NAF S 125®
(HFC-125 + D-Limonene)
NAF S 227®
(HFC-227ea + D-Limonene)
UL LISTED TOTAL FLOODING CLEAN AGENT FIRE EXTINGUISHING SYSTEMS
APPROVED BY
www.eversafe.net
EVERSAFECORPORATE PROFILE
(053162-V)EXTINGUISHER SDN. BHD.
About Us :
Eversafe Extinguisher Sdn. Bhd. incorporated in year 1979, a member of Leeden National Oxygen Ltd, Singapore. Our production of fire-fighting equipment is housed within 2.844 acres of manufacturing and R&D facilities which allows us to offer an extensive range of high-quality products and systems.
We aim to be the global leader in the production and marketing of firefightingequipment, systems, and solutions, through the use of innovative design.
Core Values :
Vision :
Quality Control :
Manufacturing process and quality management systems have been approved to BS EN ISO 9001 by British Standards Institution.
Manufacturer/Distributor of :
Our products are in compliance with the following product standards / certification bodies:
Australian Standard (SAI Global)European Standard (BSI / LPCB)Malaysian Standard (SIRIM / IKRAM)Singapore Standard (TϋV SϋD PSB / SETSCO)Construction Product Directive, CPD / CPR (BRE)Pressure Equipment Directive, CE mark (Lloyd's Register)
Marine Equipment Directive, Wheel mark(Apragaz)Offshore Special Requirement -Sarawak Shell Bhd / Sarawak Shell Petroleum Co (SSB / SSPC)Kuwait National Petroleum Co (KNPC)Kuwait Oil Company (KOC)
b)c)
American Standard (UL)a)
d)e)f)g)
h)
i)
j)k)
Quality First
Safety is Our Priority Provide Solutions Customer Focus
Positive ChangeIntegrity AlwaysTeamwork
PRODUCT APPROVALS
1 In accordance to policy of continuous improvement, specifications are subject to change without notice.
Portable and MobileFire ExtinguishersFire Hose ReelsLanding ValvesBreeching InletsHydrant
NozzleSmoke AlarmFire BlanketCanvas HoseCabinetsCO2 Fire Extinguishing System
NAF S 227 Fire Extinguishing System(FM200 Alternative)NAF S 125 Fire Extinguishing SystemNAF S 1230 Fire Extinguishing System
Kerr Fire Foam CompoundWet Chemical Fire Suppression System
Inert Gases Fire Extinguishing System
1
2
3
4
5
6 Product Standards / Certification / Directives :
In accordance to policy of continuous improvement, specifications are subject to change without notice. 2
What edges NAF S 125® & NAF S 227® among other HFCs is the patented additive D-Limonene
WHAT D-LIMONENE DOES ?
Patented Additive D-Limonene
D-Limonene reduces the level of decomposition by-products which are harmful to humans and assets
Increase the extinguishing performances
Citrus odor contributes to early detection on leakage
✓
✓
✓
Environmental Friendly
Zero ODP
Low Order Of Toxicity
Safe For Human Occupancy
Cost Effective
Compact And Minimal Space Consumption
NAF S 125® Requires 20% Less Agent By Weight Than HFC-227ea Systems
Electrically Non-Conductive
Suitable For Electronic And Delicate Equipment
No Residue
Ease Of Clean-up
Class of Fires
Suitable For Class Fires A, B and C
NAF S 125® & NAF S 227® Engineered Total Flooding Clean Agent Fire Extinguishing System offers a wide range of cylinder capacity fire extinguishing systems in the market by choosing from four different valve types and cylinders ranging from 5 to 240 litres.
Our seamless cylinders range from 5 to 120 litres, are super-pressurized to 42 bar (600 psi). These 42 bar pressurised cylinder assemblies are the perfect choice for systems with long pipe runs or retrofitting existing Halon 1301 systems.
The working pressure of 26.8, 40.2, 75, 120, 175 and 240 litres welded cylinders is marked at 25 bar (360 psi), providing lower cost option for new systems.
Other advantages of NAF S 125® & NAF S 227® are :
Extinguishing System AdvantagesNAF S 125® & NAF S 227® Fire Extinguishing System
CERTIFIEDSAFETYPASSION
NAF S 125® (HFC-125 + D-LIMONENE) & NAF S 227® (HFC-227ea + D-LIMONENE) are gaseous extinguishing agents that are approved by Underwriters Laboratory Inc. (UL) as well United States Environmental Protection Agency (EPA) Significant New Alternatives
Policy (SNAP) as accept-able substitutes for Halon 1301 and listed in the Classification of Agents as per NFPA 2001 Standard.
3 In accordance to policy of continuous improvement, specifications are subject to change with
NAF S 125® & NAF S 227® engineered total flooding systems comply with the requirements specified in the NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems, and UL Listed. The systems are designed with maximum quality and reliability. With the credibility of EVERSAFE NAF S 125® & NAF S 227®, it is definitely a good alternative to FM 200.
UL LISTING
The use of a UL Validated Flow Calculation Program specifically developed by Hughes Associates, Inc. allow system designers to properly design NAF S 125® & NAF S 227®
systems and Authority Having Jurisdiction to determine that all design parameters have been met.
HUGHES ASSOCIATES, INC CERTIFICATION
US EPA SNAP LIST
NAF S 125® & NAF S 227®
In accordance to policy of continuous improvement, specifications are subject to change without notice. 4
NAF S 125® & NAF S 227® engineered systems are tested according to MSC/Circ. 848 and MSC/Circ. 1267 and DNV certified for marine applications such as machinery spaces and cargo pump rooms.
EVERSAFE Extinguisher SDN. BHD. operates a Quality Management System which complies with the global requirements of BS EN ISO 9001: 2015 and holds ISO 9001 certificates from BSI, United Kingdom.
EVERSAFE Extinguisher Sdn. Bhd. is UL approved Alternative Manufacturing Location (AML) to design, assemble, fill, refill, maintain and service a wide range of gas based fire protection systems with an available stock of GAS and Hardware.
EVERSAFE NAF S 125® & NAF S 227® are approved by BOMBA Malaysia for land applications in Malaysia Market, as well granted Sijil Guna Pakai (SGP) by Tenaga Nasional Berhad (TNB).
DNV MARINE CERTIFICATION
BOMBA APPROVAL CERTIFICATE
BSI ISO 9001 CERTIFICATION
SIJIL GUNA PAKAI (SGP) TNB CERTIFICATION
In accordance to policy of continuous improvement, specifications are subject to change without notice.5
NAF S 125® & NAF S 227® agents are colorless liquefied gaseous. Physical properties of the agents are very similar to those of Halon 1301, making them an ideal total flooding agent. When the gaseous are released to atmosphere their boiling point and vapor pressure cause the agents to vaporize creating an homogenous agent / air mix throughout the enclosure.
Molecular Weight
Composition
Boiling Point @ 760 mm Hg
Critical Temperature
Critical Pressure
Critical Density
Vapour Pressure @ 20˚C
Freezing Point
Viscosity of Liquid @ 25˚C
170.03
HFC-227ea (99.85%) + D-Limonene (0.15%)
-16.4°C
101.7°C
2912 kpa
621 kg/m3
4.57 bar
-131.1°C
0.184 cP
Solubility of Water in Agent @ 21˚C by weight
Specific Heat of Liquid @ 25˚C
Heat of Vapourization @ Boiling Point (25˚C)
Ozone Depletion Potential
Global Warming Potential
Atmoshperic Lifetime
0.06 %
1.184 kJ/kg°C
120.02
HFC-125 (99.85%) + D-Limonene (0.15%)
-48.5°C
66°C
3.395 kpa
571 kg/m3
13.5 bar
-102.8°C
0.154 cP
0.07 %
1.260 kJ/kg°C
132.6 kJ/kg164.7 kJ/kg
00
32203500
33 years29 years
PHYSICAL PROPERTIES NAF S 125® NAF S 227®
THE AGENTS PHYSICAL PROPERTIES
Gaseous Agent
Low Chemical Reactivity
Electrical Non-Conducting
High Weight Effeciency
Low Number of Cylinders
Low Enclosure Pressure
Zero ODP
Zero GWP
Non-VOC
Discharge Time (sec)
HALOCARBONS (HFC) INERT GAS PERFLUOROKETONES
✓✓✓✓✓✓✓
✓10
✓✓✓✓
✓✓✓60
✓
✓✓✓
10
COMPARISON BETWEEN NAF S 125® & NAF S 227®AND OTHER CLEAN AGENTS
In accordance to policy of continuous improvement, specifications are subject to change without notice. 6
1 Heat Detector
2 Smoke Detector
3 Discharge Nozzle
4 LED Evacuate Sign
5 Slave Cylinder
6 Master Cylinder
7 Manifold
8 Discharge Hose
9 Actuation Hose
10 Fire Control Panel
11 Alarm Bell
12 Abort Switch/Manual Call Point
13 Twin Flashing Light
General Installation
*Refer to system components for details and informations
1
4
5
7
8
10
126
9
11
13
32
NAF S 125® & NAF S 227® Fire Extinguishing Systems are designed with the ability to suppress fire in the shortest time possible, especially in enclosed areas occupied by human . Its clean and zero residue properties makes it the perfect solution to protect areas such as:
THE NAF S 125® & NAF S 227® SYSTEMAPPLICATION
GENERAL INSTALLATION OF NAF S 125® & NAF S 227®
4 5Archives, Data Bank & Industrial
ApplicationsMarine
Applications
Data StorageLaboratories
Archives & LibrariesClean Rooms
Military InstallationsPharmaceutical Facilities
Machinery Spaces
Cargo Pump Rooms
1 2 3
TelecommunicationFacilities
Power Generation,Transmission & Distribution
Facilities
Commercial, Institutional,Corporate & Electronic Facilities
Communication CentresCall Centres
Satellite Ground StationsCentral & Remote Cellular Sites
Power PlantPower TransmittorSubstation Rooms
Electric Rooms
Medical RoomsServer Rooms
Computer RoomsGalleries
Aviation & HangarsProcess Control Rooms
In accordance to policy of continuous improvement, specifications are subject to change without notice.7
Extinguishing System ComponentsNAF S 125® & NAF S 227® Fire Extinguishing System
Seamless Steel Cylinder Valve Assembly 42 Bar Systems
Part No. NAF S 227
Thread Valve
Nominal Cylinder CapacityDischarge Valve Type
Working PressureWorking TemperatureOverall HeightExternal DiameterFinishingApprovals
1” - 11.5 NPT
5 litre 26.8 litre13.4 litre
140 mm 229 mm140 mmRAL 3000 Flame Red Epoxy Polyester Powder Coa�ng
2010/35/EU TPED, ADR, UL Listed
615 mm 1000 mm1250 mm
SHT V20
42 bar-20°C to 50°C
SH70027410 SH70027409 SH70027408Part No. NAF S 125 SH70025410 SH70025409 SH70025408
Seamless Steel Cylinder Valve Assembly 42 Bar Systems
Part No. NAF S 227
Thread Valve
Nominal Cylinder CapacityDischarge Valve Type
Working PressureWorking TemperatureOverall HeightExternal DiameterFinishingApprovals
2 ½” - 12UN - 2B
75 litre 120 litre
267 mm 358 mmRAL 3000 Flame Red Epoxy Polyester Powder Coa�ng
2010/35/EU TPED, ADR, UL Listed
1785 mm 1680 mm
SHT V40
42 bar-20°C to 50°C
SH70027405 SH70027403Part No. NAF S 125 SH70025405 SH70025403
Seamless Steel Cylinder Valve Assembly 42 Bar Systems
Part No. NAF S 227
Thread Valve
Nominal Cylinder CapacityDischarge Valve Type
Working PressureWorking TemperatureOverall HeightExternal DiameterFinishingApprovals
G.1 ½”
40.2 litre 67.5 litre
229 mm 267 mmRAL 3000 Flame Red Epoxy Polyester Powder Coa�ng
2010/35/EU TPED, ADR, UL Listed
1370 mm 1625 mm
SHT V25
42 bar-20°C to 50°C
SH70027407 SH70027412Part No. NAF S 125 SH70025407 SH70025412
Welded Cylinder Valve Assembly 25 Bar Systems
Part No. NAF S 227
Thread Valve
Nominal Cylinder CapacityDischarge Valve Type
Working PressureWorking TemperatureOverall HeightExternal DiameterFinishingApprovals
3 ½” - 12UN - 2A
175 litre 240 litre
445 mm 445 mmRAL 3000 Flame Red Epoxy Polyester Powder Coa�ng
2010/35/EU TPED, ADR, UL Listed
1540 mm 1945 mm
SHT V65
25 bar-20°C to 50°C
SH70027414 SH70027415Part No. NAF S 125 SH70025414 SH70025415
In accordance to policy of continuous improvement, specifications are subject to change without notice. 8
Extinguishing System ComponentsNAF S 125® & NAF S 227® Fire Extinguishing System
Welded Cylinder Valve Assembly 25 Bar Systems
Part No. NAF S 227
Thread Valve
Nominal Cylinder CapacityDischarge Valve Type
Working PressureWorking TemperatureOverall HeightExternal DiameterFinishingApprovals
3 ½” - 12UN - 2A
120 litre
350 mmRAL 3000 Flame Red Epoxy Polyester Powder Coa�ng
2010/35/EU TPED, ADR, UL Listed
1750 mm
SHT V65
25 bar-20°C to 50°C
SH72527403Part No. NAF S 125 SH72525403
Welded Cylinder Valve Assembly 25 Bar Systems
Part No. NAF S 227
Thread Valve
Nominal Cylinder CapacityDischarge Valve Type
Working PressureWorking TemperatureOverall HeightExternal DiameterFinishingApprovals
3 ½” - 12UN - 2A
75 litre
350 mmRAL 3000 Flame Red Epoxy Polyester Powder Coa�ng
2010/35/EU TPED, ADR, UL Listed
1230 mm
SHT V65
25 bar-20°C to 50°C
SH72527405Part No. NAF S 125 SH72525405
Welded Cylinder Valve Assembly 25 Bar Systems
Part No. NAF S 227
Thread Valve
Nominal Cylinder CapacityDischarge Valve Type
Working PressureWorking TemperatureOverall HeightExternal DiameterFinishingApprovals
2 ½” - 12UN - 2A
40.2 litre
350 mmRAL 3000 Flame Red Epoxy Polyester Powder Coa�ng
2010/35/EU TPED, ADR, UL Listed
850 mm
SHT V40
25 bar-20°C to 50°C
SH72527407Part No. NAF S 125 SH72525407
Welded Cylinder Valve Assembly 25 Bar Systems
Part No. NAF S 227
Thread Valve
Nominal Cylinder CapacityDischarge Valve Type
Working PressureWorking TemperatureOverall HeightExternal DiameterFinishingApprovals
G ½” A
26.8 litre
350 mmRAL 3000 Flame Red Epoxy Polyester Powder Coa�ng
2010/35/EU TPED, ADR, UL Listed
750 mm
SHT V25
25 bar-20°C to 50°C
SH72527408Part No. NAF S 125 SH72525408
In accordance to policy of continuous improvement, specifications are subject to change without notice.9
Extinguishing System ComponentsNAF S 125® & NAF S 227® Fire Extinguishing System
Discharge Valve SHT V20
Part No. NAF S 227Part No. NAF S 125
Test Pressure
Admissible Cylinder Capaci�esValve Thread
Working PressureSafety Disc Pressure
ApprovalsBody Material
1” - 11.5 NPT
SH200251295 litre, 13. 5 litre, 26.8 litre
250 bar42 bar
95 ± 7 barBrass
2014/68/EU PED, UL Listed
SH20025128
Part No. NAF S 227Part No. NAF S 125
Test Pressure
Admissible Cylinder Capaci�esValve Thread
Working PressureSafety Disc Pressure
ApprovalsBody Material
G. 1½”
SH20025146SH2252514640.2 litre, 67.5 litre
250 bar42 bar
95 ± 7 barBrass
26.8 litre
25 bar60 ± 3 bar
2014/68/EU PED, UL Listed
SH20025145SH22525145
Discharge Valve SHT V25/B & SHT V25
Part No. NAF S 227Part No. NAF S 125
Test Pressure
Admissible Cylinder Capaci�esValve Thread
Working PressureSafety Disc Pressure
ApprovalsBody Material
2 ½” - 12UN
SH2002519175 litre, 100 litre, 120 litre40.2 litre
250 bar42 bar
95 ± 7 bar25 bar
60 ± 3 barBrass
2014/68/EU PED, UL Listed
SH20025190SH22525191SH22525190
Discharge Valve SHT V40/B & SHT V40
Part No. NAF S 227Part No. NAF S 125
Test Pressure
Admissible Cylinder Capaci�esValve Thread
Working PressureSafety Disc Pressure
ApprovalsBody Material
3 ½” - 12UN - 2A
SH2002502775 litre, 120 litre, 175 litre, 240 litre
150 bar25 bar
60 ± 3 barBrass
2014/68/EU PED, UL Listed
SH20025001
Discharge Valve SHT V65
In accordance to policy of continuous improvement, specifications are subject to change without notice. 10
Extinguishing System ComponentsNAF S 125® & NAF S 227® Fire Extinguishing System
Part No.
MaterialConnec�on
ApprovalsBrass
M 30 x 1.5
UL Listed
SH31009401
Manual Release
Manual Pneumatic Release
Part No.Connec�onPneuma�c Connec�onMaterialApprovals
M 30 x 1.5G ⅛”Brass
UL Listed
SH31009402
Solenoid Valve
Part No.
Current
TensionProtec�on
Temperature LimitMax. Working Pressure
530 mA
24 V DCIP-65
Class 105170 bar
Valve Body MaterialApprovals
BrassUL Listed
SH21006403
Part No.
Current
TensionProtec�on
Temperature LimitMax. Working Pressure
530 mA
24 V DCIP-65
Class 105170 bar
Valve Body MaterialApprovals
Stainless Steel AISI-303UL Listed
SH21006404
Solenoid Valve with Pneumatic Outlet
Nitrogen Pilot Cylinder Assembly
Part No.
Working Pressure
CapacityValve Thread
Working TemperatureFinishing
100 bar
3 litre Cylinder Filled with N2 at 100 barW 28.8 x ¼”
Discharge Valve Type SHT V 20-N2
- 20°C + 50°CRAL 3000 Flame Red Epoxy Polyester Powder Coa�ng
Approvals MED, CE, TPED, UL Listed
SH70025411
In accordance to policy of continuous improvement, specifications are subject to change without notice.11
Extinguishing System ComponentsNAF S 125® & NAF S 227® Fire Extinguishing System
Part No.
Length
Connec�on
Size
MaterialWorking PressureBurst PressureApprovals
Teflon PTFE & Stainless Steel Wire Braids
ISO 228R.¼”(MG) x R.¼”(MG)
ISO 228R.¼”(MG) x R.¼”(MG)
ISO 228G.⅛”(MF) x R.⅛”(HG)
DN 6 DN 8DN 8
132 bar396 bar
160 mm 580 mm 700 mm
UL Listed
SH30503290 SH30506014 SH30522001
Release Hoses
Discharge Flexible Hoses
Part No.
Length
Connec�on
MaterialWorking PressureBurst PressureApprovals
400 mmSize
ISO 228G.1”(HG) x G.1”(HF)
ISO 228G.¾”(HG) x G.¾”(HF)
DN 25 DN 20
185 bar 240 bar740 bar 960 bar
Synthe�c Rubber & High Tensile Steel Wire Braids
UL Listed
SH30502140 SH30506070ISO 228
G.1”(HG) x G.1”(HG)
DN 25 Admissible Valve Type SHT V25 & SHT V25/B SHT V20 SHT V25 & SHT V25/B
185 bar740 bar
SH30506001
Part No.Connec�on
Admissible Valve Type
Body MaterialWorking Pressure
ApprovalsBurst Test Pressure
ISO 228G.½”(FG-M)
ISO 228G.½”(FG-FG)
ISO 2282 ½” x 3” Groove
SHT V40 & SHT V40/B SHT V65Size DN 40 DN 65
132 bar396 bar
36 bar108 bar
Steel
UL Listed
SH30508080 SH23070204SH30508000
Discharge Rigid Hoses
In accordance to policy of continuous improvement, specifications are subject to change without notice. 12
Extinguishing System ComponentsNAF S 125® & NAF S 227® Fire Extinguishing System
Part No.
Working Pressure
Connec�onTriggering Pressure
MaterialApprovals
200 bar15 bar -150 bar
ISO 228 M 30 X 1.5Cone Type 1 Way 2 Ways
BrassUL Listed
SH30027303SH30027302
1 Way & 2 Ways Pneumatic Cone Release
Part No.Size Manifold Connec�onHose Connec�onMaterialApprovals
ISO 228 R1” 4” Coupling1” 3”
ISO 228 R1”ISO 228 R2”
ISO 228 G. ½” 3” Groove
2”
Galvanized SteelBrass BrassUL Listed
SH21006300 SH21006302 SH23070221
Check Valves
Part No.
Ac�va�on Pressure
Type
Test Pressure
MaterialApprovals
NIL420 bar
20 bar (Min)NIL
Working Pressure 140 bar 240 bar (Max)
Decompression ScrewType L
Decompression ScrewType C
BrassUL Listed
SH30027300 SH30027301
Relief Valve
SH21006304
Decompression Screw and Relief Valve
Part No.Head TypePneuma�c Connec�onMaterialApprovals
G. ¼”Blind Pneuma�c 2-Ways Pneuma�c
BrassUL Listed
SH26025001 SH26025002
Pneumatic Head for SHT V 65 Valve
In accordance to policy of continuous improvement, specifications are subject to change without notice.13
Extinguishing System ComponentsNAF S 125® & NAF S 227® Fire Extinguishing System
Part No.
Working Temperature
Connec�onMin. Actua�on Pressure
MaterialApprovals
-25°C to 80°CMax. Working Pressure 370 bar
10 barG. ½”
BrassDir. 2006/95/EC ; 2006/42/EC ; 2004/108/EC ; UL Listed
SH30330010
Pressure Switch With Locking Device
Part No. 180° Nozzle
Working Pressure
Part No. 360° NozzleThread SizeThread
MaterialApprovals
60 bar
⅜” ½” ¾” 1 ¼” 1 ½” 2”1”NPT
SteelUL Listed
SH30400007 SH30400008 SH30400009 SH30400010 SH30400011 SH30400012 SH30400013SH30400000 SH30400001 SH30400002 SH30400003 SH30400004 SH30400005 SH30400006
180° & 360° Nozzles
Part No.Thread SizeMaterialApprovals
⅜” ½” ¾” 1 ¼” 1 ½” 2”1”Steel AISI 303
UL Listed
SH30440032 SH30440042 SH30440052 SH30440062 SH30440072 SH30440082 SH30440092
Nozzles Threaded Diaphragms
In accordance to policy of continuous improvement, specifications are subject to change without notice. 14
Extinguishing System ComponentsNAF S 125® & NAF S 227® Fire Extinguishing System
A
Thickness
Part No.Cylinder CapacitySize (A)
MaterialFinishing
5 mm
175 litre 240 litre26 litre 40 litre600 mm 440 mm
Carbon SteelBlack
SH30601175SH3062101075 litre 120 litre
Welded Cylinder Bracket
A
Thickness
Part No.Cylinder CapacitySize (A)
MaterialFinishing
5 mm
5.0 litre 13.4 litre 26.8 litre 40.2 litre 75 litre67.5 litre 100 litre 120 litre215 mm 330 mm 365 mm 440 mm
Carbon SteelBlack
SH30621310 SH30625010 SH30626710 SH30621010
Seamless Cylinder Bracket
Internal Coa�ng
Pipe Connec�onSize Ø
FinishingApprovals
Galvanized
2 ½” - 4”BSPT Male
RAL 3000 Flame Red Epoxy Polyester Powder Coa�ng
Test PressureMaterial
100 barCarbon Steel ASTM A-105
UL Listed
Manifold
In accordance to policy of continuous improvement, specifications are subject to change without notice.15
Detection System ComponentsNAF S 125® & NAF S 227® Fire Extinguishing System
Model EE1810-13
Mains Supply
Size (W x H x L)IP Ra�ng
FinishingApprovals
230V ACIP30
368 mm x 310 mm x 90 mm
Signal Red PaintedUL/FM Listed
Extinguishant Control Panel
Model QUESTOR-SZUPart No.
Mains Supply
Size (W x H x L)IP Ra�ng
FinishingApprovals
230V ACIP30
368 mm x 310 mm x 90 mm
Signal Red PaintedUL/FM Listed
SHC80003
Extinguishant Control Panel
ModelPart No.
Approvals
Opera�ng VoltageFeature
UL ListedEquipped with Flashing LED
9-33VSHD90006
VENATOR-DU
Optical Smoke Detector
ModelPart No.
Approvals
Opera�ng VoltageFeature
UL ListedEquipped with Flashing LED
9-33VSHD90007
VENATOR-DU
135F Heat Detector
In accordance to policy of continuous improvement, specifications are subject to change without notice. 16
Detection System ComponentsNAF S 125® & NAF S 227® Fire Extinguishing System
Model
IP Ra�ng
SizeMaximum Voltage
Opera�ng TemperatureIP24D
30V DC88 mm x 88 mm x 59 mm
-20°C to 70°CFinishing Signal Red PaintedApprovals EN 54-11 / MS1745-11 BOMBA Approved
EE-302M
Manual Call Point
ModelPart No.Finishing Signal Red Painted
SHW80001
Approvals UL Listed
QUAESTOR-U
Abort Switch
Model
IP Ra�ng
Size (Ø x W)DC Rated Voltage
Opera�ng TemperatureIP33C
24V DC150 mm x 62 mm
-20°C to 70°CFinishing Signal Red PaintedApprovals EN 54-3 / MS1745-3 BOMBA Approved
EE-301
Fire Alarm Bell
ModelSize (W x H x L)Voltage
Opera�ng Temperature
12VCapacity 7 Ah
-20°C to 60°C
65 mm x 98 mm x 151 mm
Approvals UL Listed
NP7-12
Battery
In accordance to policy of continuous improvement, specifications are subject to change without notice.17
Detection System ComponentsNAF S 125® & NAF S 227® Fire Extinguishing System
Surge Arrestor
ModelSize (W x H x L)Maximum Voltage 19V AC280V AC
78.5 mm x 90 mm x 35.6 mm 60.5 mm x 90 mm x 17.5 mm
Approvals UL ListedEN 61643-11 , CE Marked
V20 FRD-24
Part No.Size (W x H x L)Opera�ng VoltageMaterial
24V DC74 mm x 90 mm x 179 mm
Mild SteelFinishing BlackApprovals Factory Manufacturing Standard
KP-305
Twin Flashing Light
Part No.Size (W x H x L)Opera�ng VoltageCurrent Consump�on
20-28V DC15mA@24V DC
89 mm x 102 mm x 254 mm
Finishing BlackApprovals Factory Manufacturing Standard
KP-309
LED Evacuate Sign
INTEGRITYTEST
ENCLOSURE
In accordance to policy of continuous improvement, specifications are subject to change with
It is laid down in NFPA 2001 standard that all total flooding clean agent systems shall have the enclosure examined and tested to locate and then effectively seal any significant air leaks that could result in a failure of the enclosure to hold the specified agent concentration level for the specified holding period of 10 minutes. Wherefore Eversafe offers a systematic gas integrity pneumatic test and provides with documented quantitative test results to our clients.
Our technicians are Retrotec certified level 3 testers who are comfortable with performing the enclosure integrity test, use Retrotec’s FanTestic Integrity software to evaluate peak pressure, free vent area & etc., and also able to do larger and more complex tests.
Our Retroctec blower door fan unit and other test equipment are calibrated and reliable, it gives accurate measurement and test results.
18
EVERSAFE® products are available in more than 45 countries worldwide
Our Global Network
+603 - 8024 9898 +603 - 8024 7878 / 9623 www.eversafe.net
[email protected] / [email protected] / [email protected]
www.facebook.com/eversafe.extinguisher
Lot 878, Jalan Subang 9, Taman Perindustrian Subang, 47500 Subang Jaya, Selangor Darul Ehsan, Malaysia.
DO
C. :
CTL
-NAF
REV
02
DAT
E: J
UN
E 20
19