ADD2 - 1
Project No. FH186084
ADDENDUM TOSPECIFICATIONS ENTITLED
“SPECIFICATIONS FORWARDLAW COLLEGE ROOF REPLACEMENT
STATE PROJECT NO. 50003317-2WARDLAW COLLEGE
COLLEGE OF EDUCATION820 SOUTH MAIN STREET
COLUMBIA, SOUTH CAROLINA””
ADDENDUM NO. 2 JULY 24, 2019
The Specifications and Drawings contained in the project manual entitled “Specifications forWardlaw College Roof Replacement, State Project No. 50003317-2, Wardlaw College, Collegeof Education, 820 South Main Street, Columbia, South Carolina” are amended as follows:
GENERAL
1. Results were returned as Negative for Asbestos at the exterior stucco wall along RoofArea F. Asbestos test results are attached.
DRAWINGS
1. Delete Drawings G-101, A-101 and A-103 in their entirety and replace with attachedDrawings G-101, A-101, A-103 (Addendum No. 2)
Nothing herein is to be interpreted or construed as changing any provisions of the specificationsexcept as specifically stated herein.
Enclosure: Asbestos Test ResultsG-101, A-101 and A-103 (Addendum No. 2)
END OF ADDENDUM
Page 1 of 3
SiteBuildingFloor Room: Equipment
COLUMBIA080ROOF
Request # Description FM00568662 HAZMAT SURVEY - 080
CP Number 50003317-2 WARDLAW COLLEGE ROOF REPLACEMENT
Project Manager Telephone
BRANHAM, DALE777-1288
Task List
23-JUL-19 HAZMAT SURVEY RESULTSSURVEY DATE: 7/23/2019
INSPECTOR #: ANTONIO THOMPSON (GR00052)
SCOPE: THE FOLLOWING SURVEY WAS PERFORMED IN PREPARATIONS TO REPAIR DAMAGE STUCCO ON THE EXTERIOR PORTION OF THE BUILDING.
ASBESTOS SECTION: STUCCO: NEGATIVE FOR ASBESTOS
INSPECTOR NOTES:1. IF A BUILDING MATERIAL IS NOT LISTED, DO NOT ASSUME THAT IT DOES NOT CONTAIN ASBESTOS. IT MAY NOT HAVE BEEN TESTED. FOR FURTHER INFORMATION, PLEASE CONTACT THE USC HAZMAT PROGRAM.
2. IF YOU ENCOUNTER ANY OTHER MATERIALS IN PLACE AND DEEM THEM SUSPECT FOR ASBESTOS AND/OR LEAD, PLEASE STOP WORK AND CONTACT THE ASBESTOS PROGRAM MANAGER FOR FURTHER TESTING OR ABATEMENT.
3. PLEASE NOTE THAT THE MATERIAL QUANTITY PROVIDED ON THE FIELD SHEET IS ONLY AN ESTIMATE FOR SAMPLING PURPOSES. THE QUANTITY
Note Date Title
WARDLAW COLLEGE
FM00568662Description HAZMAT SURVEY - 080
FIXED PRICE
Estimated Cost
Requestor Telephone Alternate Telephone
USC Work Order
Non-Available Time
Parent WO #
$ 2,958.50
CL013-57140 (FACILITIES PLANNING - CONSTR)Billing
Supervisor's Approval
EQUIPMENT
DATE WORK STARTED CAUSE
DATE WORK COMPLETED CONDITION
CLOSING REMARKS
BENCHSTOCK MATERIALSQty Description Price Per Unit
Assigned ToCrewStart DateDue dateRequest Date by
SSINCLAIRHAZMAT16-APR-18
22-FEB-18 CAMOORE
Priority 20
State/Internal Project Number H27-Z377
*FM00568662*
Page 2 of 3
02-MAY-18
30-JUN-18
HAZMAT SURVEY RESULTS
HAZMAT SURVEY RESULTS
SHOULD BE FIELD VERIFIED FOR ALL OTHER PURPOSES INCLUDING ABATEMENT. THIS SURVEY IS ONLY VALID FOR THE DESIGNATED AREA(S)/LOCATION(S) TESTED IE: (WARDLAW COLLEGE EXTERIOR WALLS).
SURVEY DATE:05/07/2018
INSPECTOR #: SIMONE WARREN (GR00052)
SCOPE: THE FOLLOWING SURVEY WAS PERFOMRED IN PREPARATION TO REMOVE/REPLACE EXISTING ROOF AT WARDLAW COLLEGE. THE FOLLOWING SECTIONS TO BE IMPACTED INCLUDE: SECTIONS A, B, C, D, E, AND F.PLEASE SEE ATTACHMENT FOR IMAGES, BIRDS EYE VIEW OF ROOF, AND SECTION DESIGNATIONS. PLEASE NOTE: IN-HOUSE ROOFERS CORE DRILLED ROOFING MATERIAL TO THE DECK. LAB RESULTS WILL REFLECT RESULTS FOR ALL LAYERS. CLIENT INDICATED THAT HVAC DUCT WORK AND HVAC DUCT MASTICS & ITS CORRESPONDING CAULK WILL NOT BE IMPACTED BY PLANNED WORK ACTIVITIES. CLIENT HAS ALSO INDICATED THAT ROOF LAYERS SHALL BE TREATED AS ONE UNIT AND OTHERWISE CANNOT BE ABATED SEPERATELY BY LAYER.
ASBESTOS SECTION :SECTIONS A,B,C,D, E AND F • ROOFING MATERIAL: POSITIVE FOR ASBESTOS• ALL EXISTING ROOF FELT:TREATED POSITIVE FOR ASBESTOS• ROOF FLASHING (TO INCLUDE ALL PATCHWORK): POSITIVE FOR ASBESTOS.• WHITE SEALANT AND ANY OTHER MATERIAL USED TO PATCH AND SEAL AREAS ON ROOF :TREATED POSITIVE FOR ASBESTOS • ALL EXISTING CAULK ENCOUNTERED: POSITIVE FOR ASBESTOS (PLEASE SEE LINE 1 INSPECTORS NOTES FOR EXCLUSIONS TO THIS LINE ITEM) • SILVER PAINTED DECORATIVE ORNAMENTS/ROOF FELT/CAULK: POSITIVE FOR ASBESTOS. PLEASE NOTE: ROOF FELT MATERIAL WAS PRESENT UNDER SILVER PAINT. RESULTS FOR ROOF FELT: 60% CHRYSOTILE. CORRESPONDING SILVER CAULK IS ALSO POSITIVE FOR ASBESTOS.• TEXTURED PLASTER (SECTION F: INTERIOR STAIRWELL): NEGATIVE FOR ASBESTOS•HVAC DUCT WORK (BLACK INTERIOR/WHITE EXTERIOR) : NEGATIVE FOR ASBESTOS
LEAD SECTION:SILVER PAINT OBSERVED ON DECORATIVE ORNAMENTS: POSITIVE FOR LEADYELLOW PAINTED WALL AT METAL COPING: POSITIVE FOR LEAD WHITE & RED PAINT ON BIRD HOUSE (METAL AND CONCRETE SUBSTRATE): POSITIVE FOR LEAD VENT PIPES: POSITIVE FOR LEADGREEN/BLACK PAINTED CAULK (SECTION C-ACCESS PANEL BOX): NEGATIVE FOR LEADELEVATOR MACHINE RM EXTERIOR WALLS: NEGATIVE FOR LEAD BEIGE PAINTED STAIR WELL (SECTION F):NEGATIVE FOR LEAD BEIGE PAINTED CEILINGS – (SECTION F- STAIRWELL): NEGATIVE FOR LEAD WHITE PAINTED HVAC BRACKET (SECTION A): NEGATIVE FOR LEAD
INSPECTORS NOTES: (PLEASE SEE ATTACHED IMAGES) DURING OBSERVATION, THERE WERE LOCATIONS WHERE EXISTING CAULK APPEARED TO BE CROSS CONTAMINATED WITH EXCESS ROOF FLASHING MATERIAL (WHICH TESTED POSITIVE FOR ASBESTOS). FOR THESE REASONS- ANY GRAY, WHITE, BEIGE, CLEAR, AND BROWN CAULK FOUND ON THE ROOF, ON PERIMETER OF DOORS, PERIMETER OF ELEVATOR MACHINE ROOM/STAIR WELL (EXTERIOR), AND/OR ON THE PERIMETER OF METAL FLASHING SHALL BE TREATED AS POSITIVE FOR ASBESTOS. SEE LIST BELOW FOR EXCLUSIONS: 1. (CAULK EXCLUSIONS)-***CAULK THAT WILL BE VIEWED AS NEGATIVE FOR ASBESTOS***: •BROWN CAULK ON PERIMETER OF EXTERIOR WINDOWS: NEGATIVE FOR ASEBSTOS
2. THERE ARE VARIOUS ITEMS ON THE ROOF, NOT LIMITED TO :SUPPORT ANCHORS FOR HVAC UNIT, EXHAUST FANS, PITCH POCKETS, VENT PIPES, HVAC UNIT BRACKETS, AND ANY OTHERS THAT HAVE CONTAMINATED ROOFING MATERIAL ON ITS SURFACE. IF THERE ANY PLANS MADE TO DISPOSE ANY OF THE PRESENT ITEMS, CONSIDERATIONS SHALL BE MADE TO DISPOSE OF ANY RESIDUAL ROOFING MATERIAL LEFT ON THESE SURFACES AS ACM.
3. THERE APPEARED TO BE A RUBBER SHEET BELOW ROOF COPINGS THAT LOOKED TO BE MECHANICALLY FASTENENED IN PLACE. THE RUBBER SHEET IS NON SUSPECT FOR ASBESTOS. IF ANY ADDITONAL MATERIAL IS ENCOUNTERED DURING REMOVAL OF ROOF COPING, AND ANYWHERE ELSE ON ROOF, PLEASE STOP WORK AND CONTACT USC HAZMAT TO REASSESS.
4. IF A BUILDING MATERIAL IS NOT LISTED, DO NOT ASSUME THAT IT DOES NOT CONTAIN ASBESTOS. IT MAY NOT HAVE BEEN TESTED. FOR FURTHER INFORMATION, PLEASE CONTACT THE USC HAZMAT PROGRAM.
5. IF YOU ENCOUNTER ANY OTHER MATERIALS IN PLACE AND DEEM THEM SUSPECT FOR ASBESTOS AND/OR LEAD, PLEASE STOP WORK AND CONTACT THE ASBESTOS PROGRAM MANAGER FOR FURTHER TESTING OR ABATEMENT.
6. PLEASE NOTE THAT THE MATERIAL QUANTITY PROVIDED ON THE FIELD SHEET IS ONLY AN ESTIMATE FOR SAMPLING PURPOSES. THE QUANTITY
FM00568662 USC Work Order*FM00568662*
Page 3 of 3
08-SEP-16
08-SEP-16
ASBESTOS SUMMARY FOR WARDLAW COLLEGE (080) – SEPTEMBER 2016
CRAWL SPACE MAY BE CONTAMINATED WITH ASBESTOS
ASBESTOS HAS BEEN FOUND IN THIS BUILDING. IF DISTURBED, ASBESTOS MAY BE HARMFUL TO YOUR HEALTH.
PLEASE DO NOT DISTURB THE FOLLOWING MATERIALS IN THIS BUILDING AS THEY HAVE BEEN FOUND TO CONTAIN ASBESTOS.
- JOINT COMPOUND / SHEETROCK (3RD FLOOR ONLY)- 9X9 FLOOR TILE- BLACK MASTIC UNDER FLOOR TILE- RESIDUAL BLACK MASTIC ON FLOORING- BLACK DUCT MASTIC- PIPE INSULATION- BLACK MASTIC ON PIPE INSULATION- RED FIRE CAULKING
IF A BUILDING MATERIAL IS NOT LISTED, DO NOT ASSUME THAT IT DOES NOT CONTAIN ASBESTOS. IT MAY NOT HAVE BEEN TESTED.
FOR FURTHER INFORMATION, PLEASE CONTACT THE USC HAZMAT PROGRAM.
THE SOIL IN CRAWL SPACES MAY BE CONTAMINATED WITH ASBESTOS FROM OLD PIPE INSULATION AND OTHER MATERIALS. PLEASE CONTACT THE USC HAZMAT PROGRAM BEFORE ENTERING THESE CRAWL SPACES.
SHOULD BE FIELD VERIFIED FOR ALL OTHER PURPOSES INCLUDING ABATEMENT. THIS SURVEY IS ONLY VALID FOR THE DESIGNATED AREA(S)/LOCATION(S) TESTED IE: SECTIONS A, B, C, D, E, F ; WARDLAW COLLEGE (ROOF).
FM00568662 USC Work Order*FM00568662*
OrderID: 021904909
Page 1 Of 2
OrderID: 021904909
Page 2 Of 2
EMSL Analytical, Inc.706 Gralin Street Kernersville, NC 27284
Tel/Fax: (336) 992-1025 / (336) 992-4175
http://www.EMSL.com / [email protected]
021904909EMSL Order:
Customer ID: UNSC62
Customer PO: 2000041931
Project ID:
Attention: Phone:USC Hazmat (803) 777-7000
Fax:University of South Carolina (803) 777-3990
Received Date:743 Greene Street 07/22/2019 10:15 AM
Analysis Date:Columbia, SC 29208 07/22/2019
Collected Date: 07/19/2019
Project: 080 Wardlaw College
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
1
021904909-0001
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
25%
20%
55%
Cellulose<1%Gray/White
Non-Fibrous
Homogeneous
Stucco
2
021904909-0002
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
30%
20%
50%
Cellulose<1%Gray
Non-Fibrous
Homogeneous
Stucco
3
021904909-0003
None DetectedCa Carbonate
Non-fibrous (Other)
30%
70%
Cellulose<1%Gray/White
Non-Fibrous
Homogeneous
Stucco
4
021904909-0004
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
30%
20%
50%
Cellulose<1%Gray
Non-Fibrous
Homogeneous
Stucco
5
021904909-0005
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
30%
20%
50%
Cellulose<1%Gray
Non-Fibrous
Homogeneous
Stucco
6
021904909-0006
None DetectedCa Carbonate
Non-fibrous (Other)
30%
70%
Cellulose<1%Gray/White
Non-Fibrous
Homogeneous
Stucco
7
021904909-0007
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
30%
20%
50%
Cellulose<1%Gray
Non-Fibrous
Homogeneous
Stucco
Analyst(s)
Cameron Evans (5)
Ryan Rains (2)
Stephen Bennett, Laboratory Manager
or Other Approved Signatory
EMSL maintains liability limited to cost of analysis . The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 "Interim
Method"), but augmented with procedures outlined in the 1993 ("final") version of the method. This report relates only to the samples reported above, and may not be reproduced, except in full, without
written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations . Interpretation and use of test results are the responsibility of the client. All
samples received in acceptable condition unless otherwise noted. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of
the federal government. EMSL recommends gravimetric reduction for all non -friable organically bound materials prior to analysis. Estimation of uncertainty is available on request.
Samples analyzed by EMSL Analytical, Inc. Kernersville, NC NVLAP Lab Code 102104-0, CA ELAP 2689, Virginia 3333-000228, West Virginia LT000321
Initial report from: 07/22/2019 17:16:39
Page 1 of 1ASB_PLM_0008_0001 - 1.78 Printed: 7/22/2019 5:16 PM
Project Location
University of South CarolinaWARDLAW COLLEGE ROOFREPLACEMENT PROJECTSTATE PROJECT No.: 50003317-2Project Address820 SUMTER STREETCOLUMBIA, SOUTH CAROLINA 29208
VICINITY MAP
SITE LOCATION
Abbreviations
Details / Elevations / Sections Identifier
MAX.
MIN.
N.I.C
NTS
O.C.
O.H
TYP.
SIM.
MAXIMUM
MINIMUM
NOT IN CONTRACT
NOT TO SCALE
ON CENTER
OPPOSITE HAND
TYPICAL
SIMILAR
XXXX
ELEVATION / DETAIL / SECTION LABEL
SHEET SHOWN ON
GeneralG-101 COVER SHEET
ArchitecturalA-101 ROOF PLANA-102 ROOF PLAN: WIND ZONESA-103 ROOF PLAN: WALKPAD LAYOUTA-502 ROOF DETAILSA-503 ROOF DETAILSA-504 ROOF DETAILSA-505 ROOF DETAILSA-506 ROOF DETAILSA-507 ROOF DETAILSA-508 ROOF DETAILSA-509 ROOF DETAILS AND
SMACNA DETAILS
Structural (Alternate No.2)S-100 STRUCTURAL GENERAL NOTESS-101 ENLARGED ROOF PLAN AREA FS-200 ELEVATIONS AND DETAILSS-201 SECTIONS AND DETAILS
Index of Drawings
SHADING IDENTIFIES EXISTING
CONDITIONS AND NOT IN SCOPE OF WORK
PROJECT SITE
LOCATION
Consulting Engineers and Scientists
CLIENT
UNIVERSITY of SOUTH CAROLINA743 Greene StreetColumbia, South Carolina
Mr. Dale Branhame: [email protected]: 803.777.1288
ENGINEERING CONSULTANT
TERRACON CONSULTANTS, INC.2701 Westport RoadCharlotte, North Carolina
Mr. Stewart S. Swing, RRO, E.I.Senior Staff Engineer I Facilitiese: [email protected]: 704.594.8905
PROJECT NAME AND ADDRESS:
ISSUE DATE:
DESIGNED BY:
TERRACON'S PROJECT NUMBER:
PROJECT TEAM:
APR REVIEWER:
DRAWN BY:
SSS
LTH
FH186084
ISSUE FOR:
ADDENDUM:No.: DATE: DESCRIPTION:
SHEET NUMBER:
07.03.2019
TITLE SHEET:
Unive
rsity o
f Sou
th Ca
rolina
WARD
LAW
COLL
EGE
ROOF
REPL
ACEM
ENT P
ROJE
CTST
ATE P
ROJE
CT No
.: 500
0331
7-2Pro
ject A
ddres
s:82
0 Sou
th Ma
in Stre
etCo
lumbia
, Sou
th Ca
rolina
2920
8
EGM II
ENGINEER STATE LICENSE SEAL
ISSUED FOR BIDDING
Consulting Engineers and Scientists
2701 Westport Road
Charlotte, North Carolina
p: 704.509.1777
terracon.com
Project No. FH186084
Terracon SC License No. 2220
G-101
COVER SHEET
2 7/23/19 ADDED WALKPADREQUIREMENTS
2
26'-0"
61'-0"
74
'-6
"2
3'-8
"
98'-9" 64'-6"
4'-3
"
101'-0" 25'-0"
77
'-1
0"
26'-0"
20'-11
1
2
"14'-3"
30
'-8
"
45
'-6
"
SV
SV
SV
SCP
ELEVATED HVAC
SCP
ON STEEL PLATFORMDP
SLT
SLT
EB
SLT SLTEB EB
SCP
SCP
SLT
EB
SL
SV
RD
SV
SV
ELEVATED HVACON STEEL PLATFORM
RD RD
RD RD
RD
RD
NOSNOS
NOS NOS
NOSNOSNOS
RD
RD
RD
RD
NOS NOS
NOS
NOS
NOS
NOS
NOS
NOS NOS
NOSNOS
RD
RD
RIDGE LINE
RIDG
E LIN
E
RD
RD
RD
NOS
NOS
NOS
NOS
RDRD
RDRD
NOS
NOS NOS
NOS
RIDGE LINE
ROOF AREA BMETAL DECK
101'-1"
ROOF AREA C3CONCRETE DECK
METAL STAIRS
CONDENSATELINE (TYP.)
CORNICE
ELECTRICALCONDUIT
ELECTRICALCONDUIT
CORNICE
CORNICE
ELECTRICALCONDUIT
STAIRS
ELEVATEDDUCT (TYP.)
ELECTRICALCONDUIT (TYP.)
CORNICE
CORNICE
DS
DS
SV SV
CCCC
CCSV
CORNICE
CONDENSATELINE (TYP.)
25A-506
24A-506
26A-507
23A-506
10A-503
TYP.
7A-502
SIM.
26A-507
9A-503
27A-507
28A-507
TYP.
2A-501
1A-501
4A-501
4aA-501
TYP.
8A-502
3A-501
5A-502
6A-502
7A-502
9A-503
16A-504
22A-506
18A-505
37A-509
17A-505
19A-505
11A-503
12A-503
ROOF AREA C4CONCRETE DECK
15A-504
15A-504SIM.
33A-508
TYP.SIM.
TYP.
30A-508
TYP.
32A-508
34A-508
TYP.
34A-508
TYP.
32A-508
31A-508
31A-508
TYP.SIM.
ROOF AREA ELIGHTWEIGHT
CONCRETE DECK
30A-508
TYP. TYP.
TYP.
TYP.
TYP.
SIM.
TYP.
33A-508
31A-508
TYP.SIM.
31A-508TYP.SIM.
34A-508
TYP.
35A-508
TYP.
35A-508
30A-508
TYP.
ROOF AREA ACONCRETE DECK
ROOF AREA C1CONCRETE DECK
ROOF AREA C2CONCRETE DECK
ROOF AREA FCONCRETE DECK
ROOF AREA DCONCRETE DECK
20A-505
6 WINDOWLOCATIONS
37A-509
6 WINDOWLOCATIONS
(OPP.)
34A-508
13A-504
9A-503
SIM.
ROOF AREA GNOT IN CONTRACT
14A-504
13A-504
SIM.
13A-504
35A-508
23A-506
DS
A-101
PROJECT NAME AND ADDRESS:
ISSUE DATE:
DESIGNED BY:
TERRACON'S PROJECT NUMBER:
PROJECT TEAM:
APR REVIEWER:
DRAWN BY:
SSS
LTH
FH186084
ISSUE FOR:
ADDENDUM:No.: DATE: DESCRIPTION:
SHEET NUMBER:
07.03.2019
TITLE SHEET:
Unive
rsity o
f Sou
th Ca
rolina
WARD
LAW
COLL
EGE
ROOF
REPL
ACEM
ENT P
ROJE
CTST
ATE P
ROJE
CT No
.: 500
0331
7-2Pro
ject A
ddres
s:82
0 Sou
th Ma
in Stre
etCo
lumbia
, Sou
th Ca
rolina
2920
8
EGM II
ENGINEER STATE LICENSE SEAL
ISSUED FOR BIDDING
Consulting Engineers and Scientists
2701 Westport Road
Charlotte, North Carolina
p: 704.509.1777
terracon.com
Project No. FH186084
Terracon SC License No. 2220
ROOF PLAN
1
WARDLAW COLLEGE ROOF PLAN
SCALE: 1/16" = 1'-0"
LEGEND
RD
CONSTRUCTION NOTES
SV
1. CONTRACTOR TO FIELD VERIFY ALL EXISTING CONDITIONS ANDDIMENSIONS.
2. ELECTRICAL CONDUITS, BOXES ,OUTLET AND CABLES MAY REQUIREPOWER TO BE DISCONNECTED PRIOR TO PERFORMING THE WORK.CONTRACTOR TO COORDINATE WITH OWNER PRIOR TO REMOVAL.
3. ABANDONED EQUIPMENT TRUSSES AND POURABLE SEALER SHOULDBE REMOVED AND DISCARDED.
4. RAISE ALL CURBS TO ACHIEVE AN 8" MINIMUM FLASHING HEIGHT.
5. CLEAN, PRIME AND PAINT BIRD HOUSES AT ROOF AREAS A, C AND D.
6. STAIRS AT ROOF AREA C3 WILL NEED TO BE REMOVED ANDREINSTALLED ONCE NEW ROOF INSTALLATION IS COMPLETED.
7. ALL EQUIPMENT SUPPORTS AND PIPE PENETRATIONS ARE TO BELIQUID FLASHED.
8. EXISTING DRAIN INSERTS WILL NEED TO BE REMOVED AT ALLDRAINS TO ALLOW FOR NEW RETRO-FIT INSERT.
9. MECHANICAL UNIT STRUTS THAT ARE ATTACHED TO PARAPET WALLWILL NEED TO BE REMOVED, STORED AND REINSTALLED ONCE NEWROOFING IS COMPLETED. STRUTS TO BE FLASHED WITH NEW LIQUIDAPPLIED FLASHING.
10. NEW CONCRETE PAD AND DOORS TO BE INSTALLED AT ROOF AREASA AND D.
11. BASE FLASHING HEIGHTS WILL VARY AT SECTIONS WHERE WALLMETAL PANELS ARE TO HAVE CONSISTENT HEIGHT.
12. ROOF AREA C2 WILL NEED CONCRETE REPAIR WORK AT WALLS TOCOMPLETE NEW ROOFING INSTALLATION.
13. PULL TEST AT LIGHTWEIGHT CONCRETE DECK SHOULD BECONDUCTED PRIOR TO NEW ROOFING INSTALLATION.
14. CRICKETS SHOULD BE INSTALLED AT ALL CURBS THAT EXCEED 24"INCHES IN WIDTH.
15. CONTRACTOR TO REMOVE AND INSTALL NEW COPING CAP AT ROOFAREA G TO ACCOMMODATE NEW PARAPET WALL HEIGHT AT ROOFAREA B.
16. PROVIDE SUPPORTS FOR ALL CONDUIT, PIPES, AND CONDENSATIONLINES. ALL SUPPORTS SHOULD BE SET ON WALKPADS.
17. ON ANY ROOF AREA THAT A DOWNSPOUT IS TO BE INSTALLED, THEDOWNSPOUT SHOULD EXTEND TO THE NEAREST ROOF DRAIN ANDBE SUPPORTED. SUPPORTS SHOULD BE INSTALLED OVER WALKPADS.
TAPERED INSULATION
TAPERED SLOPE DIRECTION
STRUCTURAL SLOPE
ROOF DRAIN
SANITARY VENT
EQUIPMENT UNIT
PARAPET WALL/CORNICE
ELEVATED DUCT
SCUPPER
SKYLIGHT
EQUIPMENT SUPPORT
VENTILATOR
COVERED CURB
SECURITY LIGHT
ELECTRICAL BOX
NEW OVERFLOW SCUPPER
GUTTER/DOWNSPOUT
DUCT SUPPORT PEDESTAL
DETAIL FLAG No. #
NOT IN CONTRACT
SCP
LS
CC
SLT
EB
NOSDS
ALTERNATE No.1:(TYPICAL ON ALL SHEETS)1. INSTALL ROOFING SYSTEM UTILIZING ADHESIVE, AND
COLD APPLIED - ADHESIVE IN LIEU OF HOT-APPLIEDASPHALT.
1. RE-ROOFING OF ROOF AREAS A, B, C1, C2, C3, C4, D, E AND Fa. LOW SLOPE ROOF AREAS TO RECEIVE NEW TWO-PLY MODIFIED
BITUMEN ROOFING SYSTEM.b. ROOF AREA C2 TO RECEIVE LIQUID PMMA ROOFING SYSTEM.
2. COATING OF VENTS (BIRDHOUSES) AT ROOF AREAS A, C, AND D.
3. WALL PANEL INSTALLATION AT AREAS A, C, D, AND E.
4. SEALANT INSTALLATION AT WINDOW PERIMETER.
5. MISCELLANEOUS WORK INCLUDES, BUT IS NOT LIMITED TO, THE INSTALLATIONOF EDGE METAL, COPING, NEW OVERFLOW SCUPPERS, RETROFIT ROOF DRAINS,GUTTERS, DOORS, DOWNSPOUTS, AND FLASHING.
6. REMOVE AND REPLACE STUCCO (TO MATCH EXISTING) AT ROOF AREA F.
BASE BID:
N
SCOPE OF WORKNOT IN SCOPE OF WORK
KEY PLAN
ROOF AREA B
ROOF AREA A
ROOF AREA C2
ROOF AREA C3
ROOF AREA C4
ROOF AREA C
ROOF AREA D
ROOF AREA F
ROOF AREA E
2 7/23/19 ADDED WALKPADREQUIREMENTS
2
26'-0"
61'-0"
74
'-6
"2
3'-8
"
98'-9" 64'-6"
4'-3
"
101'-0" 25'-0"
77
'-1
0"
26'-0"
20'-11
1
2
"14'-3"
30
'-8
"
45
'-6
"
SV
SV
SV
SCP
ELEVATED HVAC
SCP
ON STEEL PLATFORMDP
SLT
SLT
EB
SLT SLTEB EB
SCP
SCP
SLT
EB
SL
SV
RD
SV
SV
ELEVATED HVACON STEEL PLATFORM
RD RD
RD RD
RD
RD
NOSNOS
RD
RD
RD
RD
NOS
NOS
NOS
NOS
NOS NOS
RD
RD
RD
RD
RD
RDRD
RDRD
ROOF AREA BMETAL DECK
101'-1"
ROOF AREA C3CONCRETE DECK
SV SV
CCCC
CCSV
ROOF AREA C4CONCRETE DECK
ROOF AREA ELIGHTWEIGHT
CONCRETE DECK
ROOF AREA ACONCRETE DECK
ROOF AREA C1CONCRETE DECK
ROOF AREA C2CONCRETE DECK
ROOF AREA FCONCRETE DECK
ROOF AREA DCONCRETE DECK
ROOF AREA GNOT IN CONTRACT
A-103
PROJECT NAME AND ADDRESS:
ISSUE DATE:
DESIGNED BY:
TERRACON'S PROJECT NUMBER:
PROJECT TEAM:
APR REVIEWER:
DRAWN BY:
SSS
LTH
FH186084
ISSUE FOR:
ADDENDUM:No.: DATE: DESCRIPTION:
SHEET NUMBER:
07.03.2019
TITLE SHEET:
Unive
rsity o
f Sou
th Ca
rolina
WARD
LAW
COLL
EGE
ROOF
REPL
ACEM
ENT P
ROJE
CTST
ATE P
ROJE
CT No
.: 500
0331
7-2Pro
ject A
ddres
s:82
0 Sou
th Ma
in Stre
etCo
lumbia
, Sou
th Ca
rolina
2920
8
EGM II
ENGINEER STATE LICENSE SEAL
ISSUED FOR BIDDING
Consulting Engineers and Scientists
2701 Westport Road
Charlotte, North Carolina
p: 704.509.1777
terracon.com
Project No. FH186084
Terracon SC License No. 2220
1
WARDLAW COLLEGE WALKPAD LAYOUT PLAN
SCALE: 1/16" = 1'-0"
LEGEND
RD
CONSTRUCTION NOTES
SV
1. PROVIDE SUPPORTS FOR ALL CONDUIT, PIPES, AND CONDENSATIONLINES. ALL SUPPORTS SHOULD BE SET ON WALKPADS.
2. ON ANY ROOF AREA THAT A DOWNSPOUT IS TO BE INSTALLED, THEDOWNSPOUT SHOULD EXTEND TO THE NEAREST ROOF DRAIN ANDBE SUPPORTED. SUPPORTS SHOULD BE INSTALLED OVER WALKPADS.
NEW WALKPADS
ROOF DRAIN
SANITARY VENT
EQUIPMENT UNIT
PARAPET WALL/CORNICE
ELEVATED DUCT
SCUPPER
SKYLIGHT
EQUIPMENT SUPPORT
VENTILATOR
COVERED CURB
SECURITY LIGHT
ELECTRICAL BOX
NEW OVERFLOW SCUPPER
GUTTER/DOWNSPOUT
DUCT SUPPORT PEDESTAL
NOT IN CONTRACT
SCP
LS
CC
SLT
EB
NOSDS
1. RE-ROOFING OF ROOF AREAS A, B, C1, C2, C3, C4, D, E AND Fa. LOW SLOPE ROOF AREAS TO RECEIVE NEW TWO-PLY MODIFIED
BITUMEN ROOFING SYSTEM.b. ROOF AREA C2 TO RECEIVE LIQUID PMMA ROOFING SYSTEM.
2. COATING OF VENTS (BIRDHOUSES) AT ROOF AREAS A, C, AND D.
3. WALL PANEL INSTALLATION AT AREAS A, C, D, AND E.
4. SEALANT INSTALLATION AT WINDOW PERIMETER.
5. MISCELLANEOUS WORK INCLUDES, BUT IS NOT LIMITED TO, THE INSTALLATIONOF EDGE METAL, COPING, NEW OVERFLOW SCUPPERS, RETROFIT ROOF DRAINS,GUTTERS, DOORS, DOWNSPOUTS, AND FLASHING.
6. REMOVE AND REPLACE STUCCO (TO MATCH EXISTING) AT ROOF AREA F.
BASE BID:
N
SCOPE OF WORKNOT IN SCOPE OF WORK
KEY PLAN
ROOF AREA B
ROOF AREA A
ROOF AREA C2
ROOF AREA C3
ROOF AREA C4
ROOF AREA C
ROOF AREA D
ROOF AREA F
ROOF AREA E
2 7/23/19 ADDED WALKPADREQUIREMENTS
ROOF PLAN:
WALKPAD LAYOUT PLAN