indoor rmu manual

Upload: hardeepsingh08

Post on 03-Apr-2018

258 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/28/2019 Indoor RMU Manual

    1/20

    SF6 insulated Ring Main Units and CompactSwitchgear

    Instruction for Installation, Operating and Maintenance

  • 7/28/2019 Indoor RMU Manual

    2/20

    3INDEX

    Part Title Page No.

    ABB

    Ensure compliance of local legal and safety norms

    We recommend that installation and commissioning should

    be carried out by qualified and authorised personnel.

    Check that the personnel operating the apparatus have thisinstruction manual with them.

    1. General description 4

    1.1 Table of locations 5

    1.2 Dimensional drawings 62. Transport and handling 7

    2.1 Receiving Inspection 7

    2.2 Storage 7

    2.3 Rating Plate 7

    3. Technical data 8

    3.1 Electrical data 8

    4. Installation 9

    4.1 Cable compartment 10

    4.2 Cable connection 11

    4.3 Current transformers for relay protection 12

    4.4 Gas pressure 13

    5. Operation 13

    5.1 Operating conditions 13

    5.2 Operation 14

    5.3 Relays 15

    6. Additional equipment 15

    6.1 Low-voltage connections auxiliary contacts 15

    6.2 Capacitive voltage indicator 16

    6.3 Short circuit indicator 16

    6.4 Motor operation 17

    6.5 Cable testing 17

    6.6 External busbar 18

    6.7 Pressure indicator 18

    6.8 Base frame 18

    7 Maintenance 187.1 Control and monitoring the gas 18

    7. 2 Environmental certif ication 19

  • 7/28/2019 Indoor RMU Manual

    3/20

    4

    SafeRing 3 - way unit CCV - Non Extensible

    SafePlus 3 - way unit CCV - Extensible

    SafePlus 3 - way unit CCV + 1 way C - Coupling

    1. GENERAL DESCRIPTION

    Outdoor RMU with vacuum circuit-breaker in compliancewith IEC 62271-100 / IEC 62271-200 With this unit the

    transformer will be protected by a vacuum circuit breakercombined with relays and current transformers.The standard relays are based on digital technology anddo not require an auxiliary power supply. Outdoor RMU isa SF6 insulated ring main unit and is a compact switchgearfor applications in medium voltage distribution networks.Outdoor RMU can be supplied as a 1 or 3 - way standardconfigurations with additional equipment according tocustomer specification. Extensible RMU has a uniqueflexibility due to its extendibility and the possiblecombination C/V & CCV & can be extended on RHS/LHSOutdoor RMU offers a sealed stainless steel tank whichcontains all the live components and switching functions.The transformer is protected by a vacuum circuit-breaker.The units/ modules are delivered from the factory ready forinstallation.

    Routine tests are carried out on all units before dispatch.No special tools are required for installing the equipment.

    Outdoor RMU with vacuum circuit-breaker in

    compliance with IEC

    With this unit the transformer will be protected by a vacuumcircuit breaker combined with relays and currenttransformers. The standard relays are based on digitaltechnology and do not require an external auxiliary powersupply.

    62271-100 / IEC 62271-200

    ABB

  • 7/28/2019 Indoor RMU Manual

    4/20

    5

    1.1 TABLE OF LOCATIONS1. Lifting Hooks

    2. Capacitive voltage indication (additional equipment)

    3. Short circuit indicator (additional equipment)4. Pressure indicator (additional equipment)

    5. Mimic diagram

    6. Padlock device

    7. Cable compartment

    8. Circuit breaker on/off Indication

    9. Isolator

    10. Circuit breaker open/close push button

    11. Door Lock

    12. Sealing Gasket

    13. Handle

    14. Stand

    15. Paper Box

    16. Louvers

    17. Extension Cover/ Side Cover

    ABB

    7

    1415

    11

    13 2 34

    1 65

    1610

    8

    1

    17

    9

    12

  • 7/28/2019 Indoor RMU Manual

    5/20

    6

    1.2 DIMENSIONAL DRAWINGS

    ABB

    Non Extensible 3 - way unit

    Extensible 3 - way unit

    Extensible 1 - way unit

  • 7/28/2019 Indoor RMU Manual

    6/20

    NHP 304311

    7

    The units are delivered from the factory ready for installation.

    Weight table for standard SafeRing3-way Non - Ex. CCV 650 Kg3-way - Ex. CCV 700 Kg.1-way - Ex. C 250 Kg.

    The weights is without additional equipment

    RMU is fitted with lifting hooks.

    2. TRANSPORT AND HANDLING

    2.1 RECEIVING INSPECTIONUpon receiving the Outdoor RMU please check that thedelivered equipment has not been damaged during transport. Ifany such damage has occurred, a claim must be submitted tothe carrier immediately.

    After unpacking, the following must be checked:

    1. Operating handle 1 piece should be included.2. Check that the pointer on the pressure indicator is in the

    green area.3. Carry out a function test on the mechanical parts.

    Any faults or omissions must be reported immediately to thesupplier.

    2.2 STORAGEOutdoor RMU must be stored under cover in a dry andwell-ventilated area until it is installed and put into operation.

    NHP 407789

    ABB

    1-way - Ex. V 300 Kg.

    2.3 Rating Plate

  • 7/28/2019 Indoor RMU Manual

    7/20

    8

    3.1 ELECTRICAL DATA3. TECHNICAL DATA

    ABB

    C-module

    Rating Switchdisconnector Earthing switch

    Rated voltage kV 12/17,5/24

    Power frequency withstand voltage kV 281/38/50 1 281/38/50

    Impuls withstand voltage kV 95/95/125

    Rated current A 630/630/630 200/630

    Breaking capacities:

    active load A 630/630/630

    closed loop A 630/630/630

    off load cable charging A 135/135/135

    of load transformer A

    earth fault A 200/150/150

    earth fault cable charging A 115/87/87short circuit breaking current kA 21

    Making capacity kA 52,5/ 52,5/52,5 52,5/40/40Short time current 1 sec. kA

    Short time current 3 sec. kA 21/21/21 21/21/21

    V-module

    Vacuum circuitbreaker Ear thing switch

    95/95/125

    12/17,5/24

    21/16/16

    12/17,5/24 12/17,5/24

    95/95/125281/38/5028 /38/50

    52,5/52,5/52,5 52,5/40/40

    21/16/16

    95/95/125

  • 7/28/2019 Indoor RMU Manual

    8/20

    4. INSTALLATION

    units as appropriate.

    223427386

    The base must be flat and f itted with anchor bolts in accordancewith the dimensional drawing for the number of modules or

    9

    ABB

  • 7/28/2019 Indoor RMU Manual

    9/20

    10

    ABB

    and B.

    2. Removal of front section.

    1. Press the interlocking lever up to openthe door.

    3. Front section removed.

    A

    B

    Opening of cable door :

    NB!The cable door are supplied with interlocking to earthingswitches. When interlocking is fitted, the cable cabinet can onlybe accessed when the earthing switch is in the closed position.For opening the door, press the lever at the bottom and pull thedoor.

    4.1 CABLE COMPARTMENT

    4. The panel can be removed by unscrewing A

    Interlocking Lever

  • 7/28/2019 Indoor RMU Manual

    10/20

    11

    ABB

    Adjustable cable support beam (additional equipment).( Single core cable termination)

    Cable support beamCable clamp

    Earthing barFor cable termination kits please refer supplier documentation fordetails.

    The manufacturer installation instructions must be followed. Besure to lubricate the bushings thoroughly with the silicone supplied.

    NB!Where cables are not connected, the earthing switch must belocked in closed position or the bushings must be fitted with

    deadend recepticals before the unit is put into operation.

    400 S Bolted bushing

    4.2 CABLE CONNECTIONOutdoor RMU is equipped with external bushings whichcomply with DIN47636T1 & T2/EDF HN 525-61 for termination ofcables.

    All bushings are situated in the same height from the floor and areprotected by the cable cover.

    Outdoor RMU is supplied with 400 series bolted typebushing

    3 core cable termination with CT mounted.

  • 7/28/2019 Indoor RMU Manual

    11/20

    12

    ABB

    The cable shielding is led backthrough the centre hole and earthed.

    4.3 CURRENT TRANSFORMERSFOR RELAY PROTECTION

    Installing current transformers. The cable shielding is led backthrough the centre hole and earthed.

    A protection relay is installed in each vacuum circuit breakermodule. The cables from the protection relay to the currenttransformers are placed in the cable compartment, ready forconnection to the three current transformers supplied.

    Before installation:Check that the three current transformers have beendelivered and that they are all of the same type.Check that the current transformers are of the correct type,with the correctly rated transformer ratio, for thedistribution transformer rated current and for theadjustment range on the protection relay (see protectionrelay manual).

    Each current transformer must be mounted onto its high voltagecable before the cable termination is fitted.

    The earth shield on the cable must be led back through thecentre hole in the current transformer (see figure on left) andearthed on the ear thing bar in the cable compartment. Amounting plate for the current transformers is fitted in the cablecompartment.

    After the current transformers have been installed in the unit,the cables from the protection relay are connected. Refer themanual supplied with the protection relay for a description of theconnections.

    Outdoor RMU with vacuum circuit breakers are suitable for threedifferent types of protection relays: SACE PR521/ 512All these are designed so that

    there is no need for external auxiliary voltage for correctfunctioning.

    Separate manuals have been supplied for each of theseprotection relay, with examples of adjustments.

    SACE PR 521/ 512This relay offers advanced protection with facilities for constant-time, normal inverse, very inverse and extremely inversecharacteristics as well as simple earth fault protection inaccordance with IEC 60255-3.

    It is essential for correct functioning that the current transfor-mers are properly connected and that the protection relay isproperly adjusted.

    CTS with 3 core cable.

  • 7/28/2019 Indoor RMU Manual

    12/20

    13

    ABB

    5. OPERATION

    Normal ambient conditionsOutdoor RMU is generally equipped foroperation/service in normal outdoor conditions in

    The following limitations apply:Ambient temperature

    0Max. temperature +40 C0Max. temperature (24-hour average) +35 C0Min. temperature -25 C

    HumidityMax. average relative humiditymeasured over 24 hours 95%Max. average relative humiditymeasured over 1 month 90%Max height above sea level forInstallation without reducing gas pressure 1,000 metres

    Special conditionsIn accordance with IEC 60694, the manufacturer andend-user must agree about special operating conditions

    which deviate from operation under normal conditions.The manufacturer/supplier must be consulted in advance ifespecially difficult operating conditions are involved. Whenelectrical equipment is installed at more than 1,000 metresabove sea level, for example, the atmospheric pressure will belower and the overpressure in the tank will have to be reduced.

    4.4 GAS PRESSUREOutdoor RMUcontains SF6 gas with a nominal pressure

    oof1.4bar at 20 C.

    Outdoor RMU is sealed for life and is fitted with atemperature-compensated pressure indicator.

    Pointer in green area - unit has correct pressurePointer in red area - pressure is too low

    6SF Air

    ValveNOTE! Screw/unscrew

    NHP 408025

    Fillingpressurembar

    1400

    1300

    1200

    900 925 950 975 1000 1025 1050 1075 1100 mbar

    3025201510

    ient

    p.

    amb

    te

    m

    Atm.

    pressure

    5.1 OPERATING CONDITIONS

    Refilling of SF6 gas inOutdoor RMUFollowing equipment is needed gas bottle withmanometer and reduction valve adapter pressuremeasuring device

    1. Remove front cover and unscrew manometeras shown.

    2. Screw (tightening the torque.45 Nm) the adapterto the valve.

    3. Before connecting the hose from the gas bottleto the adapter, the air in the hose must be removedby running SF6 gas through the hose.

    4. When gas is flowing into the RMU/switchgear, themanometer on the g as bottle has to be observed.When it shows 0.4 bar at ambient temperature 20Celsius, (14 bar absolute) the gas filling must bestopped. See table for filling pressure above.

    5. Remove the filling hose and connect the pressuredevice to check the p ressure inside theRMU/switchgear.

    6. When the correct pressure of 0.4 bar(14 bar absolute)is obtained, remove the adapter and screw withtightening torque 45 Nm the manometer to theRMU/switchgear as shown above. Observe that thesealing between the manometer and the valve issmooth and clean.

  • 7/28/2019 Indoor RMU Manual

    13/20

    14

    ABB

    C

    A

    B

    D

    5.2 OPERATION

    All switches can be operated with the included operatinghandle.Internal mechanical interlocking between the switchdisconnector/circuit breaker and the associated earthingswitches prevents incorrect operation. The operation of theswitch disconnector/circuit breaker and earthing switches canbe further interlocked by means of a padlock. The earthingswitches are operated by a snap action mechanism, whichensures fast closing.The earthing switch is closed by turning the operating handleclockwise. Turning the operating handle anti-clockwise opensthe switch.For closing the transformer switch the spring mechanism mustbe charged. Turning the operating handle clockwise does this.Then the green 'on' button must be pressed to close the switch/breaker.An anti-reflex system, standard on all operating handles,prevents the immediate re-operation of switches.

    Fuse switch disconnector.Close: Turn the operating handle clockwise to charge theclose/open spring. Then push the green button. (A)Open:Push the red button. (B)In circuit breaker configurations, the transformer circuit breakercan be tripped by the protection relay, while in switch fuseconfigurations fuse switch disconnector can be triggered by thefuse striker pin if an over current or short-circuit occurs.

    Mechanical position indicators:C: Transformer breaker open D: Earthing switch closed

    Switch disconnector:Close:Turn the operating handle clockwise.Open:Turn the operating handle anti-clockwise.

    Earthing switch:Close:Turn the operating handle clockwise.Open:Turn the operating handle anti-clockwise.

    ABB

  • 7/28/2019 Indoor RMU Manual

    14/20

    15

    6.1 LOW-VOLTAGE CONNECTIONS

    AUXILIARY CONTACTS(2NO+2NC) can be supplied to indicate switch positions on allswitches/breakers. Access to the low-voltage connections isobtained by removing the top front panel. A shunt trip coil (AC or

    DC) can be fitted on the transformer switch/breaker.

    6.2 REMOTE CONTROL AND MONITORING UNITOutdoor RMU can be equipped with an integrated remote control andmonitoring unit (see picture left).This unit is preengineered and can be delivered and installed asa retrofit solution or complete from factory.

    6. ADDITIONAL EQUIPMENT

    5.3 RELAYSOutdoor RMU with vacuum circuit breakers are suitablefor protection relays: PR521/512

    these are designed so that there isno need for external auxiliary voltage for correct functioning.

    Separate manuals are available for each of theseprotection relay, with examples of adjustments.

    ABB

  • 7/28/2019 Indoor RMU Manual

    15/20

    16

    ABB

    6.2 CAPACITIVE VOLTAGE INDICATIONCapacitive voltage indication system.

    Phase balance check

    Voltage presence indication system(VPIS)

    6.3 SHORT CIRCUIT INDICATORThree types can be supplied:Horstman ALPHA-MHorstman ALPHA-EHorstman GAMMA

    ABB

  • 7/28/2019 Indoor RMU Manual

    16/20

    17

    ABB

    NHP 304708

    6.5 CABLE TESTING

    Voltage testing and locating cable faults can be performed intwo ways:

    1. Directly at the testing points (A) if they are fitted on the unit.Proceed as follows: engage the earthing switch. Connect thetesting equipment on top of the testing points which hold theearth bar (B). Remove the earth bar and perform the test. Refitthe earth strip before the testing equipment is disconnected

    2. Directly at the cable connectors which are designed fortesting the voltage of the cable.Follow the suppliers instructions.

    2.1. Cable connector connected

    2.2. Cable connector dismounted

    6.4 MOTOR OPERATION

    Cable switches, vacuum circuit-breakers and earthingswitches are operated by mechanisms located behind the

    front panel.The mechanisms for all the switches and breakers areoperated manually with the operating level (standard), or arefitted with motor operation (additional equipment).The earthing switch can only be operated manually and isfitted with mechanisms to achieve fault making capabilities.

    Motor operation can be easily retrofitted.

  • 7/28/2019 Indoor RMU Manual

    17/20

    18

    ABB

    6.6 EXTENSION BUSBARThe busbar can be installed at site after couplingthe units busbar are sent loose for site erection.

    6.7 PRESSURE INDICATOROutdoor RMU is always supplied with a pressureindicator in the form of a manometer.

    7. Maintenance

    All components in the SF6 tank are maintenance-free for thedeclared life expectancy of the product. The tank is made ofstainless steel.If the panels substain any scratches or damage, these must berepaired with paint to prevent corrosion.

    Mechanical parts are positioned outside the tank and behind thefront panel. This enables easy access and replacement ifrequired.

    Mechanical parts are surface-treated to prevent corrosion.Moving parts are lubricated at the factory for the product lifeexpectancy. In extreme conditions (dust, sand and pollution),inspection and maintenance will be imperative, and in somecases replacements will be necessary. Check that the lubricantis not washed or wiped away from the mechanical moving parts.

    7.1 Control And Monitoring The GasOutdoor RMU is a pressure-sealed system that normallydoes not require special inspections. However the gas pressureon the manometer should always be checked prior tooperation.

  • 7/28/2019 Indoor RMU Manual

    18/20

    Raw Material Amount % of total Re- Environmental effectsweight cycle & recycle/reuse processes320kg

    Iron 132,80 kg 42,53% Yes Separate, utilise in favour of new source (ore)Stainless steel 83,20 kg 24,93% Yes Separate, utilise in favour of new source (ore)Copper 43,98 kg 14,09% Yes Separate, utilise in favour of new source (ore)Brass 2,30 kg 0,74% Yes Separate, utilise in favour of new source (ore)

    Aluminium 8,55 kg 2,74% Yes Separate, utilise in favour of new source (ore)Zinc 3,90 kg 1,25% Yes Separate, utilise in favour of new source (ore)Silver 0,075 kg 0,024 Yes Electrolysis, utilise in favour of new source

    Thermoplastic 5,07 kg 1,63% Yes Make granulate, re-use or apply as energy superioradditive in refuse incineration

    Epoxy incl.60% quartz 26,75 kg 8,35 % Yes Grind to powder and use as high-grade energy additive

    in cement millRubber 1,35 kg 0,42 % Yes High-grade energy additive in refuse incinerationDielectric oil 0,21 kg 0,066 % Yes Reclaim or use as High-grade energy additive

    in refuse incineration

    SF6

    gas 3,24 kg 1,04% Yes ABB reclaims used SF6

    gas.

    Total for recycling 311,44kg 97,25 %

    Not specified * 9,00 kg *Stickers, Film-foils, powder coating, screws, nuts,tiny components, grease .

    Total weight ** 320,00 kg 100 %

    Packing foil 0,2 kg Yes High-grade energy additive in refuse incinerationWooden pallet 21,5 kg Yes Re-use or use as energy additive in refuse incineration

    **)All figures are collected from CCF 3-way unit with arc suppresser.

    19

    2.RECYCLING CAPABILITY

    7.2 ENVIRONMENTAL CERTIFICATION1. LIFE EXPECTANCY OF PRODUCTThe product is developed in compliance with the requirements denoted by IEC 298. The design incorporates a life span under indoor

    service conditions exceeding 30 years (IEC 298 annex GG).The switchgear is gas-tight with an expected diffusion rate of less than 0.1 % per annum. Referring to the reference-pressure of 1.4

    0bar, the switchgear will maintain gas-tightness and a gas-pressure better than 1.3 bar* throughout its designed life span. *) at 20 C.

    3.END-OF-LIFE

    ABB is committed to the protection of the environment and adhere to ISO 14001 standards. It is our obligation to facilitate end-of-

    life recycling for our products.There exist no explicit requirements for how to handle discarded switchgears at end-of-life. ABB's recycling service isaccording to IEC 1634 edition 1995 section 6: End of life of SF6 filled equipmentand in particular 6.5.2.a: Low decomposition:No special action is required; nonrecoverable parts can be disposed of normally according to local regulations.We also recommend ABB's website : http://www.abb.com/sf6 .

    ABB

  • 7/28/2019 Indoor RMU Manual

    19/20

    NOTES

  • 7/28/2019 Indoor RMU Manual

    20/20

    Vandana House1st Floor, G E RoadRamkundRaipur 492 001Tel: +91 771 - 5060816 -18Fax : +91 771 - 5023051

    ABB HouseDr. S B PathBallard EsateMumbai 400 038Tel.: +91 22-56318231-39Fax : +91 22-56318276-77

    ABB LimitedMedium Voltage EquipmentStreet No. 17,MIDC, Satpur,Nashik - 422 007.Tel: +91 253 - 2351095 - 98Fax: +91 253 - 2350644

    Embassy Star, 1st FloorNo.8, Palace RoadVasanth NagarBangalore 560 052Tel: +91 80-22949779Fax : +91 80-22949808

    Century PlazaNo. 3C, 3D, 3F, 3rd Floor,561 / 562, Anna SalaiTeynampetChennai 600 018Tel: +91 44-24340201/203Fax:+91 44 24340282

    ABB LimitedPower TechnologiesExports Marketing OfficeManeja, Vadodara 390 013Tel: +91 265-2638930Fax: +91 265-2638908Email: [email protected]

    www abb com

    4th FloorNo. 9, Lala Lajpat Rai Sarani(Elgin Road)Kolkata 700 020Tel.: +91 33-22832911/906Fax : +91 33-22832990

    NBCC Tower4th FloorNo.15, Bhikaji Cama PlaceNew Delhi - 110 066Tel.: +91 11-26186000Fax : +91 11-26197592/84035

    East West Central South

    Regional Marketing Offices :

    North