i0522-77 js condair cp3 8pp brochure aw 08/14.qxp … condensate hose 4 water filter isolation valve...

8
CONDAIR CP3 Electrode boiler steam humidifier Reliable and economic steam humidification Humidification and Evaporative Cooling

Upload: trandang

Post on 27-May-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

CONDAIR CP3Electrode boiler steam humidifierReliable and economic steam humidification

Humidification and Evaporative Cooling

i0522-77 JS Condair CP3 8pp Brochure AW 08/14.qxp_Layout 1 07/10/2014 14:25 Page 1

Condair CP3Electrode boiler steam humidifier

Electrode plugsEasy to remove

Steam cylinderCleanable or disposable options withzinc coated steel elements for long lifeand reliable operation. Condair CP3steam cylinders can last up to threetimes longer than other electrodeboilers due to the humidifier’sadvanced scale management features.

Conductivity monitoringMineral levels in the water areproactively monitored by currentsensors and precise drains areperformed to maintain an optimumwater mineral level. This reduces scalebuild-up in the steam cylinder, prolongsthe cylinders operational lifetime,minimises necessary maintenance andreduces spares costs.

Pumped drainIncreases the amount of scale removedfrom the system to prolong cylinder lifeand reduce maintenance.

i0522-77 JS Condair CP3 8pp Brochure AW 08/14.qxp_Layout 1 07/10/2014 14:25 Page 3

CasingPowder coated steel as standard withstainless steel option.

BMS connectionOptional card for remote BMSoperation.

The Condair CP3 electrode boiler steamhumidifier is an economic yetdependable solution for steamhumidification.

It is easy to install, simple to use andprovides accurate and responsivehumidity control. Innovative features,such as water conductivity monitoringand staged electrode use, maximisethe lifetime of the steam cylinder and

extend the operational periodsbetween service requirements.When servicing is needed, the CondairCP3’s design makes it easy to drain,remove and replace the disposablesteam cylinder, keeping downtime to a minimum.

Large, clear LCD display

Easy to operate keypad

LED operational indicators

Hinged control panelFor easy access to electronics.

i0522-77 JS Condair CP3 8pp Brochure AW 08/14.qxp_Layout 1 07/10/2014 14:25 Page 4

The Condair CP3 automatically calculates the conductivity of the water in theboiling cylinder to provide accurate humidity control.

Water conductivity managementAn electrode boiler humidifier operatesby passing electrical current throughwater to heat it. As the waterevaporates, its mineral contentbecomes more concentrated. Thisincreased level of conductivity affectsthe level of steam production. To maintain an accurate output, theconcentration of minerals in the water is automatically reduced throughdrainage and replacement with fresh water.

Steel electrodes with “lattice” designThe robust zinc coated steel elementsprovide a long operational life. Theirspecial lattice structure offers thegreatest possible surface area foroptimal transfer of current to thewater.

Staged electrode use to prolong lifeOnly the lower sections of theelectrodes are initially submerged andused to create steam. During operationthe parts of the electrodes submergedin the water become encrusted with

scale. As their conductivity reduces thewater level is automatically raised tosubmerge fresh unused electrodes.

This staged approach to water levelcontrol inside the cylinder prolongs thelife of the electrodes and helpsmaintain their effectiveness inproviding accurate humidity control.

Intelligent water quality and level control

i0522-77 JS Condair CP3 8pp Brochure AW 08/14.qxp_Layout 1 07/10/2014 14:25 Page 5

Flexible use, reliable performance and easy product selection -these are the strengths of the CP3 steam humidifier

The steam cylinders are at the heart of Condair CP3 system. During theevaporation process minerals willaccumulate in the steam cylinder that after, prolonged use, will need to be removed.

Depending on your level of desiredmaintenance, the Condair CP3 offers two options:

Cleanable or disposable steam cylinders

Cleanable steam cylinders thatcan be emptied of scale andreused many times

Disposable steam cylinders toreduce maintenance time andkeep the system operating

i0522-77 JS Condair CP3 8pp Brochure AW 08/14.qxp_Layout 1 07/10/2014 14:25 Page 6

Modern building management based on integrated technology. Using e-LINKS communication with the humidification system is simple, quick and clear.

Control panelOperating the Condair CP3 is child’splay. The multiple line LCD displayindicates all operating parameters,service requirements and faultdiagnostics. Control input is via theintegrated keypad. The user-friendlysoftware reliably guides you throughthe menu, even if you infrequently usethe unit.

A CP3 card stores all commissioningsettings and allows for easy re-commissioning as well ascommissioning of several units to thesame configuration.

BMS connectivityThe humidifier has an option to beoperated from a BMS and acceptsModbus Standard, BACnet or LonWorks protocols.

Easy-to-use with optional connection to BMS

for connection to a BMS

i0522-77 JS Condair CP3 8pp Brochure AW 08/14.qxp_Layout 1 07/10/2014 14:25 Page 7

Condair’s comprehensive range of steam distribution systems for any project requirement

Steam distribution must be tailored tothe requirements of each project.Whether high or low steam outputs,close humidity control or short ductsections, for every application there isan ideal solution.

Steam distribution is the key to success

Condair OptiSorp steam distributionsystem for short evaporation distance

Condair steam distribution lances fornormal humidification requirements

Condair fan unit for direct room steamhumidification

i0522-77 JS Condair CP3 8pp Brochure AW 08/14.qxp_Layout 1 07/10/2014 14:25 Page 8

Condair plc - the new name for JS HumidifiersArtex Avenue, Rustington, Littlehampton, West Sussex, BN16 3LN, UKTel: +44 (0)1903 850200 - [email protected] - www.condair.co.uk

10/2014

Specifications

1 2

3

4

5

Standard versionDisposable steam cylinderInternal PI humidity controllerControl panel with touch pad keyboard and5-line LCD displaySelf-diagnostic systemHours run timer

OptionsAll-weather protective housingSteam distribution system CondairOptiSorpPressure equalization to 10,000 Pa

(BACnet / LonWorks) for BMSconnectionHumidity sensors and humidistats

Accesssories1 Steam distribution2 Steam hose3 Condensate hose4 Water filter isolation valve5 Direct room steam

distribution system

Condair CP3 5 8 15 20 30 45 52 60 70 80 90

Heating voltage Maximum steam output in kg/h

400Vac / 3Ph / 50..60 Hz kg/h 5 8 15 20 30 45 52 60 70 80 90

230Vac / 3Ph / 50..60 Hz kg/h 5 8

Dimensions (WxHxD) mm 1x 456x620x280 1x 559x667x350 2x 559x667x350

Control voltage 230Vac/ 1 Ph / 50..60 Hz

Operating weight (per unit) kg 1x 26 1x 65 2x 65

Conformity CE, GOST, VDE

i0522-77 JS Condair CP3 8pp Brochure AW 08/14.qxp_Layout 1 07/10/2014 14:25 Page 9