  • 7/26/2019 Nexans Fibre Trunking System Installation Manual-V1

    1/14

    NEXANS CABLING [email protected] www.nexans.cn/LANsystems

    Nexans Installation Manual

    Fibre Trunking System

    Jan 2015 V1.0

  • 7/26/2019 Nexans Fibre Trunking System Installation Manual-V1

    2/14

    NEXANS CABLING [email protected] www.nexans.cn/LANsystems

    NexansFibreTrunkingS

    ystem

    Importantremark:Installationistobeperformedbyqualifiedservicepersonnel

    Important Note:Installation may require special tools like saw, cutting machine, screw driver etc.Make sure safety protection method is provided.

    Only qualified personnel is allowed.National safety regulations will overrideinstallation standards.

    All Nexans installations shall be completed in accordance with (IAW) the relevantstandards. Different countries have different applicable standards. Some regionsuse a hybrid of them so depending on your location the relevant standards shallbe followed. It is important to always check for the latest versions of standards as

    they are constantly being updated.

    For more information about installation procedures please contact TechnicalSupport Department of Nexans Cabling Solutions.

    1

  • 7/26/2019 Nexans Fibre Trunking System Installation Manual-V1

    3/14

    NEXANS CABLING [email protected] www.nexans.cn/LANsystems

    NexansFibreTrunkingS

    ystem

    Importantremark:Installationistobeperformedbyqualifiedservicepersonnel

    Fiber Pathway system:A Cable pathway is designed to hold data communication cables in buildings anddatacenters. The increasing data transfer between workstations,telecommunication rooms and data centers requires high-bandwidth. Being readyto run new applications more than a decade out requires a scalable, flexible andfuture proof system, datacenter now rely on fiber to connect between eachpatching area as backbone. A Fiber pathway system is specially designed toprotect fiber optic from physical. It also provides a versatile, scalable pathway thatreduces the costs associated with maintaining existing network operations andimplementing new services.

    Nexans provides Fibre Trunking System to secure your valuable data transmission.Fibre Trunking System allows people to modify and mantenance during datatransmission. No need to worry about future growth, a wide range of fittings canmet any consequence.

    2

  • 7/26/2019 Nexans Fibre Trunking System Installation Manual-V1

    4/14

    NEXANS CABLING [email protected] www.nexans.cn/LANsystems

    NexansFibreTrunkingS

    ystem

    Importantremark:Installationistobeperformedbyqualifiedservicepersonnel

    Before installation:

    It is important that the correct pathway solution be installed in order to meetboth the requirements of the environment into which it is being installed and thecabling products being installed within the solution.

    EN 50174-2

    EN 50600-2-4

    ANSI/TIA-569-B-2008

    Where there is a requirement to keep other cable types away from data cablesthe separation must be such that it cannot be inadvertently changed. Forexample both the data cables should be held together with velcro and powershould be tie wrapped in place to maintain the separation distances required.

    Information technology - Cabling installation- Part 2:

    Installation planning and practices inside buildings

    Information technology - Data centre facilities and

    infrastructures. Telecommunications cabling infrastructure

    Commercial Building Standard for TelecommunicationsPathways and Spaces

    3

  • 7/26/2019 Nexans Fibre Trunking System Installation Manual-V1

    5/14

    NEXANS CABLING [email protected] www.nexans.cn/LANsystems

    NexansFibreTrunkingS

    ystem

    Importantremark:Installationistobeperformedbyqualifiedservicepersonnel

    Pathways

    Where the pathway system provides continuous support, the cables mustnot be stacked more than 150mm.This is to prevent crush damage to the cablesat the bottom. EN50174-2 4.4 refers.

    Use the Nexans installation software toolkit to calculate the size of containmentyou need, this is available at http://www.nexans.co.uk/eservice/UK-en_GB/navigateproduct_540160551/LAN_Calculation_Toolkit.html

    Make sure the pathway systems have smooth surfaces and also be free of burrs,sharp edges or projections that can damage cable insulation and be free of

    pressure points that may degrade the transmission performance of the installedsystem.

    Pathways made from tray-work shall be positioned to provide a minimumclearance of 25 mm from the fixing surface and to provide as much workingspace as possible above the tray (minimum 150mm) to enable access duringinstallation and accommodate the maximum stacking height of cables.

    240 System

    240x100mm>1000 3mm Fiber patch cords>800 3.7mm MPO trunk cables or MPO patch cords

    120 System

    120x100mm>500 3mm Fiber patch cords>400 3.7mm MPO trunk cables or MPO patch cords

    SLAB150mm

    Min

    4

    http://www.nexans.co.uk/eservice/UK-en_GB/navigateproduct_540160551/LAN_Calculation_Toolkit.htmlhttp://www.nexans.co.uk/eservice/UK-en_GB/navigateproduct_540160551/LAN_Calculation_Toolkit.htmlhttp://www.nexans.co.uk/eservice/UK-en_GB/navigateproduct_540160551/LAN_Calculation_Toolkit.htmlhttp://www.nexans.co.uk/eservice/UK-en_GB/navigateproduct_540160551/LAN_Calculation_Toolkit.htmlhttp://www.nexans.co.uk/eservice/UK-en_GB/navigateproduct_540160551/LAN_Calculation_Toolkit.html
  • 7/26/2019 Nexans Fibre Trunking System Installation Manual-V1

    6/14

    NEXANS CABLING [email protected] www.nexans.cn/LANsystems

    NexansFibreTrunkingS

    ystem

    Importantremark:Installationistobeperformedbyqualifiedservicepersonnel

    Cable Management on Tray/Basket

    EN 50174-2:2009 in section 5.3.5 details the requirements

    Cable installation, installation of cables shall be in accordance with theinstructions supplied by their manufacturers/suppliers.

    Installation of cable shall be undertaken according to the installationschedule.

    When installing cables, cords or jumpers appropriate techniques shallbe applied in order to:

    eliminate cable stress caused by: - tension in suspended cable runs; -tightly pinched cable bundles; - ensuring that minimum bend radii are asspecified by the cable manufacturer, supplier or in accordance with therelevant product standard (rollers or other devices shall be used to avoiddamage);

    Ensure that the tensile load applied to the cables and cable bundles asspecified by the cable manufacturer, supplier or are in accordance withthe relevant product standards. Unless otherwise stated in the suppliers/manufacturers specification, the maximum tensile load applied to abundle shall be that specified for a single cable;

    prevent pressure marks (e.g. through improper fastening or crossovers)on the cable sheath or the cable elements;

    5

  • 7/26/2019 Nexans Fibre Trunking System Installation Manual-V1

    7/14

    NEXANS CABLING [email protected] www.nexans.cn/LANsystems

    NexansFibreTrunkingS

    ystem

    Importantremark:Installationistobeperformedbyqualifiedservicepersonnel

    Installation of supporting bracket

    A wide range of mounting hardware is provided to ensure the fiber guider couldbe mounted under any circumstance in data centers and IT rooms.

    Attached to Cable Ladder or upper ceiling or Auxiliary Framing Bar is the mostcommon way for mounting:

    Trapeze support:

    The trapeze supporting bracket is used to attach 120/240 channel to ceilingfrom above. It is a straight bracket with 2 x M 20 threaded rod and fasteners toenable fitting of the main channel mounting bracket from overhead ceiling inyour data centers.

    6

    High strength Expansion

    screws

    Max Loading: 1000kg

    Fixing the main channel on

    the bracket

    Interval of bracket < 1.5m

  • 7/26/2019 Nexans Fibre Trunking System Installation Manual-V1

    8/14

    NEXANS CABLING [email protected] www.nexans.cn/LANsystems

    NexansFibreTrunkingS

    ystem

    Importantremark:Installationistobeperformedbyqualifiedservicepersonnel

    Ladder support ( L bracket support):

    The L bracket support is used to attach 120/240 channel to provide sidemounting using the M20 thread rod or on existing rod. The L bracket providesadjustable mounting mechanism to support different mounting environments.Several accessories are available to fit certain environment.

    7

    Ladder support on existing rod

    Ladder support above ladder

  • 7/26/2019 Nexans Fibre Trunking System Installation Manual-V1

    9/14

    NEXANS CABLING [email protected] www.nexans.cn/LANsystems

    NexansFibreTrunkingS

    ystem

    Importantremark:Installationistobeperformedbyqualifiedservicepersonnel

    Auxiliary Framing support :

    You can attach 120/240 channel to auxiliary framing to provide side mountingusing the auxiliary framing kit.

    Cabinet/Rack support :Use Cabinet/Rack support kit to attach Channel on your standard Cabinet.

    8

  • 7/26/2019 Nexans Fibre Trunking System Installation Manual-V1

    10/14

    NEXANS CABLING [email protected] www.nexans.cn/LANsystems

    1 2

    3 4

    9

    Installation of In-Line Connectors:

    In-line Connectors are used to connect a wide range of connecting hardware.

    Nexans Fibre Trunking System provides Elbows, Bends, Tees and Crosses to easePathway design. All of those fitters and transits are available in 120mm and240mm width and transits allow 240mm channel convert to 120mm channel.

    NexansFibreTrunkingS

    ystem

    Importantremark:Installationistobeperformedbyqualifiedservicepersonnel

  • 7/26/2019 Nexans Fibre Trunking System Installation Manual-V1

    11/14

    NEXANS CABLING [email protected] www.nexans.cn/LANsystems

    10

    120 series:

    NexansFibreTrunkingS

    ystem

    Importantremark:Installationistobeperformedbyqualifiedservicepersonnel

    120mmEqual Tee 120mmEqual Cross

    120mmElbow

    120mmVertical Tee

    120mm45Internal/External Bends

  • 7/26/2019 Nexans Fibre Trunking System Installation Manual-V1

    12/14

    NEXANS CABLING [email protected] www.nexans.cn/LANsystems

    11

    240 series:

    NexansFibreTrunkingS

    ystem

    Importantremark:Installationistobeperformedbyqualifiedservicepersonnel

    240mmEqual Tee

    240mmEqual Cross

    240mmElbow

    240mm transit to 120mmVertical Tee

    240mm45Internal/External Bends

  • 7/26/2019 Nexans Fibre Trunking System Installation Manual-V1

    13/14

    NEXANS CABLING [email protected] www.nexans.cn/LANsystems

    12

    240mm to 120mm transition series:

    Please refer to Nexans Technical Support Team for more information

    on Site installation.

    NexansFibreTrunkingS

    ystem

    Importantremark:Installationistobeperformedbyqualifiedservicepersonnel

    240mm to120mmReducer

    240mm to120mmUnequal Cross

    240mm to 120mmUnequal Tee

  • 7/26/2019 Nexans Fibre Trunking System Installation Manual-V1

    14/14

    NEXANS CABLING SOLUTIONS

    Nexans Cabling Solutions APACNo 1 Middle Fute Road, Waigaoqiao Free Trade Zone, Shanghai,

    200131 P.R.China

    Tel: +86 21 5046 2990*180 Fax: +86 21 5046 2758

    www.nexans.cn/LANsystems

    [email protected]

    Copyright@Jan2015N

    exa

    nsCablingSolutionsAPAC

    http://www.nexans.cn/LANsystemsmailto:[email protected]:[email protected]://www.nexans.cn/LANsystems