 shows a single phase transformer of ratio 66kV to 11kV (It will have aturns ratio of 6/1). If 600 amps flow in the 11 000 volt secondary, this must be

14

Page 20: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

m600 Amps100 Amps

CT 100/1 CT 600/1

Transformer66kV / 11kVVoltage Source Load

1 Amp 1 Amp

Relay Operating Winding

Figure 10: Protection of single phase of a Transformer

balanced by 1/6 x 600 = 100 amps in the primary winding. Ignoring magnetisa-tion current (normally very small), the ratio secondary output current/ primaryinput current will always be the same as the no load voltage ratio primary volts/secondary volts (6/1 in this case) unless some or all of the transformer turns areshorted.

Now if CT’s of 100/1 and 600/1 amp ratio are inserted in the primary andsecondary connections as shown and the CT secondaries are connected to a re-lay, a current of 1 amp will circulate round the CTs, and the current through therelay operating coil will be zero (or practically so). If the transformer is partlyor wholly short circuited, the balance of currents to the relay is upset, andthe relay operates. Hence faults which occur between the HV and LV currenttransformers are detected.

3.1.7 Differential Protection of a Three Phase Transformer

The three main features of a practical transformer differential scheme for a threephase transformer to provide stability are the:

Choice of correct CT connections and ratios The type of connectionused on the main transformer determines the relay connections to the protec-tive CTs in order for currents on each side of the relay to cancel for all types ofthrough fault (phase to phase or earth faults).

Thus corresponding to a given star delta connected transformer a particulardelta star scheme of CT interconnections is required. Also the overall CT ratioshave to match the main transformer ratios (and current ratings). If the instal-lation does not conform to the required protection scheme, unwanted trippingmay occur after the load has built up above relay sensitivity.

Provision for Slight CT Mismatch As mentioned above, a biased typerelay is provided for stability as different tap ratios on the main transformers

15

Page 21: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

mresult in different current ratios for the transformer.

Provision of Stability against Magnetisation Inrush Currents Whenthe voltage supply to a transformer is suddenly switched on to liven it, magneti-sation currents are drawn from the supply of a value many times full load of thebank. These currents on one side of the bank are not matched by correspondingcurrents on the output winding and hence, fed only to one side of the relayappear as a transformer fault. The currents take many seconds to decay to thenormal low value.

These magnetisation inrush currents contain a high proportion of 100 cycleper second (100 Hz) component which is the second harmonic of the normal 50Hz supply frequency. Internal transformer fault currents for which the relay isexpected to operate do not contain this second harmonic.

This characteristic is used to make the relay immune to operation from mag-netisation inrush currents. A proportion of relay operating current is passedthrough a filter circuit, and the 100 Hz component from it is fed into a sensitivewinding on the relay which hinders it from operating. A timer of approximately20 seconds is usually employed to ensure inrush currents have stabilised.

The connections for the protection of a three phase transformer are shown inschematic form in Figure 11. Note that this diagram does not show the secondharmonic restraint nor taps on the relay.

R

Y

B

Power Transformer

Bias Coils

C.T’s C.T’s

Neutral Point

Relay Operating Coils

Figure 11: Transformer Differential Protection

Advantages

16

Page 22: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

m• High speed of operation.

• Protects external leads, cables, and bushings not covered by buchholz.

• Being unit protection - provides discrimination with time delayed non-unitprotection elsewhere on the system.

Disadvantages

• Does not detect some incipient faults. (These are detected by the buch-holz)

• Does not protect the transformer against overheating due to overloads orexternal short circuits.

3.1.8 Differential Earth Fault Protection of Star Windings

This protection consists of three phase CTs with secondaries connected in par-allel to give the earth fault current. This residual current is balanced againstthe secondary current from the transformer neutral CT and the difference isapplied to the differential relay (see Figure 13).

Thus the scheme detects earth faults between the neutral CT and the phaseCT’s, i.e. in the star winding of the transformer, LV bushings, and cable up tothe switchgear containing the CT’s.

This relay is generally used with lead sheathed cables on 11 kV installations,and phase to phase faults are practically impossible on the 11 kV side. (Faultson single core 11 kV cables will be earth faults.)

Advantages

• Low Cost.

• Fast fault clearance for heavy faults on cables as well as on the transformer.

• In conjunction with buchholz and fast protection of the delta winding, itvirtually provides unit protection of the bank, provided that short circuitsbetween phases are unlikely on either the HV or LV side, i.e. when cablesare used on the star connected side, and spacings are larger on the other.

Disadvantages

• Does not protect against phase to phase faults or short circuited turns,nor faults in the delta winding.

• When connections from the star winding are by overhead conductor in-stead of cable, phase to phase faults are not cleared, and where two banksare installed, both banks are tripped on overcurrent.

• May not detect earth faults at the neutral end of the transformer winding.

Remember

• Unit protection operates for faults within clearly defined boundaries, usu-ally between two sets of CTs.

17

Page 23: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

m

}

M

M

M

L

L

L

A2

B2

C2

E

Neutral C.I

C.T

To TripCircuit

RestrictedE/F relay

Figure 12: Differential (Restricted) Earth Fault Protection of Transformer -Operation on Fault inside Zone

}

M

M

M

L

L

L

A2

B2

C2

E

Neutral C.T

C.T

RestrictedE/F relay

To TripCircuit

Figure 13: Differential (Restricted) Earth Fault Protection of Transformer –Operation on Fault outside Zone

18

Page 24: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

m• There will be practically no current in a unit protection relay for an ex-

ternal fault.

• When unit protection operates, it trips without time delay.

• In differential protection of transformers:

• CT ratios and interconnections are chosen so that the currents com-pared in the relay are nearly equal.

• Slight mismatch of currents is permitted by the relay design (bias).

• Transformer magnetisation inrush currents could operate the relay,but restraint is provided on modern relays by using the 100 Hz con-tent.

3.2 Busbar protection

Busbar protection is another example of unit protection. The most commonrelaying principle adopted in the New Zealand transmission system is the highimpedance differential scheme, which is a circulating current scheme.

The basic principle of busbar protection is that for an un-faulted busbar thetotal input current is equal to the total output. The sum of the currents is zerofor each phase. The relays measuring the summation of the currents receive nocurrent for un-faulted conditions of the busbar. However when a busbar faultoccurs, the balance is upset, and the relay receives current causing it to operate.

The extent of the busbar and associated equipment protected by busbar pro-tection (i.e. the ”bus zone”) is dependent upon the position of the busbarprotection C.T’s. The C.T’s may be in the circuit breaker (bulk oil circuitbreakers) or adjacent to the circuit breaker.

3.2.1 Check Zones

Because the consequences of an incorrect bus zone trip can be very seriousa completely independent check zone supplied by separate bus zone currenttransformers is usually included within a bus zone protection scheme. Thecheck zone encompasses the whole bus and therefore contains both zone A1 andzone A2 in a typical three zone scheme. For a bus zone tripping to occur bothdifferential relays have to respond to a fault e.g. for a fault in zone A1, the zoneA1 differential relay and the check zone differential relay. Detecting the faultby two separate relays greatly reduces the risk of accidental trips.For this scheme for a fault within zone A, both the zone A and the check zonedifferential relays have to operate before a bus trip will occur.

In many cases it is not acceptable to remove the whole bus from service. Abus coupling CB can be used to sectionise the bus into two sections.A fault on the bus in zone A1 will be detected in zone A1 and the cheek zone.CBs 42, 52, 62 and 68 will be tripped via their bus zone relays. This leaves theother section of the bus in service.

An example of Bus Zone Protection without a check zone is shown in Figure 16.

19

Page 25: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

m

 Figure 14: Busbar protection scheme for a single busbar

42 62

68

72 92

52 82

Zone A2

Check Zone

Zone A1

Figure 15: Bus zone protection scheme for a single bus with bus section circuitbreaker

20

Page 26: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

m

Bus B

Zone B

Zone A

Bus B112 142 172

132 162 192

Figure 16: Bus zone protection for circuit breakers and a half without checkzone

21

Page 27: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

mIn this case a Bus A fault will trip CBs 112, 142 and 172 this will disconnectBus A without the loss of any supplies due to the Circuit Breaker and a halfconfiguration. The check zone is not essential, as in the case of accidental trip-ping, no supplies are lost.

However, a check zone may be included with a circuit breaker and a half scheme,so always check. The half breakers are not included in either zone and so arenot covered by the bus zone protection.

3.2.2 Blind Spots and Blind Spot Protection

A fault between 68 and the CT in Figure 17 is in the blind spot of the bus zoneprotection.

NOTE: Blind spots only exist where current transformers are separate fromthe circuit breakers.

This fault in the blind spot will be detected by the busbar protection withinthe CT zone (zone of detection) and thus the busbar protection will operatethe zone A1 circuit breakers 42, 52, 62 and 68 in Figure 17. However, the faultwill not be cleared by these trippings (even though the fault current may hesignificantly reduced).

42 62

68

72 92

52 82

Zone A

Check Zone

Zone A1Blind Spot

Figure 17: Busbar protection scheme for a single bus with a bus section circuitbreaker

The fault can be cleared by:

• Tripping the circuit breakers at the remote ends of the circuits associatedwith circuit breakers 72, 82 and 92 (no blind spot or CB fall protection

22

Page 28: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

mfitted). This would be a zone 2 tripping and would not clear the fault forapproximately 0.65 seconds.

or

• By tripping circuit breakers 72, 82 and 92 via the zone A2 trip circuitry(blind spot protection fitted).

Blind spot protection in its simplest form is only a timing relay. A faulttakes place in the blind spot in Figure 17. Zone A1 and the check zonerelays detect this fault. Zone A1 circuit breakers are opened but the faultis still supplied from zone A2 bus. A timing relay is also activated. Aftera short time, approximately 0.15 seconds, zone A1 and check zone relaysare still detecting a fault. As the zone A1 circuit breakers are open thefault must be in the blind spot and zone A2 is tripped by the timing relay.This requires a definite time to elapse, but is much faster than a zone 2tripping from remote stations. The fault in the blind spot did howeverclear both sections of the bus.

or

• Using CB fail protection

The CB fail protection would detect current flowing through the CT ad-jacent to CB 68, after the CB had opened. This would be taken as a CBfailure and a trip signal sent to CBs 42, 52, 62, 72, 82 and 92, to isolateCB 68 which had ”failed”.

Blind spot protection is now being removed and replaced with CB failure, asit completes the same function as blind spot protection, as well as protectingagainst failure of a CB to operate.

Blind spots also exist between all other circuit breakers and their CTs. Considera fault between 42 and its CT. As this is seen as a bus fault zone A1 will trip.The fault will still be supplied from the remote end of the circuit which will tripin zone 2. Other supplies on that bus have been interrupted unnecessarily. Ide-ally we are only required to trip the circuit on 42, but as the fault was ”behind”the CT it is seen on the bus and not on the circuit.

3.2.3 AC Wiring Supervision

Wiring supervision relays are required to detect abnormal voltages on the CTwiring. One - three phase relay is required, per zone. Abnormal voltages can becaused by open circuited CTs, CT isolator switch open while primary circuit ison load, AC wiring fault, etc.

If abnormal voltages are detected on the CT wiring then the protection is dis-abled for the duration of the fault.

AC wiring supervision flags are self resetting and generally only evident fora few seconds.

23

Page 29: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

m3.2.4 DC Supply Failure

In older installations a DC supply failure relay (or trip supply supervision relay)is used to detect a D.C supply failure to the bus zone protection. One relay perscheme or one per panel is generally installed.

In more modern installations it is incorporated with the bus zone protectioninoperative alarms. A loss of D.C supply to the protection will render theprotection inoperative.

3.2.5 Protection Inoperative Alarm

An alarm is fitted to each separate bus zone to indicate loss of protection. InFigure 17 these alarms are installed for zones A1 and A2. It is not necessary toinstall a separate alarm for the check zone as a fault in the check zone protectionwill alarm all zones connected to it. A loss of check zone protection in Figure17 will alarm both A1 and A2 zones.

This alarm can occur due to:

• Wiring supervision relay operation.

• The test switch being left in the test position.

• Failure of the D.C power supplies to the relay.

3.2.6 Circuit Breaker failure (CB fail) Protection

When a circuit breaker receives a trip signal, but fails to fully disconnect itsassociated faulted primary plant within its normal operating time, CB fail pro-tection will be activated.

This protection will then attempt to disconnect an adjacent circuit breakerso as to complete the disconnection of the faulted primary plant.

CB fail protection shall be enabled only when the protected circuit breakerhas been called upon to trip by operation of its associated protection systems.It shall not operate if the circuit breaker fails to open during a routine switchingoperation or automatic switching sequence unless such failure coincides with orprecipitates the development of a system fault, resulting in the operation of itsassociated protection systems.

Remember

• Busbar protection is a special case of circulating current differential pro-tection (as for generators).

• It looks more complicated because there are more than two sets of CTsfor current summations.

• When the current entering the busbar is equal to the current leaving, thesum of the currents is zero. Hence the sum of secondary currents is alsozero, and the relay is inoperative.

24

Page 30: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

m• If a fault occurs on the busbar, the balance is upset and the relay operates.

• A second differential relay must also operate for tripping to occur - thebusbar check differential relay.

• Circuit supervision relays cut out the protection after a time delay if thereis a slight out of balance of current.

• A check zone is usually included and the check zone and the faulted zonemust detect the fault before a tripping takes place.

• Bus zone protection is most effective when the bus is in several sectionsto limit the effect of the tripping.

• Blind spots exist between CBs and CTs. Faults in blind spots usuallyremove more equipment than essential from service to clear them.

3.3 Circuit Protection

3.3.1 Distance-time and definite distance protection

Distance relays are used to protect transmission lines. As their name impliesthey measure the distance from the relaying point to the fault, and trip if themeasured distance is less than the relay setting.

V

L

Substation

Generating Source (s)

Fault

I

F

Z

Figure 18: measurement of distance to fault

L = Distance of fault from substationV = Voltage of line at substationI = Line current flowing in the transmission line loopZ = Impedance of the loop

Relay Measurement Figure 18 shows two conductors of a transmission linefaulted at F.

Fault current flows from the substation around the transmission line loop andis supplied via current transformers to the relay. The voltage across the loop is

25

Page 31: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

mmeasured by the line (or busbar VT) to the relay.

Providing the resistance of the fault is negligible, the measured ratio Line Volts/Line Current (V/I) is the impedance of the transmission line loop. Also the loopimpedance z is proportional to distance L. Hence a measurement can be madeof the distance to the fault.

If the measured impedance is less than the set value, it means that the fault iscloser to the substation than the distance for which the relay is set and thereforethe trip relay will operate.

Discrimination Discrimination is provided by using the stepped time dis-tance characteristic, as shown in Figure 19. AB and BC are transmission linesfed from both ends A and C. The relay at A measures the distance to the faultwhen the fault current flows out from the busbar A into the line, and has thetime distance characteristic shown above the reference line 00. Thus for allfaults within the first 85% (approximately) of line AB, the circuit breaker at Ais tripped instantaneously. For faults further away the relay waits for about 0.5seconds (zone 2 time), then measures a longer distance zone 2 (say 120% of theline length) and if the fault is measured within this distance, breaker A trips.If the fault continues, a greater distance zone 3 is measured and tripped in stilllonger time (usually 1.2 seconds for zone 3 trippings). In addition a zone 4 maybe fitted that will operate in 4 seconds.

Relay B on the line BC has a similar characteristic with tripping time char-acteristics shown above the reference line 00. Relays at C on the line CB andB on the line BA, measure for faults flowing from right to left on the diagram,and have the characteristics shown below the reference line 00.Consider now a fault at F. Relay A measures the fault as beyond zone 1 butbefore zone 2 time elapses the fault is cleared at B. (Relay B, facing C, measuresand trips in zone 1 instantaneous time.)

Note that zone 1 of each relay is arranged to cover about 85% of a line. Thisis because the distance relays have unavoidable errors in measuring distance. Amargin has to be allowed so that faults outside’ the line are not seen as zone 1faults.

Zone 2 distance covers about 120% (or more) of the line to ensure definitedetection of all faults at the end of the line. Zone 3 provides general back upprotection (some schemes include a fourth zone for back up.)

Importance of Voltage Supply Distance relays measure distance from thecurrent/voltage ratio measurements at the relaying point. Current tends to op-erate the relay, and voltage to restrain tripping. It is therefore important thatVT supplies should always be maintained to distance relays. The absence ofVT voltage results in relays seeing an apparent fault, and provided the currentis sufficient, the relay trips. Loss of voltage means that the impedance seen bythe relay is zero.

26

Page 32: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

m

 

B

F

A C

B– Zone 2

B– Zone 1B– Zone 1

B– Zone 2

A – Zone 1

A – Zone 2

A – Zone 3

C – Zone 1

C – Zone 2

C – Zone 3

A -

time

to o

pera

teB

- tim

e to

ope

rate

C -

time

to o

pera

te

0 0

0 0

0 0

Figure 19: distance protection zones

27

Page 33: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

mi.e. voltage V = 0 therefore Z =

V

I=

0

I= 0

Measurement of Direction by Distance Relays For phase to earth, andphase to phase faults, a voltage in a selected un-faulted phase is used as a ref-erence of the direction of the fault (towards the line, or reverse direction).

The relay trips in the first two zones for faults out towards the line, but doesnot trip for reverse faults (behind the busbars).

The measurement principle used extensively combines directional measurementand distance measurement in one relay element. (One tripping contact, onlyclosed when direction is correct, and volts/amps measurements conform to set-tings).

Starting Relays Starting relays are used to sense a fault on the system, andstart the various relay measurements. If the fault is cleared elsewhere on thesystem the starting relays reset. (Starting flags do not necessarily mean that afault has occurred on that particular transmission line.)

Impedance relays are generally used on each phase, and are given directionalphase angle characteristics for better load carrying insensitivity. The startingrelays also select which phases are to be measured, and whether to measure forfaults to earth or to measure phase to phase faults.

Earth fault relays are used to initiate earth fault measurement.

Negative sequence current relays are used in some relays to initiate phase tophase fault measurement, these detect current imbalance in the three phases.

Measurement of Three Phase Faults For three phase faults close to theprotection relay, all voltages fall very low, and in particular, the phase to phasereference voltage is very low. The reference voltage is the phase to phase volt-age which is used to enable the relay to determine in which direction the faultcurrent flows, whether to the line or from the line. Without sufficient referencevoltage the relay is unable to trip.

One commonly used scheme to overcome the difficulty is to use a “memory”action. This is simply a resonant circuit tuned to 50-cycles, so that the currentin the reference winding persists for a few cycles after the reference voltage hascollapsed. Thus with the relay in service, if a three phase fault occurs the relaycan determine the direction of the fault.

However when the VT’s are directly connected to the line, and the line cir-cuit breaker is open, there is no voltage for the relays to ‘remember’ and thefeature cannot operate. This is overcome by arranging a contact to be closedfor a short time while the main breaker is being closed. If any starting relay op-erates, the trip circuit is completed through this contact, and the main breakeris tripped.

28

Page 34: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

mOther relays at the station, with already livened VT’s will sense the directionby memory action, and will not trip.

Voltage Transformer Supply A three phase switch for disconnecting thesecondary voltages is usually fitted on the relay panel, this also disconnects theD.C supply to the relay, and effectively prevents the distance relay from operat-ing. When busbar VT’s are utilised, a changeover switch is fitted to select thevoltages from one of the VT’s.

Care has to be exercised that the VT supply to relays is not lost, particularlywhen sectionalising a busbar with VT’s on it, or an accidental tripping mayresult. Care must also be exercised with busbar VT’s to ensure that the relayreceives the line terminal voltage from a VT directly connected to the line viathe line circuit breaker not through a circuitous route involving line impedances.In the latter case distance measurement would be incorrect.

Advantages of Distance Protection

• Rapid tripping for faults, which is essential near generating stations topreserve coordinated generation.

• Applicable in a complex transmission network with interconnecting gen-erating stations.

• Applicable to long and medium length lines, i.e. all but very short lines.

• Good discrimination between fault and load current.

• Good discrimination with faults external to the protected line.

• High reliability.

• Even without carrier, most faults trip in zone 1 time of 0.04 seconds;remaining faults are finally cleared within 0.5 seconds.

• With short clearing time, minimum damage to conductor strands results.This is particularly beneficial for aluminium conductors.

Disadvantages of Distance Protection

• Not suitable for short lines.

• Relatively high cost if compared with overcurrent relays.

• Requires supply of line terminal voltage.

• Complicated due to the various possible faults to be measured (differentphase combinations, zone 1 and zone 2, and starting relays).

• Measurement may be affected by fault resistance.

Remember

• All distance relays measure the distance to the fault using the voltagesand currents, and decide whether the measurement is less than the relaysetting.

29

Page 35: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

m• Stepped time distance characteristics are used for discrimination.

• The measurement by relays used in New Zealand is inherently directional.

• Three phase measurement of close up faults present a design problem,generally overcome by use of ”memory” relays.

• Distance relays measure line impedance and so must be supplied with theline terminal voltage. The line terminal voltage is the same as the busbarvoltage when the line circuit breaker is closed.

In some installations the line terminal voltage for the relay is taken froma busbar VT (usually on 110kV circuits). In such instances, if the busbaris to be split, care must be taken that the busbar VT used is directlyconnected to the line (through the line CB, and not through a circuitousroute involving line impedances) otherwise distance measurement will bewrong.

• Disconnection of the VT supply to the relay, other than by special meansprovided, can result in relay tripping due to load.

Protection Signalling with Distance Protection Communications linksbetween two stations (power line carrier, radio, etc.) are used for protectionpurposes. One application is, in conjunction with distance protection, to pro-vide fast tripping for faults over the entire length of a transmission line, in zone1 time, without any zone 2 time ”delayed trippings”.

Closure of a relay contact at station A produces a closed contact at stationB.

Acceleration with Distance Protection In the ’acceleration’ techniquetripping at one end of the line in zone 1 accelerates the operation of the zone 2measurement at the other end of the line (see Figure 20).

Consider a line AB, faulted within 15% of its length from station A. The relayat station A trips immediately, and sends a signal to station B to change itsdistance measurement from 85% of the line length to 120%. The relay at B nowdetects the fault and trips without having to wait for zone 2 time to elapse.One advantage of this carrier signal system is that there is no danger of trip-ping a remote circuit breaker during communications or protection maintenance.

The same signal as used for accelerated distance protection can be used withearth fault directional comparison protection. The two protections can be com-bined and are on most Transpower 220 kV transmission line protection schemes.

The loss of carrier (or other signalling channel) results in the loss of the di-rectional comparison and the distance protection reverts to plain distance pro-tection.

30

Page 36: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

m  

Tim

e

Tim

e

Postion of Fault

0 0

Normal characteristics of relay at B

Zone 2 time shortened by signal from A

Tripping characteristic of relay at A

A B

Figure 20: Acceleration of Distance measurement

Directional Protection with Carrier Blocking In this scheme the zone 2measurement of 120% of the line length trips with virtually no time delay, unlessa signal is received from the adjacent station indicating that the fault is externalto the line. In this event the relay temporarily changes to 85% line measurement.

This scheme requires careful coordination of relay and carrier signal timings,but the carrier signal does not have to be sent over a faulted transmission line.It has been used on the New Zealand grid but is currently out of favour.

Command Tripping Another use of a signalling system is command trip-ping. Under this scheme the signal trips directly. Wrong tripping due to a spu-rious signal (electrical interference from arcing of isolators etc.) can be avoidedby coding the signal.

This scheme would be used say in tripping a circuit breaker at a remote con-trolled station if a buchholz relay operated, and there was no local circuitbreaker.

Permissive Tripping In this scheme tripping from a signal received is onlypermitted if a local fault detector relay operates as well. The local fault detectorcould be, say, undervoltage relays.

Signalling Systems

• Power Line Carrier Chop System - In this system a ”carrier” signal is sentunder healthy conditions. To send a signal, the carrier is removed. Receiptof no carrier at the other end causes the action required. The protectionsignal shuts itself down at both ends of the line after a set time delay andbrings up an alarm. This system operated satisfactorily for many years,but is now being gradually replaced.

31

Page 37: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

m• Frequency Shift Signalling - Under normal conditions a steady signal

(guard signal) is sent. To transmit a protection signal, the guard sig-nal is stopped, and replaced by an operate signal of a different frequency.Hence the name frequency shift. The transmission medium may be carrieror radio.

Directional Comparison Earth Fault (DCEF) Signalling systems arealso used to link directional earth fault relays at both ends of a transmissionline, thus enabling them to function as DCEF protections. In this scheme if arelay senses an earth fault in the line direction (towards its companion station)it sends a trip signal.

The primary condition of a faulted transmission line for tripping by DCEFis that fault current is fed inwards towards the line from both ends; hence therelaying condition for tripping is that each protection is both sending and re-ceiving a trip signal (see Figure 21).

Fault

RELAY RELAY

Trip Trip

RELAY RELAY

Trip Block

Fault

Figure 21: Differential comparison Earth fault protection

If the fault is external to the line, the primary fault current flows out of theprotected line at one end. The corresponding relay swings to the ”block” posi-tion and does not transmit a ”trip” signal, hence neither of the line breakers istripped.

This protection can detect earth faults more sensitively than distance protection,and hence detects faults at towers with relatively high tower footing resistanceto earth.

The same carrier signal can be used for DCEF as for distance protection withacceleration.

32

Page 38: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

m3.3.2 Auto Reclose

The majority of faults on transmission lines are transient ones, and when theline has been disconnected at both ends the arc at the fault de-ionises (cools),after which the line may be successfully re-livened. When a signal system is usedto provide fast tripping at both ends of the line (eliminating any zone 2 delayedtripping) high speed auto reclose can be used successfully. Thus the carrier isnot used directly for reclosing the breaker at the far end, but it ensures that thebreakers at both ends are tripped before either is reclosed.

If the signalling link (acceleration) is out of service, successful auto-reclose willstill take place for faults within the middle 70% of the line. Faults within 15%of either end will be cleared from one end in delayed zone 2 time and no reclose(since reclose is initiated from zone 1 tripping only). The other end will trip inzone 1 with auto reclose but this will be unsuccessful since the remote CB hasnot yet tripped.

Early model signalling schemes had circuitry which automatically switched outauto reclose should the acceleration fail. Later schemes do not have this facility.

3.3.3 Pilot Wire Protection

The protection described for generators and transformers is satisfactory wherethe distance between the two sets of CT’s is relatively short, but if such a sys-tem were applied to feeders several kilometres long, the CT secondary e.m.f.s.would have to be high enough to circulate 5A at full load (and several timesthis under fault conditions) through pilot circuits of high impedance. This isimpracticable and the provision of long pilot wires of low impedance is also un-economic. The permissible voltage developed across pilots must also be limitedto practical values.

A method that minimises both the number of pilot cores and the magnitudeof the current circulating in the pilot wires uses a summation transformer toderive a single phase relay current as shown in Figure 22. Each line CT energisesa different number of turns on the summation transformer primary and so thereis an output current even when the system is healthy and balanced.Pilot wire protection is very suitable for short lines, provided that satisfactorypilot wires can be provided. However if the pilot becomes faulty the protectionwill either trip or not operate, depending on whether the pilot fault is a shortcircuit or an open circuit and on the type of pilot wire protection used (as wellas on the load in the transmission line).

It is of course essential that the pilot wires can withstand the voltages whichdevelop, including fault conditions. Pilot wire supervision is generally fitted tocheck the soundness of pilots under normal conditions but it may not indicateflashover of pilots under system faults.

Taking pilot wire protection out of service has to be done in such a sequencethat neither of the two relays at the two ends of the line may operate. Generallyit necessitates:

33

Page 39: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

mY

B

R

SummationTransformer

Output

Figure 22: Summation Transformer

• Removal of trips from relay at end A, and at end B.

• Removal of current from relay at end A, and at end B.

• If applicable, open pilots at ends A and B, and short pilot wires to earth.

Since protection is lost if pilot wires become faulty, to increase reliability twopairs of pilot wires can be provided for each transmission line, over separateroutes so that they are unlikely to fail together.Advantages

• A unit scheme with fast operation.

• Cheap if pilots are available at low cost.

• About the only type of available fast protection for short lines.

Disadvantages

• Needs other protection to cover adjacent busbars, and other blind spots(i.e. unprotected parts of the system).

• If pilots are faulty, protection is lost. Duplication of pilots is a costlyexercise.

• High vulnerability of pilots to failure and high cost of maintenance.

34

Page 40: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

mIn the experience of electricity distribution in New Zealand, overhead pilots aresubject to short circuits from wind, pole interference by vehicles, animals, de-bris, kites, rifle fire and lightning.

Buried pilots are subject to interference from bulldozers and other digging op-erations, particularly in city areas. Also rise in earth voltages during faults cancause insulation breakdown. Altogether the cost of maintenance of pilot wireshas been a great deterrent to using this form of protection.Remember

• Pilot wire protection is a modified form of differential protection.

• If the pilot wires are defective, so is the protection.

• Protection will trip for short or open circuited pilots, depending on typeof protection.

• Pilot wire protection is excellent for short lines, if the reliability of thepilots is good.

• If the protection has to be taken out of service with the transmission linein service, the correct sequence for operating test switches requires anoperator at each substation.

3.3.4 220kV Oil-filled Cable Protection

Where the cables are to be buried an alternative to pilot wire protection couldbe using oil filled cables. The oil in the cables is for insulation purposes and isunder pressure.

Should the pressure increase, an alarm will be triggered and is an indicationof excessive heat being generated in the cable. A source of this heat could beoverloading of the cables.

A low pressure alarm and low pressure trip are also provided to indicate anydamage to the cable (possibly from an external source) and hence remove thecircuit from service.

Additionally a buchholz relay can be fitted at the end of the cable to indicate afault within the circuit.Remember

• By protection signalling, relay contacts can be actuated at a remote stationby communications link.

• Distance protection line end clearing times (zone 2 times) can be shortenedconsiderably by inter signalling.

• The main scheme used in New Zealand is the ”acceleration” method.

• Either radio or power line carrier is used to link stations at each end of aline.

35

Page 41: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

m• Directional comparison earth fault protection detects internal line faults

to earth by comparing the direction of current flow.

• The condition of tripping from direction comparison earth fault protectionDCEF) is that each relay at the line ends receives and transmits a ”linefaulted” (trip) signal.

• Directional comparison earth fault protection is more sensitive, generally,than distance protection.

• Directional comparison earth fault protection is combined with distanceprotection.

3.4 Generator Protection

Generators are an important component of the power system. They are expen-sive both in terms of initial investment and down time. If they suffer damagethey cannot he quickly repaired. It is therefore economic to provide them witha protection system which reduces the possibility of damage from any internalfault or other cause.

Insulation breakdown may be caused by electrical stress, mechanical damage,thermal or chemical degradation or a combination of these. Insulation failurein a generator is most likely to cause damage, as the windings are in close prox-imity to the magnetic core. If a fault occurs, heavy currents may circulate. Thecore plates may be burned and the insulating varnish between laminations maybe damaged by fault currents. This would require the core to be dismantled,which is a costly process. High speed tripping is essential to minimise damage.

Breakdown of stator insulation may cause earth faults, phase to phase faults orthree phase faults. Phase to phase faults and three phase faults may or maynot involve earth. However, experience has shown that phase to phase faultswhich do not initially involve earth, very rapidly do so. Three phase faults areamongst the rarest type of fault on a generator. Protection for phase to phasefaults also provides protection for three phase faults.

All generators are provided with two stator protection schemes. These arestator differential protection and stator earth fault protection. The more recentinstallations also include stator inter-turn protection.

3.4.1 Generator Earth Faults

Probably the most likely fault in a generator is a phase to earth breakdown.The stator windings are solidly connected to earth free delta connected wind-ings on the output (and if present, the unit transformer) transformer. They arestar connected at the generator neutral point and the star point is connected toearth sometimes directly but most often through a current limiting component.The current limiting component provides a moderate restraint against the flowof massive earth fault currents. This has the effect of minimising damage tothe generator winding resulting from an earth fault. This is important since asevere earth fault inside a generator can cause extensive damage to windings

36

Page 42: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

mand insulation and possibly cause an internal fire and also It can weld togethersections of iron laminations which could necessitate stator rebuilding.

A generator connected directly to a step up transformer and operating on theunit system will be considered. This form of connection is commonly found inthermal generating stations. The generator neutral point is earthed through avoltage transformer which is arranged to initiate an alarm or to immediatelytrip the unit when the voltage between the neutral point and earth exceeds apre determined value. Such a system is illustrated in Figure 23.

 

Generator Transformer Station Busbars

Earth Fault Protection Zone

To Alarm trip circuit

Unit Auxiliary Board

Figure 23: Generator stator earth fault protection

Also shown by a dotted line in Figure 23 is the earth fault protection zone; theearth fault protection responds to an earth fault in equipment only within thisarea. It is seen that in addition to the generator stator windings, the primarywindings of the generator and unit auxiliary transformers and interconnectingcables also are supervised by the stator earth fault protection scheme.

For an earth fault outside the protection zone, while the generator phase cur-rents will become unbalanced, no current will flow in the generator neutralvoltage transformer connection because of the delta connection of the primarywindings on the generator and unit auxiliary transformers, and so the earthfault protection remains inoperative.

It has been pointed out that the earth fault current is limited by the impedanceof the voltage transformer in the generator neutral. The magnitude of the faultcurrent depends also on the location of the fault with respect to the neutralpoint.

37

Page 43: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

m3.4.2 Stator Differential Protection

This protection, sometimes called circulating current protection, is designedprincipally to protect the generator against internal phase to phase faults. De-pending on the method of neutral earthing, a measure of protection againstphase to earth faults may be provided, but in most cases, a separate statorearth fault protection scheme is necessary. Because of the high current andpossible damage following a phase to phase fault, the differential protection isdesigned to clear the fault practically instantaneously.

Generator differential protection is a scheme whereby the current at the neutralend and the current at the terminal end in each of the three phase windings iscompared. The circuit is arranged so that any inequality between these currentsdue to a fault will cause a spill current to flow through the differential relay,causing it to operate.

In order to measure the current entering and leaving each of the three phasewindings, each winding has a CT connected at the neutral end and another atthe terminal end. The secondary windings of these CT’s are interconnected insuch a way that a current normally circulates in the secondary circuit. Hencethe term circulating current protection. Figure 24 shows the usual position ofthe differential protection CT’s.

Protection Zone

Stator

Windings

Neutral Point

StatorOutput

Figure 24: Location of differential protection CT’s

A feature of the differential protection is that it will respond only to faultswithin the protection zone and will remain unresponsive to through faults; thatis, faults external to the protection zone. The protection zone is that area be-tween the two sets of CT’s as shown in Figure 24

Figure 25 shows the basic connections for a differential protection scheme on asingle phase basis. It can be seen that any fault which results in an inequalitybetween the current entering and leaving the winding will cause the differentialrelay to operate. Under through fault conditions, the increase in current affectsboth CT’s equally and although there is an increase in the current circulating

38

Page 44: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

min the secondary circuit, the currents remain balanced and the relay does notoperate.

I

Single Phase Stator Winding

Neutral Point

Current circulating in

C.T secondary

circult

Differential Relay(Zero Spill Current under

healthy conditions)

Neutral Point

Figure 25: Basic generator differential scheme

Both phase to phase and phase to earth faults cause an inequality between thecurrents entering and leaving the stator windings and hence a resultant spillcurrent flows through the differential relay. When the neutral point is earthedthrough a high impedance device such as a voltage transformer however, theearth fault current is so low that the resultant spill current in most cases isbelow that necessary to operate the differential relay. In these cases, therefore,differential protection provides principally for phase to phase faults only.

Two other faults, an open circuit and an inter-turn fault in one of the phasewindings, also will not be detected by the normal differential protection scheme.In the former case, no current flows in the phase winding and in the latter case,the fault current flows only in the local circuit between the turns involved, andhence the CT’s at either end of the phase windings will not detect a conditionof unbalance. In both cases, however, a fault to earth will usually develop andprotection will be provided by the normal stator earth fault protection.

3.4.3 Generator Stator Over-Currents

It is not usual to provide protection on an A.C generator for external three phaseshort circuits. This is because the overcurrent relay required for this protectionnormally would not operate in time before the short circuit current fell belowthe relay setting.

When considering the protective gear for generators, one must have a broadknowledge of the characteristics of rotating machines.

Immediately a short circuit occurs on the generator, the short circuit currentrises to between 5 and 10 times full load. The initial stator current rises to a

39

Page 45: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

mvalue which is limited only by the sub transient leakage reactance of the ma-chine which, for all intents and purposes, is equal to the leakage reactance. Theleakage reactance is due to the flux set up by the stator magnetomotive forcewhich fails to cross the air gap. The increase in stator current which is predom-inantly of a lagging characteristic causes a demagnetising effect by opposing theair gap flux, but it is an appreciable time before a major change in the air gapflux can he completed. The net effect is a gradual decrease in the short circuitcurrent over a period of seconds to a value which can be well below full load ofthe machine.

Modern A.C generators are able to withstand the effects of an external shortcircuit for a short period, provided the three phase currents are balanced.

Sustained three phase faults external to the machine are not dangerous. Themost likely sequel is loss of synchronism and instability, after the fault hascleared. No special protective system is installed to guard against this con-dition. It is the duty of the automatic regulator to deal with the generatorstability.

One of the most dangerous conditions for a generator is sustained unbalancedcurrent. This causes a very rapid rise of temperature in the rotor due to in-creased currents which may result in mechanical weakening or even failure.

Generators are protected for overcurrent faults. Current transformers energiseinduction pattern relays which give an inverse time feature. This overcurrentprotection is essentially a back up protection to the previously mentioned differ-ential and earth fault protection as the settings are high in order not to operateunder emergency load conditions and to grade and provide discrimination withthe other protection systems.

3.4.4 Negative Phase Sequence Protection

This is provided where generators are not able to supply currents which areunbalanced in the three phases without producing rotor overheating.

Negative phase sequence currents in the generator stator are caused by un-balanced loading. This unbalanced loading is usually caused by an open circuitof one phase at some point in the system external to the generator (internalfaults are cleared by the differential protection), and could persist for sufficienttime to cause dangerous overheating of the generator rotor.

The negative phase sequence component of unbalanced stator currents producesa backward rotating magnetic field which will induce currents at the rotor sur-face of twice normal frequency. If this condition persists, damage may be causedby overheating of the rotor body, slot wedges and rotor end winding retainingrings. The Huntly machines may continue to operate with a maximum negativephase sequence component of current of only 15% of full load current, a reflec-tion of the high electrical loading of the machines.

With the increase in size of units the time factor for allowing the negative

40

Page 46: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

mphase sequence current to flow in the generator has diminished.

Before we discuss protecting plant against negative phase sequence currentswe shall specify what we mean by this term, and how the phenomena affectscertain items of plant.

Let us assume phasors, 120◦ (electrical) apart rotated in a counter clockwisedirection, (according to convention) so the sequence in which the phasors wouldpass a fixed spot ‘F’ would be R, Y and B as in Figure 26 using colour conven-tion.

 

R

B Y

F

Figure 26: Positive phase sequence

Now if the rotation was reversed so that the phasors rotated in a clockwisedirection, passing F in the sequence, R, B and Y as in Figure 27, we wouldhave a negative phase sequence system. If we had the three phase cables con-nected to terminals, you can see that a complete phase reversal from positivephase sequence (PPS) to negative phase sequence (NPS) is produced, merely bychanging the Y and B connections in the example shown. (Changing any twophase connections would produce the same result.)In addition to positive and negative phase sequences, a three phase power systemcan produce another phenomenon known as zero phase sequence (ZPS). This canbe displayed vectoriaIly as three phasors rotating together as shown in Figure28.Now, different system faults can cause various combinations of positive, nega-tive and/or zero phase sequences to occur in varying amounts. For example, aphase to phase fault will create a mixture of PPS and NPS. A phase to earthfault may cause a combination of PPS, NPS and ZPS. An open circuit phaseconnection (such as one phase of a breaker failing to close) may also cause PPS+ NPS + ZPS.

When ”seen” from an individual generator, the amounts of PPS, NPS and ZPSwill depend upon the load being supplied, the severity of the fault, and amountof generation on the system and the distance the fault is from the machine (inother words the impedance to the machine.

41

Page 47: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

m

 

R

B Y

F

Figure 27: Negative sequence rotation

 

RoYo

Bo

Figure 28: Zero phase sequence

42

Page 48: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

mIt is the negative sequence component that has a damaging effect on a turbo-alternator by producing excessive heat in the rotor. This is explained by refer-ence to Figure 29 (a) and (b).

Rotor

S

N

N

Stator PPS Field

Rotor

Stator

Rotor

S

N

N

Stator NPS Field

Rotor

Stator

Stator PPS Field

Figure 29: Effects of PPS and NPS on turbo-alternator (top - Positive phasesequence; bottom - Negative phase sequence)

Figure 29(a) shows a rotor moving in a counter clockwise direction, locked tothe field produced in the stator by the system to which the machine is synchro-nised. The North Pole of the rotor is locked to the South Pole of the rotatingfield produced by the stator with current drawn from the power system. Underthese conditions there is no relative movement between rotor and stator

Now, let us see what happens when a negative sequence component is intro-duced from the power system into the stator winding of the machine. Thepositive sequence still produces a stator field in the counter clockwise sense.The steam turbine still drives the rotor in a counter clockwise sense and at thesame speed as the PPS field. The Negative sequence is producing a rotatingfield in the opposite direction to the PPS field and the rotor. The relative speedof NPS field and rotor is twice rotor speed so that currents are induced in therotor at twice system frequency (100 Hz on New Zealand system). Because the

43

Page 49: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

mrotor is designed to operate under static flux conditions, and to give a high me-chanical strength, it is made from a solid steel forging. This solid forging givesmany paths for the induced currents (at 100Hz) induced by the NPS component.The end result is rapid heating of the rotor, destruction of the rotor insulationand perhaps bending of the rotor itself. The latter could result in catastrophicdisintegration of the machine since the rotor may weigh many tonnes and isrotating at 3000 rpm.

Therefore, the modern turbo alternator must be protected from the effects ofnegative phase sequence.

3.4.5 Reverse Power Protection

When the prime mover power falls below the level needed to keep a generatorspinning at synchronous speed, power flows in the reverse direction and themachine becomes a motor. Although this action is wasteful it does not damagethe generator but if the prime mover is a steam turbine, running it with airin its low pressure stages will cause severe overheating and damage might becaused to the turbine blades. However with the protection systems installed onThermal Units the circumstances in which motoring can take place will be mostinfrequent in the life of the Unit. This is because for any speculated type offault the HVCB will be tripped before motoring can take place. The protectivedevices which operate should trip the HVCB when the forward power is about0.5% of the MW power rating.

Steam driven units have a reverse power relay which either gives an alarm,or after a relay operation shuts down the unit.

Damage arises if the protection system fails due to some mal-operation in whichcase operator action will be necessary. However, it must be remembered that itis normal for more than one sensitive relay to be fitted to reduce this risk.

Hydro machines with tail water depression have a reverse power relay to preventmotoring with a turbine scroll case full of water.

44

Page 50: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

m4 Non-Unit protection

Non unit Protection will respond to a fault over a wide area of the system. Ingeneral the area will not be precisely defined and will be influenced by factorssuch as system fault level, system configuration etc. Operation of non unit pro-tection will provide only a rough indication of the fault location.

Typical examples are overcurrent protection, unrestricted earth fault protection.

Where both unit and non Unit protection have operated the unit protectionflags will provide a more positive indication of fault location than those of thenon unit protection.

If a transformer tripped and the flaggings were on the differential relay, thenthe fault must be between the CTs (unit protection). This unit will includethe transformer and usually connecting cables or buswork. A Buchholz trip-ping would indicate a fault within the transformer. If however, the transformertripped on overcurrent (non unit protection) the fault would he outside thetransformer. The overcurrent would indicate the transformer was overloaded,perhaps due to a fault on the system or to excess system loading. The flagginggiven do not identify the location of, or reason for the overload.

4.1 Overcurrent Relays

Current magnitude is widely used as a means of detecting faults on low voltagedistribution systems, but not so widely on extra high voltage (E.H.V) transmis-sion circuits. In general faster fault clearance is necessary on E.H.V. systems,faster and more expensive protection schemes are justified.

The need for ”selectivity” with overcurrent protection is clear in the simplestsystems. Consider the situation where one incoming feeder set to trip at 400Agives supply to two outgoing feeders each set to trip at 200A, i.e.If a fault occurs on feeder C the resultant current will flow through the twocircuit breakers A and C in series. Unless the time delay on A exceeds that onC by a safe margin both circuit breakers will open. This is not necessary toclear the fault. A should remain closed to maintain supply to feeder B.

A variety of time characteristics are used with overcurrent relays. Inverse timecurrent relays offer better selectivity and permit lower time settings where thelevel of generation is reasonably constant and the fault current is controlledby the fault location. Very inverse time characteristics are used where sharperselectivity is required, for matching the time characteristics of fuses, or for theprotection of power rectifiers.

Instantaneous overcurrent relays are sometimes added to inverse time currentrelays to reduce the tripping time under maximum short circuit conditions.

Overcurrent relays protect against faults between 2 or all 3 phases. These relaysdo not necessarily give satisfactory protection for phase to earth faults as thecurrent magnitude may be restricted by the earth impedance.

45

Page 51: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

m12

B

C

200 A

200 A

400 A

Figure 30:

4.2 Earth Fault Relays

Most faults within equipment are due to an insulation failure on one phase al-lowing current to flow to earth, a condition which may lead rapidly to a faultbetween phases and possibly to danger to personnel. Earth fault protection istherefore required to detect a fault to earth and disconnect it from the systemin the shortest possible time.

One principle of operation of earth fault protection is based on the fact thatin a balanced circuit currents in the three phases sum up (vectorially) to zero.When a fault between one phase and earth occurs this balance is upset and theout of balance (or residual) current is fed to the relay.

Earth fault relays are essentially overcurrent relays which, by virtue of the relayCT connections, are sensitive only to earth faults. Current settings are muchlower than for overcurrent relays since normally no current flows in the relay.

Earth fault relays are used in unit protection schemes where they will oper-ate only for faults within a clearly identified part of the system.

Earth fault relays are also used for non unit protection. For example: feederprotection, LV bus bar and feeder back up protection, HV bus bar and lineback up protection, and Inverse time relays on interconnecting and generatortransformers.

4.3 Earth Fault Protection of Transformers

A typical combination of overcurrent and earth fault relays on the HV primary(delta) side of a transformer shown in Figure 31.

46

Page 52: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

mThe earth fault relay is instantaneous in operating and very low earth faultsettings can usually be obtained. For unearthed windings delta or star the pro-tection would consist of a single pole instantaneous earth fault relay with orwithout a series resistor depending on the type of relay. This is the “plain earthfault” system of protection and is shown in Figure 31.

Stabilizing resistor

Earth fault RelayOver Currentrelay

Trip Coil

Figure 31: Earth fault protection on the Delta side of a transformer

4.4 Earth Fault Protection on Circuits

Most 11kV and 33kV feeders have an earth fault relay operating on the principleof residual current in the three phases.The connection of the earth fault relay is similar to that of the star transformerin Figure 31. In the case of the circuit a CT is not used in the neutral or earth ofthe transformer. Without this CT the earth relay will only detect an earth faultfrom the CT’s outwards (i.e. away from the transformer). At a substation eachfeeder would have protection similar to that in Figure 32. As each responds toearth faults past the CTs each feeder is easily separately protected.

47

Page 53: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

mC.T.s

Over current Relay coilsR.Y & B Phases Earth Fault

Relay Coil

Figure 32: Overcurrent and Earth Leakage Relays Connections

4.5 Earth Fault on Interconnecting and Generator Trans-formers

The relay used on these is simply an inverse time over current relay connectedto a CT in the neutral of the transformer. As earth return is not used on ourprimary transmission then usually very little current flows through the neutral.

FCT

Figure 33:

Remember

• Protection may be unit or non unit.

• Protection must he selective to disconnect only the faulted equipment.

• Earth fault relays may have time delay built in.

• Some non unit protection gives no indication as to location of fault.

48

Page 54: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

m4.6 Time Graded (Non-Unit) Protection

Time grading is commonly used in protection to selectively trip circuit breakerswhen a fault occurs on the system. A simple case is that of instantaneousovercurrent definite time protection applied to line breakers fed in series (seeFigure 34).

1.5 sec 1.0 sec 1.5 sec F

A B C D

Figure 34:

A

B

C

1.5

1.0

0.5

0

Relay A Operated

Fault Current at “F”

Primary Current

OperatingTime

(Sec’s)

Instantaneous Relays with Definite Time

Figure 35: Instantaneous relays with Definite Time

Time Graded Protection Figure 34 shows transmission line AD, fed fromend A, supplying power to substations B, C and D in series. Circuit breakers atA, B and C are fitted with instantaneous overcurrent relays, tripping in definitetimes of 1.5, 1.0 and 0.5 seconds. The overcurrent settings are high enough tocarry load currents, but operate for fault currents. The tripping characteristicsare shown in Figure 35.

When a line fault occurs at F on section CD, relays at A, B and C all carrythe same fault current and pick up. But the time setting of C of 0.5 secondsis less than B by an adequate margin, and the smallest section of line, CD is

49

Page 55: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

mA

B

C

Relay A Operated

Fault Current at “F”

Primary Current

OperatingTime

(Sec’s)

Inverse Time Relays

Figure 36: Inverse Time relays

disconnected. It can be seen that discrimination is thus obtained, and that itapplies for all values of primary currents which could occur.

Similarly a fault on line section BC results in breaker B opening but breaker Aremains closed.

Figure 36 represents inverse time (IDMT) relays, at A, B and C, with B op-erating 0.5 seconds later than C for any fault current up to maximum value.Similarly relay A discriminates with B.

Thus time grading is applied to inverse time relays as well as instantaneousdefinite time relays.

Discrimination for Earth Faults Discrimination for earth faults is providedby time settings on the earth fault relays. Suppose in our example of Figure 34,the earth fault relay at C is given a clearing time for earth faults of 2 seconds.Earth fault relay B is then set to clear earth faults in 2.5 seconds, and A is setto clear earth faults in 3 seconds.

The clearing times for earth faults can be, and generally are, quite differentfrom phase faults clearing times - if C discriminates with B for earth faults, andC also discriminates with B for phase faults, C discriminates for all types offaults.Remember

• Time graded protection is a form of non unit protection.

• If it operates the fault may be anywhere on the system from the protectionCT towards the load, limited only by relay sensitivity.

50

Page 56: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

m• Time discrimination is commonly used to trip faults from the system se-

lectively.

• Earth fault protection time settings may be completely distinct from phasefault protection (overcurrent) time settings (as well as having differentsensitivities).

4.7 Directional Relays

A directional characteristic (obtained by providing VT’s) is required in manylocations to provide selectivity and to prevent healthy plant backfeeding thefault.

 

Voltage circuit

Current Circuit

Disk (Rotating)

Figure 37: Directional relay

Figure 37 shows the directional component of a directional overcurrent relay.When the current flow is in the required direction the rotation of the disk de-tected and contacts are closed and the inverse time relay is in service. When thecurrent flow is in the reverse direction the disk rotates in the reverse directionand the contacts are open and the inverse time relay will not operate.

Direction overcurrent relays improve protection on feeders in parallel.

It can be seen from the diagrams below that if non directional relays are appliedto parallel feeders any faults occurring on the line will inevitably, irrespectiveof the relay settings chosen, isolate both lines and completely disrupt supply.To ensure selective operation (i.e. remove only the faulted feeder) it is usualto connect relays R3 and R4 such that they only operate for faults occurringin the line in the direction indicated. They should also operate before the nondirectional relays R1 and R2.Remember

• Overcurrent relay can be fitted with a directional element, so they onlyoperate when the current flow is in one direction.

• Direction protection improves selecting on parallel feeders.

51

Page 57: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

m

Figure 38: Non-Directional relays applied to parallel feeders

 

R1 (1SEC) R3 (0.5SEC)

R2 (1SEC) R4 (0.5Sec)

Figure 39: Directional relays applied to parallel feeders

52

Page 58: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

m5 Backup Protection

Even protection with very high reliability can fail to operate, and other inde-pendent protection is called upon to act. The main protection is called ’primaryprotection’, and the reserve protection is called ’back up protection’.

Back up protection generally takes the form of another protection nearer thesource than the primary protection. Thus for an 11 kV feeder fitted with over-current and earth fault protection, the over current and earth fault protectionon the transformer bank acts as back up protection.

Back up protection is generally less sensitive, slower to operate, and does notprovide the selectivity of primary protection. That the back up protection is in-ferior is generally not given sufficient emphasis. Removal of primary protectionalways involves a calculated risk.

Take the case of feeder protection. The back up overcurrent protection, pri-marily for transformer overcurrent protection with high CT ratios, may onlyrespond for faults on the first 3 or 4 kilometres, and the earth fault protectionmay not be able to operate unless contact is made with a well earthed conductor.

Distance protection measures a longer distance if it receives only a part of theline fault current, i.e. if there is other fault currents fed into the line.

B

A

110 IA

IAF

IF

IA910

Backuprelay

Protected Line

Figure 40: Illustration of gross errors in distance measurement with feed inbetween relay and fault

For example Figure 40 shows a back up relay which receives only 1/10 of thefault current and therefore sees a distance 10 times as great (= 10 AF + AB inthe diagram).

The starting relays at B will probably not respond. The trend in back upprotection is to provide duplicate primary protection, with duplicate trip coilson circuit breakers, and duplicate tripping batteries.Remember

• Back up protection is unlikely to be as sensitive or selective as primaryprotection.

53

Page 59: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

m• Permission is required from the equipment owner before protection is taken

out of service.

• Removal of VT supplies on which protection depends for operation willalso require permission.

• Consider taking the main equipment out of service instead of removingthe protection.

54

Page 60: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

m6 Measuring Voltage and Current

6.1 Voltage Transformers

The voltage transformer (VT) is used to step down a given primary voltage, ac-curately to a definite secondary voltage. The usual secondary voltage is 110V.On 3 phase VT’s the secondaries are usually 63.5V each, star connected to givea line voltage of 110V. The secondary winding is isolated from the primarywinding. The VT works on a similar principle to power transformers but VT’sare never used to supply any power load as the current in the transformer wouldcause ‘copper losses’ and the secondary voltage would he inaccurate. The VTis only used to supply relays, meters, potential lamps, master clocks etc.

Oil filled double wound VT’s are used for line voltages up to 110kV. On 220kVlines and other 110kV equipment CVT’s are used.

Two types of capacitor voltage transformer or CVT are in use. Older CVT’suse a stack of 10 capacitors of equal value connected in series between phaseand earth to act as a voltage divider. A VT is connected across the capacitor atthe earth end of the stack. The primary voltage of the VT is therefore equal to10% of the phase voltage. That is on a 220kV circuit 12700. The voltage ratioof the VT is then 12700 to 63.5V.

Modern CVT’s are built with the capacitors enclosed in a bushing with theVT mounted at the base.

On all CVT’s a connecting network is used on the primary of the VT. Thishas calibration adjustments to allow for errors in ratio (due to the tolerance ofcapacitor values) and phase displacement (due to the phase displacement in thecapacitors).

6.2 Current Transformers

The current transformer (CT) is designed so that the secondary circuit producesan accurate percentage of the current in the primary circuit. The secondary cir-cuit is also isolated from the primary circuit. The secondary circuit is earthedat one point. For line CTs this is usually in the outdoor junction box at thestar point of the CT connection.

There are two main types of CTs used for two different uses: measuring CT’sused with instruments and meters, and protective CTs used with protectiverelays. Measuring CTS are designed to maintain their specified ratio of trans-formation up to 150

Protective CTs are designed to maintain their specified ratio to at least 600%,sometimes 2000% or even 3000% of rated current. These CTs must be accurateunder heavy current fault conditions to operate the relays.

One CT is therefore not suitable for both metering and protection circuits.Line CTs used on extra high voltage circuits contain several individual CTs

55

Page 61: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

mwithin the one enclosure, 5 being typical 2 for metering and 3 for protection.CTs not in use are short circuited and earthed. Some circuit breakers have CTsin their bushings. Typical CT secondary currents are 1 or 5 amps. If a linecarries a full load of 1000A, the CT ratio will be 1000:1 or 1000:5, dependingon the current required by the metering and protection in use.

NOTE. A CT must not be energised with its secondary open circuited. Withno secondary demagnetising magneto motive force produced, the core usuallysaturates and produces a very high voltage, often several thousand volts in thesecondary winding. This can damage insulation and endanger life.Remember

• Faults and abnormal conditions must be removed as quickly as possible.This requires the automatic operation of protective devices.

• CTs are designed for one of two uses.

• CTs secondaries must be earthed at one point for safety.

• A ”Current Transformer” or a CB bushing may contain several separateCT’s.

• VT’s may be a double wound oil filled transformer if the high voltage is110kV or less. At 110kV and above capacitor voltage transformers areused.

56

Page 62: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

mA Pre 1985 relay codes

Electrical protection relays are designated by a Standard Code which indicatesthe type and duty of the relay. Each relay is prefixed by the number of the circuitbreaker which it trips. In the case of the generator protection at Huntly, thereare 3 220kV C.B.’s which are tripped and the number of the Bus ’B’ Selectorbreaker is used as the prefix. A letter follows this number to indicate the relayfunction in the protection scheme. The letters applicable to the protectionschemes at Huntly are as follows:

A Instantaneous Overcurrent

B Instantaneous Earth Fault

C Definite Time

D Tripping

E Inverse-Time Overcurrent

F Inverse-Time Earth Fault

H Distance

I Negative Phase Sequence

J Differential

M Temperature (including motor thermal overload)

N Change-Over (auto reclose)

P Directional Earth Fault

Q Differential Earth Fault

R Buchholz or Oil Pressure

S Under voltage

U Uni-directional protection signalling system

X Special Functions (low forward power, boiler trip, turbine trip, etc)

In addition, where more than one relay of the same class is associated with thesame circuit breaker, a number suffix is applied. Also the individual phasesfrom which the relay is supplied may be indicated by R, Y or B following thenumber suffix.

Example:-

262 E1 (R) - indicates an inverse-time overcurrent relay, fed from Red phaseand associated with C.B. 262, ie Generator 1 circuit. This relay is in fact the220kV Generator Transformer 1 inverse time overcurrent relay.

262 E2 (R) - indicates a similar class relay and is the unit transformer highvoltage inverse time overcurrent relay.

57

Page 63: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

mB Post 1985 relay codes

Since the mid 80’s most plant commissioned in New Zealand has followed theAmerican National Standards Institute ANSI/IEEE C37.2 code for numberingof electrical protection relays. Each relay is designated by its device functionnumber, with appropriate suffix letter or letter where necessary which denotethe main device to which the relay is applied or related.

Some of the standard device numbers applicable to the Huntly Unit 5 site areas follows:

14 underspeed device is a device that functions when the speed of a machinefalls below a predetermined value

21 distance relay is a relay that functions when the circuit admittance, impedance,or reactance increases or decreases beyond a predetermined value

25 synchronizing or synchronism-check device is a device that operates whentwo A.C circuits are within the desired limits of frequency, phase angle,and voltage, to permit or to cause the paralleling of these two circuits

27 undervoltage relay is a relay which operates when its input voltage is lessthan a predetermined value

28 flame detector is a device that monitors the presence of the pilot or mainflame in such apparatus as a gas turbine or a steam boiler

32 directional power relay is a relay which operates on a predetermined valueof power flow in a given direction, or upon reverse power such as thatresulting from the motoring of a generator upon loss of its prime mover

41 field circuit breaker is a device that functions to apply or remove the fieldexcitation of a machine

46 reverse-phase or phase-balance current relay is a relay that functions whenthe polyphase currents are of reverse-phase sequence, or when the polyphasecurrents are unbalanced or contain negative phase-sequence componentsabove a given amount

47 phase-sequence voltage relay is a relay that functions upon a predeterminedvalue of polyphase voltage in the desired phase sequence

50 instantaneous overcurrent or rate-of-rise relay is a relay that functions in-stantaneously on an excessive value of current or on an excessive rate ofcurrent rise

52 A.C circuit breaker is a device that is used to close and interrupt an A.Cpower circuit under normal conditions or to interrupt this circuit underfault or emergency conditions

59 overvoltage relay is a relay which operates when its input voltage is morethan a predetermined value

58

Page 64: Power Station Electrical Protection - storage.googleapis.comstorage.googleapis.com/wzukusers/user-12873790/documents... · Power Station Electrical Protection} M M M L L L M L E A

richa

rdsmith

@as

ia.co

m81 frequency relay is a relay that responds to the frequency of an electrical

quantity, operating when the frequency or rate of change of frequencyexceeds or is less than a predetermined value

86 lockout relay is a hand or electrically reset auxiliary relay that is operatedupon the occurrence of abnormal conditions to maintain associated equip-ment or devices inoperative until it is reset

87 differential protective relay is a protective relay that functions on a percent-age or phase angle or other quantitative difference of two currents, or ofsome other electrical quantities

Some of the standard suffix letters that can be applied to device numbers areas follows:

A Alarm or Auxiliary power

B Battery

D Discharge or DC direct current

E Exciter

F Feeder

G Generator

M Motor or Metering

N Neutral

R Reactor or rectifier

S Synchronising

T Transformer

Examples:-

41E Field circuit breaker

87G Generator differential relay

87T Transformer differential relay

46 Negative phase sequence

59