extinguishing systems fire extinguishing systems for
TRANSCRIPT
![Page 1: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/1.jpg)
Page 1 Kalidasan S BT IN SSP-OPJune 2017
Fire Extinguishing Systems
Building Technologies
Extinguishing SystemsFor Critical Infrastructures
![Page 2: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/2.jpg)
Page 2 Kalidasan S BT IN SSP-OPJune 2017
ContentsKnow the components and functional in detailKnow the integration of Fire Alarm SystemHow does gas system operates in fire scenarioDo’s and Don’t of the systemComparison of Cylinder Quantity for various Clean Agents
Why Siemens and our Strength
![Page 3: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/3.jpg)
Page 3 Kalidasan S BT IN SSP-OPJune 2017
SINORIX HARDWARE
Discharge Valve
Model : VSB 33
QTY : 1 No per Cylinder
![Page 4: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/4.jpg)
Page 4 Kalidasan S BT IN SSP-OPJune 2017
Pressure Gauge with Low Pressure Switch
Model :PRESCODEM60
QTY : 1 No per Cylinder
![Page 5: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/5.jpg)
Page 5 Kalidasan S BT IN SSP-OPJune 2017
TOR MULTI
Model :TOR MULTI
QTY : 1 No per Cylinder
![Page 6: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/6.jpg)
Page 6 Kalidasan S BT IN SSP-OPJune 2017
TOR UNIT
Model :TOR UNIT
QTY : 1 No per System
![Page 7: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/7.jpg)
Page 7 Kalidasan S BT IN SSP-OPJune 2017
TOR END
Model :TOR END
QTY : 1 No per System
![Page 8: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/8.jpg)
Page 8 Kalidasan S BT IN SSP-OPJune 2017
Flexible Discharge Hose
Model : FRF 33
QTY : 1 No per Cylinder
![Page 9: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/9.jpg)
Page 9 Kalidasan S BT IN SSP-OPJune 2017
Check Valve
Model : CARF 33
QTY : 1 No per Cylinder
• Check valves are used only for centralised system.
• Fixed between the discharge hose and manifold.
![Page 10: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/10.jpg)
Page 10 Kalidasan S BT IN SSP-OPJune 2017
Electrical Actuator with Solenoid
Model : DEMADEM
QTY : 1 No per System
Note : The cable assembly must not be connected to the solenoid until all the testing has been completed, and the system is ready to be put into service
![Page 11: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/11.jpg)
Page 11 Kalidasan S BT IN SSP-OPJune 2017
Manual Actuator
Model : CM 16 (Centralised)
QTY : 1 No per System
![Page 12: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/12.jpg)
Page 12 Kalidasan S BT IN SSP-OPJune 2017
Manual Pneumatic Actuator
Model : DEPYM (Modular)
QTY : 1 No per System
![Page 13: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/13.jpg)
Page 13 Kalidasan S BT IN SSP-OPJune 2017
Pneumatic Actuator
Model : CP 16
QTY : 1 No per Cylinder
![Page 14: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/14.jpg)
Page 14 Kalidasan S BT IN SSP-OPJune 2017
Actuation Hose
Model : FLEJIC - 4
QTY : 1 No per Cylinder + One
![Page 15: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/15.jpg)
Page 15 Kalidasan S BT IN SSP-OPJune 2017
TEE
Model : TEJIC
QTY : 1 No per Cylinder
![Page 16: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/16.jpg)
Page 16 Kalidasan S BT IN SSP-OPJune 2017
ELBOW
Model : EQJIC
QTY : 1 No per System
![Page 17: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/17.jpg)
Page 17 Kalidasan S BT IN SSP-OPJune 2017
UNION
Model : UNIJIC (Modular)
QTY : 1 No per System
![Page 18: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/18.jpg)
Page 18 Kalidasan S BT IN SSP-OPJune 2017
Pressure Switch
Model : PRESSBOX
QTY : 1 No per System
• Pressure switch is mounted on the manifold.
• It operates upon gas discharge and gives an indication to the panel as “Gas discharged”.
![Page 19: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/19.jpg)
Page 19 Kalidasan S BT IN SSP-OPJune 2017
Nozzle
Model : BUCEFA / BFFP
There must not be any obstruction adjacent to the nozzle, such as beams or columns, ducts, racks, panels etc., that could affect the discharge pattern.
![Page 20: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/20.jpg)
Page 22 Kalidasan S BT IN SSP-OPJune 2017
Consolidated List of Hardware
SLSL NoNo H/w DescriptionH/w Description ModelModel QtyQty UnitUnit
1 Discharge Valve VSB 33 1 Per Cylinder
2 Pressure Gauge PRESCODEM 1 Per Cylinder
3 Elect. Actuator DEMADEM 1 Per System
4 Manual Actuator CM 16 1 Per System (Centralised)
5 Manual Actuator DEPYM 1 Per System (Modular)
6 Pneumatic Actuator CP 16 1 Per Cylinder
7 Flex. Discharge Hose FRF 33 1 Per Cylinder
8 Flex. Actuation Hose FLEJIC-4 1 Per Cylinder + One
9 Pressure Switch PRESSBOX 1 Per System
10 Check Valve CARF 33 1 Per Cylinder (Centralised)
11 Tee TEJIC 1 Per Cylinder
12 Elbow EQJIC 1 Per System
13 Union UNIJIC 1 Per System (Modular)
![Page 21: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/21.jpg)
Page 23 Kalidasan S BT IN SSP-OPJune 2017
Silent nozzle for Data Centre
Hard Hard disc will damage due to sound level higher disc will damage due to sound level higher thanthan
100 db during a gas 100 db during a gas dischargedischarge
![Page 22: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/22.jpg)
Page 24 Kalidasan S BT IN SSP-OPJune 2017
Integration with FAS
![Page 23: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/23.jpg)
Page 25 Kalidasan S BT IN SSP-OPJune 2017
Discharge Or Dump Test
Optional:
The dump test using N2 gas shall be performed to verify the flow is continuous and that the piping and nozzles are unobstructed
![Page 24: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/24.jpg)
Page 26 Kalidasan S BT IN SSP-OPJune 2017
DO’s AND DON’TsDO’s AND DON’Ts
GAS RELEASE PANEL
DO’s :1. Ensure to keep the panel in auto mode 2. Keep the key in isolate position.
DON’TS :
1. Press manual release unless it is necessary2. Isolate zones unless essential
![Page 25: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/25.jpg)
Page 27 Kalidasan S BT IN SSP-OPJune 2017
DO’s AND DON’TsDO’s AND DON’TsCYLINDER
DON’Ts :1. Remove solenoid from discharge valve2. Pull manual lever unless it is necessary
AFTER FIRE
DON’TS :1. Open Doors / Windows until the fire is Completely put out.2. Enter the protected area until the clean agent has been removed
from the area / the area is ventilated.
![Page 26: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/26.jpg)
Page 28 Kalidasan S BT IN SSP-OPJune 2017
First Aid Measures …
In case of accidental discharge OR
leakage during the installation of
cylinders, the following First Aid
measures should be adopted :
![Page 27: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/27.jpg)
Page 29 Kalidasan S BT IN SSP-OPJune 2017
First Aid Measures …
Inhalation :
Remove the victim to fresh air.
Eye Contact :
Blow away excess chemical quickly.
Flush eyes with warm water for 20 minutes.
![Page 28: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/28.jpg)
Page 30 Kalidasan S BT IN SSP-OPJune 2017
First Aid Measures …
Skin Contact :
For frostbite-immediately flush affected area with warm water warm water for 20 minutes.
Under running water carefully cut away clothing that sticks to damaged skin and remove rest of the garments.
![Page 29: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/29.jpg)
Page 31 Kalidasan S BT IN SSP-OPJune 2017
First Aid Measures …
Ingestion :
Make the victim to drink 300 ml of water, if conscious.
Medical Attention:
Obtain medical attention immediately by calling or visiting a physician.
![Page 30: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/30.jpg)
Page 32 Kalidasan S BT IN SSP-OPJune 2017
Inert Gas Extinguishing Systems
Inert Gas
Basic Product
&
System
Information’s
![Page 31: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/31.jpg)
Page 33 Kalidasan S BT IN SSP-OPJune 2017
Types Inert GasesGas Composition
Nitrogen (N2 ) : N2 -- 100%
Argon (Ar ) : Ar -- 100%
Argonite : Ar – 50%
N2 -- 50%
Inergen : Ar – 40%
N2 -- 52%
![Page 32: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/32.jpg)
Page 34 Kalidasan S BT IN SSP-OPJune 2017
Extinguishing principle
Inert gas systems aim to drop the O2 to between 10% and 14%. Ideally inert gas systems aim for 12.5% O2
![Page 33: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/33.jpg)
Page 35 Kalidasan S BT IN SSP-OPJune 2017
Characteristic of Nitrogen (N2)
Room Ambient After Extinguishing
Oxygen
21%
Nitrogen
79 %
Nitrogen
89%
Oxygen 10-12%
Nitrogen – an Inert Gas
![Page 34: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/34.jpg)
Page 36 Kalidasan S BT IN SSP-OPJune 2017
Inert Gas – Design Concentration
Sinorix N2 Sinorix Ar
IG-100
NFPA 2001 Class A&C -- 36.0 %Class B -- 43.7 %
Filling / Cylinder
17.9 Kgs -- 200 Bar 24.9 Kgs -- 300 Bar
Flooding Factor
0.519 Kgs / M3
IG-01
NFPA 2001 Class A&C -- 36.8 %Class B -- 51.0 %
Filling / Cylinder
28.2 Kgs -- 200 Bar 40.3 Kgs -- 300 Bar
Flooding Factor
0.759 Kgs / M3
![Page 35: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/35.jpg)
Page 37 Kalidasan S BT IN SSP-OPJune 2017
Toxic Level for the Inert Gases
NOAEL : 43 Vol %
LOAEL : 52 Vol %
![Page 36: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/36.jpg)
Page 38 Kalidasan S BT IN SSP-OPJune 2017
Discharge Time for Inert Gases
Maximum Discharge Time
60 Sec
![Page 37: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/37.jpg)
Page 39 Kalidasan S BT IN SSP-OPJune 2017
Working Pressure
System working Pressure 200 / 300 Bar
Pressure afterthe Orifice
60 Bar
![Page 38: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/38.jpg)
Page 40 Kalidasan S BT IN SSP-OPJune 2017
Inert Gas – High & Low Pressure
Sector-valve
Pressure restrictor
High pressure partLow pressure part
![Page 39: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/39.jpg)
Page 41 Kalidasan S BT IN SSP-OPJune 2017
Advantages of N2 & Ar
Zero ODP
Zero GWP
No toxicity to human
Low Cost re-fill
No damage to the equipment
Centralised cylinder location
![Page 40: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/40.jpg)
Page 42 Kalidasan S BT IN SSP-OPJune 2017
Better Gas compared to Pre-mixed gases
Faster re-filling due to local availability
Lower shut down cost
No dependency on specialised suppliers
No expensive license-fees on a Natural gas
![Page 41: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/41.jpg)
Page 43 Kalidasan S BT IN SSP-OPJune 2017
Cylinder Bank Configuration - 11 to 15 Cylinders in a Single Row. One Manifold
![Page 42: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/42.jpg)
Page 44 Kalidasan S BT IN SSP-OPJune 2017
Cylinder Bank Configuration - 22 to 30 Cylinders in Two Rows. One Manifold
![Page 43: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/43.jpg)
Page 45 Kalidasan S BT IN SSP-OPJune 2017
Cylinder Bank Configuration - 34 to 60 Cylinders in Two Rows. Two Manifold
![Page 44: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/44.jpg)
Page 46 Kalidasan S BT IN SSP-OPJune 2017
Cylinder Bank With Selector Valves
![Page 45: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/45.jpg)
Page 47 Kalidasan S BT IN SSP-OPJune 2017
Min. Requirement on Storage Space
Four-line arrangement exclusively offered by Siemens Fire Safety!
Compact cylinder assemblies allow significant reduction of storage space! maximum of 60 cylinders ( 1700 m3 EDP-Room)
![Page 46: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/46.jpg)
Page 48 Kalidasan S BT IN SSP-OPJune 2017
Use of total volume of
storage rooms
is possible only with
four line arrangement!
Storage Example
![Page 47: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/47.jpg)
Page 49 Kalidasan S BT IN SSP-OPJune 2017
All extinguishing systems using Inert gases do need
Over-Pressure Relief openings to avoid complete destruction of
the protected area.
Overpressure Relief Openings
![Page 48: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/48.jpg)
Page 50 Kalidasan S BT IN SSP-OPJune 2017
Approvals of Sinorix N2
VdS, Germany
CNPP French
LPC
Hong Kong FSD and China
![Page 49: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/49.jpg)
Page 51 Kalidasan S BT IN SSP-OPJune 2017
ComparisonChemical Gases:
Rapid discharge
Low extinguishing concentration
Less gas quantity
Lesser cylinder storage space
Lower working pressure
Formation by products
Shorter Pipe network
Inert GasesLonger discharge timeHigh extinguishing concentration
More gas quantityMore cylinder storage spaceVery high working pressure No formation of by productsLonger Pipe network
![Page 50: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/50.jpg)
May 2013Page 52 Version 2.0 Building Technologies / Extinguishing
Overview Sinorix Sinorix 1230Extinguishing
300 m3300 m3 500 m3500 m3 Room volumeRoom volume
Schematic representationSchematic representation
System design Costs as influencing factor
System costs are affected by a number of factors.The ratios can change with increasing room size.
Cos
tsC
osts
System System technologytechnology System System
technologytechnology
Natural Natural GasGas Chemical Chemical
AgentAgent
![Page 51: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/51.jpg)
Page 54 Kalidasan S BT IN SSP-OPJune 2017
5 cyl 10 cyl 15 cyl
Directional Valves
Room 1 Room 2 Room 3
Multi Sector Protection - 42 bar
![Page 52: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/52.jpg)
Page 55 Kalidasan S BT IN SSP-OPJune 2017
Multi-sector system using chemical agents
4
5
6
1
2
3
![Page 53: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/53.jpg)
Page 56 Kalidasan S BT IN SSP-OPJune 2017
Multi-sector system …
![Page 54: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/54.jpg)
Page 57 Kalidasan S BT IN SSP-OPJune 2017
Multi-sector system …
![Page 55: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/55.jpg)
Page 58 Kalidasan S BT IN SSP-OPJune 2017
Multi-sector system …
![Page 56: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/56.jpg)
Page 59 Kalidasan S BT IN SSP-OPJune 2017
Multi-sector system
![Page 57: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/57.jpg)
Page 60 Kalidasan S BT IN SSP-OPJune 2017
Live Discharge - Video
D:\KALIDAS\Lai-30.12.2010\SinorixN2-Ar-CO
![Page 58: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/58.jpg)
Page 61 Kalidasan S BT IN SSP-OPJune 2017
What Makes up a Complete System?
Fire Detection and Alarm System
Control and Gas Release Panel
Agent Cylinders
Hardware
Piping Network and Manifold
Discharge Nozzles
![Page 59: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/59.jpg)
Page 62 Kalidasan S BT IN SSP-OPJune 2017
Why Siemens ?Guaranteed genuine agent and hardwareCredible Source- Perfect audit trail of purchase and sale- Open book approach. Ready for Audit
Design validation and confirmation
An organization with high level of governance and ethical practiceAbility to assist in analyzing the facility and implementation of the system
Contd…
![Page 60: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/60.jpg)
Page 63 Kalidasan S BT IN SSP-OPJune 2017
Our Strength
Full fledged in-house technical / design team
Specialize in design & supply of both chemical and inert gas system
The filling station located at Pondichery has the “ State of the Art Technology” to fill in clean agents offered
Maintain a stock of the agent in bulk quantities for immediate re-filling of discharged systems
![Page 61: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/61.jpg)
Page 64 Kalidasan S BT IN SSP-OPJune 2017
Silent Nozzle for 42bar SinorixTM1230 SystemVdS Approval Certificates
![Page 62: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/62.jpg)
Page 65 Kalidasan S BT IN SSP-OPJune 2017
Q & A
![Page 63: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/63.jpg)
Page 66 Kalidasan S BT IN SSP-OPJune 2017
Further Connect
Kalidasan SSolution Architect
Fire Suppression Systems
M: 96000 48776
![Page 64: Extinguishing Systems Fire Extinguishing Systems For](https://reader030.vdocuments.site/reader030/viewer/2022032322/623197701aa56159bd2c5bd8/html5/thumbnails/64.jpg)
Page 67 Kalidasan S BT IN SSP-OPJune 2017
Thank you