Asset: P.S. 39 - BROOKLYN, 417 6TH AVENUE, New York, 11215 Inspection Id Inspection Type Time In Last Edited SA : K039 Architectural - Senior 2018-11-26 10:32 AM 2018-12-13 6:58 PM AA : K039 Architectural - Associate 2018-11-26 11:00 AM 2018-12-11 11:34 AM Asset Data Question Answer Was the building fully accessible for inspection Yes Principal(s) Information Principal Name Anita De Paz Organization P.S. 39 - Brooklyn Did you meet with this Principal? Yes Did this Principal provide feedback? Yes Summary of Principal's Feedback The Principal's comments are as follows: 1. There are many windows with defective balances. 2. The exterior doors at Exits 5 and 6 are deteriorated. 3. The pneumatic valves and steam traps are defective. Custodian Was not present Fireman Eddie Jordan Building Square Footage 26,000 Comments on the Area None Comments on the Stories (Floors) plus Basements 3+B+Attic Comments on the Number of Classrooms 20 Comments on the Year Built 1877 Student Population 413 Staff Population 56 Weather Fair Facade Photo Corner of 6th Avenue and 8th Street - Northeast View NYC Department of Education Architectural Inspection Building Condition Assessment Survey 2018 - 2019 K039 PB/A&W Print Date: 6/21/2019 Page 1 of 26

Upload: others

Post on 10-Jul-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: NYC Department of Education - NYCSCA102, 104 and 106, water leaks fixed, Basement Boys and Girls Toilet Room upgrades Year: 2016 Systems: Wood Flooring replacement, thirteen Interior

Asset: P.S. 39 - BROOKLYN, 417 6TH AVENUE, New York, 11215

Inspection Id Inspection Type Time In Last Edited

SA : K039 Architectural - Senior 2018-11-26 10:32 AM 2018-12-13 6:58 PM

AA : K039 Architectural - Associate 2018-11-26 11:00 AM 2018-12-11 11:34 AM

Asset Data

Question Answer

Was the building fully accessible for inspection Yes

Principal(s) Information

Principal Name Anita De Paz

Organization P.S. 39 - Brooklyn

Did you meet with this Principal? Yes

Did this Principal provide feedback? Yes

Summary of Principal's Feedback The Principal's comments are as follows: 1. There are many windowswith defective balances. 2. The exterior doors at Exits 5 and 6 aredeteriorated. 3. The pneumatic valves and steam traps are defective.

Custodian Was not present

Fireman Eddie Jordan

Building Square Footage 26,000

Comments on the Area None

Comments on the Stories (Floors) plus Basements 3+B+Attic

Comments on the Number of Classrooms 20

Comments on the Year Built 1877

Student Population 413

Staff Population 56

Weather Fair

Facade Photo

Corner of 6th Avenue and 8th Street -Northeast View

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K039

PB/A&W Print Date: 6/21/2019Page 1 of 26

Page 2: NYC Department of Education - NYCSCA102, 104 and 106, water leaks fixed, Basement Boys and Girls Toilet Room upgrades Year: 2016 Systems: Wood Flooring replacement, thirteen Interior

Main Entrance Photo

Facade A - 6th Avenue

NilRoof Photo

Have any Systems/Major Building Components been upgraded? Yes

Systems: Eight new Doors, Floors and Ceilings repaired in Rooms102, 104 and 106, water leaks fixed, Basement Boys andGirls Toilet Room upgrades

Year: 2016

Systems: Wood Flooring replacement, thirteen Interior Doorsreplacement

Year: 2015

Systems: Exterior Modernization Program including DrainageSystem upgrade, Flood Elimination project, Roofingreplacement including Flashing, Leaders, Gutters, Copingand Cornice replacement, Main Entrance Stair repair, NewUnisex HC compliant Student Toilet Rooms on the 1stFloor, Side Stair, Exterior Walls Thoro Sealed, ExteriorConcrete Pavement replaced

Year: 2013-15

Systems: Partial Foundation Walls repairs

Year: 2012

Systems: Partial Areaway Grating replacement including Drains,partial Exterior Stairs and Railing repairs, new MusicRoom, partial Student Toilet Room upgrades, partialFlooring replacement on 1st and 2nd Floors.

Year: 2010

Systems: Window and Exterior Guards replacement

Year: 2009

Have there been any New Building Additions? No

Tandem Schools? No

Leased Space? No

Priority Condition

PriorityCondition ExistLast Year?

PriorityCategory

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

No Tripping Hazard Severelydamage stairtread is apotentialtripping hazard.

SITE |STAIRS/RAMPS: EXTERIOR |Stairs/ramps

Near the LowerLevelPlayground

Eddie Jordan Fireman

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K039

PB/A&W Print Date: 6/21/2019Page 2 of 26

Page 3: NYC Department of Education - NYCSCA102, 104 and 106, water leaks fixed, Basement Boys and Girls Toilet Room upgrades Year: 2016 Systems: Wood Flooring replacement, thirteen Interior

Structural Engineer Required

StructuralCondition Type

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

No condition recorded

Accessibility

Accessibility Status Question Response

Is the primary or secondary entrance on an accessible route? No

Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem

FireAlarmStrobe

FUNCTIONAL ACCESSIBILITY

Exterior Routes

Exterior Entrances & Exits Yes

Exterior H/C Lifts No No

Exterior Ramps and Railings No Yes

Interior Routes

Corridor and Lobby H/C Lifts No Yes

Interior Corridor Doors and Hardware Yes Yes

Interior Corridors and Lobbies No Change in Elevation

Interior Elevators No

Interior Lobby Doors and Hardware Yes

Interior Ramps No

Rooms & Spaces

Art Rooms Room 105 Yes No Not on Accessible Route

Auditorium No

Cafeteria Basement Yes No Not on Accessible Route No No

Classrooms None on Accessible Route Yes No Not on Accessible Route

Computer Rooms Room 302 Yes No Not on Accessible Route

Gymnasium No

Library No

Main Office Room 100 Yes No Not on Accessible Route

Multi-purpose Room No

Nurse's Room Room 100B Yes No Not on Accessible Route

Pool No

Science Lab No

Toilet Rooms (Boys) None on Accessible Route Yes No Not on Accessible Route

Toilet Rooms (Girls) None on Accessible Route Yes No Not on Accessible Route

Toilet Rooms (Staff) None on Accessible Route Yes No Not on Accessible Route

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K039

PB/A&W Print Date: 6/21/2019Page 3 of 26

Page 4: NYC Department of Education - NYCSCA102, 104 and 106, water leaks fixed, Basement Boys and Girls Toilet Room upgrades Year: 2016 Systems: Wood Flooring replacement, thirteen Interior

Building Template

Inspection

Question Response

Architectural

EXTERIOR Inspected

AREAWAY Inspected

InspectedInstance on AW1 - AW3

Instance Condition 2 - Between Good and Fair

Instance Quantity 3

Instance Quantity Uom EACH

Deficiency AREAWAY WALLS: DETERIORATED COPING STONE

Roof Plan reference

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K039

PB/A&W Print Date: 6/21/2019Page 4 of 26

Page 5: NYC Department of Education - NYCSCA102, 104 and 106, water leaks fixed, Basement Boys and Girls Toilet Room upgrades Year: 2016 Systems: Wood Flooring replacement, thirteen Interior

Question Response

EXTERIOR

AREAWAY

Deficiency Photo1

AW2

Violations No violations recorded.

Deficiency AREAWAY WALLS: OPEN JOINTS

Roof Plan reference

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade D - AW3

Violations No violations recorded.

AWNINGS AND CANOPIES Does not Exist

CHIMNEY Inspected

Material Type(s) Masonry

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

COPING Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

CORNICE Inspected

Condition 1 - Good

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K039

PB/A&W Print Date: 6/21/2019Page 5 of 26

Page 6: NYC Department of Education - NYCSCA102, 104 and 106, water leaks fixed, Basement Boys and Girls Toilet Room upgrades Year: 2016 Systems: Wood Flooring replacement, thirteen Interior

Question Response

EXTERIOR

CORNICE Inspected

Deficiency No deficiencies recorded

DOORS Inspected

DOORS AND FRAMES Inspected

Condition 5 - Poor

Deficiency WOOD: DETERIORATED DOOR AND FRAME - MINORDETERIORATION

Roof Plan reference

Deficiency Quantity 2

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

Deficiency WOOD: DETERIORATED DOOR AND FRAME - MAJORDETERIORATION

Roof Plan reference

Deficiency Quantity 10

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K039

PB/A&W Print Date: 6/21/2019Page 6 of 26

Page 7: NYC Department of Education - NYCSCA102, 104 and 106, water leaks fixed, Basement Boys and Girls Toilet Room upgrades Year: 2016 Systems: Wood Flooring replacement, thirteen Interior

Question Response

EXTERIOR

DOORS Inspected

DOORS AND FRAMES Inspected

Facade A - Main Entrance

Violations No violations recorded.

DOOR HARDWARE Inspected

Condition 3 - Fair

Deficiency No deficiencies recorded

LINTELS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

TRANSOM/SIDE LIGHT Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

EXTERIOR WALLS Inspected

Material Type(s) Masonry

Replacement Quantity 15,000

Replacement Uom S.F.

InspectedInstance on All Facades

Instance Condition 2 - Between Good and Fair

Instance Quantity 15,000

Instance Quantity Uom S.F.

Deficiency BRICK: OPEN JOINTS

Roof Plan reference

Elevation

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPOINT

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K039

PB/A&W Print Date: 6/21/2019Page 7 of 26

Page 8: NYC Department of Education - NYCSCA102, 104 and 106, water leaks fixed, Basement Boys and Girls Toilet Room upgrades Year: 2016 Systems: Wood Flooring replacement, thirteen Interior

Question Response

EXTERIOR

EXTERIOR WALLS

Deficiency Photo1

Facade B

Violations No violations recorded.

EXTERIOR SOFFITS Does not Exist

LOADING DOCK Does not Exist

LOUVER Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

PARAPETS Does not Exist

PLAZA DECK Does not Exist

ROOF Inspected

Roofing Inspected

Replacement Quantity 9,000

Replacement Uom S.F.

ROOF HATCH/SMOKE HATCH Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

ROOF BARRIER Does not Exist

ROOF CAGE Does not Exist

ROOF FENCE Does not Exist

ROOFING Inspected

InspectedInstance on Asphalt Shingle: Roofs 1 - 4

Instance Condition 2 - Between Good and Fair

Instance Quantity 7,800

Instance Quantity Uom S.F.

Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?

No

Installation Year 2013

Source of Installation Custodial Staff

Deficiency No deficiencies recorded

InspectedInstance on Metal: Roofs 5 - 9

Instance Condition 1 - Good

Instance Quantity 500

Instance Quantity Uom S.F.

Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?

No

Installation Year 2013

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K039

PB/A&W Print Date: 6/21/2019Page 8 of 26

Page 9: NYC Department of Education - NYCSCA102, 104 and 106, water leaks fixed, Basement Boys and Girls Toilet Room upgrades Year: 2016 Systems: Wood Flooring replacement, thirteen Interior

Question Response

EXTERIOR

ROOF

Roofing

ROOFING

Source of Installation Custodial Staff

Deficiency No deficiencies recorded

InspectedInstance on Slate Roof: Roof 10

Instance Condition 1 - Good

Instance Quantity 700

Instance Quantity Uom S.F.

Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?

No

Installation Year 2013

Source of Installation Custodial Staff

Deficiency No deficiencies recorded

ROOFING DRAINS Does not Exist

Specialties Does not Exist

STAIRS/RAMPS: EXTERIOR Inspected

BUILDING CHEEK/FLANK WALLS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

RAILINGS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

STAIRS/RAMPS Inspected

Condition 3 - Fair

Deficiency STONE: CRACKS, SPALLING

Roof Plan reference

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K039

PB/A&W Print Date: 6/21/2019Page 9 of 26

Page 10: NYC Department of Education - NYCSCA102, 104 and 106, water leaks fixed, Basement Boys and Girls Toilet Room upgrades Year: 2016 Systems: Wood Flooring replacement, thirteen Interior

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR Inspected

STAIRS/RAMPS

Facade B - Exit 3A

Violations No violations recorded.

WINDOWS Inspected

Replacement Quantity 5,000

Replacement Uom S.F.

EXTERIOR GUARDS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LINTELS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

WINDOWS Inspected

Material Type(s) Aluminum

InspectedInstance on Aluminum - Double Hung: All Facades

Instance Condition 3 - Fair

Instance Quantity 5,000

Instance Quantity Uom S.F.

Installation Year 2009

Source of Installation Custodial Staff

Deficiency ALUMINUM - DOUBLE HUNG: INOPERABLE BALANCE

Roof Plan reference

Elevation

Deficiency Quantity 100

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K039

PB/A&W Print Date: 6/21/2019Page 10 of 26

Page 11: NYC Department of Education - NYCSCA102, 104 and 106, water leaks fixed, Basement Boys and Girls Toilet Room upgrades Year: 2016 Systems: Wood Flooring replacement, thirteen Interior

Question Response

EXTERIOR

WINDOWS Inspected

WINDOWS

Deficiency Photo1

Facade B - Room 300B

Violations No violations recorded.

INTERIOR Inspected

POOLS Does not Exist

STRUCTURAL Inspected

COLUMNS/BEAMS/BEARING WALLS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

FLOOR STRUCTURE Inspected

Condition 2 - Between Good and Fair

Deficiency CONCRETE SLAB ON GRADE: THRU CRACKS

Deficiency Location/Instance Basement - Boiler Room

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 5

Deficiency Photo1

Boiler Room

Violations No violations recorded.

FOUNDATION WALLS Inspected

Material Type(s) Masonry

Condition 4 - Between Fair and Poor

Deficiency BRICK: CRACKED/SPALLED

Deficiency Location/Instance Basement - Near Exit 1

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action RESTITCH

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K039

PB/A&W Print Date: 6/21/2019Page 11 of 26

Page 12: NYC Department of Education - NYCSCA102, 104 and 106, water leaks fixed, Basement Boys and Girls Toilet Room upgrades Year: 2016 Systems: Wood Flooring replacement, thirteen Interior

Question Response

INTERIOR

STRUCTURAL

FOUNDATION WALLS

Deficiency Photo1

Basement - Near Exit 1

Violations No violations recorded.

Deficiency BRICK: CRACKED/SPALLED

Deficiency Location/Instance Basement - Boiler Room, Gas Meter Room

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action RESTITCH

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 5

Deficiency Photo1

Boiler Room

Violations 35322244X

ROOF STRUCTURE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

VAULTS-BUNKERS Does not Exist

AUDITORIUM Does not Exist

CAFETERIA Inspected

InspectedInstance on Basement

Ceiling

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

Not RequiredInstance on Basement

Fixed Equipment

Does not ExistInstance on Basement

Floor Finish

InspectedInstance on Basement

Condition 2 - Between Good and Fair

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K039

PB/A&W Print Date: 6/21/2019Page 12 of 26

Page 13: NYC Department of Education - NYCSCA102, 104 and 106, water leaks fixed, Basement Boys and Girls Toilet Room upgrades Year: 2016 Systems: Wood Flooring replacement, thirteen Interior

Question Response

INTERIOR

CAFETERIA

Floor Finish

Deficiency VINYL TILES: DETERIORATED SUBSTRATE

Deficiency Location/Instance Near the Girls Toilet Room

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near the Girls Toilet Room

Violations No violations recorded.

Sliding-folding Partition

Does not ExistInstance on Basement

Stage

Does not ExistInstance on Basement

Walls

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency BRICK: CRACKS/SPALLING

Deficiency Location/Instance Near the window

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near the window

Violations No violations recorded.

Window Curtains/Shades/Blinds

Does not ExistInstance on Basement

CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected

Ceiling Inspected

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K039

PB/A&W Print Date: 6/21/2019Page 13 of 26

Page 14: NYC Department of Education - NYCSCA102, 104 and 106, water leaks fixed, Basement Boys and Girls Toilet Room upgrades Year: 2016 Systems: Wood Flooring replacement, thirteen Interior

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency WOOD: DAMAGED/DETERIORATED

Deficiency Location/Instance Rooms 207, 208, 301, 302, 304, and others

Deficiency Quantity 80

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 302

Violations No violations recorded.

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency BRICK: CRACKS/SPALLING

Deficiency Location/Instance Near Exit 2

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near Exit 2

Violations No violations recorded.

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Room 306, near Exit 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K039

PB/A&W Print Date: 6/21/2019Page 14 of 26

Page 15: NYC Department of Education - NYCSCA102, 104 and 106, water leaks fixed, Basement Boys and Girls Toilet Room upgrades Year: 2016 Systems: Wood Flooring replacement, thirteen Interior

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Walls

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 306

Violations No violations recorded.

Specialties Does not Exist

GYMNASIUM Does not Exist

INTERIOR DOOR HARDWARE Inspected

Condition 3 - Fair

Deficiency No deficiencies recorded

INTERIOR GUARDS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

KITCHEN Inspected

InspectedInstance on Basement

Ceiling

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on Basement

Condition 3 - Fair

Deficiency METAL CLAD WOOD: DETERIORATED DOOR

Deficiency Location/Instance Storage Room/Office

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K039

PB/A&W Print Date: 6/21/2019Page 15 of 26

Page 16: NYC Department of Education - NYCSCA102, 104 and 106, water leaks fixed, Basement Boys and Girls Toilet Room upgrades Year: 2016 Systems: Wood Flooring replacement, thirteen Interior

Question Response

INTERIOR

KITCHEN

Door(s)

Deficiency Photo1

Storage Room/Office

Violations No violations recorded.

Floor Finish

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LIBRARY Does not Exist

LOCKER ROOM Does not Exist

MULTI-PURPOSE ROOM Does not Exist

SCIENCE DEMO ROOM Does not Exist

SCIENCE LAB Does not Exist

SCIENCE PREP ROOM Does not Exist

SHOWER ROOM Does not Exist

STAIRS/RAMPS: INTERIOR Inspected

Do Letter Stair Signs Exist? Partially

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 5 - Poor

Deficiency METAL CLAD WOOD: DETERIORATED DOOR AND FRAME

Deficiency Location/Instance Stairs AB/1,2, C/2, FG/1

Deficiency Quantity 5

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K039

PB/A&W Print Date: 6/21/2019Page 16 of 26

Page 17: NYC Department of Education - NYCSCA102, 104 and 106, water leaks fixed, Basement Boys and Girls Toilet Room upgrades Year: 2016 Systems: Wood Flooring replacement, thirteen Interior

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Door(s)

Deficiency Photo1

Stair AB/2

Violations No violations recorded.

Partition Inspected

Condition 3 - Fair

Deficiency GLASS PANEL: DAMAGED/DETERIORATED

Deficiency Location/Instance Stairs AB/Basement,1,2

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair AB/1

Violations No violations recorded.

Railings Inspected

Condition 3 - Fair

Deficiency METAL: BROKEN BRACKET

Deficiency Location/Instance Stairs C/2, FG/1

Deficiency Quantity 3

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K039

PB/A&W Print Date: 6/21/2019Page 17 of 26

Page 18: NYC Department of Education - NYCSCA102, 104 and 106, water leaks fixed, Basement Boys and Girls Toilet Room upgrades Year: 2016 Systems: Wood Flooring replacement, thirteen Interior

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Railings

Deficiency Photo1

Stair FG/1

Violations No violations recorded.

Stairs and Landings Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency BRICK: CRACKS/SPALLING

Deficiency Location/Instance Stair FG /Basement

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair FG /Basement

Violations No violations recorded.

Deficiency CERAMIC TILE: BROKEN/ MISSING

Deficiency Location/Instance Stairs AB/1,2,3

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K039

PB/A&W Print Date: 6/21/2019Page 18 of 26

Page 19: NYC Department of Education - NYCSCA102, 104 and 106, water leaks fixed, Basement Boys and Girls Toilet Room upgrades Year: 2016 Systems: Wood Flooring replacement, thirteen Interior

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Walls

Deficiency Photo1

Stair AB/1

Violations No violations recorded.

TOILET ROOMS - STAFF Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stalls Does not Exist

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

TOILET ROOMS - STUDENTS Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stalls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LIFE SAFETY Inspected

F.D. HOLDING AREA Does not Exist

STEEL STAIRS Does not Exist

SITE Inspected

CONTAINERIZATION Does not Exist

Drainage System for Asphalt Does not Exist

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K039

PB/A&W Print Date: 6/21/2019Page 19 of 26

Page 20: NYC Department of Education - NYCSCA102, 104 and 106, water leaks fixed, Basement Boys and Girls Toilet Room upgrades Year: 2016 Systems: Wood Flooring replacement, thirteen Interior

Question Response

SITE

Drainage System for Concrete Inspected

Catch Basins/Manhole - Surrounded by concrete Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

Culverts - Concrete Covering Does not Exist

Drainage System for Soil Does not Exist

DRINKING FOUNTAINS Does not Exist

FENCES Inspected

Condition 3 - Fair

Deficiency CONCRETE CURB: DAMAGED/DETERIORATED

Deficiency Location/Instance 6th Avenue

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

6th Avenue

Violations No violations recorded.

Deficiency WROUGHT IRON: DAMAGED/DETERIORATED

Deficiency Location/Instance 6th Avenue

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

6th Avenue

Violations No violations recorded.

Deficiency CHAIN LINK: DAMAGED POST/RAIL

Deficiency Location/Instance Near the Upper Level Playground

Deficiency Quantity 40

Quantity Uom L.F.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K039

PB/A&W Print Date: 6/21/2019Page 20 of 26

Page 21: NYC Department of Education - NYCSCA102, 104 and 106, water leaks fixed, Basement Boys and Girls Toilet Room upgrades Year: 2016 Systems: Wood Flooring replacement, thirteen Interior

Question Response

SITE

FENCES

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near the Upper Level Playground

Violations No violations recorded.

IRRIGATION SYSTEM Does not Exist

PAVING Inspected

Student Non-Use Inspected

Gravel Exists? No

Asphalt Does not Exist

Concrete Inspected

Condition 3 - Fair

Deficiency CRACKS - MAJOR

Deficiency Location/Instance Northwest - Principal parking area

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Northwest - Principal parking area

Violations No violations recorded.

Pavers Does not Exist

Student Use Inspected

Gravel Exists? No

Asphalt Does not Exist

Concrete Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

Pavers Does not Exist

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K039

PB/A&W Print Date: 6/21/2019Page 21 of 26

Page 22: NYC Department of Education - NYCSCA102, 104 and 106, water leaks fixed, Basement Boys and Girls Toilet Room upgrades Year: 2016 Systems: Wood Flooring replacement, thirteen Interior

Question Response

SITE

PAVING

Site Sidewalks & Walkways Inspected

Asphalt Does not Exist

Concrete Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

Pavers Does not Exist

DOT Sidewalk Inspected

Asphalt Does not Exist

Concrete Inspected

Condition 4 - Between Fair and Poor

Deficiency DAMAGED CURBS

Deficiency Location/Instance 6th Avenue

Deficiency Quantity 10

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

6th Avenue

Violations No violations recorded.

Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS

Deficiency Location/Instance 6th Avenue

Deficiency Quantity 550

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

6th Avenue

Violations No violations recorded.

Pavers Does not Exist

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K039

PB/A&W Print Date: 6/21/2019Page 22 of 26

Page 23: NYC Department of Education - NYCSCA102, 104 and 106, water leaks fixed, Basement Boys and Girls Toilet Room upgrades Year: 2016 Systems: Wood Flooring replacement, thirteen Interior

Question Response

SITE

PLAYGROUNDS Inspected

InspectedInstance on Upper Level Playground

InspectedInstance on Lower Level Playground

Benches

InspectedInstance on Upper Level Playground

Condition 1 - Good

Deficiency No deficiencies recorded

InspectedInstance on Lower Level Playground

Condition 1 - Good

Deficiency No deficiencies recorded

Fence

InspectedInstance on Upper Level Playground

Condition 2 - Between Good and Fair

Deficiency WROUGHT IRON: DAMAGED/DETERIORATED

Deficiency Location/Instance Upper Level Playground

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Upper Level Playground

Violations No violations recorded.

Pavement

InspectedInstance on Upper Level Playground

Condition 1 - Good

Deficiency No deficiencies recorded

InspectedInstance on Lower Level Playground

Condition 1 - Good

Deficiency No deficiencies recorded

Play Equipment

InspectedInstance on Upper Level Playground

Condition 1 - Good

Deficiency No deficiencies recorded

InspectedInstance on Lower Level Playground

Condition 1 - Good

Deficiency No deficiencies recorded

Safety Surfacing

InspectedInstance on Upper Level Playground

Condition 1 - Good

Deficiency No deficiencies recorded

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K039

PB/A&W Print Date: 6/21/2019Page 23 of 26

Page 24: NYC Department of Education - NYCSCA102, 104 and 106, water leaks fixed, Basement Boys and Girls Toilet Room upgrades Year: 2016 Systems: Wood Flooring replacement, thirteen Interior

Question Response

SITE

PLAYGROUNDS

Safety Surfacing

InspectedInstance on Lower Level Playground

Condition 1 - Good

Deficiency No deficiencies recorded

Unpaved Area

Does not ExistInstance on Upper Level Playground

Does not ExistInstance on Lower Level Playground

PLAYING SURFACE Does not Exist

RETAINING WALLS Inspected

Are there any Retaining Walls 6' OR higher facing publicstreet/sidewalk?

No

Condition 3 - Fair

Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR

Deficiency Location/Instance Near the Lower Level Playground

Deficiency Quantity 25

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near the Lower Level Playground

Violations No violations recorded.

SEATING Does not Exist

SITE WALLS (NOT RETAINING WALLS) Does not Exist

STAIRS/RAMPS: EXTERIOR Inspected

Railings Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Site Cheek/flank Walls Inspected

Condition 2 - Between Good and Fair

Deficiency BRICK: CRACKS/SPALLING - MAJOR

Deficiency Location/Instance Near the Playground

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K039

PB/A&W Print Date: 6/21/2019Page 24 of 26

Page 25: NYC Department of Education - NYCSCA102, 104 and 106, water leaks fixed, Basement Boys and Girls Toilet Room upgrades Year: 2016 Systems: Wood Flooring replacement, thirteen Interior

Question Response

SITE

STAIRS/RAMPS: EXTERIOR

Site Cheek/flank Walls

Deficiency Photo1

Near the Playground

Violations No violations recorded.

Stairs/ramps Inspected

Condition 2 - Between Good and Fair

Deficiency STONE: CRACKS/SPALLING

Deficiency Location/Instance Near the Lower Level Playground

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near the Lower Level Playground

Violations No violations recorded.

Deficiency STONE: CRACKS/SPALLING

Deficiency Location/Instance Near the Lower Level Playground

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

Deficiency Photo1

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K039

PB/A&W Print Date: 6/21/2019Page 25 of 26

Page 26: NYC Department of Education - NYCSCA102, 104 and 106, water leaks fixed, Basement Boys and Girls Toilet Room upgrades Year: 2016 Systems: Wood Flooring replacement, thirteen Interior

Question Response

SITE

STAIRS/RAMPS: EXTERIOR

Stairs/ramps

Near the Lower Level Playground

Violations No violations recorded.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K039

PB/A&W Print Date: 6/21/2019Page 26 of 26