Uponor Group HeadquartersPlaza Loiste, Vantaa, FinlandIlari AhoNovember 2013
8 April 2023 ©Uponor 2
Plaza LoisteKey Facts
• 7 240 m² office space• 6 office floors, of which 2 for Uponor
• First BREEAM Very Good certified office complex in Finland
• Energy Class A
• UFHC, ceiling cooling, ground energy
• Architect: Forma-Futura Oy• Developer: NCC Property Development• HVAC design: Optiplan Oy, Uponor
8 April 2023 ©Uponor 3
BOILER ROOM• Connections to district heating and
boreholes
FREE COOLING11 boreholes with Uponor G12
providing free cooling to Uponor floors
ENTRANCE AREASnow and ice
melting
UPONOR FLOORS• Underfloor heating
and cooling with free cooling from
boreholes• Ceiling cooling for
peak demand• Air circulation chillers
for peak demand in meeting rooms
VENTILATION MACHINERY ROOM • Mechanical supply/
exhaust with high efficiency heat
recovery• Water chillers for
peak cooling demand
FLOORS 1 - 5• Underfloor heating
8 April 2023 ©Uponor 4
8 April 2023 ©Uponor 5
Plaza Loiste Environmental Performance
Free cooling for energy efficiency
• Free cooling energy from the boreholes covers the cooling demand of the Uponor offices
• Purchased cooling energy need eliminated on an annual basis
• Monitoring program established from the cooling season 2014 onwards
Anna Forsström: G-12 ENERGIANKERUUPUTKIEN KÄYTTÖ MAAVIILEÄN KERUUSSAOpinnäytetyö, Ympäristöteknologia, YAMK ,Toukokuu 2013
Energy production of the Plaza Loiste borehole cooling system
Simulated energy production of the borehole field
Cooling energy demand of the building
kWh/month
Mo
nth
8 April 2023 ©Uponor 6
Plaza Loiste occupant survey
Thermal environment and sensation
• High satisfaction level, with some remarks on too cold temperature levels especially in the meeting rooms
• Regulation of the meeting room fan coil units has been adjusted after the summer period, and they should now work appropriately during the next cooling season
8 April 2023 ©Uponor 7
Plaza Loiste occupant survey
Air movement
• Individual comments related to draught in meeting rooms caused by the fan coil units; this should be corrected by the adjustments that have already been made.
8 April 2023 ©Uponor 8
Performance monitoring and verification
• Plaza Loiste is a pilot project in the national RYM Indoor Environment research program
• Monitoring and evaluation will be carried out regarding
― indoor environment quality― building energy performance― long term performance of the
borehole field― optimisation of the solution
• Partners― Aalto University― VTT Technical Research Centre of
Finland