Model IE36CT4IEC Indoor Current Transformer
Design Characteristics
Construction - epoxy•Base Plate - electro galvanized steel•Primary Terminals - copper or brass •Tested per IEC 61869-2 •Ambient Temperature - design suitable from•-25°C thru 40°C Altitude - design suitable up to 1000m above•sea levelOther technical specifications may be available•upon request.
Required Technical Specifications
Product Data
Service conditions•Insulation level•Frequency •Number of secondaries •Current ratio•
Please refer to our website www.gedigitalEnergy.com/iti for complete product offering1 of 2Subject to change without notice
Type (Model) Symbol UOM IE36CT4
Highest Voltage for Equipment (r.m.s.) Um (kV) 36
Test Voltages (kV) 70/170
Rated Frequency fR (Hz) 50 or 60
Maximum Rated Primary Current In (A) 1500
Secondary Rated Current (A) 1 or 2 or 5
Rated Short-Time Thermal Current (1s) Ith (kA) 1250 x In ; Max. 50
Rated Dynamic Current Idyn (kA) 2.5 Ith ; Max. 125
Weight ± (10%) (kg) 21
Rated burden for each secondary•Accuracy class for each secondary•Standards •Continuous primary current •Short time thermal current•
222±2
M12
M12
DOUBLE RATIO
C1C2
P1 P2
360±
2
259±2
2x10 - 2x600A
NET WEIGHT 21 ± 10 %kg NOTE: DO NOT CONTAIN ANY PCB
184
350±2
120 3232
32 120 32
225±
2
P1 P2 259±
2
350±2
184
98
20
Ø213±2
3
SINGLE RATIO
300±2
DIMENSIONS:
Model IE36CT4IEC Indoor Current Transformer
CS00A47726 Rev. 05/2015
North America / WorldwideToll Free + 1-800-547-8629 (NA Only)Tel: + 1-905-294-6222Fax: +1-905-201-2098email: [email protected]
AsiaTel: +86-21-2401-3208Fax: +86-21-5423-5080 email: [email protected]
Europe / Middle East / AfricaTel: +34-94-485-88-00Fax: +34-94-485-88-35email: [email protected]
BrazilTel: +55-11-3614-1700Fax: +55-11-3614-1799 email: [email protected]
Please refer to our website www.gedigitalEnergy.com/iti for complete product offering
IndiaTel: +91 80 41314617
+91 99 45478935
2 of 2Subject to change without notice