Draiange System Calcualtions
References :
1- The Institute of Plumbing (IOP)
2-American Society of Plumbing
Engineers (ASPE)
3-Uniform Plumbing Code ( UPC)
4- PWA Regulation
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
2/43
All below load values data is taken from Uniform Plumbing Code (UPC)
SBMP 1
FIXTURE No. D.UTOTAL
D.U
Area Drain (4'' trap) 9 8 72
Trench (4'' trap) 11 8 88
Funnel Floor Drain (4'' trap) 2 8 16
Floor Drain (3'' trap) 0 6 0
176
88
5.544
Drain Sump Pumps and Sump Pits Calculations:
5.5 L/s
Total Pipe Length 218.54 m
Equivalent Length 327.81 m
Friction Loss in pipes 400 Pa/m
Static Height 5 m
Output data:
Sump Pump Flow Rate 5.5 l/s
Sump Pump Head 18.2 m
FLOW (L/s)
Input data:Sump Pit Inflow Rate
SUBMERSIBLE DRAIN WATER :
A. SUBMERSIBLE PUMP SERVING PARKING DRAIN
TOTAL
Flow in gpm (Each 2 FU equals 1 gpm)
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
3/43
Sump Pit number: 1
Pump Flow (from submersible pump calculations) 5.54 L/S
Usable Pit Volume:
T min :is the cycle time for the pump in seconds
V req :is the required volume between the start and stop level in Litre
Q : is the incoming flow to the pit (pump flow) in L/s
Recommended starts & stops per hour: 15
T min = 240 seconds
Q req = 5.544 L/s
V req = 332.64 Litre
Pit Dimensions
Pit Length 1200 mm
Pit Width 1200 mm
Pit Area 1.44 m2
Usable Depth 0.231 m
Lowest pipe invert level 0.82 m
Minimum wet level considered for pump operation 0.3 m
Total Pit depth 1.351 m
Pit dimensions: Length (m) x Width (m) x Depth (m) = 1.2 m x 1.2 m x 1.35 m
SUMP PIT SIZING
All below load values data is taken from PWA Vol 3 and Salmson pump recommendations
=
= ×
4
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
4/43
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
5/43
Sump Pit number: 2
Pump Flow (from submersible pump calculations) 7.06 L/S
Usable Pit Volume:
T min :is the cycle time for the pump in seconds
V req :is the required volume between the start and stop level in Litre
Q : is the incoming flow to the pit (pump flow) in L/s
Recommended starts & stops per hour: 15
T min = 240 seconds
Q req = 7.056 L/s
V req = 423.36 Litre
Pit Dimensions
Pit Length 1200 mm
Pit Width 1200 mm
Pit Area 1.44 m2
Usable Depth 0.294 m
Lowest pipe invert level 0.88 m
Minimum wet level considered for pump operation 0.3 m
Total Pit depth 1.474 m
Pit dimensions: Length (m) x Width (m) x Depth (m) = 1.2 m x 1.2 m x 1.47 m
SUMP PIT SIZING
All below load values data is taken from PWA Vol 3 and Salmson pump recommendations
=
= ×
4
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
6/43
All below load values data is taken from Uniform Plumbing Code (UPC)
SBMP 3
FIXTURE No. D.UTOTAL
D.U
Area Drain (4'' trap) 5 8 40
Trench (4'' trap) 18 8 144
Funnel Floor Drain (4'' trap) 3 8 24
Floor Drain (3'' trap) 0 6 0
208
104
6.552
Drain Sump Pumps and Sump Pits Calculations:
6.6 L/s
Total Pipe Length 110.03 m
Equivalent Length 165.045 m
Friction Loss in pipes 400 Pa/m
Static Height 5.15 m
Output data:
Sump Pump Flow Rate 6.6 l/s
Sump Pump Head 11.8 m
FLOW (L/s)
Input data:Sump Pit Inflow Rate
SUBMERSIBLE DRAIN WATER :
A. SUBMERSIBLE PUMP SERVING PARKING DRAIN
TOTAL
Flow in gpm (Each 2 FU equals 1 gpm)
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
7/43
Sump Pit number: 3
Pump Flow (from submersible pump calculations) 6.55 L/S
Usable Pit Volume:
T min :is the cycle time for the pump in seconds
V req :is the required volume between the start and stop level in Litre
Q : is the incoming flow to the pit (pump flow) in L/s
Recommended starts & stops per hour: 15
T min = 240 seconds
Q req = 6.552 L/s
V req = 393.12 Litre
Pit Dimensions
Pit Length 1200 mm
Pit Width 1200 mm
Pit Area 1.44 m2
Usable Depth 0.273 m
Lowest pipe invert level 0.9 m
Minimum wet level considered for pump operation 0.3 m
Total Pit depth 1.473 m
Pit dimensions: Length (m) x Width (m) x Depth (m) = 1.2 m x 1.2 m x 1.47 m
SUMP PIT SIZING
All below load values data is taken from PWA Vol 3 and Salmson pump recommendations
=
= ×
4
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
8/43
All below load values data is taken from Uniform Plumbing Code (UPC)
SBMP 4
`
FIXTURE No. D.UTOTAL
D.U
Area Drain (4'' trap) 8 8 64
Trench (4'' trap) 24 8 192
Funnel Floor Drain (4'' trap) 1 8 8
Floor Drain (3'' trap) 0 6 0
264
132
8.316
Drain Sump Pumps and Sump Pits Calculations:
8.3 L/s
Total Pipe Length 40.47 m
Equivalent Length 60.705 m
Friction Loss in pipes 400 Pa/m
Static Height 5.25 m
Output data:
Sump Pump Flow Rate 8.3 l/s
Sump Pump Head 7.7 m
FLOW (L/s)
Input data:Sump Pit Inflow Rate
SUBMERSIBLE DRAIN WATER :
A. SUBMERSIBLE PUMP SERVING PARKING DRAIN
TOTAL
Flow in gpm (Each 2 FU equals 1 gpm)
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
9/43
Sump Pit number: 4
Pump Flow (from submersible pump calculations) 8.32 L/S
Usable Pit Volume:
T min :is the cycle time for the pump in seconds
V req :is the required volume between the start and stop level in Litre
Q : is the incoming flow to the pit (pump flow) in L/s
Recommended starts & stops per hour: 15
T min = 240 seconds
Q req = 8.316 L/s
V req = 498.96 Litre
Pit Dimensions
Pit Length 1200 mm
Pit Width 1200 mm
Pit Area 1.44 m2
Usable Depth 0.3465 m
Lowest pipe invert level 0.95 m
Minimum wet level considered for pump operation 0.3 m
Total Pit depth 1.5965 m
Pit dimensions: Length (m) x Width (m) x Depth (m) = 1.2 m x 1.2 m 1.60 m
SUMP PIT SIZING
All below load values data is taken from PWA Vol 3 and Salmson pump recommendations
=
= ×
4
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
10/43
All below load values data is taken from BS 12056-2
SBMP 5
FIXTURE No. D.UTOTAL
D.U
WASH BASIN 28 0.3 8.4
SHOWER 0 0.4 0
BATH TUB 0 1.3 0
URINAL 0 0.4 0
DISHASHER 0 0.2 0
WASHING MACHINE 0 1.2 0
KITCHEN SINK 0 1.3 0
WC 36 1.7 61.2
69.6
1
8.34266
Drain Sump Pumps and Sump Pits Calculations:
8.3 L/s
Total Pipe Length 124.71 m
Equivalent Length 187.065 m
Friction Loss in pipes 400 Pa/m
Static Height 10 m
Output data:
Sump Pump Flow Rate 8.3 l/s
Sump Pump Head 17.5 m
BS REFERENCE TABLES
FLOW (L/s)
Input data:
Sump Pit Inflow Rate
SUBMERSIBLE DRAIN WATER :
A. SUBMERSIBLE PUMP SERVING PUBLIC TOILETS
TOTAL
K
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
11/43
Sump Pit number: 5
Pump Flow (from submersible pump calculations) 8.34 L/S
Usable Pit Volume:
T min :is the cycle time for the pump in seconds
V req :is the required volume between the start and stop level in Litre
Q : is the incoming flow to the pit (pump flow) in L/s
Recommended starts & stops per hour: 15
T min = 240 seconds
Q req = 8.3426614 L/s
V req = 500.55969 Litre
Pit Dimensions
Pit Length 1800 mm
Pit Width 1800 mm
Pit Area 3.24 m2
Usable Depth 0.15449 m
Lowest pipe invert level 0.6 m
Clearance below inlet pipe (for 2nd pump operation) 0.2 m
Minimum wet level considered for pump operation 0.3 mTotal Pit depth 1.25449 m
Pit dimensions: Length (m) x Width (m) x Depth (m) = 1.8 m x 1.8 m x 1.25 m
SUMP PIT SIZING
All below load values data is taken from PWA Vol 3 and Salmson pump recommendations
=
= ×
4
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
12/43
All below load values data is taken from BS 12056-2
SBMP 6
FIXTURE No. D.UTOTAL
D.U
WASH BASIN 18 0.3 5.4
SHOWER 2 0.4 0.8
BATH TUB 0 1.3 0
URINAL 0 0.4 0
DISHASHER 0 0.2 0
WASHING MACHINE 0 1.2 0
KITCHEN SINK 0 1.3 0
WC 10 1.7 17
23.2
1
4.81664
Drain Sump Pumps and Sump Pits Calculations:
4.8 L/s
Total Pipe Length 131.2 m
Equivalent Length 196.8 m
Friction Loss in pipes 400 Pa/m
Static Height 10 m
Output data:
Sump Pump Flow Rate 4.8 l/s
Sump Pump Head 17.9 m
BS REFERENCE TABLES
FLOW (L/s)
Input data:
Sump Pit Inflow Rate
SUBMERSIBLE DRAIN WATER :
A. SUBMERSIBLE PUMP SERVING PUBLIC TOILETS
TOTAL
K
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
13/43
Sump Pit number: 6
Pump Flow (from submersible pump calculations) 4.8 L/S
Usable Pit Volume:
T min :is the cycle time for the pump in seconds
V req :is the required volume between the start and stop level in Litre
Q : is the incoming flow to the pit (pump flow) in L/s
Recommended starts & stops per hour: 15
T min = 240 seconds
Q req = 4.8166378 L/s
V req = 288.99827 Litre
Pit Dimensions
Pit Length 1800 mm
Pit Width 1800 mm
Pit Area 3.24 m2
Usable Depth 0.0892 m
Lowest pipe invert level 0.97 m
Clearance below inlet pipe (for 2nd pump operation) 0.2 m
Minimum wet level considered for pump operation 0.3 mTotal Pit depth 1.5592 m
Pit dimensions: Length (m) x Width (m) x Depth (m) = 1.8 m x 1.8 m x 1.56 m
SUMP PIT SIZING
All below load values data is taken from PWA Vol 3 and Salmson pump recommendations
=
= ×
4
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
14/43
All below load values data is taken from BS 12056-2
SBMP 7
FIXTURE No. D.UTOTAL
D.U
WASH BASIN 23 0.3 6.9
SHOWER 2 0.4 0.8
BATH TUB 0 1.3 0
URINAL 4 0.4 1.6
DISHASHER 0 0.2 0
WASHING MACHINE 0 1.2 0
KITCHEN SINK 0 1.3 0
WC 18 1.7 30.6
39.9
1
6.31664
Drain Sump Pumps and Sump Pits Calculations:
6.3 L/s
Total Pipe Length 111.8 m
Equivalent Length 167.7 m
Friction Loss in pipes 400 Pa/m
Static Height 10 m
Output data:
Sump Pump Flow Rate 6.3 l/s
Sump Pump Head 16.8 m
BS REFERENCE TABLES
FLOW (L/s)
Input data:
Sump Pit Inflow Rate
SUBMERSIBLE DRAIN WATER :
A. SUBMERSIBLE PUMP SERVING PUBLIC TOILETS
TOTAL
K
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
15/43
Sump Pit number: 7
Pump Flow (from submersible pump calculations) 6.32 L/S
Usable Pit Volume:
T min :is the cycle time for the pump in seconds
V req :is the required volume between the start and stop level in Litre
Q : is the incoming flow to the pit (pump flow) in L/s
Recommended starts & stops per hour: 15
T min = 240 seconds
Q req = 6.3166447 L/s
V req = 378.99868 Litre
Pit Dimensions
Pit Length 1500 mm
Pit Width 1500 mm
Pit Area 2.25 m2
Usable Depth 0.16844 m
Lowest pipe invert level 0.94 m
Clearance below inlet pipe (for 2nd pump operation) 0.2 m
Minimum wet level considered for pump operation 0.3 mTotal Pit depth 1.60844 m
Pit dimensions: Length (m) x Width (m) x Depth (m) = 1.5 m x 1.5 m x 1.61 m
SUMP PIT SIZING
All below load values data is taken from PWA Vol 3 and Salmson pump recommendations
=
= ×
4
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
16/43
All below load values data is taken from Uniform Plumbing Code (UPC)
SBMP 8
FIXTURE No. D.UTOTAL
D.U
Area Drain (4'' trap) 3 8 24
Trench (4'' trap) 6 8 48
Funnel Floor Drain (4'' trap) 1 8 8
Floor Drain (3'' trap) 0 6 0
80
40
2.52
Drain Sump Pumps and Sump Pits Calculations:
2.5 L/s
Total Pipe Length 186.35 m
Equivalent Length 279.525 m
Friction Loss in pipes 400 Pa/m
Static Height 5 m
Output data:
Sump Pump Flow Rate 2.5 l/s
Sump Pump Head 16.2 m
FLOW (L/s)
Input data:Sump Pit Inflow Rate
SUBMERSIBLE DRAIN WATER :
A. SUBMERSIBLE PUMP SERVING PARKING DRAIN
TOTAL
Flow in gpm (Each 2 FU equals 1 gpm)
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
17/43
Sump Pit number: 8
Pump Flow (from submersible pump calculations) 2.52 L/S
Usable Pit Volume:
T min :is the cycle time for the pump in seconds
V req :is the required volume between the start and stop level in Litre
Q : is the incoming flow to the pit (pump flow) in L/s
Recommended starts & stops per hour: 15
T min = 240 seconds
Q req = 2.52 L/s
V req = 151.2 Litre
Pit Dimensions
Pit Length 1200 mm
Pit Width 1200 mm
Pit Area 1.44 m2
Usable Depth 0.105 m
Lowest pipe invert level 0.93 m
Minimum wet level considered for pump operation 0.3 m
Total Pit depth 1.335 m
Pit dimensions: Length (m) x Width (m) x Depth (m) = 1.2 m x 1.2 m x 1.34 m
SUMP PIT SIZING
All below load values data is taken from PWA Vol 3 and Salmson pump recommendations
=
= ×
4
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
18/43
All below load values data is taken from Uniform Plumbing Code (UPC)
SBMP 9
Drain Sump Pumps and Sump Pits Calculations:
3.2 L/s
Total Pipe Length 222.5 m
Equivalent Length 333.75 m
Friction Loss in pipes 400 Pa/m
Static Height 4.75 m
Output data:
Sump Pump Flow Rate 3.2 l/s
Sump Pump Head 18.1 m
Input data:
Sump Pit Inflow Rate
SUBMERSIBLE DRAIN WATER :
A. SUBMERSIBLE PUMP SERVING PARKING DRAIN
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
19/43
Pump Flow (from submersible pump calculations) 3.15 L/S From ASME A17.1
Usable Pit Volume:
Tmin :is the cycle time for the pump in seconds
V req :is the required volume between the start and stop level in Litre
Q : is the incoming flow to the pit (pump flow) in L/s
Recommended starts & stops per hour: 15
Tmin = 240 seconds
Q req = 3.15 L/s
V req = 189 Litre
Pit Dimensions
Pit Length 600 mm
Pit Width 600 mm
Pit Area 0.36 m2
Usable Depth 0.525 m
Lowest pipe invert level 0.25 mMinimum wet level considered for pump operation 0.3 m
Total Pit depth 1.075 m
Pit dimensions: Length (m) x Width (m) x Depth (m) = 0.6 m x 0.6 m x 1.08 m
SUMP PIT SIZING
All below load values data is taken from PWA Vol 3 and Salmson pump recommendations
ℎ =
= ×
4
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
20/43
All below load values data is taken from Uniform Plumbing Code (UPC)
SBMP 10
Drain Sump Pumps and Sump Pits Calculations:
3.2 L/s
Total Pipe Length 169.67 m
Equivalent Length 254.505 m
Friction Loss in pipes 400 Pa/m
Static Height 4.75 m
Output data:
Sump Pump Flow Rate 3.2 l/s
Sump Pump Head 15 m
Input data:
Sump Pit Inflow Rate
SUBMERSIBLE DRAIN WATER :
A. SUBMERSIBLE PUMP SERVING PARKING DRAIN
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
21/43
Pump Flow (from submersible pump calculations) 3.15 L/S From ASME A17.1
Usable Pit Volume:
Tmin :is the cycle time for the pump in seconds
V req :is the required volume between the start and stop level in Litre
Q : is the incoming flow to the pit (pump flow) in L/s
Recommended starts & stops per hour: 15
Tmin = 240 seconds
Q req = 3.15 L/s
V req = 189 Litre
Pit Dimensions
Pit Length 600 mm
Pit Width 600 mm
Pit Area 0.36 m2
Usable Depth 0.525 m
Lowest pipe invert level 0.25 mMinimum wet level considered for pump operation 0.3 m
Total Pit depth 1.075 m
Pit dimensions: Length (m) x Width (m) x Depth (m) = 0.6 m x 0.6 m x 1.08 m
SUMP PIT SIZING
All below load values data is taken from PWA Vol 3 and Salmson pump recommendations
ℎ =
= ×
4
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
22/43
All below load values data is taken from Uniform Plumbing Code (UPC)
SBMP 11
Drain Sump Pumps and Sump Pits Calculations:
3.2 L/s
Total Pipe Length 35.75 m
Equivalent Length 53.625 m
Friction Loss in pipes 400 Pa/m
Static Height 4.75 m
Output data:
Sump Pump Flow Rate 3.2 l/s
Sump Pump Head 6.9 m
Input data:
Sump Pit Inflow Rate
SUBMERSIBLE DRAIN WATER :
A. SUBMERSIBLE PUMP SERVING PARKING DRAIN
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
23/43
Pump Flow (from submersible pump calculations) 3.15 L/S From ASME A17.1
Usable Pit Volume:
Tmin :is the cycle time for the pump in seconds
V req :is the required volume between the start and stop level in Litre
Q : is the incoming flow to the pit (pump flow) in L/s
Recommended starts & stops per hour: 15
Tmin = 240 seconds
Q req = 3.15 L/s
V req = 189 Litre
Pit Dimensions
Pit Length 600 mm
Pit Width 600 mm
Pit Area 0.36 m2
Usable Depth 0.525 m
Lowest pipe invert level 0.25 mMinimum wet level considered for pump operation 0.3 m
Total Pit depth 1.075 m
Pit dimensions: Length (m) x Width (m) x Depth (m) = 0.6 m x 0.6 m x 1.08 m
SUMP PIT SIZING
All below load values data is taken from PWA Vol 3 and Salmson pump recommendations
ℎ =
= ×
4
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
24/43
All below load values data is taken from Uniform Plumbing Code (UPC)
SBMP 12
Drain Sump Pumps and Sump Pits Calculations:
3.2 L/s
Total Pipe Length 183.62 m
Equivalent Length 275.43 m
Friction Loss in pipes 400 Pa/m
Static Height 4.75 m
Output data:
Sump Pump Flow Rate 3.2 l/s
Sump Pump Head 15.8 m
Input data:
Sump Pit Inflow Rate
SUBMERSIBLE DRAIN WATER :
A. SUBMERSIBLE PUMP SERVING PARKING DRAIN
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
25/43
Pump Flow (from submersible pump calculations) 3.15 L/S From ASME A17.1
Usable Pit Volume:
Tmin :is the cycle time for the pump in seconds
V req :is the required volume between the start and stop level in Litre
Q : is the incoming flow to the pit (pump flow) in L/s
Recommended starts & stops per hour: 15
Tmin = 240 seconds
Q req = 3.15 L/s
V req = 189 Litre
Pit Dimensions
Pit Length 600 mm
Pit Width 600 mm
Pit Area 0.36 m2
Usable Depth 0.525 m
Lowest pipe invert level 0.25 mMinimum wet level considered for pump operation 0.3 m
Total Pit depth 1.075 m
Pit dimensions: Length (m) x Width (m) x Depth (m) = 0.6 m x 0.6 m x 1.08 m
SUMP PIT SIZING
All below load values data is taken from PWA Vol 3 and Salmson pump recommendations
ℎ =
= ×
4
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
26/43
All below load values data is taken from Uniform Plumbing Code (UPC)
SBMP 13
AreaRain fall
IntensityFlow
Cooling Tower Yard And
Chilller Room446 45.6 5.65
2.07
7.72
Drain Sump Pumps and Sump Pits Calculations:
7.7 L/sTotal Pipe Length 185.75 m
Equivalent Length 278.625 m
Friction Loss in pipes 400 Pa/m
Static Height 0 m
Output data:
Sump Pump Flow Rate 7.7 l/s
Sump Pump Head 11.2 m
FLOW (L/s)
Input data:
Sump Pit Inflow Rate
SUBMERSIBLE DRAIN WATER :
A. SUBMERSIBLE PUMP SERVING PARKING DRAIN
Cooling Tower Blow Down
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
27/43
Sump Pit number: 13
Pump Flow (from submersible pump calculations) 7.72 L/S
Usable Pit Volume:
Tmin :is the cycle time for the pump in seconds
V req :is the required volume between the start and stop level in Litre
Q : is the incoming flow to the pit (pump flow) in L/s
Recommended starts & stops per hour: 15
Tmin = 240 seconds
Q req = 7.72 L/s
V req = 463.16 Litre
Pit Dimensions
Pit Length 1200 mm
Pit Width 1200 mm
Pit Area 1.44 m2
Usable Depth 0.32164 mLowest pipe invert level 0.428 m
Minimum wet level considered for pump operation 0.3 m
Total Pit depth 1.04964 m
Pit dimensions: Length (m) x Width (m) x Depth (m) = 1.2 m x 1.2 m x 1.05 m
SUMP PIT SIZING
All below load values data is taken from PWA Vol 3 and Salmson pump recommendations
ℎ =
= ×
4
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
28/43
SWP 1
Drain Sump Pumps and Sump Pits Calculations:
20.0 L/s *
Total Pipe Length 259.58 m
Equivalent Length 389.37 m
Friction Loss in pipes 115 Pa/m
Static Height 10 m
Output data:
Sump Pump Flow Rate 20.0 l/s
Sump Pump Head 14.5 m
*max. allowable flow permitted for SDC-02
Input data:
Sump Pit Inflow Rate
STORM WATER PUMP :
A. STORM WATER PUMP
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
29/43
Water Distribution Calculations
References :
1- International Plumbing Code 2009
(IPC)
2-Kahramaa Regulation
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
30/43
A.Souq waqif domestic water tank (Ref. WT-01)
700 Car
Including
staff
Water Consumption (Public Amenities) : 40 L /Capita/Day
Water Storage Period : 1 Days
Water Consumption Per Day:700*40*1= 28000 L/day
30.00 m3
60.00 m3
Domestic Cold water Tank:
No. of car park:
48-hour Domestic Cold water Tank storage
24-hour Domestic Cold water Tank storage
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
31/43
All below load values data is taken from Inernational Plumbing Code -Table E 103.3 (2) and E 103.3 (3)
friction loss Head
Network Segman Dia. (mm) Act. L (m) Tot. L (m)Flowrate
(L/s)
F. Loss
(Pa/m)
01 TO 02 110 12.30 21.53 7.53 255.00
02 TO 03 110 17.60 30.80 6.44 191.00
03 TO 04 110 7.10 12.43 6.43 190.00
04 TO 05 90 53.70 93.98 4.48 528.00
05 TO 06 63 28.00 49.00 2.08 351.00
06 TO 07 63 34.50 60.38 2.06 345.00
07 TO 08 63 24.80 43.40 2.05 342.00
08 TO 09 63 31.70 55.48 2.03 336.00
09 TO 10 63 28.50 49.88 2.00 327.00
10 TO 11 63 30.00 52.50 1.99 324.00
11 TO 12 63 5.30 9.28 1.97 318.00
12 TO 13 63 12.20 21.35 1.95 312.00
13 TO 14 63 15.10 26.43 1.93 306.00
14 TO 15 32 12.72 22.26 0.46 590.00
15 TO 16 32 33.81 59.17 0.37 394.00
EH-1 10000
Total Friction loss 23.23 m
Static Head = 7.6 m
Residual Pressure Head= 15 m
Total head needed is 45.83 m
4.58 Bar
13133.40
10000.00
2949.45
6661.20
8086.05
23312.00
Water Booster Pump:
A. LOAD VALUES, IN WATER SUPPLY FIXTURE UNITS (wsfu) FOR ALL AREAS
C. Pump Head :
Pump Head
P. Drop (Pa)
5488.88
5882.80
Elec. Heater
2360.75
49618.80
17199.00
20829.38
14842.80
18639.60
16309.13
17010.00
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
32/43
All below data regarding Fixtues and flow (L/hr) for each fixture is taken from Table 10 Chapter 49
of ASHRAE HVAC Applications Handbook (2007 )
Demand Factor : 0.3
Storage Capacity Factor : 2
FIXTURE OCCUPANCYFLOW RATE
(L/H/FIX.)Qty.
Washbasin Public 23 3
Washbasin Private 7.6 1
Possible maximum demand 76.6 Liter
Probable maximum demand 23 LiterTotal Storage Capacity 46 Liter
Manufacturer Selection for E. heater Capacity 50 Liter
Time Required to Heat Cylinder 1 hours
Cold Water Temperature 25 C
Required Hot Water Temperature 60 C
Heating Coil Electrical Load 1 kW
B. Refering to ASHRAE table we will follow data to calculate calorifier
Demand Factor : 0.3
Storage Capacity Factor : 2
FIXTURE OCCUPANCYFLOW RATE
(L/H/FIX.)Qty.
Washbasin Public 23 4
Washbasin Private 7.6 1
Possible maximum demand 99.6 LiterProbable maximum demand 29.88 Liter
Total Storage Capacity 59.76 Liter
Manufacturer Selection for E. heater Capacity 80 Liter
A. Refering to ASHRAE table we will follow data to calculate calorifier
Electrical Hot Water Calculations:
REF. EH-1
REF. EH-2
TOTALS
69.00
76.60
TOTALS
92.00
99.60
7.60
7.60
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
33/43
Time Required to Heat Cylinder 1 hours
Cold Water Temperature 25 C
Required Hot Water Temperature 60 C
Heating Coil Electrical Load 2 kW
C. Refering to ASHRAE table we will follow data to calculate calorifier
Demand Factor : 0.3
Storage Capacity Factor : 2
FIXTURE OCCUPANCYFLOW RATE
(L/H/FIX.)Qty.
Washbasin Public 23 9
Washbasin Private 7.6 4
Possible maximum demand 237.4 Liter
Probable maximum demand 71.22 Liter
Total Storage Capacity 142.44 Liter
Manufacturer Selection for E. heater Capacity 150 Liter
Time Required to Heat Cylinder 1 hours
Cold Water Temperature 25 C
Required Hot Water Temperature 60 C
Heating Coil Electrical Load 3 kW
REF. EH-3
TOTALS
207.00
30.40
237.40
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
34/43
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
35/43
Female Toilet B311
Sanitary Fixture Qty.Fixture unit
FU*
Fixture
Unit
Bathroom Group 1 3.6 3.6
Lavatory 4 2 8
WC 5 5 25
TOTAL 36.6
Note
* Fixture unit based on IPC 2009 Table E103.3(2)
** Pipe sizes are based on PPR-PN16
Male Toilet B312
Sanitary Fixture Qty.Fixture unit
FU*
Fixture
Unit
Bathroom Group 1 3.6 3.6
Lavatory 4 2 8
WC 5 5 25
TOTAL 36.6
Note
* Fixture unit based on IPC 2009 Table E103.3(2)
** Pipe sizes are based on PPR-PN16
Male Toilet B351A
Sanitary Fixture Qty.Fixture unit
FU*
Fixture
Unit
Bathroom Group 2 2.7 5.4
Lavatory 4 2 8Urinal 4 5 20
WC 4 5 20
TOTAL 53.4
Note
* Fixture unit based on IPC 2009 Table E103.3(2)
** Pipe sizes are based on PPR-PN16
Parking Souq Waqif
Basement 2 - Pipe Sizing Calculations
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
36/43
Female Toilet B351B
Sanitary Fixture Qty.Fixture unit
FU*
Fixture
Unit
Bathroom Group 2 3.6 7.2
Lavatory 5 2 10
WC 4 5 20
TOTAL 37.2
Note
* Fixture unit based on IPC 2009 Table E103.3(2)
** Pipe sizes are based on PPR-PN16
Female Toilet B358
Sanitary Fixture Qty.Fixture unit
FU*
Fixture
Unit
Bathroom Group 1 2.7 2.7
Lavatory 3 2 6
WC 1 5 5
TOTAL 13.7
Note
* Fixture unit based on IPC 2009 Table E103.3(2)
** Pipe sizes are based on PPR-PN16
Male Toilet B359
Sanitary Fixture Qty.Fixture unit
FU*
Fixture
Unit
Bathroom Group 1 2.7 2.7
Lavatory 3 2 6
WC 1 5 5TOTAL 13.7
Note
* Fixture unit based on IPC 2009 Table E103.3(2)
** Pipe sizes are based on PPR-PN16
Parking Souq Waqif
Basement 2 - Pipe Sizing Calculations
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
37/43
Female Toilet B369
Sanitary Fixture Qty.Fixture unit
FU*
Fixture
Unit
Bathroom Group 1 2.7 2.7
Lavatory 3 2 6
WC 2 5 10
TOTAL 18.7
Note
* Fixture unit based on IPC 2009 Table E103.3(2)
** Pipe sizes are based on PPR-PN16
Male Toilet B370
Sanitary Fixture Qty.Fixture unit
FU*
Fixture
Unit
Bathroom Group 1 2.7 2.7
Lavatory 3 2 6
WC 2 5 10
TOTAL 18.7
Note
* Fixture unit based on IPC 2009 Table E103.3(2)
** Pipe sizes are based on PPR-PN16
Parking Souq Waqif
Basement 2 - Pipe Sizing Calculations
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
38/43
Male Toilet B202
Sanitary Fixture Qty.Fixture unit
FU*
Fixture
Unit
Bathroom Group 1 2.7 2.7
Lavatory 3 2 6
WC 4 5 20
TOTAL 28.7
Note
* Fixture unit based on IPC 2009 Table E103.3(2)
** Pipe sizes are based on PPR-PN16
Female Toilet B203
Sanitary Fixture Qty.Fixture unit
FU*
Fixture
Unit
Bathroom Group 1 2.7 2.7
Lavatory 3 2 6
WC 4 5 20
TOTAL 28.7
Note
* Fixture unit based on IPC 2009 Table E103.3(2)
** Pipe sizes are based on PPR-PN16
Female Toilet B209
Sanitary Fixture Qty.Fixture unit
FU*
Fixture
Unit
Bathroom Group 1 2.7 2.7Lavatory 4 2 8
WC 6 5 30
TOTAL 40.7
Note
* Fixture unit based on IPC 2009 Table E103.3(2)
** Pipe sizes are based on PPR-PN16
Parking Souq Waqif
Basement 1 - Pipe Sizing Calculations
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
39/43
Male Toilet B210
Sanitary Fixture Qty.Fixture unit
FU*
Fixture
Unit
Bathroom Group 1 2.7 2.7
Lavatory 4 2 8
WC 6 5 30
TOTAL 40.7
Note
* Fixture unit based on IPC 2009 Table E103.3(2)
** Pipe sizes are based on PPR-PN16
Male Toilet B257
Sanitary Fixture Qty.Fixture unit
FU*
Fixture
Unit
Lavatory 4 2 8
Bathroom Group 1 2.7 2.7
WC 3 5 15
TOTAL 25.7
Note
* Fixture unit based on IPC 2009 Table E103.3(2)
** Pipe sizes are based on PPR-PN16
Female Toilet B258
Sanitary Fixture Qty.Fixture unit
FU*
Fixture
Unit
Lavatory 4 2 8Bathroom Group 1 2.7 2.7
WC 3 5 15
TOTAL 25.7
Note
* Fixture unit based on IPC 2009 Table E103.3(2)
** Pipe sizes are based on PPR-PN16
Basement 1 - Pipe Sizing Calculations
Parking Souq Waqif
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
40/43
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
41/43
A PPE NDI X E
TABLE E103.3(2)
LOAD VALUES ASSIGNED TO FIXTURESa
LOAD VALUES, IN WATER SUPPLY FIXTURE UNITS (wsfu)TYPE OF SUPPLY
FIXTURE OCCUPANCY CONTROL Cold Hot Total
Bathroom group Private Flush tank 2.7 1.5 3.6
Bathroom group Private Flush valve 6.0 3.0 8.0
Bathtub Private Faucet 1.0 1.0 1.4
Bathtub Public Faucet 3.0 3.0 4.0
Bidet Private Faucet 1.5 1.5 2.0
Combination fixture Private Faucet 2.25 2.25 3.0
Dishwashing machine Private Automatic - 1.4 1.4
Drinking fountain Offices, etc. 3/8" valve 0.25 - 0.25
Kitchen sink Private Faucet 1.0 1.0 1.4
Kitchen sink Hotel , restaurant Faucet 3.0 3.0 4.0
Laundry trays ( l to 3) Private Faucet 1.0 1.0 1.4
Lavatory Private Faucet 0.5 0.5 0.7
Lavatory Public Faucet 1.5 1.5 2.0
Service sink Offices, etc. Faucet 2.25 2.25 3.0
Shower head Public Mixing valve 3.0 3.0 4.0
Shower head Private Mixing valve 1.0 1.0 1.4
Urinal Public 1" flush valve 10.0 - 10.0
Urinal Public flush valve 5.0 - 5.0
Urinal Public Flush tank 3.0 - 3.0
Washing machine (8 lb) Private Automatic 1.0 1.0 1.4
Washing machine (8 lb) Public Automatic 2.25 2.25 3.0
Washing machine (15Ib) Public Automatic 3.0 3.0 4.0
Water closet Private Flush valve 6.0 - 6.0
Water closet Private Flush tank 2.2 - 2.2
Water closet Public Flush valve 10.0 - 10.0
Water closet Public Flush tank 5.0 - 5.0
Water closet Public or private Flushometer tank 2.0 - 2.0
For SI: 1 inch = 25.4 mm, 1 pound = 0.454 kg.
a. F or fIXtures not listed , loads should be assumed by comparing the fixture to one listed using water in similar quantities and atsimilar rates. The assigned loads for
fIXtures with both hot and cold water supplies are given for separate hot and cold water loads and for total load. The separate hot and cold water loads beingthree-fourths o f the total load for the fixture in each case.
130 2009 INTERNATIONAL PLUMBING CODE®
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
42/43
TABLE E103.3(3)
TABLE FOR ESTIMATING DEMAND
AP PENDI X E
SUPPLY SYSTEMS PREDOMINANTLY FOR FLUSH TANKS SUPPLY SYSTEMS PREDOMINANTLY FOR FLUSH VALVES
Load Demand Load Demand
(Water supply fixture units) (Gallons per minute) (Cubic feet per minute) (Water supply fixture units) (Gallons per minute) (Cubic feet per minute)
1 3.0 0.04104 - - -
2 5.0 0.0684 - - -
3 6.5 0.86892 - - -
4 8.0 1.06944 - - -
5 9.4 1.256592 5 15.0 2.0052
6 10.7 1.430376 6 17.4 2.326032
7 11.8 1.577424 7 19.8 2.646364
8 12.8 1.711104 8 22.2 2.967696
9 13.7 1.831416 9 24.6 3.288528
10 14.6 1.951728 10 27.0 3.60936
11 15.4 2.058672 11 27.8 3.716304
12 16.0 2.13888 12 28 .6 3.823248
13 16.5 2.20572 13 29.4 3.930192
14 17.0 2.27256 14 30.2 4.037136
15 17.5 2.3394 15 31.0 4.14408
16 18.0 2.90624 16 31.8 4.241024
17 18.4 2.459712 17 32.6 4.357968
18 18.8 2.513184 18 33.4 4.464912
19 19.2 2.566656 19 34.2 4.571856
20 19.6 2.620128 20 35.0 4.6788
25 21.5 2.87412 25 38.0 5.07984
30 23.3 3.114744 30 42.0 5.61356
35 24.9 3.328632 35 44.0 5.88192
40 26.3 3.515784 40 46.0 6.14928
45 27 .7 3.702936 45 48.0 6.41664
50 29.1 3.890088 50 50.0 6.684
60 32.0 4.27776 60 54.0 7.21872
70 35.0 4.6788 70 58.0 7.75344
80 38.0 5.07984 80 61.2 8.181216
90 41.0 5.48088 90 64.3 8.595624
100 43.5 5.81508 100 67.5 9.0234
120 48 .0 6.41664 120 73.0 9.75864
140 52.5 7.0182 140 77.0 10.29336
160 57.0 7.61976 160 81.0 10.82808
180 61.0 8.15448 180 85.5 11.42964
200 65.0 8.6892 200 90.0 12.0312
225 70.0 9.3576 225 95.5 12.76644
250 75.0 10.026 250 101.0 13.50168
(continued)
2009 INTERNATIONAL PLUMBING CODE® 131
-
8/18/2019 Mechanical Calculations- Plumbing.pdf
43/43
APPENDI X E
TABLE E103.3(3)-continuedTABLE FOR ESTIMATING DEMAND
SUPPLY SYSTEMS PREDOMINANTLY FOR FLUSH TANKS SUPPLY SYSTEMS PREDOMINANTLY FOR FLUSH VALVES
Load Demand Load Demand
(Water supply fixture units) (Gallons per minute) (Cubic feet per minute) (Water supply fixture units) (Gallons per minute) (Cubic feet per minute)
275 80.0 10.6944 275 104.5 13.96956
300 85.0 11.3628 300 108.0 14.43744
400 105.0 14.0364 400 127.0 16.97736
500 124.0 16.57632 500 143.0 19.11624
750 170.0 22.7256 750 177.0 23.66136
1,000 208.0 27.80544 1,000 208.0 27.80544
1,250 239.0 31.94952 1,250 239.0 31.94952
1,500 269.0 35.95992 1,500 269.0 35.95992
1,750 297.0 39.70296 1,750 297.0 39.70296
2,000 325.0 43.446 2,000 325.0 43.446
2,500 380 .0 50.7984 2,500 380 .0 50.7984
3,000 433.0 57.88344 3,000 433.0 57.88344
4,000 525.0 70.182 4,000 525.0 70.182
5,000 593.0 79.27224 5,000 593.0 79.27224