    Draiange System Calcualtions

    References :

    1- The Institute of Plumbing (IOP)

    2-American Society of Plumbing

    Engineers (ASPE)

    3-Uniform Plumbing Code ( UPC)

    4- PWA Regulation

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    2/43

    All below load values data is taken from Uniform Plumbing Code (UPC)

    SBMP 1

    FIXTURE No. D.UTOTAL

    D.U

     Area Drain (4'' trap) 9 8 72

    Trench (4'' trap) 11 8 88

    Funnel Floor Drain (4'' trap) 2 8 16

    Floor Drain (3'' trap) 0 6 0

    176

    88

    5.544

    Drain Sump Pumps and Sump Pits Calculations:

    5.5 L/s

    Total Pipe Length 218.54 m

    Equivalent Length 327.81 m

    Friction Loss in pipes 400 Pa/m

    Static Height 5 m

    Output data:

    Sump Pump Flow Rate 5.5 l/s

    Sump Pump Head 18.2 m

    FLOW (L/s)

    Input data:Sump Pit Inflow Rate

     SUBMERSIBLE DRAIN WATER :

    A. SUBMERSIBLE PUMP SERVING PARKING DRAIN

    TOTAL

    Flow in gpm (Each 2 FU equals 1 gpm)

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    3/43

    Sump Pit number: 1

    Pump Flow (from submersible pump calculations) 5.54 L/S

    Usable Pit Volume:

    T min  :is the cycle time for the pump in seconds

    V req  :is the required volume between the start and stop level in Litre

    Q   : is the incoming flow to the pit (pump flow) in L/s

    Recommended starts & stops per hour: 15

    T min = 240 seconds

    Q req = 5.544 L/s

    V req  = 332.64 Litre

    Pit Dimensions

    Pit Length 1200 mm

    Pit Width 1200 mm

    Pit Area 1.44 m2

    Usable Depth 0.231 m

    Lowest pipe invert level 0.82 m

    Minimum wet level considered for pump operation 0.3 m

    Total Pit depth 1.351 m

    Pit dimensions: Length (m) x Width (m) x Depth (m) = 1.2 m x 1.2 m x 1.35 m

    SUMP PIT SIZING

    All below load values data is taken from PWA Vol 3 and Salmson pump recommendations

       =

       

    =  × 

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    4/43

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    5/43

    Sump Pit number: 2

    Pump Flow (from submersible pump calculations) 7.06 L/S

    Usable Pit Volume:

    T min  :is the cycle time for the pump in seconds

    V req  :is the required volume between the start and stop level in Litre

    Q   : is the incoming flow to the pit (pump flow) in L/s

    Recommended starts & stops per hour: 15

    T min = 240 seconds

    Q req = 7.056 L/s

    V req  = 423.36 Litre

    Pit Dimensions

    Pit Length 1200 mm

    Pit Width 1200 mm

    Pit Area 1.44 m2

    Usable Depth 0.294 m

    Lowest pipe invert level 0.88 m

    Minimum wet level considered for pump operation 0.3 m

    Total Pit depth 1.474 m

    Pit dimensions: Length (m) x Width (m) x Depth (m) = 1.2 m x 1.2 m x 1.47 m

    SUMP PIT SIZING

    All below load values data is taken from PWA Vol 3 and Salmson pump recommendations

       =

       

    =  × 

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    6/43

    All below load values data is taken from Uniform Plumbing Code (UPC)

    SBMP 3

    FIXTURE No. D.UTOTAL

    D.U

     Area Drain (4'' trap) 5 8 40

    Trench (4'' trap) 18 8 144

    Funnel Floor Drain (4'' trap) 3 8 24

    Floor Drain (3'' trap) 0 6 0

    208

    104

    6.552

    Drain Sump Pumps and Sump Pits Calculations:

    6.6 L/s

    Total Pipe Length 110.03 m

    Equivalent Length 165.045 m

    Friction Loss in pipes 400 Pa/m

    Static Height 5.15 m

    Output data:

    Sump Pump Flow Rate 6.6 l/s

    Sump Pump Head 11.8 m

    FLOW (L/s)

    Input data:Sump Pit Inflow Rate

     SUBMERSIBLE DRAIN WATER :

    A. SUBMERSIBLE PUMP SERVING PARKING DRAIN

    TOTAL

    Flow in gpm (Each 2 FU equals 1 gpm)

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    7/43

    Sump Pit number: 3

    Pump Flow (from submersible pump calculations) 6.55 L/S

    Usable Pit Volume:

    T min  :is the cycle time for the pump in seconds

    V req  :is the required volume between the start and stop level in Litre

    Q   : is the incoming flow to the pit (pump flow) in L/s

    Recommended starts & stops per hour: 15

    T min = 240 seconds

    Q req = 6.552 L/s

    V req  = 393.12 Litre

    Pit Dimensions

    Pit Length 1200 mm

    Pit Width 1200 mm

    Pit Area 1.44 m2

    Usable Depth 0.273 m

    Lowest pipe invert level 0.9 m

    Minimum wet level considered for pump operation 0.3 m

    Total Pit depth 1.473 m

    Pit dimensions: Length (m) x Width (m) x Depth (m) = 1.2 m x 1.2 m x 1.47 m

    SUMP PIT SIZING

    All below load values data is taken from PWA Vol 3 and Salmson pump recommendations

       =

       

    =  × 

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    8/43

    All below load values data is taken from Uniform Plumbing Code (UPC)

    SBMP 4

    `

    FIXTURE No. D.UTOTAL

    D.U

     Area Drain (4'' trap) 8 8 64

    Trench (4'' trap) 24 8 192

    Funnel Floor Drain (4'' trap) 1 8 8

    Floor Drain (3'' trap) 0 6 0

    264

    132

    8.316

    Drain Sump Pumps and Sump Pits Calculations:

    8.3 L/s

    Total Pipe Length 40.47 m

    Equivalent Length 60.705 m

    Friction Loss in pipes 400 Pa/m

    Static Height 5.25 m

    Output data:

    Sump Pump Flow Rate 8.3 l/s

    Sump Pump Head 7.7 m

    FLOW (L/s)

    Input data:Sump Pit Inflow Rate

     SUBMERSIBLE DRAIN WATER :

    A. SUBMERSIBLE PUMP SERVING PARKING DRAIN

    TOTAL

    Flow in gpm (Each 2 FU equals 1 gpm)

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    9/43

    Sump Pit number: 4

    Pump Flow (from submersible pump calculations) 8.32 L/S

    Usable Pit Volume:

    T min  :is the cycle time for the pump in seconds

    V req  :is the required volume between the start and stop level in Litre

    Q   : is the incoming flow to the pit (pump flow) in L/s

    Recommended starts & stops per hour: 15

    T min = 240 seconds

    Q req = 8.316 L/s

    V req  = 498.96 Litre

    Pit Dimensions

    Pit Length 1200 mm

    Pit Width 1200 mm

    Pit Area 1.44 m2

    Usable Depth 0.3465 m

    Lowest pipe invert level 0.95 m

    Minimum wet level considered for pump operation 0.3 m

    Total Pit depth 1.5965 m

    Pit dimensions: Length (m) x Width (m) x Depth (m) = 1.2 m x 1.2 m 1.60 m

    SUMP PIT SIZING

    All below load values data is taken from PWA Vol 3 and Salmson pump recommendations

       =

       

    =  × 

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    10/43

    All below load values data is taken from BS 12056-2

    SBMP 5

    FIXTURE No. D.UTOTAL

    D.U

    WASH BASIN 28 0.3 8.4

    SHOWER 0 0.4 0

    BATH TUB 0 1.3 0

    URINAL 0 0.4 0

    DISHASHER 0 0.2 0

    WASHING MACHINE 0 1.2 0

    KITCHEN SINK 0 1.3 0

    WC 36 1.7 61.2

    69.6

    1

    8.34266

    Drain Sump Pumps and Sump Pits Calculations:

    8.3 L/s

    Total Pipe Length 124.71 m

    Equivalent Length 187.065 m

    Friction Loss in pipes 400 Pa/m

    Static Height 10 m

    Output data:

    Sump Pump Flow Rate 8.3 l/s

    Sump Pump Head 17.5 m

    BS REFERENCE TABLES

    FLOW (L/s)

    Input data:

    Sump Pit Inflow Rate

     SUBMERSIBLE DRAIN WATER :

    A. SUBMERSIBLE PUMP SERVING PUBLIC TOILETS

    TOTAL

    K

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    11/43

    Sump Pit number: 5

    Pump Flow (from submersible pump calculations) 8.34 L/S

    Usable Pit Volume:

    T min  :is the cycle time for the pump in seconds

    V req  :is the required volume between the start and stop level in Litre

    Q   : is the incoming flow to the pit (pump flow) in L/s

    Recommended starts & stops per hour: 15

    T min = 240 seconds

    Q req = 8.3426614 L/s

    V req  = 500.55969 Litre

    Pit Dimensions

    Pit Length 1800 mm

    Pit Width 1800 mm

    Pit Area 3.24 m2

    Usable Depth 0.15449 m

    Lowest pipe invert level 0.6 m

    Clearance below inlet pipe (for 2nd pump operation) 0.2 m

    Minimum wet level considered for pump operation 0.3 mTotal Pit depth 1.25449 m

    Pit dimensions: Length (m) x Width (m) x Depth (m) = 1.8 m x 1.8 m x 1.25 m

    SUMP PIT SIZING

    All below load values data is taken from PWA Vol 3 and Salmson pump recommendations

       =

       

    =  × 

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    12/43

    All below load values data is taken from BS 12056-2

    SBMP 6

    FIXTURE No. D.UTOTAL

    D.U

    WASH BASIN 18 0.3 5.4

    SHOWER 2 0.4 0.8

    BATH TUB 0 1.3 0

    URINAL 0 0.4 0

    DISHASHER 0 0.2 0

    WASHING MACHINE 0 1.2 0

    KITCHEN SINK 0 1.3 0

    WC 10 1.7 17

    23.2

    1

    4.81664

    Drain Sump Pumps and Sump Pits Calculations:

    4.8 L/s

    Total Pipe Length 131.2 m

    Equivalent Length 196.8 m

    Friction Loss in pipes 400 Pa/m

    Static Height 10 m

    Output data:

    Sump Pump Flow Rate 4.8 l/s

    Sump Pump Head 17.9 m

    BS REFERENCE TABLES

    FLOW (L/s)

    Input data:

    Sump Pit Inflow Rate

     SUBMERSIBLE DRAIN WATER :

    A. SUBMERSIBLE PUMP SERVING PUBLIC TOILETS

    TOTAL

    K

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    13/43

    Sump Pit number: 6

    Pump Flow (from submersible pump calculations) 4.8 L/S

    Usable Pit Volume:

    T min  :is the cycle time for the pump in seconds

    V req  :is the required volume between the start and stop level in Litre

    Q   : is the incoming flow to the pit (pump flow) in L/s

    Recommended starts & stops per hour: 15

    T min = 240 seconds

    Q req = 4.8166378 L/s

    V req  = 288.99827 Litre

    Pit Dimensions

    Pit Length 1800 mm

    Pit Width 1800 mm

    Pit Area 3.24 m2

    Usable Depth 0.0892 m

    Lowest pipe invert level 0.97 m

    Clearance below inlet pipe (for 2nd pump operation) 0.2 m

    Minimum wet level considered for pump operation 0.3 mTotal Pit depth 1.5592 m

    Pit dimensions: Length (m) x Width (m) x Depth (m) = 1.8 m x 1.8 m x 1.56 m

    SUMP PIT SIZING

    All below load values data is taken from PWA Vol 3 and Salmson pump recommendations

       =

       

    =  × 

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    14/43

    All below load values data is taken from BS 12056-2

    SBMP 7

    FIXTURE No. D.UTOTAL

    D.U

    WASH BASIN 23 0.3 6.9

    SHOWER 2 0.4 0.8

    BATH TUB 0 1.3 0

    URINAL 4 0.4 1.6

    DISHASHER 0 0.2 0

    WASHING MACHINE 0 1.2 0

    KITCHEN SINK 0 1.3 0

    WC 18 1.7 30.6

    39.9

    1

    6.31664

    Drain Sump Pumps and Sump Pits Calculations:

    6.3 L/s

    Total Pipe Length 111.8 m

    Equivalent Length 167.7 m

    Friction Loss in pipes 400 Pa/m

    Static Height 10 m

    Output data:

    Sump Pump Flow Rate 6.3 l/s

    Sump Pump Head 16.8 m

    BS REFERENCE TABLES

    FLOW (L/s)

    Input data:

    Sump Pit Inflow Rate

     SUBMERSIBLE DRAIN WATER :

    A. SUBMERSIBLE PUMP SERVING PUBLIC TOILETS

    TOTAL

    K

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    15/43

    Sump Pit number: 7

    Pump Flow (from submersible pump calculations) 6.32 L/S

    Usable Pit Volume:

    T min  :is the cycle time for the pump in seconds

    V req  :is the required volume between the start and stop level in Litre

    Q   : is the incoming flow to the pit (pump flow) in L/s

    Recommended starts & stops per hour: 15

    T min = 240 seconds

    Q req = 6.3166447 L/s

    V req  = 378.99868 Litre

    Pit Dimensions

    Pit Length 1500 mm

    Pit Width 1500 mm

    Pit Area 2.25 m2

    Usable Depth 0.16844 m

    Lowest pipe invert level 0.94 m

    Clearance below inlet pipe (for 2nd pump operation) 0.2 m

    Minimum wet level considered for pump operation 0.3 mTotal Pit depth 1.60844 m

    Pit dimensions: Length (m) x Width (m) x Depth (m) = 1.5 m x 1.5 m x 1.61 m

    SUMP PIT SIZING

    All below load values data is taken from PWA Vol 3 and Salmson pump recommendations

       =

       

    =  × 

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    16/43

    All below load values data is taken from Uniform Plumbing Code (UPC)

    SBMP 8

    FIXTURE No. D.UTOTAL

    D.U

     Area Drain (4'' trap) 3 8 24

    Trench (4'' trap) 6 8 48

    Funnel Floor Drain (4'' trap) 1 8 8

    Floor Drain (3'' trap) 0 6 0

    80

    40

    2.52

    Drain Sump Pumps and Sump Pits Calculations:

    2.5 L/s

    Total Pipe Length 186.35 m

    Equivalent Length 279.525 m

    Friction Loss in pipes 400 Pa/m

    Static Height 5 m

    Output data:

    Sump Pump Flow Rate 2.5 l/s

    Sump Pump Head 16.2 m

    FLOW (L/s)

    Input data:Sump Pit Inflow Rate

     SUBMERSIBLE DRAIN WATER :

    A. SUBMERSIBLE PUMP SERVING PARKING DRAIN

    TOTAL

    Flow in gpm (Each 2 FU equals 1 gpm)

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    17/43

    Sump Pit number: 8

    Pump Flow (from submersible pump calculations) 2.52 L/S

    Usable Pit Volume:

    T min  :is the cycle time for the pump in seconds

    V req  :is the required volume between the start and stop level in Litre

    Q   : is the incoming flow to the pit (pump flow) in L/s

    Recommended starts & stops per hour: 15

    T min = 240 seconds

    Q req = 2.52 L/s

    V req  = 151.2 Litre

    Pit Dimensions

    Pit Length 1200 mm

    Pit Width 1200 mm

    Pit Area 1.44 m2

    Usable Depth 0.105 m

    Lowest pipe invert level 0.93 m

    Minimum wet level considered for pump operation 0.3 m

    Total Pit depth 1.335 m

    Pit dimensions: Length (m) x Width (m) x Depth (m) = 1.2 m x 1.2 m x 1.34 m

    SUMP PIT SIZING

    All below load values data is taken from PWA Vol 3 and Salmson pump recommendations

       =

       

    =  × 

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    18/43

    All below load values data is taken from Uniform Plumbing Code (UPC)

    SBMP 9

    Drain Sump Pumps and Sump Pits Calculations:

    3.2 L/s

    Total Pipe Length 222.5 m

    Equivalent Length 333.75 m

    Friction Loss in pipes 400 Pa/m

    Static Height 4.75 m

    Output data:

    Sump Pump Flow Rate 3.2 l/s

    Sump Pump Head 18.1 m

    Input data:

    Sump Pit Inflow Rate

     SUBMERSIBLE DRAIN WATER :

    A. SUBMERSIBLE PUMP SERVING PARKING DRAIN

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    19/43

    Pump Flow (from submersible pump calculations) 3.15 L/S From ASME A17.1

    Usable Pit Volume:

    Tmin  :is the cycle time for the pump in seconds

    V req  :is the required volume between the start and stop level in Litre

    Q   : is the incoming flow to the pit (pump flow) in L/s

    Recommended starts & stops per hour: 15

    Tmin = 240 seconds

    Q req = 3.15 L/s

    V req  = 189 Litre

    Pit Dimensions

    Pit Length 600 mm

    Pit Width 600 mm

    Pit Area 0.36 m2

    Usable Depth 0.525 m

    Lowest pipe invert level 0.25 mMinimum wet level considered for pump operation 0.3 m

    Total Pit depth 1.075 m

    Pit dimensions: Length (m) x Width (m) x Depth (m) = 0.6 m x 0.6 m x 1.08 m

    SUMP PIT SIZING

     All below load values data is taken from PWA Vol 3 and Salmson pump recommendations

     ℎ  =

       

    =  ×

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    20/43

    All below load values data is taken from Uniform Plumbing Code (UPC)

    SBMP 10

    Drain Sump Pumps and Sump Pits Calculations:

    3.2 L/s

    Total Pipe Length 169.67 m

    Equivalent Length 254.505 m

    Friction Loss in pipes 400 Pa/m

    Static Height 4.75 m

    Output data:

    Sump Pump Flow Rate 3.2 l/s

    Sump Pump Head 15 m

    Input data:

    Sump Pit Inflow Rate

     SUBMERSIBLE DRAIN WATER :

    A. SUBMERSIBLE PUMP SERVING PARKING DRAIN

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    21/43

    Pump Flow (from submersible pump calculations) 3.15 L/S From ASME A17.1

    Usable Pit Volume:

    Tmin  :is the cycle time for the pump in seconds

    V req  :is the required volume between the start and stop level in Litre

    Q   : is the incoming flow to the pit (pump flow) in L/s

    Recommended starts & stops per hour: 15

    Tmin = 240 seconds

    Q req = 3.15 L/s

    V req  = 189 Litre

    Pit Dimensions

    Pit Length 600 mm

    Pit Width 600 mm

    Pit Area 0.36 m2

    Usable Depth 0.525 m

    Lowest pipe invert level 0.25 mMinimum wet level considered for pump operation 0.3 m

    Total Pit depth 1.075 m

    Pit dimensions: Length (m) x Width (m) x Depth (m) = 0.6 m x 0.6 m x 1.08 m

    SUMP PIT SIZING

     All below load values data is taken from PWA Vol 3 and Salmson pump recommendations

     ℎ  =

       

    =  ×

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    22/43

    All below load values data is taken from Uniform Plumbing Code (UPC)

    SBMP 11

    Drain Sump Pumps and Sump Pits Calculations:

    3.2 L/s

    Total Pipe Length 35.75 m

    Equivalent Length 53.625 m

    Friction Loss in pipes 400 Pa/m

    Static Height 4.75 m

    Output data:

    Sump Pump Flow Rate 3.2 l/s

    Sump Pump Head 6.9 m

    Input data:

    Sump Pit Inflow Rate

     SUBMERSIBLE DRAIN WATER :

    A. SUBMERSIBLE PUMP SERVING PARKING DRAIN

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    23/43

    Pump Flow (from submersible pump calculations) 3.15 L/S From ASME A17.1

    Usable Pit Volume:

    Tmin  :is the cycle time for the pump in seconds

    V req  :is the required volume between the start and stop level in Litre

    Q   : is the incoming flow to the pit (pump flow) in L/s

    Recommended starts & stops per hour: 15

    Tmin = 240 seconds

    Q req = 3.15 L/s

    V req  = 189 Litre

    Pit Dimensions

    Pit Length 600 mm

    Pit Width 600 mm

    Pit Area 0.36 m2

    Usable Depth 0.525 m

    Lowest pipe invert level 0.25 mMinimum wet level considered for pump operation 0.3 m

    Total Pit depth 1.075 m

    Pit dimensions: Length (m) x Width (m) x Depth (m) = 0.6 m x 0.6 m x 1.08 m

    SUMP PIT SIZING

     All below load values data is taken from PWA Vol 3 and Salmson pump recommendations

     ℎ  =

       

    =  ×

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    24/43

    All below load values data is taken from Uniform Plumbing Code (UPC)

    SBMP 12

    Drain Sump Pumps and Sump Pits Calculations:

    3.2 L/s

    Total Pipe Length 183.62 m

    Equivalent Length 275.43 m

    Friction Loss in pipes 400 Pa/m

    Static Height 4.75 m

    Output data:

    Sump Pump Flow Rate 3.2 l/s

    Sump Pump Head 15.8 m

    Input data:

    Sump Pit Inflow Rate

     SUBMERSIBLE DRAIN WATER :

    A. SUBMERSIBLE PUMP SERVING PARKING DRAIN

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    25/43

    Pump Flow (from submersible pump calculations) 3.15 L/S From ASME A17.1

    Usable Pit Volume:

    Tmin  :is the cycle time for the pump in seconds

    V req  :is the required volume between the start and stop level in Litre

    Q   : is the incoming flow to the pit (pump flow) in L/s

    Recommended starts & stops per hour: 15

    Tmin = 240 seconds

    Q req = 3.15 L/s

    V req  = 189 Litre

    Pit Dimensions

    Pit Length 600 mm

    Pit Width 600 mm

    Pit Area 0.36 m2

    Usable Depth 0.525 m

    Lowest pipe invert level 0.25 mMinimum wet level considered for pump operation 0.3 m

    Total Pit depth 1.075 m

    Pit dimensions: Length (m) x Width (m) x Depth (m) = 0.6 m x 0.6 m x 1.08 m

    SUMP PIT SIZING

     All below load values data is taken from PWA Vol 3 and Salmson pump recommendations

     ℎ  =

       

    =  ×

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    26/43

     All below load values data is taken from Uniform Plumbing Code (UPC)

    SBMP 13

     AreaRain fall

    IntensityFlow

    Cooling Tower Yard And

    Chilller Room446 45.6 5.65

    2.07

    7.72

    Drain Sump Pumps and Sump Pits Calculations:

    7.7 L/sTotal Pipe Length 185.75 m

    Equivalent Length 278.625 m

    Friction Loss in pipes 400 Pa/m

    Static Height 0 m

    Output data:

    Sump Pump Flow Rate 7.7 l/s

    Sump Pump Head 11.2 m

    FLOW (L/s)

    Input data:

    Sump Pit Inflow Rate

     SUBMERSIBLE DRAIN WATER :

     A. SUBMERSIBLE PUMP SERVING PARKING DRAIN

     Cooling Tower Blow Down

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    27/43

    Sump Pit number: 13

    Pump Flow (from submersible pump calculations) 7.72 L/S

    Usable Pit Volume:

    Tmin  :is the cycle time for the pump in seconds

    V req  :is the required volume between the start and stop level in Litre

    Q   : is the incoming flow to the pit (pump flow) in L/s

    Recommended starts & stops per hour: 15

    Tmin = 240 seconds

    Q req = 7.72 L/s

    V req  = 463.16 Litre

    Pit Dimensions

    Pit Length 1200 mm

    Pit Width 1200 mm

    Pit Area 1.44 m2

    Usable Depth 0.32164 mLowest pipe invert level 0.428 m

    Minimum wet level considered for pump operation 0.3 m

    Total Pit depth 1.04964 m

    Pit dimensions: Length (m) x Width (m) x Depth (m) = 1.2 m x 1.2 m x 1.05 m

    SUMP PIT SIZING

     All below load values data is taken from PWA Vol 3 and Salmson pump recommendations

     ℎ  =

       

    =  ×

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    28/43

    SWP 1

    Drain Sump Pumps and Sump Pits Calculations:

    20.0 L/s *

    Total Pipe Length 259.58 m

    Equivalent Length 389.37 m

    Friction Loss in pipes 115 Pa/m

    Static Height 10 m

    Output data:

    Sump Pump Flow Rate 20.0 l/s

    Sump Pump Head 14.5 m

    *max. allowable flow permitted for SDC-02

    Input data:

    Sump Pit Inflow Rate

    STORM WATER PUMP :

    A. STORM WATER PUMP

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    29/43

    Water Distribution Calculations

    References :

    1- International Plumbing Code 2009 

    (IPC)

    2-Kahramaa Regulation

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    30/43

    A.Souq waqif domestic water tank (Ref. WT-01)

    700 Car

    Including

    staff 

    Water Consumption (Public Amenities) : 40 L /Capita/Day

    Water Storage Period  : 1 Days

    Water Consumption Per Day:700*40*1= 28000 L/day

    30.00 m3

    60.00 m3

    Domestic Cold water Tank:

    No. of car park:

    48-hour Domestic Cold water Tank storage

    24-hour Domestic Cold water Tank storage

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    31/43

    All below load values data is taken from Inernational Plumbing Code -Table E 103.3 (2) and E 103.3 (3)

     friction loss Head 

     Network Segman Dia. (mm) Act. L (m) Tot. L (m)Flowrate

    (L/s)

    F. Loss

    (Pa/m)

    01 TO 02 110 12.30 21.53 7.53 255.00

    02 TO 03 110 17.60 30.80 6.44 191.00

    03 TO 04 110 7.10 12.43 6.43 190.00

    04 TO 05 90 53.70 93.98 4.48 528.00

    05 TO 06 63 28.00 49.00 2.08 351.00

    06 TO 07 63 34.50 60.38 2.06 345.00

    07 TO 08 63 24.80 43.40 2.05 342.00

    08 TO 09 63 31.70 55.48 2.03 336.00

    09 TO 10 63 28.50 49.88 2.00 327.00

    10 TO 11 63 30.00 52.50 1.99 324.00

    11 TO 12 63 5.30 9.28 1.97 318.00

    12 TO 13 63 12.20 21.35 1.95 312.00

    13 TO 14 63 15.10 26.43 1.93 306.00

    14 TO 15 32 12.72 22.26 0.46 590.00

    15 TO 16 32 33.81 59.17 0.37 394.00

    EH-1 10000

    Total Friction loss 23.23 m

    Static Head = 7.6 m

    Residual Pressure Head= 15 m

    Total head needed is 45.83 m

    4.58 Bar

    13133.40

    10000.00

    2949.45

    6661.20

    8086.05

    23312.00

    Water Booster Pump:

    A. LOAD VALUES, IN WATER SUPPLY FIXTURE UNITS (wsfu) FOR ALL AREAS

    C. Pump Head :

    Pump Head

    P. Drop (Pa)

    5488.88

    5882.80

    Elec. Heater

    2360.75

    49618.80

    17199.00

    20829.38

    14842.80

    18639.60

    16309.13

    17010.00

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    32/43

    All below data regarding Fixtues and flow (L/hr) for each fixture is taken from Table 10 Chapter 49

    of ASHRAE HVAC Applications Handbook (2007 )

    Demand Factor : 0.3

    Storage Capacity Factor : 2

     FIXTURE OCCUPANCYFLOW RATE

    (L/H/FIX.)Qty.

    Washbasin Public 23 3

    Washbasin Private 7.6 1

    Possible maximum demand 76.6 Liter

    Probable maximum demand 23 LiterTotal Storage Capacity 46 Liter

    Manufacturer Selection for E. heater Capacity  50 Liter 

    Time Required to Heat Cylinder 1 hours

    Cold Water Temperature 25 C

    Required Hot Water Temperature 60 C

    Heating Coil Electrical Load  1 kW 

    B. Refering to ASHRAE table we will follow data to calculate calorifier

    Demand Factor : 0.3

    Storage Capacity Factor : 2

     FIXTURE OCCUPANCYFLOW RATE

    (L/H/FIX.)Qty.

    Washbasin Public 23 4

    Washbasin Private 7.6 1

    Possible maximum demand 99.6 LiterProbable maximum demand 29.88 Liter

    Total Storage Capacity 59.76 Liter

    Manufacturer Selection for E. heater Capacity  80 Liter 

    A. Refering to ASHRAE table we will follow data to calculate calorifier

    Electrical Hot Water Calculations:

    REF. EH-1

    REF. EH-2

    TOTALS

    69.00

    76.60

    TOTALS

    92.00

    99.60

    7.60

    7.60

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    33/43

    Time Required to Heat Cylinder 1 hours

    Cold Water Temperature 25 C

    Required Hot Water Temperature 60 C

    Heating Coil Electrical Load  2 kW 

    C. Refering to ASHRAE table we will follow data to calculate calorifier

    Demand Factor : 0.3

    Storage Capacity Factor : 2

     FIXTURE OCCUPANCYFLOW RATE

    (L/H/FIX.)Qty.

    Washbasin Public 23 9

    Washbasin Private 7.6 4

    Possible maximum demand 237.4 Liter

    Probable maximum demand 71.22 Liter

    Total Storage Capacity 142.44 Liter

    Manufacturer Selection for E. heater Capacity  150 Liter 

    Time Required to Heat Cylinder 1 hours

    Cold Water Temperature 25 C

    Required Hot Water Temperature 60 C

    Heating Coil Electrical Load  3 kW 

    REF. EH-3

    TOTALS

    207.00

    30.40

    237.40

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    34/43

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    35/43

    Female Toilet B311

    Sanitary Fixture Qty.Fixture unit

    FU*

    Fixture

     Unit

    Bathroom Group 1 3.6 3.6

    Lavatory 4 2 8

    WC 5 5 25

    TOTAL 36.6

    Note

    * Fixture unit based on IPC 2009 Table E103.3(2)

    ** Pipe sizes are based on PPR-PN16

    Male Toilet B312

    Sanitary Fixture Qty.Fixture unit

    FU*

    Fixture

     Unit

    Bathroom Group 1 3.6 3.6

    Lavatory 4 2 8

    WC 5 5 25

    TOTAL 36.6

    Note

    * Fixture unit based on IPC 2009 Table E103.3(2)

    ** Pipe sizes are based on PPR-PN16

    Male Toilet B351A

    Sanitary Fixture Qty.Fixture unit

    FU*

    Fixture

     Unit

    Bathroom Group 2 2.7 5.4

    Lavatory 4 2 8Urinal 4 5 20

    WC 4 5 20

    TOTAL 53.4

    Note

    * Fixture unit based on IPC 2009 Table E103.3(2)

    ** Pipe sizes are based on PPR-PN16

    Parking Souq Waqif 

    Basement 2 - Pipe Sizing Calculations

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    36/43

    Female Toilet B351B

    Sanitary Fixture Qty.Fixture unit

    FU*

    Fixture

     Unit

    Bathroom Group 2 3.6 7.2

    Lavatory 5 2 10

    WC 4 5 20

    TOTAL 37.2

    Note

    * Fixture unit based on IPC 2009 Table E103.3(2)

    ** Pipe sizes are based on PPR-PN16

    Female Toilet B358

    Sanitary Fixture Qty.Fixture unit

    FU*

    Fixture

     Unit

    Bathroom Group 1 2.7 2.7

    Lavatory 3 2 6

    WC 1 5 5

    TOTAL 13.7

    Note

    * Fixture unit based on IPC 2009 Table E103.3(2)

    ** Pipe sizes are based on PPR-PN16

    Male Toilet B359

    Sanitary Fixture Qty.Fixture unit

    FU*

    Fixture

     Unit

    Bathroom Group 1 2.7 2.7

    Lavatory 3 2 6

    WC 1 5 5TOTAL 13.7

    Note

    * Fixture unit based on IPC 2009 Table E103.3(2)

    ** Pipe sizes are based on PPR-PN16

    Parking Souq Waqif 

    Basement 2 - Pipe Sizing Calculations

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    37/43

    Female Toilet B369

    Sanitary Fixture Qty.Fixture unit

    FU*

    Fixture

     Unit

    Bathroom Group 1 2.7 2.7

    Lavatory 3 2 6

    WC 2 5 10

    TOTAL 18.7

    Note

    * Fixture unit based on IPC 2009 Table E103.3(2)

    ** Pipe sizes are based on PPR-PN16

    Male Toilet B370

    Sanitary Fixture Qty.Fixture unit

    FU*

    Fixture

     Unit

    Bathroom Group 1 2.7 2.7

    Lavatory 3 2 6

    WC 2 5 10

    TOTAL 18.7

    Note

    * Fixture unit based on IPC 2009 Table E103.3(2)

    ** Pipe sizes are based on PPR-PN16

    Parking Souq Waqif 

    Basement 2 - Pipe Sizing Calculations

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    38/43

    Male Toilet B202

    Sanitary Fixture Qty.Fixture unit

    FU*

    Fixture

     Unit

    Bathroom Group 1 2.7 2.7

    Lavatory 3 2 6

    WC 4 5 20

    TOTAL 28.7

    Note

    * Fixture unit based on IPC 2009 Table E103.3(2)

    ** Pipe sizes are based on PPR-PN16

    Female Toilet B203

    Sanitary Fixture Qty.Fixture unit

    FU*

    Fixture

     Unit

    Bathroom Group 1 2.7 2.7

    Lavatory 3 2 6

    WC 4 5 20

    TOTAL 28.7

    Note

    * Fixture unit based on IPC 2009 Table E103.3(2)

    ** Pipe sizes are based on PPR-PN16

    Female Toilet B209

    Sanitary Fixture Qty.Fixture unit

    FU*

    Fixture

     Unit

    Bathroom Group 1 2.7 2.7Lavatory 4 2 8

    WC 6 5 30

    TOTAL 40.7

    Note

    * Fixture unit based on IPC 2009 Table E103.3(2)

    ** Pipe sizes are based on PPR-PN16

    Parking Souq Waqif 

    Basement 1 - Pipe Sizing Calculations

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    39/43

    Male Toilet B210

    Sanitary Fixture Qty.Fixture unit

    FU*

    Fixture

     Unit

    Bathroom Group 1 2.7 2.7

    Lavatory 4 2 8

    WC 6 5 30

    TOTAL 40.7

    Note

    * Fixture unit based on IPC 2009 Table E103.3(2)

    ** Pipe sizes are based on PPR-PN16

    Male Toilet B257

    Sanitary Fixture Qty.Fixture unit

    FU*

    Fixture

     Unit

    Lavatory 4 2 8

    Bathroom Group 1 2.7 2.7

    WC 3 5 15

    TOTAL 25.7

    Note

    * Fixture unit based on IPC 2009 Table E103.3(2)

    ** Pipe sizes are based on PPR-PN16

    Female Toilet B258

    Sanitary Fixture Qty.Fixture unit

    FU*

    Fixture

     Unit

    Lavatory 4 2 8Bathroom Group 1 2.7 2.7

    WC 3 5 15

    TOTAL 25.7

    Note

    * Fixture unit based on IPC 2009 Table E103.3(2)

    ** Pipe sizes are based on PPR-PN16

    Basement 1 - Pipe Sizing Calculations

    Parking Souq Waqif 

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    40/43

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    41/43

     A PPE NDI X E

    TABLE E103.3(2)

    LOAD VALUES ASSIGNED TO FIXTURESa

    LOAD VALUES,   IN  WATER SUPPLY FIXTURE UNITS (wsfu)TYPE OF SUPPLY

    FIXTURE OCCUPANCY CONTROL Cold Hot Total

    Bathroom group Private Flush tank 2.7 1.5 3.6

    Bathroom group Private Flush valve 6.0 3.0 8.0

    Bathtub Private Faucet 1.0 1.0 1.4

    Bathtub Public Faucet   3.0 3.0   4.0

    Bidet Private Faucet   1.5 1.5   2.0

    Combination fixture Private Faucet 2.25   2.25   3.0

    Dishwashing machine Private Automatic   -   1.4 1.4

    Drinking fountain   Offices, etc.   3/8" valve   0.25   -   0.25

    Kitchen sink Private Faucet 1.0 1.0 1.4

    Kitchen sink    Hotel , restaurant   Faucet 3.0 3.0 4.0

    Laundry trays  ( l   to 3)   Private Faucet   1.0 1.0   1.4

    Lavatory Private Faucet   0.5 0.5 0.7

    Lavatory Public Faucet   1.5 1.5   2.0

    Service sink    Offices, etc.   Faucet 2.25 2.25 3.0

    Shower head Public Mixing valve 3.0 3.0 4.0

    Shower head Private Mixing valve 1.0 1.0 1.4

    Urinal Public   1" flush valve   10.0   -   10.0

    Urinal Public   flush valve   5.0   -   5.0

    Urinal Public Flush tank     3.0   -   3.0

    Washing machine  (8  lb)   Private Automatic   1.0 1.0   1.4

    Washing machine  (8  lb)   Public Automatic 2.25 2.25 3.0

    Washing machine (15Ib)   Public Automatic 3.0 3.0 4.0

    Water closet Private Flush valve 6.0   -   6.0

    Water closet Private Flush tank 2.2   -   2.2

    Water closet Public Flush valve 10.0   -   10.0

    Water closet Public Flush tank     5.0   -   5.0

    Water closet Public or private Flushometer tank 2.0   -   2.0

    For SI: 1 inch =  25.4 mm, 1 pound  = 0.454 kg.

    a.   F or fIXtures not listed  , loads should be assumed by comparing the fixture to one listed using water in similar quantities and atsimilar rates. The assigned loads for 

    fIXtures with both hot and cold water supplies are given for separate hot and cold water loads and for total load. The separate hot and cold water loads beingthree-fourths o f  the total load for the fixture in each case.

    130   2009 INTERNATIONAL  PLUMBING CODE®

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    42/43

    TABLE E103.3(3)

    TABLE FOR ESTIMATING DEMAND

     AP PENDI X E

    SUPPLY SYSTEMS PREDOMINANTLY FOR FLUSH TANKS SUPPLY SYSTEMS PREDOMINANTLY FOR FLUSH VALVES

    Load Demand Load Demand

    (Water supply fixture units) (Gallons per minute) (Cubic feet per minute) (Water supply fixture units) (Gallons per minute) (Cubic feet per minute)

    1 3.0 0.04104   - - -

    2 5.0 0.0684   - - -

    3   6.5 0.86892   - - -

    4   8.0   1.06944   - - -

    5 9.4   1.256592   5   15.0 2.0052

    6   10.7 1.430376   6   17.4 2.326032

    7 11.8 1.577424 7 19.8 2.646364

    8   12.8 1.711104   8   22.2 2.967696

    9   13.7 1.831416   9   24.6 3.288528

    10 14.6 1.951728 10 27.0 3.60936

    11   15.4 2.058672   11   27.8 3.716304

    12 16.0 2.13888   12 28 .6 3.823248

    13 16.5 2.20572   13   29.4 3.930192

    14   17.0 2.27256   14   30.2 4.037136

    15   17.5 2.3394   15   31.0 4.14408

    16   18.0 2.90624   16   31.8 4.241024

    17   18.4 2.459712   17   32.6 4.357968

    18 18.8 2.513184   18   33.4   4.464912

    19 19.2 2.566656   19   34.2 4.571856

    20   19.6 2.620128 20   35.0   4.6788

    25   21.5 2.87412   25   38.0 5.07984

    30   23.3 3.114744   30   42.0 5.61356

    35   24.9 3.328632   35   44.0 5.88192

    40 26.3 3.515784 40 46.0 6.14928

    45 27 .7 3.702936   45   48.0 6.41664

    50   29.1   3.890088 50 50.0   6.684

    60   32.0 4.27776   60   54.0 7.21872

    70 35.0 4.6788 70 58.0 7.75344

    80   38.0 5.07984   80   61.2 8.181216

    90   41.0 5.48088   90   64.3 8.595624

    100 43.5 5.81508 100 67.5 9.0234

    120 48 .0 6.41664 120   73.0   9.75864

    140   52.5 7.0182 140   77.0   10.29336

    160   57.0   7.61976 160   81.0   10.82808

    180 61.0 8.15448 180 85.5 11.42964

    200 65.0 8.6892 200 90.0 12.0312

    225 70.0 9.3576 225 95.5 12.76644

    250   75.0   10.026 250 101.0   13.50168

    (continued)

    2009 INTERNATIONAL PLUMBING   CODE®   131

  • 8/18/2019 Mechanical Calculations- Plumbing.pdf

    43/43

     APPENDI X E

    TABLE  E103.3(3)-continuedTABLE FOR ESTIMATING DEMAND

    SUPPLY SYSTEMS PREDOMINANTLY FOR FLUSH TANKS SUPPLY SYSTEMS PREDOMINANTLY FOR FLUSH VALVES

    Load Demand Load Demand

    (Water  supply fixture units)   (Gallons per minute) (Cubic feet per minute) (Water   supply fixture units)   (Gallons per minute) (Cubic feet per minute)

    275 80.0 10.6944 275 104.5 13.96956

    300   85.0 11.3628   300   108.0 14.43744

    400 105.0 14.0364 400 127.0 16.97736

    500   124.0   16.57632   500   143.0 19.11624

    750 170.0   22.7256 750 177.0 23.66136

    1,000 208.0 27.80544 1,000 208.0 27.80544

    1,250   239.0 31.94952   1,250   239.0 31.94952

    1,500   269.0 35.95992   1,500   269.0 35.95992

    1,750   297.0 39.70296   1,750   297.0 39.70296

    2,000   325.0 43.446   2,000   325.0 43.446

    2,500   380 .0 50.7984   2,500   380 .0 50.7984

    3,000 433.0 57.88344 3,000 433.0 57.88344

    4,000   525.0 70.182   4,000   525.0 70.182

    5,000 593.0   79.27224   5,000 593.0   79.27224