1mrk504134-uen - en application manual transformer protection ret650 1.3 iec

402
Relion ® 650 series Transformer protection RET650 Application Manual

Upload: tony

Post on 25-Dec-2015

271 views

Category:

Documents


12 download

DESCRIPTION

tr

TRANSCRIPT

Page 1: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Relion® 650 series

Transformer protection RET650Application Manual

Page 2: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC
Page 3: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Document ID: 1MRK 504 134-UENIssued: March 2013

Revision: -Product version: 1.3

© Copyright 2013 ABB. All rights reserved

Page 4: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

CopyrightThis document and parts thereof must not be reproduced or copied without writtenpermission from ABB, and the contents thereof must not be imparted to a thirdparty, nor used for any unauthorized purpose.

The software and hardware described in this document is furnished under a licenseand may be used or disclosed only in accordance with the terms of such license.

This product includes software developed by the OpenSSL Project for use in theOpenSSL Toolkit. (http://www.openssl.org/)

This product includes cryptographic software written/developed by: Eric Young([email protected]) and Tim Hudson ([email protected]).

TrademarksABB and Relion are registered trademarks of the ABB Group. All other brand orproduct names mentioned in this document may be trademarks or registeredtrademarks of their respective holders.

WarrantyPlease inquire about the terms of warranty from your nearest ABB representative.

ABB AB

Substation Automation Products

SE-721 59 Västerås

Sweden

Telephone: +46 (0) 21 32 50 00

Facsimile: +46 (0) 21 14 69 18

http://www.abb.com/substationautomation

Page 5: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

DisclaimerThe data, examples and diagrams in this manual are included solely for the conceptor product description and are not to be deemed as a statement of guaranteedproperties. All persons responsible for applying the equipment addressed in thismanual must satisfy themselves that each intended application is suitable andacceptable, including that any applicable safety or other operational requirementsare complied with. In particular, any risks in applications where a system failure and/or product failure would create a risk for harm to property or persons (including butnot limited to personal injuries or death) shall be the sole responsibility of theperson or entity applying the equipment, and those so responsible are herebyrequested to ensure that all measures are taken to exclude or mitigate such risks.

This document has been carefully checked by ABB but deviations cannot becompletely ruled out. In case any errors are detected, the reader is kindly requestedto notify the manufacturer. Other than under explicit contractual commitments, inno event shall ABB be responsible or liable for any loss or damage resulting fromthe use of this manual or the application of the equipment.

Page 6: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

ConformityThis product complies with the directive of the Council of the EuropeanCommunities on the approximation of the laws of the Member States relating toelectromagnetic compatibility (EMC Directive 2004/108/EC) and concerningelectrical equipment for use within specified voltage limits (Low-voltage directive2006/95/EC). This conformity is the result of tests conducted by ABB inaccordance with the product standards EN 50263 and EN 60255-26 for the EMCdirective, and with the product standards EN 60255-1 and EN 60255-27 for the lowvoltage directive. The product is designed in accordance with the internationalstandards of the IEC 60255 series.

Page 7: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Table of contents

Section 1 Introduction.....................................................................15This manual......................................................................................15Intended audience............................................................................15Product documentation.....................................................................16

Product documentation set..........................................................16Document revision history...........................................................17Related documents......................................................................17

Symbols and conventions.................................................................18Symbols.......................................................................................18Document conventions................................................................19

Section 2 Application......................................................................21RET650 application..........................................................................21Available functions............................................................................26

Main protection functions.............................................................26Back-up protection functions.......................................................26Control and monitoring functions.................................................27Station communication................................................................31Basic IED functions.....................................................................32

RET650 application examples..........................................................33Adaptation to different applications.............................................33Two-winding HV/MV, Y/Δ-transformer.........................................33Two-winding HV/MV, Y/Y-transformer.........................................34Functionality table........................................................................35Three-winding HV/MV1/MV2, Y/Y/Δ-transformer........................37Three-winding HV/MV1/MV2, Y/Y/Δ-transformer........................38Functionality table........................................................................38

Section 3 RET650 setting examples..............................................41Setting example for a two-winding HV/MV transformer, Y/Δ-transformer.......................................................................................41

Calculating general settings for analogue inputs 8I 2U...............42Calculating settings for global base values GBASVAL................43Calculating settings for transformer differential protectionT2WPDIF ....................................................................................44Calculating settings for restricted earth fault protectionREFPDIF ....................................................................................48Calculating settings for instantaneous phase overcurrentprotection, HV-side, PHPIOC .....................................................49

Table of contents

1Application Manual

Page 8: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Calculating settings for four step phase overcurrentprotection 3-phase output, HV-side, OC4PTOC .........................50

Calculating general settings ..................................................50Calculating settings for step 1................................................50

Calculating settings for four step phase overcurrentprotection 3-phase output, LV-side OC4PTOC ..........................53

Calculating general settings...................................................54Calculating settings for step 1 ...............................................54Calculating settings for step 4................................................55

Calculating settings for four step residual overcurrentprotection, zero or negative sequence direction HV-sideEF4PTOC ...................................................................................57

Calculating general settings...................................................58Calculating settings for step 1................................................58Calculating settings for step 2................................................60Calculating settings for step 4................................................61

Calculating settings for two step residual overvoltageprotection LV-side, ROV2PTOV .................................................62Calculating settings for HV-side breaker failure protection,CCRBRF .....................................................................................63Calculating settings for LV-side breaker failure protection,CCRBRF .....................................................................................64

Section 4 Analog inputs..................................................................67Introduction.......................................................................................67Setting guidelines.............................................................................67

Setting of the phase reference channel.......................................67Setting of current channels..........................................................68

Example 1..............................................................................68Example 2..............................................................................69Examples on how to connect, configure and set CTinputs for most commonly used CT connections....................70Example on how to connect a star connected three-phase CT set to the IED.........................................................71Example how to connect delta connected three-phaseCT set to the IED....................................................................74Example how to connect single-phase CT to the IED............77

Setting of voltage channels.........................................................79Example.................................................................................79Examples how to connect, configure and set VT inputsfor most commonly used VT connections..............................80Examples on how to connect a three phase-to-earthconnected VT to the IED........................................................80Example on how to connect a phase-to-phaseconnected VT to the IED........................................................82

Table of contents

2Application Manual

Page 9: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Example how to connect the open delta VT to the IEDfor low impedance earthed or solidly earthed powersystems..................................................................................84Example on how to connect a neutral point VT to theIED.........................................................................................86

Section 5 Local human-machine interface.....................................89Local HMI.........................................................................................89

Display.........................................................................................89LEDs............................................................................................91Keypad........................................................................................91Local HMI functionality................................................................92

Protection and alarm indication..............................................92Parameter management ........................................................94Front communication..............................................................94

Section 6 Differential protection.....................................................97Transformer differential protection T2WPDIF and T3WPDIF ..........97

Identification................................................................................97Application...................................................................................97Setting guidelines........................................................................98

Inrush restraint methods.........................................................98Overexcitation restraint method.............................................98Cross-blocking between phases............................................99Restrained and unrestrained differential protection................99Elimination of zero sequence currents.................................100Internal/External fault discriminator......................................101Differential current alarm......................................................103Switch onto fault feature.......................................................103

Setting example.........................................................................103CT Connections....................................................................103

Restricted earth-fault protection, low impedance REFPDIF ..........105Identification..............................................................................105Application.................................................................................106

Application examples...........................................................106Setting guidelines......................................................................110

Setting and configuration......................................................110Settings................................................................................111

1Ph High impedance differential protection HZPDIF .....................111Identification..............................................................................111Application.................................................................................112

The basics of the high impedance principle.........................112Connection examples for high impedance differentialprotection...................................................................................118

Table of contents

3Application Manual

Page 10: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Connections for 1Ph restricted earth fault and highimpedance differential protection.........................................118

Setting guidelines......................................................................119Configuration........................................................................119Settings of protection function..............................................119Restricted earth fault protection REFPDIF...........................120Alarm level operation............................................................122

Section 7 Impedance protection...................................................125Power swing detection ZMRPSB ...................................................125

Identification..............................................................................125Application.................................................................................125

General.................................................................................125Basic characteristics.............................................................126

Setting guidelines......................................................................126Underimpedance protection for generators and transformersZGCPDIS .......................................................................................134

Identification..............................................................................134Application.................................................................................134Setting guidelines......................................................................134

Load enchroachment LEPDIS........................................................136Identification..............................................................................136Application.................................................................................136Setting guidelines......................................................................136

Resistive reach with load encroachment characteristic........136

Section 8 Current protection.........................................................139Instantaneous phase overcurrent protection 3-phase outputPHPIOC .........................................................................................139

Identification..............................................................................139Application.................................................................................139Setting guidelines......................................................................140

Meshed network without parallel line...................................140Meshed network with parallel line........................................142

Four step phase overcurrent protection 3-phase outputOC4PTOC .....................................................................................144

Identification..............................................................................144Application.................................................................................144Setting guidelines......................................................................145

Settings for steps 1 to 4 .......................................................1462nd harmonic restrain...........................................................148

Instantaneous residual overcurrent protection EFPIOC ................154Identification..............................................................................154Application.................................................................................154

Table of contents

4Application Manual

Page 11: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Setting guidelines......................................................................154Four step residual overcurrent protection, zero, negativesequence direction EF4PTOC .......................................................156

Identification..............................................................................157Application.................................................................................157Setting guidelines......................................................................159

Settings for steps 1 and 4 ....................................................159Common settings for all steps..............................................1612nd harmonic restrain...........................................................162Transformer application example.........................................163

Thermal overload protection, two time constants TRPTTR ...........166Identification..............................................................................166Application.................................................................................166Setting guideline........................................................................168

Breaker failure protection 3-phase activation and outputCCRBRF ........................................................................................170

Identification..............................................................................170Application.................................................................................170Setting guidelines......................................................................170

Pole discordance protection CCRPLD ..........................................173Identification..............................................................................173Application.................................................................................173Setting guidelines......................................................................174

Directional over-/under-power protection GOPPDOP/GUPPDUP......................................................................................175

Application.................................................................................175Directional overpower protection GOPPDOP ...........................177

Identification.........................................................................177Setting guidelines.................................................................177

Directional underpower protection GUPPDUP..........................181Identification.........................................................................181Setting guidelines.................................................................181

Negative sequence based overcurrent function DNSPTOC ..........184Identification..............................................................................184Application.................................................................................184Setting guidelines......................................................................184

Section 9 Voltage protection........................................................187Two step undervoltage protection UV2PTUV ................................187

Identification..............................................................................187Application.................................................................................187Setting guidelines......................................................................188

Equipment protection, such as for motors andgenerators............................................................................188

Table of contents

5Application Manual

Page 12: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Disconnected equipment detection......................................188Power supply quality ...........................................................188Voltage instability mitigation.................................................188Backup protection for power system faults...........................188Settings for Two step undervoltage protection.....................189

Two step overvoltage protection OV2PTOV ..................................190Identification..............................................................................190Application.................................................................................190Setting guidelines......................................................................191

Two step residual overvoltage protection ROV2PTOV .................193Identification..............................................................................193Application.................................................................................193Setting guidelines......................................................................194

Equipment protection, such as for motors, generators,reactors and transformers....................................................194Power supply quality............................................................194High impedance earthed systems........................................194Direct earthed system..........................................................195Settings for Two step residual overvoltage protection..........196

Overexcitation protection OEXPVPH ............................................197Identification..............................................................................197Application.................................................................................198Setting guidelines......................................................................199

Recommendations for input and output signals...................199Settings................................................................................199

Section 10 Frequency protection....................................................201Underfrequency protection SAPTUF .............................................201

Identification..............................................................................201Application.................................................................................201Setting guidelines......................................................................201

Overfrequency protection SAPTOF ...............................................202Identification..............................................................................202Application.................................................................................202Setting guidelines......................................................................203

Rate-of-change frequency protection SAPFRC .............................203Identification..............................................................................204Application.................................................................................204Setting guidelines......................................................................204

Section 11 Secondary system supervision.....................................207Fuse failure supervision SDDRFUF...............................................207

Identification..............................................................................207Application.................................................................................207

Table of contents

6Application Manual

Page 13: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Setting guidelines......................................................................208General.................................................................................208Setting of common parameters............................................208Negative sequence based....................................................209Zero sequence based...........................................................210Delta U and delta I ...............................................................210Dead line detection...............................................................211

Breaker close/trip circuit monitoring TCSSCBR.............................211Identification..............................................................................211Application.................................................................................211

Section 12 Control..........................................................................217Apparatus control ..........................................................................217

Identification..............................................................................217Application.................................................................................217Interaction between modules.....................................................224Setting guidelines......................................................................226

Switch controller (SCSWI)....................................................227Bay control (QCBAY)...........................................................227

Interlocking.....................................................................................228Identification..............................................................................228Application.................................................................................228Configuration guidelines............................................................229Interlocking for busbar earthing switch BB_ES .........................229

Application............................................................................230Signals in single breaker arrangement.................................230Signals in double-breaker arrangement...............................234Signals in 1 1/2 breaker arrangement..................................235

Interlocking for bus-section breaker A1A2_BS..........................235Application............................................................................235Signals from all feeders........................................................236Configuration setting............................................................239

Interlocking for bus-section disconnector A1A2_DC ................240Application............................................................................240Signals in single breaker arrangement.................................240Signals in double-breaker arrangement...............................243Signals in 1 1/2 breaker arrangement..................................246

Interlocking for bus-coupler bay ABC_BC ................................247Application............................................................................247Configuration........................................................................248Signals from all feeders........................................................248Signals from bus-coupler......................................................250Configuration setting............................................................252

Interlocking for 1 1/2 CB BH .....................................................253

Table of contents

7Application Manual

Page 14: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Application............................................................................253Configuration setting............................................................254

Interlocking for double CB bay DB ...........................................255Application............................................................................255Configuration setting............................................................256

Interlocking for line bay ABC_LINE ..........................................256Application............................................................................256Signals from bypass busbar.................................................257Signals from bus-coupler......................................................258Configuration setting............................................................261

Interlocking for transformer bay AB_TRAFO ............................262Application............................................................................262Signals from bus-coupler......................................................262Configuration setting............................................................263

Voltage control ...............................................................................264Identification..............................................................................264Application.................................................................................264Setting guidelines......................................................................291

TR8ATCC general settings..................................................291TR8ATCC Setting group .....................................................292TCMYLTC general settings..................................................298

Logic rotating switch for function selection and LHMIpresentation SLGGIO.....................................................................299

Identification..............................................................................299Application.................................................................................299Setting guidelines......................................................................299

Selector mini switch VSGGIO.........................................................300Identification..............................................................................300Application.................................................................................300Setting guidelines......................................................................301

IEC61850 generic communication I/O functions DPGGIO.............301Identification..............................................................................301Application.................................................................................301Setting guidelines......................................................................301

Single point generic control 8 signals SPC8GGIO.........................302Identification..............................................................................302Application.................................................................................302Setting guidelines......................................................................302

Automation bits AUTOBITS............................................................303Identification..............................................................................303Application.................................................................................303Setting guidelines......................................................................303

Section 13 Logic.............................................................................305

Table of contents

8Application Manual

Page 15: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Tripping logic common 3-phase output SMPPTRC .......................305Identification..............................................................................305Application.................................................................................305

Three-phase tripping ...........................................................305Lock-out................................................................................306Blocking of the function block...............................................306

Setting guidelines......................................................................306Trip matrix logic TMAGGIO............................................................307

Identification..............................................................................307Application.................................................................................307Setting guidelines......................................................................307

Configurable logic blocks................................................................308Identification..............................................................................308Application.................................................................................309

Configuration........................................................................309Fixed signals FXDSIGN..................................................................310

Identification..............................................................................310Application.................................................................................310

Boolean 16 to integer conversion B16I...........................................311Identification..............................................................................311Application.................................................................................312Setting guidelines......................................................................312

Boolean 16 to integer conversion with logic noderepresentation B16IFCVI................................................................312

Identification..............................................................................312Application.................................................................................312Setting guidelines......................................................................312

Integer to boolean 16 conversion IB16A........................................313Identification..............................................................................313Application.................................................................................313Setting guidelines......................................................................313

Integer to boolean 16 conversion with logic noderepresentation IB16FCVB...............................................................313

Identification..............................................................................313Application.................................................................................313Settings......................................................................................314

Elapsed time integrator with limit transgression and overflowsupervision TEIGGIO.....................................................................314

Identification..............................................................................314Application.................................................................................314Setting guidelines......................................................................314

Section 14 Monitoring.....................................................................317IEC61850 generic communication I/O functions SPGGIO.............317

Table of contents

9Application Manual

Page 16: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Identification..............................................................................317Application.................................................................................317Setting guidelines......................................................................317

IEC61850 generic communication I/O functions 16 inputsSP16GGIO.....................................................................................317

Identification..............................................................................317Application.................................................................................317Setting guidelines......................................................................318

IEC61850 generic communication I/O functions MVGGIO.............318Identification..............................................................................318Application.................................................................................318Setting guidelines......................................................................318

Measurements................................................................................319Identification..............................................................................319Application.................................................................................319Setting guidelines......................................................................321Setting examples.......................................................................324

Measurement function application for a 110kV OHL............324Measurement function application for a powertransformer...........................................................................326

Event counter CNTGGIO................................................................328Identification..............................................................................328Application.................................................................................328Setting guidelines......................................................................328

Limit counter L4UFCNT..................................................................328Function description..................................................................329Application.................................................................................329

Setting guidelines.................................................................329Disturbance report .........................................................................329

Identification..............................................................................329Application.................................................................................330Setting guidelines......................................................................331

Binary input signals..............................................................334Analog input signals.............................................................334Sub-function parameters......................................................334Consideration.......................................................................335

Measured value expander block MVEXP.......................................336Identification..............................................................................336Application.................................................................................336Setting guidelines......................................................................336

Station battery supervision SPVNZBAT.........................................336Identification..............................................................................336Application.................................................................................337

Insulation gas monitoring function SSIMG.....................................337

Table of contents

10Application Manual

Page 17: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Identification..............................................................................337Application.................................................................................337

Insulation liquid monitoring function SSIML....................................338Identification..............................................................................338Application.................................................................................338

Circuit breaker condition monitoring SSCBR..................................338Identification..............................................................................338Application.................................................................................338

Section 15 Metering.......................................................................343Pulse counter PCGGIO..................................................................343

Identification..............................................................................343Application.................................................................................343Setting guidelines......................................................................343

Energy calculation and demand handling EPTMMTR....................344Identification..............................................................................344Application.................................................................................344Setting guidelines......................................................................345

Section 16 Station communication.................................................347IEC61850-8-1 communication protocol .........................................347

Identification..............................................................................347Application.................................................................................347

Horizontal communication via GOOSE................................349Setting guidelines......................................................................352

DNP3 protocol................................................................................352IEC 60870-5-103 communication protocol.....................................352IEC 61850-8-1 redundant station bus communication...................353Application......................................................................................353Setting guidelines...........................................................................354

Section 17 Basic IED functions......................................................357Self supervision with internal event list ..........................................357

Identification..............................................................................357Application.................................................................................357

Time synchronization......................................................................358Identification..............................................................................358Application.................................................................................358Setting guidelines......................................................................359

Parameter setting group handling..................................................361Identification..............................................................................361Application.................................................................................361Setting guidelines......................................................................362

Test mode functionality TESTMODE..............................................362

Table of contents

11Application Manual

Page 18: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Identification..............................................................................362Application.................................................................................362Setting guidelines......................................................................362

Change lock CHNGLCK.................................................................363Identification..............................................................................363Application.................................................................................363Setting guidelines......................................................................364

IED identifiers TERMINALID..........................................................364Identification..............................................................................364Application.................................................................................364

Customer specific settings...................................................364Product information PRODINF.......................................................364

Identification..............................................................................364Application.................................................................................365

Factory defined settings.......................................................365Primary system values PRIMVAL...................................................366

Identification..............................................................................366Application.................................................................................366

Signal matrix for analog inputs SMAI.............................................366Identification..............................................................................366Application.................................................................................366Setting guidelines......................................................................367

Summation block 3 phase 3PHSUM..............................................369Identification..............................................................................369Application.................................................................................370Setting guidelines......................................................................370

Global base values GBASVAL.......................................................370Identification..............................................................................370Application.................................................................................370Setting guidelines......................................................................371

Authority check ATHCHCK.............................................................371Identification..............................................................................371Application.................................................................................371

Authorization handling in the IED.........................................372Authority status ATHSTAT.............................................................373

Identification..............................................................................373Application.................................................................................373

Denial of service.............................................................................374Identification..............................................................................374Application.................................................................................374Setting guidelines......................................................................374

Section 18 Requirements...............................................................375Current transformer requirements..................................................375

Table of contents

12Application Manual

Page 19: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Current transformer classification..............................................375Conditions..................................................................................376Fault current..............................................................................377Secondary wire resistance and additional load.........................377General current transformer requirements................................377Rated equivalent secondary e.m.f. requirements......................378

Transformer differential protection.......................................3781 Ph high impedance differential protection.........................379Breaker failure protection.....................................................380Non-directional instantaneous and definitive time, phaseand residual overcurrent protection......................................380Non-directional inverse time delayed phase and residualovercurrent protection..........................................................381Directional phase and residual overcurrent protection.........382

Current transformer requirements for CTs according toother standards..........................................................................383

Current transformers according to IEC 60044-1,class P, PR...........................................................................383Current transformers according to IEC 60044-1, classPX, IEC 60044-6, class TPS(and old British Standard, class X).......................................383Current transformers according to ANSI/IEEE.....................383

Voltage transformer requirements..................................................384SNTP server requirements.............................................................385

SNTP server requirements........................................................385

Section 19 Glossary.......................................................................387

Table of contents

13Application Manual

Page 20: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

14

Page 21: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Section 1 Introduction

1.1 This manual

The application manual contains application descriptions and setting guidelinessorted per function. The manual can be used to find out when and for what purposea typical protection function can be used. The manual can also provides assistancefor calculating settings.

1.2 Intended audience

This manual addresses the protection and control engineer responsible forplanning, pre-engineering and engineering.

The protection and control engineer must be experienced in electrical powerengineering and have knowledge of related technology, such as protection schemesand communication principles.

1MRK 504 134-UEN - Section 1Introduction

15Application Manual

Page 22: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

1.3 Product documentation

1.3.1 Product documentation set

IEC07000220-3-en.vsd

Pla

nnin

g &

pur

chas

e

Eng

inee

ring

Inst

allin

g

Com

mis

sion

ing

Ope

ratio

n

Mai

nten

ance

Dec

omm

issi

onin

gD

eins

talli

ng &

dis

posa

l

Application manual

Operation manual

Installation manual

Engineering manual

Communication protocol manual

Technical manual

Commissioning manual

IEC07000220 V3 EN

Figure 1: The intended use of manuals throughout the product lifecycle

The engineering manual contains instructions on how to engineer the IEDs usingthe various tools available within the PCM600 software. The manual providesinstructions on how to set up a PCM600 project and insert IEDs to the projectstructure. The manual also recommends a sequence for the engineering ofprotection and control functions, LHMI functions as well as communicationengineering for IEC 60870-5-103, IEC 61850 and DNP 3.0.

The installation manual contains instructions on how to install the IED. Themanual provides procedures for mechanical and electrical installation. The chaptersare organized in the chronological order in which the IED should be installed.

The commissioning manual contains instructions on how to commission the IED.The manual can also be used by system engineers and maintenance personnel forassistance during the testing phase. The manual provides procedures for thechecking of external circuitry and energizing the IED, parameter setting andconfiguration as well as verifying settings by secondary injection. The manualdescribes the process of testing an IED in a substation which is not in service. The

Section 1 1MRK 504 134-UEN -Introduction

16Application Manual

Page 23: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

chapters are organized in the chronological order in which the IED should becommissioned. The relevant procedures may be followed also during the serviceand maintenance activities.

The operation manual contains instructions on how to operate the IED once it hasbeen commissioned. The manual provides instructions for the monitoring,controlling and setting of the IED. The manual also describes how to identifydisturbances and how to view calculated and measured power grid data todetermine the cause of a fault.

The application manual contains application descriptions and setting guidelinessorted per function. The manual can be used to find out when and for what purposea typical protection function can be used. The manual can also provides assistancefor calculating settings.

The technical manual contains application and functionality descriptions and listsfunction blocks, logic diagrams, input and output signals, setting parameters andtechnical data, sorted per function. The manual can be used as a technical referenceduring the engineering phase, installation and commissioning phase, and duringnormal service.

The communication protocol manual describes the communication protocolssupported by the IED. The manual concentrates on the vendor-specificimplementations.

The point list manual describes the outlook and properties of the data pointsspecific to the IED. The manual should be used in conjunction with thecorresponding communication protocol manual.

1.3.2 Document revision historyDocument revision/date History-/March 2013 First release

1.3.3 Related documentsDocuments related to RET650 Identity numberApplication manual 1MRK 504 134-UEN

Technical manual 1MRK 504 135-UEN

Commissioning manual 1MRK 504 136-UEN

Product Guide, configured 1MRK 504 137-BEN

Type test certificate 1MRK 504 137-TEN

Application notes for Circuit Breaker Control 1MRG006806

1MRK 504 134-UEN - Section 1Introduction

17Application Manual

Page 24: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

650 series manuals Identity numberCommunication protocol manual, DNP 3.0 1MRK 511 280-UEN

Communication protocol manual, IEC 61850–8–1 1MRK 511 281-UEN

Communication protocol manual, IEC 60870-5-103 1MRK 511 282-UEN

Cyber Security deployment guidelines 1MRK 511 285-UEN

Point list manual, DNP 3.0 1MRK 511 283-UEN

Engineering manual 1MRK 511 284-UEN

Operation manual 1MRK 500 096-UEN

Installation manual 1MRK 514 016-UEN

Accessories, 650 series 1MRK 513 023-BEN

MICS 1MRG 010 656

PICS 1MRG 010 660

PIXIT 1MRG 010 658

1.4 Symbols and conventions

1.4.1 Symbols

The electrical warning icon indicates the presence of a hazardwhich could result in electrical shock.

The warning icon indicates the presence of a hazard which couldresult in personal injury.

The caution icon indicates important information or warning relatedto the concept discussed in the text. It might indicate the presenceof a hazard which could result in corruption of software or damageto equipment or property.

The information icon alerts the reader of important facts andconditions.

The tip icon indicates advice on, for example, how to design yourproject or how to use a certain function.

Although warning hazards are related to personal injury, it is necessary tounderstand that under certain operational conditions, operation of damaged

Section 1 1MRK 504 134-UEN -Introduction

18Application Manual

Page 25: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

equipment may result in degraded process performance leading to personal injuryor death. It is important that the user fully complies with all warning andcautionary notices.

1.4.2 Document conventions

• Abbreviations and acronyms in this manual are spelled out in the glossary. Theglossary also contains definitions of important terms.

• Push button navigation in the LHMI menu structure is presented by using thepush button icons.For example, to navigate between the options, use and .

• HMI menu paths are presented in bold.For example, select Main menu/Settings.

• LHMI messages are shown in Courier font.For example, to save the changes in non-volatile memory, select Yes andpress .

• Parameter names are shown in italics.For example, the function can be enabled and disabled with the Operation setting.

• Each function block symbol shows the available input/output signal.• the character ^ in front of an input/output signal name indicates that the

signal name may be customized using the PCM600 software.• the character * after an input/output signal name indicates that the signal

must be connected to another function block in the applicationconfiguration to achieve a valid application configuration.

1MRK 504 134-UEN - Section 1Introduction

19Application Manual

Page 26: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

20

Page 27: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Section 2 Application

2.1 RET650 application

RET650 provides fast and selective protection, monitoring and control for two- andthree-winding transformers, autotransformers, generator-transformer units andshunt reactors. The IED is designed to operate correctly over a wide frequencyrange in order to accommodate power system frequency variations duringdisturbances and generator start-up and shut-down. Apparatus control for up to 8apparatuses with interlocking can be included in one IED by function blockengineering.

A very fast differential protection function with built-in transformer ratio matchingand vector group compensation makes this IED the ideal solution even for the mostdemanding applications. Since RET650 has very low requirements on the mainCTs, no interposing CTs are required. The differential protection function isprovided with 2nd harmonic and wave-block restraint features to avoid tripping formagnetizing inrush current, and 5th harmonic restraint to avoid tripping foroverexcitation.

The differential function offers a high sensitivity for low-level internal faults. Theunique and innovative sensitive differential protection feature of the RET650provides the best possible coverage for winding internal turn-to-turn faults, basedon the theory of symmetrical components .

A low impedance restricted earth-fault protection function is available as acomplimentary sensitive and fast main protection against winding earth faults. Thisfunction includes a directional zero-sequence current criterion for additional security.

Tripping from pressure relief/Buchholz and temperature devices can beimplemented through the IED's binary inputs, where trip signal conditioning can beperformed (pulsing, lockout, additional logics, etc). The binary inputs arethoroughly stabilized against disturbances in order to prevent incorrect operationsdue to for example DC system capacitive discharges or DC earth faults.

Versatile phase, earth, negative and zero sequence overcurrent functions withdirectional capability provide further alternative backup protections. Thermaloverload with two time-constants, overexcitation (volts per hertz) and over/undervoltage protection functions are also available.

A built-in disturbance and event recorder provides valuable data to the user aboutstatus and operation for post-fault disturbance analysis.

1MRK 504 134-UEN - Section 2Application

21Application Manual

Page 28: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Breaker failure protection allows high speed back-up tripping of surroundingbreakers.

Three packages have been defined for the following applications:

• Two-winding transformer in single breaker arrangements (A01)• Three-winding transformer in single breaker arrangements (A05)• One or two transformer tap changer control (A07)

The packages are preconfigured and ready for direct use. Analog and tripping IOhas been pre-defined for basic use. Other signals need to be applied as required foreach application.

The graphical configuration tool ensures simple and fast testing and commissioning.

Section 2 1MRK 504 134-UEN -Application

22Application Manual

Page 29: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

T2W PDIF

87T 3Id/I

CC RBRF

50BF 3I> BF

CC RBRF

50BF 3I> BF

OC4 PTOC

50/51 3I>

OC4 PTOC

50/51 3I>

CC RPLD

52PD PD

EF4 PTOC

51N IN>

CC RPLD

52PD PD

TR PTTR

49 Ith

C MSQI

Meter.

V MMXU

Meter.

C MMXU

Meter.

CV MMXN

Meter.

TCS SCBR

Cond

TCS SCBR

Cond

SPVN ZBAT

Cond

TR8 ATCC

90 U

TCM YLTC

84

UV2 PTUV

27 U<

OV2 PTOV

59 U>

PH PIOC

50 3I>>

TR PTTR

49 Ith

REF PDIF

87N IdN/I

Other configured functions

REF PDIF

87N IdN/I

EF4 PTOC

51N/67N IN>

DRP RDRE

Mont.

YY

P

ROV2 PTOV

59N 3U0>

RET650 A01 - 2 Winding Transformer protection 10AI (8I+2U)

20 MVA110±11*1.5% / 21 kV

105 / 550 AYNd5

20 kV Bus

110 kV Bus

200/1

600/120kV/100V

200/1

600/1

IEC61850

ANSI IEC

Function Enabled in Settings

IEC61850

ANSI IEC

Function Disabled in Settings

W1

W2

IEC09000645-4-en.vsd

IEC09000645 V4 EN

Figure 2: A typical protection application for a two-winding transformer insingle breaker arrangement

1MRK 504 134-UEN - Section 2Application

23Application Manual

Page 30: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

RET650 A05 - 3 Winding Transformer protection 20AI 2*(6I+4U)

W1

T3W PDIF

87T 3Id/I

CC RBRF

50BF 3I> BF

CC RBRF

50BF 3I> BF

OC4 PTOC

50/51 3I>

OC4 PTOC

51/67 3I>

CC RPLD

52PD PD

CC RBRF

50BF 3I> BF

CC RPLD

52PD PD

EF4 PTOC

51N IN>

CC RPLD

52PD PD

TR PTTR

49 Ith

TR PTTR

49 Ith

V MSQI

Meter.

C MSQI

Meter.

V MMXU

Meter.

C MMXU

Meter.

CV MMXN

Meter.

V MSQI

Meter.

C MSQI

Meter.

V MMXU

Meter.

C MMXU

Meter.

CV MMXN

Meter.

TCS SCBR

Cond

TCS SCBR

Cond

TCS SCBR

Cond

SPVN ZBAT

Cond

TR8 ATCC

90 U

TCM YLTC

84

UV2 PTUV

27 U<

OV2 PTOV

59 U>

PH PIOC

50 3I>>

TR PTTR

49 Ith

REF PDIF

87N IdN/I

Other configured functions

REF PDIF

87N IdN/I

REF PDIF

87N IdN/I

OEX PVPH

24 U/f>

OC4 PTOC

51/67 3I>

EF4 PTOC

51N/67N IN>

EF4 PTOC

51N/67N IN>

DRP RDRE

Mont.

CV MMXN

Meter.

YY

@

ROV2 PTOV

59N 3UO>

35 kV Bus

110 kV Bus

10 kV Bus

IEC61850

ANSI IEC

Function Onin Settings

IEC61850

ANSI IEC

Function Off in Settings

Transformer Data:40/40/15 MVA

110±11*1.5% / 36.75 / 10.5 kV210/628/825 A

YNyn0d5

110kV/100V

300/1

1000/1

800/1

800/1

300/1

10kV/100V

35kV/100V

1000/1W3 W2

IEC09000646-3-en.vsd

IEC09000646 V3 EN

Figure 3: A typical protection application for a three-winding transformer insingle breaker arrangement

Section 2 1MRK 504 134-UEN -Application

24Application Manual

Page 31: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

RET650 A07 – OLTC Control for 1 or 2 Transformers 10AI (6I+4U)

TR PTTR

49 Ith

EF4 PTOC

51N/67N IN>

CV MMXN

Meter.

T1

OC4 PTOC

50/51 3I>

ETP MMTR

Meter.

ROV PTOV

59N 3U0>

T2TRx ATCC

90 UUV2 PTOV

27 U<

OV2 PTOV

59 U>

TR PTTR

49 Ith

EF4 PTOC

51N/67N IN>

CV MMXN

Meter.OC4 PTOC

50/51 3I>

ETP MMTR

Meter.

ROV2 PTOV

59N 3Uo>TR8 ATCC

90 U

UV2 PTUV

27 U<

OV2 PTOV

59 U>

T1

T2

YY

Ø

YY

Ø

TCM YLTC

84

TCM YLTC

84

TCS SCBR

Cond

TCS SCBR

Cond

SPVN ZBAT

Cond

Other configured functions

DRP RDRE

Mont.

T1 Data:20 MVA

110±11*1.5% / 21 kV105 / 550 A

YNd5XT=11 %

T2 Data:20 MVA

110±11*1.5% / 21 kV105 / 550 A

YNd5XT=11 %

20 kV Bus #1 20 kV Bus #2

IEC61850

ANSI IEC

Function Enabled in Settings

IEC61850

ANSI IEC

Function Disabled in Settings

600/1

20kV/100V

600/1

20kV/100V

W2

W2

IEC09000647-4-en.vsd

IEC09000647 V4 EN

Figure 4: A typical tap changer control application for one or two transformers

1MRK 504 134-UEN - Section 2Application

25Application Manual

Page 32: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

2.2 Available functions

2.2.1 Main protection functionsIEC 61850 orFunction name

ANSI Function description Transformer

RET

650

RET

650

(A01

)2W

/1C

B

RET

650

(A05

)3W

/1C

B

RET

650

(A07

)O

LTC

Differential protection

T2WPDIF 87T Transformer differential protection, two winding 0–1 1

T3WPDIF 87T Transformer differential protection, three winding 0–1 1

REFPDIF 87N Restricted earth fault protection, low impedance 0–3 2 3

HZPDIF 87 1Ph High impedance differential protection 0–2 2 2

Impedance protection

ZMRPSB 68 Power swing detection 0–1

ZGCPDIS 21G Underimpedance protection for generators andtransformers

0–1

LEPDIS Load encroachment 0–1

2.2.2 Back-up protection functionsIEC 61850 orFunction name

ANSI Function description Transformer

RET

650

RET

650

(A01

)2W

/1C

B

RET

650

(A05

)3W

/1C

B

RET

650

(A07

)O

LTC

Current protection

PHPIOC 50 Instantaneous phase overcurrent protection, 3–phase output

0–3 2 3

OC4PTOC 51/67 Four step directional phase protection, 3–phaseoutput

0–3 2 3 2

EFPIOC 50N Instantaneous residual overcurrent protection 0–3 2 3

EF4PTOC 51N/67N Four step residual overcurrent protection, zero/negative sequence direction

0–3 2 3 2

TRPTTR 49 Thermal overload protection, two time constants 0–3 2 3 2

CCRBRF 50BF Breaker failure protection, 3–phase activationand output

0–3 2 3

CCRPLD 52PD Pole discordance protection 0–3 2 3

GUPPDUP 37 Directional underpower protection 0–2 1 1 2

GOPPDOP 32 Directional overpower protection 0–2 1 1 2

DNSPTOC 46 Negative sequence based overcurrent function 0–2 1 2

Table continues on next page

Section 2 1MRK 504 134-UEN -Application

26Application Manual

Page 33: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

IEC 61850 orFunction name

ANSI Function description Transformer

RET

650

RET

650

(A01

)2W

/1C

B

RET

650

(A05

)3W

/1C

B

RET

650

(A07

)O

LTC

Voltage protection

UV2PTUV 27 Two step undervoltage protection 0–2 1 1 2

OV2PTOV 59 Two step overvoltage protection 0–2 1 1 2

ROV2PTOV 59N Two step residual overvoltage protection 0–2 1 1 2

OEXPVPH 24 Overexcitation protection 0–1 1 1

Frequency protection

SAPTUF 81 Underfrequency function 0–4 4 4 4

SAPTOF 81 Overfrequency function 0–4 4 4 4

SAPFRC 81 Rate-of-change frequency protection 0–4 2 2 4

2.2.3 Control and monitoring functionsIEC 61850 or Functionname

ANSI Function description Transformer

RET

650

RET

650

(A01

)2W

/1C

B

RET

650

(A05

)3W

/1C

B

RET

650

(A07

)O

LTC

Control

TR8ATCC 90 Automatic voltage control for tap changer,parallel control

0–2 1 1 2

TCMYLTC 84 Tap changer control and supervision, 6binary inputs

0–2 1 1 2

SLGGIO Logic Rotating Switch for function selectionand LHMI presentation

15 15 15 15

VSGGIO Selector mini switch 20 20 20 20

DPGGIO IEC 61850 generic communication I/Ofunctions double point

16 16 16 16

SPC8GGIO Single point generic control 8 signals 5 5 5 5

AUTOBITS AutomationBits, command function forDNP3.0

3 3 3 3

I103CMD Function commands for IEC60870-5-103 1 1 1 1

I103IEDCMD IED commands for IEC60870-5-103 1 1 1 1

I103USRCMD Function commands user defined forIEC60870-5-103

4 4 4 4

I103GENCMD Function commands generic forIEC60870-5-103

50 50 50 50

I103POSCMD IED commands with position and select forIEC60870-5-103

50 50 50 50

Table continues on next page

1MRK 504 134-UEN - Section 2Application

27Application Manual

Page 34: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

IEC 61850 or Functionname

ANSI Function description Transformer

RET

650

RET

650

(A01

)2W

/1C

B

RET

650

(A05

)3W

/1C

B

RET

650

(A07

)O

LTC

Apparatus control and Interlocking

APC8 Apparatus control for single bay, max 8 app.(1CB) incl. interlocking

0–1

SCILO 3 Logical node for interlocking

BB_ES 3 Interlocking for busbar earthing switch

A1A2_BS 3 Interlocking for bus-section breaker

A1A2_DC 3 Interlocking for bus-section disconnector

ABC_BC 3 Interlocking for bus-coupler bay

BH_CONN 3 Interlocking for 1 1/2 breaker diameter

BH_LINE_A 3 Interlocking for 1 1/2 breaker diameter

BH_LINE_B 3 Interlocking for 1 1/2 breaker diameter

DB_BUS_A 3 Interlocking for double CB bay

DB_BUS_B 3 Interlocking for double CB bay

DB_LINE 3 Interlocking for double CB bay

ABC_LINE 3 Interlocking for line bay

AB_TRAFO 3 Interlocking for transformer bay

SCSWI Switch controller

QCBAY Bay control 1 1 1 1

LOCREM Handling of LR-switch positions 1 1 1 1

LOCREMCTRL LHMI control of Permitted Source ToOperate (PSTO)

1 1 1 1

CBC2 Circuit breaker control for 2CB 0–1 1

CBC3 Circuit breaker control for 3CB 0–1 1

CBC4 Circuit breaker control for 4CB 0–1 1

Secondary system supervision

SDDRFUF Fuse failure supervision 0–1

TCSSCBR Breaker close/trip circuit monitoring 3 3 3 3

Logic

SMPPTRC 94 Tripping logic, common 3–phase output 1–3 2 3 2

TMAGGIO Trip matrix logic 12 12 12 12

OR Configurable logic blocks 283 283 283 283

INVERTER Configurable logic blocks 140 140 140 140

PULSETIMER Configurable logic blocks 40 40 40 40

GATE Configurable logic blocks 40 40 40 40

XOR Configurable logic blocks 40 40 40 40

LOOPDELAY Configurable logic blocks 40 40 40 40

Table continues on next page

Section 2 1MRK 504 134-UEN -Application

28Application Manual

Page 35: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

IEC 61850 or Functionname

ANSI Function description Transformer

RET

650

RET

650

(A01

)2W

/1C

B

RET

650

(A05

)3W

/1C

B

RET

650

(A07

)O

LTC

TIMERSET Configurable logic blocks 40 40 40 40

AND Configurable logic blocks 280 280 280 280

SRMEMORY Configurable logic blocks 40 40 40 40

RSMEMORY Configurable logic blocks 40 40 40 40

Q/T Configurable logic blocks Q/T 0–1

ANDQT Configurable logic blocks Q/T 120

ORQT Configurable logic blocks Q/T 120

INVERTERQT Configurable logic blocks Q/T 120

XORQT Configurable logic blocks Q/T 40

SRMEMORYQT Configurable logic blocks Q/T 40

RSMEMORYQT Configurable logic blocks Q/T 40

TIMERSETQT Configurable logic blocks Q/T 40

PULSETIMERQT Configurable logic blocks Q/T 40

INVALIDQT Configurable logic blocks Q/T 12

INDCOMBSPQT Configurable logic blocks Q/T 20

INDEXTSPQT Configurable logic blocks Q/T 20

FXDSIGN Fixed signal function block 1 1 1 1

B16I Boolean 16 to Integer conversion 16 16 16 16

B16IFCVI Boolean 16 to Integer conversion with logicnode representation

16 16 16 16

IB16A Integer to Boolean 16 conversion 16 16 16 16

IB16FCVB Integer to Boolean 16 conversion with logicnode representation

16 16 16 16

TEIGGIO Elapsed time integrator with limittransgression and overflow supervision

12 12 12 12

Monitoring

CVMMXN Measurements 6 6 6 6

CMMXU Phase current measurement 10 10 10 10

VMMXU Phase-phase voltage measurement 6 6 6 6

CMSQI Current sequence component measurement 6 6 6 6

VMSQI Voltage sequence measurement 6 6 6 6

VNMMXU Phase-neutral voltage measurement 6 6 6 6

AISVBAS Function block for service valuespresentation of the analog inputs

1 1 1 1

TM_P_P2 Function block for service valuespresentation of primary analog inputs600TRM

1 1 1 1

Table continues on next page

1MRK 504 134-UEN - Section 2Application

29Application Manual

Page 36: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

IEC 61850 or Functionname

ANSI Function description Transformer

RET

650

RET

650

(A01

)2W

/1C

B

RET

650

(A05

)3W

/1C

B

RET

650

(A07

)O

LTC

AM_P_P4 Function block for service valuespresentation of primary analog inputs 600AIM

1 1 1 1

TM_S_P2 Function block for service valuespresentation of secondary analog inputs600TRM

1 1 1 1

AM_S_P4 Function block for service valuespresentation of secondary analog inputs600AIM

1 1 1 1

CNTGGIO Event counter 5 5 5 5

L4UFCNT Event counter with limit supervision 12 12 12 12

DRPRDRE Disturbance report 1 1 1 1

AnRADR Analog input signals 4 4 4 4

BnRBDR Binary input signals 6 6 6 6

SPGGIO IEC 61850 generic communication I/Ofunctions

64 64 64 64

SP16GGIO IEC 61850 generic communication I/Ofunctions 16 inputs

16 16 16 16

MVGGIO IEC 61850 generic communication I/Ofunctions

16 16 16 16

MVEXP Measured value expander block 66 66 66 66

SPVNZBAT Station battery supervision 0–1 1 1 1

SSIMG 63 Insulation gas monitoring function 0–2 2 2 2

SSIML 71 Insulation liquid monitoring function 0–2 2 2 2

SSCBR Circuit breaker condition monitoring 0–3 2 3 2

I103MEAS Measurands for IEC60870-5-103 1 1 1 1

I103MEASUSR Measurands user defined signals forIEC60870-5-103

3 3 3 3

I103AR Function status auto-recloser forIEC60870-5-103

1 1 1 1

I103EF Function status earth-fault forIEC60870-5-103

1 1 1 1

I103FLTPROT Function status fault protection forIEC60870-5-103

1 1 1 1

I103IED IED status for IEC60870-5-103 1 1 1 1

I103SUPERV Supervison status for IEC60870-5-103 1 1 1 1

I103USRDEF Status for user defined signals forIEC60870-5-103

20 20 20 20

Metering

PCGGIO Pulse counter 16 16 16 16

ETPMMTR Function for energy calculation and demandhandling

3 3 3 3

Section 2 1MRK 504 134-UEN -Application

30Application Manual

Page 37: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

2.2.4 Station communicationIEC 61850 or Functionname

ANSI Function description Transformer

RET

650

RET

650

(A01

)2W

/1C

B

RET

650

(A05

)3W

/1C

B

RET

650

(A07

)O

LTC

Station communication

IEC61850-8-1 IEC 61850 communication protocol 1 1 1 1

DNPGEN DNP3.0 communication general protocol 1 1 1 1

RS485DNP DNP3.0 for RS-485 communicationprotocol

1 1 1 1

CH1TCP DNP3.0 for TCP/IP communicationprotocol

1 1 1 1

CH2TCP DNP3.0 for TCP/IP communicationprotocol

1 1 1 1

CH3TCP DNP3.0 for TCP/IP communicationprotocol

1 1 1 1

CH4TCP DNP3.0 for TCP/IP communicationprotocol

1 1 1 1

OPTICALDNP DNP3.0 for optical RS-232 communicationprotocol

1 1 1 1

MSTSERIAL DNP3.0 for serial communication protocol 1 1 1 1

MST1TCP DNP3.0 for TCP/IP communicationprotocol

1 1 1 1

MST2TCP DNP3.0 for TCP/IP communicationprotocol

1 1 1 1

MST3TCP DNP3.0 for TCP/IP communicationprotocol

1 1 1 1

MST4TCP DNP3.0 for TCP/IP communicationprotocol

1 1 1 1

RS485GEN RS485 1 1 1 1

OPTICALPROT Operation selection for optical serial 1 1 1 1

RS485PROT Operation selection for RS485 1 1 1 1

DNPFREC DNP3.0 fault records for TCP/IPcommunication protocol

1 1 1 1

OPTICAL103 IEC60870-5-103 Optical serialcommunication

1 1 1 1

RS485103 IEC60870-5-103 serial communication forRS485

1 1 1 1

GOOSEINTLKRCV Horizontal communication via GOOSE forinterlocking

59 59 59 59

GOOSEBINRCV GOOSE binary receive 4 4 4 4

GOOSEVCTRCONF GOOSE VCTR configuration for send andreceive

1 1 1 1

VCTRSEND Voltage control sending block for GOOSE 1 1 1 1

GOOSEVCTRRCV Voltage control receiving block for GOOSE 3 3 3 3

Table continues on next page

1MRK 504 134-UEN - Section 2Application

31Application Manual

Page 38: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

IEC 61850 or Functionname

ANSI Function description Transformer

RET

650

RET

650

(A01

)2W

/1C

B

RET

650

(A05

)3W

/1C

B

RET

650

(A07

)O

LTC

ETHFRNTETHLAN1GATEWAY

Ethernet configuration of front port, LAN1port and gateway

1 1 1 1

ETHLAN1_AB Ethernet configuration of LAN1 port 1

PRPSTATUS System component for parallellredundancy protocol

1

CONFPROT IED Configuration Protocol 1 1 1 1

ACTIVLOG Activity logging parameters 1 1 1 1

SECALARM Component for mapping security eventson protocols such as DNP3 and IEC103

1 1 1 1

AGSAL Generic security application component 1 1 1 1

GOOSEDPRCV GOOSE function block to receive a doublepoint value

32 32 32 32

GOOSEINTRCV GOOSE function block to receive aninteger value

32 32 32 32

GOOSEMVRCV GOOSE function block to receive ameasurand value

16 16 16 16

GOOSESPRCV GOOSE function block to receive a singlepoint value

64 64 64 64

2.2.5 Basic IED functionsIEC 61850/Functionblock name

Function description

Basic functions included in all products

INTERRSIG Self supervision with internal event list 1

SELFSUPEVLST Self supervision with internal event list 1

TIMESYNCHGEN Time synchronization 1

SNTP Time synchronization 1

DTSBEGIN, DTSEND,TIMEZONE

Time synchronization, daylight saving 1

IRIG-B Time synchronization 1

SETGRPS Setting group handling 1

ACTVGRP Parameter setting groups 1

TESTMODE Test mode functionality 1

CHNGLCK Change lock function 1

TERMINALID IED identifiers 1

PRODINF Product information 1

SYSTEMTIME System time 1

Table continues on next page

Section 2 1MRK 504 134-UEN -Application

32Application Manual

Page 39: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

IEC 61850/Functionblock name

Function description

RUNTIME IED Runtime comp 1

PRIMVAL Primary system values 1

SMAI_20_1 -SMAI_20_12

Signal matrix for analog inputs 2

3PHSUM Summation block 3 phase 12

GBASVAL Global base values for settings 6

ATHSTAT Authority status 1

ATHCHCK Authority check 1

AUTHMAN Authority management 1

FTPACCS FTPS access with password 1

DOSFRNT Denial of service, frame rate control for front port 1

DOSLAN1 Denial of service, frame rate control for LAN1A and LAN1B ports 1

DOSSCKT Denial of service, socket flow control 1

SAFEFILECOPY Safe file copy function 1

BCSCONF Basic communication system 1

SECALARM Component for mapping security events on protocols such as DNP3 and IEC103 1

2.3 RET650 application examples

2.3.1 Adaptation to different applications

The IED can be used in a wide range of applications. This is done by selectingfrom the comprehensive function library in the IED. A selection of commonapplications are described below.

• Application 1: Two-winding HV/MV, Y/Δ-transformer; HV:solidly earthed,MV:high impedance earthed

• Application 2: Two-winding HV/MV, Y/Y-transformer; HV:solidly earthed,MV:high impedance earthed

• Application 3: Three-winding HV/MV1/MV2, Y/Y/Δ- transformer;HV:solidly earthed, MV1:solidly earthed, MV2:high impedance earthed

• Application 4: Three-winding HV/MV1/MV2, Y/Y/Δ-transformer; HV:solidlyearthed, MV1:solidly earthed, MV2:solidly earthed

2.3.2 Two-winding HV/MV, Y/Δ-transformerThis application example is a two-winding HV/MV, Y/Δ-transformer with thefollowing properties:

1MRK 504 134-UEN - Section 2Application

33Application Manual

Page 40: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

• High voltage solidly earthed• Medium voltage high impedance earthed

11

1

33

IEC09000435-1-en.vsd

RET650

Ph-Ph

IEC09000435 V1 EN

Figure 5: Two-winding HV/MV transformer, Y/Δ-transformer; HV:solidlyearthed, MV:high impedance earthed

Table 1: Typical data for the transformer application

Item DataHigh voltage side system voltage (UN,HV) 110 – 220 kV

Medium voltage side system voltage (UM,HV) 11 – 110 kV

Transformer rated power (SN) 15 – 150 MVA

On line tap changer On the HV-side winding

Short circuit power level infeed at HV-side 500 – 10 000 MVA

Short circuit power level infeed at MV-side 0 – 5 000 MVA

2.3.3 Two-winding HV/MV, Y/Y-transformerThis application example is a two-winding HV/MV Y/Y-transformer with thefollowing properties:

• High voltage solidly earthed• Medium voltage high impedance earthed

Section 2 1MRK 504 134-UEN -Application

34Application Manual

Page 41: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

1

33

1

1

1

IEC09000436-1-en.vsd

Ph-Ph

RET650

IEC09000436 V1 EN

Figure 6: Two-winding HV/MV, Y/Y-transformer; HV:solidly earthed, MV:highimpedance earthed

Table 2: Typical data for the transformer application

Item DataHigh voltage side system voltage (UN,HV) 110 – 220 kV

Medium voltage side system voltage (UM,HV) 11 – 110 kV

Transformer rated power (SN) 15 – 150 MVA

On line tap changer On the HV-side winding

Short circuit power level infeed at HV-side 500 – 10 000 MVA

Short circuit power level infeed at MV-side 0 – 5 000 MVA

2.3.4 Functionality tableThe proposal for functionality choice for the different application cases are shownin table 3.

In the table the recommendations have the following meaning:

• On: It is recommended to have the function activated in the application• Off: It is recommended to have the function deactivated in the application• Application dependent: The decision to have the function activated or not is

dependent on the specific conditions in each case

Application 1 and Application 2 in table 3 are according toapplication examples given in previous sections.

1MRK 504 134-UEN - Section 2Application

35Application Manual

Page 42: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Table 3: Selection of functions in different applications

Function Application 1 Application 2Transformer differential protection, twowinding T2WPDIF

On On

Restricted earth fault protection REFPDIF(instance 1)

On On

Restricted earth fault protection REFPDIF(instance 2)

Application dependent Application dependent

Instantaneous phase overcurrent protectionPHPIOC (instance 1 on HV side)

On On

Instantaneous phase overcurrent protectionPHPIOC (instance 2 on MV side)

Off Off

Four step phase overcurrent protectionOC4PTOC (instance 1 on HV-side)

On On

Four step phase overcurrent protectionOC4PTOC (instance 2 on MV-side)

On On

Instantaneous residual overcurrentprotection EFPIOC (instance 1 on HV-sideneutral point)

On On

Instantaneous residual overcurrentprotection EFPIOC (instance 2 on MV-sideneutral point)

Off Off

Four step residual overcurrent protectionEF4PTOC (instance 1 on HV-side)

On On

Four step residual overcurrent protectionEF4PTOC (instance 2 on MV-side)

Application dependent Application dependent

Thermal overload protection TRPTTR(instance 1 on HV-side)

On On

Thermal overload protection, two timeconstants TRPTTR (instance 2 on MV-side)

Application dependent Application dependent

Breaker failure protection CCRBRF(instance 1 on HV-side)

On On

Breaker failure protection CCRBRF(instance 2 on MV-side)

On On

Pole discordance protection CCRPLD Application dependent Application dependent

Directional under-power protectionGUPPDUP

Application dependent Application dependent

Directional over-power protectionGOPPDOP

Application dependent Application dependent

Negative sequence based overcurrentprotection DNSPTOC

On On

Two step undervoltage protection UV2PTUV Application dependent Application dependent

Two step overvoltage protection OV2PTOV Application dependent Application dependent

Two step residual overvoltage protectionROV2PTOV

On On

Overexcitation protection OEXPVPH Off Off

Under frequency protection SAPTUF Application dependent Application dependent

Over frequency protection SAPTOF Application dependent Application dependent

Table continues on next page

Section 2 1MRK 504 134-UEN -Application

36Application Manual

Page 43: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Function Application 1 Application 2Rate-of-change frequency protectionSAPFRC

Application dependent Application dependent

Breaker close/trip circuit monitoringTCSSCBR

On On

Automatic voltage control for tap changer,single control TR1ATCC

On On

2.3.5 Three-winding HV/MV1/MV2, Y/Y/Δ-transformerThis application example is a three-winding HV/MV1/MV2, Y/Y/Δ-transformerwith the following properties:

• High voltage solidly earthed• Medium voltage 1 solidly earthed• Medium voltage 2 Delta

IEC09000437-2-en.vsd

1

3

33

1

3

3

1

1

RET650

IEC09000437 V2 EN

Figure 7: Three-winding HV/MV1/MV2, Y/Y/Δ-transformer; HV:solidlyearthed, MV1:solidly earthed, MV2: Delta

Table 4: Typical data for the transformer application

Item DataHigh voltage side system voltage (UN,HV) 110 – 400 kV

Medium voltage side1 system voltage (UM1,HV) 11 – 110 kV

Medium voltage side2 system voltage (UM2,HV) 11 – 110 kV

Transformer rated power (SN) 25 – 500 MVA

On line tap changer On the HV-side winding

Short circuit power level infeed at HV-side 500 – 10 000 MVA

Short circuit power level infeed at MV1-side 0 – 5 000 MVA

Short circuit power level infeed at MV2-side 0 – 5 000 MVA

1MRK 504 134-UEN - Section 2Application

37Application Manual

Page 44: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

2.3.6 Three-winding HV/MV1/MV2, Y/Y/Δ-transformerThis application example is a three-winding HV/MV1/MV2, Y/Y/Δ-transformerwith the following properties:

• High voltage solidly earthed• Medium voltage 1 solidly earthed• Medium voltage 2 Delta

IEC09000438-2-en.vsd

RET650

1

3

33

1

3

3

1

1

.

IEC09000438 V2 EN

Figure 8: Three-winding HV/MV1/MV2, Y/Y/Δ-transformer; HV:solidlyearthed, MV1:solidly earthed, MV2:Delta

Table 5: Typical data for the transformer application

Item DataHigh voltage side system voltage (UN,HV): 110 – 400 kV

Medium voltage side1 system voltage (UM1,HV) 11 – 110 kV

Medium voltage side2 system voltage (UM2,HV) 11 – 110 kV

Transformer rated power (SN) 25 – 500 MVA

On line tap changer On the HV-side winding

Short circuit power level infeed at HV-side 500 – 10 000 MVA

Short circuit power level infeed at MV1-side 0 – 5 000 MVA

Short circuit power level infeed at MV2-side 0 – 5 000 MVA

2.3.7 Functionality tableThe proposal for functionality choice for the different application cases are shownin table 6. In the table the recommendations has the following meaning:

Section 2 1MRK 504 134-UEN -Application

38Application Manual

Page 45: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

• On: It is recommended to have the function activated in the application• Off: It is recommended to have the function deactivated in the application• Application dependent: The decision to have the function activated or not is

dependent on the specific conditions in each case

Application 3 and Application 4 in table 6 are according toapplication examples given in previous sections.

Table 6: Selection of functions in different applications

Function Application 3 Application 4Transformer differential protection, three winding T3WPDIF On On

Restricted earth fault protection REFPDIF (instance 1 on HV-side) On On

Restricted earth fault protection REFPDIF (instance 2 on MV1-side) On Application dependent

Restricted earth fault protection REFPDIF (instance 3 on MV2-side) Application dependent Application dependent

Instantaneous phase overcurrent protection PHPIOC (instance 1 on HV side) On On

Instantaneous phase overcurrent protection PHPIOC (instance 2 on MV1-side)

Off Off

Instantaneous phase overcurrent protection PHPIOC (instance 3 on MV2-side)

Off Off

Four step phase overcurrent protection OC4PTOC (instance 1 on HV-side) On On

Four step phase overcurrent protection OC4PTOC (instance 2 on MV1-side) On On

Four step phase overcurrent protection OC4PTOC (instance 3 on MV2-side) On On

Instantaneous residual overcurrent protection EFPIOC (instance 1 on HV-side)

On On

Instantaneous residual overcurrent protection EFPIOC (instance 2 on MV1-side)

Application dependent Application dependent

Instantaneous residual overcurrent protection EFPIOC (instance 3 on MV2-side)

Off Application dependent

Four step residual overcurrent protection EF4PTOC (HV side neutral point) On On

Four step residual overcurrent protection EF4PTOC (MV1 side neutral point) On On

Four step residual overcurrent protection EF4PTOC (MV2 side neutral point) Application dependent On

Thermal overload protection, two time constants TRPTTR (instance 1 on HV-side)

On On

Thermal overload protection, two time constants TRPTTR (instance 2 onMV1-side)

Application dependent Application dependent

Thermal overload protection, two time constants TRPTTR (instance 3 onMV2-side)

Application dependent Application dependent

Breaker failure protection CCRBRF (instance 1 on HV-side) On On

Breaker failure protection CCRBRF (instance 2 on MV1-side) On On

Breaker failure protection CCRBRF (instance 3 on MV2-side) On On

Pole discordance protection CCRPLD Application dependent Application dependent

Directional under-power protection GUPPDUP Application dependent Application dependent

Directional over-power protection GOPPDOP Application dependent Application dependent

Table continues on next page

1MRK 504 134-UEN - Section 2Application

39Application Manual

Page 46: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Function Application 3 Application 4Two step undervoltage protection UV2PTUV Application dependent Application dependent

Two step overvoltage protection OV2PTOV Application dependent Application dependent

Two step residual overvoltage protection ROV2PTOV On On

Overexcitation protection OEXPVPH On On

Under frequency protection SAPTUF Application dependent Application dependent

Over frequency protection SAPTOF Application dependent Application dependent

Rate-of-change of frequency protection SAPFRC Application dependent Application dependent

Breaker close/trip circuit monitoring TCSSCBR On On

Automatic voltage control for tap changer, single control TR1ATCC On On

Section 2 1MRK 504 134-UEN -Application

40Application Manual

Page 47: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Section 3 RET650 setting examples

3.1 Setting example for a two-winding HV/MVtransformer, Y/Δ-transformer

The application example has a 145/22 kV transformer as shown in figure 9.

11

1

33

Ph-Ph

145 kV 22 kV

IEC09000446-1-en.vsd

RET650

IEC09000446 V1 EN

Figure 9: Two-winding HV/MV transformer, Y/Δ-transformer

Table 7: Typical data for the transformer applicationThe following data is assumed:Item DataTransformer rated power SN 60 MVA

Transformer high voltage side rated voltage UN1 145 kV ±9 · 1.67 % (with on load tap changer)

Transformer low voltage side rated voltage UN2 22 kV

Transformer vector group YNd11

Transformer impedance voltage at tap changermid point: ek

12 %

Maximum allowed continuous overload 1.30 · SN

Phase CT ratio at 145 kV level 300/1 A

CT at 145 kV earth point 300/1 A

Phase CT ratio at 22 kV level 2 000/1 A

22 kV VT ratio/22

30 11

3. 0 11

3./ kV

High positive sequence source impedance at theHV side

j10 Ω (about 2 100 MVA)

Low positive sequence source impedance at theHV side

j3.5 Ω (about 6 000 MVA)

Table continues on next page

1MRK 504 134-UEN - Section 3RET650 setting examples

41Application Manual

Page 48: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Item DataHigh zero sequence source impedance at theHV side

j20 Ω

Low zero sequence source impedance at the HVside

j15 Ω

Positive sequence source impedance at the LVside

∞ (no generation in the 22 kV network)

Only settings that need adjustment due to the specific applicationare described in setting examples. It is recommended to keep thedefault values for all settings that are not described. Refer to thetechnical manual for setting tables for each protection and controlfunction.

Refer to the setting guideline section in the Application manual forguidelines on how to set functions that are not presented in thesetting examples.

Use the parameter setting tool in PCM600 to set the IED accordingto the calculations for the particular application.

3.1.1 Calculating general settings for analogue inputs 8I 2UThe analogue input module has the capability of 8 current inputs (1 A) and 2voltage inputs.

The 145 kV current CTs (three phase current transformer group) are connected toinputs 1 – 3 (L1, L2, L3).

The 22 kV current CTs (three phase current transformer group) are connected toinputs 4 – 6 (L1, L2, L3).

The 145 kV neutral point CT is connected to input 7 (IN).

The input 8 is not used. The input is used for connection of the low voltage sideneutral point CT (not in this application)

The 22 kV phase-to-phase (L1 – L2) VT is connected to input 9.

The 22 kV open delta connected VT (residual voltage) is connected to input 10.

1. Set the 145 kV current transformer input 1.1.1. Set CTStarPoint1 to ToObject

Section 3 1MRK 504 134-UEN -RET650 setting examples

42Application Manual

Page 49: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

(The CT secondary is earthed towards the protected transformer)1.2. Set CTSec1 to 1 A

(The rated secondary current of the CT)1.3. Set CTPrim1 to 300 A

(The rated primary current of the CT)2. Set current inputs 2 and 3 to the same values as for current input 1.3. Set the 22 kV current transformer input 4.

3.1. Set CTStarPoint4 to ToObject(The CT secondary is earthed towards the protected transformer)

3.2. Set CTSec4 to 1 A(The rated secondary current of the CT)

3.3. Set CTPrim4 to 2000 A(The rated primary current of the CT)

4. Set current inputs 5 and 6 to the same values as for current input 4.5. Set the 145 kV neutral point current transformer input 7.

5.1. Set CTStarPoint7 to ToObject(The CT secondary is earthed towards the protected line)

5.2. Set CTSec7 to 1 A(The rated secondary current of the CT)

5.3. Set CTPrim7 to 300 A(The rated primary current of the CT)

Current input 8 is intended for connection of a low voltageside neutral point CT. In this application the input is not used.

6. Set the voltage transformer inputs 9 and 10.6.1. Set VTSec9 to 110 V

(The rated secondary voltage of the VT, given as phase-phase voltage)6.2. Set VTPrim9 to 22 kV

(The rated secondary voltage of the VT, given as phase-phase voltage)6.3. Set VTSec10 to 110 V/√3

(The rated secondary voltage of the VT, given as phase-phase voltage)6.4. Set VTPrim10 to 22 kV

(The rated secondary voltage of the VT, given as phase-phase voltage)

3.1.2 Calculating settings for global base values GBASVALEach function uses primary base values as a reference for the settings. The basevalues are defined in Global base values for setting GBASVAL function. It ispossible to include up to GBASVAL function. In this application GBASVALinstance 1 is used to define the base for 145 kV inputs and GBASVAL instance 2for 22 kV inputs.

1MRK 504 134-UEN - Section 3RET650 setting examples

43Application Manual

Page 50: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

For transformer protection it is recommended to set the base parameters accordingto the power transformer primary rated values:

1. Set Global Base 11.1. Set IBase to 239 A1.2. Set UBase to 145 kV1.3. Set SBase to 60 MVA (SBase=√3·UBase·IBase)

2. Set Global Base 22.1. Set IBase to 1575 A2.2. Set UBase to 22 kV2.3. Set SBase to 60 MVA (SBase=√3·UBase·IBase)

There are six instances of global base GBASVAL function, eachinstance includes the three parameters: IBase, UBase, SBase. TheGlobalBaseSel setting which can be found in the different IEDfunctions references a specific instance of the GBASVAL function.

3.1.3 Calculating settings for transformer differential protectionT2WPDIF

1. Set GlobalBaseSelW1 to 1 (HV)2. Set GlobalBaseSelW2 to 2 (LV)

To relate the function settings to the rated data of the transformer, the twowindings should be referenced to GlobalBaseSelW1 and GlobalBaseSelW2 1(HV-side) and 2 (LV-side).

3. Set the vector group of the transformer3.1. Set ConnectTypeW1 to WYE (Y)3.2. Set ConnectTypeW2 to Delta (D)3.3. Set ClockNumberW2 to 11 [30 deg lead]

4. Set system residual current elimination4.1. Set ZSCurrSubtrW1 to On4.2. Set ZSCurrSubtrW2 to Off

The transformer is solidly earthed at the 145 kV side. In case of an earth-faultin the 145 kV system residual current flows from the transformer. Thisresidual current is seen as a differential current. To prevent an unwanted tripduring an external earth-fault the zero sequence current shall be eliminatedfrom the measured transformer current. Since zero sequence currents can notflow in a delta winding this elimination is only needed for the solidlyearthedY winding.

5. Set I2/I1Ratio to 15 % (default)

Section 3 1MRK 504 134-UEN -RET650 setting examples

44Application Manual

Page 51: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

When the transformer is energized an inrush current occurs. This current isseen as a differential current. With a combination of the second harmonicrestraint and the waveform restraint methods it is possible to get a protectionwith high security and stability against inrush effects and at the same timemaintain high performance in case of heavy internal faults even if the currenttransformers are saturated. Both these restraint methods are used. It isrecommended to use the parameter I2/I1Ratio = 15% as the default value incase no special reasons exist to choose a different value.

6. Set I5/I1Ratio to 25 % (default)When the transformer is overexcited due to high voltage and/or low networkfrequency, the excitation current increases significantly. This current is seenas a differential current. The differential protection function is provided witha fifth harmonic restraint to prevent the protection from operation during anoverexcitation condition of the power transformer. It is recommended to usethe parameter I5/I1Ratio = 25% as the default value in case no special reasonsexist to choose a different value.

7. Set CrossBlockEn to OnIf any of the above mentioned restrain functions (waveform restrain, secondharmonic restrain or fifth harmonic restrain) is activated in one phase, cross-blocking can be used to prevent operation of the differential protection in theother phases as well. It is recommended to set the cross-blocking on.

8. Set restrain characteristics8.1. Set EndSection1 to 1.25 IBase8.2. Set EndSection2 to 3 IBase8.3. Set SlopeSection2 to 40 %8.4. Set SlopeSection3 to 80 %

The characteristic of the restrained and unrestrained differential protection isshown in figure 10. The differential current limit for operation of theprotection is shown as a function of the restrain current. The restrain currentis equal to the highest transformer phase current. The restrain characteristic isdefined by the parameters: IdMin, EndSection1, EndSection2, SlopeSection2and SlopeSection3. The settings of EndSection1, EndSection2, SlopeSection2and SlopeSection3 are defined as advanced parameters and the default valuesare recommended.

1MRK 504 134-UEN - Section 3RET650 setting examples

45Application Manual

Page 52: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Section 1

Operate conditionally

UnrestrainedLimit

Section 2 Section 3

Restrain

Operate unconditionally

5

4

3

2

1

00 1 2 3 4 5

IdMin

EndSection1

EndSection2restrain current

[ times I1r ]

operate current[ times I1r ]

SlopeSection2

SlopeSection3

en05000187.vsdGUID-F6F9E16D-A762-4518-A9E1-A4B2A962821B V1 EN

Figure 10: Transformer differential protection operation characteristic

9. Set IdMin to ≥0.3 IBaseDuring normal operation there is a ”false” differential current measured bythe protection due to the following:• Deviation tap changer position compared to the nominal transformer ratio• Difference in current transformer error

The measured differential current with the tap changer position in the extremepositions can be calculated:• At the tap position giving the lowest LV voltage the transformer ratio is

166.8/22 kV. At 1.25 times the rated power (EndSection1) the 145 kVcurrent is:

1.25 60 0.2603 166.8HVI kA×

= =×

GUID-5461E726-C83D-4B02-B2A6-E3F376308529 V1 EN (Equation 1)

This corresponds to 1.088 times the rated current. The low voltage sidecurrent is 1.25 times the rated current and thus the differential current is about0.16 times the rated transformer current.

Section 3 1MRK 504 134-UEN -RET650 setting examples

46Application Manual

Page 53: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

• At the tap position giving the highest LV voltage the transformer ratio is123.2/22 kV. At 1.25 times the rated power (EndSection1) the 145 kVcurrent is:

1.25 60 0.3523 123.2HVI kA×

= =×

GUID-6C914C3F-86A8-450C-9CCF-16BCA07A48E2 V1 EN (Equation 2)

This corresponds to 1.471 times the rated current. The low voltage sidecurrent is 1.25 times the rated current and thus the differential current is about0.22 times the rated transformer current.The current transformers class is 5P which gives a maximum amplitude errorof circa 1 %. The IED accuracy is given as circa 5% at nominal values toassure that the load current does not cause unwanted operation IdMin is set to0.30 times the rated transformer current.

10. Set IdUnre to 10.0 IBaseThe unrestrained differential protection function operates without anystabilization. The setting principle is that the unrestrained function shall onlybe able to detect internal faults. This means that the current setting shall belarger than the largest fault current through the transformer during externalfaults. A very simple way to estimate this current is as:

1 1 8.330.12k

IdUnre IBase IBase IBasee

³ × = × = ×

GUID-D44EC374-13ED-4E91-A420-F9C7460F71C2 V2 EN (Equation 3)

If instead the feeding network is considered and a three-phase-fault at the lowvoltage side of the transformer is calculated, the following current resultsthrough the transformer (145 kV level):

2145 145 1 83

3 1453 3 5 0 1260

net TI . kA

( Z Z )( . . )

= = =× +

× + ×

GUID-D49C58EF-F9FD-4BAD-943A-55C186968C2F V2 EN (Equation 4)

This corresponds to 7.6 times the transformer rated current. If we consider80% saturation the differential current will approximately be 0.8 * 1.83kA =1.464kA. An additional safety margin of 1.2 is chosen. The setting of IdUnrshould then comply with the following formula with respect to the performedcalculations:

1.83kAIdUnr >= 1.2 0.8 = 7.4 IBase239

× × ×

IECEQUATION2412 V1 EN (Equation 5)11. Set NegSeqDiffEn, IMinNegSeq and NegSeqROA

11.1. Set NegSeqDiffEn to On (default)11.2. Set IMinNegSeq to >0.04 IBase (default)11.3. Set NegSeqROA to 60º (default)

The transformer differential protection has external/internal faultdiscriminator function, based on negative sequence current. The settings of

1MRK 504 134-UEN - Section 3RET650 setting examples

47Application Manual

Page 54: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

NegSeqDiffEn, IMinNegSeq and NegSeqROA are defined as advancedparameters and the default values are recommended.

3.1.4 Calculating settings for restricted earth fault protectionREFPDIFThe restricted earth fault protection is applied to the solidly earthed 145 kVwinding as shown in figure 11.

Restricted earth-fault protection

IEC09000448-1-en.vsd

IEC09000448 V1 EN

Figure 11: Restricted earth fault protection application

1. Set GlobalBaseSel to 1.The (HV) winding data should be related to Global base 1

2. Set IdMin to 30 % of IBase

Section 3 1MRK 504 134-UEN -RET650 setting examples

48Application Manual

Page 55: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

IEC98000017-3-en.vsd

bias current in per unit

0 1 2 3 4 5 6

1

2

3

4

5operate current in pu

default base sensitivity 30 %

operate

Base Sensitivity Idmin

*************************************Range : 4 % to 100 % rated currentStep : 1 % transformer rated current

minimum base sensitivity 100 %

maximum base sensitivity 5 % block

zone 1 zone 2

1.25 pu

second slope

first slope

IEC98000017 V4 EN

Figure 12: Restricted earth fault protection trip characteristic

The operate characteristic is shown in figure 12. The only setting to be madeis to set IdMin. The default value is 30 % of IBase. This setting is recommended.

3.1.5 Calculating settings for instantaneous phase overcurrentprotection, HV-side, PHPIOC

1. Set GlobalBaseSel to 1The (HV) winding data should be related to Global base 1.

2. Set IP>> to 1000 % of IBaseThe instantaneous phase overcurrent protection on the high voltage side isused for fast trip ping during severe internal faults. The protection shall beselective with respect to the protections of the outgoing 22 kV feeders.Therefore the maximum 145 kV current during a three-phase short circuit onthe 22 kV side of the transformer is calculated:

2145 145 1.83

3 ( ) 1453 (3.5 0.12)60

net TI kA

Z Z= = =

× +× + ×

GUID-662F8080-2FA3-47D9-B030-CDB4D502DB53 V2 EN (Equation 6)

The dynamic overreach, due to fault current DC-component, shall beconsidered in the setting. This factor is less that 5 %. The setting is chosenwith a safety margin of 1.2:

1MRK 504 134-UEN - Section 3RET650 setting examples

49Application Manual

Page 56: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Iset ≥ 1.2 · 1.05 · 1 830 = 2 306 ASettingIP>> = 1000 % of IBase

3.1.6 Calculating settings for four step phase overcurrentprotection 3-phase output, HV-side, OC4PTOCThe phase overcurrent protection is difficult to set as the short circuit current ishighly dependent of the switching state in the power system as well as the faulttype. In order to achieve setting that assure a selective fault clearance, a largenumber of calculations have to be made with different fault locations, differentswitching states in the system and different fault types.

The 145 kV phase overcurrent protection has the following tasks:

• Backup protection for short circuits on the transformer• Backup protection for short circuits on 22 kV busbar• Backup protection for short circuits on outgoing 22 kV feeders (if possible)

Although it is possible to make hand calculations of the different faults it isrecommended to use computer based fault calculations.

The following principle for the phase overcurrent protection is proposed:

• Only one step (step 1) is used. The time delay principle is chosen according tonetwork praxis, in this case inverse time characteristics using IEC Normalinverse.

3.1.6.1 Calculating general settings

1. Set GlobalBaseSel to 1For the (HV) winding data should be related to Global base 1

2. Set DirMode1 to Non-directionalThe function shall be non-directional

3. Set Characterist1 to IEC Norm.inv.For the choice of the time delay characteristic IEC Normal inverse is used inthis network.

3.1.6.2 Calculating settings for step 1

1. Set I1> to 140% of IBase (334 A primary current)

Section 3 1MRK 504 134-UEN -RET650 setting examples

50Application Manual

Page 57: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

The first requirement is that the phase overcurrent protection shall never tripfor load current during the extreme high load situations. It is assumed that thetransformer shall be able to be operated up to 130 % of the rated powerduring limited time. The protection resetting ratio shall be considered as well.The reset ratio is 0.95. The minimum setting can be calculated as:

1 60 10001 3 3270 95 3 145puI . A

³ × × =×

GUID-23DBA3B9-4E20-4210-901B-3CB4B8B2BC38 V1 EN (Equation 7)

The next requirement is that the protection shall be able to detect all shortcircuits within the defined protected zone. In this case it is required, ifpossible, that the protection shall detect phase-to-phase short circuit at themost remote point of the outgoing feeders as shown in figure 13.

RET 650

11

1

33

Ph-Ph

145 kV 22 kV

I>

IEC09000450_1_en.vsd

IEC09000450 V1 EN

Figure 13: Fault calculation for phase overcurrent protection setting

A phase-phase-earth short circuit is applied. In this calculation the shortcircuit power of the feeder shall be minimized (the source impedancemaximized).The longest 22 kV feeder has an impedance of Z = 3 + j10 Ω. The externalnetwork has a maximum source impedance of Zsc = j10 Ω (145 kV level).This impedance is transformed to the 22 kV level:

2

,2222 10 0.23

145scZ j jæ ö= × = Wç ÷è ø

GUID-FA8FA533-48E3-45FA-A22A-584CD0F754BF V1 EN (Equation 8)

The transformer impedance referred to 22 kV level is:

2

,2222 0.12 0.9760TZ j j= × = W

GUID-78CEC42F-9A02-411B-B6D3-95017467242B V1 EN (Equation 9)

The fault current can be calculated as follows:

2

220003 3 948

2 0.23 0.97 3 10sc phI Aj j j

= × =+ + +

GUID-2C4DC073-E49B-45BB-8136-96B455CC57A1 V1 EN (Equation 10)

1MRK 504 134-UEN - Section 3RET650 setting examples

51Application Manual

Page 58: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

This fault current is recalculated to the 145 kV level:

2 ,14522 948 144

145sc phI A= × =

GUID-2E36019B-9370-4703-9B31-91870BBD7BDB V1 EN (Equation 11)

This current is smaller than the required minimum setting to avoid anunwanted trip when experiencing a large load current. This means that the145 kV phase overcurrent protection cannot serve as complete back-upprotection for the outgoing 22 kV feeders.

2. Set k1 to 0.15The time setting must be coordinated with the feeder protections to assureselectivity. It can be stated that there is no need for selectivity between thehigh voltage side phase overcurrent protection and the low voltage side phaseovercurrent protection.The feeder short circuit protections have the following setting:I>: 300 A which corresponds to 45 A on 145 kV level.I>>: 6 000 A which corresponds to 910 A on 145 kV level.Characterist: IEC Normal Inverse (IEC Norm. inv.) with k-factor = 0.25The setting of the k-factor for the 145 kV phase overcurrent protection isderived from graphical study of the inverse time curves. It is required that thesmallest time difference between the inverse time curves shall be 0.4 s. Withthe setting k1 = 0.15 the time margin between the characteristics is about 0.4 sas shown in figure 14.

Section 3 1MRK 504 134-UEN -RET650 setting examples

52Application Manual

Page 59: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

IEC09000451 V1 EN

Figure 14: Inverse time operation characteristics for selectivity

3.1.7 Calculating settings for four step phase overcurrentprotection 3-phase output, LV-side OC4PTOCThe 22 kV phase overcurrent protection has the following purpose:

• Main protection for short circuits on 22 kV busbar• Backup protection for short circuits on outgoing 22 kV feeders (if possible)

The reach of the phase overcurrent line protection is dependent on the operationstate and the fault type. Therefore the setting must be based on fault calculationsmade for different faults, fault points and switching states in the network. Althoughit is possible to make manual calculations of the different faults it is recommendedto use computer based fault calculations.

The following principle for the phase overcurrent protection is proposed:

1MRK 504 134-UEN - Section 3RET650 setting examples

53Application Manual

Page 60: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

• Step 1 serves as the main protection for the 22 kV busbar. This step has a shortdelay and also has blocking input from the phase overcurrent protections of the22 kV feeders. This is a way to achieve a fast trip of 22 kV busbar shortcircuits while the selectivity is realized by means of the blocking from thefeeder protections.

• Step 4 is used as back-up short circuit protection for the 22 kV feeders as faras possible. The time delay principle is chosen according to network praxis, inthis case inverse time characteristics using IEC Normal inverse. As the stepshall have an inverse time characteristic the step 4 function is used.

An inverse time characteristics is not available for step 2 and 3.

3.1.7.1 Calculating general settings

1. Set GlobalBaseSel to 2The settings are made in primary values. These values are given in the basesettings in Global base 2.

2. Set directional mode2.1. Set DirMode1 to Non-directional2.2. Set DirMode4 to Non-directional

The function shall be non-directional.3. Set Characterist1 to IEC Def.Time

Step 1 shall have definite time delay4. Set Characterist4 to IEC Norm.inv

Step 4: For the choice of the time delayed characteristic IEC Normal inverseis used in this network.

3.1.7.2 Calculating settings for step 1

1. Set I1> to 500 % of IBaseThe requirement is that step 1 shall detect all short circuits on the 22 kVbusbar. The external network has a maximum source impedance of Zsc = j10Ω (145 kV level). This impedance is transformed to 22 kV level:

2

,2222 10 0.23

145scZ j jæ ö= × = Wç ÷è ø

GUID-A4805F4D-20EC-4B39-A39D-925513515FA5 V1 EN (Equation 12)

The transformer impedance, referred to 22 kV level, is:

2

,2222 0.12 0.9760TZ j j= × = W

GUID-CB0D94B6-5BFA-42EB-AE4A-B0EE898A0D78 V1 EN (Equation 13)

Calculation of a phase-to-phase short circuit at this busbar:

Section 3 1MRK 504 134-UEN -RET650 setting examples

54Application Manual

Page 61: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

23 22000 / 3 9167

2 0.23 0.97sc phI Aj j

= × =+

GUID-846C7A33-F976-45DF-95E9-75124D6A24D2 V1 EN (Equation 14)

The setting is chosen to 5 IBase which corresponds to 7 875 A primary current.2. Set t1 to 0.1 s

The time delay must be chosen so that the blocking signal shall be able toprevent unwanted operation during feeder short circuits. 0.1 s should besufficient.

3.1.7.3 Calculating settings for step 4

The first requirement is that the phase overcurrent protection shall never trip forload current during extreme high load situations. It is assumed that the transformershall be able to be operated up to 130% of the rated power during the limited time.The protection resetting ratio of 0.95 shall also be considered. The minimumsetting can be calculated as follows:

1 60 10001.3 21550.95 3 22puI A×

³ × × =×

GUID-4D6B62EC-32DC-433E-B1C8-D23E8D06D017 V1 EN (Equation 15)

The next requirement is that the protection shall be able to detect all short circuitswithin the defined protected zone. In this case it is required, if possible, that theprotection shall detect phase-to-phase short circuit at the most remote point of theoutgoing feeders as shown in figure 15.

145kV

11

1

33

IEC09000452-1-en.vsd

RET650

Ph-Ph

22kV

I>

IEC09000452 V1 EN

Figure 15: Fault calculation for phase overcurrent protection

A phase-phase-earth short circuit is applied. In this calculation the short circuitpower of the feeder shall be minimized (the source impedance maximized).

1. Set I2> to 140 % of IBase2205 A primary current.The longest 22 kV feeder has an impedance of Z = 3 + j10 Ω. The externalnetwork has a maximum source impedance of Zsc = j10 Ω (145 kV level).This impedance is transformed to the 22 kV level:

1MRK 504 134-UEN - Section 3RET650 setting examples

55Application Manual

Page 62: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

2

,2222 10 0.23

145scZ j jæ ö= × = Wç ÷è ø

GUID-BA67F1FC-2DCE-4E04-BBB3-FABB86FDEA3A V1 EN (Equation 16)

The transformer impedance, referred to 22 kV level is:The phase-to-phase fault current can be calculated as follows:

23 22000 / 3 949

2 0.23 0.97 3 10sc phI Aj j j

= × =+ + +

GUID-BAA8989B-EF8F-4277-9B2B-EBBCA35ED7C2 V1 EN (Equation 17)

This current is smaller than the required minimum setting to avoid unwantedtrip at large load current. This means that the 22 kV phase overcurrentprotection cannot serve as complete back-up protection for the outgoing 22kV feeders.

2. Set k4 to 0.15The feeder short circuit protections has the following setting:I>: 300 A.I>>: 6 000 A.Characteristic: IEC Normal Inverse with k-factor = 0.25The setting of the k-factor for the 22 kV phase overcurrent protection isderived from graphical study of the inverse time curves. It is required that thesmallest time difference between the inverse time curves is 0.4 s. With thesetting k4= 0.15 the time margin between the characteristics is about 0.4 s asshown in figure 16.

Section 3 1MRK 504 134-UEN -RET650 setting examples

56Application Manual

Page 63: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

IEC09000453 V1 EN

Figure 16: Inverse time operation characteristics for selectivity

3.1.8 Calculating settings for four step residual overcurrentprotection, zero or negative sequence direction HV-sideEF4PTOCThe protection is fed from the 145 kV neutral point of the current transformer.

The residual overcurrent protection is more difficult to set as the earth-fault currentis highly dependent on the network configuration of the power system. In order toachieve settings that assure selective fault clearance, a large number of calculationshave to be made with different fault locations, different switching states in thesystem and different earth-fault types. Below one example of setting of residualovercurrent protection for a line in a meshed solidly earthed system is given.

1MRK 504 134-UEN - Section 3RET650 setting examples

57Application Manual

Page 64: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

If there is no generation at the low voltage side of the generator the transformer canonly feed earth-fault currents as long as any of the non faulted lines are still inoperation. If there is generation connected to the low voltage side of thetransformer the transformer can only feed 145 kV earth-faults.

The residual overcurrent protection has the following purpose:

• Fast and sensitive protection for earth-faults on the 145 kV busbar• Backup protection for earth-faults in the 145 kV transformer winding• Backup protection for earth-faults on the outgoing 145 kV lines• Sensitive detection of high resistive earth-faults and series faults in the 145 kV

network

The reach of the residual overcurrent line protection is dependent on the operationstate and the fault type. Therefore the setting must be based on fault calculationsmade for different faults, fault points and switching states in the network. Althoughit is possible to make hand calculations of the different faults it is recommended touse computer based fault calculations.

The following principle for the residual overcurrent protection is proposed:

• Step 1 (IN1>) with a high current setting and a short delay (about 0.4 s). Step1 is a non-directional function. This step gives a fast trip for busbar earth-faults and some earth-faults on the lines.

• Step 2 (IN2>) with a current setting, if possible, that enables detection of earth-faults on the 145 kV lines out from the substation. Step 2 is a non-directionalfunction. The function has a delay to enable selectivity with respect to the lineprotections.

• Step 4 (IN4>) with a current setting that enables detection of high resistiveearth-faults and series faults in the network. Step 3 is a non-directionalfunction. The function has a longer delay to enable selectivity.

3.1.8.1 Calculating general settings

The (HV) winding data should be related to Global base 1.

1. Set GlobalBaseSel to 1, IBase = 240 A2. Set DirMode1, DirMode2 and DirMode4 to Non-directional3. Set DirMode3 to Off

3.1.8.2 Calculating settings for step 1

Set the operating residual current level and time delay

1. Set IN1> to 689% of IBase, corresponding to 1650 A

Section 3 1MRK 504 134-UEN -RET650 setting examples

58Application Manual

Page 65: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Faults are applied at the 145 kV busbar as shown in figure 17.

11

1

33

IEC09000454-1-en.vsd

IN>

RET650

Ph-Ph

22kV145kV

IEC09000454 V1 EN

Figure 17: Fault calculation for 145 kV residual overcurrent protectionsetting

The following fault types are applied: phase-phase-earth short circuit and phase-earth-fault. The source impedance (both positive sequence and zero sequence)at the 145 kV level gives the following residual current from the transformerduring a phase-to-earth busbar fault (the current is hand-calculated but isnormally calculated in a computer).The zero sequence transformer impedance is assumed to be equal to thepositive sequence short circuit impedance:

2 2

0145 0.12 42

60N

T kN

UZ j e j jS

= × = × = W

GUID-50CCC0F7-742D-45C4-84BC-923222214C69 V1 EN (Equation 18)

The residual current from the transformer during a single phase-earth-faultand with maximum short circuit power is:

0,0

0, 00, 01,

0, 0

3 15 3 1453 3.715 4215 42 2 3.52 15 42

netT

net Tnet Tnet

net T

Z U jI kAZ Z j jZ Z j j jZ j jZ Z

× ×= × = × =

× ×+ + × +× +++

GUID-CC2E2412-4939-4285-A491-FCCC0AE0F939 V1 EN (Equation 19)

The residual current from the transformer during a single phase-earth-faultand with minimum short circuit power is:

0,0

0, 00, 01,

0, 0

3 20 3 1453 2.420 4220 42 2 102 20 42

netT

net Tnet Tnet

net T

Z U jI kAZ Z j jZ Z j j jZ j jZ Z

× ×= × = × =

× ×+ + × +× +++

GUID-991D27BC-4413-4A9B-BF49-F25986545C73 V1 EN (Equation 20)

The residual current from the transformer during a phase-to-phase to earth-fault and with maximum short circuit power is:

1MRK 504 134-UEN - Section 3RET650 setting examples

59Application Manual

Page 66: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

0,0

0, 00, 01,

0, 0

3 15 3 1453 2.615 4215 42 3.5 22 15 42

netT

net Tnet Tnet

net T

Z U jI kAZ Z j jZ Z j j jZ j jZ Z

× ×= × = × =

× ×+ + + ×+ ×++

GUID-CA17A1A5-E141-4F0B-B7C0-74683F9F9AD1 V1 EN (Equation 21)

The residual current from the transformer during a phase-to-phase to earth-fault and with minimum short circuit power is:

0,0

0, 00, 01,

0, 0

3 20 3 1453 2.220 4220 42 10 22 20 42

netT

net Tnet Tnet

net T

Z U jI kAZ Z j jZ Z j j jZ j jZ Z

× ×= × = × =

× ×+ + + ×+ ×++

GUID-933BE756-31CD-45BA-B3EB-5DC00CA25DC0 V1 EN (Equation 22)

To assure that the protection detects all earth-faults on the 145 kV busbar theprotection should be set as follows:IN1> ≤ 0.75 · 2.2 = 1.65 kA = 687 % IBase

11

1

33

IEC09000455-1-en.vsd

IN>

145kV RET650

Ph-Ph

22kV85%

IEC09000455 V1 EN

Figure 18: Fault calculation for 145 kV residual overcurrent protectionselectivity

The calculations show that the largest residual current from the transformer =1.2 kA.To assure selectivity the setting must fulfil:Ihigh,set ≥ 1.2 · k · 3I0 maxwhich gives about 1 500 A ,where k is the transient overreach (due to thefault current DC-component) of the overcurrent function. For the four stepresidual overcurrent function; k = 1.05.

2. Set t1 to 0.4 sCharacterist1: ANSI Def.TimeAs the protection should be set for a time delay of 0.4 s the selectivity to theline protections should be assured. Therefore earth-faults should be calculatedwhere the fault point on the lines is at zone 1 reach (about 85 % out on the line).

3.1.8.3 Calculating settings for step 2

Section 3 1MRK 504 134-UEN -RET650 setting examples

60Application Manual

Page 67: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

1. Set IN2> to 400% of IBase, corresponding to 956 ATo assure that step 2 detects all earth-faults on the outgoing lines earth-faultscalculations are made where single phase-faults and phase-to-phase-to earth-faults are applied to the adjacent busbars.

11

1

33

IEC09000456-1-en.vsd

IN>

145kV RET650 22kV

Ph-Ph

IEC09000456 V1 EN

Figure 19: Fault calculation for sufficient reach of the 145 kV residualovercurrent protection

The minimum residual current to detect works out as 3I0AB,min = 1.0 kA.2. Set t2 to 0.8 s

Characteristic2: ANSI Def.TimeThe delay of IN2> should be set longer than the distance protection zone 2(normally 0,4 s). 0.8 s is proposed.

3.1.8.4 Calculating settings for step 4

1. Set IN4> to 42 % of IBase, corresponding to 100 AThe current setting of step 4 should be chosen according to standardprocedure in the grid. From experience it can be concluded that a settingdown to about 100 A can be used. This setting is however highly dependenton the line configuration, mainly if the line is transposed or not.The delay of IN4> should be set larger than the delay of the sensitive residualcurrent protection of the lines.

2. Set k4 to 0.3Characterist4: RD type

3. Set t4Min to 1.2 s4. Set inverse time delay of type RD to logarithmic

If definite time delay is used there is some risk of unselective trip during highresistive earth-faults or series faults. If a dependent time delay (inverse time)is used some degree of selectivity can be achieved.Here an inverse time delay of the RD type is selected: logarithmic

1MRK 504 134-UEN - Section 3RET650 setting examples

61Application Manual

Page 68: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

3.1.9 Calculating settings for two step residual overvoltageprotection LV-side, ROV2PTOVThe residual overvoltage protection is fed from the open delta connected voltagetransformer at the 22 kV side of the transformer.

The residual overvoltage protection has the following purpose:

• Back-up protection for earth-faults on the 22 kV feeders out from the substation.• Main protection for earth-faults on the 22 kV busbar• Main protection for earth-faults on the 22 kV transformer winding

The residual voltage protection has two steps. In this application step 1 should tripthe 22 kV circuit breaker and if the earth-fault is situated in the transformer 22 kVwinding or between the transformer and the 22 kV breaker the 145 kV breaker istripped from step 2.

The voltage setting of the protection is dependent on the required sensitivity andthe system earthing. The 22 kV system has earthing through a Petersen coil(connected to the system via a separate earthing transformer) and a parallel neutralpoint resistor. The Petersen coil is tuned to compensate for the capacitive earth-fault current in the 22 kV system. The neutral point resistor gives a 10 A earth-faultcurrent during a zero resistance earth-fault. This means that the resistance is

22000 3 127010N

/R W= =

GUID-4ECDF824-B17E-436D-A668-ACA06BB375F7 V2 EN (Equation 23)

The total zero sequence impedance of the 22 kV system is:

Z0 = 3RN // j3XN // — jXC Ω / phase

As the Petersen coil is tuned the zero sequence impedance is:

Z0 = 3RN Ω / phase

The residual voltage during a resistive earth-fault in the 22 kV system is:

0

0 0

13 3

1 1

Phaseo

f fphase

U UU orR RUZ Z

= =× ×

+ +

GUID-AD49C138-F37B-4690-9E37-BA2BAD678A17 V1 EN (Equation 24)

In our case the requirement is that earth-faults with a resistance up to 5 000 Ω shallbe detected. This gives:

0 1 0 203 500013 1270

phase

U .U

= =×

GUID-42D376ED-052F-4E9B-B4D9-8D679127BC0C V1 EN (Equation 25)

Section 3 1MRK 504 134-UEN -RET650 setting examples

62Application Manual

Page 69: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Step 1 and step 2 is given the same voltage setting but step 2 shall have longer timedelay.

The residual earth-fault protection shall have a definite time delay. The time settingis set longer than the time delay of the earth-fault protection of the outgoing feedershaving maximum 2 s delay. The time delay for step 1 is set to 3 s and the timedelay for step 2 is set to 4 s.

1. Set GlobalBaseSel to 2The (LV) winding data should be related to Global base 2.

2. Set Characterist1 to Definite time3. Set U1> to 20 % of UBase4. Set t1 to 3.0 s5. Set U2> to 20 % of UBase6. Set t2 to 4.0 s

3.1.10 Calculating settings for HV-side breaker failure protection,CCRBRFThe breaker failure protection can use either the position indication of the circuitbreaker or measure the current going through the CT in order to detect correctbreaker functioning. For transformer protections it is most suitable to use currentmeasurement as a circuit breaker failure check.

1. Set GlobalBaseSel to 1The (HV) winding data should be related to Global base 1.

2. Set FunctionMode to Current3. Set BuTripMode to 1 out of 4

The current measurement function uses the three-phase currents from the lineCT and either, a measured residual current or a calculated 3I0. Based on thisanalogue data one of the following rules can be chosen in order to determinea breaker failure:• 1 out of 3: at least one of the three-phase current shall be larger than the

set level to detect failure to break• 1 out of 4: at least one of the three-phase current and the residual current

shall be larger than the set level to detect failure to break• 2 out of 4: at least two of the three-phase current and the residual

current shall be larger than the set level to detect failure to break.

As the residual current protection is one of the protection functions to initiatethe breaker failure protection the setting 1 out of 4 is chosen.

4. Set IP> to 20 % of IBaseIP> should be set lower than the smallest current to be detected by thedifferential protection which is set 30% of IBase.

5. Set IN> to 20 % of IBase

1MRK 504 134-UEN - Section 3RET650 setting examples

63Application Manual

Page 70: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

IN> should be set lower than the smallest current to be detected by the mostsensitive step of the residual ovecurrent protection which is 100 A.

6. Set the re-tip time delay t1 to 07. Set t2 to 0.17 s

The delay time of the breaker failure protection (BuTrip) is chosen accordingto figure 20.The maximum opening time of the circuit breaker is considered to be 100 ms.The breaker failure protection BFP maximum reset time is 15 ms.A margin of about 2 cycles should be chosen. This gives a minimum settingof back-up trip delay t2 of about 155ms.

Time

The fault occurs

Protection operate time

Trip and Start BFP

Normal tcbopen

Margin

Retrip delay t1 tcbopen after re-trip

tBFPreset

Minimum back-up trip delay t2

Critical fault clearance time for stability

en05000479.vsdEN05000479 V1 EN

Figure 20: Overexcitation protection characteristics

3.1.11 Calculating settings for LV-side breaker failure protection,CCRBRFThe breaker failure protection can use either the position indication of the circuitbreaker or measure the current going through the CT in order to detect correctbreaker functioning. For transformer protections it is most suitable to use currentmeasurement as a circuit breaker failure check.

1. Set GlobalBaseSel to 2

Section 3 1MRK 504 134-UEN -RET650 setting examples

64Application Manual

Page 71: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

The (LV) winding data should be related to Global base 2.2. Set FunctionMode to Current3. Set BuTripMode to 1 out of 3

The current measurement function uses the three-phase currents from the lineCT and either, a measured residual current or a calculated 3I0. Based on thisanalogue data one of the following rules can be chosen in order to determinea breaker failure:• 1 out of 3: at least one of the three-phase current shall be larger than the

set level to detect failure to break• 1 out of 4: at least one of the three-phase current and the residual current

shall be larger than the set level to detect failure to break• 2 out of 4: at least two of the three-phase current and the residual

current shall be larger than the set level to detect failure to break.

There is no residual current measurement protection on the 22 kV side of thetransformer. Therefore 1 out of 3 is chosen.

4. Set IP> to 20 % of IBaseIP> should be set lower than the smallest current to be detected by thedifferential protection which is set 25 % of IBase.

5. Set the re-tip time delay t1 to 0 s6. Set t2 to 0.17 s

The delay time of the breaker failure protection (BuTrip) is chosen accordingto figure 20.The maximum open time of the circuit breaker is considered to be 100 ms.The BFP maximum reset time is 15 ms.A margin of about 2 cycles should be chosen. This gives a minimum settingof back-up trip delay t2 of about 155ms.

1MRK 504 134-UEN - Section 3RET650 setting examples

65Application Manual

Page 72: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Time

The fault occurs

Protection operate time

Trip and Start BFP

Normal tcbopen

Margin

Retrip delay t1 tcbopen after re-trip

tBFPreset

Minimum back-up trip delay t2

Critical fault clearance time for stability

en05000479.vsdEN05000479 V1 EN

Figure 21: Time sequences for breaker failure protection setting

Section 3 1MRK 504 134-UEN -RET650 setting examples

66Application Manual

Page 73: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Section 4 Analog inputs

4.1 Introduction

Analog input channels in the IED must be set properly in order to get correctmeasurement results and correct protection operations. For power measuring andall directional and differential functions the directions of the input currents must bedefined in order to reflect the way the current transformers are installed/connectedin the field ( primary and secondary connections ). Measuring and protectionalgorithms in the IED use primary system quantities. Consequently the settingvalues are expressed in primary quantities as well and therefore it is important toset the transformation ratio of the connected current and voltage transformersproperly.

The availability of CT and VT inputs, as well as setting parameters depends on theordered IED.

A reference PhaseAngleRef must be defined to facilitate service values reading.This analog channels phase angle will always be fixed to zero degrees and all otherangle information will be shown in relation to this analog input. During testing andcommissioning of the IED the reference channel can be changed to facilitate testingand service values reading.

4.2 Setting guidelines

4.2.1 Setting of the phase reference channelAll phase angles are calculated in relation to a defined reference. An appropriateanalog input channel is selected and used as phase reference. The parameterPhaseAngleRef defines the analog channel that is used as phase angle reference.

The initially connected phase-to-earth voltage is usually chosen as PhaseAngleRef.A phase-to-phase voltage can also be used in theory, but a 30 degree phase shiftbetween the current and voltage is observed in this case.

If no suitable voltage is available, the initially connected current channel can beused. Although the phase angle difference between the different phases will befirm, the whole system will appear to rotate when observing the measurementfunctions.

1MRK 504 134-UEN - Section 4Analog inputs

67Application Manual

Page 74: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

The phase reference does not work if the current channel is notavailable. For example, when the circuit breaker is opened and nocurrent flows. Although the phase angle difference between thedifferent phases is firm, the whole system appears to be rotatingwhen the measurement functions are observed.

4.2.2 Setting of current channelsThe direction of a current depends on the connection of the CT. Unless indicatedotherwise, the main CTs are supposed to be star connected. The IED can beconnected with its earthing point towards the object or away from the object. Thisinformation must be set in the IED via the parameter CTStarPoint, which can bechanged between FromObject and ToObject. Internally in the IED algorithms andIED functions, the convention of the directionality is defined as follows:

A positive value of current, power, and so on (forward) means that the quantity hasa direction towards the object. - A negative value of current, power, and so on(reverse) means a direction away from the object. See figure 22.

Protected ObjectLine, transformer, etc

ForwardReverse

Definition of directionfor directional functions

Measured quantity ispositive when flowing

towards the object

e.g. P, Q, I

ReverseForward

Definition of directionfor directional functions

e.g. P, Q, IMeasured quantity ispositive when flowing

towards the object

Set parameterCTStarPoint

Correct Setting is"ToObject"

Set parameterCTStarPoint

Correct Setting is"FromObject"

en05000456.vsdIEC05000456 V1 EN

Figure 22: Internal convention of the directionality in the IED

With correct setting of the primary CT direction, CTStarPoint set to FromObject orToObject, a positive quantity always flows towards the protected object and adirection defined as Forward is always looking towards the protected object. Thefollowing examples show the principle.

4.2.2.1 Example 1

Two IEDs used for protection of two objects.

Section 4 1MRK 504 134-UEN -Analog inputs

68Application Manual

Page 75: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Transformerprotection

TransformerLine

Line

Setting of current input:Set parameter

CTStarPoint with Transformer as

reference object.Correct setting is

"ToObject"

ForwardReverse

Definition of direction for directional functions

Line protection

Setting of current input:Set parameter

CTStarPoint with Transformer as

reference object.Correct setting is

"ToObject"

Setting of current input:Set parameter

CTStarPoint withLine as

reference object.Correct setting is

"ToObject"

IEC11000020-2-en.vsd

IsIs

Ip Ip Ip

IED IED

IEC11000020 V2 EN

Figure 23: Example how to set CTStarPoint parameters in the IED

The figure 23 shows the most common case where the objects have their own CTs.For the transformer protection, the protected object is the transformer. Thereforeboth CTStarPoint directions should be set ToObject. For the line protection, theprotected object is the line. The line CT is earthed towards the busbar, therefore theCTStarPoint should be set FromObject.

4.2.2.2 Example 2

Two IEDs used for protection of two objects and sharing a CT.

1MRK 504 134-UEN - Section 4Analog inputs

69Application Manual

Page 76: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Transformerprotection

Setting of current input:Set parameter

CTStarPoint with Transformer as

reference object.Correct setting is

"ToObject"

ForwardReverse

Definition of direction for directional

functions

Line protection

Setting of current input:Set parameter

CTStarPoint with Transformer as

reference object.Correct setting is

"FromObject"

Setting of current input:Set parameter

CTStarPoint withLine as

reference object.Correct setting is

"ToObject"

IED IED

IEC11000021_1_en.vsdIEC11000021 V2 EN

Figure 24: Example how to set CTStarPoint parameters in the IED

This example is similar to example 1, but the power transformer is feeding just oneline; both line protection IED and transformer protection IED use the same CT.The CT direction is set with different reference objects for the two IEDs though itis the same current from the same CT that is feeding the two IEDs. With thesesettings the directional functions of the line protection shall be set to Forward tolook towards the line.

4.2.2.3 Examples on how to connect, configure and set CT inputs for mostcommonly used CT connections

Figure 25 defines the marking of current transformer terminals commonly usedaround the world:

In the SMAI function block, you have to set if the SMAI block ismeasuring current or voltage. This is done with the parameter:AnalogInputType: Current/voltage. The ConnectionType: phase -phase/phase-earth and GlobalBaseSel.

Section 4 1MRK 504 134-UEN -Analog inputs

70Application Manual

Page 77: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

ISec

I Pri

S1 (X1)

P1(H1)

P2(H2)

S2 (X2)

P2(H2)

P1(H1)

x x

a) b) c)

en06000641.vsd

S2 (X2) S1 (X1)

IEC06000641 V1 EN

Figure 25: Commonly used markings of CT terminals

Where:

a) is symbol and terminal marking used in this document. Terminals marked with a dot indicatesthe primary and secondary winding terminals with the same (that is, positive) polarity

b) and c) are equivalent symbols and terminal marking used by IEC (ANSI) standard for CTs. Note thatfor these two cases the CT polarity marking is correct!

It shall be noted that depending on national standard and utility practices, the ratedsecondary current of a CT has typically one of the following values:

• 1A• 5A

However in some cases the following rated secondary currents are used as well:

• 2A• 10A

The IED fully supports all of these rated secondary values.

4.2.2.4 Example on how to connect a star connected three-phase CT set tothe IED

Figure 26 gives an example about the wiring of a star connected three-phase CT setto the IED. It gives also an overview of the actions which are needed to make thismeasurement available to the built-in protection and control functions within theIED as well.

For correct terminal designations, see the connection diagramsvalid for the delivered IED.

1MRK 504 134-UEN - Section 4Analog inputs

71Application Manual

Page 78: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

L1IL

1

IL2

IL3

L2 L3

Protected Object

CT 600/5Star Connected

IL1

IL2

IL3

IED

IEC13000002-3-en.vsd

1 2

3

4

SMAI_20_2BLOCKREVROT^GRP2L1^GRP2L2^GRP2L3^GRP2N

AI3PAI1AI2AI3AI4AIN

5

IEC13000002 V3 EN

Figure 26: Star connected three-phase CT set with star point towards the protected object

Where:

1) The drawing shows how to connect three individual phase currents from a star connectedthree-phase CT set to the three CT inputs of the IED.

2) The current inputs are located in the TRM or AIM modules. It shall be noted that for allthese current inputs the following setting values shall be entered for the example shown infigure 26.

• CTprim=600A• CTsec=5A• CTStarPoint=ToObject

Inside the IED only the ratio of the first two parameters is used. The third parameter as setin this example will have no influence on the measured currents (that is, currents arealready measured towards the protected object).

Table continues on next page

Section 4 1MRK 504 134-UEN -Analog inputs

72Application Manual

Page 79: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

3) These three connections are the links between the three current inputs and the three inputchannels of the preprocessing function block 4). Depending on the type of functions, whichneed this current information, more than one preprocessing block might be connected inparallel to the same three physical CT inputs.

4) The preprocessing block that has the task to digitally filter the connected analog inputs andcalculate:

• fundamental frequency phasors for all four input channels (phase L1, L2, L3 andneutral quantity, if any, are connected to GRPN input)

• harmonic content for all four input channels• positive, negative and zero sequence quantities by using the fundamental frequency

phasors for the first three input channels (channel one taken as reference forsequence quantities)

These calculated values are then available for all built-in protection and control functionswithin the IED, which are connected to this preprocessing function block. For thisapplication most of the preprocessing settings can be left to the default values.If frequency tracking and compensation is required (this feature is typically required onlyfor IEDs installed in power plants), then the setting parameters DFTReference shall be setaccordingly.Section SMAI in this manual provides information on adaptive frequency tracking for thesignal matrix for analogue inputs (SMAI).

5) AI3P in the SMAI function block is a grouped signal which contains all the data about thephases L1, L2, L3 and neutral quantity; in particular the data about fundamental frequencyphasors, harmonic content and positive sequence, negative and zero sequence quantitiesare available.AI1, AI2, AI3, AI4 are the output signals from the SMAI function block which contain thefundamental frequency phasors and the harmonic content of the corresponding inputchannels of the preprocessing function block.AIN is the signal which contains the fundamental frequency phasors and the harmoniccontent of the neutral quantity; this data is calculated by the preprocessing function blockon the basis of the inputs GRPL1, GRPL2 and GRPL3.

Another alternative is to have the star point of the three-phase CT set as shown infigure :

1MRK 504 134-UEN - Section 4Analog inputs

73Application Manual

Page 80: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

L1IL

1

IL2

IL3

L2 L3

Protected Object

CT 800/1Star Connected

IL1

IL2

IL3

IED

IEC11000026-3-en.vsd

4 1

2

3

SMAI_20_2BLOCKREVROT^GRP2L1^GRP2L2^GRP2L3^GRP2N

AI3PAI1AI2AI3AI4AIN

5

IEC11000026 V3 EN

Figure 27: Star connected three-phase CT set with its star point away from the protected object

In the example in figure 27 case everything is done in a similar way as in the abovedescribed example (figure 26). The only difference is the setting of the parameterCTStarPoint of the used current inputs on the TRM (item 2 in the figure):

• CTprim=600A• CTsec=5A• CTStarPoint=FromObject

Inside the IED only the ratio of the first two parameters is used. The thirdparameter as set in this example will negate the measured currents in order toensure that the currents are measured towards the protected object within the IED.

4.2.2.5 Example how to connect delta connected three-phase CT set to theIED

Figure 28 gives an example how to connect a delta connected three-phase CT set tothe IED. It gives an overview of the required actions by the user in order to makethis measurement available to the built-in protection and control functions in theIED as well.

For correct terminal designations, see the connection diagramsvalid for the delivered IED.

Section 4 1MRK 504 134-UEN -Analog inputs

74Application Manual

Page 81: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

L1

IL1

IL2

IL3

L2 L3

Protected Object

IED

CT

600/

5 in

Del

taD

AB

Con

nect

ed

IL1-IL2

IL2-IL3

IL3-IL1

1 2

3

4

IEC11000027-2-en.vsd

SMAI_20

IEC11000027 V2 EN

Figure 28: Delta DAB connected three-phase CT set

1MRK 504 134-UEN - Section 4Analog inputs

75Application Manual

Page 82: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Where:

1) shows how to connect three individual phase currents from a delta connected three-phaseCT set to three CT inputs of the IED.

2) is the TRM or AIM where these current inputs are located. It shall be noted that for allthese current inputs the following setting values shall be entered.

600 3463

sec 5

primCT A

CT A

= =

=

IECEQUATION2413 V1 EN (Equation 26)

• CTStarPoint=ToObject

3) are three connections, which connect these three current inputs to three input channels ofthe preprocessing function block 4). Depending on the type of functions which need thiscurrent information, more then one preprocessing block might be connected in parallel tothese three CT inputs.

4) is a Preprocessing block that has the task to digitally filter the connected analog inputs andcalculate:

• fundamental frequency phasors for all three input channels• harmonic content for all three input channels• positive, negative and zero sequence quantities by using the fundamental frequency

phasors for the first three input channels (channel one taken as reference forsequence quantities)

These calculated values are then available for all built-in protection and control functionswithin the IED, which are connected to this preprocessing function block. For thisapplication most of the preprocessing settings can be left to the default values.If frequency tracking and compensation is required (this feature is typically required onlyfor IEDs installed in the generating stations) then the setting parameters DFTReferenceshall be set accordingly.

Another alternative is to have the delta connected CT set as shown in figure 29:

Section 4 1MRK 504 134-UEN -Analog inputs

76Application Manual

Page 83: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

L1

IL1

IL2

IL3

L2 L3

Protected Object

IED

CT

800/

1 in

Del

taD

CA

Con

nect

ed

IL3-IL2

IL2-IL1

IL1-IL3

2

3

4

IEC11000028-2-en.vsd

SMAI_20

IEC11000028 V2 EN

Figure 29: Delta DAC connected three-phase CT set

In this case, everything is done in a similar way as in the above described example,except that for all used current inputs on the TRM the following setting parametersshall be entered:

sec

800 4623

1

primCT A

CT A

= =

=IECEQUATION2414 V1 EN (Equation 27)

• CTStarPoint=ToObject

4.2.2.6 Example how to connect single-phase CT to the IED

Figure 30 gives an example how to connect the single-phase CT to the IED. Itgives an overview of the required actions by the user in order to make thismeasurement available to the built-in protection and control functions within theIED as well.

For correct terminal designations, see the connection diagramsvalid for the delivered IED.

1MRK 504 134-UEN - Section 4Analog inputs

77Application Manual

Page 84: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Protected Object

L1 L2 L3

IED IN

P

INS

INS

2

IEC11000029-3-en.vsd

4

3

CT

1000

/1

a)

b)

(+)

(+)

(-)

(-)(+)

(-)

1 SMAI_20_2BLOCKREVROT^GRP2L1^GRP2L2^GRP2L3^GRP2N

AI3PAI1AI2AI3AI4AIN

IEC11000029 V3 EN

Figure 30: Connections for single-phase CT input

Section 4 1MRK 504 134-UEN -Analog inputs

78Application Manual

Page 85: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Where:

1) shows how to connect single-phase CT input in the IED.

2) is TRM or AIM where these current inputs are located. For all these current inputs thefollowing setting values shall be entered.For connection (a) shown in figure 30:

sec

6005

primCT ACT A

==

IECEQUATION2415 V1 EN (Equation 28)

CTStarPoint=ToObject For connection (b) shown in figure 30:

sec

6005

primCT ACT A

==

IECEQUATION2415 V1 EN (Equation 29)

CTStarPoint=FromObject

3) shows the connection made in SMT tool, which connect this CT input to the fourth inputchannel of the preprocessing function block 4).

4) is a Preprocessing block that has the task to digitally filter the connected analog inputsand calculate:These calculated values are then available for all built-in protection and controlfunctions within the IED, which are connected to this preprocessing function block..If frequency tracking and compensation is required (this feature is typically requiredonly for IEDs installed in the power plants) then the setting parameters DFTReferenceshall be set accordingly.Section “Preprocessing blocks SMAI” provides information on adaptive frequencytracking for the signal matrix for analogue inputs (SMAI).

4.2.3 Setting of voltage channelsAs the IED uses primary system quantities the main VT ratios must be known tothe IED. This is done by setting the two parameters VTsec and VTprim for eachvoltage channel. The phase-to-phase value can be used even if each channel isconnected to a phase-to-earth voltage from the VT.

4.2.3.1 Example

Consider a VT with the following data:

132 1103 3kV V

EQUATION2016 V1 EN (Equation 30)

The following setting should be used: VTprim=132 (value in kV) VTsec=110(value in V)

1MRK 504 134-UEN - Section 4Analog inputs

79Application Manual

Page 86: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

4.2.3.2 Examples how to connect, configure and set VT inputs for mostcommonly used VT connections

Figure 31 defines the marking of voltage transformer terminals commonly usedaround the world.

A(H1)

B(H2)

b(X2)

a(X1)

A(H1)

N(H2)

n(X2)

a(X1)

b) c)

A(H1)

N(H2)

dn(X2)

da(X1)

d)

UPri

+ +USec

a)

en06000591.vsdIEC06000591 V1 EN

Figure 31: Commonly used markings of VT terminals

Where:

a) is the symbol and terminal marking used in this document. Terminals marked with a dotindicate the primary and secondary winding terminals with the same (positive) polarity

b) is the equivalent symbol and terminal marking used by IEC (ANSI) standard for phase-to-earth connected VTs

c) is the equivalent symbol and terminal marking used by IEC (ANSI) standard for open deltaconnected VTs

d) is the equivalent symbol and terminal marking used by IEC (ANSI) standard for phase-to-phase connected VTs

It shall be noted that depending on national standard and utility practices the ratedsecondary voltage of a VT has typically one of the following values:

• 100 V• 110 V• 115 V• 120 V• 230 V

The IED fully supports all of these values and most of them will be shown in thefollowing examples.

4.2.3.3 Examples on how to connect a three phase-to-earth connected VT tothe IED

Figure 32 gives an example about the wiring of a a three phase-to-earth connectedVT to the IED. It gives also an overview of the actions which are needed to makethis measurement available to the built-in protection and control functions withinthe IED.

Section 4 1MRK 504 134-UEN -Analog inputs

80Application Manual

Page 87: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

For correct terminal designations, see the connection diagramsvalid for the delivered IED.

L1

IEDL2

L3

663

1103

kV

V

4 1

3

2

663

1103

kV

V

663

1103

kV

V

IEC11000031-5-en.vsd

SMAI_20_2BLOCKREVROT^GRP2L1^GRP2L2^GRP2L3^GRP2N

AI3PAI1AI2AI3AI4AIN

IEC11000031 V5 EN

Figure 32: A Three phase-to-earth connected VT

1MRK 504 134-UEN - Section 4Analog inputs

81Application Manual

Page 88: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Where:

1) shows how to connect three secondary phase-to-earth voltages to three VT inputs onthe IED

2) is the TRM or AIM where these three voltage inputs are located. For these threevoltage inputs, the following setting values shall be entered:VTprim =66 kVVTsec = 110 VThe ratio of the entered values exactly corresponds to the ratio of one individual VT.

6666 3

1101103

=

EQUATION1903 V1 EN (Equation 31)

3) are three connections made in Signal Matrix Tool (SMT), which connect these threevoltage inputs to first three input channels of the preprocessing function block 4).Depending on the type of functions which need this voltage information, more then onepreprocessing block might be connected in parallel to these three VT inputs. Section SMAIprovides information on adaptive frequency tracking for the signal matrix for analogueinputs (SMAI).

4) is a Preprocessing block that has the task to digitally filter the connected analog inputsand calculate:

• fundamental frequency phasors for all four input channels• harmonic content for all four input channels• positive, negative and zero sequence quantities by using the fundamental

frequency phasors for the first three input channels (channel one taken asreference for sequence quantities)

These calculated values are then available for all built-in protection and controlfunctions within the IED, which are connected to this preprocessing function block in theconfiguration tool. For this application most of the preprocessing settings can be left tothe default values.If frequency tracking and compensation is required (this feature is typically requiredonly for IEDs installed in power plants), then the setting parameters DFTReferenceshall be set accordingly.Section “Signal matrix for analog inputs SMAI” provides information on adaptivefrequency tracking for the signal matrix for analogue inputs (SMAI).

4.2.3.4 Example on how to connect a phase-to-phase connected VT to the IED

Figure 33 gives an example how to connect a phase-to-phase connected VT to theIED. It gives an overview of the required actions by the user in order to make thismeasurement available to the built-in protection and control functions within theIED as well. It shall be noted that this VT connection is only used on lower voltagelevels (that is, rated primary voltage below 40 kV).

For correct terminal designations, see the connection diagramsvalid for the delivered IED.

Section 4 1MRK 504 134-UEN -Analog inputs

82Application Manual

Page 89: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

L1

IED

L2

L3

1

2 3

4

13.8120

kVV

IEC11000032-1-en.vsd

SMAI_20

IEC11000032 V1 EN

Figure 33: A Phase-to-phase connected VT

Where:

1) shows how to connect the secondary side of a phase-to-phase VT to the VT inputs on theIED

2) is the TRM or AIM where this voltage input is located. The following setting values shall beentered:VTprim=13.8 kVVTsec=120 V

3) are three connections, which connects these three voltage inputs to three input channelsof the preprocessing function block 4). Depending on the type of functions, which need thisvoltage information, more than one preprocessing block might be connected in parallel tothese three VT inputs

4) Preprocessing block has a task to digitally filter the connected analog inputs and calculate:

• fundamental frequency phasors for all four input channels• harmonic content for all four input channels• positive, negative and zero sequence quantities by using the fundamental frequency

phasors for the first three input channels (channel one taken as reference forsequence quantities)

These calculated values are then available for all built-in protection and control functionswithin the IED, which are connected to this preprocessing function block. For thisapplication most of the preprocessing settings can be left to the default values. Howeverthe following settings shall be set as shown here:ConnectionType=Ph-PhUBase=13.8 kVIf frequency tracking and compensation is required (this feature is typically required onlyfor IEDs installed in the generating stations) then the setting parameters DFTReferenceshall be set accordingly.

1MRK 504 134-UEN - Section 4Analog inputs

83Application Manual

Page 90: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

4.2.3.5 Example how to connect the open delta VT to the IED for lowimpedance earthed or solidly earthed power systems

Figure 34 gives an example about the connection of an open delta VT to the IEDfor low impedance earthed or solidly earthed power systems. It shall be noted thatthis type of VT connection presents secondary voltage proportional to 3U0 to the IED.

In case of a solid earth fault close to the VT location the primary value of 3Uo willbe equal to:

33

Ph PhPh E

UUo U-

-= =

EQUATION1926 V1 EN (Equation 32)

The primary rated voltage of such VT is always equal to UPh-E Therefore, threeseries connected VT secondary windings will give the secondary voltage equalonly to one individual VT secondary winding rating. Thus the secondary windingsof such open delta VTs quite often has a secondary rated voltage close to rated phase-to-phase VT secondary voltage, that is, 115V or 115/√3V as in this particularexample. Figure 34 gives an overview of the actions which are needed to make thismeasurement available to the built-in protection and control functions within the IED.

For correct connections, see the connection diagrams valid for thedelivered IED.

Section 4 1MRK 504 134-UEN -Analog inputs

84Application Manual

Page 91: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

L1

IEDL2

L3

1383

1153

kV

V

+3Uo

1383

1153

kV

V

1383

1153

kV

V

1

2

3

4

IEC11000035-1-en.vsd

SMAI_20

IEC11000035 V1 EN

Figure 34: Open delta connected VT in low impedance or solidly earthed power system

1MRK 504 134-UEN - Section 4Analog inputs

85Application Manual

Page 92: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Where:

1) The drawing shows the wiring of the secondary side of the open delta VT to one VTinput in the IED.

+3Uo shall be connected to the IED.

2) The voltage inputs are located on the TRM or AIM modules. The following settingvalues shall be entered for this voltage channel:

1383 138

3VTprim kV= × =

EQUATION1928 V1 EN (Equation 33)

115sec 3 115

3VT V= × =

EQUATION1929 V1 EN (Equation 34)

Inside the IED, only the ratio of these two parameters is used. It shall be noted thatthe ratio of the entered values exactly corresponds to ratio of one individual opendelta VT.

138138 3

1151153

=

EQUATION1930 V1 EN (Equation 35)

3) These connections are the links between the voltage input and the input channel ofthe preprocessing function block 4).

4) The preprocessing block has the task to digitally filter the connected analog inputsand calculate:

• fundamental frequency phasors for all four input channels• harmonic content for all four input channels• positive, negative and zero sequence quantities by using the fundamental

frequency phasors for the first three input channels (channel one taken asreference for sequence quantities)

These calculated values are then available for all built-in protection and controlfunctions within the IED, which are connected to this preprocessing function block.For this application most of the preprocessing settings can be left to the default values.If frequency tracking and compensation is required (this feature is typically requiredonly for IEDs installed in the generating stations) then the setting parametersDFTReference shall be set accordingly.Section preprocessing blocks SMAI provides information on adaptive frequencytracking for the signal matrix for analogue inputs (SMAI).

4.2.3.6 Example on how to connect a neutral point VT to the IED

Figure 35 gives an example on how to connect a neutral point VT to the IED. Thistype of VT connection presents secondary voltage proportional to U0 to the IED.

Section 4 1MRK 504 134-UEN -Analog inputs

86Application Manual

Page 93: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

In case of a solid earth fault in high impedance earthed or unearthed systems theprimary value of Uo voltage will be equal to:

03

Ph PhPh E

UU U--= =

EQUATION1931 V2 EN (Equation 36)

Figure 35 gives an overview of required actions by the user in order to make thismeasurement available to the built-in protection and control functions within theIED as well.

For correct terminal designations, see the connection diagramsvalid for the delivered IED.

L1 L2 L3

IED

6.63

100

kV

V

RUo

1

IEC11000036-1-en.vsd

4

SMAI_20

3

Protected Object

2

IEC11000036 V1 EN

Figure 35: Neutral point connected VT

1MRK 504 134-UEN - Section 4Analog inputs

87Application Manual

Page 94: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Where:

1) shows how to connect the secondary side of neutral point VT to one VT input in the IED.

U0 shall be connected to the IED.

2) is the TRM or AIM where this voltage input is located. For this voltage input the followingsetting values shall be entered:

6.63.81

3VTprim kV= =

EQUATION1933 V1 EN (Equation 37)

sec 100VT V=

EQUATION1934 V1 EN (Equation 38)

3) shows the connection which connects this voltage input to the fourth input channel of thepreprocessing function block 4).

4) is a preprocessing block that has the task to digitally filter the connected analog inputs andcalculate:These calculated values are then available for all built-in protection and control functionswithin the IED, which are connected to this preprocessing function block. For thisapplication most of the preprocessing settings can be left to the default values.If frequency tracking and compensation is required (this feature is typically required onlyfor IEDs installed in the generating stations) then the setting parameters DFTReferenceshall be set accordingly.Section preprocessing blocks SMAI provides information on adaptive frequency trackingfor the signal matrix for analogue inputs (SMAI).

Section 4 1MRK 504 134-UEN -Analog inputs

88Application Manual

Page 95: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Section 5 Local human-machine interface

5.1 Local HMI

IEC12000175 V1 EN

Figure 36: Local human-machine interface

The LHMI of the IED contains the following elements:

• Display (LCD)• Buttons• LED indicators• Communication port for PCM600

The LHMI is used for setting, monitoring and controlling.

5.1.1 DisplayThe LHMI includes a graphical monochrome display with a resolution of 320 x240 pixels. The character size can vary. The amount of characters and rows fittingthe view depends on the character size and the view that is shown.

The display view is divided into four basic areas.

1MRK 504 134-UEN - Section 5Local human-machine interface

89Application Manual

Page 96: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

IEC13000063-1-en.vsd

IEC13000063 V1 EN

Figure 37: Display layout

1 Path

2 Content

3 Status

4 Scroll bar (appears when needed)

The function button panel shows on request what actions are possible with thefunction buttons. Each function button has a LED indication that can be used as afeedback signal for the function button control action. The LED is connected to therequired signal with PCM600.

IEC12000025-2-en.vsd

IEC12000025 V2 EN

Figure 38: Function button panel

Section 5 1MRK 504 134-UEN -Local human-machine interface

90Application Manual

Page 97: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

The alarm LED panel shows on request the alarm text labels for the alarm LEDs.Three alarm LED pages are available.

GUID-D20BB1F1-FDF7-49AD-9980-F91A38B2107D V1 EN

Figure 39: Alarm LED panel

The function button and alarm LED panels are not visible at the same time. Eachpanel is shown by pressing one of the function buttons or the Multipage button.Pressing the ESC button clears the panel from the display. Both the panels havedynamic width that depends on the label string length that the panel contains.

5.1.2 LEDsThe LHMI includes three protection status LEDs above the display: Ready, Startand Trip.

There are 15 programmable alarm LEDs on the front of the LHMI. Each LED canindicate three states with the colors: green, yellow and red. The alarm texts relatedto each three-color LED are divided into three pages.

There are 3 separate pages of LEDs available. The 15 physical three-color LEDs inone LED group can indicate 45 different signals. Altogether, 135 signals can beindicated since there are three LED groups. The LEDs can be configured withPCM600 and the operation mode can be selected with the LHMI or PCM600.

5.1.3 KeypadThe LHMI keypad contains push-buttons which are used to navigate in differentviews or menus. The push-buttons are also used to acknowledge alarms, resetindications, provide help and switch between local and remote control mode.

The keypad also contains programmable push-buttons that can be configured eitheras menu shortcut or control buttons.

1MRK 504 134-UEN - Section 5Local human-machine interface

91Application Manual

Page 98: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

IEC11000247 V2 EN

Figure 40: LHMI keypad with object control, navigation and command push-buttons and RJ-45 communication port

1...5 Function button

6 Close

7 Open

8 Escape

9 Left

10 Down

11 Up

12 Right

13 User Log on

14 Enter

15 Remote/Local

16 Uplink LED

17 Ethernet communication port (RJ-45)

18 Multipage

19 Menu

20 Clear

21 Help

22 Programmable alarm LEDs

23 Protection status LEDs

5.1.4 Local HMI functionality

5.1.4.1 Protection and alarm indication

Protection indicatorsThe protection indicator LEDs are Ready, Start and Trip.

The start and trip LEDs are configured via the disturbance recorder.

Section 5 1MRK 504 134-UEN -Local human-machine interface

92Application Manual

Page 99: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

The yellow and red status LEDs are configured in the disturbancerecorder function, DRPRDRE, by connecting a start or trip signalfrom the actual function to a BxRBDR binary input function blockusing the PCM600 and configure the setting to Off, Start or Trip forthat particular signal.

Table 8: Ready LED (green)

LED state DescriptionOff Auxiliary supply voltage is disconnected.

On Normal operation.

Flashing Internal fault has occurred.

Table 9: Start LED (yellow)

LED state DescriptionOff Normal operation.

On A protection function has started and an indication message is displayed.

• The start indication is latching and must be reset via communicationor by pressing .

Flashing A flashing yellow LED has a higher priority than a steady yellow LED.The IED is in test mode and protection functions are blocked.

• The indication disappears when the IED is no longer in test modeand blocking is removed.

Table 10: Trip LED (red)

LED state DescriptionOff Normal operation.

On A protection function has tripped and an indication message is displayed.

• The trip indication is latching and must be reset via communicationor by pressing .

Alarm indicatorsThe 15 programmable three-color LEDs are used for alarm indication. Anindividual alarm/status signal, connected to any of the LED function blocks, can beassigned to one of the three LED colors when configuring the IED.

1MRK 504 134-UEN - Section 5Local human-machine interface

93Application Manual

Page 100: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Table 11: Alarm indications

LED state DescriptionOff Normal operation. All activation signals are off.

On • Follow-S sequence: The activation signal is on.• LatchedColl-S sequence: The activation signal is on, or it is off but the indication

has not been acknowledged.• LatchedAck-F-S sequence: The indication has been acknowledged, but the

activation signal is still on.• LatchedAck-S-F sequence: The activation signal is on, or it is off but the

indication has not been acknowledged.• LatchedReset-S sequence: The activation signal is on, or it is off but the

indication has not been acknowledged.

Flashing • Follow-F sequence: The activation signal is on.• LatchedAck-F-S sequence: The activation signal is on, or it is off but the

indication has not been acknowledged.• LatchedAck-S-F sequence: The indication has been acknowledged, but the

activation signal is still on.

5.1.4.2 Parameter management

The LHMI is used to access the IED parameters. Three types of parameters can beread and written.

• Numerical values• String values• Enumerated values

Numerical values are presented either in integer or in decimal format withminimum and maximum values. Character strings can be edited character bycharacter. Enumerated values have a predefined set of selectable values.

5.1.4.3 Front communication

The RJ-45 port in the LHMI enables front communication.

• The green uplink LED on the left is lit when the cable is successfullyconnected to the port.

Section 5 1MRK 504 134-UEN -Local human-machine interface

94Application Manual

Page 101: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

GUID-D71BA06D-3769-4ACB-8A32-5D02EA473326 V1 EN

Figure 41: RJ-45 communication port and green indicator LED

1 RJ-45 connector

2 Green indicator LED

When a computer is connected to the IED front port with a crossed-over cable, theIED's DHCP server for the front interface assigns an IP address to the computer ifDHCPServer = On. The default IP address for the front port is 10.1.150.3.

Do not connect the IED front port to a LAN. Connect only a singlelocal PC with PCM600 to the front port.

1MRK 504 134-UEN - Section 5Local human-machine interface

95Application Manual

Page 102: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

96

Page 103: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Section 6 Differential protection

6.1 Transformer differential protection T2WPDIF andT3WPDIF

6.1.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Transformer differential protection, two-winding

T2WPDIF

3Id/I

SYMBOL-BB V1 EN

87T

Transformer differential protection,three-winding

T3WPDIF

3Id/I

SYMBOL-BB V1 EN

87T

6.1.2 ApplicationThe transformer differential protection is a unit protection. It serves as the mainprotection of transformers in case of winding failure. The protective zone of adifferential protection includes everything between the connected CTs. Thisincludes the transformer and may include the bus-works or cables and also thegenerator stator windings when implemented as a block scheme.

A transformer differential protection compares the current flowing into thetransformer with the current leaving the transformer. A correct analysis of faultconditions by the differential protection must take into consideration changes dueto the voltage, current and phase angle transformation caused by the protectedtransformer. Traditional transformer differential protection functions requiredauxiliary transformers for correction of the phase shift and transformation ratio.The numerical microprocessor based differential algorithm as implemented in theRET670 compensates for both the turns-ratio and the phase shift internally in thesoftware. No auxiliary current transformers are necessary.

The differential current should theoretically be zero during normal load or duringexternal faults if the turn-ratio and the phase shift are correctly compensated for.However, there are several different phenomena other than internal faults that will

1MRK 504 134-UEN - Section 6Differential protection

97Application Manual

Page 104: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

cause result in unwanted and false differential currents. The main reasons forunwanted differential currents are:

• mismatch due to varying tap changer positions• different characteristics, loads and operating conditions of the current

transformers• zero sequence currents that only flow on one side of the power transformer• normal magnetizing currents• magnetizing inrush currents• overexcitation magnetizing currents

6.1.3 Setting guidelinesThe parameters for the Transformer differential protection function are set via thelocal HMI or Protection and Control IED Manager (PCM600).

IED values for the primary current (setting IBase), the primary voltage (settingUBase) and the primary power (setting SBase) for a particular winding are set as aglobal base value GBASVAL. The settings GlobalBaseSelW1, GlobalBaseSelW2and GlobalBaseSelW3 in the differential protection function are used to select thecorresponding GBASVAL function as a reference.

6.1.3.1 Inrush restraint methods

With a combination of the second harmonic restraint and the waveform restraintmethods it is possibly to create a protection with high security and stability againsttransformer inrush effects and at the same time maintain stability in case of heavyexternal faults, even if the current transformers are saturated. The second harmonicrestraint function has a settable level. If the ratio of the second harmonic tofundamental harmonic content in the differential current is above the settable limit,the operation of the differential protection is restrained. It is recommended to keepthe parameter I2/I1Ratio = 15% as the default value in case no special reasons existto choose a different value.

6.1.3.2 Overexcitation restraint method

In case of an overexcited transformer, the winding currents contain odd harmoniccomponents because the currents waveform are symmetrical relative to the timeaxis. As the third harmonic currents cannot flow into a delta winding, the fifthharmonic is the lowest harmonic which can serve as a criterion for overexcitation.The differential protection function is provided with a fifth harmonic restraint toprevent the protection from operation during an overexcitation condition of apower transformer. If the ratio of the fifth harmonic to fundamental harmonic in thedifferential current is above a settable limit the operation is restrained. It isrecommended to use I5/I1Ratio = 25% as default value in case no special reasonsexist to choose another setting. Transformers likely to be exposed to overvoltage orunderfrequency conditions (that is, generator step-up transformers in power

Section 6 1MRK 504 134-UEN -Differential protection

98Application Manual

Page 105: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

stations) should be provided with an overexcitation protection based on V/Hz toachieve a trip before the core thermal limit is reached.

6.1.3.3 Cross-blocking between phases

The basic definition of cross-blocking is that one of the three phases can blockoperation (that is, tripping) of the other two phases due to the harmonic pollution(2nd or 5th harmonic content) or waveform characteristic of the differential currentin that phase; the user can control the cross-blocking between the phases via thesetting parameter CrossBlockEn.

When the parameter CrossBlockEn is set to On, cross blocking between phases willbe introduced. The phase with the operating point above the set bias characteristicwill be able to cross-block the other two phases if it is self-blocked by any of thepreviously explained restrain criteria. As soon as the operating point for this phaseis below the set bias characteristic, cross blocking from that phase will be inhibited.The default (recommended) setting value for this parameter is On. When parameterCrossBlockEn is set to Off, any cross blocking between phases will be disabled.

6.1.3.4 Restrained and unrestrained differential protection

The first section of the restrain characteristic gives the highest sensitivity and isused to determine small or high impedance fault within the protected zone.

The second section of the restrain characteristic has an increased slope in order todeal with increased differential current due to additional power transformer lossesduring heavy loading of the transformer and external fault currents. The thirdsection of the restrain characteristic decreases the sensitivity of the restraineddifferential function further in order to cope with CT saturation and transformerlosses during heavy through faults. A default setting for the operating characteristicwith IdMin = 0.3 * IBase is recommended in normal applications. If the conditionsare known in more detail, higher or lower sensitivity can be chosen. The selectionof suitable characteristic should in such cases be based on the knowledge of theclass of the current transformers, availability of information on the tap changerposition, short circuit power of the systems, and so on.

The unrestrained operation level has a default value of IdUnre = 10pu, which istypically acceptable for most of the standard power transformer applications. In thefollowing case, this setting need to be changed accordingly:

• For differential applications on HV shunt reactors, due to the fact that there isno heavy through-fault condition, the unrestrained differential operation levelcan be set to IdUnre = 1.75pu for additional security

The overall operating characteristic of the transformer differential protection isshown in figure 42.

1MRK 504 134-UEN - Section 6Differential protection

99Application Manual

Page 106: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Section 1

Operate conditionally

UnrestrainedLimit

Section 2 Section 3

Restrain

Operate unconditionally

5

4

3

2

1

00 1 2 3 4 5

IdMin

EndSection1

EndSection2restrain current[ times IBase ]

operate current[ times IBase ]

SlopeSection2

SlopeSection3

en05000187-2.vsdIEC05000187 V2 EN

Figure 42: Representation of the restrained-, and the unrestrained operatecharacteristics

100%Ioperateslope IrestrainD= D ×

EQUATION1246 V1 EN (Equation 39)

and where the restrained characteristic is defined by the settings:

1. IdMin

2. EndSection1

3. EndSection2

4. SlopeSection2

5. SlopeSection3

6.1.3.5 Elimination of zero sequence currents

A differential protection may operate unwanted due to external earth-faults in caseswhere the zero sequence current can flow on only one side of the powertransformer. This is the case when zero sequence current cannot be properlytransformed to the other side of the power transformer. Power transformer

Section 6 1MRK 504 134-UEN -Differential protection

100Application Manual

Page 107: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

connection groups of the Yd or Dy type cannot transform zero sequence current. Ifa delta winding of a power transformer is earthed via an earthing transformer insidethe zone protected by the differential protection there will be an unwanteddifferential current in case of an external earth-fault. The same is true for anearthed star winding. Even if both the star and delta winding are earthed, the zerosequence current is usually limited by the earthing transformer on the delta side ofthe power transformer, which may result in differential current as well. To makethe overall differential protection insensitive to external earth-faults in thesesituations the zero sequence currents must be eliminated from the powertransformer IED currents on the earthed windings, so that they do not appear asdifferential currents. The elimination of zero sequence current is done numericallyby setting ZSCurrSubtrWx=Off or On and doesn't require no auxiliary transformersor zero sequence traps.

6.1.3.6 Internal/External fault discriminator

The internal/external fault discriminator operation is based on the relative positionof the two phasors (in case of a two-winding transformer) representing the W1 andW2 negative sequence current contributions. It performs a directional comparisonbetween these two phasors.

In order to perform a directional comparison of the two phasors their magnitudesmust be high enough so that one can be sure that they are due to a fault. On theother hand, in order to guarantee a good sensitivity of the internal/external faultdiscriminator, the value of this minimum limit must not be too high. Therefore thislimit value (IMinNegSeq) is settable in the range from 1% to 20% of the respectivewinding current. The default value is 4%. Only if the magnitude of both negativesequence current contributions are above the set limit, the relative position betweenthese two phasors is checked. If either of the negative sequence currentcontributions is too small (less than the set value for IMinNegSeq), no directionalcomparison is made in order to avoid the possibility to produce a wrong decision.

This magnitude check, guarantees stability of the algorithm when the powertransformer is energized, since no current will be measured on the low voltage sideof the power transformer. In cases where the protected transformer can beenergized with a load connected on the LV side (e.g. a step-up transformer in apower station with directly connected auxiliary transformer on its LV side) thevalue for this setting shall be increased to at least 12%. This is necessary in order toprevent unwanted operation due to LV side currents during the transformerenergization.

The setting NegSeqROA represents the so-called Relay Operate Angle, whichdetermines the boundary between the internal and external fault regions. It can beselected in the range from 30 degrees to 90 degrees, with a step of 1 degree. Thedefault value is 60 degrees. The default setting 60 degrees somewhat favorssecurity in comparison to dependability. If the user has no well-justified reason foranother value, 60 degrees shall be applied.

1MRK 504 134-UEN - Section 6Differential protection

101Application Manual

Page 108: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

If the above conditions concerning magnitudes are fulfilled, the internal/externalfault discriminator compares the relative phase angle between the negativesequence current contributions from the HV side and LV side of the powertransformer using the following two rules (assuming both CT's have their earthingpoint connected towards the object):

• If the negative sequence currents contributions from HV and LV sides are inphase or at least in the internal fault region, the fault is internal.

• If the negative sequence currents contributions from HV and LV sides are 180degrees out of phase or at least in the external fault region, the fault is external.

Under external fault condition and with no current transformer saturation, therelative angle is theoretically equal to 180 degrees. During internal fault and withno current transformer saturation, the angle shall ideally be 0 degrees, but due topossible different negative sequence source impedance angles on HV and LV sideof power transformer, it may differ somewhat from the ideal zero value.

The internal/external fault discriminator has proved to be very reliable. If a fault isdetected, and at the same time the internal/external fault discriminator characterizesthis fault as an internal, any eventual blocking signals produced by either theharmonic or the waveform restraints are ignored.

If the bias current is more than 110% of IBase, the negative sequence threshold(IMinNegSeq) is increased linearly to desensitize the internal/external faultdiscriminator during through faults and CT saturation, which will create falsenegative sequence currents. This assures response times of the differentialprotection below one power system cycle (below 20 ms for 50 Hz system) for allmore severe internal faults. Even for heavy internal faults with severely saturatedcurrent transformers the internal/external fault discriminator will make thedifferential protection operate well below one cycle, since the harmonic distortionsin the differential currents do not slow down the differential protection operation.

The sensitive negative sequence current based differential protection, which detectsminor internal faults, and where the speed is not as essential as stability againstunwanted trips, is restrained when the bias current is more than 150% of IBase. Forthe sensitive negative sequence protection to be reactivated, the bias current mustdrop back below 110% of IBase. The sensitive negative sequence protection isalways restrained by the harmonic restraint.

External faults happen ten to hundred times more often than internal ones as far asthe power transformers are concerned. If a disturbance is detected and the internal/external fault discriminator characterizes this fault as an external fault, theconventional additional criteria (2nd harmonic, 5th harmonic, waveform block) areposed on the differential algorithm before its trip is allowed. This assures highstability during external faults. However, at the same time the differential functionis still capable of trip ping quickly for evolving faults.

The principle of the internal/external fault discriminator can be extended toautotransformers and transformers with three windings. If all three windings are

Section 6 1MRK 504 134-UEN -Differential protection

102Application Manual

Page 109: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

connected to their respective networks then three directional comparisons aremade, but only two comparisons are necessary in order to positively determine theposition of the fault with respect to the protected zone. The directional comparisonsare: W1 - (W2 + W3); W2 - (W1 + W3); W3 - (W1 + W2). The rule applied by theinternal/external fault discriminator in case of three-winding power transformers is:

• If all comparisons indicate an internal fault, then it is an internal fault.• If any comparison indicates an external fault, then it is an external fault

If one of the windings is not connected, the algorithm automatically reduces to thetwo-winding version. Nevertheless, the whole power transformer is protected,including the non-connected winding.

6.1.3.7 Differential current alarm

Differential protection continuously monitors the level of the fundamentalfrequency differential currents and gives an alarm if the pre-set value issimultaneously exceeded in all three phases. Set the time delay defined byparameter tAlarmDelay two times longer than the on-load tap-changer mechanicaloperating time (For example, typical setting value 10s).

6.1.3.8 Switch onto fault feature

The Transformer differential (TW2PDIF for two winding and TW3PDIF for threewinding) function in the IED has a built-in, advanced switch onto fault feature.This feature can be enabled or disabled by the setting parameter SOTFMode. WhenSOTFMode = On this feature is enabled. It shall be noted that when this feature isenabled it is not possible to test the 2nd harmonic blocking feature by simplyinjecting one current with superimposed second harmonic. In that case the switchon to fault feature will operate and the differential protection will trip. However fora real inrush case the differential protection function will properly restrain fromoperation.

For more information about the operating principles of the switch onto fault featureplease read the “Technical Manual”..

6.1.4 Setting example

6.1.4.1 CT Connections

The IED has been designed with the assumption that all main CTS are starconnected. The IED can be used in applications where the main CTs are deltaconnected. For such applications the following shall be kept in mind:

1MRK 504 134-UEN - Section 6Differential protection

103Application Manual

Page 110: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

1. The ratio for delta connected CTs shall be set √(3)=1.732 times smaller thanthe actual individual phase CT ratio.

2. The power transformer vector group shall typically be set as Yy0 because thecompensation for the actual phase shift is provided by the external delta CTconnection.

3. The zero sequence current is eliminated by the main CT delta connections.Thus on sides where CTs are connected in delta the zero sequence currentelimination shall be set to Off in the IED.

The following table summarizes the most commonly used star-delta vector groupsaround the world and provides information about the required type of main CTdelta connection on the star side of the protected transformer.

IEC vector group Positive sequence no-loadvoltage phasor diagram

Required delta CT connection type on star sideof the protected power transformer and internalvector group setting in the IED

YNd1 Y

IEC06000559 V1 EN

Yy0

Dyn1Y

IEC06000560 V1 EN

Yy0

YNd11 Y

IEC06000561 V1 EN

Yy0

Table continues on next page

Section 6 1MRK 504 134-UEN -Differential protection

104Application Manual

Page 111: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

IEC vector group Positive sequence no-loadvoltage phasor diagram

Required delta CT connection type on star sideof the protected power transformer and internalvector group setting in the IED

Dyn11

Y

IEC06000562 V1 EN

Yy0

YNd5 Y

IEC06000563 V1 EN

Yy6

Dyn5

YIEC06000564 V1 EN

Yy6

6.2 Restricted earth-fault protection, low impedanceREFPDIF

6.2.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Restricted earth-fault protection, lowimpedance

REFPDIF

IdN/I

SYMBOL-AA V1 EN

87N

1MRK 504 134-UEN - Section 6Differential protection

105Application Manual

Page 112: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

6.2.2 ApplicationA breakdown of the insulation between a transformer winding and the core or thetank may result in a large fault current which causes severe damage to the windingsand the transformer core. A high gas pressure may develop, damaging thetransformer tank.

Fast and sensitive detection of earth faults in a power transformer winding can beobtained in solidly earthed or low impedance earthed networks by the restricted earth-fault protection. The only requirement is that the power transformer winding isconnected to earth in the star point (in case of star-connected windings) or througha separate earthing transformer (in case of delta-connected windings).

The low impedance restricted earth-fault protection REFPDIF is a windingprotection function. It protects the power transformer winding against faultsinvolving earth. Observe that single phase-to-earth faults are the most commonfault types in transformers. A sensitive earth-fault protection is therefore desirable.

A restricted earth-fault protection is the fastest and the most sensitive protection, apower transformer winding can have and will detect faults such as:

• earth faults in the transformer winding when the network is earthed through animpedance

• earth faults in the transformer winding in solidly earthed network when thepoint of the fault is close to the winding star point.

The restricted earth-fault protection is not affected, as a differential protection, withthe following power transformer related phenomena:

• magnetizing inrush currents• overexcitation magnetizing currents• load tap changer• external and internal phase faults which do not involve earth• symmetrical overload conditions

Due to its features, REFPDIF is often used as a main protection of the transformerwinding for all faults involving earth.

6.2.2.1 Application examples

Transformer winding, solidly earthedThe most common application is on a solidly earthed transformer winding. Theconnection is shown in figure 43.

Section 6 1MRK 504 134-UEN -Differential protection

106Application Manual

Page 113: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

IEC09000109-4-en.vsd

REFDIF

I3PW1CT1

I3P

IdN/I

Protected winding

IEC09000109-4-EN V1 EN

Figure 43: Connection of the low impedance Restricted earth-fault functionREFPDIF for a directly (solidly) earthed transformer winding

Transformer winding, earthed through zig-zag earthing transformerA common application is for low reactance earthed transformer where the earthingis through separate zig-zag earthing transformers. The fault current is then limitedto typical 800 to 2000 A for each transformer. The connection for this applicationis shown in figure 44.

1MRK 504 134-UEN - Section 6Differential protection

107Application Manual

Page 114: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

REFDIF - 1

I3PW1CT1

I3P

IdN/I

Protectedwinding W1

I3PW2CT1

I3P

IdN/I

REFDIF - 2

Protected winding W2

Earthingtransformer

IEC09000110-4-en.vsd

IEC09000110-4-EN V1 EN

Figure 44: Connection of the low impedance Restricted earth-fault functionREFPDIF for a zig-zag earthing transformer

Autotransformer winding, solidly earthedAutotransformers can be protected with the low impedance restricted earth-faultprotection function REFPDIF. The complete transformer will then be protectedincluding the HV side, the neutral connection and the LV side. The connection ofREFPDIF for this application is shown in figure 45.

Section 6 1MRK 504 134-UEN -Differential protection

108Application Manual

Page 115: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

IEC09000111-4-en.vsd

Auto -transformer

REFDIF

I3PW1CT1

I3P

IdN/I

I3PW2CT1

HV (W1)

LV (W2)

IEC09000111-4-EN V1 EN

Figure 45: Connection of restricted earth fault, low impedance functionREFPDIF for an autotransformer, solidly earthed

Reactor winding, solidly earthedReactors can be protected with the low impedance restricted earth fault protectionfunction REFPDIF. The connection of REFPDIF for this application is shown infigure 46.

1MRK 504 134-UEN - Section 6Differential protection

109Application Manual

Page 116: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Reactor

REFDIF

I3PW1CT1

I3P

IdN/I

IEC09000112-4-en.vsdIEC09000112-4 V1 EN

Figure 46: Connection of the low impedance restricted earth-fault protectionfunction REFPDIF for a solidly earthed reactor

CT earthing directionTo make thelow impedance restricted earth-fault protection functionREFPDIFoperate correctly, the main CTs are always supposed to be starconnected. The main CT's neutral (star) formation can be positioned in either way,ToObject or FromObject.

6.2.3 Setting guidelines

6.2.3.1 Setting and configuration

Analog input signalsI3P: Neutral point current .

I3PW1CT1: Phase currents for winding 1.

I3PW2CT1: Phase currents for winding 2. Used only for autotransformers.

Section 6 1MRK 504 134-UEN -Differential protection

110Application Manual

Page 117: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Binary input signalsBLOCK: The input will block the operation of the function. Can be used, forexample, to block for a limited time the operation during special service conditions.

Binary output signalsSTART: The start output indicates that Idiff is in the operate region of thecharacteristic. It can be used to initiate disturbance recorder.

TRIP: The trip output is activated when all operating criteria are fulfilled.

DIROK: The output is activated when the directional criteria has been fulfilled.The output can be used for information purposes normally during testing. It can bechecked from the debug tool or connected as a signal to the disturbance recorder.The information is also available on the local HMI.

BLK2H: The output is activated when the function is blocked due to a too highlevel of second harmonics. The output can be used for information purposesnormally during testing. It can be checked from the debug tool or connected as asignal to the disturbance recorder. The information is also available on the local HMI.

6.2.3.2 Settings

The parameters for the low impedance restricted earth fault protection functionREFPDIF are set via the local HMI or through the Protection and Control Manager(PCM600).

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

Operation: The operation of REFPDIF can be switched On/Off.

IdMin: The setting gives the minimum operation value. The setting is in percent ofthe IBase value. The neutral current (I3P) must always be larger than half of thisvalue. A normal setting is 30% of power transformer-winding rated current for thesolidly earthed winding.

6.3 1Ph High impedance differential protection HZPDIF

6.3.1 Identification

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

1Ph High impedance differentialprotection HZPDIF Id

SYMBOL-CC V2 EN

87

1MRK 504 134-UEN - Section 6Differential protection

111Application Manual

Page 118: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

6.3.2 ApplicationThe 1Ph High impedance differential protection function HZPDIF can be used as arestricted earth fault protection.

Id

IEC05000177-2-en.vsdIEC05000177 V2 EN

Figure 47: Application of a 1Ph High impedance differential protectionHZPDIF function

6.3.2.1 The basics of the high impedance principle

The high impedance differential protection principle has been used for many yearsand is well documented. The operating characteristic provides very good sensitivityand high speed operation. One main benefit offered by the principle is an absolutestability (that is, no operation) for external faults even in the presence of heavy CTsaturation. The principle is based on the CT secondary current circulating betweeninvolved current transformers and not through the IED due to its high impedance,normally in the range of hundreds of ohms and sometimes above kiloohm. Whenan internal fault occurs the current cannot circulate and is forced through thedifferential circuit causing operation.

Section 6 1MRK 504 134-UEN -Differential protection

112Application Manual

Page 119: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Id

IEC05000164-2-en.vsd

R

Metrosil

IEC05000164 V3 EN

Figure 48: Example for the high impedance restricted earth fault protectionapplication

For a through fault one current transformer might saturate when the other CTs stillwill feed current. For such a case a voltage will be developed across the stabilisingresistor. The calculations are made with the worst situations in mind and aminimum operating voltage UR is calculated according to equation 40

( )maxUR IF Rct Rl> × +EQUATION1531 V1 EN (Equation 40)

where:

IFmax is the maximum through fault current at the secondary side of the CT

Rct is the current transformer secondary resistance and

Rl is the maximum loop resistance of the circuit at any CT.

1MRK 504 134-UEN - Section 6Differential protection

113Application Manual

Page 120: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

The minimum operating voltage has to be calculated (all loops) and the function isset higher than the highest achieved value (setting U>Trip). As the loop resistanceis the value to the connection point from each CT, it is advisable to do all the CTcore summations in the switchgear to have shortest possible loops. This will givelower setting values and also a better balanced scheme. The connection in to thecontrol room can then be from the most central bay.

For an internal fault, circulation is not possible, due to the high impedance.Depending on the size of current transformer, relatively high voltages will bedeveloped across the series resistor. Note that very high peak voltages can appear.To prevent the risk of flashover in the circuit, a voltage limiter must be included.The voltage limiter is a voltage dependent resistor (Metrosil).

The external unit with stabilizing resistor has a value of either 6800 ohms or 1800ohms (depending on ordered alternative) with a shorting link to allow adjustment tothe required value. Select a suitable value of the resistor based on the UR voltagecalculated. A higher resistance value will give a higher sensitivity and a lowervalue a lower sensitivity.

The function has a recommended operating current range 40 mA to 1.0A for 1 Ainputs and 200 mA to 5A for 5A inputs. This, together with the selected and setvalue, is used to calculate the required value of current at the set U>Trip andSeriesResitor values.

The CT inputs used for 1Ph High impedance differential protectionHZPDIF function, shall be set to have ratio 1:1. So the parametersCTsecx and CTprimx of the relevant channel x of TRM and/or AIMshall be set equal to 1 A by PST in PCM600; The parameterCTStarPointx may be set to ToObject.

The tables 12, 13 below show, the operating currents for different settings ofoperating voltages and selected resistances. Adjust as required based on tables 12,13 or to values in between as required for the application.

Minimum ohms can be difficult to adjust due to the small valuecompared to the total value.

Normally the voltage can be increased to higher values than the calculatedminimum U>Trip with a minor change of total operating values as long as this isdone by adjusting the resistor to a higher value. Check the sensitivity calculationbelow for reference.

Section 6 1MRK 504 134-UEN -Differential protection

114Application Manual

Page 121: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Table 12: 1 A channels: input with minimum operating down to 20 mA

OperatingvoltageU>Trip

Stabilizingresistor Rohms

Operatingcurrent level1 A

Stabilizingresistor Rohms

Operatingcurrent level1 A

Stabilizingresistor Rohms

Operatingcurrent level1 A

20 V 1000 0.020 A -- -- -- --

40 V 2000 0.020 A 1000 0.040 A -- --

60 V 3000 0.020 A 1500 0.040 A 600 0.100 A

80 V 4000 0.020 A 2000 0.040 A 800 0.100 A

100 V 5000 0.020 A 2500 0.040 A 1000 0.100 A

150 V 6000 0.020 A 3750 0.040 A 1500 0.100 A

200 V 6800 0.029 A 5000 0.040 A 2000 0.100 A

Table 13: 5 A channels: input with minimum operating down to 100 mA

OperatingvoltageU>Trip

Stabilizingresistor R1ohms

Operatingcurrent level5 A

Stabilizingresistor R1ohms

Operatingcurrent level5 A

Stabilizingresistor R1ohms

Operatingcurrent level5 A

20 V 200 0.100 A 100 0.200 A -- --

40 V 400 0.100 A 200 0.200 A 100 0.400

60 V 600 0.100 A 300 0.200 A 150 0.400 A

80 V 800 0.100 A 400 0.200 A 200 0.400 A

100 V 1000 0.100 A 500 0.200 A 250 0.400 A

150 V 1500 0.100 A 750 0.200 A 375 0.400 A

200 V 2000 0.100 A 1000 0.200 A 500 0.400 A

The current transformer saturating voltage must be at least 2 · U>Trip to havesufficient operating margin. This must be checked after calculation of U>Trip.

When the R value has been selected and the U>Trip value has been set, thesensitivity of the scheme IP can be calculated. The sensitivity is decided by thetotal current in the circuit according to equation 41.

( )IP n IR Ires lmag= × + +åEQUATION1747 V1 EN (Equation 41)

where:

n is the CT ratio

IP primary current at IED pickup,

IR IED pickup current

Ires is the current through the non-linear resistorand

ΣImag is the sum of the magnetizing currents from all CTs in the circuit (for example, 4 CTs forrestricted earth fault protection, 2 CTs for reactor differential protection, 3-5 CTs forautotransformer differential protection , the number of feeders, including the buscoupler,for busbar differential protection).

1MRK 504 134-UEN - Section 6Differential protection

115Application Manual

Page 122: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

It should be remembered that the vectorial sum of the currents must be used (IEDs,Metrosil and resistor currents are resistive). The current measurement is insensitiveto DC component in fault current to allow the use of only the AC components ofthe fault current in the above calculations.

The voltage dependent resistor (Metrosil) characteristic is shown in figure 52.

A shunt can be added in parallel to the non-linear resistor in order to desensitize thefunction.

Series resistor thermal capacityThe series resistor is dimensioned for 200 W. Preferable the U>Trip2/SeriesResistor should always be lower than 200 W to allow continuous activationduring testing. If this value is exceeded, testing should be done with a transient faults.

The series resistor is dimensioned for 200 W. The condition: U>Trip2/SeriesResistor shall be fulfilled. In this condition the continuous injection isallowed during testing.

Section 6 1MRK 504 134-UEN -Differential protection

116Application Manual

Page 123: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

I>

R

Rres

Rl

Rct Rct

Rl

UR

a) Through load situation

b) Through fault situation

UR

UR

c) Internal faults

UR

Protected Object

IEC05000427-2-en.vsd

IEC05000427 V2 EN

Figure 49: The high impedance principle for one phase with two currenttransformer inputs

1MRK 504 134-UEN - Section 6Differential protection

117Application Manual

Page 124: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

6.3.3 Connection examples for high impedance differentialprotection

WARNING! USE EXTREME CAUTION! Dangerously highvoltages might be present on this equipment, especially on the platewith resistors. Do any maintenance ONLY if the primary objectprotected with this equipment is de-energized. If required bynational law or standard, enclose the plate with resistors with aprotective cover or in a separate box.

6.3.3.1 Connections for 1Ph restricted earth fault and high impedancedifferential protection

Restricted earth fault protection REF is a typical application for 1Ph Highimpedance differential protection HZPDIF. Typical CT connections for highimpedance based REF protection scheme are shown in figure 50.

L1(A)

L2(B)

L3(C)

Protected Object

CT 1500/5Star/Wye

Connected

7

8

9

10

11

12

1

2

3

4

5

6

AI01 (I)

AI02 (I)

AI03 (I)

AI04 (I)

AI05 (I)

AI06 (I)

6

7

8

IED

X1

R1

12

4 5

U R2

13

4

2

1 2 3

N

1-Ph Plate with Metrosil and Resistor

23

5

4

9

N

L1(A)

L2(B)

L3(C)

CT

1500

/5

1

IEC07000194_2_en.vsd

AI3P

AI1

AI2

AI3

AI4

AIN

SMAI2

BLOCK

^GRP2L1

^GRP2L2

^GRP2L3

^GRP2N

TYPE

IEC07000194 V2 EN

Figure 50: CT connections for restricted earth fault protection

Pos Description

1 Scheme earthing point

Note that it is of outmost importance to insure that only one earthing pointexist in such scheme.

Section 6 1MRK 504 134-UEN -Differential protection

118Application Manual

Page 125: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

2 One-phase plate with stabilizing resistor and metrosil.

3 Necessary connection for the metrosil. Shown connections are applicable for both types of one-phase plate.

4 Position of optional test switch for secondary injection into the high impedance differential IED.

5 Necessary connection for stabilizing resistor. Shown connections are applicable for both typesof one-phase plate.

6 How to connect REFPDIF high impedance scheme to one CT input in IED.

7 Transformer input module where this current input is located.

Note that the CT ratio for high impedance differential protection applicationmust be set as one.

• For main CTs with 1A secondary rating the following setting values shall be entered:CTprim = 1A and CTsec = 1A

• For main CTs with 5A secondary rating the following setting values shall be entered:CTprim = 5A and CTsec = 5A

• The parameter CTStarPoint shall always be left to the default value ToObject

8 Connection made in the Signal Matrix, which connects this current input to first input channelof the preprocessing function block (9). For high impedance differential protectionpreprocessing function block in 3ms task shall be used.

9 Preprocessing block, which has a task to digitally filter the connected analogue inputs.Preprocessing block output AI1 shall be connected to one instances of 1Ph high impedancedifferential protection function HZPDIF (for example, instance 1 of HZPDIF in the configurationtool).

6.3.4 Setting guidelinesThe setting calculations are individual for each application. Refer to the differentapplication descriptions below.

6.3.4.1 Configuration

The configuration is done in the Application Configuration tool. For example,signals from external check criteria shall be connected to the inputs as required forthe application.

BLOCK input is used to block the function for example, from external check criteria.

BLKTR input is used to block the function tripping for example, from externalcheck criteria. The alarm level will be operative.

6.3.4.2 Settings of protection function

Operation: The operation of the high impedance differential function can beswitched On or Off.

1MRK 504 134-UEN - Section 6Differential protection

119Application Manual

Page 126: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

U>Alarm: Set the alarm level. The sensitivity can roughly be calculated as adivider from the calculated sensitivity of the differential level. A typical setting is10% of U>Trip It can be used as scheme supervision stage.

tAlarm: Set the time for the alarm. A typical setting is 2-3 seconds.

U>Trip: Set the trip level according to the calculations in the examples for eachapplication example. The level is selected with margin to the calculated requiredvoltage to achieve stability. Values can be 20-200 V dependent on the application.

SeriesResistor: Set the value of the stabilizing series resistor. Calculate the valueaccording to the examples for each application. Adjust the resistor as close aspossible to the calculated example. Measure the value achieved and set this valuehere.

The value shall always be high impedance. This means forexample, for 1A circuits say bigger than 400 ohms (400 VA) andfor 5 A circuits say bigger than 100 ohms (2500 VA). This ensuresthat the current will circulate and not go through the differentialcircuit at through faults.

That the settings of U>Alarm, U>Trip and SeriesResistor must bechosen such that both U>Alarm/SeriesResistor and U>Trip/SeriesResistor are >5% of IRated of the used current input.Normally the settings shall also be such that U>Alarm/SeriesResistor and U>Trip/SeriesResistor both gives a value<4*IRated of the used current input. If not it must be considered thelimitation in how long time the actual current is allowed to persistnot to overload the current input.

6.3.4.3 Restricted earth fault protection REFPDIF

For solidly earthed systems a restricted earth fault protection REF is often providedas a complement to the normal transformer differential IED. The advantage withthe restricted earth fault IEDs is their high sensitivity. Sensitivities of 2-8% can beachieved whereas the normal differential IED will have sensitivities of 20-40%.The level for high impedance restricted earth fault function is dependent of thecurrent transformers magnetizing currents.

Restricted earth fault IEDs have very fast response time due to the simplemeasuring principle and the measurement of one winding only.

The connection of a restricted earth fault IED is shown in figure 51. It is connectedacross each directly or low ohmic earthed transformer winding in figure 51.

It is quite common to connect the restricted earth fault IED in the same currentcircuit as the transformer differential IED. Due to the difference of measuring

Section 6 1MRK 504 134-UEN -Differential protection

120Application Manual

Page 127: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

principle, the detection of earth faults may be somewhat limited. Such faults arethen only detected by REF function. The mixed connection using the 1Ph Highimpedance differential protection HZPDIF function should be avoided and the lowimpedance scheme should be used instead.

Id

IEC05000177-2-en.vsdIEC05000177 V2 EN

Figure 51: Application of HZPDIF function as a restricted earth fault IED for anYNd transformer

Setting example

It is strongly recommended to use the highest tap of the CTwhenever high impedance protection is used. This helps in utilizingmaximum CT capability, minimize the current, thereby reducingthe stability voltage limit. Another factor is that during internalfaults, the voltage developed across the selected tap is limited bythe non-linear resistor but in the unused taps, owing to auto-transformer action, voltages much higher than design limits mightbe induced.

Basic data: Transformer rated current on HV winding: 250 A

Current transformer ratio: 300/1 A (Note: Must be the same at all locations)

CT Class: 10 VA 5P20

Cable loop resistance: <50 m 2.5mm2 (one way) gives 2 · 0.4 ohm at 75° C

Max fault current: The maximum through fault current is limited by thetransformer reactance, use 15 · rated current of thetransformer

1MRK 504 134-UEN - Section 6Differential protection

121Application Manual

Page 128: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Calculation:

( )25015 0.66 0.8 18.25

300UR V> × × + =

EQUATION1219 V1 EN (Equation 42)

Select a setting of U>Trip=20 V.

The current transformer saturation voltage at 5% error can roughly be calculated from the rated values.

( )5 10 0.66 20 213.2E P V> + × =

EQUATION1220 V1 EN (Equation 43)

that is, greater than 2 · U>Trip

Check from the table of selected resistances the required series stabilizing resistorvalue to use. Since this application requires high sensitivity, select SeriesResistor=1000 ohm which gives a current of 20 mA.

To calculate the sensitivity at operating voltage, refer to equation 44 which isacceptable as it gives around 10% minimum operating current.

( )30020 0 5 0 4 20 60 .25.5

1IP approx A= × ° + ° + × - ° £

EQUATION1221 V1 EN (Equation 44)

The magnetizing current is taken from the magnetizing curve for the currenttransformer cores which should be available. The value at U>Trip is taken. For thevoltage dependent resistor current the top value of voltage 20 · √2 is used and thetop current used. Then the RMS current is calculated by dividing with√2. Use themaximum value from the curve.

6.3.4.4 Alarm level operation

The 1Ph High impedance differential protection HZPDIF function has a separatealarm level, which can be used to give alarm for problems with an involved currenttransformer circuit. The setting level is normally selected to be around 10% of theoperating voltage U>Trip.

The setting of U>Alarm is related to the value of the stabilizing resistor and theminimum current sensitivity. The setting example shows the calculation procedureof the setting value of U> Alarm.

As seen in the setting examples above the sensitivity of HZPDIF function isnormally high, which means that the function will in many cases operate also forshort circuits or open current transformer secondary circuits. However thestabilizing resistor can be selected to achieve sensitivity higher than normal load

Section 6 1MRK 504 134-UEN -Differential protection

122Application Manual

Page 129: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

current and/or separate criteria can be added to the operation, like a check zone.This can be either another IED, with the same HZPDIF function, or be a checkabout the fault condition, which is performed by an earth overcurrent function orneutral point voltage function.

For such cases where operation is not expected during normal service the alarmoutput should be used to activate an external shorting of the differential circuitavoiding continuous high voltage in the circuit. A time delay of a few seconds isused before the shorting and alarm are activated. Auxiliary relays with contacts thatcan withstand high voltage shall be used, like RXMVB types.

IEC05000749 V1 EN

Figure 52: Current voltage characteristics for the non-linear resistors, in the range 10-200 V, the averagerange of current is: 0.01–10 mA

1MRK 504 134-UEN - Section 6Differential protection

123Application Manual

Page 130: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

124

Page 131: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Section 7 Impedance protection

7.1 Power swing detection ZMRPSB

7.1.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Power swing detection ZMRPSB

Zpsb

SYMBOL-EE V1 EN

68

7.1.2 Application

7.1.2.1 General

Various changes in power system may cause oscillations of rotating units. Themost typical reasons for these oscillations are big changes in load or changes inpower system configuration caused by different faults and their clearance. As therotating masses strive to find a stable operate condition, they oscillate with dampedoscillations until they reach the final stability.

The extent of the oscillations depends on the extent of the disturbances and on thenatural stability of the system.

The oscillation rate depends also on the inertia of the system and on the totalsystem impedance between different generating units. These oscillations causechanges in phase and amplitude of the voltage difference between the oscillatinggenerating units in the power system, which reflects further on in oscillating powerflow between two parts of the system - the power swings from one part to another -and vice versa.

Distance IEDs located in interconnected networks see these power swings as theswinging of the measured impedance in relay points. The measured impedancevaries with time along a locus in an impedance plane, see figure 53. This locus canenter the operating characteristic of a distance protection and cause, if nopreventive measures have been considered, its unwanted operation.

1MRK 504 134-UEN - Section 7Impedance protection

125Application Manual

Page 132: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

R

jX

Operating characteristic

Impedance locus atpower swing

IEC09000224_1_en.vsdIEC09000224 V1 EN

Figure 53: Impedance plane with Power swing detection operatingcharacteristic and impedance locus at power swing

7.1.2.2 Basic characteristics

Power swing detection function (ZMRPSB) reliably detects power swings withperiodic time of swinging as low as 200 ms (which means slip frequency as high as10% of the rated frequency on the 50 Hz basis). It detects the swings under normalsystem operating conditions.

ZMRPSB function is able to secure selective operation for internal faults duringpower. The operation of the distance protection function remains stable for externalfaults during the power swing condition, even with the swing (electrical) centrelocated on the protected power line.

The operate characteristic of the ZMRPSB function is easily adjustable to theselected impedance operate characteristics of the corresponding controlled distanceprotection zones as well as to the maximum possible load conditions of theprotected power lines.

7.1.3 Setting guidelinesSetting guidelines are prepared in the form of a setting example for the protectedpower line as part of a two-machine system presented in figure 54.

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

Section 7 1MRK 504 134-UEN -Impedance protection

126Application Manual

Page 133: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

99001019.vsd

~~

EA

dA= const dB= f(t)

EB

A BZSA ZSBZL

R

IEC99001019 V1 EN

Figure 54: Protected power line as part of a two-machine system

Reduce the power system with protected power line into equivalent two-machinesystem with positive sequence source impedances ZSA behind the IED and ZSBbehind the remote end bus B. Observe a fact that these impedances can not bedirectly calculated from the maximum three-phase short circuit currents for faultson the corresponding busbar. It is necessary to consider separate contributions ofdifferent connected circuits.

The required data is as follows:

400rU kV=EQUATION1321 V1 EN

Rated system voltage

min 380U kV=EQUATION1322 V1 EN

Minimum expected system voltage under critical systemconditions

50rf Hz=EQUATION1323 V1 EN

Rated system frequency

4003pU kV=

EQUATION1324 V1 EN

Rated primary voltage of voltage protection transformers used

0.113sU kV=

EQUATION1325 V1 EN

Rated secondary voltage of voltage instrument transformers used

1200pI A=EQUATION1326 V1 EN

Rated primary current of current protection transformers used

1sI A=EQUATION1327 V1 EN

Rated secondary current of current protection transformers used

( )1 10.71 75.6LZ j= + WEQUATION1328 V1 EN

Line positive sequence impedance

Table continues on next page

1MRK 504 134-UEN - Section 7Impedance protection

127Application Manual

Page 134: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

( )1 1.15 43.5SAZ j= + WEQUATION1329 V1 EN

Positive sequence source impedance behind A bus

( )1 5.3 35.7SBZ j= + WEQUATION1330 V1 EN

Positive sequence source impedance behind B bus

max 1000S MVA=EQUATION1331 V1 EN

Maximum expected load in direction from A to B (with minimumsystem operating voltage Umin)

( )maxcos 0.95j =EQUATION1332 V1 EN

Power factor at maximum line loading

max 25j = °EQUATION1333 V1 EN

Maximum expected load angle

2.5sif Hz=EQUATION1334 V1 EN

Maximum possible initial frequency of power oscillation

7.0scf Hz=EQUATION1335 V1 EN

Maximum possible consecutive frequency of power oscillation

The impedance transformation factor, which transforms the primary impedances tothe corresponding secondary values is calculated according to equation 45.Consider a fact that all settings are performed in primary values. The impedancetransformation factor is presented for orientation and testing purposes only.

1200 0.11 0.331 400

p s

s p

I UKIMPI U

= × = × =

EQUATION1336 V1 EN (Equation 45)

The minimum load impedance at minimum expected system voltage is equal toequation 46.

2 2min

minmax

380 144.41000L

UZS

= = = W

EQUATION1337 V1 EN (Equation 46)

The minimum load resistance RLmin at maximum load and minimum systemvoltage is equal to equation 47.

( )min min maxcos 144.4 0.95 137.2L LR Z j= × = × = WEQUATION1338 V1 EN (Equation 47)

Section 7 1MRK 504 134-UEN -Impedance protection

128Application Manual

Page 135: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

The system impedance ZS is determined as a sum of all impedance in an equivalenttwo-machine system, see figure 54. Its value is calculated according to equation 48.

( )1 1 1 17.16 154.8S SA L SBZ Z Z Z j= + + = + WEQUATION1339 V1 EN (Equation 48)

The calculated value of the system impedance is of informative nature and helpsdetermining the position of oscillation center, see figure 55, which is for generalcase calculated according to equation 49.

1

1

SCO SA

B

A

ZZ ZEE

= -

+

EQUATION1340 V1 EN (Equation 49)

In particular cases, when

A BE E=EQUATION1342 V1 EN (Equation 50)

resides the center of oscillation on impedance point, see equation 51.

( )1 7.43 33.92

SCO SA

ZZ Z j= - = + W

EQUATION1341 V1 EN (Equation 51)

1MRK 504 134-UEN - Section 7Impedance protection

129Application Manual

Page 136: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

R

jX

ArgLd(ZMRPSB)ArgLd

(FDPSPDIS)

Z S1

jXZ SA

1

Z L1

Z SB

1

Impedance locus for |EA| = |E

B|

R

Z CO

IEC09000225-1-en.vsdIEC09000225 V1 EN

Figure 55: Impedance diagrams with corresponding impedances underconsideration

The outer boundary of oscillation detection characteristic in forward directionRLdOutFw should be set with certain safety margin KL compared to the minimumexpected load resistance RLmin. When the exact value of the minimum loadresistance is not known, the following approximations may be considered for lineswith rated voltage 400 kV:

Section 7 1MRK 504 134-UEN -Impedance protection

130Application Manual

Page 137: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

• KL = 0.9 for lines longer than 150 km• KL = 0.85 for lines between 80 and 150 km• KL = 0.8 for lines shorter than 80 km

Multiply the required resistance for the same safety factor KL with the ratiobetween actual voltage and 400kV when the rated voltage of the line underconsideration is higher than 400kV. The outer boundary RLdOutFw obtains in thisparticular case its value according to equation 52.

min 0.9 137.2 123.5L LRLdOutFw K R= × = × = WEQUATION1343 V1 EN (Equation 52)

It is a general recommendation to set the inner boundary RLdInFw of theoscillation detection characteristic to 80% or less of its outer boundary. Exceptionsare always possible, but must be considered with special care especially when itcomes to settings of timers tP1 and tP2 included in oscillation detection logic. Thisrequires the maximum permitted setting values of factor kLdRFw = 0.8.Equation 53 presents the corresponding maximum possible value of RLdInFw.

RLdInFw = kLdRFw·RLdOutFw = 98.8WEQUATION1344 V2 EN (Equation 53)

The load angles, which correspond to external δOut and internal δIn boundary ofproposed oscillation detection characteristic in forward direction, are calculatedwith sufficient accuracy according to equation 54 and 55 respectively.

155.752 arc tan 2 arc tan 64.52 2 123.5

dæ ö æ öç ÷= × = × = °ç ÷ç ÷× ×è øè ø

SOut

ZRLdOutFw

EQUATION1345 V1 EN (Equation 54)

max

155.752 arc tan 2 arc tan 76.52 2 98.8

dæ ö æ öç ÷= × = × = °ç ÷ç ÷× ×è øè ø

SIn

ZRLdInFw

EQUATION1346 V1 EN (Equation 55)

The required setting tP1 of the initial oscillation detection timer depends on theload angle difference according to equation 56.

76.5 64.51 13.3360 2.5 360

In Out

si

tP msfd d- ° - °

= = =× ° × °

EQUATION1347 V1 EN (Equation 56)

The general tendency should be to set the tP1 time to at least 30 ms, if possible.Since it is not possible to further increase the external load angle δOut, it is

1MRK 504 134-UEN - Section 7Impedance protection

131Application Manual

Page 138: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

necessary to reduce the inner boundary of the oscillation detection characteristic.The minimum required value is calculated according to the procedure listed inequation 57, 58, 59 and 60.

min1 30tP ms=EQUATION1348 V1 EN (Equation 57)

min min360 1 360 2.5 0.030 64.5 91.5In si Outf tPd d- = ° × × + = ° × × + ° = °EQUATION1349 V1 EN (Equation 58)

max1min

155.75 75.891.52 tan2 tan

22d -

= = = Wæ ö æ ö×× ç ÷ç ÷

è øè ø

S

in

ZRLdInFw

EQUATION1350 V1 EN (Equation 59)

max1 75.8 0.61123.5

= = =RLdInFwkLdRFwRLdOutFw

EQUATION1351 V1 EN (Equation 60)

Also check if this minimum setting satisfies the required speed for detection ofconsecutive oscillations. This requirement will be satisfied if the proposed settingof tP2 time remains higher than 10 ms, see equation 61.

max91.5 64.52 10.7

360 7 360In Out

sc

tP msfd d- ° - °

= = =× ° × °

EQUATION1352 V1 EN (Equation 61)

The final proposed settings are as follows:

RLdOutFw = 123.5Ω

kLdRFw = 0.61

tP1 = 30 ms

tP2 = 10 ms

Consider RLdInFw = 75.0Ω.

Do not forget to adjust the setting of load encroachment resistanceRLdFw in Phase selection with load encroachment (FDPSPDIS) tothe value equal to or less than the calculated value RLdInFw. It is atthe same time necessary to adjust the load angle in FDPSPDIS tofollow the condition presented in equation 62.

Section 7 1MRK 504 134-UEN -Impedance protection

132Application Manual

Page 139: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Index PHS designates correspondence to FDPSPDIS function andindex PSD the correspondence to ZMRPSB function.

( )tanarc tan³ PSD

PHS

ArgLdArgLd

kLdRFwEQUATION1353 V2 EN (Equation 62)

Consider equation 63,

max 25PSDArgLd j= = °EQUATION1354 V1 EN (Equation 63)

then it is necessary to set the load argument in FDPSPDIS function to not less thanequation 64.

( ) ( )tan tan 25arc tan arc tan 37.5

0.61é ù é ù°

³ = = °ê ú ê úë û ë û

PSDPHS

ArgLdArgLd

kLdRFwEQUATION1355 V1 EN (Equation 64)

It is recommended to set the corresponding resistive reach parameters in reversedirection (RLdOutRv and kLdRRv) to the same values as in forward direction,unless the system operating conditions, which dictate motoring and generatingtypes of oscillations, requires different values. This decision must be made on basisof possible system contingency studies especially in cases, when the direction oftransmitted power may change fast in short periods of time. It is recommended touse different setting groups for operating conditions, which are changing onlybetween different periods of year (summer, winter).

System studies should determine the settings for the hold timer tH. The purpose ofthis timer is, to secure continuous output signal from Power swing detectionfunction (ZMRPSB) during the power swing, even after the transient impedanceleaves ZMRPSB operating characteristic and is expected to return within a certaintime due to continuous swinging. Consider the minimum possible speed of powerswinging in a particular system.

The tR1 inhibit timer delays the influence of the detected residual current on theinhibit criteria for ZMRPSB. It prevents operation of the function for shorttransients in the residual current measured by the IED.

The tR2 inhibit timer disables the output START signal from ZMRPSB function, ifthe measured impedance remains within ZMRPSB operating area for a time longerthan the set tR2 value. This time delay was usually set to approximately twoseconds in older power-swing devices.

1MRK 504 134-UEN - Section 7Impedance protection

133Application Manual

Page 140: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

7.2 Underimpedance protection for generators andtransformers ZGCPDIS

7.2.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Underimpedance protection forgenerators and transformers

ZGCPDIS 21G

7.2.2 ApplicationIn the case of a static excitation system receiving its power from the generatorterminals, the magnitude of a sustained phase-to-phase short-circuit currentdepends on the generator terminal voltage. In case of a nearby multi-phase fault,the generator terminal voltage may drop to quite low level (for example <25%) andthe generator fault current may consecutively fall below the pickup of theovercurrent relay. The short-circuit current may drop below rated current after 0.5 -1 s also for generators with excitation system not fed from the generator terminalsif the fault occurs when the automatic voltage regulator is out of service. The underimpedance protection is then the best generator backup protection which can beused under such circumstances. For this reason, an impedance measuring relay isgenerally recommended for generator back-up short-circuit protection.

The impedance relay is normally connected to current transformers on thegenerator neutral side to provide back-up also when the generator is disconnectedfrom the system. At reduced voltages, the current required for operation will bereduced. At zero voltage, operation is obtained with a current bigger than 15 % ofIBase (that is, generator rated current).

The underimpedance protection for generators and transformers function(ZGCPDIS) in the 650 series is designed to meet basic requirements for applicationas backup protection for generators and transformers.

7.2.3 Setting guidelinesThe settings for the underimpedance function are done in primary ohms. Theinstrument transformer ratios that have been set for the analogue input module isused to automatically convert the measured secondary input signals to primaryvalues used in ZGCPDIS .

The following basics must be considered, depending on the application, whencalculating the setting values:

Section 7 1MRK 504 134-UEN -Impedance protection

134Application Manual

Page 141: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

• Errors introduced by current and voltage instrument transformers, particularlyunder transient conditions.

The setting values of all parameters that belong to ZGCPDIS must correspond tothe parameters of the protected object and coordinated to the selectivity plan for thenetwork.

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

For ZGCPDIS function always use Global base values whichsetting correspond to the generator rated data.

ZGCPDIS function has an offset mho characteristic and evaluates three phase-to-phase impedance measuring loops. It has a forward and reverse impedance settingaccording to figure 56.

The relevant phase-to-phase measuring loop is released as soon asthe measured current is above 15% of IBase.

ZFwd

ZRev

ImpedanceAng

X

R

IEC10000184_2_en.vsdIEC10000184 V2 EN

Figure 56: Operating characteristic for phase-to-phase loops

1MRK 504 134-UEN - Section 7Impedance protection

135Application Manual

Page 142: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

7.3 Load enchroachment LEPDIS

7.3.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Load encroachment LEPDIS - -

7.3.2 ApplicationHeavy load transfer is common in many power networks and may make faultresistance coverage difficult to achieve. In such a case, Load encroachmentLEPDIS function can be used to enlarge the resistive setting of theunderimpedance measuring zones without interfering with the load.

Each of the three measuring phase-to-phase loops has its own load encroachmentcharacteristic.

7.3.3 Setting guidelines

7.3.3.1 Resistive reach with load encroachment characteristic

The procedure for calculating the settings for the load encroachment consistsbasically of defining the load angle ArgLd and the blinder RLd, as shown infigure 57.

Section 7 1MRK 504 134-UEN -Impedance protection

136Application Manual

Page 143: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

R

X

RLd

ArgLd

ArgLdArgLd

ArgLd

IEC10000144-1-en.vsd

RLd

IEC10000144 V2 EN

Figure 57: Load encroachment characteristic

The load angle ArgLd is the same in forward and reverse direction, so it could besuitable to begin to calculate the setting for that parameter. The parameter is set tothe maximum possible load angle at the maximum active load. A value larger than20° must be used considering a normal PF=0.8 corresponding to an angle of 36 deg.

The blinder, RLd, can be calculated according to equation:

= ×2 min

0.8expmax

URLd

PEQUATION2351 V1 EN (Equation 65)

where:

Pexp max is the maximum exporting active power

Umin is the minimum voltage for which the Pexp max occurs

0.8 is a security factor to ensure that the setting of RLd can belesser than the calculated minimal resistive load.

1MRK 504 134-UEN - Section 7Impedance protection

137Application Manual

Page 144: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

138

Page 145: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Section 8 Current protection

8.1 Instantaneous phase overcurrent protection 3-phase output PHPIOC

8.1.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Instantaneous phase overcurrentprotection 3-phase output

PHPIOC

3I>>

SYMBOL-Z V1 EN

50

8.1.2 ApplicationLong transmission lines often transfer great quantities of electric power fromproduction to consumption areas. The unbalance of the produced and consumedelectric power at each end of the transmission line is very large. This means that afault on the line can easily endanger the stability of a complete system.

The transient stability of a power system depends mostly on three parameters (atconstant amount of transmitted electric power):

• The type of the fault. Three-phase faults are the most dangerous, because nopower can be transmitted through the fault point during fault conditions.

• The magnitude of the fault current. A high fault current indicates that thedecrease of transmitted power is high.

• The total fault clearing time. The phase angles between the EMFs of thegenerators on both sides of the transmission line increase over the permittedstability limits if the total fault clearing time, which consists of the protectionoperating time and the breaker opening time, is too long.

The fault current on long transmission lines depends mostly on the fault positionand decreases with the distance from the generation point. For this reason theprotection must operate very quickly for faults very close to the generation (andrelay) point, for which very high fault currents are characteristic.

The instantaneous phase overcurrent protection 3-phase output PHPIOC canoperate in 10 ms for faults characterized by very high currents.

1MRK 504 134-UEN - Section 8Current protection

139Application Manual

Page 146: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

8.1.3 Setting guidelinesThe parameters for instantaneous phase overcurrent protection 3-phase outputPHPIOC are set via the local HMI or PCM600.

This protection function must operate only in a selective way. So check all systemand transient conditions that could cause its unwanted operation.

Only detailed network studies can determine the operating conditions under whichthe highest possible fault current is expected on the line. In most cases, this currentappears during three-phase fault conditions. But also examine single-phase-to-earthand two-phase-to-earth conditions.

Also study transients that could cause a high increase of the line current for shorttimes. A typical example is a transmission line with a power transformer at theremote end, which can cause high inrush current when connected to the networkand can thus also cause the operation of the built-in, instantaneous, overcurrentprotection.

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

IP>>: Set operate current in % of IBase.

8.1.3.1 Meshed network without parallel line

The following fault calculations have to be done for three-phase, single-phase-to-earth and two-phase-to-earth faults. With reference to figure 58, apply a fault in Band then calculate the current through-fault phase current IfB. The calculationshould be done using the minimum source impedance values for ZA and themaximum source impedance values for ZB in order to get the maximum throughfault current from A to B.

~ ~ZA ZBZ L

A B

IED

I fB

Fault

IEC09000022-1-en.vsdIEC09000022 V1 EN

Figure 58: Through fault current from A to B: IfB

Section 8 1MRK 504 134-UEN -Current protection

140Application Manual

Page 147: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Then a fault in A has to be applied and the through fault current IfA has to becalculated, figure 59. In order to get the maximum through fault current, theminimum value for ZB and the maximum value for ZA have to be considered.

IEC09000023-1-en.vsd

~ ~ZA ZBZ L

A B

IED

I fA

Fault

IEC09000023 V1 EN

Figure 59: Through fault current from B to A: IfA

The IED must not trip for any of the two through-fault currents. Hence theminimum theoretical current setting (Imin) will be:

Imin MAX I fA IfB,( )³

EQUATION78 V1 EN (Equation 66)

A safety margin of 5% for the maximum protection static inaccuracy and a safetymargin of 5% for the maximum possible transient overreach have to be introduced.An additional 20% is suggested due to the inaccuracy of the instrumenttransformers under transient conditions and inaccuracy in the system data.

The minimum primary setting (Is) for the instantaneous phase overcurrentprotection 3-phase output is then:

min1.3sI I³ ×

EQUATION79 V3 EN (Equation 67)

The protection function can be used for the specific application only if this settingvalue is equal to or less than the maximum fault current that the IED has to clear, IFin figure 60.

1MRK 504 134-UEN - Section 8Current protection

141Application Manual

Page 148: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

IEC09000024-1-en.vsd

~ ~ZA ZBZ L

A B

IED

I F

Fault

IEC09000024 V1 EN

Figure 60: Fault current: IF

100Is

IPIBase

>>= ×

EQUATION1147 V3 EN (Equation 68)

8.1.3.2 Meshed network with parallel line

In case of parallel lines, the influence of the induced current from the parallel lineto the protected line has to be considered. One example is given in figure 61 wherethe two lines are connected to the same busbars. In this case the influence of theinduced fault current from the faulty line (line 1) to the healthy line (line 2) isconsidered together with the two through fault currents IfA and IfB mentionedpreviously. The maximal influence from the parallel line for the IED in figure 61will be with a fault at the C point with the C breaker open.

A fault in C has to be applied, and then the maximum current seen from the IED(IM ) on the healthy line (this applies for single-phase-to-earth and two-phase-to-earth faults) is calculated.

Section 8 1MRK 504 134-UEN -Current protection

142Application Manual

Page 149: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

IEC09000025-1-en.vsd

~ ~ZA ZB

ZL1A B

I M

Fault

IED

ZL2

M

CLine 1

Line 2

IEC09000025 V1 EN

Figure 61: Two parallel lines. Influence from parallel line to the through faultcurrent: IM

The minimum theoretical current setting for the overcurrent protection function(Imin) will be:

Imin MAX I fA IfB IM, ,( )³

EQUATION82 V1 EN (Equation 69)

Where IfA and IfB have been described in the previous paragraph. Considering thesafety margins mentioned previously, the minimum setting (Is) for theinstantaneous phase overcurrent protection 3-phase output is then:

Is ³1.3·IminEQUATION83 V2 EN (Equation 70)

The protection function can be used for the specific application only if this settingvalue is equal or less than the maximum phase fault current that the IED has to clear.

The IED setting value IP>> is given in percentage of the primary base currentvalue, IBase. The value for IP>> is given from this formula:

100Is

IPIBase

>>= ×

EQUATION1147 V3 EN (Equation 71)

1MRK 504 134-UEN - Section 8Current protection

143Application Manual

Page 150: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

8.2 Four step phase overcurrent protection 3-phaseoutput OC4PTOC

8.2.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Four step phase overcurrent protection3-phase output

OC4PTOC

44 alt

3I>

TOC-REVA V1 EN

51/67

8.2.2 ApplicationThe Four step phase overcurrent protection 3-phase output OC4PTOC is used inseveral applications in the power system. Some applications are:

• Short circuit protection of feeders in distribution and subtransmission systems.Normally these feeders have radial structure.

• Back-up short circuit protection of transmission lines.• Back-up short circuit protection of power transformers.• Short circuit protection of different kinds of equipment connected to the power

system such as; shunt capacitor banks, shunt reactors, motors and others.• Back-up short circuit protection of power generators.

If VT inputs are not available or not connected, setting parameterDirModex (x = step 1, 2, 3 or 4) shall be left to default value Non-directionalor set to Off.

In many applications several steps with different current pick up levels and timedelays are needed. OC4PTOC can have up to four different, individual settable,steps. The flexibility of each step of OC4PTOC is great. The following options arepossible:

Non-directional / Directional function: In most applications the non-directionalfunctionality is used. This is mostly the case when no fault current can be fed fromthe protected object itself. In order to achieve both selectivity and fast faultclearance, the directional function can be necessary.

Choice of delay time characteristics: There are several types of delay timecharacteristics available such as definite time delay and different types of inversetime delay characteristics. The selectivity between different overcurrent protectionsis normally enabled by co-ordination between the function time delays of thedifferent protections. To enable optimal co-ordination between all overcurrent

Section 8 1MRK 504 134-UEN -Current protection

144Application Manual

Page 151: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

protections, they should have the same time delay characteristic. Therefore a widerange of standardized inverse time characteristics are available: IEC and ANSI.

The time characteristic for step 1 and 4 can be chosen as definite time delay orinverse time characteristic. Step 2 and 3 are always definite time delayed and areused in system where IDMT is not needed.

Power transformers can have a large inrush current, when being energized. Thisphenomenon is due to saturation of the transformer magnetic core during parts ofthe period. There is a risk that inrush current will reach levels above the pick-upcurrent of the phase overcurrent protection. The inrush current has a large 2ndharmonic content. This can be used to avoid unwanted operation of the protection.Therefore, OC4PTOC have a possibility of 2nd harmonic restrain if the level ofthis harmonic current reaches a value above a set percentage of the fundamentalcurrent.

8.2.3 Setting guidelines

When inverse time overcurrent characteristic is selected, theoperate time of the stage will be the sum of the inverse time delayand the set definite time delay. Thus, if only the inverse time delayis required, it is important to set the definite time delay for thatstage to zero.

The parameters for Four step phase overcurrent protection 3-phase outputOC4PTOC are set via the local HMI or PCM600.

The following settings can be done for OC4PTOC.

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

MeasType: Selection of discrete Fourier filtered (DFT) or true RMS filtered (RMS)signals. RMS is used when the harmonic contents are to be considered, for examplein applications with shunt capacitors.

Operation: The protection can be set to Off or On

2ndHarmStab: Operate level of 2nd harmonic current restrain set in % of thefundamental current. The setting range is 5 - 100% in steps of 1%. Default settingis 20%.

1MRK 504 134-UEN - Section 8Current protection

145Application Manual

Page 152: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Uref

Idir

IEC09000636_1_vsd

1

2

2

3

4

IEC09000636 V1 EN

Figure 62: Directional function characteristic

1. RCA = Relay characteristic angle 55°2. ROA = Relay operating angle 80°3. Reverse4. Forward

8.2.3.1 Settings for steps 1 to 4

n means step 1 and 4. x means step 1, 2, 3 and 4.

DirModex: The directional mode of step x. Possible settings are Off/Non-directional/Forward/Reverse.

Characteristn: Selection of time characteristic for step n. Definite time delay anddifferent types of inverse time characteristics are available according to table 14.Step 2 and 3 are always definite time delayed.

Section 8 1MRK 504 134-UEN -Current protection

146Application Manual

Page 153: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Table 14: Inverse time characteristics

Curve nameANSI Extremely Inverse

ANSI Very Inverse

ANSI Normal Inverse

ANSI Moderately Inverse

ANSI/IEEE Definite time

ANSI Long Time Extremely Inverse

ANSI Long Time Very Inverse

ANSI Long Time Inverse

IEC Normal Inverse

IEC Very Inverse

IEC Inverse

IEC Extremely Inverse

IEC Short Time Inverse

IEC Long Time Inverse

IEC Definite Time

ASEA RI

RXIDG (logarithmic)

The different characteristics are described in Technical manual.

Ix>: Operate phase current level for step x given in % of IBase.

tx: Definite time delay for step x. Used if definite time characteristic is chosen.

kn: Time multiplier for inverse time delay for step n.

IMinn: Minimum operate current for step n in % of IBase. Set IMinn below Ix> forevery step to achieve ANSI reset characteristic according to standard. If IMinn isset above Ix> for any step the ANSI reset works as if current is zero when currentdrops below IMinn.

tnMin: Minimum operate time for all inverse time characteristics. At high currentsthe inverse time characteristic might give a very short operation time. By settingthis parameter the operation time of the step can never be shorter than the setting.Setting range: 0.000 - 60.000s in steps of 0.001s.

1MRK 504 134-UEN - Section 8Current protection

147Application Manual

Page 154: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Current

Operatetime

IMinn

tnMin

IEC09000164-1-en.vsdIEC09000164 V1 EN

Figure 63: Minimum operate current and operation time for inverse timecharacteristics

In order to fully comply with curves definition setting parameter tnMin shall be setto the value, which is equal to the operating time of the selected inverse curve formeasured current of twenty times the set current pickup value. Note that theoperating time value is dependent on the selected setting value for time multiplierkn.

HarmRestrainx: Enable block of step n from the harmonic restrain function (2ndharmonic). This function should be used when there is a risk if power transformerinrush currents might cause unwanted trip. Can be set Off/On.

8.2.3.2 2nd harmonic restrain

If a power transformer is energized there is a risk that the transformer core willsaturate during part of the period, resulting in an inrush transformer current. Thiswill give a declining residual current in the network, as the inrush current isdeviating between the phases. There is a risk that the phase overcurrent functionwill give an unwanted trip. The inrush current has a relatively large ratio of 2nd

harmonic component. This component can be used to create a restrain signal toprevent this unwanted function.

The settings for the 2nd harmonic restrain are described below.

Section 8 1MRK 504 134-UEN -Current protection

148Application Manual

Page 155: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

2ndHarmStab: The rate of 2nd harmonic current content for activation of the 2ndharmonic restrain signal, to block chosen steps. The setting is given in % of thefundamental frequency residual current. The setting range is 5 - 100% in steps of1%. The default setting is 20% and can be used if a deeper investigation shows thatno other value is needed..

HarmRestrainx: This parameter can be set Off/On, to disable or enable the 2ndharmonic restrain.

The four step phase overcurrent protection 3-phase output can be used in differentways, depending on the application where the protection is used. A generaldescription is given below.

The operating current setting of the inverse time protection, or the lowest currentstep of the definite time protection, must be defined so that the highest possibleload current does not cause protection operation. Here consideration also has to betaken to the protection reset current, so that a short peak of overcurrent does notcause operation of the protection even when the overcurrent has ceased. Thisphenomenon is described in figure 64.

Operate current

Current I

The IED does not reset

Line phase current

Time t

Reset current

IEC05000203-en-2.vsdIEC05000203 V3 EN

Figure 64: Operate and reset current for an overcurrent protection

The lowest setting value can be written according to equation 72.

1MRK 504 134-UEN - Section 8Current protection

149Application Manual

Page 156: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

ImaxIpu 1.2k

³ ×

EQUATION1262 V2 EN (Equation 72)

where:

1.2 is a safety factor

k is the resetting ratio of the protection

Imax is the maximum load current

The maximum load current on the line has to be estimated. There is also a demandthat all faults, within the zone that the protection shall cover, must be detected bythe phase overcurrent protection. The minimum fault current Iscmin, to be detectedby the protection, must be calculated. Taking this value as a base, the highest pickup current setting can be written according to equation 73.

Ipu 0.7 Iscmin£ ×EQUATION1263 V2 EN (Equation 73)

where:

0.7 is a safety factor

Iscmin is the smallest fault current to be detected by the overcurrent protection.

As a summary the operating current shall be chosen within the interval stated inequation 74.

Imax1.2 Ipu 0.7 Iscmink

× £ £ ×

EQUATION1264 V2 EN (Equation 74)

The high current function of the overcurrent protection, which only has a shortdelay of the operation, must be given a current setting so that the protection isselective to other protection in the power system. It is desirable to have a rapidtripping of faults within as large portion as possible of the part of the power systemto be protected by the protection (primary protected zone). A fault currentcalculation gives the largest current of faults, Iscmax, at the most remote part of theprimary protected zone. Considerations have to be made to the risk of transientoverreach, due to a possible DC component of the short circuit current. The lowestcurrent setting of the most rapid stage, of the phase overcurrent protection, can bewritten according to

Section 8 1MRK 504 134-UEN -Current protection

150Application Manual

Page 157: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

max1.2 t schighI k I³ × ×

EQUATION1265 V1 EN (Equation 75)

where:

1.2 is a safety factor

kt is a factor that takes care of the transient overreach due to the DC component of the faultcurrent and can be considered to be less than 1.1

Iscmax is the largest fault current at a fault at the most remote point of the primary protection zone.

The operate times of the phase overcurrent protection has to be chosen so that thefault time is so short that protected equipment will not be destroyed due to thermaloverload, at the same time as selectivity is assured. For overcurrent protection, in aradial fed network, the time setting can be chosen in a graphical way. This ismostly used in the case of inverse time overcurrent protection. Figure 65 showshow the time-versus-current curves are plotted in a diagram. The time setting ischosen to get the shortest fault time with maintained selectivity. Selectivity isassured if the time difference between the curves is larger than a critical timedifference.

en05000204.wmfIEC05000204 V1 EN

Figure 65: Fault time with maintained selectivity

1MRK 504 134-UEN - Section 8Current protection

151Application Manual

Page 158: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

To assure selectivity between different protections, in the radial network, therehave to be a minimum time difference Dt between the time delays of twoprotections. The minimum time difference can be determined for different cases.To determine the shortest possible time difference, the operation time ofprotections, breaker opening time and protection resetting time must be known.These time delays can vary significantly between different protective equipment.The following time delays can be estimated:

Protection operationtime:

15-60 ms

Protection resetting time: 15-60 ms

Breaker opening time: 20-120 ms

Example for time coordinationAssume two substations A and B directly connected to each other via one line, asshown in the figure 66. Consider a fault located at another line from the station B.The fault current to the overcurrent protection of IED B1 has a magnitude so thatthe protection will have instantaneous function. The overcurrent protection of IEDA1 must have a delayed function. The sequence of events during the fault can bedescribed using a time axis, see figure 66.

Section 8 1MRK 504 134-UEN -Current protection

152Application Manual

Page 159: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

I> I>

A1 B1 Feeder

Time axis

t=0 t=t1 t=t2 t=t3The faultoccurs

ProtectionB1 trips

Breaker atB1 opens

ProtectionA1 resets

en05000205.vsd

IEC05000205 V1 EN

Figure 66: Sequence of events during fault

where:

t=0 is when the fault occurs

t=t1 is when the trip signal from the overcurrent protection at IED B1 is sent to the circuit breaker.The operation time of this protection is t1

t=t2 is when the circuit breaker at IED B1 opens. The circuit breaker opening time is t2 - t1

t=t3 is when the overcurrent protection at IED A1 resets. The protection resetting time is t3 - t2.

To ensure that the overcurrent protection at IED A1, is selective to the overcurrentprotection at IED B1, the minimum time difference must be larger than the time t3.There are uncertainties in the values of protection operation time, breaker openingtime and protection resetting time. Therefore a safety margin has to be included.With normal values the needed time difference can be calculated according toequation 76.

40 100 40 40 220t ms ms ms ms msD ³ + + + =EQUATION1266 V1 EN (Equation 76)

where it is considered that:

the operate time of overcurrent protection B1 is 40 ms

the breaker open time is 100 ms

the resetting time of protection A1 is 40 ms and

the additional margin is 40 ms

1MRK 504 134-UEN - Section 8Current protection

153Application Manual

Page 160: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

8.3 Instantaneous residual overcurrent protectionEFPIOC

8.3.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Instantaneous residual overcurrentprotection

EFPIOC

IN>>

IEF V1 EN

50N

8.3.2 ApplicationIn many applications, when fault current is limited to a defined value by the objectimpedance, an instantaneous earth-fault protection can provide fast and selectivetripping.

The Instantaneous residual overcurrent EFPIOC, which can operate in 15 ms (50Hz nominal system frequency) for faults characterized by very high currents, isincluded in the IED.

8.3.3 Setting guidelinesThe parameters for the Instantaneous residual overcurrent protection EFPIOC areset via the local HMI or PCM600.

Some guidelines for the choice of setting parameter for EFPIOC is given.

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

The setting of the function is limited to the operate residual current to theprotection (IN>>).

The basic requirement is to assure selectivity, that is EFPIOC shall not be allowedto operate for faults at other objects than the protected object (line).

For a normal line in a meshed system single phase-to-earth faults and phase-to-phase-to-earth faults shall be calculated as shown in figure 67 and figure 68. The residualcurrents (3I0) to the protection are calculated. For a fault at the remote line end thisfault current is IfB. In this calculation the operational state with high sourceimpedance ZA and low source impedance ZB should be used. For the fault at thehome busbar this fault current is IfA. In this calculation the operational state withlow source impedance ZA and high source impedance ZB should be used.

Section 8 1MRK 504 134-UEN -Current protection

154Application Manual

Page 161: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

~ ~ZA ZBZ L

A B

IED

I fB

Fault

IEC09000022-1-en.vsd

IEC09000022 V1 EN

Figure 67: Through fault current from A to B: IfB

IEC09000023-1-en.vsd

~ ~ZA ZBZ L

A B

IED

I fA

Fault

IEC09000023 V1 EN

Figure 68: Through fault current from B to A: IfA

The function shall not operate for any of the calculated currents to the protection.The minimum theoretical current setting (Imin) will be:

Imin MAX IfA IfA,( )³

EQUATION284 V1 EN (Equation 77)

A safety margin of 5% for the maximum static inaccuracy and a safety margin of5% for maximum possible transient overreach have to be introduced. An additional20% is suggested due to inaccuracy of instrument transformers under transientconditions and inaccuracy in the system data.

The minimum primary current setting (Is) is:

m1.3.Is inI ³EQUATION285 V2 EN (Equation 78)

In case of parallel lines with zero sequence mutual coupling a fault on the parallelline, as shown in figure 69, should be calculated.

1MRK 504 134-UEN - Section 8Current protection

155Application Manual

Page 162: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

IEC09000025-1-en.vsd

~ ~ZA ZB

ZL1A B

I M

Fault

IED

ZL2

M

CLine 1

Line 2

IEC09000025 V1 EN

Figure 69: Two parallel lines. Influence from parallel line to the through faultcurrent: IM

The minimum theoretical current setting (Imin) will in this case be:

I m in M AX IfA I fB IM, ,( )³

EQUATION287 V1 EN (Equation 79)

Where:

IfA and IfB have been described for the single line case.

Considering the safety margins mentioned previously, the minimum setting (Is) is:

m1.3.Is inI ³EQUATION288 V2 EN (Equation 80)

Transformer inrush current shall be considered.

The setting of the protection is set as a percentage of the base current (IBase).

Operation: set the protection to On or Off.

IN>>: Set operate current in % of IBase. IBase is a global parameter valid for allfunctions in the IED.

8.4 Four step residual overcurrent protection, zero,negative sequence direction EF4PTOC

Section 8 1MRK 504 134-UEN -Current protection

156Application Manual

Page 163: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

8.4.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Four step residual overcurrentprotection, zero or negative sequencedirection

EF4PTOC

2

IEC11000263 V1 EN

51N/67N

8.4.2 ApplicationThe four step residual overcurrent protection, zero or negative sequence directionEF4PTOC is used in several applications in the power system. Some applications are:

• Earth-fault protection of feeders in effectively earthed distribution systems.Normally these feeders have radial structure.

• Back-up earth-fault protection of subtransmission and transmission lines.• Sensitive earth-fault protection of transmission lines. EF4PTOC can have

better sensitivity to detect resistive phase-to-earth-faults compared to distanceprotection.

• Back-up earth-fault protection of power transformers with earth source atsubstation.

• Earth-fault protection of different kinds of equipment connected to the powersystem such as shunt capacitor banks, shunt reactors and others.

• Negative sequence direcitonal earth-fault protection of feeders with PTsconnected in Open Delta connection from which it is not possible to deriveZero sequence voltage.

• Negative sequence directional earth-fault protection of double-circuit mediumor long transmission lines with significant mutual coupling.

In many applications several steps with different current operating levels and timedelays are needed. EF4PTOC can have up to four, individual settable steps. Theflexibility of each step of EF4PTOC is great. The following options are possible:

Non-directional/Directional function: In some applications the non-directionalfunctionality is used. This is mostly the case when no fault current can be fed fromthe protected object itself. In order to achieve both selectivity and fast faultclearance, the directional function can be necessary. This can be the case for earth-fault protection in meshed and effectively earthed transmission systems. Thedirectional residual overcurrent protection is also well suited to operate inteleprotection communication schemes, which enables fast clearance of earth faultson transmission lines. The directional function uses the polarizing quantity asdecided by setting. Voltage polarizing (3U0 or U2) is most commonly used, butalternatively current polarizing (3I0 or I2) where currents in transformer neutralsproviding the neutral (zero sequence) source (ZN) is used to polarize (IPol · ZN)the function. Dual polarizing where the sum of both voltage and currentcomponents is allowed to polarize can also be selected.

1MRK 504 134-UEN - Section 8Current protection

157Application Manual

Page 164: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Choice of time characteristics: There are several types of time characteristicsavailable such as definite time delay and different types of inverse timecharacteristics. The selectivity between different overcurrent protections isnormally enabled by co-ordination between the operate time of the differentprotections. To enable optimal co-ordination all overcurrent protections, to be co-ordinated against each other, should have the same time characteristic. Therefore awide range of standardized inverse time characteristics are available: IEC andANSI. The time characteristic for step 1 and 4 can be chosen as definite time delayor inverse time characteristic. Step 2 and 3 are always definite time delayed and areused in system where IDMT is not needed.

Table 15: Time characteristics

Curve nameANSI Extremely Inverse

ANSI Very Inverse

ANSI Normal Inverse

ANSI Moderately Inverse

ANSI/IEEE Definite time

ANSI Long Time Extremely Inverse

ANSI Long Time Very Inverse

ANSI Long Time Inverse

IEC Normal Inverse

IEC Very Inverse

IEC Inverse

IEC Extremely Inverse

IEC Short Time Inverse

IEC Long Time Inverse

IEC Definite Time

ASEA RI

RXIDG (logarithmic)

Power transformers can have a large inrush current, when being energized. Thisinrush current can have residual current components. The phenomenon is due tosaturation of the transformer magnetic core during parts of the cycle. There is a riskthat inrush current will give a residual current that reaches level above theoperating current of the residual overcurrent protection. The inrush current has alarge second harmonic content. This can be used to avoid unwanted operation ofthe protection. Therefore, EF4PTOC has a possibility of second harmonic restrain2ndHarmStab if the level of this harmonic current reaches a value above a setpercentage of the fundamental current.

Section 8 1MRK 504 134-UEN -Current protection

158Application Manual

Page 165: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

8.4.3 Setting guidelines

When inverse time overcurrent characteristic is selected, theoperate time of the stage will be the sum of the inverse time delayand the set definite time delay. Thus, if only the inverse time delayis required, it is important to set the definite time delay for thatstage to zero.

The parameters for the four step residual overcurrent protection, zero or negativesequence direction EF4PTOC are set via the local HMI or PCM600.

The following settings can be done for the four step residual overcurrent protection.

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

Operation: Sets the protection to On or Off.

EnaDir: Enables the directional calculation in addition to the directional modeselection in each step.

8.4.3.1 Settings for steps 1 and 4

n means step 1 and 4. x means step 1, 2, 3 and 4.

DirModex: The directional mode of step x. Possible settings are Off/Non-directional/Forward/Reverse.

Characteristx: Selection of time characteristic for step x. Definite time delay anddifferent types of inverse time characteristics are available.

Inverse time characteristic enables fast fault clearance of high current faults at thesame time as selectivity to other inverse time phase overcurrent protections can beassured. This is mainly used in radial fed networks but can also be used in meshednetworks. In meshed networks the settings must be based on network faultcalculations.

To assure selectivity between different protections, in the radial network, therehave to be a minimum time difference Dt between the time delays of twoprotections. The minimum time difference can be determined for different cases.To determine the shortest possible time difference, the operation time ofprotections, breaker opening time and protection resetting time must be known.These time delays can vary significantly between different protective equipment.The following time delays can be estimated:

Protection operate time: 15-60 ms

Protection resetting time: 15-60 ms

Breaker opening time: 20-120 ms

1MRK 504 134-UEN - Section 8Current protection

159Application Manual

Page 166: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

The different characteristics are described in the Technical Manual (TM).

INx>: Operate residual current level for step x given in % of IBase.

kn: Time multiplier for the dependent (inverse) characteristic for step n.

IMinn: Minimum operate current for step n in % of IBase. Set IMinn below INx>for every step to achieve ANSI reset characteristic according to standard. If IMinnis set above INx for any step the ANSI reset works as if current is zero whencurrent drops below IMinn.

tnMin: Minimum operating time for inverse time characteristics. At high currentsthe inverse time characteristic might give a very short operation time. By settingthis parameter the operation time of the step n can never be shorter than the setting.

Current

Operatetime

IMinn

tnMin

IEC09000164-1-en.vsdIEC09000164 V1 EN

Figure 70: Minimum operate current and operate time for inverse timecharacteristics

In order to fully comply with curves definition the setting parameter txMin shall beset to the value which is equal to the operate time of the selected IEC inverse curvefor measured current of twenty times the set current pickup value. Note that theoperate time value is dependent on the selected setting value for time multiplier kn.

Section 8 1MRK 504 134-UEN -Current protection

160Application Manual

Page 167: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

8.4.3.2 Common settings for all steps

tx: Definite time delay for step x. Used if definite time characteristic is chosen.

AngleRCA: Relay characteristic angle given in degree. This angle is defined asshown in figure 71. The angle is defined positive when the residual current lags thereference voltage (Upol = 3U0 or U2)

Upol = 3U0 or U2

I>Dir

RCA

Operation

en 05000135-4-nsi.vsd

IEC05000135 V4 EN

Figure 71: Relay characteristic angle given in degree

In a normal transmission network a normal value of RCA is about 65°. The settingrange is -180° to +180°.

polMethod: Defines if the directional polarization is from

• Voltage (3U0 or U2)• Current (3I0 · ZNpol or 3I2 ·ZNpol where ZNpol is RNpol + jXNpol), or• both currents and voltage, Dual (dual polarizing, (3U0 + 3I0 · ZNpol) or (U2 +

I2 · ZNpol)).

Normally voltage polarizing from the internally calculated residual sum or anexternal open delta is used.

Current polarizing is useful when the local source is strong and a high sensitivity isrequired. In such cases the polarizing voltage (3U0) can be below 1% and it is thennecessary to use current polarizing or dual polarizing. Multiply the required setcurrent (primary) with the minimum impedance (ZNpol) and check that the

1MRK 504 134-UEN - Section 8Current protection

161Application Manual

Page 168: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

percentage of the phase-to-earth voltage is definitely higher than 1% (minimum3U0>UPolMin setting) as a verification.

RNPol, XNPol: The zero-sequence source is set in primary ohms as base for thecurrent polarizing. The polarizing voltage is then achieved as 3I0 · ZNpol. TheZNpol can be defined as (ZS1-ZS0)/3, that is the earth return impedance of thesource behind the protection. The maximum earth-fault current at the local sourcecan be used to calculate the value of ZN as U/(√3 · 3I0) Typically, the minimumZNPol (3 · zero sequence source) is set. Setting is in primary ohms.

When the dual polarizing method is used it is important that the product INx>·ZNpol is not greater than 3U0. If so, there is a risk for incorrect operation for faultsin the reverse direction.

IPolMin: is the minimum earth-fault current accepted for directional evaluation.For smaller currents than this value the operation will be blocked. Typical setting is5-10% of IBase.

UPolMin: Minimum polarization (reference) residual voltage for the directionalfunction, given in % of UBase/√3.

I>Dir: Operate residual current release level in % of IBase for directionalcomparison scheme. The setting is given in % of IBase and must be set below thelowest INx> setting, set for the directional measurement. The output signals,STFW and STRV can be used in a teleprotection scheme. The appropriate signalshould be configured to the communication scheme block.

8.4.3.3 2nd harmonic restrain

If a power transformer is energized there is a risk that the current transformer corewill saturate during part of the period, resulting in a transformer inrush current.This will give a declining residual current in the network, as the inrush current isdeviating between the phases. There is a risk that the residual overcurrent functionwill give an unwanted trip. The inrush current has a relatively large ratio of 2ndharmonic component. This component can be used to create a restrain signal toprevent this unwanted function.

At current transformer saturation a false residual current can be measured by theprotection. Also here the 2nd harmonic restrain can prevent unwanted operation.

2ndHarmStab: The rate of 2nd harmonic current content for activation of the 2ndharmonic restrain signal. The setting is given in % of the fundamental frequencyresidual current.

HarmRestrainx: Enable block of step x from the harmonic restrain function.

Section 8 1MRK 504 134-UEN -Current protection

162Application Manual

Page 169: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

8.4.3.4 Transformer application example

Two main cases are of interest when residual overcurrent protection is used for apower transformer, namely if residual current can be fed from the protectedtransformer winding or not.

The protected winding will feed earth-fault (residual) current to earth faults in theconnected power system. The residual current fed from the transformer at externalphase-to-earth faults, is highly dependent of the total positive and zero-sequencesource impedances as well as the residual current distribution between the networkzero-sequence impedance and the transformer zero-sequence impedance. Anexample of this application is shown in figure 72.

IN>

alt

Three phase CTsummated

Single CT

YN/D or YN/Ytransformer

en05000490.vsdIEC05000490 V1 EN

Figure 72: Residual overcurrent protection application on a directly earthedtransformer winding

In this case the protection has two different tasks:

• Detection of earth faults on the transformer winding, to which the protection isconnected.

• Detection of earth faults in the power system, to which the protected windingis connected.

It can be suitable to use a residual overcurrent protection with at least two steps.Step 1 shall have a short definite time delay and a relatively high current setting, inorder to detect and clear high current earth faults in the transformer winding or inthe power system close to the transformer. Step 2 shall have a longer time delay(definite or inverse time delay) and a lower current operation level. Step 2 shalldetect and clear transformer winding earth faults with low earth-fault current, thatis, faults close to the transformer winding neutral point. If the current setting gap

1MRK 504 134-UEN - Section 8Current protection

163Application Manual

Page 170: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

between step 1 and step 2 is large another step can be introduced with a current andtime delay setting between the two described steps.

The transformer inrush current will have a large residual current component. Toprevent unwanted function of the earth-fault overcurrent protection, the 2ndharmonic restrain blocking should be used, at least for the sensitive step 2.

If the protected winding will not feed earth-fault (residual) current to earth faults inthe connected power system the application is as shown in figure 73.

IN>

Three phase CTsummated

Y/Y, Y/D or D/Ytransformer

en05000491.vsdIEC05000491 V1 EN

Figure 73: Residual overcurrent protection application on an isolatedtransformer winding

In the calculation of the fault current fed to the protection, at different earth faults,are highly dependent on the positive and zero sequence source impedances, as wellas the division of residual current in the network. Earth-fault current calculationsare necessary for the setting.

Setting of step 1One requirement is that earth faults at the busbar, where the transformer winding isconnected, shall be detected. Therefore a fault calculation as shown in figure 74 ismade.

Section 8 1MRK 504 134-UEN -Current protection

164Application Manual

Page 171: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

IN>

alt

Three phase CTsummated

Single CT

YN/D or YN/Ytransformer

Single phase-to-earth fault

3I0

IEC05000492-en-2.vsdIEC05000492 V2 EN

Figure 74: Step 1 fault calculation 1

This calculation gives the current fed to the protection: 3I0fault1.

To assure that step 1, selectivity to other earth-fault protections in the network ashort delay is selected. Normally, a delay in the range 0.3 – 0.4 s is appropriate. Toassure selectivity to line faults, tripped after a delay (typically distance protectionzone 2) of about 0.5 s the current setting must be set so high so that such faultsdoes not cause unwanted step 1 trip. Therefore, a fault calculation as shown infigure 75 is made.

IN>

alt

Three phase CTsummated

Single CT

YN/D or YN/Ytransformer

Single phase-to-earth fault

3I0

IEC05000493-en-2.vsd

IEC05000493 V2 EN

Figure 75: Step 1 fault calculation 1

1MRK 504 134-UEN - Section 8Current protection

165Application Manual

Page 172: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

The fault is located at the borderline between instantaneous and delayed operationof the line protection, such as Distance protection or line residual overcurrentprotection. This calculation gives the current fed to the protection: 3I0fault2

The setting of step 1 can be chosen within the interval shown in equation 81.

0fault 2 step1 0fault13I lowmar I 3I highmar× < < ×

EQUATION1455 V2 EN (Equation 81)

Where:

lowmar is a margin to assure selectivity (typical 1.2) and

highmar is a margin to assure fast fault clearance of busbar fault (typical 1.2).

Setting of step 2The setting of the sensitive step 2 is dependent of the chosen time delay. Often arelatively long definite time delay or inverse time delay is chosen. The currentsetting can be chosen very low. As it is required to detect earth faults in thetransformer winding, close to the neutral point, values down to the minimumsetting possibilities can be chosen. However, one must consider zero-sequencecurrents that can occur during normal operation of the power system. Such currentscan be due to un-transposed lines.

In case to protection of transformer windings not feeding residual current atexternal earth faults a fast lowcurrent step can be acceptable.

8.5 Thermal overload protection, two time constantsTRPTTR

8.5.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Thermal overload protection, two timeconstants

TRPTTR

SYMBOL-A V1 EN

49

8.5.2 ApplicationTransformers in the power system are designed for a certain maximum load current(power) level. If the current exceeds this level the losses will be higher than

Section 8 1MRK 504 134-UEN -Current protection

166Application Manual

Page 173: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

expected. As a consequence the temperature of the transformer will increase. If thetemperature of the transformer reaches too high values the equipment might bedamaged:

• The insulation within the transformer will experience forced ageing. As aconsequence of this, the risk of internal phase-to-phase or phase-to-earth faultswill increase.

• There might be hot spots within the transformer, which will degrade the paperinsulation. It might also cause bubbling in the transformer oil.

In stressed situations in the power system it can be required to overloadtransformers for a limited time. This should be done without the above mentionedrisks. The thermal overload protection provides information and makes temporaryoverloading of transformers possible.

The permissible load level of a power transformer is highly dependent on thecooling system of the transformer. There are two main principles:

• OA: The air is naturally circulated to the coolers without fans and the oil isnaturally circulated without pumps.

• FOA: The coolers have fans to force air for cooling and pumps to force thecirculation of the transformer oil.

The protection can have two sets of parameters, one for non-forced cooling and onefor forced cooling. Both the permissive steady state loading level as well as thethermal time constant is influenced by the cooling system of the transformer. Thetwo parameters sets can be activated by the binary input signal COOLING. Thiscan be used for transformers where forced cooling can be taken out of operation,for example at fan or pump faults.

The thermal overload protection estimates the internal heat content of thetransformer (temperature) continuously. This estimation is made by using a thermalmodel of the transformer, which is based on current measurement.

If the heat content of the protected transformer reaches a set alarm level a signalcan be given to the operator. Two alarm levels are available. This enablespreventive actions in the power system to be taken before dangerous temperaturesare reached. If the temperature continues to increase to the trip value, the protectioninitiates a trip of the protected transformer.

After tripping by the thermal overload protection, the transformer will cool downover time. There will be a time gap before the heat content (temperature) reachessuch a level so that the transformer can be taken into service again. Therefore, thefunction will continue to estimate the heat content using a set cooling timeconstant. Energizing of the transformer can be blocked until the heat content hasreached a set level.

1MRK 504 134-UEN - Section 8Current protection

167Application Manual

Page 174: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

8.5.3 Setting guidelineThe parameters for the thermal overload protection, two time constants (TRPTTR)are set via the local HMI or through the Protection and Control Manager (PCM600).

The following settings can be done for the thermal overload protection:

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

Operation: Sets the mode of operation. Off switches off the complete function.

IRef: Reference level of the current given in % of IBase. When the current is equalto IRef the final (steady state) heat content is equal to 1. It is suggested to give asetting corresponding to the rated current of the transformer winding. Transformerrated current / IBase* 100%.

IBase1: Base current for setting given as percentage of IBase. This setting shall berelated to the status with no COOLING input. It is suggested to give a settingcorresponding to the rated current of the transformer with natural cooling (OA).

IBase2: Base current for setting given as percentage of IBase. This setting shall berelated to the status with activated COOLING input. It is suggested to give asetting corresponding to the rated current of the transformer with forced cooling(FOA). If the transformer has no forced cooling IBase2 can be set equal to IBase1.

Tau1: The thermal time constant of the protected transformer, related to IBase1 (nocooling) given in minutes.

Tau2: The thermal time constant of the protected transformer, related to IBase2(with cooling) given in minutes.

The thermal time constant should be obtained from the transformer manufacturersmanuals. The thermal time constant is dependent on the cooling and the amount ofoil. Normal time constants for medium and large transformers (according to IEC60076-7) are about 2.5 hours for naturally cooled transformers and 1.5 hours forforced cooled transformers.

The time constant can be estimated from measurements of the oil temperatureduring a cooling sequence (described in IEC 60076-7). It is assumed that thetransformer is operated at a certain load level with a constant oil temperature(steady state operation). The oil temperature above the ambient temperature isDQo0. Then the transformer is disconnected from the grid (no load). After a time tof at least 30 minutes the temperature of the oil is measured again. Now the oiltemperature above the ambient temperature is DQot. The thermal time constant cannow be estimated as:

0ln lno ot

tt =DQ - DQ

EQUATION1180 V1 EN (Equation 82)

Section 8 1MRK 504 134-UEN -Current protection

168Application Manual

Page 175: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

If the transformer has forced cooling (FOA) the measurement should be made bothwith and without the forced cooling in operation, giving Tau2 and Tau1.

The time constants can be changed if the current is higher than a set value or lowerthan a set value. If the current is high it is assumed that the forced cooling isactivated while it is deactivated at low current. The setting of the parameters belowenables automatic adjustment of the time constant.

Tau1High: Multiplication factor to adjust the time constant Tau1 if the current ishigher than the set value IHighTau1. IHighTau1 is set in % of IBase1.

Tau1Low: Multiplication factor to adjust the time constant Tau1 if the current islower than the set value ILowTau1. ILowTau1 is set in % of IBase1.

Tau2High: Multiplication factor to adjust the time constant Tau2 if the current ishigher than the set value IHighTau2. IHighTau2 is set in % of IBase2.

Tau2Low: Multiplication factor to adjust the time constant Tau2 if the current islower than the set value ILowTau2. ILowTau2 is set in % of IBase2.

The possibility to change time constant with the current value as the base can beuseful in different applications. Below some examples are given:

• In case a total interruption (low current) of the protected transformer allcooling possibilities will be inactive. This can result in a changed value of thetime constant.

• If other components (motors) are included in the thermal protection, there is arisk of overheating of that equipment in case of very high current. The thermaltime constant is often smaller for a motor than for the transformer.

ITrip: The steady state current that the transformer can withstand. The setting isgiven in % of IBase1 or IBase2.

Alarm1: Heat content level for activation of the signal ALARM1. ALARM1 is setin % of the trip heat content level.

Alarm2: Heat content level for activation of the output signal ALARM2. ALARM2is set in % of the trip heat content level.

ResLo: Lockout release level of heat content to release the lockout signal. Whenthe thermal overload protection trips a lock-out signal is activated. This signal isintended to block switching on of the protected circuit transformer as long as thetransformer temperature is high. The signal is released when the estimated heatcontent is below the set value. This temperature value should be chosen below thealarm temperature. ResLo is set in % of the trip heat content level.

Warning: If the calculated time to trip factor is below the setting Warning awarning signal is activated. The setting is given in minutes.

1MRK 504 134-UEN - Section 8Current protection

169Application Manual

Page 176: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

8.6 Breaker failure protection 3-phase activation andoutput CCRBRF

8.6.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Breaker failure protection, 3-phaseactivation and output

CCRBRF

3I>BF

SYMBOL-U V1 EN

50BF

8.6.2 ApplicationIn the design of the fault clearance system the N-1 criterion is often used. Thismeans that a fault needs to be cleared even if any component in the fault clearancesystem is faulty. One necessary component in the fault clearance system is thecircuit breaker. It is from practical and economical reason not feasible to duplicatethe circuit breaker for the protected component. Instead a breaker failure protectionis used.

Breaker failure protection, 3-phase activation and output (CCRBRF) will issue aback-up trip command to adjacent circuit breakers in case of failure to trip of the“normal” circuit breaker for the protected component. The detection of failure tobreak the current through the breaker is made by means of current measurement oras detection of remaining trip signal (unconditional).

CCRBRF can also give a re-trip. This means that a second trip signal is sent to theprotected circuit breaker. The re-trip function can be used to increase theprobability of operation of the breaker, or it can be used to avoid back-up trip ofmany breakers in case of mistakes during relay maintenance and test.

8.6.3 Setting guidelinesThe parameters for Breaker failure protection 3-phase activation and outputCCRBRF are set via the local HMI or PCM600.

The following settings can be done for the breaker failure protection.

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

Operation: Off/On

Section 8 1MRK 504 134-UEN -Current protection

170Application Manual

Page 177: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

FunctionMode This parameter can be set Current or Contact. This states the waythe detection of failure of the breaker is performed. In the mode current the currentmeasurement is used for the detection. In the mode Contact the long duration ofbreaker position signal is used as indicator of failure of the breaker. The modeCurrent&Contact means that both ways of detections are activated. Contact modecan be usable in applications where the fault current through the circuit breaker issmall. This can be the case for some generator protection application (for examplereverse power protection) or in case of line ends with weak end infeed.

RetripMode: This setting states how the re-trip function shall operate. Retrip Offmeans that the re-trip function is not activated. CB Pos Check (circuit breakerposition check) and Current means that a phase current must be larger than theoperate level to allow re-trip. CB Pos Check (circuit breaker position check) andContact means re-trip is done when circuit breaker is closed (breaker position isused). No CBPos Check means re-trip is done without check of breaker position.

Table 16: Dependencies between parameters RetripMode and FunctionMode

RetripMode FunctionMode DescriptionRetrip Off N/A the re-trip function is not

activated

CB Pos Check Current a phase current must be largerthan the operate level to allowre-trip

Contact re-trip is done when breakerposition indicates that breakeris still closed after re-trip timehas elapsed

Current&Contact both methods are used

No CBPos Check Current re-trip is done without check ofbreaker position

Contact re-trip is done without check ofbreaker position

Current&Contact both methods are used

BuTripMode: Back-up trip mode is given to state sufficient current criteria to detectfailure to break. For Current operation 2 out of 4 means that at least two currents,of the three-phase currents and the residual current, shall be high to indicatebreaker failure. 1 out of 3 means that at least one current of the three-phase currentsshall be high to indicate breaker failure. 1 out of 4 means that at least one current ofthe three-phase currents or the residual current shall be high to indicate breakerfailure. In most applications 1 out of 3 is sufficient. For Contact operation meansback-up trip is done when circuit breaker is closed (breaker position is used).

IP>: Current level for detection of breaker failure, set in % of IBase. Thisparameter should be set so that faults with small fault current can be detected. Thesetting can be chosen in accordance with the most sensitive protection function tostart the breaker failure protection. Typical setting is 10% of IBase.

1MRK 504 134-UEN - Section 8Current protection

171Application Manual

Page 178: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

I>BlkCont: If any contact based detection of breaker failure is used this functioncan be blocked if any phase current is larger than this setting level. If theFunctionMode is set Current&Contact breaker failure for high current faults aresafely detected by the current measurement function. To increase security thecontact based function should be disabled for high currents. The setting can begiven within the range 5 – 200% of IBase.

IN>: Residual current level for detection of breaker failure set in % of IBase. Inhigh impedance earthed systems the residual current at phase- to-earth faults arenormally much smaller than the short circuit currents. In order to detect breakerfailure at single-phase-earth faults in these systems it is necessary to measure theresidual current separately. Also in effectively earthed systems the setting of theearth-fault current protection can be chosen to relatively low current level. TheBuTripMode is set 1 out of 4. The current setting should be chosen in accordance tothe setting of the sensitive earth-fault protection. The setting can be given withinthe range 2 – 200 % of IBase.

t1: Time delay of the re-trip. The setting can be given within the range 0 – 60s insteps of 0.001 s. Typical setting is 0 – 50ms.

t2: Time delay of the back-up trip. The choice of this setting is made as short aspossible at the same time as unwanted operation must be avoided. Typical setting is90 – 200ms (also dependent of re-trip timer).

The minimum time delay for the re-trip can be estimated as:

_2 1³ + + +cbopen BFP reset margint t t t tEQUATION1430 V1 EN (Equation 83)

where:

tcbopen is the maximum opening time for the circuit breaker

tBFP_reset is the maximum time for breaker failure protection to detect correct breaker function (thecurrent criteria reset)

tmargin is a safety margin

It is often required that the total fault clearance time shall be less than a givencritical time. This time is often dependent of the ability to maintain transientstability in case of a fault close to a power plant.

Section 8 1MRK 504 134-UEN -Current protection

172Application Manual

Page 179: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Time

The fault occurs

Protection operate time

Trip and Start CCRBRF

Normal tcbopen

Margin

Retrip delay t1 tcbopen after re-trip

tBFPreset

Minimum back-up trip delay t2

Critical fault clearance time for stability

IEC05000479_2_en.vsdIEC05000479 V2 EN

Figure 76: Time sequence

8.7 Pole discordance protection CCRPLD

8.7.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Pole discordance protection CCRPLD

PD

SYMBOL-S V1 EN

52PD

8.7.2 ApplicationThere is a risk that a circuit breaker will get discordance between the poles atcircuit breaker operation: closing or opening. One pole can be open and the othertwo closed, or two poles can be open and one closed. Pole discordance of a circuitbreaker will cause unsymmetrical currents in the power system. The consequenceof this can be:

1MRK 504 134-UEN - Section 8Current protection

173Application Manual

Page 180: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

• Negative sequence currents that will give stress on rotating machines• Zero sequence currents that might give unwanted operation of sensitive earth-

fault protections in the power system.

It is therefore important to detect situations with pole discordance of circuitbreakers. When this is detected the breaker should be tripped directly.

Pole discordance protection CCRPLD will detect situation with deviating positionsof the poles of the protected circuit breaker. The protection has two differentoptions to make this detection:

• By connecting the auxiliary contacts in the circuit breaker so that logic iscreated and a signal can be sent to the pole discordance protection, indicatingpole discordance.

• Each phase current through the circuit breaker is measured. If the differencebetween the phase currents is larger than a CurrUnsymLevel this is anindication of pole discordance, and the protection will operate.

8.7.3 Setting guidelinesThe parameters for the Pole discordance protection CCRPLD are set via the localHMI or PCM600.

The following settings can be done for the pole discordance protection.

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

Operation: Off or On

tTrip: Time delay of the operation.

ContSel: Operation of the contact based pole discordance protection. Can be set:Off/PD signal from CB. If PD signal from CB is chosen the logic to detect polediscordance is made in the vicinity to the breaker auxiliary contacts and only onesignal is connected to the pole discordance function.

CurrSel: Operation of the current based pole discordance protection. Can be set:Off/CB oper monitor/Continuous monitor. In the alternative CB oper monitor thefunction is activated only directly in connection to breaker open or close command(during 200 ms). In the alternative Continuous monitor function is continuouslyactivated.

CurrUnsymLevel: Unsymmetrical magnitude of lowest phase current compared tothe highest, set in % of the highest phase current.

CurrRelLevel: Current magnitude for release of the function in % of IBase.

Section 8 1MRK 504 134-UEN -Current protection

174Application Manual

Page 181: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

8.8 Directional over-/under-power protectionGOPPDOP/GUPPDUP

8.8.1 ApplicationThe task of a generator in a power plant is to convert mechanical energy availableas a torque on a rotating shaft to electric energy.

Sometimes, the mechanical power from a prime mover may decrease so much thatit does not cover bearing losses and ventilation losses. Then, the synchronousgenerator becomes a synchronous motor and starts to take electric power from therest of the power system. This operating state, where individual synchronousmachines operate as motors, implies no risk for the machine itself. If the generatorunder consideration is very large and if it consumes lots of electric power, it maybe desirable to disconnect it to ease the task for the rest of the power system.

Often, the motoring condition may imply that the turbine is in a very dangerousstate. The task of the reverse power protection is to protect the turbine and not toprotect the generator itself.

Steam turbines easily become overheated if the steam flow becomes too low or ifthe steam ceases to flow through the turbine. Therefore, turbo-generators shouldhave reverse power protection. There are several contingencies that may causereverse power: break of a main steam pipe, damage to one or more blades in thesteam turbine or inadvertent closing of the main stop valves. In the last case, it ishighly desirable to have a reliable reverse power protection. It may prevent damageto an otherwise undamaged plant.

During the routine shutdown of many thermal power units, the reverse powerprotection gives the tripping impulse to the generator breaker (the unit breaker). Bydoing so, one prevents the disconnection of the unit before the mechanical powerhas become zero. Earlier disconnection would cause an acceleration of the turbinegenerator at all routine shutdowns. This should have caused overspeed and highcentrifugal stresses.

When the steam ceases to flow through a turbine, the cooling of the turbine bladeswill disappear. Now, it is not possible to remove all heat generated by the windagelosses. Instead, the heat will increase the temperature in the steam turbine andespecially of the blades. When a steam turbine rotates without steam supply, theelectric power consumption will be about 2% of rated power. Even if the turbinerotates in vacuum, it will soon become overheated and damaged. The turbineoverheats within minutes if the turbine loses the vacuum.

The critical time to overheating a steam turbine varies from about 0.5 to 30 minutesdepending on the type of turbine. A high-pressure turbine with small and thinblades will become overheated more easily than a low-pressure turbine with long

1MRK 504 134-UEN - Section 8Current protection

175Application Manual

Page 182: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

and heavy blades. The conditions vary from turbine to turbine and it is necessary toask the turbine manufacturer in each case.

Power to the power plant auxiliaries may come from a station service transformerconnected to the secondary side of the step-up transformer. Power may also comefrom a start-up service transformer connected to the external network. One has todesign the reverse power protection so that it can detect reverse power independentof the flow of power to the power plant auxiliaries.

Hydro turbines tolerate reverse power much better than steam turbines do. OnlyKaplan turbine and bulb turbines may suffer from reverse power. There is a riskthat the turbine runner moves axially and touches stationary parts. They are notalways strong enough to withstand the associated stresses.

Ice and snow may block the intake when the outdoor temperature falls far belowzero. Branches and leaves may also block the trash gates. A complete blockage ofthe intake may cause cavitations. The risk for damages to hydro turbines can justifyreverse power protection in unattended plants.

A hydro turbine that rotates in water with closed wicket gates will draw electricpower from the rest of the power system. This power will be about 10% of therated power. If there is only air in the hydro turbine, the power demand will fall toabout 3%.

Diesel engines should have reverse power protection. The generator will take about15% of its rated power or more from the system. A stiff engine may requireperhaps 25% of the rated power to motor it. An engine that is good run in mightneed no more than 5%. It is necessary to obtain information from the enginemanufacturer and to measure the reverse power during commissioning.

Gas turbines usually do not require reverse power protection.

Figure 77 illustrates the reverse power protection with underpower protection andwith overpower protection. The underpower protection gives a higher margin andshould provide better dependability. On the other hand, the risk for unwantedoperation immediately after synchronization may be higher. One should set theunderpower protection (reference angle set to 0) to trip if the active power from thegenerator is less than about 2%. One should set the overpower protection(reference angle set to 180) to trip if the power flow from the network to thegenerator is higher than 1%.

Section 8 1MRK 504 134-UEN -Current protection

176Application Manual

Page 183: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Underpower protection Overpower protection

Q Q

P P

Operating point without turbine torque

Margin Margin

OperateLine

OperateLine

Operating point without turbine torque

IEC09000019-2-en.vsdIEC09000019 V2 EN

Figure 77: Reverse power protection with underpower or overpower protection

8.8.2 Directional overpower protection GOPPDOP

8.8.2.1 Identification

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Directional overpower protection GOPPDOPP >

2DOCUMENT172362-IMG158942

V2 EN

32

8.8.2.2 Setting guidelines

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

Operation: With the parameter Operation the function can be set On/Off.

Mode: The voltage and current used for the power measurement. The settingpossibilities are shown in table 17.

For reverse power applications PosSeq or Arone modes are strongly recommended.

1MRK 504 134-UEN - Section 8Current protection

177Application Manual

Page 184: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Table 17: Complex power calculation

Set value Mode Formula used for complex power calculationL1, L2, L3 * * *

1 1 2 2 3 3L L L L L LS U I U I U I= × + × + ×

EQUATION1697 V1 EN (Equation 84)

Arone * *1 2 1 2 3 3L L L L L LS U I U I= × - ×

EQUATION1698 V1 EN (Equation 85)

PosSeq *3 PosSeq PosSeqS U I= × ×

EQUATION1699 V1 EN (Equation 86)

L1L2 * *1 2 1 2( )L L L LS U I I= × -

EQUATION1700 V1 EN (Equation 87)

L2L3 * *2 3 2 3( )L L L LS U I I= × -

EQUATION1701 V1 EN (Equation 88)

L3L1 * *3 1 3 1( )L L L LS U I I= × -

EQUATION1702 V1 EN (Equation 89)

L1 *1 13 L LS U I= × ×

EQUATION1703 V1 EN (Equation 90)

L2 *2 23 L LS U I= × ×

EQUATION1704 V1 EN (Equation 91)

L3 *3 33 L LS U I= × ×

EQUATION1705 V1 EN (Equation 92)

The function has two stages that can be set independently.

With the parameter OpMode1(2) the function can be set On/Off.

The function gives trip if the power component in the direction defined by thesetting Angle1(2) is larger than the set pick up power value Power1(2)

Section 8 1MRK 504 134-UEN -Current protection

178Application Manual

Page 185: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Operate

Angle1(2)

Power1(2)

P

Q

en06000440.vsdIEC06000440 V1 EN

Figure 78: Overpower mode

The setting Power1(2) gives the power component pick up value in the Angle1(2)direction. The setting is given in p.u. of the generator rated power, see equation 93.

Minimum recommended setting is 1.0% of SN. Note also that at the same time theminimum IED pickup current shall be at least 9 mA secondary.

3NS UBase IBase= × ×

EQUATION1708 V1 EN (Equation 93)

The setting Angle1(2) gives the characteristic angle giving maximum sensitivity ofthe power protection function. The setting is given in degrees. For active power theset angle should be 0° or 180°. 180° should be used for generator reverse powerprotection in 50Hz network while -179.5° should be used for generator reversepower protection in 60Hz network. This angle adjustment in 60Hz networks willimprove accuracy of the power function.

1MRK 504 134-UEN - Section 8Current protection

179Application Manual

Page 186: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Operate Angle1(2 ) = 180 o

Power1(2)

P

Q

IEC06000557-2-en.vsdIEC06000557 V2 EN

Figure 79: For reverse power the set angle should be 180° in the overpowerfunction

TripDelay1(2) is set in seconds to give the time delay for trip of the stage after pickup.

The possibility to have low pass filtering of the measured power can be made asshown in the formula:

( )1Old CalculatedS k S k S= × + - ×

EQUATION1893 V1 EN (Equation 94)

Where

S is a new measured value to be used for the protection function

Sold is the measured value given from the function in previous execution cycle

SCalculated is the new calculated value in the present execution cycle

k is settable parameter

The value of k=0.98 or even k=0.99 is recommended in generator reverse powerapplications as the trip delay is normally quite long. This filtering will improveaccuracy of the power function.

Section 8 1MRK 504 134-UEN -Current protection

180Application Manual

Page 187: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

8.8.3 Directional underpower protection GUPPDUP

8.8.3.1 Identification

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Directional underpower protection GUPPDUPP <

2SYMBOL-LL V2 EN

37

8.8.3.2 Setting guidelines

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

Operation: With the parameter Operation the function can be set On/Off.

Mode: The voltage and current used for the power measurement. The settingpossibilities are shown in table 18.

For reverse power applications PosSeq or Arone modes are strongly recommended.

Table 18: Complex power calculation

Set value Mode Formula used for complex power calculationL1, L2, L3 * * *

1 1 2 2 3 3L L L L L LS U I U I U I= × + × + ×

EQUATION1697 V1 EN (Equation 95)

Arone * *1 2 1 2 3 3L L L L L LS U I U I= × - ×

EQUATION1698 V1 EN (Equation 96)

PosSeq *3 PosSeq PosSeqS U I= × ×

EQUATION1699 V1 EN (Equation 97)

L1L2 * *1 2 1 2( )L L L LS U I I= × -

EQUATION1700 V1 EN (Equation 98)

L2L3 * *2 3 2 3( )L L L LS U I I= × -

EQUATION1701 V1 EN (Equation 99)

L3L1 * *3 1 3 1( )L L L LS U I I= × -

EQUATION1702 V1 EN (Equation 100)

Table continues on next page

1MRK 504 134-UEN - Section 8Current protection

181Application Manual

Page 188: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Set value Mode Formula used for complex power calculationL1 *

1 13 L LS U I= × ×

EQUATION1703 V1 EN (Equation 101)

L2 *2 23 L LS U I= × ×

EQUATION1704 V1 EN (Equation 102)

L3 *3 33 L LS U I= × ×

EQUATION1705 V1 EN (Equation 103)

The function has two stages that can be set independently.

With the parameter OpMode1(2) the function can be set On/Off.

The function gives trip if the power component in the direction defined by thesetting Angle1(2) is smaller than the set pick up power value Power1(2)

Operate

Angle1(2)

Power1(2)

P

Q

en06000441.vsdIEC06000441 V1 EN

Figure 80: Underpower mode

The setting Power1(2) gives the power component pick up value in the Angle1(2)direction. The setting is given in p.u. of the generator rated power, see equation 104.

Minimum recommended setting is 1.0% of SN. At the same time the minimum IEDpickup current shall be at least 9 mA secondary.

Section 8 1MRK 504 134-UEN -Current protection

182Application Manual

Page 189: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

3NS UBase IBase= × ×

EQUATION1708 V1 EN (Equation 104)

The setting Angle1(2) gives the characteristic angle giving maximum sensitivity ofthe power protection function. The setting is given in degrees. For active power theset angle should be 0° or 180°. 0° should be used for generator low forward activepower protection.

OperateAngle1(2) = 0°

Power1(2)

P

Q

en06000556.vsdIEC06000556 V1 EN

Figure 81: For low forward power the set angle should be 0° in theunderpower function

TripDelay1(2) is set in seconds to give the time delay for trip of the stage after pickup.

The possibility to have low pass filtering of the measured power can be made asshown in the formula:

( )1Old CalculatedS k S k S= × + - ×

EQUATION1893 V1 EN (Equation 105)

Where

S is a new measured value to be used for the protection function

Sold is the measured value given from the function in previous execution cycle

SCalculated is the new calculated value in the present execution cycle

k is settable parameter

1MRK 504 134-UEN - Section 8Current protection

183Application Manual

Page 190: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

The value of k=0.98 or even k=0.99 is recommended in generator low forwardpower applications as the trip delay is normally quite long. This filtering willimprove accuracy of the power function.

8.9 Negative sequence based overcurrent functionDNSPTOC

8.9.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Negative sequence based overcurrentfunction

DNSPTOC

3I2>

IEC09000132 V2 EN

46

8.9.2 ApplicationNegative sequence based overcurrent function DNSPTOC is typically used assensitive earth-fault protection of power lines, where incorrect zero sequencepolarization may result from mutual induction between two or more parallel lines.

Additionally, it is applied in applications on cables, where zero sequenceimpedance depends on the fault current return paths, but the cable negativesequence impedance is practically constant.

The directional function is current and voltage polarized. The function can be set toforward, reverse or non-directional independently for each step. Both steps areprovided with a settable definite time delay.

DNSPTOC protects against all unbalanced faults including phase-to-phase faults.The minimum start current of the function must be set to above the normal systemunbalance level in order to avoid unwanted operation.

8.9.3 Setting guidelinesBelow is an example of Negative sequence based overcurrent function(DNSPTOC) used as a sensitive earth-fault protection for power lines. Thefollowing settings must be done in order to ensure proper operation of the protection:

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

Section 8 1MRK 504 134-UEN -Current protection

184Application Manual

Page 191: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

• setting RCADir to value +65 degrees, that is, the negative sequence currenttypically lags the inverted negative sequence voltage for this angle during thefault

• setting ROADir to value 90 degrees• setting LowVolt_VM to value 2%, that is, the negative sequence voltage level

above which the directional element will be enabled• setting Operation_OC1 to On• setting StartCurr_OC1 to value between 3-10%, (typical values)• setting tDef_OC1 to insure proper time coordination with other earth-fault

protections installed in the vicinity of this power line• setting DirMode_OC1 to Forward• setting DirPrinc_OC1 to IcosPhi&U• setting ActLowVolt1_VM to Block

DNSPTOC is used in directional comparison protection scheme for the power lineprotection, when communication channels to the remote end of this power line areavailable. In that case, two negative sequence overcurrent steps are required - onein forward and another in reverse direction. The OC1 stage is used to detect faultsin forward direction and the OC2 stage is used to detect faults in reverse direction.

However, the following must be noted for such application:

• setting RCADir and ROADir are applicable for both steps OC1 and OC2• setting DirMode_OC1 must be set to Forward• setting DirMode_OC2 must be set to Reverse• setting StartCurr_OC2 must be made more sensitive than pickup value of the

forward OC1 element, that is, typically 60% of StartCurr_OC1 set pickuplevel in order to insure proper operation of the directional comparison schemeduring current reversal situations

• the start signals STOC1 and STOC2 from OC1 and OC2 elements is used tosend forward and reverse signals to the remote end of the power line

• the available scheme communications function block within IED is usedbetween the protection function and the teleprotection communicationequipment, in order to insure proper conditioning of the above two start signals.

ActLowVolt1 and ActLowVolt2 should not be set to Memory.

1MRK 504 134-UEN - Section 8Current protection

185Application Manual

Page 192: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

186

Page 193: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Section 9 Voltage protection

9.1 Two step undervoltage protection UV2PTUV

9.1.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Two step undervoltage protection UV2PTUV

3U<

SYMBOL-R-2U-GREATER-THANV2 EN

27

9.1.2 ApplicationTwo-step undervoltage protection function (UV2PTUV) is applicable in allsituations, where reliable detection of low phase voltages is necessary. It is usedalso as a supervision and fault detection function for other protection functions, toincrease the security of a complete protection system.

UV2PTUV is applied to power system elements, such as generators, transformers,motors and power lines in order to detect low voltage conditions. Low voltageconditions are caused by abnormal operation or fault in the power system.UV2PTUV is used in combination with overcurrent protections, either as restraintor in logic "and gates" of the trip signals issued by the two functions. Otherapplications are the detection of "no voltage" condition, for example, before theenergization of a HV line or for automatic breaker trip in case of a blackout.UV2PTUV is also used to initiate voltage correction measures, like insertion ofshunt capacitor banks to compensate for reactive load and thereby increasing thevoltage. The function has a high measuring accuracy to allow applications tocontrol reactive load.

UV2PTUV is used to disconnect apparatuses, like electric motors, which will bedamaged when subject to service under low voltage conditions. UV2PTUV dealswith low voltage conditions at power system frequency, which can be caused bythe following reasons:

1. Malfunctioning of a voltage regulator or wrong settings under manual control(symmetrical voltage decrease).

2. Overload (symmetrical voltage decrease).3. Short circuits, often as phase-to-earth faults (unsymmetrical voltage decrease).

1MRK 504 134-UEN - Section 9Voltage protection

187Application Manual

Page 194: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

UV2PTUV prevents sensitive equipment from running under conditions that couldcause their overheating and thus shorten their life time expectancy. In many cases,it is a useful function in circuits for local or remote automation processes in thepower system.

9.1.3 Setting guidelinesAll the voltage conditions in the system where UV2PTUV performs its functionsshould be considered. The same also applies to the associated equipment, itsvoltage and time characteristic.

There is a very wide application area where general undervoltage functions areused. All voltage related settings are made as a percentage of the global settingsbase voltage UBase, which normally is set to the primary rated voltage level (phase-to-phase) of the power system or the high voltage equipment under consideration.

The setting for UV2PTUV is normally not critical, since there must be enough timeavailable for the main protection to clear short circuits and earth faults.

Some applications and related setting guidelines for the voltage level are describedin the following sections.

9.1.3.1 Equipment protection, such as for motors and generators

The setting must be below the lowest occurring "normal" voltage and above thelowest acceptable voltage for the equipment.

9.1.3.2 Disconnected equipment detection

The setting must be below the lowest occurring "normal" voltage and above thehighest occurring voltage, caused by inductive or capacitive coupling, when theequipment is disconnected.

9.1.3.3 Power supply quality

The setting must be below the lowest occurring "normal" voltage and above thelowest acceptable voltage, due to regulation, good practice or other agreements.

9.1.3.4 Voltage instability mitigation

This setting is very much dependent on the power system characteristics, andthorough studies have to be made to find the suitable levels.

9.1.3.5 Backup protection for power system faults

The setting must be below the lowest occurring "normal" voltage and above thehighest occurring voltage during the fault conditions under consideration.

Section 9 1MRK 504 134-UEN -Voltage protection

188Application Manual

Page 195: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

9.1.3.6 Settings for Two step undervoltage protection

The following settings can be done for two step undervoltage protection (UV2PTUV).

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

ConnType: Sets whether the measurement shall be phase-to-earth fundamentalvalue, phase-to-phase fundamental value, phase-to-earth RMS value or phase-to-phase RMS value.

Operation: Off/On.

UV2PTUV measures selectively phase-to-earth voltages, or phase-to-phase voltagechosen by the setting ConnType.

This means operation for phase-to-earth voltage if:

(%) ( )3

U UBase kV< ×

EQUATION1447 V1 EN (Equation 106)

and operation for phase-to-phase voltage if:

U (%) UBase(kV)< ×EQUATION1990 V1 EN (Equation 107)

Characteristic1: This parameter gives the type of time delay to be used for step 1.The setting can be. Definite time/Inverse Curve A/Inverse Curve B. The choice ishighly dependent of the protection application.

OpModen: This parameter describes how many of the three measured voltages thatshould be below the set level to give operation for step n (n=step 1 and 2). Thesetting can be 1 out of 3, 2 out of 3 or 3 out of 3. It is sufficient that one phasevoltage is low to give operation. If the function shall be insensitive for single phase-to-earth faults 2 out of 3 can be chosen.

Un<: Set undervoltage operation value for step n (n=step 1 and 2), given as % ofthe global parameter UBase. This setting is highly dependent of the protectionapplication. Here it is essential to consider the minimum voltage at non-faultedsituations. This voltage is larger than 90% of nominal voltage.

tn: Time delay for step n (n=step 1 and 2), given in s. This setting is highlydependent of the protection application. In many applications the protectionfunction does not directly trip where there is short circuit or earth faults in thesystem. The time delay must be coordinated to the short circuit protection.

t1Min: Minimum operating time for inverse time characteristic for step 1, given ins. When using inverse time characteristic for the undervoltage function during verylow voltages can give a short operation time. This might lead to unselective trip.

1MRK 504 134-UEN - Section 9Voltage protection

189Application Manual

Page 196: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

By setting t1Min longer than the operation time for other protections suchunselective tripping can be avoided.

k1: Time multiplier for inverse time characteristic. This parameter is used forcoordination between different inverse time delayed undervoltage protections.

The function must be externally blocked when the protected objectis disconnected.

9.2 Two step overvoltage protection OV2PTOV

9.2.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Two step overvoltage protection OV2PTOV

3U>

SYMBOL-C-2U-SMALLER-THANV2 EN

59

9.2.2 ApplicationTwo step overvoltage protection OV2PTOV is applicable in all situations, wherereliable detection of high voltage is necessary. OV2PTOV is used for supervisionand detection of abnormal conditions, which, in combination with other protectionfunctions, increase the security of a complete protection system.

High overvoltage conditions are caused by abnormal situations in the powersystem. OV2PTOV is applied to power system elements, such as generators,transformers, motors and power lines in order to detect high voltage conditions.OV2PTOV is used in combination with low current signals, to identify atransmission line, open in the remote end. In addition to that, OV2PTOV is alsoused to initiate voltage correction measures, like insertion of shunt reactors, tocompensate for low load, and thereby decreasing the voltage. The function has ahigh measuring accuracy and hysteresis setting to allow applications to controlreactive load.

OV2PTOV is used to disconnect apparatuses, like electric motors, which will bedamaged when subject to service under high voltage conditions. It deals with highvoltage conditions at power system frequency, which can be caused by:

1. Different kinds of faults, where a too high voltage appears in a certain powersystem, like metallic connection to a higher voltage level (broken conductor

Section 9 1MRK 504 134-UEN -Voltage protection

190Application Manual

Page 197: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

falling down to a crossing overhead line, transformer flash over fault from thehigh voltage winding to the low voltage winding and so on).

2. Malfunctioning of a voltage regulator or wrong settings under manual control(symmetrical voltage decrease).

3. Low load compared to the reactive power generation (symmetrical voltagedecrease).

4. Earth-faults in high impedance earthed systems causes, beside the high voltagein the neutral, high voltages in the two non-faulted phases, (unsymmetricalvoltage increase).

OV2PTOV prevents sensitive equipment from running under conditions that couldcause their overheating or stress of insulation material, and, thus, shorten their lifetime expectancy. In many cases, it is a useful function in circuits for local orremote automation processes in the power system.

9.2.3 Setting guidelinesThe parameters for Two step overvoltage protection (OV2PTOV) are set via thelocal HMI or PCM600.

All the voltage conditions in the system where OV2PTOV performs its functionsshould be considered. The same also applies to the associated equipment, itsvoltage and time characteristic.

There is a very wide application area where general overvoltage functions are used.All voltage related settings are made as a percentage of a settable base primaryvoltage, which normally is set to the nominal voltage level (phase-to-phase) of thepower system or the high voltage equipment under consideration.

The time delay for the OV2PTOV can sometimes be critical and related to the sizeof the overvoltage - a power system or a high voltage component can withstandsmaller overvoltages for some time, but in case of large overvoltages the relatedequipment should be disconnected more rapidly.

Some applications and related setting guidelines for the voltage level are given below:

Equipment protection, such as for motors, generators, reactors andtransformersHigh voltage can cause overexcitation of the core and deteriorate the windinginsulation. The setting must be above the highest occurring "normal" voltage andbelow the highest acceptable voltage for the equipment.

Equipment protection, capacitorsHigh voltage can deteriorate the dielectricum and the insulation. The setting mustbe above the highest occurring "normal" voltage and below the highest acceptablevoltage for the capacitor.

1MRK 504 134-UEN - Section 9Voltage protection

191Application Manual

Page 198: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

High impedance earthed systemsIn high impedance earthed systems, earth-faults cause a voltage increase in the non-faulty phases. OV2PTOV can be used to detect such faults. The setting must beabove the highest occurring "normal" voltage and below the lowest occurringvoltage during faults. A metallic single-phase earth-fault causes the non-faultedphase voltages to increase a factor of √3.

The following settings can be done for Two step overvoltage protectionGlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

ConnType: Sets whether the measurement shall be phase-to-earth fundamentalvalue, phase-to-phase fundamental value, phase-to-earth RMS value or phase-to-phase RMS value.

Operation: Off/On .

OV2PTOV measures the phase-to-earth voltages, or phase-to-phase voltages asselected. The function will operate if the voltage gets higher than the set percentageof the global set base voltage UBase. This means operation for phase-to-earthvoltage over:

( )(%)3

UBase kVU > ×

IEC09000054 V1 EN (Equation 108)

and operation for phase-to-phase voltage over:

U (%) UBase(kV)> ×EQUATION1993 V1 EN (Equation 109)

Characteristic1: This parameter gives the type of time delay to be used. The settingcan be. Definite time/Inverse Curve A/Inverse Curve B/Inverse Curve C. Thechoice is highly dependent of the protection application.

OpModen: This parameter describes how many of the three measured voltages thatshould be above the set level to give operation for step n (n=step 1 and 2). Thesetting can be 1 out of 3, 2 out of 3 or 3 out of 3. In most applications it is sufficientthat one phase voltage is high to give operation. If the function shall be insensitivefor single phase-to-earth faults 3 out of 3 can be chosen, because the voltage willnormally rise in the non-faulted phases at single phase-to-earth faults.

Un>: Set overvoltage operating value for step n (n=step 1 and 2), given as % of theglobal parameter UBase. The setting is highly dependent of the protectionapplication. Here it is essential to consider the Maximum voltage at non-faultedsituations. Normally this voltage is less than 110% of nominal voltage.

tn: time delay for step n (n=step 1 and 2), given in s. The setting is highlydependent of the protection application. In many applications the protection

Section 9 1MRK 504 134-UEN -Voltage protection

192Application Manual

Page 199: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

function has the task to prevent damages to the protected object. The speed mightbe important for example in case of protection of transformer that might beoverexcited. The time delay must be co-ordinated with other automated actions inthe system.

t1Min: Minimum operating time for inverse time characteristic for step 1, given ins. For very high voltages the overvoltage function, using inverse timecharacteristic, can give very short operation time. This might lead to unselectivetrip. By setting t1Min longer than the operation time for other protections suchunselective tripping can be avoided.

k1: Time multiplier for inverse time characteristic. This parameter is used for co-ordination between different inverse time delayed undervoltage protections.

9.3 Two step residual overvoltage protectionROV2PTOV

9.3.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Two step residual overvoltageprotection

ROV2PTOV

3U0>

IEC10000168 V1 EN

59N

9.3.2 ApplicationTwo step residual overvoltage protection ROV2PTOV is primarily used in highimpedance earthed distribution networks, mainly as a backup for the primary earth-fault protection of the feeders and the transformer. To increase the security fordifferent earth-fault related functions, the residual overvoltage signal can be usedas a release signal. The residual voltage can be measured either at the transformerneutral or from a voltage transformer open delta connection. The residual voltagecan also be calculated internally, based on measurement of the three-phase voltages.

In high impedance earthed systems the residual voltage will increase in case of anyfault connected to earth. Depending on the type of fault and fault resistance theresidual voltage will reach different values. The highest residual voltage, equal tothree times the phase-to-earth voltage, is achieved for a single phase-to-earth fault.The residual voltage increases approximately to the same level in the whole systemand does not provide any guidance in finding the faulted component. Therefore,ROV2PTOV is often used as a backup protection or as a release signal for thefeeder earth-fault protection.

1MRK 504 134-UEN - Section 9Voltage protection

193Application Manual

Page 200: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

9.3.3 Setting guidelinesAll the voltage conditions in the system where ROV2PTOV performs its functionsshould be considered. The same also applies to the associated equipment, itsvoltage and time characteristic.

There is a very wide application area where general single input or residualovervoltage functions are used. All voltage related settings are made as apercentage of a settable base voltage, which can be set to the primary nominalvoltage (phase-phase) level of the power system or the high voltage equipmentunder consideration.

The time delay for ROV2PTOV is seldom critical, since residual voltage is relatedto earth-faults in a high impedance earthed system, and enough time must normallybe given for the primary protection to clear the fault. In some more specificsituations, where the single overvoltage protection is used to protect some specificequipment, the time delay is shorter.

Some applications and related setting guidelines for the residual voltage level aregiven below.

9.3.3.1 Equipment protection, such as for motors, generators, reactors andtransformers

High residual voltage indicates earth-fault in the system, perhaps in the componentto which Two step residual overvoltage protection (ROV2PTOV) is connected. Forselectivity reasons to the primary protection for the faulted device ROV2PTOVmust trip the component with some time delay. The setting must be above thehighest occurring "normal" residual voltage and below the highest acceptableresidual voltage for the equipment

9.3.3.2 Power supply quality

The setting must be above the highest occurring "normal" residual voltage andbelow the highest acceptable residual voltage, due to regulation, good practice orother agreements.

9.3.3.3 High impedance earthed systems

In high impedance earthed systems, earth faults cause a neutral voltage in thefeeding transformer neutral. Two step residual overvoltage protection ROV2PTOVis used to trip the transformer, as a backup protection for the feeder earth-faultprotection, and as a backup for the transformer primary earth-fault protection. Thesetting must be above the highest occurring "normal" residual voltage, and belowthe lowest occurring residual voltage during the faults under consideration. Ametallic single-phase earth fault causes a transformer neutral to reach a voltageequal to the nominal phase-to-earth voltage.

Section 9 1MRK 504 134-UEN -Voltage protection

194Application Manual

Page 201: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

The voltage transformers measuring the phase-to-earth voltages measure zerovoltage in the faulty phase. The two healthy phases will measure full phase-to-phase voltage, as the earth is available on the faulty phase and the neutral has a fullphase-to-earth voltage. The residual overvoltage will be three times the phase-to-earth voltage. See Figure 82.

IEC07000190 V1 EN

Figure 82: Earth fault in Non-effectively earthed systems

9.3.3.4 Direct earthed system

In direct earthed systems, an earth fault on one phase indicates a voltage collapse inthat phase. The two healthy phases will have normal phase-to-earth voltages. The

1MRK 504 134-UEN - Section 9Voltage protection

195Application Manual

Page 202: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

residual sum will have the same value as the remaining phase-to-earth voltage. SeeFigure 83.

IEC07000189 V1 EN

Figure 83: Earth fault in Direct earthed system

9.3.3.5 Settings for Two step residual overvoltage protection

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

Operation: Off or On

UBase is used as voltage reference for the voltage. The voltage can be fed to theIED in different ways:

1. The IED is fed from a normal voltage transformer group where the residualvoltage is created from the phase-to-earth voltages within the protectionsoftware.

2. The IED is fed from a broken delta connection normal voltage transformergroup. In an open delta connection the protection is fed by the voltage 3U0(single input). The Setting chapter in the application manual explains how theanalog input needs to be set.

3. The IED is fed from a single voltage transformer connected to the neutral pointof a power transformer in the power system. In this connection the protectionis fed by the voltage UN=U0 (single input). The Setting chapter in theapplication manual explains how the analog input needs to be set.ROV2PTOV will measure the residual voltage corresponding nominal phase-to-

Section 9 1MRK 504 134-UEN -Voltage protection

196Application Manual

Page 203: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

earth voltage for a high impedance earthed system. The measurement will bebased on the neutral voltage displacement.

Characteristic1: This parameter gives the type of time delay to be used. The settingcan be, Definite time or Inverse curve A or Inverse curve B or Inverse curve C. Thechoice is highly dependent of the protection application.

Un>: Set overvoltage operate value for step n (n=step 1 and 2), given as % ofresidual voltage corresponding to global set parameter UBase:

( ) ( )% 3U UBase kV> ×IECEQUATION2290 V1 EN (Equation 110)

The setting is dependent of the required sensitivity of the protection and the systemearthing. In non-effectively earthed systems the residual voltage can be maximumthe rated phase-to-earth voltage, which should correspond to 100%.

In effectively earthed systems this value is dependent of the ratio Z0/Z1. Therequired setting to detect high resistive earth-faults must be based on networkcalculations.

tn: time delay of step n (n=step 1 and 2), given in s. The setting is highlydependent of the protection application. In many applications, the protectionfunction has the task to prevent damages to the protected object. The speed mightbe important for example in case of protection of transformer that might beoverexcited. The time delay must be co-ordinated with other automated actions inthe system.

t1Min: Minimum operate time for inverse time characteristic for step 1, given in s.For very high voltages the overvoltage function, using inverse time characteristic,can give very short operation time. This might lead to unselective trip. By settingt1Min longer than the operation time for other protections such unselective trippingcan be avoided.

k1: Time multiplier for inverse time characteristic. This parameter is used for co-ordination between different inverse time delayed undervoltage protections.

9.4 Overexcitation protection OEXPVPH

9.4.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Overexcitation protection OEXPVPH

U/f >

SYMBOL-Q V1 EN

24

1MRK 504 134-UEN - Section 9Voltage protection

197Application Manual

Page 204: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

9.4.2 ApplicationThe Overexcitation protection (OEXPVPH) has current inputs to allow calculationof the load influence on the induced voltage. This gives a more exact measurementof the magnetizing flow. For power transformers with unidirectional load flow, thevoltage to OEXPVPH should therefore be taken from the feeder side.

Heat accumulated in critical parts during a period of overexcitation will be reducedgradually when the excitation returns to the normal value. If a new period ofoverexcitation occurs after a short time interval, the heating will start from a higherlevel, therefore, OEXPVPH must have thermal memory. A fixed cooling timeconstant of 20 minutes is used.

The function should preferably be configured to use a three-phase voltage input ifavailable. It then uses the positive sequence quantities of voltages and currents.When configured to a single phase-to-phase voltage input, a corresponding phase-to-phase current is calculated.

Analog measurements shall not be taken from any winding where aload tap changer is located.

Some different connection alternatives are shown in figure 84.

G

U/f>

24

U/f>

24

U/f>

24

en05000208.vsd

IEC05000208 V1 EN

Figure 84: Alternative connections of an Overexcitation protectionOEXPVPH(Volt/Hertz)

Section 9 1MRK 504 134-UEN -Voltage protection

198Application Manual

Page 205: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

9.4.3 Setting guidelines

9.4.3.1 Recommendations for input and output signals

Please refer to the Technical manual for a list of setting parameters.

Binary Input signalsBLOCK: The input will block the operation of the Overexcitation protectionOEXPVPH. The block input can be used to block the operation for a limited timeduring special service conditions.

RESET: OEXPVPH has a thermal memory, which can take a long time to reset.Activation of the RESET input will reset the function instantaneously.

Binary Output signalsSTART: The START output indicates that the setV/Hz>> level has been reached.

TRIP: The TRIP output is activated after the operate time for the U/f level has expired.

ALARM: The output is activated when the alarm level has been reached and thealarm timer has elapsed.

9.4.3.2 Settings

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

Operation: The operation of the Overexcitation protection OEXPVPH can be set toOn/Off.

V/Hz>: Operating level for the inverse characteristic. The operation is based on therelation between rated voltage and rated frequency and set as a percentage factor.Normal setting is around 108-110% depending of the capability curve for thetransformer/generator.

V/Hz>>: Operating level for the tMin definite time delay used at highovervoltages. The operation is based on the relation between rated voltage andrated frequency and set as a percentage factor. Normal setting is around 110-180%depending of the capability curve of the transformer/generator. Setting should beabove the knee-point when the characteristic starts to be straight on the high side.

kForIEEE: The time constant for the IEEE inverse characteristic. Select the onegiving the best match to the transformer capability.

tMin: The operating times at voltages higher than the set V/Hz>>. The setting shallmatch capabilities on these high voltages. Typical setting can be 1-10 second.

AlarmLevel: Setting of the alarm level in percentage of the set trip level. The alarmlevel is normally set at around 98% of the trip level.

1MRK 504 134-UEN - Section 9Voltage protection

199Application Manual

Page 206: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

tAlarm: Setting of the time delay to alarm from when the alarm level has beenreached. Typical setting is 5 seconds.

Section 9 1MRK 504 134-UEN -Voltage protection

200Application Manual

Page 207: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Section 10 Frequency protection

10.1 Underfrequency protection SAPTUF

10.1.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Underfrequency protection SAPTUF

f <

SYMBOL-P V1 EN

81

10.1.2 ApplicationUnderfrequency protection SAPTUF is applicable in all situations, where reliabledetection of low fundamental power system frequency is needed. The powersystem frequency, and the rate of change of frequency, is a measure of theunbalance between the actual generation and the load demand. Low fundamentalfrequency in a power system indicates that the available generation is too low tofully supply the power demanded by the load connected to the power grid.SAPTUF detects such situations and provides an output signal, suitable for loadshedding, generator boosting, HVDC-set-point change, gas turbine start up and soon. Sometimes shunt reactors are automatically switched in due to low frequency,in order to reduce the power system voltage and hence also reduce the voltagedependent part of the load.

SAPTUF is very sensitive and accurate and is used to alert operators that frequencyhas slightly deviated from the set-point, and that manual actions might be enough.The underfrequency signal is also used for overexcitation detection. This isespecially important for generator step-up transformers, which might be connectedto the generator but disconnected from the grid, during a roll-out sequence. If thegenerator is still energized, the system will experience overexcitation, due to thelow frequency.

10.1.3 Setting guidelinesAll the frequency and voltage magnitude conditions in the system where SAPTUFperforms its functions should be considered. The same also applies to theassociated equipment, its frequency and time characteristic.

1MRK 504 134-UEN - Section 10Frequency protection

201Application Manual

Page 208: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

There are two specific application areas for SAPTUF:

1. to protect equipment against damage due to low frequency, such as generators,transformers, and motors. Overexcitation is also related to low frequency

2. to protect a power system, or a part of a power system, against breakdown, byshedding load, in generation deficit situations.

The under frequency START value is set in Hz. All voltage magnitude relatedsettings are made as a percentage of a global base voltage parameter. The UBasevalue should be set as a primary phase-to-phase value.

Some applications and related setting guidelines for the frequency level are givenbelow:

Equipment protection, such as for motors and generatorsThe setting has to be well below the lowest occurring "normal" frequency and wellabove the lowest acceptable frequency for the equipment.

Power system protection, by load sheddingThe setting has to be below the lowest occurring "normal" frequency and wellabove the lowest acceptable frequency for power stations, or sensitive loads. Thesetting level, the number of levels and the distance between two levels (in time and/or in frequency) depends very much on the characteristics of the power systemunder consideration. The size of the "largest loss of production" compared to "thesize of the power system" is a critical parameter. In large systems, the loadshedding can be set at a fairly high frequency level, and the time delay is normallynot critical. In smaller systems the frequency START level has to be set at a lowervalue, and the time delay must be rather short.

10.2 Overfrequency protection SAPTOF

10.2.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Overfrequency protection SAPTOF

f >

SYMBOL-O V1 EN

81

10.2.2 ApplicationOverfrequency protection function SAPTOF is applicable in all situations, wherereliable detection of high fundamental power system frequency is needed. The

Section 10 1MRK 504 134-UEN -Frequency protection

202Application Manual

Page 209: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

power system frequency, and rate of change of frequency, is a measure of theunbalance between the actual generation and the load demand. High fundamentalfrequency in a power system indicates that the available generation is too largecompared to the power demanded by the load connected to the power grid.SAPTOF detects such situations and provides an output signal, suitable forgenerator shedding, HVDC-set-point change and so on. SAPTOF is very sensitiveand accurate and can also be used to alert operators that frequency has slightlydeviated from the set-point, and that manual actions might be enough.

10.2.3 Setting guidelinesAll the frequency and voltage magnitude conditions in the system where SAPTOFperforms its functions must be considered. The same also applies to the associatedequipment, its frequency and time characteristic.

There are two specific application areas for SAPTOF:

1. to protect equipment against damage due to high frequency, such asgenerators, and motors

2. to protect a power system, or a part of a power system, against breakdown, byshedding generation, in over production situations.

The overfrequency start value is set in Hz. All voltage magnitude related settingsare made as a percentage of a settable global base voltage parameter UBase. TheUBase value should be set as a primary phase-to-phase value.

Some applications and related setting guidelines for the frequency level are givenbelow:

Equipment protection, such as for motors and generatorsThe setting has to be well above the highest occurring "normal" frequency and wellbelow the highest acceptable frequency for the equipment.

Power system protection, by generator sheddingThe setting must be above the highest occurring "normal" frequency and below thehighest acceptable frequency for power stations, or sensitive loads. The settinglevel, the number of levels and the distance between two levels (in time and/or infrequency) depend very much on the characteristics of the power system underconsideration. The size of the "largest loss of load" compared to "the size of thepower system" is a critical parameter. In large systems, the generator shedding canbe set at a fairly low frequency level, and the time delay is normally not critical. Insmaller systems the frequency START level has to be set at a higher value, and thetime delay must be rather short.

10.3 Rate-of-change frequency protection SAPFRC

1MRK 504 134-UEN - Section 10Frequency protection

203Application Manual

Page 210: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

10.3.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Rate-of-change frequency protection SAPFRC

df/dt ><

SYMBOL-N V1 EN

81

10.3.2 ApplicationRate-of-change frequency protection (SAPFRC), is applicable in all situations,where reliable detection of change of the fundamental power system voltagefrequency is needed. SAPFRC can be used both for increasing frequency and fordecreasing frequency. SAPFRC provides an output signal, suitable for loadshedding or generator shedding, generator boosting, HVDC-set-point change, gasturbine start up and so on. Very often SAPFRC is used in combination with a lowfrequency signal, especially in smaller power systems, where loss of a fairly largegenerator will require quick remedial actions to secure the power system integrity.In such situations load shedding actions are required at a rather high frequencylevel, but in combination with a large negative rate-of-change of frequency theunderfrequency protection can be used at a rather high setting.

10.3.3 Setting guidelinesThe parameters for Rate-of-change frequency protection SAPFRC are set via thelocal HMI or or through the Protection and Control Manager (PCM600).

All the frequency and voltage magnitude conditions in the system where SAPFRCperforms its functions should be considered. The same also applies to theassociated equipment, its frequency and time characteristic.

There are two specific application areas for SAPFRC:

1. to protect equipment against damage due to high or too low frequency, such asgenerators, transformers, and motors

2. to protect a power system, or a part of a power system, against breakdown byshedding load or generation, in situations where load and generation are not inbalance.

SAPFRC is normally used together with an overfrequency or underfrequencyfunction, in small power systems, where a single event can cause a large imbalancebetween load and generation. In such situations load or generation shedding has totake place very quickly, and there might not be enough time to wait until thefrequency signal has reached an abnormal value. Actions are therefore taken at afrequency level closer to the primary nominal level, if the rate-of-change frequencyis large (with respect to sign).

Section 10 1MRK 504 134-UEN -Frequency protection

204Application Manual

Page 211: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

SAPFRCSTART value is set in Hz/s. All voltage magnitude related settings aremade as a percentage of a settable base voltage, which normally is set to theprimary nominal voltage level (phase-phase) of the power system or the highvoltage equipment under consideration.

SAPFRC is not instantaneous, since the function needs some time to supply astable value. It is recommended to have a time delay long enough to take care ofsignal noise. However, the time, rate-of-change frequency and frequency stepsbetween different actions might be critical, and sometimes a rather short operationtime is required, for example, down to 70 ms.

Smaller industrial systems might experience rate-of-change frequency as large as 5Hz/s, due to a single event. Even large power systems may form small islands witha large imbalance between load and generation, when severe faults (orcombinations of faults) are cleared - up to 3 Hz/s has been experienced when asmall island was isolated from a large system. For more "normal" severedisturbances in large power systems, rate-of-change of frequency is much less,most often just a fraction of 1.0 Hz/s.

1MRK 504 134-UEN - Section 10Frequency protection

205Application Manual

Page 212: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

206

Page 213: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Section 11 Secondary system supervision

11.1 Fuse failure supervision SDDRFUF

11.1.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Fuse failure supervision SDDRFUF - -

11.1.2 ApplicationDifferent protection functions within the protection IED, operates on the basis ofthe measured voltage in the relay point. Examples are:

• impedance protection functions• undervoltage function• energizing check function and voltage check for the weak infeed logic

These functions can operate unintentionally if a fault occurs in the secondarycircuits between the voltage instrument transformers and the IED.

It is possible to use different measures to prevent such unwanted operations.Miniature circuit breakers in the voltage measuring circuits, located as close aspossible to the voltage instrument transformers, are one of them. Separate fuse-failure monitoring IEDs or elements within the protection and monitoring devicesare another possibilities. These solutions are combined to get the best possibleeffect in the fuse failure supervision function (SDDRFUF).

SDDRFUF function built into the IED products can operate on the basis of externalbinary signals from the miniature circuit breaker or from the line disconnector. Thefirst case influences the operation of all voltage-dependent functions while thesecond one does not affect the impedance measuring functions.

The negative sequence detection algorithm, based on the negative-sequencemeasuring quantities, a high value of voltage 3U2 without the presence of thenegative-sequence current 3I2, is recommended for use in isolated or high-impedance earthed networks.

The zero sequence detection algorithm, based on the zero sequence measuringquantities, a high value of voltage 3U0 without the presence of the residual current3I0, is recommended for use in directly or low impedance earthed networks. In

1MRK 504 134-UEN - Section 11Secondary system supervision

207Application Manual

Page 214: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

cases where the line can have a weak-infeed of zero sequence current this functionshall be avoided.

A criterion based on delta current and delta voltage measurements can be added tothe fuse failure supervision function in order to detect a three phase fuse failure.This is beneficial for example during three phase transformer switching.

11.1.3 Setting guidelines

11.1.3.1 General

The negative and zero sequence voltages and currents always exist due to differentnon-symmetries in the primary system and differences in the current and voltageinstrument transformers. The minimum value for the operation of the current andvoltage measuring elements must always be set with a safety margin of 10 to 20%,depending on the system operating conditions.

Pay special attention to the dissymmetry of the measuring quantities when thefunction is used on longer untransposed lines, on multicircuit lines and so on.

The settings of negative sequence, zero sequence and delta algorithm are in percentof the base voltage and base current for the function, UBase and IBaserespectively. Set UBase to the primary rated phase-phase voltage of the potentialvoltage transformer and IBase to the primary rated current of the current transformer.

11.1.3.2 Setting of common parameters

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

The settings of negative sequence, zero sequence and delta algorithm are in percentof the global base voltage and global base current for the function, UBase andIBase respectively.

The voltage threshold USealIn< is used to identify low voltage condition in thesystem. Set USealIn< below the minimum operating voltage that might occurduring emergency conditions. We propose a setting of approximately 70% of theglobal parameter UBase.

The drop off time of 200 ms for dead phase detection makes it recommended toalways set SealIn to On since this will secure a fuse failure indication at persistentfuse fail when closing the local breaker when the line is already energized from theother end. When the remote breaker closes the voltage will return except in thephase that has a persistent fuse fail. Since the local breaker is open there is nocurrent and the dead phase indication will persist in the phase with the blown fuse.When the local breaker closes the current will start to flow and the function detectsthe fuse failure situation. But due to the 200 ms drop off timer the output BLKZwill not be activated until after 200 ms. This means that distance functions are notblocked and due to the “no voltage but current” situation might issue a trip.

Section 11 1MRK 504 134-UEN -Secondary system supervision

208Application Manual

Page 215: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

The operation mode selector OpMode has been introduced for better adaptation tosystem requirements. The mode selector makes it possible to select interactionsbetween the negative sequence and zero sequence algorithm. In normalapplications the OpMode is set to either UNsINs for selecting negative sequencealgorithm or UZsIZs for zero sequence based algorithm. If system studies or fieldexperiences shows that there is a risk that the fuse failure function will not beactivated due to the system conditions, the dependability of the fuse failurefunction can be increased if the OpMode is set to UZsIZs OR UNsINs orOptimZsNs. In mode UZsIZs OR UNsINs both the negative and zero sequencebased algorithm is activated and working in an OR-condition. Also in modeOptimZsNs both the negative and zero sequence algorithm are activated and theone that has the highest magnitude of measured sequence current will operate. Ifthere is a requirement to increase the security of the fuse failure function OpModecan be selected to UZsIZs AND UNsINs, which gives that both negative and zerosequence algorithm is activated working in an AND-condition, that is, bothalgorithms must give condition for block in order to activate the output signalsBLKU or BLKZ.

11.1.3.3 Negative sequence based

The relay setting value 3U2> is given in percentage of the base voltage UBase andshould not be set lower than according to equation 111.

3 23 2 100UU

UBase³ ×

EQUATION1519 V3 EN (Equation 111)

where:

3U2 is the maximal negative sequence voltage during normal operation conditions, plus a marginof 10...20%

UBase is setting of the global base voltage for all functions in the IED.

The setting of the current limit 3I2< is in percentage of global parameter IBase.The setting of 3I2< must be higher than the normal unbalance current that mightexist in the system and can be calculated according to equation 112.

3 23 2 100=< ×II

IBaseEQUATION1520 V3 EN (Equation 112)

where:

3I2 is the maximal negative sequence current during normal operating conditions, plus a marginof 10...20%

IBase is the setting of base current for the function

1MRK 504 134-UEN - Section 11Secondary system supervision

209Application Manual

Page 216: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

11.1.3.4 Zero sequence based

The relay setting value 3U0> is given in percentage of the global parameter UBase.The setting of 3U0> should not be set lower than according to equation 113.

3 03 0 100

UU

UBase>= ×

EQUATION1521 V2 EN (Equation 113)

where:

3U0 is the maximal zero sequence voltage during normal operation conditions, plus a margin of10...20%

UBase is setting of global base voltage all functions in the IED.

The setting of the current limit 3I0< is done in percentage of the global parameterIBase. The setting of 3I0< must be higher than the normal unbalance current thatmight exist in the system. The setting can be calculated according to equation 114.

3 03 0 100= ×<II

IBaseEQUATION2293 V2 EN (Equation 114)

where:

3I0< is the maximal zero sequence current during normal operating conditions, plus a margin of10...20%

IBase is setting of global base current all functions in the IED.

11.1.3.5 Delta U and delta I

Set the operation mode selector OpDUDI to On if the delta function shall be inoperation.

The setting of DU> should be set high (approximately 60% of UBase) and thecurrent threshold DI< low (approximately 10% of IBase) to avoid unwantedoperation due to normal switching conditions in the network. The delta current anddelta voltage function shall always be used together with either the negative or zerosequence algorithm. If USetprim is the primary voltage for operation of dU/dt andISetprim the primary current for operation of dI/dt, the setting of DU> and DI<will be given according to equation 115 and equation 116.

100primDUUSetUBase

³ ×

EQUATION1523 V2 EN (Equation 115)

Section 11 1MRK 504 134-UEN -Secondary system supervision

210Application Manual

Page 217: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

100primDIISetIBase

£ ×

EQUATION1524 V3 EN (Equation 116)

The voltage thresholds UPh> is used to identify low voltage condition in thesystem. Set UPh> below the minimum operating voltage that might occur duringemergency conditions. A setting of approximately 70% of UBase is recommended.

The current threshold IPh> shall be set lower than the IMinOp for the distanceprotection function. A 5...10% lower value is recommended.

11.1.3.6 Dead line detection

The condition for operation of the dead line detection is set by the parametersIDLD< for the current threshold and UDLD< for the voltage threshold.

Set the IDLD< with a sufficient margin below the minimum expected load current.A safety margin of at least 15-20% is recommended. The operate value musthowever exceed the maximum charging current of an overhead line, when only onephase is disconnected (mutual coupling to the other phases).

Set the UDLD< with a sufficient margin below the minimum expected operatingvoltage. A safety margin of at least 15% is recommended.

11.2 Breaker close/trip circuit monitoring TCSSCBR

11.2.1 Identification

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Breaker close/trip circuit monitoring TCSSCBR - -

11.2.2 ApplicationTCSSCBR detects faults in the electrical control circuit of the circuit breaker. Thefunction can supervise both open and closed coil circuits. This kind of supervisionis necessary to find out the vitality of the control circuits continuously.

Trip circuit supervision generates a current of approximately 1.0mA through the supervised circuit. It must be ensured that thiscurrent will not cause a latch up of the controlled object.

1MRK 504 134-UEN - Section 11Secondary system supervision

211Application Manual

Page 218: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

To protect the trip circuit supervision circuits in the IED, the outputcontacts are provided with parallel transient voltage suppressors.The breakdown voltage of these suppressors is 400 +/– 20 V DC.

1

PSM

2

RsRext

(+)

(-)

HW

SW

PO1

TCS1

IS

V

IS: Constant current generator. Current level ~ 1,0 mA (Ic)V: Transient Voltage Suppressor Breakdown Voltage 380 to 400 VDC

Ic

TCSSCBRTCS_STATEBLOCK

ALARM

IEC13000025-2-en.vsd

GUID-B056E9DB-E3E5-4300-9150-45916F485CA7 V2 EN

Figure 85: Operating principle of the trip-circuit supervision with an externalresistor. The TCSSCBR blocking switch is not required since theexternal resistor is used.

If TCS is required only in a closed position, the external shunt resistance can beomitted. When the circuit breaker is in the open position, TCS sees the situation asa faulty circuit. One way to avoid TCS operation in this situation would be to blockthe supervision function whenever the circuit breaker is open.

Section 11 1MRK 504 134-UEN -Secondary system supervision

212Application Manual

Page 219: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

1

PSM

2

Rs

(+)

(-)

HW

S W

PO1

TCS1

IS

V

IS: Constant current generator. Current level ~ 1,0 mA (Ic)V: Transient Voltage Suppressor Breakdown Voltage 380 to 400 VDC

Ic

CBPOS_open

TCSSCBRTCS_STATEBLOCK

ALARM

IEC13000026-2-en.vsd

GUID-6B09F9C7-86D0-4A7A-8E08-8E37CAE53249 V3 EN

Figure 86: Operating principle of the trip-circuit supervision without anexternal resistor. The circuit breaker open indication is set to blockTCSSCBR when the circuit breaker is open.

Trip-circuit supervision and other trip contactsIt is typical that the trip circuit contains more than one trip contact in parallel, forexample in transformer feeders where the trip of a Buchholz relay is connected inparallel with the feeder terminal and other relays involved.

GUID-7264738C-F9D7-48F0-B6FC-F85FD10D5B84 V1 EN

Figure 87: Constant test current flow in parallel trip contacts and trip-circuitsupervision

1MRK 504 134-UEN - Section 11Secondary system supervision

213Application Manual

Page 220: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Several trip-circuit supervision functions parallel in circuitNot only the trip circuit often have parallel trip contacts, it is also possible that thecircuit has multiple TCS circuits in parallel. Each TCS circuit causes its ownsupervising current to flow through the monitored coil and the actual coil current isa sum of all TCS currents. This must be taken into consideration when determiningthe resistance of Rext.

Trip-circuit supervision with auxiliary relaysMany retrofit projects are carried out partially, that is, the old electromechanicalrelays are replaced with new ones but the circuit breaker is not replaced. Thiscreates a problem that the coil current of an old type circuit breaker can be too highfor the protection IED trip contact to break.

The circuit breaker coil current is normally cut by an internal contact of the circuitbreaker. In case of a circuit breaker failure, there is a risk that the protection IEDtrip contact is destroyed since the contact is obliged to disconnect high level ofelectromagnetic energy accumulated in the trip coil.

An auxiliary relay can be used between the protection IED trip contact and thecircuit breaker coil. This way the breaking capacity question is solved, but the TCScircuit in the protection IED monitors the healthy auxiliary relay coil, not thecircuit breaker coil. The separate trip circuit supervision relay is applicable for thisto supervise the trip coil of the circuit breaker.

Dimensioning of the external resistorUnder normal operating conditions, the applied external voltage is divided betweenthe relay’s internal circuit and the external trip circuit so that at the minimum 10 V(3...10 V) remains over the relay’s internal circuit. Should the external circuit’sresistance be too high or the internal circuit’s too low, for example due to weldedrelay contacts, the fault is detected.

Mathematically, the operation condition can be expressed as:

U R R I V DCc ext s c− + × ≥( ) 10

GUID-34BDFCA2-E72E-4602-9F0D-281CDDF0A93A V1 EN (Equation 117)

Uc Operating voltage over the supervised trip circuit

Ic Measuring current through the trip circuit, appr. 1.0 mA (0.85...1.20 mA)

Rext external shunt resistance

Rs trip coil resistance

If the external shunt resistance is used, it has to be calculated not to interfere withthe functionality of the supervision or the trip coil. Too high a resistance causes toohigh a voltage drop, jeopardizing the requirement of at least 20 V over the internalcircuit, while a resistance too low can enable false operations of the trip coil.

Section 11 1MRK 504 134-UEN -Secondary system supervision

214Application Manual

Page 221: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Table 19: Values recommended for the external resistor Rext

Operating voltage Uc Shunt resistor Rext

48 V DC 10 kΩ, 5 W

60 V DC 22 kΩ, 5 W

110 V DC 33 kΩ, 5 W

220 V DC 68 kΩ, 5 W

Due to the requirement that the voltage over the TCSSCBR contact must be 20V orhigher, the correct operation is not guaranteed with auxiliary operating voltageslower than 48V DC because of the voltage drop in Rext and the operating coil oreven voltage drop of the feeding auxiliary voltage system which can cause too lowvoltage values over the TCSSCBR contact. In this case, erroneous alarming can occur.

At lower (<48V DC) auxiliary circuit operating voltages, it is recommended to usethe circuit breaker position to block unintentional operation of TCSSCBR. The useof the position indication is described earlier in this chapter.

1MRK 504 134-UEN - Section 11Secondary system supervision

215Application Manual

Page 222: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

216

Page 223: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Section 12 Control

12.1 Apparatus control

12.1.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Bay control QCBAY - -

Local remote LOCREM - -

Local remote control LOCREMCTRL - -

12.1.2 ApplicationThe apparatus control is a function for control and supervising of circuit breakers,disconnectors, and earthing switches within a bay. Permission to operate is givenafter evaluation of conditions from other functions such as interlocking,synchrocheck, operator place selection and external or internal blockings.

The complete apparatus control function is not included in thisproduct, and the information below is included for understanding ofthe principle for the use of QCBAY, LOCREM, andLOCREMCTRL for the selection of the operator place.

Figure 88 gives an overview from what places the apparatus control functionreceive commands. Commands to an apparatus can be initiated from the ControlCentre (CC), the station HMI or the local HMI on the IED front.

1MRK 504 134-UEN - Section 12Control

217Application Manual

Page 224: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Station HMI

GW

cc

Station bus

breakers disconnectors earthing switchesIEC08000227.vsd

ApparatusControl

IED

I/O

Local HMI

ApparatusControl

IED

I/O

ApparatusControl

IED

I/O

Local HMI

Local HMI

IEC08000227 V1 EN

Figure 88: Overview of the apparatus control functions

Features in the apparatus control function:

• Operation of primary apparatuses• Select-Execute principle to give high security• Selection function to prevent simultaneous operation• Selection and supervision of operator place• Command supervision• Block/deblock of operation• Block/deblock of updating of position indications• Substitution of position indications• Overriding of interlocking functions• Overriding of synchrocheck• Operation counter• Suppression of Mid position

The apparatus control function is realized by means of a number of function blocksdesignated:

• Switch controller SCSWI• Circuit breaker SXCBR• Circuit switch SXSWI• Position evaluation POS_EVAL• Select release SELGGIO

Section 12 1MRK 504 134-UEN -Control

218Application Manual

Page 225: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

• Bay control QCBAY• Local remote LOCREM• Local remote control LOCREMCTRL

SCSWI, SXCBR, QCBAY and SXSWI are logical nodes according to IEC 61850.The signal flow between these function blocks appears in figure 89. The functionLogical node Interlocking (SCILO) in the figure 89 is the logical node forinterlocking.

Control operation can be performed from the local IED HMI. If the administratorhas defined users with the UMT tool, then the local/remote switch is underauthority control. If not, the default (factory) user is the SuperUser that canperform control operations from the local IED HMI without LogOn. The defaultposition of the local/remote switch is on remote.

IEC09000338-1-en.vsd

SXCBRSCSWI

SCILO

SCSWI

SCILO

SXSWI

-QA1

-QB1

-QB9

IEC 61850

QCBAY

IEC09000338 V1 EN

Figure 89: Signal flow between apparatus control function blocks

The IEC 61850 communication has always priority over binaryinputs, e.g. a block command on binary inputs will not preventcommands over IEC 61850.

1MRK 504 134-UEN - Section 12Control

219Application Manual

Page 226: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Accepted originator categories for PSTOIf the requested command is accepted due to the authority allocation control, therespective value will change. Otherwise the attribute blocked-by-switcing-hierarkyis set in the cause signal. If the PSTO value is changed under a command, then thecommand is reset.

The accepted originator categories for each PSTO value are shown in Table 20

Table 20: Accepted originator categories for each PSTO

PermittdSourceToOperate Originator

0 = Off 4,5,6

1 = Local 1,4,5,6

2 = Remote 2,3,4,5,6

3 = Faulty 4,5,6

4 = Not in use 1,2,3,4,5,6

5 = All

PSTO = All, then it is no priority between operator places. All operator places areallowed to operate at the same time.

According to IEC61850 standard the orCat attribute in originator category aredefined in Table 21

Table 21: orCat attribute according to IEC61850

Value Description

0 not-supported

1 bay-control

2 station-control

3 remote-control

4 automatic-bay

5 automatic-station

6 automatic-remote

7 maintenance

8 process

Switch controller (SCSWI)The Switch controller (SCSWI) initializes and supervises all functions to properlyselect and operate switching primary apparatuses. The Switch controller mayhandle and operate on one three-phase device.

After the selection of an apparatus and before the execution, the switch controllerperforms the following checks and actions:

Section 12 1MRK 504 134-UEN -Control

220Application Manual

Page 227: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

• A request initiates to reserve other bays to prevent simultaneous operation.• Actual position inputs for interlocking information are read and evaluated if

the operation is permitted.• The synchrocheck/synchronizing conditions are read and checked, and

performs operation upon positive response.• The blocking conditions are evaluated• The position indications are evaluated according to given command and its

requested direction (open or closed).

The command sequence is supervised regarding the time between:

• Select and execute.• Select and until the reservation is granted.• Execute and the final end position of the apparatus.• Execute and valid close conditions from the synchrocheck.

At error the command sequence is cancelled.

The mid position of apparatuses can be suppressed at SCSWI by setting thetIntermediate at (SXCBR/SXSWI) to an appropriate value.

The switch controller is not dependent on the type of switching device SXCBR orSXSWI. The switch controller represents the content of the SCSWI logical node(according to IEC 61850) with mandatory functionality.

Reservation function (SELGGIO)The purpose of the reservation function is to grant permission to operate only onedevice at a time in a group, like a bay or a station, thereby preventing double operation.

For interlocking evaluation in a substation, the position information from switchingdevices, such as circuit breakers, disconnectors and earthing switches can berequired from the same bay or from several other bays. When information isneeded from other bays, it is exchanged over the serial station bus between thedistributed IEDs. The problem that arises, even at a high speed of communication,is a time interval during which the information about the position of the switchingdevices are uncertain. The interlocking function uses this information forevaluation, which means that also the interlocking conditions will be uncertain.

To ensure that the interlocking information is correct at the time of operation, areservation method is available in the IEDs. With this reservation method thereserved signal can be used for evaluation of permission to select and operate theapparatus.

This functionality is realized over the station bus by means of the function blockSELGGIO.

The SELECTED output signal from the respective SCSWI function block in theown bay is connected to the inputs of the SELGGIO function block. The outputsignal RESERVED from SELGGIO is connected to the input RES_EXT of theSCSWI function block. If the bay is not currently reserved, the SELGGIO output

1MRK 504 134-UEN - Section 12Control

221Application Manual

Page 228: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

signal RESERVED is FALSE. Selection for operation on the SCSWI block is nowpossible. Once any SCSWI block is selected, and if its output SELECTED isconnected to the SELGGIO block, then other SCSWI functions as configured areblocked for selection. The RESERVED signal from SELGGIO is also sent to otherbay devices.

Due to the design of the plant, some apparatus might need reservation of the ownbay as well as reservations from other bays. Received reservation from other baysare handled by a logical OR together with own bay reservation from the SELGGIOfunction block that checks whether the own bay is currently reserved.

SELGGIOSELECT1SELECT2SELECT3SELECT4SELECT5SELECT6SELECT7SELECT8SELECT9SELECT10SELECT11SELECT12SELECT13SELECT14SELECT15SELECT16

RESERVED

BAY 1

BAY 2

BAY 3

RESERVED

IEC09000258-1.vsd

³1

IEC09000258 V1 EN

Figure 90: Reservations from own and other bays

The reservation can also be realized with external wiring according to theapplication example in figure 91. This solution is realized with external auxiliaryrelays and extra binary inputs and outputs in each IED.

Section 12 1MRK 504 134-UEN -Control

222Application Manual

Page 229: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

SCSWI

SELECTED

RES_EXT

IEDIED

OR

Other SCWI in the bay to SELGGIO

SELGGIO

SELECT1

+

BI BOBI BO

IEC09000259_1_en.vsd

IEC09000259 V1 EN

Figure 91: Application principles for reservation with external wiring

The solution in figure 91 can also be realized over the station bus according to theapplication example in figure 92.

SCSWI

SELECTED

RES_EXT

IEDIED

OROther SCSWI in the bay to SELGGIO

Station bus. . .

SELGGIO

SELECT1

RESGRANT

GOOSEINTLKRCV

IEC09000260_2_en.vsd

IEC09000260 V2 EN

Figure 92: Application principle for an alternative reservation solution

Bay control (QCBAY)The Bay control (QCBAY) is used to handle the selection of the operator place forthe bay. The function gives permission to operate from two types of locationseither from Remote (for example, control centre or station HMI) or from Local(local HMI on the IED) or from all (Local and Remote). The Local/Remote switchposition can also be set to Off, which means no operator place selected that is,operation is not possible neither from local nor from remote.

QCBAY also provides blocking functions that can be distributed to differentapparatuses within the bay. There are two different blocking alternatives:

1MRK 504 134-UEN - Section 12Control

223Application Manual

Page 230: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

• Blocking of update of positions• Blocking of commands

The function does not have a corresponding functionality defined in the IEC 61850standard, which means that this function is included as a vendor specific logical node.

IEC13000016-1-en.vsdIEC13000016 V1 EN

Figure 93: APC - Local remote function block

12.1.3 Interaction between modulesA typical bay with apparatus control function consists of a combination of logicalnodes or functions that are described here:

• The Switch controller (SCSWI) initializes all operations for one apparatus andperforms the actual switching and is more or less the interface to the drive ofone apparatus. It includes the position handling as well as the control of theposition.

• The Circuit breaker (SXCBR) is the process interface to the circuit breaker forthe apparatus control function.

• The Circuit switch (SXSWI) is the process interface to the disconnector or theearthing switch for the apparatus control function.

Section 12 1MRK 504 134-UEN -Control

224Application Manual

Page 231: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

• The Bay control (QCBAY) fulfils the bay-level functions for the apparatuses,such as operator place selection and blockings for the complete bay.

• The function (SELGGIO), deals with reservation of the bay.• The Four step overcurrent protection (OC4PTOC) trips the breaker.• The Protection trip logic (SMPPTRC) connects the "trip" outputs of one or

more protection functions to a common "trip" to be transmitted to SXCBR.• The Autorecloser (SMBRREC) consists of the facilities to automatically close

a tripped breaker with respect to a number of configurable conditions.• The logical node Interlocking (SCILO) provides the information to SCSWI

whether it is permitted to operate due to the switchyard topology. Theinterlocking conditions are evaluated with separate logic and connected toSCILO .

• The Synchrocheck, energizing check, and synchronizing (SESRSYN)calculates and compares the voltage phasor difference from both sides of anopen breaker with predefined switching conditions (synchrocheck). Also thecase that one side is dead (energizing-check) is included.

• The logical node Generic Automatic Process Control, GAPC, is an automaticfunction that reduces the interaction between the operator and the system.With one command, the operator can start a sequence that will end with aconnection of a process object (for example a line) to one of the possible busbars.

The overview of the interaction between these functions is shown in figure 94 below.

1MRK 504 134-UEN - Section 12Control

225Application Manual

Page 232: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

IEC09000207_1_en.vsd

OC4PTOC (Overcurrent)

SXCBR(Circuit breaker)

Interlockingfunctionblock

(Not a LN)

SCSWI(Switching control)

QCBAY(Bay control)

SMBRREC

(Auto-recloser)

I/O

Trip

Close rel.

Selected

Star

t SM

BRR

EC

Close CB

Position

Reserved

Operator placeselection

SCSWI(Switching control)

SXSWI(Disconnector)

Open cmd

Close cmd

Position

SESRSYN(Synchrocheck)

SCILO

SCILO

Synchrocheck OK

SELGGIO(Reservation) Selected

Reserved

Enable close

Enable open

Open rel.

Close rel.Open rel.

SMPPTRC(Trip logic)

Position

Enab

leop

en

Enab

lecl

ose

Pos.

from

ot

her b

ays

I/O

Open cmdClose cmd

(Interlocking)

(Interlocking)

IEC09000207 V1 EN

Figure 94: Example overview of the interactions between functions in a typicalbay

12.1.4 Setting guidelinesThe setting parameters for the apparatus control function are set via the local HMIor PCM600.

Section 12 1MRK 504 134-UEN -Control

226Application Manual

Page 233: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

12.1.4.1 Switch controller (SCSWI)

The parameter CtlModel specifies the type of control model according to IEC61850. For normal control of circuit breakers, disconnectors and earthing switchesthe control model is set to SBO Enh (Select-Before-Operate) with enhanced security.

When the operation shall be performed in one step, the model direct control withnormal security is used.

At control with enhanced security there is an additional supervision of the statusvalue by the control object, which means that each command sequence must beterminated by a termination command.

The parameter PosDependent gives permission to operate depending on theposition indication, that is, at Always permitted it is always permitted to operateindependent of the value of the position. At Not perm at 00/11 it is not permitted tooperate if the position is in bad or intermediate state.

tSelect is the maximum time between the select and the execute command signal,that is, the time the operator has to perform the command execution after theselection of the object to operate. When the time has expired, the selected outputsignal is set to false and a cause-code is given over IEC 61850.

tSynchrocheck is the allowed time for the synchrocheck function to fulfill the closeconditions. When the time has expired, the control function is reset.

The timer tSynchronizing supervises that the signal synchronizing in progress isobtained in SCSWI after start of the synchronizing function. The start signal for thesynchronizing is obtained if the synchrocheck conditions are not fulfilled. Whenthe time has expired, the control function is reset. If no synchronizing function isincluded, the time is set to 0, which means no start of the synchronizing function.

tExecutionFB is the maximum time between the execute command signal and thecommand termination. When the time has expired, the control function is reset.

12.1.4.2 Bay control (QCBAY)

If the parameter AllPSTOValid is set to No priority, all originators from local andremote are accepted without any priority.

1MRK 504 134-UEN - Section 12Control

227Application Manual

Page 234: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

12.2 Interlocking

12.2.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Logical node for interlocking SCILO - 3

Interlocking for busbar earthing switch BB_ES - 3

Interlocking for bus-section breaker A1A2_BS - 3

Interlocking for bus-sectiondisconnector

A1A2_DC - 3

Interlocking for bus-coupler bay ABC_BC - 3

Interlocking for 1 1/2 breaker diameter BH_CONN - 3

Interlocking for 1 1/2 breaker diameter BH_LINE_A - 3

Interlocking for 1 1/2 breaker diameter BH_LINE_B - 3

Interlocking for double CB bay DB_BUS_A - 3

Interlocking for double CB bay DB_BUS_B - 3

Interlocking for double CB bay DB_LINE - 3

Interlocking for line bay ABC_LINE - 3

Interlocking for transformer bay AB_TRAFO - 3

12.2.2 ApplicationThe main purpose of switchgear interlocking is:

• To avoid the dangerous or damaging operation of switchgear• To enforce restrictions on the operation of the substation for other reasons for

example, load configuration. Examples of the latter are to limit the number ofparallel transformers to a maximum of two or to ensure that energizing isalways from one side, for example, the high voltage side of a transformer.

This section only deals with the first point, and only with restrictions caused byswitching devices other than the one to be controlled. This means that switchinterlock, because of device alarms, is not included in this section.

Disconnectors and earthing switches have a limited switching capacity.Disconnectors may therefore only operate:

• With basically zero current. The circuit is open on one side and has a smallextension. The capacitive current is small (for example, < 5A) and powertransformers with inrush current are not allowed.

• To connect or disconnect a parallel circuit carrying load current. The switchingvoltage across the open contacts is thus virtually zero, thanks to the parallelcircuit (for example, < 1% of rated voltage). Paralleling of power transformersis not allowed.

Section 12 1MRK 504 134-UEN -Control

228Application Manual

Page 235: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Earthing switches are allowed to connect and disconnect earthing of isolatedpoints. Due to capacitive or inductive coupling there may be some voltage (forexample < 40% of rated voltage) before earthing and some current (for example <100A) after earthing of a line.

Circuit breakers are usually not interlocked. Closing is only interlocked againstrunning disconnectors in the same bay, and the bus-coupler opening is interlockedduring a busbar transfer.

The positions of all switching devices in a bay and from some other bays determinethe conditions for operational interlocking. Conditions from other stations areusually not available. Therefore, a line earthing switch is usually not fullyinterlocked. The operator must be convinced that the line is not energized from theother side before closing the earthing switch. As an option, a voltage indication canbe used for interlocking. Take care to avoid a dangerous enable condition at theloss of a VT secondary voltage, for example, because of a blown fuse.

The switch positions used by the operational interlocking logic are obtained fromauxiliary contacts or position sensors. For each end position (open or closed) a trueindication is needed - thus forming a double indication. The apparatus controlfunction continuously checks its consistency. If neither condition is high (1 orTRUE), the switch may be in an intermediate position, for example, moving. Thisdynamic state may continue for some time, which in the case of disconnectors maybe up to 10 seconds. Should both indications stay low for a longer period, theposition indication will be interpreted as unknown. If both indications stay high,something is wrong, and the state is again treated as unknown.

In both cases an alarm is sent to the operator. Indications from position sensorsshall be self-checked and system faults indicated by a fault signal. In theinterlocking logic, the signals are used to avoid dangerous enable or releaseconditions. When the switching state of a switching device cannot be determinedoperation is not permitted.

12.2.3 Configuration guidelinesThe following sections describe how the interlocking for a certain switchgearconfiguration can be realized in the IED by using standard interlocking modulesand their interconnections. They also describe the configuration settings. Theinputs for delivery specific conditions (Qx_EXy) are set to 1=TRUE if they are notused, except in the following cases:

• QB9_EX2 and QB9_EX4 in modules BH_LINE_A and BH_LINE_B• QA1_EX3 in module AB_TRAFO

when they are set to 0=FALSE.

12.2.4 Interlocking for busbar earthing switch BB_ES

1MRK 504 134-UEN - Section 12Control

229Application Manual

Page 236: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

12.2.4.1 Application

The interlocking for busbar earthing switch (BB_ES) function is used for onebusbar earthing switch on any busbar parts according to figure 95.

QC

en04000504.vsd

IEC04000504 V1 EN

Figure 95: Switchyard layout BB_ES

The signals from other bays connected to the module BB_ES are described below.

12.2.4.2 Signals in single breaker arrangement

The busbar earthing switch is only allowed to operate if all disconnectors of the bus-section are open.

Section 1 Section 2

A1A2_DC(BS)B1B2_DC(BS)

AB_TRAFO ABC_LINEBB_ES

ABC_LINE

(WA1)A1(WA2)B1(WA7)C C

B2A2

en04000505.vsd

BB_ESABC_BC

IEC04000505 V1 EN

Figure 96: Busbars divided by bus-section disconnectors (circuit breakers)

The interlocking functionality in 650 series cannot handle thetransfer bus (WA7)C.

To derive the signals:

Signal BB_DC_OP All disconnectors on this part of the busbar are open.

VP_BB_DC The switch status of all disconnector on this part of the busbar is valid.

EXDU_BB No transmission error from any bay containing the above information.

These signals from each line bay (ABC_LINE), each transformer bay(AB_TRAFO), and each bus-coupler bay (ABC_BC) are needed:

Section 12 1MRK 504 134-UEN -Control

230Application Manual

Page 237: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Signal QB1OPTR QB1 is open.

QB2OPTR QB2 is open (AB_TRAFO, ABC_LINE)

QB220OTR QB2 and QB20 are open (ABC_BC)

QB7OPTR QB7 is open.

VPQB1TR The switch status of QB1 is valid.

VPQB2TR The switch status of QB2 is valid.

VQB220TR The switch status of QB2and QB20 is valid.

VPQB7TR The switch status of QB7 is valid.

EXDU_BB No transmission error from the bay that contains the above information.

These signals from each bus-section disconnector bay (A1A2_DC) are also needed.For B1B2_DC, corresponding signals from busbar B are used. The same type ofmodule (A1A2_DC) is used for different busbars, that is, for both bus-sectiondisconnectors A1A2_DC and B1B2_DC.

Signal DCOPTR The bus-section disconnector is open.

VPDCTR The switch status of bus-section disconnector DC is valid.

EXDU_DC No transmission error from the bay that contains the above information.

If no bus-section disconnector exists, the signal DCOPTR, VPDCTR andEXDU_DC are set to 1 (TRUE).

If the busbar is divided by bus-section circuit breakers, the signals from the bus-section coupler bay (A1A2_BS) rather than the bus-section disconnector bay(A1A2_DC) must be used. For B1B2_BS, corresponding signals from busbar B areused. The same type of module (A1A2_BS) is used for different busbars, that is,for both bus-section circuit breakers A1A2_BS and B1B2_BS.

Signal QB1OPTR QB1 is open.

QB2OPTR QB2 is open.

VPQB1TR The switch status of QB1 is valid.

VPQB2TR The switch status of QB2 is valid.

EXDU_BS No transmission error from the bay BS (bus-section coupler bay) that contains theabove information.

For a busbar earthing switch, these conditions from the A1 busbar section are valid:

1MRK 504 134-UEN - Section 12Control

231Application Manual

Page 238: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

QB1OPTR (bay 1/sect.A1) BB_DC_OP

VP_BB_DC

EXDU_BB

en04000506.vsd

QB1OPTR (bay n/sect.A1)

. . .

. . .

. . .

VPQB1TR (bay 1/sect.A1)

VPQB1TR (bay n/sect.A1)VPDCTR (A1/A2)

EXDU_BB (bay n/sect.A1)

. . .

. . .

. . .

. . .

. . .

. . .

&

&

&

DCOPTR (A1/A2)

EXDU_BB (bay 1/sect.A1)

EXDU_DC (A1/A2)

IEC04000506 V1 EN

Figure 97: Signals from any bays in section A1 to a busbar earthing switch inthe same section

For a busbar earthing switch, these conditions from the A2 busbar section are valid:

QB1OPTR (bay 1/sect.A2) BB_DC_OP

VP_BB_DC

EXDU_BB

en04000507.vsd

QB1OPTR (bay n/sect.A2)

. . .

. . .

. . .

VPQB1TR (bay 1/sect.A2)

VPQB1TR (bay n/sect.A2)VPDCTR (A1/A2)

EXDU_BB (bay n/sect.A2)

. . .

. . .

. . .

. . .

. . .

. . .

&

&

&

DCOPTR (A1/A2)

EXDU_BB (bay 1/sect.A2)

EXDU_DC (A1/A2)IEC04000507 V1 EN

Figure 98: Signals from any bays in section A2 to a busbar earthing switch inthe same section

For a busbar earthing switch, these conditions from the B1 busbar section are valid:

Section 12 1MRK 504 134-UEN -Control

232Application Manual

Page 239: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

QB2OPTR(QB220OTR)(bay 1/sect.B1) BB_DC_OP

VP_BB_DC

EXDU_BB

en04000508.vsd

QB2OPTR (QB220OTR)(bay n/sect.B1)

. . .

. . .

. . .

VPQB2TR(VQB220TR) (bay 1/sect.B1)

VPQB2TR(VQB220TR) (bay n/sect.B1)VPDCTR (B1/B2)

EXDU_BB (bay n/sect.B1)

. . .

. . .

. . .

. . .

. . .

. . .

&

&

&

DCOPTR (B1/B2)

EXDU_BB (bay 1/sect.B1)

EXDU_DC (B1/B2)IEC04000508 V1 EN

Figure 99: Signals from any bays in section B1 to a busbar earthing switch inthe same section

For a busbar earthing switch, these conditions from the B2 busbar section are valid:

QB2OPTR(QB220OTR) (bay 1/sect.B2) BB_DC_OP

VP_BB_DC

EXDU_BB

en04000509.vsd

QB2OPTR(QB220OTR) (bay n/sect.B2)

. . .

. . .

. . .

VPQB2TR(VQB220TR) (bay 1/sect.B2)

VPQB2TR(VQB220TR) (bay n/sect.B2)VPDCTR (B1/B2)

EXDU_BB (bay n/sect.B2)

. . .

. . .

. . .

. . .

. . .

. . .

&

&

&

DCOPTR (B1/B2)

EXDU_BB (bay 1/sect.B2)

EXDU_DC (B1/B2)IEC04000509 V1 EN

Figure 100: Signals from any bays in section B2 to a busbar earthing switch inthe same section

For a busbar earthing switch on bypass busbar C, these conditions are valid:

1MRK 504 134-UEN - Section 12Control

233Application Manual

Page 240: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

QB7OPTR (bay 1) BB_DC_OP

VP_BB_DC

EXDU_BB

en04000510.vsd

&

&

&

QB7OPTR (bay n)

. . .

. . .

. . .

VPQB7TR (bay 1)

VPQB7TR (bay n)

EXDU_BB (bay 1)

EXDU_BB (bay n)

. . .

. . .

. . .

. . .

. . .

. . .

IEC04000510 V1 EN

Figure 101: Signals from bypass busbar to busbar earthing switch

12.2.4.3 Signals in double-breaker arrangement

The busbar earthing switch is only allowed to operate if all disconnectors of the bussection are open.

Section 1 Section 2

A1A2_DC(BS)B1B2_DC(BS) BB_ESBB_ES

DB_BUS

(WA1)A1(WA2)B1 B2

A2

en04000511.vsd

DB_BUS

IEC04000511 V1 EN

Figure 102: Busbars divided by bus-section disconnectors (circuit breakers)

To derive the signals:

Signal BB_DC_OP All disconnectors of this part of the busbar are open.

VP_BB_DC The switch status of all disconnectors on this part of the busbar are valid.

EXDU_BB No transmission error from any bay that contains the above information.

These signals from each double-breaker bay (DB_BUS) are needed:

Signal QB1OPTR QB1 is open.

QB2OPTR QB2 is open.

VPQB1TR The switch status of QB1 is valid.

VPQB2TR The switch status of QB2 is valid.

EXDU_DB No transmission error from the bay that contains the above information.

Section 12 1MRK 504 134-UEN -Control

234Application Manual

Page 241: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

These signals from each bus-section disconnector bay (A1A2_DC) are also needed.For B1B2_DC, corresponding signals from busbar B are used. The same type ofmodule (A1A2_DC) is used for different busbars, that is, for both bus-sectiondisconnectors A1A2_DC and B1B2_DC.

Signal DCOPTR The bus-section disconnector is open.

VPDCTR The switch status of bus-section disconnector DC is valid.

EXDU_DC No transmission error from the bay that contains the above information.

The logic is identical to the double busbar configuration described in section“Signals in single breaker arrangement”.

12.2.4.4 Signals in 1 1/2 breaker arrangement

The busbar earthing switch is only allowed to operate if all disconnectors of the bus-section are open.

Section 1 Section 2

A1A2_DC(BS)B1B2_DC(BS) BB_ESBB_ES

BH_LINE

(WA1)A1(WA2)B1 B2

A2

en04000512.vsdBH_LINE

IEC04000512 V1 EN

Figure 103: Busbars divided by bus-section disconnectors (circuit breakers)

The project-specific logic are the same as for the logic for the double busbarconfiguration described in section “Signals in single breaker arrangement”.

Signal BB_DC_OP All disconnectors on this part of the busbar are open.

VP_BB_DC The switch status of all disconnectors on this part of the busbar is valid.

EXDU_BB No transmission error from any bay that contains the above information.

12.2.5 Interlocking for bus-section breaker A1A2_BS

12.2.5.1 Application

The interlocking for bus-section breaker (A1A2_BS) function is used for one bus-section circuit breaker between section 1 and 2 according to figure 104. Thefunction can be used for different busbars, which includes a bus-section circuitbreaker.

1MRK 504 134-UEN - Section 12Control

235Application Manual

Page 242: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

QA1

WA1 (A1)

QB2

QC4

QB1

QC3

WA2 (A2)

en04000516.vsd

QC2QC1

A1A2_BSIEC04000516 V1 EN

Figure 104: Switchyard layout A1A2_BS

The signals from other bays connected to the module A1A2_BS are described below.

12.2.5.2 Signals from all feeders

If the busbar is divided by bus-section circuit breakers into bus-sections and bothcircuit breakers are closed, the opening of the circuit breaker must be blocked if abus-coupler connection exists between busbars on one bus-section side and if onthe other bus-section side a busbar transfer is in progress:

Section 1 Section 2

A1A2_BSB1B2_BS

ABC_LINEABC_BC

ABC_LINEABC_BC

(WA1)A1(WA2)B1(WA7)C C

B2A2

en04000489.vsd

AB_TRAFOAB_TRAFO

IEC04000489 V1 EN

Figure 105: Busbars divided by bus-section circuit breakers

The interlocking functionality in 650 series can not handle thetransfer bus (WA7)C.

To derive the signals:

Signal BBTR_OP No busbar transfer is in progress concerning this bus-section.

VP_BBTR The switch status of BBTR is valid.

EXDU_12 No transmission error from any bay connected to busbar 1(A) and 2(B).

Section 12 1MRK 504 134-UEN -Control

236Application Manual

Page 243: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

These signals from each line bay (ABC_LINE), each transformer bay(AB_TRAFO), and bus-coupler bay (ABC_BC) are needed:

Signal QB12OPTR QB1 or QB2 or both are open.

VPQB12TR The switch status of QB1 and QB2 are valid.

EXDU_12 No transmission error from the bay that contains the above information.

These signals from each bus-coupler bay (ABC_BC) are needed:

Signal BC12OPTR No bus-coupler connection through the own bus-coupler between busbar WA1 and

WA2.

VPBC12TR The switch status of BC_12 is valid.

EXDU_BC No transmission error from the bay that contains the above information.

These signals from the bus-section circuit breaker bay (A1A2_BS, B1B2_BS) areneeded.

Signal S1S2OPTR No bus-section coupler connection between bus-sections 1 and 2.

VPS1S2TR The switch status of bus-section coupler BS is valid.

EXDU_BS No transmission error from the bay that contains the above information.

For a bus-section circuit breaker between A1 and A2 section busbars, theseconditions are valid:

1MRK 504 134-UEN - Section 12Control

237Application Manual

Page 244: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

S1S2OPTR (B1B2)BC12OPTR (sect.1)

QB12OPTR (bay 1/sect.2)

QB12OPTR (bay n/sect.2)

S1S2OPTR (B1B2)BC12OPTR (sect.2)

QB12OPTR (bay 1/sect.1)

QB12OPTR (bay n /sect.1)

BBTR_OP

VP_BBTR

EXDU_12

en04000490.vsd

>1&

>1&

. . .

. . .

. . .

. . .

&

&

VPS1S2TR (B1B2)VPBC12TR (sect.1)

VPQB12TR (bay 1/sect.2)

VPQB12TR (bay n/sect.1). . .. . .

VPBC12TR (sect.2)VPQB12TR (bay 1/sect.1)

VPQB12TR (bay n/sect.1)

. . .

. . .

&

EXDU_12 (bay 1/sect.2)

EXDU_12 (bay n /sect.2)

EXDU_12(bay 1/sect.1)

EXDU_12 (bay n /sect.1)

EXDU_BS (B1B2)EXDU_BC (sect.1)

EXDU_BC (sect.2)

. . .

. . .

. . .

. . .

IEC04000490 V1 EN

Figure 106: Signals from any bays for a bus-section circuit breaker betweensections A1 and A2

For a bus-section circuit breaker between B1 and B2 section busbars, theseconditions are valid:

Section 12 1MRK 504 134-UEN -Control

238Application Manual

Page 245: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

S1S2OPTR (A1A2)BC12OPTR (sect.1)

QB12OPTR (bay 1/sect.2)

QB12OPTR (bay n/sect.2)

S1S2OPTR (A1A2)BC12OPTR (sect.2)

QB12OPTR (bay 1/sect.1)

QB12OPTR (bay n /sect.1)

BBTR_OP

VP_BBTR

EXDU_12

en04000491.vsd

>1&

>1&

. . .

. . .

. . .

. . .

&

&

VPS1S2TR (A1A2)VPBC12TR (sect.1)

VPQB12TR (bay 1/sect.2)

VPQB12TR (bay n/sect.1). . .. . .

VPBC12TR (sect.2)VPQB12TR (bay 1/sect.1)

VPQB12TR (bay n/sect.1)

. . .

. . .

&

EXDU_12(bay 1/sect.2)

EXDU_12 (bay n /sect.2)

EXDU_12 (bay 1/sect.1)

EXDU_12 (bay n /sect.1)

EXDU_BS (A1A2)EXDU_BC (sect.1)

EXDU_BC (sect.2)

. . .

. . .

. . .

. . .

IEC04000491 V1 EN

Figure 107: Signals from any bays for a bus-section circuit breaker betweensections B1 and B2

12.2.5.3 Configuration setting

If there is no other busbar via the busbar loops that are possible, then either theinterlocking for the QA1 open circuit breaker is not used or the state for BBTR isset to open. That is, no busbar transfer is in progress in this bus-section:

• BBTR_OP = 1• VP_BBTR = 1

1MRK 504 134-UEN - Section 12Control

239Application Manual

Page 246: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

12.2.6 Interlocking for bus-section disconnector A1A2_DC

12.2.6.1 Application

The interlocking for bus-section disconnector (A1A2_DC) function is used for onebus-section disconnector between section 1 and 2 according to figure 108.A1A2_DC function can be used for different busbars, which includes a bus-sectiondisconnector.

WA1 (A1) WA2 (A2)

QB

QC1 QC2

A1A2_DC en04000492.vsd

IEC04000492 V1 EN

Figure 108: Switchyard layout A1A2_DC

The signals from other bays connected to the module A1A2_DC are described below.

12.2.6.2 Signals in single breaker arrangement

If the busbar is divided by bus-section disconnectors, the condition no otherdisconnector connected to the bus-section must be made by a project-specific logic.

The same type of module (A1A2_DC) is used for different busbars, that is, for bothbus-section disconnector A1A2_DC and B1B2_DC. But for B1B2_DC,corresponding signals from busbar B are used.

Section 1 Section 2

A1A2_DC(BS)B1B2_DC(BS)

ABC_LINEABC_BC

ABC_LINE

(WA1)A1(WA2)B1(WA7)C C

B3A3

en04000493.vsd

AB_TRAFOAB_TRAFO

A2B2

IEC04000493 V1 EN

Figure 109: Busbars divided by bus-section disconnectors (circuit breakers)

The interlocking functionality in 650 series can not handle thetransfer bus (WA7)C.

Section 12 1MRK 504 134-UEN -Control

240Application Manual

Page 247: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

To derive the signals:

Signal S1DC_OP All disconnectors on bus-section 1 are open.

S2DC_OP All disconnectors on bus-section 2 are open.

VPS1_DC The switch status of disconnectors on bus-section 1 is valid.

VPS2_DC The switch status of disconnectors on bus-section 2 is valid.

EXDU_BB No transmission error from any bay that contains the above information.

These signals from each line bay (ABC_LINE), each transformer bay(AB_TRAFO), and each bus-coupler bay (ABC_BC) are needed:

Signal QB1OPTR QB1 is open.

QB2OPTR QB2 is open (AB_TRAFO, ABC_LINE).

QB220OTR QB2 and QB20 are open (ABC_BC).

VPQB1TR The switch status of QB1 is valid.

VPQB2TR The switch status of QB2 is valid.

VQB220TR The switch status of QB2 and QB20 are valid.

EXDU_BB No transmission error from the bay that contains the above information.

If there is an additional bus-section disconnector, the signal from the bus-sectiondisconnector bay (A1A2_DC) must be used:

Signal DCOPTR The bus-section disconnector is open.

VPDCTR The switch status of bus-section disconnector DC is valid.

EXDU_DC No transmission error from the bay that contains the above information.

If there is an additional bus-section circuit breaker rather than an additional bus-section disconnector the signals from the bus-section, circuit-breaker bay(A1A2_BS) rather than the bus-section disconnector bay (A1A2_DC) must be used:

Signal QB1OPTR QB1 is open.

QB2OPTR QB2 is open.

VPQB1TR The switch status of QB1 is valid.

VPQB2TR The switch status of QB2 is valid.

EXDU_BS No transmission error from the bay BS (bus-section coupler bay) that contains theabove information.

For a bus-section disconnector, these conditions from the A1 busbar section are valid:

1MRK 504 134-UEN - Section 12Control

241Application Manual

Page 248: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

QB1OPTR (bay 1/sect.A1) S1DC_OP

VPS1_DC

EXDU_BB

en04000494.vsd

&

&

&

QB1OPTR (bay n/sect.A1)

. . .

. . .

. . .

VPQB1TR (bay 1/sect.A1)

VPQB1TR (bay n/sect.A1)

EXDU_BB (bay 1/sect.A1)

EXDU_BB (bay n/sect.A1)

. . .

. . .

. . .

. . .

. . .

. . .

IEC04000494 V1 EN

Figure 110: Signals from any bays in section A1 to a bus-section disconnector

For a bus-section disconnector, these conditions from the A2 busbar section are valid:

QB1OPTR (bay 1/sect.A2) S2DC_OP

VPS2_DC

EXDU_BB

en04000495.vsd

QB1OPTR (bay n/sect.A2)

. . .

. . .

. . .

VPQB1TR (bay 1/sect.A2)

VPQB1TR (bay n/sect.A2)VPDCTR (A2/A3)

EXDU_BB (bay n/sect.A2)

. . .

. . .

. . .

. . .

. . .

. . .

&

&

&

DCOPTR (A2/A3)

EXDU_BB (bay 1/sect.A2)

EXDU_DC (A2/A3)IEC04000495 V1 EN

Figure 111: Signals from any bays in section A2 to a bus-section disconnector

For a bus-section disconnector, these conditions from the B1 busbar section are valid:

Section 12 1MRK 504 134-UEN -Control

242Application Manual

Page 249: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

QB2OPTR (QB220OTR)(bay 1/sect.B1) S1DC_OP

VPS1_DC

EXDU_BB

en04000496.vsd

QB2OPTR (QB220OTR)(bay n/sect.B1)

. . .

. . .

. . .

VPQB2TR (VQB220TR)(bay 1/sect.B1)

VPQB2TR (VQB220TR)(bay n/sect.B1)

EXDU_BB (bay 1/sect.B1)

EXDU_BB (bay n/sect.B1)

. . .

. . .

. . .

. . .

. . .

. . .

&

&

&

IEC04000496 V1 EN

Figure 112: Signals from any bays in section B1 to a bus-section disconnector

For a bus-section disconnector, these conditions from the B2 busbar section are valid:

QB2OPTR (QB220OTR)(bay 1/sect.B2) S2DC_OP

VPS2_DC

EXDU_BB

en04000497.vsd

QB2OPTR (QB220OTR)(bay n/sect.B2)

. . .

. . .

. . .

VPQB2TR(VQB220TR) (bay 1/sect.B2)

VPQB2TR(VQB220TR) (bay n/sect.B2)VPDCTR (B2/B3)

EXDU_BB (bay n/sect.B2)

. . .

. . .

. . .

. . .

. . .

. . .

&

&

&

DCOPTR (B2/B3)

EXDU_BB (bay 1/sect.B2)

EXDU_DC (B2/B3)IEC04000497 V1 EN

Figure 113: Signals from any bays in section B2 to a bus-section disconnector

12.2.6.3 Signals in double-breaker arrangement

If the busbar is divided by bus-section disconnectors, the condition for the busbardisconnector bay no other disconnector connected to the bus-section must be madeby a project-specific logic.

The same type of module (A1A2_DC) is used for different busbars, that is, for bothbus-section disconnector A1A2_DC and B1B2_DC. But for B1B2_DC,corresponding signals from busbar B are used.

1MRK 504 134-UEN - Section 12Control

243Application Manual

Page 250: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Section 1 Section 2

A1A2_DC(BS)B1B2_DC(BS)

DB_BUS DB_BUSDB_BUS DB_BUS

(WA1)A1(WA2)B1 B2

A2

en04000498.vsd

IEC04000498 V1 EN

Figure 114: Busbars divided by bus-section disconnectors (circuit breakers)

To derive the signals:

Signal S1DC_OP All disconnectors on bus-section 1 are open.

S2DC_OP All disconnectors on bus-section 2 are open.

VPS1_DC The switch status of all disconnectors on bus-section 1 is valid.

VPS2_DC The switch status of all disconnectors on bus-section 2 is valid.

EXDU_BB No transmission error from double-breaker bay (DB) that contains the aboveinformation.

These signals from each double-breaker bay (DB_BUS) are needed:

Signal QB1OPTR QB1 is open.

QB2OPTR QB2 is open.

VPQB1TR The switch status of QB1 is valid.

VPQB2TR The switch status of QB2 is valid.

EXDU_DB No transmission error from the bay that contains the above information.

The logic is identical to the double busbar configuration “Signals in single breakerarrangement”.

For a bus-section disconnector, these conditions from the A1 busbar section are valid:

Section 12 1MRK 504 134-UEN -Control

244Application Manual

Page 251: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

QB1OPTR (bay 1/sect.A1) S1DC_OP

VPS1_DC

EXDU_BB

en04000499.vsd

&

&

&

QB1OPTR (bay n/sect.A1)

. . .

. . .

. . .

VPQB1TR (bay 1/sect.A1)

VPQB1TR (bay n/sect.A1)

EXDU_DB (bay 1/sect.A1)

EXDU_DB (bay n/sect.A1)

. . .

. . .

. . .

. . .

. . .

. . .

IEC04000499 V1 EN

Figure 115: Signals from double-breaker bays in section A1 to a bus-sectiondisconnector

For a bus-section disconnector, these conditions from the A2 busbar section are valid:

QB1OPTR (bay 1/sect.A2) S2DC_OP

VPS2_DC

EXDU_BB

en04000500.vsd

&

&

&

QB1OPTR (bay n/sect.A2)

. . .

. . .

. . .

VPQB1TR (bay 1/sect.A2)

VPQB1TR (bay n/sect.A2)

EXDU_DB (bay 1/sect.A2)

EXDU_DB (bay n/sect.A2)

. . .

. . .

. . .

. . .

. . .

. . .

IEC04000500 V1 EN

Figure 116: Signals from double-breaker bays in section A2 to a bus-sectiondisconnector

For a bus-section disconnector, these conditions from the B1 busbar section are valid:

1MRK 504 134-UEN - Section 12Control

245Application Manual

Page 252: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

QB2OPTR (bay 1/sect.B1) S1DC_OP

VPS1_DC

EXDU_BB

en04000501.vsd

&

&

&

QB2OPTR (bay n/sect.B1)

. . .

. . .

. . .

VPQB2TR (bay 1/sect.B1)

VPQB2TR (bay n/sect.B1)

EXDU_DB (bay 1/sect.B1)

EXDU_DB (bay n/sect.B1)

. . .

. . .

. . .

. . .

. . .

. . .

IEC04000501 V1 EN

Figure 117: Signals from double-breaker bays in section B1 to a bus-sectiondisconnector

For a bus-section disconnector, these conditions from the B2 busbar section are valid:

QB2OPTR (bay 1/sect.B2) S2DC_OP

VPS2_DC

EXDU_BB

en04000502.vsd

&

&

&

QB2OPTR (bay n/sect.B2)

. . .

. . .

. . .

VPQB2TR (bay 1/sect.B2)

VPQB2TR (bay n/sect.B2)

EXDU_DB (bay 1/sect.B2)

EXDU_DB (bay n/sect.B2)

. . .

. . .

. . .

. . .

. . .

. . .

IEC04000502 V1 EN

Figure 118: Signals from double-breaker bays in section B2 to a bus-sectiondisconnector

12.2.6.4 Signals in 1 1/2 breaker arrangement

If the busbar is divided by bus-section disconnectors, the condition for the busbardisconnector bay no other disconnector connected to the bus-section must be madeby a project-specific logic.

The same type of module (A1A2_DC) is used for different busbars, that is, for bothbus-section disconnector A1A2_DC and B1B2_DC. But for B1B2_DC,corresponding signals from busbar B are used.

Section 12 1MRK 504 134-UEN -Control

246Application Manual

Page 253: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Section 1 Section 2

A1A2_DC(BS)B1B2_DC(BS)

BH_LINE

(WA1)A1(WA2)B1 B2

A2

en04000503.vsd

BH_LINE BH_LINE BH_LINE

IEC04000503 V1 EN

Figure 119: Busbars divided by bus-section disconnectors (circuit breakers)

The project-specific logic is the same as for the logic for the double-breakerconfiguration.

Signal S1DC_OP All disconnectors on bus-section 1 are open.

S2DC_OP All disconnectors on bus-section 2 are open.

VPS1_DC The switch status of disconnectors on bus-section 1 is valid.

VPS2_DC The switch status of disconnectors on bus-section 2 is valid.

EXDU_BB No transmission error from breaker and a half (BH) that contains the aboveinformation.

12.2.7 Interlocking for bus-coupler bay ABC_BC

12.2.7.1 Application

The interlocking for bus-coupler bay (ABC_BC) function is used for a bus-couplerbay connected to a double busbar arrangement according to figure 120. Thefunction can also be used for a single busbar arrangement with transfer busbar ordouble busbar arrangement without transfer busbar.

1MRK 504 134-UEN - Section 12Control

247Application Manual

Page 254: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

QB1 QB2

QC1

QA1

WA1 (A)

WA2 (B)

WA7 (C)

QB7QB20

QC2

en04000514.vsdIEC04000514 V1 EN

Figure 120: Switchyard layout ABC_BC

The interlocking functionality in 650 series can not handle thetransfer bus (WA7)C.

12.2.7.2 Configuration

The signals from the other bays connected to the bus-coupler module ABC_BC aredescribed below.

12.2.7.3 Signals from all feeders

To derive the signals:

Signal BBTR_OP No busbar transfer is in progress concerning this bus-coupler.

VP_BBTR The switch status is valid for all apparatuses involved in the busbar transfer.

EXDU_12 No transmission error from any bay connected to the WA1/WA2 busbars.

These signals from each line bay (ABC_LINE), each transformer bay(AB_TRAFO), and bus-coupler bay (ABC_BC), except the own bus-coupler bayare needed:

Signal QQB12OPTR QB1 or QB2 or both are open.

VPQB12TR The switch status of QB1 and QB2 are valid.

EXDU_12 No transmission error from the bay that contains the above information.

Section 12 1MRK 504 134-UEN -Control

248Application Manual

Page 255: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

For bus-coupler bay n, these conditions are valid:

QB12OPTR (bay 1)QB12OPTR (bay 2)

. . .

. . .QB12OPTR (bay n-1)

& BBTR_OP

VPQB12TR (bay 1)VPQB12TR (bay 2)

. . .

. . .VPQB12TR (bay n-1)

& VP_BBTR

EXDU_12 (bay 1)EXDU_12 (bay 2)

. . .

. . .EXDU_12 (bay n-1)

& EXDU_12

en04000481.vsd

IEC04000481 V1 EN

Figure 121: Signals from any bays in bus-coupler bay n

If the busbar is divided by bus-section disconnectors into bus-sections, the signalsBBTR are connected in parallel - if both bus-section disconnectors are closed. Sofor the basic project-specific logic for BBTR above, add this logic:

Section 1 Section 2

A1A2_DC(BS)B1B2_DC(BS)

ABC_LINEABC_BC

ABC_LINE ABC_BC

(WA1)A1(WA2)B1(WA7)C C

B2A2

en04000482.vsd

AB_TRAFO

IEC04000482 V1 EN

Figure 122: Busbars divided by bus-section disconnectors (circuit breakers)

The interlocking functionality in 650 series cannot handle thetransfer bus (WA7)C.

The following signals from each bus-section disconnector bay (A1A2_DC) areneeded. For B1B2_DC, corresponding signals from busbar B are used. The sametype of module (A1A2_DC) is used for different busbars, that is, for both bus-section disconnector A1A2_DC and B1B2_DC.

Signal DCOPTR The bus-section disconnector is open.

VPDCTR The switch status of bus-section disconnector DC is valid.

EXDU_DC No transmission error from the bay that contains the above information.

1MRK 504 134-UEN - Section 12Control

249Application Manual

Page 256: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

If the busbar is divided by bus-section circuit breakers, the signals from the bus-section coupler bay (A1A2_BS), rather than the bus-section disconnector bay(A1A2_DC), have to be used. For B1B2_BS, corresponding signals from busbar Bare used. The same type of module (A1A2_BS) is used for different busbars, thatis, for both bus-section circuit breakers A1A2_BS and B1B2_BS.

Signal S1S2OPTR No bus-section coupler connection between bus-sections 1 and 2.

VPS1S2TR The switch status of bus-section coupler BS is valid.

EXDU_BS No transmission error from the bay that contains the above information.

For a bus-coupler bay in section 1, these conditions are valid:

BBTR_OP (sect.1)

DCOPTR (A1A2)DCOPTR (B1B2)

BBTR_OP (sect.2)

&VP_BBTR (sect.1)

VPDCTR (A1A2)VPDCTR (B1B2)

VP_BBTR (sect.2)

EXDU_12 (sect.1)

EXDU_DC (B1B2)EXDU_12 (sect.2)

VP_BBTR

EXDU_12

en04000483.vsd

&EXDU_DC (A1A2)

BBTR_OP

>1&

IEC04000483 V1 EN

Figure 123: Signals to a bus-coupler bay in section 1 from any bays in eachsection

For a bus-coupler bay in section 2, the same conditions as above are valid bychanging section 1 to section 2 and vice versa.

12.2.7.4 Signals from bus-coupler

If the busbar is divided by bus-section disconnectors into bus-sections, the signalsBC_12 from the busbar coupler of the other busbar section must be transmitted tothe own busbar coupler if both disconnectors are closed.

Section 12 1MRK 504 134-UEN -Control

250Application Manual

Page 257: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Section 1 Section 2

A1A2_DC(BS)B1B2_DC(BS)

ABC_BCABC_BC

(WA1)A1(WA2)B1(WA7)C C

B2A2

en04000484.vsd

IEC04000484 V1 EN

Figure 124: Busbars divided by bus-section disconnectors (circuit breakers)

The interlocking functionality in 650 series can not handle thetransfer bus (WA7)C.

To derive the signals:

Signal BC_12_CL Another bus-coupler connection exists between busbar WA1 and WA2.

VP_BC_12 The switch status of BC_12 is valid.

EXDU_BC No transmission error from any bus-coupler bay (BC).

These signals from each bus-coupler bay (ABC_BC), except the own bay, are needed:

Signal BC12CLTR A bus-coupler connection through the own bus-coupler exists between busbar WA1

and WA2.

VPBC12TR The switch status of BC_12 is valid.

EXDU_BC No transmission error from the bay that contains the above information.

These signals from each bus-section disconnector bay (A1A2_DC) are also needed.For B1B2_DC, corresponding signals from busbar B are used. The same type ofmodule (A1A2_DC) is used for different busbars, that is, for both bus-sectiondisconnector A1A2_DC and B1B2_DC.

Signal DCCLTR The bus-section disconnector is closed.

VPDCTR The switch status of bus-section disconnector DC is valid.

EXDU_DC No transmission error from the bay that contains the above information.

If the busbar is divided by bus-section circuit breakers, the signals from the bus-section coupler bay (A1A2_BS), rather than the bus-section disconnector bay(A1A2_DC), must be used. For B1B2_BS, corresponding signals from busbar Bare used. The same type of module (A1A2_BS) is used for different busbars, thatis, for both bus-section circuit breakers A1A2_BS and B1B2_BS.

1MRK 504 134-UEN - Section 12Control

251Application Manual

Page 258: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Signal S1S2CLTR A bus-section coupler connection exists between bus sections 1 and 2.

VPS1S2TR The switch status of bus-section coupler BS is valid.

EXDU_BS No transmission error from the bay containing the above information.

For a bus-coupler bay in section 1, these conditions are valid:

DCCLTR (A1A2)DCCLTR (B1B2)

BC12CLTR (sect.2)

VPDCTR (A1A2)VPDCTR (B1B2)

VPBC12TR (sect.2)

EXDU_DC (A1A2)EXDU_DC (B1B2)EXDU_BC (sect.2)

& BC_12_CL

VP_BC_12

EXDU_BC

en04000485.vsd

&

&

IEC04000485 V1 EN

Figure 125: Signals to a bus-coupler bay in section 1 from a bus-coupler bay inanother section

For a bus-coupler bay in section 2, the same conditions as above are valid bychanging section 1 to section 2 and vice versa.

12.2.7.5 Configuration setting

If there is no bypass busbar and therefore no QB2 and QB7 disconnectors, then theinterlocking for QB2 and QB7 is not used. The states for QB2, QB7, QC71 are setto open by setting the appropriate module inputs as follows. In the functional blockdiagram, 0 and 1 are designated 0=FALSE and 1=TRUE:

• QB2_OP = 1• QB2_CL = 0

• QB7_OP = 1• QB7_CL = 0

• QC71_OP = 1• QC71_CL = 0

If there is no second busbar B and therefore no QB2 and QB20 disconnectors, thenthe interlocking for QB2 and QB20 are not used. The states for QB2, QB20, QC21,BC_12, BBTR are set to open by setting the appropriate module inputs as follows.In the functional block diagram, 0 and 1 are designated 0=FALSE and 1=TRUE:

Section 12 1MRK 504 134-UEN -Control

252Application Manual

Page 259: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

• QB2_OP = 1• QB2_CL = 0

• QB20_OP = 1• QB20_CL = 0

• QC21_OP = 1• QC21_CL = 0

• BC_12_CL = 0• VP_BC_12 = 1

• BBTR_OP = 1• VP_BBTR = 1

12.2.8 Interlocking for 1 1/2 CB BH

12.2.8.1 Application

The interlocking for 1 1/2 breaker diameter (BH_CONN, BH_LINE_A,BH_LINE_B) functions are used for lines connected to a 1 1/2 breaker diameteraccording to figure 126.

1MRK 504 134-UEN - Section 12Control

253Application Manual

Page 260: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

WA1 (A)

WA2 (B)

QB1QC1

QA1

QC2

QC9

QB6

QB9

QB2QC1

QA1

QC2

QC3

QB6

QC3

QB62QB61 QA1

QC1 QC2QC9

QB9

BH_LINE_A BH_LINE_B

BH_CONNen04000513.vsd

IEC04000513 V1 EN

Figure 126: Switchyard layout 1 1/2 breaker

Three types of interlocking modules per diameter are defined. BH_LINE_A andBH_LINE_B are the connections from a line to a busbar. BH_CONN is theconnection between the two lines of the diameter in the 1 1/2 breaker switchyardlayout.

For a 1 1/2 breaker arrangement, the modules BH_LINE_A, BH_CONN andBH_LINE_B must be used.

12.2.8.2 Configuration setting

For application without QB9 and QC9, just set the appropriate inputs to open stateand disregard the outputs. In the functional block diagram, 0 and 1 are designated0=FALSE and 1=TRUE:

• QB9_OP = 1• QB9_CL = 0

• QC9_OP = 1• QC9_CL = 0

If, in this case, line voltage supervision is added, then rather than setting QB9 toopen state, specify the state of the voltage supervision:

Section 12 1MRK 504 134-UEN -Control

254Application Manual

Page 261: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

• QB9_OP = VOLT_OFF• QB9_CL = VOLT_ON

If there is no voltage supervision, then set the corresponding inputs as follows:

• VOLT_OFF = 1• VOLT_ON = 0

12.2.9 Interlocking for double CB bay DB

12.2.9.1 Application

The interlocking for a double busbar double circuit breaker bay includingDB_BUS_A, DB_BUS_B and DB_LINE functions are used for a line connected toa double busbar arrangement according to figure 127.

WA1 (A)

WA2 (B)

QB1QC1

QA1

QC2

QC9

QB61

QB9

QB2QC4

QA2

QC5

QC3

QB62

DB_BUS_B

DB_LINE

DB_BUS_A

en04000518.vsdIEC04000518 V1 EN

Figure 127: Switchyard layout double circuit breaker

Three types of interlocking modules per double circuit breaker bay are defined.DB_BUS_A handles the circuit breaker QA1 that is connected to busbar WA1 andthe disconnectors and earthing switches of this section. DB_BUS_B handles thecircuit breaker QA2 that is connected to busbar WA2 and the disconnectors andearthing switches of this section.

1MRK 504 134-UEN - Section 12Control

255Application Manual

Page 262: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

For a double circuit-breaker bay, the modules DB_BUS_A, DB_LINE andDB_BUS_B must be used.

12.2.9.2 Configuration setting

For application without QB9 and QC9, just set the appropriate inputs to open stateand disregard the outputs. In the functional block diagram, 0 and 1 are designated0=FALSE and 1=TRUE:

• QB9_OP = 1• QB9_CL = 0

• QC9_OP = 1• QC9_CL = 0

If, in this case, line voltage supervision is added, then rather than setting QB9 toopen state, specify the state of the voltage supervision:

• QB9_OP = VOLT_OFF• QB9_CL = VOLT_ON

If there is no voltage supervision, then set the corresponding inputs as follows:

• VOLT_OFF = 1• VOLT_ON = 0

12.2.10 Interlocking for line bay ABC_LINE

12.2.10.1 Application

The interlocking for line bay (ABC_LINE) function is used for a line connected toa double busbar arrangement with a transfer busbar according to figure 128. Thefunction can also be used for a double busbar arrangement without transfer busbaror a single busbar arrangement with/without transfer busbar.

Section 12 1MRK 504 134-UEN -Control

256Application Manual

Page 263: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

QB1 QB2QC1

QA1

QC2

QB9QC9

WA1 (A)

WA2 (B)

WA7 (C)

QB7

en04000478.vsdIEC04000478 V1 EN

Figure 128: Switchyard layout ABC_LINE

The interlocking functionality in 650 series can not handle thetransfer bus (WA7)C.

The signals from other bays connected to the module ABC_LINE are describedbelow.

12.2.10.2 Signals from bypass busbar

To derive the signals:

Signal BB7_D_OP All line disconnectors on bypass WA7 except in the own bay are open.

VP_BB7_D The switch status of disconnectors on bypass busbar WA7 are valid.

EXDU_BPB No transmission error from any bay containing disconnectors on bypass busbar WA7

These signals from each line bay (ABC_LINE) except that of the own bay are needed:

Signal QB7OPTR Q7 is open

VPQB7TR The switch status for QB7 is valid.

EXDU_BPB No transmission error from the bay that contains the above information.

For bay n, these conditions are valid:

1MRK 504 134-UEN - Section 12Control

257Application Manual

Page 264: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

QB7OPTR (bay 1)QB7OPTR (bay 2)

. . .

. . .QB7OPTR (bay n-1)

& BB7_D_OP

VPQB7TR (bay 1)VPQB7TR (bay 2)

. . .

. . .VPQB7TR (bay n-1)

& VP_BB7_D

EXDU_BPB (bay 1)EXDU_BPB (bay 2)

. . .

. . .EXDU_BPB (bay n-1)

& EXDU_BPB

en04000477.vsd

IEC04000477 V1 EN

Figure 129: Signals from bypass busbar in line bay n

12.2.10.3 Signals from bus-coupler

If the busbar is divided by bus-section disconnectors into bus sections, the busbar-busbar connection could exist via the bus-section disconnector and bus-couplerwithin the other bus section.

Section 1 Section 2

A1A2_DC(BS)B1B2_DC(BS)

ABC_LINE ABC_BCABC_LINE ABC_BC

(WA1)A1(WA2)B1(WA7)C C

B2A2

en04000479.vsd

IEC04000479 V1 EN

Figure 130: Busbars divided by bus-section disconnectors (circuit breakers)

The interlocking functionality in 650 series can not handle thetransfer bus (WA7)C.

To derive the signals:

Signal BC_12_CL A bus-coupler connection exists between busbar WA1 and WA2.

BC_17_OP No bus-coupler connection between busbar WA1 and WA7.

BC_17_CL A bus-coupler connection exists between busbar WA1and WA7.

BC_27_OP No bus-coupler connection between busbar WA2 and WA7.

Table continues on next page

Section 12 1MRK 504 134-UEN -Control

258Application Manual

Page 265: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Signal BC_27_CL A bus-coupler connection exists between busbar WA2 and WA7.

VP_BC_12 The switch status of BC_12 is valid.

VP_BC_17 The switch status of BC_17 is valid.

VP_BC_27 The switch status of BC_27 is valid.

EXDU_BC No transmission error from any bus-coupler bay (BC).

These signals from each bus-coupler bay (ABC_BC) are needed:

Signal BC12CLTR A bus-coupler connection through the own bus-coupler exists between busbar WA1

and WA2.

BC17OPTR No bus-coupler connection through the own bus-coupler between busbar WA1 andWA7.

BC17CLTR A bus-coupler connection through the own bus-coupler exists between busbar WA1and WA7.

BC27OPTR No bus-coupler connection through the own bus-coupler between busbar WA2 andWA7.

BC27CLTR A bus-coupler connection through the own bus-coupler exists between busbar WA2and WA7.

VPBC12TR The switch status of BC_12 is valid.

VPBC17TR The switch status of BC_17 is valid.

VPBC27TR The switch status of BC_27 is valid.

EXDU_BC No transmission error from the bay that contains the above information.

These signals from each bus-section disconnector bay (A1A2_DC) are also needed.For B1B2_DC, corresponding signals from busbar B are used. The same type ofmodule (A1A2_DC) is used for different busbars, that is, for both bus-sectiondisconnector A1A2_DC and B1B2_DC.

Signal DCOPTR The bus-section disconnector is open.

DCCLTR The bus-section disconnector is closed.

VPDCTR The switch status of bus-section disconnector DC is valid.

EXDU_DC No transmission error from the bay that contains the above information.

If the busbar is divided by bus-section circuit breakers, the signals from the bus-section coupler bay (A1A2_BS), rather than the bus-section disconnector bay(A1A2_DC) must be used. For B1B2_BS, corresponding signals from busbar B areused. The same type of module (A1A2_BS) is used for different busbars, that is,for both bus-section circuit breakers A1A2_BS and B1B2_BS.

1MRK 504 134-UEN - Section 12Control

259Application Manual

Page 266: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Signal S1S2OPTR No bus-section coupler connection between bus-sections 1 and 2.

S1S2CLTR A bus-section coupler connection exists between bus-sections 1 and 2.

VPS1S2TR The switch status of bus-section coupler BS is valid.

EXDU_BS No transmission error from the bay that contains the above information.

For a line bay in section 1, these conditions are valid:

BC12CLTR (sect.1)

DCCLTR (A1A2)DCCLTR (B1B2)

>1&

BC12CLTR (sect.2)

&VPBC12TR (sect.1)

VPDCTR (A1A2)VPDCTR (B1B2)

VPBC12TR (sect.2)

>1&

BC17OPTR (sect.1)

DCOPTR (A1A2)BC17OPTR (sect.2)

>1&

BC17CLTR (sect.1)

DCCLTR (A1A2)BC17CLTR (sect.2)

&VPBC17TR (sect.1)

VPDCTR (A1A2)VPBC17TR (sect.2)

>1&

>1&

&

&

BC27OPTR (sect.1)

DCOPTR (B1B2)BC27OPTR (sect.2)

BC27CLTR (sect.1)

DCCLTR (B1B2)BC27CLTR (sect.2)

VPBC27TR (sect.1)VPDCTR (B1B2)

VPBC27TR (sect.2)

EXDU_BC (sect.1)EXDU_DC (A1A2)EXDU_DC (B1B2)EXDU_BC (sect.2)

BC_12_CL

VP_BC_12

BC_17_OP

BC_17_CL

VP_BC_17

BC_27_OP

BC_27_CL

VP_BC_27

EXDU_BC

en04000480.vsd

IEC04000480 V1 EN

Figure 131: Signals to a line bay in section 1 from the bus-coupler bays in eachsection

Section 12 1MRK 504 134-UEN -Control

260Application Manual

Page 267: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

For a line bay in section 2, the same conditions as above are valid by changingsection 1 to section 2 and vice versa.

12.2.10.4 Configuration setting

If there is no bypass busbar and therefore no QB7 disconnector, then theinterlocking for QB7 is not used. The states for QB7, QC71, BB7_D, BC_17,BC_27 are set to open by setting the appropriate module inputs as follows. In thefunctional block diagram, 0 and 1 are designated 0=FALSE and 1=TRUE:

• QB7_OP = 1• QB7_CL = 0

• QC71_OP = 1• QC71_CL = 0

• BB7_D_OP = 1

• BC_17_OP = 1• BC_17_CL = 0• BC_27_OP = 1• BC_27_CL = 0

• EXDU_BPB = 1

• VP_BB7_D = 1• VP_BC_17 = 1• VP_BC_27 = 1

If there is no second busbar WA2 and therefore no QB2 disconnector, then theinterlocking for QB2 is not used. The state for QB2, QC21, BC_12, BC_27 are setto open by setting the appropriate module inputs as follows. In the functional blockdiagram, 0 and 1 are designated 0=FALSE and 1=TRUE:

• QB2_OP = 1• QB2_CL = 0

• QC21_OP = 1• QC21_CL = 0

• BC_12_CL = 0• BC_27_OP = 1• BC_27_CL = 0

• VP_BC_12 = 1

1MRK 504 134-UEN - Section 12Control

261Application Manual

Page 268: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

12.2.11 Interlocking for transformer bay AB_TRAFO

12.2.11.1 Application

The interlocking for transformer bay (AB_TRAFO) function is used for atransformer bay connected to a double busbar arrangement according to figure 132.The function is used when there is no disconnector between circuit breaker andtransformer. Otherwise, the interlocking for line bay (ABC_LINE) function can beused. This function can also be used in single busbar arrangements.

QB1 QB2QC1

QA1

QC2

WA1 (A)

WA2 (B)

QA2

QC3

T

QC4

QB4QB3

QA2 and QC4 are notused in this interlocking

AB_TRAFO

en04000515.vsdIEC04000515 V1 EN

Figure 132: Switchyard layout AB_TRAFO

The signals from other bays connected to the module AB_TRAFO are describedbelow.

12.2.11.2 Signals from bus-coupler

If the busbar is divided by bus-section disconnectors into bus-sections, the busbar-busbar connection could exist via the bus-section disconnector and bus-couplerwithin the other bus-section.

Section 12 1MRK 504 134-UEN -Control

262Application Manual

Page 269: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Section 1 Section 2

A1A2_DC(BS)B1B2_DC(BS)

AB_TRAFO ABC_BCAB_TRAFO ABC_BC

(WA1)A1(WA2)B1(WA7)C C

B2A2

en04000487.vsd

IEC04000487 V1 EN

Figure 133: Busbars divided by bus-section disconnectors (circuit breakers)

The interlocking functionality in 650 series cannot handle thetransfer bus (WA7)C.

The project-specific logic for input signals concerning bus-coupler are the same asthe specific logic for the line bay (ABC_LINE):

Signal BC_12_CL A bus-coupler connection exists between busbar WA1 and WA2.

VP_BC_12 The switch status of BC_12 is valid.

EXDU_BC No transmission error from bus-coupler bay (BC).

The logic is identical to the double busbar configuration “Signals from bus-coupler“.

12.2.11.3 Configuration setting

If there are no second busbar B and therefore no QB2 disconnector, then theinterlocking for QB2 is not used. The state for QB2, QC21, BC_12 are set to openby setting the appropriate module inputs as follows. In the functional blockdiagram, 0 and 1 are designated 0=FALSE and 1=TRUE:

• QB2_OP = 1• QB2QB2_CL = 0

• QC21_OP = 1• QC21_CL = 0

• BC_12_CL = 0• VP_BC_12 = 1

If there is no second busbar B at the other side of the transformer and therefore noQB4 disconnector, then the state for QB4 is set to open by setting the appropriatemodule inputs as follows:

1MRK 504 134-UEN - Section 12Control

263Application Manual

Page 270: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

• QB4_OP = 1• QB4_CL = 0

12.3 Voltage control

12.3.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Automatic voltage control for tapchanger

TR8ATCC

U

IEC10000166 V1 EN

90

Tap changer control and supervision, 6binary inputs

TCMYLTC

IEC10000167 V1 EN

84

12.3.2 ApplicationWhen the load in a power network is increased the voltage will decrease and viceversa. To maintain the network voltage at a constant level, power transformers areusually equipped with an load tap changer. This alters the power transformer ratioin a number of predefined steps and in that way changes the voltage. Each stepusually represents a change in voltage of approximately 0.5-1.7%.

The voltage control function is intended for control of power transformers with amotor driven load tap changer. The function is designed to regulate the voltage atthe secondary side of the power transformer. The control method is based on a step-by-step principle which means that a control pulse, one at a time, will be issued tothe tap changer mechanism to move it one position up or down. The length of thecontrol pulse can be set within a wide range to accommodate different types of tapchanger mechanisms. The pulse is generated whenever the measured voltage, for agiven time, deviates from the set reference value by more than the preset deadband(degree of insensitivity).

The voltage can be controlled at the point of voltage measurement, as well as aload point located out in the network. In the latter case, the load point voltage iscalculated based on the measured load current and the known impedance from thevoltage measuring point to the load point.

The automatic voltage control can be either for a single transformer, or for paralleltransformers. Parallel control of power transformers with an IED can be made inthree alternative ways:

Section 12 1MRK 504 134-UEN -Control

264Application Manual

Page 271: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

• With the master-follower method• With the reverse reactance method• With the circulating current method

Of these alternatives, the first and the last require communication between thefunction control blocks of the different transformers, whereas the middlealternative does not require any communication.

The voltage control includes many extra features such as possibility to avoidsimultaneous tapping of parallel transformers, extensive tap changer monitoringincluding contact wear and hunting detection, monitoring of the power flow in thetransformer so that for example, the voltage control can be blocked if the powerreverses and so on.

The voltage control function is built up by two function blocks which both arelogical nodes in IEC 61850-8-1:

• Automatic voltage control for tap changer, TR8ATCC for parallel control.• Tap changer control and supervision, 6 binary inputs, TCMYLTC

Automatic voltage control for tap changer, TR8ATCC is a function designed toautomatically maintain the voltage at the LV-side side of a power transformerwithin given limits around a set target voltage. A raise or lower command isgenerated whenever the measured voltage, for a given period of time, deviates fromthe set target value by more than the preset deadband value (degree ofinsensitivity). A time delay (inverse or definite time) is set to avoid unnecessaryoperation during shorter voltage deviations from the target value, and in order tocoordinate with other automatic voltage controllers in the system.

TCMYLTCis an interface between the Automatic voltage control for tap changer,TR8ATCC and the transformer load tap changer itself. More specifically thismeans that it gives command-pulses to a power transformer motor driven load tapchanger and that it receives information from the load tap changer regarding tapposition, progress of given commands, and so on.

TCMYLTC also serves the purpose of giving information about tap position to thetransformer differential protection.

Control location local/remoteThe tap changer can be operated from the front of the IED or from a remote placealternatively. On the IED front there is a local remote switch that can be used toselect the operator place. For this functionality the Apparatus control functionblocks Bay control (QCBAY), Local remote (LOCREM) and Local remote control(LOCREMCTRL) are used.

Information about the control location is given to TR8ATCC function throughconnection of the Permitted Source to Operate (PSTO) output of the QCBAYfunction block to the input PSTO of the TR8ATCC function block.

1MRK 504 134-UEN - Section 12Control

265Application Manual

Page 272: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Control ModeThe control mode of the automatic voltage control for tap changer function,TR8ATCC for parallel control can be:

• Manual• Automatic

The control mode can be changed from the local location via the command menuon the local HMI under Main menu/ Control/Commands/TR8ATCC (90)/1:TR8ATCC, or changed from a remote location via binary signals connected tothe MANCTRL, AUTOCTRL inputs on TR8ATCC function block.

Measured QuantitiesIn normal applications, the LV side of the transformer is used as the voltagemeasuring point. If necessary, the LV side current is used as load current tocalculate the line-voltage drop to the regulation point.

Automatic voltage control for tap changer, TR8ATCC function block has threeinputs I3P1, I3P2 and U3P2 corresponding to HV-current, LV-current and LV-voltage respectively. These analog quantities are fed to the IED via the transformerinput module, the Analog to Digital Converter and thereafter a Pre-ProcessingBlock. In the Pre-Processing Block, a great number of quantities for example, phase-to-phase analog values, sequence values, max value in a three phase group etc., arederived. The different function blocks in the IED are then “subscribing” onselected quantities from the pre-processing blocks. In case of TR8ATCC, there arethe following possibilities:

• I3P1 represents a three-phase group of phase current with the highest currentin any of the three phases considered. As only the highest of the phase currentis considered, it is also possible to use one single-phase current as well as two-phase currents. In these cases, the currents that are not used will be zero.

• For I3P2 and U3P2 the setting alternatives are: any individual phase current/voltage, as well as any combination of phase-phase current/voltage or thepositive sequence current/voltage. Thus, single-phase as well as, phase-phaseor three-phase feeding on the LV-side is possible but it is commonly selectedfor current and voltage.

Section 12 1MRK 504 134-UEN -Control

266Application Manual

Page 273: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

OLT

C

raise,lowersignals/alarms

positionBIO

AIM

IED

IL1,IL2,IL3

TRMIL1,IL2,IL3 or ILi,ILj or ILi

UL1,UL2,UL3 or ULi,ULj or ULi

High Voltage Side

(Load Current) IL

Low Voltage Side

Line Impedance R+jX

UB (Busbar Voltage)

Load Center UL (Load Point Voltage)

IEC11000064-1-en.vsdIEC11000064 V1 EN

Figure 134: Signal flow for a single transformer with voltage control

On the HV side, the three-phase current is normally required in order to feed the three-phase over current protection that blocks the load tap changer in case of over-current above harmful levels.

The voltage measurement on the LV-side can be made single phase-earth.However, it shall be remembered that this can only be used in solidly earthedsystems, as the measured phase-earth voltage can increase with as much as a factor√3 in case of earth faults in a non-solidly earthed system.

The analog input signals are normally common with other functions in the IED forexample, protection functions.

The LV-busbar voltage is designated UB, the load current IL andload point voltage UL.

Automatic voltage control for a single transformerAutomatic voltage control for tap changer, parallel control TR8ATCC measuresthe magnitude of the busbar voltage UB. If no other additional features are enabled(line voltage drop compensation), this voltage is further used for voltage regulation.

1MRK 504 134-UEN - Section 12Control

267Application Manual

Page 274: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

TR8ATCC then compares this voltage with the set voltage, USet and decideswhich action should be taken. To avoid unnecessary switching around the setpoint,a deadband (degree of insensitivity) is introduced. The deadband is symmetricalaround USet, see figure 135, and it is arranged in such a way that there is an outerand an inner deadband. Measured voltages outside the outer deadband start thetimer to initiate tap commands, whilst the sequence resets when the measuredvoltage is once again back inside the inner deadband. One half of the outerdeadband is denoted ΔU. The setting of ΔU, setting Udeadband should be set to avalue near to the power transformer’s tap changer voltage step (typically 75–125%of the tap changer step).

Voltage MagnitudeUmaxU2UsetU1UminUblock0

Raise Cmd

*) Action in accordance with setting

Security Range

Lower Cmd

IEC06000489_2_en.vsd

DD U UDUin DUin

*) *) *)

IEC06000489 V2 EN

Figure 135: Control actions on a voltage scale

During normal operating conditions the busbar voltage UB, stays within the outerdeadband (interval between U1 and U2 in figure 135). In that case no actions willbe taken by TR8ATCC. However, if UB becomes smaller than U1, or greater thanU2, an appropriate lower or raise timer will start. The timer will run as long as themeasured voltage stays outside the inner deadband. If this condition persists longerthan the preset time delay, TR8ATCC will initiate that the appropriate ULOWERor URAISE command will be sent from Tap changer control and supervision, 6binary inputs TCMYLTC to the transformer load tap changer. If necessary, theprocedure will be repeated until the magnitude of the busbar voltage again fallswithin the inner deadband. One half of the inner deadband is denoted ΔUin. Theinner deadband ΔUin, setting UDeadbandInner should be set to a value smallerthan ΔU. It is recommended to set the inner deadband to 25-70% of the ΔU value.

This way of working is used by TR8ATCC while the busbar voltage is within thesecurity range defined by settings Umin and Umax.

A situation where UB falls outside this range will be regarded as an abnormalsituation.

When UB falls below setting Ublock, or alternatively, falls below setting Umin butstill above Ublock, or rises above Umax, actions will be taken in accordance withsettings for blocking conditions (refer to table 25).

If the busbar voltage rises above Umax, TR8ATCC can initiate one or more faststep down commands (ULOWER commands) in order to bring the voltage backinto the security range (settings Umin, and Umax). The fast step down function

Section 12 1MRK 504 134-UEN -Control

268Application Manual

Page 275: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

operation can be set in one of the following three ways: off /auto/auto and manual,according to the setting FSDMode. The ULOWER command, in fast step downmode, is issued with the settable time delay tFSD.

The measured RMS magnitude of the busbar voltage UB is shown on the local HMIas value BUSVOLT under Main menu/Tests/Function status/Control/TR8ATCC (90)/1:TR8ATCC/Outputs.

Time characteristicThe time characteristic defines the time that elapses between the moment whenmeasured voltage exceeds the deadband interval until the appropriate URAISE orULOWER command is initiated.

The purpose of the time delay is to prevent unnecessary load tap changeroperations caused by temporary voltage fluctuations and to coordinate load tapchanger operations in radial networks in order to limit the number of load tapchanger operations. This can be done by setting a longer time delay closer to theconsumer and shorter time delays higher up in the system.

The first time delay, t1, is used as a time delay (usually long delay) for the firstcommand in one direction. It can have a definite or inverse time characteristic,according to the setting t1Use (Constant/Inverse). For inverse time characteristicslarger voltage deviations from the USet value will result in shorter time delays,limited by the shortest time delay equal to the tMin setting. This setting should becoordinated with the tap changer mechanism operation time.

Constant (definite) time delay is independent of the voltage deviation.

The inverse time characteristic for the first time delay follows the formulas:

DA UB USet= -

IECEQUATION2294 V1 EN (Equation 118)

DADU

=D

EQUATION1986 V1 EN (Equation 119)

t1tMin D=

EQUATION1848 V2 EN (Equation 120)

Where:

DA absolute voltage deviation from the set point

D relative voltage deviation in respect to set deadband value

1MRK 504 134-UEN - Section 12Control

269Application Manual

Page 276: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

For the last equation, the condition t1 > tMin shall also be fulfilled. This practicallymeans that tMin will be equal to the set t1 value when absolute voltage deviationDA is equal to ΔU ( relative voltage deviation D is equal to 1). For other values seefigure 136. It should be noted that operating times, shown in the figure 136 are for30, 60, 90, 120, 150 & 180 seconds settings for t1 and 10 seconds for tMin.

t1=180

t1=150

t1=120

t1=90

t1=60

t1=30

IEC06000488_2_en.vsd

IEC06000488 V2 EN

Figure 136: Inverse time characteristic for TR8ATCC

The second time delay, t2, will be used for consecutive commands (commands inthe same direction as the first command). It can have a definite or inverse timecharacteristic according to the setting t2Use (Constant/Inverse). Inverse timecharacteristic for the second time delay follows the similar formulas as for the firsttime delay, but the t2 setting is used instead of t1.

Line voltage dropThe purpose with the line voltage drop compensation is to control the voltage, notat the power transformer low voltage side, but at a point closer to the load point.

Figure 137 shows the vector diagram for a line modelled as a series impedancewith the voltage UB at the LV busbar and voltage UL at the load center. The loadcurrent on the line is IL, the line resistance and reactance from the station busbar tothe load point are RL and XL. The angle between the busbar voltage and thecurrent, is j. If all these parameters are known UL can be obtained by simplevector calculation.

Values for RL and XL are given as settings in primary system ohms. If more thanone line is connected to the LV busbar, an equivalent impedance should becalculated and given as a parameter setting.

Section 12 1MRK 504 134-UEN -Control

270Application Manual

Page 277: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

The line voltage drop compensation function can be turned On/Off by the settingparameter OperationLDC. When it is enabled, the voltage UL will be used by theAutomatic voltage control for tap changer function, TR8ATCC for parallel controlfor voltage regulation instead of UB. However, TR8ATCC will still perform thefollowing two checks:

1. The magnitude of the measured busbar voltage UB, shall be within the securityrange, (setting Umin and Umax). If the busbar voltage falls-out of this rangethe line voltage drop compensation calculations will be temporarily stoppeduntil the voltage UB comes back within the range.

2. The magnitude of the calculated voltage UL at the load point, can be limitedsuch that it is only allowed to be equal to or smaller than the magnitude of UB,otherwise UB will be used. However, a situation where UL>UB can be causedby a capacitive load condition, and if the wish is to allow for a situation likethat, the limitation can be removed by setting the parameter OperCapaLDC toOn.

~ Load

RL XL

UB

UL

UB

RLIL

jXLIL Re

en06000487.vsdIEC06000487 V1 EN

Figure 137: Vector diagram for line voltage drop compensation

The calculated load voltage UL is shown on the local HMI as value ULOAD underMain menu/Control/Commands/TR8ATCC (90)/X:TR8ATCC.

Load voltage adjustmentDue to the fact that most loads are proportional to the square of the voltage, it ispossible to provide a way to shed part of the load by decreasing the supply voltagea couple of percent.

It is possible to do this voltage adjustment in two different ways in Automaticvoltage control for tap changer, parallel control TR8ATCC:

1. Automatic load voltage adjustment, proportional to the load current.2. Constant load voltage adjustment with four different preset values.

In the first case the voltage adjustment is dependent on the load and maximumvoltage adjustment should be obtained at rated load of the transformer.

In the second case, a voltage adjustment of the set point voltage can be made infour discrete steps (positive or negative) activated with binary signals connected to

1MRK 504 134-UEN - Section 12Control

271Application Manual

Page 278: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

TR8ATCC function block inputs LVA1, LVA2, LVA3 and LVA4. Thecorresponding voltage adjustment factors are given as setting parametersLVAConst1, LVAConst2, LVAConst3 and LVAConst4. The inputs are activated witha pulse, and the latest activation of anyone of the four inputs is valid. Activation ofthe input LVARESET in TR8ATCC block, brings the voltage setpoint back toUSet.

With these factors, TR8ATCC adjusts the value of the set voltage USet accordingto the following formula:

Usetadjust = Uset + Sa × IL + Sci

IBaseEQUATION1865 V2 EN (Equation 121)

Uset, adjust Adjusted set voltage in per unit

USet Original set voltage: Base quality is Un2

Sa Automatic load voltage adjustment factor, setting VRAuto

IL Load current

IBase Rated current, LV winding (for winding 2, which is defined in a global basefunction, selected with setting GlobalBaseSel2 for TR8ATCC)

Sci Constant load voltage adjust. factor for active input i (corresponding toLVAConst1, LVAConst2, LVAConst3 and LVAConst4)

It shall be noted that the adjustment factor is negative in order to decrease the loadvoltage and positive in order to increase the load voltage. After this calculationUset, adjust will be used by TR8ATCC for voltage regulation instead of the originalvalue USet. The calculated set point voltage USet, adjust is shown on the local HMIas a service value USETOUT under and Main menu/Control/Commands/TR8ATCC (90)/X:TR8ATCC.

Automatic control of parallel transformersParallel control of power transformers means control of two or more powertransformers connected to the same busbar on the LV side and in most cases alsoon the HV side. Special measures must be taken in order to avoid a runawaysituation where the tap changers on the parallel transformers gradually diverge andend up in opposite end positions.

Three alternative methods can be used in an IED for parallel control with theAutomatic voltage control for tap changer, TR8ATCC:

• master-follower method• reverse reactance method• circulating current method

In order to realize the need for special measures to be taken when controllingtransformers in parallel, consider first two parallel transformers which are

Section 12 1MRK 504 134-UEN -Control

272Application Manual

Page 279: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

supposed to be equal with similar tap changers. If they would each be in automaticvoltage control for single transformer that is, each of them regulating the voltageon the LV busbar individually without any further measures taken, then thefollowing could happen. Assuming for instance that they start out on the same tapposition and that the LV busbar voltage UB is within USet ± DU, then a gradualincrease or decrease in the load would at some stage make UB fall outside USet ±DU and a lower or raise command would be initiated. However, the rate of changeof voltage would normally be slow, which would make one tap changer act beforethe other. This is unavoidable and is due to small inequalities in measurement andso on. The one tap changer that responds first on a low voltage condition with araise command will be prone to always do so, and vice versa. The situation couldthus develop such that, for example T1 responds first to a low busbar voltage witha raise command and thereby restores the voltage. When the busbar voltagethereafter at a later stage gets high, T2 could respond with a lower command andthereby again restore the busbar voltage to be within the inner deadband. However,this has now caused the load tap changer for the two transformers to be 2 tappositions apart, which in turn causes an increasing circulating current. This courseof events will then repeat with T1 initiating raise commands and T2 initiatinglower commands in order to keep the busbar voltage within USet ± DU, but at thesame time it will drive the two tap changers to its opposite end positions. Highcirculating currents and loss of control would be the result of this runaway tapsituation.

Parallel control with the master-follower methodIn the master-follower method, one of the transformers is selected to be master, andwill regulate the voltage in accordance with the principles for Automatic voltagecontrol. Selection of the master is made by activating the binary inputFORCMAST in TR8ATCC function block for one of the transformers in the group.

The followers can act in two alternative ways depending on the setting of theparameter MFMode. When this setting is Follow Cmd, raise and lower commands(URAISE and ULOWER) generated by the master, will initiate the correspondingcommand in all follower TR8ATCCs simultaneously, and consequently they willblindly follow the master irrespective of their individual tap positions. Effectivelythis means that if the tap positions of the followers were harmonized with themaster from the beginning, they would stay like that as long as all transformers inthe parallel group continue to participate in the parallel control. On the other handfor example, one transformer is disconnected from the group and misses a one tapstep operation, and thereafter is reconnected to the group again, it will thereafterparticipate in the regulation but with a one tap position offset.

If the parameter MFMode is set to Follow Tap, then the followers will read the tapposition of the master and adopt to the same tap position or to a tap position withan offset relative to the master, and given by setting parameter TapPosOffs(positive or negative integer value). The setting parameter tAutoMSF introduces atime delay on URAISE/ULOWER commands individually for each follower whensetting MFMode has the value Follow Tap.

1MRK 504 134-UEN - Section 12Control

273Application Manual

Page 280: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Selecting a master is made by activating the input FORCMAST in TR8ATCCfunction block. Deselecting a master is made by activating the input RSTMAST.These two inputs are pulse activated, and the most recent activation is valid that is,an activation of any of these two inputs overrides previous activations. If none ofthese inputs has been activated, the default is that the transformer acts as a follower(given of course that the settings are parallel control with the master follower method).

When the selection of master or follower in parallel control, or automatic control insingle mode, is made with a three position switch in the substation, an arrangementas in figure 138 below is arranged with ACT tool.

M

F

I SNGLMODE

FORCMAST

RSTMAST

TR8ATCC

IEC09000333-1-en.vsd

BIO

IEC09000333 V1 EN

Figure 138: Principle for a three-position switch Master/Follower/Single

Parallel control with the reverse reactance methodConsider figure 139 with two parallel transformers with equal rated data andsimilar tap changers. The tap positions will diverge and finally end up in a runawaytap situation if no measures to avoid this are taken.

Section 12 1MRK 504 134-UEN -Control

274Application Manual

Page 281: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Load

T1

I L

T2

UB

UL

IT1 IT2

en06000486.vsdIEC06000486 V1 EN

Figure 139: Parallel transformers with equal rated data.

In the reverse reactance method, the line voltage drop compensation is used. Thepurpose is to control the voltage at a load point further out in the network. The verysame function can also be used here but with a completely different objective.

Figure 140, shows a vector diagram where the principle of reverse reactance hasbeen introduced for the transformers in figure 139. The transformers are heresupposed to be on the same tap position, and the busbar voltage is supposed to givea calculated compensated value UL that coincides with the target voltage USet.

IEC06000485_2_en.vsd

UB

RLIT1=RLIT2

jXLIT1=jXLIT2

IT1=IT2=(IT1+IT2)/2

UL1=UL2=USet

IEC06000485 V2 EN

Figure 140: Vector diagram for two transformers regulated exactly on targetvoltage.

A comparison with figure 137 gives that the line voltage drop compensation for thepurpose of reverse reactance control is made with a value with opposite sign on XL,hence the designation “reverse reactance” or “negative reactance”. Effectively this

1MRK 504 134-UEN - Section 12Control

275Application Manual

Page 282: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

means that, whereas the line voltage drop compensation in figure 137 gave avoltage drop along a line from the busbar voltage UB to a load point voltage UL,the line voltage drop compensation in figure 140 gives a voltage increase (actually,by adjusting the ratio XL/RL with respect to the power factor, the length of thevector UL will be approximately equal to the length of UB) from UB up towards thetransformer itself. Thus in principal the difference between the vector diagrams infigure 137 and figure 140 is the sign of the setting parameter XL.

If now the tap position between the transformers will differ, a circulating currentwill appear, and the transformer with the highest tap (highest no load voltage) willbe the source of this circulating current. Figure 141 below shows this situation withT1 being on a higher tap than T2.

Load

T1 T2

UB

UL

IT1 IT2

UB

UL1 RIT1

jXLIT1

Icc

-Icc

(IT1+IT2)/2IT1

IT2

UL2

RLIT2

jXLIT2

IEC06000491-2-en.vsd

ICC...T2

ICC...T1

IL

IEC06000491 V2 EN

Figure 141: Circulating current caused by T1 on a higher tap than T2.

The circulating current Icc is predominantly reactive due to the reactive nature ofthe transformers. The impact of Icc on the individual transformer currents is that itincreases the current in T1 (the transformer that is driving Icc) and decreases it inT2 at the same time as it introduces contradictive phase shifts, as can be seen infigure 141. The result is thus, that the line voltage drop compensation calculatedvoltage UL for T1 will be higher than the line voltage drop compensationcalculated voltage UL for T2, or in other words, the transformer with the higher tapposition will have the higher UL value and the transformer with the lower tapposition will have the lower UL value. Consequently, when the busbar voltageincreases, T1 will be the one to tap down, and when the busbar voltage decreases,T2 will be the one to tap up. The overall performance will then be that the runawaytap situation will be avoided and that the circulating current will be minimized.

Section 12 1MRK 504 134-UEN -Control

276Application Manual

Page 283: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Parallel control with the circulating current methodTwo transformers with different turns ratio, connected to the same busbar on the HV-side, will apparently show different LV-side voltage. If they are now connected tothe same LV busbar but remain unloaded, this difference in no-load voltage willcause a circulating current to flow through the transformers. When load is put onthe transformers, the circulating current will remain the same, but now it will besuperimposed on the load current in each transformer. Voltage control of paralleltransformers with the circulating current method means minimizing of thecirculating current at a given voltage target value, thereby achieving:

1. that the busbar or load voltage is regulated to a preset target value2. that the load is shared between parallel transformers in proportion to their

ohmic short circuit reactance

If the transformers have equal percentage impedance given in the respectivetransformer MVA base, the load will be divided in direct proportion to the ratedpower of the transformers when the circulating current is minimized.

This method requires extensive exchange of data between the TR8ATCC functionblocks (one TR8ATCC function for each transformer in the parallel group).TR8ATCC function block can either be located in the same IED, where they areconfigured in PCM600 to co-operate, or in different IEDs. If the functions arelocated in different IEDs they must communicate via GOOSE interbaycommunication on the IEC 61850 communication protocol. .

The busbar voltage UB is measured individually for each transformer in the parallelgroup by its associated TR8ATCC function. These measured values will then beexchanged between the transformers, and in each TR8ATCC block, the mean valueof all UB values will be calculated. The resulting value UBmean will then be used ineach IED instead of UB for the voltage regulation, thus assuring that the same valueis used by all TR8ATCC functions, and thereby avoiding that one erroneousmeasurement in one transformer could upset the voltage regulation. At the sametime, supervision of the VT mismatch is also performed. This works such that, if ameasured voltage UB, differs from UBmean with more than a preset value (settingparameter VTmismatch) and for more than a pre set time (setting parametertVTmismatch) an alarm signal VTALARM will be generated.

The calculated mean busbar voltage UBmean is shown on the local HMI as a servicevalue BusVolt under Main menu/Tests/Function status/Control/TR8ATCC (90)/1:TR8ATCC/Outputs.

Measured current values for the individual transformers must be communicatedbetween the participating TR8ATCC functions, in order to calculate the circulatingcurrent.

The calculated circulating current Icc_i for transformer “i” is shown on the HMI asa service value ICIRCUL under Main menu/Control/Commands/TR8ATCC(90)/X:TR8ATCC.

1MRK 504 134-UEN - Section 12Control

277Application Manual

Page 284: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

When the circulating current is known, it is possible to calculate a no-load voltagefor each transformer in the parallel group. To do that the magnitude of thecirculating current in each bay, is first converted to a voltage deviation, Udi, withequation 122:

_di i cc i iU C I X= ´ ´

EQUATION1869 V1 EN (Equation 122)

where Xi is the short-circuit reactance for transformer i and Ci, is a settingparameter named Comp which serves the purpose of alternatively increasing ordecreasing the impact of the circulating current in TR8ATCC control calculations.It should be noted that Udi will have positive values for transformers that producecirculating currents and negative values for transformers that receive circulatingcurrents.

Now the magnitude of the no-load voltage for each transformer can beapproximated with:

i Bmean diU U U= +EQUATION1870 V1 EN (Equation 123)

This value for the no-load voltage is then simply put into the voltage controlfunction for single transformer. There it is treated as the measured busbar voltage,and further control actions are taken as described previously in section "Automaticvoltage control for a single transformer". By doing this, the overall control strategycan be summarized as follows.

For the transformer producing/receiving the circulating current, the calculated no-load voltage will be greater/smaller than the measured voltage UBmean. Thecalculated no-load voltage will then be compared with the set voltage USet. Asteady deviation which is outside the outer deadband will result in ULOWER orURAISE being initiated alternatively. In this way the overall control action willalways be correct since the position of a tap changer is directly proportional to thetransformer no-load voltage. The sequence resets when UBmean is inside the innerdeadband at the same time as the calculated no-load voltages for all transformers inthe parallel group are inside the outer deadband.

In parallel operation with the circulating current method, different USet values forindividual transformers can cause the voltage regulation to be unstable. For thisreason, the mean value of USet for parallel operating transformers can beautomatically calculated and used for the voltage regulation. This is set On/Off bysetting parameter OperUsetPar. The calculated mean USet value is shown on thelocal HMI as a service value USETPAR under Main menu/Control/Commands/TR8ATCC (90)/X:TR8ATCC.

The use of mean USet is recommended for parallel operation with the circulatingcurrent method, especially in cases when Load Voltage Adjustment is also used.

Section 12 1MRK 504 134-UEN -Control

278Application Manual

Page 285: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Line voltage drop compensation for parallel controlThe line voltage drop compensation for a single transformer is described in section"Line voltage drop". The same principle is used for parallel control with thecirculating current method and with the master – follower method, except that thetotal load current, IL, is used in the calculation instead of the individual transformercurrent. (See figure 137 for details). The same values for the parameters Rline andXline shall be set in all IEDs in the same parallel group. There is no automaticchange of these parameters due to changes in the substation topology, thus theyshould be changed manually if needed.

Adapt mode, manual control of a parallel group

Adapt mode (operation with the circulating current method)When the circulating current method is used, it is also possible to manually controlthe transformers as a group. To achieve this, the setting OperationAdapt must beset On, then the control mode for one TR8ATCC shall be set to “Manual” via thebinary input MANCTRL or the local HMI under Main menu/Control/Commands/TR8ATCC (90)/1:TR8ATCC whereas the other TR8ATCCs are left in“Automatic”. TR8ATCCs in automatic mode will then observe that onetransformer in the parallel group is in manual mode and will then automatically beset in adapt mode. As the name indicates they will adapt to the manual tapping ofthe transformer that has been put in manual mode.

TR8ATCC in adapt mode will continue the calculation of Udi, but instead ofadding Udi to the measured busbar voltage, it will compare it with the deadbandDU. The following control rules are used:

1. If Udi is positive and its modulus is greater thanDU, then initiate an ULOWERcommand. Tapping will then take place after appropriate t1/t2 timing.

2. If Udi is negative and its modulus is greater than DU, then initiate an URAISEcommand. Tapping will then take place after appropriate t1/t2 timing.

3. If Udi modulus is smaller thanDU, then do nothing.

The binary output signal ADAPT on the TR8ATCC function block will beactivated to indicate that this TR8ATCC is adapting to another TR8ATCC in theparallel group.

It shall be noted that control with adapt mode works as described under thecondition that only one transformer in the parallel group is set to manual mode viathe binary input MANCTRL or, the local HMI Main menu/Control/Commands/TR8ATCC (90)/1:TR8ATCC.

In order to operate each tap changer individually when the circulating currentmethod is used, the operator must set each TR8ATCC in the parallel group, in manual.

Adapt mode (operation with the master follower method)When in master follower mode, the adapt situation occurs when the settingOperationAdapt is On, and the master is put in manual control with the followers

1MRK 504 134-UEN - Section 12Control

279Application Manual

Page 286: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

still in parallel master-follower control. In this situation the followers will continueto follow the master the same way as when it is automatic control.

If one follower in a master follower parallel group is put in manual mode, still withthe setting OperationAdaptOn, the rest of the group will continue in automaticmaster follower control. The follower in manual mode will of course disregard anypossible tapping of the master. However, as one transformer in the parallel group isnow exempted from the parallel control, the binary output signal ADAPT onTR8ATCC function block will be activated for the rest of the parallel group.

Power monitoringThe level (with sign) of active and reactive power flow through the transformer,can be monitored. This function can be utilized for different purposes for example,to block the voltage control function when active power is flowing from the LVside to the HV side or to initiate switching of reactive power compensation plant,and so on.

There are four setting parameters P>, P<, Q> and Q< with associated outputs inTR8ATCC function blocks PGTFWD, PLTREV, QGTFWD and QLTREV. Whenpassing the pre-set value, the associated output will be activated after the commontime delay setting tPower.

The definition of direction of the power is such that the active power P is forwardwhen power flows from the HV-side to the LV-side as shown in figure 142. Thereactive power Q is forward when the total load on the LV side is inductive( reactance) as shown in figure 142.

ATCC

IED

HV-side

Pforward

LV-sideIEC06000536_1_en.vsd

Qforward (inductive)

IEC06000536 V2 EN

Figure 142: Power direction references

With the four outputs in the function block available, it is possible to do more thanjust supervise a level of power flow in one direction. By combining the outputswith logical elements in ACT tool, it is also possible to cover for example, intervalsas well as areas in the P-Q plane.

Section 12 1MRK 504 134-UEN -Control

280Application Manual

Page 287: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Busbar topology logicInformation of the busbar topology that is, position of circuit breakers andisolators, yielding which transformers that are connected to which busbar andwhich busbars that are connected to each other, is vital for the Automatic voltagecontrol for tap changer, parallel control function TR8ATCC when the circulatingcurrent or the master-follower method is used. This information tells eachTR8ATCC, which transformers that it has to consider in the parallel control.

In a simple case, when only the switchgear in the transformer bays needs to beconsidered, there is a built-in function in TR8ATCC block that can provideinformation on whether a transformer is connected to the parallel group or not. Thisis made by connecting the transformer CB auxiliary contact status to TR8ATCCfunction block input DISC, which can be made via a binary input, or via GOOSEfrom another IED in the substation. When the transformer CB is open, thisactivates that input which in turn will make a corresponding signal DISC=1 inTR8ATCC data set. This data set is the same data package as the package thatcontains all TR8ATCC data transmitted to the other transformers in the parallelgroup (see section "Exchange of information between TR8ATCC functions" formore details). Figure 143 shows an example where T3 is disconnected which willlead to T3 sending the DISC=1 signal to the other two parallel TR8ATCC modules(T1 and T2) in the group. Also see table 24.

T1 T2 T3

99000952.VSD

U1 U2 U3

Z1 Z2 Z3I1 I2 I3=0

IL=I1+I2

IEC99000952 V1 EN

Figure 143: Disconnection of one transformer in a parallel group

When the busbar arrangement is more complicated with more buses and bus couplers/bus sections, it is necessary to engineer a specific station topology logic. This logiccan be built in the ACT tool in PCM600 and will keep record on whichtransformers that are in parallel (in one or more parallel groups). In eachTR8ATCC function block there are four binary inputs (T1INCLD,..., T4INCLD)that will be activated from the logic depending on which transformers that are inparallel with the transformer to whom the TR8ATCC function block belongs.

TR8ATCC function block is also fitted with four outputs (T1PG,..., T4PG) forindication of the actual composition of the parallel group that it itself is part of. Ifparallel operation mode has been selected in the IED with setting TrfId = Tx, thenthe TxPG signal will always be set to 1. The parallel function will consider

1MRK 504 134-UEN - Section 12Control

281Application Manual

Page 288: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

communication messages only from the voltage control functions working inparallel (according to the current station configuration). When the parallel voltagecontrol function detects that no other transformers work in parallel it will behave asa single voltage control function in automatic mode.

Exchange of information between TR8ATCC functionsEach transformer in a parallel group needs an Automatic voltage control for tapchanger, parallel control TR8ATCC function block of its own for the parallelvoltage control. Communication between these TR8ATCCs is made either on theGOOSE interbay communication on the IEC 61850 protocol if TR8ATCCfunctions reside in different IEDs, or alternatively configured internally in one IEDif multiple instances of TR8ATCC reside in the same IED. Complete exchange ofTR8ATCC data, analog as well as binary, on GOOSE is made cyclically every 300ms.

TR8ATCC function block has an output ATCCOUT. This output contains two setsof signals. One is the data set that needs to be transmitted to other TR8ATCCblocks in the same parallel group, and the other is the data set that is transferred tothe TCMYLTC function block for the same transformer as TR8ATCC blockbelongs to.

There are 10 binary signals and 6 analog signals in the data set that is transmittedfrom one TR8ATCC block to the other TR8ATCC blocks in the same parallel group:

Table 22: Binary signals

Signal ExplanationTimerOn This signal is activated by the transformer that has started its timer and is

going to tap when the set time has expired.

automaticCTRL Activated when the transformer is set in automatic control

mutualBlock Activated when the automatic control is blocked

disc Activated when the transformer is disconnected from the busbar

receiveStat Signal used for the horizontal communication

TermIsForcedMaster Activated when the transformer is selected Master in the master-followerparallel control mode

TermIsMaster Activated for the transformer that is master in the master-follower parallelcontrol mode

termReadyForMSF Activated when the transformer is ready for master-follower parallel controlmode

raiseVoltageOut Order from the master to the followers to tap up

lowerVoltageOut Order from the master to the followers to tap down

Table 23: Analog signals

Signal ExplanationvoltageBusbar Measured busbar voltage for this transformer

ownLoadCurrim Measured load current imaginary part for this transformer

ownLoadCurrre Measured load current real part for this transformer

Table continues on next page

Section 12 1MRK 504 134-UEN -Control

282Application Manual

Page 289: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Signal ExplanationreacSec Transformer reactance in primary ohms referred to the LV side

relativePosition The transformer's actual tap position

voltage Setpoint The transformer's set voltage (USet) for automatic control

Manual configuration of VCTR GOOSE data set is required. Notethat both data value attributes and quality attributes have to bemapped. The following data objects must be configured:

• BusV• LodAIm• LodARe• PosRel• SetV• VCTRStatus• X2

The transformers controlled in parallel with the circulating current method or themaster-follower method must be assigned unique identities. These identities areentered as a setting in each TR8ATCC, and they are predefined as T1, T2, T3,T4( transformers 1 to 4). In figure 143 there are three transformers with the parameterTrfId set to T1, T2 and T3, respectively.

For parallel control with the circulating current method or the master-followermethod alternatively, the same type of data set as described above, must beexchanged between two TR8ATCC. To achieve this, each TR8ATCC istransmitting its own data set on the output ATCCOUT as previously mentioned. Toreceive data from the other transformers in the parallel group, the outputATCCOUT from each transformer must be connected (via GOOSE or internally inthe application configuration) to the inputs HORIZx (x = identifier for the othertransformers in the parallel group) on TR8ATCC function block. Apart from this,there is also a setting in each TR8ATCC T1RXOP=Off/On,..., T4RXOP=Off/On.This setting determines from which of the other transformer individuals that datashall be received. Settings in the three TR8ATCC blocks for the transformers infigure 143, would then be according to the table 24:

Table 24: Setting of TxRXOP

TrfId=T1 T1RXOP=Off T2RXOP=On T3RXOP=On T4RXOP=Off

TrfId=T2 T1RXOP=On T2RXOP=Off T3RXOP=On T4RXOP=Off

TrfId=T3 T1RXOP=On T2RXOP=On T3RXOP=Off T4RXOP=Off

Observe that this parameter must be set to Off for the “own” transformer. (fortransformer with identity T1 parameter T1RXOP must be set to Off, and so on.

Blocking

1MRK 504 134-UEN - Section 12Control

283Application Manual

Page 290: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Blocking conditionsThe purpose of blocking is to prevent the tap changer from operating underconditions that can damage it, or otherwise when the conditions are such thatpower system related limits would be exceeded or when, for example theconditions for automatic control are not met.

For the Automatic voltage control for tap changer function, TR8ATCC for parallelcontrol, three types of blocking are used:

Partial Block: Prevents operation of the tap changer only in one direction (onlyURAISE or ULOWER command is blocked) in manual and automatic control mode.

Auto Block: Prevents automatic voltage regulation, but the tap changer can still becontrolled manually.

Total Block: Prevents any tap changer operation independently of the controlmode (automatic as well as manual).

Setting parameters for blocking that can be set in TR8ATCC under general settingsin local HMI are listed in table 25.

Table 25: Blocking settings

Setting Values (Range) DescriptionOCBk(automaticallyreset)

AlarmAuto BlockAuto&Man Block

When any one of the three HV currents exceeds thepreset value IBlock, TR8ATCC will be temporarily totallyblocked. The outputs IBLK and TOTBLK or AUTOBLK willbe activated depending on the actual parameter setting.

OVPartBk(automaticallyreset)

AlarmAuto&Man Block

If the busbar voltage UB (not the compensated load pointvoltage UL) exceeds Umax (see figure 135, furtherURAISE commands will be blocked if the valueAuto&Man Block is selected. If permitted by setting, a faststep down action will be initiated in order to re-enter intothe range Umin < UB < Umax. The Fast Step downfunction can be set active for automatic control orautomatic as well as manual control and it is blockedwhen the lowest voltage tap position is reached. The timedelay for the fast step down function is separately set.The output UHIGH will be activated as long as the voltageis above Umax.

UVPartBk(automaticallyreset)

AlarmAuto&Man Block

If the busbar voltage UB (not the calculated load pointvoltage UL) is between Ublock and Umin (see figure 135),further ULOWER commands will be blockedindependently of the control mode when the valueAuto&Man Block is selected. The output ULOW will be set.

UVBk(automaticallyreset)

AlarmAuto BlockAuto&Man Block

If the busbar voltage UB falls below Ublock this blockingcondition is active. It is recommended to block automaticcontrol in this situation and allow manual control. This isbecause the situation normally would correspond to adisconnected transformer and then it should be allowed tooperate the tap changer before reconnecting thetransformer. The outputs UBLK and TOTBLK orAUTOBLK will be activated depending on the actualparameter setting.

Table continues on next page

Section 12 1MRK 504 134-UEN -Control

284Application Manual

Page 291: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Setting Values (Range) DescriptionCmdErrBk(manually reset)

AlarmAuto BlockAuto&Man Block

Typical operating time for a tap changer mechanism isaround 3-8 seconds. Therefore, the function should waitfor a position change before a new command is issued.The command error signal, CMDERRAL on theTCMYLTC function block, will be set if the tap changerposition does not change one step in the correct directionwithin the time given by the setting tTCTimeout inTCMYLTC function block. The tap changer moduleTCMYLTC will then indicate the error until a successfulcommand has been carried out or it has been reset bychanging control mode of TR8ATCC function to Manualand then back to Automatic. The outputs CMDERRAL onTCMYLTC and TOTBLK or AUTOBLK on TR8ATCC willbe activated depending on the actual parameter setting.This error condition can be reset by the input RESETERRon TCMYLTC function block, or alternatively by changingcontrol mode of TR8ATCC function to Manual and thenback to Automatic.

TapChgBk(manually reset

AlarmAuto BlockAuto&Man Block

If the input TCINPROG of TCMYLTC function block isconnected to the tap changer mechanism, then thisblocking condition will be active if the TCINPROG inputhas not reset when the tTCTimeout timer has timed out.The output TCERRAL will be activated depending on theactual parameter setting. In correct operation theTCINPROG shall appear during the URAISE/ULOWERoutput pulse and disappear before the tTCTimeout timehas elapsed.This error condition can be reset by the input RESETERRon TCMYLTC function block, or alternatively by changingcontrol mode of TR8ATCC function to Manual and thenback to Automatic.

Table continues on next page

1MRK 504 134-UEN - Section 12Control

285Application Manual

Page 292: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Setting Values (Range) DescriptionTapPosBk(automaticallyreset/manuallyreset)

AlarmAuto BlockAuto&Man Block

This blocking/alarm is activated by either:

1. The tap changer reaching an end position i.e. one ofthe extreme positions according to the settingparameters LowVoltTapand HighVoltTap. When thetap changer reaches one of these two positionsfurther commands in the corresponding direction willbe blocked. Effectively this will then be a partialblock if Auto Block or Auto&Man Blockis set. Theoutputs POSERRAL and LOPOSAL or HIPOSALwill be activated.

2. Tap Position Error which in turn can be caused byone of the following conditions:

• Tap position is out of range that is, the indicatedposition is above or below the end positions.

• The tap changer indicates that it has changed morethan one position on a single raise or lower command.

• The tap position reading shows a BCD code error(unaccepted combination) or a parity fault.

• Indication of hardware fault on BIO or AIM module.Supervision of the input hardware module isprovided by connecting the corresponding errorsignal to the INERR input (input module error) orBIERR on TCMYLTC function block.

• Interruption of communication with the tap changer.

The outputs POSERRAL and AUTOBLK or TOTBLK willbe set.This error condition can be reset by the input RESETERRon TCMYLTCfunction block, or alternatively by changingcontrol mode of TR8ATCC function to Manual and thenback to Automatic.

CircCurrBk(automaticallyreset)

AlarmAuto BlockAuto&Man Block

When the magnitude of the circulating current exceedsthe preset value (setting parameter CircCurrLimit) forlonger time than the set time delay (setting parametertCircCurr) it will cause this blocking condition to be fulfilledprovided that the setting parameter OperCCBlock is On.The signal resets automatically when the circulatingcurrent decreases below the preset value. Usually thiscan be achieved by manual control of the tap changers.TR8ATCC outputs ICIRC and TOTBLK or AUTOBLK willbe activated depending on the actual parameter setting.

MFPosDiffBk(manually reset)

AlarmAuto Block

In the master-follower mode, if the tap difference betweena follower and the master is greater than the set value(setting parameter MFPosDiffLim) then this blockingcondition is fulfilled and the outputs OUTOFPOS andAUTOBLK (alternatively an alarm) will be set.

Setting parameters for blocking that can be set in TR8ATCC under setting groupNx in local HMI are listed in table 26.

Section 12 1MRK 504 134-UEN -Control

286Application Manual

Page 293: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Table 26: Blocking settings

Setting Value (Range) DescriptionTotalBlock (manually reset) On/Off TR8ATCC function can be totally

blocked via the settingparameter TotalBlock, which canbe set On/Off from the localHMI . The output TOTBLK willbe activated.

AutoBlock (manually reset) On/Off TR8ATCC function can beblocked for automatic control viathe setting parameter AutoBlock,which can be set On/Off fromthe local HMI . The outputAUTOBLK will be set.

TR8ATCC blockings that can be made via input signals in the function block arelisted in table 27.

Table 27: Blocking via binary inputs

Input name Activation DescriptionBLOCK (manually reset) On/Off(via binary input) The voltage control function can

be totally blocked via the binaryinput BLOCK on TR8ATCCfunction block. The outputTOTBLK will be activated.

EAUTOBLK (manually reset) On/Off(via binary input) The voltage control function canbe blocked for automatic controlvia the binary input EAUTOBLKon TR8ATCC function block.The output AUTOBLK will beactivated. Deblocking is madevia the input DEBLKAUT.

Blockings activated by the operating conditions and there are no setting or separateexternal activation possibilities are listed in table 28.

1MRK 504 134-UEN - Section 12Control

287Application Manual

Page 294: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Table 28: Blockings without setting possibilities

Activation Type of blocking DescriptionDisconnectedtransformer(automatically reset)

Auto Block Automatic control is blocked for a transformer whenparallel control with the circulating current method isused, and that transformer is disconnected from theLV-busbar. . The binary input signal DISC inTR8ATCC function shall be used to supervise if thetransformer LV circuit breaker is closed or not. Theoutputs TRFDISC and AUTOBLK will be activated .Blocking will be removed when the transformer isreconnected (input signal DISC set back to zero).

No Master/More thanone Master(automatically reset)

Auto Block Automatic control is blocked when parallel controlwith the master-follower method is used, and themaster is disconnected from the LV-busbar. Also ifthere for some reason should be a situation withmore than one master in the system, the sameblocking will occur. The binary input signal DISC inTR8ATCC function shall be used to supervise if thetransformer LV circuit breaker is closed or not. Theoutputs TRFDISC, MFERR and AUTOBLK will beactivated. The followers will also be blocked bymutual blocking in this situation. Blocking will beremoved when the transformer is reconnected (inputsignal DISC set back to zero).

One transformer in aparallel group switchedto manual control(automatically reset)

Auto Block When the setting OperationAdapt is “Off”, automaticcontrol will be blocked when parallel control with themaster-follower or the circulating current method isused, and one of the transformers in the group isswitched from auto to manual. The output AUTOBLKwill be activated.

Communication error(COMMERR) (automaticdeblocking)

Auto block If the horizontal communication (GOOSE) for any oneof TR8ATCCs in the group fails it will cause blockingof automatic control in all TR8ATCC functions, whichbelong to that parallel group. This error condition willbe reset automatically when the communication is re-established. The outputs COMMERR and AUTOBLKwill be set.

Circulating current method

Mutual blockingWhen one parallel instance of voltage control TR8ATCC blocks its operation, allother TR8ATCCs working in parallel with that module, shall block their operationas well. To achieve this, the affected TR8ATCC function broadcasts a mutualblock to the other group members. When mutual block is received from any of thegroup members, automatic operation is blocked in the receiving TR8ATCCs thatis, all units of the parallel group.

The following conditions in any one of TR8ATCCs in the group will cause mutualblocking when the circulating current method is used:

• Over-Current• Total block via settings• Total block via configuration• Analog input error• Automatic block via settings

Section 12 1MRK 504 134-UEN -Control

288Application Manual

Page 295: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

• Automatic block via configuration• Under-Voltage• Command error• Position indication error• Tap changer error• Circulating current• Communication error

Master-follower methodWhen the master is blocked, the followers will not tap by themselves and there isconsequently no need for further mutual blocking. On the other hand, when afollower is blocked there is a need to send a mutual blocking signal to the master.This will prevent a situation where the rest of the group otherwise would be able totap away from the blocked individual, and that way cause high circulating currents.

Thus, when a follower is blocked, it broadcasts a mutual block on the horizontalcommunication. The master picks up this message, and blocks its automaticoperation as well.

Besides the conditions listed above for mutual blocking with the circulating currentmethod, the following blocking conditions in any of the followers will also causemutual blocking:

• Master-follower out of position• Master-follower error (No master/More than one master)

GeneralIt should be noted that partial blocking will not cause mutual blocking.

TR8ATCC, which is the “source” of the mutual blocking will set its AUTOBLKoutput as well as the output which corresponds to the actual blocking condition forexample, IBLK for over-current blocking. The other TR8ATCCs that receive amutual block signal will only set its AUTOBLK output.

The mutual blocking remains until TR8ATCC that dispatched the mutual blocksignal is de-blocked. Another way to release the mutual blocking is to forceTR8ATCC, which caused mutual blocking to Single mode operation. This is doneby activating the binary input SNGLMODE on TR8ATCC function block or bysetting the parameter OperationPAR to Off from the built-in local HMI .

TR8ATCC function can be forced to single mode at any time. It will then behaveexactly the same way as described in section "Automatic voltage control for asingle transformer", except that horizontal communication messages are still sentand received, but the received messages are ignored. TR8ATCC is at the same timealso automatically excluded from the parallel group.

Disabling of blockings in special situations

1MRK 504 134-UEN - Section 12Control

289Application Manual

Page 296: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

When the Automatic voltage control for tap changer TR8ATCC for parallelcontrol, function block is connected to read back information (tap position valueand tap changer in progress signal) it may sometimes be difficult to find timingdata to be set in TR8ATCC for proper operation. Especially at commissioning offor example, older transformers the sensors can be worn and the contacts maybebouncing etc. Before the right timing data is set it may then happen that TR8ATCCbecomes totally blocked or blocked in auto mode because of incorrect settings. Inthis situation, it is recommended to temporarily set these types of blockings toalarm instead until the commissioning of all main items are working as expected.

Hunting detectionHunting detection is provided in order to generate an alarm when the voltagecontrol gives an abnormal number of commands or abnormal sequence ofcommands within a pre-defined period of time.

There are three hunting functions:

1. The Automatic voltage control for tap changer function, TR8ATCC forparallel control will activate the output signal DAYHUNT when the number oftap changer operations exceed the number given by the setting DayHuntDetectduring the last 24 hours (sliding window). Active as well in manual as inautomatic mode.

2. TR8ATCC function will activate the output signal HOURHUNT when thenumber of tap changer operations exceed the number given by the settingHourHuntDetect during the last hour (sliding window). Active as well inmanual as in automatic mode.

3. TR8ATCC function will activate the output signal HUNTING when the totalnumber of contradictory tap changer operations (RAISE, LOWER, RAISE,LOWER, and so on) exceeds the pre-set value given by the settingNoOpWindow within the time sliding window specified via the settingparameter tWindowHunt. Only active in automatic mode.

Hunting can be the result of a narrow deadband setting or some other abnormalitiesin the control system.

Wearing of the tap changer contactsTwo counters, ContactLife and NoOfOperations are available within the Tapchanger control and supervision function, 6 binary inputs TCMYLTC. They can beused as a guide for maintenance of the tap changer mechanism. The ContactLifecounter represents the remaining number of operations (decremental counter) atrated load.

ContactLife ContactLifen+1 n Irated

Iloada

æ ö= - ç ÷ç ÷

è øEQUATION1873 V2 EN (Equation 124)

Section 12 1MRK 504 134-UEN -Control

290Application Manual

Page 297: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

where n is the number of operations and α is an adjustable setting parameter,CLFactor, with default value is set to 2. With this default setting an operation atrated load (current measured on HV-side) decrements the ContactLife counter with1.

The NoOfOperations counter simply counts the total number of operations(incremental counter).

Both counters are stored in a non-volatile memory as well as, the times and dates oftheir last reset. These dates are stored automatically when the command to reset thecounter is issued. It is therefore necessary to check that the IED internal time iscorrect before these counters are reset. The counter value can be reset on the localHMI under Main menu/Clear/Clear counters/TCMLYTC (84)/n:TCMYLTC/ContLifeCounter

Both counters and their last reset dates are shown on the local HMI as servicevalues CLCNT_VAL and CNT_VAL under Main menu/Tests/Function status/Control/TCMYLTC (84)/n:TCMYLTC/Outputs/CLCNT_VAL and Mainmenu/Tests/Function status/Control/TCMYLTC (84)/n:TCMYLTC/Outputs/CNT_VAL

12.3.3 Setting guidelines

12.3.3.1 TR8ATCC general settings

Base IED values for primary current (setting IBase), primary voltage (settingUBase) and primary power (setting SBase) for a particular winding are set in aGlobal base values for settings function GBASVAL. Settings GlobalBaseSel1 andGlobalBaseSel2 are used to select the corresponding GBASVAL function forreference of base values.

TrfId: The transformer identity is used to identify transformer individuals in aparallel group. Thus, transformers that can be part of the same parallel group musthave unique identities. Moreover, all transformers that communicate over the samehorizontal communication (GOOSE) must have unique identities.

Xr2: The reactance of the transformer in primary ohms referred to the LV side.

tAutoMSF: Time delay set in a follower for execution of a raise or lower commandgiven from a master. This feature can be used when a parallel group is controlled inthe master-follower mode, follow tap, and it is individually set for each follower,which means that different time delays can be used in the different followers inorder to avoid simultaneous tapping if this is wanted. It shall be observed that it isnot applicable in the follow command mode.

OperationAdapt: This setting enables or disables adapt mode for parallel controlwith the circulating current method or the master-follower method.

MFMode: Selection of Follow Command or Follow Tap in the master-follower mode.

1MRK 504 134-UEN - Section 12Control

291Application Manual

Page 298: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

CircCurrBk: Selection of action to be taken in case the circulating current exceedsCircCurrLimit.

CmdErrBk: Selection of action to be taken in case the feedback from the tapchanger has resulted in command error.

OCBk: Selection of action to be taken in case any of the three phase currents on theHV-side has exceeded Iblock.

MFPosDiffBk: Selection of action to be taken in case the tap difference between afollower and the master is greater than MFPosDiffLim.

OVPartBk: Selection of action to be taken in case the busbar voltage UB exceedsUmax.

TapChgBk: Selection of action to be taken in case a Tap Changer Error has beenidentified.

TapPosBk: Selection of action to be taken in case of Tap Position Error, or if thetap changer has reached an end position.

UVBk: Selection of action to be taken in case the busbar voltage UB falls belowUblock.

UVPartBk: Selection of action to be taken in case the busbar voltage UB is betweenUblock and Umin.

12.3.3.2 TR8ATCC Setting group

GeneralOperation: Switching automatic voltage control for tap changer, TR8ATCCfunction On/Off.

MeasMode: Selection of single phase, or phase-phase, or positive sequencequantity to be used for voltage and current measurement on the LV-side. Theinvolved phases are also selected. Thus, single phase as well as phase-phase or three-phase feeding on the LV-side is possible but it is commonly selected for currentand voltage.

TotalBlock: When this setting is On, TR8ATCC function that is, the voltage controlis totally blocked for manual as well as automatic control.

AutoBlock: When this setting is On, TR8ATCC function that is, the voltage controlis blocked for automatic control.

OperationFSDMode: This setting enables/disables the fast step down function. Enabling canbe for automatic and manual control, or for only automatic control alternatively.

tFSD: Time delay to be used for the fast step down tapping.

Section 12 1MRK 504 134-UEN -Control

292Application Manual

Page 299: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

VoltageUSet: Setting value for the target voltage, to be set in per cent of UBase.

UDeadband: Setting value for one half of the outer deadband, to be set in per centof UBase. The deadband is symmetrical around USet, see section "Automaticvoltage control for a single transformer", figure 135. In that figure UDeadband isequal to DU. The setting is normally selected to a value near the powertransformer’s tap changer voltage step (typically 75 - 125% of the tap changer step).

UDeadbandInner: Setting value for one half of the inner deadband, to be set in percent of UBase. The inner deadband is symmetrical around USet, see section"Automatic voltage control for a single transformer",figure 135. In that figureUDeadbandInner is equal to DUin. The setting shall be smaller than UDeadband.Typically the inner deadband can be set to 25-70% of the UDeadband value.

Umax: This setting gives the upper limit of permitted busbar voltage (see section"Automatic voltage control for a single transformer", figure 135). It is set in percent of UBase. If OVPartBk is set to Auto&ManBlock, then busbar voltages aboveUmax will result in a partial blocking such that only lower commands are permitted.

Umin This setting gives the lower limit of permitted busbar voltage (see section"Automatic voltage control for a single transformer", figure 135). It is set in percent of UBase. If UVPartBk is set to Auto&ManBlock, then busbar voltages belowUmin will result in a partial blocking such that only raise commands are permitted.

Ublock: Voltages below Ublock normally correspond to a disconnected transformerand therefore it is recommended to block automatic control for this condition(setting UVBk). Ublock is set in per cent of UBase.

Timet1Use: Selection of time characteristic (definite or inverse) for t1.

t1: Time delay for the initial (first) raise/lower command.

t2Use: Selection of time characteristic (definite or inverse) for t2.

t2: Time delay for consecutive raise/lower commands. In the circulating currentmethod, the second, third, etc. commands are all executed with time delay t2independently of which transformer in the parallel group that is tapping. In the master-follower method with the follow tap option, the master is executing the second,third, etc. commands with time delay t2. The followers on the other hand read themaster’s tap position, and adapt to that with the additional time delay given by thesetting tAutoMSF and set individually for each follower.

tMin: The minimum operate time when inverse time characteristic is used (seesection "Time characteristic", figure 136).

Line voltage drop compensation (LDC)OpertionLDC: Sets the line voltage drop compensation function On/Off.

1MRK 504 134-UEN - Section 12Control

293Application Manual

Page 300: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

OperCapaLDC: This setting, if set On, will permit the load point voltage to begreater than the busbar voltage when line voltage drop compensation is used. Thatsituation can be caused by a capacitive load. When the line voltage dropcompensation function is used for parallel control with the reverse reactancemethod, then OperCapaLDC must always be set On.

Rline and Xline: For line voltage drop compensation, these settings give the lineresistance and reactance from the station busbar to the load point. The settings forRline and Xline are given in primary system ohms. If more than one line isconnected to the LV busbar, equivalent Rline and Xline values should becalculated and given as settings.

When the line voltage drop compensation function is used for parallel control withthe reverse reactance method, then the compensated voltage which is designated“load point voltage” UL is effectively an increase in voltage up into thetransformer. To achieve this voltage increase, Xline must be negative. Thesensitivity of the parallel voltage regulation is given by the magnitude of Rline andXline settings, with Rline being important in order to get a correct control of thebusbar voltage. This can be realized in the following way. Figure 137 shows thevector diagram for a transformer controlled in a parallel group with the reversereactance method and with no circulation (for example, assume two equaltransformers on the same tap position). The load current lags the busbar voltage UBwith the power factor j and the argument of the impedance Rline and Xline isdesignated j1.

Load voltage adjustment (LVA)LVAConst1: Setting of the first load voltage adjustment value. This adjustment ofthe target value USet is given in percent of UBase.

LVAConst2: Setting of the second load voltage adjustment value. This adjustmentof the target value USet is given in percent ofUBase.

LVAConst3: Setting of the third load voltage adjustment value. This adjustment ofthe target value USet is given in percent of UBase.

LVAConst4: Setting of the fourth load voltage adjustment value. This adjustment ofthe target value USet is given in percent of UBase.

VRAuto: Setting of the automatic load voltage adjustment. This adjustment of thetarget valueUSet is given in percent of UBase, and it is proportional to the loadcurrent with the set value reached at the nominal current IBase (for winding 2which is defined in a global base function, selected with setting GlobalBaseSel2forTR8ATCC).

Tap changer control (TCCtrl)Iblock: Current setting of the over current blocking function. In case, thetransformer is carrying a current exceeding the rated current of the tap changer forexample, because of an external fault. The tap changer operations shall be

Section 12 1MRK 504 134-UEN -Control

294Application Manual

Page 301: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

temporarily blocked. This function typically monitors the three phase currents onthe HV side of the transformer.

DayHuntDetect: Setting of the number of tap changer operations required duringthe last 24 hours (sliding window) to activate the signal DAYHUNT

HourHuntDetect: Setting of the number of tap changer operations required duringthe last hour (sliding window) to activate the signal HOURHUNT

tWindowHunt: Setting of the time window for the window hunting function. Thisfunction is activated when the number of contradictory commands to the tapchanger exceeds the specified number given by NoOpWindow within the timetWindowHunt.

NoOpWindow: Setting of the number of contradictory tap changer operations(RAISE, LOWER, RAISE, LOWER etc.) required during the time windowtWindowHunt to activate the signal HUNTING.

PowerP>: When the active power exceeds the value given by this setting, the outputPGTFWD will be activated after the time delay tPower. It shall be noticed that thesetting is given with sign, which effectively means that a negative value of P>means an active power greater than a value in the reverse direction. This is shownin figure 144 where a negative value of P> means pickup for all values to the rightof the setting. Reference is made to figure 142 for definition of forward and reversedirection of power through the transformer.

en06000634_2_en.vsd

PP>

IEC06000634 V2 EN

Figure 144: Setting of a negative value for P>

P<: When the active power falls below the value given by this setting, the outputPLTREV will be activated after the time delay tPower. It shall be noticed that thesetting is given with sign, which effectively means that, for example a positivevalue of P< means an active power less than a value in the forward direction. Thisis shown in figure 145 where a positive value of P< means pickup for all values tothe left of the setting. Reference is made to figure 142 for definition of forward andreverse direction of power through the transformer.

1MRK 504 134-UEN - Section 12Control

295Application Manual

Page 302: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

en06000635_2_en.vsd

PP<

IEC06000635 V2 EN

Figure 145: Setting of a positive value for P<

Q>: When the reactive power exceeds the value given by this setting, the outputQGTFWD will be activated after the time delay tPower. It shall be noticed that thesetting is given with sign, which effectively means that the function picks up for allvalues of reactive power greater than the set value, similar to the functionality forP>.

Q<: When the reactive power in reverse direction falls below the value given bythis setting, the output QLTREV will be activated after the time delay tPower. Itshall be noticed that the setting is given with sign, which effectively means that thefunction picks up for all values of reactive power less than the set value, similar tothe functionality for P<.

tPower: Time delay for activation of the power monitoring output signals(PGTFWD, PLTREV, QGTFWD and QLTREV).

Parallel control (ParCtrl)OperationPAR: Setting of the method for parallel operation.

OperCCBlock: This setting enables/disables blocking if the circulating currentexceeds CircCurrLimit.

CircCurrLimit: Pick up value for the circulating current blocking function. Thesetting is made in percent of IBase (for winding 2 which is defined in a global basefunction, selected with setting GlobalBaseSel2 for TR8ATCC).

tCircCurr: Time delay for the circulating current blocking function.

Comp: When parallel operation with the circulating current method is used, thissetting increases or decreases the influence of the circulating current on the regulation.

If the transformers are connected to the same bus on the HV- as well as the LV-side, Comp can be calculated with the following formula which is valid for anynumber of two-winding transformers in parallel, irrespective if the transformers areof different size and short circuit impedance.

2 UComp a 100%n p´D

= ´ ´´

EQUATION1941 V1 EN (Equation 125)

Section 12 1MRK 504 134-UEN -Control

296Application Manual

Page 303: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

where:

• DU is the deadband setting in percent.

• n denotes the desired number of difference in tap position between thetransformers, that shall give a voltage deviation Udi which corresponds to thedead-band setting.

• p is the tap step (in % of transformer nominal voltage).

• a is a safety margin that shall cover component tolerances and other non-linearmeasurements at different tap positions (for example, transformer reactanceschanges from rated value at the ends of the regulation range). In most cases avalue of a = 1.25 serves well.

This calculation gives a setting of Comp that will always initiate an action (starttimer) when the transformers have n tap positions difference.

OperSimTap: Enabling/disabling the functionality to allow only one transformer ata time to execute a Lower/Raise command. This setting is applicable only to thecirculating current method, and when enabled, consecutive tap changes of the nexttransformer (if required) will be separated with the time delay t2.

OperUsetPar: Enables/disables the use of a common setting for the target voltageUSet. This setting is applicable only to the circulating current method, and whenenabled, a mean value of the USet values for the transformers in the same parallelgroup will be calculated and used.

VTmismatch: Setting of the level for activation of the output VTALARM in casethe voltage measurement in one transformer bay deviates to the mean value of allvoltage measurements in the parallel group.

tVTmismatch: Time delay for activation of the output VTALARM.

T1RXOP.......T4RXOP: This setting is set On for every transformer that canparticipate in a parallel group with the transformer in case. For this transformer(own transformer), the setting must always be Off.

TapPosOffs: This setting gives the tap position offset in relation to the master sothat the follower can follow the master’s tap position including this offset.Applicable when regulating in the follow tap command mode.

MFPosDiffLim: When the difference (including a possible offset according toTapPosOffs) between a follower and the master reaches the value in this setting,then the output OUTOFPOS in the Automatic voltage control for tap changer,parallel control TR8ATCC function block of the follower will be activated after thetime delay tMFPosDiff.

tMFPosDiff: Time delay for activation of the output OUTOFPOS.

1MRK 504 134-UEN - Section 12Control

297Application Manual

Page 304: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Transformer nameINSTNAME: This setting can be used for indicating in tools and the local HMI towhich transformer a certain instance of the function belongs.

12.3.3.3 TCMYLTC general settings

Base IED values for primary current (setting IBase), primary voltage (settingUBase) and primary power (setting SBase) for a particular winding are set in aGlobal base values for settings function GBASVAL. Settings GlobalBaseSel1 andGlobalBaseSel2 are used to select the corresponding GBASVAL function forreference of base values.

LowVoltTap: This gives the tap position for the lowest LV-voltage.

HighVoltTap: This gives the tap position for the highest LV-voltage.

CodeType: This setting gives the method of tap position reading.

UseParity: Sets the parity check On/Off for tap position reading when this is madeby Binary, BCD, or Gray code.

tStable: This is the time that needs to elapse after a new tap position has beenreported to TCMYLTC until it is accepted.

CLFactor: This is the factor designated “a” in equation 125. When a tap changeroperates at nominal load current(current measured on the HV-side), theContactLife counter decrements with 1, irrespective of the setting of CLFactor.The setting of this factor gives the weighting of the deviation with respect to theload current.

InitCLCounter: The ContactLife counter monitors the remaining number ofoperations (decremental counter). The setting InitCLCounter then gives the startvalue for the counter that is, the total number of operations at rated load that the tapchanger is designed for.

EnabTapCmd: This setting enables/disables the lower and raise commands to thetap changer. It shall be On for voltage control, and Off for tap position feedback tothe transformer differential protection T2WPDIF or T3WPDIF.

TCMYLTC Setting group

GeneralOperation: Switching the TCMYLTC function On/Off.

tTCTimeout: This setting gives the maximum time interval for a raise or lowercommand to be completed.

tPulseDur: Length of the command pulse (URAISE/ULOWER) to the tap changer.It shall be noticed that this pulse has a fixed extension of 4 seconds that adds to thesetting value of tPulseDur.

Section 12 1MRK 504 134-UEN -Control

298Application Manual

Page 305: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

12.4 Logic rotating switch for function selection andLHMI presentation SLGGIO

12.4.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Logic rotating switch for functionselection and LHMI presentation

SLGGIO - -

12.4.2 ApplicationThe logic rotating switch for function selection and LHMI presentation function(SLGGIO) (or the selector switch function block, as it is also known) is used to geta selector switch functionality similar with the one provided by a hardware multi-position selector switch. Hardware selector switches are used extensively byutilities, in order to have different functions operating on pre-set values. Hardwareswitches are however sources for maintenance issues, lower system reliability andextended purchase portfolio. The virtual selector switches eliminate all theseproblems.

SLGGIO function block has two operating inputs (UP and DOWN), one blockinginput (BLOCK) and one operator position input (PSTO).

SLGGIO can be activated both from the local HMI and from external sources(switches), via the IED binary inputs. It also allows the operation from remote (likethe station computer). SWPOSN is an integer value output, giving the actual outputnumber. Since the number of positions of the switch can be established by settings(see below), one must be careful in coordinating the settings with the configuration(if one sets the number of positions to x in settings – for example, there will beonly the first x outputs available from the block in the configuration). Also thefrequency of the (UP or DOWN) pulses should be lower than the setting tPulse.

The operation from local HMI is from select or indication buttons (32 positions).Typical applications are: Select operating modes for e.g. Auto reclose, Energizingcheck, Earth-fault protection (IN,UN). The output integer can be connected to anInteger to Binary function block to give the position as a boolean for use in theconfiguration.

12.4.3 Setting guidelinesThe following settings are available for the Logic rotating switch for functionselection and LHMI presentation (SLGGIO) function:

Operation: Sets the operation of the function On or Off.

1MRK 504 134-UEN - Section 12Control

299Application Manual

Page 306: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

NrPos: Sets the number of positions in the switch (max. 32). This setting influencethe behavior of the switch when changes from the last to the first position.

OutType: Steady or Pulsed.

tPulse: In case of a pulsed output, it gives the length of the pulse (in seconds).

tDelay: The delay between the UP or DOWN activation signal positive front andthe output activation.

StopAtExtremes: Sets the behavior of the switch at the end positions – if set toDisabled, when pressing UP while on first position, the switch will jump to the lastposition; when pressing DOWN at the last position, the switch will jump to the firstposition; when set to Enabled, no jump will be allowed.

12.5 Selector mini switch VSGGIO

12.5.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Selector mini switch VSGGIO - -

12.5.2 ApplicationSelector mini switch (VSGGIO) function is a multipurpose function used in theconfiguration tool in PCM600 for a variety of applications, as a general purposeswitch. VSGGIO can be used for both acquiring an external switch position(through the IPOS1 and the IPOS2 inputs) and represent it through the single linediagram symbols (or use it in the configuration through the outputs POS1 andPOS2) as well as, a command function (controlled by the PSTO input), givingswitching commands through the CMDPOS12 and CMDPOS21 outputs.

The output POSITION is an integer output, showing the actual position as aninteger number 0 – 3.

An example where VSGGIO is configured to switch Autorecloser on–off from abutton symbol on the local HMI is shown in figure 146. The I and O buttons on thelocal HMI are normally used for on–off operations of the circuit breaker.

Section 12 1MRK 504 134-UEN -Control

300Application Manual

Page 307: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

IEC07000112-2-en.vsd

PSTO

CMDPOS12

IPOS1

NAM_POS1NAM_POS2

IPOS2

CMDPOS21OFFON

VSGGIO

SMBRRECONOFF

SETON

INTONE

INVERTERINPUT OUT

IEC07000112 V2 EN

Figure 146: Control of Autorecloser from local HMI through Selector mini switch

12.5.3 Setting guidelinesSelector mini switch (VSGGIO) function can generate pulsed or steady commands(by setting the Mode parameter). When pulsed commands are generated, the lengthof the pulse can be set using the tPulse parameter. Also, being accessible on thesingle line diagram (SLD), this function block has two control modes (settablethrough CtlModel): Dir Norm and SBO Enh.

12.6 IEC61850 generic communication I/O functionsDPGGIO

12.6.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

IEC 61850 generic communication I/Ofunctions

DPGGIO - -

12.6.2 ApplicationThe IEC61850 generic communication I/O functions (DPGGIO) function block isused to send three logical outputs to other systems or equipment in the substation.The three inputs are named OPEN, CLOSE and VALID, since this function blockis intended to be used as a position indicator block in interlocking and reservationstation-wide logics.

12.6.3 Setting guidelinesThe function does not have any parameters available in the local HMI or PCM600.

1MRK 504 134-UEN - Section 12Control

301Application Manual

Page 308: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

12.7 Single point generic control 8 signals SPC8GGIO

12.7.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Single point generic control 8 signals SPC8GGIO - -

12.7.2 ApplicationThe Single point generic control 8 signals (SPC8GGIO) function block is acollection of 8 single point commands, designed to bring in commands fromREMOTE (SCADA) to those parts of the logic configuration that do not needcomplicated function blocks that have the capability to receive commands (forexample SCSWI). In this way, simple commands can be sent directly to the IEDoutputs, without confirmation. Confirmation (status) of the result of the commandsis supposed to be achieved by other means, such as binary inputs and SPGGIOfunction blocks.

PSTO is the universal operator place selector for all controlfunctions. Even if PSTO can be configured to allow LOCAL orALL operator positions, the only functional position usable with theSPC8GGIO function block is REMOTE.

12.7.3 Setting guidelinesThe parameters for the single point generic control 8 signals (SPC8GGIO) functionare set via the local HMI or PCM600.

Operation: turning the function operation On/Off.

There are two settings for every command output (totally 8):

Latchedx: decides if the command signal for output x is Latched (steady) or Pulsed.

tPulsex: if Latchedx is set to Pulsed, then tPulsex will set the length of the pulse (inseconds).

Section 12 1MRK 504 134-UEN -Control

302Application Manual

Page 309: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

12.8 Automation bits AUTOBITS

12.8.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

AutomationBits, command function forDNP3 AUTOBITS - -

12.8.2 ApplicationThe AUTOBITS function block (or the automation bits function block) is usedwithin PCM600 in order to get into the configuration the commands comingthrough the DNP3 protocol.AUTOBITS function block have 32 individual outputswhich each can be mapped as a Binary Output point in DNP3. The output isoperated by a "Object 12" in DNP3. This object contains parameters for control-code, count, on-time and off-time. To operate an AUTOBITS output point, send acontrol-code of latch-On, latch-Off, pulse-On, pulse-Off, Trip or Close. Theremaining parameters are regarded as appropriate. For example, pulse-On, on-time=100, off-time=300, count=5 would give 5 positive 100 ms pulses, 300 ms apart.

See the communication protocol manual for a detailed description of the DNP3protocol

12.8.3 Setting guidelinesAUTOBITS function block has one setting, (Operation: On/Off) enabling ordisabling the function. These names will be seen in the DNP communicationconfiguration tool in PCM600.

1MRK 504 134-UEN - Section 12Control

303Application Manual

Page 310: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

304

Page 311: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Section 13 Logic

13.1 Tripping logic common 3-phase output SMPPTRC

13.1.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Tripping logic common 3-phase output SMPPTRC

I->O

SYMBOL-K V1 EN

94

13.1.2 ApplicationAll trip signals from the different protection functions shall be routed through thetrip logic. In its simplest alternative the logic will only link the internal TRIPsignals to a binary output and make sure that the pulse length is long enough.

The tripping logic common 3-phase output (SMPPTRC) offers only three-phasetripping. A three-phase trip for all faults offers a simple solution and is oftensufficient in well meshed transmission systems and in High Voltage (HV) systems.

One SMPPTRC function block should be used for each breaker, if the object isconnected to the system via more than one breaker.

To prevent closing of a circuit breaker after a trip the function can block theclosing of the circuit breaker (trip lock-out).

13.1.2.1 Three-phase tripping

A simple application with three-phase tripping from the tripping logic common 3-phase output SMPPTRC utilizes part of the function block. Connect the inputsfrom the protection function blocks to the input TRIN. If necessary (normally thecase) use the trip matrix logic TMAGGIO to combine the different function outputsto this input. Connect the output TRIP to the required binary outputs.

A typical connection is shown below in figure 147.

1MRK 504 134-UEN - Section 13Logic

305Application Manual

Page 312: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

IEC11000054-1-en.vsd

IEC11000054 V1 EN

Figure 147: Tripping logic common 3-phase output SMPPTRC is used for asimple three-phase tripping application

13.1.2.2 Lock-out

This function block is provided with possibilities to initiate lock-out. The lock-outcan be set to only activate the block closing output CLLKOUT or initiate the blockclosing output and also maintain the trip signal (latched trip).

The lock-out can then be manually reset after checking the primary fault byactivating the input reset Lock-Out RSTLKOUT or via the HMI.

If external conditions are required to initiate Lock-out but not initiate trip this canbe achieved by activating input SETLKOUT. The setting AutoLock = Off meansthat the internal trip will not activate lock-out so only initiation of the inputSETLKOUT will result in lock-out. This is normally the case for overhead lineprotection where most faults are transient. Unsuccessful autoreclose and back-upzone tripping can in such cases be connected to initiate Lock-out by activating theinput SETLKOUT.

13.1.2.3 Blocking of the function block

Blocking can be initiated internally by logic, or by the operator using acommunication channel. Total blockage of Tripping logic (SMPPTRC) function isdone by activating the input BLOCK and can be used to block the output ofSMPPTRC in the event of internal failures.

13.1.3 Setting guidelinesThe parameters for Tripping logic common 3-phase output SMPPTRC are set viathe local HMI or through the Protection and Control Manager (PCM600).

The following trip parameters can be set to regulate tripping.

Section 13 1MRK 504 134-UEN -Logic

306Application Manual

Page 313: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Operation: Sets the mode of operation. Off switches the function off. The normalselection is On.

TripLockout: Sets the scheme for lock-out. Off only activates the lock-out output.On activates the lock-out output and latches the output TRIP. The normal selectionis Off.

AutoLock: Sets the scheme for lock-out. Off only activates lock-out through theinput SETLKOUT. On additonally allows activation through the trip functionitself. The normal selection is Off.

tTripMin: Sets the required minimum duration of the trip pulse. It should be set toensure that the breaker is tripped correctly. Normal setting is 0.150s.

13.2 Trip matrix logic TMAGGIO

13.2.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Trip matrix logic TMAGGIO - -

13.2.2 ApplicationThe 12 Trip matrix logic TMAGGIO function each with 32 inputs are used to routetrip signals and other logical output signals to the tripping logics SMPPTRC andSPTPTRC or to different output contacts on the IED.

TMAGGIO 3 output signals and the physical outputs allows the user to adapt thesignals to the physical tripping outputs according to the specific application needsfor settable pulse or steady output.

13.2.3 Setting guidelinesOperation: Turns the operation of the function On/Off.

PulseTime: Defines the pulse time duration. When used for direct tripping ofcircuit breaker(s) the pulse time duration shall be set to approximately 0.150seconds in order to obtain satisfactory minimum duration of the trip pulse to thecircuit breaker trip coils. Used only for ModeOutputx: Pulsed.

OnDelay: Used to prevent output signals to be given for spurious inputs. Normallyset to 0 or a low value. Used only for ModeOutputx: Steady.

OffDelay: Defines a minimum on time for the outputs. When used for directtripping of circuit breaker(s) the off delay time shall be set to approximately 0.150

1MRK 504 134-UEN - Section 13Logic

307Application Manual

Page 314: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

seconds in order to obtain a satisfactory minimum duration of the trip pulse to thecircuit breaker trip coils. Used only for ModeOutputx: Steady.

ModeOutputx: Defines if output signal OUTPUTx (where x=1-3) is Steady orPulsed. A steady signal follows the status of the input signals, with respect to OnDelayand OffDelay. A pulsed signal will give a pulse once, when the Outputx risesfrom 0 to 1.

13.3 Configurable logic blocks

13.3.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

OR Function block OR - -

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Inverter function block INVERTER - -

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

PULSETIMER function block PULSETIMER - -

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Controllable gate function block GATE - -

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Exclusive OR function block XOR - -

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Logic loop delay function block LOOPDELAY - -

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Timer function block TIMERSET - -

Section 13 1MRK 504 134-UEN -Logic

308Application Manual

Page 315: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

AND function block AND - -

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Set-reset memory function block SRMEMORY - -

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Reset-set with memory function block RSMEMORY - -

13.3.2 ApplicationA set of standard logic blocks, like AND, OR etc, and timers are available foradapting the IED configuration to the specific application needs.

There are no settings for AND gates, OR gates, inverters or XOR gates.

For normal On/Off delay and pulse timers the time delays and pulse lengths are setfrom the local HMI or via the PST tool.

Both timers in the same logic block (the one delayed on pick-up and the onedelayed on drop-out) always have a common setting value.

For controllable gates, settable timers and SR flip-flops with memory, the settingparameters are accessible via the local HMI or via the PST tool.

13.3.3.1 Configuration

Logic is configured using the ACT configuration tool in PCM600.

Execution of functions as defined by the configurable logic blocks runs accordingto a fixed sequence with different cycle times.

For each cycle time, the function block is given an serial execution number. This isshown when using the ACT configuration tool with the designation of the functionblock and the cycle time, see example below.

1MRK 504 134-UEN - Section 13Logic

309Application Manual

Page 316: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

IEC09000695_2_en.vsdIEC09000695 V2 EN

Figure 148: Example designation, serial execution number and cycle time forlogic function

The execution of different function blocks within the same cycle is determined bythe order of their serial execution numbers. Always remember this whenconnecting two or more logical function blocks in series.

Always be careful when connecting function blocks with a fastcycle time to function blocks with a slow cycle time.Remember to design the logic circuits carefully and always checkthe execution sequence for different functions. In other cases,additional time delays must be introduced into the logic schemes toprevent errors, for example, race between functions.Default value on all four inputs of the AND gate are logical 1which makes it possible for the user to just use the required numberof inputs and leave the rest un-connected. The output OUT has adefault value 0 initially, which will suppress one cycle pulse if thefunction has been put in the wrong execution order.

13.4 Fixed signals FXDSIGN

13.4.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Fixed signals FXDSIGN - -

13.4.2 ApplicationThe Fixed signals function FXDSIGN generates nine pre-set (fixed) signals thatcan be used in the configuration of an IED, either for forcing the unused inputs inother function blocks to a certain level/value, or for creating certain logic. Boolean,integer, floating point, string types of signals are available.

Section 13 1MRK 504 134-UEN -Logic

310Application Manual

Page 317: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Example for use of GRP_OFF signal in FXDSIGNThe Restricted earth fault function REFPDIF can be used both for auto-transformers and normal transformers.

When used for auto-transformers, information from both windings parts, togetherwith the neutral point current, needs to be available to the function. This means thatthree inputs are needed.

I3PW1CT1I3PW2CT1 I3P

REFPDIF

IEC09000619_3_en.vsdIEC09000619 V3 EN

Figure 149: REFPDIF function inputs for autotransformer application

For normal transformers only one winding and the neutral point is available. Thismeans that only two inputs are used. Since all group connections are mandatory tobe connected, the third input needs to be connected to something, which is theGRP_OFF signal in FXDSIGN function block.

I3PW1CT1I3PW2CT1 I3P

REFPDIF

GRP_OFFFXDSIGN

IEC09000620_3_en.vsdIEC09000620 V3 EN

Figure 150: REFPDIF function inputs for normal transformer application

13.5 Boolean 16 to integer conversion B16I

13.5.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Boolean 16 to integer conversion B16I - -

1MRK 504 134-UEN - Section 13Logic

311Application Manual

Page 318: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

13.5.2 ApplicationBoolean 16 to integer conversion function B16I is used to transform a set of 16binary (logical) signals into an integer. It can be used – for example, to connectlogical output signals from a function (like distance protection) to integer inputsfrom another function (like line differential protection). B16I does not have alogical node mapping.

13.5.3 Setting guidelinesThe function does not have any parameters available in Local HMI or Protectionand Control IED Manager (PCM600).

13.6 Boolean 16 to integer conversion with logic noderepresentation B16IFCVI

13.6.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Boolean 16 to integer conversion withlogic node representation

B16IFCVI - -

13.6.2 ApplicationBoolean 16 to integer conversion with logic node representation functionB16IFCVI is used to transform a set of 16 binary (logical) signals into an integer.B16IFCVI can receive an integer from a station computer – for example, over IEC61850–8–1. These functions are very useful when you want to generate logicalcommands (for selector switches or voltage controllers) by inputting an integernumber. B16IFCVI has a logical node mapping in IEC 61850.

13.6.3 Setting guidelinesThe function does not have any parameters available in the local HMI or Protectionand Control IED Manager (PCM600).

Section 13 1MRK 504 134-UEN -Logic

312Application Manual

Page 319: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

13.7 Integer to boolean 16 conversion IB16A

13.7.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Integer to boolean 16 conversion IB16A - -

13.7.2 ApplicationInteger to boolean 16 conversion function (IB16A) is used to transform an integerinto a set of 16 binary (logical) signals. It can be used – for example, to connectinteger output signals from one function to binary (logical) inputs to anotherfunction. IB16A function does not have a logical node mapping.

13.7.3 Setting guidelinesThe function does not have any parameters available in the local HMI or Protectionand Control IED Manager (PCM600).

13.8 Integer to boolean 16 conversion with logic noderepresentation IB16FCVB

13.8.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Integer to boolean 16 conversion withlogic node representation

IB16FCVB - -

13.8.2 ApplicationInteger to boolean 16 conversion with logic node representation function(IB16FCVB) is used to transform an integer into a set of 16 binary (logical)signals. IB16FCVB function can receive an integer from a station computer – forexample, over IEC 61850–8–1. These functions are very useful when the userwants to generate logical commands (for selector switches or voltage controllers)by inputting an integer number. IB16FCVB function has a logical node mapping inIEC 61850.

1MRK 504 134-UEN - Section 13Logic

313Application Manual

Page 320: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

13.8.3 SettingsThe function does not have any parameters available in the local HMI or Protectionand Control IED Manager (PCM600)

13.9 Elapsed time integrator with limit transgression andoverflow supervision TEIGGIO

13.9.1 IdentificationFunction Description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2 devicenumber

Elapsed time integrator TEIGGIO - -

13.9.2 ApplicationThe function TEIGGIO is used for user defined logics and it can also be used fordifferent purposes internally in the IED . An application example is the integrationof elapsed time during the measurement of neutral point voltage or neutral currentat earth fault conditions.

Settable time limits for warning and alarm are provided. The time limit foroverflow indication is fixed.

13.9.3 Setting guidelinesThe settings tAlarm and tWarning are user settable limits defined in seconds. Theachievable resolution of the settings depends on the level of the values defined.

A resolution of 10 ms can be achieved when the settings are defined within the range

1.00 second ≤ tAlarm ≤ 99 999.99 seconds

1.00 second ≤ tWarning ≤ 99 999.99 seconds.

If the values are above this range the resolution becomes lower

99 999.99 seconds ≤ tAlarm ≤ 999 999.9 seconds

99 999.99 seconds≤ tWarning ≤ 999 999.9 seconds

Note that tAlarm and tWarning are independent settings, that is,there is no check if tAlarm > tWarning.

Section 13 1MRK 504 134-UEN -Logic

314Application Manual

Page 321: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

tOverflow is for overflow supervision with a default value tOverflow = 999 999.9seconds. The outputs freeze if an overflow occurs.

1MRK 504 134-UEN - Section 13Logic

315Application Manual

Page 322: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

316

Page 323: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Section 14 Monitoring

14.1 IEC61850 generic communication I/O functionsSPGGIO

14.1.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

IEC 61850 generic communication I/Ofunctions

SPGGIO - -

14.1.2 ApplicationIEC 61850–8–1 generic communication I/O functions (SPGGIO) function is usedto send one single logical output to other systems or equipment in the substation. Ithas one visible input, that should be connected in ACT tool.

14.1.3 Setting guidelinesThe function does not have any parameters available in Local HMI or Protectionand Control IED Manager (PCM600).

14.2 IEC61850 generic communication I/O functions 16inputs SP16GGIO

14.2.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

IEC 61850 generic communication I/Ofunctions 16 inputs

SP16GGIO - -

14.2.2 ApplicationSP16GGIO function block is used to send up to 16 logical signals to other systemsor equipment in the substation. Inputs should be connected in ACT tool.

1MRK 504 134-UEN - Section 14Monitoring

317Application Manual

Page 324: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

14.2.3 Setting guidelinesThe function does not have any parameters available in Local HMI or Protectionand Control IED Manager (PCM600).

14.3 IEC61850 generic communication I/O functionsMVGGIO

14.3.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

IEC61850 generic communication I/Ofunctions

MVGGIO - -

14.3.2 ApplicationIEC61850 generic communication I/O functions (MVGGIO) function is used tosend the instantaneous value of an analog signal to other systems or equipment inthe substation. It can also be used inside the same IED, to attach a RANGE aspectto an analog value and to permit measurement supervision on that value.

14.3.3 Setting guidelinesThe settings available for IEC61850 generic communication I/O functions(MVGGIO) function allows the user to choose a deadband and a zero deadband forthe monitored signal. Values within the zero deadband are considered as zero.

The high and low limit settings provides limits for the high-high-, high, normal,low and low-low ranges of the measured value. The actual range of the measuredvalue is shown on the range output of MVGGIO function block. When a Measuredvalue expander block (MVEXP) is connected to the range output, the logicaloutputs of the MVEXP are changed accordingly.

Section 14 1MRK 504 134-UEN -Monitoring

318Application Manual

Page 325: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

14.4 Measurements

14.4.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Measurements CVMMXN

P, Q, S, I, U, f

SYMBOL-RR V1 EN

-

Phase current measurement CMMXU

I

SYMBOL-SS V1 EN

-

Phase-phase voltage measurement VMMXU

U

SYMBOL-UU V1 EN

-

Current sequence componentmeasurement

CMSQI

I1, I2, I0

SYMBOL-VV V1 EN

-

Voltage sequence measurement VMSQI

U1, U2, U0

SYMBOL-TT V1 EN

-

Phase-neutral voltage measurement VNMMXU

U

SYMBOL-UU V1 EN

-

14.4.2 ApplicationMeasurement functions is used for power system measurement, supervision andreporting to the local HMI, monitoring tool within PCM600 or to station level forexample, via IEC 61850. The possibility to continuously monitor measured valuesof active power, reactive power, currents, voltages, frequency, power factor etc. isvital for efficient production, transmission and distribution of electrical energy. Itprovides to the system operator fast and easy overview of the present status of thepower system. Additionally, it can be used during testing and commissioning ofprotection and control IEDs in order to verify proper operation and connection ofinstrument transformers (CTs and VTs). During normal service by periodiccomparison of the measured value from the IED with other independent meters theproper operation of the IED analog measurement chain can be verified. Finally, it

1MRK 504 134-UEN - Section 14Monitoring

319Application Manual

Page 326: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

can be used to verify proper direction orientation for distance or directionalovercurrent protection function.

The available measured values of an IED are depending on theactual hardware (TRM) and the logic configuration made in PCM600.

All measured values can be supervised with four settable limits that is, low-lowlimit, low limit, high limit and high-high limit. A zero clamping reduction is alsosupported, that is, the measured value below a settable limit is forced to zero whichreduces the impact of noise in the inputs. There are no interconnections regardingany settings or parameters, neither between functions nor between signals withineach function.

Zero clampings are handled by ZeroDb for each signal separately for each of thefunctions. For example, the zero clamping of U12 is handled by ULZeroDb inVMMXU, zero clamping of I1 is handled by ILZeroDb in CMMXU.

Dead-band supervision can be used to report measured signal value to station levelwhen change in measured value is above set threshold limit or time integral of allchanges since the last time value updating exceeds the threshold limit. Measurevalue can also be based on periodic reporting.

The measurement function, CVMMXN, provides the following power systemquantities:

• P, Q and S: three phase active, reactive and apparent power• PF: power factor• U: phase-to-phase voltage amplitude• I: phase current amplitude• F: power system frequency

The output values are displayed in the local HMI under Main menu/Tests/Function status/Monitoring/CVMMXN/Outputs

The measuring functions CMMXU, VNMMXU and VMMXU provide physicalquantities:

• I: phase currents (amplitude and angle) (CMMXU)• U: voltages (phase-to-earth and phase-to-phase voltage, amplitude and angle)

(VMMXU, VNMMXU)

It is possible to calibrate the measuring function above to get better then class 0.5presentation. This is accomplished by angle and amplitude compensation at 5, 30and 100% of rated current and at 100% of rated voltage.

The power system quantities provided, depends on the actualhardware, (TRM) and the logic configuration made in PCM600.

Section 14 1MRK 504 134-UEN -Monitoring

320Application Manual

Page 327: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

The measuring functions CMSQI and VMSQI provide sequence componentquantities:

• I: sequence currents (positive, zero, negative sequence, amplitude and angle)• U: sequence voltages (positive, zero and negative sequence, amplitude and

angle).

The CVMMXN function calculates three-phase power quantities by usingfundamental frequency phasors (DFT values) of the measured current respectivelyvoltage signals. The measured power quantities are available either, asinstantaneously calculated quantities or, averaged values over a period of time (lowpass filtered) depending on the selected settings.

14.4.3 Setting guidelinesThe available setting parameters of the measurement function CVMMXN,CMMXU, VMMXU, CMSQI, VMSQI, VNMMXU are depending on the actualhardware (TRM) and the logic configuration made in PCM600.

The parameters for the Measurement functions CVMMXN, CMMXU, VMMXU,CMSQI, VMSQI, VNMMXU are set via the local HMI or PCM600.

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

Operation: Off/On. Every function instance (CVMMXN, CMMXU, VMMXU,CMSQI, VMSQI, VNMMXU) can be taken in operation (On) or out of operation(Off).

The following general settings can be set for the Measurement function(CVMMXN).

PowAmpFact: Amplitude factor to scale power calculations.

PowAngComp: Angle compensation for phase shift between measured I & U.

Mode: Selection of measured current and voltage. There are 9 different ways ofcalculating monitored three-phase values depending on the available VT inputsconnected to the IED. See parameter group setting table.

k: Low pass filter coefficient for power measurement, U and I.

UAmpCompY: Amplitude compensation to calibrate voltage measurements at Y%of Ur, where Y is equal to 5, 30 or 100.

IAmpCompY: Amplitude compensation to calibrate current measurements at Y% ofIr, where Y is equal to 5, 30 or 100.

IAngCompY: Angle compensation to calibrate angle measurements at Y% of Ir,where Y is equal to 5, 30 or 100.

1MRK 504 134-UEN - Section 14Monitoring

321Application Manual

Page 328: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Parameters IBase, Ubase and SBase have been implemented as asettings instead of a parameters, which means that if the values ofthe parameters are changed there will be no restart of theapplication. As restart is required to activate new parametersvalues, the IED must be restarted in some way. Either manually orby changing some other parameter at the same time.

The following general settings can be set for the Phase-phase currentmeasurement (CMMXU).

IAmpCompY: Amplitude compensation to calibrate current measurements at Y% ofIr, where Y is equal to 5, 30 or 100.

IAngCompY: Angle compensation to calibrate angle measurements at Y% of Ir,where Y is equal to 5, 30 or 100.

The following general settings can be set for the Phase-phase voltagemeasurement (VMMXU).

UAmpCompY: Amplitude compensation to calibrate voltage measurements at Y%of Ur, where Y is equal to 5, 30 or 100.

UAngCompY: Angle compensation to calibrate angle measurements at Y% of Ur,where Y is equal to 5, 30 or 100.

The following general settings can be set for all monitored quantities included inthe functions (CVMMXN, CMMXU, VMMXU, CMSQI, VMSQI, VNMMXU) Xin setting names below equals S, P, Q, PF, U, I, F, IL1-3, UL1-3UL12-31, I1, I2,3I0, U1, U2 or 3U0.

Xmin: Minimum value for analog signal X.

Xmax: Maximum value for analog signal X.

Xmin and Xmax values are directly set in applicable measuring unit,V, A, and so on, for all measurement functions, except CVMMXNwhere Xmin and Xmax values are set in % of the base quantity.

XZeroDb: Zero point clamping. A signal value less than XZeroDb is forced to zero.

XRepTyp: Reporting type. Cyclic (Cyclic), amplitude deadband (Dead band) orintegral deadband (Int deadband). The reporting interval is controlled by theparameter XDbRepInt.

XDbRepInt: Reporting deadband setting. Cyclic reporting is the setting value and isreporting interval in seconds. Amplitude deadband is the setting value in % ofmeasuring range. Integral deadband setting is the integral area, that is, measuredvalue in % of measuring range multiplied by the time between two measured values.

Section 14 1MRK 504 134-UEN -Monitoring

322Application Manual

Page 329: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Limits are directly set in applicable measuring unit, V, A , and soon, for all measureing functions, except CVMMXN where limitsare set in % of the base quantity.

XHiHiLim: High-high limit.

XHiLim: High limit.

XLowLim: Low limit.

XLowLowLim: Low-low limit.

XLimHyst: Hysteresis value in % of range and is common for all limits.

All phase angles are presented in relation to defined reference channel. Theparameter PhaseAngleRef defines the reference, see settings for analog inputmodules in PCM600.

Calibration curvesIt is possible to calibrate the functions (CVMMXN, CMMXU, VNMMXU andVMMXU) to get class 0.5 presentations of currents, voltages and powers. This isaccomplished by amplitude and angle compensation at 5, 30 and 100% of ratedcurrent and voltage. The compensation curve will have the characteristic foramplitude and angle compensation of currents as shown in figure 151 (example).The first phase will be used as reference channel and compared with the curve forcalculation of factors. The factors will then be used for all related channels.

1MRK 504 134-UEN - Section 14Monitoring

323Application Manual

Page 330: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

IEC05000652 V2 EN

Figure 151: Calibration curves

14.4.4 Setting examplesThree setting examples, in connection to Measurement function (CVMMXN), areprovided:

• Measurement function (CVMMXN) application for a 110kV OHL• Measurement function (CVMMXN) application on the secondary side of a

transformer• Measurement function (CVMMXN) application for a generator

For each of them detail explanation and final list of selected setting parametersvalues will be provided.

The available measured values of an IED are depending on theactual hardware (TRM) and the logic configuration made in PCM600.

14.4.4.1 Measurement function application for a 110kV OHL

Single line diagram for this application is given in figure 152:

Section 14 1MRK 504 134-UEN -Monitoring

324Application Manual

Page 331: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

110kV Busbar

110kV OHL

P Q

600/1 A110 0,1/

3 3kV

IEC09000039-2-en.vsd

IED

IEC09000039-1-EN V2 EN

Figure 152: Single line diagram for 110kV OHL application

In order to monitor, supervise and calibrate the active and reactive power asindicated in figure 152 it is necessary to do the following:

1. Set correctly CT and VT data and phase angle reference channelPhaseAngleRef (see settings for analog input modules in PCM600) usingPCM600 for analog input channels

2. Connect, in PCM600, measurement function to three-phase CT and VT inputs3. Set under General settings parameters for the Measurement function:

• general settings as shown in table 29.• level supervision of active power as shown in table 30.• calibration parameters as shown in table 31.

Table 29: General settings parameters for the Measurement function

Setting Short Description Selectedvalue

Comments

Operation Operation Off/On On Function must be On

PowAmpFact Amplitude factor to scale powercalculations

1.000 It can be used duringcommissioning to achieve highermeasurement accuracy.Typically no scaling is required

PowAngComp Angle compensation for phaseshift between measured I & U

0.0 It can be used duringcommissioning to achieve highermeasurement accuracy.Typically no angle compensationis required. As well here requireddirection of P & Q measurementis towards protected object (asper IED internal default direction)

Mode Selection of measured currentand voltage

L1, L2, L3 All three phase-to-earth VTinputs are available

k Low pass filter coefficient forpower measurement, U and I

0.00 Typically no additional filtering isrequired

1MRK 504 134-UEN - Section 14Monitoring

325Application Manual

Page 332: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Table 30: Settings parameters for level supervision

Setting Short Description Selectedvalue

Comments

PMin Minimum value -100 Minimum expected load

PMax Minimum value 100 Maximum expected load

PZeroDb Zero point clamping in 0.001% ofrange

3000 Set zero point clamping to 45MW that is, 3% of 200 MW

PRepTyp Reporting type db Select amplitude deadbandsupervision

PDbRepInt Cycl: Report interval (s), Db: In% of range, Int Db: In %s

2 Set ±Δdb=30 MW that is, 2%(larger changes than 30 MW willbe reported)

PHiHiLim High High limit (physical value) 60 High alarm limit that is, extremeoverload alarm

PHiLim High limit (physical value) 50 High warning limit that is,overload warning

PLowLim Low limit (physical value) -50 Low warning limit. Not active

PLowLowlLim Low Low limit (physical value) -60 Low alarm limit. Not active

PLimHyst Hysteresis value in % of range(common for all limits)

2 Set ±Δ Hysteresis MW that is, 2%

Table 31: Settings for calibration parameters

Setting Short Description Selectedvalue

Comments

IAmpComp5 Amplitude factor to calibratecurrent at 5% of Ir

0.00

IAmpComp30 Amplitude factor to calibratecurrent at 30% of Ir

0.00

IAmpComp100 Amplitude factor to calibratecurrent at 100% of Ir

0.00

UAmpComp5 Amplitude factor to calibratevoltage at 5% of Ur

0.00

UAmpComp30 Amplitude factor to calibratevoltage at 30% of Ur

0.00

UAmpComp100 Amplitude factor to calibratevoltage at 100% of Ur

0.00

IAngComp5 Angle calibration for current at5% of Ir

0.00

IAngComp30 Angle pre-calibration for currentat 30% of Ir

0.00

IAngComp100 Angle pre-calibration for currentat 100% of Ir

0.00

14.4.4.2 Measurement function application for a power transformer

Single line diagram for this application is given in figure 153.

Section 14 1MRK 504 134-UEN -Monitoring

326Application Manual

Page 333: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

110kV Busbar

200/1

35 / 0,1kV

35kV Busbar

500/5

P Q

31,5 MVA110/36,75/(10,5) kV

Yy0(d5)

UL1L2

IEC09000040-1-en.vsd

IED

IEC09000040-1-EN V1 EN

Figure 153: Single line diagram for transformer application

In order to measure the active and reactive power as indicated in figure 153, it isnecessary to do the following:

1. Set correctly all CT and VT and phase angle reference channel PhaseAngleRef(see settings for analog input modules in PCM600) data using PCM600 foranalog input channels

2. Connect, in PCM600, measurement function to LV side CT & VT inputs3. Set the setting parameters for relevant Measurement function as shown in the

following table 32:

1MRK 504 134-UEN - Section 14Monitoring

327Application Manual

Page 334: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Table 32: General settings parameters for the Measurement function

Setting Short description Selectedvalue

Comment

Operation Operation Off/On On Function must be On

PowAmpFact Amplitude factor to scale powercalculations

1.000 Typically no scaling is required

PowAngComp Angle compensation for phaseshift between measured I & U

180.0 Typically no angle compensationis required. However here therequired direction of P & Qmeasurement is towards busbar(Not per IED internal defaultdirection). Therefore anglecompensation have to be used inorder to get measurements inaliment with the requireddirection.

Mode Selection of measured currentand voltage

L1L2 Only UL1L2 phase-to-phasevoltage is available

k Low pass filter coefficient forpower measurement, U and I

0.00 Typically no additional filtering isrequired

14.5 Event counter CNTGGIO

14.5.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Event counter CNTGGIOS00946 V1 EN

-

14.5.2 ApplicationEvent counter (CNTGGIO) has six counters which are used for storing the numberof times each counter has been activated. CNTGGIO can be used to count howmany times a specific function, for example the tripping logic, has issued a tripsignal. All six counters have a common blocking and resetting feature.

14.5.3 Setting guidelinesOperation: Sets the operation of Event counter (CNTGGIO) On or Off.

14.6 Limit counter L4UFCNT

Section 14 1MRK 504 134-UEN -Monitoring

328Application Manual

Page 335: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

14.6.1 Function descriptionFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Limit counter L4UFCNT -

14.6.2 ApplicationLimit counter (L4UFCNT) is intended for applications where positive and/ornegative flanks on a binary signal need to be counted.

The limit counter provides four independent limits to be checked against theaccumulated counted value. The four limit reach indication outputs can be utilizedto initiate proceeding actions. The output indicators remain high until the reset ofthe function.

It is also possible to initiate the counter from a non-zero value by resetting thefunction to the wanted initial value provided as a setting.

If applicable, the counter can be set to stop or rollover to zero and continuecounting after reaching the maximum count value. The steady overflow output flagindicates the next count after reaching the maximum count value. It is also possibleto set the counter to rollover and indicate the overflow as a pulse, which lasts up tothe first count after rolling over to zero. In this case, periodic pulses will begenerated at multiple overflow of the function.

14.6.2.1 Setting guidelines

The parameters for Limit counter L4UFCNT are set in the local HMI or PCM600.

14.7 Disturbance report

14.7.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Disturbance report DRPRDRE - -

Analog input signals A1RADR - -

Analog input signals A2RADR - -

Analog input signals A3RADR - -

Analog input signals A4RADR - -

Binary input signals B1RBDR - -

Binary input signals B2RBDR - -

Binary input signals B3RBDR - -

Table continues on next page

1MRK 504 134-UEN - Section 14Monitoring

329Application Manual

Page 336: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Binary input signals B4RBDR - -

Binary input signals B5RBDR - -

Binary input signals B6RBDR - -

14.7.2 ApplicationTo get fast, complete and reliable information about disturbances in the primary and/or in the secondary system it is very important to gather information on faultcurrents, voltages and events. It is also important having a continuous event-logging to be able to monitor in an overview perspective. These tasks areaccomplished by the disturbance report function DRPRDRE and facilitate a betterunderstanding of the power system behavior and related primary and secondaryequipment during and after a disturbance. An analysis of the recorded dataprovides valuable information that can be used to explain a disturbance, basis forchange of IED setting plan, improve existing equipment, and so on. Thisinformation can also be used in a longer perspective when planning for anddesigning new installations, that is, a disturbance recording could be a part ofFunctional Analysis (FA).

Disturbance report DRPRDRE, always included in the IED, acquires sampled dataof all selected analog and binary signals connected to the function blocks that is,

• maximum 30 external analog signals,• 10 internal derived analog signals, and• 96 binary signals.

Disturbance report function is a common name for several functions that is,Indications, Event recorder, Event list, Trip value recorder, Disturbance recorder.

Disturbance report function is characterized by great flexibility as far asconfiguration, starting conditions, recording times, and large storage capacity areconcerned. Thus, disturbance report is not dependent on the operation of protectivefunctions, and it can record disturbances that were not discovered by protectivefunctions for one reason or another. Disturbance report can be used as an advancedstand-alone disturbance recorder.

Every disturbance report recording is saved in the IED. The same applies to allevents, which are continuously saved in a ring-buffer. Local HMI can be used toget information about the recordings, and the disturbance report files may beuploaded in the PCM600 using the Disturbance handling tool, for report reading orfurther analysis (using WaveWin, that can be found on the PCM600 installationCD). The user can also upload disturbance report files using FTP or MMS (over61850–8–1) clients.

Section 14 1MRK 504 134-UEN -Monitoring

330Application Manual

Page 337: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

If the IED is connected to a station bus (IEC 61850-8-1), the disturbance recorder(record made and fault number) and the fault locator information are available asGOOSE or Report Control data.

14.7.3 Setting guidelinesThe setting parameters for the Disturbance report function DRPRDRE are set viathe local HMI or PCM600.

It is possible to handle up to 40 analog and 96 binary signals, either internal signalsor signals coming from external inputs. The binary signals are identical in allfunctions that is, Disturbance recorder, Event recorder, Indication, Trip valuerecorder and Event list function.

User-defined names of binary and analog input signals is set using PCM600. Theanalog and binary signals appear with their user-defined names. The name is usedin all related functions (Disturbance recorder, Event recorder, Indication, Tripvalue recorder and Event list).

Figure 154 shows the relations between Disturbance report, included functions andfunction blocks. Event list, Event recorder and Indication uses information fromthe binary input function blocks (BxRBDR). Trip value recorder uses analoginformation from the analog input function blocks (AxRADR),. Disturbance reportfunction acquires information from both AxRADR and BxRBDR.

Trip value rec

Event list

Event recorder

Indications

Disturbancerecorder

A1-4RADR

B1-6RBDR

Disturbance Report

Binary signals

Analog signalsA4RADR

B6RBDR

DRPRDRE

IEC09000337-2-en.vsdIEC09000337 V2 EN

Figure 154: Disturbance report functions and related function blocks

1MRK 504 134-UEN - Section 14Monitoring

331Application Manual

Page 338: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

For Disturbance report function there are a number of settings which alsoinfluences the sub-functions.

Three LED indications placed above the LCD screen makes it possible to get quickstatus information about the IED.

Green LED: Steady light In Service

Flashing light Internal failure

Dark No power supply

Yellow LED: Function controlled by SetLEDnsetting in Disturbance report function.

Red LED: Function controlled by SetLEDnsetting in Disturbance report function.

OperationThe operation of Disturbance report function DRPRDRE has to be set On or Off. IfOff is selected, note that no disturbance report is registered, and none sub-functionwill operate (the only general parameter that influences Event list).

Operation = Off:

• Disturbance reports are not stored.• LED information (yellow - start, red - trip) is not stored or changed.

Operation = On:

• Disturbance reports are stored, disturbance data can be read from the localHMI and from a PC using PCM600.

• LED information (yellow - start, red - trip) is stored.

Every recording will get a number (0 to 999) which is used as identifier (localHMI, disturbance handling tool and IEC 61850). An alternative recordingidentification is date, time and sequence number. The sequence number isautomatically increased by one for each new recording and is reset to zero atmidnight. The maximum number of recordings stored in the IED is 100. The oldestrecording will be overwritten when a new recording arrives (FIFO).

To be able to delete disturbance records, Operation parameter hasto be On.

Section 14 1MRK 504 134-UEN -Monitoring

332Application Manual

Page 339: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

The maximum number of recordings depend on each recordingstotal recording time. Long recording time will reduce the number ofrecordings to less than 100.

The IED flash disk should NOT be used to store any user files. Thismight cause disturbance recordings to be deleted due to lack of diskspace.

Recording timesThe different recording times for Disturbance report are set (the pre-fault time, post-fault time, and limit time). These recording times affect all sub-functions more orless but not the Event list function.

Prefault recording time (PreFaultRecT) is the recording time before the startingpoint of the disturbance. The setting should be at least 0.1 s to ensure enoughsamples for the estimation of pre-fault values in the Trip value recorder function.

Postfault recording time (PostFaultRecT) is the maximum recording time after thedisappearance of the trig-signal (does not influence the Trip value recorder function).

Recording time limit (TimeLimit) is the maximum recording time after trig. Theparameter limits the recording time if some trigging condition (fault-time) is verylong or permanently set (does not influence the Trip value recorder function).

Post retrigger (PostRetrig) can be set to On or Off. Makes it possible to chooseperformance of Disturbance report function if a new trig signal appears in the post-fault window.

PostRetrig = Off

The function is insensitive for new trig signals during post fault time.

PostRetrig = On

The function completes current report and starts a new complete report that is, thelatter will include:

• new pre-fault- and fault-time (which will overlap previous report)• events and indications might be saved in the previous report too, due to overlap• new trip value calculations if installed, in operation and started

Operation in test modeIf the IED is in test mode and OpModeTest = Off. Disturbance report function doesnot save any recordings and no LED information is displayed.

If the IED is in test mode and OpModeTest = On. Disturbance report functionworks in normal mode and the status is indicated in the saved recording.

1MRK 504 134-UEN - Section 14Monitoring

333Application Manual

Page 340: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

14.7.3.1 Binary input signals

Up to 96 binary signals can be selected among internal logical and binary inputsignals. The configuration tool is used to configure the signals.

For each of the 96 signals, it is also possible to select if the signal is to be used as atrigger for the start of the Disturbance report and if the trigger should be activatedon positive (1) or negative (0) slope.

OperationN: Disturbance report may trig for binary input N (On) or not (Off).

TrigLevelN: Trig on positive (Trig on 1) or negative (Trig on 0) slope for binaryinput N.

14.7.3.2 Analog input signals

Up to 40 analog signals can be selected among internal analog and analog inputsignals. PCM600 is used to configure the signals.

The analog trigger of Disturbance report is not affected if analog input M is to beincluded in the disturbance recording or not (OperationM = On/Off).

If OperationM = Off, no waveform (samples) will be recorded and reported ingraph. However, Trip value, pre-fault and fault value will be recorded and reported.The input channel can still be used to trig the disturbance recorder.

If OperationM = On, waveform (samples) will also be recorded and reported in graph.

NomValueM: Nominal value for input M.

OverTrigOpM, UnderTrigOpM: Over or Under trig operation, Disturbance reportmay trig for high/low level of analog input M (On) or not (Off).

OverTrigLeM, UnderTrigLeM: Over or under trig level, Trig high/low levelrelative nominal value for analog input M in percent of nominal value.

14.7.3.3 Sub-function parameters

All functions are in operation as long as Disturbance report is in operation.

IndicationsIndicationMaN: Indication mask for binary input N. If set (Show), a status changeof that particular input, will be fetched and shown in the disturbance summary onlocal HMI. If not set (Hide), status change will not be indicated.

SetLEDN: Set yellow Start and red Trip LED on local HMI in front of the IED ifbinary input N changes status.

Section 14 1MRK 504 134-UEN -Monitoring

334Application Manual

Page 341: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Disturbance recorderOperationM: Analog channel M is to be recorded by the disturbance recorder (On)or not (Off).

If OperationM = Off, no waveform (samples) will be recorded and reported ingraph. However, Trip value, pre-fault and fault value will be recorded and reported.The input channel can still be used to trig the disturbance recorder.

If OperationM = On, waveform (samples) will also be recorded and reported in graph.

Event recorderEvent recorder function has no dedicated parameters.

Trip value recorderZeroAngleRef: The parameter defines which analog signal that will be used asphase angle reference for all other analog input signals. This signal will also beused for frequency measurement and the measured frequency is used whencalculating trip values. It is suggested to point out a sampled voltage input signal,for example, a line or busbar phase voltage (channel 1-30).

Event listEvent list function has no dedicated parameters.

14.7.3.4 Consideration

The density of recording equipment in power systems is increasing, since thenumber of modern IEDs, where recorders are included, is increasing. This leads toa vast number of recordings at every single disturbance and a lot of information hasto be handled if the recording functions do not have proper settings. The goal is tooptimize the settings in each IED to be able to capture just valuable disturbancesand to maximize the number that is possible to save in the IED.

The recording time should not be longer than necessary (PostFaultrecT andTimeLimit).

• Should the function record faults only for the protected object or cover more?• How long is the longest expected fault clearing time?• Is it necessary to include reclosure in the recording or should a persistent fault

generate a second recording (PostRetrig)?

Minimize the number of recordings:

• Binary signals: Use only relevant signals to start the recording that is,protection trip, carrier receive and/or start signals.

• Analog signals: The level triggering should be used with great care, sinceunfortunate settings will cause enormously number of recordings. Ifnevertheless analog input triggering is used, chose settings by a sufficientmargin from normal operation values. Phase voltages are not recommended fortrigging.

1MRK 504 134-UEN - Section 14Monitoring

335Application Manual

Page 342: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Remember that values of parameters set elsewhere are linked to the information ona report. Such parameters are, for example, station and object identifiers, CT andVT ratios.

14.8 Measured value expander block MVEXP

14.8.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Measured value expander block MVEXP - -

14.8.2 ApplicationThe current and voltage measurements functions (CVMMXN, CMMXU, VMMXUand VNMMXU), current and voltage sequence measurement functions (CMSQIand VMSQI) and IEC 61850 generic communication I/O functions (MVGGIO) areprovided with measurement supervision functionality. All measured values can besupervised with four settable limits, that is low-low limit, low limit, high limit andhigh-high limit. The measure value expander block (MVEXP) has been introducedto be able to translate the integer output signal from the measuring functions to 5binary signals, that is below low-low limit, below low limit, normal, above high-high limit or above high limit. The output signals can be used as conditions in theconfigurable logic.

14.8.3 Setting guidelinesThe function does not have any parameters available in Local HMI or Protectionand Control IED Manager (PCM600).

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

14.9 Station battery supervision SPVNZBAT

14.9.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Station battery supervision function SPVNZBAT U<> -

Section 14 1MRK 504 134-UEN -Monitoring

336Application Manual

Page 343: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

14.9.2 ApplicationUsually, the load on the DC system is a constant resistance load, for example,lamps, LEDs, electronic instruments and electromagnetic contactors in a steadystate condition. A transient RL load exists when breakers are tripped or closed.

The battery voltage has to be continuously monitored as the batteries can withstandmoderate overvoltage and undervoltage only for a short period of time.

• If the battery is subjected to a prolonged or frequent overvoltage, it leads to theageing of the battery, which may lead to the earlier failure of the battery. Theother occurrences may be the thermal runaway, generation of heat or increasedamount of hydrogen gas and the depletion of fluid in case of valve regulatedbatteries.

• If the value of the charging voltage drops below the minimum recommendedfloat voltage of the battery, the battery does not receive sufficient chargingcurrent to offset internal losses, resulting in a gradual loss of capacity.• If a lead acid battery is subjected to a continuous undervoltage, heavy

sulfation occurs on the plates, which leads to the loss of the battery capacity.

14.10 Insulation gas monitoring function SSIMG

14.10.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Insulation gas monitoring function SSIMG - 63

14.10.2 ApplicationInsulation gas monitoring function (SSIMG) is used for monitoring the circuitbreaker condition. Proper arc extinction by the compressed gas in the circuitbreaker is very important. When the pressure becomes too low compared to therequired value, the circuit breaker operation gets blocked to minimize the risk ofinternal failure. Binary information based on the gas pressure in the circuit breakeris used as input signals to the function. In addition to that, the function generatesalarms based on received information.

1MRK 504 134-UEN - Section 14Monitoring

337Application Manual

Page 344: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

14.11 Insulation liquid monitoring function SSIML

14.11.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Insulation liquid monitoring function SSIML - 71

14.11.2 ApplicationInsulation liquid monitoring function (SSIML) is used for monitoring the circuitbreaker condition. Proper arc extinction by the compressed oil in the circuit breakeris very important. When the level becomes too low, compared to the requiredvalue, the circuit breaker operation is blocked to minimize the risk of internalfailures. Binary information based on the oil level in the circuit breaker is used asinput signals to the function. In addition to that, the function generates alarmsbased on received information.

14.12 Circuit breaker condition monitoring SSCBR

14.12.1 Identification

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Circuit breaker condition monitoring SSCBR - -

14.12.2 ApplicationSSCBR includes different metering and monitoring subfunctions.

Circuit breaker statusCircuit breaker status monitors the position of the circuit breaker, that is, whetherthe breaker is in an open, closed or intermediate position.

Circuit breaker operation monitoringThe purpose of the circuit breaker operation monitoring is to indicate that thecircuit breaker has not been operated for a long time. The function calculates thenumber of days the circuit breaker has remained inactive, that is, has stayed in thesame open or closed state. There is also the possibility to set an initial inactive day.

Section 14 1MRK 504 134-UEN -Monitoring

338Application Manual

Page 345: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Breaker contact travel timeHigh travelling times indicate the need for maintenance of the circuit breakermechanism. Therefore, detecting excessive travelling time is needed. During theopening cycle operation, the main contact starts opening. The auxiliary contact Aopens, the auxiliary contact B closes, and the main contact reaches its openingposition. During the closing cycle, the first main contact starts closing. Theauxiliary contact B opens, the auxiliary contact A closes, and the main contactreaches its close position. The travel times are calculated based on the statechanges of the auxiliary contacts and the adding correction factor to consider thetime difference of the main contact's and the auxiliary contact's position change.

Operation counterRoutine maintenance of the breaker like the lubricating breaker mechanism, isgenerally based on a number of operations. A suitable threshold setting, to raise analarm when the number of operation cycle exceeds the set limit, helps preventivemaintenance. This can also be used to indicate the requirement for oil sampling fordielectric testing in case of an oil circuit breaker.

The change of state can be detected from the binary input of the auxiliary contact.There is a possibility to set an initial value for the counter which can be used toinitialize this functionality after a period of operation or in case of refurbishedprimary equipment.

Accumulation of Iyt

Accumulation of Iyt calculates the accumulated energy ΣIyt where the factor y isknown as the current exponent. The factor y depends on the type of the circuitbreaker. For oil circuit breakers the factor y is normally 2. In case of a high-voltagesystem, the factor y can be 1.4...1.5.

Remaining life of the breakerEvery time the breaker operates, the life of the circuit breaker reduces due towearing. The wearing in the breaker depends on the tripping current, and theremaining life of the breaker is estimated from the circuit breaker trip curveprovided by the manufacturer.

Example for estimating the remaining life of a circuit breaker

1MRK 504 134-UEN - Section 14Monitoring

339Application Manual

Page 346: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

A071114 V3 EN

Figure 155: Trip Curves for a typical 12 kV, 630 A, 16 kA vacuum interrupter

Nr the number of closing-opening operations allowed for the circuit breaker

Ia the current at the time of tripping of the circuit breaker

Calculation of Directional Coefficient

The directional coefficient is calculated according to the formula:

Section 14 1MRK 504 134-UEN -Monitoring

340Application Manual

Page 347: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Directional Coef

B

A

I

I

f

r

=

= −

log

log

.2 2609

A070794 V2 EN (Equation 126)

Ir Rated operating current = 630 A

If Rated fault current = 16 kA

A Op number rated = 30000

B Op number fault = 20

Calculation for estimating the remaining life

The equation shows that there are 30,000 possible operations at the rated operatingcurrent of 630 A and 20 operations at the rated fault current 16 kA. Therefore, ifthe tripping current is 10 kA, one operation at 10 kA is equivalent to30,000/500=60 operations at the rated current. It is also assumed that prior to thistripping, the remaining life of the circuit breaker is 15,000 operations. Therefore,after one operation of 10 kA, the remaining life of the circuit breaker is15,000-60=14,940 at the rated operating current.

Spring charging time indicationFor normal circuit breaker operation, the circuit breaker spring should be chargedwithin a specified time. Therefore, detecting long spring charging time indicatesthe time for circuit breaker maintenance. The last value of the spring charging timecan be given as a service value.

Gas pressure supervisionThe gas pressure supervision monitors the gas pressure inside the arc chamber.When the pressure becomes too low compared to the required value, the circuitbreaker operations are locked. A binary input is available based on the pressurelevels in the function, and alarms are generated based on these inputs.

1MRK 504 134-UEN - Section 14Monitoring

341Application Manual

Page 348: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

342

Page 349: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Section 15 Metering

15.1 Pulse counter PCGGIO

15.1.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Pulse counter PCGGIO

S00947 V1 EN

-

15.1.2 ApplicationPulse counter (PCGGIO) function counts externally generated binary pulses, forinstance pulses coming from an external energy meter, for calculation of energyconsumption values. The pulses are captured by the binary input module (BIO),and read by the PCGGIO function. The number of pulses in the counter is thenreported via the station bus to the substation automation system or read via thestation monitoring system as a service value. When using IEC 61850–8–1, a scaledservice value is available over the station bus.

The normal use for this function is the counting of energy pulses from externalenergy meters. An optional number of inputs from the binary input module in IEDcan be used for this purpose with a frequency of up to 10 Hz. PCGGIO can also beused as a general purpose counter.

15.1.3 Setting guidelinesFrom PCM600, these parameters can be set individually for each pulse counter:

• Operation: Off/On• tReporting: 0-3600s• EventMask: NoEvents/ReportEvents

The configuration of the inputs and outputs of PCGGIO function block is madewith PCM600.

On the binary input output module (BIO), the debounce filter default time is set to5 ms, that is, the counter suppresses pulses with a pulse length less than 5 ms. The

1MRK 504 134-UEN - Section 15Metering

343Application Manual

Page 350: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

binary input channels on the binary input output module (BIO) have individualsettings for debounce time, oscillation count and oscillation time. The values canbe changed in the local HMI and PCM600 under Main menu/Configuration/I/Omodules

The debunce time should be set to the same value for all channelson the board

The setting isindividual for all input channels on the binary inputoutput module (BIO), that is, if changes of the limits are made forinputs not connected to the pulse counter, it will not influence theinputs used for pulse counting.

15.2 Energy calculation and demand handling EPTMMTR

15.2.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Energy calculation and demandhandling

ETPMMTR

WhIEC10000169 V1 EN

-

15.2.2 ApplicationEnergy calculation and demand handling function ETPMMTR is intended forstatistics of the forward and reverse active and reactive energy. It has a highaccuracy basically given by the measurements function (CVMMXN). This functionhas a site calibration possibility to further increase the total accuracy.

The function is connected to the instantaneous outputs of (CVMMXN) as shown infigure 156.

Section 15 1MRK 504 134-UEN -Metering

344Application Manual

Page 351: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

PQ

STACCRSTACCRSTDMD

TRUEFALSEFALSE

CVMMXN

IEC09000106.vsd

ETPMMTRP_INSTQ_INST

IEC09000106 V1 EN

Figure 156: Connection of energy calculation and demand handling functionETPMMTR to the measurements function (CVMMXN)

The energy values can be read through communication in MWh and MVarh inmonitoring tool of PCM600 and/or alternatively the values can be presented on thelocal HMI. The local HMI graphical display is configured with PCM600 Graphicaldisplay editor tool (GDE) with a measuring value which is selected to the activeand reactive component as preferred. All four values can also be presented.

Maximum demand values are presented in MWh or MVarh in the same way.

Alternatively, the values can be presented with use of the pulse counters function(PCGGIO). The output values are scaled with the pulse output setting valuesEAFAccPlsQty, EARAccPlsQty, ERFAccPlsQty and ERRAccPlsQty of the energymetering function and then the pulse counter can be set-up to present the correctvalues by scaling in this function. Pulse counter values can then be presented onthe local HMI in the same way and/or sent to the SA system throughcommunication where the total energy then is calculated by summation of theenergy pulses. This principle is good for very high values of energy as thesaturation of numbers else will limit energy integration to about one year with 50kV and 3000 A. After that the accumulation will start on zero again.

15.2.3 Setting guidelinesThe parameters are set via the local HMI or PCM600.

The following settings can be done for the energy calculation and demand handlingfunction ETPMMTR:

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

Operation: Off/On

tEnergy: Time interval when energy is measured.

StartAcc: Off/On is used to switch the accumulation of energy on and off.

The input signal STACC is used to start accumulation. Input signalSTACC cannot be used to halt accumulation. The energy content isreset every time STACC is activated. STACC can for example, be

1MRK 504 134-UEN - Section 15Metering

345Application Manual

Page 352: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

used when an external clock is used to switch two active energymeasuring function blocks on and off to have indication of two tariffs.

tEnergyOnPls: gives the pulse length ON time of the pulse. It should be at least100 ms when connected to the Pulse counter function block. Typical value can be100 ms.

tEnergyOffPls: gives the OFF time between pulses. Typical value can be 100 ms.

EAFAccPlsQty and EARAccPlsQty: gives the MWh value in each pulse. It shouldbe selected together with the setting of the Pulse counter (PCGGIO) settings togive the correct total pulse value.

ERFAccPlsQty and ERRAccPlsQty: gives the MVarh value in each pulse. It shouldbe selected together with the setting of the Pulse counter (PCGGIO) settings togive the correct total pulse value.

For the advanced user there are a number of settings for direction, zero clamping,max limit, and so on. Normally, the default values are suitable for these parameters.

Section 15 1MRK 504 134-UEN -Metering

346Application Manual

Page 353: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Section 16 Station communication

16.1 IEC61850-8-1 communication protocol

16.1.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

IEC 61850-8-1 communication protocol IEC 61850-8-1 - -

16.1.2 ApplicationIEC 61850-8-1 communication protocol allows vertical communication to HSIclients and allows horizontal communication between two or more intelligentelectronic devices (IEDs) from one or several vendors to exchange information andto use it in the performance of their functions and for correct co-operation.

GOOSE (Generic Object Oriented Substation Event), which is a part of IEC 61850–8–1 standard, allows the IEDs to communicate state and control informationamongst themselves, using a publish-subscribe mechanism. That is, upon detectingan event, the IED(s) use a multi-cast transmission to notify those devices that haveregistered to receive the data. An IED can, by publishing a GOOSE message,report its status. It can also request a control action to be directed at any device inthe network.

Figure 157 shows the topology of an IEC 61850–8–1 configuration. IEC 61850–8–1 specifies only the interface to the substation LAN. The LAN itself is left to thesystem integrator.

1MRK 504 134-UEN - Section 16Station communication

347Application Manual

Page 354: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

KIOSK 2 KIOSK 3

Station HSIBase System

EngineeringWorkstation

SMSGateway

Printer

CC

IEC09000135_en.vsd

KIOSK 1

IED 1

IED 2

IED 3

IED 1

IED 2

IED 3

IED 1

IED 2

IED 3

IEC09000135 V1 EN

Figure 157: Example of a communication system with IEC 61850–8–1

Figure 158 shows the GOOSE peer-to-peer communication.

Control Protection Control ProtectionControl and protection

GOOSE

en05000734.vsd

Station HSIMicroSCADA

Gateway

IEDA

IEDA

IEDA

IEDA

IEDA

IEC05000734 V1 EN

Figure 158: Example of a broadcasted GOOSE message

Section 16 1MRK 504 134-UEN -Station communication

348Application Manual

Page 355: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

16.1.2.1 Horizontal communication via GOOSE

GOOSE messages are sent in horizontal communication between the IEDs. Theinformation, which is exchanged, is used for station wide interlocking, breakerfailure protection, busbar voltage selection and so on.

The simplified principle is shown in Figure 159 and can be described as follows.When IED1 has decided to transmit the data set it forces a transmission via thestation bus. All other IEDs receive the data set, but only those who have this dataset in their address list will take it and keep it in an input container. It is defined,that the receiving IED will take the content of the received data set and makes itavailable for the application configuration.

IEC08000145.vsd

IED1 IED3IED2

DO1/DA1DO1/DA2DO2/DA1DO2/DA2DO3/DA1DO3/DA2

IED1IED1IED1IED1IED1IED1

SMT

Receive-FB

DA1DA2DO1

DA1DA2DA1DA2DO3

DA1DA2DO2

Stationbus

DO1/DA1DO1/DA2DO2/DA1DO2/DA2DO3/DA1DO3/DA2

IED1IED1IED1IED1IED1IED1

PLC Program

FBa FBb FBc

IEC08000145 V1 EN

Figure 159: SMT: GOOSE principle and signal routing with SMT

Special function blocks take the data set and present it via the function block asoutput signals for application functions in the application configuration. DifferentGOOSE receive function blocks are available for the specific tasks.

SMT links the different data object attributes (for example stVal or magnitude) tothe output signal to make it available for functions in the application configuration.When a matrix cell array is marked red the IEC 61850–8–1 data attribute type doesnot fit together, even if the GOOSE receive function block is the partner. SMTchecks this on the content of the received data set. See Figure 160

1MRK 504 134-UEN - Section 16Station communication

349Application Manual

Page 356: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

IEC08000174.vsdIEC08000174 V1 EN

Figure 160: SMT: GOOSE marshalling with SMT

GOOSE receive function blocks extract process information, received by the dataset, into single attribute information that can be used within the applicationconfiguration. Crosses in the SMT matrix connect received values to the respectivefunction block signal in SMT, see Figure 161

The corresponding quality attribute is automatically connected bySMT. This quality attribute is available in ACT, through the outputsof the available GOOSE function blocks.

Section 16 1MRK 504 134-UEN -Station communication

350Application Manual

Page 357: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

IEC11000056-1-en.vsd

IEC11000056 V1 EN

Figure 161: SMT: GOOSE receive function block with converted signals

GOOSEVCTRCONF function is used to control the rate (in seconds) at whichvoltage control information from TR8ATCC is transmitted/received to/from otherIEDs via GOOSE communication. GOOSEVCTRCONF function is visible in PST.

The following voltage control information can be sent from TR8ATCC viaGOOSE communication:

• BusV• LoadAIm• LoadARe• PosRel• SetV• VCTRStatus• X2

GOOSEVCTRRCV component receives the voltage control data from GOOSEnetwork at the user defined rate.

This component also checks the received data validity, communication validity andtest mode. Communication validity will be checked upon the rate of data reception.Data validity also depends upon the communication. If communication is invalidthen data validity will also be invalid. IEC 61850 also checks for data validityusing internal parameters which will also be passed to the DATAVALID output.

1MRK 504 134-UEN - Section 16Station communication

351Application Manual

Page 358: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

16.1.3 Setting guidelinesThere are two settings related to the IEC 61850–8–1 protocol:

Operation User can set IEC 61850 communication to On or Off.

GOOSE has to be set to the Ethernet link where GOOSE traffic shall be send andreceived.

IEC 61850–8–1 specific data (logical nodes etc.) per includedfunction in an IED can be found in the communication protocolmanual for IEC 61850–8–1.

The setting parameters for GOOSEVCTRCONF are described below:

SendOperation: This setting sets the send functionality ON or OFF.

ReceiveOperation: This setting sets the receive functionality ON or OFF.

SendInterval: This parameter sets the rate at which VCTR Send component need totransmit the GOOSE message over network. Default value of the send interval is0.3s. Minimum value of the send interval can be set to 0.1s and maximum as 5.0s.

ReceiveInterval: This parameter sets the rate at which VCTR receive componentneed to receive the GOOSE message from the network. Default value of thereceive interval is 0.8s. Minimum value of the send interval can be set to 0.1s andmaximum as 10.0s

Receive interval should be greater than the send interval. With thisconfiguration receiving component shall always have the updatedvalue. For example ReceiveInterval > 2•SendInterval.

16.2 DNP3 protocol

DNP3 (Distributed Network Protocol) is a set of communications protocols used tocommunicate data between components in process automation systems. For adetailed description of the DNP3 protocol, see the DNP3 Communication protocolmanual.

16.3 IEC 60870-5-103 communication protocol

IEC 60870-5-103 is an unbalanced (master-slave) protocol for coded-bit serialcommunication exchanging information with a control system, and with a datatransfer rate up to 19200 bit/s. In IEC terminology, a primary station is a master

Section 16 1MRK 504 134-UEN -Station communication

352Application Manual

Page 359: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

and a secondary station is a slave. The communication is based on a point-to-pointprinciple. The master must have software that can interpret IEC 60870-5-103communication messages.

The Communication protocol manual for IEC 60870-5-103 includes the 650 seriesvendor specific IEC 60870-5-103 implementation.

IEC 60870-5-103 protocol can be configured to use either the optical serial orRS485 serial communication interface on the COM03 or the COM05communication module. The functions Operation selection for optical serialOPTICALPROT and Operation selection for RS485 RS485PROT are used toselect the communication interface.

See the Engineering manual for IEC103 60870-5-103 engineeringprocedures in PCM600.

The function IEC60870-5-103 Optical serial communication, OPTICAL103, isused to configure the communication parameters for the optical serialcommunication interface. The function IEC60870-5-103 serial communication forRS485, RS485103, is used to configure the communication parameters for theRS485 serial communication interface.

16.4 IEC 61850-8-1 redundant station bus communication

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

System component for parallelredundancy protocol

PRPSTATUS - -

16.5 Application

Parallel redundancy protocol status (PRPSTATUS) is used to supervise and assureredundant Ethernet communication over two channels. This will secure datatransfer even though one communication channel might not be available for somereason. PRPSTATUS provides redundant communication over the station busrunning IEC 61850-8-1 protocol. The redundant communication uses port L1_Aand L1_B on the COM3 module.

1MRK 504 134-UEN - Section 16Station communication

353Application Manual

Page 360: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Switch A Switch B1 2

DataData

DataData

IEC13000003-1-en.vsd

IED

PRPSTATUS

1 2

COM03

A B

Duo

Redundancy Supervision

Station Control System

IEC13000003 V1 EN

Figure 162: Redundant station bus

16.6 Setting guidelines

The redundant station bus communication is configured using the local HMI, MainMenu/Configuration/Communication/TCP-IP configuation/ETHLAN1_AB

The settings can be viewed and OperationMode can be set in the Parameter Settingtool in PCM600 under IED Configuration/Communication/TCP-IPconfiguration/ETHLAN1_AB where

OperationMode can be set to Off, NonRedundant(A) or PRP(A+B). The redundantcommunication will be activated when this parameter is set to PRP(A+B).

The ETHLAN1_AB in the Parameter Setting tool is relevant only when the COM03module is present.

Section 16 1MRK 504 134-UEN -Station communication

354Application Manual

Page 361: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

IEC13000009-1-en.vsdIEC13000009 V1 EN

Figure 163: PRP1 Configured in the Parameter Setting tool

IEC13000010-1-en.vsdIEC13000010 V1 EN

Figure 164: Lock/Unlock parameter

IEC13000008-1-en.vsd

IEC13000008 V1 EN

Figure 165: PST screen: OperationMode is set to PRP(A+B)

1MRK 504 134-UEN - Section 16Station communication

355Application Manual

Page 362: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

356

Page 363: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Section 17 Basic IED functions

17.1 Self supervision with internal event list

17.1.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Internal error signal INTERRSIG - -

Internal event list SELFSUPEVLST - -

17.1.2 ApplicationThe protection and control IEDs have many functions included . Self supervisionwith internal event list (SELFSUPEVLST) and internal error signals(INTERRSIG) function provide supervision of the IED. The fault signals make iteasier to analyze and locate a fault.

Both hardware and software supervision is included and it is also possible toindicate possible faults through a hardware contact on the power supply module and/or through the software communication.

Internal events are generated by the built-in supervisory functions. The supervisoryfunctions supervise the status of the various modules in the IED and, in case offailure, a corresponding event is generated. Similarly, when the failure is corrected,a corresponding event is generated.

The event list is updated every 10s hence, an event will not bevisible in the event list as soon as it is created.

Apart from the built-in supervision of the various modules, events are alsogenerated when the status changes for the:

• built-in real time clock (in operation/out of order).• external time synchronization (in operation/out of order).• Change lock (on/off)

Events are also generated:

• whenever any setting in the IED is changed.

1MRK 504 134-UEN - Section 17Basic IED functions

357Application Manual

Page 364: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

The internal events are time tagged with a resolution of 1 ms and stored in a list.The list can store up to 40 events. The list is based on the FIFO principle, that is,when it is full, the oldest event is overwritten. The list can be cleared via the localHMI .

The list of internal events provides valuable information, which can be used duringcommissioning and fault tracing.

17.2 Time synchronization

17.2.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Time synchronization TIMESYNCHGEN

- -

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Time system, summer time begins DSTBEGIN - -

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Time system, summer time ends DSTEND - -

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Time synchronization via IRIG-B IRIG-B - -

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Time synchronization via SNTP SNTP - -

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Time zone from UTC TIMEZONE - -

17.2.2 ApplicationUse a common global source for example GPS time synchronization inside eachsubstation as well as inside the area of the utility responsibility to achieve a

Section 17 1MRK 504 134-UEN -Basic IED functions

358Application Manual

Page 365: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

common time base for the IEDs in a protection and control system. This makescomparison and analysis of events and disturbance data between all IEDs in thepower system possible.

Time-tagging of internal events and disturbances are an excellent help whenevaluating faults. Without time synchronization, only the events within the IED canbe compared to one another. With time synchronization, events and disturbanceswithin the entire station, and even between line ends, can be compared duringevaluation.

In the IED, the internal time can be synchronized from a number of sources:

• SNTP• IRIG-B• DNP• IEC60870-5-103

Micro SCADA OPC server should not be used as a timesynchronization source.

17.2.3 Setting guidelines

System timeThe time is only possible to set inside the IED via the local HMI by navigating toConfiguration/Time/SYSTEMTIME with year, month, day, hour, minute andsecond.

SynchronizationWith external time synchronization the setting how to synchronize for the real-timeclock (TIME) are set via local HMI or PCM600.

TimeSynchThe setting TIMESYNCGEN is used to set the source of the time synchronization.The setting alternatives are:

CoarseSyncSrc which can have the following values:

• Off• SNTP• DNP• IEC60870-5-103

FineSyncSource which can have the following values:

1MRK 504 134-UEN - Section 17Basic IED functions

359Application Manual

Page 366: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

• Off• SNTP• IRIG-B

The parameter SyncMaster defines if the IED is a master, or not a master for timesynchronization in a system of IEDs connected in a communication network(IEC61850-8-1). The SyncMaster can have the following values:

• Off• SNTP -Server

The time synchronization fine tunes the clock.

IEC 60870-5-103 time synchronizationAn IED with IEC 60870-5-103 protocol can be used for time synchronization, butfor accuracy reasons, it is not recommended. In some cases, however, this kind ofsynchronization is needed, for example, when no other synchronization is available.

First, set the IED to be synchronized via IEC 60870-5-103 either from IEDConfiguration/Time/Synchronization/TIMESYNCHGEN:1 in PST or from thelocal HMI.

GUID-68284E7B-A24D-4E78-B5BA-736B29F50E9A V1 EN

Figure 166: Settings under TIMESYNCHGEN:1 in PST

Only CoarseSyncSrc can be set to IEC 60870-5-103, not FineSyncSource.

After setting up the time synchronization source, the user must check and modifythe IEC 60870-5-103 time synchronization specific settings, under Main menu/Configuration/Communication/Station communication/IEC60870-5-103.

• MasterTimeDomain specifies the format of the time sent by the master. Formatcan be:• Coordinated Universal Time (UTC)• Local time set in the master (Local)• Local time set in the master adjusted according to daylight saving time

(Local with DST)• TimeSyncMode specifies the time sent by the IED. The time synchronisation is

done using the following ways:• IEDTime: The IED sends the messages with its own time.• LinMasTime: The IED measures the offset between its own time and the

master time, and applies the same offset for the messages sent as in the

Section 17 1MRK 504 134-UEN -Basic IED functions

360Application Manual

Page 367: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

IEDTimeSkew. But in LinMasTime it applies the time changes occurredbetween two synchronised messages.

• IEDTimeSkew: The IED measures the offset in between its own time andthe master time and applies the same offset for the messages sent.

• EvalTimeAccuracy evaluates time accuracy for invalid time. Specifies theaccuracy of the synchronization (5, 10, 20 or 40 ms). If the accuracy is lessthan the specified value, the “Bad Time” flag is raised. To accommodate thosemasters that are really bad in time sync, the EvalTimeAccuracy can be set toOff.

According to the standard, the “Bad Time” flag is reported when synchronizationhas been omitted in the protection for >23 h.

17.3 Parameter setting group handling

17.3.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Setting group handling SETGRPS - -

Parameter setting groups ACTVGRP - -

17.3.2 ApplicationFour different groups of settings are available to optimize IED operation fordifferent power system conditions. By creating and switching between fine tunedsetting sets, either from the local HMI or configurable binary inputs, results in ahighly adaptable IED that can cope with a variety of power system scenarios.

Different conditions in networks with different voltage levels require highlyadaptable protection and control IEDs to best provide for dependability, securityand selectivity requirements. Protection IEDs operate with a higher degree ofavailability, especially, if the setting values of their parameters are continuouslyoptimized according to the conditions in the power system.

Operational departments can plan for different operating conditions in the primarypower system equipment. The protection engineer can prepare the necessaryoptimized and pre-tested settings in advance for different protection functions.different groups of setting parameters are available in the IED. Any of them can beactivated through the different programmable binary inputs by means of external orinternal control signals.

The four different groups of setting parameters are available in the IED. Any ofthem can be activated through different inputs by means of external programmablebinary or internal control signals.

1MRK 504 134-UEN - Section 17Basic IED functions

361Application Manual

Page 368: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

17.3.3 Setting guidelinesThe setting ActiveSetGrp, is used to select which parameter group to be active. Theactive group can also be selected with configured input to the function blockACTVGRP.

The parameter MaxNoSetGrp defines the maximum number of setting groups inuse to switch between. Only the selected number of setting groups will be availablein the Parameter Setting tool (PST) for activation with the ACTVGRP function block.

17.4 Test mode functionality TESTMODE

17.4.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Test mode functionality TESTMODE - -

17.4.2 ApplicationThe protection and control IEDs may have a complex configuration with manyincluded functions. To make the testing procedure easier, the IEDs include thefeature that allows individual blocking of all functions except the function(s) theshall be tested.

This means that it is possible to see when a function is activated or trips. It alsoenables the user to follow the operation of several related functions to checkcorrect functionality and to check parts of the configuration, and so on.

17.4.3 Setting guidelinesThere are two possible ways to place the IED in the TestMode= On” state. Thismeans that if the IED is set to normal operation (TestMode = Off), but the functionsare still shown being in the test mode, the input signal INPUT on the TESTMODEfunction block must be activated in the configuration.

Forcing of binary output signals is only possible when the IED is in test mode.

Section 17 1MRK 504 134-UEN -Basic IED functions

362Application Manual

Page 369: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

17.5 Change lock CHNGLCK

17.5.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Change lock function CHNGLCK - -

17.5.2 ApplicationChange lock function CHNGLCK is used to block further changes to the IEDconfiguration once the commissioning is complete. The purpose is to make itimpossible to perform inadvertent IED configuration and setting changes.

However, when activated, CHNGLCK will still allow the following actions thatdoes not involve reconfiguring of the IED:

• Monitoring• Reading events• Resetting events• Reading disturbance data• Clear disturbances• Reset LEDs• Reset counters and other runtime component states• Control operations• Set system time• Enter and exit from test mode• Change of active setting group

The binary input controlling the function is defined in ACT or SMT. TheCHNGLCK function is configured using ACT.

LOCK Binary input signal that will activate/deactivate the function, defined in ACT orSMT.

ACTIVE Output status signal

OVERRIDE Set if function is overridden

When CHNGLCK has a logical one on its input, then all attempts to modify theIED configuration and setting will be denied and the message "Error: Changesblocked" will be displayed on the local HMI; in PCM600 the message will be"Operation denied by active ChangeLock". The CHNGLCK function should beconfigured so that it is controlled by a signal from a binary input card. Thisguarantees that by setting that signal to a logical zero, CHNGLCK is deactivated. Ifany logic is included in the signal path to the CHNGLCK input, that logic must be

1MRK 504 134-UEN - Section 17Basic IED functions

363Application Manual

Page 370: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

designed so that it cannot permanently issue a logical one to the CHNGLCK input.If such a situation would occur in spite of these precautions, then please contact thelocal ABB representative for remedial action.

17.5.3 Setting guidelinesThe Change lock function CHNGLCK does not have any parameters available inthe local HMI or PCM600.

17.6 IED identifiers TERMINALID

17.6.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

IED identifiers TERMINALID - -

17.6.2 Application

17.6.2.1 Customer specific settings

The customer specific settings are used to give the IED a unique name and address.The settings are used by a central control system to communicate with the IED.The customer specific identifiers are found in the local HMI under Configuration/Power system/Identifiers/TERMINALID

The settings can also be made from PCM600. For more information about theavailable identifiers, see the technical manual.

Use only characters A - Z, a - z and 0 - 9 in station, unit and objectnames.

17.7 Product information PRODINF

17.7.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Product information PRODINF - -

Section 17 1MRK 504 134-UEN -Basic IED functions

364Application Manual

Page 371: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

17.7.2 Application

17.7.2.1 Factory defined settings

The factory defined settings are very useful for identifying a specific version andvery helpful in the case of maintenance, repair, interchanging IEDs betweendifferent Substation Automation Systems and upgrading. The factory made settingscan not be changed by the customer. They can only be viewed. The settings arefound in the local HMI under Main menu/Diagnostics/IED status/Productidentifiers

The following identifiers are available:

• IEDProdType• Describes the type of the IED (like REL, REC or RET). Example: REL650

• ProductVer• Describes the product version. Example: 1.2.3

1 is the Major version of the manufactured product this means, new platform of theproduct

2 is the Minor version of the manufactured product this means, new functions or newhardware added to the product

3 is the Major revision of the manufactured product this means, functions or hardwareis either changed or enhanced in the product

• ProductDef• Describes the release number, from the production. Example: 1.2.3.4

where;

1 is the Major version of the manufactured product this means, new platform of theproduct

2 is the Minor version of the manufactured product this means, new functions or newhardware added to the product

3 is the Major revision of the manufactured product this means, functions or hardwareis either changed or enhanced in the product

4 is the Minor revision of the manufactured product this means, code is corrected in theproduct

• SerialNo: the structure of the SerialNo is as follows, for example, T0123456where

01 is the last two digits in the year when the IED was manufactured that is, 2001

23 is the week number when the IED was manufactured

456 is the sequential number of the IEDs produced during the production week

• OrderingNo: the structure of the OrderingNo is as follows, for example,1MRK008526-BA. This alphanumeric string has no specific meaning except,that it is used for internal identification purposes within ABB.

• ProductionDate: states the production date in the “YYYY-MM_DD” format.

1MRK 504 134-UEN - Section 17Basic IED functions

365Application Manual

Page 372: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

17.8 Primary system values PRIMVAL

17.8.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Primary system values PRIMVAL - -

17.8.2 ApplicationThe rated system frequency and phasor rotation are set under Main menu/Configuration/ Power system/ Primary values/PRIMVAL in the local HMI andPCM600 parameter setting tree.

17.9 Signal matrix for analog inputs SMAI

17.9.1 Identification

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Signal matrix for analog inputs SMAI_20_x - -

17.9.2 ApplicationSignal matrix for analog inputs function (SMAI), also known as the preprocessorfunction, processes the analog signals connected to it and gives information aboutall aspects of the analog signals connected, like the RMS value, phase angle,frequency, harmonic content, sequence components and so on. This information isthen used by the respective functions in ACT (for example protection,measurement or monitoring).

The SMAI function is used within PCM600 in direct relation with the SignalMatrix tool or the Application Configuration tool.

The SMAI function blocks for the 650 series of products arepossible to set for two cycle times either 5 or 20ms. The functionblocks connected to a SMAI function block shall always have thesame cycle time as the SMAI block.

Section 17 1MRK 504 134-UEN -Basic IED functions

366Application Manual

Page 373: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

17.9.3 Setting guidelinesThe parameters for the signal matrix for analog inputs (SMAI) functions are set viathe local HMI or via the PCM600.

Every SMAI function block can receive four analog signals (three phases and oneneutral value), either voltage or current. SMAI outputs give information aboutevery aspect of the 3ph analog signals acquired (phase angle, RMS value,frequency and frequency derivates, and so on – 244 values in total). Besides theblock “group name”, the analog inputs type (voltage or current) and the analoginput names that can be set directly in ACT.

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

DFTRefExtOut: Parameter valid only for function block SMAI_20_1:1 andSMAI_20_1:2 .

These 2 SMAI blocks can be used as reference blocks for other SMAI blocks; thesetting is related to the output signal SPFCOUT, and it defines the source for thisoutput, when the adaptive frequency tracking is used. The possible options are:InternalDFTRef (i.e. fixed DFT reference based on set system frequency): it is notused when the adaptive frequency tracking is needed. DFTRefGrpn (where n is anumber from 1 to 12): it define the SMAI block numbered n, within its task, that isthe reference for the adaptive frequency tracking. That reference SMAI shall bevoltage type, and shall be connected to a 3-phase voltage transformer which supplyvoltage in all the needed operating conditions. ExternalDFTRef : the reference isbased on what is connected to input DFTSPFC.

DFTReference: Reference DFT for the SMAI block.

These DFT reference block settings decide DFT reference for DFT calculations.The settings InternalDFTRef will use fixed DFT reference based on set systemfrequency. The setting DFTRefGrpn (where n is a number from 1 to 12) will usethe SMAI block numbered n, within its task, as reference for the adaptivefrequency tracking. The setting ExternalDFTRef will use reference based on whatis connected to input DFTSPFC.

The setting ConnectionType: Connection type for that specific instance (n) of theSMAI (if it is Ph-N or Ph-Ph). Depending on connection type setting the notconnected Ph-N or Ph-Ph outputs will be calculated.

Negation: Negation means rotation with 1800 of the vectors. If the user wants tonegate the 3ph signal, it is possible to choose to negate only the phase signalsNegate3Ph, only the neutral signal NegateN or both Negate3Ph+N.

MinValFreqMeas: The minimum value of the voltage for which the frequency iscalculated, expressed as percent of the voltage in the selected Global Base voltagegroup (n) (for each instance 1<n<6).

1MRK 504 134-UEN - Section 17Basic IED functions

367Application Manual

Page 374: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Settings DFTRefExtOut and DFTReference shall be set to defaultvalue InternalDFTRef if no VT inputs are available.

Even if the user sets the AnalogInputType of a SMAI block to“Current”, the MinValFreqMeas is still visible. However, using thecurrent channel values as base for frequency measurement is notrecommendable for a number of reasons, not last among thembeing the low level of currents that one can have in normaloperating conditions.

Example of adaptive frequency tracking

IEC09000029_1_en.vsd

SMAI instance 3 phase groupSMAI_20_1:1 1SMAI_20_2:1 2SMAI_20_3:1 3SMAI_20_4:1 4SMAI_20_5:1 5SMAI_20_6:1 6SMAI_20_7:1 7SMAI_20_8:1 8SMAI_20_9:1 9SMAI_20_10:1 10SMAI_20_11:1 11SMAI_20_12:1 12

Task time group 1

SMAI instance 3 phase groupSMAI_20_1:2 1SMAI_20_2:2 2SMAI_20_3:2 3SMAI_20_4:2 4SMAI_20_5:2 5SMAI_20_6:2 6SMAI_20_7:2 7SMAI_20_8:2 8SMAI_20_9:2 9SMAI_20_10:2 10SMAI_20_11:2 11SMAI_20_12:2 12

Task time group 2

DFTRefGrp7

IEC09000029 V1 EN

Figure 167: SMAI instances as organized in different task time groups and thecorresponding parameter numbers

The example shows a situation with adaptive frequency tracking with one referenceselected for all instances. In practice each instance can be adapted to the needs ofthe actual application. The adaptive frequency tracking is needed in IEDs thatbelong to the protection system of synchronous machines and that are active duringrun-up and shout-down of the machine. In other application the usual setting of theparameter DFTReference of SMAI is InternalDFTRef.

Example 1

Section 17 1MRK 504 134-UEN -Basic IED functions

368Application Manual

Page 375: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

SMAI_20_7:1BLOCKDFTSPFCREVROT^GRP1L1^GRP1L2^GRP1L3^GRP1N

SPFCOUTAI3P

AI1AI2AI3AI4AIN

SMAI_20_1-12:2BLOCKDFTSPFCREVROT^GRP1L1^GRP1L2^GRP1L3^GRP1N

SPFCOUTAI3P

AI1AI2AI3AI4AIN

IEC09000028-2-en.vsdIEC09000028 V2 EN

Figure 168: Configuration for using an instance in task time group 1 as DFTreference

Assume instance SMAI_20_7:1 in task time group 1 has been selected in theconfiguration to control the frequency tracking (For the SMAI_20_x of task timegroup 1). Observe that the selected reference instance (i.e. frequency trackingmaster) must be a voltage type. Observe that positive sequence voltage is used forthe frequency tracking feature.

For task time group 1 this gives the following settings (see Figure 167 for numbering):

SMAI_20_1:1 DFTRefExtOut = DFTRefGrp7 to route SMAI_20_7:1 reference tothe SPFCOUT output, DFTReference = DFTRefGrp7 for SMAI_20_7:1 to useSMAI_20_7:1 as reference (see Figure 168). .

SMAI_20_2:1 - SMAI_20_12:1 DFTReference = DFTRefGrp7 for SMAI_20_2:1 -SMAI_20_12:1 to use SMAI_20_7:1 as reference.

For task time group 2 this gives the following settings:

SMAI_20_2:2: DFTReference = ExternalDFTRef to use DFTSPFC input asreference (SMAI_20_7:1); DFTRefExtOut = ExternalDFTRef (even if the outputSPCFOUT is not wired in AC).

SMAI_20_2:2 - SMAI_20_12:2 DFTReference = ExternalDFTRef to useDFTSPFC input as reference (SMAI_20_7:1)

17.10 Summation block 3 phase 3PHSUM

17.10.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Summation block 3 phase 3PHSUM - -

1MRK 504 134-UEN - Section 17Basic IED functions

369Application Manual

Page 376: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

17.10.2 ApplicationSummation block 3 phase function 3PHSUM is used to get the sum of two sets ofthree-phase analog signals (of the same type) for those IED functions that mightneed it.

17.10.3 Setting guidelinesThe summation block receives the three-phase signals from SMAI blocks. Thesummation block has several settings.

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

SummationType: Summation type (Group 1 + Group 2, Group 1 - Group 2, Group2 - Group 1 or –(Group 1 + Group 2)).

DFTReference: The reference DFT block (InternalDFT Ref,DFTRefGrp1 orExternal DFT ref) .

FreqMeasMinVal: The minimum value of the voltage for which the frequency iscalculated, expressed as percent of UBase (for each instance x).

17.11 Global base values GBASVAL

17.11.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Global base values GBASVAL - -

17.11.2 ApplicationGlobal base values function (GBASVAL) is used to provide global values,common for all applicable functions within the IED. One set of global valuesconsists of values for current, voltage and apparent power and it is possible to havesix different sets.

This is an advantage since all applicable functions in the IED use a single source ofbase values. This facilitates consistency throughout the IED and also facilitates asingle point for updating values when necessary.

Each applicable function in the IED has a parameter, GlobalBaseSel, defining oneout of the six sets of GBASVAL functions.

Section 17 1MRK 504 134-UEN -Basic IED functions

370Application Manual

Page 377: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

17.11.3 Setting guidelinesUBase: Phase-to-phase voltage value to be used as a base value for applicablefunctions throughout the IED.

IBase: Phase current value to be used as a base value for applicable functionsthroughout the IED.

SBase: Standard apparent power value to be used as a base value for applicablefunctions throughout the IED, typically SBase=√3·UBase·IBase.

17.12 Authority check ATHCHCK

17.12.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Authority check ATHCHCK - -

17.12.2 ApplicationTo safeguard the interests of our customers, both the IED and the tools that areaccessing the IED are protected, by means of authorization handling. Theauthorization handling of the IED and the PCM600 is implemented at both accesspoints to the IED:

• local, through the local HMI• remote, through the communication ports

The IED users can be created, deleted and edited only with PCM600 IED usermanagement tool.

1MRK 504 134-UEN - Section 17Basic IED functions

371Application Manual

Page 378: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

IEC12000202-1-en.vsdIEC12000202 V1 EN

Figure 169: PCM600 user management tool

17.12.2.1 Authorization handling in the IED

At delivery the default user is the SuperUser. No Log on is required to operate theIED until a user has been created with the IED User Management..

Once a user is created and written to the IED, that user can perform a Log on, usingthe password assigned in the tool. Then the default user will be Guest.

If there is no user created, an attempt to log on will display a message box: “Nouser defined!”

If one user leaves the IED without logging off, then after the timeout (set in Mainmenu/Configuration/HMI/Screen/SCREEN:1) elapses, the IED returns to Gueststate, when only reading is possible. By factory default, the display timeout is set to60 minutes.

If one or more users are created with the IED User Management and written to theIED, then, when a user attempts a Log on by pressing the key or when the userattempts to perform an operation that is password protected, the Log on windowopens.

Section 17 1MRK 504 134-UEN -Basic IED functions

372Application Manual

Page 379: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

The cursor is focused on the User identity field, so upon pressing the key, onecan change the user name, by browsing the list of users, with the “up” and “down”arrows. After choosing the right user name, the user must press the key again.

When it comes to password, upon pressing the key, the following characterswill show up: “”. The user must scroll for every letter in thepassword. After all the letters are introduced (passwords are case sensitive) chooseOK and press the key again.

At successful Log on, the local HMI shows the new user name in the status bar atthe bottom of the LCD. If the Log on is OK, when required to change for examplea password protected setting, the local HMI returns to the actual setting folder. Ifthe Log on has failed, an "Error Access Denied" message opens. If a user enters anincorrect password three times, that user will be blocked for ten minutes before anew attempt to log in can be performed. The user will be blocked from logging in,both from the local HMI and PCM600. However, other users are to log in duringthis period.

17.13 Authority status ATHSTAT

17.13.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Authority status ATHSTAT - -

17.13.2 ApplicationAuthority status (ATHSTAT) function is an indication function block, whichinforms about two events related to the IED and the user authorization:

• the fact that at least one user has tried to log on wrongly into the IED and itwas blocked (the output USRBLKED)

• the fact that at least one user is logged on (the output LOGGEDON)

The two outputs of ATHSTAT function can be used in the configuration fordifferent indication and alarming reasons, or can be sent to the station control forthe same purpose.

1MRK 504 134-UEN - Section 17Basic IED functions

373Application Manual

Page 380: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

17.14 Denial of service

17.14.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Denial of service, frame rate control forfront port

DOSFRNT - -

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Denial of service, frame rate control forLAN1 port

DOSLAN1 - -

17.14.2 ApplicationThe denial of service functions (DOSFRNT,DOSLAN1 and DOSSCKT) aredesigned to limit the CPU load that can be produced by Ethernet network traffic onthe IED. The communication facilities must not be allowed to compromise theprimary functionality of the device. All inbound network traffic will be quotacontrolled so that too heavy network loads can be controlled. Heavy network loadmight for instance be the result of malfunctioning equipment connected to thenetwork.

DOSFRNT, DOSLAN1 and DOSSCKT measures the IED load fromcommunication and, if necessary, limit it for not jeopardizing the IEDs control andprotection functionality due to high CPU load. The function has the following outputs:

• LINKUP indicates the Ethernet link status• WARNING indicates that communication (frame rate) is higher than normal• ALARM indicates that the IED limits communication

17.14.3 Setting guidelinesThe function does not have any parameters available in the local HMI or PCM600.

Section 17 1MRK 504 134-UEN -Basic IED functions

374Application Manual

Page 381: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Section 18 Requirements

18.1 Current transformer requirements

The performance of a protection function will depend on the quality of themeasured current signal. Saturation of the current transformer (CT) will causedistortion of the current signal and can result in a failure to operate or causeunwanted operations of some functions. Consequently CT saturation can have aninfluence on both the dependability and the security of the protection. Thisprotection IED has been designed to permit heavy CT saturation with maintainedcorrect operation.

18.1.1 Current transformer classificationTo guarantee correct operation, the current transformers (CTs) must be able tocorrectly reproduce the current for a minimum time before the CT will begin tosaturate. To fulfill the requirement on a specified time to saturation the CTs mustfulfill the requirements of a minimum secondary e.m.f. that is specified below.

There are several different ways to specify CTs. Conventional magnetic core CTsare usually specified and manufactured according to some international or nationalstandards, which specify different protection classes as well. There are manydifferent standards and a lot of classes but fundamentally there are three differenttypes of CTs:

• High remanence type CT• Low remanence type CT• Non remanence type CT

The high remanence type has no limit for the remanent flux. This CT has amagnetic core without any airgap and a remanent flux might remain almost infinitetime. In this type of transformers the remanence can be up to around 80% of thesaturation flux. Typical examples of high remanence type CT are class P, PX, TPS,TPX according to IEC, class P, X according to BS (old British Standard) and nongapped class C, K according to ANSI/IEEE.

The low remanence type has a specified limit for the remanent flux. This CT ismade with a small air gap to reduce the remanence to a level that does not exceed10% of the saturation flux. The small air gap has only very limited influences onthe other properties of the CT. Class PR, TPY according to IEC are low remanencetype CTs.

1MRK 504 134-UEN - Section 18Requirements

375Application Manual

Page 382: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

The non remanence type CT has practically negligible level of remanent flux.This type of CT has relatively big air gaps in order to reduce the remanence topractically zero level. In the same time, these air gaps reduce the influence of the DC-component from the primary fault current. The air gaps will also decrease themeasuring accuracy in the non-saturated region of operation. Class TPZ accordingto IEC is a non remanence type CT.

Different standards and classes specify the saturation e.m.f. in different ways but itis possible to approximately compare values from different classes. The ratedequivalent limiting secondary e.m.f. Eal according to the IEC 60044 – 6 standard isused to specify the CT requirements for the IED. The requirements are alsospecified according to other standards.

18.1.2 ConditionsThe requirements are a result of investigations performed in our network simulator.The current transformer models are representative for current transformers of highremanence and low remanence type. The results may not always be valid for nonremanence type CTs (TPZ).

The performances of the protection functions have been checked in the range fromsymmetrical to fully asymmetrical fault currents. Primary time constants of at least120 ms have been considered at the tests. The current requirements below are thusapplicable both for symmetrical and asymmetrical fault currents.

Depending on the protection function phase-to-earth, phase-to-phase and three-phase faults have been tested for different relevant fault positions for example,close in forward and reverse faults, zone 1 reach faults, internal and external faults.The dependability and security of the protection was verified by checking forexample, time delays, unwanted operations, directionality, overreach and stability.

The remanence in the current transformer core can cause unwanted operations orminor additional time delays for some protection functions. As unwantedoperations are not acceptable at all maximum remanence has been considered forfault cases critical for the security, for example, faults in reverse direction andexternal faults. Because of the almost negligible risk of additional time delays andthe non-existent risk of failure to operate the remanence have not been consideredfor the dependability cases. The requirements below are therefore fully valid for allnormal applications.

It is difficult to give general recommendations for additional margins forremanence to avoid the minor risk of an additional time delay. They depend on theperformance and economy requirements. When current transformers of lowremanence type (for example, TPY, PR) are used, normally no additional margin isneeded. For current transformers of high remanence type (for example, P, PX, TPS,TPX) the small probability of fully asymmetrical faults, together with highremanence in the same direction as the flux generated by the fault, has to be kept inmind at the decision of an additional margin. Fully asymmetrical fault current willbe achieved when the fault occurs at approximately zero voltage (0°).

Section 18 1MRK 504 134-UEN -Requirements

376Application Manual

Page 383: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Investigations have shown that 95% of the faults in the network will occur whenthe voltage is between 40° and 90°. In addition fully asymmetrical fault currentwill not exist in all phases at the same time.

18.1.3 Fault currentThe current transformer requirements are based on the maximum fault current forfaults in different positions. Maximum fault current will occur for three-phasefaults or single phase-to-earth faults. The current for a single phase-to-earth faultwill exceed the current for a three-phase fault when the zero sequence impedancein the total fault loop is less than the positive sequence impedance.

When calculating the current transformer requirements, maximum fault current forthe relevant fault position should be used and therefore both fault types have to beconsidered.

18.1.4 Secondary wire resistance and additional loadThe voltage at the current transformer secondary terminals directly affects thecurrent transformer saturation. This voltage is developed in a loop containing thesecondary wires and the burden of all relays in the circuit. For earth faults the loopincludes the phase and neutral wire, normally twice the resistance of the singlesecondary wire. For three-phase faults the neutral current is zero and it is justnecessary to consider the resistance up to the point where the phase wires areconnected to the common neutral wire. The most common practice is to use fourwires secondary cables so it normally is sufficient to consider just a singlesecondary wire for the three-phase case.

The conclusion is that the loop resistance, twice the resistance of the singlesecondary wire, must be used in the calculation for phase-to-earth faults and thephase resistance, the resistance of a single secondary wire, may normally be usedin the calculation for three-phase faults.

As the burden can be considerable different for three-phase faults and phase-to-earth faults it is important to consider both cases. Even in a case where the phase-to-earth fault current is smaller than the three-phase fault current the phase-to-earthfault can be dimensioning for the CT depending on the higher burden.

In isolated or high impedance earthed systems the phase-to-earth fault is not thedimensioning case and therefore the resistance of the single secondary wire alwayscan be used in the calculation, for this case.

18.1.5 General current transformer requirementsThe current transformer ratio is mainly selected based on power system data forexample, maximum load. However, it should be verified that the current to theprotection is higher than the minimum operating value for all faults that are to be

1MRK 504 134-UEN - Section 18Requirements

377Application Manual

Page 384: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

detected with the selected CT ratio. The minimum operating current is different fordifferent functions and normally settable so each function should be checked.

The current error of the current transformer can limit the possibility to use a verysensitive setting of a sensitive residual overcurrent protection. If a very sensitivesetting of this function will be used it is recommended that the current transformershould have an accuracy class which have an current error at rated primary currentthat is less than ±1% (for example, 5P). If current transformers with less accuracyare used it is advisable to check the actual unwanted residual current during thecommissioning.

18.1.6 Rated equivalent secondary e.m.f. requirementsWith regard to saturation of the current transformer all current transformers of highremanence and low remanence type that fulfill the requirements on the ratedequivalent secondary e.m.f. Eal below can be used. The characteristic of the nonremanence type CT (TPZ) is not well defined as far as the phase angle error isconcerned. If no explicit recommendation is given for a specific function wetherefore recommend contacting ABB to confirm that the non remanence type canbe used.

The CT requirements for the different functions below are specified as a ratedequivalent limiting secondary e.m.f. Eal according to the IEC 60044-6 standard.Requirements for CTs specified in different ways are given at the end of this section.

18.1.6.1 Transformer differential protection

The current transformers must have a rated equivalent secondary e.m.f. Eal that islarger than the maximum of the required secondary e.m.f. Ealreq below:

sn Ral alreq nt CT L 2

pn r

I SE E 30 I R RI I

æ ö³ = × × × + +ç ÷

è øEQUATION1412 V1 EN (Equation 127)

sn Ral alreq tf CT L 2

pn r

I SE E 2 I R RI I

æ ö³ = × × × + +ç ÷

è øEQUATION1413 V1 EN (Equation 128)

where:

Int The rated primary current of the power transformer (A)

Itf Maximum primary fundamental frequency current that passes two main CTs andthe power transformer (A)

Ipn The rated primary CT current (A)

Isn The rated secondary CT current (A)

Table continues on next page

Section 18 1MRK 504 134-UEN -Requirements

378Application Manual

Page 385: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Ir The rated current of the protection IED (A)

RCT The secondary resistance of the CT (W)

RL The resistance of the secondary wire and additional load (W). The loopresistance containing the phase and neutral wires must be used for faults insolidly earthed systems. The resistance of a single secondary wire should beused for faults in high impedance earthed systems.

SR The burden of an IED current input channel (VA). SR=0.010 VA/channel for Ir=1A and Sr=0.250 VA/channel for Ir=5 A

In substations with breaker-and-a-half or double-busbar double-breakerarrangement, the fault current may pass two main CTs for the transformerdifferential protection without passing the power transformer. In such cases and ifboth main CTs have equal ratios and magnetization characteristics the CTs mustsatisfy equation 127 and equation 129.

sn Ral alreq f CT L 2

pn r

I SE E I R RI I

æ ö³ = × × + +ç ÷

è øEQUATION1414 V1 EN (Equation 129)

where:

If Maximum primary fundamental frequency current that passes two main CTs without passingthe power transformer (A)

18.1.6.2 1 Ph high impedance differential protection

The CTs connected to the IED must have a rated equivalent secondary e.m.f. Ealthat is larger than or equal to the required equivalent secondary e.m.f. Ealreq below:

snal alreq s tmax CT L

pn

IE E 2 U 2 I (R R )

I³ = × = × × × +

where:

Us Set operate value to the voltage relay (V)

Ikmax Maximum primary fundamental frequency fault current for through fault current for externalfaults (A)

Ipn The rated primary CT current (A)

Isn The rated secondary CT current (A)

RCT The secondary resistance of the CT (Ω)

RL The resistance of the secondary cable from the CT up to a common junction point (Ω). Theloop resistance containing the phase and neutral wires, must be used for faults in solidlyearthed systems and the resistance of a single-phase wire should be used for faults in highimpedance earthed systems.

1MRK 504 134-UEN - Section 18Requirements

379Application Manual

Page 386: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

All CTs to the same protection should have identical turn ratios. Consequentlyauxiliary CTs cannot normally be used. The IED must be provided with separatecores.

18.1.6.3 Breaker failure protection

The CTs must have a rated equivalent secondary e.m.f. Eal that is larger than orequal to the required secondary e.m.f. Ealreq below:

sn Ral alreq op CT L 2

pn r

I SE E 5 I R RI I

æ ö³ = × × × + +ç ÷

è øEQUATION1380 V1 EN (Equation 131)

where:

Iop The primary operate value (A)

Ipn The rated primary CT current (A)

Isn The rated secondary CT current (A)

Ir The rated current of the protection IED (A)

RCT The secondary resistance of the CT (W)

RL The resistance of the secondary cable and additional load (W). The loop resistancecontaining the phase and neutral wires, must be used for faults in solidly earthed systems.The resistance of a single secondary wire should be used for faults in high impedanceearthed systems.

SR The burden of an IED current input channel (VA). SR=0.010 VA/channel for Ir=1 A andSR=0.250 VA/channel for Ir=5 A

18.1.6.4 Non-directional instantaneous and definitive time, phase and residualovercurrent protection

The CTs must have a rated equivalent secondary e.m.f. Eal that is larger than orequal to the required secondary e.m.f. Ealreq below:

Section 18 1MRK 504 134-UEN -Requirements

380Application Manual

Page 387: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

sn Ral alreq op CT L 2

pn r

I SE E 1,5 I R RI I

æ ö³ = × × × + +ç ÷

è øEQUATION1381 V1 EN (Equation 132)

where:

Iop The primary operate value (A)

Ipn The rated primary CT current (A)

Isn The rated secondary CT current (A)

Ir The rated current of the protection IED (A)

RCT The secondary resistance of the CT (W)

RL The resistance of the secondary cable and additional load (W). The loop resistancecontaining the phase and neutral wires, must be used for faults in solidly earthed systems.The resistance of a single secondary wire should be used for faults in high impedanceearthed systems.

SR The burden of an IED current input channel (VA). SR=0.010 VA/channel for Ir=1 A andSR=0.250 VA/channel for Ir=5 A

18.1.6.5 Non-directional inverse time delayed phase and residual overcurrentprotection

The requirement according to Equation 133 and Equation 134 does not need to befulfilled if the high set instantaneous or definitive time stage is used. In this caseEquation 132 is the only necessary requirement.

If the inverse time delayed function is the only used overcurrent protection functionthe CTs must have a rated equivalent secondary e.m.f. Eal that is larger than orequal to the required secondary e.m.f. Ealreq below:

sn Ral alreq op CT L 2

pn r

I SE E 20 I R RI I

æ ö³ = × × × + +ç ÷

è øEQUATION1076 V1 EN (Equation 133)

where

Iop The primary current set value of the inverse time function (A)

Ipn The rated primary CT current (A)

Isn The rated secondary CT current (A)

Ir The rated current of the protection IED (A)

Table continues on next page

1MRK 504 134-UEN - Section 18Requirements

381Application Manual

Page 388: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

RCT The secondary resistance of the CT (W)

RL The resistance of the secondary cable and additional load (W). The loopresistance containing the phase and neutral wires, must be used for faults insolidly earthed systems. The resistance of a single secondary wire should beused for faults in high impedance earthed systems.

SR The burden of an IED current input channel (VA). SR=0.010 VA/channel for Ir=1A and SR=0.250 VA/channel for Ir=5 A

Independent of the value of Iop the maximum required Eal is specified according tothe following:

sn Ral alreq max k max CT L 2

pn r

I SE E I R RI I

æ ö³ = × × + +ç ÷

è øEQUATION1077 V1 EN (Equation 134)

where

Ikmax Maximum primary fundamental frequency current for close-in faults (A)

18.1.6.6 Directional phase and residual overcurrent protection

If the directional overcurrent function is used the CTs must have a rated equivalentsecondary e.m.f. Eal that is larger than or equal to the required equivalentsecondary e.m.f. Ealreq below:

sn Ral alreq k max CT L 2

pn r

I SE E I R RI I

æ ö³ = × × + +ç ÷

è øEQUATION1078 V1 EN (Equation 135)

where:

Ikmax Maximum primary fundamental frequency current for close-in forward and reverse faults (A)

Ipn The rated primary CT current (A)

Isn The rated secondary CT current (A)

Ir The rated current of the protection IED (A)

RCT The secondary resistance of the CT (W)

RL The resistance of the secondary cable and additional load (W). The loop resistancecontaining the phase and neutral wires, must be used for faults in solidly earthed systems.The resistance of a single secondary wire should be used for faults in high impedanceearthed systems.

SR The burden of an IED current input channel (VA). Sr=0.010 VA/channel for Ir=1 A andSr=0.250 VA/channel for Ir=5 A

Section 18 1MRK 504 134-UEN -Requirements

382Application Manual

Page 389: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

18.1.7 Current transformer requirements for CTs according toother standardsAll kinds of conventional magnetic core CTs are possible to use with the IEDs ifthey fulfill the requirements corresponding to the above specified expressed as therated equivalent secondary e.m.f. Eal according to the IEC 60044-6 standard. Fromdifferent standards and available data for relaying applications it is possible toapproximately calculate a secondary e.m.f. of the CT comparable with Eal. Bycomparing this with the required secondary e.m.f. Ealreq it is possible to judge if theCT fulfills the requirements. The requirements according to some other standardsare specified below.

18.1.7.1 Current transformers according to IEC 60044-1, class P, PR

A CT according to IEC 60044-1 is specified by the secondary limiting e.m.f. E2max.The value of the E2max is approximately equal to the corresponding Eal accordingto IEC 60044-6. Therefore, the CTs according to class P and PR must have asecondary limiting e.m.f. E2max that fulfills the following:

2 max max alreqE E>

EQUATION1383 V2 EN (Equation 136)

18.1.7.2 Current transformers according to IEC 60044-1, class PX, IEC60044-6, class TPS (and old British Standard, class X)

CTs according to these classes are specified approximately in the same way by arated knee-point e.m.f. Eknee (Ek for class PX, EkneeBS for class X and the limitingsecondary voltage Ual for TPS). The value of the Eknee is lower than thecorresponding Eal according to IEC 60044-6. It is not possible to give a generalrelation between the Eknee and the Eal but normally the Eknee is approximately 80 %of the Eal. Therefore, the CTs according to class PX, X and TPS must have a ratedknee-point e.m.f. Eknee that fulfills the following:

Eknee » Ek » EkneeBS » Ual > 0.8 · (maximum of Ealreq)EQUATION2100 V1 EN (Equation 137)

18.1.7.3 Current transformers according to ANSI/IEEE

Current transformers according to ANSI/IEEE are partly specified in differentways. A rated secondary terminal voltage UANSI is specified for a CT of class C.

1MRK 504 134-UEN - Section 18Requirements

383Application Manual

Page 390: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

UANSI is the secondary terminal voltage the CT will deliver to a standard burden at20 times rated secondary current without exceeding 10 % ratio correction. Thereare a number of standardized UANSI values for example, UANSI is 400 V for a C400CT. A corresponding rated equivalent limiting secondary e.m.f. EalANSI can beestimated as follows:

Ea lANSI 20 Isn RCT UA NSI+× × 20 Isn RC T× × 20 Isn ZbANSI× ×+= =

EQUATION971 V1 EN (Equation 138)

where:

ZbANSI The impedance (that is, complex quantity) of the standard ANSI burden for the specific Cclass (W)

UANSI The secondary terminal voltage for the specific C class (V)

The CTs according to class C must have a calculated rated equivalent limitingsecondary e.m.f. EalANSI that fulfills the following:

alANSI alreqE max imum of E>

EQUATION1384 V1 EN (Equation 139)

A CT according to ANSI/IEEE is also specified by the knee-point voltageUkneeANSI that is graphically defined from an excitation curve. The knee-pointvoltage UkneeANSI normally has a lower value than the knee-point e.m.f. accordingto IEC and BS. UkneeANSI can approximately be estimated to 75 % of thecorresponding Eal according to IEC 60044 6. Therefore, the CTs according to ANSI/IEEE must have a knee-point voltage UkneeANSI that fulfills the following:

EkneeANSI > 0.75 · (maximum of Ealreq)EQUATION2101 V1 EN (Equation 140)

18.2 Voltage transformer requirements

The performance of a protection function will depend on the quality of themeasured input signal. Transients caused by capacitive voltage transformers(CVTs) can affect some protection functions.

Magnetic or capacitive voltage transformers can be used.

The capacitive voltage transformers (CVTs) should fulfill the requirementsaccording to the IEC 60044–5 standard regarding ferro-resonance and transients.The ferro-resonance requirements of the CVTs are specified in chapter 7.4 of thestandard.

Section 18 1MRK 504 134-UEN -Requirements

384Application Manual

Page 391: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

The transient responses for three different standard transient response classes, T1,T2 and T3 are specified in chapter 15.5 of the standard. CVTs according to allclasses can be used.

The protection IED has effective filters for these transients, which gives secure andcorrect operation with CVTs.

18.3 SNTP server requirements

18.3.1 SNTP server requirementsThe SNTP server to be used is connected to the local network, that is not more than4-5 switches or routers away from the IED. The SNTP server is dedicated for itstask, or at least equipped with a real-time operating system, that is not a PC withSNTP server software. The SNTP server should be stable, that is, eithersynchronized from a stable source like GPS, or local without synchronization.Using a local SNTP server without synchronization as primary or secondary serverin a redundant configuration is not recommended.

1MRK 504 134-UEN - Section 18Requirements

385Application Manual

Page 392: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

386

Page 393: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Section 19 Glossary

AC Alternating current

ACT Application configuration tool within PCM600

A/D converter Analog-to-digital converter

ADBS Amplitude deadband supervision

AI Analog input

ANSI American National Standards Institute

AR Autoreclosing

ASCT Auxiliary summation current transformer

ASD Adaptive signal detection

AWG American Wire Gauge standard

BI Binary input

BOS Binary outputs status

BR External bistable relay

BS British Standards

CAN Controller Area Network. ISO standard (ISO 11898) forserial communication

CB Circuit breaker

CCITT Consultative Committee for International Telegraph andTelephony. A United Nations-sponsored standards bodywithin the International Telecommunications Union.

CCVT Capacitive Coupled Voltage Transformer

Class C Protection Current Transformer class as per IEEE/ ANSI

CMPPS Combined megapulses per second

CMT Communication Management tool in PCM600

CO cycle Close-open cycle

Codirectional Way of transmitting G.703 over a balanced line. Involvestwo twisted pairs making it possible to transmit informationin both directions

COMTRADE Standard format according to IEC 60255-24

Contra-directional Way of transmitting G.703 over a balanced line. Involvesfour twisted pairs, two of which are used for transmittingdata in both directions and two for transmitting clock signals

1MRK 504 134-UEN - Section 19Glossary

387Application Manual

Page 394: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

CPU Central processing unit

CR Carrier receive

CRC Cyclic redundancy check

CROB Control relay output block

CS Carrier send

CT Current transformer

CVT Capacitive voltage transformer

DAR Delayed autoreclosing

DARPA Defense Advanced Research Projects Agency (The USdeveloper of the TCP/IP protocol etc.)

DBDL Dead bus dead line

DBLL Dead bus live line

DC Direct current

DFC Data flow control

DFT Discrete Fourier transform

DHCP Dynamic Host Configuration Protocol

DIP-switch Small switch mounted on a printed circuit board

DI Digital input

DLLB Dead line live bus

DNP Distributed Network Protocol as per IEEE Std 1815-2012

DR Disturbance recorder

DRAM Dynamic random access memory

DRH Disturbance report handler

DSP Digital signal processor

DTT Direct transfer trip scheme

EHV network Extra high voltage network

EIA Electronic Industries Association

EMC Electromagnetic compatibility

EMF Electromotive force

EMI Electromagnetic interference

EnFP End fault protection

EPA Enhanced performance architecture

ESD Electrostatic discharge

FCB Flow control bit; Frame count bit

Section 19 1MRK 504 134-UEN -Glossary

388Application Manual

Page 395: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

FOX 20 Modular 20 channel telecommunication system for speech,data and protection signals

FOX 512/515 Access multiplexer

FOX 6Plus Compact time-division multiplexer for the transmission ofup to seven duplex channels of digital data over optical fibers

G.703 Electrical and functional description for digital lines used bylocal telephone companies. Can be transported overbalanced and unbalanced lines

GCM Communication interface module with carrier of GPSreceiver module

GDE Graphical display editor within PCM600

GI General interrogation command

GIS Gas-insulated switchgear

GOOSE Generic object-oriented substation event

GPS Global positioning system

GSAL Generic security application

HDLC protocol High-level data link control, protocol based on the HDLCstandard

HFBR connectortype

Plastic fiber connector

HMI Human-machine interface

HSAR High speed autoreclosing

HV High-voltage

HVDC High-voltage direct current

IDBS Integrating deadband supervision

IEC International Electrical Committee

IEC 60044-6 IEC Standard, Instrument transformers – Part 6:Requirements for protective current transformers fortransient performance

IEC 61850 Substation automation communication standard

IEC 61850–8–1 Communication protocol standard

IEEE Institute of Electrical and Electronics Engineers

IEEE 802.12 A network technology standard that provides 100 Mbits/s ontwisted-pair or optical fiber cable

IEEE P1386.1 PCI Mezzanine Card (PMC) standard for local bus modules.References the CMC (IEEE P1386, also known as CommonMezzanine Card) standard for the mechanics and the PCI

1MRK 504 134-UEN - Section 19Glossary

389Application Manual

Page 396: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

specifications from the PCI SIG (Special Interest Group) forthe electrical EMF (Electromotive force).

IEEE 1686 Standard for Substation Intelligent Electronic Devices(IEDs) Cyber Security Capabilities

IED Intelligent electronic device

I-GIS Intelligent gas-insulated switchgear

Instance When several occurrences of the same function are availablein the IED, they are referred to as instances of that function.One instance of a function is identical to another of the samekind but has a different number in the IED user interfaces.The word "instance" is sometimes defined as an item ofinformation that is representative of a type. In the same wayan instance of a function in the IED is representative of atype of function.

IP 1. Internet protocol. The network layer for the TCP/IPprotocol suite widely used on Ethernet networks. IP is aconnectionless, best-effort packet-switching protocol. Itprovides packet routing, fragmentation and reassemblythrough the data link layer.2. Ingression protection, according to IEC standard

IP 20 Ingression protection, according to IEC standard, level 20

IP 40 Ingression protection, according to IEC standard, level 40

IP 54 Ingression protection, according to IEC standard, level 54

IRF Internal failure signal

IRIG-B: InterRange Instrumentation Group Time code format B,standard 200

ITU International Telecommunications Union

LAN Local area network

LIB 520 High-voltage software module

LCD Liquid crystal display

LDD Local detection device

LED Light-emitting diode

MCB Miniature circuit breaker

MCM Mezzanine carrier module

MVB Multifunction vehicle bus. Standardized serial bus originallydeveloped for use in trains.

NCC National Control Centre

OCO cycle Open-close-open cycle

OCP Overcurrent protection

Section 19 1MRK 504 134-UEN -Glossary

390Application Manual

Page 397: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

OLTC On-load tap changer

OV Over-voltage

Overreach A term used to describe how the relay behaves during a faultcondition. For example, a distance relay is overreachingwhen the impedance presented to it is smaller than theapparent impedance to the fault applied to the balance point,that is, the set reach. The relay “sees” the fault but perhaps itshould not have seen it.

PCI Peripheral component interconnect, a local data bus

PCM Pulse code modulation

PCM600 Protection and control IED manager

PC-MIP Mezzanine card standard

PMC PCI Mezzanine card

POR Permissive overreach

POTT Permissive overreach transfer trip

Process bus Bus or LAN used at the process level, that is, in nearproximity to the measured and/or controlled components

PSM Power supply module

PST Parameter setting tool within PCM600

PT ratio Potential transformer or voltage transformer ratio

PUTT Permissive underreach transfer trip

RASC Synchrocheck relay, COMBIFLEX

RCA Relay characteristic angle

RFPP Resistance for phase-to-phase faults

RFPE Resistance for phase-to-earth faults

RISC Reduced instruction set computer

RMS value Root mean square value

RS422 A balanced serial interface for the transmission of digitaldata in point-to-point connections

RS485 Serial link according to EIA standard RS485

RTC Real-time clock

RTU Remote terminal unit

SA Substation Automation

SBO Select-before-operate

SC Switch or push button to close

SCS Station control system

1MRK 504 134-UEN - Section 19Glossary

391Application Manual

Page 398: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

SCADA Supervision, control and data acquisition

SCT System configuration tool according to standard IEC 61850

SDU Service data unit

SMA connector Subminiature version A, A threaded connector with constantimpedance.

SMT Signal matrix tool within PCM600

SMS Station monitoring system

SNTP Simple network time protocol – is used to synchronizecomputer clocks on local area networks. This reduces therequirement to have accurate hardware clocks in everyembedded system in a network. Each embedded node caninstead synchronize with a remote clock, providing therequired accuracy.

SRY Switch for CB ready condition

ST Switch or push button to trip

Starpoint Neutral point of transformer or generator

SVC Static VAr compensation

TC Trip coil

TCS Trip circuit supervision

TCP Transmission control protocol. The most common transportlayer protocol used on Ethernet and the Internet.

TCP/IP Transmission control protocol over Internet Protocol. The defacto standard Ethernet protocols incorporated into 4.2BSDUnix. TCP/IP was developed by DARPA for Internetworking and encompasses both network layer and transportlayer protocols. While TCP and IP specify two protocols atspecific protocol layers, TCP/IP is often used to refer to theentire US Department of Defense protocol suite based uponthese, including Telnet, FTP, UDP and RDP.

TNC connector Threaded Neill-Concelman, a threaded constant impedanceversion of a BNC connector

TPZ, TPY, TPX,TPS

Current transformer class according to IEC

UMT User management tool

Underreach A term used to describe how the relay behaves during a faultcondition. For example, a distance relay is underreachingwhen the impedance presented to it is greater than theapparent impedance to the fault applied to the balance point,that is, the set reach. The relay does not “see” the fault butperhaps it should have seen it. See also Overreach.

Section 19 1MRK 504 134-UEN -Glossary

392Application Manual

Page 399: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

UTC Coordinated Universal Time. A coordinated time scale,maintained by the Bureau International des Poids et Mesures(BIPM), which forms the basis of a coordinateddissemination of standard frequencies and time signals. UTCis derived from International Atomic Time (TAI) by theaddition of a whole number of "leap seconds" to synchronizeit with Universal Time 1 (UT1), thus allowing for theeccentricity of the Earth's orbit, the rotational axis tilt (23.5degrees), but still showing the Earth's irregular rotation, onwhich UT1 is based. The Coordinated Universal Time isexpressed using a 24-hour clock, and uses the Gregoriancalendar. It is used for aeroplane and ship navigation, whereit is also sometimes known by the military name, "Zulutime." "Zulu" in the phonetic alphabet stands for "Z", whichstands for longitude zero.

UV Undervoltage

WEI Weak end infeed logic

VT Voltage transformer

X.21 A digital signalling interface primarily used for telecomequipment

3IO Three times zero-sequence current. Often referred to as theresidual or the earth-fault current

3UO Three times the zero sequence voltage. Often referred to asthe residual voltage or the neutral point voltage

1MRK 504 134-UEN - Section 19Glossary

393Application Manual

Page 400: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

394

Page 401: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

395

Page 402: 1MRK504134-UEN - En Application Manual Transformer Protection RET650 1.3 IEC

Contact us

ABB ABSubstation Automation ProductsSE-721 59 Västerås, SwedenPhone +46 (0) 21 32 50 00Fax +46 (0) 21 14 69 18

www.abb.com/substationautomation

1MR

K 5

04 1

34-U

EN

Cop

yrig

ht 2

013

AB

B. A

ll rig

hts

rese

rved

.